Thermozone AD Corinte
R
0,1 m
3,5 m
2,0 m
3,0 m
AD Corinte E/W
1,0 m
13,2 m/s
3,4 m/s
4,4 m/s
3,7 m/s
5,8 m/s
3,3 m/s
4,5 m/s
3,6 m/s
7,0 m/s
14,0 m/s
Peak*1 AMCA*2
2008-02-23
Thermozone® AD CorinteAir curtains for doors with heights of up to 3,5 metres
AD Corinte is intended for exclusive shop entrances and other environments with high demands in respect of design. Available in polished stainless steel as standard, can also be obtained in brushed or mirror-finished stainless steel.
AD Corinte includes new fan technology with radial fans which means further improvements in respect of sound level and performance.
Cold draughts and energy loss can be prevented whilst the AD Corinte contributes to the heating of the premises.
The availability of three lengths provides the opportunity to cover openings of different widths and heights.The air curtains can be installed vertically on either or both sides of the entrance, or a number of units can be mounted side by side over the doorway.
It is recommended that the units are supplied with a frequency inverter. Fan motors can be connected for 3x230V or 3x400V.
AD Corinte with water heat is equipped with a coarse filter to protect fans / water battery. Can also be equipped with a fine filter, class F5 (EU5) as an accessory.
AD Corinte with electrical heat may be equipped with an aluminium filter.
Air velocity profile
Vertical: 2,2 and 2,5 metresElectrical heat 15 – 22,5 kW
Water heat Horizontal: 1,7 and 2,2 metres
Ambient, no heat
• Fricofantechnologyusingradialfanswhichmeansfurther improvements in respect of sound level and performance.
• Producedinpolishedstainlesssteelasstandard,butalso available in brushed or mirror-polished stainless steel. Colour intake and outlet grille: black, RAL 9005
•ADCorinteisavailableforhorizontalorverticalmounting.
•TheADCorintehasanexclusivedesignthatsuitsshop entrances and office environments.
•AfinefilterF5(EU5)isavailableasanaccessoryforwater heated units.
• Forverticalmounting,electricityand/orwatermaybeconnected from above or below.
• OptimizedairflowwithThermozonetechnology.
*¹) Peak values.*²) Mean values according to AMCA 220-05 "Test methods for Air Curtain Units"
This product is sold and serviced by:
For contact details, see www.besam.com.
Thermozone AD Corinte
Design and specifications are subject to change without notice.
Technical specifications | Thermozone AD Corinte E with electrical heat 3
Type Output steps [kW]
Airflow [m3/h]
∆t*5
[°C]
Sound level*6 [dB(A)]
Output motor [W]
Voltage*3
motor [V]
Voltage inverter [V]
Amperage motor 400V3~/ 230V3~ [A]
Voltage [V] Amperage [A] heat
Length [mm]
Weight [kg]
ADCH17E*¹ 0/7,5/15 1400/3000 32/15 40/60 1100 230V3~/400V3~ 230V~ 1,7/2,8 400V3~/21,7 1700 85
ADCH22E 0/10/20 1800/4000 33/15 42/61 1665 230V3~/400V3~ 230V~ 2,5/4,3 400V3~/28,9 2200 110
ADCV22E*2 0/10/20 1800/4000 33/15 42/61 1665 230V3~/400V3~ 230V~ 2,5/4,3 400V3~/28,9 2200 110
ADCV25E 0/11,2/22,5 2050/4500 33/15 43/63 1930 230V3~/400V3~ 230V~ 2,9/5,0 400V3~/32,5 2450 125
Technical specifications | Thermozone AD Corinte WL with water heat, coil for low tempered water < 80/60 °C 2
Type Output*4 [kW]
Airflow [m3/h]
∆t*4,5
[°C]
Water volume [l]
Sound level*6 [dB(A)]
Output motor [W]
Voltage motor*3 [V]
Voltage inverter [V]
Amperage motor 400V3~/ 230V3~ [A]
