2018 IFC and IBC Fire Protection Systems with MT amendments

26
2018 IFC and IBC Fire Protection Systems with MT amendments Copyright 2021 International Code Council 1 2018 IFC and IBC Fire Protection Systems 2018 IFC and IBC Fire Protection Systems Based on the 2018 International Fire Code ® (IFC ® ) 2018 International Building Code ® (IBC ® ) and State of Montana Amendments Presenter Instructions Presenter Instructions Many of these slides contain animation and graphics When reviewing this presentation, you should utilize the “slide show presentation mode” or in the “reading view” This will allow you to become aware of the animation and graphics on the slides Click the “View” in the header, then click “Reading View” in the “Presentation Views” group Slides which contain animation will have one or more dots at the bottom left corner of the slide. For example, there are 6 dots at the bottom of this slide Each dot represents a “click” which is needed for animation on the slide before the next slide will appear With each “click,” as an animation occurs, a dot will also disappear When all the dots are gone, the next “click” will take you to the next slide Also note, “FCO” will be used to designate the Fire Code Official 2 2018 IFC Fire Protection Systems Welcome Welcome Instructor Introduction Exits Breaks and Schedule Cell Phones Student Introductions – Poll Questions 1 - 3 3 2018 IFC Fire Protection Systems Description Description This seminar is designed to guide participants through the 2018 IFC requirements related to fire protection systems (Chapter 9) – With State of Utah Amendments These requirements include: Fire sprinkler systems Fire-extinguishing systems Standpipe systems Fire alarm systems Automatic detection systems Smoke control/exhaust systems Other fire protection devices and equipment 4 1 2 3 4

Transcript of 2018 IFC and IBC Fire Protection Systems with MT amendments

Page 1: 2018 IFC and IBC Fire Protection Systems with MT amendments

2018 IFC and IBC Fire Protection Systems with MT amendments

Copyright 2021 International Code Council 1

2018 IFC and IBC Fire

Protection Systems

2018 IFC and IBC Fire

Protection SystemsBased on the 2018 International Fire Code® (IFC®)

2018 International Building Code® (IBC®) and

State of Montana Amendments

Presenter InstructionsPresenter Instructions Many of these slides contain animation and graphics

When reviewing this presentation, you should utilize the “slide show

presentation mode” or in the “reading view”

This will allow you to become aware of the animation and graphics

on the slides

Click the “View” in the header, then click “Reading View” in the

“Presentation Views” group

Slides which contain animation will have one or more dots at the bottom

left corner of the slide. For example, there are 6 dots at the bottom of

this slide

Each dot represents a “click” which is needed for animation on the slide

before the next slide will appear

With each “click,” as an animation occurs, a dot will also disappear

When all the dots are gone, the next “click” will take you to the next

slide

Also note, “FCO” will be used to designate the Fire Code Official

2

2018 IFC Fire Protection Systems

WelcomeWelcome

Instructor Introduction

Exits

Breaks and Schedule

Cell Phones

Student Introductions – Poll Questions 1 - 3

3 2018 IFC Fire Protection Systems

DescriptionDescription

This seminar is designed to guide participants through

the 2018 IFC requirements related to fire protection

systems (Chapter 9) – With State of Utah Amendments

These requirements include:

Fire sprinkler systems

Fire-extinguishing systems

Standpipe systems

Fire alarm systems

Automatic detection systems

Smoke control/exhaust systems

Other fire protection devices and equipment

4

1 2

3 4

Page 2: 2018 IFC and IBC Fire Protection Systems with MT amendments

2018 IFC and IBC Fire Protection Systems with MT amendments

Copyright 2021 International Code Council 2

2018 IFC Fire Protection Systems

GoalGoal

Participants will be able to apply key provisions

regarding fire protection systems in the 2018 IFC

to aid in code application, administration and

enforcement

5 2018 IFC Fire Protection Systems

ObjectivesObjectives Upon completion, participants will be

better able to:

Define key terms

Explain why a fire protection system must conform to

code criteria and referenced standards

Determine where and when fire protection systems

are required

Explain the principles of how a fire protection system

detects and manages a fire

Understand the relationship between the code

(IFC/IBC) and the referenced standards

6

2018 IFC Fire Protection Systems

Prerequisite UnderstandingPrerequisite Understanding

Occupancy classifications are based on the use

and character of the building

Many code requirements are based on the

occupancy classification

7

Fire Protection SystemsFire Protection Systems

Module 1

5 6

7 8

Page 3: 2018 IFC and IBC Fire Protection Systems with MT amendments

2018 IFC and IBC Fire Protection Systems with MT amendments

Copyright 2021 International Code Council 3

2018 IFC Fire Protection Systems

Fire Protection SystemsFire Protection Systems

Definition of a Fire Protection System:

Approved devices, equipment and systems or

combinations of systems used to detect a fire,

activate an alarm, extinguish or control a fire,

control or manage smoke and products of a fire or

any combination thereof.

Given this definition, a fire protection

system is required to perform certain

functions

2018 IFC

§202

Page 27

9 2018 IFC Fire Protection Systems

Fire Protection SystemsFire Protection Systems

10

2018 IFC Fire Protection Systems

The IFC’s Intent for

Fire Protection Systems

The IFC’s Intent for

Fire Protection Systems

When a fire protection system is required, it is:

Designed and constructed in accordance with the

applicable NFPA standards

As modified by the code

Designed for the respective hazards being protected

Inspected and maintained in accordance with the IFC

and the applicable standards

Modified when the hazard changes and the fire

protection system is not capable of controlling a fire

11

• Fire sprinklers on combustible balconies in

multifamily dwellings – §903.3.1.2.1

• Exempt fire sprinkler locations – §903.3.1.1.1

• Limited area fire sprinkler system – §903.3.8

2018 IFC Fire Protection Systems

Why the IFC Requires a

Fire Protection System

Why the IFC Requires a

Fire Protection System

Fire protection systems are required inside or

outside of buildings because of:

Occupancy classification in the fire area or the

building

Occupant load of the fire area or building

Height or area of the building

Quantity of haz mat stored or used inside of a building

Type of hazard stored or used inside of a building

Fire loss history for specific hazards

12

Group I-2

Fire area has an OL ≥300

Building has a story with OL ≥30

and ≥55’ above LLFDVAStoring or using >100 lbs pyroxylin plastics

Type IIB dry cleaning operation

Spray application of flammable finishes

9 10

11 12

Page 4: 2018 IFC and IBC Fire Protection Systems with MT amendments

2018 IFC and IBC Fire Protection Systems with MT amendments

Copyright 2021 International Code Council 4

2018 IFC Fire Protection Systems

Chapter 9 ArrangementChapter 9 Arrangement

IFC Chapter 9 is divided into 15 sections, including:

