2018 IFC and IBC Fire Protection Systems with MT amendments
Transcript of 2018 IFC and IBC Fire Protection Systems with MT amendments
2018 IFC and IBC Fire Protection Systems with MT amendments
Copyright 2021 International Code Council 1
2018 IFC and IBC Fire
Protection Systems
2018 IFC and IBC Fire
Protection SystemsBased on the 2018 International Fire Code® (IFC®)
2018 International Building Code® (IBC®) and
State of Montana Amendments
Presenter InstructionsPresenter Instructions Many of these slides contain animation and graphics
When reviewing this presentation, you should utilize the “slide show
presentation mode” or in the “reading view”
This will allow you to become aware of the animation and graphics
on the slides
Click the “View” in the header, then click “Reading View” in the
“Presentation Views” group
Slides which contain animation will have one or more dots at the bottom
left corner of the slide. For example, there are 6 dots at the bottom of
this slide
Each dot represents a “click” which is needed for animation on the slide
before the next slide will appear
With each “click,” as an animation occurs, a dot will also disappear
When all the dots are gone, the next “click” will take you to the next
slide
Also note, “FCO” will be used to designate the Fire Code Official
2
2018 IFC Fire Protection Systems
WelcomeWelcome
Instructor Introduction
Exits
Breaks and Schedule
Cell Phones
Student Introductions – Poll Questions 1 - 3
3 2018 IFC Fire Protection Systems
DescriptionDescription
This seminar is designed to guide participants through
the 2018 IFC requirements related to fire protection
systems (Chapter 9) – With State of Utah Amendments
These requirements include:
Fire sprinkler systems
Fire-extinguishing systems
Standpipe systems
Fire alarm systems
Automatic detection systems
Smoke control/exhaust systems
Other fire protection devices and equipment
4
1 2
3 4
2018 IFC and IBC Fire Protection Systems with MT amendments
Copyright 2021 International Code Council 2
2018 IFC Fire Protection Systems
GoalGoal
Participants will be able to apply key provisions
regarding fire protection systems in the 2018 IFC
to aid in code application, administration and
enforcement
5 2018 IFC Fire Protection Systems
ObjectivesObjectives Upon completion, participants will be
better able to:
Define key terms
Explain why a fire protection system must conform to
code criteria and referenced standards
Determine where and when fire protection systems
are required
Explain the principles of how a fire protection system
detects and manages a fire
Understand the relationship between the code
(IFC/IBC) and the referenced standards
6
2018 IFC Fire Protection Systems
Prerequisite UnderstandingPrerequisite Understanding
Occupancy classifications are based on the use
and character of the building
Many code requirements are based on the
occupancy classification
7
Fire Protection SystemsFire Protection Systems
Module 1
5 6
7 8
2018 IFC and IBC Fire Protection Systems with MT amendments
Copyright 2021 International Code Council 3
2018 IFC Fire Protection Systems
Fire Protection SystemsFire Protection Systems
Definition of a Fire Protection System:
Approved devices, equipment and systems or
combinations of systems used to detect a fire,
activate an alarm, extinguish or control a fire,
control or manage smoke and products of a fire or
any combination thereof.
Given this definition, a fire protection
system is required to perform certain
functions
2018 IFC
§202
Page 27
9 2018 IFC Fire Protection Systems
Fire Protection SystemsFire Protection Systems
10
2018 IFC Fire Protection Systems
The IFC’s Intent for
Fire Protection Systems
The IFC’s Intent for
Fire Protection Systems
When a fire protection system is required, it is:
Designed and constructed in accordance with the
applicable NFPA standards
As modified by the code
Designed for the respective hazards being protected
Inspected and maintained in accordance with the IFC
and the applicable standards
Modified when the hazard changes and the fire
protection system is not capable of controlling a fire
11
• Fire sprinklers on combustible balconies in
multifamily dwellings – §903.3.1.2.1
• Exempt fire sprinkler locations – §903.3.1.1.1
• Limited area fire sprinkler system – §903.3.8
2018 IFC Fire Protection Systems
Why the IFC Requires a
Fire Protection System
Why the IFC Requires a
Fire Protection System
Fire protection systems are required inside or
outside of buildings because of:
Occupancy classification in the fire area or the
building
Occupant load of the fire area or building
Height or area of the building
Quantity of haz mat stored or used inside of a building
Type of hazard stored or used inside of a building
Fire loss history for specific hazards
12
Group I-2
Fire area has an OL ≥300
Building has a story with OL ≥30
and ≥55’ above LLFDVAStoring or using >100 lbs pyroxylin plastics
Type IIB dry cleaning operation
Spray application of flammable finishes
9 10
11 12
2018 IFC and IBC Fire Protection Systems with MT amendments
Copyright 2021 International Code Council 4
2018 IFC Fire Protection Systems
Chapter 9 ArrangementChapter 9 Arrangement
IFC Chapter 9 is divided into 15 sections, including:
901: General
903: Automatic Sprinkler Systems
904: Alternative Fire-extinguishing Systems
905: Standpipe Systems
907: Fire Alarm and Detection Systems
908: Emergency Alarm Systems
909: Smoke Control Systems
910: Smoke and Heat Removal
914: Fire Protection Based on Special Detailed Requirements of
Use and Occupancy
915: Carbon Monoxide Detection
13
IBC Ch 9 is almost
identical to IFC Ch 9
Some differences
occur in §901
2018 IFC Fire Protection Systems
General Provisions
§901
General Provisions
§901Provision IFC Section IBC Section
Construction documents 901.2 −
Permits 901.3 −
Installation 901.4 901.2
Modifications − 901.3
Threads − 901.4
Acceptance testing 901.5 901.5
Inspection, testing and maintenance 901.6 901.3
Fire areas 901.4.3 901.7
Pump and riser room size − 901.8
Systems out of service 901.7 −
Removal of or tampering with equipment 901.8 −
Termination of monitoring service 901.9 −
Recall of fire protection components 901.10 −
14
2018 IFC Fire Protection Systems
Construction Documents
§901.2
Construction Documents
§901.2 Fire Code Official (FCO) are
authorized to require the
submittal, review and approval of
design drawings and calculations
for fire protection systems
A contractor’s statement of
compliance can be required
Documents must show that
the system complies with the:
Plans
Applicable standard
Manufacturer’s instructions
15 2018 IFC Fire Protection Systems
Construction Documents - 901.2
Montana Amendment
Construction Documents - 901.2
Montana Amendment Administrative Rule 24.301.146 (13)
In new or existing structures, the building official
may allow the installation of noncode compliant
equipment, facilities, or structural elements
including but not limited to fire-extinguishing
(sprinkler) systems or fire-resistive construction,
which are not required by the building code, upon
the finding that such installation does not
negatively impact the overall compliance of the
structure with the building code.
