GRID INDIA POWER CABLES PVT. LTD.
Product Information 2009
An ISO 9001:2008
c e r t i f i e d c o m p a n y
manufacturing a range of cables for the
power sector. With state-of the art
manufacturing facilities at IMT-Manesar, Gurgaon
& Bhiwadi (Rajasthan), products such as LT PVC /
XLPE Insulated Power Cables, Copper Control Cables,
Aerial Bunched Cables, Instrumentation cables and
Conductors are among the best selling products from the
company. However this is just the beginning, Ambitious
expansion plans are afoot and the company is further investing to
set a world class facility for manufacture of Power Cables upto 1.1KV
including a large expansion in MV and LT Cables. The HV cables
plant and this expansion project shall be on stream by
December’2009.
With a rapidly expanding sales and marketing footprint across the
country, the company is expected to close the year 2009 with estimated sales of
Rupees 130 Cores. Some of the prominent customers of the company are various
State Electricity Boards & PSU’s like NTPC, PWD, UPSEB, HPSEB, APTRANSCO,
KESCO, MES, DOT, DGS&D and Railways etc.
Quality and commitment are the keywords at Grid Cables. The company has in house
testing facilities as per Bureau of Indian Standards & ISO:9001:2008 Quality
Management. The company is also registered with quality Marketing Department
New Delhi.
In order to further validate the in-house quality standards, the company, has got its
products tested as per Bureau of Indian Standards by outside Govt. Laboratories like
Quality Marketing Centre Faridabad, Haryana. Regional Test Centre – New Delhi,
ERDA – Vadodara, Gujrat and Quality Marketing Centre – Mohali. The company had
been assessed technically and financially by the Quality Assurance wing of DGS&D,
New Delhi. Grid Cables is on the approved list of NTPC, approved and sole suppliers of
Uttar Pradesh Power Corporation Limited, Rajasthan Electricity Board amongst
others.
An unswerving commitment to quality, ethical business practices and constant quest
to bring better products to the market have been the guiding principles for this
relatively young and on-the-go company in the power cables industry.
GRID INDIA POWER CABLES PVT. LTD.
Product Rangel LT XLPE / PVC Power Cables l LT Control Cables
l Single / Multicore Flexible Cables
l Aerial Bunched Cables
l Instrumentation Cables
l House Wires
l Concentric Cables
l Any type of Special Cables
l All type of Conductors
Log on to www.gridcables.com
Sector wise List of Prominent Customers
Ajmer Vidyut Vitran Nigam Ltd.Chhatisgarh State Electricity BoardCentral Electricity Supply Co. Ltd.Dakshin Gujarat Vij Company LimitedGujarat Energy Transmission Company Ltd.Himachal Pradesh State Electricity BoardIndian Railway Project Management UnitJaipur Vidyut Vitran Nigam Ltd.Jodhpur Vidyut Vitran Nigam LimitedKanpur Electricity Supply Co. Ltd.Kerala State Electricity BoardMP Poorva Kshetra Vidyut Vitran Co. Ltd.Madhya Gujarat Vij Company LimitedMizoram Electricity BoardPaschimanchal Vidyut Vitran Nigam Ltd.Purvanchal Vidyut Vitran Nigam Ltd.Uttar Gujarat Vij Company LimitedUP Corporation Sugar Factories Federation LimitedUttar Pradesh Power Corporation Ltd.
Bharat Heavy Electricals LimitedBharat Coking Coal LimitedIndian Oil Corporation Ltd.Mahanadi Coalfields LimitedNational Thermal Power CorporationNorthern Central RailwayNorthern Coalfields LimitedOrissa Small Industries Ltd.Rastriya Chemical FertilizerTehri Hydro Development Corporation Ltd.
ABB LimitedAngelique International Ltd.Annapurna Construction & TransmissionAvadh Transformers Pvt. Ltd.A2Z Maintenance & Engineering Services Pvt. Ltd.Bajaj Hindustan Sugar Works Pvt. Ltd.Darshan Sugar Pvt. Ltd.Easun Reyrolle Ltd. Godrej & Boyce Mfg. Co. Ltd. ICOMM Tele Ltd.Job Power Infra Engineering Ltd.KEC International Ltd.Kirloskar Brothers Ltd.KVK Construction Pvt. Ltd.Maytas Infra Ltd.National Steel and Agro India Ltd.Omaxe Construction Ltd.Ramky Infrastructure Ltd.RPG Transmission Ltd.Sonalika Tractor Pvt. Ltd.The Energy & Research Institute (TERI)TATA Projects Ltd.Vaishali Steels Pvt. Ltd.Vertex EngineersVijay Electricals Ltd.
State Electricity Boards
Public Sector
Private Sector
1) POWER CABLES
2) CONTROL CABLES
3) INSTRUMENTATION CABLES
4) SPECIAL CABLES
5) TEMPERATURE RESISTANT CABLES
6) MATERIAL HANDLING CABLES
7) DATA TRANSMISSION CABLES
Complete range of LT Power Cables armoured / unarmoured are available in Cu and Al Conductor to serve all applications.
Grid Cables provides LT Cu / Al Control cables with PVC / XLPE insulation. These are available in armoured / unarmoured version. The cores available are upto 1 to 61 in number and various cross sections. As an alternative to armoured cables, Grid Cables also provide Steel Wire Braided Cables (YSY) as these cables offers the advantage of mechanical strength along with high flexibility.
Grid Cables provide LT Copper Cables made from virgin PVC, Polyurethane and PE. The cores available are upto 1 to 100 in number and various cross sections. The cables are made up of bare / tinned copper wires. These cables can be provided with or without EMI protection with copper screening or aluminium foil screening. As an alternative to armoured cables, also provides Steel Wire Braided Cables (YSY) as these cables offer the advantage of mechanical strength along with flexibility.
Grid Cables has the capabilities to manufacture as per clients requirement. We can design and develop composite cables to serve our customer’s highest requirements.
We offer cables made of Teflon (250°C) for high temperature.
A wide range of PVC based cables can be used for material handling systems like lifts, EOT cranes and other similar systems.
A wide range of copper cables in screened, screened twisted, metal foiled etc. are available used for high speed data transmission with various factory automation systems involving PLC’s and other distributed control systems (DCS) and also heat resistant signal cables.
APPLICATION AREAS OF GRID CABLES PRODUCTS
www.gridcables.com
LT XLPE / PVC Power Cables
An ISO: 9001-2008 Certified Company
www.gridcables.com
CROSS LINKED POLYETHYLENE (XLPE)XLPE means cross-linked polyethylene or vulcanized polyethylene. The basic material is low density polyethylene. Polyethylene is a thermoplastic material consisting of long chain of hydrocarbon molecules. At elevated temperatures these molecules tend to move relative to one another so that the material becomes increasingly deformable and will eventually melt at the temperature around 110°C.
By means of process similar to the vulcanization of rubber the polyethylene molecules can be cross-linked. The process of cross-linking or vulcanization consists of producing chemical bonds at interval between the long molecular chain to give a “ladder” effect which prevents slippage between molecules as a result of cross-linking the material becomes heat resistant and does not soften at higher temperatures. Further it has better resistance to stress cracking and good resistance to ageing in hot air. Wit the change of structure there is no adverse effect on electrical properties.
Advantage of “GRID CABLES” XLPE Cables
n Dielectric losses are very small.
n Higher current carrying capacity.
n Higher short circuit rating 250°C as against 160°C for PVC.
n “GRID CABLES” XLPE can retain flexibility down upto - 40°C
n Jointing and Termination is easy.
n Light in weight
n They are not prone to fatigue damages due to vibrations or loading cycles.
n Has better resistance to most chemicals, oils, acids, etc.
n Can be installed along cable routes without elevation limitations.
COMPARISON OF MAIN PROPERTIES BETWEEN PVC AND XLPE INSULATION
Characteristics
Permitivity (50Hz , 20°C)Dielectric loss factor (50Hz, 20°C)Volume resistivity (27°C)Max. conductor temp.Max. short circuit temp.Tensile strength Elongation at breakFlexibility at -10°CResistance to abrasion
Unit
--Ohms cm (min.)°C°CN / mm2 (min.)---
PVC
4 - 60.05 - 0.07
131x107016012.5ExcellentPoorMedium
XLPE
2.30.0004
141X109025012.5MediumGoodGood
An ISO: 9001-2008 Certified Company
www.gridcables.com
1. Maximum conductor temperature 70°C2. Ambient air temperature 40°C3. Ground temperature 30°C4. Depth of laying ( for cable laid 75cm directly in group) (1.1KV)
Ground Temp °CRating factor
Depth of laying (cms)Rating factor upto 25 sq.mm
No. of cablesSingle core D.C. Cables & multicore power cablesSingle core A.C. Cables
Air temp. °CRating factor
No. of cables
2 cables3 cables4 cables6 cables8 cables
No. of cables
4 cables5 cables8 cables
151.17
751.00
11.0
1.0
251.25
Touching0.780.680.610.530.48
Touching0.600.510.45
201.12
900.99
20.90
0.80
301.16
15cm0.810.710.650.580.54
15cm0.670.570.51
251.06
1050.98
30.80
0.75
351.09
30cm0.850.770.720.660.62
30cm0.730.630.57
301.0
1200.97
40.75
0.70
401.00
45cm0.880.810.760.710.67
45cm0.760.670.59
350.94
1500.96
50.70
0.65
350.94
60cm0.900.830.790.760.72
60cm0.780.690.61
400.87
150 & above0.95
60.65
0.60
450.90
450.79
500.80
500.70
550.69
550.60
5. Thermal resistivity of soil 150°C cm/watt6. Thermal resistivity of cable 650°C7. Max. short circuit conductor temp. 160°C8. Max Ambient Air Temperature 55°C
The current ratings in table 1& 2 based on the normal conditions of installation as described below :-
Installation method and rating factors are given in tables 1 to 6.
TABLE 1 : Rating for variations in ground temperature for cables laid directly in ground and in ducts
TABLE 5 : Rating factors for variation in depth of laying in ground
TABLE 6 : Group rating factors for cables installed in ground, separated by more than 7 cms.
TABLE 2 : Rating factors for variation in ambient air temperature
TABLE 3 : Rating factors of ground of twin and multicore cables laid directly in ground in horizontal formation
TABLE 4 : Rating factors of ground of twin and multicore cables laid directly in ground in tier formation
Rating factor for axial spacing
Rating factor for axial spacing
An ISO: 9001-2008 Certified Company
www.gridcables.com
CURRENT RATINGS (XLPE)Basic assumption and condition for installation
Max. conductor temperature at continuous operation…………………..90°C Ambient air
Temperature…………………………………………………...................40°C
Ground temperature…………………………………………..…..…..…30°C
Thermal resistivity of soil…………………………….………………….150°C Cm/W
Depth of laying……………………………………….…...……………..750mm
Max. conductor temperature for short circuit…………………………...250°C
151.12
251.14
Ground temperature °CRating factor
Air temperature °CRating factor
201.08
301.10
251.03
351.04
301.00
401.00
350.96
450.95
400.91
500.90
Rating factors for variation in ground temperature
Rating factors for vibration in ambient air temperature
No. of cables 23456
Depth of laying
7590105120150180>
Touching0.790.690.620.580.54
Upto 25 mm21.000.990.980.970.960.95
15cm0.820.750.690.650.61
25 to 300 mm21.000.980.970.960.940.93
30cm0.870.790.740.720.69
Above 300mm21.000.970.960.950.920.91
45cm0.900.830.790.760.75
Rating factors cables laid directly laid in ground in horizontal formation
Rating factor for variation in depth of laying in ground
Distance of cables
Size
An ISO: 9001-2008 Certified Company
www.gridcables.com
1 Core Aluminium PVC Armoured Power Cables
Nominal Dimensions of Armour Wire (mm)1.401.401.401.401.401.401.401.401.601.601.601.601.602.002.002.002.002.002.50
Min. Thickness of PVC Outer Sheath (mm)1.241.241.241.241.241.241.241.401.401.401.401.401.561.561.561.721.881.882.04
Overall Dia-meter (approx.) (mm)
11121314151618202224272831353940485257
Approx. Net Wt. of Cable (Kg/Km)
16018021024031036045056072083098011601450171021902730344041205090
Max. D.C. Resis-tance
0 at 20 C (Ohms/Km)7.41004.61003.08001.91001.20000.86800.64100.44300.32000.25300.20600.16400.12500.10000.07780.06050.04690.03670.0291
Max. A.C. Resist-ance at
070 C (Ohms/Km)8.89005.53003.70002.29001.44001.04000.77000.53000.38000.30000.25000.20000.15000.12000.09340.07260.05630.04400.0349
Approx. Reactance at 50 Hz (Ohms / Km)
0.1580.1480.1380.1280.1200.1140.1100.1030.1010.0960.0940.0920.0900.0880.0880.0870.0860.0830.082
Approx. Capac-itance (mFd/Km)
0.470.560.670.810.871.001.031.211.271.421.421.441.531.561.561.571.571.751.94
Direct in Ground
2 Cables Amps3644597597120145175210240270305335370410435485525570
In Duct
2 Cables Amps3342567193110130155195200220240270295335355395420445
In Air
2 Cables Amps3241567299120150185215240270305350395455490560640740
3 Cables Amps3139516686100120140175195220240270295325345390442485
3 Cables Amps3037516584100115135155170190210225245275295320350380
3 Cables Amps2735476484105130155190220250290335380435480550600720
Thick-nessof PVCInsulatio(Nom.) (mm)1.301.301.301.301.501.501.701.701.901.902.102.302.502.803.003.403.903.904.00
Min.No.of wires
1116666121515153030305353535353
No. of cores and cross sectional area
1C x 41C x 61C x 101C x 161C x 251C x 351C x 501C x 701C x 951C x 1201C x 1501C x 1851C x 2401C x 3001C x 4001C x 5001C x 6301C x 8001C x 1000
CURRENT RATINGS
1 Core Aluminium PVC Unarmoured Power Cables
Nom. Thickness of Outer Sheath (mm)
891011121315171921232528303539444853
Overall Diameter (approx.) (mm)
1001101301602202603304105306407709201160139017602200282034304180
Net Wt. of Cable (Approx.) (Kg/Km)
7.41004.61003.08001.91001.20000.86800.64100.44300.32000.25300.20600.16400.12500.10000.07780.06050.04690.03670.0291
Max. D.C. Resis-tance
0at 20 C (Ohms/Km)
8.89005.53003.70002.29001.44001.04000.77000.53000.38000.30000.25000.20000.15000.12000.09340.07260.05630.04400.0349
Max. A.C. Resis-tance
0at 70 C (Ohms/Km)
0.1370.1270.1180.110.0.1050.1000.0980.0910.0880.0860.0850.0840.0820.0800.0800.0790.0770.0770.076
Approx. Capa-citance (mFd/Km)
0.580.680.831.011.051.221.221.431.471.621.621.621.721.741.811.761.771.982.20
Direct in Ground
2 Cables Amps
3644547597120145170205230265300335370410435485525570
In Duct
2 Cables Amps
3342567193110130155180200220240270295335355395420445
In Air
2 Cables Amps
3241567299120150185215240270305350395455490560650735
3 Cables Amps
3139516686100120140175195220240270295325345390440490
3 Cables Amps
3037516584100115135155170190210225245275295320350380
3 Cables Amps
2735476484105130155190220250290335380435480550640720
Min. No. of wires
1.001.001.001.001.201.201.401.401.601.601.802.002.202.402.603.003.403.403.40
Thickness of Insul-ation (Nom.) (mm)
1.801.801.801.801.801.801.801.801.802.002.002.002.002.002.202.202.402.402.60
