NPi_Committed to Nuclear Excellence Kewaunee Nuclear Power Plant
Operated by Nuclear Management Company, LLC
NRC-03-082 1 OCFR50.55a
August 6, 2003
U.S. Nuclear Regulatory CommissionATTN: Document Control DeskWashington, DC 20555
KEWAUNEE NUCLEAR POWER PLANTDOCKET 50-305LICENSE No. DPR-432003 INSERVICE INSPECTION (ISI) SUMMARY REPORT
As required by ASME Boiler and Pressure Vessel Code, Section Xl; Code of Federal Regulation1 OCFR50.55a; and Wisconsin Administrative Code Department of Commerce, Subchapter V:Chapter Comm. 41.55(3), various ISI examinations were performed as part of the 2003Refueling Outage. The outage took place from April 5, 2003 through May 11, 2003; i.e. closingof G1. This letter transmits the Inservice Inspection Summary Report as required by paragraphIWA-6230 of Section Xl.
Two separate ASME Section Xl inservice examination programs are implemented at the KNPP.One program is for pressure retaining piping/vessel and component supports and the otherprogram for the metal containment. The 2003 refueling outage constituted the secondinspection year of the third period of the third interval for the piping/vessel and componentsupport program. The 2003 refueling outage was also the second inspection year of the secondperiod of the first interval for the metal containment program. Examinations for the piping/vesseland component support program were performed in accordance with the ASME Boiler andPressure Vessel Code Section Xl 1989 Edition. Examinations for the metal containmentprogram were performed in accordance with the 1992 Edition up to and including the 1992Addenda of Section Xl of the ASME Boiler and Pressure Vessel Code. These requirementswere implemented in accordance with the "Kewaunee Nuclear Power Plant Third Ten-YearInservice Inspection (ISI) Program 1994-2004," "Kewaunee Nuclear Power Plant First 10-YearInservice Inspection Class MC (ISI) Program 1996-2006," Plant Technical Specifications, andnondestructive examination procedures.
N490 Highway 42 * Kewaunee, Wisconsin 54216-9510Telephone: 920.388.2560
Docket 50-305NRC-03-082August 6, 2003Page 2
The following items were examined for Class 1, Class 2, Class 3 Components, and theirsupports:
1. Reactor Vessel Control Rod Drive Mechanisms and 3/4" Head Vent Line2. Regenerative Heat Exchanger Tubesheet to Shell Weld3. Reactor Coolant Pump Main Flange Bolting, Flange Surfaces, and No. 1 Seal Housing
Bolting4. Reactor Coolant Pump External Casing Weld and Casing Internal Surfaces5. Reactor Coolant Pump Flywheel6. Class 1 and Class 2 Piping Welds7. Class 1, Class 2, Class 3 Piping and Component Supports and Hangers8. Class 1 and Class 2 Reactor Vessel Conoseal Bolting, Steam Generator Primary Side
Manway Bolting, Pressurizer Manway Bolting, Flange Bolting, and Valve Bonnet Bolting9. Preservice Examination of Class 1 Reactor Coolant Pump Main Flange Bolt
10. Preservice Examination of Class 1 Piping Welds11. Preservice Examination of Class 1 Valve Bonnet Bolting12. Preservice Examination of Component Cooling Water Heat Exchangers 1A and 1 B
Supports13. Accumulator Tanks 1A and 1 B 2", 1," and 3/" Coupling Base Metal14. Class 1 System Leakage Test15. Class 2 and Class 3 System Inservice and Functional System Pressure Tests
The following items were examined for the Class MC Reactor Building Containment Vessel:
1. Accessible Surface Areas2. Circumferential Weld3. Containment Penetration Bellows4. Airlocks5. Seals and Gaskets
The following items were examined in accordance with Kewaunee Nuclear Power PlantTechnical Specifications:
1. Eddy Current Testing of Steam Generators
In addition, the following examinations were performed in excess of ASME Boiler and PressureVessel Code Section Xi 1989 Edition Requirements and included:
1. Portions of the Service Water System were radiographed for wall loss, pits, nodules, andsand, mud or other sediments
2. Balance of plant piping subject to erosion/corrosion was examined by radiographic,ultrasonic, and visual techniques
3. Nuclear Regulatory Commission Order EA-03-009-lssuance of Order Establishing InterimInspection Requirements For Reactor Pressure Vessel Heads at Pressurized WaterReactors
Docket 50-305NRC-03-082August 6, 2003Page 3
Please find attached a copy of the following documentation that summarizes the inserviceinspection activities and results for the Kewaunee Nuclear Power Plant 2003 Refueling Outage.
1. Summary of recordable indications and a description of how they were dispositioned(Attachment 1)
2. Summary of Class 1 and 2 Repairs and Replacements of Components 1 inch in diameter orsmaller (Attachment 2)
3. Form NIS-1 Owners Report for Inservice Inspections of Class 1, Class 2, and Class 3Components (Attachment 3)
4. Form NIS-1 Owners Report for Inservice Inspections for Class MC Components(Attachment 4)
5. Form NIS-2 Owner's Report for Repair or Replacements (61 Total) (Attachment 5)6. Examination Summary for Scheduled and Augmented Inservice Inspection (ISI) Program
(Attachment 6)7. Examination Summary for Inservice Inspection (ISI) Class MC Program (Attachment 7)8. Examination Summary for Steam Generator Eddy Current (Attachment 8)9. Examination Summary for Nuclear Regulatory Commission Order EA-03-009 (Attachment 9)
10. A summary of examinations which were limited by geometric, metallurgical, ordesign/access restrictions and their associated data sheets (Attachment 10)
The final reports for each of these examinations are on file in the QA/QC Records Vault at theKewaunee Nuclear Power Plant. These records are available for review as deemed necessary.
Additional Comments
The next Refueling Outage at the Kewaunee Nuclear Power Plant is tentatively scheduled forSeptember 2004.
Thomas CoutuSite Vice-President, Kewaunee Plant
PEB
Attachment
cc - U.S. NRC - Region IlIl (w/o attach)U.S. NRC - Senior Resident Inspector (w/o attach)
ATTACHMENT 1
NUCLEAR MANAGEMENT COMPANY, LLCKEWAUNEE NUCLEAR PLANT
DOCKET 50-305
August 6, 2003
Letter from Thomas Coutu (NMC)
To
Document Control Desk (NRC)
Summary of Recordable Indications and Description of Disposition
Docket 50-305NRC-03-082August 6, 2003Attachment 1, Page 1
TABLE 1TYPE OR LOCATION OF RECORDABLE INDICATION METHOD NO. OF RI'S
(RI) l M.Reactor Vessel Conoseal Bolting Visual (VT-3) 2 ConosealsSteam Generator Primary Manway Bolting Visual (VT-I) 1 Stud2" Piping Socket Weld Surface (PT) 1 WeldComponent Supports and Hangers Visual (VT-3) 12 SupportsPiping Flange Bolting Visual (VT-3) 3 FlangesValve Bonnet Bolting Visual (VT-3) 6 ValvesSystem Pressure Tests Visual (VT-2) 16 Items
Disposition of Class 1, Class 2, and Class 3 indications have been completed in accordancewith the rules of ASME Boiler and Pressure Vessel Code Section Xl 1989 Edition and ASMEBoiler and Pressure Vessel Code Section Xl 1992 Edition up to and including 1992 Addenda forClass MC Components. Applicable codes, standards, and engineering criteria were used todisposition indications associated with the non-code-required examinations. Recordableindications for Class 1, Class 2, Class 3 and Class MC have been dispositioned as summarizedbelow:
1. A 0.375" long linear indication (identified as a forging lap) on 2" socket weld RTD-W70Swas recorded during performance of liquid penetrant examinations. This LinearIndication was unacceptable per ASME Boiler and Pressure Vessel Code Section Xl1989 Edition Table IWB-3514-2. The linear indication was reduced in size under workorder 03-004115 by light filing with a small file, reexamined and accepted with a 0.100"linear acceptable ASME Boiler and Pressure Vessel Code Section Xl 1989 Edition TableIWB-3514-2 indication.
2. Visual (VT-1, VT-2, and VT-3) indications recorded on reactor vessel conoseal bolting,steam generator primary side manway bolting, piping flange bolting, valve bonnetbolting, component and piping supports and hangers during system pressure tests were:(1) evaluated and accepted, or (2) repaired, reexamined and accepted by: NuclearManagement Company, LLC; Maintenance, Quality Control, Engineering and TechnicalSupport, or Inservice Inspection Personnel and reviewed by the Authorized NuclearInservice Inspector.
ATTACHMENT 2
NUCLEAR MANAGEMENT COMPANY, LLCKEWAUNEE NUCLEAR PLANT
DOCKET 50-305
August 6, 2003
Letter from Thomas Coutu (NMC)
To
Document Control Desk (NRC)
Summary of Class 1 and 2 ReDairs and Replacement of Components 1 inch in Diameter ofSmaller
Docket 50-305NRC-03-082August 6, 2003Attachment 2, Page 1
The following summarizes the repairs and replacements performed following the 2001 RefuelingOutage and during the 2003 Refueling Outage by grinding, buffing, filing, cutting, or welding onthe Class 1 and Class 2 pressure boundary. These repairs and replacements are in addition tothose itemized on the attached Forms "NIS-2 Owner's Report for Repairs or Replacements."
Comronent Class Reference Reeair/Replacement Method
/2 Rupture Disc. XK-100-18 Welding of Replacement Rupture Disc.
