RIDGE
HIP
VALLEY
RIDGE
GA
BLE
EAVE
EAVE
METERDISC.
COMBINER
DN
6/1
2
DN
6/1
2
20'-4"
61'-10"
20'
PZ
2=48
"
PZ2=48"
3'
PZ2=48"
PZ3
PZ3
PZ1
PZ1
1 STORY SINGLE FAMILY
RESIDENCE, W/ TILE ROOF
GARAGE
MAIN DISTRIBUTION PANEL
PZ3PZ2=48"
PZ2=48" 48"
PZ1
COMBINATION SERVICE ENTRANCE
RAIL
ATTACHMENT
PV MODULEATTACHMENT
RAILPV MODULE
13'-4"
24"
48" 24"
METERPV AC DISC.AC COMBINER
EXIST. ROOF SHEETING
EXIST. ROOF TRUSS
(2) LAG BOLT (RE NOTES)
TRUSS 24" C-C
EXIST.MEMBRANE
WATER PROOFING
PV MODULE PV MODULE
PV MODULE CLAMP
ROOF TILE
RAIL PROFILE
LAG BOLTS 48" C-C
RAIL
S-HOOK
BASE
MECHANICAL DESIGN
PROFESSIONAL ELECTRICAL
SERVICES, INC.
185 S. CHARLES RICHARD
BEALL BLVD.
DEBARY, FL 32713
386-668-4222 OFFICE
LICENSE #EC13001686
OWNER:
FELLER ALVIN
Siggi Brocks
c A d v i c e I n c
P H : 8 1 3 9 1 9 9 1 5 4
M A I L @ C A D V I C E . U S
N A B C E P
P V A - 0 9 2 6 1 6 - 0 1 5 6 9 1
REVISIONS:
DRAWN: SB
SHEET #: Jan. 16, 20
SITUS:
7799 NILE RIVER RD
WEST PALM BEACH FL 33411
PARCEL ID: 74-42-43-21-12-000-9860
EOR:
ALLEN GEZELMAN,
FL PE 59180
PH.813 909 1956
16502 Hanna Rd
Lutz, FL 33549
www.gezelmanpe.com
SCALE: 1" = 40'-0"
PARCEL - (PROPERTY APPRAISER) SITE PLAN
SCALE: 1/8" = 1'-0"
SOLAR ARRY - MODULE ROOF LAYOUT
SCALE: 1-1/2" = 1'-0"
ROOF ATTACHMENT DETAIL
INSTALLATION LOCATION
SCALE: NTS
SPIDER RAX ATTACHMENT ASSEMBLY
THIS “PAPER” PLAN IS INTENDED TO PROVIDE THE ESSENTIAL INFORMATION NEEDED BY AHJ
(AUTHORITY HAVING JURISDICTION) AND INSTALLERS.
PV CERTIFICATION: IN ACCORDANCE WITH FLORIDA HB 1021, ENGINEER OF RECORD FOR THIS
PLAN CERTIFIES THAT ALL ELECTRICAL & STRUCTURAL COMPONENTS & THE DESIGN OF THE
SYSTEM HEREIN SPECIFIED SATISFY ALL FLORIDA REQUIREMENTS APPLICABLE TO THIS PV
INSTALLATION.
SCOPE OF WORK: INSTALLATION OF A 5.25 KW LINE SIDE CONNECTED GRID INTERACTIVE
SOLAR PHOTOVOLTAIC ROOF TOP SYSTEM WITH SEPARATE MICROINVERTERS.
DESIGN CRITERIA: SINGLE FAMILY RESIDENCE, 1 STORY, TILE ROOF, SLOPE 6 12, BUILDING HGT
<25FT, ROOF TRUSS 2X4 @24" OC., EAVE HGT 10FT.
ASCE 7.10: VULT 166 / VASD129-MPH, RISK CATEGORY II, EXPOSURE CATEGORY B, PRESSURE
ZONE (PZ) 2 - WIDTH 4-FT.