901: General

903: Automatic Sprinkler Systems

904: Alternative Fire-extinguishing Systems

905: Standpipe Systems

907: Fire Alarm and Detection Systems

908: Emergency Alarm Systems

909: Smoke Control Systems

910: Smoke and Heat Removal

914: Fire Protection Based on Special Detailed Requirements of

Use and Occupancy

915: Carbon Monoxide Detection

13

IBC Ch 9 is almost

identical to IFC Ch 9

Some differences

occur in §901

2018 IFC Fire Protection Systems

General Provisions

§901

General Provisions

§901Provision IFC Section IBC Section

Construction documents 901.2 −

Permits 901.3 −

Installation 901.4 901.2

Modifications − 901.3

Threads − 901.4

Acceptance testing 901.5 901.5

Inspection, testing and maintenance 901.6 901.3

Fire areas 901.4.3 901.7

Pump and riser room size − 901.8

Systems out of service 901.7 −

Removal of or tampering with equipment 901.8 −

Termination of monitoring service 901.9 −

Recall of fire protection components 901.10 −

14

2018 IFC Fire Protection Systems

Construction Documents

§901.2

Construction Documents

§901.2 Fire Code Official (FCO) are

authorized to require the

submittal, review and approval of

design drawings and calculations

for fire protection systems

A contractor’s statement of

compliance can be required

Documents must show that

the system complies with the:

Plans

Applicable standard

Manufacturer’s instructions

15 2018 IFC Fire Protection Systems

Construction Documents - 901.2

Montana Amendment

Construction Documents - 901.2

Montana Amendment Administrative Rule 24.301.146 (13)

In new or existing structures, the building official

may allow the installation of noncode compliant

equipment, facilities, or structural elements

including but not limited to fire-extinguishing

(sprinkler) systems or fire-resistive construction,

which are not required by the building code, upon

the finding that such installation does not

negatively impact the overall compliance of the

structure with the building code.

16

13 14

15 16

Page 5: 2018 IFC and IBC Fire Protection Systems with MT amendments

2018 IFC and IBC Fire Protection Systems with MT amendments

Copyright 2021 International Code Council 5

2018 IFC Fire Protection Systems

Construction Documents - 901.2

Montana Amendment

Construction Documents - 901.2

Montana Amendment Administrative Rule 24.301.146 (13)

Subsection 901.2, Fire Protection Systems, is

modified by deleting the exception and replacing

with the following: "Any fire protection system or

portion thereof not required by this code shall

be permitted to be installed for partial or

complete protection at the discretion of the

building official."

17 2018 IFC Fire Protection Systems

Construction Documents – 902.8

Montana Amendment

Construction Documents – 902.8

Montana Amendment Administrative Rule 24.301.146 (16)

Delete Subsection 903.2.8 and replace with the

following:

18

2018 IFC Fire Protection Systems

Construction Documents – 902.8

Montana Amendment

Construction Documents – 902.8

Montana Amendment Administrative Rule 24.301.146 (16)

Delete Subsection 903.2.8 and replace with the

following:

19 2018 IFC Fire Protection Systems

Construction Documents – 902.8

Montana Amendment

Construction Documents – 902.8

Montana Amendment "1. An approved automatic sprinkler system installed in

accordance with Section 903.3 shall be provided in all

Group R buildings meeting any of the following criteria:

"a. 9 or more transient guests or 5 or more transient

guestrooms;

"b. 9 or more occupants in other than dwelling units;

"c. 5 or more dwelling units; or

"d. more than 2 stories.

20

17 18

19 20

Page 6: 2018 IFC and IBC Fire Protection Systems with MT amendments

2018 IFC and IBC Fire Protection Systems with MT amendments

Copyright 2021 International Code Council 6

2018 IFC Fire Protection Systems

Construction Documents – 902.8

Montana Amendment

Construction Documents – 902.8

Montana Amendment "2. In lieu of the above required automatic sprinkler

system in buildings not more than three stories

above the lowest level of exit discharge, each

transient guestroom may be provided with at least

one door leading directly to an exterior exit access

that leads directly to approved exits.

21 2018 IFC Fire Protection Systems

Construction Documents – 902.8

Montana Amendment

Construction Documents – 902.8

Montana Amendment "3. "Transient guest" for the purpose of this

subsection shall mean an occupant who is

primarily transient in nature, staying at one location

for 30 days or less."

"4. "The requirements for automatic sprinkler

systems for R-4 occupancies are found in ARM

24.301.146."

22

2018 IFC Fire Protection Systems

Construction Documents - 903.3.5

Montana Amendment

Construction Documents - 903.3.5

Montana Amendment Administrative Rule 24.301.146 (14)

Subsection 903.3.5

Inadequate Water Supply

Amended by addition of the following:

23 2018 IFC Fire Protection Systems

Construction Documents - 903.3.5

Montana Amendment

Construction Documents - 903.3.5

Montana Amendment "This subsection shall apply to buildings which are

required by the International Building Code to be

provided with an automatic fire extinguishing system

and do not have access to an existing multiple user

water supply system, such as a municipal water supply

system or a private community water supply system,

capable of providing the water supply requirements of

National Fire Protection Association Standard for the

Installation of Sprinkler Systems, 2016 edition (NFPA

13).

24

21 22

23 24

Page 7: 2018 IFC and IBC Fire Protection Systems with MT amendments

2018 IFC and IBC Fire Protection Systems with MT amendments

Copyright 2021 International Code Council 7

2018 IFC Fire Protection Systems

Construction Documents - 903.3.5

Montana Amendment

Construction Documents - 903.3.5

Montana Amendment Under such circumstances, water storage

requirements may be modified by the building official.

The modified design shall include sufficient storage

onsite to operate the hydraulically remote area for the

response time of the local fire department.

Response time is the time from alarm to the time the

fire department can apply water to the fire.

25 2018 IFC Fire Protection Systems

Construction Documents - 903.3.5

Montana Amendment

Construction Documents - 903.3.5

Montana Amendment Response time shall be established by the use of the

formula T = 6.5 minutes (mobilization time) + 1.7

minutes/mile D (travel time), where T is response time,

in minutes, and D is distance, in miles, from the fire

station to the building.