ATTACHMENT 3
NUCLEAR MANAGEMENT COMPANY, LLCKEWAUNEE NUCLEAR PLANT
DOCKET 50-305
August 6, 2003
Letter from Thomas Coutu (N MC)
To
Document Control Desk (NRC)
Form NIS-1 Owner's Report for Inservice Inspections of Class 1, Class 2, and Class 3Components
Page 1 of 10
FORM NIS-1 OWNER'S REPORT FOR INSERVICE INSPECTIONSAS REQUIRED BY THE PROVISIONS OF THE ASME CODE RULES
1. OWNER - WISCONSIN PUBLIC SERVICE CORPORATION, 700 NORTH ADAMS,P.O. BOX 19001, GREEN BAY, WISCONSIN 54307- 9001
2. PLANT - KEWAUNEE, N490 HIGHWAY 42, KEWAUNEE, WISCONSIN 54216-9511
3. PLANT UNIT - NO. 1
4. OWNER CERTIFICATE OF AUTHORIZATION - N/A
5. COMMERCIAL SERVICE DATE - JUNE 16, 1974
6. NATIONAL BOARD NUMBER FOR UNIT - N/A
7. COMPONENTS INSPECTED -
COMPONENT ORAPPURTENANCE
Reactor Vessel RV
Pressurizer PZR
Steam Generator SG-1A
Steam Generator SG-1B
Excess Letdown HeatExchanger AHEL-1A
Excess Letdown HeatExchanger AHEL-IB
Class 1 Piping
Reactor CoolantPump RCP-1A
Reactor CoolantPump RCP-1B
MANUFACTUREROR INSTALLER
CombustionEngineering
Westinghouse
Westinghouse/Ansaldo EnergiaMilano
Westinghouse/Ansaldo EnergiaMilano
Sentry
Sentry
Texas PipeBending
Westinghouse
Westinghouse
MANUFACTUREROR INSTALLER
SERIAL NO.
CE69202
1151
1141/0202
1142/0201
3996-5E
3996-6E
STATE ORPROVINCE NO.
U11480
U11402
U11400
U11401
U11407
U11408
NATIONALBOARD NO.
21010
68-23
68-28/151
68-29/150
364
365
1A-1-618J871-GO1
1B-2-618J871-G02
Page 2 of 10
FORM NIS-1 OWNER'S REPORT FOR INSERVICE INSPECTIONSAS REQUIRED BY THE PROVISIONS OF THE ASME CODE RULES
1. OWNER - WISCONSIN PUBLIC SERVICE CORPORATION, 700 NORTH ADAMS,P.O. BOX 19001, GREEN BAY, WISCONSIN 54307- 9001
2. PLANT - KEWAUNEE, N490 HIGHWAY 42, KEWAUNEE, WISCONSIN 54216-9511
3. PLANT UNIT - NO. 1
4. OWNER CERTIFICATE OF AUTHORIZATION - N/A
5. COMMERCIAL SERVICE DATE - JUNE 16,1974
6. NATIONAL BOARD NUMBER FOR UNIT - N/A
7. COMPONENTS INSPECTED -
COMPONENT ORAPPURTENANCE
MANUFACTUREROR INSTALLER
MANUFACTUREROR INSTALLER
SERIAL NO.STATE OR
PROVINCE NO.NATIONALBOARD NO.
Residual HeatExchangerAHRS1-1A
Residual HeatExchangerAHRS2-1B
Charging PumpPulsation DampenerAPD-1A
Charging PumpPulsation DampenerAPD-1B
Charging PumpPulsation DampenerAPD-1C
Seal Water HeatExchanger AHSW
Volume Control TankVCT
Joseph Oat andSons
Joseph Oat andSons
Greer Hydraulics
Greer Hydraulics
Greer Hydraulics
Atlas
Joseph Oat andSons
1817-1E
1817-1F
U11046
U11424
344
345
GNI-1848
GNI-1846
GNI-1847
734
1787-1C
U11404
U11425
596
376
Regenerative HeatExchanger ARG
Joseph Oat andSons
1831-13 U11409U11410U11411
413414415
Page 3 of 10
FORM NIS-1 OWNER'S REPORT FOR INSERVICE INSPECTIONSAS REQUIRED BY THE PROVISIONS OF THE ASME CODE RULES
1. OWNER - WISCONSIN PUBLIC SERVICE CORPORATION, 700 NORTH ADAMS,P.O. BOX 19001, GREEN BAY, WISCONSIN 54307- 9001
2. PLANT - KEWAUNEE, N490 HIGHWAY 42, KEWAUNEE, WISCONSIN 54216-9511
3. PLANT UNIT - NO. 1
4. OWNER CERTIFICATE OF AUTHORIZATION - N/A
5. COMMERCIAL SERVICE DATE - JUNE 16,1974
6. NATIONAL BOARD NUMBER FOR UNIT - N/A
7. COMPONENTS INSPECTED -
COMPONENT ORAPPURTENANCE
MANUFACTUREROR INSTALLER
MANUFACTUREROR INSTALLER
SERIAL NO.STATE OR
PROVINCE NO.NATIONALBOARD NO.
Letdown HeatExchanger AHLD
Atlas 1206 U11405 1031
Seal Water InjectionFilter AFSI-1A
Seal Water InjectionFilter AFSI-1B
Reactor CoolantFilter AFRC
Seal Water FilterAFSW
Class 2 Piping
Charging PumpAPCH-1A
Charging PumpAPCH-1B
Charging PumpAPCH-1C
CommercialFilters
CommercialFilters
AMF Cuno
AMF Cuno
Texas PipeBending
Ajax Iron Works
Ajax Iron Works
Ajax Iron Works
101072 1172
101073 1173
121 2616
123 2618
6578
6576
6577
Charging PumpAPCH-1A SuctionStabilizer
Greer Hydraulics GH1-10234 568
Page 4 of 10
FORM NIS-1 OWNER'S REPORT FOR INSERVICE INSPECTIONSAS REQUIRED BY THE PROVISIONS OF THE ASME CODE RULES
1. OWNER - WISCONSIN PUBLIC SERVICE CORPORATION, 700 NORTH ADAMS,P.O. BOX 19001, GREEN BAY, WISCONSIN 54307- 9001
2. PLANT - KEWAUNEE, N490 HIGHWAY 42, KEWAUNEE, WISCONSIN 54216-9511
3. PLANT UNIT - NO.1
4. OWNER CERTIFICATE OF AUTHORIZATION - N/A
5. COMMERCIAL SERVICE DATE - JUNE 16,1974
6. NATIONAL BOARD NUMBER FOR UNIT - N/A
7. COMPONENTS INSPECTED -
COMPONENT ORAPPURTENANCE
MANUFACTUREROR INSTALLER
MANUFACTUREROR INSTALLER
SERIAL NO.STATE OR
PROVINCE NO.NATIONALBOARD NO.
Charging PumpAPCH-1B SuctionStablizer
Charging PumpAPCH-1C SuctionStablizer
Greer Hydraulics
Greer Hydraulics
GH1-10235
GH1-10236
569
570
Residual HeatRemoval PumpAPRH1-1A
Residual HeatRemoval PumpAPRH2-1B
Byron Jackson
Byron Jackson
681N0277
681N0276
Refueling WaterStorage Tank
Diesel GeneratorAHDG-1A CoolingWater Exchangers (2)
Diesel GeneratorAHDG-1B CoolingWater Exchangers (2)
General AmericanTransportationCompany
ITT StandardCorp.
ITT StandardCorp.
C-8297/1969
750797-01-2&
750797-01-3
750797-01-1&
750797-01-4
Page 5 of 10
FORM NIS-1 OWNER'S REPORT FOR INSERVICE INSPECTIONSAS REQUIRED BY THE PROVISIONS OF THE ASME CODE RULES
1. OWNER - WISCONSIN PUBLIC SERVICE CORPORATION, 700 NORTH ADAMS,P.O. BOX 19001, GREEN BAY, WISCONSIN 54307- 9001
2. PLANT - KEWAUNEE, N490 HIGHWAY 42, KEWAUNEE, WISCONSIN 54216-9511
3. PLANT UNIT - NO. 1
4. OWNER CERTIFICATE OF AUTHORIZATION - N/A
5. COMMERCIAL SERVICE DATE - JUNE 16,1974
6. NATIONAL BOARD NUMBER FOR UNIT - N/A
7. COMPONENTS INSPECTED -
COMPONENT ORAPPURTENANCE
MANUFACTUREROR INSTALLER
MANUFACTUREROR INSTALLER
SERIAL NO.STATE OR
PROVINCE NO.NATIONALBOARD NO.
Auxiliary FeedwaterPump APFM-1AMotor Driven
Auxiliary FeedwaterPump APFM-1BMotor Driven
Auxiliary FeedwaterPump APFT TurbineDriven
Reactor CoolantPump RCPC-1ALube Oil Cooler
Pacific Pump
Pacific Pump
Pacific Pump
PerfexCorporation
46573
46574
46575
723701-1 4014
Reactor CoolantPump RCPC-1B LubeOil Cooler
Class 3 Piping
Containment FanCooler AHCF-1A
PerfexCorporation
Texas PipeBending
JoyManufacturingand American AirFilter
723701-2 4015
GF14402
Page 6 of 10
FORM NIS-1 OWNER'S REPORT FOR INSERVICE INSPECTIONSAS REQUIRED BY THE PROVISIONS OF THE ASME CODE RULES
1. OWNER - WISCONSIN PUBLIC SERVICE CORPORATION, 700 NORTH ADAMS,P.O. BOX 19001, GREEN BAY, WISCONSIN 54307- 9001
2. PLANT - KEWAUNEE, N490 HIGHWAY 42, KEWAUNEE, WISCONSIN 54216-9511
3. PLANT UNIT - NO. 1
4. OWNER CERTIFICATE OF AUTHORIZATION - N/A
5. COMMERCIAL SERVICE DATE - JUNE 16, 1974
6. NATIONAL BOARD NUMBER FOR UNIT - N/A
7. COMPONENTS INSPECTED -
COMPONENT ORAPPURTENANCE
MANUFACTUREROR INSTALLER
MANUFACTUREROR INSTALLER
SERIAL NO.STATE OR
PROVINCE NO.NATIONALBOARD NO.
