12-24kV Vacuum Circuit Breaker · 2016. 5. 23. · VCB, from incoming material quality control to...
Transcript of 12-24kV Vacuum Circuit Breaker · 2016. 5. 23. · VCB, from incoming material quality control to...
GE imagination at work
GEIndustrial
12-24kV Vacuum Circuit Breaker
More Than 80 Years of Interrupter Experience
GE pioneered experimental vacuum interrupters in the 1920's. Refined it and introduced the world's first vacuum interrupter distribution breaker in the 1960's. To date, this interrupter design has been the world leader in vacuum technology and has accumulated over 45 years of reliable field service.
World Class Quality
Manufactured, assembled and tested all in the same sophisticated facility, SecoVac is the product of state of the art manufacturing processes assured by ISO 9001:2000 and ISO14001 certification. Precision Tooled parts, computer aided design and advanced production techniques, as well as the protection of the "E Coat" (cathodic electrocoating) paint process have resulted in a standard of excellence unmatched in the industry.
Universal Applications SecoVac is designed, assembled and tested to meet or exceed applicable IEC, GB and DL standards. It is suitable for applications in all major industries including T & D, Oil & Gas, Automotive, Processing Plants, Iron and Steel mill, Mining, Commercial Buildings, etc.
It provides protection for all types of applications: cable, overhead lines, motors, capacitors, transformers, busbar sections, etc.
Environment Friendly
Selecting low environmental impact technologies has become increasingly important to engineers tasked with choosing equipment for an application. With commitment to environment protection, the solid insulation of epoxy resin is used for SecoVac series MV embedded pole vacuum circuit breaker instead of SF6 gas.
GE imagination at work
SecoVac 12-24kV
Predominant Vacuum Technology
SecoVac 01
Vacuum switching technology is nowadays the dominant switchingprinciple in medium voltage. Innovative developments are leading to acontinuously increasing market growth, based on the fundamentaladvantages such as reliability, availability, compactness and, last but notleast , the environmental friendliness of the vacuum as a switchingmedium.
Vacuum Interrupter
The switching element of the vacuum circuit-breaker is the vacuuminterrupter. It consists of an arc chamber, which is located between twoceramic insulators. Terminal studs connect the contacts to the externalterminals. One contact is fixed within the housing, the other one ismoveable. The metal bellows enable the contact movement and provide ahermetic connection to the interrupter housing. The contact stroke is onlya few millimeters. The internal pressure in the vacuum interrupter is lessthan 10-7 bar. The vacuum circuit-breaker has no arc-quenching medium.The properties of the contact material and the contact geometry definethe switching behavior and the switching capacity.
After contact separation, the resultant arc evaporates contact materialfrom the contact surfaces. The arc current thus flows throw a materialvapour plasma until the next current zero. Near the current zero, the arc isextinguished, and the metal vapour looses its conductivity within a fewmicroseconds as a consequence of the recombination of the chargecarrier ions. In this way, the contact gap is de-ionized and the dielectricstrength restored very fast. The metal vapour condenses on the contactsurfaces. Only a very small portion condenses on the arc chamber wall.The arc chamber wall has the function of a vapour shield, to preventcondensation of the metallic vapour onto the insulators
Automatic Pressure Gelation
A special cushion layer made of high insulation, gas tight and strong elastic material was employed around the surface of the ceramic tube of vacuum interrupter before it was embedded, so the cracking is thoroughly avoided.
SecoVac is the first completed series MV embedded pole vacuum circuit breaker in the world which employs the latest and mature technology of Automatic Pressure Gelation (APG) to embed the vacuum interrupter and connection terminals within epoxy resin. Compared with complete air insulated vacuum circuit breaker or assembly pole vacuum circuit composite insulation, SecoVac is of solid insulation, on one hand, the risk of insulation fault caused by adverse operating environment such as dust, humidity and small animals are eliminated thoroughly, so SecoVac is a vacuum circuit breaker with high environmental resistance. On the other hand, thanks to the embedded pole design, the distribution of electrical field of the pole is much even than that in the assembly pole vacuum circuit breaker, so the insulation strength is improved dramatically.