Length mm]
Weight [kg]
ADCH17WL*¹ 33 1400/3000 42/32 2,8 39/59 1060 230V3~/400V3~ 230V~ 1,6/2,7 1700 85
ADCH22WL 46 1800/4000 43/33 3,6 42/60 1565 230V3~/400V3~ 230V~ 2,3/4,1 2200 110
ADCV22WL*² 46 1800/4000 43/33 3,6 42/60 1565 230V3~/400V3~ 230V~ 2,3/4,1 2200 110
ADCV25WL 52 2050/4500 43/34 4,0 42/61 1750 230V3~/400V3~ 230V~ 2,6/4,6 2450 125
Technical specifications | Thermozone AD Corinte A without heat 1
Type Output [kW]
Airflow [m3/h]
Sound level*6 [dB(A)]
Output motor [W]
Voltage*3 motor [V]
Voltage inverter [V]
Amperage motor 400V3~/230V3~ [A]
Length [mm]
Weight [kg]
ADCH17A*¹ 0 1400/3000 40/60 1100 230V3~/400V3~ 230V~ 1,7/2,8 1700 73
ADCH22A 0 1800/4000 42/61 1665 230V3~/400V3~ 230V~ 2,5/4,3 2200 95
ADCV22A*² 0 1800/4000 42/61 1665 230V3~/400V3~ 230V~ 2,5/4,3 2200 95
ADCV25A 0 2050/4500 43/63 1930 230V3~/400V3~ 230V~ 2,9/5,0 2450 108
*¹) For horizontal mounting (H= horizontal).*²) For vertical mounting (V= vertical).*3) Delivered connected for 230V3~. Convertible from 230V3~ to 400V3~.*4) Applicable at water temperature 80/60 °C, air temperature in + 15 °C.*5) ∆t= temperature rise of passing air at maximum heat output and lowest/highest airflow.*6) Conditions: Distance to the unit: 5 metres. Directional factor: 2. Equivalent absorption area: 200 m2.
ProtectionclassADCorinteA/E/W:IP20.CE compliant.
Thermozone AD Corinte
44 134
15
01
00
15045
44134
10
01
50
45150
40
25170
40140
25
40
40140
170
Dimensions
Upper part of the unit – seen from above
Bottom part of the unit – seen from above
Intake
Outlet
Opening
Connection hatchConnection hatch
Vertical
Thermozone AD Corinte
80
60
Extension hood
Connections from above Connections from below
Thermozone AD Corinte
1700/2200
1670/2170
180
3535
80
40
1
Ø12
Dimensions
Horizontal
Thermozone AD Corinte
Min 180 mm
75
376
Min 180 mm50
Positioning, mounting and installation
MountingAD Corinte can be mounted either vertically or horizontally.
Forhorizontalmounting,theunitmaybemountedon the wall or on the ceiling with the enclosed brackets. For suspended mounting from the ceiling, suitable devices (threaded bars, rails etc.) are fixed on the brackets.
A mounting edging is included with the vertically mountedunits.Theedgingisputonthefloorbeneaththeaircurtain.Theunitisanchoredtothefloorwithexpansion-shell bolts for instance.
WhenorderingADCorinteforverticalmountingitis necessary to specify on which side of the opening it should be positioned. It is recommended to specify if electricity and/or water connections should be made from above or below, but this can be altered on site.
WhenorderingADCorinteforhorizontalmounting,it is necessary to specify left or right connection (seen from inside the building).
The unit can be provided with an extension hood to cover the distance between unit and ceiling (max length 1000 mm).
Connection AD Corinte E 3ThermozoneADCorinteshouldbeequippedwithafrequency inverter (FC15A/FC15M) for variable fan speed regulation. The electrical connection may be done from above or below. The appliance should be preceded by a triple pole switch with at least 3 mm breaking gap. For units with electrical heating, power and control should be supplied separately.
For connection between inverter and motors a cable with braided, tinned copper mesh shield (type C4), with 85 % coverage should be used.
