SampleDrawings 02/16/17
Project #
Jamesway Incubator
Detail Drawings Sheet ListP1 ScheduleP2 ScheduleP3 HVAC - Top ViewP4 HVAC Isometric ViewP5 HVAC Incubator and Hatcher SectionsP6 HVAC Wash/Pull/Chick Rooms SectionsP7 Cold Water Pipping LayoutP8 Cold Water Pipping - Incubator RoomP9 Cold Water Pipping Isometric ViewP10 Cold Water Pipping - Hatcher RoomP11 Pipping Details - Incubator RoomsP12 Pipping Details - Hatcher RoomsP13 Humidity & Compressed AirP14 HVAC Isometric ViewP15 Guardian Controls - Low VoltageP16 Guardian Controls - PressureP17 Guardian Controls - High VoltageP18 Guardian Controls - Isometric ViewP19 Guardian Controls SectionP20 Guardian Controls NotesP21 Backup Alarm LayoutP22 Backup Alarm - Isometeric ViewP23 Hatchcom LayoutP24 Hatchcom - Isometric View
PROJECT DETAILS
REV.DRAWING NUMBERCHECKED BY
DATE
DRAWN BY
SCALE
CLIENT NAME
PROJECT NUMBER
THIS DRAWING IS FOR QUOTATION ONLY; IT IS NOTTO BE USED FOR CONSTRUCTION.
WHERE A DISCREPANCY OCCURS BETWEEN THISDRAWING AND ANY SITE
DIMENSIONS/SPECIFICATIONS, THIS MUST BEREPORTED BEFORE ANY OF THE WORK SHOWN ON
THIS DRAWING IS COMMENCED.
THE CONTENTS OF THIS DRAWING IS THE COPYRIGHTOF JAMESWAY INCUBATOR COMPANY INC AND MUST
NOT BE REPRODUCED IN WHOLE OR IN PARTWITHOUT THEIR WRITTEN CONSENT BEING GIVEN
AND RECEIVED.
JAMESWAY INCUBATOR COMPANY INC
NOTES
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
A
B
C
D
E
F
G
H
JAMESWAY IncubatorCompany Inc30 High Ridge CourtCambridge, Ontario, CanadaN1R 7L3Tel 519 624 4646Fax 519 624 [email protected]
Schedule
CR DM P1
02/02/17 Project #
Jamesway IncubatorSample
Drawings
Mechanical Equipment Schedule
Mark Manufacturer Location Type CoolingNo. ofStages Heating
Supply AirCFM
CoolingTotal
Tonnage
HeatingTotal
Capacity Voltage Phase Hertz FLAShippingWeight
RTU-1 Aaon, Inc. Egg Room RNB-011 Mechanical 2 NaturalGas
4400 CFM 11 156000 Btu 220 V 3 60 Hz 48 A 1735.00 lb
RTU-2 Aaon, Inc. Incubator Room 2 RNC-016 Mechanical 2 NaturalGas
6400 CFM 16 328000 Btu 220 V 3 60 Hz 20 A 2514.00 lb
RTU-3 Aaon, Inc. Incubator Room 1 RNC-016 Mechanical 2 NaturalGas
6400 CFM 16 328000 Btu 220 V 3 60 Hz 20 A 2514.00 lb
RTU-4 Aaon, Inc. Hatcher Room 2 RNA-008 Mechanical 2 NaturalGas
3200 CFM 8 102400 Btu 220 V 3 60 Hz 40 A 1191.00 lb
RTU-5 Aaon, Inc. Hatcher Room 1 RNA-008 Mechanical 2 NaturalGas
3200 CFM 8 102400 Btu 220 V 3 60 Hz 40 A 1191.00 lb
RTU-6 Aaon, Inc. Pull Room RNB-011 Mechanical 2 NaturalGas
4400 CFM 11 156000 Btu 220 V 3 60 Hz 48 A 1735.00 lb
RTU-7 Aaon, Inc. Wash Room RNA-008 Mechanical 2 NaturalGas
3200 CFM 8 102400 Btu 220 V 3 60 Hz 40 A 1191.00 lb
RTU-8 Aaon, Inc. Chick Room RNB-013 Mechanical 2 NaturalGas
5200 CFM 13 68300 Btu 220 V 3 60 Hz 63 A 1869.00 lb
RTU-9 Aaon, Inc. Chick Room RNB-013 Mechanical 2 NaturalGas
5200 CFM 13 68300 Btu 220 V 3 60 Hz 63 A 1869.00 lb
Exhaust FansLocation Mark Manufacturer Count Type Shutter Part
Egg Room EF-1 Multi-Fan 1 4E30Q - 12" HV1092Hatcher Room 2 EF-2 Multi-Fan 1 4E34Q - 14" HV1093Hatcher Room 1 EF-3 Multi-Fan 1 4E34Q - 14" HV1093Incubator Room 1 EF-4 Multi-Fan 1 4E40Q - 16" HV1094Incubator Room 2 EF-5 Multi-Fan 1 4E40Q - 16" HV1094Pull Room EF-6 Multi-Fan 1 4E34Q - 14" HV1093Clean Room EF-7 Multi-Fan 1 4E30Q - 12" HV1092Chick Room EF-8 Multi-Fan 1 4E40Q - 16" HV1094
PROJECT DETAILS
REV.DRAWING NUMBERCHECKED BY
DATE
DRAWN BY
SCALE
CLIENT NAME
PROJECT NUMBER
THIS DRAWING IS FOR QUOTATION ONLY; IT IS NOTTO BE USED FOR CONSTRUCTION.
WHERE A DISCREPANCY OCCURS BETWEEN THISDRAWING AND ANY SITE
DIMENSIONS/SPECIFICATIONS, THIS MUST BEREPORTED BEFORE ANY OF THE WORK SHOWN ON
THIS DRAWING IS COMMENCED.
THE CONTENTS OF THIS DRAWING IS THE COPYRIGHTOF JAMESWAY INCUBATOR COMPANY INC AND MUST
NOT BE REPRODUCED IN WHOLE OR IN PARTWITHOUT THEIR WRITTEN CONSENT BEING GIVEN
AND RECEIVED.
