Energy AutomationSIPROTEC 5
Line Protection Devices
7/22/2019 SIPROTEC 5 - Line Protection Devices_V1.0_en-US
2/18
Energy Sector
Siemens AG 2011
Energy AutomationPage 2 V 1.0
Understanding the line protection product portfolio
Major ordering features
New applications and new functions
Scope of functions and application templates
What you will learn
Training objective
7/22/2019 SIPROTEC 5 - Line Protection Devices_V1.0_en-US
3/18
Energy Sector
Siemens AG 2011
Energy AutomationPage 3 V 1.0
Content
Content
Product portfolio
New applications and functions
Scope of functions and
application templates
7/22/2019 SIPROTEC 5 - Line Protection Devices_V1.0_en-US
4/18
Energy Sector
Siemens AG 2011
Energy AutomationPage 4 V 1.0
Siprotec 5 Line ProtectionProduct portfolio according marked segments
Transmission with 1/3pole tripping (7SA87/ 7SD87/ 7SL87/7VK87)
tripping time < 1 cycle
HW with expandable CTs, VTs (e.g. 1,5 CB application) and binary I/Os
required
Transmission, Subtransmission and Distribution with 3-pole tripping
7SA86/ 7SD86/ 7SL86
Tripping time < 1 cycle
HW with expandable CTs, VTs (e.g. 1,5 CB application) and binary I/Os
required
7SA84/ 7SD84
Tripping time > 1,25 cycles
Fixed amount of analogue and binary I/Os
Next click next page
7/22/2019 SIPROTEC 5 - Line Protection Devices_V1.0_en-US
5/18
Energy Sector
Siemens AG 2011
Energy AutomationPage 5 V 1.0
Siprotec 5 Line ProtectionScope of devices
Definition by main protection functions and main differentiating features:
7 xx yy
7SA .. Distance protection
7SD .. Differential protection
7SL .. Dist. + Diff. protection =
7VK .. Breaker Management
2 in 1
... 84 3pole tripping, HW not expandable
... 86 3pole tripping, HW expandable/changeable
... 87 1/3pole tripping, HW expandable/changeable
7SA84 7SA86 7SA87 7SD84 7SD86 7SD87 7SL86 7SL87 7VK87
Distance
Protectionx x x
Differential
Protectionx x x
Dist. + Diff.Protection
x x
Breaker
Managementx
3pole tripping x x x x x
1/3pole tripping x x x x
Hardware
extendablex x x x x x x
Main Protection
Main Features
Next click next page
7/22/2019 SIPROTEC 5 - Line Protection Devices_V1.0_en-US
6/18
Energy Sector
Siemens AG 2011
Energy AutomationPage 6 V 1.0
Siprotec 5 Line Protection
Standard variants
Type 1 1/3, 4I, 4U, 7BI, 14BO, 16 LED
Type 2 1/3, 4I, 4U, 11BI, 9BO, 16 LED
Type 3 1/2, 4I, 4U, 13BI, 21BO, 16 LED
Type 4 1/2, 4I, 4U, 19BI, 30BO, 16 LED
Type 5 1/2, 4I, 4U, 21BI, 17BO(4P), 16 LED
Type 6 1/2, 4I, 4U, 15BI, 18BO(4HS), 16 LED
Type 7 1/2, 8I, 8U, 15BI, 20BO, 16 LED
Type 8 2/3, 4I, 4U, 31BI, 46BO, 16 LEDType 9 2/3, 4I, 4U, 29BI, 23BO(4P), 16 LED
Type 10 2/3, 4I, 4U, 27BI, 34BO(4HS), 16 LED
Type 11 2/3, 8I, 8U, 27BI, 36BO, 16 LED
Type 12 5/6, 8I, 8U, 27BI, 33BO(8HS), 16 LED
Plug In modules
Free configuration on
existing ports
Standard variants simplify the ordering process with regards to hardware configuration The product code is automatically built within the Configurator
One type only ! 1/3, 4I, 4U, 5BI, 8BO, 16 LED
7xx86/87 HW expandable and changeable!
7xx84 HW not expandable !
Next click next page
7/22/2019 SIPROTEC 5 - Line Protection Devices_V1.0_en-US
7/18Energy Sector
Siemens AG 2011
Energy AutomationPage 7 V 1.0
Siprotec 5 Line Protection
Ordering configuration
Example:
7SL87-AAAA-AA0-0AAAA0-AA2111-12111A-DAA000-000AA0-CH1BA1-CF0
All configuration criteria are coded within the Long Product Code
The first 5 digits define the Device Type device specific base price
The Hardware Configurationis based on common module system common price structure
The Functional Classdefines the number of needed function pointscommon price structure
Significant Property(position 21) define major price offsets device specific Add-On price
which cannot be addressed by function points.
