1

GRID

PROTECTION

Customer Benefits• Idealforovervoltage/un-

dervoltageapplication.• Adjustablevoltagerating• Operation annunciation in

theformofflag• Drawouttypecase• Completely dust proof by

IP5Xclassprotection

Type VAGM 22Instantaneous Voltage Relays

Page 2: PROTECTION Instantaneous Voltage Relayssystemcontrols.co.in/datasheet/VAGM High Res.pdf · 2018-06-15 · 2 Type VAGM 22 Instantaneous Voltage Relays Type VAGM 22 Features • Adjustable

2

Type VAGM 22

Instantaneous Voltage Relays

Type VAGM 22

Features

• Adjustablesettingrange• Veryhighdropoff/pickupratio• Unaffectedbynormalvariationinfrequencyofinputvoltage• Simpleandrobustconstruction• Positiveactionwithoutchatter

Application

Instantaneousover–voltageprotectionofgenerators,capaci-tors etc., definite timeundervoltageprotectionof acmotors,automaticvoltagechangeoverschemesandotherinstantane-ousanddefinitetimeundervoltageandovervoltageapplica-tionsrequiringadjustablesettings.

General description

VAGM22isstandardattractedarmaturerelaywithsevenequalsettingadjustableonaplugboard.

Adccoilisusedwithaninternallymountedbridgerectifiertoobtainadropoff/pickupratiooftheorderof90%.Aresistanceconnectedinserieswiththecoilistappedsuitablyandthetapsareconnectedtotheplugboardtoobtainsevenequalsetting.Acapacitorisusedtoserveasafilterunitforthebridgerectifieranditalsoactsasasurgesuppressorforprotectionthediodesofthebridgerectifieragainsthighvoltagetransients.

The dc coil is fittedwith a normally open light duty contactwhichisarragedtoenergiseanauxiliaryunitwhichprovidesthenecessaryoutputcontacts.

TypeVAGM22isasinglepolerelaywithitsauxiliaryunit.

Technical data

Voltage rating and setting

Relaysaresuppliedsuitableforoperationon110volts,50Hzsystemandhavethefollowingstandardsettingranges:

Overvoltagerelay110-140%adjustableinsevenequalsteps

Under-voltagerelay40-80%adjustableinsevenequalsteps

Resetting voltages

Overvoltagerelay:90%ofsettingvoltageUnder–voltagerelayrelay:110%ofsettingvoltage

Operating times

Over-voltagerelay:

0.060secondat110%voltagesetting

Undervoltagerelay:

0.025secondatzerovoltage.Thesetimesareinclusiveoftheopetatingtimeoftheassociatedauxiliaryunit.

VAGM22relaywithdrawnfromcase

Page 3: PROTECTION Instantaneous Voltage Relayssystemcontrols.co.in/datasheet/VAGM High Res.pdf · 2018-06-15 · 2 Type VAGM 22 Instantaneous Voltage Relays Type VAGM 22 Features • Adjustable

3

Type VAGM 22

Burdens (VAG coil)

Over-voltagerelay:

Maximumburdenatnominalvoltageis0.9VA

Under-voltagerelay:Maximumburdenatnominalvoltage(i.e.relaysetatthelow-estsetting)is2.5VA.

Thermal rating

Over–Voltagerelay:

TheVAGunitcanwithstandthreetimesthesettingvoltageonanysettingcontinuously.

Under-voltagerelay:

TheVAGunitcanwithstandtwotimesthepick-up(resetting)voltageonanysettingcontinuously.

Accuracy

Theover-voltageandunderrelaysconformtoerrorclassindexE5.0asperBS142–1966and5.0asperIS3231-1955.

Operation indicator

Therelayscanbefitted,ifrequired,withanoperationindicatorontheauxiliaryunit.Theindicatorishandresetbymeansofapush-rodprotruding through the relaycase.On theunder-voltagerelay,ofreverseoperationindicatorisfittedi.e.itoper-atesondrop-offorlossofvoltage.

Contacts

Uptothreepairsofstandardself-resetcontactscanbeprovidedontheauxiliaryunitoftherelayinanycombinationof‘Make’and ‘Break’. Theauxiliaryunit is alwaysenergizedbyanor-mallyopen,lightdutycontactoftheVAGunitincaseofunder-voltage relay. The auxiliary unit can be fitted with blow-outmagnetcontactsalso,ifrequired,forbreakingheavyorhighlyinductivedcloads.