Containment FanCooler AHCF-1B
JoyManufacturingand American AirFilter
GF14399
Containment FanCooler AHCF-1C
Containment FanCooler AHCF-1D
Safety Injection PumpAPSI-1A
Safety Injection PumpAPSI-1B
Safety Injection PumpLube Oil CoolerAHSC-1A
Safety Injection PumpLube Oil CoolerAHSC-1B
JoyManufacturingand American AirFilter
JoyManufacturingand American AirFilter
Bingham Pump
Bingham Pump
Thermxchanger
Thermxchanger
GF14401
GF14400
290696
290697
X10199A2
X10199A3
Page 7 of 10
FORM NIS-1 OWNER'S REPORT FOR INSERVICE INSPECTIONSAS REQUIRED BY THE PROVISIONS OF THE ASME CODE RULES
1. OWNER - WISCONSIN PUBLIC SERVICE CORPORATION, 700 NORTH ADAMS,P.O. BOX 19001, GREEN BAY, WISCONSIN 54307- 9001
2. PLANT - KEWAUNEE, N490 HIGHWAY 42, KEWAUNEE, WISCONSIN 54216-9511
3. PLANT UNIT - NO. 1
4. OWNER CERTIFICATE OF AUTHORIZATION - N/A
5. COMMERCIAL SERVICE DATE - JUNE 16,1974
6. NATIONAL BOARD NUMBER FOR UNIT - N/A
7. COMPONENTS INSPECTED -
COMPONENT ORAPPURTENANCE
MANUFACTUREROR INSTALLER
MANUFACTUREROR INSTALLER
SERIAL NO.STATE OR
PROVINCE NO.NATIONALBOARD NO.
Safety Injection PumpHeat Exchangers (2)AHSC-1A
Safety Injection PumpHeat Exchangers (2)AHSC-1B
Borg Warner
Borg Warner
854030:854030
854030:854030
Residual HeatRemoval PumpAHRHRP-1A ShaftSeal Heat Exchanger
Residual HeatRemoval PumpAHRHRP-1B ShaftSeal Heat Exchanger
Accumulator TankACC-1A
Accumulator TankACC-1B
Containment SprayPump APCS-1A
Borg Warner
Borg Warner
Wyatt
Wyatt
Ingersoll Rand
681N0276
681N0276
H-5645-69
H-5644-69
U11397
U11398
0670-74
Page 8 of 10
FORM NIS-1 OWNER'S REPORT FOR INSERVICE INSPECTIONSAS REQUIRED BY THE PROVISIONS OF THE ASME CODE RULES
1. OWNER - WISCONSIN PUBLIC SERVICE CORPORATION, 700 NORTH ADAMS,P.O. BOX 19001, GREEN BAY, WISCONSIN 54307- 9001
2. PLANT - KEWAUNEE, N490 HIGHWAY 42, KEWAUNEE, WISCONSIN 54216-9511
3. PLANT UNIT - NO. 1
4. OWNER CERTIFICATE OF AUTHORIZATION - N/A
5. COMMERCIAL SERVICE DATE - JUNE 16,1974
6. NATIONAL BOARD NUMBER FOR UNIT - N/A
7. COMPONENTS INSPECTED -
COMPONENT ORAPPURTENANCE
MANUFACTUREROR INSTALLER
MANUFACTUREROR INSTALLER
SERIAL NO.STATE OR
PROVINCE NO.NATIONALBOARD NO.
Containment SprayPump APCS-1B
Containment SprayPump APCS-1AGland Seal Cooler
Containment SprayPump APCS-1BGland Seal Cooler
Component CoolingPump APCC-1A
Component CoolingPump APCC-1B
Service Water PumpAPSW-1A1
Ingersoll Rand
Helliflow
Helliflow
Ingersoll DresserPump Flow Serv.
0670-75
49486938
6080694
0600009
Ingersoll DresserPump Flow Serv.
WorthingtonPump
0600010
VTP27737
Service Water PumpAPSW-1A2
WorthingtonPump
75 TU-1719-1
Service Water PumpAPSW-1B1
Service Water PumpAPSW-1B2
WorthingtonPump
WorthingtonPump
VTP27736
VTP27738
Page 9 of 10
FORM NIS-1 OWNER'S REPORT FOR INSERVICE INSPECTIONSAS REQUIRED BY THE PROVISIONS OF THE ASME CODE RULES
1. OWNER - WISCONSIN PUBLIC SERVICE CORPORATION, 700 NORTH ADAMS,P.O. BOX 19001, GREEN BAY, WISCONSIN 54307- 9001
2. PLANT - KEWAUNEE, N490 HIGHWAY 42, KEWAUNEE, WISCONSIN 54216-9511
3. PLANT UNIT - NO. 1
4. OWNER CERTIFICATE OF AUTHORIZATION - N/A
5. COMMERCIAL SERVICE DATE - JUNE 16,1974
6. NATIONAL BOARD NUMBER FOR UNIT - N/A
7. COMPONENTS INSPECTED -
COMPONENT ORAPPURTENANCE
MANUFACTUREROR INSTALLER
MANUFACTUREROR INSTALLER
SERIAL NO.STATE OR
PROVINCE NO.NATIONALBOARD NO.
Spent Fuel Pool HeatExchanger AHSF
Main Steam MoistureSeparator
Spent Fuel Pool PumpAPSF-1A
Struther Wells 1-68-06-1519 U11445
Wright Austin
Gould Pumps
6230 X.R. 6008
786A519.1
Spent Fuel Pool PumpAPSF-1B
Gould Pumps 786A519.2
Service Water PumpStrainer ASSW-1A1
Service Water PumpStrainer ASSW-1A2
Service Water PumpStrainer ASSW-1B1
Service Water PumpStrainer ASSW-1B2
Component CoolingHeat ExchangerAHCC1-1A
S.P. KinneyEngineers
S.P. KinneyEngineers
S.P. KinneyEngineers
S.P. KinneyEngineers
Engineers andFabricators Co.
2278
2279
2280
2281
S-26125 U39499 3269
Page 10 of 10
FORM NIS-1 OWNER'S REPORT FOR INSERVICE INSPECTIONSAS REQUIRED BY THE PROVISIONS OF THE ASME CODE RULES
1. OWNER - WISCONSIN PUBLIC SERVICE CORPORATION, 700 NORTH ADAMS,P.O. BOX 19001, GREEN BAY, WISCONSIN 54307- 9001
2. PLANT - KEWAUNEE, N490 HIGHWAY 42, KEWAUNEE, WISCONSIN 54216-9511
3. PLANT UNIT - NO. 1
4. OWNER CERTIFICATE OF AUTHORIZATION - N/A
5. COMMERCIAL SERVICE DATE - JUNE 16, 1974
6. NATIONAL BOARD NUMBER FOR UNIT - N/A
7. COMPONENTS INSPECTED -
COMPONENT ORAPPURTENANCE
MANUFACTUREROR INSTALLER
MANUFACTUREROR INSTALLER
SERIAL NO.STATE OR
PROVINCE NO.NATIONALBOARD NO.
Component CoolingHeat ExchangerAHCC2-1B
Component CoolingSurge Tank ATCS
Engineers andFabricators
Sharpsville Steel
S-26126
714
U39500
U11421
3270
714
Control Room AirConditioning Unit 1ACoil
Control Room AirConditioning Unit 1BCoil
Trane Company
Trane Company
K11H202002
K11H202003
Control Room AirConditioning ExpansionTank 1A
Control Room AirConditioning ExpansionTank 1B
ITT Bell and Gossett
ITT Bell and Gossett 116013
FORM NIS-1 (Back)
8. Examination Dates: May 8, 2002 to May 11, 2003
9. Inspection Period Identification:
10. Inspection Interval Identification:
3rd
3rd
11. Applicable Edition of Section XI: 1989 Addenda: None
12. Date/Revision of Inspection Plan: November 27, 2000/Revision 2
13. Abstract of Examinations and Tests. Include a list of examinations and tests and a statementconcerning status of work required for the Inspection Plan. Reference Tab C
14. Abstract of Results of Examinations and Tests. Reference Tab B and Tab F
15. Abstract of Corrective Measures. Reference Tab B and Tab FUtilization of ASME Boiler and Pressure vessel Code Section XI: Code Cases: N-416-1, N-416-2,N-460, N-48 1, N-49 1, N-498 and N-498- 1.
We certify that a) the statements made in this report are correct, b) the examinations and tests meetthe Inspection Plan as required by the ASME Code, Section XI, and c) corrective measures takenconform to the rules of the ASME Code, Section XI.
Certificate of Authorization No. (If applicable): /V14 Expiration Date: Ho
Date: St4 a Zy 23 20 Q93 Signed: WGconi. PAlti SeevJe By:Owner
CERTIFICATE OF INSERVICE INSPECTION
I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and theState or Province of £daseeo'SJ.. and employed by i44er$e eb r64 ,, o1.r- -r of
W4,e eg C r. have inspected the components described in this Owner's Report during the periodA yf4v 8 Rev to MuAy /, 0403 , and state that to the best of my knowledge and belief, the Owner has
performed examinations and tests and taken corrective measures described in this Owner's Report in accordance with theInspection Plan and as required by the ASME Code, Section XI.
By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or implied, concerning theexaminations, tests, and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor hisemployer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connectedwith this inspction.
W 4A, Commissions A'S77s/ 7 iJ1s /0o02 Xs .5. A/ Inspfctor's Signature National Board, State. Province, and Endorsements
Date: A14,f 23 20 &.3I
ATTACHMENT 4
NUCLEAR MANAGEMENT COMPANY, LLCKEWAUNEE NUCLEAR PLANT
DOCKET 50-305
August 6, 2003
Letter from Thomas Coutu (NIMC)
To
Document Control Desk (NRC)
Form NIS-1 Owner's ReDort for Inservice Inspections for Class MC Comoonents
FORM NIS-1 OWNER'S REPORT FOR INSERVICE INSPECTIONSAS REQUIRED BY THE PROVISIONS OF THE ASME CODE RULES
1. OWNER - WISCONSIN PUBLIC SERVICE CORPORATION, 700 NORTH ADAMS,P.O. BOX 19001, GREEN BAY, WISCONSIN 54307- 9001
2. PLANT - KEWAUNEE, N490 HIGHWAY 42, KEWAUNEE, WISCONSIN 54216-9511
3. PLANT UNIT - NO. 1
4. OWNER CERTIFICATE OF AUTHORIZATION - N/A
5. COMMERCIAL SERVICE DATE - JUNE 16,1974
6. NATIONAL BOARD NUMBER FOR UNIT - N/A
7. COMPONENTS INSPECTED -
COMPONENT ORAPPURTENANCE
Reactor BuildingContainment Vessel
Personnel Airlock
MANUFACTUREROR INSTALLER
Chicago Bridgeand IronCompany
Chicago Bridgeand IronCompany
MANUFACTUREROR INSTALLER
SERIAL NO.