JAMESWAY INCUBATOR COMPANY INC
NOTES
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
A
B
C
D
E
F
G
H
JAMESWAY IncubatorCompany Inc30 High Ridge CourtCambridge, Ontario, CanadaN1R 7L3Tel 519 624 4646Fax 519 624 [email protected]
Schedule
CR DM P2
02/02/17 Project #
Jamesway IncubatorSample
Drawings
Duct ScheduleSystem Type Size Length
Return Air 20"x26" 7' - 3 3/8"Supply Air 22"x22" 4' - 11 13/32"Supply Air 25"x36" 1 1/2"Hatcher Room 1Return Air 13"x20" 2' - 5"Return Air 13"x32" 2' - 0 7/16"Supply Air 20"x20" 3' - 0 5/16"Supply Air 25"x22" 10 3/16"Hatcher Room 2Return Air 13"x20" 2' - 5"Return Air 13"x32" 2' - 0 7/16"Supply Air 20"x20" 3' - 0 5/16"Supply Air 25"x22" 10 3/16"Pull RoomReturn Air 18"x20" 10' - 1 3/8"Supply Air 22"x22" 2' - 11 3/32"Supply Air 22"x36" 3 29/32"
Duct ScheduleSystem Type Size Length
Return Air 15"x20" 11' - 9 31/32"Return Air 21"x50" 11 27/32"Supply Air 20"x20" 13' - 8 19/32"Chick RoomReturn Air 20"x20" 21' - 10 7/16"Return Air 45"x14" 7' - 6 23/32"Supply Air 24"x24" 17' - 2 19/32"Supply Air 36"x25" 3' - 10 5/16"Clean RoomSupply Air 20"x20" 3' - 6"Supply Air 22"x25" 9 1/16"Clean roomReturn Air 14"x20" 6' - 8"Return Air 20"x14" 2' - 0 7/16"Egg RoomReturn Air 14"x45" 2' - 1 19/32"
Air Terminal ScheduleType Count Size
Chick RoomReturn Filter 20x25x2 6 20"x25"Supply Grill 24x24 2 22"x22"Clean roomSupply Grill 20x20 5 18"x18"Return Filter 20x25x2 2 20"x25"Egg RoomSupply Grill 22x22 1 20"x20"Return Filter 20x25x2 7 20"x25"Hatcher Room 1Supply Grill 20x20 1 18"x18"Return Filter 20x20x2 1 20"x20"Hatcher Room 2Supply Grill 20x20 1 18"x18"Return Filter 20x20x2 1 20"x20"Pull RoomSupply Grill 22x22 1 20"x20"Return Filter 20x25x2 3 20"x25"
Circulating Pumps
Manufacturer Model Count
FlowRate
(GPM)FT. ofHead
HorsePower RPM
Disconnect SwitchModel
DisconnectSwitch Size
(AMP)Goulds 3ST1H5B4 2 100 60 3 3500 LBSRLT163PMZ33 16Goulds 4SH2L45A0 2 144 136 10 3450 LBSRLT163PMZ33 16
Chiller SpecificationCount Make Model
ELECTRICALComments
Flow Rate(GPM) Weight (lb)Freq. Volt. Phase
1 Trane CGAM035 60 Hz 220 V 3 35 Ton 45 1750
2P6
2P5
1P5
3P6
1P6
Egg Room
Incub
ator R
oom
1
Hatcher Room 2
Incub
ator R
oom
2
Pull Room
Clean room
Chick Room
Duc
t Siz
e22
"x22
"
Duct Size18"x20"
Duc
t Siz
e22
"x22
"Duct Size20"x26"
Duct Size20"x20"
Duct Size24"x24"
Duct Size24"x24"
Duct Size20"x20"
Duct Size20"x20"
Duc
t Siz
e13
"x20
"
Duct Size14"x20"
Duct Size20"x20"
EF-8
EF-6
EF-4
EF-1
EF-2
EF-7
EF-3
EF-5
Duct Size20"x20"
Duc
t Siz
e13
"x20
"
RTU-3
RTU-2
RTU-1
RTU-4
RTU-5
RTU-6
RTU-8
RTU-7
RTU-9RTU-8
Duc
t Siz
e20
"x20
"D
uct S
ize
20"x
20"
Duct Size15"x20"
Duct Size15"x20"
Duc
t Siz
e20
"x20
"D
uct S
ize
20"x
20"
Hatcher Room 1
PROJECT DETAILS
REV.DRAWING NUMBERCHECKED BY
DATE
DRAWN BY
SCALE
CLIENT NAME
PROJECT NUMBER
THIS DRAWING IS FOR QUOTATION ONLY; IT IS NOTTO BE USED FOR CONSTRUCTION.
WHERE A DISCREPANCY OCCURS BETWEEN THISDRAWING AND ANY SITE
DIMENSIONS/SPECIFICATIONS, THIS MUST BEREPORTED BEFORE ANY OF THE WORK SHOWN ON
THIS DRAWING IS COMMENCED.
THE CONTENTS OF THIS DRAWING IS THE COPYRIGHTOF JAMESWAY INCUBATOR COMPANY INC AND MUST
NOT BE REPRODUCED IN WHOLE OR IN PARTWITHOUT THEIR WRITTEN CONSENT BEING GIVEN
AND RECEIVED.
JAMESWAY INCUBATOR COMPANY INC
NOTES
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
A
B
C
D
E
F
G
H
JAMESWAY IncubatorCompany Inc30 High Ridge CourtCambridge, Ontario, CanadaN1R 7L3Tel 519 624 4646Fax 519 624 [email protected]
1 : 250
HVAC - Top View
CR DM P3
02/02/17 Project #
Jamesway IncubatorSample
Drawings1 : 2501 HVAC
PROJECT DETAILS
REV.DRAWING NUMBERCHECKED BY
DATE
DRAWN BY
SCALE
CLIENT NAME
PROJECT NUMBER
THIS DRAWING IS FOR QUOTATION ONLY; IT IS NOTTO BE USED FOR CONSTRUCTION.
WHERE A DISCREPANCY OCCURS BETWEEN THISDRAWING AND ANY SITE
DIMENSIONS/SPECIFICATIONS, THIS MUST BEREPORTED BEFORE ANY OF THE WORK SHOWN ON
THIS DRAWING IS COMMENCED.
THE CONTENTS OF THIS DRAWING IS THE COPYRIGHTOF JAMESWAY INCUBATOR COMPANY INC AND MUST
NOT BE REPRODUCED IN WHOLE OR IN PARTWITHOUT THEIR WRITTEN CONSENT BEING GIVEN
AND RECEIVED.
JAMESWAY INCUBATOR COMPANY INC
NOTES
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
A
B
C
D
E
F
G
H
JAMESWAY IncubatorCompany Inc30 High Ridge CourtCambridge, Ontario, CanadaN1R 7L3Tel 519 624 4646Fax 519 624 [email protected]
HVAC Isometric View
CR DM P4
02/17/17 Project #
Jamesway IncubatorSample
Drawings
1 HVAC Isometric View
Level 10"
Ground0.00'
Roof15.00'
Ground0"
Roof15' - 0"
RTU-3
EF-4
Incubator Room 1
P120
Duct Size20"x20"
Duct Size20"x20"
Level 10"
Ground0.00'
Roof15.00'
121314
Ground0"
Roof15' - 0"
RTU-4
EF-2
Duct Size20"x13"
Return Filter 20x20x2
Supply Grill 20x20
Hatcher Room 2 Hatcher Room 1P40 hatcher
EF-3
RTU-5
Return Filter 20x20x2
Supply Grill 20x20
P40 hatcher
Future expansion
PROJECT DETAILS
REV.DRAWING NUMBERCHECKED BY
DATE
DRAWN BY
SCALE
CLIENT NAME
PROJECT NUMBER
THIS DRAWING IS FOR QUOTATION ONLY; IT IS NOTTO BE USED FOR CONSTRUCTION.
WHERE A DISCREPANCY OCCURS BETWEEN THISDRAWING AND ANY SITE
DIMENSIONS/SPECIFICATIONS, THIS MUST BEREPORTED BEFORE ANY OF THE WORK SHOWN ON
THIS DRAWING IS COMMENCED.
THE CONTENTS OF THIS DRAWING IS THE COPYRIGHTOF JAMESWAY INCUBATOR COMPANY INC AND MUST
NOT BE REPRODUCED IN WHOLE OR IN PARTWITHOUT THEIR WRITTEN CONSENT BEING GIVEN
AND RECEIVED.
JAMESWAY INCUBATOR COMPANY INC
NOTES
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
A
B
C
D
E
F
G
H
JAMESWAY IncubatorCompany Inc30 High Ridge CourtCambridge, Ontario, CanadaN1R 7L3Tel 519 624 4646Fax 519 624 [email protected]
1/8" = 1'-0"
HVAC Incubator and Hatcher Sections
CR DM P5
02/02/17 Project #
Jamesway IncubatorSample
Drawings
1/8" = 1'-0"1 Incubator Room
1/8" = 1'-0"2 Hatcher Rooms
Level 10"
Ground0.00'
Roof15.00'
16 17 18
Ground0"
Roof15' - 0"
3P6
Chick RoomPull Room
RTU-9
RTU-7
Return Filter 20x25x2
Supply Grill 20x20
Return Filter 20x25x2
Supply Grill 24x24
EF-8
RTU-7
Duc
t Siz
e14
"x45
"
Duc
t Siz
e14
"x20
"
12
Egg Room
RTU-1
Duct Size26"x20"
Return Filter 20x25x2
Supply Grill 22x22
EF-1
Ground0.00'
Roof15.00'
3 4 6 8
Ground0"
Roof15' - 0"
1P6
EF-6
RTU-6
Supply Grill 22x22
Return Filter 20x25x2
Pull RoomPROJECT DETAILS
REV.DRAWING NUMBERCHECKED BY
DATE
DRAWN BY
SCALE
CLIENT NAME
PROJECT NUMBER
THIS DRAWING IS FOR QUOTATION ONLY; IT IS NOTTO BE USED FOR CONSTRUCTION.
