Asset: P.S. 361 (OLD 89) - BROOKLYN, 3109 NEWKIRK AVENUE, New York, 11226
Inspection Id Inspection Type Time In Last Edited
SA : K864 Architectural - Senior 2019-01-03 8:59 AM 2019-01-14 11:12 AM
AA : K864 Architectural - Associate 2019-01-03 8:32 AM 2019-01-03 6:55 PM
Asset Data
Question Answer
Was the building fully accessible for inspection Yes
Principal(s) Information
Principal Name Mary Magruder
Organization Success Academy - Brooklyn
Did you meet with this Principal? No
Did this Principal provide feedback? No
Custodian Matty Turturici
Fireman Gilbert Rosario
Building Square Footage 57000
Comments on the Area None
Comments on the Stories (Floors) plus Basements 3+B+Attic
Comments on the Number of Classrooms 27
Comments on the Year Built 1897
Student Population 285
Staff Population 67
Weather Fair
Facade Photo
Corner of Newkirk Avenue and E 32ndStreet-Northwest View
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K864
PB/A&W Print Date: 6/21/2019Page 1 of 45
Main Entrance Photo
Facade A-Newkirk Avenue
Roof Photo
Roof 5-Northeast View
Have any Systems/Major Building Components been upgraded? Yes
Systems: Exterior Entrance Doors upgraded (3); MultipurposeRoom (Room 111), Upgrades to Multipurpose Room (3rdFloor-Cafeteria), Multipurpose Room (3rdFloor-Gymnasium)
Year: 2018
Systems: Waterproofing Exterior Walls
Year: 2015
Systems: Partial Exterior Walls repointed, Partial Shingle Roofingrepairs
Year: 2013
Systems: Exterior Face Brick replacement at rear Walls
Year: 2006
Systems: Roofs, Windows, Exterior Guards replacement;Swimming Pool repairs
Year: 1998
Have there been any New Building Additions? No
Tandem Schools? No
Leased Space? No
Priority Condition
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K864
PB/A&W Print Date: 6/21/2019Page 2 of 45
PriorityCondition ExistLast Year?
PriorityCategory
ConditionDescription
ComponentAffected
LocationDescription
Person(s)Notified
Person(s) Title PhotoImage
No Missing InteriorFire Doors
Missing FireDoor is apotential safetyhazard
INTERIOR |CLASSROOMS/CORRIDORS/ADMINSPACES |Door(s)
Corridor nearRoom 104
Gilbert Rosario Fireman
No Missing InteriorFire Doors
Missing FireDoor is apotential safetyhazard
INTERIOR |STAIRS/RAMPS: INTERIOR |Door(s)
StairG/Basement
Gilbert Rosario Fireman
No Potential FallingDebris
Damaged andloose ceilingtiles are apotential safetyhazard.
INTERIOR |CLASSROOMS/CORRIDORS/ADMINSPACES |Ceiling
Room 211 Gilbert Rosario Fireman
Yes Tripping Hazard Large gaps (3")in safety mats isa potentialsafety hazard.
SITE |PLAYGROUNDS | SafetySurfacing
West side ofwest Playground
Gilbert Rosario Fireman
Structural Engineer Required
StructuralCondition Type
ConditionDescription
ComponentAffected
LocationDescription
Person(s)Notified
Person(s) Title PhotoImage
No condition recorded
Accessibility
Accessibility Status Question Response
Is the primary or secondary entrance on an accessible route? No
Physical Breakdown Structure Exists Required Complies Deficiency AudioInductionSystem
FireAlarmStrobe
FUNCTIONAL ACCESSIBILITY
Exterior Routes
Exterior Entrances & Exits Yes
Exterior H/C Lifts No No
Exterior Ramps and Railings No Yes
Interior Routes
Corridor and Lobby H/C Lifts No Yes
Interior Corridor Doors and Hardware Yes Yes
Interior Corridors and Lobbies No Change in Elevation
Interior Elevators No
Interior Lobby Doors and Hardware Yes
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K864
PB/A&W Print Date: 6/21/2019Page 3 of 45
Physical Breakdown Structure Exists Required Complies Deficiency AudioInductionSystem
FireAlarmStrobe
Interior Routes
Interior Ramps No
Rooms & Spaces
Art Rooms Room 104 Yes No Not on Accessible Route
Auditorium No
Cafeteria No
Classrooms None on Accessible Route Yes No Not on Accessible Route
Computer Rooms No
Gymnasium No
Library No
Main Office Room 109 Yes No Not on Accessible Route
Multi-purpose Room Room 111, 3rd Floor-Gymnasium, 3rdFloor-Cafeteria
Yes No Not on Accessible Route No Yes
Nurse's Room Room 107A Yes No Not on Accessible Route
Pool Basement Yes No Not on Accessible Route
Science Lab No
Toilet Rooms (Boys) None on Accessible Route Yes No Not on Accessible Route
Toilet Rooms (Girls) None on Accessible Route Yes No Not on Accessible Route
Toilet Rooms (Staff) None on Accessible Route Yes No Not on Accessible Route
Building Template
Inspection
Question Response
Architectural
EXTERIOR Inspected
AREAWAY Inspected
InspectedInstance on AW1
Instance Condition 3 - Fair
Instance Quantity 1
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K864
PB/A&W Print Date: 6/21/2019Page 4 of 45
Question Response
EXTERIOR
AREAWAY
Instance Quantity Uom EACH
Deficiency AREAWAY STAIRS: DETERIORATEDTREADS/RISERS/NOSINGS
Roof Plan reference
Deficiency Quantity 15
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
AW1
Violations No violations recorded.
