Datasheet No.Rev
Code
OIL-100-EK-I-DS-0808 A0 Sht.No:02 of 07
CREATION OF SURFACE PRODUCTION
FACILITIES (GGS) AT EAST KHAGORIJAN
Revision Index
DATA SHEET FOR PRESSURE SAFETY VALVE
3. Revision Sheet 03 of 07
4. Notes Sheet 04 of 07
TABLE OF CONTENTS
5. DS-1 05 of 07
Description Sheet Number
1. Cover Sheet 01 of 07
2. Index Sheet 02 of 07
6. DS-2 06 of 07
7. DS-3 07 of 07
Datasheet No.Rev
Code
OIL-100-EK-I-DS-0808 A0 Sht.No: 03 of 07
RevTenability for
extra Claim Impact on MTO
A0
REVISION List
HOLD List
Issued for Review
Revision IndexCREATION OF SURFACE PRODUCTION FACILITIES
(GGS) AT EAST KHAGORIJAN
DATA SHEET FOR PRESSURE SAFETY VALVE
Rev Disc. Reasons
Datasheet No.Rev
Code
OIL-100-EK-I-DS-0808 A0 04 of 07
secured.
3. Nozzle, Seat and Disc for the above tags shall be forged.
4. All stud bolt and nut material shall be ASTM A193 Gr. B7M & Heavy hex nuts shall be ASTM A194 Gr. 2HM.
5. Painting shall be as per Protective Coating specification for Onshore Structures and Facilities.
6. All castings and welding shall be 100% radio graphed.
7. Carbon steel springs with Nickel plating shall be used for temperature services lower than 250 Deg C.
Tungsten alloy springs shall be used for temperatures greater than 250 Deg.C.
8. All relief valves of size 1" and above shall be full nozzle full lift type. Relief valves with size less than 1" shall be modified
nozzle type.
9. The pressure relief valve shall meet the requirements of API recommended practice RP 526 ‚Flanged Steel Safety Relief
Valves and RP 521‚ Pressure Relieving and Anti Pressurizing system and shall be of direct acting angle pattern,
full nozzle entry and high capacity type.
CREATION OF SURFACE PRODUCTION
FACILITIES (GGS) AT EAST KHAGORIJAN
Revision Index
DATA SHEET FOR PRESSURE SAFETY VALVE
Notes:
1. Documentation required :- Calibration Certificate,Material Certificates to 3.1 as per EN10204,Pressure test procedure/ Report
, NDT procedure / Report, Operating & Maintenance Instructions & Spare Parts List, Hydro Test, Pop test report & Installation
dimension Drawings.
2. All Instruments to be supplied with SS316 name plate with tag no. permanently inscribed. Tags shall be permanently
TITLE ITEM/TAG No. DATA SHEET No.
PRESSURE SAFETY VALVE
PROJECT DESCRIPTION PROJECT No. SHEET REV
CREATION OF SURFACE PRODUCTION FACILITIES (GGS) AT EAST KHAGORIJAN 05 OF 07 A0
MPC CONTRACTOR PURCHASE ORDER No. REQUISITION NO. SPECIFICATION No.
TBA
CLIENT NAME REV No. BY DATE DATE APP. DATE
OIL INDIA LIMITED / TEC LIMITED A0 IMR 28-Nov-18 28-Nov-18 MSR/ VSR 28-Nov-18
CLIENT DOCUMENT No.
-
ORIGINATOR ORIG. DATE
19-Sep-18
UNITS:- Pressure psig kg/cm2 g kPag Flow : Gas MMscfd Sm
3/hr
Temp O C O F Liquid: m3/hr USgpm
1 TAG No.
2 SERVICE
3 VESSEL No.
4 LINE No.
5 P &ID NUMBER
6 FULL NOZZLE/SEMI-NOZZLE
7 SAFETY / RELIEF / SAFETY RELIEF
8 CONV., BELLOWS, PILOT OP.
9 BONNET TYPE
10 SIZE INLET OUTLET 1" 1" 1" 1"
11 FL. RATING INLET 300# 300# 300# 300#
12 FL. FACE INLET OUTLET RF RF RF RF
13 BODY
14 BONNET
15 NOZZLE, SEAT and DISC
16 RESILIENT SEAT SEAL
17 GUIDE AND RINGS
18 SPRING
19 BELLOWS
20 CAP: SCREWED or BOLTED
21 LEVER: OPEN or PACKED
22 TEST GAG
23 CODE
24 BASIS
25 VESSEL SIZE DIA X T/T
26 FLUID STATE HOT OIL HOT OIL LIQUID HOT OIL
27
28 OPERATING S.G MOL. WEIGHT
29 OPER. PRESS SET PRESS ATM ATM 5.5 5.5
30 OPER. TEMP REL. TEMP 27-50 27-50 200 200
31 CONSTANT
32 BACK PRESSURE VARIABLE
33 TOTAL
34 % ALLOWABLE OVER PRESSURE
35 OVER PRESSURE FACTOR
36 COMPRESSIBILITY FACTOR
37 LATENT HEAT OF VAPORIZATION (KJ/Kg)
38 RATIO OF SPECIFIC HEATS Cp / Cv
39 OPERATING VISCOSITY cP
40 VAPOUR GAS MASS FRACTION
41 BAROMETRIC PRESSURE
42 ENVIRONMENTAL FACTOR
43 VESSEL / WETTED
44 RATED CAPACITY
45 CALCULATED AREA inch2
46 SELECTED AREA inch2
47 ORIFICE DESIGNATION
48 MANUFACTURER
49 MODEL No.
50 NOTES:-
51 REFER NOTES SHEET
52
53
54
55
56
57
58
59
* BY VENDOR
GE
NE
RA
LC
ON
NE
CT
ION
MA
TE
RIA
LO
PT
ION
SF
LU
ID D
AT
A
REQUIRED CAPACITY (VAPOUR/LIQUID)
* * * *
* * * *
* *
* * * *
* * * *
* *
12 12 12 12
REQUIRED REQUIRED REQUIRED
TBA TBA TBA TBA
LIQUID LIQUID HOT OIL
API RP 520 API RP 520 API RP 520 API RP 520
THERMAL EXPANSION THERMAL EXPANSION THERMAL EXPANSION THERMAL EXPANSION
LIQUID
SS 316 SS 316 SS 316 SS 316
SCREWED SCREWED SCREWED SCREWED
SS 316
CS with Nickle Plate CS with Nickle Plate CS with Nickle Plate CS with Nickle Plate
SS 316
OUTLET
CS, ASTM A105 CS, ASTM A105 CS, ASTM A105 CS, ASTM A105
CARBON STEEL CARBON STEEL CARBON STEEL CARBON STEEL
Hot Oil Return to Hot Oil
Return Drum
Hot Oil Return to Hot Oil Return Drum
Bypass
Hot oil to Hot Oil Drain Drum
(EK-MBD-3320)
Hot oil to Hot Oil Drain Drum
(EK-MBD-3320) Bypass
- - - -
N/A N/A N/A N/A
REQUIRED
17039-EK-P-DW-0202-13 17039-EK-P-DW-0202-13 17039-EK-P-DW-0203-10 17039-EK-P-DW-0203-10
300#
RF
2"
300#
RF
N/A N/A N/A N/A
SS 316 SS 316 SS 316 SS 316
SS 316 SS 316
IMR
barg MMSCMD kg/hr
kg/hr BLPD
FULL NOZZLE, FULL LIFT FULL NOZZLE, FULL LIFT FULL NOZZLE, FULL LIFT FULL NOZZLE, FULL LIFT
SAFETY RELIEF SAFETY RELIEF SAFETY RELIEF SAFETY RELIEF
CONVENTIONAL CONVENTIONAL CONVENTIONAL CONVENTIONAL
CLOSED BONNET CLOSED BONNET CLOSED BONNET CLOSED BONNET
2"
300#
RF
2"
300#
RF
2"
2"-HM-41-3753-BC01 2"-HM-41-3753A-BC01 2"-HM-41-3734-BC01-1N 2"-HM-41-3734A-BC01-1N
20-PSV-1380A 20-PSV-1380B 41-PSV-3728A 41-PSV-3728B
KIP-17039
- -
REFER BELOW OIL-100-EK-I-DS-0808
CKD DESCRIPTION
MV ISSUED FOR REVIEW
TITLE ITEM/TAG No. DATA SHEET No.
PRESSURE SAFETY VALVE
PROJECT DESCRIPTION PROJECT No. SHEET REV
CREATION OF SURFACE PRODUCTION FACILITIES (GGS) AT EAST KHAGORIJAN 06 OF 07 A0
MPC CONTRACTOR PURCHASE ORDER No. REQUISITION NO. SPECIFICATION No.
TBA
CLIENT NAME REV No. BY DATE DATE APP. DATE
OIL INDIA LIMITED / TEC LIMITED A0 IMR 28-Nov-18 28-Nov-18 MSR/ VSR 28-Nov-18
CLIENT DOCUMENT No.
-
ORIGINATOR ORIG. DATE
19-Sep-18
UNITS:- Pressure psig kg/cm2 g kPag Flow : Gas MMscfd Sm
3/hr
Temp O C O F Liquid: m3/hr USgpm
1 TAG No.
2 SERVICE
3 VESSEL No.
4 LINE No.
5 P &ID NUMBER
6 FULL NOZZLE/SEMI-NOZZLE
7 SAFETY / RELIEF / SAFETY RELIEF
8 CONV., BELLOWS, PILOT OP.
9 BONNET TYPE
10 SIZE INLET OUTLET 1" 1" 1" 1"
11 FL. RATING INLET 300# 300# 300# 300#
12 FL. FACE INLET OUTLET RF RF RF RF
13 BODY
14 BONNET
15 NOZZLE, SEAT and DISC
16 RESILIENT SEAT SEAL
17 GUIDE AND RINGS
18 SPRING
19 BELLOWS
20 CAP: SCREWED or BOLTED
21 LEVER: OPEN or PACKED
22 TEST GAG
23 CODE
24 BASIS
25 VESSEL SIZE DIA X T/T
26 FLUID STATE HOT OIL HOT OIL LIQUID HOT OIL
27
28 OPERATING S.G MOL. WEIGHT
29 OPER. PRESS SET PRESS 5.5 5.5 5.5 5.5
30 OPER. TEMP REL. TEMP 200 200 200 200
31 CONSTANT
32 BACK PRESSURE VARIABLE
33 TOTAL
34 % ALLOWABLE OVER PRESSURE
35 OVER PRESSURE FACTOR
36 COMPRESSIBILITY FACTOR
37 LATENT HEAT OF VAPORIZATION (KJ/Kg)
38 RATIO OF SPECIFIC HEATS Cp / Cv
39 OPERATING VISCOSITY cP
40 VAPOUR GAS MASS FRACTION
41 BAROMETRIC PRESSURE
42 ENVIRONMENTAL FACTOR
43 VESSEL / WETTED
44 RATED CAPACITY
45 CALCULATED AREA inch2
46 SELECTED AREA inch2
47 ORIFICE DESIGNATION
48 MANUFACTURER
49 MODEL No.
50 NOTES:-
51 REFER NOTES SHEET
52
53
54
55
56
57
58
59
REFER BELOW OIL-100-EK-I-DS-0808
KIP-17039
- -
IMR
CKD DESCRIPTION
MV ISSUED FOR REVIEW
Hot Oil to Hot Oil Drain
DrumHot Oil to Hot Oil Drain Drum Bypass
Hot oil return to Hot Oil Drain Drum
(EK-MBD-3320)
Hot oil return to Hot Oil Drain Drum
(EK-MBD-3320) Bypass
barg MMSCMD kg/hr
kg/hr BLPD
17039-EK-P-DW-0203-11 17039-EK-P-DW-0203-11 17039-EK-P-DW-0203-14 17039-EK-P-DW-0203-14
FULL NOZZLE, FULL LIFT FULL NOZZLE, FULL LIFT FULL NOZZLE, FULL LIFT FULL NOZZLE, FULL LIFT
- - - -
2"-HM-41-3737-BC01-1N 2"-HM-41-3737A-BC01-1N 2"-HM-41-3671-BC01-1N 2"-HM-41-3671A-BC01-1N
CO
NN
EC
TIO
N 2" 2" 2" 2"
OUTLET
SAFETY RELIEF SAFETY RELIEF SAFETY RELIEF SAFETY RELIEF
CONVENTIONAL CONVENTIONAL CONVENTIONAL CONVENTIONAL
GE
NE
RA
L
41-PSV-3729A 41-PSV-3729B 41-PSV-0121A 41-PSV-0121B
300# 300# 300# 300#
RF RF RF RF
CLOSED BONNET CLOSED BONNET CLOSED BONNET CLOSED BONNET
SS 316 SS 316 SS 316 SS 316
MA
TE
RIA
L
CS, ASTM A105 CS, ASTM A105 CS, ASTM A105 CS, ASTM A105
CARBON STEEL CARBON STEEL CARBON STEEL CARBON STEEL
CS with Nickle Plate CS with Nickle Plate CS with Nickle Plate CS with Nickle Plate
N/A N/A N/A N/A
SS 316 SS 316 SS 316 SS 316
SS 316 SS 316 SS 316 SS 316
OP
TIO
NS
SCREWED SCREWED SCREWED SCREWED
N/A N/A N/A N/A
REQUIRED
THERMAL EXPANSION THERMAL EXPANSION THERMAL EXPANSION THERMAL EXPANSION
TBA TBA TBA TBA
REQUIRED REQUIRED REQUIRED
API RP 520 API RP 520 API RP 520 API RP 520
FL
UID
DA
TA
LIQUID LIQUID HOT OIL LIQUID
REQUIRED CAPACITY (VAPOUR/LIQUID)
12 12 12 12
* * * *
* * * *
* * * *
* BY VENDOR
* * * *
* * * *
TITLE ITEM/TAG No. DATA SHEET No.
PRESSURE SAFETY VALVE
PROJECT DESCRIPTION PROJECT No. SHEET REV
CREATION OF SURFACE PRODUCTION FACILITIES (GGS) AT EAST KHAGORIJAN 07 OF 07 A0
MPC CONTRACTOR PURCHASE ORDER No. REQUISITION NO. SPECIFICATION No.
TBA
CLIENT NAME REV No. BY DATE DATE APP. DATE
OIL INDIA LIMITED / TEC LIMITED A0 IMR 28-Nov-18 28-Nov-18 MSR/ VSR 28-Nov-18
CLIENT DOCUMENT No.
-
ORIGINATOR ORIG. DATE
19-Sep-18
UNITS:- Pressure psig kg/cm2 g kPag Flow : Gas MMscfd Sm
3/hr
Temp O C O F Liquid: m3/hr USgpm
1 TAG No.
2 SERVICE
3 VESSEL No.
4 LINE No.
5 P &ID NUMBER
6 FULL NOZZLE/SEMI-NOZZLE
7 SAFETY / RELIEF / SAFETY RELIEF
8 CONV., BELLOWS, PILOT OP.
9 BONNET TYPE
10 SIZE INLET OUTLET 1" 1"
11 FL. RATING INLET 300# 300#
12 FL. FACE INLET OUTLET RF RF
13 BODY
14 BONNET
15 NOZZLE, SEAT and DISC
16 RESILIENT SEAT SEAL
17 GUIDE AND RINGS
18 SPRING
19 BELLOWS
20 CAP: SCREWED or BOLTED
21 LEVER: OPEN or PACKED
22 TEST GAG
23 CODE
24 BASIS
25 VESSEL SIZE DIA X T/T
26 FLUID STATE HOT OIL HOT OIL
27
28 OPERATING S.G MOL. WEIGHT
29 OPER. PRESS SET PRESS
30 OPER. TEMP REL. TEMP AMB AMB
31 CONSTANT
32 BACK PRESSURE VARIABLE
33 TOTAL
34 % ALLOWABLE OVER PRESSURE
35 OVER PRESSURE FACTOR
36 COMPRESSIBILITY FACTOR
37 LATENT HEAT OF VAPORIZATION (KJ/Kg)
38 RATIO OF SPECIFIC HEATS Cp / Cv
39 OPERATING VISCOSITY cP
40 VAPOUR GAS MASS FRACTION
41 BAROMETRIC PRESSURE
42 ENVIRONMENTAL FACTOR
43 VESSEL / WETTED
44 RATED CAPACITY
45 CALCULATED AREA inch2
46 SELECTED AREA inch2
47 ORIFICE DESIGNATION
48 MANUFACTURER
49 MODEL No.
50 NOTES:-
51 REFER NOTES SHEET
52
53
54
55
56
57
58
59
REFER BELOW OIL-100-EK-I-DS-0808
KIP-17039
- -
IMR
CKD DESCRIPTION
MV ISSUED FOR REVIEW
Hot oil retrun to Hot Oil
Drain Tank
Hot oil retrun to Hot Oil Drain Tank
ByPass
barg MMSCMD kg/hr
kg/hr BLPD
17039-EK-P-DW-0206-04 17039-EK-P-DW-0206-04
FULL NOZZLE, FULL LIFT FULL NOZZLE, FULL LIFT
- -
2"-HM-41-6637-BC01-1N 2"-HM-41-6856-BC01-1N
CO
NN
EC
TIO
N 2" 2"
OUTLET
SAFETY RELIEF SAFETY RELIEF
CONVENTIONAL CONVENTIONAL
GE
NE
RA
L
41-PSV-6624A 41-PSV-6624B
300# 300#
RF RF
CLOSED BONNET CLOSED BONNET
SS 316 SS 316
MA
TE
RIA
L
CS, ASTM A105 CS, ASTM A105
CARBON STEEL CARBON STEEL
CS with Nickle Plate CS with Nickle Plate
N/A N/A
SS 316 SS 316
SS 316 SS 316
OP
TIO
NS
SCREWED SCREWED
N/A N/A
REQUIRED
THERMAL EXPANSION THERMAL EXPANSION
TBA TBA
REQUIRED
API RP 520 API RP 520
FL
UID
DA
TA
LIQUID LIQUID
REQUIRED CAPACITY (VAPOUR/LIQUID)
12 12
* *
* *
* *
* BY VENDOR
* *
* *
Datasheet NumberRev
Code
OIL-100-EK-I-DS-0814 A0 Sheet No.: 02 of 06
SHEET No.
1 COVER SHEET
2 INDEX SHEET
3 REVISION SHEET
4 NOTES SHEET
5 DS - SDV
6 SDV- LIST
CREATION OF SURFACE PRODUCTION
FACILITIES (GGS) AT EAST KHAGORIJAN
Revision Index
DATA SHEET FOR ACTUATED ON OFF VALVES
INDEX SHEET
TITLE
Datasheet NumberRev
Code
OIL-100-EK-I-DS-0814 A0 Sheet No: 03 of 06
REV No. LIST OF PAGES OF UPDATED / MODIFIED SECTIONS, IF ANY
A0 FIRST ISSUE
CREATION OF SURFACE PRODUCTION
FACILITIES (GGS) AT EAST KHAGORIJAN
Revision Index
DATA SHEET FOR ACTUATED ON OFF VALVES
REVISION RECORD SHEET
PURPOSE
ISSUED FOR REVIEW
Datasheet Number Rev Code
OIL-100-EK-I-DS-0814 A0 Sheet No: 04 of 06
3. Orientation of the actuator will be along the pipe axis.
4. Valve body thickness shall be as per ASME B16.34 plus C.A.
5. All instrument painting shall be as per Painting Specification
6. All fastners including stud-bolts and nuts material shall be ASTM A193 Gr. B7/B7M & Heavy hex nuts shall be ASTM A194 Gr. 2H/2HM
with Zinc coated ( hot dipped ) according to ASME B16.5.
7. Air Filter Regulators shall be provided with manual drainage facility, an integral pressure gauge calibrated in barg. Body material shall be
SS316 and filter element is 5 micron size.
8. Flange finish shall be in accordance with ASNI B16.5, for Raised Face (RF) flanges and shall be smooth finish to 125-250 AARH
9. All actuator valves accessories like solenoid valve, filter regulator, etc. shall be mounted on the valve actuator and tubed by vendor
using bright annealed SS316 (ASTM A269) tubing, tube size shall be 10mm O.D. X 1mm W.T.minimum. All tube fittings shall be imperial
and 316 SS double compression type
10. All components such as air filter regulators, limit switches, solenoid valve shall be factory mounted, tubed / wired in completely assemble
condition and bolted to a SS 316 mounting plate which is fixed to a support with SS316 bolts.
11. Spare cable entry shall be plugged with SS316 Ex'd' certified plug.
12. Actuator to be sized for maximum pressure drop equal to the valve design pressure with minimum instrument air supply pressure (5.5 barg).
13. Actuator shall be sized for 1.5 times the required seating torque of the valve when the valve is closed against maximum differential pressure.
14. Actuator shall be supplied with a pressure relief valve to protect the actuator from overpressure if the actuator design pressure is lower
than the maximum instrument air pressure indicated in the datasheet.
17. The valve stem and linkage mechanism shall be consistance with actuator torque characteristic. The maximum torque developed by actuator shall not exceed that
which can be safely sustained by the valve stem. Valve stem or shaft and its trim shall be of blowout proof design and be capable of withstanding the maximum
actuator torque/thrust.
18. The mounting of the actuator shall be suitable for supporting the actuator without external attachments and shall be capable of
resisting actuator's maximum torque force.
19. Limit switches shall be supplied with hermetically sealed NAMUR Inductive proximity switches.
All valves shall be provided with an integral open/close mechanical position indicator(yellow/black) which shall be clearly visible from all angles.
20. Solenoid valve shall have SS 316 body, trim with viton or equal resilient seat (to be anti-explosion decompression type) and surge
suppression diode integrally mounted in enclosure. Open port of solenoid valve shall fitted with a bug screen.
All valves shall be provided with an integral open/close mechanical position indicator(yellow/black) which shall be clearly visible from all angles.
20. Solenoid valve shall have SS 316 body, trim with viton or equal resilient seat (to be anti-explosion decompression type) and surge
suppression diode integrally mounted in enclosure. Open port of solenoid valve shall fitted with a bug screen.
21. Flying leads termination cable are not acceptable for solenoid valve and limit switches.
23. Hydrotest pressure and seat test pressure shall be as per ASME code requirement.
24. Vendor shall verify all sizing calculations to confirm datasheets, selection and shall conform with his quotation. Vendor is responsible to confirm that the
specified pneumatic ON/OFF valve will operate satisfactorily for the given service conditions.
25. Stroke time should not exceed 3 times body size (inches) in seconds or be less than body size (inches) in seconds. Maximum stroke time of any valve is 30 sec.
26. All electrical components shall be suitable for hazardous area with ingress protection IP 65 (min).
27. All Actuated ON/OFF Valve assemblies (valve, actuator, solenoid valve, air pressure regulator and valve position switches) shall be SIL- 2 certified.
28. The Valves above 25Kgs shall be provided with eye bolts as per the requirements for site handling.
29. Valve actuators assemblies shall be equipped with adjustable controls to regulate their stroking speed.
31. All ball valves over 2” shall incorporate anti-static feature ensuring electrical continuity between ball, stem and body.
32. Actuator colour coding shall be fail open valve-Green and fail close valve-Red.
33. All Casting & Welding shall be 100% Radio graphed.
the required stroke-speed, fail safe action.
36. Other auxiliary devices such as air lock relay, pilot relay, booster relay volume tank etc. shall be provided as parts of the actuating system in order to achieve
35. Stem for ball valves shall be anti-blowout type and for floating ball valves, seat spring shall be provided.
CREATION OF SURFACE PRODUCTION FACILITIES (GGS)
AT EAST KHAGORIJAN
Revision Index
DATA SHEET FOR ACTUATED ON OFF VALVES
Notes:
1. Documentation required :- Calibration Certificate , Ingress Protection Certificate, Material Certificates to 3.1 as per EN 10204, Hydro test ,
operating & Maintenance Instructions & Spare Parts List.
2. All instruments to be supplied with a SS 316 Name plate with Tag no. permanently inscribed. Tags shall be Permanently secured.
TITLE ITEM/TAG No. DATA SHEET No.
DATA SHEET FOR ACTUATED ON OFF VALVES
PROJECT DESCRIPTION VME PROJECT No SPECIFICATION No.
CREATION OF SURFACE PRODUCTION FACILITIES (GGS) AT EAST KHAGORIJAN
MPC CONTRACTOR SUPPLIER DOC.NO REQUISITION No. SHEET REV
TBA A0
CLIENT NAME REV No. BY DATE CKD DATE APP. DATE
OIL INDIA LIMITED A0 IMR 28-Nov-18 MV 28-Nov-18 MSR/ VSR 28-Nov-18
CLIENT DOC .No
ORIGINATOR ORIG. DATE
14-Sep-18
UNITS:- Pressure barg kg/cm2 g kPa g psi g Flow : Gas MMscfd SCMH Sm3/hr kg/hr
Temp 0 C 0 F Liquid: m3/hr kg./hr bpd USgpm
1 55
2 FLUID REFER ANNEXURE-1 56 TYPE
3 LINE No. REFER ANNEXURE-1 57 MFR *
4 P&ID No. REFER ANNEXURE-1 58 SIZE REFER ANNEXURE-1
5 LINE SIZE AND SCHEDULE REFER ANNEXURE-1 59 SPRING ACTION OPEN / CLOSE REFER ANNEXURE-1
6 CORROSION ALLOWANCE REFER ANNEXURE-1 60 MAX ALLOWABLE PRESSURE *
7 61 MIN REQUIRED PRESSURE *
8 FLOW RATE 62 AIR FLUID PRESSURE -
9 OP. PRESSURE / OP. TEMP. ( barg/ OC) 63 AVAILABLE AIR PR. MIN / NOR / MAX. 6 / 8 / 10 barg
10 SPEC. GRAV. 64 BREAK TORQUE RUN TORQUE
11 LIQ. DENSITY AT OP. PR & TEMP (kg/m3) 65 TIME OPEN CLOSE
12 VISCOSITY cP 66 ACTUATOR COLOUR YES
13 DESIGN TEMPERATURE (OC) REFER ANNEXURE-1 67 ACT ORIENTATION PARALLEL TO FLOW
14 DESIGN PRESSURE (barg) REFER ANNEXURE-1 68 HANDWHEEL TYPE -
15 Dp SHUT-OFF PRESSURE (bar) REFER ANNEXURE-1 69 AIR FAILURE VALVE SET AT -
16 70 AIR CONSUMPTION *
17 DESIGN CODE API 6D 71 POSITION INDICATION (LOCAL) YES
18 FIRE-SAFE API-6FA /API 607/ BS 6755 72 POSITION INDICATION (REMOTE) YES - SEE LINES 75~83
19 SEAT LEAKAGE CLASS ANSI FCI 70.2, Class VI or Equal 73 ACCUMULATOR AS REQUIRED BASED ON VALVE TYPE
20 74 PNEUMATIC CONNECTION 1/4" NPTF
21 TYPE BALL VALVE 75
22 SIZE / RATING (in) NB REFER ANNEXURE-1 76 TAG No. REFER ANNEXURE-1
23 FLANGE FACE FINISH REFER ANNEXURE-1 77 TYPE
24 CONFIGURATION REFER ANNEXURE-1 78 MFR & MODEL *
25 MATERIAL BODY 79 CONTACTS / RATING 24VDC @ 2 A
26 BALL 80 ACTUATION POINTS OPEN / CLOSE
27 STEM 81 ENCLOSURE
28 SEAT RING 82 ENCLOSURE MATERIAL SS316
29 SEAT INSERT 83 CABLE ENTRY ISO M20 X 1.5 mm (2 nos)
30 FIRE SEAL 84
31 PACKING 85 TAG No.
32 BOLT / NUT 86 TYPE
33 OTHER SPECIFICATIONS - 87 AIR SUPPLY SIGNAL
34 RUN TORQUE BREAK TORQUE 88 MFR & MODEL
35 BODY TEST PRESSURE 1.5 TIMES OF THE DESIGN PRESSURE 89 MANUAL RESET
36 SEAT TEST PRESSURE 1.1 TIMES OF THE DESIGN PRESSURE 90 MATERIAL BODY/HOUSING
37 LIMIT STOPS NO 91 PILOT ACTION
38 MFR * 92 PILOT CONNECTION
39 MODEL * 93
40 94 MFR & MODEL *
41 a) PNEUMATIC TUBE SIZE ¼” O.D. X 0.035” W.T 95 MATERIAL ENCLOSURE 316 SS IP 65
42 b) ALL CABLE ENTRIES ISO M20 X 1.5 mm 96 INTEGRAL PRESSURE GAUGE YES
43 c) ALL TUBES AND FITTINGS MATERIAL 316 SS, SEE LINES 50 97 DESIGN PRESSURE SET PRESSURE 10 barg *
44 d) AREA CLASSIFICATION ZONE - 2, Gr IIA & IIB, T3 98 PORT SIZE 1/4" NPTF
45 SPEED CONTROLLER LOCAL INDICATOR. 99
46 100 TAG No. REFER ANNEXURE-1
47 101 QTY REFER ANNEXURE-1
48 102 TYPE 3 / 2 -WAY, UNIVERSAL
49 LIMIT SWITCHES SHALL BE PROVIDED WITH INTEGRAL TERMINAL BLOCK 103 POWER SUPPLY 24 VDC, < 6 WATT, H COIL INSULATION
50 ALL TUBE FITTINGS SHALL BE IMPERIAL AND DOUBLE 104 ENCLOSURE TYPE Ex'd' / IP 65
51 FERRULE COMPRESSION TYPE. 105 MFR & MODEL *
52 VENT/EXHAUST CONNECTIONS TO BE PROVIDED WITH BUG SCREEN 106 MANUAL RESET YES
53 107 MATERIAL BODY/HOUSING 316 SS
54 108 PORT SIZE CABLE ENTRY 1/4'' NPTF ISO 1/2" NPT(F) X 1.5 mm
NOTES:- * BY VENDOR
Refer Notes sheet
ZONE - 2, Gr IIA & IIB, T3
ISSUED FOR REVIEW
ACTUATOR (PNEUMATIC)
ANNEXURE-2
FILTER REGULATOR (NOTE-8)
ADDITIONAL INFORMATION
YES YES SOLENOID VALVE (NOTE-20,21)
REFER ANNEXURE-1 VALVE CODE
REFER ANNEXURE-1 VALVE CODE
REFER ANNEXURE-1 VALVE CODE PNEUMATIC PILOT VALVE
REFER ANNEXURE-1 VALVE CODE
REFER ANNEXURE-1
REFER ANNEXURE-1 VALVE CODE Ex'ia' / IP 65
NA REFER ANNEXURE-3
NA REFER ANNEXURE-3
NA
APPLICABLE CODES AND SPECIFICATIONS
VALVE (NOTE-30,31,32)
SWITCHES
INDUCTIVE PROXIMITY SWITCH WITH NAMUR
REFER ANNEXURE-1 VALVE CODE
REFER ANNEXURE-1 VALVE CODE
NA
DESCRIPTION
-
IMR
GENERAL
QUARTER TURN, SPRING RETURN DOUBLE ACTING
PISTON
PROCESS CONDITIONS
NA
REFER ANNEXURE-1 OIL-100-EK-I-DS-0814
KIP-17039 -
- - 05 of 06
A0
S.NO TAG NO P&ID No. LINE N0. FLUID VALVE SIZE (in) CONFIGURATION
LINE SIZE (in) / SCH
or WALL THK. / C.A
(mm)
RATING
FLANGE
FINISH
(AARH)
VALVE CODE
DESIGN
PRESSURE
(kg/cm2g)
DESIGN
TEMP. (OC)
ΔP SHUTOFF
PRESSURE (bar)FAIL POSITION LIMIT SWITCH TAG NO.
SOLENOID
VALVE TAG NO.
SOLENOID
VALVE QTYACTUATOR SIZE
NACE
REQUIREMENTBOLT / NUT MATERIAL VALVE MODEL NO
LIMIT SWITCH /
SOLENOID VALVE
MODEL NO
ACTUATOR
MODEL
VALVE
SCHEMATICS
NO.