The modified water supply shall be sufficient to operate

the system for the response time calculated above but

not be less than 20 minutes.

Water supply requirements shall be established by

using the area/density method as defined in NFPA 13.

26

2018 IFC Fire Protection Systems

Construction Documents - 903.3.5

Montana Amendment

Construction Documents - 903.3.5

Montana Amendment A reduction in water storage of up to 50 percent, but

not less than that required for a 20-minute supply is

allowed.

All automatic fire sprinkler system designs and

components shall be in compliance with NFPA 13.

When a modified water storage is allowed, the

automatic fire sprinkler system must be equipped with

a flow alarm, digital alarm communicator transmitter,

and a fire department connection.

27 2018 IFC Fire Protection Systems

Construction Documents - 903.3.5

Montana Amendment

Construction Documents - 903.3.5

Montana Amendment The automatic fire sprinkler system shall be monitored

by an approved central station in accordance with

NFPA 72, National Fire Alarm Code, 2016 edition."

28

25 26

27 28

Page 8: 2018 IFC and IBC Fire Protection Systems with MT amendments

2018 IFC and IBC Fire Protection Systems with MT amendments

Copyright 2021 International Code Council 8

2018 IFC Fire Protection Systems

Table 1020.1 - Montana AmendmentTable 1020.1 - Montana Amendment

(18) For "R" occupancies that are exempt from the

requirements of a fire sprinkler system, pursuant to

ARM 24.301.146(16), Table 1020.1, referenced in

subsection 1020.1, shall be amended in regard to

"R" occupancies by the deletion of the language

"Greater than 10" and insertion of the language

"Greater than 8" under the heading "Occupant

Load Serviced By Corridor."

29 2018 IFC Fire Protection Systems

R-4 - Montana AmendmentR-4 - Montana Amendment

(39) Notwithstanding any other provisions within

the International Building Code, the following adult

group residential facilities, licensed by the

Department of Public Health and Human Services

will be classified and treated as follows:

(a) Category A assisted living facilities with 9 to 19

residents, as referenced in 50-5-226, MCA, will be

classified as an R-4 occupancy for building permit

and construction standard purposes. Automatic fire

sprinkler systems are not required.

30

2018 IFC Fire Protection Systems

R-4 - Montana AmendmentR-4 - Montana Amendment

(b) Category B assisted living facilities with 9 to 19

residents, as referenced in 50-5-226, MCA, will be

classified as an R-4 occupancy for building permit

and construction standards purposes. In addition, a

Category B assisted living facility shall have an

automatic fire sprinkler system and provide an

accessible sleeping room or space for each

Category B resident.

31 2018 IFC Fire Protection Systems

R-4 - Montana AmendmentR-4 - Montana Amendment

(c) An assisted living facility with 20 or more

residents, in any combination of Category A or

Category B, will be classified as an R-2 occupancy

for building permit and construction standards and

shall meet accessibility standards as provided in

Subsection 1103 of the International Building

Code. Automatic fire sprinkler systems are

required. A fire wall cannot be used to isolate and

reduce occupant loads in order to avoid an R-2

classification.

32

29 30

31 32

Page 9: 2018 IFC and IBC Fire Protection Systems with MT amendments

2018 IFC and IBC Fire Protection Systems with MT amendments

Copyright 2021 International Code Council 9

2018 IFC Fire Protection Systems

Required vs Non-Required

§901.4.1 and §901.4.2

Required vs Non-Required

§901.4.1 and §901.4.2

Required fire protection systems must comply

with the code and the applicable standards

Non-required fire protection systems must ALSO

comply with the code and the applicable

standards

Wherever, any code modification or allowance is

made as a result of sprinklers, the system becomes a

required system

33 2018 IFC Fire Protection Systems

Additional Fire Protection

Systems

§901.4.4

Additional Fire Protection

Systems

§901.4.4

Where the FCO deems

a hazard to be of a

unique nature or unduly

difficult for fire

department access,

additional fire protection

features can be

required

34

2018 IFC Fire Protection Systems

Pump and Riser Room

§901.4.6

Pump and Riser Room

§901.4.6

Pump room or riser room

is not required, but, if

provided, they must have

adequate room for service

Following

manufacturer’s

specifications

Ability to remove largest

piece of equipment and

reinstall

35 2018 IFC Fire Protection Systems

Pump and Riser Room

§901.4.6.1 – 901.4.64

Pump and Riser Room

§901.4.6.1 – 901.4.64

Access

Marking on Access Doors

Approved Sign

Min height – 2”

Min Stroke width – ½ in

Environment

> 400 F

Lighting

36

33 34

35 36

Page 10: 2018 IFC and IBC Fire Protection Systems with MT amendments

2018 IFC and IBC Fire Protection Systems with MT amendments

Copyright 2021 International Code Council 10

2018 IFC Fire Protection Systems

Fire Pumps

§913

Fire Pumps

§913

Must meet NFPA 20

requirements

Pump room maintained >40°F

Cables and circuits protected by

2-HR construction or UL 2196

IBC §913.2.1: 1-HR separation,

2-HR in high-rise, or ≥50’

Class II fuel supply is not

included in MAQ if it meets IFC

§603.3.2

37

IFC §603.3.2:

• ≤660 gallon

• ≤3,000 gallon if in PAST

and room is sprinklered

Pyrotenax MI cable—2-hour fire-rated cable

Graphic courtesy of Pentair Thermal Management

2018 IFC Fire Protection Systems

Installation Acceptance Testing

§901.5

Installation Acceptance Testing

§901.5

Before a fire protection

system can be approved it

must be tested

Fire protection systems

must be accepted and

approved based on the

applicable NFPA fire

protection system standards

38

Photo courtesy of Protection Development Inc.

2018 IFC Fire Protection Systems

Systems Out of Service

§901.7

Systems Out of Service

§901.7

Fire protection system impairment

is a critical event that must be

reported to the FCO

Impairment of fire protection

systems requires:

An individual be designated as the

impairment coordinator

A plan of action for the impairment

39

Impairment coordinator:

• Responsible for all work

• Notify FD of the status

• Ensure system is restored

2018 IFC Fire Protection Systems

Poll QuestionPoll Question

Question #4: Who is responsible for arranging

and scheduling the Final Inspection and

Acceptance Testing for a Fire Protection

System?

