Measuring and monitoring 01
VAMP 96 and VAMP 260 Measuring and monitoring units
CUSTOMER BENEFITS
• �Intelligent�measuring�and�monitoring�unitsThe VAMP meters come with an extensive selection of pre-configured data screens and measurements that you can use or customize to fit your metering requirements.
• �Demand�and�Power�Factor�ControlAvoid penalties with automated load shedding, scheduling, peak shaving or capacitor bank control.
• �Equipment�Monitoring�and�ControlImprove process yields and extend equipment life. Extensive analog and digital I/O enables system monitoring and control.
• �Power�quality�and�Disturbance�AnalysisCapturing abnormal disturbances in power quality like harmonics, voltage interruptions, voltage sags/swells and unbalancing.
• �Preventative�MaintenanceSet up alarms to warn of pending problems in advance.
• �Extensive�communication�and�SCADA�connectivityIEC 61850, IEC 60870-5-101, IEC 60870-5-103, Modbus TCP, Profibus DP, DNP3.0, DNP TCP, SPA, MBus (VAMP 96).
VAMP 96 and VAMP 260 metering devices are designed for remote or stand- alone monitoring of industrial and utility applications where energy consumption and billing shall be monitored by cost centers or individual feeder. Demand and power factor control, equipment monitoring, alarms for preventive maintenance and disturbance capturing are standard features in VAMP 96 and VAMP 260.
As a member of VAMP protection relay family these meters come with an extensive communication capabilities.
Measuring and monitoring VAMP 96, VAMP 260 02
VAMP 96 VAMP 260Operational segment Industrial and
utility substations Industrial and
utility substations
Application Power, energy, power quality metering,
event handling andI/O unit for SCADA and
process automation
Power, energy, power quality metering,
event handling,control, alarming,
temperature monitoring and
I/O unit for SCADA andprocess automation
CT and VT input connection
Metering core Metering or protection core
Auxiliary supply range 100 – 240 V ac100 – 330 V dc
or20 – 67 V dc
18 – 36 V dcor
40 – 265 V dc / ac
Number of digital inputs 3 6
Number of RTD inputs - Optionally 4 - 16
Number of heavy trip contacts - 2
Number of alarm contacts - 3 +1
Number of mA outputs - 4
Number of solid state outputs 1 pc NO
A RIGHT PRODUCT FOR EVERY APPLICATION
Product overviewVAMP 96 MEASURING AND MONITORING UNIT
The VAMP 96 is a modern basic multimeter used as a stand alone meter in industrial low and medium voltage power distribution distribution panels. This meter can be connected to SCADA or energy management system in order to provide required measurements, alarms, condition data, events to the opera-tor using various communication protocols. VAMP 96 shall be connected to measurement core of the current and voltage transformers Typical application of VAMP 96 is to measure energy by production cost centers and to show energy savings.
VAMP 260 POWER MONITORING UNIT
The VAMP 260 is designed for a heavy duty industrial applications where the environmental and disturbance conditions are demanding. This power monitor-ing unit can be connected to the protection cores of the current and voltage transformers as the design of the unit is equal to the requirements used in protection relays. Having six digital inputs, two circuit breaker controlling, four alarming duty contacts and four analogue ( mA ) outputs this unit is unique in the market.
Quick selection table
A VAMP 260 is a unique high accurate meter as it can be connected to either protection or measurement core of the current transformers.
VAMP 96 is a basic multimeter used either stand-alone or part of monitoring / SCADA system
Measuring and monitoring VAMP 96, VAMP 260
VAMP 96 VAMP 260Operational segment Industrial and
utility substations Industrial and
utility substations
Application Power, energy, power quality metering,
event handling andI/O unit for SCADA and
process automation
Power, energy, power quality metering,
event handling,control, alarming,
temperature monitoring and
I/O unit for SCADA andprocess automation
CT and VT input connection
Metering core Metering or protection core
Auxiliary supply range 100 – 240 V ac100 – 330 V dc
or20 – 67 V dc
18 – 36 V dcor
40 – 265 V dc / ac
Number of digital inputs 3 6
Number of RTD inputs - Optionally 4 - 16
Number of heavy trip contacts - 2
Number of alarm contacts - 3 +1
Number of mA outputs - 4
Number of solid state outputs 1 pc NO
03
Communication
As VAMP 96 and VAMP 260 are members of VAMP protection relay family the meters benefit of the communication protocols widely used in other VAMP devices. The metering and control devices are often interfaced with Profibus DP, MODBUS TCP, Modbus RTU or SPA communication in industrial applications. Utilities request IEC 61850 , IEC 60870-5-101, IEC 60870-5-103, DNP 3.0 and SPA protocols.
