1 Low Voltage Power Supplies for ALICE TB 26.7.04 L.Jirden u Recall: u target devices & possible...

21
1 Low Voltage Power Low Voltage Power Supplies for ALICE Supplies for ALICE TB 26.7.04 TB 26.7.04 L.Jirden L.Jirden Recall: target devices & possible solutions Outstanding actions

Transcript of 1 Low Voltage Power Supplies for ALICE TB 26.7.04 L.Jirden u Recall: u target devices & possible...

Page 1: 1 Low Voltage Power Supplies for ALICE TB 26.7.04 L.Jirden u Recall: u target devices & possible solutions u Outstanding actions.

1

Low Voltage Power Low Voltage Power Supplies for ALICESupplies for ALICE

TB 26.7.04TB 26.7.04L.JirdenL.Jirden

Recall: target devices & possible solutions

Outstanding actions

Page 2: 1 Low Voltage Power Supplies for ALICE TB 26.7.04 L.Jirden u Recall: u target devices & possible solutions u Outstanding actions.

2

Target devicesTarget devices Wiener

PL500 F8: product exists; water cooling; some control limitations

PL500 F12: prototype exists; might not be commercialized

Marathon: Prototype exists; should replace F8, F12

Caen SY1527: product exist; no water cooling Easy prototype exist; B-field tolerant Sasy prototype exist; high B-field tolerant

Arem Pro Device H/W prototype exists; no water cooling

Page 3: 1 Low Voltage Power Supplies for ALICE TB 26.7.04 L.Jirden u Recall: u target devices & possible solutions u Outstanding actions.

3

Wiener Marathon Wiener Marathon systemsystem

UX

CR

PFCAC/DC

Digitalcontrol

Power modules

230 VAC

CANbus

Water cooling

B-tol: 300 gaussRad tol: ?

DC/DCAnalogcontrol

Power modules

230 VAC CANbus

PFCAC/DC

Digitalcontrol

380 VDC

B-shield

B-tol: 1200 gaussRad tolerant

Page 4: 1 Low Voltage Power Supplies for ALICE TB 26.7.04 L.Jirden u Recall: u target devices & possible solutions u Outstanding actions.

4

UX

CR

Caen Easy systemCaen Easy system

no cooling

230 VAC

CANbus

Powersupply

48 VDC

DC/DC DC/DC DC/DC

Digitalcontrol

Digitalcontrol

Digitalcontrol

SY1527main-frame

ethernet

Branchcontroller

EASY:B-tol: 1000 gauss

:Rad tol

B-tol: 50 gaussRad tol: ?

SASY: B-tol: 5000 gauss

: Rad tol

Page 5: 1 Low Voltage Power Supplies for ALICE TB 26.7.04 L.Jirden u Recall: u target devices & possible solutions u Outstanding actions.

5

UX

CR

Arem Pro PSArem Pro PS

230 VAC RS232

AC/DCpower

AC/DCpower

AC/DCpower

modulecontrol

modulecontrol

cratecontrol

ethernet

B-tol: ? gaussRad tol: ?

no cooling

Page 6: 1 Low Voltage Power Supplies for ALICE TB 26.7.04 L.Jirden u Recall: u target devices & possible solutions u Outstanding actions.

6

LVPS – possible LVPS – possible solutions Isolutions I

Detector

PS chan [no]

Target device Module [A]

Crates [no]

When require

d

Common purchase

SPD 20 Wiener Marathon 50 4 4Q05 Yes?

or 240 Caen Easy 9 4

SDD 216 Arem Pro ?? 6 6 4Q05 ?

SSD 448 Caen SY1527 ?? 3.6 5 ? ?

TPC 72 Wiener Marathon 50 22 4Q05 yes

TRD 180 Wiener Marathon 50? 45? 3Q05 yes

TOF ? Caen Sasy ? ? ? no

HMPID 100 Wiener Marathon 30? 14? 3Q05 Yes, commit before 05

Page 7: 1 Low Voltage Power Supplies for ALICE TB 26.7.04 L.Jirden u Recall: u target devices & possible solutions u Outstanding actions.

7

LVPS possible LVPS possible solutions IIsolutions II

Detector

PS chan [no]

Target device Module [A]

Crates [no]

When require

d

Common purchase

PHOS &CPV

11 Wiener Marathon 20 – 115?

5? ? yes

FMD ? ? ? ? ? ?

