HVAC è PLUMBING
Engineering
Consultants,
Inc.
FIRE PROTECTION
200 riverhills
business park
suite 235
Birmingham, AL 35242
Phone: 205-995-4979
bbgsengineering.comPM: DES.: BBGS NO.:
è
è
16.10.227.2LJBLJB
SHEET TITLE
PROJECT NUMBER
ISSUE DATE
DRAWN BY
CHECKED BY
SHEET NUMBER
REVISIONS
1127
03/22/2017
LJB
TENANT REVIEW ISSUE
2030
OWE
NSBO
RO-K
YMA
RCH
22, 2
017
TENA
NT R
EVIEW
CMH Architects, Inc.[Blakeney S. Nelson, Architect]1800 International Park DriveSuite 300Birmingham, AL 35243(205)969-2696 - TEL(205)969-3930 - FAXwww.cmharch.comCopyright © 2017 CMH Architects, Inc.
O W
E N
S B
O R
O ,
K E
N T
U C
K Y
GATEW
AY CO
MMON
S--
PHAS
E 1 -
-
KEY PLAN
PLUMBING LEGEND,SCHEDULES, DETAILS,NOTES & FLOOR PLANS
MDS
P1.0
18" BEND
DECK
4" SEWER PIPE
18" BEND
CONCRETE SLAB OR
FINISHED FLOOR
CLEAN-OUT WITH
COUNTERSUNK PLUG
SEALANT
FINISHED FLOOR
TO TENANT'S
SANITARY
SEWER
STRUCTURE AT
UPPER LEVEL
CONCRETE SLAB OR
FINISHED FLOOR
GRADE AT LOWER
LEVEL
SCALE:SCALE:
PLUMBING FIXTURE SCHEDULE
MANUF.FIXTURE TYPE
NO.
FIXTURE
NO.
TYPE & MODEL
TEST
STANDARD
PIPE SIZES
SUPPORT
VENTWASTE
REMARKS
HWCW
WATER CLOSET
FLOOR
3" 2" 1"
MOUNT
ADA
COMPLIANT
KOHLER
HIGHCREST
K-4302
60LOCHINVAREWH-1 ESJ030K2 4.5 19 GPH 208/1/60SEE NOTES 1, 2, 3
TEMP.
RISE °F
ELECTRIC WATER HEATER SCHEDULE
MANUFACTURERUNIT
NO.
KWMODEL RECOVERY VOLTAGE REMARKS
WC-1
--
NOTES:
1. PROVIDE 30 AMP NON-FUSED DISCONNECT SINGLE PHASE.
2. WATER HEATER SHALL BE INSTALLED PER ALL MANUFACTURES GUIDELINES. ANY SUBSTITUTIONS OF EQUIPMENT SHALL BE EQUAL TO MODEL SCHEDULED AND HAVE ROSS CORP. APPROVAL.
3. PROVIDE "AMTROL" MODEL ST-5 THERMAL EXPANSION TANK.
02 FLOOR DRAIN
NTS
01 CLEAN-OUT
NTS
GENERAL NOTES
1. LOCATIONS OF UTILITIES SHOWN ON PLANS ARE APPROXIMATE.
COORDINATE WITH CIVIL DRAWINGS PRIOR TO BIDDING.
3. ALL OUTSIDE CLEANOUTS SHALL BE BROUGHT TO GRADE AND
EMBEDDED IN 18"X18"X6" THICK CONCRETE PAD. (J.R. SMITH
4258 OR EQUAL.)
4. WHEREVER DISSIMILAR METALS ARE CONNECTED ON WATER
LINES, A DIELECTRIC UNION SHALL BE USED.
5. ALL HORIZONTAL WATER, FIRE AND VENT PIPING IS RUN
ABOVE CEILING AS SHOWN UNLESS OTHERWISE NOTED.
6. ALL HORIZONTAL SANITARY PIPING IS RUN BELOW FLOOR AS
SHOWN UNLESS OTHERWISE NOTED.
9. COORDINATE ALL PIPE ROUTING TO AVOID CONFLICTS WITH,
STRUCTURAL, MECHANICAL, AND ELECTRICAL FEATURES OF
BUILDING.
8. ALL WALL HYDRANTS AND FREEZE PROOF BOX SHALL BE
MOUNTED 24" ABOVE FINISH GRADE OR FINISH FLOOR
UNLESS OTHERWISE NOTED.