C4454
C4454
STATE OR NATIONALPROVINCE NO. BOARD NO.
U11423 ...
U11423 ---
FORM NIS-1 (Back)
8. Examination Dates: April 5, 2003 to May 11, 2003
9. Inspection Period Identification:
10. Inspection Interval Identification:
2nd
1st
11. Applicable Edition of Section XI: 1992 Addenda: 1992
12. Date/Revision of Inspection Plan: September 25, 2000/Revision 1
13. Abstract of Examinations and Tests. Include a list of examinations and tests and a statementconcerning status of work required for the Inspection Plan. Reference Tab C
14. Abstract of Results of Examinations and Tests. Reference Tab B and Tab F
15. Abstract of Corrective Measures. Reference Tab B and Tab F
We certify that a) the statements made in this report are correct, b) the examinations and tests meetthe Inspection Plan as required by the ASME Code, Section XI, and c) corrective measures takenconform to the rules of the ASME Code, Section XI.
Certificate of Authorization No. (If appli
Date: A4aY 2 3 20 o 3
A/A Expiration Date: Am4
Signed: PXAi, lc rse By:Owner
CERTIFICATE OF INSERVICE INSPECTION
I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and theState or Province of 6 and employed by 9.4,ereroC t Sg4o" /j3w (i, Cr of
#40cretaf C7 . have inspected the components described in this Owner's Report during the periodApttc T. 2zo 3 to AlAy go 20o03 ,and state that to the best of my knowledge and belief, the Owner has
performed examinations and tests and taken corrective measures described in this Owner's Report in accordance with theInspection Plan and as required by the ASME Code, Section XI.
By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or implied, concerning theexaminations, tests, and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor hisemployer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connectedwith this inspectn.
___ /1 Commissions 1e-zdi2/ gJis/~oozj( zs A/ Inspector's 3tgnature National Board, State. P~roince, ahd Endorsements
Date: 414 2 3 20 v3
ATTACHMENT 5
NUCLEAR MANAGEMENT COMPANY, LLCKEWAUNEE NUCLEAR PLANT
DOCKET 50-305
August 6, 2003
Letter from Thomas Coutu (NMC)
To
Document Control Desk (NRC)
Form NIS-2 Owner's Report for Repair or Replacement (61 Total)
FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTAs Required by the Provisions of the ASME Code Section Xi
1. Owner Wisconsin Public Service Corporation
700 North Adams P.O.Box 19001 Green Bay, WI 54307-9001
2. Plant Kewaunee Nuclear Power Plant
N490 HWY 42 Kewaunee, WI 54216-9511
3. Work Performed By Nuclear Management Companv, LLC
700 First Street. Hudson, Wisconsin 54016
4. Identification of System 02 Class 3 SERVICE WATER
5. (a) Applicable Construction Code B16.34
(b) Applicable Edition of Section Xl Utilized for Repairs or Replacements 1989
6. Identification of Components Repaired or Replaced and Replacement Components
Date 3/6/2003
Sheet 1 of 2
Unit No. 1
Work Order 01-011101
Type Code Sym. Stamp NA
Authorization No. NA
Expiration Date NA
Code Case N-416-1
Name of Name of ManufacturerComponent Manufacturer Serial No.
SW-1041A-2 CONBRACO INDUSTRIES NAINC.
NationalBoard No.
NA
Other YearID Built
SW 134-217 2002
Repaired,Replaced, orReplacement
REPLACEMENT
ASMECode
Stamped
N
7. Description of Work INSTALL NEW CLASS 3 AIR CONDITIONING COOLING WATER SYSTEM 2 1/2' VALVE SW-1041A-2, 2 - 2 1/2"FLANGES AND 2 -2 1/2" BUTT WELDS.
8. Tests conducted Hydrostatic g Pneumatic g
Other EJ Pressure 69 psiNominal Operating Pressure p
Test Temp. 40 deg. F
Exempt n
9. Remarks UTILIZATION OF ASME BOILER AND PRESSURE VESSEL CODE SECTION XI: CODE CASE N-416-1.
Applicable Manufacturer's Data Reports to be Attached
NIS-2 (Back)
Sheet 2 of 2
Date: 3/6/2003
Name of Component: SW-1041A-2
Work Order Number: 01-011101
Certificate of Compliance
We Certify that the statements made in the report are correct and this REPLACEMENT conforms to the rules of the
ASME Code Section Xl. Repair or Replacement
Type Code Symbol Stamp NA
Certificate of Authorization No. NA Expiration Date NA
Signed f4 C.A M L, * Date god .20 Q3Owner or Owner's Designee, Title
Certificate of INSERVICE INSPECTION
I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors
and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of Hartford, CT
have inspected the components described in the Owner's Report during the period ,,1-/- O to G -"'3, and state that
to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described
in this Owner's Report in accordance with the requirements of the ASME Code, Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning
the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor
his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising
from or connected with this inspection.
Commissions NB7741, I, N, IS, A WIS 100024
Inspectors Signature National Board, State, Province, and Endorsements
Date 6 - lo 20o 3
FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTAs Required by the Provisions of the ASME Code Section Xi
1. Owner Wisconsin Public Service Corporation
700 North Adams P.O.Box 19001 Green Bay. WI 54307-9001
2. Plant Kewaunee Nuclear Power Plant
N490 HWY 42 Kewaunee. WI 54216-9511
3. Work Performed By Nuclear Management Company. LLC
700 First Street. Hudson. Wisconsin 54016
4. Identification of System 34 Class 2 RESIDUAL HEAT REMOVAL
5. (a) Applicable Construction Code B31.1-1967
(b) Applicable Edition of Section Xi Utilized for Repairs or Replacements 1989
6. Identification of Components Repaired or Replaced and Replacement Components
Date 5/13/2003
Sheet 1 of 2
Unit No. I
Work Order 01-016562
Type Code Sym. Stamp NA
Authorization No. NA
Expiration Date NA
Code Case NA
Name ofComponent
RHR-F3
Name ofManufacturer
NF
ManufacturerSerial No.
NA
NationalBoard No.
NA
OtherID
NA
YearBuilt
1967
Repaired,Replaced, orReplacement
REPAIRED
ASMECode
Stamped
N
7. Description of Work REPAIR LEAK ON CLASS 2 RESIDUAL HEAT REMOVAL SYSTEM 10 SUCTION FLANGE RHR-F3.
8. Tests conducted Hydrostatic
Other [
Pneumatic r] Nominal Operating Pressure [x]Pressure 375 psi Test Temp. 112 deg. F
Exempt n
9. Remarks NOT APPLICABLE.
Applicable Manufacturers Data Reports to be Attached
NIS-2 (Back)
Sheet 2 of 2
Date: 5/13/2003
Name of Component: RHR-F3
Work Order Number: 01-016562
Certificate of Compliance
We Certify that the statements made in the report are correct and this REPAIRED conforms to the rules of the
ASME Code Section Xi. Repair or Replacement
Type Code Symbol Stamp NA
Certificate of Authorization No. NA Expiration Date NA
Signed bAf4C. L;kOMuAA l Date ,20 03Owner or Owners Designee, Title
Certificate of INSERVICE INSPECTION
I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors
and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of Hartford, CT
have inspected the components described in the Owners Report during the period . /-OZ to C - -03, and state that
to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described
in this Owner's Report in accordance with the requirements of the ASME Code, Section Xi.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning
the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor
his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising
from or connected with this inspection.
go G o -iature Commissions NB7741, I, N, IS, A WIS 100024
Inspec s Signature National Board, State, Province, and Endorsements
Date 64 - /a 20 0
FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTAs Required by the Provisions of the ASME Code Section Xl
1. Owner Wisconsin Public Service Corporation
700 North Adams P.O.Box 19001 Green Bay, WI 54307-9001
2. Plant Kewaunee Nuclear Power Plant
N490 HWY 42 Kewaunee, WI 54216-9511
3. Work Performed By Nuclear Management Company, LLC
700 First Street. Hudson, Wisconsin 54016
4. Identification of System 34 Class 2 RESIDUAL HEAT REMOVAL
5. (a) Applicable Construction Code B31.1-1967
(b) Applicable Edition of Section Xl Utilized for Repairs or Replacements 1989
6. Identification of Components Repaired or Replaced and Replacement Components
Date 4/25/2003
Sheet 1 of 2
Unit No. 1
Work Order 01-022099
Type Code Sym. Stamp NA
Authorization No. NA
Expiration Date NA
Code Case NA
Name ofComponent
Name ofManufacturer
VICKERY-SIMMSINC.
ManufacturerSerial No.
NF
NationalBoard No.
NA
OtherID
YearBuilt
Repaired,Replaced, orReplacement
ASMECode
Stampedl
FE-626
27020 1970 REPAIRED N
7. Description of Work REPAIR DUE TO LEAKAGE CLASS 2 RESIDUAL HEAT REMOVAL SYSTEM 10" FLANGE FE-626.
8. Tests conducted Hydrostatic 2
Other [n
Pneumatic Nominal Operating Pressure 1-3
Pressure .150 psi Test Temp. 93 deg. F
Exempt n
9. Remarks NOT APPLICABLE.
Applicable Manufacturer's Data Reports to be Attached
NIS-2 (Back)Sheet 2 of 2
Date: 4/25/2003
Name of Component: FE-626
Work Order Number: 01-022099
Certificate of Compliance
We Certify that the statements made in the report are correct and this REPAIRED conforms to the rules of the
ASME Code Section XI. Repair or Replacement
Type Code Symbol Stamp NA
Certificate of Authorization No. NA Expiration Date NA
Signed 0 eAh CW AC4v & Date ,20 a 3Owner or Owner's Designee, Title
Certificate of INSERVICE INSPECTION
I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors
and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of Hartford, CT
have inspected the components described in the Owner's Report during the period A -/-dZ to 6 -A -°3, and state that
to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described
in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning
the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor
his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising
from or connected with this inspection.