In addition to this, the VAMP 96 has a MBus protocol in order to support connectivity with the Automatic Meter Management (AMM) systems.
VAMPSET setting and configuration tool
VARIOUS COMMUNICATION ALTERNATIVES TO OUR DEMAND
VAMPSET is a user-friendly, free-of-charge relay management software for setting parameters and configuring VAMP relays. Via the VAMPSET software, relay parameters, configurations and recorded data can be exchanged between PC and VAMP relays. Supporting the COMTRADE format, VAMPSET also incorporates tools for analysing relay events, waveforms and trends from data recorded by the relays, e.g. during a network fault situation.
Using a standard serial cable the PC running VAMPSET connects to the front port of the VAMP relays. The VAMPSET software also supports TCP/IP communication via an optional port. Featuring true multi-language support the software runs on Windows 7 / Vista / XP / 2000 / NT and Windows 98 / 95 without any need for configuration of the PC.
VAMP relays support standard COMTRADE type disturbance recording files which can be uploaded/downloaded for evaluation of any network event recorded.
The phase sequences for currents and voltages can be read on-line from the clear and explicit phasor diagram screen for easy commissioning of the relay .
Measuring and monitoring VAMP 96, VAMP 260 04
Functionality t
VAM
P 96
VAM
P 26
0
Symbol Function
Mea
sure
men
t and
mon
itorin
g fu
nctio
ns
IL1,IL2, IL3 Current, 10...30 min demandI1 Positive sequence currentI2 Negative sequence currentILav Average demand current, min, maxIo Neutral currentU12rms,U23rms,U31rms Phase to phase RMS voltage, min, maxUL1,UL2,UL3 Phase to ground voltageUL1rms,UL2rms,UL3rms Phase to ground RMS voltage, min, maxPhasors Phasor diagram of IL1, IL2, IL3, UL1, UL2, UL3, U12, U23, U31, Uo, IoU1 Positive sequence voltageU2 Negative sequence voltageU2/U1 Relative voltage unbalanceUo Residual voltageP, Pda, PL1, PL2, PL3 Active fundamental power, 10...30min demand, per phasePrms Active RMS power, 10...30min demandPrms Active RMS power, total, min, max, 10...30min demandQ, Qda, QL1, QL2, QL3 Reactive fundamental power, 15 min demand, per phaseQrms Reactive RMS power, 10...30min demandQrms Reactive RMS power, total, min, max, 10...30min demandS, Sda, SL1, SL2, SL3 Apparent fundamental power, 10...30min demand, per phaseSrms Apparent RMS power, total, min, max, 15 min demandPF, PFda, PFL1, PFL2, PFL3 Power factor, per phase
PQ-diagramCos Cosine phiiTan Tan phiiF, fda System frequency, 10...30 min demandE+, E- Active energy, imported / exportedEq+, Eq- Reactive energy, imported / exported
Energy doseNumber of energy pulse outputs 1 4
Pow
er q
ualit
yLo
ggin
g, m
athe
mat
ical
func
tions
THD of IL1,IL2,IL3 Total harmonic distortion of phase currentsH of IL1,IL2,IL3 Harmonics of phase currents up to 15thTHD of U Total harmonic distortion of phase to phase or phase to ground voltagesH of U Harmonics of phase to phase or phase to ground voltages up to 15th
Sag and swellVoltage interruptions
Rh Running hour counterAlarm channels 8 8
>, < ComparisonUser’s logic AND, AND+OR, CT, INVAND, INVOR, OR, OR+AND, RS, RS_D, XOR, delays
Number of day / week timers 4 4
Com
mun
icat
ion
EC 60870-5-101IEC 60870-5-103IEC 61850 Modbus RTU / TCPProfibus DPSPADNP 3.0 / DNP TCP Modbus RTU slave
Har
dwar
e