REV
1 41-SDV-3750 17039-EK-P-DW-0202-13 2"-HM-41-3762-BC01-HC HOT OIL 2" GATE VALVE 2"/ XS/ 3 300# RF 125 - 250 GTBC01R FOW+0.07 108 FOW+0.07 FAIL CLOSE 41-ZSL/ZSH-3750 41-SXV-3750 1 * Not RequiredASTM A 193 Gr. B7 / ASTM A
194 Gr. 2H (ASME B16.5)* * * * A0
2 41-SDV-3727 17039-EK-P-DW-0203-10 4"-HM-41-3725-BC01-1N HOT OIL 3" GATE VALVE 4"/ STD/ 3 300# RF 125 - 250 GTBC01R 12/FV 250 12/FV FAIL CLOSE 41-ZSL/ZSH-3727 41-SXV-3727 1 * Not RequiredASTM A 193 Gr. B7 / ASTM A
194 Gr. 2H (ASME B16.5)* * * * A0
3 41-SDV-3730 17039-EK-P-DW-0203-11 3"-HM-41-3727-BC01-1N HOT OIL 3" GATE VALVE 3"/ STD/ 3 300# RF 125 - 250 GTBC01R FOW+0.07 90 FOW+0.07 FAIL CLOSE 41-ZSL/ZSH-3730 41-SXV-3730 1 * Not RequiredASTM A 193 Gr. B7 / ASTM A
194 Gr. 2H (ASME B16.5)* * * * A0
4 41-SDV-3668 17039-EK-P-DW-0203-14 3"-HM-41-8611-BC01-1N HOT OIL 3" GATE VALVE 3"/ STD/ 3 300# RF 125 - 250 GTBC01R FOW+0.07 90 FOW+0.07 FAIL CLOSE 41-ZSL/ZSH-3668 41-SXV-3668 1 * Not RequiredASTM A 193 Gr. B7 / ASTM A
194 Gr. 2H (ASME B16.5)* * * * A0
5 66-SDV-6643A 17039-EK-P-DW-0206-02 4"-TW-66-6604-AC01CLARIFIED/
TREATED WATER4" GATE VALVE 4"/ STD/ 3 150# RF 125 - 250 GTAC01R FOW+0.07 80 FOW+0.07 FAIL CLOSE 66-ZSL/ZSH-6643A 66-SXV-6643A 1 * Not Required
ASTM A 193 Gr. B7 / ASTM A
194 Gr. 2H (ASME B16.5)* * * * A0
6 66-SDV-6643B 17039-EK-P-DW-0206-02 4"-TW-66-6604-AC01CLARIFIED/
TREATED WATER4" GATE VALVE 4"/ STD/ 3 150# RF 125 - 250 GTAC01R FOW+0.07 80 FOW+0.07 FAIL CLOSE 66-ZSL/ZSH-6643B 66-SXV-6643B 1 * Not Required
ASTM A 193 Gr. B7 / ASTM A
194 Gr. 2H (ASME B16.5)* * * * A0
7 41-SDV-6623 17039-EK-P-DW-0206-04 2"-HM-41-3674-BC01-1N HOT OIL 2" GATE VALVE 2"/ XS/ 3 300# RF 125 - 250 GTBC01R 15 80 15 FAIL CLOSE 41-ZSL/ZSH-6623 41-SXV-6623 1 * Not RequiredASTM A 193 Gr. B7 / ASTM A
194 Gr. 2H (ASME B16.5)* * * * A0
8 66-SDV-6640 17039-EK-P-DW-0206-06 4"-WE-66-6605-AC01OFF-SPEC
EFFLUENT WATER4" GATE VALVE 4"/ STD/ 3 150# RF 125 - 250 GTAC01R FOW+0.07 80 FOW+0.07 FAIL CLOSE 66-ZSL/ZSH-6640 66-SXV-6640 1 * Not Required
ASTM A 193 Gr. B7 / ASTM A
194 Gr. 2H (ASME B16.5)* * * * A0
9 53-SDV-5516 17039-EK-P-DW-0212-01 4"-WP-53-5504-AC01 WATER 4" FULL BORE/ FLOATING BALL 4"/ STD/ 3 150# RF 125 - 250 BFAC01R 7/FV 80 7/FV FAIL CLOSE 53-ZSL/ZSH-5516 53-SXV-5516 1 * Not RequiredASTM A 193 Gr. B7 / ASTM A
194 Gr. 2H (ASME B16.5)* * * * A0
10 53-SDV-5636 17039-EK-P-DW-0212-01 4"-WP-53-5508B-AC01 WATER 4" FULL BORE/ FLOATING BALL 4"/ STD/ 3 150# RF 125 - 250 BFAC01R 7/FV 80 7/FV FAIL CLOSE 53-ZSL/ZSH-5636 53-SXV-5636 1 * Not RequiredASTM A 193 Gr. B7 / ASTM A
194 Gr. 2H (ASME B16.5)* * * * A0
11 53-SDV-5607 17039-EK-P-DW-0212-04 3"-WD-53-5534-AS20FRESH POTABLE
WATER3" FULL BORE/ FLOATING BALL 3"/ STD/ 3 150# RF 125 - 250 BFAS20R FOW+0.07 80 FOW+0.07 FAIL CLOSE 53-ZSL/ZSH-5607 53-SXV-5607 1 * Not Required
ASTM A 193 Gr. B7 / ASTM A
194 Gr. 2H (ASME B16.5)* * * * A0
12 53-SDV-5630 17039-EK-P-DW-0212-04 4"-WD-53-5611A-AS20FRESH POTABLE
WATER4" FULL BORE/ FLOATING BALL 4"/ STD/ 3 150# RF 125 - 250 BFAS20R FOW+0.07 80 FOW+0.07 FAIL CLOSE 53-ZSL/ZSH-5630 53-SXV-5630 1 * Not Required
ASTM A 193 Gr. B7 / ASTM A
194 Gr. 2H (ASME B16.5)* * * * A0
13 71-SDV-7101 17039-EK-P-DW-0217-01 4"-WP-71-7101-AC01 WATER 4" GATE VALVE 4"/ STD/ 3 150# RF 125 - 250 GTAC01R FOW 80 FOW FAIL CLOSE 71-ZSL/ZSH-7101 71-SXV-7101 1 * Not RequiredASTM A 193 Gr. B7 / ASTM A
194 Gr. 2H (ASME B16.5)* * * * A0
14 56-XV-4010 17039-EK-P-DW-0207-01 4"-OW-56-5410-AC01 OILY WATER 4" GATE VALVE 4"/ STD/ 3 150# RF 125 - 250 GTAC01R 11/FV 100 11/FV FAIL CLOSE 56-ZSL/ZSH-4010 56-SXV-4010 1 * Not RequiredASTM A 193 Gr. B7 / ASTM A
194 Gr. 2H (ASME B16.5)* * * * A0
15 56-XV-4009 17039-EK-P-DW-0207-01 4"-OW-56-4019-AC01 OILY WATER 4" GATE VALVE 4"/ STD/ 3 150# RF 125 - 250 GTAC01R 11/FV 100 11/FV FAIL CLOSE 56-ZSL/ZSH-4009 56-SXV-4009 1 * Not RequiredASTM A 193 Gr. B7 / ASTM A
194 Gr. 2H (ASME B16.5)* * * * A0
16 71-XV-8008 17039-EK-P-DW-0217-01 2"-WP-53-4639A-AC01 WATER 2" GATE VALVE 2"/ STD/ 3 150# RF 125 - 250 GTAC01R FOW 80 FOW FAIL CLOSE 71-ZSL/ZSH-8008 71-SXV-8008 1 * Not RequiredASTM A 193 Gr. B7 / ASTM A
194 Gr. 2H (ASME B16.5)* * * * A0
17 71-XV-8009 17039-EK-P-DW-0217-01 2"-WP-53-4639B-AC01 WATER 2" GATE VALVE 2"/ STD/ 3 150# RF 125 - 250 GTAC01R FOW 80 FOW FAIL CLOSE 71-ZSL/ZSH-8009 71-SXV-8009 1 * Not RequiredASTM A 193 Gr. B7 / ASTM A
194 Gr. 2H (ASME B16.5)* * * * A0
OIL-100-EK-I-DS-0814 Sheet No.: 06 of 06
Document Title
DATA SHEET FOR ACTUATED ON OFF VALVES
CREATION OF SURFACE PRODUCTION FACILITIES (GGS) AT EAST KHAGORIJAN Document No. Rev.
* To be provided by vendor
REMARKS
Datasheet NumberRev
Code
OIL-100-EK-I-DS-0815 A0 Sheet No.: 02 of 06
SHEET No.
1 COVER SHEET
2 INDEX SHEET
3 REVISION SHEET
4 NOTES SHEET
5 DATA SHEET - MOTOR OPERATED VALVE
6 MOTOR OPERATED VALVE- LIST
INDEX SHEET
TITLE
CREATION OF SURFACE PRODUCTION
FACILITIES (GCS) AT EAST KHAGORIJAN
Revision Index
DATA SHEET FOR MOTOR OPERATED VALVES
Datasheet NumberRev
Code
OIL-100-EK-I-DS-0815 A0 Sheet No: 03 of 06
REV No. LIST OF PAGES OF UPDATED / MODIFIED SECTIONS, IF ANY
A0 FIRST ISSUE
REVISION RECORD SHEET
PURPOSE
ISSUED FOR REVIEW
CREATION OF SURFACE PRODUCTION
FACILITIES (GCS) AT EAST KHAGORIJAN
Revision Index
DATA SHEET FOR MOTOR OPERATED VALVES
Datasheet Number Rev Code
OIL-100-EK-I-DS-0815 A0Sheet No: 04 of 06
15. Spare cable entry shall be plugged with Ex'd' certified plug. All cable glands shall be Nickel-plated Brass.
16. The Valves above 25Kgs shall be provided with eye bolts as per requirement for site handling.
17. All MOV Shall be as per API 6D Ball Valve, split body and Floating Ball fro size upto 4" and Trunnion Mounted Ball for size 6" and above.
18. Vendor shall propose the type of cable between Motor Operated Valve to Local control panel and motor control station to MOV.
19. The switches shall be provided with requisite number of potential-free contacts for valve actuator operation and for indication on remote panels.
20. Cable details for 2-wire communication and cable between LCP to MOV shall be provided by VENDOR.
21. 2-Wire Digital Communication With hardwiring feature shall be provided.
22. The motor shall be designed for valve actuator service with high starting torque and shall be suitable for direct on-line starting.
23. The motor shall be provided with thermostat(s)/ thermister(s)/ embedded in the hot spots of motor winding for protecting the motor.
24. The MOV Actuators shall be provided with ‘K-Mass’ type or equivalent fireproofing and the fireproofing shall be rated be rated for 30 minutes.
25. MOV Push button shall be outside the Dyke Area.
REFERENCE DOCUMENTS:
17039-EK-I-DB-8001_Functional specification for package instruments_Rev C
3. MOV shall be designed to be immune to radio frequency & electromagnetic interference with field strength of 15 volts/meter or
CREATION OF SURFACE PRODUCTION FACILITIES (GCS)
AT EAST KHAGORIJAN
Revision Index
DATA SHEET FOR MOTOR OPERATED VALVES
Notes:
1. Documentation required :- Calibration Certificate, Ingress Protection Certificate, Material Certificates to 3.1 as per EN 10204, Hydro test ,
operating & Maintenance Instructions & Spare Parts List.
2. All instruments to be supplied with a SS 316 Name plate with Tag no. permanently inscribed. Tags shall be Permanently secured.
5. The motor shall be able to operate the actuator at 75% of rated voltage.
less over frequency range of 50 hz to 450 mhz.
4. Motor & control system shall be provided with lightning protection circuits (galvanic isolation via transformer) and shall be
designed and manufactured to operate in 100% or above RH environment.
8. Certification for use in Hazardous Area:
6. MOV Actuator operating with AC power supply shall be provided with Phase instantaneous reversal protection.
7. The actuator shall be provided with maximum three adequately sized cable entries viz, one for power cable and two for control cables.
(a) VENDOR / SUPPLIER to submit approval certification from CMRI for items manufactured in India.
(b) Certificates from statutory authorities like FM, CSA, UL, CENELEC & ATEX, etc. for items
9. Manual override and handwheel arrangement shall be provided to manually open and close the valve.
10. The MOV actuator shall have an integral control unit, motor starter, control gear, spring-return open/ close push button.
11. Local status indications shall be provided for MOV Open/Close position. Additionally, contacts shall be provided for remote status indication of MOV
Open/Close position.
12. Painting shall be as per Protective Coating specification for Onshore Structures and Facilities.
13. Cable glands shall be double compression explosion proof type made of nickel plated brass, certified for area classification
ZONE 1, GAS GROUP-IIA / IIB, TEMP.CL T3 in case of hazard area, and have an ingress protection of IP65.
14. Local Control Panel is required for Open & close operation & OFF selector switch on MOV actuator. Pull & Push type is required in LCP for open / close.
26. MOV shall have Open & Close Remote operation from Control room and at Field just outside the Dyke.
17039-CM-M-SP-2001_Piping material specification_Rev D
17039-CM-M-SP-2002_Valve material specificatio_Rev D
TITLE ITEM/TAG No. DATA SHEET No.
DATA SHEET FOR MOTOR OPERATED VALVES
PROJECT DESCRIPTION PROJECT NO SHEET REV
05 OF 06 A0
CONTRACTOR CLIENT CONTRACT No. REQUISITION No. SPECIFICATION No.
CLIENT NAME REV No. BY DATE CKD DATE APP. DATE
A VS 28-Nov-18 PG 28-Nov-18 MV 28-Nov-18 ISSUED FOR REVIEW
CLIENT'S REF
-
ORIGINATOR ORIG. DATE
28-Nov-18
UNITS:- Pressure barg kg/cm2 g Kg/cm2 kPa g psi g Flow : Gas MMscfd SCMH Sm
3/hr kg/hr
Temp 0
C 0 F Liquid: m
3/hr kg./hr KLPD USgpm
1 63
2 FLUID REFER MOV LIST 64
3 SERVICE REFER MOV LIST 65
4 LINE No / P&ID No REFER MOV LIST 66
5 LINE SIZE AND SCHEDULE REFER MOV LIST 67
6 CORROSION ALLOWANCE REFER MOV LIST 68
7 69
8 OP. PRESSURE (kg/cm2g) REFER MOV LIST 70
9 OP. TEMP. ( OC) REFER MOV LIST 71
10 SPEC. GRAV. REFER MOV LIST 72
11 LIQ. DENSITY AT OP. PR & TEMP (kg/m3) REFER MOV LIST 73
12 VISCOSITY (cP) REFER MOV LIST 74
13 DESIGN TEMPERATURE (OC) REFER MOV LIST 75
14 DESIGN PRESSURE (kg/cm2g) REFER MOV LIST 76
15 DP SHUT-OFF PRESSURE (kg/cm2g) REFER MOV LIST 77
16 78
17 79
18 80
19 81
20 82
21 TYPE BALL TYPE, FIRE SAFE & NON RUBBING 83
22 SIZE / RATING (in) REFER MOV LIST 84
23 ON-OFF 85 OPENING / CLOSING TIME
24 VALVE DUTY FULLY OPEN & FULL CLOSE 86 TORQUE / LOAD CURRENT *
25 FLANGE FACE FINISH 125 to 250 in AARH 87
26 MATERIAL : BODY ASTM A216 Gr.WCB 88
27 BONNET ASTM A216 Gr.WCB 89
28 BALL & STEM F316 SS (or) ENP A105 CS & A182 F316 90
29 SEAT / BODY SEAT RING PEEK 91
30 ANSI / FCI LEAKAGE CLASS CLASS IV 92
31 STEM PACKING / GASKET 93
32 BOLT & NUT 94
33 HAND WHEEL MALLEABLE IRON / DUCTILE IRON / CAST STEEL / FAB. ST. 95
34 PORT TYPE FULL PORT 96
35 SPEED OF OPERATION (DESIGN / ACTUAL) * 97
36 BODY TEST PRESSURE 1.5 TIMES OF THE DESIGN PRESSURE 98
37 SEAT TEST PRESSURE 1.1 TIMES OF THE DESIGN PRESSURE 99 INTERNAL VOLT FREE CONTACT
38 TORQUE LIMIT STOPS YES 100
39 MANUFACTURER 101
40 MODEL 102
41 QUANTITY 103
42 104
43 105
44 a) ALL CABLE ENTRIES 106
45 b) AREA CLASSIFICATION 107
46 SPEED CONTROLLER / LOCAL INDICATOR. NA REQUIRED 108
47 109
48 OPERATION - REFER LINES 51 ~ 123 110
49 111
50 112
51 MANUAL OPERATOR YES 113
52 HAND WHEEL TURNS / RATIO * 114
53 LOCKED DECLUTCH LEVER YES 115
54 INPUT SIGNAL YES 116
55 OUTPUT SIGNAL YES 117
56 VALVE POSITION TRANSMITTER YES 118
57 FIRE SAFE REQUIREMENTS YES 119
58 FAIL SAFE CONDITION REFER MOV LIST 120
59 121
60 122
61 123
62 124
63 NOTES:- * - TO BE CONFIRMED BY VENDOR
64 Refer Notes sheet
APPLICABLE CODES AND SPECIFICATION
DESIGN CODE API 6D , API 598
CONTROL SUPPLYPROCESS CONDITIONS
MOTOR THERMAL PROTECTION CLASS
FAILURE ACTION OPEN / CLOSE
HANDWHEEL
SIL CERTIFICATION
CONTROL FEATURES
REFER MOV LISTLOCAL CONTROL PANEL
EMERGENCY PUSH BUTTON YES
SELECTOR SWITCH YES
SELECTOR SWITCH INDICATION OPEN / CLOSE / REMOTE
REMOTE AND LOCAL CONTROL
FAULT RELAY
INTERPOSING RELAY
VALVE POSITION INDICATION
MOTOR TEMPERATURE ALARM
LIMIT SWITCH & TORQUE SWITCH
REFER MOV LIST OIL-100-EK-I-DS-0815
CREATION OF SURFACE PRODUCTION FACILITIES (GCS) AT EAST KHAGORIJAN
GENERAL
17039-EK-I-DB-8001
OIL INDIA LIMITED
VS
ACTUATOR (ELECTRIC)
ELECTRICALLY OPERATED - MULTI TURN,
NON INTRUSIVE & SMARTTYPE
TBA
KIP-17039
- -
DESCRIPTION
FIRE SAFE
*
DUTY RATING
NOT REQUIRED
SEALING TORQUE *
BREAK AWAY TORQUE *
TAG No.
TYPE
GEAR TYPE / GEAR RATIO
VALVE
MECHANICAL BRAKE
API 607 , API 6FA
REFER MOV LIST
*
*
CLOCKWISE TO OPEN
*
TOP
STAY PUT
*
< 60 SEC
-
ELECTRIC FAILURE
SQUIRREL CAGE INDUCTION
REFER MOV LIST
TORQUE RANGE
MAX. THRUST
ROTATION
SPEED
MOUNTING POSITION
ENCLOSURE
RUNNING TORQUE
60 STARTS / HOUR
REVERSING CONTACTOR YES
CONTROL TRANSFORMER YES
OVERLOAD PROTECTION YES
REFER MOV LIST
MOTOR TYPE
MFR & MODEL
SIZE / RATING OF MOTOR
MOTOR STARTER INTEGRAL
24 VDC
CLASS F
CLASS B
REFER MOV LIST
REQUIRED
MOTOR INSULATION
EXPANDED GRAPHITE + GRAPHOIL FILLER
CHARACTERISTIC / CONTRL RANGE
HOT STANDBY MASTER CONTROL
STATION IN CONTROL ROOMREQUIRED
ACTUATOR WIRING FEATURE REFER MOV LIST
S2-15 min.
INTERFACING WITH BPCS REFER MOV LIST
MFR & MODEL REFER MOV LIST
CONTACTS / RATING 1 A at 2V DC
ACTUATION POINTS OPEN / CLOSE
ENCLOSURE
REFER MOV LIST
REFER MOV LIST
ADDITIONAL INFORMATION
1/2" NPT (M) DOUBLE COMPRESSION / NICKEL PLATED BRASS
OPTIONS
CABLE ENTRY / MATERIAL1/2" NPT (M) DOUBLE COMPRESSION /
NICKEL PLATED BRASS
415 VAC ±10% / 50HZ ±3% / 3 PHASE
Ex'd' / IP 65 INBUILT WITH ACTUATOR
ENCLOSURE MATERIAL DIE-CAST ALUMINUM
DUTY RATING
VOLT / FREQ / PH.
YES
MECHANICAL DISPLAY & LCD DISPLAY ON
MOV
YES
NO
YES
-
YES (OPEN / CLOSE)
REFER MOV LIST
CONSTRUCTION FLAME PROOF
FULL CURRENT (AMPS) *
STARTING CURRENT *
NUMBER OF STARTS / HOUR
SWITCHES
Ex'd'
SYSTEM EARTHING SOILDLY EARTHED
CONTACTORS / SELECTOR SWITCH &
PUSH BUTTON MAKE*
ASTM A 193 Gr. B7 / ASME B16.5 &
ASTM A 194 Gr. 2H / ASME B16.5
OTHER ACCESSORIES COMPLETELY ASSEMBLED FOR THE CORRECT AND SATISFACTORY
OPERATION OF MOV
S.NO TAG NO. SERVICE DESCRIPTION FLUID / PHASE INSTRUMENT TYPE AREA CLASSIFICATION P&ID NOLINE NO /
EQUIPMENT NO.
LINE SIZE (in)
/ SCH / C.A
(mm)
PIPE LINE
INSULATION
STEAM
TRACING
PRESSURE
RATING
FAIL
ACTION
LOCAL
CONTROL
PANEL WITH
PUSH
BUTTON
INTERFACING
WITH BPCS
OP.
PRESSURE
(kg/cm2g)
OP.
TEMP.
( OC)
DESIGN
PRESSURE
IN kg/cm2
DESIGN
TEMPERATURE
IN 0C
SPECIFIC
GRAVITY
LIQ. DENSITY
AT OP. PR &
TEMP (kg/m3)
VISCOSITY
(cP)
DP SHUT-
OFF
PRESSURE
(kg/cm2g)
VALVE
MAKE
&
MODEL
NO
LIMIT
SWITCH
MAKE
&
MODEL NO
ACTUATOR
(ELECTRIC)
MAKE
&
MODEL NO
SIZE /
RATING OF
MOTOR
REMARKS
1 20-MOV-0303 Well Fluid from Test Separator Well Fluid/ LiquidMOTOR OPERATED
VALVE
ZONE 1, GAS GROUP-IIA/
IIB, TEMP.CL T3
17039-EK-P-DW-0202-
132"-PT-20-0205-FC01 2"/ XXS/ 3mm NO YES 2500# RTJ
FAIL
LAST
NOT
REQUIREDYES 5-90 27-50 100/FV 100 0.87 870 10.7 100 * * * */ 3-Phase
2 20-MOV-3750Crude Oil from Test Tank To Test Tank
Transformer Pump Crude Oil/ Liquid
MOTOR OPERATED
VALVE
ZONE 1, GAS GROUP-IIA/
IIB, TEMP.CL T3
17039-EK-P-DW-0202-
134"-PL-44-1380-AC01 4"/ STD/ 3mm NO NO 150# RF
FAIL
LAST
NOT
REQUIREDYES ATM 27-50 FOL+0.07 90 0.87 870 10.7 FOL+0.07 * * * */ 3-Phase
3 20-MOV-0979A Crude to Treated Crude Storage Tank Crude Oil/ LiquidMOTOR OPERATED
VALVE
ZONE 1, GAS GROUP-IIA/
IIB, TEMP.CL T3
17039-EK-P-DW-0203-
10
4"-PL-20-0811A-
AC014"/ STD/ 3mm NO NO 150# RF
FAIL
LAST
NOT
REQUIREDYES 10 55 15 90 0.87 870 10.7 15 * * * */ 3-Phase
4 20-MOV-0980 Treated Crude to Crude Charge Pump Crude/ LiquidMOTOR OPERATED
VALVE
ZONE 1, GAS GROUP-IIA/
IIB, TEMP.CL T3
17039-EK-P-DW-0203-
106"-PL-20-0822-AC01 6"/ STD/ 3mm NO YES 150# RF
FAIL
LAST
NOT
REQUIREDYES ATM 55 FOL+0.07 90 0.87 870 10.7 FOL+0.07 * * * */ 3-Phase
5 20-MOV-0978A Crude to Treated Crude Storage Tank Crude/ LiquidMOTOR OPERATED
VALVE
ZONE 1, GAS GROUP-IIA/
IIB, TEMP.CL T3
17039-EK-P-DW-0203-
104"-PL-20-0816-AC01 4"/ STD/ 3mm NO YES 150# RF
FAIL
LAST
NOT
REQUIREDYES ATM 55 FOL+0.07 90 0.87 870 10.7 FOL+0.07 * * * */ 3-Phase
6 20-MOV-0978B Treated Crude from crude exchanger Crude/ LiquidMOTOR OPERATED
VALVE
ZONE 1, GAS GROUP-IIA/
IIB, TEMP.CL T3
17039-EK-P-DW-0203-
114"-PL-20-0818-AC01 4"/ STD/ 3mm NO YES 150# RF
FAIL
LAST
NOT
REQUIREDYES ATM 55 FOL+0.07 90 0.87 870 10.7 FOL+0.07 * * * */ 3-Phase
7 20-MOV-0979B Crude from crude dispatch pump PSV Crude/ LiquidMOTOR OPERATED
VALVE
ZONE 1, GAS GROUP-IIA/
IIB, TEMP.CL T3
17039-EK-P-DW-0203-
11
4"-PL-20-0811B-
AC014"/ STD/ 3mm NO NO 150# RF
FAIL
CLOSE
NOT
REQUIREDYES ATM 55 FOL+0.07 90 0.87 870 10.7 FOL+0.07 * * * */ 3-Phase
8 20-MOV-0981 Treated Crude to Crude Charge Pump Crude/ LiquidMOTOR OPERATED
VALVE
ZONE 1, GAS GROUP-IIA/
IIB, TEMP.CL T3
17039-EK-P-DW-0203-
116"-PL-20-0825-AC01 6"/ STD/ 3mm NO YES 150# RF
FAIL
LAST
NOT
REQUIREDYES ATM 55 FOL+0.07 90 0.87 870 10.7 FOL+0.07 * * * */ 3-Phase
9 20-MOV-1120 Crude to Crude Circulation pumps Crude/ LiquidMOTOR OPERATED
VALVE
ZONE 1, GAS GROUP-IIA/
IIB, TEMP.CL T3
17039-EK-P-DW-0203-
148"-PL-20-0459-AC01 8"/ 20/ 3mm NO YES 150# RF
FAIL
LAST
NOT
REQUIREDYES ATM 55 FOL+0.07 90 0.87 870 10.7 FOL+0.07 * * * */ 3-Phase
10 20-MOV-1119A
Crude from Closed Drain Tfr./ Crude
Exchanger/ Flare Recovery Pumps/ Oil
Tfr. Pumps
Crude Oil/ LiquidMOTOR OPERATED
VALVE
ZONE 1, GAS GROUP-IIA/
IIB, TEMP.CL T3
17039-EK-P-DW-0203-
146"-PL-20-0458-AC01 6"/ STD/ 3mm NO YES 150# RF
FAIL
LAST
NOT
REQUIREDYES 5 55 10 90 0.87 870 10.7 10 * * * */ 3-Phase
11 20-MOV-1119B From Crude circulation pumps Crude Oil/ LiquidMOTOR OPERATED
VALVE
ZONE 1, GAS GROUP-IIA/
IIB, TEMP.CL T3
17039-EK-P-DW-0203-
143"-PL-20-0391-AC01 3"/ STD/ 3mm NO YES 150# RF
FAIL
LAST
NOT
REQUIREDYES 10 55 15 90 0.87 870 10.7 15 * * * */ 3-Phase
12 66-MOV-6612Skim Oil from Effluent treatment
packageSkim Oil/ Liquid
MOTOR OPERATED
VALVE
ZONE 1, GAS GROUP-IIA/
IIB, TEMP.CL T3
17039-EK-P-DW-0206-
042"-PL-66-6603-AC01 2"/ XS/ 3mm NO NO 150# RF
FAIL
LAST
NOT
REQUIREDYES ATM 55 FOL+0.07 90 0.87 870 10.7 FOL+0.07 * * * */ 3-Phase
13 66-MOV-6623 Skim Oil To Skim Oil Transfer Pumps Skim Oil/ LiquidMOTOR OPERATED
VALVE
ZONE 1, GAS GROUP-IIA/
IIB, TEMP.CL T3
17039-EK-P-DW-0206-
042"-PL-66-6635-AC01 2"/ XS/ 3mm NO NO 150# RF
FAIL
LAST
NOT
REQUIREDYES ATM 55 FOL+0.07 90 0.87 870 10.7 FOL+0.07 * * * */ 3-Phase
14 20-MOV-2004 Metering Skid Inlet Crude Oil/ LiquidMOTOR OPERATED
VALVE
ZONE 1, GAS GROUP-IIA/
IIB, TEMP.CL T3
17039-EK-P-DW-0219-
013"-PL-20-2402-AC01 3"/ STD/ 3mm NO NO 150# RF
FAIL
CLOSEREQUIRED YES 10 55 15 90 0.87 870 10.7 15 * * * */ 3-Phase
LOCAL CONTROL
PANEL WITH
PUSH BUTTON
15 20-MOV-2005 Metering Skid Inlet Crude Oil/ LiquidMOTOR OPERATED
VALVE
ZONE 1, GAS GROUP-IIA/
IIB, TEMP.CL T3
17039-EK-P-DW-0219-
013"-PL-20-2403-AC01 3"/ STD/ 3mm NO NO 150# RF
FAIL
CLOSEREQUIRED YES 10 55 15 90 0.87 870 10.7 15 * * * */ 3-Phase
LOCAL CONTROL
PANEL WITH
PUSH BUTTON
16 20-MOV-2006 Metering Skid Inlet Crude Oil/ LiquidMOTOR OPERATED
VALVE
ZONE 1, GAS GROUP-IIA/
IIB, TEMP.CL T3
17039-EK-P-DW-0219-
013"-PL-20-2404-AC01 3"/ STD/ 3mm NO NO 150# RF
FAIL
CLOSEREQUIRED YES 10 55 15 90 0.87 870 10.7 15 * * * */ 3-Phase
LOCAL CONTROL
PANEL WITH
PUSH BUTTON
17 20-MOV-2007 Metering Skid Inlet Crude Oil/ LiquidMOTOR OPERATED
VALVE
ZONE 1, GAS GROUP-IIA/
IIB, TEMP.CL T3
17039-EK-P-DW-0219-
013"-PL-20-2405-AC01 3"/ STD/ 3mm NO NO 150# RF
FAIL
CLOSEREQUIRED YES 10 55 15 90 0.87 870 10.7 15 * * * */ 3-Phase
LOCAL CONTROL
PANEL WITH
PUSH BUTTON
MOTOR OPERATED VALVE LIST
DATA SHEET FOR MOTOR OPERATED VALVES OIL-100-EK-I-DS-0815 A0 Sht.No: 06 of 06
CREATION OF SURFACE PRODUCTION FACILITIES (GCS) AT EAST KHAGORIJAN
Document Title Document No Rev
Page 3 of 5
Datasheet NumberRev
Code
OIL-100-EK-I-DS-0816 A0 Sheet No.: 02 of 05
SHEET No.
1 COVER SHEET
2 INDEX SHEET
3 REVISION SHEET
4 NOTES SHEET
5
INDEX SHEET
TITLE
CREATION OF SURFACE PRODUCTION
FACILITIES (GGS) AT EAST KHAGORIJAN
Revision Index
DATA SHEET FOR FLOAT AND BOARD TYPE LEVEL
INDICATOR
DATA SHEET FOR FLOAT AND BOARD TYPE LEVEL INDICATOR
Datasheet NumberRev
Code
OIL-100-EK-I-DS-0816 A0 Sheet No: 03 of 05
REV No. LIST OF PAGES OF UPDATED / MODIFIED SECTIONS, IF ANY
A0 FIRST ISSUE
CREATION OF SURFACE PRODUCTION
FACILITIES (GGS) AT EAST KHAGORIJAN
Revision Index
DATA SHEET FOR FLOAT AND BOARD TYPE LEVEL
INDICATOR
REVISION RECORD SHEET
PURPOSE
ISSUED FOR REVIEW
Datasheet Number Rev Code
OIL-100-EK-I-DS-0816 A0 Sheet No: 04 of 05
4. All weldings & castings (if any) shall be 100% radiographed.
5. Painting shall be Manufacturer standard suitable to all aggressive environment.
6. Sufficent float and guide wire to be supplied on single length to cut at site as per requirement.
7. The pointer is in `TOP POSITION' when tank is `EMPTY' and in `BOTTOM POSITION' when `FULL'. Pointer indicates 'Level'.
