KLEA Energy Analyzer
• Moduler design• No connector cables• No fixing screws• State of the art technology
mounting on panelsconnection to system Easy
Data Collection Platform
Dual Source Energy Measurement
• All forms of energy can be collected by one KLEA.• 2 Digital I/O is standart in KLEA.• Plus 5 I/O is optional.• User can collect data from gas, water and/or pressure meters.• Production quantity can be collected by a limit switch or a dry contact coming from a proximity sensor.• User can calculate total consumption of all forms of energy and calculate energy cost per product.
• Generators produces much more expensive energy compared to utility supply.• Klea has generator input and it is activated once generator is on.• Users can set Tariff 2 to measure genset usage as a power supply and this brings users to identify the exact cost of the energy.
QuantityCounting
WaterMeter
GasMeter
KLEA
DistributionPanel
MOBDUS
ETORTCP/IP
LOAD NETWORK
MOBDUSRS 485
UtilityGenset
KLEA
ETOR
TCP/IP
Multi-Tariff Energy Measurement
• In addition to Tariff 2, Tariff 1 is splitted into three with adjustable start & end times for each sub-tariff.• User can use these sub-tariffs in order to measure energy consumption for different shifts in a facility.• Tariff 1-1, 1-2 and 1-3 values are also saved in non-volatile memory. User can read these values from the screen remotely Modbus communication.
Demand Management
Data Logging
• User can adjust demand period between 1 to 60 minutes.• Klea keeps demand for I, P ,Q, and, S for each phase.• Klea monitors P, Q, S and I values and gets the average values of 4 parameters for each demand period.• Klea logs the maximum value of the average values in a month.• Klea keeps 4 months demand logs for 4 parameters with time stamp.• P, Q, S and I values are measured for each phase and sum.
• Klea measures 68 different energy parameters.• Klea logs 80 days hourly 240 days daily 36 months monthly real time measurements of 68 parameters.• Klea logs 4 months demand values.• Klea logs 50 recent alarms with time stamp.• 1 MB Memory
T1-1
12
6
T1-3
T1-2
3
4
57
8
10
11
2
1
9
Surge Withstand 100 A/1 sec
Signal Waveform Monitoring
Programmable Analog Outputs
Klea current inputs can withstand surges upto 100 A for 1 second.
In medium voltage applications, current transformers may generate peak currents in secondary windings. These peak values may reach upto 100 A and as a result of this current inputs of the analyzer may burn out and create an open circuit for secondary connections ofthe CT.
This may result with an explosion on CT since secondary side is open circuited.
• Klea’s high sampling rate enables the user to monitor a real time signal waveform.• Klea’s sampling rate per period is 512.• User can monitor the effects of harmonics on the system from this screen.
• Klea can be used as an energy transducer in substation automation projects.• Some models have either 2 or 4 programmable analog outputs and user can set any measured parameter to be disclosed with any of the output channel.