Number of phase current CT inputs, protection core 3Number of phase current CT inputs, measurement core 3Number of residual current CT inputs, measurement coreNumber of voltage inputs 3 3Number of digital inputs 3 6Number of heavy duty trip outputs 2Number of alarm outputs 1 3+1Number of mA outputs 4Number of RTD inputsNumber of optional RTD inputs 4-16
Measuring and monitoring VAMP 96, VAMP 260 05
Connection diagrams
VAMP 260 VAMP 260
X1
1
23
45
6
X111
1213
1415
16
X2
12
34
56
789
AO1
AO2
AO3
AO4
L1
L2
L3
P2
P1
VAMP 260
VAMP 260 is connected to line voltages in a 400 V network
VAMP 260 is connected to phase voltages in a 400 V network
VAMP 260 VAMP 260
X1
1
23
45
6
X111
1213
1415
16
X2
12
34
56
789
AO1
AO2
AO3
AO4
L1
L2
L3
P2
P1
VAMP 260
VAMP 260 is connected to line voltages in a 400 V network
VAMP 260 is connected to phase voltages in a 400 V network
Energypulse outputDI
X2B:8 +12V
X2B:4 DI2
X2B:5 DI3
X2B:3 DI1
IL3X1:5
X1:6
IL1
IL2
X1:1
X1:2
X1:3
X1:4
X3
X4
Local
Remote
X2A:7
X2A:8
Relay out
V A Hz
VA W var
P.F cosfii tanfii
Wh varh THD
U&I harmonics
L1 L2 L3N
10/0.4kV
10kV
~
X2A:5
X2A:3
X2A:4
X2A:2 N
U1
U2
U3
X2B:1Uaux
X2B:2
R
VAMP96_LVCON_2
Generaldigital inputs
Measurement functions
VAMP 96
VAMP 260CONNECTION DIAGRAM
VAMP 96 CONNECTION DIAGRAM
Measuring and monitoring VAMP 96, VAMP 260 06
OK
Power
Error
Com
Alarm
TripABC
VAMP 255
1.0-100.04 - 0.39
1937.60
1395.47
24
5
PANEL MOUNTING VAMP 200 SERIES
3
SEMI-FLUSH VAMP 200 SERIES
41
1.0 -100.04 - 0.39
271.06
1817.13
281.10
B A
210.83
>
2a2b
1375.39
Panel mountingSemi-flush
mmin
2088.19
1556.10
1907.48
200.79
Raising frame B Fixing bracket
VYX076 40 mm /1.57″ 169 mm/ 6.65″ Standard for 200 series
VYX077 60 mm /2.36″ 149 mm/ 5.87″ Standard for 200 series
VYX233 100 mm / 3.94″ 109 mm/4.29″ 2 x VYX199 needed
A
OK
Power
Error
Com
Alarm
TripABC
OK
Power
Error
Com
Alarm
TripABC
OKOK
VAMP 255
Power
ErrorCom
Alarm
TripABC
VAMP 255
VAMP 255
Dimensional drawings
VAMP 260 PANEL MOUNTING
Measuring and monitoring VAMP 96, VAMP 260 07
1
ALARM POWER
3 4mmin
1
107,04.21
96,03.78
96,03.78
90,03.54
150,55.93
123,54.86
18,00.71
9,00.35
96,03.78
1 2 3 4 5
X36 7 8 9
X2A1 2 3 4 5 6 7 8 9
1 2 3 4 5 6X1
X2B1 2 3 4 5 6 7 8 9
VY091
90,03.54
107,04.21
96,03.78
88,03.46
mmin
2
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9X2A
1 2 3 4 5 6X1
X36 7 8 9
1 2 3 4 5
3b
3a
1.0-10mm0.04-0.39
151,36.0
91,03.58
89,03.50
ALARM POWER
VAMP 96Measuring and Monitoring Unit
EC
ø4,50.18
> 200.79
5
171,36.74
151,36.0
60,02.36
1234.84
VY2
80A
EC
ALARM POWER
VY2
80A
EC
C E
VY10C
ALARM POWER
EC
ALARM POWER
VY2
80A
EC
ALARM POWER
VY2
80A
EC
ALARM POWER
VY2
80A
EC
mmin
1,0-10mm0.04-0.39
89,03.50
91,03,58
21
3 4
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9X2A
1 2 3 4 5 6X1
X36 7 8 9
1 2 3 4 54a
4a
4b
4b
4b
> 20
0.79
5
mmin
107,04.21
96,03.78
96,03.78
90,03.54
150,55.93
123,54.8618,0
0.71
9,00.35
96,03.78
1 2 3 4 5
X36 7 8 9
X2A1 2 3 4 5 6 7 8 9
1 2 3 4 5 6X1
X2B1 2 3 4 5 6 7 8 9
VY091
90,03.54
107,04.21
96,03.78
88,03.46
mmin
ALARM POWER
VY2
80A
EC
ALARM POWERALARM POWER
VY2
80A
EC
ALARM POWER
VY2
80A
EC
ALARM POWER
VY2
80A
EC
ALARM POWER
VY2
80A
EC
C E
VY10C
ALARM POWER
EC
1
VAMP 96 PANEL MOUNTING
SEMI-FLUSH MOUNTING
Measuring and monitoring VAMP 96, VAMP 260 08
Typical applications
VAMP 260 power monitoring unit
applied for monitoring of power
and energy at industrial power
distribution. Energy pulses drive
Energy Management System
whereas the alarms and load
information goes via the serial
communication to the Control
Center. The mA outputs control
analogue meters of the switchgear.