WIND LOADS: WORSE CASE WIND FORCE UPLIFT: (PSF) PZ1 -23.8, PZ2 -44.9
MODULE: DIMS 40" X 66.93", AREA: 18.6 FT2 , WEIGHT: 40.79 LB
CENTER MODULE CONTRIBUTARY AREA/STANDOFF (@48" C-C)= 4FT X 5.58 FT/ 2=11.16 FT2
UPLIFT / STAND OFF @ -23.8 PSF (PZ1) = -265.6 LBF, NET UPLIFT/STANDOFF = 238 LBF
UPLIFT / STAND OFF @ -44.9 PSF (PZ2) = -501.1 LBF, NET UPLIFT/STANDOFF = 473 LBF
LIVE LOADS ROOF: FBC 2017 1607.12.5.1
TABLE 1607.1
• UNIFORM LR < 20 LB/SF
• CONCENTRATED < 300 LB
PV ARRAY
• PV LIVE LOAD = 2.5 LB/SF
• PV CONCENTRATED LOAD = 2.5 LB/FT2 X 11.16 FT2 = 27.90 LB/STANDOFF
RAIL & ATTACHMENT: "QUICK MOUNT PV " ETL LISTED UL STD 2703
• "Q-RAIL LIGHTRAIL" ALLOWABLE RAIL SPAN SHALL NOT EXCEED 50"
• "SPIDER RAX "BLACK WIDOW" MOUNTING SYSTEM TO BE ATTACHED WITH TWO 516" SS.
LAGBOLTS MIN 3" EMBEDMENT INTO RAFTER OR USING (8) 1-1/4"X10 WOOD SCREWS INTO
ROOF DECKING. "SPIDER RAX" ATTACHMENTS SHALL BE INSTALLED @ 48" C-C AND
STAGGERED ON RAFTERS WHERE POSSIBLE.
• CONTRACTOR SHALL PROVIDE WATERPROOFING PER OEM INSTRUCTIONS.
• NOTES: IF A CONFLICT SHOULD OCCUR BETWEEN A DRAWING AND/OR SPECIFICATION
HEREON AND AN OEM DETAIL, OEM SHALL PREVAIL.
1. SOLAR EQUIPMENT ADDS LESS THAN 2.5-PSF GRAVITY LOAD TO STRUCTURE.
2. MODULES SHALL BE INSTALLED PORTRAIT IN THE AREA SHOWN HERON.
3. MODULE GRAVITY & WIND LOADS SHALL BE TRANSMITTED TO STRUCTURAL FRAMING OF
ROOF USING QUICK MOUNT PV RAILING AND SPIDER RAX ATTACHMENT SYSTEM AS SHOWN IN
SPECIFICATION SHEETS IN THIS PLAN SET AND OEM INSTRUCTION TO THESE PRODUCTS.
4. EACH PV MODULE SHALL BE ATTACHED ON EACH SIDE BY MIN 2 PV MODULE CLAMPS.
5. ADJOINING MODULES SHALL SHARE PV MODULE CLAMPS.
6. THERE SHALL BE TWO QUICKMOUNT RAILS CROSSING EACH PV MODULE PERPENDICULAR.
7. CONTRACTOR SHALL LEAVE SUFFCIENT ROOF ACCESS IN ACCORDANCE WITH THE
REQUIREMENTS OF NFPA 1 SECTION 11
(AVAILABLE @ HTTP://GEZELMANPE.COM/REFERENCE/NFPA1.PDF)
8. CONTRACTOR SHALL PROVIDE AHJ WITH OTHER INFORMATION AS REQUIRED SUCH AS OEM -
MANUALS AND DATA SHEETS OF PRODUCTS USED IN THIS DESIGN.
9. CONTRACTER MAY FIELD ADJUST PANLEL LAYOUT AND POSITION DUE TO ON SITE
OBSTRUCTION OR AREA SHADING AS NEEDED AS LONG AS SUCH ADJUSTMENT DOES NOT
INVALIDATED OTHER ENGINEERING REQUIRMENTS DESCRIBED IN THIS DOCUMENT.
10.EOR(ENGINEER OF RECORD)IS AVAILABLE VIA EMAIL COMMUNICATIONS
11. EOR (ENGINEER OF RECORD) IS PERMITTED TO USE SIGNATURE STAMP TO SIGN DOCUMENTS.
FL BOARD OF ENGINEERS GRANTED WAIVER OR VARIANCE OF RULE 61G15-23.002(1), FAC. WAIVER IS
AVAILABLE @ HTTP://GEZELMANPE.COM/REFERENCE/FBPE_SIGNATURE_STAMP_OFFICIAL_APPROVAL.PDF
SCALE: NTS
SERVICE LOCATION
INSTALLATION LOCATION
PV AC DISC AND COMBINER
SPIDER RAX TILE HOOK
PV QUICKMOUNT
RAIL, RE SPEC SHEETS
PRE-INSTALLED
BUTYL SEAL
BASE PLATE ATTACHMENT
RE. NOTES
MECHANIOCAL SPECS
PROFESSIONAL ELECTRICAL
SERVICES, INC.