Deficiency AREAWAY SLAB: CRACKS AND SPALLING
Roof Plan reference
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K864
PB/A&W Print Date: 6/21/2019Page 5 of 45
Question Response
EXTERIOR
AREAWAY
Deficiency Photo1
AW1
Violations No violations recorded.
AWNINGS AND CANOPIES Does not Exist
CHIMNEY Inspected
Material Type(s) Masonry
Condition 3 - Fair
Deficiency BRICK: OPEN JOINTS
Roof Plan reference
Deficiency Quantity 25
Quantity Uom S.F.
Potential Action REPOINT
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
CH1
Violations No violations recorded.
COPING Inspected
Condition 3 - Fair
Deficiency CAST STONE: CRACKED/BROKEN PIECES
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K864
PB/A&W Print Date: 6/21/2019Page 6 of 45
Question Response
EXTERIOR
COPING
Roof Plan reference
Deficiency Quantity 55
Quantity Uom L.F.
Potential Action REPLACE-IN-KIND
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Roof 6
Violations No violations recorded.
CORNICE Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
DOORS Inspected
DOORS AND FRAMES Inspected
Condition 5 - Poor
Deficiency METAL CLAD: DETERIORATED DOOR - MAJORDETERIORATION
Roof Plan reference
Deficiency Quantity 2
Quantity Uom EACH
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K864
PB/A&W Print Date: 6/21/2019Page 7 of 45
Question Response
EXTERIOR
DOORS
DOORS AND FRAMES
Deficiency Photo1
Facade E-Door I, H
Violations No violations recorded.
Deficiency METAL CLAD: DETERIORATED DOOR AND FRAME - MINORDETERIORATION
Roof Plan reference
Deficiency Quantity 2
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 4
Deficiency Photo1
Facade H-Exit C3
Violations 35290250Z
Deficiency METAL CLAD: DETERIORATED DOOR AND FRAME - MAJORDETERIORATION
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K864
PB/A&W Print Date: 6/21/2019Page 8 of 45
Question Response
EXTERIOR
DOORS
DOORS AND FRAMES
Roof Plan reference
Deficiency Quantity 2
Quantity Uom EACH
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 4
Deficiency Photo1
Facade B-Exit B2
Violations 35290250Z
DOOR HARDWARE Inspected
Condition 3 - Fair
Deficiency No deficiencies recorded
LINTELS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
TRANSOM/SIDE LIGHT Inspected
Condition 4 - Between Fair and Poor
Deficiency WOOD: EXCESSIVELY WEATHERED
Roof Plan reference
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K864
PB/A&W Print Date: 6/21/2019Page 9 of 45
Question Response
EXTERIOR
DOORS
TRANSOM/SIDE LIGHT
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Facade A-Main Entrance
Violations No violations recorded.
EXTERIOR WALLS Inspected
Material Type(s) Masonry
Replacement Quantity 23,000
Replacement Uom S.F.
InspectedInstance on All Facades
Instance Condition 3 - Fair
Instance Quantity 23,000
Instance Quantity Uom S.F.
Deficiency BRICK: CRACKS/DISPLACED/SPALLED BRICK AT BUILDINGCORNERS
Roof Plan reference
Elevation
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REMOVE AND REBUILD
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K864
PB/A&W Print Date: 6/21/2019Page 10 of 45
Question Response
EXTERIOR
EXTERIOR WALLS
Deficiency Photo1
Facade C
Violations No violations recorded.
Deficiency BRICK: OPEN JOINTS
Roof Plan reference
Elevation
Deficiency Quantity 40
Quantity Uom S.F.
Potential Action REPOINT
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Facade H
Violations No violations recorded.
Deficiency BRICK: MINOR CRACKS AND SPALLING
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K864
PB/A&W Print Date: 6/21/2019Page 11 of 45
Question Response
EXTERIOR
EXTERIOR WALLS
Roof Plan reference
Elevation
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action RESTITCH
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Facade H
Violations No violations recorded.