No. of cores and cross secti-onal area1116666121515153030305353535353
Type
1C x 41C x 61C x 101C x 161C x 251C x 351C x 501C x 701C x 951C x 1201C x 1501C x 1851C x 2401C x 3001C x 4001C x 5001C x 6301C x 8001C x 1000
CURRENT RATINGS
An ISO: 9001-2008 Certified Company
www.gridcables.com
1 Core Copper PVC Armoured Power Cables
1 Core Copper PVC Unrmoured Power Cables
Min. Thick-ness of PVC Outer Sheath (mm)1.241.241.241.241.241.241.241.401.401.401.401.401.561.561.561.721.881.882.04
Net Wt. of Cable(Approx.) (Kg/Km)
115143189246357456595802108313321616204825623159401949966570824810219
Overall Diameter (approx.) (mm)
11121314151618202224272831353940485257
Max. D.C. Resistance
0 at 20 C (Ohms/Km)
4.613.081.831.150.7270.5240.3870.2680.1930.1530.1240.09910.07540.06010.04700.03660.02830.02210.0176
Approx. Net Wt. of Cable (Kg/Km)
178212264325448555705941126015121819227128543464442655047161900011091
Max. A.C. Resistance
0at 70 C (Ohms/Km)
5.523.692.191.380.870.6270.4630.3210.2310.1840.1490.1200.09120.0740.05920.04680.03790.03140.0271
Max. D.C. Resis-tance
0 at 20 C (Ohms/Km)4.613.081.831.150.7270.5240.3870.2680.1930.1530.1240.09910.07540.06010.04700.03660.02830.02210.0176
Max. A.C. Resis-tance
0at 70 C (Ohms/Km)
5.523.692.191.380.8700.6270.4630.3210.2310.1840.1490.1200.09120.07390.05920.04680.03790.03140.0271
Approx. Reac-tance at 50 Hz (Ohms/ Km)
0.1580.1480.1380.1280.1200.1140.1100.1030.1010.0960.0940.0920.0900.0880.0880.0870.0860.0830.082
Approx. Reactance at 50 Hz (Ohm/Km)
0.1580.1480.1380.1280.1200.1140.1100.1030.1010.0960.0940.0920.0900.0880.0880.0870.0860.0830.082
Approx. Capaci-tance (mFd/Km)
0.470.560.670.810.871.001.031.211.271.421.421.441.531.561.561.571.571.751.94
Approx. Capaci-tance (mFd/Km)
0.470.560.670.810.871.001.031.211.271.421.421.441.531.561.561.571.571.751.94
Direct in Ground
2 Cables Amps
46577594125150180220265300340380420465500540590664733
Direct in Ground
2 Cables Amps
46577594125150180220265300340380420465500540590664733
In Duct
2 Cables Amps
42547292120140165200230255280305340370405430465523579
In Duct
2 Cables Amps
42547292120140165200230255280305340370405430465523579
In Air
2 Cables Amps
43547292125155190235275310345390445500570610680766856
In Air
2 Cables Amps
43547292125155190235275310345390445500570610680766856
3 Cables Amps
39496585110135155190220250280305345375400425470530585
3 Cables Amps
39496585110135155190220250280305345375400425470530585
3 Cables Amps
38486483110125150175200220245260285310335355375425467
3 Cables Amps
38486483110125150175200220245260285310335355375425467
3 Cables Amps
35446082110130165205245280320370425475550590660743830
3 Cables Amps
35446082110130165205245280320370425475550590660743830
Thick-ness of PVC Insu-lation (Nom.) (mm)1.31.31.31.31.51.51.71.71.91.92.12.32.52.83.03.43.93.94.0
Over all Diameter (approx.) (mm)
891011121315171921232528303539444853
Nominal Dimen-sions of Armour Wire (mm)
1.401.401.401.401.401.401.401.401.601.601.601.601.602.002.002.002.002.002.50
Normal Dimen-sions of Armour Wire
1.801.801.801.801.801.801.801.801.802.002.002.002.002.002.202.202.402.402.60
Min. No.of wires
1166666121518183034345353535353
No. of cores and cross sectional area
1C x 41C x 61C x 101C x 161C x 251C x 351C x 501C x 701C x 951C x 1201C x 1501C x 1851C x 2401C x 3001C x 4001C x 5001C x 6301C x 8001C x 1000
No. of cores and cross sectional area
1C x 41C x 61C x 101C x 161C x 251C x 351C x 501C x 701C x 951C x 1201C x 1501C x 1851C x 2401C x 3001C x 4001C x 5001C x 6301C x 8001C x 1000
CURRENT RATINGS
CURRENT RATINGS
An ISO: 9001-2008 Certified Company
www.gridcables.com
1 Core Aluminium XLPE Armoured Power Cables
No. of cores and cross sectional area
1C x 251C x 351C x 501C x 701C x 951C x 1201C x 1501C x 1851C x 2401C x 3001C x 4001C x 5001C x 6301C x 8001C x 1000
Min. No. of wires
666121518183034345353535353
Thickness of XLPE Insulation (Nom.) (mm)
1.201.201.301.401.401.501.701.902.002.102.402.602.803.103.30
Nominal Dimensions of Armour Wire (mm)
1.401.401.401.401.601.601.601.601.601.602.002.002.002.002.50
Min. Thickness of PVC Outer Sheath (mm)1.24001.24001.24001.24001.40001.40001.40001.40001.40001.56001.56001.56001.72001.88002.0400
Overall Diameter (Approx.)
140001500017000190002100023000250002700029000320003700040000450005000056000
Approx. Net Wt. of Cable (Approx.)
27032039049065076088010501280153020002410299037304730
Max. D.C.Resistance
0at 20 C (Ohm/Km)
1.20000.86800.64100.44300.32000.25300.20600.16400.12500.10000.07780.06050.04690.03670.0291
Max. A.C.Resistance
0at 90 C (Ohms/Km)
1.54001.11000.82000.56700.41000.32500.26500.21000.16200.13000.10230.08080.06480.05300.0444
Approx. Reactance at 50 Hz (Ohm/Km)
0.1160.1100.1030.0990.0970.0930.0910.0900.0860.0850.0850.0830.0820.0810.081
Approx. Capac-itance (mFd/Km)
0.400.470.500.550.640.670.670.670.720.750.750.770.810.880.88
Direct in Ground
Amps96114135166198225253286332376431490557600650
CURRENT RATINGS
In Air
Amps981211501872302683093604335015966938148901050
1 Core Aluminium XLPE Unrmoured Power Cables
No. of cores and cross sectional area
1C x 251C x 351C x 501C x 701C x 951C x 1201C x 1501C x 1851C x 2401C x 3001C x 4001C x 5001C x 6301C x 8001C x 1000
Min. No. of wires
666121515153030305353535353
Thickness of Insulation (Nom.) (mm
0.900.901.001.101.101.201.401.601.701.802.002.202.402.602.80
Nom. Thickness of Outer Sheath (mm)
1.801.801.801.801.801.802.002.002.002.002.202.202.202.402.60
Overall Diameter (Approx.)
121315161820222427293336414651
Net Wt. of Cable (Approx.) (Kg/Km)
1902302803704605606908401030124015901960246031003850
Max. D.C. Resis-tance
0at 20 C (Ohms/Km)1.20000.86800.64100.44300.32000.25300.20600.16400.12500.10000.07750.06050.04690.03670.0291
Max. A.C. Resistance
0at 90 C (Ohms/Km)
1.54001.11000.82000.56700.41000.32500.26500.21100.16200.13000.10230.08080.06480.05300.0444
Approx. Reactance at 50 Hz (Ohm/Km)
0.1020.0970.0920.0880.0850.0820.0820.0820.0790.0780.0770.0760.0750.0750.068
Approx. Capacitance (mFd/Km)
0.520.600.630.680.790.790.790.790.840.860.880.900.940.971.01
Direct in Ground
Amps96114135166198225253286332376431490557600650
CURRENT RATINGS
In Air
Amps981211501872302683093604335015966938148901050
1 Core Aluminium XLPE Armoured Power Cables
1 Core Aluminium XLPE Unrmoured Power Cables
An ISO: 9001-2008 Certified Company
www.gridcables.com
1 Core Copper XLPE Unarmoured Power Cables
Thickness of XLPE Insulation (Nom.) (mm)
0.900.901.001.101.101.201.401.601.701.802.002.202.402.602.80
Nom. Thickness of PVC Outer Sheath (mm)1.81.81.81.801.801.802.002.002.002.002.22.22.22.42.6
Max. D.C. Resistance
0at 20 C(Ohms/Km)
0.7270.5240.3870.2680.1930.1530.1240.09910.07540.06010.04700.03660.02830.02110.0176
Approx. Net Wt. of Cable (Kg/Km)
3154095327319731207149118382356291637204708602276769587
Max. A.C. Resistance
0at 90 C(Ohms/Km)
0.930.6710.4950.3430.2470.1960.1590.1270.09650.07690.06020.04680.03620.02830.0225
Direct in Ground
Amps132156186228264300336366414450480570564660723
In Air
Amps1321561982462943363844445105706607088259451063
Approx. Reactance at 50 Hz (Ohm/Km)
0.1020.0970.0920.0880.0850.0820.0820.0820.0790.0780.0770.0760.0750.0750.068
Approx. Capacitance (mFd/Km)
0.520.600.630.680.790.790.790.790.840.860.880.900.940.971.01
CURRENT RATINGSOverall Diameter (Approx.)
121315161820222427293336414651
Min. No. of wires
666121518183034345353535353
No. of cores and cross sectional area
1C x 251C x 351C x 501C x 701C x 951C x 1201C x 1501C x 1851C x 2401C x 3001C x 4001C x 5001C x 6301C x 8001C x 1000
1 Core Copper XLPE Armoured Power Cables
Thickness of XLPE Insulation (Nom.) (Mm)
1.201.201.301.401.401.501.701.902.002.102.402.602.803.103.30
Nom. Thickness of PVC Outer Sheath (mm)1.401.401.401.401.601.601.601.601.601.602.002.002.002.002.50
Max. D.C. Resistance
0at 20 C(Ohms/Km)
0.7270.5240.3870.2680.1930.1530.1240.09910.07540.06010.04700.03660.02830.02210.0176
Approx. Net Wt. of Cable (Kg/Km)
395500634846113913901667203925843184409951186511825010386
Max. A.C. Resistance
0 at 90 C(Ohms/Km)
0.9300.6710.4950.3430.2470.1960.1590.1270.09650.07690.06020.04680.03620.02830.0225
Direct in Ground
Amps132156186228264300336366414450480570564660723
In Air
Amps11321561982462943363844445105706607088259451063
Approx. Reactance at 50 Hz (Ohm/Km)
0.1160.1100.1030.0990.0970.0930.0910.0900.0860.0850.0850.0830.0820.0810.081
Approx. Capacitance (mFd/Km)
0.400.470.500.550.640.670.670.670.720.750.750.770.810.880.88
CURRENT RATINGSOverall Diameter (Approx.)
141517192123252729323740455056
Min. Thickness of PVC Outer Sheath (mm)1.241.241.241.241.401.401.401.401.401.561.561.561.721.882.04
Min. No. of wires
666121518183034345353535353
No. of cores and cross sectional area
1C x 251C x 351C x 501C x 701C x 951C x 1201C x 1501C x 1851C x 2401C x 3001C x 4001C x 5001C x 6301C x 8001C x 1000
1 Core Copper XLPE Unarmoured Power Cables
1 Core Copper XLPE Armoured Power Cables
An ISO: 9001-2008 Certified Company
www.gridcables.com
No. of cores and cross sectional area
2C x 1.52C x 2.52C x 42C x 62C x 102C x 162C x 252C x 352C x 502C x 702C x 952C x 1202C x 1502C x 1852C x 2402C x 3002C x 400
2 Core Aluminium PVC Unarmoured Power Cables
No. of cores and cross sectional area
2C x 1.52C x 2.52C x 42C x 62C x 102C x 162C x 252C x 352C x 502C x 702C x 952C x 1202C x 1502C x 1852C x 2402C x 3002C x 400
2 Core Aluminium PVC Armoured Power Cables
2 Core Aluminium PVC Armoured Power Cables
2 Core Aluminium PVC Unamoured Power Cables
Min. No. of wires
1111166661215151530303053
Min. No. of wires
1111166661215151530303053
Thick-ness of PVC Insulation (Nom.) (Mm)0.80.91.01.01.01.01.21.21.41.41.61.61.82.02.22.42.6
Thick-ness of PVC Insulation(Nom.) (mm)0.800.901.001.001.001.001.201.201.401.401.601.601.802.002.202.402.60
Min. Thicknessof PVCInner-sheath(mm)0.30.30.30.30.30.30.30.30.30.30.40.40.40.50.50.60.7
Min. Thicknessof PVC Innersheath (mm)0.300.300.300.300.300.300.300.300.300.300.400.400.400.500.500.600.70
Nominal Dimensions of Armour (mm)
Strip-----4x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.8
Nom. Thickness of Outer Sheath (mm)
1.801.801.801.801.801.802.002.002.002.002.202.202.402.402.602.803.20
Wire1.401.401.401.401.401.601.601.601.601.602.002.002.002.002.502.503.15
Overall Diameter (Approx.)
10.4011.9013.4014.4015.9017.8018.7020.2022.7025.3029.0031.0034.5037.5042.5046.5052.50
Min. Thickness of PVC Outer Sheath (mm)
Strip Armour-----1.401.401.401.401.561.561.561.721.882.042.202.36
Wire Armour1.241.241.241.241.241.401.401.401.561.561.561.721.721.882.042.202.52
Net Wt. of Cable(Approx.)
1702102653203903304605506908501125131015751910236529603755
Overall Diameter (Approx.) (mm)
Strip Armour-----20.521.022.525.028.031.533.537.041.045.550.055.5
Max. D.C. Resist-ance
0 at 20 C (Ohms/Km)18.1012.107.414.613.081.911.200.8680.6410.4430.3200.2530.2060.1640.1250.1000.0778
Wire Armour13.515.016.517.519.022.523.024.027.029.534.036.539.543.049.053.560.5
Max. A.C. Resistance
0 at 70 C (Ohms/Km)
21.7214.528.895.533.702.291.441.040.770.530.380.300.250.200.150.120.09
Approx. Net. Wet. Of Cable
Strip Armour (Kg/Km)-----565700810100012301520176520802500307537604560
Wire Armour(Kg/Km)3904505506407458309051040129015102060236027003175423049506560
Approx. Reactance at 50 Hz (Ohm/Km)
0.1260.1190.1160.1100.1000.0970.0970.0970.0940.0900.0900.0870.0870.0870.0870.0860.086
Max.D.C.Resis-tanc at
020 C (Ohms/Km)18.1012.107.414.613.081.911.200.8680.6410.4430.3200.2530.2060.1640.1250.1000.0778
Approx. Capacitance (mFd/Km)
0.1400.1500.1600.1900.2200.2900.3200.3700.3700.4400.4400.4900.4900.4900.5000.5200.530
Max. A.C. Resis-tance at
070 (Ohms/Km)21.7214.528.895.533.702.291.441.040.770.530.380.300.250.200.150.120.09
Approx. React-ance at 50 Hz (Ohm/Km)0.1260.1190.1160.1100.1000.0970.0970.0970.0940.0900.0900.0870.0870.0870.0870.0860.086
Direct in Ground
Amps18253240557090110135160190210240275320355385
CURRENT RATINGS
Approx. Capacitance (mFd/Km)
0.140.150.160.190.220.290.320.370.370.440.440.490.490.490.500.520.53
IIn duct
Amps1621273445587692115140170190210240275305345
Direct in Ground
Amps18253240557090110135160190210240275320355385
CURRENT RATINGS
in duct
Amps1621273445587692115140170190210240275305345
In Air
Amps1621273547597899125150185210240275325365420
In Air
Amps1621273547597899125150185210240275325365420
An ISO: 9001-2008 Certified Company
www.gridcables.com
2 Core Copper PVC Armoured Power Cables
2 Core Copper PVC Armoured Power Cables
2 Core Copper PVC Unarmoured Power Cables
2 Core Copper PVC Unarmoured Power Cables
Min. Thicknessof PVCInner-sheath(mm)0.30.30.30.30.30.30.30.30.30.30.40.40.40.50.50.60.7
Nominal Dimensions of Armour (mm)
Strip-----4x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.8
Min. Thickness of PVC Outer Sheath (mm)
Strip Armour-----1.401.401.401.401.561.561.561.721.882.042.202.36
Overall Diameter (Approx.) (mm)
Strip Armour-----20.521.022.525.028.031.533.537.041.045.550.055.5
Approx. Net. Wet. Of Cable
Strip Armour (Kg/Km)-----7499941222155020352649318538354689596273849188
Max.D.C.Resis-tanc at
020 C (Ohms/Km)12.17.414.613.081.831.150.7270.5240.3870.2680.1930.1530.1240.09910.07540.06010.0470
Max. A.C. Resis-tance at
070 C (Ohms/Km)14.58.875.523.692.191.380.870.6270.4630.3210.2310.1840.1490.1200.09120.07390.0592
Approx. React-ance at 50 Hz (Ohm/Km)0.1260.1190.1160.1100.1000.0970.0970.0970.0940.0900.0900.0870.0870.0870.0870.0860.086
Approx. Capacitance (mFd/Km)
0.140.150.160.190.220.290.320.370.370.440.440.490.490.490.500.520.53
Direct in Ground
Amps233241507090115140165205240275310350405450490
In Air
Amps202735456078105125155195230265305350410465530
Thick-ness of PVC Insulation (Nom.) (Mm)0.80.91.01.01.01.01.21.21.41.41.61.61.82.02.22.42.6
Min. No. of wires
1111666661215181830343453
No. of cores and cross sectional area
2C x 1.52C x 2.52C x 42C x 62C x 102C x 162C x 252C x 352C x 502C x 702C x 952C x 1202C x 1502C x 1852C x 2402C x 3002C x 400
CURRENT RATINGS
Wire1.401.401.401.401.401.601.601.601.601.602.002.002.002.002.502.503.15
Wire Armour1.241.241.241.241.241.401.401.401.561.561.561.721.721.882.042.202.52
Wire Armour13.515.016.517.519.022.523.024.027.029.534.036.539.543.049.053.560.5
Wire Armour(Kg/Km)407482596711863912119715311836231631873775444953597100856211171
Min. Thickness of PVC Innersheath (mm)0.300.300.300.300.300.300.300.300.300.300.400.400.400.500.500.600.70
Nom. Thickness of Outer Sheath (mm)1.801.801.801.801.801.802.002.002.002.002.202.202.402.402.602.803.20
Overall Diameter (Approx.)