Connection AD Corinte W 2ThermozoneADCorinteshouldbeequippedwithafrequency inverter (FC15A/FC15M) for variable fan speed regulation. The water connection may be done fromaboveorbelow.Whenconnectingthewaterontop or from below, there is space, but limited, inside the unit for pipe connections. The appliance should be preceded by a triple pole switch with at least 3 mm breaking gap.
For connection between inverter and motors a cable with braided, tinned copper mesh shield (type C4), with 85 % coverage should be used.
Fig. 1: Minimum distance for water supplied units (for electrical units see www.frico.se)
Thermozone AD Corinte
Control kits
Electrical heat 3
Airflowandheatoutputarecontrolledautomaticallybased on the opening of the door, outdoor temperature and the room temperature.
The system is based on an advanced microprocessing regulator in an attractive design.
All parameters are pre-programmed for easy and quick installation.
Complete control kit:
- ADEA, regulator (complete with outdoor sensor, built-in room sensor and door contact).
- ADEAEB, control board, for external mounting.
- FC15A, frequency inverter with EMC filter.Read more about operation and usage of ADEA in chapter on Controls and accessories.
Water heat 2
Level 1Airflowiscontrolledmanuallywithafrequencyinverter.Room thermostat controls the heat output via actuator/valve.
Complete control kit:
- FC15M, frequency inverter with EMC filter.
- T10,roomthermostatIP30(optionKRT1900,IP55).
- VR20/25, set of valves (option only actuator/valve
SD20/TVV20 or TVV25).
Level 2Airflowandheatoutputarecontrolledautomaticallybased on the opening of the door, outdoor temperature and the room temperature.
The system is based on an advanced microprocessing regulator in an attractive design.
All parameters are pre-programmed for easy and quick installation.
Complete control kit:
- ADEA, regulator (complete with outdoor sensor, built-in room sensor and door contact).
- ADEAEB, control board, for external mounting.
- VR20/25, set of valves (option only actuator/valve
SD20/TVV20 or TVV25).
- FC15A, frequency inverter with EMC filter.Read more about operation and usage of ADEA in chapter on Controls and accessories.
Ambient 1
Airflowiscontrolledmanuallywithafrequencyinverter.
Complete control kit:
- FC15M, frequency inverter with EMC filter.
See chapter on Controls and accessories or contact Frico for further alternatives.
FC15A/FC15M, frequency inverterFrequency inverter for variable fan speed control of AD Corinte. Input voltage 230V~, output voltage 3x230V~. Max input inverter 16 A at 230V~ supply voltage. EMC-filterisincludedasstandard.IP20.Allsettingsarepre-programmed for regulation in combination with ADEA. FC15M is similar to FC15A but pre-programmed for manual fan speed control.
ADCEH, extension hoodExtension hood used to cover the space between the ceiling and the air curtain for a neat finish.