Deficiency STONE: CHIPPED/SPALLED/BROKEN PIECES
Roof Plan reference
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K864
PB/A&W Print Date: 6/21/2019Page 12 of 45
Question Response
EXTERIOR
EXTERIOR WALLS
Elevation
Deficiency Quantity 30
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Facade H
Violations No violations recorded.
EXTERIOR SOFFITS Does not Exist
LOADING DOCK Does not Exist
LOUVER Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
PARAPETS Inspected
Material Type(s) Masonry
Replacement Quantity 4,000
Replacement Uom C.F.
InspectedInstance on All Facades
Instance Condition 3 - Fair
Instance Quantity 4,000
Instance Quantity Uom C.F.
Deficiency BRICK: MINOR CRACKS, SPALLING
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K864
PB/A&W Print Date: 6/21/2019Page 13 of 45
Question Response
EXTERIOR
PARAPETS
Roof Plan reference
Deficiency Quantity 100
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Roof 5
Violations No violations recorded.
PLAZA DECK Does not Exist
ROOF Inspected
Roofing Inspected
Replacement Quantity 13,700
Replacement Uom S.F.
ROOF HATCH/SMOKE HATCH Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
LEADERS, GUTTERS, DOWNSPOUTS, SCUPPERS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
ROOF BARRIER Does not Exist
ROOF CAGE Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
ROOF FENCE Does not Exist
ROOFING Inspected
InspectedInstance on Asphalt Shingle: Roofs 1, 7
Instance Condition 4 - Between Fair and Poor
Instance Quantity 4,000
Instance Quantity Uom S.F.
Does the roof have major mechanical equipment sitting onDunnage Steel less than 18" above the Roofing?
No
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K864
PB/A&W Print Date: 6/21/2019Page 14 of 45
Question Response
EXTERIOR
ROOF
Roofing
ROOFING
Dunnage Steel less than 18" above the Roofing?
Installation Year 1998
Source of Installation Custodial Staff
Deficiency ASPHALT SHINGLE: ROOFING: DAMAGED, WORN-OUT ORMISSING SHINGLES CURLING UP
Roof Plan reference
Deficiency Quantity 35
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Roof 7
Violations No violations recorded.
Deficiency ASPHALT SHINGLE: ROOFING: MAJOR ACTIVE ROOF LEAKSIN INSTRUCTIONAL SPACE
Roof Plan reference
Deficiency Quantity 50
Quantity Uom S.F.
Potential Action REPLACE ROOFING
Urgency of Action PRIORITY 5
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K864
PB/A&W Print Date: 6/21/2019Page 15 of 45
Question Response
EXTERIOR
ROOF
Roofing
ROOFING
Purpose of Action LEVEL 2
Deficiency Photo1
Room 308 (Roof 7)
Violations No violations recorded.
Deficiency ASPHALT SHINGLE: ROOFING: BEYOND USEFUL LIFE
Deficiency Location/Instance Asphalt Shingle: Roofs 1, 7
Deficiency Quantity 4,000
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 1
Purpose of Action LEVEL 2
Deficiency Photo1 No photo recorded
Violations No violations recorded.
InspectedInstance on Built-Up: Roofs 2-6, 8, 11-15
Instance Condition 4 - Between Fair and Poor
Instance Quantity 8,700
Instance Quantity Uom S.F.
Does the roof have major mechanical equipment sitting onDunnage Steel less than 18" above the Roofing?
No
Installation Year 1998
Source of Installation Custodial Staff
Deficiency BUILT-UP: ROOFING: MAJOR ACTIVE ROOF LEAKS ININSTRUCTIONAL SPACE
Roof Plan reference
Deficiency Quantity 100
Quantity Uom S.F.
Potential Action REPLACE ROOFING WITHOUT MAJOR EQUIPMENTREMOVAL
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K864
PB/A&W Print Date: 6/21/2019Page 16 of 45
Question Response
EXTERIOR
ROOF
Roofing
ROOFING
Deficiency Photo1
3rd Floor Multipurpose Room / Cafeteria (Roof 4)
Violations No violations recorded.
Deficiency BUILT-UP: ROOFING: BEYOND USEFUL LIFE
Deficiency Location/Instance Built-Up: Roofs 2-6, 8, 11-15
Deficiency Quantity 8,700
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 1
Purpose of Action LEVEL 2
Deficiency Photo1 No photo recorded
Violations No violations recorded.
InspectedInstance on Modified Bitumen: Roofs 9, 10, 16
Instance Condition 3 - Fair
Instance Quantity 1,000
Instance Quantity Uom S.F.
Does the roof have major mechanical equipment sitting onDunnage Steel less than 18" above the Roofing?
No
Installation Year 1998
Source of Installation Custodial Staff
Deficiency MODIFIED BITUMEN: ROOFING: BEYOND USEFUL LIFE
Deficiency Location/Instance Modified Bitumen: Roofs 9, 10, 16
Deficiency Quantity 1,000
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 1
Purpose of Action LEVEL 2
Deficiency Photo1 No photo recorded
Violations No violations recorded.