185 S. CHARLES RICHARD
BEALL BLVD.
DEBARY, FL 32713
386-668-4222 OFFICE
LICENSE #EC13001686
OWNER:
FELLER ALVIN
Siggi Brocks
c A d v i c e I n c
P H : 8 1 3 9 1 9 9 1 5 4
M A I L @ C A D V I C E . U S
N A B C E P
P V A - 0 9 2 6 1 6 - 0 1 5 6 9 1
REVISIONS:
DRAWN: SB
SHEET #: Jan. 9, 20
SITUS:
7799 NILE RIVER RD
WEST PALM BEACH FL 33411
PARCEL ID: 74-42-43-21-12-000-9860
EOR:
ALLEN GEZELMAN,
FL PE 59180
PH.813 909 1956
16502 Hanna Rd
Lutz, FL 33549
www.gezelmanpe.com
MECHANIOCAL SPECS
PROFESSIONAL ELECTRICAL
SERVICES, INC.
185 S. CHARLES RICHARD
BEALL BLVD.
DEBARY, FL 32713
386-668-4222 OFFICE
LICENSE #EC13001686
OWNER:
FELLER ALVIN
Siggi Brocks
c A d v i c e I n c
P H : 8 1 3 9 1 9 9 1 5 4
M A I L @ C A D V I C E . U S
N A B C E P
P V A - 0 9 2 6 1 6 - 0 1 5 6 9 1
REVISIONS:
DRAWN: SB
SHEET #: Jan. 9, 20
SITUS:
7799 NILE RIVER RD
WEST PALM BEACH FL 33411
PARCEL ID: 74-42-43-21-12-000-9860
EOR:
ALLEN GEZELMAN,
FL PE 59180
PH.813 909 1956
16502 Hanna Rd
Lutz, FL 33549
www.gezelmanpe.com
-+ --+ -
-+ --+ -
STRING A: X 4SOUTH
STRING B: X 11SOUTH
G
JB1L1L2L1L2L1L2
L2L1N
G
TRANSITION THRU ATTIC (OPTIONAL)
ON GRAGAE WALL ADJACENT TO METER
MAX 6'-0"
1 283
4
5
6
7
9
10
11
NOM SYS. VOLTAGE: 240VSTRING OUTPUT CIRCUIT (IQ7+ x11 )
MAX CONT.CURRENT:13.31 AMP
NOM. SYS. VOLTAGE: 240VCOMBINER OUTPUT CIRCUIT (IQ7+ x15)
MAX CONT.CURRENT:18.15 AMP
4
12
3 5
6
A
B
D
E
B
C
L2
COMBINER
LOAD CENTER
NG
ENVOY
L1
20A
20A
10A
MLO
B
E60A
150A
G
EX
IST
ING
G.E
.
N
C
SERVICE DISC.
SERVICE DISC.
ELECTRICAL DESIGN
□ COMPONENT SCHEDULE
1 SOLAR PHOTOVOLTAIC MODULE (15) LG 350W LG350Q1C-A FSEC# 400694 UL 1703 LISTED
2 MICROINVERTER (15) ENPHASE IQ7+ NEC 690.12RAPIDSHUTDOWN COMPLIANT
3 END CAP ENPHASE TERMINATION CAP INSTALLED ON END OF IQ CABLE
4 JUNCTION BOX - OPTIONAL 240 VAC,1ɸ, NEMA 3R INSTALL UNDER ARRAY
5 COBINER ENPHASE IQ COMBINER, 125A BBR, MLO,NEMA 3R (3) EATON BRK-20A-2P-240
6 COMMUNICATION GATEWAY ENPHASE ENVOY MANUF. PREINSTALLED
7 AC DISCONNECT, LOCKABLE 240V,MIN 60AMP,1ɸ,NEMA3R, NON FUSED MOUNTED WITHIN 6FT OF METER
8 PV MODULE MOUNTING CLAMP W/ INTEGRATED BONDING UL 2703 LISTED
9 EXIST. COMBINATION SERVICE ENTRANCE DEVICE 240V,1ɸ, 200A RATED, 150A MAIN BREAKER LOCATED AT GARAGE, SURFACE MOUNT
10 METER CAN - EXISTING LOCATED AT GARAGE REPLACE METER WITH BIDIRECTIONAL
11 POINT OF CONNECTION 240V,1ɸ, MIN 60 AMP RATED EXISTING SERVICE DISC. BREAKER CIRCUIT
○ WIRE SCHEDULE
1 PV SOURCE CIRCUIT MNFC. PROVIDED CABLE ASSEMBLIES WITH MC4 LOCKING CONNECTORS
2 ENPHASE Q CABLE L-L MANUFACTURER PROVIDED CABLE ASSEMBLY #12 AWG STRANDED