WHERE A DISCREPANCY OCCURS BETWEEN THISDRAWING AND ANY SITE
DIMENSIONS/SPECIFICATIONS, THIS MUST BEREPORTED BEFORE ANY OF THE WORK SHOWN ON
THIS DRAWING IS COMMENCED.
THE CONTENTS OF THIS DRAWING IS THE COPYRIGHTOF JAMESWAY INCUBATOR COMPANY INC AND MUST
NOT BE REPRODUCED IN WHOLE OR IN PARTWITHOUT THEIR WRITTEN CONSENT BEING GIVEN
AND RECEIVED.
JAMESWAY INCUBATOR COMPANY INC
NOTES
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
A
B
C
D
E
F
G
H
JAMESWAY IncubatorCompany Inc30 High Ridge CourtCambridge, Ontario, CanadaN1R 7L3Tel 519 624 4646Fax 519 624 [email protected]
1/8" = 1'-0"
HVAC Wash/Pull/Chick Rooms Sections
CR DM P6
02/02/17 Project #
Jamesway IncubatorSample
Drawings
1/8" = 1'-0"1 Chick/Wash Room
1/8" = 1'-0"2 Egg room 1/8" = 1'-0"3 Pull Room
2P10
1P11
3"ø
4"ø
2"ø
1 1/4"ø
2 1/
2"ø
2 1/
2"ø
2 1/
2"ø
2 1/
2"ø
1 1/4"ø
2"ø
2"ø
4"ø
2 1/
2"ø
2 1/
2"ø
2 1/
2"ø2 1/
2"ø2 1/
2"ø
Chiller
Tank - 800 Gal
Pump 100 GPMPump 144 GPM
3"ø
Balancing Valve
Pressure Gauge
Balancing Valve
Check Valve
2 1/
2"ø
2 1/
2"ø
2 1/
2"ø
Check Valve
Pressure Gauge
Balancing Valve
Balancing Valve
Check Valve
Shut-Off Valve
Pressure Gauge
800 Gallons tank
Pump
Balancing Valve
Pressure GaugePressure Gauge
PROJECT DETAILS
REV.DRAWING NUMBERCHECKED BY
DATE
DRAWN BY
SCALE
CLIENT NAME
PROJECT NUMBER
THIS DRAWING IS FOR QUOTATION ONLY; IT IS NOTTO BE USED FOR CONSTRUCTION.
WHERE A DISCREPANCY OCCURS BETWEEN THISDRAWING AND ANY SITE
DIMENSIONS/SPECIFICATIONS, THIS MUST BEREPORTED BEFORE ANY OF THE WORK SHOWN ON
THIS DRAWING IS COMMENCED.
THE CONTENTS OF THIS DRAWING IS THE COPYRIGHTOF JAMESWAY INCUBATOR COMPANY INC AND MUST
NOT BE REPRODUCED IN WHOLE OR IN PARTWITHOUT THEIR WRITTEN CONSENT BEING GIVEN
AND RECEIVED.
JAMESWAY INCUBATOR COMPANY INC1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
A
B
C
D
E
F
G
H
JAMESWAY IncubatorCompany Inc30 High Ridge CourtCambridge, Ontario, CanadaN1R 7L3Tel 519 624 4646Fax 519 624 [email protected]
NOTES:1. THE WATER PIPING SYSTEM SHOULDINCLUDE PROPER PLUMBING HARDWARE TOMINIMIZE WATER HAMMER EFFECT. THISSYSTEM IS DESIGNED ONLY FOR
2. CONNECT TO THE FACILITY'S WATERSYSTEM. A FILTRATION SYSTEM IS STRONGLYRECOMMENDED TO MINIMIZE FUTUREBLOCKAGE IN LINES OR LEAKS THROUGHSOLENOIDS.3. PLEASE REFER TO CONNECTION IMAGES FORDETAILS.4. SYSTEM WATER PUMPS: SPECIFICATIONS TOBE DETERMINED. PLEASE USE CHILLERMANUFACTURER'S SPECIFICRECOMMENDATIONS.5. BALANCE VALVES & SYSTEM TO ACHIEVE US gal/min MINIMUM THROUGH EACHINCUBATOR ECU AND US gal/minMINIMUM THROUGH EACH HATCHER ECU, IFPRESENT.(a) WHERE AMBIENT TEMPERATURE GOESBELOW FREEZING, GLYCOL TO BE ADDED.(b) ALL PIPE WORK TO BE INSULADED.6. FLUSH SYSTEM OF DEBRIS BEFORECONNECTING TO INCUBATORS.7. PROVIDE PIPING SYSTEM AS PER ALL LOCALCODES. ALL PIPES, GAUGES, VALVES, FITTINGSETC. SUPPLIED BY OTHERS.8. ALL PIPING SYSTEM SUPPLIED (BY OTHERS).OFFICIAL START UP OF CHILLERS/BOILERS ISNOT PERFORMED BY JAMESWAY. THIS IS TO BEDONE BY A CERTIFIED PLUMBER.9. ALL PIPING CONNECTIONS TO INCUBATORSARE MADE WITH 1/2" DIA. COPPER PIPE.PROVIDE FLEXIBLE HOSE CONNECTION FROMSUPPLY PIPING TO INCUBATOR & HATCHERSCONNECTIONS.10. ALL PIPE DIMENSIONS LISTED AREINTERNAL DIAMETER.11. PIPES CAN BE COPPER, PVC OR PEX FORCOLD WATER.12. PIPES CAN BE COPPER, CPVC OR PEX FORHOT WATER.13. INSTALL AIR VENTS AT THE HIGHEST POINTOF EACH BRANCH & ANY OTHER REQUIREDLOCATIONS.14. DRAWINGS ARE SCHEMATICREPRESENTATIONS; ACTUAL EQUIPMENTLOCATIONS TO BE DETERMINED BY CERTIFIEDPLUMBER.
As indicated
Cold Water Pipping Layout
CR DM P7
02/02/17 Project #
Jamesway IncubatorSample
Drawings
12 P120 IINCUBATORS AND 6 P40 HATCHERS
144140
1 : 2501 Cold Water Pipping
1/8" = 1'-0"Cold Water Pipping Legend
14 15
2 1/2"ø2 1/2"ø
Balancing Valve
Shut-Off Valve
P120 P120
Incubator Room 1
P120
2 1/
2"ø
2 1/
2"ø
2 1/
2"ø
3/4"ø ø3/4"
ø3/4"
Shut-Off Valve
Shut-Off Valve
Balancing Valve
Check Valve
Shut-Off Valve
Pressure Gauge
800 Gallons tank
Pump
PROJECT DETAILS
REV.DRAWING NUMBERCHECKED BY
DATE
DRAWN BY
SCALE
CLIENT NAME
PROJECT NUMBER
THIS DRAWING IS FOR QUOTATION ONLY; IT IS NOTTO BE USED FOR CONSTRUCTION.
WHERE A DISCREPANCY OCCURS BETWEEN THISDRAWING AND ANY SITE
DIMENSIONS/SPECIFICATIONS, THIS MUST BEREPORTED BEFORE ANY OF THE WORK SHOWN ON
THIS DRAWING IS COMMENCED.
THE CONTENTS OF THIS DRAWING IS THE COPYRIGHTOF JAMESWAY INCUBATOR COMPANY INC AND MUST
NOT BE REPRODUCED IN WHOLE OR IN PARTWITHOUT THEIR WRITTEN CONSENT BEING GIVEN
AND RECEIVED.
