SG, SH SERIES - shinko-technos.co.jp · Started to manufacture electrical switchboard instrumen ts....

16
Exclusive lineup for BS (building system)/PA (process automation) SG, SH SERIES

Transcript of SG, SH SERIES - shinko-technos.co.jp · Started to manufacture electrical switchboard instrumen ts....

Page 1: SG, SH SERIES - shinko-technos.co.jp · Started to manufacture electrical switchboard instrumen ts. 1949 Incorporated and officially named Shinko Electric Instrument Co., Ltd. 1953Developed

Exclusive l ineup for BS (bui lding system)/PA (process automation)

SG, SH SERIES

Page 2: SG, SH SERIES - shinko-technos.co.jp · Started to manufacture electrical switchboard instrumen ts. 1949 Incorporated and officially named Shinko Electric Instrument Co., Ltd. 1953Developed
Page 3: SG, SH SERIES - shinko-technos.co.jp · Started to manufacture electrical switchboard instrumen ts. 1949 Incorporated and officially named Shinko Electric Instrument Co., Ltd. 1953Developed

In addit ion to the know-how we have developed over many years , we a im to contr ibute to the future society through act iv i t ies such as establ ished qual i ty control system ( received ISO9001 cert ificat ion) to guarantee customer sat is fact ion as wel l as improve -ment of the g lobal envi ronment to be able to rea l ize our coexistence with society [ received ISO4001 cert ificat ion (HQ only) ] .

We cont r ibute to the fu ture by prov id ing our h igh-qua l i ty se rv ices and env i ronmenta l conservat ion act iv i t ies .

Fukuoka factoryHead office (Minoo-city, Osaka)

ISO9001 ISO14001(HQ only)

We s t r i v e t o c r e a t e p r oduc t s t h a t a r e no t on l y i nnova t i v e bu t h e l p t o ma i n t a i n t h e h a rmony be tween peop l e and i ndu s t r y .

Establ ished in 1945 as an electr ical switchboard instrument manufacturer ( in Yodogawa-ku, Osaka-city) .Having manufactured and sold temperature control equipment for industr ia l use for over 70 years .

Company H i s to ry1945 Sadao Kitagawa established Shinko Electric Instrument Works,

Ltd. in Yodogawa-ku, Osaka-city.Started to manufacture electrical switchboard instruments.

1949 Incorporated and officially named Shinko Electric Instrument Co., Ltd.1953 Developed and started to manufacture electron tube type automatic

temperature controllers.1960 Developed and started to manufacture transistor type automatic temperature

controllers.1961 Head office and factory completed in Minoo-city, Osaka.1968 Sanda factory completed in Sanda-city, Hyogo.1973 Fukuoka factory completed in Mii-gun, Fukuoka.1980 Developed microcomputer based temperature controller, became a pioneer

of the industry. 1985 Tokushima factory completed in Oe-gun, Tokushima

(Currently, Yoshinogawa-city, Tokushima).Established the Central research laboratory at the head office, in Osaka.

1991 Changed company name to SHINKO TECHNOS CO., LTD.2005 Moved head office to Senbahigashi, Minoo-city, Osaka.

Trans i t ion o f Conver te r s2005 Signal conditioners for industrial use SA series released2005 Small-sized signal conditioners for industrial use SB series released2010 Plug-in type signal conditioners SE, SF series released2015 New plug-in signal conditioners released

We have been a c cumu la t i ng e xpe r i ence s i n t he measu remen t and con t ro l fie ld s f o r o ve r a ha l f - c en tu r y and p l a y i ng a s i gn i fi can t r o l e i n suppo r t i ng ou r affluen t soc i e t y .E spec i a l l y i n t he con t ro l fie ld , we t a ke p r i de i n hav ing suppo r t ed v a r i ou s i ndus t r i e s f o r a l ong pe r i od o f t ime .

SHINKO TECHNOS CO. , LTD .

Product L ine Various types of indicating controllers, programmable controllersEnvironment measuring instruments, thermocouples, RTDsSignal conditioners, recorders, indicatorsTemperature control boards, etc.