REFERENCE DOCUMENTS:
17039-EK-I-DB-8001_Functional specification for package instruments_Rev C
Notes:
1. Documentation required :- Calibration Certificate , Material Certificates to 3.1 as per EN 10204, Hydro test ,
Pressure test Procedure/Report , Operating & Maintenance Instructions & Spare Parts List.
2. All instruments to be supplied with a SS 316 Name plate with Tag no. permanently inscribed. Tags shall be Permanently secured.
3. All stud bolt material shall be ASTM A 193 Gr. B7 & Heavy hex nuts shall be ASTM A194 Gr. 2H.
CREATION OF SURFACE PRODUCTION FACILITIES (GGS)
AT EAST KHAGORIJAN
Revision Index
DATA SHEET FOR FLOAT AND BOARD TYPE LEVEL INDICATOR
8. The gauge board is supplied in 1mtr sections and multiple gauge boards are connected through gauge brackets as per ordered measuring range.
TITLE ITEM/TAG No.
PROJECT DESCRIPTION PROJECT NO. REV
A0
EPC CONTRACTOR PURCHASE ORDER No. SPECIFICATION No.
CLIENT NAME REV No. BY DATE CKD DATE APP. DATE DESCRIPTION
A0 VS 29-Nov-18 PGN 29-Nov-18 MV 29-Nov-18 ISSUED FOR REVIEW
CLIENT DOC NO
UNITS:- Pressure barg kg/cm2 g kPa g psig Level: mm
Temp °C
1 TAG No.
2 TYPE
3 P&ID No.
4 SERVICE
GENERAL 5 VESSEL No.
6 TANK ROOF TYPE
7 TANK HEIGHT mm
8 NOZZLE HEIGHT mm 150 (FROM TOP OF TANK) 150 (FROM TOP OF TANK)
9 FLUID STATE
10 PRESS MAX. NOR.
PROCESS 11 TEMP. MAX. NOR.
CONDITIONS 12 SPEC. GR.
13 VISCOSITY cP
14 TYPE
15 QUANTITY
16 SCALE RANGE mm
17 LOCAL INDICATION
GAUGE BOARD 18 MOUNTING
19 TEST PRESSURE
20
21 ENCLOSURE PROTECTION
22 SPRING ASSEMBLY
23 DRIVE BUSHING
24 TAG NO.
25 SWITCH CONTACTS
SWITCHES 26 CONTACT RATING
27 CABLE ENTRIES
28 ENCLOSURE PROTECTION
29 AREA CLASSIFICATION
30 LEVEL GAUGE / GAUGE HEAD
31 PIPE MOUNTING PARTS
32 TOP ANCHOR ASSEMBLY
33 ELBOW
MATERIAL 34 FLOAT & PULLEY
35 GUIDE WIRE KNOB
36 TAPE / WIRE
37 BOTTOM ANCHOR ASSEMBLY
PERFORMANCE 38 ACCURACY
39 REPEATABILITY
40
41 NEGATOR CASSETTE
42 CONDUITS ELBOWS
OPTIONS 43 SUPPORT BRACKETS
44 INSPECTION HATCHES
45
OTHERS 46 MANUFACTURER
47 MODEL
NOTES :
REFER NOTES SHEET
17039-EK-I-DB-8001
OIL INDIA LIMITED
DATA SHEET No.
DATA SHEET FOR FLOAT AND BOARD TYPE LEVEL INDICATOR AS BELOW OIL-100-EK-I-DS-0816
SHEET
CREATION OF SURFACE PRODUCTION FACILITIES (GGS)
AT EAST KHAGORIJAN KIP-17039 05 OF 05
-
ORIGINATOR ORIG. DATE
VS 29-Nov-18
REQUISITION NO.
TBA - -
17039-EK-P-DW-0217-01 17039-EK-P-DW-0217-01
FIRE WATER STORAGE TANK FIRE WATER STORAGE TANK
71-LI-8005 71-LI-8004
FLOAT & BOARD FLOAT & BOARD
10000 10000
EK-ABJ-3110A EK-ABJ-3110B
VERTICAL CONE ROOF VERTICAL CONE ROOF
FIRE WATER
FOW+0.07 / ATM
80 / 41
1
FOW+0.07 / ATM
80 / 41
1
1 1
FIRE WATER
0 - 10000 0 - 10000
CALIBRATED GAUGE BOARD CALIBRATED GAUGE BOARD
LEVEL INDICATOR LEVEL INDICATOR
1 1
CONN. SIZE :TYPE & RATING 3 No's 1 1/2" 150#RF 3 No's 1 1/2" 150#RF
IP 65 IP 65
SIDE MOUNTED SIDE MOUNTED
- -
- -
- -
SPRING STEEL SPRING STEEL
- -
- -
- -
- -
- -
SS 316 SS 316
CAST ALUMINUM (EPOXY COATED) CAST ALUMINUM (EPOXY COATED)
CAST ALUMINUM (EPOXY COATED) CAST ALUMINUM (EPOXY COATED)
SS 316 SS 316
SS 316 SS 316
SS 316 SS 316
SS 316 SS 316
± 2mm ± 2mm
- -
SS 316 SS 316
YES YES
YES YES
NO NO
* *
* *
NO NO
Datasheet NumberRev
Code
OIL-100-EK-I-DS-0817 A0 SHEET 02 OF 05
SHEET No.
1 COVER SHEET
2 INDEX SHEET
3 REVISION SHEET
4 NOTES SHEET
5 71-FE-7266
CREATION OF SURFACE PRODUCTION
FACILITIES (GGS) AT EAST KHAGORIJAN
Revision Index
DATASHEET - FLOW ELEMENT (ORIFICE)
TITLE
INDEX SHEET
Datasheet NumberRev
Code
OIL-100-EK-I-DS-0817 A0 SHEET 03 OF 05
REV No. LIST OF PAGES OF UPDATED / MODIFIED SECTIONS, IF ANY
A0 FIRST ISSUE
CREATION OF SURFACE PRODUCTION
FACILITIES (GGS) AT EAST KHAGORIJAN
Revision Index
DATASHEET - FLOW ELEMENT (ORIFICE)
REVISION RECORD SHEET
PURPOSE
ISSUED FOR REVIEW
Datasheet NumberRev
Code
OIL-100-EK-I-DS-0817 A0 SHEET 04 OF 05
1 Documentation required :- Calibration Certificate,Material Certificates to 3.1 as per EN10204, weather proof certificate, Pressure test
procedure/Report, NDT Procedure/ report, Operating & Maintenance Instructions & Spare Parts List.
1 The upstream side of the orifice plate tab handle shall be permanently marked “UPSTREAM”.
2 The downstream side of the orifice plate tab handle shall be permanently marked Instrument tag number,Orifice bore diameter in mm,
Line size ( in mm ) and flange rating( in ANSI ),Plate material.
3 Orifice Flanges shall be in accordance with ANSI B 16.36 & ANSI class 300 rated as minimum.
4 The beta ratio (d/D) shall be kept in between 0.2 and 0.7.
5 Normal flow rates shall be calculated in such a way that its value is approximately 70% to 80% of design flow.
6 Orifice plate for ring-type joint flanges shall be supplied with plate carrying holders.
7 Orifice plates shall be bored for the maximum flow that will give an even meter factor or Meter max.
8 Each flange shall have two pressure taps to facilitate ease of installation. One of the pressure taps shall be provided with 1/2" NPTM plug.
9 The given minimum flowrate is based on 30% turndown of normal flowrate.
10 Design life of all instruments shall be 20 years.
11 Minimum, normal and maximum ambient temperaures are 8°C, 28°C & 38°C.
12 Flow element sizing calculation shall be as per ISO 5167. For gas measurements, the sizing and Installation shall beAGA 3 /AGA 8 report.
13 Orifice assembly shall include supply of plates, flanges, stud, bolts, nuts, jack screw, gasket / plate, holder & plugs.
14 All stud bolt material shall be Zinc coated (hot dipped) according to ASTM A153.
HOLD:
1 Design pressure & design temperature.
CREATION OF SURFACE PRODUCTION
FACILITIES (GGS) AT EAST KHAGORIJAN
Revision Index
DATASHEET - FLOW ELEMENT (ORIFICE)
NOTES SHEET
ITEM/TAG No. DATA SHEET No.
VME PROJECT No
REQUISITION No. REV
A0
REV No. BY DATE CKD DATE APP. DATE
A0 IMR 29-Nov-18 MV 29-Nov-18 MSR/ VSR 29-Nov-18
UNITS: Pressure: kg/cm2 g Temp: Flow: Gas: - Liquid:
1 10
2 TYPE CONCENTRIC OTHER SQUARE EDGE PADDLE 11 TAPS FLANGE CORNER
3 STANDARD ISO 5167 OTHER (AGA REPORT 3) 12 PIPE OTHER
4 BORE MAXIMUM RATE NEAREST 1/8 in. 13 TAP SIZE 1/2"NPTF OTHER
5 MATERIAL SS 304 SS 316 OTHER 14 TYPE WELD NECK FLANGENECK
6 RING MATERIAL SS316 15 SLIP-ON THREADED
7 16 MATERIAL CARBON STEEL
8 17 FLANGES INCLUDED BY OTHERS
9 18 RATING 300# RF
10 TAG NO.
11SERVICE
12 P & ID No.
13 LINE No.
14 LINE SIZE/SCH
15 LINE INSULATION
16 NACE
17 FLUID TYPE
18 SUSPENDED SOLIDS
19 PRESSURE (MAX. / NORM. / MIN. ) - -
20 TEMPERATURE (MAX. / NORM. / MIN.) - -
21 DESIGN (PRESS / TEMP.)
22 SPECIFIC GRAVITY BASE | OPERATING
23 BASE PRESSURE
24 BASE TEMPERATURE
25 ALLOWABLE PRESS. DROP ACROSS METER (kg/cm2)
26 FLUID VISCOSITY cP
27 DENSITY kg/m3 MOLECULAR WEIGHT
28- -
29 PERMANENT PRESSURE LOSS
30 FLOW (MIN / NORMAL / MAX) -
31 VELOCITY (MIN / NOR / MAX) -
32 SPECIFIC HEAT RATIO (Cp/Cv)
33 COMPRESSIBILITY FACTOR (Z)
34 CORROSIVE COMPONENT (MOLE FRACTION)
35 TYPE OF METER
36 DIFF. RANGE-DRY ( mbar)
37 SEAL SP. GR AT 60 deg F
38 STATIC PRESSURE RANGE
39 CHART or SCALE RANGE
40 CHART MULTIPLIER
41 METER MAX. m3/hr
42 BETA =d/D
43 ORIFICE BORE DIAMETER mm
44 LINE I.D mm
45 FLANGE RATING
46 FLANGE MATERIAL
47 PLATE THICKNESS (mm)
48 STUD & BOLT MATERIAL ASTM A 193 Gr. B7 / ASME B16.5 (Hot dip galvanized)
49 GASKET MATERIAL
50 RING TYPE & NO.
51 STRAIGHT LENGTH
52 FLOW COMPUTER
53 FLOW STRAIGHTENER
54 MODEL NO. FOR PLATE
55 MANUFACTURER
56 NOTES: * BY VENDOR
57 REFER NOTES SHEET
58
ATM
41
FOW 80
- 0.541
995.4
-
*
Not Required
LIQUID
N/A
DIFFERENTIAL PRESSURE
*
206.37
-
ASTM A105, CS hot dip Galvanized
*
SP.WND SS316 + CNAF
-
-
-
0 - 450
*
300# RF
-
-
-
0.64
1.116 psia
410 m3/hr
-
NO
-
OT
HE
R
OP
TIO
NS
ME
TE
RP
LA
TE
& F
LA
NG
E
° C
GE
NE
RA
LS
ER
VIC
E C
ON
DIT
ION
S
VAPOUR PRESSURE / PULSAION / STEADY FLOW
ORIFICE PLATES ORIFICE FLANGES
m3/hr
71-FE-7266
FIRE WATER FR.FW PUMP DISCAHRGE (TEST
LINE)
17039-EK-P-DW-0217-01
8"-WF-71-7108-AG01
8" / HVY
*
-
0-250
-
CREATION OF SURFACE PRODUCTION FACILITIES (GGS) AT EAST KHAGORIJAN KIP-17039
TBA -
EPC CONTRACTOR
TITLE
DATASHEET - FLOW ELEMENT (ORIFICE) REFER BELOW
PROJECT DESCRIPTION
OIL-100-EK-I-DS-0817
SPECIFICATION No.
05 of 05
-
SHEET
CLIENT NAME DESCRIPTION
OIL INDIA LIMITED ISSUED FOR REVIEW
IMR 17-Sep-18
CLIENT DOC .No
-
ORIGINATOR ORIG.DATE
Datasheet NumberRev
Code
OIL-100-EK-I-DS-0818 A0 Sheet No.: 02 of 05
SHEET No.
1 COVER SHEET
2 INDEX SHEET
3 REVISION SHEET
4 NOTES SHEET
5 DATA SHEET FOR DP TYPE LEVEL TRANSMITTER
INDEX SHEET
TITLE
CREATION OF SURFACE PRODUCTION
FACILITIES (GGS) AT EAST KHAGORIJAN
Revision Index
DATA SHEET FOR DP TYPE LEVEL TRANSMITTER
Datasheet NumberRev
Code
OIL-100-EK-I-DS-0818 A0 Sheet No: 03 of 06
REV No. LIST OF PAGES OF UPDATED / MODIFIED SECTIONS, IF ANY
A0 FIRST ISSUE
CREATION OF SURFACE PRODUCTION
FACILITIES (GGS) AT EAST KHAGORIJAN
Revision Index
DATA SHEET FOR DP TYPE LEVEL TRANSMITTER
REVISION RECORD SHEET
PURPOSE
ISSUED FOR REVIEW
Datasheet Number Rev Code
OIL-100-EK-I-DS-0818 A0 Sheet No: 04 of 05
REFERENCE DOCUMENTS:
17039-EK-I-DB-8001_Functional specification for package instruments_Rev C
5. All field transmitters shall be" SMART" type, 2-wire 24VDC loop powered communicating on 4-20mA signal mode with superimposed
CREATION OF SURFACE PRODUCTION FACILITIES (GGS) AT
EAST KHAGORIJAN
Revision Index
DATA SHEET FOR DP TYPE LEVEL TRANSMITTER
Notes:
1. Documentation required :- Calibration Certificate , Ingress Protection Certificate, Material Certificates to 3.1 as per EN 10204, Hydro test , Explosion proof & weather
proof certificate, Pressure test Procedure/Report , Operating & Maintenance Instructions & Spare Parts List.
2. All instruments to be supplied with a SS 316 Name plate with Tag no. permanently inscribed. Tags shall be Permanently secured.
3. All transmitters shall be provided with integral indicator (LCD type) with engineering unit indicating total level in mm & %.
4. Instrumentation shall meet the Electromagnetic interference requirements according to EN 50081-2 and EN 50082-2.
HART digital transmission signal for remote calibration and diagnostics from HART maintenance system.
6. Flange finish shall be in accordance with ANSI B16.5, for Raised Face (RF) flanges and shall be smooth finish to 125-250 AARH and 63 AARH for Ring type joint (RTJ) .
7. The housing of all transmitters shall be SS 316 minimum and suitable for aggressive offshore environment.
8. Certified plug shall be provided for spare cable entry.
9. All Transmitters shall be provided with SIL-2 (min) certification.
10. The over-range/static pressure protection of the transmitter shall be 130% of range.
11. Painting shall be Manufacturer standard suitable to all aggressive environment.
12. The design of electronic instruments shall be in compliance with the electromagnetic compatibility requirements as per IEC-61000-4.
TITLE ITEM/TAG No. DATA SHEET No.
DATA SHEET FOR DP TYPE LEVEL TRANSMITTER
PROJECT DESCRIPTION PROJECT NO REV
05 05 A0
CONTRACTOR REQUISITION No. SPECIFICATION No.
TBA
CLIENT NAME REV No. BY DATE CKD DATE APP. DATE
A0 VS 29-Nov-18 MV 29-Nov-18 PG 29-Nov-18 ISSUED FOR REVIEW
CLIENT'S REF
-
ORIGINATOR ORIG. DATE
29-Nov-18
UNITS: Pressure: kg/cm2 g Temp:
1. Mounting Remote (2" Pipe Mounted) 8. Zero Suppression Required
2. Accuracy ± 0.25% of Span 9. Zero Elevation Required
3. Over Pressure Limit * 10. Zero Adjust Location External
4. Ambient Temp. Limit 8 to 38°C 11. Span Adjust Location External
5. Output 4-20 mAdc, HART Protocol with SMART Tr. 12. Enclosure Rating IP 65
6. Power Supply 24 VDC Loop powered 13. Area Classification Zone 2, Gas Group IIA&IIB, T3
7. Indicating Yes, LCD in engineering unit 14. Equipment Certification Ex 'ia'
1. Service Level 11. Housing Material Polyurethane Coated Aluminum
2. Process connetion 2" Flange, 150# RF ANSI, 316SS 12. Xmtr Diaphragm. Material SS 316
3. Electrical Connection 1/2" NPT(F) 13. O-Ring Material Glass-Filled PTFE
4. Mounting Bracket Yes, For 2" Pipe 14. Sensor Fill Fluid Silicone Oil
5. Process Seal Type Diaphragm 15. Diaphragm Seal Material N/A
6. Hydrotest Req'd Yes 16. Capillary Material N/A
7. Diaphragm Seal No 17. Drain/Vent Material SS 316
8. Capillary Length N/A 18. Flange Bolt Material SS 316
9. Capillary Fill Fluid N/A 19. Bracket Bolt Material SS 316
10. Drain / Vent 20. SIL Compliance SIL-2
21. Manufacturer *
1) Each instrument shall include a SS 316 tag permanently attached to the instrument using SS 316 screws, SS 316 bolts or ss 316 wire.
2) Transmitter un-used conduit entry shall be plugged with certified Ex'd' Plug.
3) Painting shall be Manufacturer standard suitable for Hazardous environment.
4) All Level transmitters (DP type) shall be provided with 5 valve manifold.
5) For General notes refer Notes section.
1 53-LIT-5512 17039-EK-P-DW-0212-01 * 2500 0 - 2500 ATM FOW+0.07 AMB 80 1000 1 * -
2 53-LIT-5513 17039-EK-P-DW-0212-01 * 2500 0 - 2500 ATM FOW+0.07 AMB 80 1000 1 * -
3 53-LIT-5538 17039-EK-P-DW-0212-04 * 2500 0 - 2500 ATM FOW+0.07 AMB 80 1000 1 * -
4 53-LIT-5541 17039-EK-P-DW-0212-04 * 2500 0 - 2500 ATM FOW+0.07 AMB 80 1000 1 * -
* To be Provided By Vendor.
CREATION OF SURFACE PRODUCTION FACILITIES (GGS) AT EAST KHAGORIJAN KIP-17039
SEE BELOW TABLE OIL-100-EK-I-DS-0818
VS
DESCRIPTION
OIL INDIA LIMITED
- 17039-EK-I-DB-8001
CLIENT CONTRACT No.
-
SHEET
OF
Remarks
° C
GENERAL
C O N S T R U C T I O N
NOTES
P&ID Number
Instrument
Range
in mmH20
specific
gravity
Model
Number
Yes (1/4" Drain connection pipe
plug
supplied with Manifold)
S.No. Tag Number Service DescriptionOperating
Temp. (°C)
Design
Temp.
(°C)
Calibrated
Range
in mm
Potable wate storage tank
(EK-ABJ-3270)
Potable wate storage tank
(EK-ABJ-3270)
Industrial Water Storage Tank (EK-
ABJ-3220)
Industrial Water Storage Tank (EK-
ABJ-3220)
Density
(kg/m3)
Operating
pressure
(Kg/cm2)
C-C
DIST.
(mm)
Design
pressure
(Kg/cm2)
Datasheet NumberRev
Code
OIL-100-EK-I-DS-0819 A0 SHEET 02 OF 05
SHEET No.
1 COVER SHEET
2 INDEX SHEET
3 REVISION SHEET
4 NOTES SHEET
5 DS-FI (ROTAMETER)
INDEX SHEET
CREATION OF SURFACE PRODUCTION FACILITIES (GGS)
AT EAST KHAGORIJAN
Revision Index
DATA SHEET FOR FLOW INDICATOR (ROTAMETER)
TITLE
Datasheet NumberRev
Code
OIL-100-EK-I-DS-0819 A0 SHEET 03 OF 05
REV No. LIST OF PAGES OF UPDATED / MODIFIED SECTIONS, IF ANY
FIRST ISSUE
REVISION RECORD SHEET
CREATION OF SURFACE PRODUCTION FACILITIES (GGS) AT
EAST KHAGORIJAN
Revision Index
DATA SHEET FOR FLOW INDICATOR (ROTAMETER)
PURPOSE
A0 ISSUED FOR REVIEW
Datasheet NumberRev
Code
OIL-100-EK-I-DS-0819 A0Sheet No.: 04 of 05
2. All instruments to be supplied with a SS 316 Name plate with Tag no. permanently inscribed. Tags shall be Permanently secured.
3. The metering tube shall have self-guided floats, with top and bottom float stops.
4. An arrow mark indication of flow shall be marked on the body.
5. All stud bolt material shall be ASTM A 193 Gr. B7 / ASME B16.5 (Hot dip galvanized).
6. Float shall have dimensional stability and shall not respond to variations in viscosity.
7. Indicating scales shall have full length safety glass with shields and gaskets on both sides.
8. Armoured meters shall have a metal tube with magnetically coupled integral indicator.
9. The range of the Rotameter shall be selected such that the normal flow rate is between 50% and 70% of the instrument range.
10. The flow rate shall be indicated by the vertical position of the float or magnetically coupled pointer.
Notes Sheet
CREATION OF SURFACE PRODUCTION FACILITIES (GGS) AT
EAST KHAGORIJAN
Revision Index
DATA SHEET FOR FLOW INDICATOR (ROTAMETER)
1. Documentation required :- Calibration certificate, Material certificates to 3.1 as per EN10204, weather proof to IP66 certificate by ATEX or Equivalent body, Pressure
test procedure/Report, Hydrostatic Test Report, GAD Wiring diagram, Operating and Maintenance Instructions & Spare Parts List.
TITLE DATA SHEET No.
DATA SHEET FOR FLOW INDICATOR (ROTAMETER) OIL-100-EK-I-DS-0819
PROJECT DESCRIPTION SHEET REV
CREATION OF SURFACE PRODUCTION FACILITIES (GGS) AT EAST KHAGORIJAN 05 OF 05 A0
EPC CONTRACTOR
TBA
REV No. BY DATE CKD DATE APP. DATE DESCRIPTION
OIL INDIA LIMITED A0 IMR 29-Nov-18 MV 29-Nov-18 MSR/VSR 29-Nov-18 Issued For Review
ORIG. DATE
28-Sep-18
UNITS:- Pressure bar g kg/cm2 g kPa g psi g Flow: Liquid LPH m
3/hr USgpm
Temp 0 C
0 F Gas Sm
3/hr SCFM MMscfd
1
2 SERVICE
3 LINE No.
4 P &ID No.
5 LINE SIZE/SCH
6 FUNCTION
GENERAL 7 MOUNTING
8 POWER SUPPLY
9 CONN. SIZE THREADED THREADED
10 INLET DIR. OUTLET DIR. VERTICAL BOTTOM VERTICAL TOP VERTICAL BOTTOM VERTICAL TOP
11 FLANGE/FITTING MATERIAL SS 316 SS 316
12 PACKING or O-RING MATERIAL
13 ENCLOSURE MATERIAL
14 SIZE SS 316 SS 316
15 TUBE MATERIAL SS 316 SS 316
16 METER SCALE: LENGTH & TYPE
METER 17 METER SCALE RANGE m3/hr
18 METER FACTOR
19 RATED ACCURACY
20 ENCL. PROTECTION
21 FLUID
22 COLOUR or TRANSPARENT
23 MAXIMUM FLOW RATE
24 NORMAL FLOW
FLUID 25 OPERATING SG MW
DATA 26 MAX. OPERATING VISCOSITY cP
27 AMB Amb
28 LIQUID DENSITY
29 STD DENSITY
30 MAX. ALLOWABLE PRESS DROP kg/cm2
31 DESIGN PRESSURE/TEMP. kg/cm2 /°C 80 80
EXT 32 EXTENSION WELL MATERIAL
33 STUD, BOLT &GASKET MATERIAL
34 TRANSMITTER OUTPUT
XMTR 35 TRANS. ENCLOSURE CLASS
36 HAZARDOUS AREA
37 LOCAL INDICATION
38 DIAL SIZE
39 NO. OF CONTACTS
ALARM 40 RATING
41 ACTION
42 VALVE SIZE & MATERIAL
43 VALVE LOCATION
44 CONST. DIFF. RELAY MATERIAL
OPTIONS 45 PURGE METER TUBING
46 AIR SET
47 DAMPING DEVICE
48 CABLE CONNECTION
49 IS BARRIER
50 CALIBRATION
51 MANUFACTURER
52
53 NOTES:-
Refer Notes section.
-
IMR
TAG NO. 42-FI-3910 42-FI-3912
CLIENT DOC.No:
CLIENT CONTRACT No. REQUISITION No.
ORIGINATOR
SPECIFICATION No.
- - -
CLIENT NAME
17039-EK-P-DW-0206-01 17039-EK-P-DW-0206-01
1/2"/ SCH 160 1/2"/ SCH 160
Water scale inhibitor injection pumps (EK-
PBA-5130A/B) outlet
De-oiler injection pumps
( EK-PBA-5090A/B) Outlet
1/2"-CS-42-3879-GT20 1/2"-CS-42-3900-GT20
TYPE 1/2"NPTF 1/2"NPTF
FLOW MEASUREMENT (LOCAL INDICATION) FLOW MEASUREMENT (LOCAL INDICATION)
INLINE INLINE
- -
MFR STD. MFR STD.
N/A N/A
FLOAT MATL. SS 316 SS 316
DIRECT READING (LINEAR) DIRECT READING (LINEAR
SS 316 SS 316
FLOAT GUIDE 1/2" 1/2"
±2 % OF FULL SCALE READING ±2 % OF FULL SCALE READING
IP 65 IP 65
* *
10 10
MIN FLOW 0.9 lit/hr 1.4 lit/hr
Chemical, Water Scale Inhibitor Chemical, De-Oiler
TRANSPARENT TRANSPARENT
kg/m³ 1000 980
0.1 0.1
OP. PRESS./TEMP. 6.5 6.5
lb/ft3
INDICATORYES YES
MFD STD MFD STD
- -
- -
- -
- -
- -
- -
MODEL No.
- -
Required with Certificates Required with Certificates
ITEM/TAG No.
REFER BELOW
PROJECT NO.
KIP-17039
YES YES
10 10
Datasheet NumberRev
Code
OIL-100-EK-I-DS-0820 A0 Sheet No.: 02 of 05
SHEET No.
1 COVER SHEET
2 INDEX SHEET
3 REVISION SHEET
4 NOTES SHEET
5 DATA SHEET FOR DIFFERENTIAL PRESSURE TRANSMITTER
INDEX SHEET
TITLE
CREATION OF SURFACE PRODUCTION
FACILITIES (GGS) AT EAST KHAGORIJAN
Revision Index
DATA SHEET FOR DIFFERENTIAL PRESSURE
TRANSMITTER
Datasheet NumberRev
Code
OIL-100-EK-I-DS-0820 A0 Sheet No: 03 of 06
REV No. LIST OF PAGES OF UPDATED / MODIFIED SECTIONS, IF ANY
A0 FIRST ISSUE
REVISION RECORD SHEET
PURPOSE
ISSUED FOR REVIEW
CREATION OF SURFACE PRODUCTION
FACILITIES (GGS) AT EAST KHAGORIJAN
Revision Index
DATA SHEET FOR DIFFERENTIAL PRESSURE
TRANSMITTER
Datasheet Number Rev Code
OIL-100-EK-I-DS-0820 A0 Sheet No: 04 of 05
REFERENCE DOCUMENTS:
17039-EK-I-DB-8001_Functional specification for package instruments_Rev C
1. Design condition to be confirmed
Hold:
6. Flange finish shall be in accordance with ANSI B16.5, for Raised Face (RF) flanges and shall be smooth finish to 125-250 AARH and 63 AARH for Ring type joint (RTJ) .
7. The housing of all transmitters shall be SS 316 minimum and suitable for hazardous area.
8. Certified plug shall be provided for spare cable entry.
9. Transmitters in safety loops shall be provided with SIL-2 (min) certification.
10. The over-range/static pressure protection of the transmitter shall be 130% of range.
11. Painting shall be Manufacturer standard suitablefor hazardous area.
12. The design of electronic instruments shall be in compliance with the electromagnetic compatibility requirements as per IEC-61000-4.
5. All field transmitters shall be" SMART" type, 2-wire 24VDC loop powered communicating on 4-20mA signal HART
CREATION OF SURFACE PRODUCTION FACILITIES (GGS) AT
EAST KHAGORIJAN
Revision Index
DATA SHEET FOR DIFFERENTIAL PRESSURE TRANSMITTER
Notes:
1. Documentation required :- Calibration Certificate , Ingress Protection Certificate, Material Certificates to 3.1 as per EN 10204, Hydro test , weather
proof certificate, Pressure test Procedure/Report , Operating & Maintenance Instructions & Spare Parts List.
2. All instruments to be supplied with a SS 316 Name plate with Tag no. permanently inscribed. Tags shall be Permanently secured.
3. All transmitters shall be provided with integral indicator (LCD type) with engineering unit indicating total level in mm & %.
4. Instrumentation shall meet the Electromagnetic interference requirements according to EN 50081-2 and EN 50082-2.
TITLE ITEM/TAG No. DATA SHEET No.
DATA SHEET FOR DIFFERENTIAL PRESSURE TRANSMITTER
PROJECT DESCRIPTION PROJECT NO REV
05 05 A0
MPC CONTRACTOR REQUISITION No. SPECIFICATION No.
TBA
CLIENT NAME REV No. BY DATE CKD DATE APP. DATE
A0 VS 29-Nov-18 PGN 29-Nov-18 MV 29-Nov-18 ISSUED FOR REVIEW
CLIENT'S REF
-
ORIGINATOR ORIG. DATE
29-Nov-18
UNITS: Pressure: kg/cm2 g Temp:
1. MOUNTING REMOTE (2" PIPE MOUNTED) 8. ZERO SUPPRESSION REQUIRED
2. ACCURACY ± 0.25% OF SPAN 9. ZERO ELEVATION REQUIRED
3. OVER PRESSURE LIMIT * 10. ZERO ADJUST LOCATION EXTERNAL
4. AMBIENT TEMP. LIMIT 11 TO 34°C 11. SPAN ADJUST LOCATION EXTERNAL
5. OUTPUT 4-20 MADC, HART PROTOCOL WITH SMART TR. 12. ENCLOSURE RATING IP 65
6. POWER SUPPLY 24 VDC LOOP POWERED 13. AREA CLASSIFICATION ZONE 2, GAS GROUP IIA/IIB, T3
7. INDICATING YES, LCD IN ENGINEERING UNIT 14. EQUIPMENT CERTIFICATION EX 'IA'
1. SERVICE PRESSURE 11. HOUSING MATERIAL SS 316
2. PROCESS CONNECTION 1/2" NPT 12. XMTR DIAPHRAGM. MATERIAL N/A
3. ELECTRICAL CONNECTION 1/2" NPT(F) 13. O-RING MATERIAL GLASS-FILLED PTFE
4. MOUNTING BRACKET YES, FOR 2" PIPE 14. SENSOR FILL FLUID SILICONE OIL
5. PROCESS SEAL TYPE N/A 15. DIAPHRAGM SEAL MATERIAL N/A
6. HYDROTEST REQ'D NO 16. CAPILLARY MATERIAL N/A
7. DIAPHRAGM SEAL NO 17. DRAIN/VENT MATERIAL SS 316
8. CAPILLARY LENGTH N/A 18. FLANGE BOLT MATERIAL N/A
9. CAPILLARY FILL FLUID N/A 19. BRACKET BOLT MATERIAL SS 316
10. DRAIN / VENT 20. SIL COMPLIANCE SIL-2
21. MANUFACTURER *
1) EACH INSTRUMENT SHALL INCLUDE A SS 316 TAG PERMANENTLY ATTACHED TO THE INSTRUMENT USING SS 316 SCREWS, SS 316 BOLTS OR SS 316 WIRE.
