Maestro Occupancy Sensing SwitchThe Lutron Maestro Occupancy sensing switch combines a Maestro switch with a passive infrared occupancy or vacancy sensor. The sensor detects the heat from occupants moving within an area to determine whether the space is occupied. Based on the feedback from the sensor, the occupancy sensing switch will adjust the load accordingly.
Features• PassiveinfraredsensorswithexclusiveLutronXCTTechnology
for fine motion detection• 180°sensorfield-of-view• Upto30ftx30ft(9mx9m)[900ft2(81m2)]majormotion
coverageand20ftx20ft(6mx6m)[400ft2(36 m2)]minormotion coverage
• OccupancyversioncanbesettoAuto-ON/Auto-OFForManual-ON/Auto-OFF
• VacancyversionavailabletomeetCATitle24requirements• Adjustabletimeout(1,5,15,or30minutes)andhigh/low
sensitivity adjustment• Occupancysensingswitchloads:incandescent,halogen,ELV,
MLV,CFL,LED,magneticfluorescent,electronicfluorescent,and fan.
Note: "XX"inmodelnumberrepresentscolor/finishcode.
Models availableMS-OPS2-XX1
MS-OPS2H-XX-C2
MS-OPS5M-XX3
MS-OPS5MH-XX-C2
MS-OPS6M2-DV-XXMS-OPS6M2N-DV-XXUMS-OPS6M-DV-XXMS-VPS2-XX1
MS-VPS5M-XX3
MS-VPS6M2-DV-XXMS-VPS6M2N-DV-XXUMS-VPS6M-DV-XX
MS-OPS2MS-OPS2H-XX-CMS-OPS5MMS-OPS5MH-XX-CMS-OPS6M2-DVMS-OPS6M2N-DVMS-VPS2MS-VPS5MMS-VPS6M2-DVMS-VPS6M2N-DV
UMS-OPS6M-DVUMS-VPS6M-DV
1Forclamshellpackaging,addan"H"afterthe"2".AvailableinAL,IV,LA,andWH.2ClamshellpackagedproductforCanada.AvailableinAL,IV,LA,andWH.3Forclamshellpackaging,addan"H"afterthe"M".AvailableinAL,IV,LA,andWH.
Maestro Sensor
369666d 2 09.27.17
® SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Switch with Occupancy/ Vacancy Sensor
SpecificationsRegulatory Approvals
• UL®ListedtoU.S.andCanadiansafetyrequirements.
• NOMCertification(MS-modelsonly).
Power• 120V~50/60Hz1
• 120–277V~50/60Hz1
Key Design Features• Alllightingloads• Crush/tamperresistantlens• Smartambientlightdetection• Adaptiveswitchingalgorithmforextendedrelaylife• XCTTechnologyforfinemotiondetection• LutronpatentedSoftswitch
Environment• Ambientoperatingtemperature:32°Fto104°F
(0°Cto40°C),0%–90%humidity,non-condensing.Indooruseonly.
Warranty• 5-YearLimitedWarranty.ForadditionalWarranty
information, please visit www.lutron.com/TechnicalDocumentLibrary/Sensor_Warranty.pdf
Additional Information• WhenusingMS-OPS2,MS-OPS5M,
MS-OPS6M2-DV,MS-VPS2,MS-VPS5M,orMS-VPS6M2-DVonGFI-controlledcircuits,pleasesee LutronP/N048440 on www.lutron.com
• ForMaestroOccupancysensingdimmermodels,please see LutronP/N369270 on www.lutron.com
• ForusewithMA-AS,MSC-AS,MA-AS-277,orMSC-AS-277tocontroltheloadfrommorethantwolocations, please see LutronP/N048435 on www.lutron.com
• Formoreinformation,pleasesee www.lutron.com/occvacsensors
• LutronCustomerAssistance:1.844.LUTRON1
Advanced FeaturesSwitching
• Standardzerocross—maximizesrelaylifebyswitchingatthepointofminimumenergyontheACpower curve
• Adaptivezerocross—maximizesrelaylifebyswitchingatthepointofminimumenergyontheACpowercurve.Activelyadaptstovariationsinrelaytiming
• LutronPatentedSoftswitchcircuit—eliminatesarcingat mechanical contacts when loads are switched. Extendsrelaylifetoanaverageof1,000,000cycles(on/off)forresistive,capacitive,orinductivesources
XCT TechnologyAdvancedsensingtechnologyforfinemotiondetection ensures that the lights stay on while the room is occupied, and that the sensor does not turn on falsely when there is no occupancy in the room.Formoreinformation,seewww.lutron.com/TechnicalDocumentLibrary/white%20paper%20XCT%204-23-09%20B.pdf
