ATS Daco Korea

download ATS Daco Korea

of 12

Transcript of ATS Daco Korea

  • 8/12/2019 ATS Daco Korea

    1/12

    DAERYUK Co., Ltd. 1

    ATSAut o Transfer Sw itch

    Automatic Transfer Switch

    ATSFunction of ATS Auto Changer 2Spec ification of M-Type 3 ~ 8

    Spec ification of T-Type 9 ~ 11

    DAERYUK Co. Ltd.

  • 8/12/2019 ATS Daco Korea

    2/12

    ATSAut o Transfer Sw itch

    Item Description

    Manual select Manual select switch is used to transfer AST to the normal power on manual mode.

    Timer On auto mode, Timer is used to set the transfer time from the emergency power to the normal

    power, up to 30 seconds, when the normal power is recovered.

    Timer lamp This time lamp is flickering when the transfer (from emergency to normal) is completed.

    Also, it means the setting value of timer is passed when Timer is set.

    Power Normal power indication lamp

    ATS position It shows that ATS is located on the normal power position if this lamp is on.

    Manual It shows the manual mode is selected. It is flickering when ATS is transferred by manual selectswitch.

    Auto It shows the auto mode is selected. It is flickering when it is automatically transferred after time

    setting value.

    ATS position It shows that ATS is located on the emergency power position if this lamp is on.

    Power Emergency power indication lamp

    Timer lamp It is flickering when the transfer (from normal to emergency) is completed after the time setting

    value.

    Timer On auto mode, Timer is used to set the transfer time from the normal power to the emergency

    power, up to 30 seconds, when the normal power is off.

    Manual select Manual select switch is used to transfer AST to the emergency power on manual mode.

    Auto/ Manual Auto/ Manual switch is used to select Auto mode or Manual mode.

    ATSAut o Transfer Sw itch

    A1, A2: Normal power

    B1, B2: Emergency power

    Aa, Ba: Auxiliary contact

    DAERYUK Co., Ltd. 2

  • 8/12/2019 ATS Daco Korea

    3/12

    ATSAut o Transfer Sw itch

    M-Type: Specification and inner circuit

    Features

    1. Compact size enables to reduce the size

    of control panel.

    2. One-coil, one-moving contact, one-arc

    chamber

    >> Easy maintenance

    3. First-input After-trip system enables to

    protect the main contac t.

    Specification

    DR

    64/66

    DR

    68

    DR

    610

    DR

    612

    DR

    616

    DR

    620

    DR

    625

    DR

    632

    DR

    640

    Rated voltage AC 690V and DC 125V

    Rated current 400 600 800 1000 1200 1600 2000 2500 3200 4000

    Connection (Back)

    Number of poles 3P 4P 3P 4P 3P 4P 3P 4P 3P 4P 3P 4P 3P 4P 3P 4P 3P 4P

    Weight(kg) 36 41 38 50 44 52 47 57 55 68 63 73 87 105 96 120 170 210

    Opening time 0.09 sec

    Change-over Time 0.12 sec

    AC 110V 10 10 10 12 16 20 20 20 24 24 36 40 60 60 80 80 80 80

    AC 220V 5 5 5 6 8 10 10 10 12 18 20 30 30 30 40 40 40 40Operating

    currentDC 110V 10 10 10 12 16 20 20 20 24 24 36 40 60 60 80 80 80 80

    Inner circuit Index

    A1-A2: Power Terminal

    B1-B2: Power Terminal

    P: DC Power Terminal

    N: DC Power Terminal

    C1-C2: Input signal

    D : Rec tifier

    Xb: Input-control swtich

    Aux: Auxiliary switch

    Aa : Contac t of A

    power input

    Ba: Contact of B power

    input

    DAERYUK Co., Ltd. 3

  • 8/12/2019 ATS Daco Korea

    4/12

    ATSAut o Transfer Sw itch

    External control circuit (AC, DC)

    - Control Power AC Index

    A1-A2: Power Terminal

    B1-B2: Power Terminal

    C1-C2: Input signal

    Note : Please refer to this drawing when you configure the circuit for the stable operation.

    - Control Power DC Index

    27T: Relay for 27X

    operation signal

    delay.

    27X: Relay for A power

    operation.84T: Relay for 84X

    operation signal

    delay.

    84X: Relay for B power

    operation.

    C/S: Manual select switch

    Auto/Manu: Auto/

    Manual select switch

    P, N: Power control terminal C1: Operation signal terminal for A-power C2: Operation signal terminal for B-Power

    Note) Please refer to this drawing when you configure the circuit for the stable operation.

    Caution1. Please use thickness of power cable more than 2mm up to ATS 2500A

    3.5mm from ATS 2500A.

    And, use the cable on the power terminal for DC control power.