VAMP 260
VAMP 96 is a basic metering and control device used for measuring power and
energy of production cost centers in industrial applications. The same meter can
be used by the utilities for detecting consumed energy per feeder.
VAMP 96
Serial communicationEnergy pulses
EnergyManagement System
RemoteControl Center
VAMP 260
VAMP 260
U
I Vamp96
U
I
110/10kV
10kV
Vamp96
Modbus, Profibus DP, TCP/IP
VAMP 96 VAMP 96
EnergyManagement System
3
3
3
3
10/0.4kV 10/0.4kV
Measuring and monitoring VAMP 96, VAMP 260 9
Order Codes
V 260 -
Nominal current [A] 1 = 1 A 5 = 5 ANominal Voltage [V] C = 100.. 240 VFrequency [Hz]7 = Standard relay Supply voltage [V] A = 40.. 265 Vac/dc B = 18.. 36 VdcOptional hardware (communication port 1) A = None B = Plastic/Plastic serial fibre interfaceC = Profibus interface D = RS 485 interface (4-wire)E = Glass/Glass serial fibre interfaceF = Rx Plastic/Tx Glass serial fibre interface G = Rx Glass/Tx Plastic serial fibre interfaceH = RJ-45 10Mbps ethernet interface M = RJ-45 10Mbps ethernet inc. IEC 61850O = LC 100 Mbps ethernet fibre interface inc. IEC 61850P = RJ-45 100Mbps ethernet interface inc. IEC 61850R = 2 x LC 100 Mbps ethernet fibre interface inc. IEC 61850S = 2 x RJ-45 100 Mbps ethernet interface inc. IEC 61850Analog Outputs & firmware E = None, standard firmwareF = 4 pcs, standard firmware
V 96 1 C 7 A
Accessories
V
AMP
96
VAM
P 26
0
Order code Description Note
VEA 3 CGi External Ethernet Interface Module
VPA 3 CG Profibus Interface Module
VSE001PP Fiber optic Interface Module
VSE002 RS485 Interface Module
VSE003 RS485 Interface Module, Ext I/O interface
VSE004 RS485 Interface Module, Ext I/O interface
VSE009 External DeviceNet interface module
VIO 12 AB RTD Module, 12pcs RTD inputs, RS 485 Communication (24-230 Vac/dc)
VIO 12 AC RTD/mA Module, 12pcs RTD inputs, PTC, mA inputs/outputs, RS232, RS485 and Optical Tx/Rx Communication (24 Vdc)
VIO 12 AD RTD/mA Module, 12pcs RTD inputs, PTC, mA inputs/outputs, RS232, RS485 and Optical Tx/Rx Communication (48-230 Vac/dc)
VX003-3 RS232 programming cable (Vampset, VEA 3CGi) Cable length 3 m
VX028-3 Interface cable to VPA 3 CG (Profibus module) Cable length 3 m
VX032-3 Back panel programming cable Cable length 3 m
VX030-3 Interface cable to VEA 3 CGi (Ethernet module) Cable length 3 m
VX004-M3 TTL/RS232 converter cable (PLC, VEA 3CGi) Cable length 3 m
VX007-F3 TTL/RS232 converter cable (VPA 3CG) Cable length 3 m
VAM 16D External LED module Disables rear local communication
VYX076 Raising Frame for 200-serie Height 40 mm
VYX077 Raising Frame for 200-serie Height 60 mm
VYX233 Raising Frame for 200-serie Height 100 mm
V200WAF V200 wall assembly frame
VYX420 Raising frame for Vamp 96 and Wimo6CP10
VAM
P 26
0
VAMP 260VAMP 96
Nominal current [A] 1 = 1 A / 5 ANominal Voltage [V] C = 100.. 240 VFrequency [Hz]7 = 50/60 Hz Supply voltage [V] A = 100.. 240 Vac/dc B = 18 .. 75 VdcG = 9 .. 36 VdcOptional hardware A = None O = LC 100 Mbps ethernet fiber inter- face inc. IEC 61850 and M-busP = RJ-45 100 Mbps ethernet interface inc. IEC 61850 and M-busOptional hardware A = Version 6 firmware * B = Standard firmware