SecoVac 12-24kV
The first APG process
Vacuum interrupter aftersurface treatment
Injection of LSR through APG process
LSR buffering layer molding
Injection of epoxy resin through APG process
2
4
1
37
5
6
8
1 Fixed contact piece
2 Connection disc
3 Ceramic insulator
4 Arc chamber
5 Metal bellows
6 Guide
7 Moving contact piece
8 Moving contact piece terminal
Embedded poles
Vacuum interrupter has extremely high internal dielectric strength resulting from the ULV while the external dielectric strength is however limited by the insulation capacity of the air, therefore also requires embedding the chamber in a solid material, In such cases, the vacuum interrupter is additionally well protected against external mechanical influences such as impacts.
The main advantages of embedded poles are high dielectric strength without additional external compensation in air, usability in an extremely wide range of climatic conditions, and good protection of the vacuum interrupter from dust, mechanical impacts and moisture. On the operating mechanism side, it is equipped with modularized, standardized and simplified spring mechanism, the whole spring mechanism is made up of separated closing and opening modules which can be preassembled and easily replaced on-site of end-users without any changing of the original dynamic characteristic of the breaker, so the lead time for delivery and down time for maintenance will be shortened.
The second APG process
Unique and Proven Embedded Pole Technology
Product Performance Features
SecoVac 12-24kV
1. Tulip Contact
2. Contact Arm
3. Lower Contact Terminal
4. Upper Contact Terminal
5. Embedded Pole
6. Vacuum Interrupter
7. Moving contact pieces
8. Metal Bellows
9. Disc Spring for Contact Pressure
10. Shutter Driving Plate
2
2
3
4
5
6
7
8
9
10 11 12 13 14 15
16
17
18
19
20
1
1
11. Insulated Coupling Rod
12. Opening Spring
13. Earthing Contact of Cart
14. Classis of Cart
15. Hole for Driving Screw
16. Locking Piece
17. Operating Shaft
18. Operation Cover
19. Closing Spring
20. Secondary Plug
SecoVac series MV embedded pole vacuum circuit breaker uses the latest and mature technology of Automatic Pressure Gelation (APG) to embed the vacuuminterrupter and connection terminals within epoxy resin. The vacuum interrupter is cast in the epoxy resin, so inside the epoxy resin there is no screw fixationthat will cause the concentrated harsh electrical field inside the epoxy resin and will consequently result in decrease of the electrical insulation strength of thepole. Thanks to the embedded pole technology, the assembly of the pole is simplified, and the assembly accuracy as well as quality of the embedded pole iseasily to be controlled by the state of the art production process. The embedded pole technology also obviously improve the environmental resistantcapability of the breaker, as the primary circuit of the breaker is completely embedded inside the epoxy resin, the risk of insulation fault caused by adverseoperating environment such as dust, humidity, ingression of small animals, polluted ambient and high altitude operating site are eliminated thoroughly.
The key know how of the embedded pole technology is the buffering layer betweenepoxy resin and ceramic housing of vacuum interrupter, the material and processingof the buffering layer is essential to ensure the integrity of epoxy resin of theembedded pole provide adequate adhesion between each other in any circumstance.Our patented LSR (Liquid Silicon Rubber) buffering layer and double APG (AutoPressure Gelation) process adopted in the producing of the embedded polethoroughly eliminates the cracking of the epoxy resin caused by the large differenceof thermal expansion coefficient between epoxy resin and ceramic in case of rapidchanging of the ambient temperature. APG process for LSR buffering layer ensuresthat there will not be any air gap or bubble between the buffering layer and ceramichousing, hence, the high electrical insulation strength of the embedded pole ofSecoVac series MV embedded pole vacuum circuit breaker is guaranteed.
The partial discharge value of embedded pole manufactured by our patented LSR(Liquid Silicon Rubber) buffering layer and double APG (Auto Pressure Gelation)process is below 5pc with an applied testing voltage of 1.2Um.