T0 4 Caen Easy ? 1 ? yes

V0 ? Caen Easy ? 1 ? ?

PMD ? Wiener Marathon ? ? ? yes

ZDC ? ? ? ? ? ?

MTK 364 Wiener Marathon 25? 31? 2Q05 yes

MTG 16 Wiener Marathon 115? 2? 4Q04 yes

TOTAL 1461 + ?

3 manufacturers -5 types

3.6 - 250

136 + ?

4Q04- 4Q05

9 yes; 5 ?; 1 no

Page 8: 1 Low Voltage Power Supplies for ALICE TB 26.7.04 L.Jirden u Recall: u target devices & possible solutions u Outstanding actions.

8

Outstanding actionsOutstanding actions

Send out market survey: end June done

Finalize ALICE requirements: before mid August Electrical characteristics: as drafted unless protests Suggested size of modules: 10A, 30A, 50A,

with possibility to operate modules in parallel to at least 250A control functions:

Remote voltage control: ? Grouping: yes (if not too expensive) Remote power on/off: yes (if not too expensive)

Radiation policy: TC 30 August 04 Issue the tender: early September

Finalize technical spec: Merge ALICE requirements with other experiments Final draft to detectors end August for ok

Send out tender

Page 9: 1 Low Voltage Power Supplies for ALICE TB 26.7.04 L.Jirden u Recall: u target devices & possible solutions u Outstanding actions.

9

Page 10: 1 Low Voltage Power Supplies for ALICE TB 26.7.04 L.Jirden u Recall: u target devices & possible solutions u Outstanding actions.

10

Detector Detector requirementsrequirements

Quantities ALICE total ~160 LVPS crates and ~2000 PS

channels

Draft technical specification (Spec) Electrical characteristics Mechanical characteristics Monitoring and control Cooling Environment Standard chapters on:

construction, safety, reliability, quality assurance, documentation

Page 11: 1 Low Voltage Power Supplies for ALICE TB 26.7.04 L.Jirden u Recall: u target devices & possible solutions u Outstanding actions.

11

Spec:Spec:Electrical Electrical

CharacteristicsCharacteristics DC Output

Modular design; 2 – 7 V, 4 – 250 A modules

LVPS 2 – 7 V, 4A

LVPS 2 – 7 V, 250A

24h stability < 5mV or 0.1%

6m stability < 20mV or 0.5%

Noise & ripple < 10mV p to p

Page 12: 1 Low Voltage Power Supplies for ALICE TB 26.7.04 L.Jirden u Recall: u target devices & possible solutions u Outstanding actions.

12

Spec:Spec:Mechanical Mechanical

CharacteristicsCharacteristicsTYPICAL RACK LAYOUT

4U

1U

max 6U

1U

max 6U

VENTILATOR & CONTR.

HEAT EXCHANGER

LV PS

LV PS

HEAT EXCHANGER

LV PS

FRONT VIEW

LV PS

LV PS

SPACE

FOR

CABLES

600 mm300 mm

SIDE VIEW

Page 13: 1 Low Voltage Power Supplies for ALICE TB 26.7.04 L.Jirden u Recall: u target devices & possible solutions u Outstanding actions.

13

Spec:Spec:Monitoring & ControlMonitoring & Control

LVPS 1LOCAL PANEL

Ethernet

CANbus

Provided by manufacturer

External interlock

OPC Server

PC

OPC Server

PC

PCI “Kvaser”

Two options:a) Via CANbus b) Via Ethernet

LVPS 1LOCAL PANEL

Page 14: 1 Low Voltage Power Supplies for ALICE TB 26.7.04 L.Jirden u Recall: u target devices & possible solutions u Outstanding actions.

14

Spec: MONITORING AND Spec: MONITORING AND CONTROL FUNCTIONSCONTROL FUNCTIONS

VOLTAGES MON CON Individual channels ESS

CURRENTS MON 12 bit resolution ESS

RAMPING RATE MON CON Individual channels DES

TEMPERATURE MON Sensor above power circuits

ESS

OVER-CURRENT TRIP OFF VALUE

MON CON Individual channels ESS

FAN STATUS MON Out of limit warning ESS

OVER-VOLTAGE STATUS MON Individual channels DES

OVER-CURRENT STATUS MON Individual channels ESS

OVER-TEMP MON Out of limit warning ESS

MON = MONITOR

CON = CONTROL

ESS = ESSENTIAL

DES = DESIREDFUNCTIONS/PARAM

Page 15: 1 Low Voltage Power Supplies for ALICE TB 26.7.04 L.Jirden u Recall: u target devices & possible solutions u Outstanding actions.