      

SG, SH series

Page 4: SG, SH SERIES - shinko-technos.co.jp · Started to manufacture electrical switchboard instrumen ts. 1949 Incorporated and officially named Shinko Electric Instrument Co., Ltd. 1953Developed

Features Common to All Series

Standard Features for Multi, Air-Conditioning Control, Alarm, Link Series

Booting up the equipment is easier with a computer via USB bus power.

Boo t ing up the equ ipment i s e a s i e r w i th a compute r v i a USB bus powe r . A l l p roduc t s c an be s e t by the compute r . ( Loade r t e rm ina l equ ipped )Be ing connec ted to a compute r t h rough a spec i a l c ab l e , t h i s p roduc t s t a r t s up v i a USB bus powe r and s imp l i fie s mak ing s e t t i ng changes .E x c l u s i ve s e t t i ng so f twa re i s a va i l ab l e .The so f twa re c an be down loaded f r om Sh inko webs i t e f o r f r ee .

PC Setting Possible

Space-saving, Compatible design

• Dep th i s sho r t ened by 15 mm ( compa red to ma rke t s t anda rd ) .• Suffic ien t l oad r e s i s t ance , Ou tpu t impedance 750 Ω fo r bo th 1 -ou tpu t and 2 -ou tpu t s• Bu i l t - i n shun t r e s i s to r o r e x t e rna l l y moun ted shun t r e s i s to r i s s e l e c t ab l e .• 2 -w i r e t r an sm i t t e r c an be connec ted .

Compatible Design All products support 85 to 264 V AC.

Worldwide Power Supply

All products can be mounted in close contact.

Close Contact Mounting Possible.

Standard style can be delivered on the following day. (excluding a part of products)

Prompt Delivery System

Various option settings

• Mu l t i - r o t a t i on t r immer A l l owance o f ad ju s tmen t w id th enab l e s fine ad ju s tmen t .• Coa t i ngs a r e a va i l ab l e . Th i s c an be u sed when env i ronmenta l coun te rmeasu re s need t o be t a ken .

Options

The industry ’s first !Bui l t - in white LED backl ight l iquid crystalDisplay modes are available to meet customer needs.

11-segments d i sp lay (a lphanumer ic charac te rs can be used . )Mounted in a dark pane l , the d i sp lay i s eas i l y seen .Mul t i , A i r - cond i t ion ing cont ro l , L ink Ser ies : Up to 13 d i sp lay modes and up to 12 a la rm types a re ava i l ab le .Auto l ights -out i s a l so ava i l ab le .

Display Pattern

Manual setting mode, Lock, Custom functions

Sta r tup ad jus tment funct ion (manua l se t t ing mode) , d i sp lay lock ower ) a re p rov ided .

Multifunctional

*A special cable (sold separately) is needed. Power is supplied from the computer, so no wiring is required for the main unit.

funct ion , cus tom d i sp lay (8 d ig i t s fo r upper and l

Page 5: SG, SH SERIES - shinko-technos.co.jp · Started to manufacture electrical switchboard instrumen ts. 1949 Incorporated and officially named Shinko Electric Instrument Co., Ltd. 1953Developed

MATRIX

Signal Conditioner Type Input Type Output Type

Signal Conditioner Type Input Type Output Type

High/Low Se lec tor Current, voltage input *1 Current, voltage output

Ratio Transmitter(Ratio, bias) Current, voltage input Current, voltage output

Split-Range Transmitter Current, voltage input Current, voltage input *2 

AIR-CONDITIONING CONTROL

◯ ×

× ◯

◎ ◯

Limiter Current, voltage input Current, voltage output ◎ ◯

ALARM

Instrumentation Signal Input Alarm Setter (4 to 20 mA, 1 to 5 V only)