16
13 14
15 16
2018 IFC and IBC Fire Protection Systems with MT amendments
Copyright 2021 International Code Council 5
2018 IFC Fire Protection Systems
Construction Documents - 901.2
Montana Amendment
Construction Documents - 901.2
Montana Amendment Administrative Rule 24.301.146 (13)
Subsection 901.2, Fire Protection Systems, is
modified by deleting the exception and replacing
with the following: "Any fire protection system or
portion thereof not required by this code shall
be permitted to be installed for partial or
complete protection at the discretion of the
building official."
17 2018 IFC Fire Protection Systems
Construction Documents – 902.8
Montana Amendment
Construction Documents – 902.8
Montana Amendment Administrative Rule 24.301.146 (16)
Delete Subsection 903.2.8 and replace with the
following:
18
2018 IFC Fire Protection Systems
Construction Documents – 902.8
Montana Amendment
Construction Documents – 902.8
Montana Amendment Administrative Rule 24.301.146 (16)
Delete Subsection 903.2.8 and replace with the
following:
19 2018 IFC Fire Protection Systems
Construction Documents – 902.8
Montana Amendment
Construction Documents – 902.8
Montana Amendment "1. An approved automatic sprinkler system installed in
accordance with Section 903.3 shall be provided in all
Group R buildings meeting any of the following criteria:
"a. 9 or more transient guests or 5 or more transient
guestrooms;
"b. 9 or more occupants in other than dwelling units;
"c. 5 or more dwelling units; or
"d. more than 2 stories.
20
17 18
19 20
2018 IFC and IBC Fire Protection Systems with MT amendments
Copyright 2021 International Code Council 6
2018 IFC Fire Protection Systems
Construction Documents – 902.8
Montana Amendment
Construction Documents – 902.8
Montana Amendment "2. In lieu of the above required automatic sprinkler
system in buildings not more than three stories
above the lowest level of exit discharge, each
transient guestroom may be provided with at least
one door leading directly to an exterior exit access
that leads directly to approved exits.
21 2018 IFC Fire Protection Systems
Construction Documents – 902.8
Montana Amendment
Construction Documents – 902.8
Montana Amendment "3. "Transient guest" for the purpose of this
subsection shall mean an occupant who is
primarily transient in nature, staying at one location
for 30 days or less."
"4. "The requirements for automatic sprinkler
systems for R-4 occupancies are found in ARM
24.301.146."
22
2018 IFC Fire Protection Systems
Construction Documents - 903.3.5
Montana Amendment
Construction Documents - 903.3.5
Montana Amendment Administrative Rule 24.301.146 (14)
Subsection 903.3.5
Inadequate Water Supply
Amended by addition of the following:
23 2018 IFC Fire Protection Systems
Construction Documents - 903.3.5
Montana Amendment
Construction Documents - 903.3.5
Montana Amendment "This subsection shall apply to buildings which are
required by the International Building Code to be
provided with an automatic fire extinguishing system
and do not have access to an existing multiple user
water supply system, such as a municipal water supply
system or a private community water supply system,
capable of providing the water supply requirements of
National Fire Protection Association Standard for the
Installation of Sprinkler Systems, 2016 edition (NFPA
13).
24
21 22
23 24
2018 IFC and IBC Fire Protection Systems with MT amendments
Copyright 2021 International Code Council 7
2018 IFC Fire Protection Systems
Construction Documents - 903.3.5
Montana Amendment
Construction Documents - 903.3.5
Montana Amendment Under such circumstances, water storage
requirements may be modified by the building official.
The modified design shall include sufficient storage
onsite to operate the hydraulically remote area for the
response time of the local fire department.
Response time is the time from alarm to the time the
fire department can apply water to the fire.
25 2018 IFC Fire Protection Systems
Construction Documents - 903.3.5
Montana Amendment
Construction Documents - 903.3.5
Montana Amendment Response time shall be established by the use of the
formula T = 6.5 minutes (mobilization time) + 1.7
minutes/mile D (travel time), where T is response time,
in minutes, and D is distance, in miles, from the fire
station to the building.
The modified water supply shall be sufficient to operate
the system for the response time calculated above but
not be less than 20 minutes.
Water supply requirements shall be established by
using the area/density method as defined in NFPA 13.
26
2018 IFC Fire Protection Systems
Construction Documents - 903.3.5
Montana Amendment
Construction Documents - 903.3.5
Montana Amendment A reduction in water storage of up to 50 percent, but
not less than that required for a 20-minute supply is
allowed.
All automatic fire sprinkler system designs and
components shall be in compliance with NFPA 13.
When a modified water storage is allowed, the
automatic fire sprinkler system must be equipped with
a flow alarm, digital alarm communicator transmitter,
and a fire department connection.
27 2018 IFC Fire Protection Systems
Construction Documents - 903.3.5
Montana Amendment
Construction Documents - 903.3.5
Montana Amendment The automatic fire sprinkler system shall be monitored
by an approved central station in accordance with
NFPA 72, National Fire Alarm Code, 2016 edition."