* Only optional hardware, A available
Measuring and monitoring VAMP 96, VAMP 260 10
Technical data, tests and environmental conditions
Measuring circuitry VAMP 96 VAMP 260
Rated current In 1 A or 5 A 1 A or 5 A
- Current measuring range 1 x In 0 - 5 x In
- Thermal withstand 1,2 x In (continuously) 4 x In (continuously)20 x In (for 10 s)100 x In (for 1 s)
- Burden < 0.1 VA (In = 1 A)< 0.2 VA (In = 5 A)
< 0.1 VA (In = 1 A)< 0.2 VA (In = 5 A)
Rated voltage Un 0 – 264 V 50 - 240 V (configurable)
- Voltage measuring range 90 – 264 V 0 – 265 V
- Continuous voltage withstand 264 V 275 V
- Burden < 0.5V A < 0.5V A
Rated frequency fn 45 – 65 Hz 45 – 65 Hz
- Frequency measuring range 16 – 75 Hz 16 – 75 Hz
Terminal Block:- Solid or stranded wire
Max. wire dimension: 2,5 mm2 (13-14 AWG) Max. wire dimension: 4 mm2 (10-12 AWG)
Auxiliary voltage
Rated voltage UauxType A (standard) Type B (option) Type A (standard) Type B (option)
100 – 240 V ac/dc24 V dc100 - 330 V dc
20 – 67 V dc110/120/220/240 V ac/dc
40 - 265 V ac/dc 24 V dc48/60/110/125/220 V dc
18 - 36 V dc 100 - 330 V dc
Power consumption 5 W (normal conditions) < 7 W (normal conditions)< 15 W (output relays activated)
Max. permitted interruption time < 50 ms (110 V dc)
Terminal Block:- Phoenix MVSTBW or equivalent Max. wire dimension: 2.5 mm2 (13-14 AWG) Max. wire dimension: 2.5 mm2 (13-14 AWG)
Digital inputs
Number of inputs 3 6
Operation time 0.00 – 60.00 s (step 0.01 s) 0.00 – 60.00 s (step 0.01 s)
Polarity NO (normal open) or NC (normal closed) NO (normal open) or NC (normal closed)
Inaccuracy:- Operate time +/- 1 % +/- 1 %
Internal operating voltage 12 V dc 48 V dc
Current drain when active (max.) Approx. 5mA Approx. 20 mA
Current drain, average value < 1 mA
Terminal block:- Phoenix MVSTBW or equivalent Max. wire dimension: 2.5 mm2 (13-14 AWG) Max. wire dimension: 2.5 mm2 (13-14 AWG)
Trip contacts
Number of contacts - 2 making contacts
Rated voltage - 250 V ac/dc
Continuous carry - 5 A
Max. making current - 15 A
Breaking capacity, AC - 2 000 VA
Breaking capacity, DC (L/R=40ms) - 50 W
Contact material - AgNi 90/10
Terminal Block:- Phoenix MVSTBW or equivalent
-Max. wire dimension: 2.5 mm2 (13-14 AWG)
Accuracy
Current +/- 0.4 % of value when I > 0.5 x In +/- 0.3 % of In
Voltage +/- 0.5 % of value +/- 0.5 %
Frequency: +/- 10 mHz +/- 10 mHz
Active power +/- 1 % of value +/- 1 % of value
Reactive power +/- 1 % of value +/- 1 % of value
Active energy +/- 1 % of value +/- 1 % of value
Reactive energy +/- 1 % of value +/- 1 % of value
Measuring and monitoring VAMP 96, VAMP 260 11
Alarm contacts VAMP 96 VAMP 260Number of contacts 1 normally open
1 change-over contact (IF relay)3 change-over contacts (relays A1, A2 and A3)x
Rated voltage 48 V ac/dc 250 V ac/dc
Max. make current 120 mA 15 A
Continuous carry 3 A 5 A
Breaking capacity, AC - 2 000 VA
Contact material - AgNi 0.15 goldplated
Terminal Block:- Phoenix MVSTBW or equivalent
Max. wire dimension: 2.5 mm2 (13-14 AWG) Max. wire dimension: 2.5 mm2 (13-14 AWG)
Local serial communication portNumber of ports 1 on front and 1 shared with remote on rear panel 1 on front and 1 on rear panel