10.4011.9013.4014.4015.9017.8018.7020.2022.7025.3029.0031.0034.5037.5042.5046.5052.50
Net Wt. of Cable (Approx.)
194248316397515521766971125816762276276033664143535366548466
Max. A.C. Resistance
0at 20 C(Approx.) (Ohm/Km)12.17.414.613.081.831.150.7270.5240.3870.2680.1930.1530.1240.09910.07540.06010.0470
Max. D.C. Resistance
0at 70 C (Ohms/Km)14.58.875.523.692.191.380.870.6270.4630.3210.2310.1840.1490.1200.09120.07390.0532
Approx. Reactance at 50 Hz (Ohm/Km)
0.1260.1190.1160.1100.1000.0970.0970.0970.0940.0900.0900.0870.0870.0870.0870.0860.086
Approx. Capac-itance (mFd/Km)
0.140.150.410.470.560.760.860.981.021.181.201.311.311.311.341.411.45
Direct inGroundAmps233241507090115140165205240275310350405450491
In duct
Amps20273544587597120145180215235270300345385425
In Air
Amps202735456078105125155195230265305350410465530
Thickness of PVCInsulation (Nom.) (mm)0.800.901.001.001.001.001.201.201.401.401.601.601.802.002.202.402.60
Min. No. of wires
1111666661215181830343453
No. of cores and cross sectional area
2C x 1.52C x 2.52C x 42C x 62C x 102C x 162C x 252C x 352C x 502C x 702C x 952C x 1202C x 1502C x 1852C x 2402C x 3002C x 400
CURRENT RATINGS
An ISO: 9001-2008 Certified Company
www.gridcables.com
2 Core Aluminium XLPE Armoured Power Cables
2 Core Aluminium XLPE Unarmoured Power Cables
No. of cores and cross sectional area
2C x 252C x 352C x 502C x 702C x 952C x 1202C x 1502C x 1852C x 2402C x 3002C x 400
No. of cores and cross sectional area
2C x 252C x 352C x 502C x 702C x 952C x 1202C x 1502C x 1852C x 2402C x 3002C x 400
Min. No. of wires
6661215151530303053
Min. No. of wires
6661215151530303053
Thick-ness of PVC Insulation (Nom.) (Mm)0.900.901.001.101.101.201.401.601.701.802.00
Thickness of Insulation(Nom.) (mm)
0.900.901.001.101.101.201.401.601.701.802.00
Min. Thicknessof PVCInner-sheath(mm)0.30.30.30.30.40.40.40.50.50.60.6
Nominal Dimensions of Armour (mm)
Strip1.601.601.601.602.002.002.002.002.502.502.50
Min. Thickness of inner sheath (mm)
0.30.30.30.30.40.40.40.50.50.60.6
Wire4x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.8
Min. Thickness of PVC Outer Sheath (mm)
Strip Armour1.401.401.401.561.561.561.721.882.042.202.36
Nom. Thickness of Outer Sheath (mm)
2.002.002.002.002.202.202.202.402.602.803.00
Wire Armour1.401.401.401.561.561.561.721.721.882.042.36
Overall Diameter (Approx.)
1820222528303336404449
Overall Diameter (Approx.) (mm)
Strip Armour2122242731333639454854
Wire Armour1921232628313437414450
Net Wt. of Cable (Approx.)
420.00510.00630.00800.001040.001260.001480.001840.002250.002810.003530.00
Approx. Net. Wet. Of Cable
Strip Armour (Kg/Km)840970115014301900222025503030393046505600
Max. D.C. Resistance
0at 20 C (Ohms/Km)
1.200.870.640.440.320.250.210.160.130.100.08
Wire Armour(Kg/Km)63074090011401390166019302320279033904230
Max. A.C. Resistance
0at 90 C (Ohms/Km)
1.541.110.820.570.410.330.270.210.160.130.10
Max.D.C.Resis-tanc at
020 C (Ohms/Km)1.20000.86800.64100.44300.32000.25300.20600.16400.12500.10000.0778
Max. A.C. Resis-tance at
090 C (Ohms/Km)1.54001.11000.82000.56700.41000.32500.26500.21100.16200.13000.1023
Approx. Reactance at 50 Hz (Ohm/Km)
0.0800.0800.0780.0770.0740.0720.0720.0720.0720.0710.070
Approx. React-ance at 50 Hz (Ohm/Km)0.0800.0800.0780.0770.0740.0720.0720.0720.0720.0710.070
Approx. Capacitance (mFd/Km)
0.200.230.240.260.290.290.290.290.310.330.33
Approx. Capacitance (mFd/Km)
0.200.230.240.260.290.290.290.290.310.330.33
CURRENT RATINGS
Direct in Ground
Amps112138169200238262300344400444481
CURRENT RATINGS
Direct in Ground
Amps112138169200238262300344400444481
In Air
Amps98124156188231262300344406456525
In Air
Amps98124156188231262300344406456525
2 Core Aluminium XLPE Armoured Power Cables
2 Core Aluminium XLPE Unarmoured Power Cables
An ISO: 9001-2008 Certified Company
www.gridcables.com
2 Core Copper XLPE Armoured Power Cables
2 Core Copper XLPE Armoured Power Cables
2 Core Copper XLPE Unamoured Power Cables
Thick-ness of XLPE Insu-lation (Nom.) (Mm)
0.900.901.001.101.101.201.401.601.701.802.00
Min. Thick-ness of PVC inner sheath (mm)
0.30.30.30.30.40.40.40.50.50.60.6
Max.D.C. Resis-tance at
020 C (Ohms/Km)
0.7270.5240.3870.2680.1930.1530.1240.09910.07540.06010.0470
Max. A.C. Resis-tance at
090 C (Ohms/Km)
0.9300.6710.4950.3430.2470.1960.1590.1270.09650.07690.0602
Approx. Reac-tance at 50 Hz (Ohm/Km)
0.0800.0800.0780.0770.0740.0720.0720.0720.0720.0710.070
Approx. Capac-itance (mFd/Km)
0.200.230.240.260.290.290.290.290.310.330.33
Nominal Dimensions of Armour (mm)
Strip4x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.8
Min. Thickness of PVC Outer Sheath (mm)
Strip Armour1.401.401.401.561.561.561.721.882.042.202.36
Overall Diameter (Approx.) (mm)
Strip Armour21.122.024.027.031.033.036.039.045.048.054.0
Approx. Net. Wet of Cable
Strip Armour (Kg/Km)10591299160721062847342940624936648778319688
Direct in GroundAmps144175206256300344388438506562612
In Air
Amps131150194244288331381438512581662
Wire1.601.601.601.602.002.002.002.002.502.502.50
Wire Armour1.401.401.401.561.561.561.721.721.882.042.36
Wire Armour19.021.023.026.028.031.034.037.041.044.050.0
Wire Armour (Kg/Km)8721087137918452388291835004295544966788437
CURRENT RATINGSMin. No. of wires
6661215181830343453
No. of cores and cross sectional area
2C x 252C x 352C x 502C x 702C x 952C x 1202C x 1502C x 1852C x 2402C x 3002C x 400
Thickness of XLPE Insulation (Nom.) (mm)
0.900.901.001.101.101.201.401.601.701.802.00
Min. Thickness of PVC inner sheath (mm)0.30.30.30.30.40.40.40.50.50.60.6
Overall Diameter (Approx.)
18.020.022.025.028.030.033.036.040.044.049.0
Approx. Net Wt. of Cable (Approx.)
672865111415192048252630623813491761077732
Max. D.C. Resistance
0 at 20 C(Ohms/Km)
0.7270.5240.3870.2680.1930.1530.1240.09910.07540.06010.0470
Direct in Ground
Amps144175206256300344388438506562612
In Air
Amps131150194244288331381438512581662
Max. A.C. Resistance
0at 90 C (Ohms/Km)
0.9300.6710.4950.3430.2470.1960.1590.1270.09650.07690.0602
Approx. Reactance at 50 Hz (Ohm/Km)
0.0800.0800.0780.0770.0740.0720.0720.0720.0720.0710.070
Approx. Capacitance (mFd/Km)
0.200.230.240.260.290.290.290.290.310.330.33
CURRENT RATINGSNom. Thickness of PVC Outer Sheath (mm)2.002.002.002.002.202.202.202.402.602.803.00
Min. No. of wires
6661215181830343453
No. of cores and cross sectional area
2C x 252C x 352C x 502C x 702C x 952C x 1202C x 1502C x 1852C x 2402C x 3002C x 400
2 Core CopperXLPE Unarmoured Power Cables
An ISO: 9001-2008 Certified Company
www.gridcables.com
3 Core Aluminium pvc Armoured Power Cables
3 Core Aluminium pvc Armoured Power Cables
3 Core Aluminium pvc Unarmoured Power Cables
No. of cores and cross sectional area3C x 1.53C x 2.53C x 43C x 63C x 103C x 163C x 253C x 353C x 503C x 703C x 953C x 1203C x 1503C x 1853C x 2403C x 3003C x 400
3 Core Aluminium PVC Unarmoured Power Cables
No. of cores and cross sectional area
3C x 1.53C x 2.53C x 43C x 63C x 103C x 163C x 253C x 353C x 503C x 703C x 953C x 1203C x 1503C x 1853C x 2403C x 3003C x 400
Min. No. of wires
1111166661215151530303053
Min. No.Of wires
1111166661215151530303053
Thickness of pvc Insulation (nom) (min.)
0.80.91.01.01.01.01.21.21.41.41.61.61.82.02.22.42.6
Min. Thick-ness of Innersheath (mm)0.30.30.30.30.30.30.30.30.30.40.40.40.50.50.60.60.7
Thick-ness of PVC Insulation (Nom.) (Mm)0.800.901.001.001.001.001.201.201.401.401.601.601.802.002.202.402.60
Nominal Dimensions of Armour (mm)
Strip-----4x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.8
Min. Thick-ness of PVC Inner-sheath (mm)0.300.300.300.300.300.300.300.300.300.400.400.400.500.500.600.600.70
Wire1.401.401.401.401.401.601.601.601.602.002.002.002.002.502.502.503.15
Min. Thickness of PVC Outer Sheath (mm)
Strip Armour-----1.401.401.401.561.561.561.721.881.882.202.362.52
Nom. Thick-ness of Outer Sheath (mm)1.801.801.801.801.801.802.002.002.002.202.202.202.402.602.803.003.40
Wire Armour1.241.241.241.241.401.401.401.401.561.561.721.721.882.042.202.362.68
Overall Diameter (Approx.)
11.0012.0013.5014.4015.6016.8020.2021.7024.8028.5031.6034.7038.9044.5049.0053.5062.00
Overall Diameter (Approx.) (mm)
Strip Armour-----19.522.524.027.530.534.538.041.545.552.056.564.5
Wire Armour14.015.016.517.519.521.024.025.529.033.037.040.044.049.055.060.069.5
Net Wt. of Cable (Approx.)
19023030035043543560073092012151545183022502760351542755400
Approx. Net. Wet of Cable
Strip Armour (Kg/Km)-----6808801025131016301990237528253365425051406270
Max. D.C. Resis-tance
0at 20 C (Ohm/Km)
18.1012.107.414.613.081.911.200.8680.6410.4430.3200.2530.2060.1640.1250.1000.0778
Wire Armour (Kg/Km)42050059568583089011201305160521602645305035604590562066508720
Max. D.C. Resistance
0at 20 C (Ohms/Km)
18.1012.107.414.613.081.911.200.8680.6410.4430.3200.2530.2060.1640.1250.1000.0778
Max. A.C. Resis-tance
0at 70 C (Ohms/Km)21.7214.528.895.533.702.291.441.040.770.530.380.300.250.200.150.120.09
Approx. React-ance at 50 Hz (Ohm/Km)0.1260.1190.1160.1100.1000.0970.0970.0970.0940.0900.0900.0870.0870.0870.0870.0860.086
Max. A.C. Resistance
0at 70 C (Ohms/Km)
21.7214.528.895.533.702.291.441.040.770.530.380.300.250.200.150.120.09
Approx. Capa-citance (mFd/Km)
0.1400.1500.4100.4700.5600.7600.8600.9801.0201.1801.2001.3101.3101.3101.3401.4101.450
Approx. React-ance at 50 Hz (Ohm/Km)0.1260.1190.1160.1100.1000.0970.0970.0970.0940.0900.0900.0870.0870.0870.0870.0860.086
Approx.Capaci-tance (mFd/Km)
0.140.150.410.470.560.760.860.981.021.181.201.311.311.311.341.411.45
Direct in GroundAmps
1621283546607692110135165185210235275305335
CURRENT RATINGS
Direct in GroundAmps1621283546607692110135165185210235275305335
CURRENT RATINGS
In duct
Amps
141823303950637795115140155175200235260290
In duct
Amps141823303950637795115140155175200235280290
In Air
Amps1318233040517086105130155180205240280315375
In AirAmps
1318233040517086105130155180205240280315375
An ISO: 9001-2008 Certified Company
www.gridcables.com
3 Core Copper pvc Unarmoured Power Cables
Min. Thick-ness of PVC Inner-sheath (mm)0.30.30.30.30.30.30.30.30.30.40.40.40.50.50.60.60.7
Nom. Thick-ness of Outer Sheath (mm)1.801.801.801.801.801.802.002.002.002.202.202.202.402.602.803.003.40
Overall Diameter (Approx.)
