• Universal High Voltage Test System HVA-Series
• Tan Delta Test System TD-Series
• Partial Discharge Detection and Location for • Partial Discharge Detection and Location for
MV Cables PD-Series
HIGH VOLTAGE DIAGNOSTICS SARL
Why VLF Cabel Testing?
► Space charges that can occur under elevated DC voltages. Water trees can result in localized stress enhancements.
► Reapplication of normal AC power: Water tree sites can ultimately lead to an electrical tree or trees.
HIGH VOLTAGE DIAGNOSTICS SARL
► Once an electrical tree has been initiated, complete cable failure is normally imminent and inevitable.
► A single water tree which converts to an electrical tree is causing a cable to fail!
Why VLF Cabel Testing?
► D.C. Testing of XLPE will only find gross defects.
► Diagnostic testing like Tan Delta or Partial Discharge is not possible with D.C.
► D.C. only tests the resistive component (R) or
HIGH VOLTAGE DIAGNOSTICS SARL
► D.C. only tests the resistive component (R) or conductance in a cable.
Why VLF Cabel Testing?
►Why nearly no 50Hz-Tests?
P = L (ω.C) U2
P = L (2.PHI.freq.C) U2 = 1 (2 * 3.14 * 50 * 0.33) 142 = 20 kVA
HIGH VOLTAGE DIAGNOSTICS SARL
VPE-Cabel 14kV Test 1000m 95mm2(C = 330nF/km typical cabel)
Result: Too Heavy, too expensive
VLF Testing
Standards
• IEEE 400 & IEEE 400:2 – Revised 2001 (USA)
• IEC 60060-3 (Europe & International)
• CENERLEC HD 620 & 621 (Europe & International)
• VDE 0276 Part 620
• SANS 10198 (South Africa)
• NEN3620/C1 ( Nederland)
HIGH VOLTAGE DIAGNOSTICS SARL
VLF Testing
VLF 0,1Hz Voltage Testing according DIN VDE 0276 (HD 620 S1)
Cable
PVC
and
Test Voltage Voltage Time
DC 5,6 – 8 U0 15 – 30 min
AC 45 - 65 Hz 2 U 30 min
HIGH VOLTAGE DIAGNOSTICS SARL
and
PILC
VPE
(XLPE/PE)
AC 45 - 65 Hz 2 U0 30 min
AC 0,1 Hz 3 U0 30 min
AC 45 - 65 Hz 2 U0 60 min
AC 0,1 Hz 3 U0 60 min
VLF Testing
Advantage Disadvantage
� Sinusoidal Waveform
� Stresses both resistivity R and impedance R, L and C
� Higher breakdown strength than 50Hz
� Tan Delta measurements – possible
Partial discharge measurements – possible
not 50Hz but
0.1Hz
HIGH VOLTAGE DIAGNOSTICS SARL
� Partial discharge measurements – possible
� Stress lines similar to 50Hz on cable, terminations &
joints.
� Sinusoidal is symmetrical under any load (electronically
generated)
HVA 30Universal High Voltage Test System
Output Voltage
• Sinusoidal: 0-33 kV peak, 23kV RMS
• DC ±: 0-30 kV (both polarities)
• Square-Wave: 0-30kV
Output Current
• 15mA
HIGH VOLTAGE DIAGNOSTICS SARL
• 15mA
Frequency
• 0,01Hz to 0,1Hz
Load
• 0,5µF @ 0,1Hz @ 23kV RMS
• 12µF Maximum Capacitance!
HVA 30Universal High Voltage Test System
Auto Frequency Selection
AC (VLF) Symmetrical and load independent across full range
Fast Trip Out and Fault Conditioning Burn Modes
HIGH VOLTAGE DIAGNOSTICS SARL
Less than 20kg
Modes
Programmable Fully Automatic Test Sequences
HVA 30Universal High Voltage Test System
Battery (optional)
Build-in 12kV Feedback Protection!