2) TRANSMITTER UN-USED CONDUIT ENTRY SHALL BE PLUGGED WITH CERTIFIED EX'D' PLUG.
3) PAINTING SHALL BE MANUFACTURER STANDARD SUITABLE FOR HAZARDOUS ENVIRONMENT.
4) DIFFERNTIAL PRESSURE TRANSMITTER SHALL BE PROVIDED WITH 5 VALVE MANIFOLD.
5) FOR GENERAL NOTES REFER NOTES SECTION.
1 20-PDT-2000 17039-EK-P-DW-0219-01 * 10 15 (HOLD) 55 90 (HOLD) 870 0.87 * -
2 20-PDT-2001 17039-EK-P-DW-0219-01 * 10 15 (HOLD) 55 90 (HOLD) 870 0.87 * -
3 20-PDT-2002 17039-EK-P-DW-0219-01 * 10 15 (HOLD) 55 90 (HOLD) 870 0.87 * -
4 20-PDT-2003 17039-EK-P-DW-0219-01 * 10 15 (HOLD) 55 90 (HOLD) 870 0.87 * -
* To be Provided By Vendor.
ACROSS BASKET TYPE STRAINER
(3"-PL-20-2402-AC01) / CRUDE
OIL
ACROSS BASKET TYPE STRAINER
(3"-PL-20-2403-AC01) / CRUDE
OIL
DENSITY
(KG/M3)
OPERATING
PRESSURE
(KG/CM2)
DESIGN
PRESSURE
(KG/CM2)
CALIBRATED RANGE
IN KG/CM2
0 - 1
0 - 1
0 - 1
0 - 1
ACROSS BASKET TYPE STRAINER
(3"-PL-20-2404-AC01) / CRUDE
OIL
ACROSS BASKET TYPE STRAINER
(3"-PL-20-2405-AC01) / CRUDE
OIL
REMARKS
° C
GENERAL
C O N S T R U C T I O N
NOTES
P&ID NUMBER
INSTRUMENT
RANGE
IN KG/CM2
SPECIFIC
GRAVITY
MODEL
NUMBER
YES (1/4" DRAIN CONNECTION PIPE
PLUG
SUPPLIED WITH MANIFOLD)
S.NO. TAG NUMBER LOCATION / SERVICE
OPERATIN
G TEMP.
(°C)
DESIGN
TEMP.
(°C)
CREATION OF SURFACE PRODUCTION FACILITIES (GGS) AT EAST KHAGORIJAN KIP-17039
SEE BELOW TABLE OIL-100-EK-I-DS-0820
VS
DESCRIPTION
OIL INDIA LIMITED
- 17039-EK-I-DB-8001
CLIENT CONTRACT No.
-
SHEET
OF
Datasheet NumberRev
Code
OIL-100-EK-I-DS-0821 A0 Sheet No.: 02 of 05
SHEET No.
1 COVER SHEET
2 INDEX SHEET
3 REVISION SHEET
4 NOTES SHEET
5 DS - PT
CREATION OF SURFACE PRODUCTION
FACILITIES (GGS) AT EAST KHAGORIJAN
Revision Index
DATA SHEET FOR PRESSURE TRANSMITTER
INDEX SHEET
TITLE
Datasheet NumberRev
Code
OIL-100-EK-I-DS-0821 A0 Sheet No: 03 of 06
REV No. LIST OF PAGES OF UPDATED / MODIFIED SECTIONS, IF ANY
A0 FIRST ISSUE
CREATION OF SURFACE PRODUCTION
FACILITIES (GGS) AT EAST KHAGORIJAN
Revision Index
DATA SHEET FOR PRESSURE TRANSMITTER
REVISION RECORD SHEET
PURPOSE
ISSUED FOR REVIEW
Datasheet Number Rev Code
OIL-100-EK-I-DS-0821 A0 Sheet No: 04 of 05
6. The housing of all transmitters shall be SS 316 minimum and suitable for aggressive offshore environment.
7. Transmitter shall be provided with two(2) cable entry of size 1/2" NPT(F). Unused cable entries shall be plugged with ex-proof 316L SS certified plugs.
8. All Transmitters shall be provided with SIL-2 (min) certification.
5. All field transmitters shall be" SMART" type, 2-wire 24VDC loop powered communicating on 4-20mA signal mode with superimposed HART
CREATION OF SURFACE PRODUCTION FACILITIES (GGS)
AT EAST KHAGORIJAN
Revision Index
DATA SHEET FOR PRESSURE TRANSMITTER
Notes:
1. Documentation required :- Calibration Certificate , Ingress Protection Certificate, Material Certificates to 3.1 as per EN 10204, Hydro test , Explosion proof & weather
proof certificate, Pressure test Procedure/Report , SIL 2 Certificate, Operating & Maintenance Instructions & Spare Parts List.
2. All instruments to be supplied with a SS 316 Name plate with Tag no. permanently inscribed. Tags shall be Permanently secured.
3. All transmitters shall be provided with integral indicator (LCD type) with engineering unit indication.
4. Instrumentation shall meet the Electromagnetic interference requirements according to EN 50081-2 and EN 50082-2.
9. The over-range/static pressure protection of the transmitter shall be 130% of range.
10. Calibration and test certificate to be provided for each instrument.
TITLE ITEM/TAG No. DATA SHEET No.
DATA SHEET FOR PRESSURE TRANSMITTER
PROJECT DESCRIPTION PROJECT NO SHEET REV
05 OF 05 A0
MPC CONTRACTOR CLIENT CONTRACT No. REQUISITION No. SPECIFICATION No.
CLIENT NAME REV No. BY DATE CKD DATE APP. DATE
A0 IMR 29-Nov-18 MV 29-Nov-18 MSR/ VSR 29-Nov-18 ISSUED FOR REVIEW
CLIENT'S REF
-
ORIGINATOR ORIG. DATE
04-Oct-18
UNITS: Pressure: kg/cm2 g Temp: Flow: Gas: MMSCFD Liquid:
1. Mounting Direct/Manifold 9. Zero Suppression N/A
2. Accuracy ± 0.25% of Span or better 10. Zero Elevation N/A
3. Over Pressure Limit * 11. Zero Adjust Location External
4. Ambient Temp. Limit 8 to 38°C 12. Span Adjust Location External
5. Output 4-20 mA DC, 2-wire, HART Protocol with SMART Tr. 13. Enclosure Rating IP 65
6. Power Supply 24 VDC Loop powered 14. Area Classification Zone 2, Gas Group IIA&IIB, Temp. Cl. T3
7. Indicating Yes, LCD in engineering unit 15. Equipment Certification Ex'd'
8. Power consumption * 16. Load Limitation *
1. Service Gauge Pressure Transmitter 11. Housing Material Polyurethane Coated Aluminum
2. Process connetion 1/2" NPT(F) 12. Xmtr Diaphragm. Material SS 316
3. Electrical Connection 1/2" NPT(F) 13. O-Ring Material Glass-Filled PTFE
4. Mounting Bracket Not required 14. Fill Fluid Material N/A
5. Process Seal Type No 15. Diaphragm Seal Material N/A
6. Hydrotest Req'd Yes 16. Capillary Material N/A
7. Diaphragm Seal No 17. Drain/Vent Material SS 316
8. Capillary Length N/A 18. Flange Bolt Material N/A
9. Capillary Fill Fluid N/A 19. Bracket Bolt Material SS 316
10. Drain / Vent 20. Manufacturer *
21. Manifold Model No. *
1) Each instrument shall include a SS tag permanently attached to the instrument using SS screws, SS bolts or ss wire.
2) Painting shall be Manufacturer standard suitable for Hazardous environment.
3) All pressure transmitters shall be provided with 2 valve Manifold and it is to be fitted, tested & supplied along with the Instrument.
4) For General notes refer Notes section.
1 66-PT-6602 17039-EK-P-DW-0206-01 0 - 10 * 2
* To be Provided By Vendor.
CREATION OF SURFACE PRODUCTION FACILITIES (GGS) AT EAST KHAGORIJAN KIP-17039
SEE BELOW TABLE OIL-100-EK-I-DS-0821
m3/hr
IMR
DESCRIPTION
OIL INDIA LIMITED
TBA - - -
Remarks
° C
GENERAL
C O N S T R U C T I O N
NOTES
P&ID Number
Calibrated
Range
kg/cm2 g
Operating Pressure
(Kg/cm2)g
Design Pressure
(Kg/cm2)g
Model
Number
SIL
Rating
Yes (1/4" Drain connection pipe plug
supplied with Manifold)
Design
Temp.
(°C)
S.No. Tag Number Service Description
Effluent Water Transfer
pump outlet5 10 85
Flange
Size/
Rating
Datasheet NumberRev
Code
OIL-100-EK-I-DS-0822 A0 Sheet No.: 02 of 05
SHEET No.
1 COVER SHEET
2 INDEX SHEET
3 REVISION SHEET
4 NOTES SHEET
5 DS - PG
INDEX SHEET
TITLE
CREATION OF SURFACE PRODUCTION
FACILITIES (GGS) AT EAST KHAGORIJAN
Revision Index
DATA SHEET FOR PRESSURE GAUGE
Datasheet NumberRev
Code
OIL-100-EK-I-DS-0822 A0 Sheet No: 03 of 06
REV No. LIST OF PAGES OF UPDATED / MODIFIED SECTIONS, IF ANY
A0 FIRST ISSUE
REVISION RECORD SHEET
PURPOSE
ISSUED FOR REVIEW
CREATION OF SURFACE PRODUCTION
FACILITIES (GGS) AT EAST KHAGORIJAN
Revision Index
DATA SHEET FOR PRESSURE GAUGE
Datasheet Number Rev Code
OIL-100-EK-I-DS-0822 A0 Sheet No: 04 of 05
6. The pressure gauge shall have an over-range protection of at least 130% of maximum working pressure, as minimum.
7. Calibration and test certificate to be provided for each instrument.
8. Painting shall be Manufacturer standard suitable for Hazardous environment.
9. All pressure transmitters shall be provided with 2 valve Manifold and it is to be fitted, tested & supplied along with the Instrument.
10. Valve manifold shall have 1/2" NPT(F) connection on process, gauge and 1/4'' NPT(F) Connection on vent/ drain & Material shall be same as the element material.
11. Gauge construction shall ensure no leakage of process fluid to atmosphere.
12. Vendor to select the filling liquid which shall be compatible with the maximum process temperature.
13. Liquid filled damping shall be provided, suitable fluid to be selected according to the process fluid conditions.
14. Gauge shall be provided with Snubber whereever the service specified is pulsating type (i.e, Pump discharge etc.,) and the MOC shall be same as socket material.
5. Dial markings and dial colour shall be as per IS 3624.
CREATION OF SURFACE PRODUCTION FACILITIES (GGS)
AT EAST KHAGORIJAN
Revision Index
DATA SHEET FOR PRESSURE GAUGE
Notes:
1. Documentation required :- Calibration Certificate , Ingress Protection Certificate, Material Certificates to 3.1 as per EN 10204, Hydro test , Explosion proof & weather
proof certificate, Pressure test Procedure/Report , SIL 2 Certificate, Operating & Maintenance Instructions & Spare Parts List.
2. All instruments to be supplied with a SS 316 Name plate with Tag no. permanently inscribed. Tags shall be Permanently secured.
3. Bourdon tube gauges shall be tested in accordance with of BS EN 837-1.
4. The gauge shall be weather proof to IP 65 as per IEC 60529 / IS 13947, as minimum.
TITLE ITEM/TAG No. DATA SHEET No.
DATA SHEET FOR PRESSURE GAUGE
PROJECT DESCRIPTION PROJECT NO SHEET REV
05 OF 05 A0
MPC CONTRACTOR CLIENT CONTRACT No. REQUISITION No. SPECIFICATION No.
CLIENT NAME REV No. BY DATE CKD DATE APP. DATE
A0 IMR 29-Nov-18 MV 29-Nov-18 MSR/ VSR 29-Nov-18 ISSUED FOR REVIEW
CLIENT'S REF
-
ORIGINATOR ORIG. DATE
04-Oct-18
UNITS: Pressure: kg/cm2 g Temp: Flow: Gas: MMSCFD Liquid:
1. Type Local 16. Socket Material SS 316
2. Style Solid Front 17. Liquid Filled Yes
3. Mounting Direct 18. Fill Fluid Glycerin
4. Dial Size 150 mm (Note-6) 19. Process Connection 1/2" NPT(M)
5. Range Units Kg/cm2g 20. Connnection Location Bottom
6. Accuracy ± 1% of range 21. Enclosure Rating IP 65 (Min)
7. Repeatability Included in Accuracy 22. Press. GaugeManufacturer *
8. Hysteresis Included in Accuracy 23. Press. Gauge Model No. Refer Below
9. Ring Type Cam ring (Bayonet type) 24 Manifold Manufacturer *
10. Blowdown Protection Back 25. Manifold Model No. *
11. Element Type Bourdon Tube 26.
12. Diaphragm Seal Not Required 27.
13. Case Material SS 316 28.
14. Lens Material Lamited Safety Glass 29.
15. Element Material SS 316 30.
1) For General notes refer Notes sheet.
1 66-PI-6601 17039-EK-P-DW-0206-01 0 - 16 *
2 71-PI-7266 17039-EK-P-DW-0217-01 0 - 2 (Hold) *
* To be Provided By Vendor.
85
Flange
Size/
Rating
5 10
FOW+0.07Atm.+Liquid Head
S.No. Tag Number Service Description
Effluent Water Storage
Tank (EK-ABJ-3450) outlet
Fire water Storage Tanks
(EK-ABJ-3110A/B) Inlet80
Remarks
° C
GENERAL
NOTES
P&ID Number
Calibrated
Range
Kg/ Cm2 g
Operating Pressure
(Kg/cm2)
Design Pressure
(Kg/cm2)
Model
Number
Notes &
Options
Design
Temp.
(°C)
CREATION OF SURFACE PRODUCTION FACILITIES (GGS) AT EAST KHAGORIJAN KIP-17039
SEE BELOW TABLE OIL-100-EK-I-DS-0822
m3/hr
IMR
DESCRIPTION
OIL INDIA LIMITED
TBA - - -
Datasheet NumberRev
Code
OIL-100-EK-I-DS-0823 A0 Sheet No.: 02 of 05
SHEET No.
1 COVER SHEET
2 INDEX SHEET
3 REVISION SHEET
4 NOTES SHEET
5 DS - TG
INDEX SHEET
TITLE
CREATION OF SURFACE PRODUCTION
FACILITIES (GGS) AT EAST KHAGORIJAN
Revision Index
DATA SHEET FOR TEMPERATURE GAUGE WITH
THERMOWELL
Datasheet NumberRev
Code
OIL-100-EK-I-DS-0823 A0 Sheet No: 03 of 05
REV No. LIST OF PAGES OF UPDATED / MODIFIED SECTIONS, IF ANY
A0 FIRST ISSUE
REVISION RECORD SHEET
PURPOSE
ISSUED FOR REVIEW
CREATION OF SURFACE PRODUCTION
FACILITIES (GGS) AT EAST KHAGORIJAN
Revision Index
DATA SHEET FOR TEMPERATURE GAUGE WITH
THERMOWELL
Datasheet Number Rev Code
OIL-100-EK-I-DS-0823 A0 Sheet No: 04 of 05
6. The gauge shall be weatherproof to IP65 as per IEC 60529/ IS 13947 as a minimum.
5. Temperature gauges shall be of the separate socket type suitable for well installation.
CREATION OF SURFACE PRODUCTION FACILITIES (GGS)
AT EAST KHAGORIJAN
Revision Index
DATA SHEET FOR TEMPERATURE GAUGE WITH THERMOWELL
Notes:
1. Documentation required :- Calibration Certificate , Ingress Protection Certificate, Material Certificates to 3.1 as per EN 10204, Hydro test , Explosion proof & weather
proof certificate, Pressure test Procedure/Report , SIL 2 Certificate, Operating & Maintenance Instructions & Spare Parts List.
2. All instruments to be supplied with a SS 316 Name plate with Tag no. permanently inscribed. Tags shall be Permanently secured.
3. Vendor shall perform wake frequency calculations (WFC) for all thermowells according to ASME PTC 19.3 and report to be submitted.
4. Flange finish shall be in accordance with ANSI B16.5, for Raised Face (RF) flanges and shall be smooth finish to 125-250 AARH and 63 AARH for Ring type joint (RTJ) .
TITLE ITEM/TAG No. DATA SHEET No.
DATA SHEET FOR TEMPERATURE GAUGE WITH THERMOWELL
PROJECT NO SHEET REV
05 OF 05 A0
CONTRACTOR CLIENT CONTRACT No. REQUISITION No. SPECIFICATION No.
CLIENT NAME REV No. BY DATE CKD DATE APP. DATE
A0 IMR 29-Nov-18 MV 29-Nov-18 MSR/ VSR 29-Nov-18 ISSUED FOR REVIEW
CLIENT'S REF
-
ORIGINATOR ORIG. DATE
14-Sep-18
UNITS: Pressure: kg/cm2 g Temp: Flow: Gas: MMSCFD Liquid:
1. Type Bi-Metal 12. Stem Material SS 316
2. Stem Diameter To suit Thermowell dia. 13. Case Material SS 316
3. Dial Size/ Color 150mm/ White with Black Markings 14. Lens Material Shatter-Proof Glass
4. Range Units °C 15. Hermetically Sealed Yes
5. Stem Type Threaded & Union 16. Liquid Filled No
6. Stem/ Union Size 1/2" NPT 17. Capillary Connection N/A
7. External Adjustment Yes 18. Capillary Material N/A
8. Orientation Adjutable, Everyangle 19. Manufacturer *
9. Weather Protection IP 66 (Note-6)
10. Accuracy ± 1% of Span
11. Over range Protection Required, 130% of Max. range
1. Included Yes 7. Bore Diameter 0.26"
2. Material 316 stainless steel 8. Element Connection 1/2" NPT
3. Construction Solid drilled bar-stock 9. Process Connection See below
1) Each instrument shall include a SS tag permanently attached to the instrument using SS screws, SS bolts or ss wire.
2) Thermometer & Thermowell assembled together as one unit.
3) Vendor will be responsible for chosing model numbers.
4) Thermowell Tag to be same as Temperature Gauge Tag.
5) "U" Length includes Nozzle projection length.
6) It is Vendor's responsibility to ensure sensor length matches the specified U Dimensions.
120-TI-1388/
20-TW-138817039-EK-P-DW-0202-13 0 - 100
(27-50)/
90FOW+0.07 NA 500 0.1 150 *
220-TI-0989/
20-TW-098917039-EK-P-DW-0203-10 0 - 100 55/ 90 FOW+0.07 NA 500 0.1 150 *
320-TI-0997/
20-TW-099717039-EK-P-DW-0203-11 0 - 100 55/ 90 FOW+0.07 NA 500 0.1 150 *
444-TI-8043A/
44-TW-8043A17039-EK-P-DW-0203-21 0 - 100 55/ 90 FOW+0.07 NA 500 0.1 150 *
544-TI-8043B/
44-TW-8043B17039-EK-P-DW-0203-21 0 - 100 55/ 90 FOW+0.07 NA 500 0.1 150 *
620-TI-0430/
20-TW-043017039-EK-P-DW-0203-14 0 - 100 55/ 90 FOW+0.07 NA 500 0.1 150 *
766-TI-3521/
66-TI-352117039-EK-P-DW-0206-01 0 - 100 51/ 85 FOW+0.07 NA 500 0.1 150 *
866-TG-6636A/
66-TG-6636A 17039-EK-P-DW-0206-02 0 - 100 51/ 85 FOW+0.07 NA 500 0.1 150 *
966-TG-6636B/
66-TG-6636B17039-EK-P-DW-0206-02 0 - 100 51/ 85 FOW+0.07 NA 500 0.1 150 *
1066-TI-6620/
66-TI-662017039-EK-P-DW-0206-04 0 - 100 55/ 90 FOW+0.07 NA 500 0.1 150 *
1166-TG-6637/
66-TG-663717039-EK-P-DW-0206-06 0 - 100 51/ 85 FOW+0.07 NA 500 0.1 150 *
* To be Provided By Vendor.
Tag Number Service Description
PW Fr. Crude Dehydrator (EK-
MBM-A-1120B)
Treated Crude Storage Tank
(EK-BBJ-1120A)
2"/
150# RF
2"/
150# RF
PW Fr. Crude Dehydrator (EK-
MBM-A-1120A)
2"/
150# RF
Treated Crude Storage Tank
(EK-BBJ-1120B)
Crude Oil Test Tank
(EK-BBJ-1111)
2"/
150# RF
Offspec Crude Storage Tank
(EK-BBJ-1120B)
Effluent Water Storage Tank
(EK-ABJ-3454 A/B)
2"/
150# RF
2"/
150# RF
2"/
150# RF
2"/
150# RF
2"/
150# RF
2"/
150# RF
2"/
150# RF
Skim Oil Tank
(EK-ABJ-3452)
Clarified Water Storage Tank
(EK-ABJ-3451B)
Offspec Effluent Water
Storage Tank (EK-ABJ-3453)
Clarified Water Storage Tank
(EK-ABJ-3451A)
Remarks
Design
Pressure
Kg/cm2g
° C
THERMOMETER
NOTES
THERMOWELL
Model
Number
Nozzle
Projetion
Length
(mm)
Line
InsulationP&ID Number
Calibrated
Range
Deg.C
Temp.
(Normal/
Design)
Deg.C
Velocity
(m/s)
T/W
"U"/ Lag.
mm
Flange
Size &
Rating
S.No.
CREATION OF SURFACE PRODUCTION FACILITIES (GGS) AT EAST KHAGORIJAN KIP-17039
SEE BELOW TABLE OIL-100-EK-I-DS-0823
m3/hr
IMR
DESCRIPTION
OIL INDIA LIMITED
TBA - - -
PROJECT DESCRIPTION
Datasheet NumberRev
Code
OIL-100-EK-I-DS-0824 A0 Sheet No.: 02 of 05
SHEET No.
1 COVER SHEET
2 INDEX SHEET
3 REVISION SHEET
4 NOTES SHEET
5 DS - FT (Mag.type)
INDEX SHEET
TITLE
CREATION OF SURFACE PRODUCTION
FACILITIES (GGS) AT EAST KAHGORIJAN
Revision Index
DATA SHEET FOR ELECTROMAGNETIC FLOW METER
Datasheet NumberRev
Code
OIL-100-EK-I-DS-0824 A0 Sheet No: 03 of 05
REV No. LIST OF PAGES OF UPDATED / MODIFIED SECTIONS, IF ANY
A0 FIRST ISSUE
REVISION RECORD SHEET
PURPOSE
ISSUED FOR REVIEW
CREATION OF SURFACE PRODUCTION
FACILITIES (GGS) AT EAST KAHGORIJAN
Revision Index
DATA SHEET FOR ELECTROMAGNETIC FLOW METER
Datasheet Number Rev Code
OIL-100-EK-I-DS-0824 A0 Sheet No: 04 of 05
9. The over-range/static pressure protection of the transmitter shall be 130% of range.
10. Calibration and test certificate to be provided for each instrument.
11. The flow direction shall be clearly stamped or cast on the body to avoid polarity errors.
12. Meter shall have forward & reverse measurement functions and reverse flow shall be confirmed by status output / indication.
13. The Electro-Magnetic Meter’s field coils shall be hermetically sealed. Coil insulation shall be class F suitable for high temperature. Suitable grounding type system
and material shall be selected for the meter.
14. Vendor shall indicate the power supply requirements and furnish the power consumption for the meter (sensor, transmitter, display, etc.) along with
the sizing calculations for the selected meter.
15. Standard Signal types and communication protocols shall be offered. Appropriate EMI / RFI protection for the meter shall be considered.
16. Bolted coil housing with rubber or plastic gaskets is not acceptable.
6. All fastners including stud-bolts and nuts material shall be A193Gr.B7M / A194Gr.2HM with Zinc coated (hot dipped) according to ASTM A153.
6. Flange finish shall be in accordance with ANSI B16.5, for Raised Face (RF) flanges and shall be smooth finish to 125-250 AARH.
7. The housing of all transmitters shall be SS 316 minimum.
8. Transmitter shall be provided with two(2) cable entry of size 1/2" NPT(F). Unused cable entries shall be plugged with ex-proof SS certified plugs.
17. Tube liners shall be selected to meet the process requirement and shall be proven for the application.
5. All the electrical cables on the transmitters and sensors terminate to terminal blocks,flying leads are not allowed.
CREATION OF SURFACE PRODUCTION FACILITIES (GGS)
AT EAST KAHGORIJAN
Revision Index
DATA SHEET FOR ELECTROMAGNETIC FLOW METER
Notes:
1. Documentation required :- Calibration Certificate , Ingress Protection Certificate, Material Certificates to 3.1 as per EN 10204, Hydro test , Explosion proof & weather
proof certificate, Pressure test Procedure/Report , Operating & Maintenance Instructions & Spare Parts List.
2. All instruments to be supplied with a SS 316 Name plate with Tag no. permanently inscribed. Tags shall be Permanently secured.
3. All transmitters shall be provided with integral indicator (LCD type) with engineering unit indication.
4. Instrumentation shall meet the Electromagnetic interference requirements according to EN 50081-2 and EN 50082-2.
TITLE ITEM/TAG No. DATA SHEET No.
DATA SHEET FOR ELECTROMAGNETIC FLOW METER
PROJECT DESCRIPTION PROJECT No. SHEET REV
CREATION OF SURFACE PRODUCTION FACILITIES (GGS) AT EAST KAHGORIJAN 05 OF 05 A0
MPC CONTRACTOR SUPPLIET DOC.No. PURCHASE ORDER No. SPECIFICATION No.
TBA
CLIENT NAME REV No. BY DATE CKD DATE APP. DATE
OIL INDIA LIMITED A0 IMR 29-11-18 MV 29-11-18 MSR/ VSR 29-11-18
CLIENT DOC.No.:
-
ORIGINATOR ORIG. DATE
5 October 2018
UNITS:- Pressure bar g kg/cm2 g kPa g psig Flow : Gas MMSCFD MMSCMD Sm
3/hr kg/hr
Temp 0 C
0 F Liquid m
3/hr kg/hr USgpm bpd
1 TAG NO.
2 SERVICE
GENERAL 3 LINE No.
4 P & ID No.
5 LINE SIZE / SCH
6
7 FLUID
8
9 FLOW.: MIN. NORM. MAX. 1108 KPD
10 TEMP.: MIN. NORM. MAX. 51
FLUID DATA 11 PRESS.: MIN. NORM. MAX.
12
13 VACCUM POSSIBILITY
14 TEMP 85
15
16 VISCOSITY (cP)
17 PRESSURE DROP
18 METER RANGE
19 METER SIZE
20 TUBE MATERIAL
21 LINER MATERIAL
22 ELECTRODE TYPE
23 ELECTRODE MATERIAL
METER 24 METER CASING
25 POWER SUPPLY
26 GROUNDING,TYPE & MATERIAL
27 ENCLOSURE CLASS
28 CONNECTION
29 MATERIAL
30
31 ACCURACY ±0.1%
32 RANGEABILITY
33 FUNCTION
34 MOUNTING
35 ENCLOSUER CLASS
36 LENGTH SIGNAL CABLE
TRANSMITTER 37 SPAN ADJUSTMENT
38 POWER SUPPLY
39 TRANSMITTER OUTPUT
40 DISPLAY
41 INTEGRATOR
42
43 -
44 RATING
45 ACTION
46 MANUFACTURER
OPTIONS 47 METER MODEL No.
48 TRANSMITTER MODEL No.
NOTES:-
REFER NOTES SHEET
*
* TO BE SUPPLIED BY THE SCOPE OF VENDOR.
*
*
-
-
ELECTRICAL CONNECTION ISO M20 X 1.5 (2 No's)
ALARM
FORM -
LOCAL LCD DISPLAY
-
24 VDC, External
4-20 mA -ISOLATED OUTPUT (HART)
-
-
INTEGRAL WITH METER
IEC Ex'ia' / IP 65
-
TRANSMISSION & INDICATION
AREA CLASSIFICATION Zone 2, Gas Group IIA&IIB, Temp. Cl. T3
REPEATABILITY ± 0.5% OF FLOW
TYPE FLANGED / 150# RF
ASTM CS, A-105
2-RING's & SS316
Ex'ia' / IP 65
SS 316
24 VDC, External
STD, 2 No's MEASUREMENT ELECTRODE
(Note-12&13)
SS 316
SS 316
PTFE
TBA
4" *
0.54
MINIMUM
DESIGN: PRESS. 10
DENSITY/SPEC.GRAV (kg/m3) 1000
MIN.FLUID CONDUCTIVITY (S m-1)
MAX. VELOCITY ( m/sec) 1
LINE MATERIAL ASTM A 106 Gr.B
OFF-SPEC EFFLUENT WATER
17039-EK-P-DW-0206-06
4"/ Sch. STD
4"-WE-66-6659-AC01
66-FT-6635
IMR
DESCRIPTION
ISSUED FOR REVIEW
Off-Spec Effluent water Transfer Pumps
(EK-PBA-3456 A/B) Discharge
AS BELOW OIL-100-EK-I-DS-0824
KIP-17039
- - -
Datasheet NumberRev
Code
OIL-100-EK-I-DS-0825 A0 Sheet No.: 02 of 05
SHEET No.
1 COVER SHEET
2 INDEX SHEET
3 REVISION SHEET
4 NOTES SHEET
5 DATA SHEET FOR DP TYPE FLOW INDICATORS
INDEX SHEET
TITLE
CREATION OF SURFACE PRODUCTION
FACILITIES (GGS) AT EAST KHAGORIJAN
Revision Index
DATA SHEET FOR DP TYPE FLOW INDICATORS
Datasheet NumberRev
Code
OIL-100-EK-I-DS-0825 A0 Sheet No: 03 of 06
REV No. LIST OF PAGES OF UPDATED / MODIFIED SECTIONS, IF ANY
A0 FIRST ISSUE
REVISION RECORD SHEET
PURPOSE
ISSUED FOR REVIEW
CREATION OF SURFACE PRODUCTION
FACILITIES (GGS) AT EAST KHAGORIJAN
Revision Index
DATA SHEET FOR DP TYPE FLOW INDICATORS
Datasheet Number Rev Code
OIL-100-EK-I-DS-0825 A0 Sheet No: 04 of 05
6. THE DIAL COVER SHALL BE MADE OUT OF SHATTER PROOF GLASS SHEET OF THICKNESS WITH MINIMUM 3.0 MM.
7. VALVE MANIFOLD SHALL HAVE 1/2" NPT(F) CONNECTION ON PROCESS, GAUGE AND 1/4'' NPT(F) CONNECTION ON VENT/ DRAIN & MATERIAL SHALL BE SAME AS
THE ELEMENT MATERIAL.
8. GAUGE CONSTRUCTION SHALL ENSURE NO LEAKAGE OF PROCESS FLUID TO ATMOSPHERE.
9. VENDOR TO SELECT THE FILLING LIQUID WHICH SHALL BE COMPATIBLE WITH THE MAXIMUM PROCESS TEMPERATURE.
5. DIAL MARKINGS AND DIAL COLOUR SHALL BE AS PER IS 3624.
CREATION OF SURFACE PRODUCTION FACILITIES (GGS) AT EAST
KHAGORIJAN
Revision Index
DATA SHEET FOR DP TYPE FLOW INDICATORS
NOTES:
1. DOCUMENTATION REQUIRED :- CALIBRATION CERTIFICATE, INGRESS PROTECTION CERTIFICATE, MATERIAL CERTIFICATES TO 3.1 AS PER EN 10204,
HYDRO TEST, WEATHER PROOF CERTIFICATE, PRESSURE TEST PROCEDURE/REPORT, OPERATING & MAINTENANCE INSTRUCTIONS & SPARE PARTS LIST.
2. ALL INSTRUMENTS TO BE SUPPLIED WITH A SS 316 NAME PLATE WITH TAG NO. PERMANENTLY INSCRIBED. TAGS SHALL BE PERMANENTLY SECURED.
3. DP TYPE FLOW INDICATOR SHALL BE PROVIDED WITH A VISIBLE POINTER STOP TO RESTRICT THE UPPER LIMIT OF THE POINTER TRAVEL.