Actually used for 7SD/7SL only:
1 2 line ends
2 3 line ends
3 6 line ends
Device Type Significant Property
Functional Class
Hardware Configuration
Next click next page
7/22/2019 SIPROTEC 5 - Line Protection Devices_V1.0_en-US
8/18Energy Sector
Siemens AG 2011
Energy AutomationPage 8 V 1.0
Content
Content
Product portfolio
New applications and functions
Scope of functions and
application templates
7/22/2019 SIPROTEC 5 - Line Protection Devices_V1.0_en-US
9/18Energy Sector
Siemens AG 2011
Energy AutomationPage 9 V 1.0
Protection news
New applications with one device
1,5 circuit breaker 2 breaker, double busbar
Next click next page
7/22/2019 SIPROTEC 5 - Line Protection Devices_V1.0_en-US
10/18Energy Sector
Siemens AG 2011
Energy AutomationPage 10 V 1.0
Protection news
Power Swing: Two functions
Power Swing Blocking (ANSI 68)
Avoids uncontrolled tripping of the distance
protection Operates under symmetrical load conditions as
well as during single-pole auto-reclose cycles
Requires no settings
Can be configured separately to block each
distance zone
Evaluates the impedance trajectory of the
positive sequence impedance Provides a response characteristic with up to 4
impedance zones in the R/X plane
Operates independently from settings of distance
protection zones
Increments counters depending on the point at
which the impedance trajectory enters or exits
the associated impedance zone
Out-of-step protection (ANSI 78)
Next click next page
7/22/2019 SIPROTEC 5 - Line Protection Devices_V1.0_en-US
11/18Energy Sector
Siemens AG 2011Energy AutomationPage 11 V 1.0
Protection news
New protection for STUB BUS
Separate function for STUB protection
based on a differential protection principle
Both CTs connected with one protection device
(HW configuration with 8I/(8U) needed) No PDI communication required
High speed 3pole tripping
Activation through binary input by disconnector QB
Available for 7SA, 7SD, 7SL
Settings similar to 87L except communicationrelated parameters
QA2
QA1
BB 1
BB 2
A-
B-
Line
1,5 circuit breaker topology
QB
STUB BUS
protection area
STUB differential protection (ANSI 87 STUB)
Next click next page
7/22/2019 SIPROTEC 5 - Line Protection Devices_V1.0_en-US
12/18Energy Sector
Siemens AG 2011Energy AutomationPage 12 V 1.0
System function news
LOGs and Recording
LOGs Fault Recorder
Fault LOG
Operational LOG
Sensitive ground fault LOG
New:Setting history LOG
New:User LOG
New:Security LOG
New:Device diagnosis LOG
New:Physical device history LOG
New:Communication LOG
Longer single fault records
(20s with 8kHz sampling frequency)
Longer total record time
(e.g. 120s(8kHz), 1000s(1kHz) , ..)
Start and save condition configurable
Flexible configuration of channels
(analog, binary, measurement values)
Selectable sampling frequency
(1kHz, 2kHz, 4kHz, 8kHz)
Next click next page
7/22/2019 SIPROTEC 5 - Line Protection Devices_V1.0_en-US
13/18Energy Sector
Siemens AG 2011Energy AutomationPage 13 V 1.0
Content
Content
Product portfolio
New applications and functions
Scope of functions and
application templates
7/22/2019 SIPROTEC 5 - Line Protection Devices_V1.0_en-US
14/18Energy Sector
Siemens AG 2011Energy AutomationPage 14 V 1.0
2010 Line ProtectionFunction library for line protection
Each device type offers a subset of
available functions !
ANSI Function
21, 21N Distance protection [3pol., grounded]
Distance protection [isolated, compensated]
Distance protection [1/3pol., grounded]
21FL Fault locator
25 Synchronism check
27 Undervoltage protection-3ph, 3pole
Undervoltage protection-3ph, 1/3pole
Undervoltage protection-V1, 3pole
Undervoltage protection-V1, 1/3pole
Undervoltage protection-V1 invTUndervoltage protection-Vx
27WI Measures for weak and zero infeed
32, 37 32 Power protection-3ph
46, I2>dir Directional I2-definite-time overcurrent protection
49 49 Thermal overload protection
50 Instantaneous overcurrent protection, 1/3pole
Instantaneous overcurrent protection, 3pole
51 Overcurrent protection-3phase, 3pole
Overcurrent protection-3phase, 1/3pole
51N Overcurrent ground fault protection
51BF Breaker failure protection, 3pole
Breaker failure protection, 1/3pole
59 Overvoltage protection-3ph
Overvoltage protection-V1
Overvoltage protection-V1compOvervoltage protection-V0
Overvoltage protection-Vx
47 Overvoltage protection-V2
ANSI Function
67 Directional overcurrent protection-3phase, 3pole
Directional overcurrent protection-3phase, 1/3pole
67N Directional ground fault protection, 1/3pole
Directional ground fault protection, 3pole
68 Power swing blocking
68T Out-of-step protection
79 Auto. Reclosing
81 Overfrequency protection
Underfrequency protection
85/21 Teleprotection for distance protection85/67N Teleprotection for directional ground fault protection
87L Line differential protection, 3pole
Line differential protection, 1/3pole
87 STUB Stub differential protection
Swich on to fault detection
Inrush detection
Measured values (standard and extended)
Fault recorder
Monitoring and supervisionTrip-circuit supervision
Test functions
Phasor measurement
CFC
Next click next page
7/22/2019 SIPROTEC 5 - Line Protection Devices_V1.0_en-US
15/18Energy Sector
Siemens AG 2011Energy AutomationPage 15 V 1.0
Application templates
Overview
3-pole tripping functions only 1/3-pole tripping functions
Device Types
Application Template 7SA84 7SD84 7SA86 7SD86 7SL86 7SA87 7SD87 7SL87 7VK87
DIS Basic X X X
DIS MV compensated / isolated
starpoint (with AR)X X X
DIS HV overhead line, solid earthed
starpointX X X
DIS MhoHV overhead line, solidearthed starpoint
X X
DIS HV overhead line, solid earthedstarpoint, 1,5 CB
X X
DIS MhoHV overhead line, solid
earthed starpoint, 1,5 CBX
DIFF Basic X X X
DIFF overhead line X X X
DIFF overhead line with transformer X X X
DIFF overhead line, 1,5 CB X X
DIFF DIS Basic X X
DIFF DIS HV overhead line, solid
earthed starpointX X
DIFF DIS MhoHV overhead line, solidearthed starpoint
X
DIFF DIS overhead line, 1,5 CB X X
DIFF DIS Mhooverhead line, 1,5 CB X
7VK87 - Basic ( AR, Sync., Breaker
fail. prot.)