1 MaximumcurrentratingsforindividualmodelsareprovidedintheSelection Matrixonpage4.
Maestro Sensor
369666d 3 09.27.17
® SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Switch with Occupancy/ Vacancy Sensor
Custom SettingsAmbient Light DetectionLights turn on only if natural light in room is low.
• Smart—Ambientlightthresholdadjustspreciselytothe user’s preference.Instructions:Ifswitchturnsonwhenthereisenoughnaturallight,orifswitch does not turn on when there is not enough natural light, press thelargebuttonwithin5secondsofenteringtheroom.Overtime,thisinteraction will “teach” the switch your preferred setting.
• Presets—high,medium,low,anddisabled.
Sensor Operation• Occupancy/Vacancy:Auto-ON/Auto-OFFor
Manual-ON/Auto-OFF• Vacancyonly:Manual-ON/Auto-OFFonly
Timeout Options(SeeAdditional Featuresonpage5fordefaultsettings)
• 1Minute• 5Minutes• 15Minutes• 30Minutes
Sensitivity Options• Highsensitivity(default)• Lowsensitivity
Auto-ON Options(MS-OPSandUMS-OPSonly)
• Occupancy(default):Auto-ON/Auto-OFF• Vacancy*:Manual-ON/Auto-OFF• LowLight:Lightsturnononlyifneeded(ifambient
lightisbelowthreshold) *Thereisa15-secondgraceperiodthatbeginswhenthelightsare
automatically turned off, during which the lights will automatically turn back on in response to motion. This grace period is provided as a safety and convenience feature in the event that the lights turn off while the room is still occupied, so that the user does not need to manually turn thelightsbackon.After15seconds,thegraceperiodexpiresandthelights must be manually turned on.
Manual Off-While-Occupied Options(MS-OPSandUMS-OPSonly—seeAdditional Featuresonpage5fordefaultsetting)
• Enabled– WhentheOccupancysensingswitchismanually
turned off, the Occupancy sensing switch will not turn the lights back on automatically while the room is occupied.
– Oncetheroomisvacated,theAuto-ONfeaturereturns to normal operation after the timeout periodhasexpired.
– Thismaybethepreferenceinconferenceroomsor classrooms while viewing presentations. This featurerequiresmotiontokeepthelightsoff.
• Disabled– WhentheOccupancysensingswitchismanually
turnedoff,theAuto-ONfeaturewillreturntonormaloperationafter25seconds.
– Thismaybethepreferenceiftheuseralwayswants the lights to turn on upon entering and the lights to turn off when the room is vacant.
Maestro Sensor
369666d409.27.17
® SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Switch with Occupancy/ Vacancy Sensor
Selection MatrixVacancy only2 (Title 24 compliant)
Single-pole onlySingle-pole / 3-way capabilityWorks with standard mechanical 3-way switch3
Works with companion switch3, 4
All lighting loads (120 V~ only)
Max current ratingAll lighting loads (120 – 277 V~ only)
Fan (120 V~)
Light + Fan (120 V~)
Neutral wire required
Off-state powerGround wire required for functionality
Minimum load required
Relevant wiring diagram
Model Number1
MS-OPS2-XX 2A 1
MS-OPS2H-XX-C 2A 1
MS-OPS5M-XX 5A 3A 3A 2,3,5
MS-OPS5MH-XX-C 5A 3A 3A 2,3,5
MS-OPS6M2-DV-XX 6A 3A 3A 2–6
MS-OPS6M2N-DV-XX 6A 3A 3A 7–11
UMS-OPS6M-DV-XX5 6A 3A 3A 25W 12–17
MS-VPS2-XX 2A 1
MS-VPS5M-XX 5A 3A 3A 2,3,5
MS-VPS6M2-DV-XX 6A 3A 3A 2–6
MS-VPS6M2N-DV-XX 6A 3A 3A 7–11
UMS-VPS6M-DV-XX5 6A 3A 3A 25W 12–17
1 XXinmodelnumberrepresentscolor/finishcode.2 OccupancysensorscanbeconfiguredasAuto-ON/Auto-OFForManual-ON/Auto-OFF. VacancysensorsareconfiguredasManual-ON/Auto-OFFonly.