Commissions NB7741, I, N, IS, A WIS 100024
Inspectors Signature National Board, State, Province, and Endorsements
Date C - /0 ,20 CO,3
FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTAs Required by the Provisions of the ASME Code Section XI
1. Owner Wisconsin Public Service Cormoration
700 North Adams P.O.Box 19001 Green Bay. WI 54307-9001
2. Plant Kewaunee Nuclear Power Plant
N490 HWY 42 Kewaunee. WI 54216-9511
3. Work Performed By Nuclear Management ComDany. LLC
700 First Street. Hudson, Wisconsin 54016
4. Identification of System 34 Class 2 RESIDUAL HEAT REMOVAL
5. (a) Applicable Construction Code B31.1-1967
(b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989
6. Identification of Components Repaired or Replaced and Replacement Components
Date 5/13/2003
Sheet 1 of 2
Unit No. 1
Work Order 02-003489
Type Code Sym. Stamp NA
Authorization No. NA
Expiration Date NA
Code Case NA
Name ofComponent
RHR-3B
Name ofManufacturer
CRANECOMPANY
ManufacturerSerial No.
NF
NationalBoard No.
NA
Other YearDD Built
AC034-002 1972
Repaired,Replaced, orReplacement
REPAIRED
ASMECode
Stamped
N
7. Description of Work REPAIR BONNET TO BODY LEAK ON CLASS 2 RESIDUAL HEAT REMOVAL SYSTEM 8 VALVE RHR-3B.
8. Tests conducted Hydrostatic Dl
Other ElPneumatic U Nominal Operating Pressure f77Pressure 375 psi Test Temp. 112 deg. F
Exempt U
9. Remarks NOT APPLICABLE.
Applicable Manufacturers Data Reports to be Attached
NIS-2 (Back)
Sheet 2 of 2
Date: 5/1 3/2003
Name of Component: RHR-3B
Work Order Number: 02-003489
Certificate of Compliance
We Certify that the statements made in the report are correct and this REPAIRED conforms to the rules of the
ASME Code Section Xl. Repair or Replacement
Type Code Symbol Stamp NA
Certificate of Authorization No. NA Expiration Date NA
Signed Gil & idhA 1AUV 4 G~L ln 60t6v Date e ,20 QkOwner or Owner's Designee, Title
Certificate of INSERVICE INSPECTION
I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors
and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of Hartford, CT
have inspected the components described in the Owners Report during the period o? -1 2 to __-_-__3_, and state that
to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described
in this Owners Report in accordance with the requirements of the ASME Code, Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning
the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor
his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising
from or connected with this inspection.
Commissions NB7741, I, N, IS, A WIS 100024
Inspects Signature National Board, State, Province, and Endorsements
Date 6 -/0 ,20 CZ
FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTSAs Required by the Provisions of the ASME Code Section Xi
1. Owner Wisconsin Public Service Corporation
700 North Adams P.O.Box 19001 Green Bay. WI 54307-9001
2. Plant Kewaunee Nuclear Power Plant
N490 HWY 42 Kewaunee. WI 54216-9511
3. Work Performed By Nuclear Management Company. LLC
700 First Street. Hudson, Wisconsin 54016
4. Identification of System 35 Class 2 CHEMICAL AND VOLUME CONTROL
5. (a) Applicable Construction Code SEC. Vil DIV.1-1975
(b) Applicable Edition of Section Xl Utilized for Repairs or Replacements 1989
6. Identification of Components Repaired or Replaced and Replacement Components
Date 9/24/2002
Sheet 1 of 2
Unit No. 1
Work Order 02-004201
Type Code Sym. Stamp NA
Authorization No. NA
Expiration Date NA
Code Case NA
Name ofComponent
APD-1C
Name ofManufacturer
GREERHYDRAULICS
ManufacturerSerial No.
GHI-1849
NationalBoard No.
NA
OtherID
07002
YearBuilt
1975
Repaired,Replaced, orReplacement
REPLACEMENT
ASMECode
Stamped
Y
.
7. Description of Work REPLACE DAMPENER SPRING ON CLASS 2 CHEMICAL AND VOLUME CONTROL SYSTEM CHARGING PUMP iCPULSATION DAMPENER.
8. Tests conducted Hydrostatic Cl
Other nPneumatic F] Nominal Operating Pressure MPressure 2240 psi Test Temp. 114 deg. F
Exempt LI
9. Remarks NOT APPLICABLE.
Applicable Manufacturer's Data Reports to be Attached
NIS-2 (Back)
Sheet 2 of 2
Date: 9/2412002
Name of Component: APD-1 C
Work Order Number: 02-004201
Certificate of Compliance
We Certify that the statements made in the report are correct and this REPLACEMENT conforms to the rules of the
ASME Code Section Xl. Repair or Replacement
Type Code Symbol Stamp NA
Certificate of Authorization No. NA Expiration Date NA
Signed 4 A £JtWJOli/ Date .4 , 20 03Owner or Owner's Designee, Title
Certificate of INSERVICE INSPECTION
I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors
and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of Hartford, CT
have inspected the components described in the Owner's Report during the period o2-/-O 2 to 4 -6 - ,and state that
to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described
in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning
the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor
his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising
from or connected with this inspection.
/7 sh ^ - - Commissions NB7741, I, N. IS, A WIS 100024Inspectors Signature National Board, State, Province, and Endorsements
Date 6 -/0 ,20 CZ3
FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTSAs Required by the Provisions of the ASME Code Section Xl
1. Owner Wisconsin Public Service Corporation
700 North Adams P.O.Box 19001 Green Bay, WI 54307-9001
2. Plant Kewaunee Nuclear Power Plant
N490 HWY 42 Kewaunee, WI 54216-9511
3. Work Performed By Nuclear Manaaement Company. LLC
700 First Street. Hudson. Wisconsin 54016
4. Identification of System 35 Class 2 CHEMICAL AND VOLUME CONTROL
5. (a) Applicable Construction Code SEC. VIII DIV.1-1 975
(b) Applicable Edition of Section Xl Utilized for Repairs or Replacements 1989
6. Identification of Components Repaired or Replaced and Replacement Components
Date 9/24/2002
Sheet 1 of 2
Unit No. 1
Work Order 02-004262
Type Code Sym. Stamp NA
Authorization No. NA
Expiration Date NA
Code Case NA
Repaired, ASMEName of Name of Manufacturer National Other Year Replaced, or Code
Component Manufacturer Serial No. Board No. ID Built Replacement Stamped
APD-1A GREER GHI-1848 NA 07000 1975 REPLACEMENT YHYDRAULICS
7. Description of Work REPLACE DAMPENER SPRING ON CLASS 2 CHEMICAL AND VOLUME CONTROL SYSTEM CHARGING PUMP lAPULSATION DAMPENER.
8. Tests conducted Hydrostatic []
Other []Pneumatic U Nominal Operating Pressure MPressure 2240 psi Test Temp. 114 deg. F
Exempt C
9. Remarks NOT APPLICABLE.
Applicable Manufacturers Data Reports to be Attached
NIS-2 (Back)
Sheet 2 of 2
Date: 9/24/2002
Name of Component: APO-1A
Work Order Number: 02-004262
Certificate of Compliance
We Certify that the statements made in the report are correct and this REPLACEMENT conforms to the rules of the
ASME Code Section Xl. Repair or Replacement
Type Code Symbol Stamp NA
Certificate of Authorization No. NA Expiration Date NA
Signed &X/rw 1 f f i 7 Date ,20 03Owner or Owner's Designee, Title
Certificate of INSERVICE INSPECTION
I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors
and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of Hartford. CT
have inspected the components described in the Owners Report during the period - -/-O 'Z to c 4 -a03, and state that
to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described
in this Owner's Report in accordance with the requirements of the ASME Code, Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning
the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor
his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising
from or connected with this inspection.
Commissions NB7741, I, N, IS, A WIS 100024
Inspector's Signature National Board, State, Province, and Endorsements
Date 6 - /o ,20 d'-3
FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTAs Required by the Provisions of the ASME Code Section Xl
1. Owner Wisconsin Public Service Corporation
700 North Adams P.O.Box 19001 Green Bay, WI 54307-9001
2. Plant Kewaunee Nuclear Power Plant
N490 HWY 42 Kewaunee. WI 54216-9511
3. Work Performed By Nuclear Management Company. LLC
700 First Street. Hudson, Wisconsin 54016
4. Identification of System 35 Class 2 CHEMICAL AND VOLUME CONTROL
5. (a) Applicable Construction Code SEC. VIII DIV.1-1975
(b) Applicable Edition of Section Xl Utilized for Repairs or Replacements 1989
6. Identification of Components Repaired or Replaced and Replacement Components
Date 8/21/2002
Sheet I of 2
Unit No. 1
Work Order 02-004263
Type Code Sym. Stamp NA
Authorization No. NA
Expiration Date NA
Code Case NA
Name ofComponent
APD-11B
Name ofManufacturer
GREERHYDRAULICS
ManufacturerSerial No.
GHI-1846
NationalBoard No.
NA
OtherID
07001
YearBuilt
1975
Repaired,Replaced, orReplacement
REPLACEMENT
ASMECode
Stamped
Y-
7. Descripion of Work REPLACE DAMPENER SPRING ON CLASS 2 CHEMICAL AND VOLUME CONTROL SYSTEM CHARGING PUMP 1 BPULSATION DAMPENER.
8. Tests conducted Hydrostatic
Other :]
L Pneumatic ElPressure 2240 psi
Nominal Operating Pressure [ 3
Test Temp. 115 deg. F
Exempt :
9. Remarks NOT APPLICABLE.
Applicable Manufacturer's Data Reports to be Attached
NIS-2 (Back)
Sheet 2 of 2
Date: 8/21/2002
Name of Component: APD-IB
Work Order Number: 02-004263
Certificate of Compliance
We Certify that the statements made in the report are correct and this REPLACEMENT conforms to the rules of the
ASME Code Section Xl. Repair or Replacement
Type Code Symbol Stamp NA
Certificate of Authorization No. NA Expiration Date NA
Signed e &bLAJ 0 LU Date 4 ,20 aiOwner or Owner's Designee. Title
Certificate of INSERVICE INSPECTION
I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors
and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of Hartford, CT
have inspected the components described in the Owner's Report during the period A '/-OZ to 6 ' -03, and state that
to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described
in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning
the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor
his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising
from or connected with this inspection.