11.0012.0013.5014.4015.6016.8020.2021.7024.8028.5031.6034.7038.9044.5049.0053.5062.00
Net Wt. of Cable (Approx.)
218284372470629723106313671783245832764009493961147928981712540
Max. A.C. Resis-tance
0at 20 C
(Ohm/Km)14.508.875.523.692.191.380.870.6270.4630.3210.2310.1840.1490.1200.09120.07390.0592
Max. D.C. Resis-tance
0at 70 C (Ohms/Km)12.107.414.613.081.831.150.730.5240.3870.2680.1930.1530.1240.0990.0750.0600.0470
Approx. React-ance at 50 Hz (Ohm/Km)0.1260.1190.1160.1100.1000.0970.0970.0970.0940.090.090.0870.0870.0870.0870.0860.086
Approx. Capa-citance (mFd/Km)
0.1400.1500.4100.4700.5600.7600.8600.9801.0201.1801.2001.3101.3101.3101.3401.4101.450
Direct in GroundAmps
21273645607799120145175210240270300345385425
In duct
Amps
1724303850648199125150175195225255295335360
In AirAmps
17243039576690110135165200230265305355400455
Thick-ness of PVC Insulation (Nom.) (Mm)0.80.91.001.001.001.001.201.201.401.401.601.601.802.002.202.402.60
Min. No.Of wires
1111666661215181830343453
No. of cores and cross sectional area
3C x 1.53C x 2.53C x 43C x 63C x 103C x 163C x 253C x 353C x 503C x 703C x 953C x 1203C x 1503C x 1853C x 2403C x 3003C x 400
CURRENT RATINGS
Thickness of PVC Insulation (Nom.) (Mm)
0.80.91.001.001.001.001.201.201.401.401.601.601.802.002.202.402.60
Nominal Dimensions of Armour (mm)
Strip0.30.30.30.30.30.30.30.30.30.40.40.40.50.50.60.60.7
Min. Thickness of PVC Outer Sheath (mm)
Strip Armour-----1.41.41.41.561.561.561.721.881.882.202.362.52
Overall Diameter (Approx.) (mm)
Strip Armour-----19.522.524.027.530.534.538.041.545.552.056.564.5
Approx. Net. Wet of Cable
Strip Armour (Kg/Km)-----9491339168721702863375345685556676387191066513490
Max. D.C. Resistance
0at 20 C(Ohms/Km)
12.17.414.613.081.831.150.7270.5240.3870.2680.1930.1530.1240.09910.07540.06010.0470
Max. A.C. Resistance
0at 70 C (Ohms/Km)
14.58.875.523.692.191.380.870.6270.4630.3210.2310.1840.1490.1200.09120.07390.0592
Approx. React-ance at 50 Hz (Ohm/Km)0.1260.1190.1160.1100.1000.0970.0970.0970.0940.0900.0900.0870.0870.0870.0870.0860.086
Approx.Capaci-tance (mFd/Km)
0.140.150.410.470.560.760.860.981.021.181.201.311.311.311.341.411.45
Direct in GroundAmps21273645607799120145175210240270300345385425
In Air
Amps17243039576690110135165200230265305355400455
Min. No. of wires
1111666661215181830343453
Min. Thickness of PVC Inner-sheath (mm)0.30.30.30.30.30.30.30.30.30.40.40.40.50.50.60.60.7
No. of cores and cross sectional area3C x 1.53C x 2.53C x 43C x 63C x 103C x 163C x 253C x 353C x 503C x 703C x 953C x 1203C x 1503C x 1853C x 2403C x 3003C x 400
CURRENT RATINGS
Wire1.41.41.41.41.41.61.61.61.62.02.02.02.02.52.52.53.2
Wire Armour1.241.241.241.241.401.401.401.401.561.561.721.721.882.042.202.362.68
Wire Armour14.015.016.517.519.521.024.025.529.033.037.540.544.049.055.560.069.5
Wire Armour (Kg/Km)4425426637891017115315531915243033554362522162617948100621213215954
3 Core Copper ovc Armoured Power Cables
3 Core Copper pvc Armoured Power Cables
3 Core Copper pvc Unarmoured Power Cables
An ISO: 9001-2008 Certified Company
www.gridcables.com
3 Core Aluminium XLPE Armoured Power Cables
3 Core Aluminium XLPE Armoured Power Cables
3 Core Aluminium XLPE Unarmoured Power Cables
No. ofcores andcross sectional area
3C x 253C x 353C x 503C x 703C x 953C x 1203C x 1503C x 1853C x 2403C x 3003C x 400
3 Core Aluminium XLPE Unarmoured Power Cables
No. of cores and cross sectional area
3C x 253C x 353C x 503C x 703C x 953C x 1203C x 1503C x 1853C x 2403C x 3003C x 400
Min. No.ofwires
6661215151530303053
Min. No. of wires
6661215151530303053
Thicknessof Insul-ation (Nom.) (mm)
0.90.911.11.11.21.41.61.71.82
Thickness of Insulation (Nom.) (mm)
0.900.901.001.101.101.201.401.601.701.802.00
Min. Thickness of Innersheath (mm)
0.30.30.30.40.40.40.50.50.60.60.7
Nominal Dimensions of Armour (mm)
Strip
1.61.61.62.02.02.02.02.52.52.53.15
Min. Thickness of inner sheath (mm)
0.300.300.300.400.400.400.500.500.600.600.70
Wire
4x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.8
Min. Thickness of Outer Sheath (mm)
Strip Armour1.41.41.561.561.561.721.882.042.22.362.68
Nom. Thickness of Outer Sheath (mm)
2222.22.22.22.42.62.833.2
Wire Armour1.41.41.41.561.561.561.721.882.042.22.52
Overall Diameter (Approx.)
2123252932353943485359
Overall Diameter (Approx.) (mm)
Strip Armour2325283235394247535865
Wire Armour21.323263032363944495460
Net Wt. of Cable (Approx.)
52064070010801350164020202490315038904840
Approx. Net. Wet of Cable
Strip Armour (Kg/Km)9801160132019502320277032604220511060308010
Max. D.C. Resistance
0at 20 C(Ohms/Km)
1.20000.86800.64100.44300.32000.25300.20600.16400.12500.10000.0778
Wire Armour (Kg/Km)770900100014501750210025203050377045405640
Max. D.C. Resis-tance at
020 C (Ohms/Km)1.20.8680.6410.4430.3200.2530.2060.1640.1250.10.0778
Max. A.C. Resistance
0at 90 C(Ohms/Km)
1.54001.11000.82000.56700.41000.32500.26500.21100.16200.13000.1023
Max. A.C. Resistance
0at 90 C (Ohms/Km)
1.541.110.820.5670.410.3250.2650.2110.1620.130.1023
Approx. Reactance at 50 Hz (Ohm/Km)
0.0800.0800.0780.0770.0740.0720.0720.0720.0720.0710.070
Approx. Reactance at 50 Hz (Ohm/Km)
0.080.080.0780.0770.0740.0720.0720.0720.0720.0710.07
Approx. Capacitance (mFd/Km)
0.200.230.240.260.290.290.290.290.310.330.33
Approx. Capaci-tance (mFd/Km)
0.20.230.240.260.290.290.290.290.310.330.33
CURRENT RATINGS
In duct
Amps94113133164196223249282326367418
Direct in Ground
Amps94113133164196223249282326367418
CURRENT RATINGS
In Air
Amps96117142179221257292337399455530
In Air
Amps96117142179221257292337399455530
An ISO: 9001-2008 Certified Company
www.gridcables.com
Direct in GroundAmps119144174210252288324360414462510
In Air
Amps108132162198240276318366426480546
Wire1.601.601.602.002.002.002.002.502.502.503.15
Wire Armour1.401.401.401.561.561.561.721.882.042.202.52
Wire Armour1.401.401.401.561.561.561.721.882.042.202.52
Wire Armour (Kg/Km)21.323.026.030.032.036.039.044.049.054.060.0
Wire Armour (Kg/Km)117714691872257033334085498861377838966712190
3 Core Copper XLPE Armoured Power Cables
Min.Thick-ness of PVC Innersheath(mm)
0.30.30.30.40.40.40.50.50.60.60.7
Nominal Dimensions of Armour (mm)
Strip4x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.8
Min. Thickness of PVC Outer Sheath (mm)
Strip Armour1.401.401.561.561.561.721.882.042.202.362.68
Overall Diameter (Approx.) (mm)
Strip Armour23.025.028.032.035.039.042.047.053.058.065.0
Overall Diameter (Approx.) (mm)
Strip Armour23.025.028.032.035.039.042.047.053.058.065.0
Approx. Net. Wet of Cable
Strip Armour (Kg/Km)1373171321713052386847255691724591121108714437
Max. D.C.Resis-tance
0 at 20 C (Ohms/Km)0.7270.5240.3870.2680.1930.1530.1240.09910.07540.06010.0470
Max. A.C.Resistance at
090 C (Ohms/Km)0.9300.6710.4950.3430.2470.1960.1590.1270.09650.07690.0602
Approx. Reac-tance at 50 Hz (Ohm/Km)0.0800.0800.0780.0770.0740.0720.0720.0720.0720.0710.070
Approx. Capacitance (mFd/Km)
0.200.230.240.260.290.290.290.290.310.330.33
Thickness of XLPE Insulation (Nom.) (mm)
0.900.901.001.101.101.201.401.601.701.802.00
Min. No. of wires
6661215181830343453
No. of cores and cross sectional area
3C x 253C x 353C x 503C x 703C x 953C x 1203C x 1503C x 1853C x 2403C x 3003C x 400
CURRENT RATINGS
Thickness of XLPE Insulation (Nom.) (mm)
0.900.901.001.101.101.201.401.601.701.802.00
Min. Thickness of inner sheath (mm)
0.30.30.30.40.40.40.50.50.60.60.7
Overall Diameter (Approx.)
21.023.025.029.032.035.039.043.048.053.059.0
Net Wt. of Cable (Approx.)
93512191578222229483659451156007249900111429
Direct in Ground
Amps119144174210252288324360414462510
In Air
Amps108132162198240276318366426480546
Max. D.C. Resistance
0at 20 C (Ohms/Km)
0.7270.5240.3870.2680.1930.1530.1240.09910.07540.06010.0470
Max. A.C. Resistance
0at 90 C (Ohms/Km)
0.9300.6710.4950.3430.2470.1960.1560.1270.09650.07690.0602
Approx. Reactance at 50 Hz (Ohm/Km)
0.0800.0800.0780.0770.0740.0720.0720.0720.0720.0710.070
Approx. Capacitance (mFd/Km)
0.200.230.240.260.290.290.290.290.310.330.33
CURRENT RATINGSNom. Thickness of PVC Outer Sheath (mm)2.002.002.002.202.202.202.402.602.803.003.20
Min. No. of wires
6661215181830343453
No. of cores and cross sectional area
3C x 253C x 353C x 503C x 703C x 953C x 1203C x 1503C x 1853C x 2403C x 3003C x 400
3 Core Copper XLPE Unarmoured Power Cables
3 Core Copper XLPE Armoured Power Cables
3 Core Copper XLPE Unarmoured Power Cables
An ISO: 9001-2008 Certified Company
www.gridcables.com
3.5 Core Aluminium PVC Armoured Power Cables
No. ofcores andcross sectional area
3.5C x 25/163.5C x 35/163.5C x 50/253.5C x 70/353.5C x 95/503.5C x 120/703.5C x 150/703.5C x 185/953.5C x 240/1203.5C x 300/1503.5C x 400/185
No. of cores and cross sectional area3.5C x 25/163.5C x 35/163.5C x 50/253.5C x 70/353.5C x 95/503.5C x 120/703.5C x 150/703.5C x 185/953.5C x 240/1203.5C x 300/1503.5C x 400/185
3.5 Core Aluminium PVC Unarmoured Power Cables
Min. No.ofwires
6/6.6/6.6/6.12/6.15/6.15/12.15/12.30/15.30/15.30/15.53/30.
Min. No. of wires
6/6.6/6.6/6.12/6.15/6.15/12.15/12.30/15.30/15.30/15.53/30.
Thick-nessof Insul-ation (Nom.) (Mm)1.2/1.01.2/1.01.4/1.21.4/1.21.6/1.41.6/1.41.8/1.42.0/1.62.2/1.62.4/1.82.6/2.0
Thickness of PVC Insulation (Nom.) (mm)1.2/1.01.2/1.01.4/1.21.4/1.21.6/1.41.6/1.41.8/1.42.0/1.62.2/1.62.4/1.82.6/2.0
Min. Thick-ness of Innersheath (mm)0.300.300.300.400.400.500.500.500.600.600.70
Nominal Dimensions of Armour (mm)
Strip
4x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.8
Min. Thickness of PVC Innersheath (mm)0.300.300.300.400.400.500.500.500.600.600.70
Wire
1.601.601.602.002.002.002.002.502.503.153.15
Nom. Thickness of Outer Sheath (mm)2.002.002.002.202.202.402.402.603.003.203.40
Min. Thickness of Outer Sheath (mm)
Strip Armour1.401.401.561.561.561.721.882.042.202.362.68
Wire Armour1.401.401.561.561.721.881.882.042.362.522.68
Overall Diameter (Approx.)
22.7024.0027.0031.0035.0040.0042.3046.8054.5059.0067.00
Overall Diameter (Approx.) (mm)
Strip Armour25.026.029.533.537.541.045.550.057.061.570.0
Net Wt. of Cable (Approx.)
700830106013951795220025753150406049706210
Wire Armour26.527.531.036.040.043.048.053.560.066.075.0
Max. D.C. Resistance
0at 20 C (Ohm/Km)
1.200.8680.6410.4430.3200.2530.2060.1640.1250.1000.0778
Approx. Net. Wet of Cable
Strip Armour (Kg/Km)10001170147018102305276032153900484058357250
Wire Armour (Kg/Km)12601450180524053015354540305300639082109900
Max. A.C. Resistance
0at 70 C (Ohms/Km)
1.441.040.770.530.380.300.250.200.150.120.09
Max. D.C. Resis-tance at
020 C (Ohms/Km)1.20000.86800.64100.44300.32000.25300.20600.16400.12500.10000.0778
Approx. Reactance at 50 Hz (Ohm/Km)
0.0970.0970.0940.0900.0900.0870.0870.0870.0870.0860.086
Max. A.C. Resis-tance
0at 70 C (Ohms/Km)1.441.040.770.530.380.300.250.200.150.120.09
Approx. Capacitance (mFd/Km)
0.860.981.021.181.201.311.311.311.341.411.45
Approx. React-anceat 50 Hz (Ohm/Km)0.0970.0970.0940.0900.0900.0870.0870.0870.0870.0860.086
Approx. Capaci-tance (mFd/Km)
0.860.981.021.181.201.311.311.311.341.411.45
Direct inGroundAmps7692110135165185210235275305335
CURRENT RATINGS
Direct in GroundAmps7692100135165185210235275305335
CURRENT RATINGS
In duct
Amps637795115140155175200235260290
In duct
Amps637795115140155175200235260290
In Air
Amps7086105130155180205240280315375
In Air
Amps7086105130155180205240280315375
3.5 Core Aluminium PVC Unarmoured Power Cables
3.5 Core Aluminium PVC Armoured Power Cables
An ISO: 9001-2008 Certified Company
www.gridcables.com
Min. Thickness of PVC Innersheath (mm)0.300.300.300.400.400.500.500.500.600.600.70
Nom. Thickness of Outer Sheath (mm)2.002.002.002.202.202.402.402.603.003.203.40
Overall Diameter (Approx.)
22.7024.0027.0031.0035.0040.0042.3046.8054.5059.0067.00
Net Wt. of Cable (Approx.)