100 A
1 sec.5 A
Accuracy Class (0,2s)
-
-
-
IEC 62053-22 Class 0.2S
IEC 62053-23 Class 2
-
-
-
-
-
-
-
10 % Ib ≤ I ≤ Imax 0,5 Ind to 0,8 Cap
5 % Ib ≤ I ≤ Imax 0,25 Ind to 0,25 Cap
10 % Ib ≤ I ≤ Imax 0,5 Ind to 0,8 Cap
0 to 49999999999
0 to 49999999999
45 - 65 Hz
20 % Ib ≤ I ≤ Imax
20 % Ib ≤ I ≤ Imax
Umin ≤ U ≤ Umax
0,5 Ind to 0,8 Cap
0 % to 20 %
0 % to 100 %
0,2
1
0,2
0,2
2
0,05
0,2
0,5
0,2
0,5
1
1
Total active power
Total reactive power
Total apparent power
Total active energy
Total reactive energy
Frequency
Phase current
Neutral current
Voltage
Power factor
Total harmonic distortion voltage
Total harmonic distortion current
P
QV
SA
EA
ERV
f
I
INc
U
PFA
THDV
THDI
FunctionSymbol Function
FunctionPerformance ClassAccording to IEC
61557-12 Measuring Range
OtherComplementaryCharacteristics
Other Features• Graphical LCD• Language Support• Harmonics Measurement upto 51• Advanced Alarm Settings• Real Time Clock
GeneralGraphical LCD 6 buttonsPassword ProtectionSupply Voltage ACSupply Voltage DCCurrent Transformer RatioVoltage Transformer RatioConnection TypeMeasurement in QuadrantsNetworks Accuracy Class VoltageAccuracy Class CurrentAccuracy Class Active EnergyNumber of Measurement in a periodPower ConsumptionPower Quality MeasurementsHarmonics / current and voltageTHD-Voltage in %THD-Current in %Phasor DiagramData LoggingAverage, Minimum, Maximum ValuesAlarmsTime Stamp DemandVoltage Measurement InputOvervoltage CategoryMeasured Range L-NMeasured Range L-LMeasured Frequency Range Power ConsumptionSampling Freq.between 45-65 HzCurrent Measurement InputRated CurrentMeasurement RangeOvervoltage CategoryMeasurement Surge VoltagePower ConsumptionPeak current for 1 secSampling Freq.between 45-65 HzInput Outputs • Relay Outputs Max. Switching Current Max. Switching Voltage Max. Switching Power • Digital Inputs Minimum Counting Frequency Input Present or Not • Digital Outputs Switching Voltage Range Minimum Switching Frequency Isolation Level • Analog Outputs Range of Outputs 0-5 V, 0-10 V, -5-5 V, -10-10V, 0-20 mA, 4-20 mA IsolationMechanical PropertiesWeightProtection ClassAssembly TypeDimensions • Cable Cross Sections Supply Voltage, Current, Relay Outputs Stranded: Solid:
Digital I/O, RS 485 Stranded: Solid:
Ambient ConditionsOperating TemperatureStorage TemperatureRelative Humidity (no condensation)Communication and OthersModbus RTUBatteryReal Time ClockStandarts in ComplianceSafety requirements for electrical equipmentfor measurement, control, and laboratory use
EMC - Electrostatic discharge immunity testEMC - Radiated, radio-frequency, electromagnetic field immunity test
EMC - Electrical fast transient/burst immunity testEMC - Surge immunity testEMC - Immunity to conducted disturbances, induced by radio-frequency fieldsEMC - Power frequency magnetic field immunity testEMC - Voltage dips, short interruptions and voltage variations immunity testsIndustrial, scientific and medical equipment - Radio-frequencydisturbance characteristics - Limits and methods of measurement
606100 KLEA 320P
**
85-300 V AC85-300 V DC
1-5000 A1-5000 A
3P4W, 3P3W Aron4
TT, TN, IT0.20.20.5512
< 3VA
Upto 51st***
****
300 V Cat II1-300 Vrms2-500 Vrms45-65 Hz<0.1 VA25,6 kHz
6A0.01-6A
300 V Cat II2 kV
<0.2 VA100 A
25,6 kHz
210 A
250 VAC1250 VA
2100 Hz, 10 ms
Dry Contact2
5-30 VDC20 Hz, 50 ms3750 Vrms
0
--
0,404 kgIP 40 front, IP 20 rear
Panel MountW96xH96xD72
2,5 mm2 - 14AWG4mm2 - 12 AWG
2x1.5 mm2 - 2x16 AWG
1,5 mm2 - 16AWG1.5 mm2 - 16 AWG
2x0.75 mm2 - 2x18 AWG
-20 C …. +60 C..-30 C …. +80 C..