PC Software „HVA Control Center“
HIGH VOLTAGE DIAGNOSTICS SARL
Less maintainance – no oil used
No thermal limitation for operating time
HVA 30-5 Ultra High Power
Universal High Voltage Test System
Output Voltage
• Sinusoidal: 0-33 kV peak, 23kV RMS
• DC ±: 0-30 kV (both polarities)
• Square-Wave: 0-30kV
Output Current
• 85mA
HIGH VOLTAGE DIAGNOSTICS SARL
• 85mA
Frequency
• 0,01Hz to 0,1Hz
Load
• 5µF @ 0,1Hz @ 19kV RMS
• 15µF Maximum Capacitance
HVA 60Universal High Voltage Test System
Output Voltage
• Sinusoidal: 0-62 kV peak, 44kV RMS
• DC ±: 0-60 kV (both polarities)
• Square-Wave: 0-60kV
Output Current
• 37mA
HIGH VOLTAGE DIAGNOSTICS SARL
• 37mA
Frequency
• 0,01Hz to 0,1Hz
Load
• 1µF @ 0,1Hz @ 44kV RMS
• 5µF @ 0,02Hz @ 44kV RMS
• 15µF Maximum Capacitance
HVA 90Universal High Voltage Test System
Output Voltage
• Sinusoidal: 0-90 kV peak, 64kV RMS
• DC ±: 0-90 kV (both polarities)
• Square-Wave: 0-90kV
Output Current
• 40mA
HIGH VOLTAGE DIAGNOSTICS SARL
• 40mA
Frequency
• 0,01Hz to 0,1Hz
Load
• 1µF @ 0,1Hz @ 64kV RMS
• 10µF @ 0,01Hz @ 64kV RMS
• 11µF Maximum Capacitance
HVA Series
• The load independent, symmetrical output waveform avoids the
potentially destructive space charge effects caused by DC
polarization that occurs in aged extruded cables such as XLPE / PE /
EPR.
• The instrument automatically calculates the optimum frequency to • The instrument automatically calculates the optimum frequency to
energize larger loads (longer cables).
• The instrument is easily programmable allowing the operator to
setup or select test sequences in either automatic or manual mode.
HIGH VOLTAGE DIAGNOSTICS SARL
HVA Series
The HVA measures the real time output wave and digitize the
V (applied)
ITOTAL
IR
I Capacitive
IC
HIGH VOLTAGE DIAGNOSTICS SARL
The HVA measures the real time output wave and digitize the
information (Digital Signal Processor). Therefore it is possible to
measure not only the RMS leakage current but also the Capacitive
current (capacitance is displayed) AND the resistive current
(Megohm reading).
HVA SeriesExample:
HVA60 Output Load
1.0 µF @ 0.1 Hz @ 44kV RMS (Approx 3 km of cable)
2.0 µF @ 0.05 Hz @ 44kV RMS (Approx 6 km of cable)
5.0 µF @ 0.02 Hz @ 44kV RMS (Approx 15 km of cable)
Maximum Capacitance 10µF
HIGH VOLTAGE DIAGNOSTICS SARL
Based on a typical cable: 330nF/km
P 2 π F (Hz) C (µF/km) V2
(kV)
L (km)= 1216,34 2 3,1416 0,1 0,33 44 3,030085 km
Length (km) = P / (2. π . F . C(µF/km) . V2)
HVA SeriesApplications
• Cables: XLPE, PE, EPR, PILC etc.
such as IEEE 400.2, VDE 0276, CENELEC HD 620 S1, the
present draft of IEC 60060-3, etc.
• Capacitors
• Switchgear
HIGH VOLTAGE DIAGNOSTICS SARL
• Switchgear
• Transformers
• Rotating Machines (IEEE 433)
• Insulators
• Bushings
DIAGNOSTICSTAN DELTA Test System
• Easy method to diagnose the condition of the cable
isolation
• Non destructive method
• A method to diagnose “Water Trees”
HIGH VOLTAGE DIAGNOSTICS SARL
• A method to diagnose “Water Trees”
• Preventive maintenance – scheduling of repair and
replacement
Preventive maintenance
DIAGNOSTICSTAN DELTA Test System
A cable is a large capacitor.