1255156120712845380447885673708091941140014395
Max. D.C. Resistance
0at 20 C (Approx.) (Ohm/Km)0.730.5240.3870.2680.1930.1530.1240.0990.0750.0600.0470
Max. D.C. Resistance
0at 70 C (Ohms/Km)
0.870.6270.4630.3210.2310.1840.1490.12000.09120.07390.0592
Approx. Reactance at 50 Hz (Ohm/Km)
0.0970.0970.0940.0900.0900.0870.0870.0870.0870.0860.086
Approx. Capacitance (mFd/Km)
0.860.981.021.181.201.311.311.311.341.411.45
Direct inGroundAmps99120145175210240270300345385425
In duct
Amps8199125150175195225255295335360
In Air
Amps90110135165200230265305355400455
Thickness of PVC Insulation (Nom.) (mm)1.2/1.01.2/1.01.4/1.21.4/1.21.6/1.41.6/1.41.8/1.42.0/1.62.2/1.62.4/1.82.6/2.0
Min. No. of wires
6/6.6/6.6/6.12/6.15/6.18/12.18/12.30/15.34/18.34/18.53/30.
No. of cores and cross sectional area
3.5C x 25/163.5C x 35/163.5C x 50/253.5C x 70/353.5C x 95/503.5C x 120/703.5C x 150/703.5C x 185/953.5C x 240/1203.5C x 300/1503.5C x 400/185
CURRENT RATINGS
3.5 Core Copper PVC Unarmoured Power Cables
Thickness of PVC Insulation (Nom.) (mm)
1.2/1.01.2/1.01.4/1.21.4/1.21.6/1.41.6/1.41.8/1.42.0/1.62.2/1.62.4/1.82.6/2.0
Min. Thickness of PVC Inner-sheath(mm)0.30.30.30.40.40.50.50.50.60.60.7
Nominal Dimensions of Armour (mm)
Strip4x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.8
Min. Thickness of PVC Outer Sheath (mm)
Strip Armour1.401.401.561.561.561.721.882.042.202.362.68
Overall Diameter (Approx.) (mm)
Strip Armour25.026.029.533.537.541.045.550.057.061.570.0
Approx. Net. Wet of Cable Strip
Armour(Kg/Km)15841896248033024349533563597821100271227715402
Max. A.CResista-nce at
070 C (Ohms/Km)0.870.6270.4630.3210.2310.1840.1490.1200.09120.07390.0592
Approx. React-ance at 50 Hz (Ohm/Km)0.0970.0970.0940.0900.090.0870.0870.0870.0870.0860.086
Approx. Capac-itance (mFd/Km)
0.860.981.021.181.201.311.311.311.341.411.45
Direct inGroundAmps99120145175210240270300345385425
In Air
Amps90110135165200230265305355400455
Min. No. of wires
6/6.6/6.6/6.12/6.15/6.18/12.18/12.30/15.34/18.34/18.53/30.
No. of cores and cross sectional area
3.5C x 25/163.5C x 35/163.5C x 50/253.5C x 70/353.5C x 95/503.5C x 120/703.5C x 150/703.5C x 185/953.5C x 240/1203.5C x 300/1503.5C x 400/185
CURRENT RATINGS
Wire1.601.601.602.002.002.002.002.502.503.153.15
Wire Armour1.401.401.561.561.721.881.882.042.362.522.68
Wire Armour26.527.531.036.040.043.048.053.560.066.075.0
Wire Armour(Kg/Km)18282146276338764976601171169105114641460018083
Max. D.C. Resistance
0at 20 C (Ohms/Km)
0.7270.5240.3870.2680.1930.1530.1240.09910.07540.06010.0470
3.5 Core Copper PVC Armoured Power Cables
3.5 Core Copper PVC Armoured Power Cables
3.5 Core Copper PVC Unarmoured Power Cables
An ISO: 9001-2008 Certified Company
www.gridcables.com
3.5 Core Aluminium XLPE Armoured Power Cables
No. of cores and cross sectional area3.5C x 253.5C x 353.5C x 503.5C x 703.5C x 953.5C x 1203.5C x 1503.5C x 1853.5C x 2403.5C x 3003.5C x 400
3.5 Core Aluminium XLPE Unarmoured Power Cables
No. of cores and cross sectional area
3.5C x 253.5C x 353.5C x 503.5C x 703.5C x 953.5C x 1203.5C x 1503.5C x 1853.5C x 2403.5C x 3003.5C x 400
Min. No. of wires
6/6.6/6.6/6.12/6.15/6.15/12.15/12.30/15.30/15.30/15.53/30.
Min. No. of wires
6/6.6/6.6/6.12/6.15/6.15/12.15/12.30/15.30/15.30/15.53/30.
Thickness of Insulation
(min.)
0.90.91.01.11.11.21.41.61.71.82.0
Thickness of Insulation
(nom.)
0.900.901.001.101.101.201.401.601.701.802.00
(nom)
0.70.70.90.91.01.11.11.11.21.41.6
(mm)
0.700.700.900.901.001.101.101.101.201.401.60
Min. Thick-ness of Innersheath (mm)0.30.30.30.40.40.40.50.50.60.60.7
Min. Thickness of inner sheath (mm)
0.30.30.30.40.40.40.50.50.60.60.7
Nominal Dimensions of Armour (mm)
Strip1.601.601.602.002.002.002.002.502.502.503.15
Wire4x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.8
Nom. Thickness of Outer Sheath (mm)
2.002.002.002.202.202.202.402.602.803.003.40
Min. Thickness of Outer Sheath (mm)
Strip Armour1.401.401.561.561.561.721.882.042.202.362.68
Overall Diameter (Approx.)
2225273135384247525766
Wire Armour1.401.401.401.561.561.721.721.882.042.202.52
Overall Diameter (Approx.) (mm)
Strip Armour2527303438424651576171
Net Wt. of Cable (Approx.)
60072091012301550205023002860361044105650
Wire Armour2325283235394347535766
Max. D.C. Resistance
0at 20 C (Ohms/Km)
1.20000.86800.64100.44300.32000.25300.20600.16400.12500.10000.0778
Approx. Net. Wet of Cable
Strip Armour (Kg/Km)11101290158021702620316036704780576067909040
Wire Armour (Kg/Km)8701030123016102000246028403480429051706480
Max. A.C. Resistance
0at 90 C(Ohms/Km)
1.54001.11000.82000.56700.41000.32500.26500.21100.16200.13000.1023
Max. D.C. Resis-tance at
0 20 C (Ohms/Km)1.20000.86800.64100.44300.32000.25300.20600.16400.12500.10000.0778
Approx. Reactance at 50 Hz (Ohm/Km)
0.0800.0800.0780.0770.0740.0720.0720.0720.0720.0710.070
Max. A.C. Resis-tance at
090 C (Ohms/Km)1.54001.11000.82000.56700.41000.32500.26500.21100.16200.13000.1023
Approx. React-ance at 50 Hz (Ohm/Km)0.0800.0800.0780.0770.0740.0720.0720.0720.0720.0710.070
Approx. Capacitance (mFd/Km)
0.200.230.240.260.290.290.290.290.310.330.33
Approx.Capaci-tance (mFd/Km)
0.200.230.240.260.290.290.290.290.310.330.33
Direct in Ground
Amps94113133164196223249282326367418
CURRENT RATINGS
CURRENT RATINGS
Direct in GroundAmps94113133164196223249282326367418
In Air
Amps96117142179221257292337399455530
In Air
Amps96117142179221257292337399455530
3.5 Core Copper PVC Armoured Power Cables
3.5 Core Copper PVC Unarmoured Power Cables
An ISO: 9001-2008 Certified Company
www.gridcables.com
3.5 Core Copper XLPE Unarmoured Power CablesMin. No. of wires
6/6.6/6.6/6.12/6.15/6.18/12.18/15.30/15.34/18.34/18.53/30.
Thickness of XLPE Insulation (Nom.) (mm)
0.9/0.70.9/0.71.0/0.91.1/0.91.1/1.01.2/1.11.4/1.11.6/1.11.7/1.21.8/1.42.0/1.6
Nom. Thickness of PVC Outer Sheath (mm)2.002.002.002.202.202.202.402.602.803.003.40
Overall Diameter (Approx.)
22.025.027.031.035.038.042.047.052.057.066.0
Direct in Ground
Amps119144174210252288324360414462510
In Air
Amps108132162198240276318366426480546
Net Wt. of Cable (Approx.)
1102138918362567341643175178650883891040113271
Max. D.C. Resistance
0 at 20 C (Ohms/Km)
0.7270.5240.3870.2680.1930.1530.1240.09910.07540.06010.0470
Max. A.C. Resistance
0 at 90 C (Ohms/Km)
0.9300.6710.4950.3430.2470.1960.1590.1270.09650.07690.0602
Approx. Capacitance (mFd/Km)
0.200.230.240.260.290.290.290.290.310.330.33
Approx. Reactance at 50 Hz (Ohm/Km)
0.0800.0800.0780.0770.0740.0720.0720.0720.0720.0710.070
CURRENT RATINGSMin. Thickness of PVC Inner-sheath (mm)0.30.30.30.40.40.40.50.50.60.60.7
No. of cores and cross sectional area
3.5C x 25/163.5C x 35/163.5C x 50/253.5C x 70/353.5C x 95/503.5C x 120/703.5C x 150/703.5C x 185/953.5C x 240/1203.5C x 300/1503.5C x 400/185
3.5 Core Copper XLPE Armoured Power CablesNominal Dimensions of Armour (mm)
Strip4x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.8
Min. Thickness of PVC Outer Sheath (mm)
Strip Armour1.401.401.561.561.561.721.882.042.202.362.68
Overall Diameter (Approx.) (mm)
Strip Armour2527303438424651576171
Approx. Net. Wet of Cable
Strip Armour (Kg/Km)15831925246834654426549864738333104351267116498
Max. D.C. Resist-ance at
020 C (Ohms/Km)0.7270.5240.3870.2680.1930.1530.1240.09910.07540.06010.0470
Max. A.C. Resis-tance at
090 C (Ohms/Km)0.9300.6710.4950.3430.2470.1960.1590.1270.09650.07690.0602
Approx. React-ance at 50 Hz (Ohm/Km)0.0800.0800.0780.0770.0740.0720.0720.0720.0720.0710.070
Approx. Capac-itance (mFd/Km)
0.200.230.240.260.290.290.290.290.310.330.33
Direct in GroundAmps119144174210252288324360414462510
In Air
Amps108132162198240276318366426480546
Min. No. of wires
6/6.6/6.6/6.12/6.15/6.18/12.18/15.30/15.34/18.34/18.53/30.
Min. Thickness of PVC Innersheath (mm)0.30.30.30.40.40.40.50.50.60.60.7
Thick-ness of XLPE Insulation (Nom.) (mm)0.9/0.70.9/0.71.0/0.91.1/0.91.1/1.01.2/1.11.4/1.11.6/1.11.7/1.21.8/1.42.0/1.6
No. of cores and cross sectional area
3.5C x 25/163.5C x 35/163.5C x 50/253.5C x 70/353.5C x 95/503.5C x 120/703.5C x 150/703.5C x 185/953.5C x 240/1203.5C x 300/1503.5C x 400/185
CURRENT RATINGS
Wire1.601.601.602.002.002.002.002.502.502.503.15
Wire Armour1.401.401.401.561.561.721.721.882.042.202.52
Wire Armour2325283235394347535766
Wire Armour (Kg/Km)1354168021432931383148315691710090351112614059
3.5 Core Copper XLPE Armoured Power Cables
3.5 Core Copper XLPE Unarmoured Power Cables
An ISO: 9001-2008 Certified Company
www.gridcables.com
4 Core Aluminium PVC Armoured Power Cables
4 Core Aluminium PVC Armoured Power Cables
No. of cores and cross sectional area
4C x 1.54C x 2.54C x 44C x 64C x 104C x 164C x 254C x 354C x 504C x 704C x 954C x 1204C x 1504C x 1854C x 2404C x 3004C x 400
4 Core Aluminium PVC Unarmoured Power Cables
4 Core Aluminium PVC Unarmoured Power Cables
No. of cores and cross sectional area
4C x 1.54C x 2.54C x 44C x 64C x 104C x 164C x 254C x 354C x 504C x 704C x 954C x 1204C x 1504C x 1854C x 2404C x 3004C x 400
Min. No. of wires
1111166661215151530303053
Min. No. of wires
1111166661215151530303053
Thick-nessof PVC Insulation(Nom.) (mm)0.80.91.01.01.01.01.21.21.41.41.61.61.82.02.22.42.6
Thickness of PVC Insulation (Nom.) (Mm)
0.800.901.001.001.001.001.201.201.401.401.601.601.802.002.202.402.60
Min. Thickness of PVC Inner-sheath (mm)0.30.30.30.30.30.30.30.30.40.40.40.50.50.60.60.70.7
Min. Thickness of PVC Innersheath (mm)0.300.300.300.300.300.300.300.300.400.400.400.500.500.600.600.700.70
Nominal Dimensions of Armour (mm)
Strip----4x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.8
Wire1.401.401.401.401.601.601.601.602.002.002.002.002.502.502.503.153.15
Nom. Thickness of Outer Sheath (mm)
1.801.801.801.801.802.002.002.002.202.202.402.402.602.803.003.403.60
Min. Thickness of PVC Outer Sheath (mm)
Strip Armour----1.401.401.401.401.561.561.721.881.882.042.362.522.84
Wire Armour1.241.241.241.241.401.401.401.561.561.561.721.882.042.202.362.682.84
Overall Diameter (Approx.)
11.7013.2015.0016.0019.0021.5023.0025.0029.5034.0037.5041.5045.5050.0057.0063.2070.00
Overall Diameter
(Approx.) (mm)
Strip Armour----21.1523.0025.0027.5032.0036.5040.0044.5048.0053.0060.0065.5073.00
Net Wt. of Cable (Approx.)