Electrical connection RS 232 RS 232
Data transfer rate 9 600 - 38 400 kb/s 9 600 - 38 400 kb/s
Remote control connectionNumber of ports 1 shared with local port on rear panel 1 on rear panel
Electrical connection RS 232 (standard)TTL RS 485 (with external module)Plastic fibre connection (with ext. module)
TTL (standard)RS 485 (option)RS 232 (option)Plastic fibre connection (option)
Data transfer rate 9 600 kb/s 9 600 kb/s
Protocols ModBus‚ RTU masterModBus / TCPSpaBus, slaveIEC 61850IEC 60870-5-101IEC 60870-5-103Profibus DP (option)MBusDNP or Ethernet
ModBus‚ RTU masterModBus / TCPSpaBus, slaveIEC 61850IEC 60870-5-101IEC 60870-5-103Profibus DP (option)DNP or Ethernet
Analogue outputsNumber of Ports - 4 (Note: common +pole)
Electrical connection: - Current output
- Range - 0 – 20 mA (min & max configurable)
- Load - <800 W
- Accuracy - <±20mA
Isolation te9st voltage - 500 Vdc
Test voltagesInsulation test voltage(IEC 60255-5)
2 kV, 50 Hz, 1 min 2 kV, 50 Hz, 1 min
Surge voltage (IEC 60255-5) 5 kV, 1.2/50 ms, 0.5 J 5 kV, 1.2/50 ms, 0.5 J
Environmental conditionsOperating temperature -25 to +50 oC -10 to +55 oC
Operating temperature (display) 0 to +50 oC
Transport and storage temperature -10 to +60 oC -40 to +70 oC
Relative humidity < 75 % (1 year, average value) < 75% (1 year, average value)
< 90 % (30 days per year, no condensation permitted)
< 90% (30 days per year, no condensation permitted)
CasingDegree of protection (IEC 60529) IP20 IP20 / Flush mounted IP54
Dimensions (W x H x D) 96 x 96 x 151 mm 208 x 155 x 236 mm
Material Polyphenylene Oxide 1 mm steel plate
Weight 0.6 kg 4.2 kg
Color code RAL 7032 (Casing) / RAL 7035 (Back plate)
PackageDimensions (W x H x D) 180 x 100 x 101 mm 215 x 160 x 275 mm
Weight (relay, package and manual)
0.7 kg 5.2 kg
Measuring and monitoring VAMP 96, VAMP 260 12
DEVICE TRACK RECORD
• Schneider Electric’s VAMP Range specialises in protection protection relays, arc flash protection and measuring and monitoring units for power systems.
• VAMP’s medium-voltage and sub-transmission protection relays are used in numerous applications, from overhead line feeders and substations to power plants and industrial power system. Their unique integrated arc flash fault protection functionality enhances the safety of both people and property and has made VAMP a leading manufacturer in arc flash protection worldwide. All VAMP products meet the latest international standards and regulations.
• Our success is based on competitive standard products, constant development by our designers possessing experience from three protection relay generations, our long-term partnerships, flexibility and 24 h care of the customers.
01-2013 © 2
013
Sch
neid
er E
lect
ric In
dust
ries
SA
S -
All
right
s re
serv
ed
As standards, specifications and designs change from time to time, please ask for confirmation of the information given in this publication.
Design: Schneider Electric Industries SAS - WILMAPhotos: Schneider Electric Industries SAS Printed:
NRJED112388EN
This document has been printed on recycled paper.