JAMESWAY INCUBATOR COMPANY INC1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
A
B
C
D
E
F
G
H
JAMESWAY IncubatorCompany Inc30 High Ridge CourtCambridge, Ontario, CanadaN1R 7L3Tel 519 624 4646Fax 519 624 [email protected]
NOTES:1. THE WATER PIPING SYSTEM SHOULDINCLUDE PROPER PLUMBING HARDWARE TOMINIMIZE WATER HAMMER EFFECT. THISSYSTEM IS DESIGNED ONLY FOR
2. CONNECT TO THE FACILITY'S WATERSYSTEM. A FILTRATION SYSTEM IS STRONGLYRECOMMENDED TO MINIMIZE FUTUREBLOCKAGE IN LINES OR LEAKS THROUGHSOLENOIDS.3. PLEASE REFER TO CONNECTION IMAGES FORDETAILS.4. SYSTEM WATER PUMPS: SPECIFICATIONS TOBE DETERMINED. PLEASE USE CHILLERMANUFACTURER'S SPECIFICRECOMMENDATIONS.5. BALANCE VALVES & SYSTEM TO ACHIEVE US gal/min MINIMUM THROUGH EACHINCUBATOR ECU AND US gal/minMINIMUM THROUGH EACH HATCHER ECU, IFPRESENT.(a) WHERE AMBIENT TEMPERATURE GOESBELOW FREEZING, GLYCOL TO BE ADDED.(b) ALL PIPE WORK TO BE INSULADED.6. FLUSH SYSTEM OF DEBRIS BEFORECONNECTING TO INCUBATORS.7. PROVIDE PIPING SYSTEM AS PER ALL LOCALCODES. ALL PIPES, GAUGES, VALVES, FITTINGSETC. SUPPLIED BY OTHERS.8. ALL PIPING SYSTEM SUPPLIED (BY OTHERS).OFFICIAL START UP OF CHILLERS/BOILERS ISNOT PERFORMED BY JAMESWAY. THIS IS TO BEDONE BY A CERTIFIED PLUMBER.9. ALL PIPING CONNECTIONS TO INCUBATORSARE MADE WITH 1/2" DIA. COPPER PIPE.PROVIDE FLEXIBLE HOSE CONNECTION FROMSUPPLY PIPING TO INCUBATOR & HATCHERSCONNECTIONS.10. ALL PIPE DIMENSIONS LISTED AREINTERNAL DIAMETER.11. PIPES CAN BE COPPER, PVC OR PEX FORCOLD WATER.12. PIPES CAN BE COPPER, CPVC OR PEX FORHOT WATER.13. INSTALL AIR VENTS AT THE HIGHEST POINTOF EACH BRANCH & ANY OTHER REQUIREDLOCATIONS.14. DRAWINGS ARE SCHEMATICREPRESENTATIONS; ACTUAL EQUIPMENTLOCATIONS TO BE DETERMINED BY CERTIFIEDPLUMBER.
As indicated
Cold Water Pipping - Incubator Room
CR DM P8
02/02/17 Project #
Jamesway IncubatorSample
Drawings
12 P120 IINCUBATORS AND 6 P40 HATCHERS
144140
1 : 502
Cold Water Pippiping - Incubator Roomsection
1 : 451 Cold Water Pipping over Incubators
1/8" = 1'-0"Cold Water Pipping Legend
PROJECT DETAILS
REV.DRAWING NUMBERCHECKED BY
DATE
DRAWN BY
SCALE
CLIENT NAME
PROJECT NUMBER
THIS DRAWING IS FOR QUOTATION ONLY; IT IS NOTTO BE USED FOR CONSTRUCTION.
WHERE A DISCREPANCY OCCURS BETWEEN THISDRAWING AND ANY SITE
DIMENSIONS/SPECIFICATIONS, THIS MUST BEREPORTED BEFORE ANY OF THE WORK SHOWN ON
THIS DRAWING IS COMMENCED.
THE CONTENTS OF THIS DRAWING IS THE COPYRIGHTOF JAMESWAY INCUBATOR COMPANY INC AND MUST
NOT BE REPRODUCED IN WHOLE OR IN PARTWITHOUT THEIR WRITTEN CONSENT BEING GIVEN
AND RECEIVED.
JAMESWAY INCUBATOR COMPANY INC1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
A
B
C
D
E
F
G
H
JAMESWAY IncubatorCompany Inc30 High Ridge CourtCambridge, Ontario, CanadaN1R 7L3Tel 519 624 4646Fax 519 624 [email protected]
NOTES:1. THE WATER PIPING SYSTEM SHOULDINCLUDE PROPER PLUMBING HARDWARE TOMINIMIZE WATER HAMMER EFFECT. THISSYSTEM IS DESIGNED ONLY FOR
2. CONNECT TO THE FACILITY'S WATERSYSTEM. A FILTRATION SYSTEM IS STRONGLYRECOMMENDED TO MINIMIZE FUTUREBLOCKAGE IN LINES OR LEAKS THROUGHSOLENOIDS.3. PLEASE REFER TO CONNECTION IMAGESFOR DETAILS.4. SYSTEM WATER PUMPS: SPECIFICATIONSTO BE DETERMINED. PLEASE USE CHILLERMANUFACTURER'S SPECIFICRECOMMENDATIONS.5. BALANCE VALVES & SYSTEM TO ACHIEVE US gal/min MINIMUM THROUGH EACHINCUBATOR ECU AND US gal/minMINIMUM THROUGH EACH HATCHER ECU, IFPRESENT.(a) WHERE AMBIENT TEMPERATURE GOESBELOW FREEZING, GLYCOL TO BE ADDED.(b) ALL PIPEWORK TO BE ADDED.6. FLUSH SYSTEM OF DEBRIS BEFORECONNECTING TO INCUBATORS.7. PROVIDE PIPING SYSTEM AS PER ALLLOCAL CODES. ALL PIPES, GAUGES, VALVES,FITTINGS ETC. SUPPLIED BY OTHERS.8. ALL PIPING SYSTEM SUPPLIED (BY OTHERS).OFFICIAL START UP OF CHILLERS/BOILERS ISNOT PERFORMED BY JAMESWAY. THIS IS TOBE DONE BY A CERTIFIED PLUMBER.9. ALL PIPING CONNECTIONS TO INCUBATORSARE MADE WITH 1/2" DIA. COPPER PIPE.PROVIDE FLEXIBLE HOSE CONNECTION FROMSUPPLY PIPING TO INCUBATOR & HATCHERSCONNECTIONS.10. ALL PIPE DIMENSIONS LISTED AREINTERNAL DIAMETER.11. PIPES CAN BE COPPER, PVC OR PEX FORCOLD WATER.12. PIPES CAN BE COPPER, CPVC OR PEX FORHOT WATER.13. INSTALL AIR VENTS AT THE HIGHESTPOINT OF EACH BRANCH & ANY OTHERREQUIRED LOCATIONS.14. DRAWINGS ARE SCHEMATICREPRESENTATIONS; ACTUAL EQUIPMENTLOCATIONS TO BE DETERMINED BY CERTIFIEDPLUMBER.
Cold Water Pipping Isometric View
CR DM P9
02/02/17 Project #
Jamesway IncubatorSample
Drawings
12 P120 IINCUBATORS AND 6 P40 HATCHERS
144140
1 Cold Water Pipping Isometric View
EF-2
P40 hatcher P40 hatcherPressure Gauge
Balancing Valve
Check Valve
1 1/4"ø
1 1/4"ø
1 1/4"ø3/4"
ø
3/4"
ø
Shut-Off ValveShut-Off Valve
2 321
P40 hatcher P40 hatcher P40 hatcher
Check Valve
Balancing Valve
Shut-Off Valve
1 1/4"ø 1 1/4"ø1/2"ø
PROJECT DETAILS
REV.DRAWING NUMBERCHECKED BY
DATE
DRAWN BY
SCALE
CLIENT NAME
PROJECT NUMBER
THIS DRAWING IS FOR QUOTATION ONLY; IT IS NOTTO BE USED FOR CONSTRUCTION.
WHERE A DISCREPANCY OCCURS BETWEEN THISDRAWING AND ANY SITE
DIMENSIONS/SPECIFICATIONS, THIS MUST BEREPORTED BEFORE ANY OF THE WORK SHOWN ON
THIS DRAWING IS COMMENCED.
THE CONTENTS OF THIS DRAWING IS THE COPYRIGHTOF JAMESWAY INCUBATOR COMPANY INC AND MUST
NOT BE REPRODUCED IN WHOLE OR IN PARTWITHOUT THEIR WRITTEN CONSENT BEING GIVEN
AND RECEIVED.
