Page 1: FIRE ALARM DEMOLITION NOTES GENERAL FIRE ALARM NOTES

The Walker Group Architecture, IncPO Box 541, New Bern, NC 28563252.636.8778 (PHONE)252.636.8992 (FAX)

WALKERGROUP

i n c o r p o r a t e d

the

ARCHITECTURE

DISCLOSURE OF INFORMATIONCONTRACTOR SHALL COMPLY AS FOLLOWS:

(A) THE CONTRACTOR SHALL NOT RELEASE TO ANYONE OUTSIDE THE CONTRACTOR'S ORGANIZATION ANY UNCLASSIFIED INFORMATION, REGARDLESS OF MEDIUM (E.G., FILM, TAPE,DOCUMENT), PERTAINING TO ANY PART OF THIS CONTRACT OR ANY PROGRAM RELATED TO THIS CONTRACT, UNLESS-

(1) THE CONTRACTING OFFICER HAS GIVEN PRIOR WRITTEN APPROVAL; OR(2) THE INFORMATION IS OTHERWISE IN THE PUBLIC DOMAIN BEFORE THE DATE OF RELEASE(B) REQUESTS FOR APPROVAL SHALL IDENTIFY THE SPECIFIC INFORMATION TO BE RELEASED, THE MEDIUM TO BE USED, AND THE PURPOSE FOR THE RELEASE. THE CONTRACTOR SHALL

SUBMIT ITS REQUEST TO THE CONTRACTING OFFICER AT LEAST 45 DAYS BEFORE THE PROPOSED DATE FOR RELEASE.(C) THE CONTRACTOR AGREES TO INCLUDE A SIMILAR REQUIREMENT IN EACH SUBCONTRACT UNDER HIS CONTRACT. SUBCONTRACTORS SHALL SUBMIT REQUESTS FOR AUTHORIZATION

TO RELEASE THROUGH THE PRIME CONTRACTOR TO THE CONTRACTING OFFICER.

FIRE ALARM AND MASS NOTIFICATION LEGEND

FIRE ALARM MANUAL PULL STATION, 48" AFF TO ACTUATING ARM, UON

FIRE ALARM/MNS AUDIO/VISUAL (SPEAKER/STROBE)APPLIANCE, 80" AFF, OR 6" BELOW FINISHED CEILING,WHICHEVER IS LOWER, UON. SUBSCRIPT INDICATESMINIMUM CANDELA RATING OF STROBE.

SPRINKLER SYSTEM SUPERVISORY FLOW SWITCH CONNECTION

F

S

F

S

15

FIRE ALARM SYSTEM PHOTOELECTRIC SMOKE DETECTOR, CEILING MOUNTED

F15 STROBE ONLY APPLIANCE, 80" AFF OR 6" BELOW FINISHED

CEILING WHICHEVER IS LOWER, UON. SUBSCRIPT INDICATESMINIMUM CANDELA RATING OF STROBE.

H FIRE ALARM SYSTEM HEAT DETECTOR

REQ'D REQUIREDPNL PANEL

NATIONAL ELECTRICAL CODENEC

GROUNDGND

EXIST EXISTING EXISTING TO REMAINETRCONDUIT C

UNLESS OTHERWISE NOTEDUON

FIRE ALARM/ MASS NOTIFICATION SYSTEM

AREA OF REFUGE ASSISTANCEARA

ABBREVIATIONS

ABOVE FINISHED GRADEAFGABOVE FINISHED FLOORAFF

FMCP

BELOW FINISHED GRADEBFG

FIRE ALARM/MASS NOTIFICATIONCONTROL PANEL

SWP

FIRE ALARM AUDIO (SPEAKER) APPLIANCE, 80" AFG, WALL MOUNT,SUBSCRIPT "WP" INDICATES WEATHER PROOF. PROVIDE COOPERWHEELOCK SERIES STH-15S OR APPROVED EQUAL.

MASS NOTIFICATION SYSTEMMNS

FIRE ALARM CONTROL PANELFACP

GENERAL FIRE ALARM NOTESFIRE ALARM DEMOLITION NOTESGENERAL: DEMOLITION DRAWINGS ARE BASED ON EXISTING PLANS AND FIELDINVESTIGATION PRIOR TO DEMOLITION. VISIT THE EXISTING BUILDING PRIOR TO BID INORDER TO BECOME FAMILIAR WITH THE EXISTING CONDITIONS AND IN ORDER TOAVOID CONFLICTS. THE CONTRACTOR MUST PROTECT AND PRESERVE ALL EXISTINGWORK NOT PART OF PROJECT.

DASHED ITEMS: ITEMS SHOWN DASHED ON DEMOLITION PLANS ARE EXISTING ANDMUST BE REMOVED.

SOLID ITEMS: ITEMS SHOWN SOLID ON DEMOLITION PLANS ARE EXISTING TO REMAIN.

EXISTING CONDUIT: EXISTING CABLING MUST BE REPLACED. EXISTING CONDUITS THATWILL NOT BE REUSED MUST BE REMOVED WHERE THEY WILL BE EXPOSED UPONCOMPLETION OF NEW WORK. EXISTING CONDUIT TO REMAIN CONCEALED IN WALLSMUST BE ABANDONED. EXISTING CONDUIT TO REMAIN BELOW FLOOR SLAB MUST BECUT OFF ONE INCH BELOW ROUGH FLOOR AND GROUTED FLUSH. REMOVE WIRINGFROM CONDUIT THAT IS ABANDONED.

REPAIR DAMAGE: EXERCISE CARE IN REMOVAL OF DEMOLITION ITEMS. REPAIR, AT NOADDITIONAL COST TO THE OWNER, ANY DAMAGE CAUSED TO EXISTINGCONSTRUCTION AND/OR EQUIPMENT TO REMAIN.

DEMOLISHED MATERIALS: MATERIALS REMOVED UNDER DEMOLITION, NOT TO BERELOCATED OR DESIGNATED TO BE TURNED OVER TO THE OWNER, WILL BECOME THEPROPERTY OF THE CONTRACTOR AND MUST BE REMOVED COMPLETELY FROM THESITE.

SCHEDULE OUTAGES: SCHEDULED OUTAGES MUST BE COORDINATED THROUGH THEGOVERNMENT CONSTRUCTION MANAGER OR CONTRACTING OFFICER.

NOTIFICATION: NOTIFY THE GOVERNMENT CONSTRUCTION MANAGER ORCONTRACTING OFFICE PRIOR TO TURNING OFF CIRCUITS.

GENERAL: UNLESS SPECIFICALLY INDICATED OTHERWISE, WORK SHOWN ON FIREALARM DRAWINGS IS NEW WORK TO INCLUDE THE FIRE ALARM/MASS NOTIFICATIONPANEL, DEVICES, AND APPLIANCES ON DRAWINGS FOR A COMPLETE ANDOPERATIONAL SYSTEM.