7. 18" HIGH AIR CHAMBERS SHALL BE PROVIDED ON HOT AND
COLD WATER CONNECTION AT EACH FIXTURE OR EQUIPMENT.
2. ALL WORK SHALL COMPLY WITH ALL APPLICABLE NFPA, STATE,
COUNTY, AND LOCAL LAWS AND ORDINANCES.
PLUMBING SPECIFICATION
GENERAL
FURNISH ALL LABOR, MATERIALS, EQUIPMENT AND SERVICES NECESSARY
FOR PROPER COMPLETION OF ALL PLUMBING, PIPING AND DRAINAGE WORK.
WORK SHALL COMPLY WITH ALL APPLICABLE NFPA, STATE, COUNTY AND
LOCAL LAWS AND ORDINANCES. IN THE ABSENCE OF LOCAL REGULATIONS,
WORK SHALL MEET 2009 INTERNATIONAL BUILDING, PLUMBING AND GAS CODES AND
THESE DOCUMENTS.
SUBMIT FOR REVIEW SHOP DRAWINGS (MINIMUM 6 COPIES) FOR ALL
MATERIALS, FIXTURES AND EQUIPMENT PROPOSED. ALL SUBMITTALS
BOUND UNDER ONE COVER.
CONTRACTOR SHALL KEEP ACCURATE RECORDS OF INSTALLATIONS. AT
THE END OF INSTALLATION, CONTRACTOR SHALL SUBMIT TWO SETS OF
BLUE PRINTS MARKED WITH AS-BUILT CONDITIONS.
1.
2.
3.
4.
MATERIALS
PIPING
ALL PIPE SHALL BE NEW AND CONFORM TO THE LATEST ASTM
STANDARD SPECIFICATIONS.
1.
SANITARY SEWER:
A. ABOVE GRADE: SCHEDULE 40 DWV-PVC.
B. BELOW SLAB ON GRADE - SCHEDULE 40 DWV-PVC.
2.
WATER PIPING:
A. ABOVE GRADE: COPPER TUBING TYPE L HARD DRAWN WITH JOINTS
OF 95/5 SOLDER.
B. BELOW SLAB ON GRADE: TYPE SOFT COPPER WITH SIL-FOS JOINTS.
3.
INSULATION - GLASS FIBER PIPE INSULATION EQUAL TO OWENS-CORNING MODEL 556-11
INSULATE DOMESTIC HOT AND COLD WATER PIPING INTERIOR ABOVE GRADE
AS FOLLOWS:
A. 1" THICK
B. 1/2" THICK IN WALLS
1.
GENERAL
PROVIDE SLEEVES AT ALL WALL AND FLOOR PENETRATIONS. SEAL AS
REQUIRED TO PREVENT LEAKAGE, MAINTAIN FIRE RATINGS AND MAINTAIN
BUILDING INTEGRITY.
1.
INSTALLATION
DRAWINGS ARE DIAGRAMMATIC AND INDICATE GENERAL LOCATIONS
OF COMPONENTS. VERIFY DIMENSIONS BEFORE INSTALLATION.
1.
PROVIDE HANGERS, SUPPORTS AND ACCESSORIES REQUIRED FOR
INSTALLATION. SPACE HANGERS AND SUPPORTS AS REQUIRED BY
CODES AND MANUFACTURERS RECOMMENDATIONS.
2.
PROVIDE CHROMIUM PLATED BRASS FLANGES WHEREVER PIPES
PASS THROUGH EXPOSED FINISHED FLOORS, WALLS OR CEILINGS.
2.
IDENTIFY ALL PIPE WITH STENCILS OR STRAP-ON PIPE MARKERS.
COLORS TO MATCH ASTM STANDARD A-13.
3.
AFTER INSTALLATION IS COMPLETE, ALL DOMESTIC HOT AND COLD
WATER PIPING SHALL BE THOROUGHLY FLUSHED AND DISINFECTED
WITH HYPOCHLORITE SOLUTION.
4.
PROVIDE PIPE JOINTS AS REQUIRED TO COMPLETE WORK. JOINTS
SHALL BE AIR AND WATER TIGHT. ALL SOLDER JOINTS SHALL HAVE
LEAD-FREE SOLDER.
5.
PROVIDE CLEANOUTS AS SHOWN AS REQUIRED BY APPLICABLE CODES.6.