4 to 20 mA, 1 to 5 V Relay output a or b contact selectable ◯ ◯

Universal Input Alarm Setter Current, voltage input, RTD, Thermocouple input ◯ ◯

MULTI

1-Output 2-Outputs

1-Output 2-Outputs

2-Outputs 4-Outputs

2-Outputs

STANDARD

1-OutputSignal Conditioner Type Input Type Output Type

Isolator 4 to 20 mA, 1 to 5 V 4 to 20 mA, 1 to 5 V

Current Loop Supply 4 to 20 mA

RTD Transmitter RTD input

Potentiometer Transmitter Potentiometer input

DC Signal Transmitter Current, voltage input Current, voltage output

Current, voltage output

Universal Transmitter RTD , Thermocouple input

Pulse-Analog Transmitter Pulse input

Pulse Transmitter Pulse input Various pulse outputs

Linearizer

Current Loop Supply withratio setting

STANDARDMULTI

◎ ◯

◎ ◯

◎ ◯

◎ ◯

◎ ◯

◎ ◯

◎ ◯

◎ ◯

◎ ◯

◎ ×

◯ ◯

◯ ◯

◯ ◯

× ×

◯ ◯

◯ ◯

× ×

× ×

× ×

× ×

Thermocouple Transmitter Thermocouple input ◎ ◯ ◯ ◯

2-Input Math FunctionTransmitter

Current, voltage input * ◯ × × ×

Differential Transmitter Thermocouple, RTD input * ◯ × × ×

Current, voltage output

Current, voltage output

Current, voltage output

Current, voltage output

Current, voltage outputCurrent, voltage input

Current, voltage outputCurrent, voltage input

Current, voltage output

Current, voltage output

Current, voltage output

4 to 20 mA

Serial communication RS-485 output can be equipped.

*1: Input 1 and Input 2 are the same input type.*2: Output 1 and Output 2 are the same output type.

Serial communication RS-485 output can be equipped.

Relay output a or b contact selectable

Page 6: SG, SH SERIES - shinko-technos.co.jp · Started to manufacture electrical switchboard instrumen ts. 1949 Incorporated and officially named Shinko Electric Instrument Co., Ltd. 1953Developed

Transmitter types need to be specified prior to factory shipment.

MULTI SERIESMULTI SERIES

Flagship ModelPursuit of mult i - funct ions and usabi l i ty

The Industry ’s Frst ! White Backl ight L iquid Crystal Input and output d i sp lays can be eas i l y checked in the cont ro l pane l . 11 -segments d i sp lay (A lphanumer ic charac te rs can be used . )

Direct Setting Mode

Various Display Settings (Up to 13 kinds of display mode)

Simple and Multifunctional Products Lineup

With one product, ratio setting (up to x10) * and square root extraction can be executed. (This supports 2-wire transmitter.)*This is in case of the current loop supply having the ratio setting function. For 2-output types, ratio and limiter settings are available. (Refer to the next page.)

●Current Loop Supply (as power source for 2-wire transmitter)

One device handles input of current, voltage, thermocouple and RTD. Input and output are changeable, so this product is perfect for inventory or for being brought to the work site.

●Universal Input Transmitter (Various signals can be handled by one device.)

One device handles arithmetical operations and arithmetic expressions.Calorie calculations can be conducted by combining this product with the differential transmitter.

●2-Input Math Funct ion Transmitter (Al l calculat ions are handled by one unit . )

Multiple points can be set by a PC or key operation on the main unit. (Can be specified as factory default setting.)Conventionally, all correction points were set at the factory, and there was a difficulty in re-adjustment and change after delivery.

● Linearizer (Exclusive software is available.)

In the transmitter with the ratio setting function, in addition to settingsusing normal computing equations, ratio and bias value can be set by merely setting input and output values. Even when this product needs to be used on site immediately, settings can be made easily. Regular ratio and bias value settings are also available.

Direct Display (input value) for All Products. Scaling initial value is set based on the input range. (e.g. 4.00 to 20.00 for 4 to 20 mA input) Arbitrary scaling setting can also be made. Scaling indication suitable for your use is possible.

Model Display, 6 RUN Displays, 4 Custom Displays, 2 Unlit Displays are available.(Each display can be registered as a Default Display.)

One device handles calculations and data output of temperature differences from two temperature sensors.This can be used for temperature differences between the inside and outside control panels, or temperature differences at the equipment gateway.