3 Standardmechanical3-wayswitchcannotbecombinedwithcompanionswitch.4 CompanionswitchMA-AS,MSC-AS,MA-AS-277,orMSC-AS-277isrequiredformulti-locationinstallations(morethantwolocationscontrollingthesamelightingcircuit).Uptoninecompanionswitchesmaybeconnected.
5 BAA-compliantmodels.
Maestro Sensor
369666d509.27.17
® SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Switch with Occupancy/ Vacancy Sensor
Crush/tamper-resistant lens
Ambient light detection
Switching
XCT technology
Manual off-while-occupied default setting
Default timeout (minutes)
Model Number1
MS-OPS2-XX Smart Standard Disabled 5
MS-OPS2H-XX-C Smart Standard Disabled 5
MS-OPS5M-XX Smart Standard Disabled 5
MS-OPS5MH-XX-C Smart Standard Disabled 5
MS-OPS6M2-DV-XX Smart Adaptive Enabled 15
MS-OPS6M2N-DV-XX Smart Adaptive Enabled 15
UMS-OPS6M-DV-XX Presets Softswitch Enabled 5
MS-VPS2-XX Smart Standard 5
MS-VPS5M-XX Smart Standard 5
MS-VPS6M2-DV-XX Smart Adaptive 15
MS-VPS6M2N-DV-XX Smart Adaptive 15
UMS-VPS6M-DV-XX Presets Softswitch 5
Additional Features
1 XXinmodelnumberrepresentscolor/finishcode.
Maestro Sensor
369666d 6 09.27.17
® SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Switch with Occupancy/ Vacancy Sensor
5ft (1.5m)
10 ft (3m)
15ft (4.5m)
20 ft (6m)
25ft (7.5m)
30 ft (9m)
Horizontal Beam Diagram
5ft (1.5m)
5ft (1.5m)
0
10 ft (3m)
10 ft (3m)
15ft (4.5m)
15ft (4.5m)
20 ft (6m)
20 ft (6m)
25ft (7.5m)
25ft (7.5m)
30 ft (9m)
30 ft (9m)
Vertical Beam Diagram
4ft (1.2m)
00 10 ft (3m)
15ft (4.5m)
20 ft (6m)
25ft (7.5m)
30 ft (9m)
NEMA WD7 Coverage
5ft (1.5m)
5ft (1.5m)
0
10 ft (3m)
10 ft (3m)
15ft (4.5m)
15ft (4.5m)
5ft (1.5m)
Majormotioncoverage:900ft2(81m2)
Minormotioncoverage:400ft2(36m2)
Occupancy Sensing Switch Placement and Operation• TheabilityoftheOccupancysensingswitchtodetectmotionrequiresline-of-sightofroomoccupants.The
Occupancy sensing switch must have an unobstructed view of the room.• HotobjectsandmovingaircurrentscanaffecttheperformanceoftheOccupancysensingswitch.• TheperformanceoftheOccupancysensingswitchdependsonatemperaturedifferentialbetweentheambient
roomtemperatureandthatofroomoccupants.WarmerroomsmayreducetheabilityoftheOccupancysensingswitch to detect occupants.
DefinitionsMajor motion: movement of a person entering or passing through an area.Minor motion:movementofapersonoccupyinganareaandengaginginsmallactivities(e.g.,reachingforatelephone,turningthepagesofabook,openingafilefolder,pickingupacoffeecup).