Commissions NB7741, I, N, IS, A WIS i10024
Inspector's Signature National Board, State, Province, and Endorsements
Date 6e -O ,20 03
FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTAs Required by the Provisions of the ASME Code Section Xi
1. Owner Wisconsin Public Service Corporation
700 North Adams P.O.Box 19001 Green Bay. WI 54307-9001
2. Plant Kewaunee Nuclear Power Plant
N490 HWY 42 Kewaunee. WI 54216-9511
3. Work Performed By Nuclear Management Company. LLC
700 First Street. Hudson, Wisconsin 54016
4. Identification of System 23 Class 2 CONTAINMENT SPRAY
5. (a) Applicable Construction Code B1 6.5-1967
(b) Applicable Edition of Section Xi Utilized for Repairs or Replacements 1989
6. Identification of Components Repaired or Replaced and Replacement Components
Date 5/113/2003
Sheet 1 of 2
Unit No. 1
Work Order 02-007269
Type Code Sym. Stamp NA
Authorization No. NA
Expiration Date NA
Code Case NA
Name ofComponent
CI-1003
Name ofManufacturer
WILLIAM POWELLCO.
ManufacturerSerial No.
NF
NationalBoard No.
NA
Other YearID Built
ICS022-001 1968
Repaired,Replaced, orReplacement
REPAIRED
ASMECode
Stamped
N---
7. Description of Work OPEN FOR INSPECTION CLASS 2 INTERNAL CONTAINMENT SPRAY SYSTEM 2" VALVE CI-1003.
8. Tests conducted Hydrostatic []
Other nPneumatic [1 Nominal Operating Pressure E3
Pressure 17.3 psi Test Temp. 78 deg. F
Exempt n
9. Remarks NOT APPLICABLE.
Applicable Manufacturer's Data Reports to be Attached
NIS-2 (Back)
Sheet 2 of 2
Date: 5/13/2003
Name of Component: Cl-1003
Work Order Number: 02-007269
Certificate of Compliance
We Certify that the statements made in the report are correct and this REPAIRED conforms to the rules of the
ASME Code Section XI. Repair or Replacement
Type Code Symbol Stamp NA
Certificate of Authorization No. NA Expiration Date NA
Signed B4,cp A 6ZLilt1I, Date t r 20 0 3Owner or Owner's Designee, Title
Certificate of INSERVICE INSPECTION
I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors
and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of Hartford, CT
have inspected the components described in the Owners Report during the period 6- j- . to 6 - -p3, and state that
to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described
in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning
the examinations and corrective measures described in this Owners Report. Furthermore, neither the Inspector nor
his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising
from or connected with this inspection.
Commissions NB7741, I, N, IS, A WIS 100024
Inspectors Signature National Board, State, Province, and Endorsements
Date & -/O 20 03
FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTAs Required by the Provisions of the ASME Code Section Xi
1. Owner Wisconsin Public Service Corporation
700 North Adams P.O.Box 19001 Green Bay. WI 54307-9001
2. Plant Kewaunee Nuclear Power Plant
N490 HWY 42 Kewaunee. WI 54216-9511
3. Work Performed By Nuclear Management Company. LLC
700 First Street. Hudson, Wisconsin 54016
4. Identification of System 36 Class 1 REACTOR COOLANT
5. (a) Applicable Construction Code ASME ill-1 968
(b) Applicable Edition of Section Xl Utilized for Repairs or Replacements 1989
6. Identification of Components Repaired or Replaced and Replacement Components
Date 5/9/2003
Sheet 1 of 2
Unit No. 1
Work Order 02-007295
Type Code Sym. Stamp NA
Authorization No. NA
Expiration Date NA
Code Case NA
Name ofComponent
PR-3B
Name of ManufacturerManufacturer Serial No.
CROSBY, ASHTON GAGE NFCOMPANY
NationalBoard No.
NA
Other YearID Built
RC008-002 1972
Repaired,Replaced, orReplacement
REPAIRED
ASMECode
Stamped
N
7. Description of Work REMOVE CLASS 1 REACTOR COOLANT SYSTEM 6 VALVE PR-3B FOR SETPOINT TESTING.
8. Tests conducted Hydrostatic LIOther E1
Pneumatic LI Nominal Operating Pressure RlPressure 2240 psi Test Temp. 543 deg. F
Exempt [L
9. Remarks NOT APPLICABLE.
Applicable Manufacturers Data Reports to be Attached
NIS-2 (Back)Sheet 2 of 2
Date: 5/9/2003
Name of Component: PR-3B
Work Order Number: 02-007295
Certificate of Compliance
We Certify that the statements made in the report are correct and this REPAIRED conforms to the rules of the
ASME Code Section XI. Repair or Replacement
Type Code Symbol Stamp NA
Certificate of Authorization No. NA Expiration Date NA
Signed _____ Date 4 20 o3Owner or Owner's Designee, Title
Certificate of INSERVICE INSPECTION
I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors
and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of Hartford, CT
have inspected the components described in the Owner's Report during the period : /-02 to 6 -' ° and state that
to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described
in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning
the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor
his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising
from or connected with this inspection.
Commissions NB7741, I, N, IS, A WIS 100024
1nqnsctonr' Rinnature National Board, State, Province, and Endorsements
Date 6 - /0 ,20 0
FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTAs Required by the Provisions of the ASME Code Section Xi
1. Owner Wisconsin Public Service Corporation
700 North Adams P.O.Box 19001 Green Bay. WI 54307-9001
2. Plant Kewaunee Nuclear Power Plant
N490 HWY 42 Kewaunee. WI 54216-9511
3. Work Performed By Nuclear Management Company. LLC
700 First Street. Hudson. Wisconsin 54016
4. Identification of System 35 Class 2 CHEMICAL AND VOLUME CONTROL
5. (a) Applicable Construction Code B31.1-1967
(b) Applicable Edition of Section Xi Utilized for Repairs or Replacements 1989
6. Identification of Components Repaired or Replaced and Replacement Components
Date 5/20/2003
Sheet 1 of 2
Unit No. 1
Work Order 02-007418
Type Code Sym. Stamp NA
Authorization No. NA
Expiration Date NA
Code Case NA
Name ofComponent
CVC-10
Name ofManufacturer
KEROTEST MFGCORP
ManufacturerSerial No.
NV-143
NationalBoard No.
NA
OtherED
CS100-005
YearBuilt
1973
Repaired,Replaced, orReplacement
REPAIRED
ASMECode
Stamped
N
7. Description of Work OPEN FOR INSPECTION CLASS 2 CHEMICAL AND VOLUME CONTROL SYSTEM 2" VALVE CVC-10.
8. Tests conducted Hydrostatic [
Other LIPneumatic [] Nominal Operating Pressure [x]
Pressure 2245 psi Test Temp. 548 deg.F
Exempt [
9. Remarks NOT APPLICABLE.
Applicable Manufacturer's Data Reports to be Attached
NIS-2 (Back)Sheet 2 of 2
Date: 5/20/2003
Name of Component: CVC-10
Work Order Number: 02-007418
Certificate of Compliance
We Certify that the statements made in the report are correct and this REPAIRED conforms to the rules of the
ASME Code Section Xi. Repair or Replacement
Type Code Symbol Stamp NA
Certificate of Authorization No. NA Expiration Date NA
Signed CPX J1 &M,2"V &LM/l Date 20 03Owner or Owner's Designee, Title
Certificate of INSERVICE INSPECTION
I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors
and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of Hartford, CT
have inspected the components described in the Owner's Report during the period '1 -IO to 4 -6 03, and state that
to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described
in this Owner's Report in accordance with the requirements of the ASME Code, Section Xi.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning
the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor
his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising
from or connected with this inspection.
,_z' G oet-~ - Commissions NB7741, I, N. IS, A WIS 100024Inspectors Signature National Board, State, Province, and Endorsements
Date t- /° , 20 03
FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTAs Required by the Provisions of the ASME Code Section Xi
1. Owner Wisconsin Public Service Corporation
700 North Adams P.O.Box 19001 Green Bay, WI 54307-9001
2. Plant Kewaunee Nuclear Power Plant
N490 HWY 42 Kewaunee. WI 54216-9511
3. Work Performed By Nuclear Management Company, LLC
700 First Street. Hudson. Wisconsin 54016
4. Identification of System 35 Class 1 CHEMICAL AND VOLUME CONTROL
5. (a) Applicable Construction Code B31.1-1967
(b) Applicable Edition of Section Xi Utilized for Repairs or Replacements 1989
6. Identification of Components Repaired or Replaced and Replacement Components
Date 5/13/2003
Sheet 1 of 2
Unit No. 1
Work Order 02-007419
Type Code Sym. Stamp NA
Authorization No. NA
Expiration Date NA
Code Case NA
Name ofComponent
CVC-205B
Name ofManufacturer
KEROTESTMANUFACTURING
ManufacturerSerial No.
NU321
NationalBoard No.
NA
Other YearID Built
CS100-001 1973
Repaired,Replaced, orReplacement
REPAIRED
ASMECode
Stamped
N
.
7. Description of Work OPEN FOR INSPECTION CLASS 1 CHEMICAL AND VOLUME CONTROL SYSTEM 2" VALVE CVC-205B.
8. Tests conducted Hydrostatic nOther [
Pneumatic n Nominal Operating Pressure 3Pressure 2240 psi Test Temp. 543 deg. F
Exempt LI
9. Remarks NOT APPLICABLE.
Applicable Manufacturer's Data Reports to be Attached
NIS-2 (Back)
Sheet 2 of 2
Date: 5/13/2003
Name of Component: CVC-205B
Work Order Number: 02-007419
Certificate of Compliance
We Certify that the statements made in the report are correct and this REPAIRED conforms to the rules of the
ASME Code Section Xl. Repair or Replacement
Type Code Symbol Stamp NA
Certificate of Authorization No. NA Expiration Date NA
Signed get "O aaJ4 I4l &WL Date .20 aOwner or Owner's Designee, Title
Certificate of INSERVICE INSPECTION
I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors
and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of Hartford, CT
have inspected the components described in the Owner's Report during the period c} '/- 1' . to / -6 -Al, and state that
to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described
in this Owner's Report in accordance with the requirements of the ASME Code, Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning
the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor
his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising
from or connected with this inspection.