SecoVac 02
Modular Operation Mechanism
SecoVac series MV embedded pole vacuum circuit breaker is equipped with modularized, standardized and simplified operating mechanism, the mechanism consists of separated closing and opening modules, all the mechanical parts of the mechanism are integrated into these two modules . The closing and opening modules are universal to whole series of SecoVac embedded pole vacuum circuit breaker regardless of ratings, it means there is only one kind of closing and opening module for the whole SecoVac products family, thanks to such a design, the maintenance time and cost for the mechanism is low, the replacement of modules can be easily carried out on site. There is no impact on the original dynamic characteristic of the breaker after the replacement of modules, so the retest of the breaker is not required after the replacement of modules.
Another feature of the operating mechanism of SecoVac series MV embedded pole vacuum circuit breaker is that the total number of parts of the mechanism is reduced compared with the traditionally designed mechanism, so that the reliability of the mechanism is enhanced significantly.
The opening damper of the mechanism plays a very important role to ensure reliable performance and high mechanical endurance of SecoVac series MV embedded pole vacuum circuit breaker. By adoption of the opening damper, the overtravel and re-bounce of moving contacts of vacuum interrupters during the opening of this VCB is reduced to a minimum. The lower overtravel of the moving contacts means lower mechanical stress to the bellow of the vacuum interrupter, so the designed mechanical endurance of the vacuum interrupter is guaranteed. The lower re-bounce of the contact ensures low arc re-striking probability during the breaking of capacitive current, so the occurrence rate of operating overvoltage is reduced. By the contribution of the opening damper, SecoVac has successfully passed type tested as Class C2 breaker in accordance with IEC standards.
closing module
opening module
opening damperintegrated VCB
SecoVac 03
SecoVac 12-24kV
The State of the art Processing and Advanced Quality Control
The high quality of the embedded pole is achieved by using the latest APG (Auto Pressure Gelation) technology and advanced vacuum mixing and degassing technology that are carried out by the equipment. The Vogel clamping machine is an essential piece of equipment to ensure the mechanical and insulating strength of the embedded pole of SecoVac series MV embedded pole vacuum circuit breaker.
As well as the processing facilities, the testing facilities are also very important to the quality control of the breaker. In the manufacturing process of SecoVac VCB, from incoming material quality control to the final inspection and testing, every step is strictly calibrated and tested by means of testing facilities.
For every embedded pole, before it goes into the breaker assembly line, it shall go through following inspections and testing carried out in factory:
• X-ray inspection• Power frequency withstand voltage test• Partial discharge measurement• Extremely high and low temperature impulse test
Before delivery, the following tests and inspections will be done for SecoVac series MV embedded pole vacuum circuit breaker in factory by means of advanced testing equipments:
• Dynamic characteristics measurement• Power frequency withstand voltage testing• Inspection of interlocking system between breaker and withdrawable unit• Secondary wiring inspection• Circuit resistance measurement
Rated voltage up to 24kVRated current up to 4000ARated short circuit breaking current up to 50kAMechanical endurance up to 30,000 operating cyclesRated short circuit breaking times up to 50 timesDC component of short circuit breaking current up to 62%Large external creep distance reaches 20mm/kV
Full Range Product with High Technical Parameters
SecoVac 04
SecoVac 12-24kV
Front Panel
This front panel fits into a collar-frame in the equipment when the breaker is in the CONNECT position. It provides a metal barrier between the breaker compartment and the secondary device compartment. Well marked and easy-to-read operating controls and indicators include TRIP button, CLOSE button, OPEN/CLOSE indicator, CHARGE/DISCHRGE indicator, OPERATIONS counter and provision for manual charging the breaker.
Primary Disconnect
The primary disconnect finger set is rugged and easy to inspect. Designed for optimum contact, built of silver-plated copper and tested for continuous and short time current. Cycloid design is more convenient to connect and expand wider contact area than flat design. These disconnects provide proper contact integrity throughout the life of the gear for the critical primary disconnect function.