JAMESWAY INCUBATOR COMPANY INC1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
A
B
C
D
E
F
G
H
JAMESWAY IncubatorCompany Inc30 High Ridge CourtCambridge, Ontario, CanadaN1R 7L3Tel 519 624 4646Fax 519 624 [email protected]
NOTES:1. THE WATER PIPING SYSTEM SHOULDINCLUDE PROPER PLUMBING HARDWARE TOMINIMIZE WATER HAMMER EFFECT. THISSYSTEM IS DESIGNED ONLY FOR
2. CONNECT TO THE FACILITY'S WATERSYSTEM. A FILTRATION SYSTEM IS STRONGLYRECOMMENDED TO MINIMIZE FUTUREBLOCKAGE IN LINES OR LEAKS THROUGHSOLENOIDS.3. PLEASE REFER TO CONNECTION IMAGES FORDETAILS.4. SYSTEM WATER PUMPS: SPECIFICATIONS TOBE DETERMINED. PLEASE USE CHILLERMANUFACTURER'S SPECIFICRECOMMENDATIONS.5. BALANCE VALVES & SYSTEM TO ACHIEVE US gal/min MINIMUM THROUGH EACHINCUBATOR ECU AND US gal/minMINIMUM THROUGH EACH HATCHER ECU, IFPRESENT.(a) WHERE AMBIENT TEMPERATURE GOESBELOW FREEZING, GLYCOL TO BE ADDED.(b) ALL PIPE WORK TO BE INSULADED.6. FLUSH SYSTEM OF DEBRIS BEFORECONNECTING TO INCUBATORS.7. PROVIDE PIPING SYSTEM AS PER ALL LOCALCODES. ALL PIPES, GAUGES, VALVES, FITTINGSETC. SUPPLIED BY OTHERS.8. ALL PIPING SYSTEM SUPPLIED (BY OTHERS).OFFICIAL START UP OF CHILLERS/BOILERS ISNOT PERFORMED BY JAMESWAY. THIS IS TO BEDONE BY A CERTIFIED PLUMBER.9. ALL PIPING CONNECTIONS TO INCUBATORSARE MADE WITH 1/2" DIA. COPPER PIPE.PROVIDE FLEXIBLE HOSE CONNECTION FROMSUPPLY PIPING TO INCUBATOR & HATCHERSCONNECTIONS.10. ALL PIPE DIMENSIONS LISTED AREINTERNAL DIAMETER.11. PIPES CAN BE COPPER, PVC OR PEX FORCOLD WATER.12. PIPES CAN BE COPPER, CPVC OR PEX FORHOT WATER.13. INSTALL AIR VENTS AT THE HIGHEST POINTOF EACH BRANCH & ANY OTHER REQUIREDLOCATIONS.14. DRAWINGS ARE SCHEMATICREPRESENTATIONS; ACTUAL EQUIPMENTLOCATIONS TO BE DETERMINED BY CERTIFIEDPLUMBER.
As indicated
Cold Water Pipping - Hatcher Room
CR DM P10
02/02/17 Project #
Jamesway IncubatorSample
Drawings
12 P120 IINCUBATORS AND 6 P40 HATCHERS
144140
1 : 401 Cold Water Sections over Hatchers
1 : 702 Hatcher Room 2
2 1/2"ø
2 1/2"ø
2"ø1/2"ø
3/4"ø
3/4"ø
1/2"ø
P120
Shut-Off Valve
Shut-Off Valve
2 1/2"ø
2 1/2"ø
2 1/2"øø3/4"
3/4"ø1/2"ø1/2"ø
ø3/4"
Incubator Room 1
P120 P120 P120
PROJECT DETAILS
REV.DRAWING NUMBERCHECKED BY
DATE
DRAWN BY
SCALE
CLIENT NAME
PROJECT NUMBER
THIS DRAWING IS FOR QUOTATION ONLY; IT IS NOTTO BE USED FOR CONSTRUCTION.
WHERE A DISCREPANCY OCCURS BETWEEN THISDRAWING AND ANY SITE
DIMENSIONS/SPECIFICATIONS, THIS MUST BEREPORTED BEFORE ANY OF THE WORK SHOWN ON
THIS DRAWING IS COMMENCED.
THE CONTENTS OF THIS DRAWING IS THE COPYRIGHTOF JAMESWAY INCUBATOR COMPANY INC AND MUST
NOT BE REPRODUCED IN WHOLE OR IN PARTWITHOUT THEIR WRITTEN CONSENT BEING GIVEN
AND RECEIVED.
JAMESWAY INCUBATOR COMPANY INC1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
A
B
C
D
E
F
G
H
JAMESWAY IncubatorCompany Inc30 High Ridge CourtCambridge, Ontario, CanadaN1R 7L3Tel 519 624 4646Fax 519 624 [email protected]
NOTES:1. THE WATER PIPING SYSTEM SHOULDINCLUDE PROPER PLUMBING HARDWARE TOMINIMIZE WATER HAMMER EFFECT. THISSYSTEM IS DESIGNED ONLY FOR
2. CONNECT TO THE FACILITY'S WATERSYSTEM. A FILTRATION SYSTEM IS STRONGLYRECOMMENDED TO MINIMIZE FUTUREBLOCKAGE IN LINES OR LEAKS THROUGHSOLENOIDS.3. PLEASE REFER TO CONNECTION IMAGESFOR DETAILS.4. SYSTEM WATER PUMPS: SPECIFICATIONSTO BE DETERMINED. PLEASE USE CHILLERMANUFACTURER'S SPECIFICRECOMMENDATIONS.5. BALANCE VALVES & SYSTEM TO ACHIEVE US gal/min MINIMUM THROUGH EACHINCUBATOR ECU AND US gal/minMINIMUM THROUGH EACH HATCHER ECU, IFPRESENT.(a) WHERE AMBIENT TEMPERATURE GOESBELOW FREEZING, GLYCOL TO BE ADDED.(b) ALL PIPEWORK TO BE ADDED.6. FLUSH SYSTEM OF DEBRIS BEFORECONNECTING TO INCUBATORS.7. PROVIDE PIPING SYSTEM AS PER ALLLOCAL CODES. ALL PIPES, GAUGES, VALVES,FITTINGS ETC. SUPPLIED BY OTHERS.8. ALL PIPING SYSTEM SUPPLIED (BY OTHERS).OFFICIAL START UP OF CHILLERS/BOILERS ISNOT PERFORMED BY JAMESWAY. THIS IS TOBE DONE BY A CERTIFIED PLUMBER.9. ALL PIPING CONNECTIONS TO INCUBATORSARE MADE WITH 1/2" DIA. COPPER PIPE.PROVIDE FLEXIBLE HOSE CONNECTION FROMSUPPLY PIPING TO INCUBATOR & HATCHERSCONNECTIONS.10. ALL PIPE DIMENSIONS LISTED AREINTERNAL DIAMETER.11. PIPES CAN BE COPPER, PVC OR PEX FORCOLD WATER.12. PIPES CAN BE COPPER, CPVC OR PEX FORHOT WATER.13. INSTALL AIR VENTS AT THE HIGHESTPOINT OF EACH BRANCH & ANY OTHERREQUIRED LOCATIONS.14. DRAWINGS ARE SCHEMATICREPRESENTATIONS; ACTUAL EQUIPMENTLOCATIONS TO BE DETERMINED BY CERTIFIEDPLUMBER.
1 : 58
Pipping Details - Incubator Rooms
CR DM P11
02/02/17 Project #
Jamesway IncubatorSample
Drawings
12 P120 IINCUBATORS AND 6 P40 HATCHERS
144140
2 Pipping - Incubator Rooms
4 Pipping Incubator Room View Details
1 : 581 Incubator Room 1
1 1/4"ø1 1/4"ø1 1/4"ø
P40 hatcher
Pressure Gauge
Check Valve
Balancing Valve
Shut-Off Valve
PROJECT DETAILS
REV.DRAWING NUMBERCHECKED BY
DATE
DRAWN BY
SCALE
CLIENT NAME
PROJECT NUMBER
THIS DRAWING IS FOR QUOTATION ONLY; IT IS NOTTO BE USED FOR CONSTRUCTION.
WHERE A DISCREPANCY OCCURS BETWEEN THISDRAWING AND ANY SITE
DIMENSIONS/SPECIFICATIONS, THIS MUST BEREPORTED BEFORE ANY OF THE WORK SHOWN ON
THIS DRAWING IS COMMENCED.