NATURAL GAS PIPING:
1. ALL GAS PIPING ABOVE GRADE: BLACK STEEL
2. BLACK STEEL PIPE, SCHEDULE 40 ASTM A-53 OR A-106. FITTINGS ON PIPE 2"
AND SMALLER, BLACK MALLEABLE IRON SCREWED FITINGS, ASM 1197.
FITTINGS ON PIPE 2-1/2" AND LARGER, WELDED, USING BUTT WELD
FITTINGS.
3. JOINTS ON BLACK STEEL SCREWED PIPE MADE UP WITH TEFLON TAPE
APPLIED TO MALE THREADS ONLY.
4. JOINTS ON BLACK STEEL WELDED PIPE MADE UP WITH BUTT WELD
FITTINGS. MITERING AND NOTCHING FOR TEES, ETC., NOT PERMITTED.
WELDOLETS ARE PERMITTED.
5. UNIONS 2" AND SMALLER BLACK MALLEABLE IRON SCREWED UNIONS 2-1/2"
AND LARGER FLANGED.
6. ARRANGE FOR TAPPING OF UTILITY MAIN, SERVICE FROM MAIN TO METER
AND INSTALLATION AS REQUIRED BY LOCAL UTILITY. PAY ALL CHARGES,
FEES TEMPORARY DEPOSITS, ETC. (CONTRACTOR IS RESPONSIBLE TO
VERIFY PRESSURES, MAIN AND SERVICE EXTENSIONS WITH THE LOCAL
UTILITY PRIOR TO INSTALLING ANY NEW PIPE).
7. ALL GAS PIPING IN THE 2 PSIG SYSTEM, LABELED AT THE BEGINNING, AT
ALL GAS COCKS, AT ENDS AND AT 6' INTERVALS WITH LABELS READING "2
PSIG".
8. APPLIANCE TYPE REGULATORS AS SHOWN ON DRAWING. REGULATORS
SHALL HAVE VENT LIMITING DEVICE AS REQUIRED BY LOCAL CODE AND
LOCAL UTILITY, OR SHALL BE VENTED TO THE EXTERIOR AS APPROVED BY
THE ARCHITECT.
9. NATURAL GAS VALVES: PLUG COCKS - 2' AND LARGER, RESUN R-1431, AGA
SEAL OF APPROVAL, 175 PSI; 2" AND SMALLER, MILWAUKEE BB2-100, NIBCO
FP-600, CONBRACO GP-10/11 GB-50 SERIES, KITZ 58 OR RESUN R-1430 WITH
CSA SEAL OF APPROVAL, 175 PSI.
10. LAYOUT AND GRADE ALL GAS PIPING SO AS TO HAVE A MINIMUM OF
TRAPPED LINES. WHERE TRAPPING OF PIPE IS UNAVOIDABLE, PROVIDE 4"
TO 6" SCALE POCKET AT LOW POINT WITH REMOVABLE CAP FITTING
ACCESSIBLE FOR CLEANING OUT POCKET. INSTALL 175 PSIG WP BRONZE
COCK AND UNION AT ALL CONNECTIONS TO GAS FIRED EQUIPMENT.
11. INSTALL NO GAS PIPING BENEATH INTERIOR SLABS ON GRADE. WHERE GAS
PIPING MUST BE INSTALLED BELOW SLAB ON GRADE, PIPE MUST BE
ENCASED IN STEEL PIPE SEALED AND VENTED TO THE EXTERIOR.
NO SCALE
G
F
WH WALL HYDRANT - J.R. SMITH #5619
GAS LINE
BALL VALVE
GAS COCK
FIRE LINE
P TRAP
RISER DIAGRAM NUMBER
UNION
PIPE TURNING DOWN
PIPE TURNING UP
HOT WATER LINE
COLD WATER LINE
VENT LINE
SOIL OR WASTE LINE
FLOOR DRAIN - J.R. SMITH #2005 W/ TRAP GUARD
FD
#
PLUMBING LEGEND
INV INVERT
P-# PLUMBING FIXTURE NUMBER
HW HOT WATER
CW COLD WATER
VSTR VENT STACK THRU ROOF
VS VENT STACK
SS SOIL STACK
WS WASTE STACK
CO CLEAN OUT
AFF ABOVE FINISH FLOOR
CLEVIS HANGER
INSULATION
PIPE
18 GA SHEETMETAL
SADDLE 18" LONG
SUSPENDED PIPE SUPPORT
NO SCALE
SPRINKLER NOTES
1.