●Different ia l Transmitter (Temperature differences can be handled by one device. )

One device handles each setting of the pulse frequency range (mHz: Ultra-low frequency, Hz: Low frequency, kHz: Frequency) and pulse division. After our product is purchased, the frequency range and frequency settings can be changed to meet the demands of the work site. (When ordering, the specification needs to be designated.)

●Pulse Transmitter (Various pulses can be set by one device.)

Display scroll only with DISP key

Display lock function equipped.Press and hold MODE + DISP for 3 sec.Display lock, misoperation prevention

Adjustment trimmer is used.As an option, multi-rotation trimmer settings can be made.

Page 7: SG, SH SERIES - shinko-technos.co.jp · Started to manufacture electrical switchboard instrumen ts. 1949 Incorporated and officially named Shinko Electric Instrument Co., Ltd. 1953Developed

PLCDCS

Manual Setting Mode (Equipped for all MULTI series products)

Simple Operat ionThe most suitable for communication confirmation (loop check) with the host after installation.

Current Loop Supply with Ratio Setting

Temperature/humid i ty sensor

Rate o f flow, flu id leve l , p ressure gauge : 4 to 20 mA

Output 1

Output 2

Only Output 1 , Output 2 can be changed!

MULTI SERIES 23 Types in Total (Plentiful Lineup)

*Other Products with Limiter Function Thermocouple Transmitter RTD Transmitter Potentiometer Transmitter Universal Transmitter

Enter the setting mode by pressing the key for 3 sec. Output can be changed with the or key.

No sensor output change i s requ i red .

Auto Return Funct ionTo prevent forgetting to switch to automatic operation, time can be set to return to automatic operation (Default Display). (Factory default: 30 minutes)

Rat io sett ing + L imiter funct ions (Rat io t ransmitter with rat io , b ias sett ing)

Output suitable for the input device can be set .

Setting example

100

04 20

Output (mA)

Input(mA)

Output (mA)

Input(mA)

Output (mA)

Input(mA)

Upper Limiter/Lower LimiterWithout Set t ing Reverse Output

100

04 20

50 50

12

Lower LimiterRat io Set t ing x 3 T imes

100

04 20

Isolator (1-output): SGIIsolator (2-outputs): SGIWDC Signal Transmitter (1-output): SGSDC Signal Transmitter (2-outputs): SGSWCurrent Loop Supply (1-output): SGDCurrent Loop Supply (2-outputs): SGDWCurrent Loop Supply with ratio setting (1-output): SGMCurrent Loop Supply with ratio setting (2-outputs): SGMWThermocouple Transmitter (1-output): SGTThermocouple Transmitter (2-outputs): SGTWRTD Transmitter (1-output): SGRRTD Transmitter (2-outputs): SGRW

● ● ● ● ● ● ● ● ● ●● ●

Potentiometer Transmitter (1-output): SGPPotentiometer Transmitter (2-outputs): SGPWUniversal Transmitter (1-output): SGUUniversal Transmitter (2-outputs): SGUWLinearizer (1-output): SGLPulse Transmitter (1-output): SGFPulse Transmitter (2-outputs): SGFWPulse-Analog Transmitter (1-output): SGJPulse-Analog Transmitter (2-outputs): SGJWDifferential Transmitter (1-output): SGQ2-Input Math Function Transmitter (1-output): SGZ

● ● ● ● ● ● ● ● ● ●●

Page 8: SG, SH SERIES - shinko-technos.co.jp · Started to manufacture electrical switchboard instrumen ts. 1949 Incorporated and officially named Shinko Electric Instrument Co., Ltd. 1953Developed

STANDARD SERIESSTANDARD SERIES

Standard models can be delivered on the following day(excluding a part of products) .

All Products in Close Contact Mounting

Space-Saving, Compatible Design

● Depth i s shortened by 15 mm (compared to the market s tandard) .● Sufficient load res is tance : Output impedance 750 Ω for both 1-output and 2-outputs ● Bui l t - in shunt res i s tor or externa l ly mounted shunt res i s tor i s se lectable .● 2-wire t ransmit ter can be connected .

