Compact Installation InstructionsSINAMICS G120X
Edition 12/18
Scope of delivery
Maximum permissible motor cable lengths - m (ft)1)
Maximum permissible motor cable lengths - m (ft)1)
Inverter Frame Size 400 V
EMC category according to EN 61800-3Second environment, C3 First environment, C2 Second environment, C2Inverters with integrated filter
Inverters without line filters with external C3 filter
Inverters with integrated C2 filter
Inverters with integrated C3 filter
FSA … FSC 150 (492) 50 (656) 150 (492) 150 (492)FSD … FSG 200 (656) 50 (656) 150 (492)2) 150 (492)2)
FSH … FSJ 150 (492)3) 50 (984) --- 150 (492)1) The values are valid for a pulse frequency set at the factory2) 2kHz pulse frequency for FSF, 75 kW and 90 kW3) For motor cable lengths of 100 m (328 ft) ... 150 m (492 ft) with additional basic interference suppression module (available on request)
Inverter Frame Size 690 V
EMC category according to EN 61800-3Second environment, C3 Second environment, C2Inverters with integrated filter Inverters without line filters with
external C3 filterInverters with integrated C3 filter
FSD … FSE 150 (492) 50 (656) 100 (328)FSF … FSG 150 (492) 50 (656) ---FSH … FSJ 150 (492)3) 50 (656) 150 (492)2)
1) The values are valid for a pulse frequency set at the factory2) Operation in first environment, C2 only with external C2 line filter plus line reactor3) For motor cable lengths of 100 m ... 150 m, an additional basic interference suppression module shall be provided on the line side (available on request).
Frame size
Fixing Dimensions - mm (inches) Fixings (bolts, washers, nuts)
Tightening torque - Nm (lbf.in)A B Ø
A 55 (2.16) 221.5 (8.72) 5 (0.19) 4 × M4 2.5 (22.12)B 80 (3.15) 265 (10.43) 5 (0.19) 4 × M4 2.5 (22.12)C 118 (4.64) 283 (11.14) 5.5 (0.21) 4 × M5 2.5 (22.12)D 170 (6.69) 430 (16.92) 6.0 (0.23) 4 × M5 6 (53.1)E 230 (9.05) 509 (20.03) 6.5 (0.25) 4 × M6 10 (88.5)F 270 (10.62) 680 (26.77) 8.5 (0.33) 4 × M8 25 (221.26)G 265 (10.43) 970.5 (38.20) 12.0 (0.47) 4 × M10 50 (442.5)
Drill patterns FSA ... FSG
Frame size
Fixing Dimensions - mm (inches) Fixings (bolts, washers, nuts)
Tightening torque Nm (lbf. in)
A1 A2 A3 A4 A5 B G1 G2 Ø
H 160 (6.3) 150 (5.9) 160 (6.3) 225 (8.85) 225 (8.9) 1419 (55.86) 39 (1.5) 49 (1.9) 20 (0.78) 7 × M8 25 (221.26)J 200 (7.9) 290 (11.4) 200 (7.9) 345 (13.6) 345 (13.6) 1399 (55.07) 60.5 (2.4) 60.5 (2.4) 20 (0.78)
Drill patterns FSH and FSJ
EMC shield cable preparation
SINAMICS G120X
Technical data 380 V ... 480 V Technical data 500 V ... 690 VRating plate example
Dimensions and clearance distances FSA .. FSJ - mm (inches)Frame size
Height Height including shield plate
Width Depth Clearance A
Clearance B Additional depth with OP 1)
FSA 232 (9) 330 (12.9) 73 (3) 209 (8) 80 (3) 100 (4) 9 (0.35)FSB 275 (10) 383 (15) 100 (4) 209 (8) 80 (3) 100 (4) 9 (0.35)FSC 295 (11) 423 (16.6) 140 (5) 209 (8) 80 (3) 100 (4) 9 (0.35)FSD 472 (18.5) 624.6 (24.5) 200 (7.8) 239 (9.4) 300 (12) 350 (14) 9 (0.35)FSE 551 (21.6) 729 (28.7) 275 (10.8) 239 (9.4) 300 (12) 350 (14) 9 (0.35)FSF 709 (27.9) 969.4 (38) 305 (12) 360 (14) 300 (12) 350 (14) 9 (0.35)FSG 999.4 (39) 1255 (49) 305 (12) 360 (14) 300 (12) 350 (14) 9 (0.35)FSH 1696 (66.7) - 548 (21.6) 393 (15.4) 200 (8) 250 (9.8) 1) -FSJ 1621 (63.8) - 801 (31.5) 393 (15.4) 200 (8) 250 (9.8) 1) -1) For FSA to FSG, the additional depth with SINAMICS G120 Smart Access is 7 mm (0.28 inch).2) FSH and FSJ require 30 mm clearance between individual inverters.3) For FSH and FSJ a clearance distance of 100 mm is required at the front of the inverter.