Maestro Sensor
369666d 7 09.27.17
® SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Switch with Occupancy/ Vacancy Sensor
GangingWhengangingwithothercontrolsinthesamewallbox,removeinsidefins(UMS-OPS6M-DVand UMS-VPS6M-DVonly).
DimensionsMeasurementsshownas:in(mm).
Front View Side View
411⁄16
(119)
215⁄16
(75)11⁄8(30)
5/16(8)1/8(3)
DoNOTremoveoutsidefinsonEndofGangcontrols
Each control has inside fins removed
Middle of Gang control has all fins removed
Maestro Sensor
369666d809.27.17
® SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Switch with Occupancy/ Vacancy Sensor
Operation
MS-OPS2MS-OPS5MMS-OPS6M2-DVMS-OPS6M2N-DVMS-VPS2MS-VPS5MMS-VPS6M2-DVMS-VPS6M2N-DV
UMS-OPS6M-DVUMS-VPS6M-DV
Sensor Lens
TapswitchTapon/off
Sensor LED(behindlens) Pulsesduringconfigurationof custom settings and in the Test mode.
IMPORTANT NOTICEFASS—Front Accessible Service Switch— Toserviceload,removepowerbypullingtheFASSswitch out completely on either the Dimmer orCompanion Dimmer. After servicing load, pushtheFASSswitchbackinfullytorestorepowertothe control.
Status LEDIndicatesloadstatus;glowssoftlyas night light when light is off
Sensor LEDPulsestoacknowledge motion when theloadisON.
FASSFrontAccessible ServiceSwitch
TapswitchTapon/off
Sensor Lens
Mounting
Wallbox Occupancy Sensing Switch WallplateAdapter/Wallplate (soldseparately)
Mounting screws Adaptermountingscrews
Maestro Sensor
369666d 9 09.27.17
® SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Switch with Occupancy/ Vacancy Sensor
Continued on next page...
Wiring Diagrams
Single Location Installation (120 V~)-OPS2and-VPS2
Wiring Diagram 1
Occupancy sensing switch
120V~ 50/60Hz
Green
Ground
Hot/Live
Neutral
LoadBare
Black Black
1 Whenusingcontrolsinsinglelocationinstallations,tightentheblueterminalorcapbluewire.Donotconnecttheblueterminal/wiretoanyotherwireortoground.2 OnlyoneOccupancysensingswitchcanbeusedpermulti-locationcircuit.3 Asinglestandardmechanical3-wayswitchorupto9companionswitchesmaybeconnectedtomostOccupancysensingswitches.
Standardmechanical3-wayswitchcannotbecombinedwithcompanionswitch.Totalblueterminalwirelengthmaybeupto150 ft(46 m).
Single Location Installation (120 V~)1-OPS5M,-OPS6M2-DV,-VPS5M,-VPS6M2-DV
Wiring Diagram 2
120V~ 50/60Hz
Green
Ground
Hot/Live
Neutral
Load
Blue1
Bare
Black Black
Occupancy sensing switch
3-way Installation with Standard Mechanical Switch (120 V~)2, 3
-OPS5M,-OPS6M2-DV,-VPS5M,-VPS6M2-DV
Black
Blue
Green
Ground
Occupancy sensing switch
Greenscrew
Ground
120V~ 50/60Hz
Hot/Live
Neutral
Load
Standard mechanical switch
Black
Jumper wireBare
Differentcolor screw (Common)
Wiring Diagram 3
OR
Black
Blue
Ground
Occupancy sensing switch
Green
Ground120V~ 50/60Hz
Hot/Live
Neutral
Load
Standard mechanical switch
Black
Jumper wireBare
Differentcolor screw (Common)
Greenscrew
Maestro Sensor
369666d 10 09.27.17
® SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Switch with Occupancy/ Vacancy Sensor
Wiring Diagrams (continued)
Wiring Diagram 5Multi-Location Installation (120 V~)1, 2, 4
-OPS5M,-OPS6M2-DV,-VPS5M,-VPS6M2-DVwithMA-ASorMSC-AS
Blue
Green
Ground
Occupancy sensing switch4
Black
Ground120V~ 50/60Hz
Brass BrassBlack
Blue Blue
Green Green
Ground
Hot/Live
Neutral
Load
MA-AS or MSC-AS
MA-AS or MSC-AS
Bare
Black Black
1 Asinglestandardmechanical3-wayswitchorupto9companionswitchesmaybeconnectedtomostOccupancysensingswitches. Standardmechanical3-wayswitchcannotbecombinedwithcompanionswitch.Totalblueterminalwirelengthmaybeupto150 ft(46 m).