Al lowance of ad justment width enables fine adjustment .●Mult i - ro ta t ion t r immer

This can be used when envi ronmenta l countermeasures need to be taken.

●Coat ings a re ava i l ab le .

Various Option Settings 85 to 264V AC for All Products

Easier Start-up via PC Settings (Loader Terminal Equipped)

Being connected to a computer through a spec ia l cable , th is product s tar ts up v ia USB bus power and s impl ifies making sett ing changes .Exc lus ive set t ing sof tware i s ava i lab le .The sof tware can be downloaded f rom Shinko webs i te for f ree .

Transmitter types need to be specified prior to factory shipment.

Page 9: SG, SH SERIES - shinko-technos.co.jp · Started to manufacture electrical switchboard instrumen ts. 1949 Incorporated and officially named Shinko Electric Instrument Co., Ltd. 1953Developed

Isolator

● 4 to 20 mA or 1 to 5 V input is i solated, and 4 to 20 mA or 1 to 5 V is output . ● 1-output and 2-output types are avai lable . Output impedance: 750 Ω● Input and output can be changed by the PC sett ing.

Current Loop Supply

● Suppl ies power to the two-wire t ransmitter . The 4 to 20 mA input is i solated, and current or voltage i s output .● 1-output and 2-output types are avai lable . Output impedance: 750 Ω● This supports the 'SMART' t ransmitter for sensor .● Output , fi l ter t ime constant , square root extract ion can be changed by the PC sett ing.

Thermocouple Transmitter

● Various thermocouple inputs are isolated, and current or voltage is output .● 1-output and 2-output types are avai lable . Output impedance: 750 Ω● Thermocouple type, temperature range, and output type can be changed by the PC sett ing.● Cold junct ion compensat ion c i rcuit i s provided to the terminal sect ion for accuracy improvement .

RTD Transmitter

● RTD input is i solated, and current or voltage is output .● 1-output and 2-output types are avai lable . Output impedance: 750 Ω● Input type, temperature range, and output can be changed by the PC sett ing.

Potentiometer Transmitter

DC Signal Transmitter

● Current or voltage input is i solated, and current or voltage is output .● 1-output and 2-output types are avai lable . Output impedance: 750 Ω● Input and output can be changed by the PC sett ing.

● Var ious potent iometer inputs are isolated, and current or voltage is output . ● 1-output and 2-output types are avai lable . Output impedance: 750 Ω● Output can be changed by the PC sett ing.

Standard SERIES 12 Types in Total

Isolator (1-output): SHIIsolator (2-outputs): SHIWDC Signal Transmitter (1-output): SHSDC Signal Transmitter (2-outputs): SHSWCurrent Loop Supply (1-output): SHDCurrent Loop Supply (2-outputs): SHDW

● ● ● ● ● ●

● ● ● ● ● ●

Thermocouple Transmitter (1-output): SHTThermocouple Transmitter (2-outputs): SHTWRTD Transmitter (1-output): SHRRTD Transmitter (2-outputs): SHRWPotentiometer Transmitter (1-output): SHPPotentiometer Transmitter (2-outputs): SHPW

Page 10: SG, SH SERIES - shinko-technos.co.jp · Started to manufacture electrical switchboard instrumen ts. 1949 Incorporated and officially named Shinko Electric Instrument Co., Ltd. 1953Developed

SERIESAIR-CONDITIONING CONTROL SERIES

Products necessary for air-conditioning control are lined up in the MULTI series.

High/Low Selector Input value for Ch1 and Ch2 and output value can be checked.High/Low input value can be specified, but High/Low can be changed after purchase.    

Split-Range Transmitter

One unit handles V or Parallel characteristics which is required for air-conditioning control.Input value, Output 1 value and Output 2 value can be checked.

 

Ratio Transmitter (Ratio, Bias)

● Ratio setting (x 10 times) (e.g.) Input 2 mA can be changed to 20 mA. This is an adjustment function useful for a case that an output value does not match the range of the host. Ratio setting and limiter function are equipped with the output type, which enables a wide range of adjustments of output suitable for each input device.