28
25 26
27 28
2018 IFC and IBC Fire Protection Systems with MT amendments
Copyright 2021 International Code Council 8
2018 IFC Fire Protection Systems
Table 1020.1 - Montana AmendmentTable 1020.1 - Montana Amendment
(18) For "R" occupancies that are exempt from the
requirements of a fire sprinkler system, pursuant to
ARM 24.301.146(16), Table 1020.1, referenced in
subsection 1020.1, shall be amended in regard to
"R" occupancies by the deletion of the language
"Greater than 10" and insertion of the language
"Greater than 8" under the heading "Occupant
Load Serviced By Corridor."
29 2018 IFC Fire Protection Systems
R-4 - Montana AmendmentR-4 - Montana Amendment
(39) Notwithstanding any other provisions within
the International Building Code, the following adult
group residential facilities, licensed by the
Department of Public Health and Human Services
will be classified and treated as follows:
(a) Category A assisted living facilities with 9 to 19
residents, as referenced in 50-5-226, MCA, will be
classified as an R-4 occupancy for building permit
and construction standard purposes. Automatic fire
sprinkler systems are not required.
30
2018 IFC Fire Protection Systems
R-4 - Montana AmendmentR-4 - Montana Amendment
(b) Category B assisted living facilities with 9 to 19
residents, as referenced in 50-5-226, MCA, will be
classified as an R-4 occupancy for building permit
and construction standards purposes. In addition, a
Category B assisted living facility shall have an
automatic fire sprinkler system and provide an
accessible sleeping room or space for each
Category B resident.
31 2018 IFC Fire Protection Systems
R-4 - Montana AmendmentR-4 - Montana Amendment
(c) An assisted living facility with 20 or more
residents, in any combination of Category A or
Category B, will be classified as an R-2 occupancy
for building permit and construction standards and
shall meet accessibility standards as provided in
Subsection 1103 of the International Building
Code. Automatic fire sprinkler systems are
required. A fire wall cannot be used to isolate and
reduce occupant loads in order to avoid an R-2
classification.
32
29 30
31 32
2018 IFC and IBC Fire Protection Systems with MT amendments
Copyright 2021 International Code Council 9
2018 IFC Fire Protection Systems
Required vs Non-Required
§901.4.1 and §901.4.2
Required vs Non-Required
§901.4.1 and §901.4.2
Required fire protection systems must comply
with the code and the applicable standards
Non-required fire protection systems must ALSO
comply with the code and the applicable
standards
Wherever, any code modification or allowance is
made as a result of sprinklers, the system becomes a
required system
33 2018 IFC Fire Protection Systems
Additional Fire Protection
Systems
§901.4.4
Additional Fire Protection
Systems
§901.4.4
Where the FCO deems
a hazard to be of a
unique nature or unduly
difficult for fire
department access,
additional fire protection
features can be
required
34
2018 IFC Fire Protection Systems
Pump and Riser Room
§901.4.6
Pump and Riser Room
§901.4.6
Pump room or riser room
is not required, but, if
provided, they must have
adequate room for service
Following
manufacturer’s
specifications
Ability to remove largest
piece of equipment and
reinstall
35 2018 IFC Fire Protection Systems
Pump and Riser Room
§901.4.6.1 – 901.4.64
Pump and Riser Room
§901.4.6.1 – 901.4.64
Access
Marking on Access Doors
Approved Sign
Min height – 2”
Min Stroke width – ½ in
Environment
> 400 F
Lighting
36
33 34
35 36
2018 IFC and IBC Fire Protection Systems with MT amendments
Copyright 2021 International Code Council 10
2018 IFC Fire Protection Systems
Fire Pumps
§913
Fire Pumps
§913
Must meet NFPA 20
requirements
Pump room maintained >40°F
Cables and circuits protected by
2-HR construction or UL 2196
IBC §913.2.1: 1-HR separation,
2-HR in high-rise, or ≥50’
Class II fuel supply is not
included in MAQ if it meets IFC
§603.3.2
37
IFC §603.3.2:
• ≤660 gallon
• ≤3,000 gallon if in PAST
and room is sprinklered
Pyrotenax MI cable—2-hour fire-rated cable
Graphic courtesy of Pentair Thermal Management
2018 IFC Fire Protection Systems
Installation Acceptance Testing
§901.5
Installation Acceptance Testing
§901.5
Before a fire protection
system can be approved it
must be tested
Fire protection systems
must be accepted and
approved based on the
applicable NFPA fire
protection system standards
38
Photo courtesy of Protection Development Inc.
2018 IFC Fire Protection Systems
Systems Out of Service
§901.7
Systems Out of Service
§901.7
Fire protection system impairment
is a critical event that must be
reported to the FCO
Impairment of fire protection
systems requires:
An individual be designated as the
impairment coordinator
A plan of action for the impairment
39
Impairment coordinator:
• Responsible for all work
• Notify FD of the status
• Ensure system is restored
2018 IFC Fire Protection Systems
Poll QuestionPoll Question
Question #4: Who is responsible for arranging
and scheduling the Final Inspection and
Acceptance Testing for a Fire Protection
System?
Poll Question - #5: When a Fire Protection
System is to be taken out of service, the Fire
Code Official should only be notified if the
system is down for more than:
37 38
39 40
2018 IFC and IBC Fire Protection Systems with MT amendments
Copyright 2021 International Code Council 11
2018 IFC Fire Protection Systems
Important TermsImportant Terms
Two important definitions must be reviewed and
understood
Several thresholds for requirements are based
on these definitions
Level of exit discharge (LED)
Fire area
41 2018 IFC Fire Protection Systems
Level of Exit DischargeLevel of Exit Discharge
Definition of Level of Exit Discharge :
The story at the point at which an exit terminates
and an exit discharge begins.
A building can have more than one level
of exit discharge
2018 IFC
§202
Page 25
42
2018 IFC Fire Protection Systems
Level of Exit DischargeLevel of Exit Discharge
43
Highest level of
exit discharge
Lowest level of
exit discharge
2018 IFC Fire Protection Systems
Fire AreaFire Area
Definition of Fire Area:
The aggregate floor area enclosed and bounded by
fire walls, fire barriers, exterior walls or horizontal
assemblies of a building. Areas of the building not
provided with surrounding walls shall be included in
the fire area if such areas are included within the
horizontal projection of the roof or floor next above.
