Post on 23-Jun-2021
STRUTFASTCable Management Solutions
STRUTFASTCable Management Solutions
METAL FRAMING
A metal framing system, also known more generally throughout the industry as Unistrut®, was
designed as a site adaptable mechanical support method that provides an economical solution
for virtually any industrial, mining, petrochemical, infrastructure or commercial application and
complements almost any installation of cable, pipe, HVAC or general support structure. It is
easily installed and offers full flexibility to support systems for any application, incorporating a
comprehensive array of brackets, fittings and accessories available in a wide variety of channel
profiles, material thicknesses and finishes.
Load RatingsAllowable slip out, pull out and load ratings for the metal framing product range have been
derived by calculation based on ultimate load capacity prior to product failure incorporating a
1.5 factor of safety. Metal framing is typically used in either a support beam or support column
arrangement.
Support Beam technical data lists maximum allowable uniform load and mid span deflection
at various spans. Together with this data, a loading to span was designated which will give a
deflection ratio of 1/200 of the span. This will give a recognized practical beam deflection to
minimize sagging of the beam under load.
Support Column technical data lists maximum lateral loading at a range on unbraced heights.
.
Metal Framing Overview
METAL FRAMING
1 www.strutfast.co.za ISO 9001:2015
www.strutfast.co.za I ISO 9001:2015 112
www.strutfast.co.za ISO 9001:2015
METAL FRAMING
Channels and Spring Nuts
UNHARDENED SPRING NUT AND GRADE 4.8 HEX SET SCREW
M12 SPRING NUT PULL OUT STRENGTH RESISTANCE TO SLIP MAXIMUM TIGHTENING TORQUE
Size kg kg Nm
Use in F1000 350 180 50
Use in F3300 250 180 50
Safety Factor of 2
Channel And CombinationsChannels and Combinations are cold formed to size from low carbon strip steel (minimum yield strength of 250 Mpa) on a rolling mill. The channel is manufactured with a continuous opening with the two edges turned inwards. Rigid mechanical fixing may be achieved by engaging the in turned edges of the channel with the serrated grooves in the spring nuts.
Spring NutsSpring nuts are produced from steel bar and, after manufacture, zinc plated nuts can be case hardened to order. Hardened Spring nuts should be used with grade 8.8 zinc plated hex set screw. Generally, the South African market uses only
1 2 3
4 5
Channel And Spring Nut Installation
unhardened Spring nuts together with grade 4.8 zinc plated hex set screw. Spring nuts are rectangular in shape with the ends shaped as to allow a quarter turn clockwise and to prevent further turning in the channel. Two toothed grooves in the top of the nut engage the return lips of the channel, in a vice-grip like manner.
Allowable pull out strength and resistance to slip loads for torques shown.
Information is based on physical results under test conditions. The data shown is typical and given for guidance only.
Channels and Combinations
METAL FRAMING
CHANNEL
DESCRIPTION
F1000
F1001
THICKNESS
mm
2.50
2.50
AREA OF
SECTION
mm2
336.75
673.49
WEIGHT OF
PRODUCT
g/m
2644
5287
AXIS X-X AXIS Y-Y
1
103
mm4
72.367
370.48
Z
103
mm3
3.147
8.97
r
mm4
14.66
23.454
1
103
mm4
91.904
183.81
Z
103
mm3
4.45
8.901
r
mm
16.25
16.52
Design Fundamentals - Column End ConditionsK = the effective length factor, which mathematically describes the
column end conditions.
F1000 Channel (6m) F1001 Channel (6m)
F1001A F1001B F1001C F1001-C4 F1001D
F3301
Made to order
F3300
METAL FRAMING
3 www.strutfast.co.za ISO 9001:2015
Information is based on physical results under test conditions. The data shown is typical and given for guidance only.