● Normally, arithmetic expression is used for setting ratio and bias values. This product is equipped with the direct setting mode useful for making adjustments on the work site. Refer to the next page. 

Limiter

Output can be controlled at an arbitrarily set value for upper limit and lower limit.Display of input value, Output 1 value and Output 2 value (2-outputs) can be confirmed.  

Current Loop Supply (24 V DC power source) This can be used as power source for a 2-wire transmitter and as an isolator.This is lined up in other series as a current loop supply as follows.

Current loop supply with ratio setting (equipped with ratio, bias function) is also lined up.      

         Isolator, RTD transmitter, potentiometer transmitter, etc. are also lined up in the MULTI series and the Standard series.

        

AIR-CONDITIONINGCONTROL

2-inputs 1-output

1-input 2-outputs

1-input 1-output 1-input 2-outputs

1-input 1-output 1-input 2-outputs

1-input 1-output 1-input 2-outputs

MULTI series (Display, Multifunctional)Standard series (No display)

Transmitter types need to be specified prior to factory shipment.

Page 11: SG, SH SERIES - shinko-technos.co.jp · Started to manufacture electrical switchboard instrumen ts. 1949 Incorporated and officially named Shinko Electric Instrument Co., Ltd. 1953Developed

PLCDCS

Simple operat ionThe most suitable for communication confirmation (loop check) with the host after installation.

Temperature/humid i ty sensor

Rate o f flow, flu id leve l , p ressure gauge : 4 to 20 mA

Output 1

Output 2

Only Output 1 , Output 2 can be changed!

Enter the setting mode by pressing the key for 3 sec. Output can be changed with the or key.

No sensor output change i s requ i red .

Auto Return Funct ionTo prevent forgetting to switch to automatic operation, time can be set to return to automatic operation (Default Display). (Factory default: 30 minutes)

3 Functions Useful for On-Site Adjustments

Manual Setting Mode (for all products)  

Th i s funct ion enab les the se t t ing equ iva lent to the ra t io and b ias input by input t ing input/output va lues .Normal ly , ca l cu la t ing operat ion fo rmula i s requ i red , but w i th th i s d i rec t se t t ing mode , ad jus tment on the s i te can be qu ick ly made .Normal ra t io and b ias va lue can a l so be input .

Direct Setting Mode (Ratio transmitter with ratio, bias setting)This mode is the most suitable for on-site adjustments.

Ratio Setting and Limiter Functions (Ratio transmitter with ratio, bias setting)

Air-Conditioning Control Series 6 Types in Total

PLCDCS

100

04 20(mA)

100

04 20(mA)

50 50

12

100

04 20(mA)

Simple Operat ionThe most suitable for communication confirmation (loop check) with the host after installation.

Temperature/humidity sensor

Rate o f flow, flu id leve l , p ressure gauge : 4 to 20 mA

Output 1

Output 2

Only Output 1, Output 2 can be changed!

Enter the setting mode by pressing the key for 3 sec. Output can be changed with the or key.

No sensor output change i s requ i red .

Auto Return Funct ionTo prevent forgetting to switch to automatic operation, time can be set to return to automatic operation (Default Display). (Factory default: 30 minutes)

Output suitable for the input device can be set .

Setting example

Output (mA)

Input

Output (mA)

Input

Output (mA)

Input

Upper Limiter/Lower LimiterWithout Set t ing Reverse Output

Lower LimiterRat io Set t ing x 3 T imes

High/Low Selector (1-output): SGHRatio Transmitter (ratio, bias) (1-output): SGBRatio Transmitter (ratio, bias) (2-outputs): SGBWSplit-Range Transmitter (2-outputs): SGXWLimiter (1-output): SGCLimiter (2-outputs): SGCW

● ● ● ● ● ●

Page 12: SG, SH SERIES - shinko-technos.co.jp · Started to manufacture electrical switchboard instrumen ts. 1949 Incorporated and officially named Shinko Electric Instrument Co., Ltd. 1953Developed

ALARM SERIESALARM SERIES

Easier Start-up for All Products via PC settings (Loader terminal equipped)

Being connected to a PC through a special cable, this product starts up with USB bus power, and simplifies making setting changes. Exclusive setting software is available. The software can be downloaded from Shinko website for free.