2018 IFC
§202
Page 27
44
41 42
43 44
2018 IFC and IBC Fire Protection Systems with MT amendments
Copyright 2021 International Code Council 12
2018 IFC Fire Protection Systems
Fire Area Bounded by
Exterior Walls
Fire Area Bounded by
Exterior Walls
45
Fire Area 1
A building constructed with or
without fire-resistant
materials or assemblies is a
fire area
2018 IFC Fire Protection Systems
Fire Area Compartmentalized
Using Fire Barriers
Fire Area Compartmentalized
Using Fire Barriers
46
Fire Barriers
Fire Area 1 Fire Area 2 Fire Area 3
A building divided using fire-resistant
assemblies can have one or more fire areas
2018 IFC Fire Protection Systems
Fire Areas in Multistory
Buildings
Fire Areas in Multistory
Buildings
47
Fire Area 1 Fire Area 3Fire Area 2
Fire Barriers
2018 IFC Fire Protection Systems
Fire Areas in Multistory
Buildings
Fire Areas in Multistory
Buildings
48
Fire Area 3
Fire Area 1
Fire Area 2Fire-resistance-rated
Floor/Ceiling Assembly
45 46
47 48
2018 IFC and IBC Fire Protection Systems with MT amendments
Copyright 2021 International Code Council 13
2018 IFC Fire Protection Systems
Fire Areas
Using a Fire Wall
Fire Areas
Using a Fire Wall
Fire walls can divide a structure into ≥ 2 buildings
Each building becomes its own fire area
Each building can be further subdivided with fire barriers
49
Fire Area 1 Fire Area 2Fire Area 1 Fire Area 2 Fire Area 3 Fire Area 4
Building 1 Building 2
Fire Wall
Fire Barriers2018 IFC Fire Protection Systems
How Many Fire Areas?How Many Fire Areas?
50
9,000 square feet
Group B
7,000 square feet
Group A-2
16,000 square feet
Group B
Fire Area 2
Fire Area 1
Fire Barrier
Horizontal Fire-resistance-
rated Assembly
2018 IFC Fire Protection Systems
Fire Area Application
IFC §901.4.3, IBC §901.7
Fire Area Application
IFC §901.4.3, IBC §901.7
Fire areas. Where buildings, or portions thereof, are
divided into fire areas so as not to exceed the limits
established for requiring a fire protection system in
accordance with this chapter, such fire areas shall be
separated by fire barriers constructed in accordance
with §707 of the IBC or horizontal assemblies
constructed in accordance with §711 of the IBC, or
both, having a fire-resistance rating of not less than
that determined in accordance with §707.3.10 of the
International Building Code.
2018 IFC
§901.4.3
Page 103
51 2018 IFC Fire Protection Systems
IBC Table 707.3.10IBC Table 707.3.10
OCCUPANCY GROUPFIRE-RESISTANCE
RATING (hours)
H-1, H-2 4
F-1, H-3, S-1 3
A, B, E, F-2, H-4, H-5, I, M, R, S-2 2
U 1
2018 IBC
Table 707.3.10
Page 133
52
NOTE: a fire area must be at least 1-HR fire-
resistance-rated construction
But in most cases, 1-HR is not adequate
Fire-resistance Rating Requirements for Fire Barrier
Assemblies or Horizontal Assemblies Between Fire Areas
49 50
51 52
2018 IFC and IBC Fire Protection Systems with MT amendments
Copyright 2021 International Code Council 14
2018 IFC Fire Protection Systems
IBC Table 508.4IBC Table 508.4
Required Separation of Occupancies (hours)
2018 IBC
Table 508.4
Page 115
53
Occupancy
Group
A, EI-1, I-3,
I-4I-2 R a F-2,
S-2a, U
Be, F-1,
M, S-1H-1 H-2
H-3,
H-4H-5
S NS S NS S NS S NS S NS S NS S NS S NS S NS S NS
A, E N N 1 2 2 NP 1 2 N 1 1 2 NP NP 3 4 2 3 2 NP
I-1 a, I-3, I-4 - - N N 2 NP 1 NP 1 2 1 2 NP NP 3 NP 2 NP 2 NP
I-2 - - - - N N 2 NP 2 NP 2 NP NP NP 3 NP 2 NP 2 NP
R a - - - - - - N N 1 c 2 c 1 2 NP NP 3 NP 2 NP 2 NP
F-2, S-2 b, U - - - - - - - - N N 1 2 NP NP 3 4 2 3 2 NP
B e, F-1, M,
S-1- - - - - - - - - - N N NP NP 2 3 1 2 1 NP
H-1 - - - - - - - - - - - - N NP NP NP NP NP NP NP
H-2 - - - - - - - - - - - - - - N NP 1 NP 1 NP
H-3, H-4 - - - - - - - - - - - - - - - - 1 d NP 1 NP
H-5 - - - - - - - - - - - - - - - - - - N NP
Separate Group I-1
from Group M
2018 IFC Fire Protection Systems
IBC Table 706.4IBC Table 706.4
Fire Wall Fire-resistance Ratings
a. In Type II or V construction, walls shall be permitted to have
a 2-hour fire-resistance rating.