Poll Question - #5: When a Fire Protection

System is to be taken out of service, the Fire

Code Official should only be notified if the

system is down for more than:

37 38

39 40

Page 11: 2018 IFC and IBC Fire Protection Systems with MT amendments

2018 IFC and IBC Fire Protection Systems with MT amendments

Copyright 2021 International Code Council 11

2018 IFC Fire Protection Systems

Important TermsImportant Terms

Two important definitions must be reviewed and

understood

Several thresholds for requirements are based

on these definitions

Level of exit discharge (LED)

Fire area

41 2018 IFC Fire Protection Systems

Level of Exit DischargeLevel of Exit Discharge

Definition of Level of Exit Discharge :

The story at the point at which an exit terminates

and an exit discharge begins.

A building can have more than one level

of exit discharge

2018 IFC

§202

Page 25

42

2018 IFC Fire Protection Systems

Level of Exit DischargeLevel of Exit Discharge

43

Highest level of

exit discharge

Lowest level of

exit discharge

2018 IFC Fire Protection Systems

Fire AreaFire Area

Definition of Fire Area:

The aggregate floor area enclosed and bounded by

fire walls, fire barriers, exterior walls or horizontal

assemblies of a building. Areas of the building not

provided with surrounding walls shall be included in

the fire area if such areas are included within the

horizontal projection of the roof or floor next above.

2018 IFC

§202

Page 27

44

41 42

43 44

Page 12: 2018 IFC and IBC Fire Protection Systems with MT amendments

2018 IFC and IBC Fire Protection Systems with MT amendments

Copyright 2021 International Code Council 12

2018 IFC Fire Protection Systems

Fire Area Bounded by

Exterior Walls

Fire Area Bounded by

Exterior Walls

45

Fire Area 1

A building constructed with or

without fire-resistant

materials or assemblies is a

fire area

2018 IFC Fire Protection Systems

Fire Area Compartmentalized

Using Fire Barriers

Fire Area Compartmentalized

Using Fire Barriers

46

Fire Barriers

Fire Area 1 Fire Area 2 Fire Area 3

A building divided using fire-resistant

assemblies can have one or more fire areas

2018 IFC Fire Protection Systems

Fire Areas in Multistory

Buildings

Fire Areas in Multistory

Buildings

47

Fire Area 1 Fire Area 3Fire Area 2

Fire Barriers

2018 IFC Fire Protection Systems

Fire Areas in Multistory

Buildings

Fire Areas in Multistory

Buildings

48

Fire Area 3

Fire Area 1

Fire Area 2Fire-resistance-rated

Floor/Ceiling Assembly

45 46

47 48

Page 13: 2018 IFC and IBC Fire Protection Systems with MT amendments

2018 IFC and IBC Fire Protection Systems with MT amendments

Copyright 2021 International Code Council 13

2018 IFC Fire Protection Systems

Fire Areas

Using a Fire Wall

Fire Areas

Using a Fire Wall

Fire walls can divide a structure into ≥ 2 buildings

Each building becomes its own fire area

Each building can be further subdivided with fire barriers

49

Fire Area 1 Fire Area 2Fire Area 1 Fire Area 2 Fire Area 3 Fire Area 4

Building 1 Building 2

Fire Wall

Fire Barriers2018 IFC Fire Protection Systems

How Many Fire Areas?How Many Fire Areas?

50

9,000 square feet

Group B

7,000 square feet

Group A-2

16,000 square feet

Group B

Fire Area 2

Fire Area 1

Fire Barrier

Horizontal Fire-resistance-

rated Assembly

2018 IFC Fire Protection Systems

Fire Area Application

IFC §901.4.3, IBC §901.7

Fire Area Application

IFC §901.4.3, IBC §901.7

Fire areas. Where buildings, or portions thereof, are

divided into fire areas so as not to exceed the limits

established for requiring a fire protection system in

accordance with this chapter, such fire areas shall be

separated by fire barriers constructed in accordance

with §707 of the IBC or horizontal assemblies

constructed in accordance with §711 of the IBC, or

both, having a fire-resistance rating of not less than

that determined in accordance with §707.3.10 of the

International Building Code.

2018 IFC

§901.4.3

Page 103

51 2018 IFC Fire Protection Systems

IBC Table 707.3.10IBC Table 707.3.10

OCCUPANCY GROUPFIRE-RESISTANCE

RATING (hours)

H-1, H-2 4

F-1, H-3, S-1 3

A, B, E, F-2, H-4, H-5, I, M, R, S-2 2

U 1

2018 IBC

Table 707.3.10

Page 133

52

NOTE: a fire area must be at least 1-HR fire-

resistance-rated construction

But in most cases, 1-HR is not adequate

Fire-resistance Rating Requirements for Fire Barrier

Assemblies or Horizontal Assemblies Between Fire Areas

49 50

51 52

Page 14: 2018 IFC and IBC Fire Protection Systems with MT amendments

2018 IFC and IBC Fire Protection Systems with MT amendments

Copyright 2021 International Code Council 14

2018 IFC Fire Protection Systems

IBC Table 508.4IBC Table 508.4

Required Separation of Occupancies (hours)

2018 IBC

Table 508.4

Page 115

53

Occupancy

Group

A, EI-1, I-3,

I-4I-2 R a F-2,

S-2a, U

Be, F-1,

M, S-1H-1 H-2

H-3,

H-4H-5

S NS S NS S NS S NS S NS S NS S NS S NS S NS S NS

A, E N N 1 2 2 NP 1 2 N 1 1 2 NP NP 3 4 2 3 2 NP

I-1 a, I-3, I-4 - - N N 2 NP 1 NP 1 2 1 2 NP NP 3 NP 2 NP 2 NP

I-2 - - - - N N 2 NP 2 NP 2 NP NP NP 3 NP 2 NP 2 NP

R a - - - - - - N N 1 c 2 c 1 2 NP NP 3 NP 2 NP 2 NP

F-2, S-2 b, U - - - - - - - - N N 1 2 NP NP 3 4 2 3 2 NP

B e, F-1, M,

S-1- - - - - - - - - - N N NP NP 2 3 1 2 1 NP

H-1 - - - - - - - - - - - - N NP NP NP NP NP NP NP

H-2 - - - - - - - - - - - - - - N NP 1 NP 1 NP

H-3, H-4 - - - - - - - - - - - - - - - - 1 d NP 1 NP

H-5 - - - - - - - - - - - - - - - - - - N NP

Separate Group I-1

from Group M

2018 IFC Fire Protection Systems

IBC Table 706.4IBC Table 706.4

Fire Wall Fire-resistance Ratings

a. In Type II or V construction, walls shall be permitted to have

a 2-hour fire-resistance rating.