ROOFING DRAINS Inspected
Condition 3 - Fair
Deficiency DETERIORATED
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K864
PB/A&W Print Date: 6/21/2019Page 17 of 45
Question Response
EXTERIOR
ROOF
Roofing
ROOFING DRAINS
Roof Plan reference
Deficiency Quantity 1
Quantity Uom EACH
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Roof 5
Violations No violations recorded.
Specialties Inspected
BULKHEAD/PENTHOUSE Does not Exist
CUPOLA/ SPIRES/ TOWERS Does not Exist
DORMER Does not Exist
DUNNAGE STEEL Does not Exist
SKYLIGHT/ROOF VENT Inspected
Material Type(s) Plastic
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
ROOF/GRAVITY TANK Does not Exist
STAIRS/RAMPS: EXTERIOR Inspected
BUILDING CHEEK/FLANK WALLS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
RAILINGS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
STAIRS/RAMPS Inspected
Condition 3 - Fair
Deficiency CONCRETE: CRACKS/SPALLING - MINOR
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K864
PB/A&W Print Date: 6/21/2019Page 18 of 45
Question Response
EXTERIOR
STAIRS/RAMPS: EXTERIOR
STAIRS/RAMPS
Roof Plan reference
Deficiency Quantity 25
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Facade A- Main Entrance
Violations No violations recorded.
WINDOWS Inspected
Replacement Quantity 6,700
Replacement Uom S.F.
EXTERIOR GUARDS Inspected
Condition 3 - Fair
Deficiency RUST - MINOR
Roof Plan reference
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K864
PB/A&W Print Date: 6/21/2019Page 19 of 45
Question Response
EXTERIOR
WINDOWS
EXTERIOR GUARDS
Elevation
Deficiency Quantity 150
Quantity Uom S.F.
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Facade D
Violations No violations recorded.
LINTELS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
WINDOWS Inspected
Material Type(s) Aluminum
InspectedInstance on Aluminum - Double Hung: All Facades except Facades C and G
Instance Condition 3 - Fair
Instance Quantity 6,700
Instance Quantity Uom S.F.
Installation Year 1998
Source of Installation Custodial Staff
Deficiency ALUMINUM - DOUBLE HUNG: INOPERABLE BALANCE
Roof Plan reference
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K864
PB/A&W Print Date: 6/21/2019Page 20 of 45
Question Response
EXTERIOR
WINDOWS
WINDOWS
Elevation
Deficiency Quantity 134
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1 No photo recorded
Violations No violations recorded.
INTERIOR Inspected
POOLS Inspected
Instance Basement
CEILING
InspectedInstance on Basement
Condition 2 - Between Good and Fair
Deficiency PLASTER/CONCRETE: CRACKS, SPALLING
Deficiency Location/Instance Basement Pool
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Basement Pool
Violations No violations recorded.
DECK/FLOOR
InspectedInstance on Basement
Condition 2 - Between Good and Fair
Deficiency CERAMIC TILES: BROKEN/MISSING/WORN TILES
Deficiency Location/Instance Basement Pool
Deficiency Quantity 15
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K864
PB/A&W Print Date: 6/21/2019Page 21 of 45
Question Response
INTERIOR
POOLS
DECK/FLOOR
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Pool
Violations No violations recorded.
DIVING BOARD
Does not ExistInstance on Basement
POOL LINING
InspectedInstance on Basement
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
ROOF STRUCTURE
Does not ExistInstance on Basement
SEATING
Does not ExistInstance on Basement
WALLS
InspectedInstance on Basement
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
STRUCTURAL Inspected
COLUMNS/BEAMS/BEARING WALLS Inspected
Condition 2 - Between Good and Fair
Deficiency STEEL COLUMNS/BEAMS: DETERIORATED CONCRETEFIREPROOFING
Deficiency Location/Instance Basement -Pool Equipment Room
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 5
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K864
PB/A&W Print Date: 6/21/2019Page 22 of 45
Question Response
INTERIOR
STRUCTURAL
COLUMNS/BEAMS/BEARING WALLS
Deficiency Photo1
Basement-Pool Equipment Room
Violations No violations recorded.
FLOOR STRUCTURE Inspected
Condition 3 - Fair
Deficiency CONCRETE SLAB ON GRADE: MINOR CRACKS
Deficiency Location/Instance Basement-Boiler Room
Deficiency Quantity 70
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 5
Deficiency Photo1
Boiler Room
Violations No violations recorded.
FOUNDATION WALLS Inspected
Material Type(s) Masonry
Condition 3 - Fair
Deficiency BRICK: OPEN JOINTS
Deficiency Location/Instance Basement - Boiler Room
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPOINT
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 5
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K864
PB/A&W Print Date: 6/21/2019Page 23 of 45
Question Response
INTERIOR
STRUCTURAL
FOUNDATION WALLS
Deficiency Photo1
Boiler Room
Violations No violations recorded.