    2. In manual operation, please select the manual mode first and use the manual operation handle.

    DAERYUK Co., Ltd. 4

  • 8/12/2019 ATS Daco Korea

    5/12

    ATSAut o Transfer Sw itch

    Parts & Dimensions

    Type 64M 66M 68M 610M 612M 616M 620M 625M

    X1 465 510 540 620 695 760

    X2 425 470 500 580 655 720X3 235 242.5 250 257.5 270 284

    Y1 260 270

    Y2 220 230

    Y3 74.5 73.5 78

    H 260

    T 15 20 25

    P 75 90 100 130 155 175

    mm

    Type Wa Wb Wc Wn L T Y

    64M 30 10 75 11

    66M 30 10 75 11

    68M 40 10 75 11

    610M 45 12 75 13

    612M 55 12 75 13

    616M 75 40 12 75 13

    620M 100 53 12 75 13

    625M 120 40 15 75 14

    - 3P 64M ~ 625M

    - Dimensions

    Unit: mm

    Control circuit terminal

    Insert hall for Manual

    handle

    A power indication

    B power indication

    Aux switch

    Input terminal of A power

    Output terminal of load

    Input terminal of B power

    - Bus bar

    DAERYUK Co., Ltd. 5

  • 8/12/2019 ATS Daco Korea

    6/12

    ATSAut o Transfer Sw itch

    Type 64M 66M 68M 610M 612M 616M 620M 625M

    X1 540 585 620 705 785 860

    X2 500 545 580 665 745 820

    X3 235 242.5 250 257.5 270 284

    Y1 260 270Y2 220 230

    Y3 74.5 73.5 78

    H 260

    T 15 20 25

    P1 75 90 100 130 155 175

    P2 75 82 87 102 117 132

    Type Wa Wb Wc Wn L T Y

    64M 30 30 10 75 11

    66M 30 30 10 75 11

    68M 40 30 10 75 11

    610M 45 30 12 75 13

    612M 55 30 12 75 13

    616M 75 40 40 12 75 13

    620M 100 45 53 12 75 13

    625M 120 55 40 15 75 14

    - 4P 64M ~ 625M

    Unit: mm

    Control circuit terminal

    Insert hall for Manual

    handle

    A power indication

    B power indication

    Aux switch

    Input terminal of A power

    Output terminal of load

    Input terminal of B power

    - 4P 64M ~ 625M: DimensionUnit: mm

    - Bus barUnit: mm

    DAERYUK Co., Ltd. 6

  • 8/12/2019 ATS Daco Korea

    7/12

    ATSAut o Transfer Sw itch

    - 3P 632M

    Unit: mm

    - 4P 632M

    Unit: mm

    DAERYUK Co., Ltd. 7

  • 8/12/2019 ATS Daco Korea

    8/12

    ATSAut o Transfer Sw itch

    - 3P 640M

    Unit: mm

    - 4P 640M

    Unit: mm

    DAERYUK Co., Ltd. 8

  • 8/12/2019 ATS Daco Korea

    9/12

    ATSAut o Transfer Sw itch

    T-Type: Specification and inner circuit

    DR 61T DR 62T DR 64T

    Rated vol tage AC 690V and DC 125V

    Rated current 100 200 400

    Connection Front, Back

    Number of poles 2P 3P 4P 2P 3P 4P 2P 3P 4P

    Weight(kg) 5 6 7.5 6 8 10 11 14 17

    Opening time 0.06 sec

    Change-over Time 0.08 sec

    AC 110V/ 220V 16

    AC 220V/ 220V 8

    Operati

    ng

    currentDC 110V 16

    Features

    1. The protection function of wrong

    operation.

    - designed to move the center of control

    part automatically.

    2. Excellent open-close performance.

    - minimizes the arc generation.

    - Increases the life cycle.3. Easy use and maintenance

    4. Compact and light design

    - Easy to maintenance and installation.

    Specification

    DAERYUK Co., Ltd. 9

  • 8/12/2019 ATS Daco Korea

    10/12

    ATSAut o Transfer Sw itch

    External control circuit (AC, DC)

    X1 X2

    2P 3P 4P 2P 3P 4P

    X3 X4 X5 Y1 Y2 Y3 Y4 Y5 W1 W1-T W2 W2-T 1 2

    DR 61T

    DR 62T

    250 290 330 230 270 310 160 40 40 250 305 330 20 5 5

    DR 64T 270 320 360 250 300 340 165 50 45

    220 185

    260 315 340 30 7

    20 5

    7

    9

    - Inner circuit

    - Index

    Control c ircuit terminal

    Insert hall for Manual handle

    A power indication

    B power indication

    Aux switch

    Input terminal of A power

    Output terminal of load

    Input terminal of B power

    - Dimensions

    A power indication B power indication

    Insert hall for manual handle

    Control terminal Input terminal of A power

    Input terminal of B power Load terminal(output)

    DAERYUK Co., Ltd. 10

  • 8/12/2019 ATS Daco Korea

    11/12

    ATSAut o Transfer Sw itch

    - Control power: AC

    - Control power: DC

    - Index A2: Control terminal of A power A1: Operation signal terminal of A power

    B2: Control terminal of B power B1: Operation signal terminal of B power

    27T: Relay for 27X operation signal delay 27X: Relay for A power operation

    84T: Relay for 84X operation signal delay 84X: Relay for B power operation

    C S: Manual select switch Auto Manu: Auto Manual select switch

    DAERYUK Co., Ltd. 11

  • 8/12/2019 ATS Daco Korea

    12/12

    DAERYUK Co., Ltd. 12

    ATSAut o Transfer Sw itch

    M MO

    Head Office:

    #530 Samkye-Ri, Phokog-Eup, Cheoin-Gu, Yongin-City, Gyeonggi-Do, Korea

    Tel: + 82-31-334-3371 Fax: +82-31-334-3374

    Sales Office:

    #430-4 Ohsung Bldg. 1F, Bangae2-Dong Seocho-Ku Seoul, Korea

    Tel: +82-2-588-7154 Fax: +82-2-588-7159

    Website: www.e-daco.net