2 OnlyoneOccupancysensingswitchcanbeusedpermulti-locationcircuit.3 Fanloadappliesto120V~only(notfor277V~).4 Occupancy sensing switch can be installed in any location.
Continued on next page...
3-way Installation with Standard Mechanical Switch (277 V~)1, 2, 3
-OPS6M2-DV,-VPS6M2-DV
Black
Blue
Green
Ground
Occupancy sensing switch
Ground
277V~ 50/60Hz
Hot/Live
Neutral
Load
Standard mechanical switch
Black
Jumper wireBare
Differentcolor screw (Common)
Wiring Diagram 4
Black
Blue
Ground
Occupancy sensing switch
Green
Ground277V~ 50/60Hz
Hot/Live
Load
Standard mechanical switch
Black
Jumper wireBare
Differentcolor screw (Common)
Neutral
OR
Greenscrew
Greenscrew
Maestro Sensor
369666d 11 09.27.17
® SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Switch with Occupancy/ Vacancy Sensor
1 Asinglestandardmechanical3-wayswitchorupto9companionswitchesmaybeconnectedtomostOccupancysensingswitches. Standardmechanical3-wayswitchcannotbecombinedwithcompanionswitch.Totalblueterminalwirelengthmaybeupto150 ft(46 m).
2 OnlyoneOccupancysensingswitchcanbeusedpermulti-locationcircuit.3 Occupancy sensing switch can be installed in any location.4 Fanloadappliesto120V~only(notfor277V~).
Wiring Diagrams (continued)Wiring Diagram 6Multi-Location Installation (277 V~)1, 2, 3, 4
-OPS6M2-DV,-VPS6M2-DVwithMA-AS-277orMSC-AS-277Occupancy sensing
switch3
Black
Blue
Green
Ground
Black
Blue
Green
Ground
277V~ 50/60Hz
Black
Blue
Green
Ground
Hot/Live
Neutral
Load
RedRed
Bare
Black
MA-AS-277 or MSC-AS-277
MA-AS-277 or MSC-AS-277
Continued on next page...
Maestro Sensor
369666d 12 09.27.17
® SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Switch with Occupancy/ Vacancy Sensor
Single Location Installation (120-277 V~)1, 2
-OPS6M2N-DV,-VPS6M2N-DV
Wiring Diagram 7
Occupancy sensing switch
120-277V~ 50/60Hz
WhiteGround
Hot/Live
Neutral
Load
Blue1
Bare
Black Black
1 Whenusingcontrolsinsinglelocationinstallations,tightentheblueterminalorcapbluewire.DoNOTconnecttheblueterminal/wiretoanyotherwireortoground.2 Fanloadappliesto120V~only(notfor277V~).3 OnlyoneOccupancysensingswitchcanbeusedpermulti-locationcircuit.4 Asinglestandardmechanical3-wayswitchorupto9companionswitchesmaybeconnectedtomostOccupancysensingswitches.
Standardmechanical3-wayswitchcannotbecombinedwithcompanionswitch.Totalblueterminalwirelengthmaybeupto150 ft(46 m).
Wiring Diagrams (continued)
Continued on next page...
3-way Installation with Standard Mechanical Switch (120 V~)3, 4
-OPS6M2N-DV,-VPS6M2N-DV
Wiring Diagram 8
OR
Black
Blue
Ground
Occupancy sensing switch
WhiteGround120V~ 50/60Hz
Hot/Live
Neutral
Load
Standard mechanical switch
Black
Jumper wireBare
Differentcolor screw (Common)
Greenscrew
Black
Blue
WhiteGround
Occupancy sensing switch
Ground
120V~ 50/60Hz
Hot/Live
Neutral
Load
Standard mechanical switch
Black
Jumper wireBare
Differentcolor screw (Common)
Greenscrew
Maestro Sensor
369666d 13 09.27.17
® SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Switch with Occupancy/ Vacancy Sensor
1 OnlyoneOccupancysensingswitchcanbeusedpermulti-locationcircuit.2 Asinglestandardmechanical3-wayswitchorupto9companionswitchesmaybeconnectedtomostOccupancysensingswitches.