15

Spec: MONITORING AND Spec: MONITORING AND CONTROL FUNCTIONSCONTROL FUNCTIONS

DC TRIP OFF MON Individual channelsGlobal DC power

ESSESS

RESET DC TRIP OFF CON Individual channelsGlobal DC power

ESSESS

DC POWER ON/OFF MON CON Individual channelsGlobal DC power

ESSESS

AC POWER ON/OFF MON CON using external power DES

PS HEALTH MON Summary status DES

LOCAL CONTROL MON Remote control locked out ESS

PS RESET CON System reset (tbs)?? ESS

MON = MONITOR

CON = CONTROL

ESS = ESSENTIAL

DES = DESIREDFUNCTIONS/PARAM

Page 16: 1 Low Voltage Power Supplies for ALICE TB 26.7.04 L.Jirden u Recall: u target devices & possible solutions u Outstanding actions.

16

VOLTAGES CON Groups of channels DES

DC POWER ON/OFF CON Groups of channels DES

RAMPING RATE MON CON Groups of channels DES

OVER-CURRENT TRIP OFF VALUE

MON CON Groups of channels ESS

MON = MONITOR

CON = CONTROL

ESS = ESSENTIAL

DES = DESIREDFUNCTIONS/PARAM

GROUP MANAGEMENT:THE POSSIBILITY TO CONFIGURE AND PERFORM FUNCTIONS ON GROUPS OF CHANNELS WITHIN A CRATE

Spec: MONITORING Spec: MONITORING AND CONTROL AND CONTROL

FUNCTIONSFUNCTIONS

Page 17: 1 Low Voltage Power Supplies for ALICE TB 26.7.04 L.Jirden u Recall: u target devices & possible solutions u Outstanding actions.

17

Spec: OPC SERVERSpec: OPC SERVER

General Compliance with OPC standards No effect on PS output due to failure of remote

control Restart of OPC remotely Not send set points automatically at startup –

read from device PS shall maintain its set points during PS

power failure Genuine device and cache access Interactive list of device functions

Page 18: 1 Low Voltage Power Supplies for ALICE TB 26.7.04 L.Jirden u Recall: u target devices & possible solutions u Outstanding actions.

18

Maintenance To support future versions of Windows and

OPC standards To support future versions of PS firmware

Configuration Allow appropriate management of the fieldbus Human readable configuration file (such as

XML) Obtain actual configuration by scanning Setting of ranges for analog values and setting

of the dead band

Spec: OPC SERVERSpec: OPC SERVER

Page 19: 1 Low Voltage Power Supplies for ALICE TB 26.7.04 L.Jirden u Recall: u target devices & possible solutions u Outstanding actions.

19

Performance Change in Device to OPC:max 10 sec at full bus load

max 1 sec for a single PS

Device cache to OPC client: max 3 sec for all parameters

Write from OPC to device: max 1 sec Interlock to start ramp-down: max 5 ms

Spec: OPC SERVERSpec: OPC SERVER

Page 20: 1 Low Voltage Power Supplies for ALICE TB 26.7.04 L.Jirden u Recall: u target devices & possible solutions u Outstanding actions.

20

Spec: cooling, etc.Spec: cooling, etc.

Cooling Use of standard ventilators not possible due to stray magnetic

fields Water cooling recommended Installed in rack with assured vertical airflow removing max

3kW/rack Environment

Radiation Total dose: 10 mGy Fluency: 109 n/cm2

Magnetic Field up to 200 Gauss Construction

Halogen free material Safety regulations

CE certification Reliability

MTBF > 90 000 hours (excluding ventilators)

Page 21: 1 Low Voltage Power Supplies for ALICE TB 26.7.04 L.Jirden u Recall: u target devices & possible solutions u Outstanding actions.

21

Spec: QA, Spec: QA, documentationdocumentation

Quality assurance Production tests

Functional tests Load tests

Documentation User’s guide Reference manual Test and calibration reports