4. THE GAUGE SHALL BE WEATHER PROOF TO IP 65 AS PER IEC 60529 / IS 13947, AS MINIMUM.
TITLE ITEM/TAG No. DATA SHEET No.
DATA SHEET FOR DP TYPE FLOW INDICATORS
PROJECT DESCRIPTION PROJECT NO REV
05 OF 05 A0
MPC CONTRACTOR REQUISITION No. SPECIFICATION No.
CLIENT NAME REV No. BY DATE CKD DATE APP. DATE
A0 VS 29-Nov-18 PGN 29-Nov-18 MV 29-Nov-18 ISSUED FOR REVIEW
CLIENT'S REF
-
ORIGINATOR ORIG. DATE
29-Nov-18
UNITS: PRESSURE: kg/cm2 g TEMP :
1. TYPE DIRECT READING 16. PRESS. ELEMENT DIAPHRAGM
2. MOUNTING SURFACE 17. MOVEMENT MATL. SS316
3. DIAL SIZE DIAMETER: 150mm 18. ELEMENT MATL. SS316
4. COLOUR WHITE WITH BLACK LETTERS 19. SOCKET MATL. SS316
5. CASE SS316 20. CONNECTION: 1/2" NPTM
6. RING SCREWED TYPE 21. OVER RANGE PROTECTION 130% OF MAX PRESS RANGE
7. SAFETY BLOW-OUT BACK 22. ACCURACY ±1% OF FSD
8. PROTECTION SOLID FRONT 23. MANIFOLD MANUFACTURER *
9. LENS SHATTER PROOF GLASS 24 MANIFOLD MODEL NO *
10. MANIFOLD TYPE 5 - VALVE MANIFOLD MATERIAL SS 316 25.
11. MOUNTING BRACKET YOKE MOUNTING BRACKET, SS 316 FOR 2"NB PIPE STAND 26.
12. LQUID FILLED YES 27.
13. FILL FLUID SILICONE FILLED 28.
14. WEATHER PROTECTION IP 65 29.
15. MANUFACTURER * 30.
1) For General notes refer Notes sheet.
1 71-FI-7266 17039-EK-P-DW-0217-01 * 0-450 0 - 250 41 -
* To be Provided By Vendor.
80FOW
Operating
Temp. (°C)
ATM
8"-WF-71-7108-AG01 /FIRE
WATER FROM FIRE WATER
DISCHARGE PUMP TO FIRE
WATER STORAGE TANK
Remarks
° C
GENERAL
NOTES
P&ID Number
Instrument
Range
kg/cm2
Operating Pressure
(Kg/cm2)
Design
Pressure
(Kg/cm2)
Design Temp.
(°C)
Flow Range
m3/hr
Calibrated
Range
mbar
S.No. Tag Number Line Number / Service
CREATION OF SURFACE PRODUCTION FACILITIES (GGS) AT EAST KHAGORIJAN KIP-17039
SEE BELOW TABLE OIL-100-EK-I-DS-0825
VS
DESCRIPTION
OIL INDIA LIMITED
- -
CLIENT CONTRACT No.
TBA -
SHEET
Datasheet NumberRev
Code
OIL-100-EK-I-DS-0826 A0 SHEET 02 OF 10
SHEET No. TITLE
1 COVER SHEET
2 INDEX SHEET
3 REVISION SHEET
4 NOTES SHEET
5 DATA SHEET FOR RADAR TYPE LEVEL TRANSMITTER
6 DATA SHEET FOR RADAR TYPE LEVEL TRANSMITTER
7 DATA SHEET FOR RADAR TYPE LEVEL TRANSMITTER
8 DATA SHEET FOR RADAR TYPE LEVEL TRANSMITTER
INDEX SHEET
CREATION OF SURFACE PRODUCTION FACILITIES
(GGS) AT EAST KHAGORIJAN
Revision Index
DATA SHEET FOR RADAR TYPE LEVEL TRANSMITTER
Datasheet NumberRev
Code
OIL-100-EK-I-DS-0826 A0 SHEET 03 OF 10
REV No. LIST OF PAGES OF UPDATED / MODIFIED SECTIONS, IF ANY
FIRST ISSUE
PURPOSE
A0 ISSUED FOR REVIEW
REVISION RECORD SHEET
CREATION OF SURFACE PRODUCTION FACILITIES
(GGS) AT EAST KHAGORIJAN
Revision Index
DATA SHEET FOR RADAR TYPE LEVEL TRANSMITTER
Datasheet NumberRev
Code
OIL-100-EK-I-DS-0826 A0Sheet No.: 04 of 10
1.
2. Radar type level transmitter shall be provided with 1 mm thick, 30mm x 75mm SS 316 tag plate, inscribed with tag number engraved or
embossed in 5mm high and 0.3mm deep bold characters and black paint filled. The tags shall be mounted on or adjacent to the associated
instrument and either fixed with stainless steel screws or attached with stainless steel wire.
3. All stud bolt material shall be ASTM A 193 Gr. B7 / ASME B16.5 (Hot dip galvanized).
4. Transmitter shall be provided with dual cable entries. Unused cable entries shall be provided with explosion proof plugs of SS 316.
5. All weldings and castings (if any) shall be 100% radiographed.
6. Transmitters shall employ intelligent digital signal processingtechniques to filter out false echo signals.
7. Flange finish shall be in accordance with ANSI B16.5, For raised face (RF) flanges and shall be smooth finish to 125-250AARH
8. Instruments shall meet electromagnetic compatibility requirements according to IEC 61000.
9.
Hold 1:
1.
REFERENCE DOCUMENTS:
17039-EK-I-DB-8001_Functional specification for package instruments_Rev C
Documentation required :- Calibration certificate, Hydro test report, Material certificates to 3.1 as per EN10204, weather proof to
All instrumentation must be certified by a recognised european certification authority such as ATEX/FM/UL/BASEEFA/CMRI/PTB
Pressure data shall be updated later.
IP65 certificate by ATEX or Equivalent body, Pressure test procedure/Report, NDT procedure / Report, GAD Wiring diagram, Operating and
Maintenance Instructions & Spare Parts List.
Notes Sheet
CREATION OF SURFACE PRODUCTION FACILITIES
(GGS) AT EAST KHAGORIJAN
Revision Index
DATA SHEET FOR RADAR TYPE LEVEL
TRANSMITTER
TITLE
DATA SHEET FOR RADAR TYPE LEVEL TRANSMITTER
PROJECT DESCRIPTION
CREATION OF SURFACE PRODUCTION FACILITIES (GGS) AT EAST KHAGORIJAN 05 OF 10
EPC CONTRACTOR
TBA
REV No. BY DATE CKD DATE APP. DATE
OIL INDIA LIMITED A0 VS 30-Nov-18 PG 30-Nov-18 MV 30-Nov-18
ORIG. DATE
30-Nov-18
UNITS:- Pressure bar g kg/cm2 g kPa g psig LEVEL : mm
Temp 0 C
0 F
1TAG NO.
20-LIT-1382 20-LT-0986A
2SERVICE
CRUDE OIL TEST TANK CRUDE OIL TEST TANK TREATED CRUDE STORAGE TANK
3P&ID NO.
17039-EK-P-DW-0202-13 17039-EK-P-DW-0202-13 17039-EK-P-DW-0203-10
4VESSEL SIZE
6000 (I/D) X 8000 (H) 6000 (I/D) X 8000 (H) 9600 (I/D) X 14000 (H)
5
VESSEL MATERIAL
6AREA CLASSIFICATION
ZONE - 2, Gr IIA & IIB, T3 ZONE - 2, Gr IIA & IIB, T3 ZONE - 2, Gr IIA & IIB, T3
7TANK NO
EK-BBJ-1111 EK-BBJ-1111 EK-BBJ-1120A
8 UPPER FLUID / PHASE CRUDE OIL / LIQUID CRUDE OIL / LIQUID CRUDE OIL / LIQUID
9 LOWER FLUID / PHASE
10 INTERFACE
11 SUSPENDED SOLIDS
12PRESSURE (MAX. / NORM. / MIN. )
13TEMPERATURE (MAX. / NORM. / MIN.)
14DESIGN (PRESSURE / TEMPERATURE)
15 SPECIFIC GRAVITY
16 DENSITY UPPER LOWER Kg/m3
17 FLUID VISCOSITY UPPER LOWER cP
18 DIELECTRIC CONSTANT UPPER/LOWER
19 W/m-K
20 INTERNAL / EXTERNAL
21 CAGE MATERIAL
22 OVER ALL C-C C-C1
23 CONNECTION SIZE AND RATING
24 CAGE ORIENTATION / ROTATABLE HEAD
25 CAGE TO HEAD FLANGE SIZE & RATING
26 CAGE TO HEAD GASKET / BOLTING
27 DRAIN / VENT CONN. SIZE & RATING
28 COOLING EXTENSION
29 ELECTRICAL HEAT TRACING
30 STAND PIPE
31TYPE / MODEL Encapsulated Horn / * Encapsulated Horn / * Encapsulated Horn / *
32PROCESS CONNECTION
33MOC SS 316 SS 316 SS 316
34ANTENNA LENGTH DIAMETER
35MOUNTING POSITION / MOUNTING LOCATION
40 TYPE / PRINCIPLE
41 MOUNTING Direct on vessel Direct on vessel Direct on vessel
42 ACCURACY / INTER FACE ACCURACY ± 0.03% of measured distance / * ± 0.03% of measured distance / * ± 0.03% of measured distance / *
43 REPEATABILITY ± 1mm ± 1mm ± 1mm
44 PROTECTION CLASS/ENCLOSURE IP 65/ Ex'ia' IP 65/ Ex'ia' IP 65/ Ex'ia'
45 POWER SUPPLY 24VDC loop powered with HART 24VDC loop powered with HART 24VDC loop powered with HART
46 OUTPUT 4 - 20 mA 4 - 20 mA 4 - 20 mA
47 PROCESS CONNECTION AND RATING(MOC) 8", 150# RF, SS 316 8", 150# RF, SS 316 8", 150# RF, SS 316
48 CALIBRATION RANGE MIN. / MAX. (%)
49 INSTRUMENT RANGE MIN. / MAX. mm(%)
50 CABLE ENTRY | CABLE GLAND WITH PLUG SIDE ENTRY 1/2" NPT(F) w/ PLUG SIDE ENTRY 1/2" NPT(F) w/ PLUG SIDE ENTRY 1/2" NPT(F) w/ PLUG
51 LOCAL INDICATION / DISPLAY ENGG. UNIT LCD mm (%) LCD LCD
52 SIL CERTIFICATION SIL-2 SIL-2 SIL-2
53 MEASURING RANGE (FROM TANK BOTTOM) YES YES YES
54 MODEL NO. FOR SENSOR * * *
55 MODEL NO. FOR TRANSMITTTER * * *
56 MANUFACTURER * * *
57NOTES:- REFER NOTES SHEET. * To be Furnished by Vendor.
mm (%)
DESCRIPTION
20-ILT-1383
mm (%)
VESSEL TOP
*
Non Contact Type /
Pulse-burst radar technology
0-100%
0-8000mm (0-100)%
*
Non Contact Type /
Pulse-burst radar technology
0-100%
0-14000 mm (0-100)%
**
VERTICALVERTICAL VESSEL TOP
***
VESSEL TOP
0-8000mm (0-100)%
0-100%
ITEM/TAG No. DATA SHEET No.
REFER BELOW OIL-100-EK-I-DS-0826
-
PROJECT NO.
KIP-17039
SHEET REV
A0
17039-EK-I-DB-8001
SPECIFICATION No.CLIENT CONTRACT No. REQUISITION No.
-
VS
ORIGINATOR
CLIENT NAME
Client Document No.
-
Issued For Review
CA
GE
C-C2
GEN
ER
AL
SER
VIC
E C
ON
DITIO
NS
THERMAL CONDUCTIVITY LIQUID
(UPPER / LOWER)
937.2 - 940.7
15.714 - 22.05
1.4
0.248 - 0.643
OTH
ER
SA
NTEN
NA
*
Non Contact Type /
Pulse-burst radar technology
TR
AN
SM
ITTER
VERTICAL
*
15.714 - 22.05
1.4
0.248 - 0.643
ATM
AMB
FOL+0.07 / 90
ATM
AMB
FOL+0.07 / 90
3.85
1.4
0.12
ATM
AMB
FOL+0.07 / 90
SHELL / BOTTOM :CARBON STEEL + 3mm
CA,
ROOF (CS + 1.5mm)
SHELL / BOTTOM :CARBON STEEL +
3mm CA,
ROOF (CS + 1.5mm)
SHELL / BOTTOM :CARBON STEEL +
3mm CA,
ROOF (CS + 1.5mm)
899.8937.2 - 940.7
TITLE
DATA SHEET FOR RADAR TYPE LEVEL TRANSMITTER
PROJECT DESCRIPTION
CREATION OF SURFACE PRODUCTION FACILITIES (GGS) AT EAST KHAGORIJAN 6 OF 10
EPC CONTRACTOR
TBA
REV No. BY DATE CKD DATE APP. DATE
OIL INDIA LIMITED A0 VS 30-Nov-18 PG 30-Nov-18 MV 30-Nov-18
ORIG. DATE
30-Nov-18
UNITS:- Pressure bar g kg/cm2 g kPa g psig level: mm
Temp 0 C
0 F
1TAG NO.
20-LT-0988A 20-LT-0988B
2SERVICE
TREATED CRUDE STORAGE TANK TREATED CRUDE STORAGE TANK TREATED CRUDE STORAGE TANK
3P&ID NO.
17039-EK-P-DW-0203-10 17039-EK-P-DW-0203-11 17039-EK-P-DW-0203-11
4VESSEL SIZE
9600 (I/D) X 14000 (H) 9600 (I/D) X 14000 (H) 9600 (I/D) X 14000 (H)
5VESSEL MATERIAL
CARBON STEEL + 3mm CA CARBON STEEL + 3mm CA CARBON STEEL + 3mm CA
6AREA CLASSIFICATION
ZONE - 2, Gr IIA & IIB, T3 ZONE - 2, Gr IIA & IIB, T3 ZONE - 2, Gr IIA & IIB, T3
7TANK NO
EK-BBJ-1120A EK-BBJ-1120B EK-BBJ-1120B
8 UPPER FLUID / PHASE CRUDE OIL / LIQUID CRUDE OIL / LIQUID CRUDE OIL / LIQUID
9 LOWER FLUID / PHASE
10 INTERFACE
11 SUSPENDED SOLIDS
12PRESSURE (MAX. / NORM. / MIN. )
13TEMPERATURE (MAX. / NORM. / MIN.)
14DESIGN (PRESSURE / TEMPERATURE)
15 SPECIFIC GRAVITY
16 DENSITY UPPER LOWER Kg/m3
17 FLUID VISCOSITY UPPER LOWER cP
18 DIELECTRIC CONSTANT UPPER/LOWER
19 W/m-K
20 INTERNAL / EXTERNAL
21 CAGE MATERIAL
22 OVER ALL C-C C-C1
23 CONNECTION SIZE AND RATING
24 CAGE ORIENTATION / ROTATABLE HEAD
25 CAGE TO HEAD FLANGE SIZE & RATING
26 CAGE TO HEAD GASKET / BOLTING
27 DRAIN / VENT CONN. SIZE & RATING
28 COOLING EXTENSION
29 ELECTRICAL HEAT TRACING
30 STAND PIPE
31TYPE / MODEL Encapsulated Horn / * Encapsulated Horn / * Encapsulated Horn / *
32PROCESS CONNECTION
33MOC SS 316 SS 316 SS 316
34ANTENNA LENGTH DIAMETER
35MOUNTING POSITION / MOUNTING LOCATION
40 TYPE / PRINCIPLE
41 MOUNTING Direct on vessel Direct on vessel Direct on vessel
42 ACCURACY / INTER FACE ACCURACY ± 0.03% of measured distance / * ± 0.03% of measured distance / * ± 0.03% of measured distance / *
43 REPEATABILITY ± 1mm ± 1mm ± 1mm
44 PROTECTION CLASS/ENCLOSURE IP 65/ Ex'ia' IP 65/ Ex'ia' IP 65/ Ex'ia'
45 POWER SUPPLY 24VDC loop powered with HART 24VDC loop powered with HART 24VDC loop powered with HART
46 OUTPUT 4 - 20 mA 4 - 20 mA 4 - 20 mA
47 PROCESS CONNECTION AND RATING(MOC) 8", 150# RF, SS 316 8", 150# RF, SS 316 8", 150# RF, SS 316
48 CALIBRATION RANGE MIN. / MAX. (%)
49 INSTRUMENT RANGE MIN. / MAX. mm(%)
50 CABLE ENTRY | CABLE GLAND WITH PLUG SIDE ENTRY 1/2" NPT(F) w/ PLUG SIDE ENTRY 1/2" NPT(F) w/ PLUG SIDE ENTRY 1/2" NPT(F) w/ PLUG
51 LOCAL INDICATION / DISPLAY ENGG. UNIT LCD LCD LCD
52 SIL CERTIFICATION SIL-2 SIL-2 SIL-2
53 MEASURING RANGE (FROM TANK BOTTOM) YES YES YES
54 MODEL NO. FOR SENSOR * * *
55 MODEL NO. FOR TRANSMITTTER * * *
56 MANUFACTURER * * *
57NOTES:- REFER NOTES SHEET. * To be Furnished by Vendor.
0-100% 0-100% 0-100%
OTH
ER
S
mm (%)
TR
AN
SM
ITTER
Non Contact Type /
Pulse-burst radar technology
0-14000 mm (0-100)% 0-14000 mm (0-100)% 0-14000 mm (0-100)%
mm (%) mm (%)
VESSEL TOP
Non Contact Type /
Pulse-burst radar technology
Non Contact Type /
Pulse-burst radar technology
AN
TEN
NA
* * *
**
**
**
VERTICAL VESSEL TOP VERTICAL VESSEL TOP VERTICAL
GEN
ER
AL
20-LT-0986B
SER
VIC
E C
ON
DITIO
NS
THERMAL CONDUCTIVITY LIQUID (UPPER /
LOWER)
1.4
0.12
ATM
AMB
FOL+0.07 / 90
899.8
3.85
1.4
CA
GE
C-C2
ORIGINATOR
VS
ATM
AMB
FOL+0.07 / 90
899.8
3.85
CLIENT NAME
Issued For Review
Client Document No.
-
DESCRIPTION
- - 17039-EK-I-DB-8001
ITEM/TAG No. DATA SHEET No.
REFER BELOW OIL-100-EK-I-DS-0826
PROJECT NO. SHEET REV
KIP-17039 A0
CLIENT CONTRACT No. REQUISITION No. SPECIFICATION No.
0.12
ATM
AMB
FOL+0.07 / 90
899.8
3.85
1.4
0.12
TITLE
DATA SHEET FOR RADAR TYPE LEVEL TRANSMITTER
PROJECT DESCRIPTION
CREATION OF SURFACE PRODUCTION FACILITIES (GGS) AT EAST KHAGORIJAN 7 OF 10
EPC CONTRACTOR
TBA
REV No. BY DATE CKD DATE APP. DATE
OIL INDIA LIMITED A0 VS 30-Nov-18 PG 30-Nov-18 MV 30-Nov-18
ORIG. DATE
30-Nov-18
UNITS:- Pressure bar g kg/cm2 g kPa g psig Level: mm
Temp 0 C
0 F
1TAG NO.
20-LT-0423 20-LT-0424 66-LIT-3510
2SERVICE
OFFSPEC CRUDE STORAGE TANK OFFSPEC CRUDE STORAGE TANK EFFLUENT WATER
3P&ID NO.
17039-EK-P-DW-0203-14 17039-EK-P-DW-0203-14 17039-EK-P-DW-0206-01
4VESSEL SIZE
8300 (I/D) X 12000 (H) 8300 (I/D) X 12000 (H) 20000 (I/D) X 18000(W) X 4000 (H)
5VESSEL MATERIAL
CARBON STEEL + 3mm CA CARBON STEEL + 3mm CA CARBON STEEL + 3mm CA
6AREA CLASSIFICATION
ZONE - 2, Gr IIA & IIB, T3 ZONE - 2, Gr IIA & IIB, T3 ZONE - 2, Gr IIA & IIB, T3
7TANK NO
EK-BBJ-1090 EK-BBJ-1090 EK-ABJ-3450
8 UPPER FLUID / PHASE OFF SPE CRUDE OIL / LIQUID OFF SPE CRUDE OIL / LIQUID EFFLUENT WATER / LIQUID
9 LOWER FLUID / PHASE OFF SPE CRUDE OIL / LIQUID OFF SPE CRUDE OIL / LIQUID EFFLUENT WATER / LIQUID
10 INTERFACE
11 SUSPENDED SOLIDS
12PRESSURE (MAX. / NORM. / MIN. )
13TEMPERATURE (MAX. / NORM. / MIN.)
14DESIGN (PRESSURE / TEMPERATURE)
15 SPECIFIC GRAVITY
16 DENSITY UPPER LOWER Kg/m3
17 FLUID VISCOSITY UPPER LOWER cP
18 DIELECTRIC CONSTANT UPPER/LOWER
19 W/m-K
20 INTERNAL / EXTERNAL
21 CAGE MATERIAL
22 OVER ALL C-C C-C1
23 CONNECTION SIZE AND RATING
24 CAGE ORIENTATION / ROTATABLE HEAD
25 CAGE TO HEAD FLANGE SIZE & RATING
26 CAGE TO HEAD GASKET / BOLTING
27 DRAIN / VENT CONN. SIZE & RATING
28 COOLING EXTENSION
29 ELECTRICAL HEAT TRACING
30 STAND PIPE
31TYPE / MODEL Encapsulated Horn / * Encapsulated Horn / * Encapsulated Horn / *
32PROCESS CONNECTION
33MOC SS 316 SS 316 SS 316
34ANTENNA LENGTH DIAMETER
35MOUNTING POSITION / MOUNTING LOCATION
40 TYPE / PRINCIPLE
41 MOUNTING Direct on vessel Direct on vessel Direct on vessel
42 ACCURACY / INTER FACE ACCURACY ± 0.03% of measured distance / * ± 0.03% of measured distance / * ± 0.03% of measured distance / *
43 REPEATABILITY ± 1mm ± 1mm ± 1mm
44 PROTECTION CLASS/ENCLOSURE IP 65/ Ex'ia' IP 65/ Ex'ia' IP 65/ Ex'ia'
45 POWER SUPPLY 24VDC loop powered with HART 24VDC loop powered with HART 24VDC loop powered with HART
46 OUTPUT 4 - 20 mA 4 - 20 mA 4 - 20 mA
47 PROCESS CONNECTION AND RATING(MOC) 8", 150# RF, SS 316 8", 150# RF, SS 316 8", 150# RF, SS 316
48 CALIBRATION RANGE MIN. / MAX. (%)
49 INSTRUMENT RANGE MIN. / MAX. mm(%)
50 CABLE ENTRY | CABLE GLAND WITH PLUG SIDE ENTRY 1/2" NPT(F) w/ PLUG SIDE ENTRY 1/2" NPT(F) w/ PLUG SIDE ENTRY 1/2" NPT(F) w/ PLUG
51 LOCAL INDICATION / DISPLAY ENGG. UNIT LCD LCD LCD
52 SIL CERTIFICATION SIL-2 SIL-2 SIL-2
53 MEASURING RANGE (FROM TANK BOTTOM) YES YES YES
54 MODEL NO. FOR SENSOR * * *
55 MODEL NO. FOR TRANSMITTTER * * *
56 MANUFACTURER * * *
57NOTES:- REFER NOTES SHEET. * To be Furnished by Vendor.
0-100% 0-100% 0-100%
OTH
ER
S
mm (%)
TR
AN
SM
ITTER
Non Contact Type /
Pulse-burst radar technology
0-12000 mm (0-100)% 0-12000 mm (0-100)% 0-4000 mm (0-100)%
mm (%) mm (%)
VESSEL TOP
Non Contact Type /
Pulse-burst radar technology
Non Contact Type /
Pulse-burst radar technology
AN
TEN
NA
* * *
**
**
**
VERTICAL VESSEL TOP VERTICAL VESSEL TOP VERTICAL
GEN
ER
AL
SER
VIC
E C
ON
DITIO
NS
THERMAL CONDUCTIVITY LIQUID (UPPER /
LOWER)
CA
GE
C-C2
-
-
ATM
55
FOL+0.07 / 90
0.87
870
1
1.4
120
ORIGINATOR
VS
CLIENT NAME
Issued For Review
Client Document No.
-
DESCRIPTION
- - 17039-EK-I-DB-8001
ITEM/TAG No. DATA SHEET No.
REFER BELOW OIL-100-EK-I-DS-0826
PROJECT NO. SHEET REV
KIP-17039 A0
CLIENT CONTRACT No. REQUISITION No. SPECIFICATION No.
-
-
ATM
55
FOL+0.07 / 90
0.87
870
1
1.4
120
-
-
HOLD 1
51
HOLD 1 / 85
0.87
870
1
1.4
120
TITLE
DATA SHEET FOR RADAR TYPE LEVEL TRANSMITTER
PROJECT DESCRIPTION
CREATION OF SURFACE PRODUCTION FACILITIES (GGS) AT EAST KHAGORIJAN 8 OF 10
EPC CONTRACTOR
TBA
REV No. BY DATE CKD DATE APP. DATE
OIL INDIA LIMITED A0 VS 30-Nov-18 PG 30-Nov-18 MV 30-Nov-18
ORIG. DATE
30-Nov-18
UNITS:- Pressure bar g kg/cm2 g kPa g psig level : mm
Temp 0 C
0 F
1TAG NO.
66-LT-6603A 66-LT-6603B 66-LT-6614
2SERVICE
CLARIFIED WATER CLARIFIED WATER (EK-ABJ--3451A) SKIM OIL
3P&ID NO.
17039-EK-P-DW-0206-02 17039-EK-P-DW-0206-02 17039-EK-P-DW-0206-04
4VESSEL SIZE
8500 (I/D) X 12000 (H) 8500 (I/D) X 12000 (H) 5800 (I/D) X 8000 (H)
5VESSEL MATERIAL
CARBON STEEL + 3mm CA CARBON STEEL + 3mm CA CARBON STEEL + 3mm CA
6AREA CLASSIFICATION
ZONE - 2, Gr IIA & IIB, T3 ZONE - 2, Gr IIA & IIB, T3 ZONE - 2, Gr IIA & IIB, T3
7TANK NO
EK-ABJ-3451A EK-ABJ-3451B EK-ABJ-3452
8 UPPER FLUID / PHASE CLARIFIED WATER / LIQUID CLARIFIED WATER / LIQUID SKIM OIL / LIQUID
9 LOWER FLUID / PHASE - - -
10 INTERFACE
11 SUSPENDED SOLIDS
12PRESSURE (MAX. / NORM. / MIN. )
13TEMPERATURE (MAX. / NORM. / MIN.)
14DESIGN (PRESSURE / TEMPERATURE)
15 SPECIFIC GRAVITY
16 DENSITY UPPER LOWER Kg/m3
17 FLUID VISCOSITY UPPER LOWER cP
18 DIELECTRIC CONSTANT UPPER/LOWER
19 W/m-K
20 INTERNAL / EXTERNAL
21 CAGE MATERIAL
22 OVER ALL C-C C-C1
23 CONNECTION SIZE AND RATING
24 CAGE ORIENTATION / ROTATABLE HEAD
25 CAGE TO HEAD FLANGE SIZE & RATING
26 CAGE TO HEAD GASKET / BOLTING
27 DRAIN / VENT CONN. SIZE & RATING
28 COOLING EXTENSION
29 ELECTRICAL HEAT TRACING
30 STAND PIPE
31TYPE / MODEL Encapsulated Horn / * Encapsulated Horn / * Encapsulated Horn / *
32PROCESS CONNECTION
33MOC SS 316 SS 316 SS 316
34ANTENNA LENGTH DIAMETER
35MOUNTING POSITION / MOUNTING LOCATION
40 TYPE / PRINCIPLE
41 MOUNTING Direct on vessel Direct on vessel Direct on vessel
42 ACCURACY / INTER FACE ACCURACY ± 0.03% of measured distance / * ± 0.03% of measured distance / * ± 0.03% of measured distance / *
43 REPEATABILITY ± 1mm ± 1mm ± 1mm
44 PROTECTION CLASS/ENCLOSURE IP 65/ Ex'ia' IP 65/ Ex'ia' IP 65/ Ex'ia'
45 POWER SUPPLY 24VDC loop powered with HART 24VDC loop powered with HART 24VDC loop powered with HART
46 OUTPUT 4 - 20 mA 4 - 20 mA 4 - 20 mA
47 PROCESS CONNECTION AND RATING(MOC) 8", 150# RF, SS 316 8", 150# RF, SS 316 8", 150# RF, SS 316
48 CALIBRATION RANGE MIN. / MAX. (%)
49 INSTRUMENT RANGE MIN. / MAX. mm(%)
50 CABLE ENTRY | CABLE GLAND WITH PLUG SIDE ENTRY 1/2" NPT(F) w/ PLUG SIDE ENTRY 1/2" NPT(F) w/ PLUG SIDE ENTRY 1/2" NPT(F) w/ PLUG
51 LOCAL INDICATION / DISPLAY ENGG. UNIT LCD mm (%) LCD mm
(%)LCD
52 SIL CERTIFICATION SIL-2 SIL-2 SIL-2
53 MEASURING RANGE (FROM TANK BOTTOM) YES YES YES
54 MODEL NO. FOR SENSOR * * *
55 MODEL NO. FOR TRANSMITTTER * * *
56 MANUFACTURER * * *
57NOTES:- REFER NOTES SHEET. * To be Furnished by Vendor.
mm (%)
OTH
ER
S
DESCRIPTION
TR
AN
SM
ITTER
Non Contact Type /
Pulse-burst radar technology
Non Contact Type /
Pulse-burst radar technology
Non Contact Type /
Pulse-burst radar technology
0-100% 0-100% 0-100%
0-12000mm (0-100)% 0-12000mm (0-100)% 0-8000 mm (0-100)%
VERTICAL VESSEL TOP VERTICAL VESSEL TOP VERTICAL VESSEL TOP
AN
TEN
NA
* * *
**
**
**
GEN
ER
AL
SER
VIC
E C
ON
DITIO
NS
THERMAL CONDUCTIVITY LIQUID (UPPER /
LOWER)
CA
GE
C-C2
-
-
ATM
51
FOL+0.07 / 85
1
1000
0.54
1
-
ORIGINATOR
VS
CLIENT NAME
Issued For Review
Client Document No.
-
- - 17039-EK-I-DB-8001
ITEM/TAG No. DATA SHEET No.
REFER BELOW OIL-100-EK-I-DS-0826
PROJECT NO. SHEET REV
KIP-17039 A0
CLIENT CONTRACT No. REQUISITION No. SPECIFICATION No.
-
-
ATM
51
FOL+0.07 / 85
1
1000
0.54
1
-
-
-
ATM
55
FOL+0.07 / 90
0.8998
899.8
3.85
1.4
-
TITLE
DATA SHEET FOR RADAR TYPE LEVEL TRANSMITTER
PROJECT DESCRIPTION
CREATION OF SURFACE PRODUCTION FACILITIES (GGS) AT EAST KHAGORIJAN 9 OF 10
EPC CONTRACTOR
TBA
REV No. BY DATE CKD DATE APP. DATE
OIL INDIA LIMITED A0 VS 30-Nov-18 PG 30-Nov-18 MV 30-Nov-18
ORIG. DATE
30-Nov-18
UNITS:- Pressure bar g kg/cm2 g kPa g psig LEVEL : mm
Temp 0 C
0 F
1TAG NO.
66-LT-6615 71-LT-8008
2SERVICE
SKIM OIL OFF-SPEC EFFLUENT WATER FIRE WATER
3P&ID NO.