Breaker Mechanism
All the mechanical parts of the mechanism are integrated into opening and closing modules individually. The closing and opening modules are universal to whole series of SecoVac embedded pole vacuum circuit breaker in spite of the ratings. Such design assures no mechanical readjustment after the replacement, thereby not only shortens lead-time but also reduces operation and maintenance cost.
Interlock System
For personnel safety, SecoVac is designed with a number of mechanical and electrical interlocks. For example, breaker contacts must be open before the breaker can be moved to or from the CONNECT position. A positive mechanical stop is provided when the breaker reaches the CONNECT or TEST/DISCONNECT positions. Mechanical interference interlocks are provided to permit only the insertion of properly rated breakers into any specific compartment. These and other necessary interlocks provide a comprehensive protection system. Furthermore, springs automatically discharge when the breaker is withdrawn from the CONNECT position and breakers cannot be inserted in the closed position.
Breaker Features
SecoVac 05
SecoVac 12-24kV
Technical Data
Description Unit
*Other voltages are available on request.
Rated voltage
Rated current Rated power frequency withstand voltage (1min)
Rated lightning impulse withstand voltage (peak values)
Rated short circuit breaking current
Rated short time withstand current (4S)
Rated peak withstand current
Rated peak making current
Rated short circuit current breaking times
Electrical endurance
Mechanical endurance
Operating sequence
Rated auxiliary control voltage* Opening time
Breaking time
Closing time
kV
A
kV
kV
kA
kA
kA
kA
No. of times
No. of times
No. of times
V
ms
ms
ms
7.2/12
630/1250/1600/2000/2500/3150/4000
42
75
20/25/31.5/40/50
20/25/31.5/40/50
50/63/80/100/125
50/63/80/100/125
50
274(E2) IEC 62271-100:2006
30000
O-0.3s-CO-180s-COO-180s-CO-180s-CO
AC 110/220; DC110/220
35~70
25~35
40~50
24
630/1250/1600/2000/2500
65
125
20/25/31.5
20/25/31.5
50/63/80
50/63/80
50
274(E2) IEC 62271-100:2006
20000
O-0.3s-CO-180s-COO-180s-CO-180s-CO
AC 110/220; DC110/220
35~70
25~35
40~50
SecoVac 06
SecoVac 12-24kV
SecoVac 12-24kV
D
13
C
E
42.5
L
Overall Dimension
12kV SecoVac Withdrawable
Journey 8~10mm
1616
8
P
A
P
19
620
520
260
205
35
154
76
25 320
40 62
4
22
630
10
313 29603
+- 502002
98
74
370
383
438
630A Isc 31.5kA
1250A Isc 31.5kA
630A Isc 31.5kA
1250A Isc 31.5kA
1250A Isc 31.5kA
630A Isc 31.5kA
1000
800
650
Width ofSwitchgear (mm)
812
812
616
275 850
275
210
850
650
130
130
120
853836 844
853
653
836
640
844
648
466
616
466
Parameter (12kV)
150 502
210 650
150 502
P (mm)
105
120
105498503500
653640 648
503500 498
Weight (kg)A (mm) C (mm) D (mm) E (mm) L (mm)
SecoVac 07
SecoVac 12-24kV
C
D
E
19
L
48.5
R
130
280
310
62.5
W
293 2
U
320370
383
296
359.5
25
76
165
4
50
200
21.5
+0-3
M 40
16P P16
A 8
55
Journey 8~10mm
12kV SecoVac Withdrawable
4)
3)
1)
2)
Note:1)The heat radiator is only necessary for SecoVac with rated current equal to higher than 2500A.2)The lifting hook should be remove before SecoVac is put into switchgear panel.3)Contact arm system for SecoVac with rated current upto 2000A.4)Contact arm system for SecoVac with rated current 2500A and above.*The forced fan cooling is necessary when SecoVac with rated current 4000A is installed in metal-enclosed switchgear.