Frame size Terminals Terminal/connector type
Maximum cable cross-section Screw tightening torque Stripped insulation length mm (in)mm2 AWG Nm lbf.in
FSALine, motor and PE Screw-type terminal
1.5 … 2.5 16 … 14 0.5 4.4 9 ... 10 (0.4)FSB 1.5 … 6 16 … 10 0.6 5.3 12 ... 13 (0.47)FSC 1.5 …16 16 … 6 1.3 11.5 12 ... 13 (0.47)
FSD Line, motor and PE Screw-type terminal 10 … 35 8 … 2 4.5 39.8 18 (0.7)
FSE Line, motor and PE Screw-type terminal 25 … 70 4 … 3/0 10 88.5 25 (1)
FSF Line, motor and PE
Cable lug according to SN71322 for M10 screws 35 … 2 × 120 2 … 2 × 4/0 22 ... 25 194.7 ... 221.3 --
FSG Line, motor and PE
Cable lug according to SN71322 for M10 screws 35 … 2 × 185 2 … 2 × 350 MCM
50 442.5 --FSH Line, motor, PE and DC
Cable lug according to DIN 46234 for M12 screws
4 × 240 4 × 500 MCM
FSJ Screw-type terminal 6 × 240 6 × 500 MCM
Cable cross-sections and tightening torques
SINAMICS G120X Operating Instructions
https://support.industry.siemens.com/cs/ww/en/ps/13213Language versions:
WARNING
Danger to life if the safety instructions and installation instructions are not observedThe compact installation instructions only contain the most important information for installing the inverter. If the safety instructions and installation instructions in the associated documentation are not observed, accidents involving severe injuries or death can occur.
• Observe the safety instructions and installation instructions given in the associated documentation.
See also: https://support.industry.siemens.com/cs/ww/en/view/109744769
The delivery comprises at least the following components:• A ready to run inverter with loaded firmware - each converter
consists of a Power Module with a non-detachable Control Unit.• One set of connectors for connecting the input and output
terminals• One set of shield connection kit for the Power Module (available
for FSA to FSG only)• One set of shield connection kit for the Control Unit (available
for FSD to FSG only)• Compact Installation Instructions in English and German• A printed full-size drill pattern (available for FSD to FSG only),
which allows easy drilling of the necessary mounting holes.• The inverter contains open-source software (OSS). The OSS
license terms are saved in the inverter.
Options for upgrading and downgrading the firmware can be found on the Internet: http://support.automation.siemens.com/WW/news/en/67364620
Correct mounting orientation
Underwriters LaboratoriesUL and CUL LISTED POWER CONVERSION EQUIPMENT for use in a pollution degree 2 environmentISO 9001Siemens plc operates a quality management system, which complies with the requirements of ISO 9001.
European Low Voltage DirectiveEuropäische NiederspannungsrichtlinieDirective européenne basse tensionDirectiva europea "Baja tension"Direttiva europea sulla bassa tensione
Printed in United Kingdom
Operator Panels and commissioning tools
A5E45631727-004
Edition: 12/2018
EMC installation guideline
http://support.automation.siemens.com/WW/view/en/60612658
Declaration of Conformity
https://support.industry.siemens.com/cs/ww/en/ps/13222/cert
BOP-2 Operating Instructions https://support.industry.siemens.com/cs/ww/en/view/109483379
*A5E45631727*
CU Interfaces
PROFINET connections
Terminal strip X134Status LEDs
Analog Input selection DIP switchInterface X21 for Operator Panel or SINAMICS G120 Smart AccessMemory card slotReserved for future useTerminal strip X132Terminal strip X133PROFINET interface
Siemens AGDigital FactoryMotion ControlPostfach 3180
91050 ERLANGENDeutschland
© Siemens AG, 2018Änderungen vorbehalten
FSH and FSJ Switch / Terminals S41, X41 and X9
Factory settings - default settings of the Inverter
Terminal strips with wiring example
Wiring example FSB
No. Description No. DescriptionUnshielded line cable Shielded control cableCable tie Toothed strapEthernet RJ45 connectors Shielded motor cableCabinet backplane
Connections FSA ... FSC Connections FSD ... FSE Connections FSJConnections FSHConnections FSF Connections FSG
IOP-2 operating instructions https://support.industry.siemens.com/cs/ww/en/view/109752613
SINAMICS G120 Smart Access operating instructions https://support.industry.siemens.com/cs/ww/en/view/109758094
Technical support contact
Online support application https://support.industry.siemens.com/cs/ww/en/sc/2067
Product registration www.siemens.com/drive-registration
Commissioning with SINAMICS G120 Smart AccessThe new SINAMICS G120 Smart Access enables the wireless connection of mobile devices such as tablets, smartphones or laptops over Wi-Fi to the SINAMICS G120X inverter series. The module is set up using a conventional browser and standard operating system. The server functionality eliminates the need to download any additional software.
NOTE
For inverters FSA ... FSG, the R1 and F3 terminals are reserved for future use.
Block diagram
SINAMICS G120 product information https://www.siemens.com/press/en/pressrelease/?press=/en/pressrelease/2018/digitalfactory/pr2018040224dfen.htm
SINAMICS G120X product information for Protective Devices https://support.industry.siemens.com/cs/ww/en/ps/13213
For more information on the permissible types for the branch circuit protection devices, see the Product Information of Protective Devices for SINAMICS G120X Inverter.