3 ARRAY OUTPUT CIRCUIT (4), #10 THWN-2 & #10 EGC IN 3 4" LIQUID TIGHT-PVC, EMT, EMC,LFMC,LFNC OR (2)10/2 ROMAX THRU ATTIC
4 GROUND ELECTRODE CONDUCTOR #6 CU GEC, EXPOSED RUN
5 COMBINER OUTPUT CIRCUIT (3) MIN. #8 THWN-2 & #10 EGC IN 3 4" LIQUID TIGHT-PVC, EMT, EMC,LFMC OR LFNC
6 PV AC SERVICE DISCONNECT (3) MIN. #6 THWN-2 IN 3 4" LIQUID TIGHT-PVC, EMT, EMC,LFMC OR LFNC
ELECTRICAL NOTES:
COMPLIANT WITH: 2017 FBC 6TH EDITION FLORIDA BUILDING CODE, 2014 NATIONAL ELECTRICAL CODE
1. ALL ASPECTS OF THE ELECTRICAL WORK REQUIRED TO COMPLETE THE PROJECT REPRESENTED IN THIS DOCUMENT SHALL
COMPLY WITH THE MANUFACTURER'S RECOMMENDATIONS/SPECIFICATIONS AND ALL CODES, STATUTES, AND STANDARDS
ADOPTED BY THE STATE AND THE LOCAL AUTHORITY HAVING JURISDICTION.
2. THE INFORMATION PROVIDED IN THESE DOCUMENTS IS NOT EXHAUSTIVE. IT REMAINS THE CONTRACTORS RESPONSIBILITY TO
ACHIEVE THE PROPOSED INSTALLATION IN FULL EXERCISE OF AND COMPLIANCE WITH THE ITEMS IDENTIFIED IN GENERAL
ELECTRICAL NOTE 1.
3. ALL SOLAR PV MODULES ARE "UNGROUNDED".
4. ALL UNIDENTIFIED CONDUCTORS UNDER MODULES ARE UL LISTED AND MANUFACTURER PROVIDED CABLES, CONNECTORS
AND ASSEMBLIES.
5. ALL ELECTRICAL COMPONENTS, (RACEWAYS, JUNCTION BOXES, DISCONNECTS, PANEL BOARDS, ETC.), SHALL BE INSTALLED
PLUMB, LEVEL, AND IN COMPLIANCE WITH ALL APPLICABLE SECTIONS OF NEC ARTICLE 110.
6. ALL RACEWAYS SHALL BE SUPPORTED ON INTERVALS AND BY METHODS AS APPROVED/REQUIRED BY THE CURRENTLY
ADOPTED NEC ED.
7. ALL PV SOURCE AND OUTPUT RACEWAYS AND CABLES SHALL BE LIMITED TO MAX. 10FT LENGTH EXPOSURE TO AND J-BOXES
SHALL BE LOCATED OUT OF DIRECT SUNLIGHT.
8. THERE SHALL BE NO MORE THAN 6 CURRENT CARRYING AC CONDUCTORS (CCC) IN ANY RACEWAY FOR THIS INSTALLATION.
9. SOLAR PANELS TO BE BONDED TO RACKING OR EACH OTHER, UTILIZING WEEB OR UL 2703 INTEGRATED GROUNDING
CLAMPING COMPONENTS.
10. RACKING/MOUNTING SYSTEM OF ARRAY TO HAVE CONTINUOUS BONDING. ARRAY GROUNDED WITH #6 GEC.
11. CONTRACTOR SHALL VERIFY THE INSTALLATION OF A BIDIRECTIONAL UTILITY SERVICE METER.
12. CONTRACTOR SHALL REFER TO SHEET PV10 FOR DETAILED SOLAR ARRAY LOCATION AND PLACEMENT.
13. THE CONTRACTOR SHALL SEAL ALL PENETRATIONS RESULTING FROM THIS SCOPE OF WORK.
14. ALL SIGNAGE SHALL BE PROVIDED AS SHOWN OR AS REQUIRED BY THE CURRENTLY ADOPTED NEC ED.
15. TIER 1 SYSTEM : 15 MODULES X 350W, TOTAL OF 5.25 KW DC
16. UTILITY GRID INTERCONNECTION TO BE MADE LOAD SIDE OF METER AT EXISTING MAIN SERVICE DISCONNECT IN EXISTING
SERVICE WIRING ENCLOSURE.