200694
200
220
694
694
694 200
8549
115
115
79
79
79 115
684
684
684
684
648640 653
648
844
640
836
653
853
640 653 648
616
P (mm)
650
616
812
650
850
650 616
295
295735
735
295735
149
149
109
109
149109
725
725
725
844
844
836
836 853
853
844836 853
812
812850
850
812850
850 812 836 853 844 79 115 684 694 220
Parameter 12kVWidth of Switchgear (mm)
800
1250A Isc 40kA/50kA
1600A Isc 50kA
2000A Isc 50kA
1600A Isc 50kA
1250A Isc 40kA/50kA
10002500A Isc 50kA
3150A Isc 50kA
4000A* Isc 50kA
2000A Isc 50kA
210
210
210
275
2206948549 684844836 853812850275
275
275
275
275
A (mm) C (mm) D (mm) E (mm) L (mm) W (mm) M (mm) R (mm) U (mm) Weight (kg)
SecoVac 08
630A Isc 31.5kA
1250A Isc 31.5kA
1250A Isc 31.5kA
1250A Isc 31.5kA
630A Isc 31.5kA
630A Isc 31.5kA
650
800
1000
150
150
210
210
688
688
705
705
705
705
688
688
660
275
275
860
860
W
P P
G-G
688
688
705
705
510
510
660
SecoVacWidth of Phase to Phase Depth (mm) Height (mm) Width (mm)
Switchgear (mm) Distance (mm)
G
G
SecoVac 12-24kV L - Frame for 12kV SecoVac Withdrawable
205
260
705
688 ( D )
( H )
35
SecoVac 09
W
P P
310
280
H
688
B-B
( D )
B
B
SecoVac 12-24kVL - Frame for 12kV SecoVac Withdrawable
800
1250A Isc = 40kA / 50kA
1600A Isc 40kA
2000A Isc 40kA
1600A Isc 40kA
210
210
210
688
688
688
850
850
850
860
660
660
660
688275 860
(mm)
49
1250A Isc = 40kA / 50kA 275 688 860 860 49
79
79
79
SecoVacWidth of Switchgear (mm)
Phase to Phase Distance (mm)
Depth (mm) Height (mm) Width (mm)
10002000A Isc 40kA 860688275 860 79
2500A Isc 40kA 860688275 860 79
SecoVac 10
860
275 275
310
280
688
860
C-C
( W )
( H )
( D )
( P ) ( P )
C
C
Note: Forced cooling fan is necessary when SecoVac rated 4000A
SecoVac 12-24kVL - Frame for 12kV SecoVac Withdrawable
109
1000
1000 4000A Isc 50kA
3150A Isc 50kA
275
275 688
688
860
860 860
860
SecoVacWidth of Switchgear (mm)
Phase to Phase Distance (mm) Depth (mm) Height (mm) Width (mm)
SecoVac 11
SecoVac 12-24kV
4
L
44716
7
76451±2 296
310
22
790
325
E
D
42.5
C
13.5
19
35Ø
93
Ø74
0+377
5
1540
300 0-3 50
25 320383
1616 PP
A
Journey 8 10mm
24kV SecoVac Withdrawable
630A Isc 31.5kA
1250A Isc 31.5kA
1250A Isc 31.5kA
630A Isc 31.5kA
SecoVac
1000
800
Width of Switchgear (mm)
135836 853 844812850275
275 850 812 844853836 135
210
210
650 622
650 622
A (mm)P (mm) C (mm) Weight (kg)
648
648
653646
653646
125
125
L (mm)D (mm) E (mm)
SecoVac 12
SecoVac 12-24kV24kV SecoVac Withdrawable
4
Ø16
7
Ø79
38332025
300 0-3 50
Ø13
5
22
Ø10
9
812
844
296
167
447
76
441±2
310
830
815
325
836
19
13.5853
49
85016
16 8275275
Journey 8 10mm
3)
1)2)
1) The heat radiator is only necessary for SecoVac with rated current equal to or higher than 2500A2) Ø109 is adapted for SecoVac with rated current 3150A3) Ø79 is adapted for SecoVac with rated current 1600-2500A
SecoVac
1600A Isc 31.5kA
2500A Isc 31.5kA
3150A Isc 31.5kA
2000A Isc 31.5kA
Width of Switchgear (mm)
1000Ø 79
Ø 79
Ø 109
Ø 79
Dimension of Contact
SecoVac 13
SecoVac 12-24kVL - Frame for 24kV SecoVac Withdrawable
275275
275
2500A Isc 31.5KA2000A Isc 31.5KA1600A Isc 31.5KA
275275210210
1250A Isc 31.5KA630A Isc 31.5KA1250A Isc 31.5KA630A Isc 31.5KA
Phase-to- phase distance (mm)SecoVacWidth of
Switchgear (mm)Depth (mm) Height (mm)
870 937870 937
937870937870
870 937870 937
937870
Width (mm)
794
994
794994994
994994
Caution: Remove support part 1 and 2 before L-Frame in use.