COORDINATION: THE CONTRACTOR MUST REVIEW CONTRACT DOCUMENTSINCLUDING FIRE ALARM DRAWINGS AND SPECIFICATIONS. CONTRACTOR MUSTCOORDINATE AND ADJUST ACCORDINGLY AS DIRECTED BY THE COTR.

AS-BUILT DRAWINGS: SECURE AN EXTRA SET OF DRAWINGS TO BE KEPT ON SITEAND MARK DAILY, THE DRAWINGS IN RED AS THE PROJECT PROGRESSES IN ORDERTO KEEP AN ACCURATE RECORD OF ALL DEVIATIONS BETWEEN THE WORK SHOWNON THE DRAWINGS AND THE WORK WHICH IS ACTUALLY INSTALLED. THESE MARKEDDRAWINGS MUST REFLECT ANY AND ALL CHANGES AND REVISIONS TO THEORIGINAL DESIGN WHICH EXISTS IN THE COMPLETED WORK. DELIVER THE MARKEDDRAWINGS TO THE COTR AT PROJECT CLOSE-OUT. IN ADDITION, PROVIDE CONTACTID POINT DESCRIPTIONS FOR EACH DEVICE.

INSPECTIONS: ARRANGE NECESSARY INSPECTIONS. DELIVER REQUIREDINSPECTION CERTIFICATES TO THE GOVERNMENT.

LABELING: ALL CONDUIT, JUNCTION/BACKBOXES, COVERS AND COUPLINGS, WHENPROVIDED, MUST BE FACTORY PAINTED RED IN UNFINISHED AREAS (E.G. ABOVECEILINGS, MECHANICAL ROOMS, ETC.). ALL CONDUIT, JUNCTION/BACKBOXES,COVERS AND COUPLINGS, WHEN PROVIDED, ARE PERMITTED TO BE PAINTED TOMATCH THE ROOM FINISHING IN FINISHED AREAS. THE INSIDE COVER OR THEJUNCTION BOX MUST BE IDENTIFIED AS "FIRE ALARM" AND THE CONDUIT MUST HAVEPAINTED RED BANDS 3/4" WIDE AT 20' INTERVALS ON BOTH SIDES OF ALL FLOOR,WALL, AND CEILING PENTRATIONS. LABEL ALL JUNCTION BOXES WITH CIRCUITDESIGNATIONS OF THE CABLING INSIDE. PROVIDE LEGIBLE TYPED LABEL ON ALLADDRESSABLE DEVICES TO INDICATE ITS ADDRESS. FOR ANY DEVICE LOCATEDABOVE ACCESSIBLE CEILING, ATTACH A LEGIBLE TYPED LABEL TO THE CEILING GRIDINDICATING THE DEVICE NOMENCLATURE AND ADDRESS.

WORKING CLEARANCE: COORDINATE FINAL LOCATIONS OF FIRE ALARM EQUIPMENTWITH MECHANICAL DUCTWORK, PIPING ETC. AND ASSURE WORKING CLEARANCEWILL BE MET. SUFFICIENT ACCESS AND WORKING SPACE MUST BE PROVIDED ANDMAINTAINED AROUND FIRE ALARM EQUIPMENT AS REQUIRED BY THE NATIONALELECTRICAL CODE. CONTRACTOR MUST COORDINATE FINAL LOCATION OFEQUIPMENT PROVIDED.

FIRE ALARM REMOTE ANNUNCIATOR PANELFAA

MOUNTING HEIGHTS: MOUNTING HEIGHTS INDICATED ARE FROM THE FINISHEDFLOOR TO THE CENTERLINE OF THE DEVICE UNLESS OTHERWISE NOTED.

FIRE STOPPING: FOR WALL OR FLOOR PENETRATIONS THROUGH FIRE-RATEDSTRUCTURES PROVIDE FIRE-STOPPING TO SEAL THE PENETRATIONS AFTER THECONDUIT HAS BEEN INSTALLED. FIRE STOPPING FOR PENETRATIONS MUST BE ULAPPROVED PER THE PENETRATION MADE IN ORDER TO MAINTAIN FIRE-RATEDINTEGRITY OF THE STRUCTURE.

FIRE ALARM COORDINATION: THE ELECTRICAL CONTRACTOR MUST COORDINATEWITH THE FIRE ALARM SYSTEM PROVIDER AND PROVIDE POWER CONNECTIONS TOCOMPONENTS WHETHER SHOWN OR NOT. MANUFACTURERS REQUIRE VARYINGQUANTITIES OF POWER CONNECTIONS FOR EQUIPMENT LIKE EXPANDER PANELSAND POWER SUPPLIES. THESE DEVICES ARE DEPENDENT UPON THE SPECIFICMANUFACTURERS SYSTEM. THE FIRE ALARM SYSTEM SUPPLIER MUST NOTIFY THEOTHER APPROPRIATE SUB-CONTRACTORS ABOUT THESE REQUIREMENTS ANDCONNECTION MUST BE PROVIDED AS PART OF THE PROJECT.

FIRE ALARM EQUIPMENT SURVIVAL: A SMOKE DETECTOR IS REQUIRED AT ALLCONTROL PANEL LOCATIONS (I.E. FIRE ALARM PANEL, NOTIFICATION EXTENDERPANELS, TRANSMITTERS, ETC.). CONTRACTOR MUST PROVIDE SYSTEM SMOKEDETECTORS FOR ALL LOCATIONS OF FIRE ALARM PANELS, TO INCLUDE THOSESHOWN AND THOSE THAT ARE ADDED BY THE CONTRACTOR FOR THEIR SPECIFICDESIGN.

CONDUIT: ALL ADDED FIRE ALARM/MASS NOTIFICATION SYSTEM WIRING MUST BEINSTALLED IN CONDUIT (EMT MINIMUM). EXISTING EMT MAY BE REUSED WHERE ITSATISFIES REQUIREMENTS OF NFPA 70.

CONDUIT SEALS: PROVIDE CONDUIT SEAL IN ACCORDANCE WITH NFAP 70 300.7 TORACEWAYS EXPOSED TO DIFFERENT TEMPERATURES.CONDUCTORS: ALL CONDUCTORS MUST BE REPLACED WITH NEW.

INTELLIGIBILITY LEVEL: CONTRACTOR MUST VERIFY INTELLIGIBILITY LEVEL BYMEASUREMENT AFTER INSTALLATION OF 0.7 CIS FOR NAVY AND MARINE CORPPROJECTS. COMMERCIALLY AVAILABLE TEST INSTRUMENTATION MUST BE USED TOMEASURE INTELLIGIBILITY AS SPECIFIED BY IEC 60849 AND IEC 60268-16. THE MEANVALUE OF AT LEAST THREE READINGS MUST BE USED TO COMPUTE THEINTELLIGIBILITY SCORE AT EACH TEST LOCATION.