& _ 7 1*1,_ .Commissions NB7741, I, N, IS, A WIS 100024InspectoF sSignature National Board, State, Province, and Endorsements
Date 6-/0 ,20 03
FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTAs Required by the Provisions of the ASME Code Section Xi
1. Owner Wisconsin Public Service Corporation
700 North Adams P.O.Box 19001 Green Bay. WI 54307-900t
2. Plant Kewaunee Nuclear Power Plant
N490 HWY 42 Kewaunee. WI 54216-9511
3. Work Performed By Nuclear Management Company. LLC
700 First Street. Hudson, Wisconsin 54016
4. Identification of System 35 Class 1 CHEMICAL AND VOLUME CONTROL
5. (a) Applicable Construction Code B31.1-1967
(b) Applicable Edition of Section Xl Utilized for Repairs or Replacements 1989
6. Identification of Components Repaired or Replaced and Replacement Components
Date 5/13/2003
Sheet 1 of 2
Unit No. 1
Work Order 02-007420
Type Code Sym. Stamp NA
Authorization No. NA
Expiration Date NA
Code Case NA
Name ofComponent
CVC-206A
Name ofManufacturer
KEROTESTMANUFACTURING
ManufacturerSerial No.
NF
NationalBoard No.
NA
Other YearID Built
CS100-004 1973
Repaired,Replaced, orReplacement
REPAIRED
ASMECode
Stamped
N
7. Description of Work OPEN FOR INSPECTION CLASS 1 CHEMICAL AND VOLUME CONTROL SYSTEM 2" VALVE CVC-206A.
8. Tests conducted Hydrostatic 2
Other El
Pneumatic n Nominal Operating Pressure 3Pressure 2240 psi Test Temp. 543 deg. F
Exempt 1
9. Remarks NOT APPLICABLE.
Applicable Manufacturer's Data Reports to be Attached
NIS-2 (Back)Sheet 2 of 2
Date: 5/13/2003
Name of Component: CVC-206A
Work Order Number: 02-007420
Certificate of Compliance
We Certify that the statements made in the report are correct and this REPAIRED conforms to the rules of the
ASME Code Section Xi. Repair or Replacement
Type Code Symbol Stamp NA
Certificate of Authorization No. NA Expiration Date NA
Signed (e' IIM 0 Date .i 20 03Owner or Owner's Designee, Title
Certificate of INSERVICE INSPECTION
I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors
and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of Hartford, CT
have inspected the components described in the Owners Report during the period .7 -/- A to 6~ -' ° 3, and state that
to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described
in this Owners Report in accordance with the requirements of the ASME Code, Section Xl.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning
the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor
his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising
from or connected with this inspection.
- X L ^ Commissions NB7741, I, N, IS, A WIS 100024
Inspector's Signature National Board, State, Province, and Endorsements
Date 6/O - 0 3 ,20 O 3
FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTAs Required by the Provisions of the ASME Code Section Xi
1. Owner Wisconsin Public Service Corporation
700 North Adams P.O.Box 19001 Green Bay. WI 54307-9001
2. Plant Kewaunee Nuclear Power Plant
N490 HWY 42 Kewaunee. WI 54216-9511
3. Work Performed By Nuclear Management Company. LLC
700 First Street. Hudson, Wisconsin 54016
4. Identification of System 35 Class 1 CHEMICAL AND VOLUME CONTROL
5. (a) Applicable Construction Code B31.1-1967
(b) Applicable Edition of Section Xi Utilized for Repairs or Replacements 1989
6. Identification of Components Repaired or Replaced and Replacement Components
Date 5/13/2003
Sheet 1 of 2
Unit No. 1
Work Order 02-007421
Type Code Sym. Stamp NA
Authorization No. NA
Expiration Date NA
Code Case NA
Name ofComponent
CVC-206B
Name ofManufacturer
KEROTESTMANUFACTURING
ManufacturerSerial No.
NU139
NationalBoard No.
NA
Other YearID Built
CS 100-003 1973
Repaired,Replaced, orReplacement
REPAIRED
ASMECode
Stamped
N
7. Description of Work OPEN FOR INSPECTiON CLASS 1 CHEMICAL AND VOLUME CONTROL SYSTEM 2" VALVE CVC-206B.
8. Tests conducted Hydrostatic DOther []
Pneumatic Nominal Operating Pressure [23
Pressure 2240 psi Test Temp. 543 deg. F
Exempt l
9. Remarks NOT APPLICABLE
Applicable Manufacturers Data Reports to be Attached
NIS-2 (Back)
Sheet 2 of 2
Date: 5/13t2003
Name of Component: CVC-206B
Work Order Number: 02-007421
Certificate of Compliance
We Certify that the statements made in the report are correct and this REPAIRED conforms to the rules of the
ASME Code Section XI. Repair or Replacement
Type Code Symbol Stamp NA
Certificate of Authorization No. NA Expiration Date NA
Signed Ca eAA cb~u? 6l Date 6 4 2003Owner or Owner's Designee, Title
Certificate of INSERVICE INSPECTION
I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors
and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of Hartford, CT
have inspected the components described in the Owners Report during the period J -/ - ° Z to 6 6 -. 3 and state that
to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described
in this Owners Report in accordance with the requirements of the ASME Code, Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning
the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor
his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising
from or connected with this inspection.
Commissions NB7741, I, N, IS, A WIS 100024
U Inspectorlsignature National Board, State, Province, and Endorsements
Date 6- /4p ,20 O3
FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTAs Required by the Provisions of the ASME Code Section Xi
1. Owner Wisconsin Public Service Corooration
700 North Adams P.O.Box 19001 Green Say. WI 54307-9001
2. Plant Kewaunee Nuclear Power Plant
N490 HWY 42 Kewaunee. WI 54216-9511
3. Work Performed By Nuclear Management Comoany. LLC
700 First Street. Hudson, Wisconsin 54016
4. Identification of System 36 Class 1 REACTOR COOLANT
5. (a) Applicable Construction Code SEC. III-1987 ADD.
(b) Applicable Edition of Section Xl Utilized for Repairs or Replacements 1989
6. Identification of Components Repaired or Replaced and Replacement Components
Date 5/9/2003
Sheet 1 of 2
Unit No. 1
Work Order 02-007509
Type Code Sym. Stamp NA
Authorization No. NA
Expiration Date NA
Code Case NA
Repaired, ASMEName of Name of Manufacturer National Other Year Replaced, or Code
Component Manufacturer Serial No. Board No. ED Built Replacement Stamped
SG-1A- ANSALDO ENERGIA 0202 151 00035 2000 REPLACEMENT NHLMWB MILANO
7 -l ,nf W-rL, 09OI aV', r~i AQQ I I.~O.a~II REACTOR COOLANT SYSTEM STEAM GENERATOR 1A HOTLEG MANWAY STUD (1)I. -tb~lplI Vl --1 rroAvx was,
8. Tests conducted Hydrostatic D
Other nPneumatic n Nominal Operating Pressure nXPressure 2240 psi Test Temp. 543 deg. F
Exempt
9. Remarks NOT APPLICABLE.
Applicable Manufacturers Data Reports to be Attached
NIS-2 (Back)Sheet 2 of 2
Date: 5/9/2003
Name of Component: SG-1A-HLMWB
Work Order Number: 02-007509
Certificate of Compliance
We Certify that the statements made in the report are correct and this REPLACEMENT conforms to the rules of the
ASME Code Section Xi. Repair or Replacement
Type Code Symbol Stamp NA
Certificate of Authorization No. NA Expiration Date NA
Signed )% ggi e. )PAO LO &&bi Date .L ,20 o3Owner or Owner's Designee, Title
Certificate of INSERVICE INSPECTION
I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors
and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of Hartford, CT
have inspected the components described in the Owner's Report during the period e -/%O to L -Z -L , and state that
to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described
in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning
the examinations and corrective measures described In this Owner's Report. Furthermore, neither the Inspector nor
his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising
from or connected with this inspection.
t_ _ _ _ _ _ Commissions NB7741, I, N, IS, A WIS 100024
Inspector's Signature National Board, State, Province, and Endorsements
Date eV /° 20 OJ3
FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTAs Required by the Provisions of the ASME Code Section Xi
1. Owner Wisconsin Public Service Corporation
700 North Adams P.O.Box 19001 Green Bay. WI 54307-9001
2. Plant Kewaunee Nuclear Power Plant
N490 HWY 42 Kewaunee. WI 54216-9511
3. Work Performed By Nuclear Manaaement Company. LLC
700 First Street. Hudson. Wisconsin 54016
4. Identification of System 36 Class 1 REACTOR COOLANT
5. (a) Applicable Construction Code SEC.111-1987 ADD.
(b) Applicable Edition of Section Xi Utilized for Repairs or Replacements 1989
Date 5/9/2003
Sheet 1 of 2
Unit No. 1
Work Order 02-007509
Type Code Sym. Stamp NA
Authorization No. NA
Expiration Date NA
Code Case NA
6. Identification of Components Repaired or Replaced and Replacement Components
Name ofComponent
SG-1A-CLMWB
Name ofManufacturer
ANSALDO ENERGIAMILANO
ManufacturerSerial No.
0202
NationalBoard No.
151
Other
ID
00035
YearBuilt
2000
Repaired,Replaced, orReplacement
REPLACEMENT
ASMECode
Stamped
N
.
-
7. Description of Work REPLACE CLASS 1 REACTOR COLLANT SYSTEM STEAM GENERATOR lA COLDLEG MANWAY STUDS (21 AND1 MANWAY NUT..