b. For Group H-1, H-2 or H-3 buildings, also see Sections
415.7 and 415.8
2018 IBC
Table 706.4
Page 131
54
GROUPFIRE-RESISTANCE
RATING (hours)
A, B, E, H-4, I, R-1, R-2, U 3 a
F-1, H-3 b, H-5, M, S-1 3
H-1, H-2 4 b
F-2, R-3, R-4, S-2 2
2018 IFC Fire Protection Systems
Design and Installation
Requirements §903.3
Design and Installation
Requirements §903.3
Before reviewing the IFC requirements for fire
sprinkler systems, it is important to understand:
The various standards applicable to fire sprinkler
system design
The relationship between the code and the standard
55 2018 IFC Fire Protection Systems
Design and Installation
Requirements §903.3
Design and Installation
Requirements §903.3
NFPA publishes 3 standards governing the
design, installation, testing and maintenance of
fire sprinkler systems:
§903.3.1.1 – NFPA 13, Installation of Sprinkler
Systems
§903.3.1.2 – NFPA 13R, Installation of Sprinkler
Systems in Low-Rise Residential Occupancies
§903.3.1.3 – NFPA 13D, Sprinkler Systems for One-
and Two-Family Dwellings and Manufactured Homes
56
53 54
55 56
2018 IFC and IBC Fire Protection Systems with MT amendments
Copyright 2021 International Code Council 15
2018 IFC Fire Protection Systems
Application Matrix of the
Sprinkler Design Standards
Application Matrix of the
Sprinkler Design Standards
System Feature
Sprinkler Standard
NFPA 13 NFPA 13RNFPA 13D or
IRC §P2904
Extent of
ProtectionThroughout the building
Occupied
spacesOccupied spaces
Design IntentLife Safety &
Property ProtectionLife Safety Life Safety
Applicability All OccupanciesGroup R up to
4-stories or 60’
1- & 2-family dwellings
& Townhomes
Design Methods
Pipe schedule; Control mode –
discharge density/design area;
Control mode – specific
application; Suppression mode
4 sprinklers per
compartment
2 sprinklers per
compartment
Sprinklers All listed & approved typesListed
ResidentialListed Residential
Minimum H2O
Supply Duration30 to 120 minutes 30 Minutes 7 or 10 Minutes
572018 IFC Fire Protection Systems
“Installed Throughout”“Installed Throughout”
58
IFC Table 1017.2 Exit Access Travel Distance, Footnote c
Buildings equipped throughout with an automatic sprinkler
system in accordance with §903.3.1.1.
IFC Table 5003.1.1(1) MAQ per Control Area, Note d
Maximum allowable quantities shall be increased 100
percent in buildings equipped throughout with an approved
automatic sprinkler system in accordance with §903.3.1.1.
IBC Table 506.2 Allowable Area, Note S1
S1 = Buildings a maximum of one story above grade plane
equipped throughout with an automatic sprinkler system
installed in accordance with §903.3.1.1
What does
“equipped throughout” or
“installed throughout” mean?
2018 IFC Fire Protection Systems
Poll QuestionPoll Question
Question #6: Can an NFPA 13R fire sprinkler
system protect an entire building when the
primary use of the building is residential, but the
building also contains small accessory uses?
2018 IFC Fire Protection Systems
“Installed Throughout”“Installed Throughout”
Under the design of NFPA 13, are all areas in
the building protected with sprinklers?
Under the design of NFPA 13R, are all areas in
the building protected with sprinklers?
Under the design of NFPA 13D or IRC §P2904,
are all areas in the building protected with
sprinklers?
60
NO
• Attic spaces <6” high
• Concealed spaces without combustible construction NO
• Attic spaces without fuel-fired equipment
• Small bathrooms
NO
• Attic spaces without fuel-fired equipment
• Small bathrooms
• Small closets with noncombustible wall covering
So which design provides
for fire sprinklers
“installed throughout”?
57 58
59 60
2018 IFC and IBC Fire Protection Systems with MT amendments
Copyright 2021 International Code Council 16
2018 IFC Fire Protection Systems
“Installed Throughout”“Installed Throughout”
§903.3.1.1 states:
Where the provisions of this code require that a
building or portion thereof be equipped throughout
with an automatic sprinkler system in accordance with
this section, sprinklers shall be installed throughout in
accordance with NFPA 13 except as provided in
Sections 903.3.1.1.1 and 903.3.1.1.2.
61
“Installed throughout” means that sprinklers are
installed throughout the building in all locations
as required by the design standard and the code
2018 IFC Fire Protection Systems
“Installed Throughout”“Installed Throughout”
903.3.1.1.1 Exempt locations. Automatic sprinklers shall not be required in
the following rooms or areas where such rooms or areas are protected with an
approved automatic fire detection system in accordance with §907.2 that will
respond to visible or invisible particles of combustion. Sprinklers shall not be
omitted from a room merely because it is damp, of fire-resistance-rated
construction or contains electrical equipment.
1. A room where the application of water, or flame and water, constitutes a
serious life or fire hazard.
62
2. A room or space where sprinklers are considered undesirable because of the
nature of the contents, where approved by the fire code official.3. Generator and transformer rooms separated from the remainder of the
building by walls and floor/ceiling or roof/ceiling assemblies having a fire-
resistance rating of not less than 2 hours.4. Rooms or areas that are of noncombustible construction with wholly
noncombustible contents.5. Fire service access elevator machine rooms and machinery spaces.
6. Machine rooms, machinery spaces, control rooms and control spaces
associated with occupant evacuation elevators designed in accordance with
§3008 of the IBC.
• These provisions are not found in NFPA 13
• These provisions are less restrictive than NFPA 13
• §102.7.1 – code provisions take precedence over
the standard
2018 IFC Fire Protection Systems
Fire Protection SystemsFire Protection Systems
Given: 89,000 ft² Group S-1 warehouse. The fire
sprinkler system was designed to protect rack
storage of Class III commodities in double row
racks 24’ high. The original tenant moved out of
the building and the new tenant is storing Class
IV commodities.
What section would apply to ensure the
automatic sprinkler system is adequately
protecting these new commodities?
63
§901.4
2018 IFC Fire Protection Systems
Fire Protection SystemsFire Protection Systems
2. Is an anhydrous ammonia detection system in a
refrigeration machinery room a fire protection system?
3. Which of the following wall assemblies is not a method
to separate fire areas?
A.Fire wall
B.Fire partition
C.Fire barrier
D.Horizontal assembly
64
NO
§202 Definition of “Fire Protection System”
61 62
63 64
2018 IFC and IBC Fire Protection Systems with MT amendments
Copyright 2021 International Code Council 17
Automatic Sprinkler SystemsAutomatic Sprinkler Systems
Module 2
2018 IFC Fire Protection Systems
Automatic Sprinkler SystemsAutomatic Sprinkler Systems
NFPA 13 recognizes 4 types of
sprinkler systems:
Wet-pipe sprinkler system
Dry-pipe sprinkler system
Pre-action sprinkler system
Non-interlock
Single-interlock
Double-interlock
Deluge sprinkler system
66
These systems are designed
for use inside buildings with
temperatures >40°F
Graphic courtesy of Viking Corp.