b. For Group H-1, H-2 or H-3 buildings, also see Sections

415.7 and 415.8

2018 IBC

Table 706.4

Page 131

54

GROUPFIRE-RESISTANCE

RATING (hours)

A, B, E, H-4, I, R-1, R-2, U 3 a

F-1, H-3 b, H-5, M, S-1 3

H-1, H-2 4 b

F-2, R-3, R-4, S-2 2

2018 IFC Fire Protection Systems

Design and Installation

Requirements §903.3

Design and Installation

Requirements §903.3

Before reviewing the IFC requirements for fire

sprinkler systems, it is important to understand:

The various standards applicable to fire sprinkler

system design

The relationship between the code and the standard

55 2018 IFC Fire Protection Systems

Design and Installation

Requirements §903.3

Design and Installation

Requirements §903.3

NFPA publishes 3 standards governing the

design, installation, testing and maintenance of

fire sprinkler systems:

§903.3.1.1 – NFPA 13, Installation of Sprinkler

Systems

§903.3.1.2 – NFPA 13R, Installation of Sprinkler

Systems in Low-Rise Residential Occupancies

§903.3.1.3 – NFPA 13D, Sprinkler Systems for One-

and Two-Family Dwellings and Manufactured Homes

56

53 54

55 56

Page 15: 2018 IFC and IBC Fire Protection Systems with MT amendments

2018 IFC and IBC Fire Protection Systems with MT amendments

Copyright 2021 International Code Council 15

2018 IFC Fire Protection Systems

Application Matrix of the

Sprinkler Design Standards

Application Matrix of the

Sprinkler Design Standards

System Feature

Sprinkler Standard

NFPA 13 NFPA 13RNFPA 13D or

IRC §P2904

Extent of

ProtectionThroughout the building

Occupied

spacesOccupied spaces

Design IntentLife Safety &

Property ProtectionLife Safety Life Safety

Applicability All OccupanciesGroup R up to

4-stories or 60’

1- & 2-family dwellings

& Townhomes

Design Methods

Pipe schedule; Control mode –

discharge density/design area;

Control mode – specific

application; Suppression mode

4 sprinklers per

compartment

2 sprinklers per

compartment

Sprinklers All listed & approved typesListed

ResidentialListed Residential

Minimum H2O

Supply Duration30 to 120 minutes 30 Minutes 7 or 10 Minutes

572018 IFC Fire Protection Systems

“Installed Throughout”“Installed Throughout”

58

IFC Table 1017.2 Exit Access Travel Distance, Footnote c

Buildings equipped throughout with an automatic sprinkler

system in accordance with §903.3.1.1.

IFC Table 5003.1.1(1) MAQ per Control Area, Note d

Maximum allowable quantities shall be increased 100

percent in buildings equipped throughout with an approved

automatic sprinkler system in accordance with §903.3.1.1.

IBC Table 506.2 Allowable Area, Note S1

S1 = Buildings a maximum of one story above grade plane

equipped throughout with an automatic sprinkler system

installed in accordance with §903.3.1.1

What does

“equipped throughout” or

“installed throughout” mean?

2018 IFC Fire Protection Systems

Poll QuestionPoll Question

Question #6: Can an NFPA 13R fire sprinkler

system protect an entire building when the

primary use of the building is residential, but the

building also contains small accessory uses?

2018 IFC Fire Protection Systems

“Installed Throughout”“Installed Throughout”

Under the design of NFPA 13, are all areas in

the building protected with sprinklers?

Under the design of NFPA 13R, are all areas in

the building protected with sprinklers?

Under the design of NFPA 13D or IRC §P2904,

are all areas in the building protected with

sprinklers?

60

NO

• Attic spaces <6” high

• Concealed spaces without combustible construction NO

• Attic spaces without fuel-fired equipment

• Small bathrooms

NO

• Attic spaces without fuel-fired equipment

• Small bathrooms

• Small closets with noncombustible wall covering

So which design provides

for fire sprinklers

“installed throughout”?

57 58

59 60

Page 16: 2018 IFC and IBC Fire Protection Systems with MT amendments

2018 IFC and IBC Fire Protection Systems with MT amendments

Copyright 2021 International Code Council 16

2018 IFC Fire Protection Systems

“Installed Throughout”“Installed Throughout”

§903.3.1.1 states:

Where the provisions of this code require that a

building or portion thereof be equipped throughout

with an automatic sprinkler system in accordance with

this section, sprinklers shall be installed throughout in

accordance with NFPA 13 except as provided in

Sections 903.3.1.1.1 and 903.3.1.1.2.

61

“Installed throughout” means that sprinklers are

installed throughout the building in all locations

as required by the design standard and the code

2018 IFC Fire Protection Systems

“Installed Throughout”“Installed Throughout”

903.3.1.1.1 Exempt locations. Automatic sprinklers shall not be required in

the following rooms or areas where such rooms or areas are protected with an

approved automatic fire detection system in accordance with §907.2 that will

respond to visible or invisible particles of combustion. Sprinklers shall not be

omitted from a room merely because it is damp, of fire-resistance-rated

construction or contains electrical equipment.

1. A room where the application of water, or flame and water, constitutes a

serious life or fire hazard.

62

2. A room or space where sprinklers are considered undesirable because of the

nature of the contents, where approved by the fire code official.3. Generator and transformer rooms separated from the remainder of the

building by walls and floor/ceiling or roof/ceiling assemblies having a fire-

resistance rating of not less than 2 hours.4. Rooms or areas that are of noncombustible construction with wholly

noncombustible contents.5. Fire service access elevator machine rooms and machinery spaces.

6. Machine rooms, machinery spaces, control rooms and control spaces

associated with occupant evacuation elevators designed in accordance with

§3008 of the IBC.

• These provisions are not found in NFPA 13

• These provisions are less restrictive than NFPA 13

• §102.7.1 – code provisions take precedence over

the standard

2018 IFC Fire Protection Systems

Fire Protection SystemsFire Protection Systems

Given: 89,000 ft² Group S-1 warehouse. The fire

sprinkler system was designed to protect rack

storage of Class III commodities in double row

racks 24’ high. The original tenant moved out of

the building and the new tenant is storing Class

IV commodities.

What section would apply to ensure the

automatic sprinkler system is adequately

protecting these new commodities?

63

§901.4

2018 IFC Fire Protection Systems

Fire Protection SystemsFire Protection Systems

2. Is an anhydrous ammonia detection system in a

refrigeration machinery room a fire protection system?

3. Which of the following wall assemblies is not a method

to separate fire areas?