IC is very large
IR is very small
HIGH VOLTAGE DIAGNOSTICS SARL
TD = Tan Delta ( δδδδ ) = True Power
Capacitive Reactive Power
= U2/R
U2 C
= 1
CRXLPE = 1.2 x 10-3
PILC = 50 X 10-3
DIAGNOSTICSTAN DELTA Test System
Conventional System:
HIGH VOLTAGE DIAGNOSTICS SARL
DIAGNOSTICSTAN DELTA Test System
HIGH VOLTAGE DIAGNOSTICS SARL
DIAGNOSTICSTAN DELTA Test System
HIGH VOLTAGE DIAGNOSTICS SARL
TD30/TD60TAN DELTA Test System
Input Voltage
• TD30 1– 23 kV RMS TD60 1-44kV RMS
• 2 „C“Type Batteries (10hours)
Tan Delta
• Resolution: 1 x 10-5
HIGH VOLTAGE DIAGNOSTICS SARL
• Accuracy: ± 1 x 10-4 (load > 15nF)
Frequency
• 0,1Hz
Load
• Standard 15nF to 5µF (minimum 1µA RMS)
TD30/TD60 TAN DELTA Test System
3kg only! (TD60 5kg)
Comprehensive Computer software
„TD Control Center“
BluetoothTM Dongle
HIGH VOLTAGE DIAGNOSTICS SARL
No complicated wiring, easy set-up!
Bluetooth Dongle
Visual indication of TD Levels
HIGH VOLTAGE DIAGNOSTICS SARL
TD30/TD60 TAN DELTA Test System
• HVA TD Systems fits directly into the HVA Series of Generators
• TD Measurement and Pressure Testing at the same time
• No need for separate fibre optics for data transmission
• Ultra small size and light weight TD system (3kg for TD30 and 5kg for
HIGH VOLTAGE DIAGNOSTICS SARL
• Ultra small size and light weight TD system (3kg for TD30 and 5kg for TD60)
• Standard Bluetooth built in for easy setup on computers running Microsoft Windows
• Complete PC based Reporting and Storage Software included
TD30/TD60 TD Control Center
HIGH VOLTAGE DIAGNOSTICS SARL
TD30/TD60 TD Control Center
HIGH VOLTAGE DIAGNOSTICS SARL
HIGH VOLTAGE DIAGNOSTICS SARL
SMART VLFwith Tan Delta
► Diagnose your existing network quick and easy
HIGH VOLTAGE DIAGNOSTICS SARL
► Make a fingerprint of your new installations or maintenance work as a future reference
PD30/60/90Partial Discharge
High Voltage Filter &
Coupling Capacitor High Voltage VLF 0.1
Hz source
HVA series
HVA 30 / 60 / 90
HIGH VOLTAGE DIAGNOSTICS SARL
Partial Discharge
Detector
PC laptop & Software for
P.D. diagnostics and P.D.
location
PD30/60/90Partial Discharge
• A TDR snapshot is done for calibrating the PD magnitude.
• This can also provide information on the length of the cable, locations of
joints, condition of the neutral wire.
HIGH VOLTAGE DIAGNOSTICS SARL
PD30/60/90Partial Discharge
Once the cable length has been specified and the joints are located, the
cable can be energized.
Distance Fault Location
HIGH VOLTAGE DIAGNOSTICS SARL
PD30/60/90DSO graph LOC graph
Cable
lengt
h
Propagation
velocity
PD Amplitude &
Location
TDR signature
HIGH VOLTAGE DIAGNOSTICS SARL
PD discharge meter Test Voltage Meter
Coupling
Capacitor
High Voltage Diagnostics Sarl
4, Rue de Lac
CH 1897 Le Bouveret
Switzerland
ERROR: syntaxerror
OFFENDING COMMAND: --nostringval--
STACK:
/Title
()
/Subject
(D:20090428163719+02’00’)
/ModDate
()
/Keywords
(PDFCreator Version 0.9.5)
/Creator
(D:20090428163719+02’00’)
/CreationDate
(Juergen)
/Author
-mark-
Top Related