Deficiency BRICK: CRACKED/SPALLED
Deficiency Location/Instance Basement-Pool Equipment Room, Electrical Roomqq
Deficiency Quantity 50
Quantity Uom S.F.
Potential Action RESTITCH
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 5
Deficiency Photo1
Pool Equipment Room
Violations No violations recorded.
ROOF STRUCTURE Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
VAULTS-BUNKERS Does not Exist
AUDITORIUM Does not Exist
CAFETERIA Does not Exist
CLASSROOMS/CORRIDORS/ADMIN SPACES Inspected
Ceiling Inspected
Condition 2 - Between Good and Fair
Deficiency ACOUSTIC TILES: DAMAGED/MISSING - ACTIVE LEAK
Deficiency Location/Instance Room 211
Deficiency Quantity 40
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 6
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K864
PB/A&W Print Date: 6/21/2019Page 24 of 45
Question Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES
Ceiling
Deficiency Photo1
Room 211
Violations No violations recorded.
Deficiency ACOUSTIC TILES: DAMAGED/MISSING
Deficiency Location/Instance Rooms 207A, 212
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Room 207A
Violations No violations recorded.
Deficiency METAL PAN: DAMAGED/MISSING
Deficiency Location/Instance Room 307
Deficiency Quantity 15
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Room 307
Violations No violations recorded.
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K864
PB/A&W Print Date: 6/21/2019Page 25 of 45
Question Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES
Ceiling
Deficiency METAL PAN: DAMAGED/MISSING - ACTIVE LEAK
Deficiency Location/Instance Room 308
Deficiency Quantity 15
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 2
Deficiency Photo1
Room 308
Violations No violations recorded.
Deficiency PLASTER: CRACKS/SPALLING
Deficiency Location/Instance Room 308A
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Room 308A
Violations No violations recorded.
Door(s) Inspected
Condition 5 - Poor
Deficiency WOOD: MISSING DOOR
Deficiency Location/Instance Vestibules in Rooms 102, 202
Deficiency Quantity 2
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K864
PB/A&W Print Date: 6/21/2019Page 26 of 45
Question Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES
Door(s)
Deficiency Photo1
Room 202 Vestibule
Violations No violations recorded.
Deficiency WOOD: DETERIORATED DOOR AND FRAME
Deficiency Location/Instance Room 302
Deficiency Quantity 1
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Room 302
Violations No violations recorded.
Deficiency WOOD: MISSING DOOR
Deficiency Location/Instance Corridor near Room 104
Deficiency Quantity 1
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 6
Deficiency Photo1
Corridor near Room 104
Violations No violations recorded.
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K864
PB/A&W Print Date: 6/21/2019Page 27 of 45
Question Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES
Door(s)
Deficiency WOOD: DETERIORATED DOOR
Deficiency Location/Instance Main Entrance Vestibule, Rooms 201, 210, 212, 306, 307, and others
Deficiency Quantity 10
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Room 307
Violations No violations recorded.
Floor Finish Inspected
Condition 5 - Poor
Deficiency WOOD: DETERIORATED SUBSTRATE
Deficiency Location/Instance Rooms 200, 207, 302, 305
Deficiency Quantity 1,000
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Room 305
Violations No violations recorded.
Deficiency VINYL TILES: DETERIORATED SUBSTRATE
Deficiency Location/Instance Rooms 205, 307, 308, Corridor near Rooms 200, 206, and others
Deficiency Quantity 1,900
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K864
PB/A&W Print Date: 6/21/2019Page 28 of 45
Question Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES
Floor Finish
Deficiency Photo1
Room 307
Violations No violations recorded.
Walls Inspected
Condition 2 - Between Good and Fair
Deficiency PLASTER: CRACKS/SPALLING
Deficiency Location/Instance Rooms 207A, 308A
Deficiency Quantity 120
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Room 308A
Violations No violations recorded.
Deficiency PLASTER: CRACKS/SPALLING - ACTIVE LEAK
Deficiency Location/Instance Room 308
Deficiency Quantity 30
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 2
Deficiency Photo1
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K864
PB/A&W Print Date: 6/21/2019Page 29 of 45
Question Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES Inspected
Walls Inspected
Room 308
Violations No violations recorded.