DA

CT

(2) CAT6 UTP TO TELEPHONE PATCH PANELFINAL TERMINATIONS BY GOVERNMENT

PATCH PANEL

NETWORKTELEPHONE

TO

EXISTING EQUIPMENT3/4" CONDUITW/ PULL STRING

EXISTINGEXTERNALANTENNA

125'

MAX

IMUM

CAB

LE L

ENGT

H

25' MAXIMUM

DEDICATED 120V, 20A CIRCUITFROM SAME SOURCE THATFEEDS FACP.

FIRE ALARM/MASS NOTIFICATION SYSTEM RISER DIAGRAM

S F S H

TO OTHER ADDRESSABLEDEVICES

PRIMARY + BACKUP (2) CAT6 UTP (BLUE)

WP

TO OTHER ADDRESSABLEDEVICES

FAA

D

RTTO AHUSHUTDOWN

1. THE FACP IS AN EXISTING COMBINED FIRE ALARM ANDMASS NOTIFICATION SYSTEM IN THE CHAPEL BUILDING17. PROVIDE NEW SUB-PANEL FACP IN BUILDING 17A ANDNETWORK BACK TO THE EXISTING FACP IN BULDING 17.

2. THE NETWORKED FIRE ALARM AND DETECTION SYSTEMIS TO BE FULLY COMPLIANT WITH THE CURRENTEDITIONS OF UFC 3-600-01, UFC 3-600-10N, UFC 4-021-01,AND NFPA 72 FOR A FIRE ALARM AND AN EMERGENCYVOICE ALARM COMMUNICATION SYSTEM. THE SYSTEM ISDESIGNED TO INTERFACE WITH THE SITE MNS.

3. THE FACP MUST BE CAPABLE OF ACCEPTING 10 VOLTSROOT MEAN SQUARED (VRMS), 25 VRMS, 70.7 VRMSAND/OR LINE LEVEL (.707 VRMS) AUDIO INPUTS.

4. FACP MUST BE CONFIGURED TO ACCEPT DRY CONTACTINPUT FROM AN EXTERNAL INTERFACE TO ALERT THEFIRE ALARM PANEL THAT A MNS MESSAGE ISFORTHCOMING. THE FIRE ALARM PANEL MUST BECONFIGURED SO THAT WHILE THIS INPUT IS ACTIVE(CONTACT CLOSED) THE FIRE ALARM PANEL MUSTROUTE AUDIO PROVIDED BY THE MNS INTERFACEDIRECTLY TO ALL CONNECTED FIRE ALARM SPEAKERS.THE SYSTEM MUST BE PROGRAMMED SO THIS EXTERNALAUDIO INPUT WILL RECEIVE HIGHEST PRIORITY ANDOVERRIDE ALL FIRE ALARM NOTIFICATION SO LONG ASTHE INPUT IS ACTIVE. WHEN THE INPUT GOES INACTIVE(CONTACT OPEN) THE EXTERNAL AUDIO ROUTING WILLCEASE AND THE FIRE ALARM PANEL MUSTAUTOMATICALLY RETURN TO THE PRIOR NOTIFICATIONPROGRAM THAT WAS ACTIVE BEFORE THE MNSMESSAGE.

5. FACP MUST BE COMPATIBLE AND OPERABLE WITH THEEXISTING FIRE ALARM SUPERVISING STATIONSHUREGUARD III. EXISTING BASEWIDE MASSNOTIFICATION REPORTING SYSTEM IS A COOPERINDUSTRIES WAVES SYSTEM. CONTRACTOR MUSTPROVIDE ALL EQUIPMENT AND LABOR REQUIRED TOCONNECT THE NEW FIRE ALARM AND DETECTIONSYSTEM TO THE BASE'S SUPERVISING STATION. WAVESSYSTEM TRANSCEIVER TO BE PROVIDED BY THEGOVERNMENT.

6. DACT MUST BE CONFIGURED TO TRANSMIT SIGNALS INCONTACT ID FORMAT.

7. SIGNALS TRANSMITTED OVER THE PRIMARY ANDSECONDARY MEANS OF TRANSMISSION MUST BE POINTSPECIFIC WITH EACH ADDRESS AND CONDITIONINDICATED AT THE FIRE ALARM PANEL TRANSMITTEDSEPARATELY. ALL FIRE ALARMS, SUPERVISORY ALARMS,AND TROUBLE CONDITIONS MUST BE TRANSMITTED TO

THE SUPERVISING STATION. CONNECTION TO THE FIREALARM REPORTING SYSTEM AND PROGRAMMING OF THEDACT MODULE AND HEAD END EQUIPMENT SHUREGUARDIII MUST BE COORDINATED WITH THE FIRE ALARMREPORTING SYSTEM (FARS) ADMINISTRATOR.

8. PROVIDE A DOCUMENT CABINET ADJACENT TO FACP.CABINET MUST BE STEEL, LOCKING, WITH AHINGE-MOUNTED DOOR, KEYED THE SAME AS THE FACP.PROMINENTLY LABEL THE EXTERIOR OF THE CABINET"SYSTEM RECORD DOCUMENTS". CABINET MUSTINCLUDE PAPER COPIES AND A CD OF FIRE ALARMAS-BUILT DRAWINGS, LIST OF CONTACT ID DESCRIPTIONSFOR THE FIRE ALARM ADDRESSABLE DEVICES, NFPA 72RECORDS OF COMPLETION. CD MUST INCLUDESITE-SPECIFIC SOFTWARE AND O&M MANUALS STOREDIN A CD JEWEL CASE. PROVIDE A LAMINATED GRAPHICFLOOR PLAN SIZE 22"X34" ADJACENT TO THE FACP ANDMAIN ENTRANCE TO BUILDING ADJACENT TO THEANNUNCIATOR. THE DRAWING MUST DEPICT ALL FIREALARM DEVICES, REMOTE POWER SUPPLY PANELS, ANDASSOCIATED EQUIPMENT WITHIN THE FACILITY. THEDRAWING MUST ALSO INCLUDE ROOM NUMBERS.

9. FIRE ALARM PLANS INDICATE AREA OF STROBECOVERAGE AND ARE DIAGRAMMATIC ONLY.CONTRACTOR IS RESPONSIBLE FOR PROVIDINGADDITIONAL SPEAKERS FOR EACH FACILITY TO MEET ALLMASS NOTIFICATION SYSTEM INTELLIGIBILITYREQUIREMENTS IN ACCORDANCE WITH UFC 4-021-01.

10. INSTALL COOPER WHEELOCK SERIES STH-155SUPERVISED HORN LOUDSPEAKER OUTSIDE OFBUILDING.

11. LABEL ALL DEVICES WITH THEIR ADDRESSES.

12. PROVIDE ACCESS FOR THE CAMP LEJEUNE FIRE ANDEMERGENCY SERVICES FIRE ALARM TECHNICIANS TOUNINSTALL AND RETRIEVE FIRE ALARM PANELS,SYSTEMS AND COMPONENTS PRIOR TO THE DEMOLITIONOF EXISTING BUILDINGS, POC IS DAVID JONES (910)376-0437.

