5
Specifications andstandardsThe separable connector 400LRmeets the requirements ofCENELEC HD 629.1.
Up to 36 kV - 400 A
DesignSeparable connectorcomprising:1. Conductive EPDM insert.2. Conductive EPDM jacket.3. Insulating EPDM layer
moulded between the insertand the jacket.
4. Type B - 400 A interfaceas described by CENELECEN 50180 and 50181.
5. Conductor connector.6. Cable reducer.7. Earthing lead.
The screen break designenables cable outer sheathtesting without removing ordismantling the connector.
400LRINTERFACE B
ELBOW CONNECTOR
ApplicationSeparable elbow connector(plug-in type) designedto connect polymericinsulated cable to equipment(transformers, switch gear,motors...).
6/10 (12) kV6.35/11 (12) kV8.7/15 (17.5) kV
12/20 (24) kV12.7/22 (24) kV
18/30 (36) kV
Technical characteristics• The thick conductive EPDM
jacket provides a total safe totouch screen which ensuressafety for personnel.
• Each separable connector istested for AC withstand andpartial discharge prior toleaving the factory.
210 mm
365 mm
7
3
2
4
5
1
6
Separableconnector
type
VoltageUm(kV)
CurrentIr
(A)
Conductor sizes (mm2)
min. max.400LR/GK400LR/GM400LR/G
122436
400400400
502535
240240185
6
Kit contentsThe complete (K)(M)400LR/Gelbow connector kit comprisesthe following components:
The kit also comprises lubricant, wipers,installation instructions and crimp chart.
Ordering instructionsSelect the part numberwhich gives the best centringto the cable core insulationdiameter and substitute Xusing table X, according to theconductor size and type.Add a 'K' for use up to 24 kVand add an 'M' for use up to36 kV.
Conductorcontact
400LRC-X
Pin contact+ hex. key
400LRF
Bailrestraint400BA
Connector housing(K)(M)400BLR/G
Cable reducer411CA-W
+
Orderingpart number
Dia. over core insulation (mm)
min. max.
400LR/G-11-X400LR/G-15-X400LR/G-19-X400LR/G-22-X400LR/G-25-X400LR/G-27-X
12.016.020.023.526.528.5
17.522.026.531.032.537.5
Example:The copper wire screened cableis 12 kV, 150 mm2 strandedcopper with a diameter overcore insulation of 23.5 mm.Order a 400LR/G-19-150(K)M-11-2 elbow connector kit.
(K)(M)400LR/G-W-Xconnector kit
Conductorsizes
(mm²)
Aluminium Copper
DIN hexagonal Deep indent DIN hexagonal
2535507095120150185240
-35(K)M-12-250(K)M-12-270(K)M-12-295(K)M-12-2120(K)M-12-2150(K)M-12-2185(K)M-12-2240(K)M-12-2
-35KM-12-1
50(K)M-12-170(K)M-12-195(K)M-12-1120(K)M-12-1150(K)M-12-1185(K)M-12-1240(K)M-12-1
25(K)M-11-235(K)M-11-250(K)M-11-270(K)M-11-295(K)M-11-2120(K)M-11-2150(K)M-11-2185(K)M-11-2240(K)M-11-2
Table X
+ + + =
For use withother cable types.
Please contact ourrepresentative.
For outdoorapplications.
Order: +MWS.
Components can beordered individually.
For use withcopper tape
screened cables.Order: Kit MT.
For use with Alupe orC 33-226 cables.
Please contact ourrepresentative.
For use with fabric tape(graphite) screened cables.
Order additionalsemi-conductive tape
(type TSC).