PIPING LARGER THAN 2" MAY BE SCHEDULE 10 PIPE WITH ROLL GROVED JOINTS.
HANGER SPACING TO BE PER NFPA 13 REQUIREMENTS.
ALL PIPING 2" AND SMALLER SHALL BE SCHEDULE 40 STEEL WITH THREADED
JOINTS AND CAST IRON OR MALLEABLE IRON FITTINGS. PROVIDE HANGERS PER
NFPA 13 SPACING.
SPRINKLER HEADS SHALL BE QUICK RESPONSE TYPE.
4.
5.
6.
PROVIDE A PIPING PLAN SHOWING COORDINATION OF SPRINKLER PIPING WITH ALL
ITEMS ABOVE CEILING.
7.
PROVIDE SHOP DRAWINGS INCLUDING A REFLECTED CEILING PLAN INDICATING
SPRINKLER HEADS, LIGHTS AND HVAC CEILING DEVICES.
SEE ARCHITECTURAL DRAWINGS FOR NEW CEILING PLAN, HEIGHTS AND AREAS BEING
RENOVATED.
3.
PROVIDE NFPA 13 COMPLIANT SYSTEM TO PROVIDE TOTAL COVERAGE FOR
THE BUILDING AS INDICATED ON DRAWINGS.
2.
03
DETAIL OF PIPING AT EWH-1 ON SHELF04
FURNISH AND INSTALL COMPLETE WITH KOHLER K-4670-C SEAT AND SLOAN ROYAL 110 EXPOSED FLUSH VALV (3.5 GPF) WITH
VACUUM BREAKER AND STOP.
WATER CLOSET
FLOOR
3" 2" 1"
MOUNT
KOHLER
WELCOMME
K-4350
WC-2
--
FURNISH AND INSTALL COMPLETE WITH KOHLER K-4670-C SEAT AND SLOAN ROYAL 110 EXPOSED FLUSH VALV (3.5 GPF) WITH
VACUUM BREAKER AND STOP.
LAVATORY
WALL
1-1/4" 2" 1/2"
HUNG
AMERICAN LUCERNE
0355.012, WHITE
L-1
1/2"
FURNISH AND INSTALL COMPLETE WITH HERITAGE CENTERSET FAUCET 5402.172H.002.V15 WITH WRIST HANDLES, MCGUIRE 165
SUPPLIES & STOPS, 8872 P-TRAP AND TRUEBRO LAV GUARD OR APPROVED EQUAL FOR TRAP AND SUPPLIES.STANDARD
ADA
COMPLIANT
URINAL
WALL
3" 2" 3/4"
HUNG
BARDON
K4991-ET-0, WHITE
UR-1
--
FURNISH AND INSTALL COMPLETE WITH SLOAN ROYAL 186-1 H EXPOSED URINAL FLUSHOMETER, J.R. SMITH 637 CARRIER AND
SET WITH LIP AT 17" AFF.
KOHLER
MOB BASIN
FLOOR
3" 2" 1/2"
MOUNT
91
MB-1
1/2"
FURNISH AND INSTALL COMPLETE WITH STAINLESS STEEL CAP AND CENTRAL BRASS #0054-YELSRC-Q SERVICE SINK FAUCET.
FLORESTONE
DRINKING FOUNTAIN
WALL
2" 2" 1/2"
MOUNT
HAC-FS-DBL-L/R-ADA-SS
DF-1
--
FURNISH AND INSTALL COMPLETE WITH J.R. SMITH 834 CARRIER, MCGUIRE 165 SUPPLY/STOP AND 8872 P-TRAP. SET WITH
LOWER COOLER RIM AT 34" AFF FOR ADA COMPLIANCE.
HALSEY-
TAYLOR
SINK
COUNTER
1-1/2" 2" 1/2"
MOUNT
ELKAY
STAINLESS STEEL
GECR2521
S-1
1/2"
FURNISH AND INSTALL COMPLETE WITH AMERICAN STANDARD, HERITAGE FAUCET #7400.172H.002 FAUCET WITH WRIST HANDLES,
MCGUIRE 165 SUPPLIES & STOPS, 8872 P-TRAP AND TRUEBRO LAV GUARD OR APPROVED EQUAL FOR TRAP AND SUPPLIES.