Specialties Does not Exist
GYMNASIUM Does not Exist
INTERIOR DOOR HARDWARE Inspected
Condition 3 - Fair
Deficiency No deficiencies recorded
INTERIOR GUARDS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
KITCHEN Inspected
InspectedInstance on Basement
Ceiling
InspectedInstance on Basement
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s)
InspectedInstance on Basement
Condition 1 - Good
Deficiency No deficiencies recorded
Floor Finish
InspectedInstance on Basement
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Walls
InspectedInstance on Basement
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
LIBRARY Does not Exist
LOCKER ROOM Inspected
InspectedInstance on Basement - Room 09 (400SF, 28 Lockers)
Alternative use Yes
InspectedInstance on Basement - Room 08 (400SF, 28 Lockers)
Alternative use Yes
Ceiling
InspectedInstance on Basement - Room 08 (400SF, 28 Lockers)
Condition 4 - Between Fair and Poor
Deficiency PLASTER: CRACKS/SPALLING
Deficiency Location/Instance Vestibule
Deficiency Quantity 30
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K864
PB/A&W Print Date: 6/21/2019Page 30 of 45
Question Response
INTERIOR
LOCKER ROOM
Ceiling
Deficiency Photo1
Vestibule
Violations No violations recorded.
Door(s)
InspectedInstance on Basement - Room 09 (400SF, 28 Lockers)
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
InspectedInstance on Basement - Room 08 (400SF, 28 Lockers)
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Floor Finish
InspectedInstance on Basement - Room 08 (400SF, 28 Lockers)
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
InspectedInstance on Basement - Room 09 (400SF, 28 Lockers)
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Locker Room Lockers
InspectedInstance on Basement - Room 09 (400SF, 28 Lockers)
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
InspectedInstance on Basement - Room 08 (400SF, 28 Lockers)
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Walls
InspectedInstance on Basement - Room 09 (400SF, 28 Lockers)
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
InspectedInstance on Basement - Room 08 (400SF, 28 Lockers)
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
MULTI-PURPOSE ROOM Inspected
InspectedInstance on Room 111
InspectedInstance on 3rd Floor - Cafeteria
InspectedInstance on 3rd Floor - Gymnasium
Ceiling
InspectedInstance on 3rd Floor - Cafeteria
Condition 2 - Between Good and Fair
Deficiency PLASTER: CRACKS/SPALLING - ACTIVE LEAK
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K864
PB/A&W Print Date: 6/21/2019Page 31 of 45
Question Response
INTERIOR
MULTI-PURPOSE ROOM
Ceiling
Deficiency Location/Instance Left side near windows
Deficiency Quantity 15
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 2
Deficiency Photo1
Left side near windows
Violations No violations recorded.
Door(s)
InspectedInstance on 3rd Floor - Cafeteria
Condition 3 - Fair
Deficiency WOOD: DETERIORATED DOOR
Deficiency Location/Instance Storage Room
Deficiency Quantity 1
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Storage Room
Violations No violations recorded.
Fixed Equipment
Does not ExistInstance on Room 111
Does not ExistInstance on 3rd Floor - Cafeteria
Does not ExistInstance on 3rd Floor - Gymnasium
Floor Finish
InspectedInstance on 3rd Floor - Cafeteria
Condition 1 - Good
Deficiency No deficiencies recorded
InspectedInstance on 3rd Floor - Gymnasium
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K864
PB/A&W Print Date: 6/21/2019Page 32 of 45
Question Response
INTERIOR
MULTI-PURPOSE ROOM
Floor Finish
Condition 1 - Good
Deficiency No deficiencies recorded
InspectedInstance on Room 111
Condition 1 - Good
Deficiency No deficiencies recorded
Sliding-folding Partition
Does not ExistInstance on Room 111
Does not ExistInstance on 3rd Floor - Cafeteria
Does not ExistInstance on 3rd Floor - Gymnasium
Stage
Does not ExistInstance on 3rd Floor - Cafeteria
Does not ExistInstance on 3rd Floor - Gymnasium
Does not ExistInstance on Room 111
Walls
InspectedInstance on 3rd Floor - Gymnasium
Condition 2 - Between Good and Fair
Deficiency GYPSUM BOARD: DETERIORATED
Deficiency Location/Instance Opposition of windows
Deficiency Quantity 15
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Opposite of windows
Violations No violations recorded.
Window Curtains/Shades/Blinds
Does not ExistInstance on Room 111
Does not ExistInstance on 3rd Floor - Cafeteria
Does not ExistInstance on 3rd Floor - Gymnasium
SCIENCE DEMO ROOM Does not Exist
SCIENCE LAB Does not Exist
SCIENCE PREP ROOM Does not Exist
SHOWER ROOM Inspected
InspectedInstance on Basement
Alternative use Yes
Ceiling
Not RequiredInstance on Basement
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K864
PB/A&W Print Date: 6/21/2019Page 33 of 45
Question Response
INTERIOR
SHOWER ROOM
Door(s)
Does not ExistInstance on Basement
Floor Finish
Not RequiredInstance on Basement
Walls
Not RequiredInstance on Basement
STAIRS/RAMPS: INTERIOR Inspected
Do Letter Stair Signs Exist? Partially
Ceiling Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s) Inspected
Condition 4 - Between Fair and Poor
Deficiency METAL CLAD WOOD: DETERIORATED DOOR
Deficiency Location/Instance Stair BD/Basement
Deficiency Quantity 1
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Stair BD/Basement
Violations No violations recorded.