Water enters system upon activation
of detection device; sprinkler must
still activate
Water enters system upon activation
of detection device or sprinkler
Water does not enter system until
activation of detection device
and sprinkler
These systems are designed
for use inside buildings with
temperatures ≤40°F
2018 IFC Fire Protection Systems
Allowed Increases Based on Fire
Sprinkler Systems
Allowed Increases Based on Fire
Sprinkler Systems
Code Section Modification NFPA 13 NFPA 13R NFPA 13D
IBC 504.3 & 504.4 Building Height Yes No No
IBC 506.2 Building Area Yes No No
IBC 507.4, 507.5 &
507.7Unlimited building area for certain occupancies Yes No No
IFC 503.1.1 Increased distance from building to FD access road Yes Yes Yes
IFC 507.5.1 Hydrant spacing increased to 600’ Yes Yes No
IFC 1017.2 Exit access travel distance Yes Yes No
IFC Table
5003.1.1(1) & (2)
100% increase in MAQ for certain hazardous
materialsYes No No
IFC Table 5003.11.1
100% increase in the MAQ for nonflammable solid
and nonflammable and noncombustible liquid
hazardous materials in Group M & S
Yes No No
IFC Table 5704.3.4.1100% increase in the MAQ for flammable and
combustible liquids in Group M & SYes No No
67 2018 IFC Fire Protection Systems
Allowed Reductions Based on Fire
Sprinkler Systems
Allowed Reductions Based on Fire
Sprinkler SystemsCode Section Modification NFPA 13 NFPA 13R NFPA 13D
IBC 403.2.1 Reduction in shaft rating in high-rise buildings Yes No No
IBC 404.2 Decorations in, and use of, atriums Yes No No
IBC Table 508.4 Separation of occupancies Yes No No
IBC 705.8.5 Vertical separation of openings Yes Yes No
IBC 708.3 Fire-resistance rating of fire partitions Yes No No
IBC 708.4.2 Draftstopping in attics of Group R-1 & R-2 Yes Yes No
IFC Table 803.3 Reduction in flame spread rating for interior finish Yes Yes No
IFC 907.2Manual fire alarm boxes in Group A, B, E, F, M, R-1,
R-2 & R-4Yes Yes No
IFC 1007.1.1 Separation of exits Yes Yes No
IFC Table 1020.1 Corridor walls in means of egress Yes Yes No
IFC 1028.1 Exit discharge Yes Yes No
IFC Table B105.1(1)50% reduction in fire flow for Group R-3 & R-4 and
1- and 2-family dwellingsYes Yes Yes
IFC Table B105.2 75% reduction in fire flow Yes Yes Yes
68
65 66
67 68
2018 IFC and IBC Fire Protection Systems with MT amendments
Copyright 2021 International Code Council 18
2018 IFC Fire Protection Systems
Design Criteria in NFPA 13Design Criteria in NFPA 13
Pipe schedule method
Control mode – density/design area method
This includes residential and quick-response
sprinklers
Control mode – specific application method
These designs are generally limited to storage
applications or special sprinklers
Suppression mode method
Limited to Early Suppression Fast-Response (ESFR)
sprinklers
69 2018 IFC Fire Protection Systems
Types of SprinklersTypes of Sprinklers
NFPA 13 recognizes several different types of sprinklers
configured for upright, pendent or sidewall installation
Early Suppression Fast-Response (ESFR)
Extended Coverage
Quick-Response Extended Coverage
Quick-Response (QR)
Residential
Standard Spray
Special
Specific Application Control Mode
70
2018 IFC Fire Protection Systems
Special Sprinklers
NFPA 13 §8.4.8
Special Sprinklers
NFPA 13 §8.4.8
Special sprinklers have been evaluated & listed
for performance in specific conditions:
Fire tests related to the intended hazard
Spray pattern distribution with respect to obstructions
and wetting of walls and floors
Evaluation of the sprinkler’s thermal sensitivity
Sprinkler performance under horizontal or sloped
ceilings
Area of design
Allowable clearance to ceilings
71 2018 IFC Fire Protection Systems
Automatic Fire Sprinklers
Data Sheet
Automatic Fire Sprinklers
Data Sheet Sprinkler data sheets generally contain:
Sprinkler selection criteria for residential, light hazard,
ordinary hazard, extra hazard, special designs and
storage applications
Minimum design pressure
Minimum or maximum clearances from the sprinkler
to the hazard
Installation requirements based on the selected
sprinkler
The SIN (Sprinkler Identification Number)
72
69 70
71 72
2018 IFC and IBC Fire Protection Systems with MT amendments
Copyright 2021 International Code Council 19
2018 IFC Fire Protection Systems
Manufacturer Data SheetManufacturer Data Sheet
73 2018 IFC Fire Protection Systems
Manufacturer Data SheetManufacturer Data Sheet
74
2018 IFC Fire Protection Systems
Manufacturer Data SheetManufacturer Data Sheet
75 2018 IFC Fire Protection Systems
Manufacturer Data SheetManufacturer Data Sheet
76
73 74
75 76
2018 IFC and IBC Fire Protection Systems with MT amendments
Copyright 2021 International Code Council 20
2018 IFC Fire Protection Systems
Manufacturer Data SheetManufacturer Data Sheet
77 2018 IFC Fire Protection Systems
Automatic Sprinkler SystemsAutomatic Sprinkler Systems
Does IBC/IFC §1020.4 allow an increase the
length of a dead-end corridor in a Group R-1
occupancy when an NFPA 13R automatic fire
sprinkler system is installed?
What prescriptive method of design is permitted
for the design of an automatic sprinkler system?
78
NO
Only NFPA 13 system, even in Group R
§1020.4
Pipe schedule
2018 IFC Fire Protection Systems
Automatic Sprinkler SystemsAutomatic Sprinkler Systems
3.What is RTI and what range of RTI is required
for a sprinkler to be either fast response, quick
response or residential?