X
Next click next page
7/22/2019 SIPROTEC 5 - Line Protection Devices_V1.0_en-US
16/18Energy Sector
Siemens AG 2011Energy AutomationPage 16 V 1.0
Application template
7SD8 Diff overhead line
Tripping: 3pole only (7SD84/86) or 1/3pole (7SD87)
Main1 = differential protection
Emergency / Reserve = non directional overcurrent protection (50/51)
CB functions: breaker failure protection(50 BF) , auto reclose (79), synch check (25)
Supplementary: voltage(27/59) and frequency protection(81), external trip initiation, switch onto fault
Basic configuration included (MP, FG, FN, FB, PDI)
mmQA
T1.1
T5
BB
Busbar with single line feeder
U4
U1
U2
U3
I1
I2
I3
MP
VT-1ph 1
MPCT-3ph 1
MP
VT-3ph 1
FG Line FG CB
50BF
25
79
BI
BO
to
CB QA
FL
7SD8: AT Overhead line
I-3ph
U-3ph
IF IF87L
U-1ph
I-3ph
U-3ph
FG PDC
SI PDC
50 51N
SOTF
27 59
51
Ctrl
CB
T1.2I4
PDI
Protection data
interface 1
81
PDI
FG function groupe
MP measurement point
PDI/C protection data interface/communication
CB circuit breaker
Next click next page
7/22/2019 SIPROTEC 5 - Line Protection Devices_V1.0_en-US
17/18
Energy Sector Siemens AG 2011
Energy AutomationPage 17 V 1.0
Application template
7SD8 Diff overhead line, 1,5 CB
Tripping: 3pole only (7SD84/86) or 1/3pole (7SD87) Main1 = differential protection Emergency / Reserve = non directional overcurrent protection(50/51) 1,5 CB special: 2x breaker failure protection(50BF) , 2x auto reclose(79), 2x synch check(25), STUB-BUS protection Supplementary: voltage(27/59) and frequency protection(81), external trip initiation, switch onto fault Basic configuration included (MP, MN, FG, FN, FB, PDI)
mm
mm
QA2
QA1mm
BB 1
BB 2
U4
U1
U2
U3
U4
I1
I2
I3
I4
FG Line FG CB A-QA
50BF
25
79
BI
BOtoCB A- QA
FL
I1
I2
I3
I4
U1
U2
MN (+)
FG CB B-QA
50BF
Ctrl
BI
BOto
CB B- QA
A-
B-
U3
5927 81
Line
7SD8: AT Overhead line for 1,5 CB
MP
VT-1ph1
1,5 circuit breaker topology
MPCT-3ph 1
MPVT-3ph1
MPCT-3ph 1
I-3ph
U-3ph
U-3ph
I-3ph
U-3ph
I-3ph
U-1ph
IF IF
IF
U-1ph
CB
CB
25
79
Ctrl
MP
VT-1ph1
FG PDC 2PDCPDCFG PDC 1
SI
SI
Protectiondatainterface1
Protectiondatainterface2
PD I PD I
51N50 51
SOTF
PD I
87
FG function groupe
MP measurement point
PDI/C protection data interface/communication
C B circuit breaker
QB
87 STUB
Next click next page
7/22/2019 SIPROTEC 5 - Line Protection Devices_V1.0_en-US
18/18
Energy Sector Siemens AG 2011
Energy AutomationPage 18 V 1 0
Takeaways / Call to Action
SIPROTEC 5 line protection devices cover applications in transmission,sub transmission and distribution markets
Quicker Application templates, copy/paste
Modular Perfectly tailored hardware and functionality
Safer Integrated monitoring and supervision
Better New and improved functions