Screen Exclusive for Changing Set Values (Alarm 1 to Alarm 4 can be selected.)

● Relay outputs for Alarm 1 to Alarm 4 can be easily switched ON/OFF. This function is useful for checking connection after installation. Without changing the sensor input, relay operation can be checked. This is the same procedure for Manual setting mode of the MULTI series, but the operation differs.

  

Relay Output Equipped (2-outputs/4-outputs)

● Both a contact and b contact output type are available.● 4-outputs type in the same case is also available.● The case i s same with other ser ies , so th is product s impl ifies to keep ba lance in the panel . ● The c contact output type will be available soon.

Easy-to-Use Key Layout

● For the alarm series, operationality was considered. The SHIFT key (  key) is provided to improve operationality.

Auto Return Function● Time can be set to return to automatic operation (Default Display) to eliminate operator’s forgetting to switch to automatic operation. (Factory default: 30 minutes)

● An alarm value can be changed easily. Lock function can be selected. (Refer to the next page.)

Manual Test Mode

Transmitter types need to be specified prior to factory shipment.

Page 13: SG, SH SERIES - shinko-technos.co.jp · Started to manufacture electrical switchboard instrumen ts. 1949 Incorporated and officially named Shinko Electric Instrument Co., Ltd. 1953Developed

Versatile Display Patterns (2-outputs: 9 types, 4-outputs: 12 types)

Alarm 1 and Alarm 2 values are indicated. Reverses displays with the UP key.For 4-outputs, Alarm 3 and Alarm 4 display are added.

Alarm Display

Exclusive for 4 to 20 mA and 1 to 5 V inputs.The a contact and b contact are available.The c contact output type will be added soon.

Instrumentation signal input alarm setter

One unit can handle input of current, voltage, thermocouple and RTD.The a contact and b contact are available.The c contact output type will be added soon.

Universal input alarm setter

To the Alarm value priority change screen

Model Display Input value indication 2 Custom DisplaysAlarm indication 2 Unlit Displays

Display Patterns (2-outputs type)

Alarm Series 4 Types in Total

RUN Display

    

Lock for Alarm value setting is available.

Alarm Value Changing Display

Model Display Model confirmation can be made with 8 digits (upper and lower). Lower digits are automatically changed when changing the input type (excluding option setting).

Default DisplayRegistering and changing the Default Display can be easily done.The screen returns to the set Default Display when returning from setting mode.

RUN DisplayThe 2-outputs type can be selected from 3 screens. The 4-outputs type can be selected from 5 screens. The screen can be switched to the Alarm value priority change screen from this screen.

2 Custom Displays

Eight digits can be freely set. (Select from alphanumeric characters and symbols.) Screen suitable for the work site can be made by using "numbers, machine number, unit and symbol."Input value can be displayed on the upper section.

2 Unlit Displays

Selectable from the following 3 types.Unlock, Locks all set values, Locks all set values except alarm value

Exclusive lock level (exclusive for alarm series)

Return to Model Display.

● Instrumentation signal input alarm setter (4 to 20 mA, 1 to 5 V only) (2-outputs): SGAL● Instrumentation signal input alarm setter (4 to 20 mA, 1 to 5 V only) (4-outputs): SGAL● Universal input alarm setter (2-outputs): SGAU● Universal input alarm setter (4-outputs): SGAU

Press the SET key on the screens surrounded with a green dotted line, then the screen moves to the Alarm value priority change screen.

Page 14: SG, SH SERIES - shinko-technos.co.jp · Started to manufacture electrical switchboard instrumen ts. 1949 Incorporated and officially named Shinko Electric Instrument Co., Ltd. 1953Developed

D/A converter is not needed.