FIRE ALARM AND MNS MONITORING NOTES

EXISTING4100ES

NO SCALEFIRE ALARM/MASS NOTIFICATION INPUT-OUTPUT MATRIX

ACTU

ATE

COM

MON

ALA

RM S

IGNA

L

ACTU

ATE

AUDI

BLE

ALAR

M S

IGNA

L

ACTU

ATE

COM

MON

SUP

ERVI

SORY

SIG

NAL

INDI

CATO

R

ACTU

ATE

AUDI

BLE

SUPE

RVIS

ORY

SIGN

AL

ACTU

ATE

COM

MON

TRO

UBLE

SIG

NAL

INDI

CATO

R

ACTU

ATE

AUDI

BLE

COM

MON

TRO

UBLE

SIG

NAL

ACTI

VATE

DIS

PLAY

ON

FACP

AND

ANN

UNCI

ATOR

S

ACTU

ATE

AUDI

BLE

EVAC

UATI

ONSI

GNAL

S &

VOIC

E M

ESSA

GE

ACTI

VATE

VIS

UAL

EVAC

UATI

ON S

IGNA

LS

TRAN

SMIT

FIR

E AL

ARM

SIG

NAL

TO S

UPER

VISI

NG S

TATI

ON

TRAN

SMIT

SUP

ERVI

SORY

SIG

NAL

TO S

UPER

VISI

NG S

TATI

ON

TRAN

SMIT

TRO

UBLE

SIG

NAL

TO S

UPER

VISI

NG S

TATI

ON

OVER

RIDE

OTH

ER M

ESSA

GES,

ACT

IVAT

EAU

DIBL

E AN

D VI

SUAL

SIG

NALS

CONTROL UNIT ANNUNCIATION NOTIFICATION SUPP.

SYSTEM INPUTS BELOW A B C D E F G H I J K L M1 MANUAL FIRE ALARM BOXES X X X X X X 12 SMOKE DETECTORS X X X X X X 23 34

WATERFLOWS X X X X X X4

5SPRINKLER CONTROL VALVES TAMPER SWITCH X X X X

56

FIRE ALARM AC POWER FAILURE X X X X6

7FIRE ALARM SYSTEM LOW BATTERY X X X X

78

OPEN CIRCUIT X X X X8

9GROUND FAULT X X X X

910

NOTIFICATION APPLIANCE CIRCUIT SHORT X X X X10

11BASEWIDE MASS NOTIFICATION MESSAGE ACTIVE X

11A B C D E F G H I J K L M

SYSTEM OUTPUT BELOW

LOCAL OPERATING CONSOLE (LOC) X

TRX-401TRANSCEIVER

SFSWP

SF F S

FINISHED WALL

WALL MOUNTEDSMOKE/HEAT DETECTOR

CEILING MOUNTEDSMOKE/HEAT DETECTORACCEPTED HERE

4"12"

MAX

CEILING3' MINIMUM

A/C SUPPLY ORRETURN DIFFUSER

MAGNETICDOORHOLDER 5"

DOORWIDTHLESS 3"

MANUALPULLSTATION

TO EXIT DOOR5' MAXIMUM

FIREPHONEJACK 42"MIN TO 48" MAX

TO TOP OF PULLHANDLE

92" MIN AFF

AUDIBLEONLYAUDIBLE/VISUAL &

VISUAL ONLYAPPLIANCES

SYNCHRONIZE MORETHAN TWO

APPLIANCES IN ANYFIELD OF VIEW.

F I R EF I R E

FOR CEILING HEIGHTS LESS THAN 86" THEVISUAL LENS MOUNTING HEIGHT MUST BE

WITHIN 6" OF THE CEILING

96"MAXIMUM

AFF

80"MINIMUM

AFF

FINISHED FLOOR

NO SCALEFIRE ALARM SYSTEM DEVICE MOUNTING HEIGHT DETAILNO SCALE

NOTE: MEASUREMENTSSHOWN ARE TO THE CLOSESTEDGE OF THE DETECTOR

6" MINIMUM BFC

NO SCALENO SCALE

LOCAL OPERATORS CONSOLELOC

D DUCT SMOKE DETECTOR

REMOTE TEST / RESET DEVICERT

02/24/20

EXISTING CHAPEL( BUILDING 17 )

ADDITION ( BUILDING 17A )

SF

TO OTHERADDRESSABLEDEVICES

F S H D

RTTO AHUSHUTDOWN

TO OTHERADDRESSABLEDEVICESS

WP

SS

120VAC

MNSREMOTE

NEW FACP

Page 2: FIRE ALARM DEMOLITION NOTES GENERAL FIRE ALARM NOTES

1

2

3

4

5

6

7

8

F SS

F RT S

H

D

SS

RT

SHS

DFACP

1

SSWP F LOC

FAA

F S

F S WP

SWP

101VESTIBULE

102CONFESSIONAL

103SANCTUARY

104ALTAR

105

CHANGINGROMM

106CORR.

109JAN.

108UNISEX

107ELEC.

8

S

201

STORAGEMEZZANINE The Walker Group Architecture, Inc

PO Box 541, New Bern, NC 28563252.636.8778 (PHONE)252.636.8992 (FAX)

WALKERGROUP

i n c o r p o r a t e d

the

ARCHITECTURE

DISCLOSURE OF INFORMATIONCONTRACTOR SHALL COMPLY AS FOLLOWS:

(A) THE CONTRACTOR SHALL NOT RELEASE TO ANYONE OUTSIDE THE CONTRACTOR'S ORGANIZATION ANY UNCLASSIFIED INFORMATION, REGARDLESS OF MEDIUM (E.G., FILM, TAPE,DOCUMENT), PERTAINING TO ANY PART OF THIS CONTRACT OR ANY PROGRAM RELATED TO THIS CONTRACT, UNLESS-

(1) THE CONTRACTING OFFICER HAS GIVEN PRIOR WRITTEN APPROVAL; OR(2) THE INFORMATION IS OTHERWISE IN THE PUBLIC DOMAIN BEFORE THE DATE OF RELEASE(B) REQUESTS FOR APPROVAL SHALL IDENTIFY THE SPECIFIC INFORMATION TO BE RELEASED, THE MEDIUM TO BE USED, AND THE PURPOSE FOR THE RELEASE. THE CONTRACTOR SHALL

SUBMIT ITS REQUEST TO THE CONTRACTING OFFICER AT LEAST 45 DAYS BEFORE THE PROPOSED DATE FOR RELEASE.(C) THE CONTRACTOR AGREES TO INCLUDE A SIMILAR REQUIREMENT IN EACH SUBCONTRACT UNDER HIS CONTRACT. SUBCONTRACTORS SHALL SUBMIT REQUESTS FOR AUTHORIZATION

TO RELEASE THROUGH THE PRIME CONTRACTOR TO THE CONTRACTING OFFICER.