210270340420510550750900120015202000238029003580453056807040
Wire Armour14.516.017.519.023.025.027.030.034.538.042.547.051.557.064.071.078.0
Max. D.C. Resistance
0at 20 C (Approx.) (Ohm/Km)
18.1012.107.414.613.081.911.200.8680.6410.4430.3200.2530.2060.1640.1250.1000.0778
Approx. Net. Wet of Cable
Strip Armour (Kg/Km)----80083010751280162020102550304035804340546066308185
Wire Armour(Kg/Km)47056067580010301050135016202175266032803840488058107050926011020
Max. A.C. Resistance
0at70 C (Ohms/Km)
21.7214.528.895.533.702.291.441.040.770.530.380.300.250.200.150.120.09
Max. D.C. Resis-tance
0at 20 C(Ohms/Km)18.100012.10007.41004.61003.08001.91001.20000.86800.64100.44300.32000.25300.20600.16400.12500.10000.0778
Approx. Reactance at 50 Hz (Ohm/Km)
0.1260.1190.1160.1100.1000.0970.0970.0970.0940.0900.0900.0870.0870.0870.0870.0860.086
Max. A.C. Resis-tance
0 at 70 C (Ohms/Km)21.7214.528.895.533.702.291.441.040.770.530.380.300.250.200.150.120.09
Approx. Capacitance (mFd/Km)
0.1400.1500.4100.4700.5600.7600.8600.9801.0201.1801.2001.3101.3101.3101.3401.4101.450
Approx. React-ance at 50 Hz (Ohm/Km)0.1260.1190.1160.1100.1000.0970.0970.0970.0940.0900.0900.0870.0870.0870.0870.0860.086
Approx. Capac-itance (mFd/Km)
0.140.150.410.470.560.760.860.981.021.181.201.311.311.311.341.411.45
Direct in Ground
Amps1621283546607692110135165185210235275305335
CURRENT RATINGS
Direct in Ground
Amps1621283546607692110135165185210235275305335
CURRENT RATINGS
In duct
Amps141823303950637795115140155175200235260290
In duct
Amps141823303950637795115140155175200235260290
In Air
Amps1318233040517086105130155180205240280315375
In Air
Amps1318233040517086105130155180205240280315375
An ISO: 9001-2008 Certified Company
www.gridcables.com
4 Core Copper PVC Unarmoured Power Cables
4 Core Copper PVC Unarmoured Power Cables
In Air
Amps17243039576690110135165200230265305355400455
Direct in Ground
Amps21273645607799120145175210240270300345385425
Approx. Capac-itance (mFd/Km)
0.140.150.410.470.560.760.860.981.021.181.201.311.311.311.341.411.45
Approx. React-ance at 50 Hz (Ohm/Km)0.1260.1190.1160.1100.1000.0970.0970.0970.0940.0900.0900.0870.0870.0870.0870.0860.086
Max. A.C. Resis-tance
0 at 70 C (Ohms/Km)14.58.875.523.692.191.380.870.6270.4630.3210.2310.1840.1490.1200.09120.07390.0592
Max. D.C. Resis-tance
0at 20 C (Ohms/Km)12.17.414.613.081.831.150.7270.5240.3870.2680.1930.1530.1240.09910.07540.06010.0470
Wire Armour(Kg/Km)50361677194712731421193624363288426255256660836910183128071648820254
Approx. Net. Wet of Cable
Strip Armour (Kg/Km)----21.523.025.027.532.036.540.044.048.053.060.065.573.0
CURRENT RATINGS
4 Core Copper PVC Armoured Power Cables
4 Core Copper PVC Armoured Power Cables
Wire Armour14.516.017.519.023.025.027.030.034.538.042.547.051.557.064.071.078.0
Overall Diameter
(Approx.) (mm)
Strip Armour----21.1523.0025.0027.5032.0036.5040.0044.5048.0053.0060.0065.5073.00
Max. D.C. Resistance
0at20 C (Approx.) (Ohm/Km)
12.107.414.613.081.831.150.730.5240.3870.2680.1930.1530.1240.0990.0750.0600.0470
In duct
Amps1724303850648199125150175195225255295335360
In Air
Amps17243039576690110135165200230265305355400455
Max. A.C. Resistance
0at 70 C(Ohms/Km)
14.508.875.523.692.191.380.870.630.460.320.230.180.150.120.090.070.05
Approx. Reac-tance at 50 Hz (Ohm/Km)0.1260.1190.1160.1100.1000.0970.0970.0970.0940.0900.0900.0870.0870.0870.0870.0860.086
Approx. Capac-itance (mFd/Km)
0.1400.1500.4100.4700.5600.7600.8600.9801.0201.1801.2001.3101.3101.3101.3401.4101.450
Direct in Ground
Amps21273645607799120145175210240270300345385425
CURRENT RATINGSNet Wt. of Cable (Approx.)
25633544657677393513651764235431874308528864728056104151307016477
Min. Thickness of PVC Outer Sheath (mm)
Strip Armour----1.401.401.401.401.561.561.721.881.882.042.362.522.84
Wire Armour1.241.241.241.241.401.401.401.561.561.561.721.882.042.202.362.682.84
Overall Diameter (Approx.)
11.7013.2015.0016.0019.0021.5023.0025.0029.5034.0037.5041.5045.5050.0057.0063.2070.00
Nom. Thickness of Outer Sheath (mm)
1.801.801.801.801.802.002.002.002.202.202.402.402.602.803.003.403.60
Wire1.401.401.401.401.601.601.601.602.002.002.002.002.502.502.503.153.15
Nominal Dimensions of Armour (mm)
Strip----4x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.8
Min. Thickness of PVC Innersheath (mm)0.300.300.300.300.300.300.300.300.400.400.400.500.500.600.600.700.70
Min. Thickness of PVC Inner-sheath (mm)0.30.30.30.30.30.30.30.30.40.40.40.50.50.60.60.70.7
Thickness of PVC Insulation (Nom.) (mm)
0.800.901.001.001.001.001.201.201.401.401.601.601.802.002.202.402.60
Thick-nessof PVC Insulation(Nom.) (Mm)0.80.91.01.01.01.01.21.21.41.41.61.61.82.02.22.42.6
Min. No .ofwires
1111666661215181830343453
Min. No. of wires
1111666661215181830343453
No. of cores and cross sectional area
4C x 1.54C x 2.54C x 44C x 64C x 104C x 164C x 254C x 354C x 504C x 704C x 954C x 1204C x 1504C x 1854C x 2404C x 3004C x 400
No. of cores and cross sectional area
4C x 1.54C x 2.54C x 44C x 64C x 104C x 164C x 254C x 354C x 504C x 704C x 954C x 1204C x 1504C x 1854C x 2404C x 3004C x 400
An ISO: 9001-2008 Certified Company
www.gridcables.com
4 Core Aluminium XLPE Unarmoured Power Cables
4 Core Aluminium XLPE Unarmoured Power Cables
No. of cores and cross sectional area
4C x 164C x 254C x 354C x 504C x 704C x 954C x 1204C x 1504C x 1854C x 2404C x 3004C x 400
4 Core Aluminium XLPE Armoured Power Cables
4 Core Aluminium XLPE Armoured Power Cables
No. of cores and cross sectional area
4C x 164C x 254C x 354C x 504C x 704C x 954C x 1204C x 1504C x 1854C x 2404C x 3004C x 400
Min. No. of wires
66661215151530303053
Min. No. of wires
66661215151530303053
Thick-ness of Insu-lation (Nom.) (mm)0.70.90.91.01.11.11.21.41.61.71.82.0
Thickness of Insulation (Nom.) (Mm)
0.70.90.91.01.11.11.21.41.61.71.82.0
Min.Thickness of Inner Sheath (mm) 0.30.30.30.30.40.40.50.50.50.60.70.7
Min.Thickness of Inner Sheath (mm) 0.30.30.30.30.40.40.50.50.50.60.70.7
Nominal Dimensions of Armour (mm)
Strip1.601.601.601.602.002.002.002.502.502.503.153.15
Wire4x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.8
Nom. Thickness of Outer Sheath (mm)
1.802.002.002.002.202.202.402.602.803.003.203.60
Min.Thickness of Outer Sheath (mm)
Strip Armour1.401.401.401.561.561.721.882.042.202.362.522.84
Wire Armour1.401.401.401.561.561.561.721.882.042.202.362.68
Overall Diameter (Approx.)
202326293336414550566371
Overall Diameter (Approx.) (mm)
Strip Armour222628313640445055616876
Wire Armour212426303437424651576371
Net Wt. of Cable (Approx.)
-650800100013701740217026303250411050706420
Approx. Net. Wet of Cable
Strip Armour (Kg/Km) -118014101720241029003480448053306420836010070
Max. D.C. Resistance
0at 20 C(Ohms/Km)
1.91001.20000.86800.64100.44300.32000.25300.20600.16400.12500.10000.0778
Wire Armour (Kg/Km) - 9401130140018002190269032203920485059007310
Max. A.C. Resis-tance at
0 90 C (Ohms/Km)
2.45001.54001.11000.82000.56700.41000.32500.26500.21100.16200.13000.1023
Max. D.C. Resistance
0at 20 C (Ohms/Km)
1.911.20.8680.6410.4430.320.2530.2060.1640.1250.10.0778
Max. A.C. Resis-tance at
0 90 C(Ohms/Km)
2.451.541.110.820.5670.410.3250.2650.2110.1620.130.1023
Approx. React-ance at 50 Hz (Ohm/Km)
0.0800.0800.0780.0770.0740.0720.0720.0720.0720.0710.070
Approx. React-ance at 50 Hz (Ohm/Km)
0.080.080.0780.0770.0740.0720.0720.0720.0720.0710.07
Approx. Capaci-tance (mFd/Km)
0.200.230.240.260.290.290.290.290.310.330.33
Approx. Capaci-tance (mFd/Km)
0.20.230.240.260.290.290.290.290.310.330.33
Direct in GroundAmps7394113133164196223249282326367418
CURRENT RATINGS
Direct in GroundAmps7394113133164196223249282326367418
CURRENT RATINGS
In Air
Amps7096117142179221257292337399455530
In Air
Amps7096117142179221257292337399455530
An ISO: 9001-2008 Certified Company
www.gridcables.com
4 Core Copper XLPE Armoured Power Cables
4 Core Copper XLPE Armoured Power Cables
Thickness of XLPE Insulation (Nom.) (mm)
0.700.900.901.001.101.101.201.401.601.701.802.00
Nominal Dimensions of Armour (mm)Strip
4x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.8
Min. Thickness of PVC Outer Sheath (mm)
Strip Armour1.401.401.401.561.561.721.882.042.202.362.522.84
Overall Diameter (Approx.) (mm)
Strip Armour22.026.028.031.036.040.044.050.055.061.068.076.0
Approx. Net. Wet of Cable
Strip Armour (Kg/Km)121017092154273238874970658377029377117761507218669
Max. D.C. Resistance
0 at 20 C (Ohms/Km)
1.150.7270.5240.3870.2680.1930.1530.1240.09910.07540.06010.0470
Max. A.C. Resistance
0 at 90 C (Ohms/Km)
1.470.9300.6710.4950.3430.2470.1960.1590.1270.09650.07690.0602
Approx. React-ance at 50 Hz (Ohm/Km)0.0800.0800.0800.0780.0770.0740.0720.0720.0720.0720.0710.070
Approx. Capacit-ance (mFd/Km)
0.360.200.230.240.260.290.290.290.290.310.330.33
Min. No. of wires
66661215181830343453
No. of cores and cross sectional area
4C x 164C x 254C x 354C x 504C x 704C x 954C x 1204C x 1504C x 1854C x 2404C x 3004C x 400
Min. Thickness of PVC Inner-sheath (mm)0.30.30.30.30.40.40.50.50.50.60.70.7
CURRENT RATINGS
Direct in GroundAmps92119144174210252288324360414462510
In Air
Amps79108132162198240276318366426480546
Wire Armour (Kg/Km)99814731886243133014299582765008031102861198815872
Wire Armour1.601.601.601.602.002.002.002.502.502.503.153.15
Wire Armour1.401.401.401.561.561.561.721.882.042.202.362.68
Wire Armour 21.024.026.030.034.037.042.046.051.057.063.071.0
Nom. Thickness of PVC Outer Sheath (mm)1.802.002.002.002.202.202.402.602.803.003.203.60
Overall Diameter (Approx.)
20.023.026.029.033.036.041.045.050.056.063.071.0
Approx. Net Wt. of Cable (Approx.)
7131193156620572898385853245947740095841194815207
Max. D.C. Resistance
0 at 20 C (Ohms/Km)
1.150.7270.5240.3870.2680.1930.1530.1240.09910.07540.06010.0470
Approx. Reactance at 50 Hz (Ohm/Km)
0.0800.0800.0800.0780.0770.0740.0720.0720.0720.0720.0710.070
Max. ACResistance
0 at 90 C (Ohms/Km)
1.470.9300.6710.4950.3430.2470.1960.1590.1270.09650.07690.0602
Approx. Capacitance (mFd/Km)
0.360.200.230.240.260.290.290.290.290.310.330.33
CURRENT RATINGSMin. Thickness of PVC Inner-sheath (mm)0.30.30.30.30.40.40.50.50.50.60.70.7
Thickness of XLPE Insulation (Nom.) (mm)
0.700.900.901.001.101.101.201.401.601.701.802.00
Min. No. of wires
66661215181830343453
No. of cores and cross sectional area
4C x 164C x 254C x 354C x 504C x 704C x 954C x 1204C x 1504C x 1854C x 2404C x 3004C x 400
Direct in Ground
Amps92119144174210252288324360414462510
In Air
Amps79108132162198240276318366426480546
4 Core Copper XLPE Unarmoured Power Cables
4 Core Copper XLPE Unarmoured Power Cables
LT Control Cables
www.gridcables.com
An ISO: 9001-2008 Certified Company
www.gridcables.com
Core colours:-
Sheath colour:-
Conductor:-
PVC Insulation:-
PVC Sheath:-
Rated voltage:-
Test Voltage:-
Min. bending radius:-
Tensile strength:-
Max. working temperature :-
Max short circuit temperature :-
Minimum Laying Temperature:-
Use :-
CONTROL CABLESPVC Insulated and Sheathed Flexible Cables
Technical Specifications
Black / grey with reverse colour numbering+ yellow / green, Grey, Black and white
Annealed Bare Copper as per IS : 8130
Type A conforming to IS:5831
Type ST-1 conforming to IS :5831
HR, FR & FRLS sheathing as per requirement
650/1100V
2000 V.A.C.
4 time overall diameter of cable
12.50 N per sq.mm of PVC insulation and sheath
70°C, also available for 85°C as per requirement
160°C
15°C
These cables are used for flexible use for medium mechanical stredded with free movement without tensile stress in dry and moist condition for measuring and control in tool machines, conveyor belts, production lines in machinery production, steel production and electrical substations.
An ISO: 9001-2008 Certified Company
www.gridcables.com
CONSTRUCTION
1. Solid / Stranded annealed Copper Conductor & Tinned / Bare2. General Purpose / HR PVC insulation3. Cores Laid up ( filled if needed )4. FRLS / General purpose PVC inner sheath5. Armoring round galvanized steel wires / strips6. FRLS / General purpose PVC outer sheath
MAX. CONDUCTOR D.C. RESISTANCE AT 20°C – CONDUCTOR SIZE
1.5 SQ.MM – 12.1 Ohm / km (Bare) , 12.2 Ohm / km (Tinned)2.5 sq.mm – 7.41 Ohm / km (Bare), 7.56 Ohm / km (Tinned)*Dimensions specified are with stranded conductor.
Armoured PVC Control Cable IS:1554(Pt-I)-1988
Thickness of Inner sheath (min.) extruded mm0.30.30.30.30.30.30.30.30.30.30.30.30.30.30.30.30.30.30.30.30.30.30.30.30.30.30.30.30.30.4
Strip size mm
-------4x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.8------4x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.84x0.8
Thickness of PVC Outer sheath (Min.) mm-------1.241.401.401.401.401.401.401.40 1.401.401.401.401.401.401.401.561.56
Approx. OD mm
-------19.520.821.723.126.426.927.829.7 21.822.823.824.926.130.030.632.034.7
Approx. net weight of cable Kg/km
-------76083092010401250135514301670 90010201130121013551655177019402300
Round Wire Dia mm
1.41.41.41.41.41.41.41.61.61.61.61.61.61.61.61.41.41.41.41.41.41.61.61.61.61.61.61.61.62.0
Thickness of PVC Outer sheath (Min.) mm1.241.241.241.241.241.241.401.401.401.401.401.401.401.401.401.241.241.241.241.241.241.401.401.401.401.401.561.561.561.56
Approx. OD mm
13.614.115.015.916.916.920.621.522.423.324.728.028.529.431.314.815.416.417.518.718.723.424.425.426.527.732.032.633.637.1
Approx. Net weightof cable Kg/Km
4154304905456056308359501040113012651510161017001960500520590660745780111012401340145516051970210022502900
Standard Delivery Length in Mtrs.
100010001000100010001000100010001000100010001000100010001000100010001000100010001000100010001000100010001000100010001000
Direct in Ground
Amps23212116151413121111109998322727232120181716151413121211
In Air / Duct.
Amps20171714131311101099887727242419181715141313121110109
Thickness of PVC Insulation (Nom.) mm
0.80.80.80.80.80.80.80.80.80.80.80.80.80.80.80.90.90.90.90.90.90.90.90.90.90.90.90.90.90.9
No. of Cores & Cross Secitonal Area No. x mm22C x 1.53C x 1.54C x 1.55C x 1.56C x 1.57C x 1.510C x 1.512C x 1.514C x 1.516C x 1.519C x 1.524C x 1.527C x 1.530C x 1.537C x 1.52C x 2.53C x 2.54C x 2.55C x 2.56C x 2.57C x 2.510C x 2.512C x 2.514C x 2.516C x 2.519C x 2.524C x 2.527C x 2.530C x 2.537C x 2.5
Strip Armoured Cable Wire Armoured Cable Current Rating
An ISO: 9001-2008 Certified Company
www.gridcables.com
Unarmoured PVC Control Cable IS:1554(Pt-I)-1988
CONSTRUCTION
1. Solid / Stranded annealed Copper Conductor & Tinned / Bare2.General Purpose / HR PVC insulation3.Cores Laid up ( filled if needed )4.FRLS / General purpose PVC inner sheath5.FRLS / General purpose PVC Outersheath
MAX. CONDUCTOR D.C. RESISTANCE AT 20°C – CONDUCTOR SIZE
1.5 SQ.MM – 12.1 Ohm / km (Bare) , 12.2 Ohm / km (Tinned)2.5 sq.mm – 7.41 Ohm / km (Bare), 7.56 Ohm / km (Tinned)*Dimensions specified are with stranded conductor.
