CARRIER 23 XRV SCREW CHILLER PNEUMATIC HEAD PRESSURE …€¦ · positioner & actuator shown...

Post on 03-Apr-2020

27 views 0 download

Transcript of CARRIER 23 XRV SCREW CHILLER PNEUMATIC HEAD PRESSURE …€¦ · positioner & actuator shown...

WESLEY VALVE CO.MFGRS OF AUTOMATED BUTTERFLY VALVES

4938 S. Atlanta Rd., Ste. 100Atlanta, GA 30339

PHN: (404) 351-8744 FAX: (404) 351-9340

www.Wesleyvalve.com

4-20mA Control Circuit

PNEUMATIC CONDENSOR WATER VALVE

M 20#M

B

P

SCHNEIDER POS.POSITIONER& ACTUATORSHOWN

POSITIVE POSITIONER

MFGR’S POS. POSITIONER CONNECTIONSMFGR SIG.—MAIN-ACTUATOR

SCHNEIDER P M BHONEYWELL P M BJOHNSON P S OSIEMENS T S M

SCHNEIDERCP8551ELECTRONIC/PNEUMATICTRANSDUCER4-20 mA SIGNAL

M

TO P OFPOSITIVEPOSTIONER

Use for 4-20 mA Signal

SIGNAL

BLU

BLK

+

-

TOCCM

MODULE

HONEYWELLRP7517A-1009ELECTRONIC/PNEUMATICTRANSDUCER2-10 VDC SIGNAL

12

M

Use for 2-10 VDC Signal

TO P OFPOSITIVEPOSTIONER

TO ELECTRONIC/PNEUMATIC

TRANSDUCER

File:MHHPCarrierXRVPneu

CARRIER 23 XRV SCREWCARRIER 23 XRV SCREWCARRIER 23 XRV SCREW CHILLERCHILLERCHILLER PNEPNEPNEUUUMATICMATICMATICHEAD PRESSURE VALVEHEAD PRESSURE VALVEHEAD PRESSURE VALVE COCOCONNNTROLTROLTROL

Auto Demand ResetController Input (Note 1)

Auto Chilled Water ResetController Input (Note 1)

Refrigerant LeakController Input (Note 2)

(SHIELD)

(SHIELD)

Spare Temp #2 SensorCommon Return (Note 3)

Spare Temp #1 SensorCommon Supply (Note 3)

Remote Temp ResetSensor (Note 3)

I+Com

CCM Module

Control Panel

123456

J5

131425262728

J4

12

J8

Control Panel

Notes:

1. Requires a controller with a nongrounded 4-20 mA or 1-5 Vdcsignal. Not by Carrier

2. Requires a controller with a nongrounded 4-20 mA or 1-5 Vdcsignal Not by Carrier

3. Requires a sensor packageoption by CarrierI+

COM

1

2

Wire to J8 ofCCM Module

Condenser WaterReturn to Tower

Condenser WaterSupply from Tower

Locate Chiller Head Press Valvein Condenser Water Return Line

CARRIER 19XR CENTRIFUGALCHILLER CCM MODULE ANDHEAD PRESSURE VALVECONTROL CONNECTION ISIDENTICAL

To Electronic/PneumaticTransducer

Wire toTB2

I+Com

Condenser WaterSupply from Tower

Condenser WaterReturn to Tower

Locate Chiller Head Press Valvein Condenser Water Return Line

To Electronic/PneumaticTransducer

CARRIER 30 HXCCARRIER 30 HXCCARRIER 30 HXCSCREW CHILLER UNITSSCREW CHILLER UNITSSCREW CHILLER UNITSHEAD PRESSUREHEAD PRESSUREHEAD PRESSURE PNEPNEPNEU-U-U-MMMATICATICATIC VALVVALVVALVE CONTROLE CONTROLE CONTROL

Remove Jumper whenusing pump interlock

WESLEY VALVE CO.MFGRS OF AUTOMATED BUTTERFLY VALVES

4938 S. Atlanta Rd., Ste. 100Atlanta, GA 30339

PHN: (404) 351-8744 FAX: (404) 351-9340

www.Wesleyvalve.com

4-20mA Control Circuit

PNEUMATIC CONDENSOR WATER VALVE

M 20#M

B

P

SCHNEIDER POS.POSITIONER& ACTUATORSHOWN

POSITIVE POSITIONER

MFGR’S POS. POSITIONER CONNECTIONSMFGR SIG.—MAIN-ACTUATOR

SCHNEIDER P M BHONEYWELL P M BJOHNSON P S OSIEMENS T S M

SCHNEIDERCP8551ELECTRONIC/PNEUMATICTRANSDUCER4-20 mA SIGNAL

M

TO P OFPOSITIVEPOSTIONER

Use for 4-20 mA Signal

SIGNAL

BLU

BLK

+

-

HONEYWELLRP7517A-1009ELECTRONIC/PNEUMATICTRANSDUCER2-10 VDC SIGNAL

12

M

Use for 2-10 VDC Signal

TO P OFPOSITIVEPOSTIONER

TO ELECTRONIC/PNEUMATIC

TRANSDUCER

File:MHHPCarrierHXCPneu

I+

COM

14

15

Wire toTB2