95%
***
300 VAC CAT II acc. to IEC 61010-1
EN 61000-4-2EN 61000-4-3
EN 61000-4-4EN 61000-4-5EN 61000-4-6
EN 61000-4-8EN 61000-4-11
EN 55011/A1:2010
606101 KLEA 370P
**
85-300 V AC85-300 V DC
1-5000 A1-5000 A
3P4W, 3P3W Aron4
TT, TN, IT0.20.20.5512
< 3VA
Upto 51st***
****
300 V Cat II1-300 Vrms2-500 Vrms45-65 Hz<0.1 VA25,6 kHz
6A0.01-6A
300 V Cat II2 kV
<0.2 VA100 A
25,6 kHz
210 A
250 VAC1250 VA
7100 Hz, 10 ms
Dry Contact7
5-30 VDC20 Hz, 50 ms3750 Vrms
0
--
0,428 kgIP 40 front, IP 20 rear
Panel MountW96xH96xD72
2,5 mm2 - 14AWG4mm2 - 12 AWG
2x1.5 mm2 - 2x16 AWG
1,5 mm2 - 16AWG1.5 mm2 - 16 AWG
2x0.75 mm2 - 2x18 AWG
-20 C …. +60 C..-30 C …. +80 C..
95%
***
300 VAC CAT II acc. to IEC 61010-1
EN 61000-4-2EN 61000-4-3
EN 61000-4-4EN 61000-4-5EN 61000-4-6
EN 61000-4-8EN 61000-4-11
EN 55011/A1:2010
606102 KLEA 322P
**
85-300 V AC85-300 V DC
1-5000 A1-5000 A
3P4W, 3P3W Aron4
TT, TN, IT0.20.20.5512
< 3VA
Upto 51st***
****
300 V Cat II1-300 Vrms2-500 Vrms45-65 Hz<0.1 VA25,6 kHz
6A0.01-6A
300 V Cat II2 kV
<0.2 VA100 A
25,6 kHz
210 A
250 VAC1250 VA
2100 Hz, 10 ms
Dry Contact2
5-30 VDC20 Hz, 50 ms3750 Vrms
2
*Isolated
0,428 kgIP 40 front, IP 20 rear
Panel MountW96xH96xD72
2,5 mm2 - 14AWG4mm2 - 12 AWG
2x1.5 mm2 - 2x16 AWG
1,5 mm2 - 16AWG1.5 mm2 - 16 AWG
2x0.75 mm2 - 2x18 AWG
-20 C …. +60 C..-30 C …. +80 C..
95%
***
300 VAC CAT II acc. to IEC 61010-1
EN 61000-4-2EN 61000-4-3
EN 61000-4-4EN 61000-4-5EN 61000-4-6
EN 61000-4-8EN 61000-4-11
EN 55011/A1:2010
**
85-300 V AC85-300 V DC
1-5000 A1-5000 A
3P4W, 3P3W Aron4
TT, TN, IT0.20.20.5512
< 3VA
Upto 51st***
****
300 V Cat II1-300 Vrms2-500 Vrms45-65 Hz<0.1 VA25,6 kHz
6A0.01-6A
300 V Cat II2 kV
<0.2 VA100 A
25,6 kHz
210 A
250 VAC1250 VA
2100 Hz, 10 ms
Dry Contact2
5-30 VDC20 Hz, 50 ms3750 Vrms
4
*Nonisolated
0,428 kgIP 40 front, IP 20 rear
Panel MountW96xH96xD72
2,5 mm2 - 14AWG4mm2 - 12 AWG
2x1.5 mm2 - 2x16 AWG
1,5 mm2 - 16AWG1.5 mm2 - 16 AWG
2x0.75 mm2 - 2x18 AWG
-20 C …. +60 C..-30 C …. +80 C..
95%
***
300 VAC CAT II acc. to IEC 61010-1
EN 61000-4-2EN 61000-4-3
EN 61000-4-4EN 61000-4-5EN 61000-4-6
EN 61000-4-8EN 61000-4-11
EN 55011/A1:2010
606103 KLEA 324P
Wiring Diagrams
3 Phase No Neutral Aron Connection
Dimensions (mm)
3 Phase Connection With Neutral (3P4W) 3 Phase Connection No Neutral (3P3W)
Top Related