800
1000
310
471
210210
SecoVac 14
W
12
D
P P
SecoVac 12-24kV
Closing circuitClose blocking circuit2nd opening circuitOpening circuit Charging circuit
Overcurrentrelease(A phase)
Overcurrentrelease(B phase)
Overcurrentrelease(C phase)
Undervoltagerelease
Closing monitor circuitTruck Rack Block magnet
Blocking Magnet for withdrawable unit---V0Closing block magnet First opening release Closing releaseUndervoltage release Indirect overcurrent release ( optional )Second opening release ( optional )Manual chargingCharging motorRectifier ( V0 & V5 optional )
Auxiliary switch of charging MotorAuxiliary switch of block magnet- Y1Auxiliary switch of VCBAuxiliary switch for test positionAuxiliary switch for service positionAnti-pumping relayResistanceBypass of R0Connector of K0 ( the internal anti-pumping function will be dismissed if it is cut )
Y0Y1Y2Y3Y4Y7-Y9Y10PMV0-V5
1.2.3.
S1S2S3S8S9K0R0JP1JS1
Aux.switch-S1 shown for VCB-mechanism is discharged.VCB in opening and service status.The optional components are not included in basic version if not specified .
Notes:
Closing circuitClose blocking circuit2nd opening circuitOpening circuit Charging circuit
Overcurrentrelease(A phase)
Overcurrentrelease(B phase)
Overcurrentrelease(C phase)
Undervoltagerelease
Closing monitor circuitTruck Rack Block magnet
Blocking Magnet for withdrawable unit---V0Closing block magnet First opening release Closing releaseUndervoltage release Indirect overcurrent release ( optional )Second opening release ( optional )Manual chargingCharging motor
Auxiliary switch of charging MotorAuxiliary switch of block magnet- Y1Auxiliary switch of VCBAuxiliary switch for test positionAuxiliary switch for service positionAnti-pumping relayResistanceBypass of R0Connector of K0 (the internal anti-pumping function will be dismissed if it is cut )
Y0Y1Y2Y3Y4Y7-Y9Y10PM
1.2.3.
S1S2S3S8S9K0R0JP1JS1
Aux.switch-S1 shown for c.b.-mechanism discharged.VCB in opening and service status.The optional components are not includerd in basic version if not specified .
Notes:
Withdrawable Installation for AC Control
Withdrawable Installation for DC Control
Service position
Test position
Service position
Test position
Internal Wiring Diagram
SecoVac 15
SecoVac 12-24kV
Closing circuitClose blocking circuit2nd opening circuitOpening circuit Charging circuit
Overcurrentrelease(A phase)
Overcurrentrelease(B phase)
Overcurrentrelease(C phase)
Undervoltagerelease
Closing circuitClose blocking circuit2nd opening circuitOpening circuit Charging circuit
Overcurrentrelease(A phase)
Overcurrentrelease(B phase)
Overcurrentrelease(C phase)
Undervoltagerelease
Closing monitor circuit
Aux.switch-S1 shown for VCB-mechanism is discharged.VCB in opening status.The optional components are not includerd in basic version if not specified .Auxiliary switch S2 should be bypassed when block magnet Y1 is not required.The connect points in dashed are as should be connected with positive pole.