Deficiency WOOD: MISSING DOOR
Deficiency Location/Instance Stair G/Basement
Deficiency Quantity 1
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 6
Deficiency Photo1
Stair G/Basement
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K864
PB/A&W Print Date: 6/21/2019Page 34 of 45
Question Response
INTERIOR
STAIRS/RAMPS: INTERIOR
Door(s) Inspected
Violations No violations recorded.
Partition Inspected
Condition 2 - Between Good and Fair
Deficiency GLASS PANEL: DAMAGED/DETERIORATED
Deficiency Location/Instance Stair BD/1
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Stair BD/1
Violations No violations recorded.
Railings Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Stairs and Landings Inspected
Condition 2 - Between Good and Fair
Deficiency ROLLED ASPHALT: CRACKS
Deficiency Location/Instance Stair G/Basement
Deficiency Quantity 100
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Stair G/Basement
Violations No violations recorded.
Walls Inspected
Condition 2 - Between Good and Fair
Deficiency CERAMIC TILE: BROKEN/ MISSING
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K864
PB/A&W Print Date: 6/21/2019Page 35 of 45
Question Response
INTERIOR
STAIRS/RAMPS: INTERIOR
Walls
Deficiency Location/Instance Stairs AC/1, BD/3, G/Basement, 1
Deficiency Quantity 70
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Stair BD/3
Violations No violations recorded.
Deficiency PLASTER: CRACKS/SPALLING
Deficiency Location/Instance Stairs AC/3, F/3
Deficiency Quantity 35
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Stair F/3
Violations No violations recorded.
TOILET ROOMS - STAFF Inspected
Ceiling Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s) Inspected
Condition 5 - Poor
Deficiency WOOD: DETERIORATED DOOR
Deficiency Location/Instance Inside Room 207A
Deficiency Quantity 1
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K864
PB/A&W Print Date: 6/21/2019Page 36 of 45
Question Response
INTERIOR
TOILET ROOMS - STAFF
Door(s)
Purpose of Action LEVEL 2
Deficiency Photo1
Inside Room 207A
Violations No violations recorded.
Floor Finish Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Stalls Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Walls Inspected
Condition 2 - Between Good and Fair
Deficiency PLASTER: CRACKS/SPALLING
Deficiency Location/Instance Inside Room 308A
Deficiency Quantity 30
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Inside Room 308A
Violations No violations recorded.
TOILET ROOMS - STUDENTS Inspected
Ceiling Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s) Inspected
Condition 1 - Good
Deficiency No deficiencies recorded
Floor Finish Inspected
Condition 2 - Between Good and Fair
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K864
PB/A&W Print Date: 6/21/2019Page 37 of 45
Question Response
INTERIOR
TOILET ROOMS - STUDENTS
Floor Finish
Deficiency CERAMIC TILE: BROKEN/MISSING TILES
Deficiency Location/Instance Room B1
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Room B1
Violations No violations recorded.
Stalls Inspected
Condition 1 - Good
Deficiency No deficiencies recorded
Walls Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
LIFE SAFETY Inspected
F.D. HOLDING AREA Does not Exist
STEEL STAIRS Does not Exist
SITE Inspected
CONTAINERIZATION Inspected
Condition 5 - Poor
Deficiency CONCRETE PAD DAMAGED
Deficiency Location/Instance North side of Building
Deficiency Quantity 300
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
North side of Building
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K864
PB/A&W Print Date: 6/21/2019Page 38 of 45
Question Response
SITE
CONTAINERIZATION
Violations No violations recorded.
Deficiency CONTAINER DAMAGED
Deficiency Location/Instance North side of Building
Deficiency Quantity 2
Quantity Uom EACH
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
North side of Building
Violations No violations recorded.
Drainage System for Asphalt Inspected
Catch Basins/Manhole - Surrounded by asphalt Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Culverts - Asphalt Covering Does not Exist
Drainage System for Concrete Inspected
Catch Basins/Manhole - Surrounded by concrete Inspected
Condition 4 - Between Fair and Poor
Deficiency DAMAGED COVER
Deficiency Location/Instance Mini Building - Exit C, Mini Building - Old Main Entrance from East32nd Street
Deficiency Quantity 2
Quantity Uom EACH
Potential Action REPLACE
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 6
Deficiency Photo1
Mini Building - Exit C
Violations No violations recorded.