PROFESSIONAL ELECTRICAL
SERVICES, INC.
185 S. CHARLES RICHARD
BEALL BLVD.
DEBARY, FL 32713
386-668-4222 OFFICE
LICENSE #EC13001686
OWNER:
FELLER ALVIN
Siggi Brocks
c A d v i c e I n c
P H : 8 1 3 9 1 9 9 1 5 4
M A I L @ C A D V I C E . U S
N A B C E P
P V A - 0 9 2 6 1 6 - 0 1 5 6 9 1
REVISIONS:
DRAWN: SB
SHEET #: Jan. 9, 20
SITUS:
7799 NILE RIVER RD
WEST PALM BEACH FL 33411
PARCEL ID: 74-42-43-21-12-000-9860
EOR:
ALLEN GEZELMAN,
FL PE 59180
PH.813 909 1956
16502 Hanna Rd
Lutz, FL 33549
www.gezelmanpe.com
MICROINVERTER:
• MAX. SYSTEM VOLTAGE: 264V
• NOMINAL VOLTAGE: 240V
STRING OUTPUT CURRENT: (MAX. STRING = 13)
• I MAX = 1.21 AMP X 11 = 13.31 AMP
• AMPACITY RATING: 16.63 AMP
• OCPD = 20 AMP
POINT OF CONNECTION - SUPPLY SIDE IPC (705.12)
• COMBINER OUTPUT = 15X1.21A = 18.15 AMP
• TAPS = 18.15 AMP X1.25 = 22.68 AMP
• MIN. 60AMP SERVICE EQUIPMENT REQUIRED
PV SYSTEM SIGNAGE
A. PV SYSTEM DISCONNECT (NEC 690.13(B)
B. WARNING ELECTRIC SHOCK HAZARD
TERMINALS ON THE LINE AND LOAD SIDES
MAY BE ENERGIZED IN THE OPEN
POSITION (NEC 690.13(B)
C. RATED OUTPUT CURRENT18.15 AMPS
NORMAL OPERATING VOLTAGE 240 VOLT
(NEC 690.54)
D. PHOTOVOLTAIC SYSTEM EQUIPPED WITH
RAPID SHUTDOWN (NEC 690.56(C)
E. DUAL POWER SOURCE. SECOND SOURCE
IS A SOLAR PV SYSTEM (NEC 705.12(B)(3)
THE IQ 7+ MICRO HAVE INTEGRATED GROUND AND DOUBLE INSULATION, NO GEC OR EGC IS REQUIRED.
THE DC CIRCUIT IS ISOLATED AND INSULATED FROM GROUND AND MEETS THE REQUIREMENTS OF NEC
690.35.
CONTRACTOR MAY ADJUST ACTUAL
MICROINVERTER STRING LENGTH IN FIELD AS
REQUIRED. CONTRACTOR SHALL NOT EXEED THE
MAX. PERMISSABLE STRING LENGTH OF 13
MICROINVERTER PER IQ CABLE FOR THIS DESIGN.
ELECTRICAL SPECS
PROFESSIONAL ELECTRICAL
SERVICES, INC.
185 S. CHARLES RICHARD
BEALL BLVD.
DEBARY, FL 32713
386-668-4222 OFFICE
LICENSE #EC13001686
OWNER:
FELLER ALVIN
Siggi Brocks
c A d v i c e I n c
P H : 8 1 3 9 1 9 9 1 5 4
M A I L @ C A D V I C E . U S
N A B C E P
P V A - 0 9 2 6 1 6 - 0 1 5 6 9 1
REVISIONS:
DRAWN: SB
SHEET #: Jan. 9, 20
SITUS:
7799 NILE RIVER RD
WEST PALM BEACH FL 33411
PARCEL ID: 74-42-43-21-12-000-9860
EOR:
ALLEN GEZELMAN,
FL PE 59180
PH.813 909 1956
16502 Hanna Rd
Lutz, FL 33549
www.gezelmanpe.com