17039-EK-P-DW-0206-04 17039-EK-P-DW-0206-06 17039-EK-P-DW-0217-01
4VESSEL SIZE
5800 (I/D) X 8000 (H) 8500 (I/D) X12000 (H) 8300 (I/D) X 10000 (H)
5VESSEL MATERIAL
CARBON STEEL + 3mm CA CARBON STEEL + 3mm CA CARBON STEEL + 3mm CA
6AREA CLASSIFICATION
ZONE - 2, Gr IIA & IIB, T3 ZONE - 2, Gr IIA & IIB, T3 ZONE - 2, Gr IIA & IIB, T3
7TANK NO
EK-ABJ-3452 EK-ABJ-3453 EK-ABJ-3110A
8 UPPER FLUID / PHASE SKIM OIL / LIQUID - -
9 LOWER FLUID / PHASE - OFF-SPEC EFFLUENT WATER / LIQUID FIRE WATER / LIQUID
10 INTERFACE - -
11 SUSPENDED SOLIDS - -
12PRESSURE (MAX. / NORM. / MIN. )
13TEMPERATURE (MAX. / NORM. / MIN.)
14DESIGN (PRESSURE / TEMPERATURE)
15 SPECIFIC GRAVITY
16 DENSITY UPPER LOWER Kg/m3
17 FLUID VISCOSITY UPPER LOWER cP
18 DIELECTRIC CONSTANT UPPER/LOWER
19 W/m-K
20 INTERNAL / EXTERNAL
21 CAGE MATERIAL
22 OVER ALL C-C C-C1
23 CONNECTION SIZE AND RATING
24 CAGE ORIENTATION / ROTATABLE HEAD
25 CAGE TO HEAD FLANGE SIZE & RATING
26 CAGE TO HEAD GASKET / BOLTING
27 DRAIN / VENT CONN. SIZE & RATING
28 COOLING EXTENSION
29 ELECTRICAL HEAT TRACING
30 STAND PIPE
31TYPE / MODEL Encapsulated Horn / * Encapsulated Horn / * Encapsulated Horn / *
32PROCESS CONNECTION
33MOC SS 316 SS 316 SS 316
34ANTENNA LENGTH DIAMETER
35MOUNTING POSITION / MOUNTING LOCATION
40 TYPE / PRINCIPLE
41 MOUNTING Direct on vessel Direct on vessel Direct on vessel
42 ACCURACY / INTER FACE ACCURACY ± 0.03% of measured distance / * ± 0.03% of measured distance / * ± 0.03% of measured distance / *
43 REPEATABILITY ± 1mm ± 1mm ± 1mm
44 PROTECTION CLASS/ENCLOSURE IP 65/ Ex'ia' IP 65/ Ex'ia' IP 65/ Ex'ia'
45 POWER SUPPLY 24VDC loop powered with HART 24VDC loop powered with HART 24VDC loop powered with HART
46 OUTPUT 4 - 20 mA 4 - 20 mA 4 - 20 mA
47 PROCESS CONNECTION AND RATING(MOC) 8", 150# RF, SS 316 8", 150# RF, SS 316 8", 150# RF, SS 316
48 CALIBRATION RANGE MIN. / MAX. (%)
49 INSTRUMENT RANGE MIN. / MAX. mm(%)
50 CABLE ENTRY | CABLE GLAND WITH PLUG SIDE ENTRY 1/2" NPT(F) w/ PLUG SIDE ENTRY 1/2" NPT(F) w/ PLUG SIDE ENTRY 1/2" NPT(F) w/ PLUG
51 LOCAL INDICATION / DISPLAY ENGG. UNIT LCD LCD LCD
52 SIL CERTIFICATION SIL-2 SIL-2 SIL-2
53 MEASURING RANGE (FROM TANK BOTTOM) YES YES YES
54 MODEL NO. FOR SENSOR * * *
55 MODEL NO. FOR TRANSMITTTER * * *
56 MANUFACTURER * * *
57NOTES:- REFER NOTES SHEET. * To be Furnished by Vendor.
0-100% 0-100% 0-100%
OTH
ER
S
mm (%)
TR
AN
SM
ITTER
Non Contact Type /
Pulse-burst radar technology
0-8000 mm (0-100)% 0-12000mm (0-100)% 0-10000 mm (0-100)%
mm (%) mm (%)
VESSEL TOP
Non Contact Type /
Pulse-burst radar technology
Non Contact Type /
Pulse-burst radar technology
AN
TEN
NA
* * *
**
**
**
VERTICAL VESSEL TOP VERTICAL VESSEL TOP VERTICAL
GEN
ER
AL
66-LT-6631
SER
VIC
E C
ON
DITIO
NS
THERMAL CONDUCTIVITY LIQUID (UPPER /
LOWER)
1.4
-
ATM
51
FOL+0.07 / 85
1
1000
1
0.5
-
ATM
CA
GE
C-C2
ORIGINATOR
VS
-
-
ATM
55
FOL+0.07 / 90
0.8998
899.8
3.85
CLIENT NAME
Issued For Review
Client Document No.
-
DESCRIPTION
- - 17039-EK-I-DB-8001
ITEM/TAG No. DATA SHEET No.
REFER BELOW OIL-100-EK-I-DS-0826
PROJECT NO. SHEET REV
KIP-17039 A0
CLIENT CONTRACT No. REQUISITION No. SPECIFICATION No.
0.6
-
41
FOL+0.07 / 80
1
1000
1
TITLE
DATA SHEET FOR RADAR TYPE LEVEL TRANSMITTER
PROJECT DESCRIPTION
CREATION OF SURFACE PRODUCTION FACILITIES (GGS) AT EAST KHAGORIJAN 10 OF 10
EPC CONTRACTOR
TBA
REV No. BY DATE CKD DATE APP. DATE
OIL INDIA LIMITED A0 VS 30-Nov-18 PG 30-Nov-18 MV 30-Nov-18
ORIG. DATE
30-Nov-18
UNITS:- Pressure bar g kg/cm2 g kPa g psig LEVEL : mm
Temp 0 C
0 F
1TAG NO.
71-LT-8009
2SERVICE
FIRE WATER
3P&ID NO.
17039-EK-P-DW-0217-01
4VESSEL SIZE
8300 (I/D) X 10000 (H)
5VESSEL MATERIAL
CARBON STEEL + 3mm CA
6AREA CLASSIFICATION
ZONE - 2, Gr IIA & IIB, T3
7TANK NO
EK-ABJ-3110B
8 UPPER FLUID / PHASE -
9 LOWER FLUID / PHASE FIRE WATER / LIQUID
10 INTERFACE -
11 SUSPENDED SOLIDS -
12PRESSURE (MAX. / NORM. / MIN. )
13TEMPERATURE (MAX. / NORM. / MIN.)
14DESIGN (PRESSURE / TEMPERATURE)
15 SPECIFIC GRAVITY
16 DENSITY UPPER LOWER Kg/m3
17 FLUID VISCOSITY UPPER LOWER cP
18 DIELECTRIC CONSTANT UPPER/LOWER
19 W/m-K
20 INTERNAL / EXTERNAL
21 CAGE MATERIAL
22 OVER ALL C-C C-C1
23 CONNECTION SIZE AND RATING
24 CAGE ORIENTATION / ROTATABLE HEAD
25 CAGE TO HEAD FLANGE SIZE & RATING
26 CAGE TO HEAD GASKET / BOLTING
27 DRAIN / VENT CONN. SIZE & RATING
28 COOLING EXTENSION
29 ELECTRICAL HEAT TRACING
30 STAND PIPE
31TYPE / MODEL Encapsulated Horn / *
32PROCESS CONNECTION
33MOC SS 316
34ANTENNA LENGTH DIAMETER
35MOUNTING POSITION / MOUNTING LOCATION
40 TYPE / PRINCIPLE
41 MOUNTING Direct on vessel
42 ACCURACY / INTER FACE ACCURACY ± 0.03% of measured distance / *
43 REPEATABILITY ± 1mm
44 PROTECTION CLASS/ENCLOSURE IP 65/ Ex'ia'
45 POWER SUPPLY 24VDC loop powered with HART
46 OUTPUT 4 - 20 mA
47 PROCESS CONNECTION AND RATING(MOC) 8", 150# RF, SS 316
48 CALIBRATION RANGE MIN. / MAX. (%)
49 INSTRUMENT RANGE MIN. / MAX. mm(%)
50 CABLE ENTRY | CABLE GLAND WITH PLUG SIDE ENTRY 1/2" NPT(F) w/ PLUG
51 LOCAL INDICATION / DISPLAY ENGG. UNIT LCD
52 SIL CERTIFICATION SIL-2
53 MEASURING RANGE (FROM TANK BOTTOM) YES
54 MODEL NO. FOR SENSOR *
55 MODEL NO. FOR TRANSMITTTER *
56 MANUFACTURER *
57NOTES:- REFER NOTES SHEET. * To be Furnished by Vendor.
OTH
ER
STR
AN
SM
ITTER
Non Contact Type /
Pulse-burst radar technology
mm (%)
0-100%
0-10000 mm (0-100)%
AN
TEN
NA
*
**
VERTICAL VESSEL TOP
GEN
ER
AL
SER
VIC
E C
ON
DITIO
NS
THERMAL CONDUCTIVITY LIQUID (UPPER /
LOWER)
CA
GE
C-C2
ATM
41
FOL+0.07 / 80
1
1000
1
0.6
-
ORIGINATOR
VS
CLIENT NAME
Issued For Review
Client Document No.
-
DESCRIPTION
- - 17039-EK-I-DB-8001
ITEM/TAG No. DATA SHEET No.
REFER BELOW OIL-100-EK-I-DS-0826
PROJECT NO. SHEET REV
KIP-17039 A0
CLIENT CONTRACT No. REQUISITION No. SPECIFICATION No.
Datasheet NumberRev
Code
OIL-100-EK-I-DS-0801 A0 Sheet No.: 02 of 05
SHEET No.
1 COVER SHEET
2 INDEX SHEET
3 REVISION SHEET
4 NOTES SHEET
5 DS - LG (Reflex.Type)
INDEX SHEET
TITLE
CREATION OF SURFACE PRODUCTION
FACILITIES (GGS) AT EAST KHAGORIJAN
Revision Index
DATA SHEET FOR LEVEL GAUGE (REFLEX TYPE)
Datasheet NumberRev
Code
OIL-100-EK-I-DS-0801 A0 Sheet No: 03 of 05
REV No. LIST OF PAGES OF UPDATED / MODIFIED SECTIONS, IF ANY
A0 FIRST ISSUE
REVISION RECORD SHEET
PURPOSE
ISSUED FOR REVIEW
CREATION OF SURFACE PRODUCTION
FACILITIES (GGS) AT EAST KHAGORIJAN
Revision Index
DATA SHEET FOR LEVEL GAUGE (REFLEX TYPE)
Datasheet Number Rev Code
OIL-100-EK-I-DS-0801 A0 Sheet No: 04 of 05
6. Flange connection shall be in accordance with ASME B16.5
7. The external chamber shall be designed and constructed to ASME B31.3
8. All chambers shall be weld-necked type, flanges with raise face and gasket surface finishes shall be in accordance with ASME B16.5.
9. All Level Gauges shall be supplied complete with stainless steel 316 nameplate affixed to the body. Tags shall be Permanently secured. The following information shall be
shown on the name plates as a minimum:manufacturers name & trade mark, type, model no & serial no, Instrument Tag.No, moc, service/ fluid, c-c distance and visible length,
pressure and temperature rating of pressurized parts.
5. Painting shall be as per Protective Coating specification for Onshore Structures and Facilities.
CREATION OF SURFACE PRODUCTION FACILITIES (GGS)
AT EAST KHAGORIJAN
Revision Index
DATA SHEET FOR LEVEL GAUGE (REFLEX TYPE)
Notes:
1. Documentation required :- Calibration Certificate , Material Certificates to 3.1 as per EN 10204, Hydro test ,
Pressure test Procedure/Report , Operating & Maintenance Instructions & Spare Parts List.
2. Vendor shall supply spare parts for start-up and commissioning, a list of recommended spare parts for 2 years operation & performance warranty.
3. Level Gauges shall be Hydrotested to 1.5 times the process design pressure by the manufacturer prior to shipment.
4. Flange finish shall be in accordance with ANSI B16.5, for Raised Face (RF) flanges and shall be smooth finish to 125-250 AARH and 63 AARH for Ring type joint (RTJ) .
TITLE ITEM/TAG No. DATA SHEET No.
DATA SHEET FOR LEVEL GAUGE (REFLEX TYPE)
PROJECT DESCRIPTION PROJECT NO SHEET REV
05 OF 05 A0
MPC CONTRACTOR CLIENT CONTRACT No. REQUISITION No. SPECIFICATION No.
CLIENT NAME REV No. BY DATE CKD DATE APP. DATE
A0 IMR 30-Nov-18 MV 30-Nov-18 MSR/ VSR 30-Nov-18 ISSUED FOR REVIEW
CLIENT'S REF
-
ORIGINATOR ORIG. DATE
03-Oct-18
UNITS: Pressure: kg/cm2 g Temp: Flow: Gas: Liquid:
Level: mm
1. Tag Number Refer below Table 20. Mica Shield No
2. Service Refer below Table 21. Illuminator Power Supply NA NA
3. Vessel No. Refer below Table 22. Enclosure Class Cable Entry NA NA
4. Trim No. AC01 23. Power Isolation Switch NA
5. P&ID Number (Sheet No.) Refer below Table 24. Jacket or Internal Tracer NA
6. Area Classification Zone 2, Gas Gr.IIA & IIB, T3 25. Frost Extension Length NA NA
7. Measurement Local Level Measurement 26. Calibrated Scale Yes
8. Vessel Material Carbon Steel + 3mm CA 27.
9. Type Reflex Type 28. Type Offset Type
10. Sections Required 320 x 1 29. Body Material SS316
11. Connection Size Rating 30. Trim Material SS316
12. Connection Arrangement Side - Side Right 31. Packing Material NA
13. Chamber Material SS316 32. Ball Check Yes
14. Cover Material SS316 33. Vessel Connection Size Rating 2" 150#RF
15. Glass Material Toughened Borosilicate Glass 34. Vessel Connection Arrangement Side - Side
16. Bolts & Nuts Material 35. Gauge Connection Size Rating 3/4" NPT -
36. Drain :- Size Rating 3/4" 150#RF
17. Gasket Material 37. Vent :- Size Rating 3/4" 150#RF
38. Bonnet - Integral / Union / Bolted Union
39. Closing - Plain / Quick Quick
40. Renewable Seats Yes
18. Flange Material CS, ASTM A-105
19. Manufacturer *
1. For Notes refer Notes section.
Press. Temp. Press.
kg/cm2g °C kg/cm2g
1 53-LG-5505 17039-EK-P-DW-0212-01 *0 - 2500
(Hold)Atm. Amb. FOW+0.07 0.99
2"/
150# RF*
2 53-LG-5509 17039-EK-P-DW-0212-01 *0 - 2500
(Hold)Atm. Amb. FOW+0.07 0.99
2"/
150# RF*
3 53-LG-5544 17039-EK-P-DW-0212-04 *0 - 2500
(Hold)Atm. Amb. FOW+0.07 0.99
2"/
150# RF*
4 53-LG-5535 17039-EK-P-DW-0212-04 *0 - 2500
(Hold)Atm. Amb. FOW+0.07 0.99
2"/
150# RF*
* BY VENDOR
Industrial Water Storage
Tank (EK-ABJ-3220)
Industrial Water Storage
Tank (EK-ABJ-3220)
Operating
80
80
Design
Temp.
°C
Service Description
Potable Water Storage Tank
(EK-ABJ-3270)
Potable Water Storage Tank
(EK-ABJ-3270)
80
80
S.No.
NOTES
Tag Number Remarks
GENERAL
Model
Number
Size/
Rating/
Facing
P&ID Number
Visible
Length
(mm)
C-C
Distance
(mm)
Liquid
S.G
ASTM A 193 Gr. B7/ ASTM A 194 Gr. 2H as
per ASME B16.5
150# SPWND Gasket 4.5mm THK TO
ASME B 16.20: Windings - SS316, Filler-
CNAF, Inner Ring -SS316, Outer Ring- CS
GAUGE
OPTIONS
COCKS
CREATION OF SURFACE PRODUCTION FACILITIES (GGS) AT EAST KHAGORIJAN KIP-17039
SEE BELOW TABLE OIL-100-EK-I-DS-0801
m3/hr
IMR
DESCRIPTION
OIL INDIA LIMITED
TBA - - -
° C
Datasheet NumberRev
Code
OIL-100-EK-I-DS-0802 A0 Sheet No.: 02 of 07
SHEET No.
1 COVER SHEET
2 INDEX SHEET
3 REVISION SHEET
4 NOTES SHEET
5 DS - TT
6 DS - TT
7 DS - TT
INDEX SHEET
TITLE
CREATION OF SURFACE PRODUCTION
FACILITIES (GGS) AT EAST KHAGORIJAN
Revision Index
DATA SHEET FOR TEMPERATURE TRANSMITTERS
WITH THERMOWELL
Datasheet NumberRev
Code
OIL-100-EK-I-DS-0802 A0 Sheet No: 03 of 07
REV No. LIST OF PAGES OF UPDATED / MODIFIED SECTIONS, IF ANY
A0 FIRST ISSUE
REVISION RECORD SHEET
PURPOSE
ISSUED FOR REVIEW
CREATION OF SURFACE PRODUCTION
FACILITIES (GGS) AT EAST KHAGORIJAN
Revision Index
DATA SHEET FOR TEMPERATURE TRANSMITTERS
WITH THERMOWELL
Datasheet Number Rev Code
OIL-100-EK-I-DS-0802 A0 Sheet No: 04 of 07
signal for remote calibration and diagnostics from HART maintenance system.
6. Flange finish shall be in accordance with ANSI B16.5, for Raised Face (RF) flanges and shall be smooth finish to 125-250 AARH and 63 AARH for Ring type joint (RTJ) .
7. The housing of all transmitters shall be SS 316 minimum.
8. The element head shall have 2 cable entries, one of which shall be fitted with a certified plug.
9. All Transmitters shall be provided with SIL-2 (min) certification.
10. The over-range/static pressure protection of the transmitter shall be 130% of range.
5. All field transmitters shall be" SMART" type, 2-wire 24VDC loop powered communicating on 4-20mA signal mode with superimposed HART digital transmission
CREATION OF SURFACE PRODUCTION FACILITIES (GGS)
AT EAST KHAGORIJAN
Revision Index
DATA SHEET FOR TEMPERATURE TRANSMITTERS WITH
THERMOWELL
Notes:
1. Documentation required :- Calibration Certificate , Ingress Protection Certificate, Material Certificates to 3.1 as per EN 10204, Hydro test , Explosion proof & weather
proof certificate, Pressure test Procedure/Report , SIL 2 Certificate, Operating & Maintenance Instructions & Spare Parts List.
2. All instruments to be supplied with a SS 316 Name plate with Tag no. permanently inscribed. Tags shall be Permanently secured.
3. All transmitters shall be provided with integral indicator (LCD type) with engineering unit indication.
4. Instrumentation shall meet the Electromagnetic interference requirements according to EN 50081-2 and EN 50082-2.
TITLE ITEM/TAG No. DATA SHEET No.
DATA SHEET FOR TEMPERATURE TRANSMITTERS WITH THERMOWELL
PROJECT DESCRIPTION PROJECT NO SHEET REV
05 OF 07 A0
MPC CONTRACTOR CLIENT CONTRACT No. REQUISITION No. SPECIFICATION No.
CLIENT NAME REV No. BY DATE CKD DATE APP. DATE
A0 IMR 28-Nov-18 MV 28-Nov-18 MSR/ VSR 28-Nov-18 ISSUED FOR REVIEW
CLIENT'S REF
-
ORIGINATOR ORIG. DATE
14-Sep-18
UNITS: Pressure: kg/cm2 g Temp: Flow: Gas:MMSCFD Liquid:
1. Mounting Direct Mounted 8. Housing Material Polyurethane Coated Aluminum
2. Accuracy ± 0.1% of FSD 9. Bracket & Bolt Material NA
3. Temp. Limit 8°C to 45°C 10. Enclosure Rating IP 65
4. Output 4-20 mAdc, HART Protocol with SMART Tr. 11. Area Classification Zone 1, Gas Group IIA&IIB, Temp. Cl T3
5. Power Supply 24 VDC Loop powered 12. Equipment Certification IEC EEx'd'
6. Indicating Yes. LCD in engineering unit 13. Manufacturer *
7. Electrical Connection 1/2" NPT(F) 14. Model Number Note-3
1. Element Type 3-Wire, pt-100, 100Ω at 0 deg.C, RTD, IEC 751, Class A 7. Head Material NA
2. Number of Element Single (a = 0.00385) 8. Terminal Block Yes
3. Sensor Diameter 1/4" 9. Screw Cap & Chain NA
4. Sheath Material SS 316 10. Electrical Connection NA
5. Spring Loaded Yes 11. Manufacturer *
6. Extension Type / Length NA
1. Included Yes 7. Bore Diameter 0.26"
2. Material 316 stainless steel 8. Element Connection 1/2" NPT
3. Construction Solid drilled & Tapered 9. Process Connection See below
1) Each instrument shall include a SS tag permanently attached to the instrument using SS screws, SS bolts or ss wire.
2) Transmitter, Temperature Sensor & Thermowell shall be assembled and tagged individually.
3) Temperature Transmitter Model Number: *
Temperature Element Model Number: *
Thermowell Model Number: *
141-TT-3751/
41-TE-3751/
41-TW-3751
17039-EK-P-DW-0202-13 0 - 10090/
(27-50)FOW+0.07 NA 500 0.1 150
2
20-TT-1387A/
20-TE-1387A/
20-TW-1387A
17039-EK-P-DW-0202-20 0 - 10090/
(27-50)FOW+0.07 NA 500 0.1 150
3
20-TT-1387B/
20-TE-1387B/
20-TW-1387B
17039-EK-P-DW-0202-20 0 - 10090/
(27-50)FOW+0.07 NA 500 0.1 150
4
20-TT-1387C/
20-TE-1387C/
20-TW-1387C
17039-EK-P-DW-0202-20 0 - 10090/
(27-50)FOW+0.07 NA 500 0.1 150
5
20-TT-0991/
20-TE-0991/
20-TE-0991
17039-EK-P-DW-0203-10 0 - 100 90/ 55 FOW+0.07 NA 500 0.1 150
6
20-TT-0990A/
20-TE-0990A/
20-TW-0990A
17039-EK-P-DW-0203-10 0 - 100 90/ 55 FOW+0.07 NA 500 0.1 150
7
20-TT-0990B/
20-TE-0990B/
20-TW-0990B
17039-EK-P-DW-0203-10 0 - 100 90/ 55 FOW+0.07 NA 500 0.1 150
8
20-TT-0990C/
20-TE-0990C/
20-TW-0990C
17039-EK-P-DW-0203-10 0 - 100 90/ 55 FOW+0.07 NA 500 0.1 150
9
20-TT-0992/
20-TE-0992/
20-TW-0992
17039-EK-P-DW-0203-11 0 - 100 90/ 55 FOW+0.07 NA 500 0.1 150
10
20-TT-0998A/
20-TE-0998A/
20-TW-0998A
17039-EK-P-DW-0203-11 0 - 100 90/ 55 FOW+0.07 NA 500 0.1 150
11
20-TT-0998B/
20-TE-0998B/
20-TW-0998B
17039-EK-P-DW-0203-11 0 - 100 90/ 55 FOW+0.07 NA 500 0.1 150
* To be Provided By Vendor.
Crude Oil Test Tank
Crude Oil Test Tank
Hot Oil return header TCV
Temp. Control
Treated Crude Storage Tank
(ND-BBJ-1120A)
S.No. Tag Number Service Description
Hot Oil return header TCV
Temp. Control
Crude Oil Test Tank
2"/
150# RF
Velocity
(m/s)
T/W
"U"/ Lag.
mm
Flange
Size &
Rating
2"/
150# RF
2"/
150# RF
2"/
150# RF
2"/
150# RF
2"/
150# RF
2"/
150# RF
2"/
150# RF
2"/
150# RF
2"/
150# RF
2"/
150# RF
Treated Crude Storage Tank
(ND-BBJ-1120A)
Treated Crude Storage Tank
(ND-BBJ-1120A)
Treated Crude Storage Tank
(ND-BBJ-1120B)
Hot Oil return header TCV
Temp. Control
Treated Crude Storage Tank
(ND-BBJ-1120B)
Remarks
Design
Pressure
Kg/cm2g
° C
TEMPERATURE TRANSMITTER
TEMPERATURE ELEMENT
NOTES
THERMOWELL
Model
Number
Nozzle
Projetion
Length
(mm)
Line
InsulationP&ID Number
Calibrated
Range
Deg.C
Temp.
(Design/
Normal)
Deg.C
CREATION OF SURFACE PRODUCTION FACILITIES (GGS) AT EAST KHAGORIJAN KIP-17039
SEE BELOW TABLE OIL-100-EK-I-DS-0802
m3/hr
IMR
DESCRIPTION
OIL INDIA LIMITED
TBA - - -
TITLE ITEM/TAG No. DATA SHEET No.
DATA SHEET FOR TEMPERATURE TRANSMITTERS WITH THERMOWELL
PROJECT DESCRIPTION PROJECT NO SHEET REV
06 OF 07 A0
MPC CONTRACTOR CLIENT CONTRACT No. REQUISITION No. SPECIFICATION No.
CLIENT NAME REV No. BY DATE CKD DATE APP. DATE
A0 IMR 28-Nov-18 MV 28-Nov-18 MSR/ VSR 28-Nov-18 ISSUED FOR REVIEW
CLIENT'S REF
-
ORIGINATOR ORIG. DATE
14-Sep-18
UNITS: Pressure: kg/cm2 g Temp: Flow: Gas:MMSCFD Liquid:
1. Mounting Direct Mounted 8. Housing Material Polyurethane Coated Aluminum
2. Accuracy ± 0.1% of FSD 9. Bracket & Bolt Material NA
3. Temp. Limit 8°C to 45°C 10. Enclosure Rating IP 65
4. Output 4-20 mAdc, HART Protocol with SMART Tr. 11. Area Classification Zone 1, Gas Group IIA&IIB, Temp. Cl T3
5. Power Supply 24 VDC Loop powered 12. Equipment Certification IEC EEx'd'
6. Indicating Yes. LCD in engineering unit 13. Manufacturer *
7. Electrical Connection 1/2" NPT(F) 14. Model Number Note-3
1. Element Type 3-Wire, pt-100, 100Ω at 0 deg.C, RTD, IEC 751, Class A 7. Head Material NA
2. Number of Element Single (a = 0.00385) 8. Terminal Block Yes
3. Sensor Diameter 1/4" 9. Screw Cap & Chain NA
4. Sheath Material SS 316 10. Electrical Connection NA
5. Spring Loaded Yes 11. Manufacturer *
6. Extension Type / Length NA
1. Included Yes 7. Bore Diameter 0.26"
2. Material 316 stainless steel 8. Element Connection 1/2" NPT
3. Construction Solid drilled & Tapered 9. Process Connection See below
1) Each instrument shall include a SS tag permanently attached to the instrument using SS screws, SS bolts or ss wire.
2) Transmitter, Temperature Sensor & Thermowell shall be assembled and tagged individually.
3) Temperature Transmitter Model Number: *
Temperature Element Model Number: *
Thermowell Model Number: *
12
20-TT-0998C/
20-TE-0998C/
20-TW-0998C
17039-EK-P-DW-0203-11 0-100 90/ 55 FOW+0.07 NA 500 0.1 150
13 20-TIT-0431 17039-EK-P-DW-0203-14 0-100 90/ 55 FOW+0.07 NA 500 0.1 150
14
20-TT-0428A/
20-TE-0428A/
20-TW-0428A
17039-EK-P-DW-0203-14 0-100 90/ 55 FOW+0.07 NA 500 0.1 150
15
20-TT-0428B/
20-TE-0428B/
20-TW-0428B
17039-EK-P-DW-0203-14 0-100 90/ 55 FOW+0.07 NA 500 0.1 150
16
20-TT-0428C/
20-TE-0428C/
20-TW-0428C
17039-EK-P-DW-0203-14 0-100 90/ 55 FOW+0.07 NA 500 0.1 150
17
66-TIT-6622
66-TE-6622/
66-TW-6622
17039-EK-P-DW-0206-04 0-100 90 / 55 FOL+0.07 NA 500 0.1 150
18
66-TT-6620/
66-TE-6620/
66-TW-6620
17039-EK-P-DW-0206-04 0-100 90 / 55 FOL+0.07 NA 500 0.1 150
* To be Provided By Vendor.
Off Spec crude storage Tank
(ND-BBJ-1090)
2"/
150# RF
Hot Oil return header TCV
Temp. Control
2"/
150# RF
Skim Oil Tank
(ND-ABJ-3452)
2"/
150# RF
Hot Oil return header TCV
Temp. Control
2"/
150# RF
Off Spec crude storage Tank
(ND-BBJ-1090)
2"/
150# RF
Off Spec crude storage Tank
(ND-BBJ-1090)
2"/
150# RF
Treated Crude Storage Tank
(ND-BBJ-1120B)
2"/
150# RF
RemarksLine
Insulation
T/W
"U"/ Lag.
mm
Flange
Size &
Rating
Velocity
(m/s)
Nozzle
Projetion
Length
(mm)
Model
Number
TEMPERATURE ELEMENT
THERMOWELL
NOTES
S.No. Tag Number Service Description P&ID Number
Calibrated
Range
Deg.C
Temp.
(Design/
Normal)
Deg.C
Design
Pressure
Kg/cm2g
TEMPERATURE TRANSMITTER
SEE BELOW TABLE OIL-100-EK-I-DS-0802
CREATION OF SURFACE PRODUCTION FACILITIES (GGS) AT EAST KHAGORIJAN KIP-17039
TBA - - -
DESCRIPTION
OIL INDIA LIMITED
IMR
° C m3/hr
TITLE ITEM/TAG No. DATA SHEET No.
DATA SHEET FOR TEMPERATURE TRANSMITTERS WITH THERMOWELL
PROJECT DESCRIPTION PROJECT NO SHEET REV
07 OF 07 A0
MPC CONTRACTOR CLIENT CONTRACT No. REQUISITION No. SPECIFICATION No.
CLIENT NAME REV No. BY DATE CKD DATE APP. DATE
A0 IMR 28-Nov-18 MV 28-Nov-18 MSR/ VSR 28-Nov-18 ISSUED FOR REVIEW
CLIENT'S REF
-
ORIGINATOR ORIG. DATE
14-Sep-18
UNITS: Pressure: kg/cm2 g Temp: Flow: Gas:MMSCFD Liquid:
1. Mounting Direct Mounted 8. Housing Material Polyurethane Coated Aluminum
2. Accuracy ± 0.1% of FSD 9. Bracket & Bolt Material NA
3. Temp. Limit 8°C to 45°C 10. Enclosure Rating IP 65
4. Output 4-20 mAdc, HART Protocol with SMART Tr. 11. Area Classification Zone 1, Gas Group IIA&IIB, Temp. Cl T3
5. Power Supply 24 VDC Loop powered 12. Equipment Certification IEC EEx'd'
6. Indicating Yes. LCD in engineering unit 13. Manufacturer *
7. Electrical Connection 1/2" NPT(F) 14. Model Number Note-3
1. Element Type 3-Wire, pt-100, 100Ω at 0 deg.C, RTD, IEC 751, Class A 7. Head Material NA
2. Number of Element Single (a = 0.00385) 8. Terminal Block Yes
3. Sensor Diameter 1/4" 9. Screw Cap & Chain NA
4. Sheath Material SS 316 10. Electrical Connection NA
5. Spring Loaded Yes 11. Manufacturer *
6. Extension Type / Length NA
1. Included Yes 7. Bore Diameter 0.26"
2. Material 316 stainless steel 8. Element Connection 1/2" NPT
3. Construction Solid drilled & Tapered 9. Process Connection See below
1) Each instrument shall include a SS tag permanently attached to the instrument using SS screws, SS bolts or ss wire.
2) Transmitter, Temperature Sensor & Thermowell shall be assembled and tagged individually.
3) Temperature Transmitter Model Number: *
Temperature Element Model Number: *
Thermowell Model Number: *
19 44-TT-8044 17039-EK-P-DW-0203-21 0-100 90/55 FOW+0.07 NA 230 150
20 44-TT-8045 17039-EK-P-DW-0203-21 0-100 90/55 FOW+0.07 NA 230 150
21 44-TT-8044B 17039-EK-P-DW-0203-22 0-100 90/55 FOW+0.07 NA 230 150
22 44-TT-8045B 17039-EK-P-DW-0203-22 0-100 90/55 FOW+0.07 NA 230 150
* To be Provided By Vendor.