4.What type of fire sprinkler system is designed for
all sprinklers to flow simultaneously?
79
RTI = Response Time Index
RTI of 50 – 80
Deluge sprinkler systemSprinkler System
Requirements
Sprinkler System
Requirements
Module 3
77 78
79 80
2018 IFC and IBC Fire Protection Systems with MT amendments
Copyright 2021 International Code Council 21
2018 IFC Fire Protection Systems
Required Fire SprinklersRequired Fire Sprinklers
Fire sprinklers requirements are based on:
Occupancy classification
Size of fire area containing a
specific occupancy
Occupant load in a specific
occupancy
Floor level of the specific occupancy
Specific operation occurring in
the building
Modification of other code
requirements
81
Group H-5
Group F-1 fire area
>12,000 ft²
Group A-2 with OL ≥100
Group A-3 on a level
other than the LED
High-piled storage
Height/Area
Travel distance
Haz Mat quantities
2018 IFC Fire Protection Systems
Fire Sprinkler System
Installation
Fire Sprinkler System
Installation
The area to be protected by sprinklers is dependent on
the occupancy classification
82
Occupancy Classification Fire Area OccupancyEntire
Floor 1
Entire
Building
A-1, A-2, A-3, A-4 X X
A-5 2
B Ambulatory Care Facilities X
E X X 3
F-1 X 4 X
H-1, H-2, H-3, H-4 X X 5
H-5 X
I X
M X X
R X
S X X
1 The fire sprinkler system is installed
on the floor level of the occupancy and
every floor level between that floor and
the LED, including the LED
2 Fire sprinklers are required in concession
stands, retail areas, press boxes and other
accessory use areas >1,000 ft²3 Fire sprinklers required in all
floors below the LED5 Group H occupancies with >100
lbs of pyroxylin plastics
4 Fire sprinklers required in fire areas
where woodworking occurs with an area
of 2,501-12,000 ft²
Bottom line – read the code
requirements carefully
2018 IFC Fire Protection Systems
Group A-2
Fire Sprinklers in Group AFire Sprinklers in Group A
Where fire sprinklers are
required in a Group A
occupancy located on a story
other than LED, fire sprinklers
must be installed on all stories
leading to all levels of exit
discharge that are used by the
Group A occupancy
83
Automatic sprinkler
system installed on
story with Group A
Automatic sprinkler
system installed on all
stories to all LED
§903.2.1.1, 903.2.1.2,
903.2.1.3, 903.2.1.4.
2018 IFC Fire Protection Systems
Group A-1
§903.2.1.1
Group A-1
§903.2.1.1
Fire sprinklers required and throughout all
stories from the Group A-1 occupancy to and
including the levels of exit discharge serving that
occupancy where one of the following conditions
exists:
Fire area >12,000 ft²
Fire area has an OL ≥300
Fire area is located on a level other than LED
Fire area contains a multitheater complex
84
81 82
83 84
2018 IFC and IBC Fire Protection Systems with MT amendments
Copyright 2021 International Code Council 22
2018 IFC Fire Protection Systems
Group A-2
§903.2.1.2
Group A-2
§903.2.1.2
Fire sprinklers required and throughout all
stories from the Group A-2 occupancy to and
including the levels of exit discharge serving that
occupancy where one of the following conditions
exists:
Fire area >5,000 ft²
Fire area has an OL ≥100
Fire area is located on a level other than LED
85 2018 IFC Fire Protection Systems
Group A-3 & A-4
§903.2.1.3, §903.2.1.4
Group A-3 & A-4
§903.2.1.3, §903.2.1.4
Fire sprinklers required and
throughout all stories from the
Group A-3, A-4 occupancy to and
including the levels of exit
discharge serving that
occupancy where one of the
following conditions exist:
Fire area >12,000 ft²
Fire area has OL ≥300
Fire area is located on a level other
than LED
86
2018 IFC Fire Protection Systems
Group A-5
§903.2.1.5
Group A-5
§903.2.1.5
Fire sprinklers required in the following areas in
excess of 1,000 ft² that are accessory to
stadiums or arenas:
Concession areas
Retail areas
Press boxes
87
OUTDOORSTADIUM
STANDS
INTERIORSPACE THAT
INCLUDES OTHEROCCUPANCIES
2018 IFC Fire Protection Systems
Group A-5
§903.2.1.5.1
Group A-5
§903.2.1.5.1 903.2.1.5.1 Spaces under
grandstands or bleachers.
Enclosed spaces under
grandstands or bleachers shall be
equipped with an automatic
sprinkler system in accordance with
Section 903.3.1.1 where either of
the following exist:
1. The enclosed area is 1,000
square feet (93 m2) or less and is
not constructed in accordance with
Section 1029.1.1.1.
2. The enclosed area exceeds
1,000 square feet (93 m2).
88
85 86
87 88
2018 IFC and IBC Fire Protection Systems with MT amendments
Copyright 2021 International Code Council 23
2018 IFC Fire Protection Systems
Assembly Occupancies on Roofs
§903.2.1.6
Assembly Occupancies on Roofs
§903.2.1.6
Fire sprinklers are
required on all floors
between an occupied roof
and the LED discharge
where assembly uses
occur on the rooftop and:
OL >100 for Group A-2, or
OL >300 for other Group A
occupancies
89 2018 IFC Fire Protection Systems
Multiple Group A Fire Areas
Montana Amendment - 903.2.1.7
Multiple Group A Fire Areas
Montana Amendment - 903.2.1.7
Montana Amendments to the International Building Code
Administrative Rule 24.301.146
Modifications to the International Building Code
Applicable to Both the Department’s and Local
Government Code Enforcement Programs
(12) Subsection 903.2.1.7 - Multiple Fire Areas
Deleted in its entirety.