www.strutfast.co.za I ISO 9001:2015 114
www.strutfast.co.za ISO 9001:2015
METAL FRAMING
Channels and CombinationsF1000 Beam Loading Data
250
500
750
1000
1250
1500
1750
2000
2250
2500
2750
3000
SIMPLE SUPPORTEDBEAM - SPAN
mm
SAFE WORKING LOADS
LOAD APPLIED AS UDL FOR STRESS
- CUM - STABILITY CRITERIA
KG
LOAD APPLIED ASCONCENTRATED LOAD
FOR STRESS - CUM -STABILITY CRITERIA
KG
LOAD APPLIEDAS UDL FOR
DEFECTION CRITERIA- SPAN / 200
KG
LOAD APPLIED ASCONCENTRATED LOAD
FOR DEFLECTIONCRITERIA - SPAN / 200
KG
1320
660
440
330
264
220
189
165
147
132
120
110
660
330
220
165
132
110
95
83
74
66
60
55
1320
660
440
330
264
220
189
137
108
88
73
61
660
330
220
165
132
110
95
86
68
55
45
38
Section Properties
250
500
750
1000
1250
1500
1750
2000
2250
2500
2750
3000
UNBRACEDCOLUMN HEIGHT
mm
SAFE WORKING LOAD ON COLUMN APPLIED AT THE CENTROID OF THE
SECTION, FOR DIFFERING COLUMN END CONDITIONS
K = 0.8
4415
4212
3953
3660
3309
2918
2467
2055
1744
1503
1310
1153
4368
4091
3733
3314
2813
2239
1822
1505
1266
1078
910
774
4318
3959
3488
2922
2239
1744
1407
1149
942
770*
644
549*
1268
1243
1207
1161
1092
993
904
817
741
672
603
541
SAFE WORKINGLOAD APPLIED
AT OPENINGOF THE CHANNEL
SECTIONK = 10 K =12
* KL r exceeds 200
Information is based on physical results under test conditions. The data shown is typical and given for guidance only.
Cantilever Brackets
Wrap Around Cantilever Brackets
The Cantilever Bracket system is manufactured from mild steel and utilises F1000 channels welded to a back plate. All cantilever support arms for cable ladders and trays should be 50mm longer than the width of the cable ladder or tray used. The safe working load for cantilever arms is uniformly distributed over the length of the cantilever support arm. Standard Finish on Cantilever Brackets is Hot Dip Galvanised.
LENGTH
150
200
250
350
450
550
650
FIXING HOLES
1
1
1
1
2
2
2
UNIT MASS KG
0.60
0.80
1.00
1.20
1.60
1.80
2.00
LENGTH
150
200
250
350
450
550
650
UNIT MASS KG
0.91
1.10
1.30
1.50
1.70
2.00
2.20
TOTAL UDL KG
473
347
272
192
150
124
102
LENGTHSHORT
250
300
350
UNIT MASS KG
3.00
3.60
4.40
LENGTH
650
850
1050
UNIT MASS KG
4.20
5.20
6.40
TOTAL UDL KG
288
208
180
TOTAL UDL KG
288
208
180
F254S Staggered F254D Double
F223 Wrap Around
F254 Single
Flat Back Cantilever Brackets
METAL FRAMING
5 www.strutfast.co.za ISO 9001:2015
LENGTH
650
850
1050
Air Conditioning Mounting Kit
Mounting Kit Comprises:2 - Wrap Around Cantilever Brackets2 - Mounting Brackets4 - Shield Anchors8 - Hex Bolts
LENGTH: 450mm & 650mmTOTAL UDL: 200kgCOLOUR: White & Beige
TOTAL UDL KG
473
347
272
192
150
124
102
F223/2T Wrap Around
4 - Spring Nuts4 - Hex Nuts4 - Flat Washers
Information is based on physical results under test conditions. The data shown is typical and given for guidance only.
www.strutfast.co.za I ISO 9001:2015 116
www.strutfast.co.za ISO 9001:2015
METAL FRAMING
Air Conditioning Mounting Kit
General Fittings
Beam Clamps
‘Z’ Fittings
F1271 F1272 F2785 F2786
‘U’ FittingsF1047 F1377 F4047F4377 F1737
F1045
F2346
FZ04 FZ01 F4045
C/W M12 Cone Point ScrewRequires:1 x M12 Spring Nut1 x M12 Hex Set Screw
C/W M10 Cone Point Screw
FittingsStandard Fittings form an integral part of the metal framing product. Various standard fittings allow the installer to quickly assemble any solid structure to support cable management, condensers and piping, without requiring welding on site. An added advantage is that it is easy to make adjustments, dismantle and re-use all components, as and when required.
All standard fittings are available in hot dip galvanized mild steel. Standard dimensions apply to all fittings, except where noted on the part drawing and are subject to commercial tolerances.
Hole size 14mm diameter, Hole spacing 20.5mm from end of fitting, 48mm centre to centre. Fitting width 40mm and thickness 6mm unless otherwise stated.
Post BasesF2072/S1 F2858 F2073/A
64
80 100
128
100135
64
180100
186 186
137137
137
83
98
137
89 89
89137
General Fittings
Flat Fittings
F1026 F1033
Angular Fittings
F1034 F1035 F1068
F1074
F1130 & F1131
F1186-45
F1325 F1359
F1546-45
F1713
F1747 F1749 F2484
F1036 F1028 F1066 F1031 F1065
METAL FRAMING
7 www.strutfast.co.za ISO 9001:2015
F1062/3 /4
F1326
F1067 F1358
51
47
137 90
90
57
43
95
48
105105
89
90
10589
47
98
6767
51
102
89
94 80
64
60
76
89
135
137
89
137 89
40183138