Standardmechanical3-wayswitchcannotbecombinedwithcompanionswitch.Totalblueterminalwirelengthmaybeupto150 ft(46 m).3 Fanloadappliesto120V~only(notfor277V~).
Wiring Diagrams (continued)
Continued on next page...
3-way Installation with Standard Mechanical Switch (277 V~)1, 2, 3
-OPS6M2N-DV,-VPS6M2N-DV
Wiring Diagram 9
OR
Black
Blue
WhiteGround
Occupancy sensing switch
Ground
277V~ 50/60Hz
Hot/Live
Neutral
Load
Standard mechanical switch
Black
Jumper wireBare
Differentcolor screw (Common)
Greenscrew
Black
Blue
Ground
Occupancy sensing switch
White
Ground277V~ 50/60Hz
Hot/Live
Neutral
Load
Standard mechanical switch
Black
Jumper wireBare
Differentcolor screw (Common)
Greenscrew
Maestro Sensor
369666d1409.27.17
® SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Switch with Occupancy/ Vacancy Sensor
Wiring Diagrams (continued)
1 Asinglestandardmechanical3-wayswitchorupto9companionswitchesmaybeconnectedtomostOccupancysensingswitches. Standardmechanical3-wayswitchcannotbecombinedwithcompanionswitch.Totalblueterminalwirelengthmaybeupto150 ft(46 m).
2 OnlyoneOccupancysensingswitchcanbeusedpermulti-locationcircuit.3 Occupancy sensing switch can be installed in any location.4 Fanloadappliesto120V~only(notfor277V~).
Wiring Diagram 11Multi-Location Installation (277 V~)1, 2, 3, 4
-OPS6M2N-DV,-VPS6M2N-DVwithMA-AS-277orMSC-AS-277Occupancy sensing
switch3
Black
Blue
WhiteGround
Black
Blue
Green
Ground
277V~ 50/60Hz
Black
Blue
Green
Ground
Hot/Live
Neutral
Load
RedRed
Bare
Black
MA-AS-277 or MSC-AS-277
MA-AS-277 or MSC-AS-277
Wiring Diagram 10Multi-Location Installation (120 V~)1, 2, 3
-OPS6M2N-DV,-VPS6M2N-DVwithMA-ASorMSC-ASMA-AS or MSC-AS
MA-AS or MSC-AS
Blue
WhiteGround
Occupancy sensing switch3
Black
Ground
120V~ 50/60Hz
Brass BrassBlack
Blue Blue
Green Green
Ground
Hot/Live
Neutral
Load
Bare
Black Black
Continued on next page...
Maestro Sensor
369666d1509.27.17
® SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Switch with Occupancy/ Vacancy Sensor
Wiring Diagrams (continued)Wiring Diagram 12Single Location Installation1, 2
-OPS6M-DVand-VPS6M-DVOccupancy
sensing switch
120-277V~ 50/60Hz
RedBlack
Green
Ground
Hot/Live
Neutral
Load
Blue1
Multi-Location Installation (120 V~)1, 4, 5, 6
-OPS6M-DVand-VPS6M-DVwithMA-ASorMSC-AS
Wiring Diagram 14
RedBlack
Blue
Green
Ground
BrassBlack
Blue
Green
Ground
120V~ 50/60Hz
BrassBlack
Blue
Green
Ground
Hot/Live
Neutral
Load
Occupancy sensing switch6
MA-AS or MSC-AS
MA-AS or MSC-AS
Multi-Location Installation (277 V~)1, 2, 3, 4, 5, 6
-OPS6M-DVand-VPS6M-DVwithMA-AS-277orMSC-AS-277
Wiring Diagram 15
Black
Blue
Green
Ground
Black
Blue
Green
Ground
277V~ 50/60Hz
Black
Blue
Green
Ground
Hot/Live
Neutral
Load
RedRedRed
Occupancy sensing switch6
MA-AS-277 or MSC-AS-277
MA-AS-277 or MSC-AS-277
1 Whenusingcontrolsinsinglelocationinstallations,tightentheblueterminalorcapbluewire.Donotconnecttheblueterminal/wiretoanyotherwireortoground.2 Fanloadappliesto120V~only(notfor277V~).3 OptionalshuntcapacitormustbeinstalledinsidetheloadfixtureorinaseparateJ-box.4 Upto9companionswitchesmaybeconnectedtoanOccupancysensingswitch.Totalblueterminalwirelengthmaybeupto250 ft(76 m).5 OnlyoneOccupancysensingswitchcanbeusedpermulti-locationcircuit.6 Occupancy sensing switch can be installed in any location.