No. of Cores & Cross Secitonal Area No. x mm2
2C x 1.53C x 1.54C x 1.55C x 1.56C x 1.57C x 1.510C x 1.512C x 1.514C x 1.516C x 1.519C x 1.524C x 1.527C x 1.530C x 1.537C x 1.52C x 2.53C x 2.54C x 2.55C x 2.56C x 2.57C x 2.510C x 2.512C x 2.514C x 2.516C x 2.519C x 2.524C x 2.527C x 2.530C x 2.537C x 2.5
Thickness of PVC Insulation (Nom.) mm
0.80.80.80.80.80.80.80.80.80.80.80.80.80.80.80.90.90.90.90.90.90.90.90.90.90.90.90.90.90.9
Thickness of Inner sheath (min.) extruded mm
0.30.30.30.30.30.30.30.30.30.30.30.30.30.30.30.30.30.30.30.30.30.30.30.30.30.30.30.30.30.4
Thickness of Outersheath (nom.)mm
1.81.81.81.81.81.81.81.81.81.82.02.02.02.02.01.81.81.81.81.81.81.82.02.02.02.02.02.02.02.2
Approx. O.D. Mm
11.812.313.214.115.115.118.418.919.820.722.525.826.327.229.113.013.614.615.716.916.920.822.223.224.325.529.4303134.1
Approx. Net Weight of Cable Kg/Km
185190225260295315425480535595720880960104012302302402903353854205706907758609851215133014501790
Standard Delivery Length in Mtrs.
100010001000100010001000100010001000100010001000100010001000100010001000100010001000100010001000100010001000100010001000
Direct in Ground
Amps23212116151413121111109998322727232120181716151413121211
Current Rating
In Air / Duct.
Amps20171714131311101099887727242419181715141313121110109
www.gridcables.com
SingleMulticore Flexible Cables
An ISO: 9001-2008 Certified Company
www.gridcables.com
Single-core flexible cables – for Electrical Panels and Switch Boards
Features
• Higher Safety Factors
• Compact construction
• Choice of superior insulation systems for meeting IEC classification Temp. rise, protection etc.
Technical Specification
Conductor : Bunched electrolytic grade, annealed with superb flexibility according to harmonized grades H05V-K and H07-K available in various sizes from 0.5 sq.mm to 300 sq.mm
Insulation : PVC insulation upto 4 sq.mm 6 sq.mm and above generally available with HRPVC insulation or as per customer orders.
Standard colors : Grey, Red, Blue, Black, other colours as per order.
Standard packing : upto 10 sq.mm – 100 mtr. Coils , 16-130 sq.mm – longer lengths supplied on order.
SINGLE / MULTICORE FLEXIBLE CABLES
Applications and Standards
Type of insulation
70°C Heat Resistant PVC
Flame Retardant Low Smoke (FRLS)
Halogen Free Flame Retardant (HFFR) from 1.0 to 4.0 sq.mm
Typical applicationsWiring of panels for use in high ambient temperature
Wiring in high density critical installations in public places and fire prone areas
Wiring in high density critical installations in public places andfire prone areas and vicinity of electronics systems
Applicable standardsIS-694, BS 6004, IEC 60227, DIN VDE 0281-3
IEC 60332-1BS 4066-1IEC 60754-1ASTMD-2843ASTMD-2863
IEC 60322-1&3BS 4066-1&3IEC 60754-1&2ASTMD-2863BS 7211DIN VDE 0282-9
An ISO: 9001-2008 Certified Company
www.gridcables.com
Multicore Flexible Cables - For appliances & Machine Tools
Features
• Compact construction reduces weight per meter
• Rugged yet flexible for industrial use
• High temperature insulation
Technical Specifications
Conductor : High purity bright, electrolytic grade, pain annealed copper properly bunched having superb flexibility according to harmonized grades H05V-H07V-K and BS 6360 Class 5 available in various sizes. ‘Unilay’ conductor on the core will be provided on special order from 1 to 4 sq.mm
Insulation : Generally available with general purpose PVC insulation and PVC sheathing or as per customer.
Standard colours : Grey and Black
Standard Packing : 100 mtrs. Coils longer lengths supplied on order.
Cross Section Area (sq.mm)
0.50.751.01.52.54.06.010.016.0
25.035.050.070.095.0120.0150.0185.0240.0300.0
Physical and Electrical Properties
Approx. AWG
2119181614121086
4212/03/04/0---
Overall Dia Max. (mm)
2.62.83.03.804.04.84.68.09.6
11.513.015.015.017.519.021.023.526.529.5
Insulation Thickness Nom. (mm)0.600.600.600.600.700.800.801.001.00
1.21.21.41.41.61.61.82.02.202.40
Conductor NO. of wires / Max. Dia16/0.224/0.232/0.230/0.2550/0.2556/0.384/0.3140/0.3126/0.4 or 226/0.3196/0.4276/0.4396/0.4356/0.5480/0.5610/0.5750/0.5940/0.51200/0.51500/0.50
Conductor Resist. Ohm/Km at 20°C Max392619.513.37.984.953.301.911.21
0.7800.5540.3860.2720.2060.1610.1290.1060.08010.0641
Max current rating, Amp
6914243243547290
115150180240275310350400475500
Approx. Voltagedrop per amp per meter, mv46.031.022.015.09.15.73.82.21.4
0.890.640.450.320.240.190.150.120.100.08
An ISO: 9001-2008 Certified Company
www.gridcables.com
Physical and Electrical Properties
Flat submersible cable
Type of insulationStandard PVC
Heat resistant PVC upto 105°C
Standard PVC of FRLS
No. of coresCircularly Laid Up Cores
2 Cores Red, Black
3 Cores Red, Black And Green
4 Cores Red, Yellow, Blue And Green
No. core
3 CORE FLAT LAID CORES
Typical applicationsStandard PVC, HRPVC
Standard PVC, HRPVC
FRLS(Flame Retardant Low Smoke)
PropertiesConductorIns. Thickness (nom), mmSingle Core OD (max.), mmCond. Resist. (max.) ohm/kmSheath thickness (nom.), mmOverall dia. (max.) mmCurrent rating DC or single phase AC, amo voltage drop DC or phase AC, mV / A/m
Sheath thickness, (nom), mmOverall dia (max), mmCurrent rating DC or single phase AC, Amp. Voltage drop DC or single phase AC, mV / A/mSheath thickness, (nom.), mm
Overall dia (max), mmCurrent rating DC or single phase AC, AmpCurrent rating three phase ACVoltage drop DC or single phase AC, mV / A/m Voltage Drop, three phase AC
Properties
Sheath thickness , (nom), mm ConfigurationOverall dia (avg.)mmCurrent rating DC or single phase AC, Amp.Current rating, three phase ACVoltage drop DC or single phase Ac, mV / A/m Voltage drop, three phase AC
0516/0.20.62.6039.00.97.20693
0.97.606102
0.98.206610288
1.50
0.922/0.35.8x11818162925
0.7524/020.62.8026.00.97.80962
0.98.20962
0.98.80996254
2.50
0.936/0.36.75x14.124201815
1.032/0.20.63.019.50.98.01446
0.98.601446
0.99.4014144640
4.0
1.056/0.37.5x16.43225119.5
1.530/0250.63.830.30.98.601832
0.99.201832
1.010.5018183227
6.0
1.156/0.38.3x18.1042357.36.4
10.0
1.2140/0.39.5x22.5055454.43.8
2.550/0.250.74.07.981.010.502419
1.011.02419
1.01224201916
4.056/0.30.84.84.951.012.03212
1.012.503212
1.014.032251210
Applicable standardsIS 694, BS 6500, IEC 60227, DIN VDE-0281
IS 694, BS 6500, IEC 60227, DIN VDE-0281
IS 694/BS-6500, IEC 60227, DIN VDE-0281, IEC 60754-1, IEC 60332-1, BS-4066-1, ASTMD 2843, ASTMD-2863
Typical applicationsPower cords for applications, temporary power supplies, 3 core flat cables are suitable for submersible pump applications
Hi-power appliances, Ovens, Temporary Power supply in higher temp. areas
Power cords for appliances used to fire prone areas. Flame proof equipments, machine tools used in critical locations and heat zones.
Applications and standards
www.gridcables.com
Aerial Bunched Cables
An ISO: 9001-2008 Certified Company
www.gridcables.com
FeaturesGRID make Aerial Bunched Cables (ABC) is a novel concept for overhead power distribution system.
GRID make Aerial Bunched Cable are designed, manufactured and tested conforming to IS:14255, IS :7098(Pt-I) and other international specifications like IEC, NFC etc.
ApplicationsABC can conveniently be used :-
a) In theft prone areasb) As replacement of bare conductors in rural areas, in forest and in other localities like narrow street
where the space is limitedc) As replacement of bare conducts where reliability of supply is of prime importanced) As replacement of bare lines where high degree of stability of supply voltage is of importance.e) As hilly terrains where cost of erection of overhead lines or under ground cable becomes very high.f) As reinforcement of existing system without increasing voltage.g) For temporary suppliesh) Reduces burning of transformers and maintenance
AdvantagesIn comparison to bare overhead distribution lines, AB cables have very high reliability during the services. As the power and neutral conductors are insulated with the best dielectric material, resulting in the following advantages :
1. Less fault rate on account of good protection against line and ground fault by high winds or falling trees or birds especially in hilly areas and forests as encountered in rural distribution networks.
2. High insulation resistance to earth in al polluted atmosphere. Negligible currents and low losses.3. Multiple circuits of power and telephone cables could be strung in the same set of poles or any other
supports like walls etc.4. Better adaptability to run concurrently with existing over-head bare conductor system without any
interference. 5. High capacitance and low inductance leading to low impedance of lines.6. Lower voltage drop, higher current carrying capacities, vis-à-vis better voltage regulation.7. Longer spans and longer distance lines are possible with better systems stability.8. AB cables are much safer then bare conductors.9. It can be overhung in dense vegetation and forests.10. Additional connections can be easily and quickly made with hot-line connectors.11. Total lines costs are deduced. 12. Maintenance costs are reduced.13. Very difficult to tap the AB cables, thus reducing theft which leads to lower distribution loses.
AERIAL BUNCHED CABLES
An ISO: 9001-2008 Certified Company
www.gridcables.com
GRID INDIA POWER CABLES PVT. LTD. Manufactures a wide variety of cables suitable for process instrumentation. In the projects related to power generation and distribution, chemical and fertilizer industries and various other types of engineering industries, the process instrumentation plays a vita role in measurement, supervision ad control of the process. Introduction of microprocessor based / computerized instrumentation has demanded stringent quality requirements alongwith special electrical parameters for instrumentation cables. Very low level electrical signals pass between measuring end and display units / controllers which are situated far off. These low level signals are prone to external noise pickups and heavy silenuation during transmission.
All this means that the cables to be used for instrumentation should be designed and manufactured very carefully, GRID CABLES with its meticulous efforts in maintaining quality, stringent in process control during manufacture and the knowledge of cable designing, is proud to say that it is capable of supplying instrumentation cables meeting any Indian / International standard or a specific requirement desired by project authority. The efforts done by GRID CABLES are reqarded by acceptance of our quality by the country's prime organizations.
INSTRUMENTATION CABLES
Conductor:-
Insulation :-
Elements:-
Shields :-
Element laying:-
Armouring:-
Sheathing:-
Specification:-
0.4mm dia (0.126 sq.mm) to 2.5 sq.mm or higher sizes of electrolytic copper wire, Tinned / untinned, solid / stranded copper conductors.
70 Deg. C/ 85 Deg. C Grade PVC, Polyethylene, Halogen free FRLS Polymeric compounds
Pairs / Triples / Quads, colour coded / number printed ring marked / dual colour extruded.
Aluminium Polyester tape screen with copper drain wire or alternately with Copper wire braiding, individual element or overall shielding as specified.
Concentric formation or unit & ground formation as per applicable specification.
Galvanized steel wire / strip armour.
PVC 70/90 Deg. C grade, PVC FRLS, Halogen free FRLS Polymeric Compounds.
BS:5308 (1&2) IEC-189 (1&2)VDE 0815, ENI -181.00 and customer specifications
Range of Instrumentation Cables :-
OUTER SHEATH1) PVC (ST-1 ST-2)2) FRLS VPC3) Halogen Free FRLSARMOUR WIRE/STRIPGavalnised Steel
INNER SHEATH1) PVC (ST-1/ ST-2)2) FRLS VPC3) Halogen Free FRLS
INSULATION1) PVC (Type A.C)2) Polyethylene3) Halogen Free FRLS
COPPER CONDUCTOR1) Bare (ABC)2) Tinned (ATC)3) Solid4) Stranded
OVERALL SCREEN1) Copper Wire Braid2) AI-Polyester tape with copper drain wire
Cabling element
Pair Triad Unit
Element Pair
Typical Instrumentation Cable Constructions
Basic Code
GPC-2420GPC-1430GPC-2230GPC-3630GPC-5630GPC-8430
Feature
Insulation material Insulation propertyTemperature ratingThermal stability Flame retardancy Safety during burning Requirement of Oxygen to Catch Fire (% in air)Temperature required to catch fire (with 21% oxygen)Visibility during cable burning(%)Release of halogen Gas during burning (% by weight)Abrasion Resistance during installation
COMPARATIVE PROPERTIES OF GRID WIRES
Single Core PVC/HR PVC / FRLS / ZHFR Insulated Copper Conductor (Unsheathed). House Wires in Voltage Grade upto and including 1100 Volts as per IS:694-1990.
Nominal Cross Section Area of Conductor Sq.mm0.751.001.502.504.006.00
Number / Nom. Dia of wires * (Nom.) Number / mm24/0.2014/0.3022/0.3036/0.3056/0.3084/0.30
Normal PVC WirePVCNormal70°CNormalGoodAverage
>21Room temp.
<20
<20
Good
Thickness of insulation (Nom.) mm
0.600.700.700.800.800.80
Heat Resistant HR PVCPVCGood85°CVery goodGoodAverage
>21Room temp.
<20
<20
Good
Overall diameter Max. mm
2.83.23.44.24.85.6
Fire Retardant FR-PVCSpl. PVCGood70°CGoodVery goodGood
>30>250°C
<35
<20
Good
Current carrying capacity in conduit / trunking (Amps)PVC
71113182431
Fire Retardant Low Smoke FRLSSpl. PVCGood70°CGoodVery goodGood
>30>250°C
>40
<20
Good
HR PVC81316202636
FRLS
71113182431
Zero Halogen Low SmokeSpl. PolymerVery good85°CVery goodExcellentExcellent
>35>300°C
>80
Zero
Good
ZHFR
81316202636
Resistance (Max.) at 20°C Ohm / Km26.0018.1012.107.414.953.30
An ISO: 9001-2008 Certified Company
www.gridcables.com
Concentric Cables
www.gridcables.com
An ISO: 9001-2008 Certified Company
www.gridcables.com
APPLICATIONS
Power cables for energy supply are used for industry and distribution boards, power stations, house connecting boxes and street lighting and as control cables for the transmission of control impulses and test data.Overall, where increased electrical and also mechanical protection are required. These cables are installed in open air, in underground, in water, indoors and in cable ducts.
The concentric conductor (C) is allowed use as PE-, PEN-Conductor as shield.