THE CONTENTS OF THIS DRAWING IS THE COPYRIGHTOF JAMESWAY INCUBATOR COMPANY INC AND MUST
NOT BE REPRODUCED IN WHOLE OR IN PARTWITHOUT THEIR WRITTEN CONSENT BEING GIVEN
AND RECEIVED.
JAMESWAY INCUBATOR COMPANY INC1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
A
B
C
D
E
F
G
H
JAMESWAY IncubatorCompany Inc30 High Ridge CourtCambridge, Ontario, CanadaN1R 7L3Tel 519 624 4646Fax 519 624 [email protected]
NOTES:1. THE WATER PIPING SYSTEM SHOULDINCLUDE PROPER PLUMBING HARDWARE TOMINIMIZE WATER HAMMER EFFECT. THISSYSTEM IS DESIGNED ONLY FOR
2. CONNECT TO THE FACILITY'S WATERSYSTEM. A FILTRATION SYSTEM IS STRONGLYRECOMMENDED TO MINIMIZE FUTUREBLOCKAGE IN LINES OR LEAKS THROUGHSOLENOIDS.3. PLEASE REFER TO CONNECTION IMAGESFOR DETAILS.4. SYSTEM WATER PUMPS: SPECIFICATIONSTO BE DETERMINED. PLEASE USE CHILLERMANUFACTURER'S SPECIFICRECOMMENDATIONS.5. BALANCE VALVES & SYSTEM TO ACHIEVE US gal/min MINIMUM THROUGH EACHINCUBATOR ECU AND US gal/minMINIMUM THROUGH EACH HATCHER ECU, IFPRESENT.(a) WHERE AMBIENT TEMPERATURE GOESBELOW FREEZING, GLYCOL TO BE ADDED.(b) ALL PIPEWORK TO BE ADDED.6. FLUSH SYSTEM OF DEBRIS BEFORECONNECTING TO INCUBATORS.7. PROVIDE PIPING SYSTEM AS PER ALLLOCAL CODES. ALL PIPES, GAUGES, VALVES,FITTINGS ETC. SUPPLIED BY OTHERS.8. ALL PIPING SYSTEM SUPPLIED (BY OTHERS).OFFICIAL START UP OF CHILLERS/BOILERS ISNOT PERFORMED BY JAMESWAY. THIS IS TOBE DONE BY A CERTIFIED PLUMBER.9. ALL PIPING CONNECTIONS TO INCUBATORSARE MADE WITH 1/2" DIA. COPPER PIPE.PROVIDE FLEXIBLE HOSE CONNECTION FROMSUPPLY PIPING TO INCUBATOR & HATCHERSCONNECTIONS.10. ALL PIPE DIMENSIONS LISTED AREINTERNAL DIAMETER.11. PIPES CAN BE COPPER, PVC OR PEX FORCOLD WATER.12. PIPES CAN BE COPPER, CPVC OR PEX FORHOT WATER.13. INSTALL AIR VENTS AT THE HIGHESTPOINT OF EACH BRANCH & ANY OTHERREQUIRED LOCATIONS.14. DRAWINGS ARE SCHEMATICREPRESENTATIONS; ACTUAL EQUIPMENTLOCATIONS TO BE DETERMINED BY CERTIFIEDPLUMBER.
Pipping Details - Hatcher Rooms
CR DM P12
02/02/17 Project #
Jamesway IncubatorSample
Drawings
12 P120 IINCUBATORS AND 6 P40 HATCHERS
144140
1 Pipping - Hatcher Room 2 2 Pipping - Hatcher Room 2 Detailed
2P10
1P11
1/2"ø
3/4"ø
1/2"ø
3/4"
ø
1/2"
ø
3/4"
ø
1/2"
ø
1/2"ø
3/4"øRegulator & Filter
Regulator & Filter
Connect to Facility's compressor3/4" dia. pipping
Connect to Facility's water system1/2" dia. pipping
1/2"ø
3/4"ø
P120
Regulator & Filter
1/2"ø
3/4"
ø
1/2"ø
P120Shut-Off ValvePROJECT DETAILS
REV.DRAWING NUMBERCHECKED BY
DATE
DRAWN BY
SCALE
CLIENT NAME
PROJECT NUMBER
THIS DRAWING IS FOR QUOTATION ONLY; IT IS NOTTO BE USED FOR CONSTRUCTION.
WHERE A DISCREPANCY OCCURS BETWEEN THISDRAWING AND ANY SITE
DIMENSIONS/SPECIFICATIONS, THIS MUST BEREPORTED BEFORE ANY OF THE WORK SHOWN ON
THIS DRAWING IS COMMENCED.
THE CONTENTS OF THIS DRAWING IS THE COPYRIGHTOF JAMESWAY INCUBATOR COMPANY INC AND MUST
NOT BE REPRODUCED IN WHOLE OR IN PARTWITHOUT THEIR WRITTEN CONSENT BEING GIVEN
AND RECEIVED.
JAMESWAY INCUBATOR COMPANY INC
NOTES
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
A
B
C
D
E
F
G
H
JAMESWAY IncubatorCompany Inc30 High Ridge CourtCambridge, Ontario, CanadaN1R 7L3Tel 519 624 4646Fax 519 624 [email protected]
1. HUMIDITY WATER SUPPLY PER
2. ONE 1/2" (13mm) COPPER PIPE OR 1/2" (13mm)RIGID PVC PIPE CAN BE USED. NOT PROVIDED BYJAMESWAY
3. HUMIDITY LINE DROP IS TO BE FITTED WITH ASHUT-OFF VALVE
4. DRILL A 1/2" (13mm) HOLE 2" FRON THE COLDWATER RETURN, TOWARDS THE CENTREEXTRUSION, AND IN LINE WITH THE COLD WATERPIPES.
5. CONNECT TO THE INCOMING HUMIDITY WATERLINE USING A 3/8" (9.5mm) TUBE TO 1/4" (6.3mm) mptFITTING. NOT PROVIDED BY JAMESWAY.
6. THE PRESSURE MUST BE 60 TO 100 psig AT ALLTIMES. A BOOSTER PUMPS MAY BE NECESSARYON THE WATER LINE TO ENSURE MINIMUMPRESSURE IS MAINTAINED.
7. TO AVOID EXCESSIVE SCALE BUILD UP, PLEASEREFER TO PAGE 30 & 31 OF THE HATCHERYDESIGN MANUAL FOR WATER QUALITY.
8. IF A REVERSE OSMOSIS (RO) SYSTEM IS TO BEUSED, ALL PIPING SHOULD BR PVC. RO WATERWILL DAMAGE COPPER PIPES.
As indicated
Humidity & Compressed Air
CR DM P13
02/02/17 Project #
Jamesway IncubatorSample
Drawings
1 : 2501 Hum & Compressed Air
2 Regulator and Filter View
1 : 503 Hum & Compressed Air Detail
Duct Size
20"x20"
Duct Size13"x20"
RTU-4
RTU-6
P120
P40 hatcher
Supply Grill 20x20
Return Filter 20x20x2
RTU-3
RTU-2
EF-4
P120
P120
P120
P120
P120
P40 hatcher
P40 hatcher
PROJECT DETAILS
REV.DRAWING NUMBERCHECKED BY
DATE
DRAWN BY
SCALE
CLIENT NAME
PROJECT NUMBER
THIS DRAWING IS FOR QUOTATION ONLY; IT IS NOTTO BE USED FOR CONSTRUCTION.
WHERE A DISCREPANCY OCCURS BETWEEN THISDRAWING AND ANY SITE
DIMENSIONS/SPECIFICATIONS, THIS MUST BEREPORTED BEFORE ANY OF THE WORK SHOWN ON
THIS DRAWING IS COMMENCED.
THE CONTENTS OF THIS DRAWING IS THE COPYRIGHTOF JAMESWAY INCUBATOR COMPANY INC AND MUST
NOT BE REPRODUCED IN WHOLE OR IN PARTWITHOUT THEIR WRITTEN CONSENT BEING GIVEN
AND RECEIVED.