NDEMOLITION FIRST FLOOR PLANSCALE: 1/8" = 1'-0"

NDEMOLITION MEZZANINE FLOOR PLANSCALE: 1/8" = 1'-0"

1 REMOVE EXISTING FIRE ALARM CONTROL PANEL TO BE RELOCATED.REFER TO SHEET FA101 FOR NEW LOCATION.

NOTES THIS SHEET

DUE TO THE REMOVAL AND RELOCATION OF THE EXISTING FACP, THE FIRE ALARM SYSTEM MUST UNDERGO AS MUCHMINIMAL DOWN TIME AS POSSIBLE. IF THIS DOWNTIME WERE TO OCCUR AFTER CONSTRUCTION HOURS, CONTRACTORMUST COORDINATE WITH CAMP LEJEUNE PERSONNEL TO CONDUCT FIRE WATCH DURING THESE HOURS.

FIRE ALARM/MASS NOTIFICATION OPERATION NOTE:

02/24/20

Page 3: FIRE ALARM DEMOLITION NOTES GENERAL FIRE ALARM NOTES

1

2

3

4

5

6

7

8

20 CF

0.5

SWP

SF RT S

H

D

SS

RT

FHS

D

SSWP F LOC

FAA

F S

F S WP

FACP

S15

S15

F15

F15

S

S

SWP

SWP

SWP

SWP

SWP

S75

S75

F15

S15

SWP

S H

F

F

F

F

F

S15

F

F15

NAC

1

101VESTIBULE

103CONFESSIONAL102

STORAGE

104CHAPEL

105ALTAR

109CORRIDOR

108STORAGE

106VESTIBULE

107UNISEX

110MECH.

311BABYSITTING

313PANTRY

314KITCHEN

304FELLOWSHIP HALL

305MENS 306

WOMENS

310TELECOM 309

MECH/ELEC.

308OFFICE

307OFFICE

301VESTIBULE

302CORRIDOR

303JAN.

312UNISEX

LOC

2

S75

8

S

The Walker Group Architecture, IncPO Box 541, New Bern, NC 28563252.636.8778 (PHONE)252.636.8992 (FAX)

WALKERGROUP

i n c o r p o r a t e d

the

ARCHITECTURE

DISCLOSURE OF INFORMATIONCONTRACTOR SHALL COMPLY AS FOLLOWS:

(A) THE CONTRACTOR SHALL NOT RELEASE TO ANYONE OUTSIDE THE CONTRACTOR'S ORGANIZATION ANY UNCLASSIFIED INFORMATION, REGARDLESS OF MEDIUM (E.G., FILM, TAPE,DOCUMENT), PERTAINING TO ANY PART OF THIS CONTRACT OR ANY PROGRAM RELATED TO THIS CONTRACT, UNLESS-

(1) THE CONTRACTING OFFICER HAS GIVEN PRIOR WRITTEN APPROVAL; OR(2) THE INFORMATION IS OTHERWISE IN THE PUBLIC DOMAIN BEFORE THE DATE OF RELEASE(B) REQUESTS FOR APPROVAL SHALL IDENTIFY THE SPECIFIC INFORMATION TO BE RELEASED, THE MEDIUM TO BE USED, AND THE PURPOSE FOR THE RELEASE. THE CONTRACTOR SHALL

SUBMIT ITS REQUEST TO THE CONTRACTING OFFICER AT LEAST 45 DAYS BEFORE THE PROPOSED DATE FOR RELEASE.(C) THE CONTRACTOR AGREES TO INCLUDE A SIMILAR REQUIREMENT IN EACH SUBCONTRACT UNDER HIS CONTRACT. SUBCONTRACTORS SHALL SUBMIT REQUESTS FOR AUTHORIZATION

TO RELEASE THROUGH THE PRIME CONTRACTOR TO THE CONTRACTING OFFICER.NCONSTRUCTION FIRST FLOOR PLANSCALE: 1/8" = 1'-0"

1

2

REINSTALL FIRE ALARM CONTROL PANEL THIS LOCATION. REWORK/EXTENDCIRCUITRY AS NEEDED. TESTING OF SYSTEM MUST BE DONE UPONCOMPLETION OF PROJECT TO ENSURE INTEGRITY OF SYSTEM WAS KEPTINTACT DURING CONSTRUCTION.

PROVIDE (1) 1-1/4"C, SCH. 80 PVC DIRECT BURIED 24" BFG, WITH 2/C, 18AWGSTP, OSP RATED CABLE FROM EXISTING FACP TO NOTIFICATION EXTENDERPANEL IN NEW ADDITION.

NOTES THIS SHEET

NNEW WORK MEZZANINE FLOOR PLANSCALE: 1/8" = 1'-0"

02/24/20

Page 4: FIRE ALARM DEMOLITION NOTES GENERAL FIRE ALARM NOTES

The Walker Group Architecture, IncPO Box 541, New Bern, NC 28563252.636.8778 (PHONE)252.636.8992 (FAX)

WALKERGROUP

i n c o r p o r a t e d

the

ARCHITECTURE

DISCLOSURE OF INFORMATIONCONTRACTOR SHALL COMPLY AS FOLLOWS:

(A) THE CONTRACTOR SHALL NOT RELEASE TO ANYONE OUTSIDE THE CONTRACTOR'S ORGANIZATION ANY UNCLASSIFIED INFORMATION, REGARDLESS OF MEDIUM (E.G., FILM, TAPE,DOCUMENT), PERTAINING TO ANY PART OF THIS CONTRACT OR ANY PROGRAM RELATED TO THIS CONTRACT, UNLESS-

(1) THE CONTRACTING OFFICER HAS GIVEN PRIOR WRITTEN APPROVAL; OR(2) THE INFORMATION IS OTHERWISE IN THE PUBLIC DOMAIN BEFORE THE DATE OF RELEASE(B) REQUESTS FOR APPROVAL SHALL IDENTIFY THE SPECIFIC INFORMATION TO BE RELEASED, THE MEDIUM TO BE USED, AND THE PURPOSE FOR THE RELEASE. THE CONTRACTOR SHALL

SUBMIT ITS REQUEST TO THE CONTRACTING OFFICER AT LEAST 45 DAYS BEFORE THE PROPOSED DATE FOR RELEASE.(C) THE CONTRACTOR AGREES TO INCLUDE A SIMILAR REQUIREMENT IN EACH SUBCONTRACT UNDER HIS CONTRACT. SUBCONTRACTORS SHALL SUBMIT REQUESTS FOR AUTHORIZATION

TO RELEASE THROUGH THE PRIME CONTRACTOR TO THE CONTRACTING OFFICER.