8. Tests conducted Hydrostatic n Pneumatic aOther 1I Pressure 2240 psi
Nominal Operating Pressure pi Exempt LITest Temp. 543 deg. F
9. Remarks NOT APPLICABLE.
Applicable Manufacturer's Data Reports to be Attached
NIS-2 (Back)Sheet 2 of 2
Date: 519/2003
Name of Component: SG-1A-CLMWB
Work Order Number: 02-007509
Certificate of Compliance
We Certify that the statements made in the report are correct and this REPLACEMENT conforms to the rules of the
ASME Code Section Xl. Repair or Replacement
Type Code Symbol Stamp NA
Certificate of Authorization No. NA Expiration Date NA
Signed &Aaa/n0h2it &flv C0IXV Date 6n.L4,20 aOwner or Owners Designee, Title
Certificate of INSERVICE INSPECTION
I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors
and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of Hartford, CT
have inspected the components described in the Owners Report during the period c(; /-1-OX to & -' -O'3, and state that
to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described
in this Owner's Report in accordance with the requirements of the ASME Code, Section Xi.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning
the examinations and corrective measures described in this Owners Report. Furthermore, neither the Inspector nor
his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising
from or connected with this inspection.
Commissions NB7741, I, N, IS, A WIS 100024
Inspectors Signature National Board, State, Province, and Endorsements
Date 6 - /O ,20 03
FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTAs Required by the Provisions of the ASME Code Section XI
1. Owner Wisconsin Public Service Corporation
700 North Adams P.O.Box 19001 Green Bay. WI 54307-9001
2. Plant Kewaunee Nuclear Power Plant
N490 HWY 42 Kewaunee. WI 54216-9511
3. Work Performed By Nuclear Management Company. LLC
700 First Street. Hudson, Wisconsin 54016
4. Identification of System 36 Class 1 REACTOR COOLANT
5. (a) Applicable Construction Code SEC. 111-1987 ADD
(b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989
6. Identification of Components Repaired or Replaced and Replacement Components
Date 5/9/2003
Sheet 1 of 2
Unit No. 1
Work Order 02-007509
Type Code Sym. Stamp NA
Authorization No. NA
Expiration Date NA
Code Case NA
Name ofComponent
SG-1 B-HLMWB
Name ofManufacturer
ANSALDO ENERGIAMILANO
ManufacturerSerial No.
0201
NationalBoard No.
150
Other
ED
00036
YearBuilt
2000
Repaired,Replaced, orReplacement
REPLACEMENT
ASMECode
Stamped
N
7. Description of Work REPLACE CLASS 1 REACTOR COOLANT SYSTEM STEAM GENERATOR I1 HOT LEG MANWAY NUT.
8. Tests conducted Hydrostatic nOther [1
Pneumatic El Nominal Operating Pressure RPressure 2240 psi Test Temp. 543 deg. F
Exempt []
9. Remarks NOT APPLICABLE.
Applicable Manufacturer's Data Reports to be Attached
NIS-2 (Back)Sheet 2 of 2
Date: 5/9/2003
Name of Component: SG-1 B-HLMWB
Work Order Number: 02-007509
Certificate of Compliance
We Certify that the statements made in the report are correct and this REPLACEMENT conforms to the rules of the
ASME Code Section XI. Repair or Replacement
Type Code Symbol Stamp NA
Certificate of Authorization No. NA Expiration Date NA
Signed ° CCirnv tl, Date ,20 0 kOwner or Owner's Designee, Title
Certificate of INSERVICE INSPECTION
I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors
and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of Hartford, CT
have inspected the components described in the Owners Report during the period a2 -/-02 to 4 - -03, and state that
to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described
in this Owner's Report in accordance with the requirements of the ASME Code, Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning
the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor
his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising
from or connected with this inspection.
Commissions NB7741, I, N, IS, A WIS 100024
Inspector's Signature National Board, State, Province, and Endorsements
Date 6 -/0 ,2o 3
FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTAs Required by the Provisions of the ASME Code Section Xi
1. Owner Wisconsin Public Service Corporation
700 North Adams P.O.Box 19001 Green Bay. WI 54307-9001
2. Plant Kewaunee Nuclear Power Plant
N490 HWY 42 Kewaunee. WI 54216-9511
3. Work Performed By Nuclear Management Company, LLC
700 First Street. Hudson. Wisconsin 54016
4. Identification of System 36 Class 1 REACTOR COOLANT
5. (a) Applicable Construction Code SEC. 1l1-1 987 ADD.
(b) Applicable Edition of Section Xl Utilized for Repairs or Replacements 1989
6. Identification of Components Repaired or Replaced and Replacement Components
Date 5/9/2003
Sheet 1 of 2
Unit No. 1
Work Order 02-007509
Type Code Sym. Stamp NA
Authorization No. NA
Expiration Date NA
Code Case NA
Name ofComponent
SG-1 B-CLMWB
Name ofManufacturer
ANSALDO ENERGIAMILANO
ManufacturerSerial No.
0201
NationalBoard No.
150
OtherID
00036
YearBuilt
2000
Repaired,Replaced, orReplacement
REPLACEMENT
ASMECode
Stamped
N-
7. Description of Work REPLACE CLASS 1 REACTOR COOLANT SYSTEM STEAM GENERATOR 18 COLD LEG MANWAY STUD (1) AND4 MANWAY NUTS.
8. Tests conducted Hydrostatic [] Pneumatic []Other n Pressure 2240 psi
Nominal Operating Pressure EJii Test Temp. 543 deg. F
Exempt D
9. Remarks NOT APPLICABLE.
Applicable Manufacturer's Data Reports to be Attached
NIS-2 (Back)
Sheet 2 of 2
Date: 5/9/2003
Name of Component: SG-1B-CLMWB
Work Order Number 02-007509
Certificate of Compliance
We Certify that the statements made in the report are correct and this REPLACEMENT conforms to the rules of the
ASME Code Section Xi. Repair or Replacement
Type Code Symbol Stamp NA
Certificate of Authorization No. NA Expiration Date NA
Signed e A : . P 0ALWrf Date 4 20 0Owner or Owner's Designee, Title
Certificate of INSERVICE INSPECTION
I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors
and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of Hartford, CT
have inspected the components described in the Owners Report during the period A?-/ -03 to ; -' -t-3, and state that
to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described
in this Owners Report in accordance with the requirements of the ASME Code, Section Xl.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning
the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor
his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising
from or connected with this inspection.
Commissions NB7741, I, N, IS, A WIS 100024
Inspector's ignature National Board, State, Province, and Endorsements
Date 6- /O ,20 0k3
FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTAs Required by the Provisions of the ASME Code Section Xi
1. Owner Wisconsin Public Service Corporation
700 North Adams P.O.Box 19001 Green Bay. WI 54307-9001
2. Plant Kewaunee Nudear Power PlantN490 HWY 42 Kewaunee. WI 54216-9511
3. Work Performed By Nuclear Management Company. LLC
700 First Street. Hudson, Wisconsin 54016
4. Identification of System 21 Class 2 SPENT FUEL POOL COOLING
5. (a) Applicable Construction Code B31.1-1967
(b) Applicable Edition of Section Xl Utilized for Repairs or Replacements 1989
6. Identification of Components Repaired or Replaced and Replacement Components
Date 5/30/2002
Sheet 1 of 2
Unit No. 1
Work Order 02-007734
Type Code Sym. Stamp NA
Authorization No. NA
Expiration Date NA
Code Case NA
Repaired, ASMEName of Name of Manufacturer National Other Year Replaced, or Code
Component Manufacturer Serial No. Board No. ID Built Replacement Stamped
FPC-1100 ITT GRINNEL VALVE NF NA FPCO07-00 1970 REPLACEMENT NCOMPANY
7. Description of Work REPLACE DIAPHRAGM ON CLASS 2 SPENT FUEL POOL COOLING AND CLEAN-UP SYSTEM 2" VALVE FPC-1100.
8. Tests conducted Hydrostatic [] Pneumatic j1
Other [ Pressure 64 psNominal Operating Pressure M
;i Test Temp. 60 deg. F
Exempt R
9. Remarks NOT APPLICABLE.
Applicable Manufacturer's Data Reports to be Attached
NIS-2 (Back)Sheet 2 of 2
Date: 5/30/2002
Name of Component: FPC-1100
Work Order Number. 02-007734
Certificate of Compliance
We Certify that the statements made in the report are correct and this REPLACEMENT conforms to the rules of the
ASME Code Section Xi. Repair or Replacement
Type Code Symbol Stamp NA
Certificate of Authorization No. NA Expiration Date NA
Signed I9L4 l pZ d4tW Date .20 dOwner or Owner's Designee, Title
Certificate of INSERVICE INSPECTION
I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors
and the State or Province of Wisconsin and employed by Hartford Steam Boiler Inspection and Ins. Co. of Hartford, CT
have inspected the components described in the Owners Report during the period on -/-O.Z to G -6 0-, and state that
to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described
in this Owners Report in accordance with the requirements of the ASME Code, Section Xi.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning
the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor
his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising
from or connected with this inspection.
4 1 aL-* Commissions NB7741, I, N, IS, A WIS 100024Inspector's signature National Board, State, Province, and Endorsements
Date C ' /° ,2o0°3
FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTAs Required by the Provisions of the ASME Code Section Xi
1. Owner Wisconsin Public Service Corporation
700 North Adams P.O.Box 19001 Green Bay. WI 54307-9001
2. Plant Kewaunee Nuclear Power Plant
N490 HWY 42 Kewaunee, WI 54216-9511
3. Work Performed By Nuclear Management Company. LLC
700 First Street. Hudson, Wisconsin 54016
4. Identification of System 36 Class 1 REACTOR COOLANT
5. (a) Applicable Construction Code NA
(b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989
6. Identification of Components Repaired or Replaced and Replacement Components
Date 5/9/2003
Sheet 1 of 2
Unit No. 1
Work Order 02-008856
Type Code Sym. Stamp NA
Authorization No. NA
Expiration Date NA
Code Case NA
Name ofComponent
RCP-1A
Name ofManufacturer
WESTINGHOUSE
ManufacturerSerial No.
1-618J871-GO1
NationalBoard No.
NA
Other
ED
00037
YearBuilt
1970
Repaired,Replaced, orReplacement
REPLACEMENT
ASMECode
Stamped
N-
7. Description of Work REPLACE CLASS 1 REACTOR COOLANT PUMP lA SHAFT. INTERNALS. SEAL PACKAGE AND MOTORINCLUDING FLANGE CONNECTIONS TO CLASS 1 SEAL WATER CVC SYSTEM (3 TOTAL). CLASS 3COMPON