A.Fire wall

B.Fire partition

C.Fire barrier

D.Horizontal assembly

64

NO

§202 Definition of “Fire Protection System”

61 62

63 64

Page 17: 2018 IFC and IBC Fire Protection Systems with MT amendments

2018 IFC and IBC Fire Protection Systems with MT amendments

Copyright 2021 International Code Council 17

Automatic Sprinkler SystemsAutomatic Sprinkler Systems

Module 2

2018 IFC Fire Protection Systems

Automatic Sprinkler SystemsAutomatic Sprinkler Systems

NFPA 13 recognizes 4 types of

sprinkler systems:

Wet-pipe sprinkler system

Dry-pipe sprinkler system

Pre-action sprinkler system

Non-interlock

Single-interlock

Double-interlock

Deluge sprinkler system

66

These systems are designed

for use inside buildings with

temperatures >40°F

Graphic courtesy of Viking Corp.

Water enters system upon activation

of detection device; sprinkler must

still activate

Water enters system upon activation

of detection device or sprinkler

Water does not enter system until

activation of detection device

and sprinkler

These systems are designed

for use inside buildings with

temperatures ≤40°F

2018 IFC Fire Protection Systems

Allowed Increases Based on Fire

Sprinkler Systems

Allowed Increases Based on Fire

Sprinkler Systems

Code Section Modification NFPA 13 NFPA 13R NFPA 13D

IBC 504.3 & 504.4 Building Height Yes No No

IBC 506.2 Building Area Yes No No

IBC 507.4, 507.5 &

507.7Unlimited building area for certain occupancies Yes No No

IFC 503.1.1 Increased distance from building to FD access road Yes Yes Yes

IFC 507.5.1 Hydrant spacing increased to 600’ Yes Yes No

IFC 1017.2 Exit access travel distance Yes Yes No

IFC Table

5003.1.1(1) & (2)

100% increase in MAQ for certain hazardous

materialsYes No No

IFC Table 5003.11.1

100% increase in the MAQ for nonflammable solid

and nonflammable and noncombustible liquid

hazardous materials in Group M & S

Yes No No

IFC Table 5704.3.4.1100% increase in the MAQ for flammable and

combustible liquids in Group M & SYes No No

67 2018 IFC Fire Protection Systems

Allowed Reductions Based on Fire

Sprinkler Systems

Allowed Reductions Based on Fire

Sprinkler SystemsCode Section Modification NFPA 13 NFPA 13R NFPA 13D

IBC 403.2.1 Reduction in shaft rating in high-rise buildings Yes No No

IBC 404.2 Decorations in, and use of, atriums Yes No No

IBC Table 508.4 Separation of occupancies Yes No No

IBC 705.8.5 Vertical separation of openings Yes Yes No

IBC 708.3 Fire-resistance rating of fire partitions Yes No No

IBC 708.4.2 Draftstopping in attics of Group R-1 & R-2 Yes Yes No

IFC Table 803.3 Reduction in flame spread rating for interior finish Yes Yes No

IFC 907.2Manual fire alarm boxes in Group A, B, E, F, M, R-1,

R-2 & R-4Yes Yes No

IFC 1007.1.1 Separation of exits Yes Yes No

IFC Table 1020.1 Corridor walls in means of egress Yes Yes No

IFC 1028.1 Exit discharge Yes Yes No

IFC Table B105.1(1)50% reduction in fire flow for Group R-3 & R-4 and

1- and 2-family dwellingsYes Yes Yes

IFC Table B105.2 75% reduction in fire flow Yes Yes Yes

68

65 66

67 68

Page 18: 2018 IFC and IBC Fire Protection Systems with MT amendments

2018 IFC and IBC Fire Protection Systems with MT amendments

Copyright 2021 International Code Council 18

2018 IFC Fire Protection Systems

Design Criteria in NFPA 13Design Criteria in NFPA 13

Pipe schedule method

Control mode – density/design area method

This includes residential and quick-response

sprinklers

Control mode – specific application method

These designs are generally limited to storage

applications or special sprinklers

Suppression mode method

Limited to Early Suppression Fast-Response (ESFR)

sprinklers

69 2018 IFC Fire Protection Systems

Types of SprinklersTypes of Sprinklers

NFPA 13 recognizes several different types of sprinklers

configured for upright, pendent or sidewall installation

Early Suppression Fast-Response (ESFR)

Extended Coverage

Quick-Response Extended Coverage

Quick-Response (QR)

Residential

Standard Spray

Special

Specific Application Control Mode

70

2018 IFC Fire Protection Systems

Special Sprinklers

NFPA 13 §8.4.8

Special Sprinklers

NFPA 13 §8.4.8

Special sprinklers have been evaluated & listed

for performance in specific conditions:

Fire tests related to the intended hazard

Spray pattern distribution with respect to obstructions

and wetting of walls and floors

Evaluation of the sprinkler’s thermal sensitivity

Sprinkler performance under horizontal or sloped

ceilings

Area of design

Allowable clearance to ceilings

71 2018 IFC Fire Protection Systems

Automatic Fire Sprinklers

Data Sheet

Automatic Fire Sprinklers

Data Sheet Sprinkler data sheets generally contain:

Sprinkler selection criteria for residential, light hazard,

ordinary hazard, extra hazard, special designs and

storage applications

Minimum design pressure

Minimum or maximum clearances from the sprinkler

to the hazard

Installation requirements based on the selected

sprinkler

The SIN (Sprinkler Identification Number)

72

69 70

71 72

Page 19: 2018 IFC and IBC Fire Protection Systems with MT amendments

2018 IFC and IBC Fire Protection Systems with MT amendments

Copyright 2021 International Code Council 19

2018 IFC Fire Protection Systems

Manufacturer Data SheetManufacturer Data Sheet

73 2018 IFC Fire Protection Systems

Manufacturer Data SheetManufacturer Data Sheet

74

2018 IFC Fire Protection Systems

Manufacturer Data SheetManufacturer Data Sheet

75 2018 IFC Fire Protection Systems

Manufacturer Data SheetManufacturer Data Sheet

76

73 74

75 76

Page 20: 2018 IFC and IBC Fire Protection Systems with MT amendments

2018 IFC and IBC Fire Protection Systems with MT amendments

Copyright 2021 International Code Council 20

2018 IFC Fire Protection Systems

Manufacturer Data SheetManufacturer Data Sheet

77 2018 IFC Fire Protection Systems

Automatic Sprinkler SystemsAutomatic Sprinkler Systems

Does IBC/IFC §1020.4 allow an increase the

length of a dead-end corridor in a Group R-1

occupancy when an NFPA 13R automatic fire

sprinkler system is installed?