LEGEND & ABBREVIATIONS

TELECOMMUNICATIONS

TELECOMMUNICATIONS BACKBOARD

4" CONDUIT SLEEVE

DDC OUTLET, 5"X5"X2 7/8"D BOX WITH SINGLE GANG PLASTER RING

AND SINGLE GANG COVERPLATE TO MATCH ELECTRICAL OUTLET

COVERPLATE MATERIAL AND COLOR, COORDINATE MOUNTING HEIGHT

WITH DDC VENDOR PRIOR TO INSTALLATION, WITH 1 1/4"C WITH (1) 2

STRAND, SMFO CABLE. STUB CONDUIT TO CABLE TRAY AND

TERMINATE WITH GROUNDING BUSHING. CONTINUE CABLING IN CABLE

TRAY TO TELECOM ROOM.

TELEPHONE OUTLET, 5"X5"X2 7/8"D BOX WITH SINGLE GANG

PLASTER RING AND SINGLE GANG COVERPLATE TO MATCH

ELECTRICAL OUTLET COVERPLATE MATERIAL AND COLOR, 46"

AFF, UON, WITH 1 1/4"C WITH (1) CAT6 UTP CABLE (GREEN VOICE),

STUB CONDUIT TO CABLE TRAY AND TERMINATE WITH

GROUNDING BUSHING. CONTINUE CABLING IN CABLE TRAY TO

TELECOM ROOM.

GENERAL SPECIAL SYSTEMS

THE GENERAL CONTRACTOR SHALL PROVIDE A COMPLETION SCHEDULE, BROKEN DOWN

BY VARIOUS CONSTRUCTION PHASES, FOR TURN OVER OF COMPLETED ROUGH-IN FOR

CONTRACTOR TO FINISH WORK. THE CONTRACTOR SHALL COORDINATE TURN OVER WITH

VENDORS, AND SHALL TURN OVER AREAS WITH ADEQUATE TIME FOR VENDOR FINISH

WORK. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ANY EXTRA VENDOR COST

RESULTING FROM INCORRECT SYSTEMS ROUGH-IN.

THE GENERAL CONTRACTOR SHALL PROVIDE IN-WALL REINFORCEMENT AS NECESSARY

FOR ALL SYSTEMS CABINETS, SHELVES, BRACKETS, FURNITURE MOUNTS, ETC.. AND

SHALL MOUNT CABINETS, SHELVES, BRACKETS, AND FURNITURE MOUNTS IN

ACCORDANCE WITH DRAWINGS, VENDOR SUBMITTALS, AND ALL APPLICABLE CODES.

THE CONTRACTOR SHALL COORDINATE AND PROVIDE ALL REQUIRED RACEWAY SYSTEMS

FOR ALL SPECIAL SYSTEMS INCLUDING CONDUIT WITH PULL STRING, JUNCTION BOXES,

GROUNDING, BACKBOARDS, POWER CONNECTIONS, ETC. THE CONTRACTOR SHALL

COORDINATE ALL ROUGH-IN, BOX SIZES AND CONFIGURATIONS, CONDUIT SIZES AND

ROUTING WITH THE VENDOR PRIOR TO INSTALLATION OF THE RACEWAY SYSTEM.

THE CONTRACTOR SHALL PROVIDE ALL CABLING AND WIRING (EXCEPT POWER WIRING),

CABLE TRAY, JACKS, COVER PLATE COMPATIBLE WITH THE EQUIPMENT, DEVICES, RACKS,

AND COMPONENT EQUIPMENT UNLESS OTHERWISE NOTED.

FINAL DEVICE LOCATIONS AND ELEVATIONS SHALL BE COORDINATED WITH

ARCHITECTURAL PLANS, CASEWORK AND ELEVATIONS, AND VENDOR REQUIREMENTS.

TELEPHONE AND DATA SYSTEMS

THE TELEPHONE AND DATA SYSTEMS WILL BE THROUGH THE CONTRACTOR. THE

CONTRACTOR SHALL PROVIDE A COMPLETE RACEWAY SYSTEM AS INDICATED.

ALL CONDUITS SHALL BE 1 1/4" MINIMUM, SHALL HAVE A PULL WIRE AND SHALL BE

TERMINATED WITH INSULATED GROUNDING BUSHING. ALL TELEPHONE, DATA AND CABLE

TELEVISION BOXES SHALL BE 5" X 5" X 2 7/8" DEEP WITH A SINGLE GANG RISE AND BLANK

COVER PLATE UNLESS OTHERWISE INDICATED. COORDINATE CONDUIT QUANTITIES,

SIZES AND LOCATIONS.

THE BUILDING SHALL BE PRE-WIRED BY THE VENDOR DURING CONSTRUCTION PRIOR TO

CLOSING THE WALL CAVITIES.

STUB ALL CONDUITS WITH PULL WIRE FOR COMMUNICATIONS DEVICE OUT TO CABLE

TRAY AND PROVIDE INSULATED GROUND BUSHING. WHERE A FULL WALL SEPARATES THE

CONDUIT STUB OUT FROM THE DESTINATION ROOM, PROVIDE A 1 1/2" MINIMUM SLEEVE

THROUGH THE WALL, ABOVE AN ACCESSIBLE CEILING, TO ACCOMMODATE THE CABLING.

PROVIDE ALL CONDUITS AND SLEEVES PENETRATING RATED FIRE OR SMOKE WALLS

WITH APPROVED FIRE RETARDANT TO PROVIDE A UL RATED ASSEMBLY. MAINTAIN

VENDOR RECOMMENDED SEPARATION BETWEEN WIRING OF DIFFERENT SYSTEMS AND

FROM INTERFERENCE PRODUCING ELECTRICAL DEVICES SUCH AS FLUORESCENT

LIGHTS, BALLASTS, TRANSFORMERS, RELAYS, MOTOR CONTROLS, ETC..

GENERAL SPECIAL SYSTEM NOTES

REQ'D REQUIRED

PNL PANEL

NATIONAL ELECTRICAL CODENEC

GROUNDGND

EXIST EXISTING

EXISTING TO REMAINETR

CONDUIT C

RACK UNITRU

AREA OF REFUGE ASSISTANCEARA

ABBREVIATIONS

ABOVE FINISHED GRADEAFG

ABOVE FINISHED FLOORAFF

FMCP FIRE ALARM/MASS NOTIFICATION CONTROL PANEL

BELOW FINISHED GRADEBFG

BUILDING ENTRANCE PROTECTORBEP

TELECOMMUNICATIONS MAIN GROUND BUS BARTMGB

DDC OUTLET

NO SCALE

1-1/4"C TO CABLE TRAY

DDC

BLANK

385 A 386

5" X 5" X 2 1/8" BOX

1-1/4"C TO CABLE TRAY

5" X 5" X 2 7/8" BOX

MOUNTING STUDS

(1) 4 PAIR 24 AWG COPPER

CAT 6 UTP, GREEN CABLES

(1) GREEN CAT 6 UTP RJ45

JACKS

TELECOMMUNICATIONS RISER DIAGRAM

NO SCALE

FIRST FLOOR310

(4) CAT6 UTP

(TYP. FOR ALL TELE/DATA OUTLETS)

NEW BUILDING - 17A EXISTING CHAPEL

BET BUILDING ENTRANCE TERMINAL

NOTE:

(2) 4"C, SCH. 80PVC, DIRECT BURIED 24" BFG MIN. (1) 4"C TO INCLUDE (1) 1-1/4"C WITH / (1) 3" 3-CELL MAXCELL FABRIC INNERDUCT WITH (1) 12 STRAND SMFO, OSP RATED

CABLE. (1) 4"C WITH (1) 25 PAIR COPPER TELEPHONE CABLE, OSP RATED TO RP-5. FIBER DEMARC LOCATION TO BE DETERMINED BASE TELEPHONE.