NON-PRESSURE PIPING RISER DIAGRAM
NO SCALE
05
SP-1 STANCORSUMP PUMP 50 25 3600 1 60SE-50 .5 115
SUMP PUMP SCHEDULE
GPM
HZPH
RPM
DESCRIPTION
SYMBOL
MANUF.
MODEL
REMARKS
HEAD (FT)
H.P. VOLTS
ELECTRICAL DATA
CONNECT PER MANUFACTURER'S INSTRUCTIONS
LOCATION
TRENCH AT DOCK
MFD J.R. SMITH #2142 FLOOR DRAIN
5
3
4
7
2
1
CONCRETE SLAB AT DOCK
DETAIL OF TRENCH SUMP & PUMP
NO SCALE
6
STANCOR MODEL SE-50 SUBMERSIBLE EFFLUENT PUMP .5HP, 115 VOLT, 3600 RPM, 2"
DISCHARGE CONNECTION.
1.
2.
7.
3.
4.
5.
6.
STANCOR CHECK VALVE.
JUNCTION BOX WILL BE PROVIDED WITH MULTI-PIN CONNECTOR AND CORD IN LENGTHS AS
REQUIRED; 25 FT. IS STANDARD, OPTIONAL 25 FT. INCREMENTS AVAILABLE.
ALL BURIED PUMP PRESSURE DISCHARGE PIPING SHALL BE PROTECTED WITH TAPECOAT
CT CORROSION PROTECTION TAPE.
POWER CABLE, PROBE CABLE, HIGH LIQUID ALARM CABLE AND PUMP ON FLOAT CABLE.
HIGH LIQUID ALARM FLOAT WITH CLAMP DEVICE TO MOUNT TO PUMP DISCHARGE PIPING.
PUMP ON FLOAT.
OPEN GRATING SPECIFIED
BY ARCHITECT
2" DISCHARGE PIPE - BELOW
DOCK SLAB, SEE PLAN FOR
ROUTING, COORDINATE WITH
STRUCTURAL & ARCHITECTURAL
JUNCTION BOX MOUNTED ON
INTERIOR WALL OF BUILDING
06
SPRIG DETAIL
NO SCALE
RETURN BEND ASSEMBLY W/ UPRIGHT
FOR CONCEALED SPACE PROTECTION
1" SCH. 40
BRANCHLINE
MAIN CEILING
UPRIGHT SPRINKLER
FIRE SYSTEM RISER DETAIL AT BUILDING ENTRY
NO SCALE
IN
SID
E W
ALL
6" DUCTILE IRON PIPE
CONCRETE THRUST BLOCK
M.J. X FLG. ADAPTER
FINISHED FLOOR SLAB
ALL THREAD ROD
HEX NUTS & WASHER
(TYP. OF 8)
TIE-BOLTS
(TYP. 0F 4)
FIRE PROTECTION MAIN TO
O.S.&Y GATE VALVE W/ TAMPER SWITCH
FLOW SWITCH
ALARM CHECK VALVE
SPRINKLER HEADS
EXTERIOR WALL
NOTE: PENDENT HEADS TO BE SPACED IN THE CENTER OF CEILING
TILE WHERE LAY-IN CEILING OCCURS.
BRANCHLINE
SUSP. ACOUST. CLG.
1" x 0'-4"
t-t
t-t
t-t
1" X
D
RO
P
1" x ARMOVER
DROP PENDANT DETAIL
NO SCALE
FULLY CONCEALED
SPRINKLER HEAD
FORMED
CONCRETE
TRENCH
MIN
. 30"
CEILING
EWH-1
VACUUM RELIEF
EXPANSION TANK
AMTROL ST-5
SAFETY PAN
HOSE BIBB
DIELECTRIC UNION
TYPICAL
ASME P&T RELIEF VALVE
PIPE FULL SIZE
TO MB-1
3/4" EXTERIOR PLYWOOD
1"PAN DRAIN
PIPE 1" PAN DRAIN
TO MB-1
3/4"
CIRC. PUMP
ASTRO 50B
CHECK VALVE
3/4"
SHELF TO BE HOLDRITE QUICK STAND HUBBARD
MODEL #40-SWHP WM. PROVIDE REQUIRED BLOCKING
PROVIDE 26 GA GALVANIZED METAL STRAP, WRAPPED
AROUND WATER HEATER ONCE AND SECURED TO WALL
ON EACH SIDE OF WATER HEATER.