Due to the typical construction of concentric conductor it is possible to obtain many more cables joints, without cutting any conductor. In that way the operating reliability is guaranteed.
The product conforms to the EC Low-Voltage Directive 73/23/EEC and 93/68/EEC.
PROPERTIESl PVC self-extinguishing and flame retardant according to DIN VDE 0482 part 265-2-1/EN 50265-
2/1 /IEC 60332-1 (equivalent DIN VDE 0472 part 804 test method B)l The materials used in manufacture are cadmium-free and contain no silicone and free from substances harmful to the wetting properties of lacquers.l Highest permissible voltage.l Direct current systems 1.8kV.l Alternating current systems, single-phase systems 1.4kV both conductors insulated, single-phase
Systems 0.7kV one conductor grounded, three-phase systems 1.2kV with concentric conductor And a cross-section of 240 sq. mm and above 3.6kV.
TECHNICAL DATAl Power and Control cable as per DIN VDE0276 part 603, HD 603 S1 & IEC 60502.l Temperature range flexing -5°C to +50°C, fixed installation 40°C to +70°C.l Nominal voltage U0/U0,6/1 kVl Test Voltage 4kVl Max. Permissible tensile stress with cable grip for Cu-conductor = 50 N/sq.mml Minimum bending radius for single conductor approx. 15xcable ø; for multi conductor approx.
12xcable øl Power ratings see Technical informationl Caloric load values see Technical Information
CONCENTRIC CONDUCTOR CABLES upto 1100 V (NYCWY/NYY)
An ISO: 9001-2008 Certified Company
www.gridcables.com
Description and No.
Conductors x cross-sec. sq.mm
NYCWY 2X10 re/10
NYCWY 0.6 / 1KV 2x16 re /16
NYCWY 0.6 / 1KV 2x25 rm/25
NYCWY 0.6 / 1KV 3x10 re/10
NYCWY 0.6 / 1KV 3x16 re/16
NYCWY 0.6 / 1KV 3x25 rm/16
NYCWY 0.6 / 1KV 3x25 rm/25
NYCWY 0.6 / 1KV 3x35 sm/35
NYCWY 0.6 / 1KV 3x35 sm/16
NYCWY 0.6 / 1KV 3x50 sm/50
NYCWY 0.6 / 1KV 3x50 sm/25
NYCWY 0.6 / 1KV 3x70 sm/70
NYCWY 0.6 / 1KV 3x70 sm/35
NYCWY 0.6 / 1KV 3x95 sm/95
NYCWY 0.6 / 1KV 3x95 sm/50
NYCWY 0.6 / 1KV 3x120 sm/70
NYCWY 0.6 / 1KV 3x120 sm/120
NYCWY 0.6 / 1KV 3x150 sm/70
NYCWY 0.6 / 1KV 3x140 sm/150
NYCWY 0.6 / 1KV 3x185 sm/95
NYCWY 0.6 / 1KV 3x185 sm/185
NYCWY 0.6 / 1KV 3x240 sm/120
NYCWY 0.6 / 1KV 4x10 re/10
NYCWY 0.6 / 1KV 4x16 re/16
NYCWY 0.6 / 1KV 4x25 rm/16
NYCWY 0.6 / 1KV 4x35 sm/16
NYCWY 0.6 / 1KV 4x50 sm/25
NYCWY 0.6 / 1KV 4x70 sm/35
Outer Dia
19.0
21.0
24.0
19.5
22.0
26.0
26.0
27.5
27.0
29.5
29.0
34.0
33.0
38.5
38.0
41.0
42.0
45.0
46.0
50.0
51.0
57.0
20.5
23.5
28.0
29.0
33.0
37.0
Copper Weight
kg/km
312.0
489.0
763.0
408.0
643.0
902.0
1003.0
1402.0
1190.0
2000.0
1723.0
2796.0
2410.0
3791.0
3296.0
4263.0
4786.0
5100.0
5970.0
6383.0
7363.0
8242.0
504.0
796.0
1142.0
1526.0
2203.0
3082.0
Weight ca.
kg/km
650.0
850.0
1210.0
730.0
1000.0
1550.0
1600.0
1850.0
1750.0
2450.0
2250.0
3350.0
2950.0
4550.0
4100.0
5050.0
5550.0
6000.0
6900.0
7550.0
8500.0
9950.0
890.0
1250.0
1800.0
2050.0
2700.0
3750.0
AWG
8
6
4
8
6
4
4
2
2
1
1
2/0 kcmil
2/0 kcmil
3/0 kcmil
3/0 kcmil
4/0 kcmil
4/0 kcmil
300 kcmil
300 kcmil
350 kcmil
350 kcmil
500 kcmil
8
6
4
2
1
2/0
Cable constructionPlain copper conductors, as per VDE 0295 cl.1 od. Cl.2, IEC 60228, BS 6360 cl. 1 and HD 383, solid or stranded versions, conductor types.10-16 sq.mm round, solid conductors (re) alt. 10-25 sq.mm, stranded conductor (rm), 35-240 sq.mm, sector shaped conductor, stranded (sm)PVC conductor insulation, DIV4 to HD 603.1Color coded to DIN VDE 0293-308 and HD 186Conductors stranded concentricallyFilling compoundConcentric conductor (Ceander), inner layer of corrugated copper wires, outer layer with copper tapePVC outer jacket, DMV5 to HD 603.1Jacket color black
Any Type of Special Cables
www.gridcables.com
An ISO: 9001-2008 Certified Company
www.gridcables.com
Thermocouple Extension / Compensating Cables
Range of Thermo-couple extension / compensation cables
COLOUR CODES as per various Standard Specifications
These cables can also be termed as instrumentation cables, since they are used for process temperature measurement. The construction is similar to pair instrumentation cable but the conductor material is different. Thermocouples are used in processes to sense temperature and is connected to the pyrometers for indication and control. The thermocouple and pyrometer are electrically conducted by thermocouple extension / compensating cables. The conductors used for these cables are required to have similar thermo-electric (emf) properties as that of the thermocouple used for sensing the temperature. The cables are manufactured as per IS:8784, ANSI-MC 96, 1, B.S., ENI, DIN and customers specification.
ANY TYPE OF SPECIAL CABLES
Extension cables
KX (NiCr/Nia)JX (Fe/CuNi)EX (NiCr/CuNi)TX (Cu/CuNi)Compensating Cables KX(A)/VX(NiCr/NiaL)SX/RX (PtRh-Pt)
KXJXTXEX
KX(A)/VXSX/RXGreen
COMPENSATING CABLES
+ve
Yellow WhiteBluePurple
-
EXTENSION CABLES-ve
RedRedRedRed
-Black
Overall
YellowBlackBluePurple -Red
+ve
RedRedRedRed
RedRed
STANDARDS REFERRED
PositiveChromelIronChromelCopper
CopperCopper
-ve
GreenBlueBlackViolet
GreenWhite
Conductor material
Overall
GreenBlueBlackViolet
GreenWhite
+ve
BrownYellow WhiteBrown
WhiteWhite
-ve
BlueBlueBlueBlue
BlueBlue
NegativeAlumelConstantanConstantanConstantan
Constantanconstantan
Overall
RedBlackBlueBrown
RedGreen
An ISO: 9001-2008 Certified Company
www.gridcables.com
Test
Critical Oxygen Index
Temperature Index
Smoke Density Rating(Light Transmission )
Acid Gas Gas Generation
Function
To determine Percentage of Oxygen required for supporting combustion of insulating material at room temperature
To determine at what temperature normal oxygen content of 21% in air will support combustion of insulating material To determine the visibility (Light Transmission) under Fire of Insulating Material
To ascertain the amount of Hydrochloric Acid Gas evolved from insulation of Cables under fire.
Following additional test is offered on these cables :-
1)Flammability Testa) IEEE383b) IEC 332(Part-I)c) IEC-332 (Part-III)
2)Swedish Chimney Testa) SS 4241475
Specification
ASTM-d-2863
ASTM-D-2863 & BICC Handbook Chapter No. 6
ASTM-D-2843
IEC-754-I
Typical values of FRLS compound
More than 29%
More than 250°C
More than 40%
Less than 20%
Typical values of Halogen free compoundMore than 29%
More than 250°C
More than 80%
Less than 0.5%
Typical values of ordinary PVC Compound23%
0150 C
10-15%
450-50%
GRID FRLS and Halogen Free Cables
www.gridcables.comwww.gridcables.com
Conductor
An ISO: 9001-2008 Certified Company
www.gridcables.com
1. Corrosion resistance : AAAC exhibits excellent corrosion resistance especially in sea coast areas and in polluted industrial areas due to Absence of steel core
2. Lower power losses : since AAC is homogeneous (with all strands of Aluminium Alloy) with no steel component, the resistance of AAAC is lower as compared to that of ACSR.
3. Higher ampacity :AAAC can carry atleast 15-20% extra current as compared to ACSR of equal size.4. Longer life : Experience in foreign countries shows that all Aluminium Alloy Conductors are in service for over 60 years, which is
about double the life of ACSR conductors.5. Surface hardness : The surface hardness of AAAC is 80 BHN as compared to 35BHN of ACSR. This reduces damage to surface
during handling and therefore leading to lesser corona losses and radio interference at EHV.6. Thermal stability : AAA Conductors are stable upto 90°C against ACSR conductors which are stable upto 75°C.7. Higher strength to weight ratio : Since AAAC has higher strength to weight ratio, span car be increased from 2 to 15% resulting in
Overall reduction of cost in tower / supports and other accessories in transmission lines system.
CONDUCTORSADVANTAGES OF AAAC
All Aluminium Alloy Conductors
(Clauses 7.2.1 & 7.2.2) as per IS-398 (Part 4) 1994
Actual area
mm2
15
22
34
55
80
100
125
148
173
200
232
288
346
400
465
525
570
604
642
695
767
Stranding &
wire dia mm
3/2.50
7/2.00
7/2.50
7/3.15
7/3.81
7/4.26
19/2.89
19/3.15
19/3.40
19/3.66
19/3.94
37/3.15
37/3.45
37/3.71
37/4.00
61/3.31
61/3.45
61/3.55
61/3.66
61/3.81
61/4.00
Approx. Overall
Dia mm
5.39
6
7.5
9.45
11.43
12.78
14.45
15.75
17
18.3
19.7
22.05
24.15
25.97
28
29.79
31.05
31.95
32.94
34.29
36
Approx Mass
kg/km
40.15
60.16
94.00
149.20
218.26
272.86
342.51
406.91
474.02
549.40
636.67
794.05
952.56
1101.63
1280.50
1448.39
1573.71
1666.00
1771.36
1919.13
2115.54
Calculated maximum
resistance at 20°C
Ohms/km
2.3040
1.5410
0.9900
0.6210
0.4250
0.3390
0.2735
0.2298
0.1969
0.1710
0.1471
0.1182
0.0984
0.0855
0.0734
0.0651
0.0598
0.0568
0.0534
0.0492
0.0446
Approx calculated
breaking load
(kN)
4.33
6.45
10.11
16.03
23.41
29.26
36.64
43.50
50.54
58.66
68.05
84.71
101.58
117.40
136.38
146.03
158.66
167.99
178.43
193.25
213.01
An ISO: 9001-2008 Certified Company
www.gridcables.com
AAAC HS Aluminium Alloy Stranded Conductor
Aluminium Conductors, Galvanized Steel-reinforced for extra high voltages IS 398(Part 5) : 1992(Clause 8.2.2)
Stranded Aluminium Conductor Steel Reinforced (ACSR)IS-398 (Part-2) 1996Clauses 8.21 8.2.2 and 4.3.2
AAAC size equivalent to ACSR
SquirrelWeaselRabbit RacoonDog
ACSR Code word
Moie…SquirrelWeaselRabbitRaccoonDogWolfPantherKundahZebraMooseMorkulla
Conductor size sq.mm
101820305080100150200400420520560
Overall diameter mm
4.505.886.337.7710.0512.2714.1518.1321.0026.8828.6231.7731.68
Ultimate strength kN
3.976.747.6111.1218.2526.9132.4167.3489.6788.79130.32159.60120.16
Calculated Electrical resistance at 20°C Ohm/km 2.7801.6181.3940.92890.55240.37120.27920.18710.13900.073110.068680.055950.05231
Copper equivalent
611121932486496129246261322343
Nominal Aluminium (1)mm
520560690
Nominal Al-Area
mm21420305080100
Calculated Resistance at 20°C maximum Ohm/km2.3041.5410.9900.6210.4250.399
Approx. calculated breaking load kN4.3316.46710.10616.04423.47329.344
Approx. Mass
Kg/km40.1560.1394.00149.20218.26272.86
Stranding and wire dia
mm3/2.507/2.007/2.507/3.157/3.817/4.26
Stranding Nos/mm
Al.6/1.506/1.966/2.116/2.596/3.356/4.096/4.7230/2.5930/3.0042/3.5054/3.1854/3.5342/4.13
Calculated sectional area sq.mm
Al. 10.6018.1020.9831.6152.8878.83105.00158.10212.10404.10428.90528.50562.70
Calculated sectional area sq.mm
ACSR4373851282143193947269741281162119981781
Steel 1/1.501/1.961/2.111/2.591/3.351/4..097/1.577/2.597/3.004/1.967/3.187/3.537/2.30
ACSR12.3721.1224.4836.8861.7091.97118.50194.90261.50425.20484.50597.00591.70
Al.295058871452162884375861116118614611553
Steel1423274169103106289388165435537228
Stranding and wire diameterAl. (2)mm54/3.5342/4.1342/4.57
Steel (3)7/3.53528.57/2.13562.77/2.54688.9
Sectional Area
mm214.7321.9934.3654.5579.8199.77
Sectional area of Aluminium
528.5562.7688.9
Approx. overall Dia
mm5.386.007.509.4511.4312.78
Total sectional area
597.0591.7724.4
Approx overall diameter
31.7731.6835.04
Approx mass
2 0041 7872 187
Calculated resistance at 20°C
0.055 520.051 990.042 42
Approx breaking load min.
161.20120.16146.87
REC Specification No. 33/1984.
Note: (1) kN = 100,000,000 dyne = 102 kgNote: The standard length of the conductor manufactured as per specific requirement of the customer and being supplied in non-returnable wooden drums or steel drum, quite strong, to withstand any kind of transit handlings in the erection field.
On receipt of the cable drums visual inspection of drums should be made. White unloading the drums from the lorry / trailer, a crane or suitable derrick system with chain pully arrangement should be used and the drums carefully lifted and deposited on the ground. When lifting the drums with the crane, it is recommended the lagging should be kept in place to prevent the flanges from crushing on to the cable. If the crane is not available, a ramp should be prepared with approximate inclination of 1:3 or 1:4. The cable drum should be rolled over the ramp by means of ropes and winches. Under no circumstances should the drums be dropped to the ground as the shock may cause serious damage to the inner layer of the cables.
Cables should not be dragged along the earth surface.
Cable ends should always be sealed by means of suitable end sealing material to prevent miniaturization of cores and armour.
Drums should be rolled in direction of arrow marked on the drums.
Storage
The site chosen for the storage of cable drums should be dry and covered place to prevent exposure to climatic conditions and wear and tear of wooden drums and it should be preferably on a concrete / consolidated surface which will not cause the drums to sink and thus lead to flange rot and extremely difficult in moving the drums.
The drums should be stored in such a manner as to leave sufficient space between them for air circulation. It is desirable for the drums to stand on battens placed directly under the flanges.
In no case shall the drums be stored flag i.e. with flanges horizontal.
Minimum permissible bending radius
While installing the cables, the following minimum bending raidus should be observed in order so that the cable, especially insulation, may not undergo damage. Wherever possible larger bending radium should be used.
Voltage rating KVUpto 1.1 Above 1.1 to 11
Where D is outer diameter of cable.
PVC & XLPE CablesSingle Core Multicore15 D 12 D 15 D 12 D
An ISO: 9001-2008 Certified Company
www.gridcables.com
Handling & Storage