What prescriptive method of design is permitted

for the design of an automatic sprinkler system?

78

NO

Only NFPA 13 system, even in Group R

§1020.4

Pipe schedule

2018 IFC Fire Protection Systems

Automatic Sprinkler SystemsAutomatic Sprinkler Systems

3.What is RTI and what range of RTI is required

for a sprinkler to be either fast response, quick

response or residential?

4.What type of fire sprinkler system is designed for

all sprinklers to flow simultaneously?

79

RTI = Response Time Index

RTI of 50 – 80

Deluge sprinkler systemSprinkler System

Requirements

Sprinkler System

Requirements

Module 3

77 78

79 80

Page 21: 2018 IFC and IBC Fire Protection Systems with MT amendments

2018 IFC and IBC Fire Protection Systems with MT amendments

Copyright 2021 International Code Council 21

2018 IFC Fire Protection Systems

Required Fire SprinklersRequired Fire Sprinklers

Fire sprinklers requirements are based on:

Occupancy classification

Size of fire area containing a

specific occupancy

Occupant load in a specific

occupancy

Floor level of the specific occupancy

Specific operation occurring in

the building

Modification of other code

requirements

81

Group H-5

Group F-1 fire area

>12,000 ft²

Group A-2 with OL ≥100

Group A-3 on a level

other than the LED

High-piled storage

Height/Area

Travel distance

Haz Mat quantities

2018 IFC Fire Protection Systems

Fire Sprinkler System

Installation

Fire Sprinkler System

Installation

The area to be protected by sprinklers is dependent on

the occupancy classification

82

Occupancy Classification Fire Area OccupancyEntire

Floor 1

Entire

Building

A-1, A-2, A-3, A-4 X X

A-5 2

B Ambulatory Care Facilities X

E X X 3

F-1 X 4 X

H-1, H-2, H-3, H-4 X X 5

H-5 X

I X

M X X

R X

S X X

1 The fire sprinkler system is installed

on the floor level of the occupancy and

every floor level between that floor and

the LED, including the LED

2 Fire sprinklers are required in concession

stands, retail areas, press boxes and other

accessory use areas >1,000 ft²3 Fire sprinklers required in all

floors below the LED5 Group H occupancies with >100

lbs of pyroxylin plastics

4 Fire sprinklers required in fire areas

where woodworking occurs with an area

of 2,501-12,000 ft²

Bottom line – read the code

requirements carefully

2018 IFC Fire Protection Systems

Group A-2

Fire Sprinklers in Group AFire Sprinklers in Group A

Where fire sprinklers are

required in a Group A

occupancy located on a story

other than LED, fire sprinklers

must be installed on all stories

leading to all levels of exit

discharge that are used by the

Group A occupancy

83

Automatic sprinkler

system installed on

story with Group A

Automatic sprinkler

system installed on all

stories to all LED

§903.2.1.1, 903.2.1.2,

903.2.1.3, 903.2.1.4.

2018 IFC Fire Protection Systems

Group A-1

§903.2.1.1

Group A-1

§903.2.1.1

Fire sprinklers required and throughout all

stories from the Group A-1 occupancy to and

including the levels of exit discharge serving that

occupancy where one of the following conditions

exists:

Fire area >12,000 ft²

Fire area has an OL ≥300

Fire area is located on a level other than LED

Fire area contains a multitheater complex

84

81 82

83 84

Page 22: 2018 IFC and IBC Fire Protection Systems with MT amendments

2018 IFC and IBC Fire Protection Systems with MT amendments

Copyright 2021 International Code Council 22

2018 IFC Fire Protection Systems

Group A-2

§903.2.1.2

Group A-2

§903.2.1.2

Fire sprinklers required and throughout all

stories from the Group A-2 occupancy to and

including the levels of exit discharge serving that

occupancy where one of the following conditions

exists:

Fire area >5,000 ft²

Fire area has an OL ≥100

Fire area is located on a level other than LED

85 2018 IFC Fire Protection Systems

Group A-3 & A-4

§903.2.1.3, §903.2.1.4

Group A-3 & A-4

§903.2.1.3, §903.2.1.4

Fire sprinklers required and

throughout all stories from the

Group A-3, A-4 occupancy to and

including the levels of exit

discharge serving that

occupancy where one of the

following conditions exist:

Fire area >12,000 ft²

Fire area has OL ≥300

Fire area is located on a level other

than LED

86

2018 IFC Fire Protection Systems

Group A-5

§903.2.1.5

Group A-5

§903.2.1.5

Fire sprinklers required in the following areas in

excess of 1,000 ft² that are accessory to

stadiums or arenas:

Concession areas

Retail areas

Press boxes

87

OUTDOORSTADIUM

STANDS

INTERIORSPACE THAT

INCLUDES OTHEROCCUPANCIES

2018 IFC Fire Protection Systems

Group A-5

§903.2.1.5.1

Group A-5

§903.2.1.5.1 903.2.1.5.1 Spaces under

grandstands or bleachers.

Enclosed spaces under

grandstands or bleachers shall be

equipped with an automatic

sprinkler system in accordance with

Section 903.3.1.1 where either of

the following exist:

1. The enclosed area is 1,000

square feet (93 m2) or less and is

not constructed in accordance with

Section 1029.1.1.1.

2. The enclosed area exceeds

1,000 square feet (93 m2).

88

85 86

87 88

Page 23: 2018 IFC and IBC Fire Protection Systems with MT amendments

2018 IFC and IBC Fire Protection Systems with MT amendments

Copyright 2021 International Code Council 23

2018 IFC Fire Protection Systems

Assembly Occupancies on Roofs

§903.2.1.6

Assembly Occupancies on Roofs

§903.2.1.6

Fire sprinklers are

required on all floors

between an occupied roof

and the LED discharge

where assembly uses

occur on the rooftop and:

OL >100 for Group A-2, or

OL >300 for other Group A

occupancies

89 2018 IFC Fire Protection Systems

Multiple Group A Fire Areas

Montana Amendment - 903.2.1.7

Multiple Group A Fire Areas

Montana Amendment - 903.2.1.7

Montana Amendments to the International Building Code

Administrative Rule 24.301.146

Modifications to the International Building Code

Applicable to Both the Department’s and Local

Government Code Enforcement Programs

(12) Subsection 903.2.1.7 - Multiple Fire Areas

Deleted in its entirety.