LINK SERIESLINK SERIES

Equipped with RS-485 Output Terminal (MODBUS RTU) Can be built in the MULTI series 1-output type

Wiring man-hour :Digital conversion :D/A conversion :

Only one wiring with the host. Various inputs such as analog and temperature can be converted to digital.

Calculation results in the PLC can be output in analog.

Application example:

PLC Interface Unit is Available. Model: SIF-600, T2829

One unit can handle communication settings for multiple units (up to 31 units). Software for each PLC setting is available.CC-Link unit (to be released soon)

Connected with RS-485 output

Sensor, temperature,potentiometer, etc.

Flow rate, fluid level, pressure gauge

PLCDCS

Host calculation results Analog output

Analog output

Analog control devices including valve and pump

RS-485 outputBatch communication

Transmitter types need to be specified prior to factory shipment.

Page 15: SG, SH SERIES - shinko-technos.co.jp · Started to manufacture electrical switchboard instrumen ts. 1949 Incorporated and officially named Shinko Electric Instrument Co., Ltd. 1953Developed

PLC Interface Unit

Serial Communication

SIF-600 , T2829

Models with RS-485 Output Terminal

When adding serial communication, RS-485 output terminal is equipped to the bottom surface of the main body.

Corresponding PLC

Made by Mitsubishi Electric Corporation: Made by Omron Corporation:Made by Keyence Corporation:

Made by Yokogawa Electric Corporation:Made by Fuji Electric Co., Ltd.:

Power supply voltage (Specify)

100 to 240 V AC 50/60 Hz   Allowable fluctuation range: 85 to 264 V AC 24 V AC/DC 50/60 Hz   Allowable fluctuation range: 20 to 28 V AD/DC

Insulation resistance 10 MΩ or more, at 500 V DC

Dielectric strengthBetween power terminal and communication (LOCAL) terminal: 1.5 kV AC for 1 minuteBetween power terminal and communication (PLC) terminal: 1.5 kV AC for 1minuteBetween communication (PLC) terminal and communication (LOCAL) terminal: 1.5 kV AC for 1 minute

Ambient temperature/humidity Ambient temperature: 0 to 50°C, Ambient humidity: 35 to 85 %RH (non-condensing)

Power consumptionMounting method

Approx. 7 VA

Dimensions/Weight

DIN rail Dimensions: W30 x H88 x D108 mm (including a socket)Weight: Approx. 180 g (including a socket)

Accessories includedAccessories sold separately

Socket: ASK-002-1 (for ring-type terminals), Communication cable: CPP 0.1 mUSB communication cable: CMB-001

SGIL-①②-0-④SGSL-①②-0-④SGDL-A0②-0-④SGML-A0②-0-④SGTL-①②-0-④SGRL-①②-0-④SGPL-PM②-0-④SGUL-①②-0-④SGLL-①②-0-④SGFL-①②-0-④SGJL-①②-0-④SGBL-①②-0-④SGCL-①②-0-④

Bottom surface of the main body Modular jack pin arrangement

MELSEC Q series, QnA series (only corresponding to Q command), MELSEC FX series (only corresponding to Q command)CJ/CS/CP series

KV series

FA-M3 series

MICREX-SX series

CMB-001 is needed for initial setup.

IsolatorProduct name Model

DC Signal TransmitterCurrent Loop SupplyCurrent Loop Supply with ratio settingThermocouple TransmitterRTD TransmitterPotentiometer TransmitterUniversal TransmitterLinearizerPulse TransmitterPulse-Analog TransmitterRatio Transmitter (ratio, bias)LimiterContact us for type ①, ②, and ④.

RS-485 terminal

Page 16: SG, SH SERIES - shinko-technos.co.jp · Started to manufacture electrical switchboard instrumen ts. 1949 Incorporated and officially named Shinko Electric Instrument Co., Ltd. 1953Developed

2018.10 E02

SHINKO TECHNOS CO., LTD.OVERSEAS DIVISION

Head. Office : 2-5-1, Senbahigashi, Minoo, osaka, 562-0035, JapanTel : 81-72-727-6100Fax : 81-72-727-7006URL : http://www.shinko-technos.co.jp/e/E-mail : [email protected]