(1) 3"C., SCH.80 PVC, DIRECT BURIED 24"BFG MIN WITH (1) 3" 3-CELL MAXCELL FABRIC INNERDUCT WITH (1) 6 STRAND SMFO CABLE, OSP RATED (INSTALLED IN INNERDUCT),

WITH (1) 12 PAIR TELEPHONE CABLE, OSP RATED.

1

1

(1) 4 PAIR 24AWG COPPER

(TYP. FOR TELEPHONE ONLY OUTLETS)

DDC

106

25RU WALL MOUNTED CABINET,

FIBER OPTIC DISTRIBUTION PANEL,

CAT 6 PATH PANEL, FIBER PATCH

PANEL, CABLE MANAGMENT, FAN,

LOCKABLE.

WALL TELEPHONE OUTLET

NO SCALE

PB PULLBOX, TYPE 8. SEE DETAIL THIS SHEET.

(1) 2 STRAND SMFO CABLE

(1) DUPLEX "SC" TYPE JACK

385 A 386

BET

TMGB

PB

FREE STANDING 7'

EQUIPMENT RACK

3"PVC, SMART

TYPE ELBOW

WINDOW

TMGB

BET

2

2

COMBINATION TELEPHONE / DATA JACK

NO SCALE

(4) 4 PAIR 24 AWG COPPER CAT

6 UTP, GREEN CABLES FOR

EVEN NUMBERED JACKS

(2) DUAL MOLDED 8P8C JACKS

387 A 388

5" X 5" X 2 1/8" BOX

GREEN COMPUTER ICON -

EVEN NUMBERS

GREEN TELEPHONE

ICON - ODD NUMBERS 387 A 388

DIGITAL DATA CONTROLDDC

TELE/DATA OUTLET, 5"X5"X2 7/8"D BOX WITH SINGLE GANG PLASTER

RING AND SINGLE GANG COVERPLATE TO MATCH ELECTRICAL OUTLET

COVERPLATE MATERIAL AND COLOR, 18" AFF, UON, WITH 1 1/4"C WITH

(4) CAT 6 UTP CABLE (2 GREEN VOICE / 2 GREEN DATA). STUB CONDUIT

TO CABLE TRAY AND TERMINATE WITH GROUNDING BUSHING.

CONTINUE CABLING IN CABLE TRAY TO TELECOM ROOM.

DDC

LADDER TYPE CABLE TRAY

WIRE BASKET TYPE CABLE TRAY

1-1/4"C TO CABLE TRAY

30" X 48" X 24" DEEP

24" X 36" X 24" DEEP

12" X 24" X 24" DEEP

12" X 18" X 24" DEEP

12" X 12" X 24" DEEP

HANDHOLE SIZING

PROVIDE LABEL "ELECTRICAL" FOR POWER HANDHOLES OR "TELEPHONE" FOR TELEPHONE

PROVIDE WITH (2) 2 1/2" MOUSEHOLES.

PROVIDE STAINLESS STEEL BOLTS AND INSERTS.

10" x 10" AREA.

COVER AND BOX SHALL WITHSTAND A SERVICE LOAD OF NO LESS THAN 15,000 LBS OVER A

REINFORCING WITH COMPRESSIVE STRENGTH OF NO LESS THAN 10,000 PSI.

HOUSING SHALL BE A POLYMER CONCRETE REINFORCED WITH A HEAVY WEAVE FIBERGLASS

5.

4.

3.

2.

HANDHOLES, OR AS INDICATED.

REQUIRED

BOX WHEN

SECTIONAL

1.

HANDHOLE REQUIREMENTS

9

8

7

6

TYPE

5

CRUSHED ROCK

6"

EARTH

COMPACTED

PULL SLOT

SURFACE

RESISTANT

SKID

L

A

B

E

L

HEX BOLT AND

WASHER

STAINLESS STEEL

COVER

BOX AND

AROUND BOX

6"

CONCRETE RING

10"

6"

UG-6

JUNE 2002

(COMPOSITE/FIBERGLASS) TYPES 5, 6, 7, 8 & 9

STANDARD ELECTRICAL HANDHOLE (NONTRAFFIC)

SKETCH DATE STYLE

LADDER CABLE TRAY DETAIL

NO SCALE

NOTES:

1. CONTRACTOR SHALL PROVIDE PATHWAY FOR ALL LISTED SYSTEMS CABLING. TRAY MUST COMPLY WITH NEC FOR

CABLE TRAY FILL REQUIREMENTS. IN NO CASE MAY THE CABLE TRAY BE LESS THAN THE STATED MINIMUM SIZE.

2. MOUNT CABLE TRAY AT A MINIMUM OF 12" BELOW MECHANICAL DUCT WORK BUT AS HIGH AS POSSIBLE TO AVOID

TAMPERING.

3. TYPICAL MOUNT OVER RACKS IN TELCOM ROOM.

TYPICAL HANGER. SUPPORT FROM STRUCTURE

ABOVE. SPACE AT 60" ON CENTER AND WITHIN 24"

OF ENDS MINIMUM.

TYPICAL CONDUIT STUBBED ABOVE

CABLE TRAY WITH BUSHING. PROVIDE #6

AWG GROUND BETWEEN CONDUIT AND

#2 AWG CABLE TRAY GROUND WIRE.

TYPICAL CONDUIT STUBBED

THROUGH WALL TO ABOVE

CABLE TRAY WITH BUSHING.

PROVIDE #6 AWG GROUND

BETWEEN CONDUIT AND #2

AWG CABLE TRAY GROUND

WIRE.

SIZE AS INDICATED

CABLE TRAY

GROUND WIRE, #2.

MOUNT TO SIDE OF

CABLE TRAY.

2" MIN

G

G

G

G

#6 BOND GROUND

WIRE TO CABLE

TRAY GROUND

WIRE

#6 BOND GROUND

WIRE TO CABLE

TRAY GROUND

WIRE

NO SCALE

2" MIN.

NOTES:

2. MOUNT CABLE TRAY AT A MINIMUM OF 12" BELOW MECHANICAL DUCT WORK BUT AS HIGH AS POSSIBLE TO AVOID

TAMPERING.

3. TYPICAL MOUNTING METHOD.

PROVIDE MANUFACTURER RECOMMENDED

COUPLING TO SECURELY CONNECT AND

GROUND SECTIONS OF CABLE TRAY.