90
2018 IFC Fire Protection Systems
Multiple Group A Fire Areas
§903.2.1.7
Multiple Group A Fire Areas
§903.2.1.7
Sprinklers required where
multiple fire areas contain
Group A-1, A-2, A-3 or A-4
occupancies that share
egress components and OL
≥300
91
Group A-2
Restaurant
OL = 93
Group A-3
Art Gallery
OL = 123
Group M
Book Store
OL = 110
Group A-2
Restaurant
OL = 93
Group A-2
Restaurant
OL = 93
Group A-2
Restaurant
OL = 93
Group A-3
Art Gallery
OL = 123
Group M
Book Store
OL = 50
All occupancies separated
by 2-HR fire barriers
Aggregate occupant load = 309
Therefore, sprinklers are required
All occupancies separated
by 2-HR fire barriers
All fire areas considered separately
Sprinklers not required
2018 IFC Fire Protection Systems
Ambulatory Care Facilities
§903.2.2
Ambulatory Care Facilities
§903.2.2
Fire sprinklers required on floors with
a Group B Ambulatory Care Facility
when:
≥4 care recipients incapable of
self-preservation
≥1 care recipients incapable of
self-preservation on a floor other
than LED
§903.3.2 requires the installation of
QR or residential sprinklers
throughout smoke compartments
containing treatment rooms
92
How do you determine
the number of care
recipients?
Count the beds
89 90
91 92
2018 IFC and IBC Fire Protection Systems with MT amendments
Copyright 2021 International Code Council 24
2018 IFC Fire Protection Systems
Ambulatory Care Facilities
§903.2.2
Ambulatory Care Facilities
§903.2.2 In buildings where ambulatory care is
provided on levels other than the
level of exit discharge, an automatic
sprinkler system shall be installed
throughout the entire floor as well as
all floors below where such care is
provided, and all floors between the
level of ambulatory care and the
nearest level of exit discharge, the
level of exit discharge, and all floors
below the level of exit discharge.
Exception: Floors classified as an
open parking garage are not required
to be sprinklered.
93 2018 IFC Fire Protection Systems
Group E
§903.2.3
Group E
§903.2.3
Fire sprinklers required in the occupancy when
one of the following conditions exist:
1. Fire area >12,000 ft²
2. All portions below LED
Sprinklers not required in areas below LED where each
classroom has at least one exterior exit door at ground level
3. The Group E fire area has an occupant load of >300
94
2018 IFC Fire Protection Systems
Group F-1
§903.2.4
Group F-1
§903.2.4
Fire sprinklers required throughout
the building where one of the
following conditions exist:
Fire area >12,000 ft²
Fire area is >3 stories above
grade
Aggregate fire areas >24,000 ft²
Used for manufacture of
upholstered furniture or
mattresses >2,500 ft²
95 2018 IFC Fire Protection Systems
Woodworking Operations
§903.2.4.1
Woodworking Operations
§903.2.4.1
Fire sprinklers required
throughout the building
where both of the
following conditions exist:
Fire area >2,500 ft²
The process generates finely
divided waste or uses finely
divided combustible materials
96
93 94
95 96
2018 IFC and IBC Fire Protection Systems with MT amendments
Copyright 2021 International Code Council 25
2018 IFC Fire Protection Systems
Group H
§903.2.5
Group H
§903.2.5
Fire sprinklers required in
all Group H occupancies
§5004.5 requires
systems to meet
Ordinary Hazard Group 2
criteria, at minimum with
3,000 ft² design area
0.17 gpm/ft²
Many materials
require more water
97
• Flammable & combustible liquids
• Flammable & pyrophoric gases
• Level 2 & 3 aerosols
• Organic peroxides
• Oxidizers
2018 IFC Fire Protection Systems
Group H-5
§903.2.5.2
Group H-5
§903.2.5.2
Fire sprinklers required
throughout the building
IFC Table 903.2.5.2
establishes minimum
design criteria for
automatic sprinklers
based on the location in
the building
98
2018 IFC Fire Protection Systems
Group I
§903.2.6
Group I
§903.2.6
Fire sprinklers required throughout the building
§903.2.6 allows the installation of NFPA 13R
systems in Group I-1 Condition 1
§903.3.2 requires the installation of QR or
residential sprinklers in:
All areas of smoke compartments containing care
recipient sleeping units in Group I-2
Sleeping units in Group I-1
99 2018 IFC Fire Protection Systems
Group M
§903.2.7
Group M
§903.2.7
Fire sprinklers required throughout
the building where one of the
following conditions exist:
Fire area >12,000 ft²
Fire area >3 stories above
grade
Aggregate fire areas >24,000 ft²
Used for display and sale of
upholstered furniture or
mattresses >5,000 ft²
100
97 98
99 100
2018 IFC and IBC Fire Protection Systems with MT amendments
Copyright 2021 International Code Council 26
2018 IFC Fire Protection Systems
Group R
§903.2.8
Group R
§903.2.8
Fire sprinklers required throughout the building
for all Group I occupancies
NFPA 13D systems in Group R-3, R-4 Condition
1 and care facilities with ≤5 clients
NFPA 13R systems in Group R-4 Condition 2
§903.3.2 requires the installation of QR or
residential sprinklers in dwelling units and
sleeping units
101
1- & 2-family dwellings and
townhomes built under the IRC
are sprinklered in accordance
with the IRC or NFPA 13D
2018 IFC Fire Protection Systems
Pedestal/Podium Construction
IBC §510.4
Pedestal/Podium Construction
IBC §510.4
Group R occupancies with
parking beneath
Depending on the
construction and the
building’s height and area,
the design of the sprinkler
system may be based on
NFPA 13, 13R or a
combination of NFPA 13
and 13R
102
2018 IFC Fire Protection Systems
Pedestal/Podium ConstructionPedestal/Podium Construction
103
NFPA 13R for Group R IF
≤4 stories AND
height is ≤60’
3-HR horizontal
assembly
Number of stories
for Group R
Any occupancy
other than
Group H
Type IA
construction
Building height
2018 IFC Fire Protection Systems
Pedestal/Podium ConstructionPedestal/Podium Construction
104
NFPA 13 for Group R IF
>4 stories OR
height is >60’
101 102
103 104