Culverts - Concrete Covering Does not Exist
Drainage System for Soil Inspected
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K864
PB/A&W Print Date: 6/21/2019Page 39 of 45
Question Response
SITE
Drainage System for Soil
Catch Basins/Manhole - Surrounded by Soil Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Culverts - Soil Covering Does not Exist
DRINKING FOUNTAINS Does not Exist
FENCES Inspected
Condition 3 - Fair
Deficiency CONCRETE CURB: DAMAGED/DETERIORATED
Deficiency Location/Instance East 32nd Street, East 31st Street, Avenue D, Newkirk Avenue
Deficiency Quantity 400
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
East 32nd Street
Violations No violations recorded.
Deficiency WROUGHT IRON: DAMAGED/DETERIORATED
Deficiency Location/Instance East 32nd Street, Newkirk Avenue
Deficiency Quantity 80
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
East 32nd Street
Violations No violations recorded.
IRRIGATION SYSTEM Does not Exist
PAVING Inspected
Student Non-Use Inspected
Gravel Exists? No
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K864
PB/A&W Print Date: 6/21/2019Page 40 of 45
Question Response
SITE
PAVING
Student Non-Use
Asphalt Does not Exist
Concrete Inspected
Condition 3 - Fair
Deficiency DAMAGED/DETERIORATED/MISSING SECTIONS
Deficiency Location/Instance Newkirk Avenue, North side of Building
Deficiency Quantity 125
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
North side of Building
Violations No violations recorded.
Pavers Does not Exist
Student Use Inspected
Gravel Exists? No
Asphalt Inspected
Condition 4 - Between Fair and Poor
Deficiency CRACKS - MINOR
Deficiency Location/Instance Schoolyard
Deficiency Quantity 40
Quantity Uom S.F.
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1 No photo recorded
Violations No violations recorded.
Deficiency CRACKS - MAJOR
Deficiency Location/Instance Schoolyard
Deficiency Quantity 500
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K864
PB/A&W Print Date: 6/21/2019Page 41 of 45
Question Response
SITE
PAVING
Student Use
Asphalt
Deficiency Photo1
Schoolyard
Violations No violations recorded.
Concrete Does not Exist
Pavers Does not Exist
Site Sidewalks & Walkways Inspected
Asphalt Does not Exist
Concrete Inspected
Condition 3 - Fair
Deficiency DAMAGED/DETERIORATED/MISSING SECTIONS
Deficiency Location/Instance Main Entrance, East 32nd Street
Deficiency Quantity 50
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
East 32nd Street
Violations No violations recorded.
Pavers Does not Exist
DOT Sidewalk Inspected
Asphalt Does not Exist
Concrete Inspected
Condition 4 - Between Fair and Poor
Deficiency DAMAGED CURBS
Deficiency Location/Instance East 32nd Street, East 31st Street, Avenue D, Newkirk Avenue
Deficiency Quantity 90
Quantity Uom L.F.
Potential Action REPLACE
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K864
PB/A&W Print Date: 6/21/2019Page 42 of 45
Question Response
SITE
PAVING
DOT Sidewalk
Concrete
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Newkirk Avenue
Violations No violations recorded.
Deficiency DAMAGED/DETERIORATED/MISSING SECTIONS
Deficiency Location/Instance East 32nd Street, East 31st Street, Avenue D, Newkirk Avenue
Deficiency Quantity 1,000
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Avenue D
Violations No violations recorded.
Pavers Does not Exist
PLAYGROUNDS Inspected
InspectedInstance on Schoolyard - East
InspectedInstance on Schoolyard - West
Benches
InspectedInstance on Schoolyard - West
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Does not ExistInstance on Schoolyard - East
Fence
InspectedInstance on Schoolyard - West
Condition 3 - Fair
Deficiency CHAIN LINK: DAMAGED/DETERIORATED
Deficiency Location/Instance Entrance from Schoolyard
Deficiency Quantity 50
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K864
PB/A&W Print Date: 6/21/2019Page 43 of 45
Question Response
SITE
PLAYGROUNDS
Fence
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Entrance from Schoolyard
Violations No violations recorded.
Pavement
InspectedInstance on Schoolyard - West
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
InspectedInstance on Schoolyard - East
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Play Equipment
InspectedInstance on Schoolyard - East
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
InspectedInstance on Schoolyard - West
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Safety Surfacing
InspectedInstance on Schoolyard - West
Condition 3 - Fair
Deficiency DETERIORATED/MISSING
Deficiency Location/Instance West side of west Playground
Deficiency Quantity 100
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 6
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
K864
PB/A&W Print Date: 6/21/2019Page 44 of 45
Question Response
SITE
PLAYGROUNDS
Safety Surfacing
Deficiency Photo1
West side
Violations No violations recorded.
Unpaved Area
Does not ExistInstance on Schoolyard - East
Does not ExistInstance on Schoolyard - West
PLAYING SURFACE Does not Exist
RETAINING WALLS Does not Exist
SEATING Does not Exist
SITE WALLS (NOT RETAINING WALLS) Does not Exist
STAIRS/RAMPS: EXTERIOR Does not Exist