SHOP DRAWING
REV. 03
REV. 03
1:75 (A1)
MPD/MAR/451
MPD/MEP/FF/T1/1-001 A
15-MAY-12
AEC
J.P.R. Sdn. Bhd. Alliance Consulting Engineers647568-K
01/12/AD
YOUSEF
SUHAIL
NASER
15/05/2012
R
A14837
FIRE PROTECTION BY
NAFFCO
NAFFCO ELECTROMECHANICAL CO. L.L.C
UKAS
Quality System Certificate No.463
Assessed to ISO 9001:2000
QUALITY
MANAGEMENT
007
CERT
SIDE WALL SPRINKLER COVERAGE
DESIGN PARAMETER
TYPICAL SPRINKLER FIXING ARRANGEMENT
( ABOVE & BELOW SPRINKLER )
5. All fire extinguishers will be provided according NFPA10 (Edition-2013)6. All fire cabinets will be provided according NFPA14 (Edition-2013)7. Fire fighting pump set will be provided according NFPA20 (Edition-2013)
Size 65 mm dia and above shall be Ductile iron grooved fittingsSize up to 50 mm dia shall be Ductile iron,threaded fitting 500psi
2. All pipe shall be galvanized steel ERW as per ASTM A53 Gr.B Sch-40 3. Fittings-
1. All dimensions are in milli meter unless otherwise specified
4. Sprinkler system will be provided according NFPA13 (Edition-2013)
8. All fire fighting system will be provided as per UAE code
LEGENDS & SYMBOLS
ACV
NRV
9. All valves in the hose and standpipe system shall be provided with labelsto indicate what portion of the system they control
10. All fire hose cabinets shall be labeled appropriately and provided with operating instruction