JAMESWAY INCUBATOR COMPANY INC
NOTES
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
A
B
C
D
E
F
G
H
JAMESWAY IncubatorCompany Inc30 High Ridge CourtCambridge, Ontario, CanadaN1R 7L3Tel 519 624 4646Fax 519 624 [email protected]
HVAC Isometric View
CR DM P14
02/02/17 Project #
Jamesway IncubatorSample
Drawings
1 HVAC - Incubators and Hatcher Rooms
SP-C 1
SP-P 1 SP-A 1
SP-P 2 SP-A 2
SP-A 4
SP-B 2SP-B 1
CP 2
3VSD
CP 1
SP-A 3SP-P 3
PROJECT DETAILS
REV.DRAWING NUMBERCHECKED BY
DATE
DRAWN BY
SCALE
CLIENT NAME
PROJECT NUMBER
THIS DRAWING IS FOR QUOTATION ONLY; IT IS NOTTO BE USED FOR CONSTRUCTION.
WHERE A DISCREPANCY OCCURS BETWEEN THISDRAWING AND ANY SITE
DIMENSIONS/SPECIFICATIONS, THIS MUST BEREPORTED BEFORE ANY OF THE WORK SHOWN ON
THIS DRAWING IS COMMENCED.
THE CONTENTS OF THIS DRAWING IS THE COPYRIGHTOF JAMESWAY INCUBATOR COMPANY INC AND MUST
NOT BE REPRODUCED IN WHOLE OR IN PARTWITHOUT THEIR WRITTEN CONSENT BEING GIVEN
AND RECEIVED.
JAMESWAY INCUBATOR COMPANY INC1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
A
B
C
D
E
F
G
H
JAMESWAY IncubatorCompany Inc30 High Ridge CourtCambridge, Ontario, CanadaN1R 7L3Tel 519 624 4646Fax 519 624 [email protected]
1 : 230
Guardian Controls - Low Voltage
CR DM P15
02/10/17 Project #
Jamesway IncubatorSample
Drawings
1 : 2301 Guardian Controls - Low Voltage
SP-C 1
SP-P 1 SP-A 1
BB 1
SP-P 2
SP-A 2
OAR 1
OAR 2
SP-A 4
SP-B 2SP-B 1
BB 2
SP-A 3SP-P 3
BB 3
PROJECT DETAILS
REV.DRAWING NUMBERCHECKED BY
DATE
DRAWN BY
SCALE
CLIENT NAME
PROJECT NUMBER
THIS DRAWING IS FOR QUOTATION ONLY; IT IS NOTTO BE USED FOR CONSTRUCTION.
WHERE A DISCREPANCY OCCURS BETWEEN THISDRAWING AND ANY SITE
DIMENSIONS/SPECIFICATIONS, THIS MUST BEREPORTED BEFORE ANY OF THE WORK SHOWN ON
THIS DRAWING IS COMMENCED.
THE CONTENTS OF THIS DRAWING IS THE COPYRIGHTOF JAMESWAY INCUBATOR COMPANY INC AND MUST
NOT BE REPRODUCED IN WHOLE OR IN PARTWITHOUT THEIR WRITTEN CONSENT BEING GIVEN
AND RECEIVED.
JAMESWAY INCUBATOR COMPANY INC1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
A
B
C
D
E
F
G
H
JAMESWAY IncubatorCompany Inc30 High Ridge CourtCambridge, Ontario, CanadaN1R 7L3Tel 519 624 4646Fax 519 624 [email protected]
1 : 230
Guardian Controls - Pressure
CR DM P16
02/13/17 Project #
Jamesway IncubatorSample
Drawings
1 : 2301 Guardian Controls - Pressure
D
D
CP 2
3VSD
D
D
D
D
CP 1
D
D
CPX - High Volt. Power Supply(120/240 VAC, 1 phase, 50/60 H
VSDX - High Volt. Power Supply(120/240 VAC, 1 phase, 50/60 H
PROJECT DETAILS
REV.DRAWING NUMBERCHECKED BY
DATE
DRAWN BY
SCALE
CLIENT NAME
PROJECT NUMBER
THIS DRAWING IS FOR QUOTATION ONLY; IT IS NOTTO BE USED FOR CONSTRUCTION.
WHERE A DISCREPANCY OCCURS BETWEEN THISDRAWING AND ANY SITE
DIMENSIONS/SPECIFICATIONS, THIS MUST BEREPORTED BEFORE ANY OF THE WORK SHOWN ON
THIS DRAWING IS COMMENCED.
THE CONTENTS OF THIS DRAWING IS THE COPYRIGHTOF JAMESWAY INCUBATOR COMPANY INC AND MUST
NOT BE REPRODUCED IN WHOLE OR IN PARTWITHOUT THEIR WRITTEN CONSENT BEING GIVEN
AND RECEIVED.
JAMESWAY INCUBATOR COMPANY INC1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
A
B
C
D
E
F
G
H
JAMESWAY IncubatorCompany Inc30 High Ridge CourtCambridge, Ontario, CanadaN1R 7L3Tel 519 624 4646Fax 519 624 [email protected]
As indicated
Guardian Controls - High Voltage
CR DM P17
02/13/17 Project #
Jamesway IncubatorSample
Drawings
1 : 2301 Guardian Controls - High Voltage
PROJECT DETAILS
REV.DRAWING NUMBERCHECKED BY
DATE
DRAWN BY
SCALE
CLIENT NAME
PROJECT NUMBER
THIS DRAWING IS FOR QUOTATION ONLY; IT IS NOTTO BE USED FOR CONSTRUCTION.
WHERE A DISCREPANCY OCCURS BETWEEN THISDRAWING AND ANY SITE
DIMENSIONS/SPECIFICATIONS, THIS MUST BEREPORTED BEFORE ANY OF THE WORK SHOWN ON
THIS DRAWING IS COMMENCED.
THE CONTENTS OF THIS DRAWING IS THE COPYRIGHTOF JAMESWAY INCUBATOR COMPANY INC AND MUST
NOT BE REPRODUCED IN WHOLE OR IN PARTWITHOUT THEIR WRITTEN CONSENT BEING GIVEN
AND RECEIVED.
JAMESWAY INCUBATOR COMPANY INC
NOTES
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
A
B
C
D
E
F
G
H
JAMESWAY IncubatorCompany Inc30 High Ridge CourtCambridge, Ontario, CanadaN1R 7L3Tel 519 624 4646Fax 519 624 [email protected]
Guardian Controls - Isometric View
CR DM P18
02/10/17 Project #
Jamesway IncubatorSample
Drawings
1 3D Guardian Controls
1P19
BB 1 BB 2
BB 3
SP-A 1 D SP-A 2
P120P120P120 P40 hatcher
Incubator Room 2
EF-4RTU-4
RTU-2
3P19
P120 P120
SP-P 1SP-A 1
BB 1OAR 1
3VSD
CP 1
Incubator Room 2 Incubator Room 1
RTU-2 RTU-3
PROJECT DETAILS
REV.DRAWING NUMBERCHECKED BY
DATE
DRAWN BY
SCALE
CLIENT NAME
PROJECT NUMBER
THIS DRAWING IS FOR QUOTATION ONLY; IT IS NOTTO BE USED FOR CONSTRUCTION.
WHERE A DISCREPANCY OCCURS BETWEEN THISDRAWING AND ANY SITE
DIMENSIONS/SPECIFICATIONS, THIS MUST BEREPORTED BEFORE ANY OF THE WORK SHOWN ON
THIS DRAWING IS COMMENCED.
THE CONTENTS OF THIS DRAWING IS THE COPYRIGHTOF JAMESWAY INCUBATOR COMPANY INC AND MUST
NOT BE REPRODUCED IN WHOLE OR IN PARTWITHOUT THEIR WRITTEN CONSENT BEING GIVEN
AND RECEIVED.
JAMESWAY INCUBATOR COMPANY INC
NOTES
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
A
B
C
D
E
F
G
H
JAMESWAY IncubatorCompany Inc30 High Ridge CourtCambridge, Ontario, CanadaN1R 7L3Tel 519 624 4646Fax 519 624 [email protected]
1 : 100
Guardian Controls Section
CR DM P19
02/10/17 Project #
Jamesway IncubatorSample
Drawings
1 : 1003
Guardian Controls - Incubators/HatcherRooms
1 : 1001 Guardian Control - Incubator Room1 & 2
PROJECT DETAILS
REV.DRAWING NUMBERCHECKED BY
DATE
DRAWN BY
SCALE
CLIENT NAME
PROJECT NUMBER
THIS DRAWING IS FOR QUOTATION ONLY; IT IS NOTTO BE USED FOR CONSTRUCTION.