Eff.Water to Eff.Water
Storage Tank
11/2"*&
150#RF
Eff.Water to Eff.Water
Storage Tank
11/2"*&
150#RF
Line
Insulation
T/W
"U"/ Lag.
mm
Flange
Size &
Rating
Eff.Water to Eff.Water
Storage Tank
11/2"*&
150#RF
Eff.Water to Eff.Water
Storage Tank
11/2"*&
150#RF
TEMPERATURE ELEMENT
THERMOWELL
NOTES
S.No. Tag Number Service Description P&ID Number
Calibrated
Range
Deg.C
Temp.
(Design/
Normal)
Deg.C
Design
Pressure
Kg/cm2g
RemarksVelocity
(m/s)
Nozzle
Projetion
Length
(mm)
Model
Number
TEMPERATURE TRANSMITTER
SEE BELOW TABLE OIL-100-EK-I-DS-0802
CREATION OF SURFACE PRODUCTION FACILITIES (GGS) AT EAST KHAGORIJAN KIP-17039
TBA - - -
DESCRIPTION
OIL INDIA LIMITED
IMR
° C m3/hr
Datasheet NumberRev
Code
OIL-100-EK-I-DS-0803 A0 SHEET 02 OF 05
SHEET No.
1 COVER SHEET
2 INDEX SHEET
3 REVISION SHEET
4 NOTES SHEET
5 DS-CORIOLIS FLOWMETER (FISCAL FLOW METER)
INDEX SHEET
TITLE
CREATION OF SURFACE PRODUCTION FACILITIES (GGS)
AT EAST KHAGORIJAN
Revision Index
DATA SHEET FOR CORIOLIS FLOW METER
Datasheet NumberRev
Code
OIL-100-EK-I-DS-0803 A0 SHEET 03 OF 05
REV No. LIST OF PAGES OF UPDATED / MODIFIED SECTIONS, IF ANY
FIRST ISSUE
REVISION RECORD SHEET
PURPOSE
ISSUED FOR REVIEWA0
CREATION OF SURFACE PRODUCTION FACILITIES (GGS)
AT EAST KHAGORIJAN
Revision Index
DATA SHEET FOR CORIOLIS FLOW METER
Datasheet NumberRev
Code
OIL-100-EK-I-DS-0803 A0 Sheet No.: 04 of 05
2. Coriolis flow meter shall be provided with 1 mm thick, 30mm x 75mm SS 316 tag plate, inscribed with tag number engraved or embossed
in 5mm high and 0.3mm deep bold characters and black paint filled. The tags shall be mounted on or adjacent to the associated
instrument and either fixed with stainless steel screws or attached with stainless steel wire.
3. Coriolis meters shall be designed to ISO 10790.
4. All stud bolt material shall be ASTM A 193 Gr. B7 / ASME B16.5 (Hot dip galvanized).
5. The Coriolis Meter shall be provided with a local LCD display with Engineering unit indication.
6. Instrument shall meet the Electromagnetic Interference requirements to EN50082-2 / IEC 60533.
7. All weldings and castings (if any) shall be 100% radiographed.
8. Any special cable between the sensor transmitter & receiver electronics to be provided by flow meter vendor.
9. Transmitter shall be provided with dual cable entries. Unused cable entries shall be provided with explosion proof plugs of SS 316.
10. Coriolis meter shall be Ex"ia" in accordance with IEC 60079. In the event of Ex"ia" is not available or cannot be used then Ex"d" type of
11.
12. Coriolis Mass Flow Meter shall be of in-line mounting design with flow direction clearly marked on the flow tube body to ensure
proper installation.
13.
14.
Documentation required :- Calibration certificate,Material certificates to 3.1 as per EN10204, weather proof to IP65 certificate by ATEX or Equivalent body,
Pressure test procedure/Report, NDT procedure / Report, Operating and Maintenance Instructions & Spare Parts List. 1.
Meter body shall be hydrostatically tested as per requirement specified in relevant clause of ASME F 423.
protection shall be used and notified to the buyer for approval.
Mass flow meters shall be of Coriolis - two tube design.
Flanged end connection and Flange face finish of the Coriolis Mass Flow Meter shall be as per ASME B 16.5.
Notes Sheet
CREATION OF SURFACE PRODUCTION FACILITIES (GGS) AT
EAST KHAGORIJAN
Revision Index
DATA SHEET FOR CORIOLIS FLOW METER
TITLE
DATA SHEET FOR CORIOLIS FLOW METER
PROJECT DESCRIPTION REV
CREATION OF SURFACE PRODUCTION FACILITIES (GGS) AT EAST KHAGORIJAN 05 OF 05 A0
MPC CONTRACTOR
TBA -
REV No. BY DATE CKD DATE APP. DATE
OIL INDIA LIMITED A0 IMR 28-Nov-18 MV 28-Nov-18 MSR/VSR 28-Nov-18
ORIG. DATE
13-Sep-18
UNITS:- Pressure bar g kg/cm2 g kPa g psig Flow : Gas MMSCFD Sm3/hr kg/hr
Temp 0 C 0 F Liquid m3/hr kg/hr lit / hr
1 TAG NO.
2 QUANTITY
3 LINE No.
4 P & ID No.
5 LINE SIZE/SCH
6 LINE INSULATION
7 SERVICE
8 AREA CLASSIFICATION
9 ENCLOSURE
10 SIZE 150#RF 150#RF
11 125 - 250 AARH 125 - 250 AARH
12
13
14
15
16
17
18
19
20
21 MEASURING RANGE (CALIBRATED FLOW)
22
23
24
25 REPEATABILITY 100:1 100:1
26
27
28
29
30 TEMPERATURE: OPERATING / DESIGN 90 (Hold) 90 (Hold)
31 15 (Hold) 15 (Hold)
32 ALLOWABLE PRESS. DROP ACROSS METER
33
34 DENSITY kg/m3 @ OT °C - -
35 FLOW (MIN / NORMAL / MAX) m3/day - - 600 (Hold) - - 600 (Hold)
36 WATER CONTENT: (m3/day) MAXIMUM
37 NORMAL
38 MINIMUM
39
40
41
42 MODEL NO. FOR TRANSMITTTER
43
NOTES:-
REFER SHEET 4
KIP-17039
CLIENT CONTRACT No. REQUISITION No. SPECIFICATION No.
-
ITEM/TAG No. DATA SHEET No.
REFER BELOW OIL-100-EK-I-DS-0803
PROJECT NO.
-
ORIGINATOR
CLIENT NAME DESCRIPTION
Issued for Review
CLIENT DOC .No
ONE ONE
3"-PL-20-2402-AC01
IMR
KLPD
3" / STD 3" / STD
NO NO
3"-PL-20-2403-AC01
17039-ND-P-DW-0219-01 17039-ND-P-DW-0219-01
METER TYPE &
MATERIAL
RATING 3" 3"
END CONNECTION & FACE FINISH FLANGED
CRUDE OIL CRUDE OIL
ZONE-2, Gr IIA & IIB, T3 ZONE-2, Gr IIA & IIB, T3
GENERAL
20-FT-2008 20-FT-2009
FLANGED
END CONNECTION FLANGE MATERIAL CARBON STEEL A216 WCB CARBON STEEL A216 WCB
IP 65, Ex 'ia' IP 65, Ex 'ia'
OTHER WETTED PARTS MATERIAL SS 316 SS 316
ENCLOSURE MATERIAL SS 316 SS 316
SENSOR SPOOL PIECE MATERIAL CARBON STEEL A216 WCB CARBON STEEL A216 WCB
SENSOR MATERIAL SS 316 SS 316
ZONE-2, Gr IIA & IIB, T3 ZONE-2, Gr IIA & IIB, T3
ENCLOSURE MATERIAL SS 316 SS 316
TRANSMITTER
SUPPLY & SIGNAL
POWER SUPPLY 230 VAC / 60 Hz 230 VAC / 60 Hz
OUTPUT
4-20mA, DC, SMART type with HART
Protocol4-20mA, DC, SMART type with HART Protocol
AREA CLASSIFICATION
+/- 0.1 %
SENSITIVITY - -FLOW METER
DATA
* *
ADJUSTABLE RANGE - -
ACCURACY +/- 0.1 %
MINIMUM DETECTION LIMIT - -
CABLE ENTRY CONNECTION ISO M20 (METRIC) ISO M20 (METRIC)
RANGEABILITY - -
EFFECT OF TEMPERATURE
AUTOMATIC TEMPERATURE
COMPENSATIONAUTOMATIC TEMPERATURE COMPENSATION
SERVICE
CONDITIONS
FLUID AND STATE CRUDE OIL / LIQUID CRUDE OIL / LIQUID
55 55
PRESSURE: OPERATING / DESIGN 10 10
0.3 (Hold) 0.3 (Hold)
OPERATING VISCOSITY (Cp) 3.8 (Hold) 3.8 (Hold)
- -
- -
MOLECULAR WEIGHT 900 900
3.1 (Hold) 3.1 (Hold)
SHEET
MANUFACTURER * *
* *
* *
SALINITY - -
OTHERS
LOCAL DISPLAY YES YES
MODEL NO. FOR SENSOR
Datasheet NumberRev
Code
OIL-100-EK-I-DS-0807 A0 SHEET 2 OF 10
SHEET No.
1 COVER SHEET
2 INDEX SHEET
3 REVISION SHEET
4 NOTES SHEET
5 41-TV-3751
6 41-TV-0991
7 41-TV-0992
8 41-TV-0431
9 66-TV-6622
10 66-TV-6635
INDEX SHEET
TITLE
CREATION OF SURFACE PRODUCTION
FACILITIES (GGS) AT EAST KHAGORIJAN
Revision Index
DATASHEET FOR CONTROL VALVES
Datasheet NumberRev
Code
OIL-100-EK-I-DS-0807 A0 SHEET 3 OF 10
REV No. LIST OF PAGES OF UPDATED / MODIFIED SECTIONS, IF ANY
A0 FIRST ISSUEISSUED FOR REVIEW
REVISION RECORD SHEET
PURPOSE
CREATION OF SURFACE PRODUCTION
FACILITIES (GGS) AT EAST KHAGORIJAN
Revision Index
DATASHEET FOR CONTROL VALVES
Datasheet NumberRev
Code
OIL-100-EK-I-DS-0807 A0 SHEET 4 OF 10
1 Documentation required :- Calibration Certificate, Material Certificates to 3.1 as per EN10204, weather proof certificate, Pressure test procedure/Report,
NDT Procedure/ report, Certified by CMRI, Operating & Maintenance Instructions & Spare Parts List.
2 All control valves to be supplied with SS 316 Name plate with Tag no. and details engraved .The tag plate shall be permanently secured.
3 Control valve sizing shall be as per ISA-75.01.
4 Flange finish shall be in accordance with relevant piping class and ANSI B16.5, for Raised Face (RF) flanges and shall be smooth finish to 125-250AARH .
5 Valve positioner shall be" SMART" type, 2-wire 24VDC loop powered communicating on 4-20mA signal mode with superimposed HART digital transmission signal.
6 The air filter regulator shall be provided with manual drainage facility, an integral pressure gauage and suitable for the design pressure, materials of construction
for body, spring case and bowl shall be SS316.
7 All Casting valve body and bonnet shall be 100% Radio graphed.
8 Valve bonnet shall have fully retained gasket.
9 The direction of flow through a valve shall be permanently marked on the body in the form of a casting stamping or permanently fixed “arrow” plate.
10 The Valves above 25Kgs shall be provided with eye bolts as per requirement for site handling.
11 The size of control valve shall be calculated from the rates of flow and pressure drops under design conditions.
12 All positioners shall be capable of both direct and reverse action and the design shall allow easy reversal in the field.
13 All positioner shall be supplied with two Pressure gauges for air supply pressure indication and regulator signal pressure indication.
14 The control valve shall be suitable for installation in horizondal as well in vertical lines.
15 Vendor shall examine each control valve for noise generation posibilities. The noise level shall be calculated as per ISA 75.17 or any other equivalent standard
16 Control valves shall meet design pressure and temperature ratings as indicated in the manual valve data sheet.
17
18
19
20 The valve actuator colour shall be Fail close valve - Red RAL colour 3000 and Fail open valve – Green RAL colour 6002.
21 Valve packing containing asbestos in any form is strictly prohibited
22 Actuator housing material shall be steel or anodised aluminium.
23 All brackets, fixings and fittings shall be constructed from 316 SS.
24 All valves shall be subject to NDE/NDT in accordance with ASME B16.34
25 Design life shall be 20 years.
26 Minimum, normal and maximum ambient temperature are 20°C, 26°C and 30°C.
27 Painting shall be as per Protective Coating specification for Onshore Structures and Facilities.
REFERENCE DOCUMENTS:
17039-EK-I-DB-8001_Functional specification for package instruments_Rev C
17039-CM-M-SP-2001_Piping material specification_Rev D
17039-CM-M-SP-2002_Valve material specificatio_Rev D
Actuator spring shall be corrosion reistant and shall be cadmium or nickel plated. Alternately vendor standard coating shall also be acceptable These shall be of the
enclosed type. The compression of the springs shall be adjustable.
Valve stem position indicator shall be provided for every control valve. The position indicator scale shall be marked from 0 to 100% in steps of 10%.
The hand wheel actuator shall be sized to provide the required thrust for valve positioning with 178N force applied to the hand wheel.
NOTES SHEET
CREATION OF SURFACE PRODUCTION
FACILITIES (GGS) AT EAST KHAGORIJAN
Revision Index
DATASHEET FOR CONTROL VALVES
TITLE ITEM/TAG No. DATA SHEET No.
DATASHEET FOR CONTROL VALVES
PROJECT DESCRIPTION PROJECT NO SHEET REV
5 OF 10 A0
MPC CONTRACTOR PURCHASE ORDER No. REQUISITION No. SPECIFICATION No.
CLIENT NAME REV No. BY DATE CKD DATE APP. DATE
A0 VS 27-Nov-18 PGN 27-Nov-18 MV 27-Nov-18 ISSUED FOR REVIEW
CLIENT DOCUMENT No.
-
ORIGINATOR ORIG. DATE
27-Nov-18
UNITS:- Pressure barg Kg/cm2(g) bara psi g Flow : Gas: MMSCFD Sm3/hr m
3/hr kg/hr
Temp 0 C
0 F Liquid: m
3/hr kg/hr USGPM KLPD
1
2 ΔP SIZING
3
4 INLET PRESSURE
5 OUTLET PRESSURE
6 INLET TEMPERATURE
7 SPEC WT/SPEC GRAV/MOL WT
8 VISCOSITY/SPEC HEAT RATIO cP
9 VAPOUR PRESSURE Pv
10 REQUIRED Cv (Cg)
11
12
13 COMPRESSIBILITY FACTOR
14 P&ID No & LINE No: 56
15 PIPE LINE SIZE IN / OUT 2"/ 2" 57 TYPE SPRING RETURN DIAPHRAGM
16 SCHEDULE mm XS 58 MFR & MODEL *
17 PIPE LINE INSULATION / STEAM TRACING 59 SIZE * EFF AREA *
18 DESIGN PRESS. & TEMP. 60 ON/OFF NA MODULATING
19 61
20 62 SPRING ACTION OPEN/CLOSE CLOSE
21 TYPE VALVE SPEC GLOBE GVBC01Z 63 MAX ALLOWABLE PRESSURE *
22 SIZE 1" 64 MIN REQUIRED PRESSURE *
23 MAX. PRESS./TEMP. TO SUIT DESIGN CONDITION 65 AVAILABLE AIR SUPPLY PRESSURE
24 MFR & MODEL * 66 MAX 8.5 NOR - MIN 6.5
25 67 BENCH RANGE *
26 BODY / BONNET MATERIAL CARBON STEEL A105 68 ACT ORIENTATION TOP
27 PTFE / 3mm 69 HANDWHEEL TYPE HEAVY DUTY
28 END CONNECTION IN : * / 300# RF 70 AIR FAILURE VALVE CLOSE
29 OUT : * / 300# RF 71 PNEUMATIC CONNECTION 1/4"
30 FLANGE FACE FINISH 125 - 250 AARH 72
31 BONNET TYPE BOLTED 73
32 FLOW DIRECTION OVER 74 TYPE : ELECTRO-PNEUMATIC (SMART)
33 LUB & ISOLATION VALVE NA 75 MFR & MODEL
34 PACKING MATERIAL EXPANDED GRAPHITE 76 ON INCR SIGNAL OUTPUT INCR/DECR INCR
35 PACKING TYPE GRAFOIL 77 GAUGES
36 78 CAM CHARACTERISTIC *
37 79 HOUSING PROTECTION / MATERIAL
38 TYPE 80 PORT CONNECTION 1/4" NPT
39 SIZE RATED TRAVEL 81
40 CHARACTERISTIC EQUAL % 82 MFR & MODEL *
41 BALANCED/UNBALANCED UNBALANCED 83 SET PRESSURE (ADJUSTABLE)
42 RATED Cv * 84 FILTER ELEMENT
43 PLUG MATERIAL A182 F316, STELLITED 85 FILTER SIZE 5 MICRON
44 SEAT MATERIAL A182 F316, STELLITED 86 AIRSET & FILTER MATERIAL SS 316
45 CAGE/GUIDE MATERIAL A182 F316, STELLITED 87 PNEUMATIC CONNECTION 1/4" NPT
46 STEM MATERIAL A182 F316, STELLITED 88
47 89
48 HAZARDOUS AREA CLASSIFICATION ZONE - 2, Gr IIA & IIB, T3 90 HYDRO TEST/ PRESSURE YES / 1.5 TIMES OF DESIGN PRESSURE
49 ENCLOSURE PROTECTION IP 65 91 ANSI/FCI LEAKAGE CLASS
50 GAUGES SHALL BE IN 'Kg/cm2(g)' UNITS YES 92 CV / DEAD BAND TEST NA
51 CABLE ENTRY 93 NA
52 STUD,BOLT, NUTS & GASKETS 94 NA
53 TUBING: 1/4" 95 NA
54 TUBE FITTING: 0.035" THICKNESS SS 316 96 REQUIRED
55 97
NOTES:- * - BY VENDOR
REFER NOTES SHEET.
VS
FLUID CRUDE OIL TYPE NON-CORROSIVE CRIT. PRESS : 14.5 kg/cm2
FLOW RATE KLPD 27 23 20
UNITS MAXIMUM FLOW NORMAL FLOW MINIMUM FLOW ΔP SHUTOFF
41-TV-3751 OIL-100-EK-I-DS-0807
CREATION OF SURFACE PRODUCTION FACILITIES (GGS) AT EAST KHAGORIJAN KIP-17039
- - 17039-EK-I-DB-8001 TBA
OIL INDIA LIMITED
DESCRIPTION
Kg/cm2(g) 4.5
Kg/cm2(g) 4.0
O C 100 27 - 50 27 - 50
0.839
2.887
Kg/cm2(g) 0.0133
1" HEAT CONSERVATION / NA
TRAVEL %
ACTUATOR (PNEUMATIC)
ALLOWABLE dBA ≤ 85 ≤ 85 ≤ 85
17039-EK-P-DW-0202-13/
2"-HM-41-3752-BC01-HC
IBR CERTIFICATE REQUIRED, FORM IIIC
CALIBRATION AND HYSTERESIS TEST
PERFORMANCE TEST
FUNCTIONAL TEST FOR ALL ACCESSORIES
1/2" NPTF
IP 65, Ex "ia" / SS 316
ASTM A 193 Gr. B7 / ASME B16.5 &
300# SPWND Gasket 4.5mm THK TO ASME B
16.20: Windings - SS316, Filler- CNAF, Inner
Ring -SS316, Outer Ring- CS
Kg/cm2(g)
ANSI FCI 70.2 (LATEST REVISION) / Class IV
* *
GAUGES SINTERED BRONZE YES
BOLT ADJUSTMENT SET POINT *
ACCESSORIES TESTS
ACTUATOR LEAKAGE TEST
TRIM
STANDARD
AIRSET
DIAPHGRAM MATERIAL *
POSITIONER (41-TY-3751)
*
BYPASS YES NO
12 & 250 YES
MAX. STROKING TIME *
VALVE BODY/BONNET
*
LINER MATERIAL/CORR. ALLOWANCE
Kg/cm2(g)SERIAL NUMBER
TITLE ITEM/TAG No. DATA SHEET No.
DATASHEET FOR CONTROL VALVES
PROJECT DESCRIPTION PROJECT NO SHEET REV
6 OF 10 A0
MPC CONTRACTOR PURCHASE ORDER No. REQUISITION No. SPECIFICATION No.
CLIENT NAME REV No. BY DATE CKD DATE APP. DATE
A0 VS 27-Nov-18 PGN 27-Nov-18 MV 27-Nov-18 ISSUED FOR REVIEW
CLIENT DOCUMENT No.
-
ORIGINATOR ORIG. DATE
27-Nov-18
UNITS:- Pressure barg Kg/cm2(g) bara psi g Flow : Gas: MMSCFD Sm3/hr m
3/hr kg/hr
Temp 0 C
0 F Liquid: m
3/hr kg/hr USGPM KLPD
1
2 ΔP SIZING
3
4 INLET PRESSURE
5 OUTLET PRESSURE
6 INLET TEMPERATURE
7 SPEC WT/SPEC GRAV/MOL WT
8 VISCOSITY/SPEC HEAT RATIO cP
9 VAPOUR PRESSURE Pv
10 REQUIRED Cv (Cg)
11
12
13 COMPRESSIBILITY FACTOR
14 P&ID No & LINE No: 56
15 PIPE LINE SIZE IN / OUT 3"/ 3" 57 TYPE SPRING RETURN DIAPHRAGM
16 SCHEDULE mm STD 58 MFR & MODEL *
17 PIPE LINE INSULATION / STEAM TRACING 59 SIZE * EFF AREA *
18 DESIGN PRESS. & TEMP. 60 ON/OFF NA MODULATING
19 61
20 62 SPRING ACTION OPEN/CLOSE CLOSE
21 TYPE VALVE SPEC GLOBE GVBC01R 63 MAX ALLOWABLE PRESSURE *
22 SIZE 2" 64 MIN REQUIRED PRESSURE *
23 MAX. PRESS./TEMP. TO SUIT DESIGN CONDITION 65 AVAILABLE AIR SUPPLY PRESSURE
24 MFR & MODEL * 66 MAX 8.5 NOR - MIN 6.5
25 67 BENCH RANGE *
26 BODY / BONNET MATERIAL CARBON STEEL A105 / A216 WCB 68 ACT ORIENTATION TOP
27 PTFE / 3mm 69 HANDWHEEL TYPE HEAVY DUTY
28 END CONNECTION IN : * / 300# RF 70 AIR FAILURE VALVE CLOSE
29 OUT : * / 300# RF 71 PNEUMATIC CONNECTION 1/4"
30 FLANGE FACE FINISH 125 - 250 AARH 72
31 BONNET TYPE BOLTED 73
32 FLOW DIRECTION OVER 74 TYPE : ELECTRO-PNEUMATIC (SMART)
33 LUB & ISOLATION VALVE NA 75 MFR & MODEL
34 PACKING MATERIAL EXPANDED GRAPHITE 76 ON INCR SIGNAL OUTPUT INCR/DECR INCR
35 PACKING TYPE GRAFOIL 77 GAUGES
36 78 CAM CHARACTERISTIC *
37 79 HOUSING PROTECTION / MATERIAL
38 TYPE 80 PORT CONNECTION 1/4" NPT
39 SIZE RATED TRAVEL 81
40 CHARACTERISTIC EQUAL % 82 MFR & MODEL *
41 BALANCED/UNBALANCED UNBALANCED 83 SET PRESSURE (ADJUSTABLE)
42 RATED Cv * 84 FILTER ELEMENT
43 PLUG MATERIAL A182 F316, STELLITED 85 FILTER SIZE 5 MICRON
44 SEAT MATERIAL A182 F316, STELLITED 86 AIRSET & FILTER MATERIAL SS 316
45 CAGE/GUIDE MATERIAL A182 F316, STELLITED 87 PNEUMATIC CONNECTION 1/4" NPT
46 STEM MATERIAL A182 F316, STELLITED 88
47 89
48 HAZARDOUS AREA CLASSIFICATION ZONE - 2, Gr IIA & IIB, T3 90 HYDRO TEST/ PRESSURE YES / 1.5 TIMES OF DESIGN PRESSURE
49 ENCLOSURE PROTECTION IP 65 91 ANSI/FCI LEAKAGE CLASS
50 GAUGES SHALL BE IN 'Kg/cm2(g)' UNITS YES 92 CV / DEAD BAND TEST NA
51 CABLE ENTRY 93 NA
52 STUD,BOLT, NUTS & GASKETS 94 NA
53 TUBING: 1/4" 95 NA
54 TUBE FITTING: 0.035" THICKNESS SS 316 96 REQUIRED
55 97
NOTES:- * - BY VENDOR
REFER NOTES SHEET.
PERFORMANCE TEST
FUNCTIONAL TEST FOR ALL ACCESSORIES
IBR CERTIFICATE REQUIRED, FORM IIIC
ACCESSORIES TESTS
1/2" NPTF ACTUATOR LEAKAGE TEST
ASTM A 193 Gr. B7 / ASME B16.5 &
300# SPWND Gasket 4.5mm THK TO ASME B
16.20: Windings - SS316, Filler- CNAF, Inner
Ring -SS316, Outer Ring- CS
CALIBRATION AND HYSTERESIS TEST
ANSI FCI 70.2 (LATEST REVISION) / Class IV
Kg/cm2(g)
GAUGES SINTERED BRONZE YES
BOLT ADJUSTMENT SET POINT *
TRIM IP 65, Ex "ia"/ SS 316
STANDARD
* * AIRSET
*
POSITIONER (41-TY-0991)
*
BYPASS YES NO
VALVE BODY/BONNET
SERIAL NUMBER * Kg/cm2(g)
LINER MATERIAL/CORR. ALLOWANCE
DIAPHGRAM MATERIAL
12 & 250 YES
MAX. STROKING TIME *
17039-EK-P-DW-0203-10/
3"-HM-41-3729-BC01-1NACTUATOR (PNEUMATIC)
1 1/2" HEAT CONSERVATION / NA
ALLOWABLE dBA ≤ 85 ≤ 85 ≤ 85
TRAVEL %
2.887
Kg/cm2(g) 0.0133
O C 100 100 100
0.834
Kg/cm2(g) 4.5
Kg/cm2(g) 4.0
FLOW RATE KLPD 28 24 21
UNITS MAXIMUM FLOW NORMAL FLOW MINIMUM FLOW ΔP SHUTOFF
DESCRIPTION
OIL INDIA LIMITED
VS
FLUID CRUDE OIL TYPE NON-CORROSIVE CRIT. PRESS : 14.5 kg/cm2
41-TV-0991 OIL-100-EK-I-DS-0807
CREATION OF SURFACE PRODUCTION FACILITIES (GGS) AT EAST KHAGORIJAN KIP-17039
TBA - - 17039-EK-I-DB-8001
TITLE ITEM/TAG No. DATA SHEET No.
DATASHEET FOR CONTROL VALVES
PROJECT DESCRIPTION PROJECT NO SHEET REV
7 OF 10 A0
MPC CONTRACTOR PURCHASE ORDER No. REQUISITION No. SPECIFICATION No.
CLIENT NAME REV No. BY DATE CKD DATE APP. DATE
A0 VS 27-Nov-18 PGN 27-Nov-18 MV 27-Nov-18 ISSUED FOR REVIEW
CLIENT DOCUMENT No.
-
ORIGINATOR ORIG. DATE
27-Nov-18
UNITS:- Pressure barg Kg/cm2(g) bara psi g Flow : Gas: MMSCFD Sm3/hr m
3/hr kg/hr
Temp 0 C
0 F Liquid: m
3/hr kg/hr USGPM KLPD
1
2 ΔP SIZING
3
4 INLET PRESSURE
5 OUTLET PRESSURE
6 INLET TEMPERATURE
7 SPEC WT/SPEC GRAV/MOL WT
8 VISCOSITY/SPEC HEAT RATIO cP
9 VAPOUR PRESSURE Pv
10 REQUIRED Cv (Cg)
11
12
13 COMPRESSIBILITY FACTOR
14 P&ID No & LINE No: 56
15 PIPE LINE SIZE IN / OUT 3"/ 3" 57 TYPE SPRING RETURN DIAPHRAGM
16 SCHEDULE mm STD 58 MFR & MODEL *
17 PIPE LINE INSULATION / STEAM TRACING 59 SIZE * EFF AREA *
18 DESIGN PRESS. & TEMP. 60 ON/OFF NA MODULATING
19 61
20 62 SPRING ACTION OPEN/CLOSE CLOSE
21 TYPE VALVE SPEC GLOBE GVBC01R 63 MAX ALLOWABLE PRESSURE *
22 SIZE 2" 64 MIN REQUIRED PRESSURE *
23 MAX. PRESS./TEMP. TO SUIT DESIGN CONDITION 65 AVAILABLE AIR SUPPLY PRESSURE
24 MFR & MODEL * 66 MAX 8.5 NOR - MIN 6.5
25 67 BENCH RANGE *
26 BODY / BONNET MATERIAL CARBON STEEL A216 WCB 68 ACT ORIENTATION TOP
27 PTFE / 3mm 69 HANDWHEEL TYPE HEAVY DUTY
28 END CONNECTION IN : * / 300# RF 70 AIR FAILURE VALVE CLOSE
29 OUT : * / 300# RF 71 PNEUMATIC CONNECTION 1/4"
30 FLANGE FACE FINISH 125 - 250 AARH 72
31 BONNET TYPE BOLTED 73
32 FLOW DIRECTION OVER 74 TYPE : ELECTRO-PNEUMATIC (SMART)
33 LUB & ISOLATION VALVE NA 75 MFR & MODEL
34 PACKING MATERIAL EXPANDED GRAPHITE 76 ON INCR SIGNAL OUTPUT INCR/DECR NOTE-12
35 PACKING TYPE GRAFOIL 77 GAUGES
36 78 CAM CHARACTERISTIC *
37 79 HOUSING PROTECTION / MATERIAL
38 TYPE 80 PORT CONNECTION 1/4" NPT
39 SIZE RATED TRAVEL 81
40 CHARACTERISTIC EQUAL % 82 MFR & MODEL *
41 BALANCED/UNBALANCED UNBALANCED 83 SET PRESSURE (ADJUSTABLE)
42 RATED Cv * 84 FILTER ELEMENT
43 PLUG MATERIAL A182 F316, STELLITED 85 FILTER SIZE 5 MICRON
44 SEAT MATERIAL A182 F316, STELLITED 86 AIRSET & FILTER MATERIAL SS 316
45 CAGE/GUIDE MATERIAL A182 F316, STELLITED 87 PNEUMATIC CONNECTION 1/4" NPT
46 STEM MATERIAL A182 F316, STELLITED 88
47 89
48 HAZARDOUS AREA CLASSIFICATION ZONE - 2, Gr IIA & IIB, T3 90 HYDRO TEST/ PRESSURE YES / 1.5 TIMES OF DESIGN PRESSURE
49 ENCLOSURE PROTECTION IP 65 91 ANSI/FCI LEAKAGE CLASS
50 GAUGES SHALL BE IN 'Kg/cm2(g)' UNITS YES 92 CV / DEAD BAND TEST NA
51 CABLE ENTRY 93 NA
52 STUD,BOLT, NUTS & GASKETS 94 NA
53 TUBING: 1/4" 95 NA
54 TUBE FITTING: 0.035" THICKNESS SS 316 96 REQUIRED
55 97
NOTES:- * - BY VENDOR
REFER NOTES SHEET.