Closing block magnet First opening release Closing releaseUndervoltage release Indirect overcurrent release ( optional )Second opening release ( optional )Manual chargingCharging motor
Auxiliary switch of charging MotorAuxiliary switch of block magnet- Y1Auxiliary switch of VCBAnti-pumping relayResistanceBypass of R0Connector of K0 ( the internal anti-pumping function will be dismissed if it is cut )
Y1Y2Y3Y4Y7-Y9Y10PM
S1S2S3K0R0JP1JS1
1.
2.3.
4.
5.
Notes:
Closing monitor circuit
Aux.switch-S1 shown for VCB-mechanism is discharged.VCB in opening status.The optional components are not included in basic version if not specified .Auxiliary switch S2 should be bypassed when block magnet Y1 is not required.
Closing block magnet First opening release Closing releaseUndervoltage release Indirect overcurrent release ( optional )Second opening release ( optional )Manual chargingCharging motorRectifier ( V0 & V5 optional )
Auxiliary switch of charging MotorAuxiliary switch of block magnet- Y1Auxiliary switch of VCBAnti-pumping relayResistanceBypass of R0Connector of K0 ( the internal anti-pumping function will be dismissed if it is cut )
Y1Y2Y3Y4Y7-Y9Y10PMV0-V5
S1S2S3K0R0JP1JS1
1.
2.3.
4.
Notes:
Fixed Installation for DC Control
Fixed Installation for AC Control
Internal Wiring Diagram
SecoVac 16
Ordering Information
Product Type
Coding System of Catalogue Number
Symbol Meaning of the code
Basi
c ty
pe d
esig
natio
n
Rate
d vo
ltage
Ope
ratin
g m
echa
nism
Rate
d cu
rren
t
Rate
d sh
ort c
ircui
t br
eaki
ng c
urre
nt
Type
of c
ontr
ol v
olta
ge
Cont
rol v
olta
ge
Phas
e-to
-pha
se d
ista
nce
From 7.2kV up to 12kV
24kV
Spring operating mechanism
Rated current: 630 A
Rated current: 1250A
Rated current: 1600A
Rated current: 2000A
Rated current: 2500A
Rated current: 3150A
Rated current: 4000A
Rated short circuit breaking current: 20kA
Rated short circuit breaking current: 25kA
Rated short circuit breaking current: 31.5kA
Rated short circuit breaking current: 40kA
Rated short circuit breaking current: 50kA
AC auxiliary control voltage
DC auxiliary control voltage
Rated auxiiary control voltage: 110V
Rated auxiiary control voltage: 220V
Phase-to-phase distance 150mm
Phase-to-phase distance 210mm
Phase-to-phase distance 275mm
Withdrawable installation
Fixed installation
SEV T DSEV
12
24
11
22
W
F
Inst
alla
tion
mod
e
W
W
F
P15
P21
P27
T
A
D
06
12
16
20
25
31
40
20
25
31
40
50
SecoVac 12-24kV
SecoVac / -
Rated short circuit breaking current (kA): 20, 25, 31.5, 40, 50
Rated current (A): 630, 1250, 1600, 2000, 2500, 3150, 4000
Rated voltage (kV): 12, 24
SecoVac Vacuum Circuit Breaker
SecoVac 17
SecoVac
SecoVac
)
Breaker type
Rated voltage
Rated current
Rated short-circuit breaking current
Distance of Pole (P)
Motor-operated (M)
*Blocking magnet Y1
Shunt releases ON OFF Y2 Y3
Over-current releasesY7 Y8 Y9 ( optional )
Under-voltage release Y4 ( optional )
Truck blocking Y0 ( optional )
Anti-pump relay K0
2nd Release Y10 ( optional )
Secondary wiring
Withdrawable ( W type )
Fixed ( F type )
Other items
Customer :
* Blocking magnet Y1: Standard for withdrawable part; optional for fixed part.