WHERE A DISCREPANCY OCCURS BETWEEN THISDRAWING AND ANY SITE
DIMENSIONS/SPECIFICATIONS, THIS MUST BEREPORTED BEFORE ANY OF THE WORK SHOWN ON
THIS DRAWING IS COMMENCED.
THE CONTENTS OF THIS DRAWING IS THE COPYRIGHTOF JAMESWAY INCUBATOR COMPANY INC AND MUST
NOT BE REPRODUCED IN WHOLE OR IN PARTWITHOUT THEIR WRITTEN CONSENT BEING GIVEN
AND RECEIVED.
JAMESWAY INCUBATOR COMPANY INC1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
A
B
C
D
E
F
G
H
JAMESWAY IncubatorCompany Inc30 High Ridge CourtCambridge, Ontario, CanadaN1R 7L3Tel 519 624 4646Fax 519 624 [email protected]
Guardian Controls Notes
CR DM P20
02/10/17 Project #
Jamesway IncubatorSample
Drawings
Incubator Room 1
Hatcher Room 2
Egg Room
Pull Room
Clean roomChick Room
Chick Room
Back Up Alarm Panel
PROJECT DETAILS
REV.DRAWING NUMBERCHECKED BY
DATE
DRAWN BY
SCALE
CLIENT NAME
PROJECT NUMBER
THIS DRAWING IS FOR QUOTATION ONLY; IT IS NOTTO BE USED FOR CONSTRUCTION.
WHERE A DISCREPANCY OCCURS BETWEEN THISDRAWING AND ANY SITE
DIMENSIONS/SPECIFICATIONS, THIS MUST BEREPORTED BEFORE ANY OF THE WORK SHOWN ON
THIS DRAWING IS COMMENCED.
THE CONTENTS OF THIS DRAWING IS THE COPYRIGHTOF JAMESWAY INCUBATOR COMPANY INC AND MUST
NOT BE REPRODUCED IN WHOLE OR IN PARTWITHOUT THEIR WRITTEN CONSENT BEING GIVEN
AND RECEIVED.
JAMESWAY INCUBATOR COMPANY INC1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
A
B
C
D
E
F
G
H
JAMESWAY IncubatorCompany Inc30 High Ridge CourtCambridge, Ontario, CanadaN1R 7L3Tel 519 624 4646Fax 519 624 [email protected]
- EACH BACK UP ALARM PANEL REQUIRES ASEPARATE 115V/230V POWER CIRCUIT(SEVERAL PANELS CAN SHARE THE SAMECIRCUIT).
- EACH BACK UP ALARM PANEL REQUIRES ABELL OR SIREN AND A 12VDC/24VDC POWERCIRCUIT. BELL OR SIREN PROVIDED BYCUSTOMER.
- CABLES AND ALL WIRING MATERIALS TO BELAID IN PLACE BY CUSTOMER. JAMESWAY TOMAKE CONTROL WIRING CONNECTIONS ANDPERFORM INITIAL START-UP OF PANELS.
- BACK UP ALARM PANEL
- BACK UP ALARM CABLE PT 2185
1 : 150
Backup Alarm Layout
CR DM P21
02/10/17 Project #
Jamesway IncubatorSample
Drawings
1 : 1501 Backup Alarm
PROJECT DETAILS
REV.DRAWING NUMBERCHECKED BY
DATE
DRAWN BY
SCALE
CLIENT NAME
PROJECT NUMBER
THIS DRAWING IS FOR QUOTATION ONLY; IT IS NOTTO BE USED FOR CONSTRUCTION.
WHERE A DISCREPANCY OCCURS BETWEEN THISDRAWING AND ANY SITE
DIMENSIONS/SPECIFICATIONS, THIS MUST BEREPORTED BEFORE ANY OF THE WORK SHOWN ON
THIS DRAWING IS COMMENCED.
THE CONTENTS OF THIS DRAWING IS THE COPYRIGHTOF JAMESWAY INCUBATOR COMPANY INC AND MUST
NOT BE REPRODUCED IN WHOLE OR IN PARTWITHOUT THEIR WRITTEN CONSENT BEING GIVEN
AND RECEIVED.
JAMESWAY INCUBATOR COMPANY INC
NOTES
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
A
B
C
D
E
F
G
H
JAMESWAY IncubatorCompany Inc30 High Ridge CourtCambridge, Ontario, CanadaN1R 7L3Tel 519 624 4646Fax 519 624 [email protected]
Backup Alarm - Isometeric View
CR DM P22
02/10/17 Project #
Jamesway IncubatorSample
Drawings
1 3D Backup Alarm
Incubator Room 1
Hatcher Room 2
Egg Room
Pull Room
Chick Room
Ethernet Hub
Computer Station
PROJECT DETAILS
REV.DRAWING NUMBERCHECKED BY
DATE
DRAWN BY
SCALE
CLIENT NAME
PROJECT NUMBER
THIS DRAWING IS FOR QUOTATION ONLY; IT IS NOTTO BE USED FOR CONSTRUCTION.
WHERE A DISCREPANCY OCCURS BETWEEN THISDRAWING AND ANY SITE
DIMENSIONS/SPECIFICATIONS, THIS MUST BEREPORTED BEFORE ANY OF THE WORK SHOWN ON
THIS DRAWING IS COMMENCED.
THE CONTENTS OF THIS DRAWING IS THE COPYRIGHTOF JAMESWAY INCUBATOR COMPANY INC AND MUST
NOT BE REPRODUCED IN WHOLE OR IN PARTWITHOUT THEIR WRITTEN CONSENT BEING GIVEN
AND RECEIVED.
JAMESWAY INCUBATOR COMPANY INC1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
A
B
C
D
E
F
G
H
JAMESWAY IncubatorCompany Inc30 High Ridge CourtCambridge, Ontario, CanadaN1R 7L3Tel 519 624 4646Fax 519 624 [email protected]
- ETHERNET CABLES MUST BE KEPT SEPARATEFROM POWER WIRING AND ARE TYPICALLY RUN INTHEIR OWN CABLE TRAY.
- ETHERNET CABLES SHOULD BE KEPT AWAY FROMLIGHT FIXTURES.
- MAXIMUM DISTANCE FROM A MACHINE TO ANETHERNET HUB I 328 FT (100M)
- CONDUIT
- ETHERNET HUB (NOT PROVIDED BY JAMESWAY)
1 : 190
Hatchcom Layout
CR DM P23
02/10/17 Project #
Jamesway IncubatorSample
Drawings
1 : 1901 Hatchcom
PROJECT DETAILS
REV.DRAWING NUMBERCHECKED BY
DATE
DRAWN BY
SCALE
CLIENT NAME
PROJECT NUMBER
THIS DRAWING IS FOR QUOTATION ONLY; IT IS NOTTO BE USED FOR CONSTRUCTION.
WHERE A DISCREPANCY OCCURS BETWEEN THISDRAWING AND ANY SITE
DIMENSIONS/SPECIFICATIONS, THIS MUST BEREPORTED BEFORE ANY OF THE WORK SHOWN ON
THIS DRAWING IS COMMENCED.
THE CONTENTS OF THIS DRAWING IS THE COPYRIGHTOF JAMESWAY INCUBATOR COMPANY INC AND MUST
NOT BE REPRODUCED IN WHOLE OR IN PARTWITHOUT THEIR WRITTEN CONSENT BEING GIVEN
AND RECEIVED.
JAMESWAY INCUBATOR COMPANY INC
NOTES
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
A
B
C
D
E
F
G
H
JAMESWAY IncubatorCompany Inc30 High Ridge CourtCambridge, Ontario, CanadaN1R 7L3Tel 519 624 4646Fax 519 624 [email protected]
Hatchcom - Isometric View
CR DM P24
02/10/17 Project #
Jamesway IncubatorSample
Drawings
1 3D Hatchcom