The normal position, regarding the contacts, is the de-ener-gisedposition.

Contact rating : The contacts of the auxiliary unit of the relay are rated as follows :-Type of contacts Current Make & carry continuously Make & carry for 3.0 sec BreakStandard AC 1250VAwithmaximaof5Aand

660V7500VAwithmaximaof30Aand660V

1250VAwithmaximaof5Aand660V

Standard DC 1250Wwithmaximaof5Aand660V

7500Wwithmaximaof30Aand660V

100W (Resistive) or 50W (in-ductive)withmaximaof5Aand660V

Heavy duty mag-neticblow-out

DC 1250Wwithmaximaof5Aand660V

7500Wwithmaximaof30Aand660V

3¼KWmaximum

Dimensionsandweights

Relay Case size Minimum overall dimensions A p p r o x i m a t e gross weight Kg.Hight mm Widtgh mm Depth* mm

VAGM22 1DVert. 233 170 203 5.5

*Add76mmformaximumlengthofterminalstuds,alternatively,29mmforterminalscrews.Theapproximategrossweightgivenaboveisinclusiveofcartons,mountingappendagesandterminaldetails.Certifieddimensionaldrawingofcaseoutlines,panelcut-outsandmountingdetailsareavailableonrequest.TherelayscomplyfullywiththerequirementsofIS3231–1965andaresuitableforuseinnormaltropicalenvironments.

Page 4: PROTECTION Instantaneous Voltage Relayssystemcontrols.co.in/datasheet/VAGM High Res.pdf · 2018-06-15 · 2 Type VAGM 22 Instantaneous Voltage Relays Type VAGM 22 Features • Adjustable

4

GRID

InsulationTherelaymeetstherequirementsofIS32311965/ICE-255-5SeriesC-2kVfor1minute.

Case and finishRelaysaresuppliedinsinglepole,metaldrawoutcasessuitableforflushmountingarefinishedeggshellblackandtropicalised.Thedrawoutfeatureconsiderablysimplifiesmaintenanceandpermits testing to be carried out easily and quickly. A cradlemountedisolatingswitchisprovidedwhichautomaticallyiso-lates the trip circuitwhen the cradle assembly iswithdrawnfromthecaseformaintenance.Thispreventsanyinadvertenttrippingofthecircuitbreaker.Thecasecanalsobefittedwithswitchestomaintaintheunder–voltagetripcircuitsonwith-drawaloftherelayunitfromthecase.Afilterbreatherisfittedtoequalizepressureinsideandoutsidethecasewithoutadmit-tingdust.

Information required with order1. Typeofrelay(undervoltageorovervoltage)2.NominalVoltagerating.(Ifotherthan110voltsacsuitable

interposingVTswillhavetobeused.)3.Numberandtype(Standardorblowoutmagnet)of‘Make’

and‘Break’contactsrequired.4.Whetheroperationindicatorrequired.Ifsowhetheranyflag

inscriptionisrequired.5. Voltageratingoftheauxiliaryunit(*)6. Typeofmounting–flushorprojection.

(*)Itispreferabletohaveadcorseparateacauxiliaryvoltagesupplyfortheauxiliaryunit.

ALSTOMT&DINDIALIMITEDPallavaramWorks19/1,G.S.T.Road,Pallavaram,Chennai-600043Tel:91-44-22648000Fax:91-44-22640040

ALSTOMT&DWorldwideContactCentre:http://www.alstom.com/contactcentre/Tel.:+44(0)1785250070

www.grid.alstom.com

“Alstom

logoandanyalternativeversionthereofaretradem

arksandservicemarksofA

lstom

.Theothernam

esmentioned,registeredorn

ot,areth

epropertyoftheirrespective

companies.Thetechnicalandotherdatacontainedinth

edocumentareprovidedforinformationonly.NeitherALSTOM,itsofficersnoremployeesacceptresponsib

ilityforor

shouldbetakenasmakinganyrepresentationorwarranty(whetherexpressorimplied)astotheaccuracyorcom

pletenessofsuchdataortheachievementsofanyprojected

perfo

rmancecriteriawhereth

eseareindicated.Noliabilityisacceptedfora

nyrelianceplacedupontheinform

ationcontainedinth

isbrochure.A

lstom

reservesth

erightto

reviseorchangethesedataatanytimewithoutfurthernotice.”

Type VAGM 22