Single Location Installation with Shunt Capacitor1, 2, 3
-OPS6M-DVand-VPS6M-DV
Wiring Diagram 13
Occupancy sensing switch
120-277V~ 50/60Hz
Green
Ground
Hot/Live
Neutral
Load Shunt Capacitor2
Optional
RedBlack
Blue1
Continued on next page...
Maestro Sensor
369666d 16 09.27.17
® SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Switch with Occupancy/ Vacancy Sensor
Multi-Location Installation with Shunt Capacitor (277 V~)1, 2, 3, 4, 5
-OPS6M-DVand-VPS6M-DVwithMA-AS-277orMSC-AS-277
Wiring Diagram 17
Black
Blue
Green
Ground
Occupancy sensing switch4
Black
Blue
Green
Ground
277V~ 50/60Hz
Black
Blue
Green
Ground
Hot/Live
Neutral
Load
MA-AS-277 or MSC-AS-277
MA-AS-277 or MSC-AS-277
RedRedRed
Shunt Capacitor1
Optional
1 OptionalshuntcapacitormustbeinstalledinsidetheloadfixtureorinaseparateJ-box.2 Upto9companionswitchesmaybeconnectedtoanOccupancysensingswitch.Totalblueterminalwirelengthmaybeupto250 ft(76 m)3 OnlyoneOccupancysensingswitchcanbeusedpermulti-locationcircuit.4 Occupancy sensing switch can be installed in any location.5 Fanloadappliesto120V~only(notfor277V~).
Wiring Diagrams (continued)
Multi-Location Installation with Shunt Capacitor (120 V~)1, 2, 3, 4
-OPS6M-DVand-VPS6M-DVwithMA-ASorMSC-AS
Wiring Diagram 16
Black
Blue
Green
Ground
Occupancy sensing switch4
Black
Blue
Green
Ground
120V~ 50/60Hz
Black
Blue
Green
Ground
Hot/Live
Neutral
Load
MA-AS or MSC-AS
MA-AS or MSC-AS
Shunt Capacitor1
Optional
RedBrassBrass
Maestro Sensor
369666d 17 09.27.17
® SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Switch with Occupancy/ Vacancy Sensor
Colors and Finishes
• Duetoprintinglimitations,colorsandfinishesshowncannotbeguaranteedtomatchactualproductcolorsperfectly.
• Colorchipkeychainsareavailableformoreprecisecolormatching: GlossFinishes:DG-CK-1 SatinFinishes:SC-CK-1
Satin Finishes
TaupeTP
TurquoiseTQ
PlumPL
MerlotMR
TerracottaTC
SiennaSI
MidnightMN
HotHT
DesertStoneDS
EggshellES
BiscuitBI
SnowSW
PalladiumPD
GreenbriarGB
BluestoneBG
Mocha StoneMS
GoldstoneGS
SeaGlassSG
StoneST
LimestoneLS
Gloss Finishes
WhiteWH
IvoryIV
AlmondAL
LightAlmondLA
GrayGR
BrownBR
BlackBL
)Lutron,Lutron,Maestro,andSoftswitcharetrademarksofLutronElectronicsCo.,Inc.,registeredintheU.S.andothercountries.
XCTandFASSaretrademarksofLutronElectronicsCo.,Inc.