TYPICAL HANGER. SUPPORT

FROM STRUCTURE ABOVE.

SPACE AT 60" ON CENTER

AND WITHIN 24" OF ENDS

MINIMUM.

TYPICAL CONDUIT STUBBED THROUGH WALL TO

ABOVE CABLE TRAY WITH BUSHING. PROVIDE #6

AWG GROUND BETWEEN CONDUIT AND #2 AWG

CABLE TRAY GROUND WIRE.

#6 BOND GROUND

WIRE TO CABLE

TRAY GROUND

WIRE

CABLE TRAY GROUND

WIRE, #2.

MOUNT TO SIDE OF

CABLE TRAY

SIZE AS INDICATED

G

G

G

#6 BOND TO CABLE

TRAY GROUND

BONDING CLAMP

1. CONTRACTOR SHALL PROVIDE PATHWAY FOR ALL LISTED SYSTEMS CABLING. TRAY MUST COMPLY WITH UFC 3-580-1

FOR CABLE TRAY FILL REQUIREMENTS. IN NO CASE MAY THE CABLE TRAY BE LESS THAN THE STATED MINIMUM SIZE.

WIRE BASKET CABLE TRAY DETAIL - ABOVE CEILING

TYPICAL GROUND BUS BAR DETAIL

NO SCALE

LESS THAN 4 (13)

4 - 6 ( 14 - 20 )

6 - 8 ( 21 - 26 )

8 - 10 ( 27 - 33 )

10 - 13 ( 34 - 41 )

13 - 16 ( 42 - 52 )

16 - 20 ( 53 - 66 )

20 - 26 ( 67 - 84 )

26 - 32 ( 85 - 105 )

32 - 38 ( 106 - 125 )

38 - 46 ( 126 - 150 )

46 - 53 ( 151 - 175 )

53 - 76 ( 176 - 250 )

76 - 91 ( 251 - 300 )

GREATER THAN 91 ( 301 )

TBB - TELECOMMUNICATIONS BONDING BACKBONE

TBC - TELECOMMUNICATIONS BONDING CONDUCTOR

4

3

2

1

1/0

2/0

3/0

4/0

250kcmil

300kcmil

350kcmil

500kcmil

600kcmil

750kcmil

6

TBB/TBC SIZE (AWG)TBB/TBC LENGTH M (FT)

COPPER BASED BOLTS, NUTS, & LOCK

WASHERS (TYPICAL)

STAND-OFF INSULATOR, 1KV MINIMUM

(2" MINIMUM OFFSET) (TYPICAL)

COPPER MAIN TELECOMMUNICATIONS

GROUND BUS BAR ( )

4" x 12" x 1/4" THICK (TYPICAL)

TMGB

(1) #6 CU GND IN 3/4"C. CONNECT TO

ELECTRICAL PANEL GROUND ELECTRODE

SYSTEM PER NEC ARTICLE 800

TO BUILDING

STEEL

TO CABLE TRAY

TO TELECOM CABINET

MOUNTING BRACKET(S)

FACTORY DRILLED HOLES (TYPICAL)

CONTRACTOR SHALL SIZE

TELECOMMUNICATIONS GROUNDING

AND BONDING INFRASTRUCTURE

PER ANSI J-STD-607-D

EXISTING PLYWOOD BACKBOARD

8-POSITION, 8-CONDUCTORS8P8C

CATEGORYCAT

UNLESS OTHERWISE NOTEDUON

UNSHEILDED TWISTED PAIRUTP

02/24/20

Page 5: FIRE ALARM DEMOLITION NOTES GENERAL FIRE ALARM NOTES

BE

TT

MG

B

12" X 2" LADDER

TYPE CABLE TRAY

(2) 4"C

1

2

3

4

5

6

7

8

20 CF

E F G H

9

10

11

0.5

B.1 B.7BA C D

I J K L M N O P

DDC

101

VESTIBULE

103

CONFESSIONAL102

STORAGE

104

CHAPEL

105

ALTAR

109

CORRIDOR

108

STORAGE

106

VESTIBULE

107

UNISEX

110

MECH.

311

BABYSITTING

313

PANTRY

314

KITCHEN

304

FELLOWSHIP HALL

305

MENS

306

WOMENS

310

TELECOM

309

MECH/ELEC.

308

OFFICE

307

OFFICE

301

VESTIBULE

302

CORRIDOR

303

JAN.

312

UNISEX

PB3"C, MIN 24" BFG

1

T-101

1

6" X 2" WIRE

BASKET TYPE

CABLE TRAY

BET

TMGB

DDC

The Walker Group Architecture, IncPO Box 541, New Bern, NC 28563252.636.8778 (PHONE)252.636.8992 (FAX)

WALKERGROUP

i n c o r p o r a t e d

the

ARCHITECTURE

DISCLOSURE OF INFORMATIONCONTRACTOR SHALL COMPLY AS FOLLOWS:

(A) THE CONTRACTOR SHALL NOT RELEASE TO ANYONE OUTSIDE THE CONTRACTOR'S ORGANIZATION ANY UNCLASSIFIED INFORMATION, REGARDLESS OF MEDIUM (E.G., FILM, TAPE,DOCUMENT), PERTAINING TO ANY PART OF THIS CONTRACT OR ANY PROGRAM RELATED TO THIS CONTRACT, UNLESS-

(1) THE CONTRACTING OFFICER HAS GIVEN PRIOR WRITTEN APPROVAL; OR(2) THE INFORMATION IS OTHERWISE IN THE PUBLIC DOMAIN BEFORE THE DATE OF RELEASE(B) REQUESTS FOR APPROVAL SHALL IDENTIFY THE SPECIFIC INFORMATION TO BE RELEASED, THE MEDIUM TO BE USED, AND THE PURPOSE FOR THE RELEASE. THE CONTRACTOR SHALL

SUBMIT ITS REQUEST TO THE CONTRACTING OFFICER AT LEAST 45 DAYS BEFORE THE PROPOSED DATE FOR RELEASE.(C) THE CONTRACTOR AGREES TO INCLUDE A SIMILAR REQUIREMENT IN EACH SUBCONTRACT UNDER HIS CONTRACT. SUBCONTRACTORS SHALL SUBMIT REQUESTS FOR AUTHORIZATION

TO RELEASE THROUGH THE PRIME CONTRACTOR TO THE CONTRACTING OFFICER.

1 REMOVE EXISTING TELECOMMUNICATIONS EQUIPMENT, SALVAGE

EXISTING HORIZONTAL CABLES. RECONNECT EXISTING HORIZONTAL

CABLES TO NEW WALL MOUNTED CABINET.

NOTES THIS SHEET

1/8" = 1'-0"

5'0'5' 10' 20'

NCONSTRUCTION FIRST FLOOR PLANSCALE: 1/8" = 1'-0"

ENLARGED PLAN - TELECOM ROOMSCALE: 1/4" = 1'-0" T-101

1

1/4" = 1'-0"

5' 10'0' 5'

02/24/20