90

2018 IFC Fire Protection Systems

Multiple Group A Fire Areas

§903.2.1.7

Multiple Group A Fire Areas

§903.2.1.7

Sprinklers required where

multiple fire areas contain

Group A-1, A-2, A-3 or A-4

occupancies that share

egress components and OL

≥300

91

Group A-2

Restaurant

OL = 93

Group A-3

Art Gallery

OL = 123

Group M

Book Store

OL = 110

Group A-2

Restaurant

OL = 93

Group A-2

Restaurant

OL = 93

Group A-2

Restaurant

OL = 93

Group A-3

Art Gallery

OL = 123

Group M

Book Store

OL = 50

All occupancies separated

by 2-HR fire barriers

Aggregate occupant load = 309

Therefore, sprinklers are required

All occupancies separated

by 2-HR fire barriers

All fire areas considered separately

Sprinklers not required

2018 IFC Fire Protection Systems

Ambulatory Care Facilities

§903.2.2

Ambulatory Care Facilities

§903.2.2

Fire sprinklers required on floors with

a Group B Ambulatory Care Facility

when:

≥4 care recipients incapable of

self-preservation

≥1 care recipients incapable of

self-preservation on a floor other

than LED

§903.3.2 requires the installation of

QR or residential sprinklers

throughout smoke compartments

containing treatment rooms

92

How do you determine

the number of care

recipients?

Count the beds

89 90

91 92

Page 24: 2018 IFC and IBC Fire Protection Systems with MT amendments

2018 IFC and IBC Fire Protection Systems with MT amendments

Copyright 2021 International Code Council 24

2018 IFC Fire Protection Systems

Ambulatory Care Facilities

§903.2.2

Ambulatory Care Facilities

§903.2.2 In buildings where ambulatory care is

provided on levels other than the

level of exit discharge, an automatic

sprinkler system shall be installed

throughout the entire floor as well as

all floors below where such care is

provided, and all floors between the

level of ambulatory care and the

nearest level of exit discharge, the

level of exit discharge, and all floors

below the level of exit discharge.

Exception: Floors classified as an

open parking garage are not required

to be sprinklered.

93 2018 IFC Fire Protection Systems

Group E

§903.2.3

Group E

§903.2.3

Fire sprinklers required in the occupancy when

one of the following conditions exist:

1. Fire area >12,000 ft²

2. All portions below LED

Sprinklers not required in areas below LED where each

classroom has at least one exterior exit door at ground level

3. The Group E fire area has an occupant load of >300

94

2018 IFC Fire Protection Systems

Group F-1

§903.2.4

Group F-1

§903.2.4

Fire sprinklers required throughout

the building where one of the

following conditions exist:

Fire area >12,000 ft²

Fire area is >3 stories above

grade

Aggregate fire areas >24,000 ft²

Used for manufacture of

upholstered furniture or

mattresses >2,500 ft²

95 2018 IFC Fire Protection Systems

Woodworking Operations

§903.2.4.1

Woodworking Operations

§903.2.4.1

Fire sprinklers required

throughout the building

where both of the

following conditions exist:

Fire area >2,500 ft²

The process generates finely

divided waste or uses finely

divided combustible materials

96

93 94

95 96

Page 25: 2018 IFC and IBC Fire Protection Systems with MT amendments

2018 IFC and IBC Fire Protection Systems with MT amendments

Copyright 2021 International Code Council 25

2018 IFC Fire Protection Systems

Group H

§903.2.5

Group H

§903.2.5

Fire sprinklers required in

all Group H occupancies

§5004.5 requires

systems to meet

Ordinary Hazard Group 2

criteria, at minimum with

3,000 ft² design area

0.17 gpm/ft²

Many materials

require more water

97

• Flammable & combustible liquids

• Flammable & pyrophoric gases

• Level 2 & 3 aerosols

• Organic peroxides

• Oxidizers

2018 IFC Fire Protection Systems

Group H-5

§903.2.5.2

Group H-5

§903.2.5.2

Fire sprinklers required

throughout the building

IFC Table 903.2.5.2

establishes minimum

design criteria for

automatic sprinklers

based on the location in

the building

98

2018 IFC Fire Protection Systems

Group I

§903.2.6

Group I

§903.2.6

Fire sprinklers required throughout the building

§903.2.6 allows the installation of NFPA 13R

systems in Group I-1 Condition 1

§903.3.2 requires the installation of QR or

residential sprinklers in:

All areas of smoke compartments containing care

recipient sleeping units in Group I-2

Sleeping units in Group I-1

99 2018 IFC Fire Protection Systems

Group M

§903.2.7

Group M

§903.2.7

Fire sprinklers required throughout

the building where one of the

following conditions exist:

Fire area >12,000 ft²

Fire area >3 stories above

grade

Aggregate fire areas >24,000 ft²

Used for display and sale of

upholstered furniture or

mattresses >5,000 ft²

100

97 98

99 100

Page 26: 2018 IFC and IBC Fire Protection Systems with MT amendments

2018 IFC and IBC Fire Protection Systems with MT amendments

Copyright 2021 International Code Council 26

2018 IFC Fire Protection Systems

Group R

§903.2.8

Group R

§903.2.8

Fire sprinklers required throughout the building

for all Group I occupancies

NFPA 13D systems in Group R-3, R-4 Condition

1 and care facilities with ≤5 clients

NFPA 13R systems in Group R-4 Condition 2

§903.3.2 requires the installation of QR or

residential sprinklers in dwelling units and

sleeping units

101

1- & 2-family dwellings and

townhomes built under the IRC

are sprinklered in accordance

with the IRC or NFPA 13D

2018 IFC Fire Protection Systems

Pedestal/Podium Construction

IBC §510.4

Pedestal/Podium Construction

IBC §510.4

Group R occupancies with

parking beneath

Depending on the

construction and the

building’s height and area,

the design of the sprinkler

system may be based on

NFPA 13, 13R or a

combination of NFPA 13

and 13R

102

2018 IFC Fire Protection Systems

Pedestal/Podium ConstructionPedestal/Podium Construction

103

NFPA 13R for Group R IF

≤4 stories AND

height is ≤60’

3-HR horizontal

assembly

Number of stories

for Group R

Any occupancy

other than

Group H

Type IA

construction

Building height

2018 IFC Fire Protection Systems

Pedestal/Podium ConstructionPedestal/Podium Construction

104

NFPA 13 for Group R IF

>4 stories OR

height is >60’

101 102

103 104