Project : Order NO.
Quantity
7.2kV 12kV 24kV
630A 1250A 1600A 2000A 2500A 3150A 4000A
20kA 25kA 31.5kA 40kA 50kA
150mm 210mm 275mm
DC220V DC110V AC220V AC110V Other
DC220V DC110V AC220V AC110V Other
DC220V DC110V AC220V AC110V
Other
Disabled
Y7/Y9 ( AC5A ) Y7/Y8/Y9 ( AC5A )
Disabled
DC220V DC110V AC220V AC110V
Disabled
DC220V DC110V AC220V AC110V Other
Standard Non-standard ( Attached drawing .NO. :
Earthing mode: earthing with copper bar at the bottom of truck
earthing with connecter on the sides of truck Other
Secondary wiring: connect with terminal strips on the top of cabinet
with control wiring plug
with control wiring plug installed on the top of cabinet
Other
Mechanical interlock: Disabled
sticking out 120mm on the left side of principal axis
with opening release Other
( Please attach concerned drawing or data in case any special requests. )
1.
2.
3.
Prepare date Check date
SecoVac 12-24kV
Checking list for SecoVac Order
SecoVac 18
GE imagination at work
APO HeadquartersChina23F,Building C,Hi-Tech Building,900 Yishan Road,Shanghai200233Tel: +86 21 2401 3333 Fax: +86 21 5423 5080
Indonesia BRI II Tower, 15th Floor Suite 1505Jl. Jendral Sudirman No. 44-46Jakarta 10210Indonesia Tel: +62 21 5730 429 Fax: +62 21 574 7089
Philippines1873 P.Domingo St Makati City Philippines 1207 Tel: +63 2 895 7051/59 Fax: +63 2 890 8186
Thailand1126/2, Vanit Building II 16th Floor Room 1603, New Petchburi Road, Makkasan RatchathewiBangkok 10400Thailand Tel: +66 2 255 8721 Fax: +66 2 255 8733
Hongkong15/F, The Lee Gardens,33 Hysan Avenue. Causeway Bay Tel: +852 62943050 Fax: +852 23760013
Australia125-127 Long Street Smithfield, Sydney NSW 2164 AustraliaTel: +61 (0)2 8788 6911Fax: +61 (0)2 9729 0433
JapanAkasaka Park Bldg., 5-2-20 Akasaka, Minato-ku, Tokyo 107-6112 JapanTel: +81 03 5544 6781Fax: +81 03 5544 6760
Singapore240 Tanjong Pagar Road, #06-00 GE Tower Singapore 088540 Tel: +65 6220 7022 Fax: +65 6326 3015
VietnamFloor 7 Saigon Centre 65 Le Loi Street District 1 Ho Chi Minh City, Vietnam Tel: +84 8 914 6490 Fax: +84 8 827 8229
New ZealandLevel 10, Lurnley House 7 City Road.Auckland. Tel: +64 9 353 6706 Fax: +64 9 353 6707
IndiaThe Millenia, Level 6, Tower B, # 1 & 2Murphy Road, UlsoorBangalore - 560 008IndiaTel: +91 80 4143 4000Fax: +91 80 4143 4199
MalaysiaSuite 3B-8-3, Block 3B,Leval 8, Plaza Sentral,Jalan Stesen Sentral,Kuala Lumpur Sentral 50470,Kuala Lumpur, Malaysia.Tel: +603 2273 9788Fax: +603 2273 3481
Taiwan6F, No. 8 Sec. 3Min-Sheng E. Road.Taipei,Taiwan 10480Tel: +886 2 2183 7000Fax: +886 2 2516 6829
Korea3F.,GE Tower,71-3,Cheongdam-dong,Ganam-gu,Seoul 135-100 KoreaTel: +82 2 6201 4505 Fax: +82 2 6201 4545
This company reserves the right to improvethe products according to the situation.
This publication describes the status of the products at the time of its issuing and may not reflect future condition of the product.
Publication NO.GE/SV12-24/CA/2008/001