Accessories
Thermozone AD Corinte
Output charts water
AD Corinte WL
(standard coil) Incoming / outgoing water temperature 80/60 °C
Incoming air temp. = +15 °C Incoming air temp. = +20 °C
Type Fan position
Airflow [m3/h]
Output [kW]
Outgoing air temp. [°C]
Water flow [l/s]
Output [kW]
Outgoing air temp. [°C]
Water flow [l/s]
Incoming / outgoing water temperature 60/50 °C
Incoming air temp. = +15 °C Incoming air temp. = +20 °C
Type Fan position
Airflow [m3/h]
Output [kW]
Outgoing air temp. [°C]
Water flow [l/s]
Output [kW]
Outgoing air temp. [°C]
Water flow [l/s]
Incoming / outgoing water temperature 60/40 °C
Incoming air temp. = +15 °C Incoming air temp. = +20 °C
Type Fan position
Airflow [m3/h]
Output [kW]
Outgoing air temp. [°C]
Water flow [l/s]
Output [kW]
Outgoing air temp. [°C]
Water flow [l/s]
Incoming / outgoing water temperature 60/30 °C
Incoming air temp. = +15 °C Incoming air temp. = +20 °C
Type Fan position
Airflow [m3/h]
Output [kW]
Outgoing air temp. [°C]
Water flow [l/s]
Output [kW]
Outgoing air temp. [°C]
Water flow [l/s]
ADC17WL max 3000 33,5 47 0,40 30,3 49 0,36
min 1400 20,1 57 0,24 18,2 58 0,21
ADC22WL max 4000 45,9 48 0,54 41,5 50 0,49
min 1800 26,7 58 0,31 24,2 59 0,28
ADC25WL max 4500 52,0 49 0,62 47,2 50 0,56
min 2050 30,5 58 0,36 27,8 59 0,33
ADC17WL max 3000 24,5 39 0,58 21,3 41 0,50
min 1400 14,6 45 0,34 12,7 46 0,30
ADC22WL max 4000 33,4 39 0,79 29,1 41 0,69
min 1800 19,3 46 0,46 16,9 47 0,40
ADC25WL max 4500 37,9 40 0,90 33,1 41 0,78
min 2050 22,0 46 0,52 19,3 47 0,46
ADC17WL max 3000 20,2 34 0,24 16,9 36 0,20
min 1400 12,3 41 0,14 10,4 42 0,12
ADC22WL max 4000 28,1 35 0,33 23,6 37 0,28
min 1800 16,6 41 0,19 14,1 43 0,16
ADC25WL max 4500 32,0 36 0,38 27,0 37 0,32
min 2050 19,1 42 0,22 16,2 43 0,19
ADC17WL max 3000 15,1 29 0,12 11,5 31 0,09
min 1400 9,6 35 0,07 7,4 35 0,05
ADC22WL max 4000 21,6 31 0,17 16,7 32 0,13
min 1800 13,3 36 0,10 10,4 37 0,08
ADC25WL max 4500 24,9 31 0,19 19,3 32 0,15
min 2050 15,3 37 0,12 12,1 37 0,09
Thermozone AD Corinte
V V
0,01 0,1 1,00,01
0,1
0,7101,00,1
70
10
1
0,01 0,1 1,00,01
0,1
0,7101,00,1
70
10
1
AD
C22
/25
AD
C17
Pressure drop water
Water pressure drop over regulations and valves
Pres
sure
dro
p [
kPa]
Pres
sure
dro
p [
bar
]Water flow [m3/h]
Water flow [l/s]
Thepressuredropiscalculatedforanaveragetemperatureof70°C(PVV80/60).Forotherwatertemperatures,thepressuredropismultipliedbythefactorK.
Average temp. water °C 40 50 60 70 80 90
K 1,10 1,06 1,03 1,00 0,97 0,93
Water pressure drop over AD Corinte W water battery
Water flow [l/s]
Water flow [m3/h]
Pres
sure
dro
p [
kPa]
Pres
sure
dro
p [
bar
]
Thermozone AD Corinte
Wiring diagrams AD Corinte A
Ambient control options - Level 1
FC15M, frequency inverter
Design and specifications are subject to change without notice.
Thermozone AD Corinte
Wiring diagrams AD Corinte E
Electrical control options - Level 3
FC15A, frequency inverter
ADEAIS, external room sensor
MDCDC, magnetic door contact
ADEAR, regulator with display unit and built-in room sensor
ADEAOS, outdoor sensor
ADEAEB, external control board
Thermozone AD Corinte
Water control options
Water - Level 1
FC15M, frequency inverter
T10, room thermostat
SD20, actuator
TVV20/25, 2-way regulation valve
Wiring diagrams AD Corinte W
Thermozone AD Corinte
FC15A, frequency inverter
Water - Level 2
ADEAIS, external room sensor
MDCDC, magnetic door contact
ADEAR, regulator with display unit and built-in room sensor
ADEAOS, outdoor sensor
ADEAEB, external control board
SD20, actuator
TVV20/25 2-way regulation valve