PERFORMANCE TEST
FUNCTIONAL TEST FOR ALL ACCESSORIES
IBR CERTIFICATE REQUIRED, FORM IIIC
ACCESSORIES TESTS
1/2" NPTF ACTUATOR LEAKAGE TEST
ASTM A 193 Gr. B7 / ASME B16.5 &
300# SPWND Gasket 4.5mm THK TO ASME B
16.20: Windings - SS316, Filler- CNAF, Inner
Ring -SS316, Outer Ring- CS
CALIBRATION AND HYSTERESIS TEST
ANSI FCI 70.2 (LATEST REVISION) / Class IV
Kg/cm2(g)
GAUGES SINTERED BRONZE YES
BOLT ADJUSTMENT SET POINT *
TRIM IP 65, Ex "ia" / SS 316
STANDARD
* * AIRSET
*
POSITIONER (41-TY-0992)
*
BYPASS YES NO
VALVE BODY/BONNET
SERIAL NUMBER * Kg/cm2(g)
LINER MATERIAL/CORR. ALLOWANCE
DIAPHGRAM MATERIAL
12 & 250 YES
MAX. STROKING TIME *
17039-EK-P-DW-0203-11/
3"-HM-41-3736-BC01-1NACTUATOR (PNEUMATIC)
1 1/2" HEAT CONSERVATION / NA
ALLOWABLE dBA ≤ 85 ≤ 85 ≤ 85
TRAVEL %
2.887
Kg/cm2(g) 0.0133
O C 100 100 100
0.834
Kg/cm2(g) 4.5
Kg/cm2(g) 4.0
FLOW RATE KLPD 28 24 21
UNITS MAXIMUM FLOW NORMAL FLOW MINIMUM FLOW ΔP SHUTOFF
DESCRIPTION
OIL INDIA LIMITED
VS
FLUID CRUDE OIL TYPE NON-CORROSIVE CRIT. PRESS : 14.5 kg/cm2
41-TV-0992 OIL-100-EK-I-DS-0807
CREATION OF SURFACE PRODUCTION FACILITIES (GGS) AT EAST KHAGORIJAN KIP-17039
TBA - - 17039-EK-I-DB-8001
TITLE ITEM/TAG No. DATA SHEET No.
DATASHEET FOR CONTROL VALVES
PROJECT DESCRIPTION PROJECT NO SHEET REV
8 OF 10 A0
MPC CONTRACTOR PURCHASE ORDER No. REQUISITION No. SPECIFICATION No.
CLIENT NAME REV No. BY DATE CKD DATE APP. DATE
A0 VS 27-Nov-18 PGN 27-Nov-18 MV 27-Nov-18 ISSUED FOR REVIEW
CLIENT DOCUMENT No.
-
ORIGINATOR ORIG. DATE
27-Nov-18
UNITS:- Pressure barg Kg/cm2(g) bara psi g Flow : Gas: MMSCFD Sm3/hr m
3/hr kg/hr
Temp 0 C
0 F Liquid: m
3/hr kg/hr USGPM KLPD
1
2 ΔP SIZING
3
4 INLET PRESSURE
5 OUTLET PRESSURE
6 INLET TEMPERATURE
7 SPEC WT/SPEC GRAV/MOL WT
8 VISCOSITY/SPEC HEAT RATIO cP
9 VAPOUR PRESSURE Pv
10 REQUIRED Cv (Cg)
11
12
13 COMPRESSIBILITY FACTOR
14 P&ID No & LINE No: 56
15 PIPE LINE SIZE IN / OUT 3"/ 3" 57 TYPE SPRING RETURN DIAPHRAGM
16 SCHEDULE mm STD 58 MFR & MODEL *
17 PIPE LINE INSULATION / STEAM TRACING 59 SIZE * EFF AREA *
18 DESIGN PRESS. & TEMP. 60 ON/OFF NA MODULATING
19 61
20 62 SPRING ACTION OPEN/CLOSE CLOSE
21 TYPE VALVE SPEC GLOBE GVBC01R 63 MAX ALLOWABLE PRESSURE *
22 SIZE 2" 64 MIN REQUIRED PRESSURE *
23 MAX. PRESS./TEMP. TO SUIT DESIGN CONDITION 65 AVAILABLE AIR SUPPLY PRESSURE
24 MFR & MODEL * 66 MAX 8.5 NOR - MIN 6.5
25 67 BENCH RANGE *
26 BODY / BONNET MATERIAL CARBON STEEL A216 WCB 68 ACT ORIENTATION TOP
27 PTFE/ 3mm 69 HANDWHEEL TYPE HEAVY DUTY
28 END CONNECTION IN : */ 300# RF 70 AIR FAILURE VALVE CLOSE
29 OUT : */ 300# RF 71 PNEUMATIC CONNECTION 1/4"
30 FLANGE FACE FINISH 125 - 250 AARH 72
31 BONNET TYPE BOLTED 73
32 FLOW DIRECTION OVER 74 TYPE : ELECTRO-PNEUMATIC (SMART)
33 LUB & ISOLATION VALVE NA 75 MFR & MODEL
34 PACKING MATERIAL EXPANDED GRAPHITE 76 ON INCR SIGNAL OUTPUT INCR/DECR NOTE-12
35 PACKING TYPE GRAFOIL 77 GAUGES
36 78 CAM CHARACTERISTIC *
37 79 HOUSING PROTECTION / MATERIAL
38 TYPE 80 PORT CONNECTION 1/4" NPT
39 SIZE RATED TRAVEL 81
40 CHARACTERISTIC EQUAL % 82 MFR & MODEL *
41 BALANCED/UNBALANCED UNBALANCED 83 SET PRESSURE (ADJUSTABLE)
42 RATED Cv * 84 FILTER ELEMENT
43 PLUG MATERIAL A182 F316, STELLITED 85 FILTER SIZE 5 MICRON
44 SEAT MATERIAL A182 F316, STELLITED 86 AIRSET & FILTER MATERIAL SS 316
45 CAGE/GUIDE MATERIAL A182 F316, STELLITED 87 PNEUMATIC CONNECTION 1/4" NPT
46 STEM MATERIAL A182 F316, STELLITED 88
47 89
48 HAZARDOUS AREA CLASSIFICATION ZONE - 2, Gr IIA & IIB, T3 90 HYDRO TEST/ PRESSURE YES / 1.5 TIMES OF DESIGN PRESSURE
49 ENCLOSURE PROTECTION IP 65 91 ANSI/FCI LEAKAGE CLASS
50 GAUGES SHALL BE IN 'Kg/cm2(g)' UNITS YES 92 CV / DEAD BAND TEST NA
51 CABLE ENTRY 93 NA
52 STUD,BOLT, NUTS & GASKETS 94 NA
53 TUBING: 1/4" 95 NA
54 TUBE FITTING: 0.035" THICKNESS SS 316 96 REQUIRED
55 97
NOTES:- * - BY VENDOR
REFER NOTES SHEET.
PERFORMANCE TEST
FUNCTIONAL TEST FOR ALL ACCESSORIES
IBR CERTIFICATE REQUIRED, FORM IIIC
ACCESSORIES TESTS
1/2" NPTF ACTUATOR LEAKAGE TEST
ASTM A 193 Gr. B7 / ASME B16.5 &
300# SPWND Gasket 4.5mm THK TO ASME B
16.20: Windings - SS316, Filler- CNAF, Inner
Ring -SS316, Outer Ring- CS
CALIBRATION AND HYSTERESIS TEST
ANSI FCI 70.2 (LATEST REVISION) / Class IV
Kg/cm2(g)
GAUGES SINTERED BRONZE YES
BOLT ADJUSTMENT SET POINT *
TRIM IP 65, Ex "ia" / SS 316
STANDARD
* * AIRSET
*
POSITIONER (41-TY-0431)
*
BYPASS YES NO
VALVE BODY/BONNET
SERIAL NUMBER * Kg/cm2(g)
LINER MATERIAL/CORR. ALLOWANCE
DIAPHGRAM MATERIAL
FOL+0.07 & 90 YES
MAX. STROKING TIME *
17039-EK-P-DW-0203-14/ 3"-
HM-41-8612-BC01-1NACTUATOR (PNEUMATIC)
1" HEAT CONSERVATION / NA
ALLOWABLE dBA ≤ 85 ≤ 85 ≤ 85
TRAVEL %
2.887
Kg/cm2(g) 0.0133
O C 100 100 100
0.834
Kg/cm2(g) 4.5
Kg/cm2(g) 4.0
FLOW RATE KLPD 28 24 21
UNITS MAXIMUM FLOW NORMAL FLOW MINIMUM FLOW ΔP SHUTOFF
DESCRIPTION
OIL INDIA LIMITED
VS
FLUID OFFSPEC CRUDE OIL TYPE NON-CORROSIVE CRIT. PRESS : 14.5 kg/cm2
41-TV-0431 OIL-100-EK-I-DS-0807
CREATION OF SURFACE PRODUCTION FACILITIES (GGS) AT EAST KHAGORIJAN KIP-17039
TBA - - 17039-EK-I-DB-8001
TITLE ITEM/TAG No. DATA SHEET No.
DATASHEET FOR CONTROL VALVES
PROJECT DESCRIPTION PROJECT NO SHEET REV
9 OF 10 A0
MPC CONTRACTOR PURCHASE ORDER No. REQUISITION No. SPECIFICATION No.
CLIENT NAME REV No. BY DATE CKD DATE APP. DATE
A0 VS 27-Nov-18 PGN 27-Nov-18 MV 27-Nov-18 ISSUED FOR REVIEW
CLIENT DOCUMENT No.
-
ORIGINATOR ORIG. DATE
27-Nov-18
UNITS:- Pressure barg Kg/cm2(g) bara psi g Flow : Gas: MMSCFD Sm3/hr m
3/hr kg/hr
Temp 0 C
0 F Liquid: m
3/hr kg/hr USGPM KLPD
1
2 ΔP SIZING
3
4 INLET PRESSURE
5 OUTLET PRESSURE
6 INLET TEMPERATURE
7 SPEC WT/SPEC GRAV/MOL WT
8 VISCOSITY/SPEC HEAT RATIO cP
9 VAPOUR PRESSURE Pv
10 REQUIRED Cv (Cg)
11
12
13 COMPRESSIBILITY FACTOR
14 P&ID No & LINE No: 56
15 PIPE LINE SIZE IN / OUT 2"/ 2" 57 TYPE SPRING RETURN DIAPHRAGM
16 SCHEDULE mm XS 58 MFR & MODEL *
17 PIPE LINE INSULATION / STEAM TRACING 59 SIZE * EFF AREA *
18 DESIGN PRESS. & TEMP. 60 ON/OFF NA MODULATING
19 61
20 62 SPRING ACTION OPEN/CLOSE CLOSE
21 TYPE VALVE SPEC GLOBE GVBC01Z 63 MAX ALLOWABLE PRESSURE *
22 SIZE 1" 64 MIN REQUIRED PRESSURE *
23 MAX. PRESS./TEMP. TO SUIT DESIGN CONDITION 65 AVAILABLE AIR SUPPLY PRESSURE
24 MFR & MODEL * 66 MAX 8.5 NOR - MIN 6.5
25 67 BENCH RANGE *
26 BODY / BONNET MATERIAL CARBON STEEL A216 WCB 68 ACT ORIENTATION TOP
27 PTFE/ 3mm 69 HANDWHEEL TYPE HEAVY DUTY
28 END CONNECTION IN : */ 300# RF 70 AIR FAILURE VALVE CLOSE
29 OUT : */ 300# RF 71 PNEUMATIC CONNECTION 1/4"
30 FLANGE FACE FINISH 125 - 250 AARH 72
31 BONNET TYPE BOLTED 73
32 FLOW DIRECTION OVER 74 TYPE : ELECTRO-PNEUMATIC (SMART)
33 LUB & ISOLATION VALVE NA 75 MFR & MODEL
34 PACKING MATERIAL EXPANDED GRAPHITE 76 ON INCR SIGNAL OUTPUT INCR/DECR NOTE-12
35 PACKING TYPE GRAFOIL 77 GAUGES
36 78 CAM CHARACTERISTIC *
37 79 HOUSING PROTECTION / MATERIAL
38 TYPE 80 PORT CONNECTION 1/4" NPT
39 SIZE RATED TRAVEL 81
40 CHARACTERISTIC EQUAL % 82 MFR & MODEL *
41 BALANCED/UNBALANCED UNBALANCED 83 SET PRESSURE (ADJUSTABLE)
42 RATED Cv * 84 FILTER ELEMENT
43 PLUG MATERIAL A182 F316, STELLITED 85 FILTER SIZE 5 MICRON
44 SEAT MATERIAL A182 F316, STELLITED 86 AIRSET & FILTER MATERIAL SS 316
45 CAGE/GUIDE MATERIAL A182 F316, STELLITED 87 PNEUMATIC CONNECTION 1/4" NPT
46 STEM MATERIAL A182 F316, STELLITED 88
47 89
48 HAZARDOUS AREA CLASSIFICATION ZONE - 2, Gr IIA & IIB, T3 90 HYDRO TEST/ PRESSURE YES / 1.5 TIMES OF DESIGN PRESSURE
49 ENCLOSURE PROTECTION IP 65 91 ANSI/FCI LEAKAGE CLASS
50 GAUGES SHALL BE IN 'Kg/cm2(g)' UNITS YES 92 CV / DEAD BAND TEST NA
51 CABLE ENTRY 93 NA
52 STUD,BOLT, NUTS & GASKETS 94 NA
53 TUBING: 1/4" 95 NA
54 TUBE FITTING: 0.035" THICKNESS SS 316 96 REQUIRED
55 97
NOTES:- * - BY VENDOR
REFER NOTES SHEET.
PERFORMANCE TEST
FUNCTIONAL TEST FOR ALL ACCESSORIES
IBR CERTIFICATE REQUIRED, FORM IIIC
ACCESSORIES TESTS
1/2" NPTF ACTUATOR LEAKAGE TEST
ASTM A 193 Gr. B7 / ASME B16.5 &
300# SPWND Gasket 4.5mm THK TO ASME B
16.20: Windings - SS316, Filler- CNAF, Inner
Ring -SS316, Outer Ring- CS
CALIBRATION AND HYSTERESIS TEST
ANSI FCI 70.2 (LATEST REVISION) / Class IV
Kg/cm2(g)
GAUGES SINTERED BRONZE YES
BOLT ADJUSTMENT SET POINT *
TRIM IP 65, Ex "ia" / SS 316
STANDARD
* * AIRSET
*
POSITIONER (66-TY-6622)
*
BYPASS YES NO
VALVE BODY/BONNET
SERIAL NUMBER * Kg/cm2(g)
LINER MATERIAL/CORR. ALLOWANCE
DIAPHGRAM MATERIAL
12 & 250 YES
MAX. STROKING TIME *
17039-EK-P-DW-0206-04/
2"-HM-41-6642-BC01-1NACTUATOR (PNEUMATIC)
1 1/2" HEAT CONSERVATION / NA
ALLOWABLE dBA ≤ 85 ≤ 85 ≤ 85
TRAVEL %
2.887
Kg/cm2(g) 0.0133
O C 100 100 100
0.834
Kg/cm2(g) 4.5
Kg/cm2(g) 4.0
FLOW RATE KLPD 8.5 8 4.5
UNITS MAXIMUM FLOW NORMAL FLOW MINIMUM FLOW ΔP SHUTOFF
DESCRIPTION
OIL INDIA LIMITED
VS
FLUID SKIM OIL TYPE NON-CORROSIVE CRIT. PRESS : 14.5 kg/cm2
66-TV-6622 OIL-100-EK-I-DS-0807
CREATION OF SURFACE PRODUCTION FACILITIES (GGS) AT EAST KHAGORIJAN KIP-17039
TBA - - 17039-EK-I-DB-8001
TITLE ITEM/TAG No. DATA SHEET No.
DATASHEET FOR CONTROL VALVES
PROJECT DESCRIPTION PROJECT NO SHEET REV
10 OF 10 A0
MPC CONTRACTOR PURCHASE ORDER No. REQUISITION No. SPECIFICATION No.
CLIENT NAME REV No. BY DATE CKD DATE APP. DATE
A0 VS 27-Nov-18 PGN 27-Nov-18 MV 27-Nov-18 ISSUED FOR REVIEW
CLIENT DOCUMENT No.
-
ORIGINATOR ORIG. DATE
27-Nov-18
UNITS:- Pressure barg Kg/cm2(g) bara psi g Flow : Gas: MMSCFD Sm3/hr m
3/hr kg/hr
Temp 0 C
0 F Liquid: m
3/hr kg/hr USGPM KLPD
1
2 ΔP SIZING
3
4 INLET PRESSURE
5 OUTLET PRESSURE
6 INLET TEMPERATURE
7 SPEC WT/SPEC GRAV/MOL WT
8 VISCOSITY/SPEC HEAT RATIO cP
9 VAPOUR PRESSURE Pv
10 REQUIRED Cv (Cg)
11
12
13 COMPRESSIBILITY FACTOR
14 P&ID No & LINE No: 56
15 PIPE LINE SIZE IN / OUT 3"/ 3" 57 TYPE SPRING RETURN DIAPHRAGM
16 SCHEDULE mm STD 58 MFR & MODEL *
17 PIPE LINE INSULATION / STEAM TRACING 59 SIZE * EFF AREA *
18 DESIGN PRESS. & TEMP. 60 ON/OFF NA MODULATING
19 61
20 62 SPRING ACTION OPEN/CLOSE OPEN
21 TYPE VALVE SPEC GLOBE GVBC01R 63 MAX ALLOWABLE PRESSURE *
22 SIZE 2" 64 MIN REQUIRED PRESSURE *
23 MAX. PRESS./TEMP. TO SUIT DESIGN CONDITION 65 AVAILABLE AIR SUPPLY PRESSURE
24 MFR & MODEL * 66 MAX 8.5 NOR - MIN 6.5
25 67 BENCH RANGE *
26 BODY / BONNET MATERIAL CARBON STEEL A216 WCB 68 ACT ORIENTATION TOP
27 PTFE/ 3mm 69 HANDWHEEL TYPE HEAVY DUTY
28 END CONNECTION IN : */ 150# RF 70 AIR FAILURE VALVE OPEN
29 OUT : */ 150# RF 71 PNEUMATIC CONNECTION 1/4"
30 FLANGE FACE FINISH 125 - 250 AARH 72
31 BONNET TYPE BOLTED 73
32 FLOW DIRECTION UNDER 74 TYPE : ELECTRO-PNEUMATIC (SMART)
33 LUB & ISOLATION VALVE NA 75 MFR & MODEL
34 PACKING MATERIAL EXPANDED GRAPHITE 76 ON INCR SIGNAL OUTPUT INCR/DECR NOTE-12
35 PACKING TYPE GRAFOIL 77 GAUGES
36 78 CAM CHARACTERISTIC *
37 79 HOUSING PROTECTION / MATERIAL
38 TYPE 80 PORT CONNECTION 1/4" NPT
39 SIZE RATED TRAVEL 81
40 CHARACTERISTIC EQUAL % 82 MFR & MODEL *
41 BALANCED/UNBALANCED UNBALANCED 83 SET PRESSURE (ADJUSTABLE)
42 RATED Cv * 84 FILTER ELEMENT
43 PLUG MATERIAL A182 F316, STELLITED 85 FILTER SIZE 5 MICRON
44 SEAT MATERIAL A182 F316, STELLITED 86 AIRSET & FILTER MATERIAL SS 316
45 CAGE/GUIDE MATERIAL A182 F316, STELLITED 87 PNEUMATIC CONNECTION 1/4" NPT
46 STEM MATERIAL A182 F316, STELLITED 88
47 89
48 HAZARDOUS AREA CLASSIFICATION ZONE - 2, Gr IIA & IIB, T3 90 HYDRO TEST/ PRESSURE YES / 1.5 TIMES OF DESIGN PRESSURE
49 ENCLOSURE PROTECTION IP 65 91 ANSI/FCI LEAKAGE CLASS
50 GAUGES SHALL BE IN 'Kg/cm2(g)' UNITS YES 92 CV / DEAD BAND TEST NA
51 CABLE ENTRY 93 NA
52 STUD,BOLT, NUTS & GASKETS 94 NA
53 TUBING: 1/4" 95 NA
54 TUBE FITTING: 0.035" THICKNESS SS 316 96 REQUIRED
55 97
NOTES:- * - BY VENDOR
REFER NOTES SHEET.
DESCRIPTION
OIL INDIA LIMITED
VS
FLUID OFF SPEC EFFLUENT WATER TYPE NON-CORROSIVE CRIT. PRESS : 14.5 kg/cm2
66-TV-6635 OIL-100-EK-I-DS-0807
CREATION OF SURFACE PRODUCTION FACILITIES (GGS) AT EAST KHAGORIJAN KIP-17039
TBA - - 17039-EK-I-DB-8001
FLOW RATE KLPD 385 335 285
UNITS MAXIMUM FLOW NORMAL FLOW MINIMUM FLOW ΔP SHUTOFF
Kg/cm2(g) 5
Kg/cm2(g) ATM
O C 55 55 55
4.932
psia 2.472
TRAVEL %
17039-EK-P-DW-0206-06/
3"-WE-66-6661-AC01ACTUATOR (PNEUMATIC)
ALLOWABLE dBA ≤ 85 ≤ 85 ≤ 85
SERIAL NUMBER * Kg/cm2(g)
LINER MATERIAL/CORR. ALLOWANCE
DIAPHGRAM MATERIAL *
NA
FOW+0.07 & 85 YES
MAX. STROKING TIME *
VALVE BODY/BONNET
STANDARD
* * AIRSET
Kg/cm2(g)
GAUGES SINTERED BRONZE YES
POSITIONER (66-TY-6635)
*
BYPASS YES NO
TRIM IP 65, Ex "ia" / SS 316
ASTM A 193 Gr. B7 / ASME B16.5 &
150# SPWND Gasket 4.5mm THK TO ASME B
16.20: Windings - SS316, Filler- CNAF, Inner
Ring -SS316, Outer Ring- CS
CALIBRATION AND HYSTERESIS TEST
PERFORMANCE TEST
FUNCTIONAL TEST FOR ALL ACCESSORIES
IBR CERTIFICATE REQUIRED, FORM IIIC
BOLT ADJUSTMENT SET POINT *
ACCESSORIES TESTS
ANSI FCI 70.2 (LATEST REVISION) / Class IV
1/2" NPTF ACTUATOR LEAKAGE TEST
Datasheet No.Rev
Code
OIL-100-ND-I-DS-0808 A0 Sht.No:02 of 07
6. DS-2 06 of 07
7. DS-3 07 of 07
5. DS-1 05 of 07
Description Sheet Number
1. Cover Sheet 01 of 07
2. Index Sheet 02 of 07
CREATION OF SURFACE PRODUCTION
FACILITIES (OCS) AT NADUA
Revision Index
DATA SHEET FOR PRESSURE SAFETY VALVE
3. Revision Sheet 03 of 07
4. Notes Sheet 04 of 07
TABLE OF CONTENTS
Datasheet No.Rev
Code
OIL-100-ND-I-DS-0808 A0 Sht.No: 03 of 07
RevTenability for
extra Claim Impact on MTO
A0
Revision IndexCREATION OF SURFACE PRODUCTION FACILITIES (OCS)
AT NADUA
DATA SHEET FOR PRESSURE SAFETY VALVE
Rev Disc. Reasons
Issued for Review
REVISION List
HOLD List
Datasheet No.Rev
Code
OIL-100-ND-I-DS-0808 A0 04 of 07
secured.
3. Nozzle,Seat and Disc for the above tags shall be forged.
4. All stud bolt and nut material shall be ASTM A193 Gr. B7M & Heavy hex nuts shall be ASTM A194 Gr. 2HM.
5. Painting shall be as per Protective Coating specification for Onshore Structures and Facilities.
6. All castings and welding shall be 100% radio graphed.
7. Carbon steel springs with Nickel plating shall be used for temperature services lower than 250 Deg C.
Tungsten alloy springs shall be used for temperatures greater than 250 Deg.C.
8. All relief valves of size 1" and above shall be full nozzle full lift type. Relief valves with size less than 1" shall be modified
nozzle type.
9. The pressure relief valve shall meet the requirements of API recommended practice RP 526 ‚Flanged Steel Safety Relief
Valves and RP 521‚ Pressure Relieving and Anti Pressurizing system and shall be of direct acting angle pattern,
full nozzle entry and high capacity type.
Notes:
1. Documentation required :- Calibration Certificate,Material Certificates to 3.1 as per EN10204, Pressure test procedure/ Report,
NDT procedure / Report, Operating & Maintenance Instructions & Spare Parts List, Hydro Test, Pop test report & Installation
dimension Drawings.
2. All Instruments to be supplied with SS316 name plate with tag no. permanently inscribed. Tags shall be permanently
CREATION OF SURFACE PRODUCTION
FACILITIES (OCS) AT NADUA
Revision Index
DATA SHEET FOR PRESSURE SAFETY VALVE
TITLE ITEM/TAG No. DATA SHEET No.
DATA SHEET FOR PRESSURE SAFETY VALVE
PROJECT DESCRIPTION PROJECT No. SHEET REV
CREATION OF SURFACE PRODUCTION FACILITIES (OCS) AT NADUA 05 OF 07 A0
MPC CONTRACTOR PURCHASE ORDER No. REQUISITION NO. SPECIFICATION No.
TBA
CLIENT NAME REV No. BY DATE DATE APP. DATE
OIL INDIA LIMITED / TEC LIMITED A0 IMR 28-Nov-18 28-Nov-18 MSR/ VSR 28-Nov-18
CLIENT DOCUMENT No.
-
ORIGINATOR ORIG. DATE
19-Sep-18
UNITS:- Pressure psig kg/cm2 g kPag Flow : Gas MMscfd Sm
3/hr
Temp O C O F Liquid: m3/hr USgpm
1 TAG No.
2 SERVICE
3 VESSEL No.
4 LINE No.
5 P &ID NUMBER
6 FULL NOZZLE/SEMI-NOZZLE
7 SAFETY / RELIEF / SAFETY RELIEF
8 CONV., BELLOWS, PILOT OP.
9 BONNET TYPE
10 SIZE INLET OUTLET 1" 1" 1" 1"
11 FL. RATING INLET 300# 300# 300# 300#
12 FL. FACE INLET OUTLET RF RF RF RF
13 BODY
14 BONNET
15 NOZZLE, SEAT and DISC
16 RESILIENT SEAT SEAL
17 GUIDE AND RINGS
18 SPRING
19 BELLOWS
20 CAP: SCREWED or BOLTED
21 LEVER: OPEN or PACKED
22 TEST GAG
23 CODE
24 BASIS
25 VESSEL SIZE DIA X T/T
26 FLUID STATE HOT OIL HOT OIL LIQUID HOT OIL
27
28 OPERATING S.G MOL. WEIGHT
29 OPER. PRESS SET PRESS ATM ATM 5.5 5.5
30 OPER. TEMP REL. TEMP 27-50 27-50 200 200
31 CONSTANT
32 BACK PRESSURE VARIABLE
33 TOTAL
34 % ALLOWABLE OVER PRESSURE
35 OVER PRESSURE FACTOR
36 COMPRESSIBILITY FACTOR
37 LATENT HEAT OF VAPORIZATION (KJ/Kg)
38 RATIO OF SPECIFIC HEATS Cp / Cv
39 OPERATING VISCOSITY cP
40 VAPOUR GAS MASS FRACTION
41 BAROMETRIC PRESSURE
42 ENVIRONMENTAL FACTOR
43 VESSEL / WETTED
44 RATED CAPACITY
45 CALCULATED AREA inch2
46 SELECTED AREA inch2
47 ORIFICE DESIGNATION
48 MANUFACTURER
49 MODEL No.
50 NOTES:-
51 REFER NOTES SHEET
52
53
54
55
56
57
58
59
KIP-17039
- -
REFER BELOW OIL-100-ND-I-DS-0808
CKD DESCRIPTION
MV ISSUED FOR REVIEW
2"-HM-41-3753-BC01 2"-HM-41-3753A-BC01 2"-HM-41-3734-BC01-1N 2"-HM-41-3734A-BC01-1N
20-PSV-1380A 20-PSV-1380B 41-PSV-3728A 41-PSV-3728B
FULL NOZZLE, FULL LIFT FULL NOZZLE, FULL LIFT FULL NOZZLE, FULL LIFT FULL NOZZLE, FULL LIFT
SAFETY RELIEF SAFETY RELIEF SAFETY RELIEF SAFETY RELIEF
CONVENTIONAL CONVENTIONAL CONVENTIONAL CONVENTIONAL
CLOSED BONNET CLOSED BONNET CLOSED BONNET CLOSED BONNET
2"
300#
RF
2"
300#
RF
2"
IMR
barg MMSCMD kg/hr
kg/hr BLPD
N/A N/A N/A N/A
REQUIRED
17039-ND-P-DW-0202-20 17039-ND-P-DW-0202-20 17039-ND-P-DW-0203-10 17039-ND-P-DW-0203-10
300#
RF
2"
300#
RF
N/A N/A N/A N/A
SS 316 SS 316 SS 316 SS 316
SS 316 SS 316
Hot Oil Return to Hot Oil
Return Drum
Hot Oil Return to Hot Oil Return Drum
Bypass
Hot oil to Hot Oil Drain Tank
(ND-MBD-3320)
Hot oil to Hot Oil Drain Tank
(ND-MBD-3320) Bypass
- - - -
OUTLET
CS, ASTM A105 CS, ASTM A105 CS, ASTM A105 CS, ASTM A105
CARBON STEEL CARBON STEEL CARBON STEEL CARBON STEEL
SS 316 SS 316 SS 316 SS 316
SCREWED SCREWED SCREWED SCREWED
SS 316
CS with Nickle Plate CS with Nickle Plate CS with Nickle Plate CS with Nickle Plate
SS 316
REQUIRED REQUIRED REQUIRED
TBA TBA TBA TBA
LIQUID LIQUID HOT OIL
API RP 520 API RP 520 API RP 520 API RP 520
THERMAL EXPANSION THERMAL EXPANSION THERMAL EXPANSION THERMAL EXPANSION
LIQUID
12 12 12 12
* * * *
* *
* * * *
* * * *
* *
* BY VENDOR
GE
NE
RA
LC
ON
NE
CT
ION
MA
TE
RIA
LO
PT
ION
SF
LU
ID D
AT
A
REQUIRED CAPACITY (VAPOUR/LIQUID)
* * * *
TITLE ITEM/TAG No. DATA SHEET No.
PRESSURE SAFETY VALVE
PROJECT DESCRIPTION PROJECT No. SHEET REV
CREATION OF SURFACE PRODUCTION FACILITIES (OCS) AT NADUA 06 OF 07 A0
MPC CONTRACTOR PURCHASE ORDER No. REQUISITION NO. SPECIFICATION No.
TBA
CLIENT NAME REV No. BY DATE DATE APP. DATE
OIL INDIA LIMITED / TEC LIMITED A0 IMR 28-Nov-18 28-Nov-18 MSR/ VSR 28-Nov-18
CLIENT DOCUMENT No.
-
ORIGINATOR ORIG. DATE
19-Sep-18
UNITS:- Pressure psig kg/cm2 g kPag Flow : Gas MMscfd Sm
3/hr
Temp O C O F Liquid: m3/hr USgpm
1 TAG No.
2 SERVICE
3 VESSEL No.
4 LINE No.
5 P &ID NUMBER
6 FULL NOZZLE/SEMI-NOZZLE
7 SAFETY / RELIEF / SAFETY RELIEF
8 CONV., BELLOWS, PILOT OP.
9 BONNET TYPE
10 SIZE INLET OUTLET 1" 1" 1" 1"
11 FL. RATING INLET 300# 300# 300# 300#
12 FL. FACE INLET OUTLET RF RF RF RF
13 BODY
14 BONNET
15 NOZZLE, SEAT and DISC
16 RESILIENT SEAT SEAL
17 GUIDE AND RINGS
18 SPRING
19 BELLOWS
20 CAP: SCREWED or BOLTED
21 LEVER: OPEN or PACKED
22 TEST GAG
23 CODE
24 BASIS
25 VESSEL SIZE DIA X T/T
26 FLUID STATE HOT OIL HOT OIL LIQUID HOT OIL
27
28 OPERATING S.G MOL. WEIGHT
29 OPER. PRESS SET PRESS 5.5 5.5 5.5 5.5
30 OPER. TEMP REL. TEMP 200 200 200 200
31 CONSTANT
32 BACK PRESSURE VARIABLE
33 TOTAL
34 % ALLOWABLE OVER PRESSURE
35 OVER PRESSURE FACTOR
36 COMPRESSIBILITY FACTOR
37 LATENT HEAT OF VAPORIZATION (KJ/Kg)
38 RATIO OF SPECIFIC HEATS Cp / Cv
39 OPERATING VISCOSITY cP
40 VAPOUR GAS MASS FRACTION
41 BAROMETRIC PRESSURE
42 ENVIRONMENTAL FACTOR
43 VESSEL / WETTED
44 RATED CAPACITY
45 CALCULATED AREA inch2
46 SELECTED AREA inch2
47 ORIFICE DESIGNATION
48 MANUFACTURER
49 MODEL No.
50 NOTES:-
51 REFER NOTES SHEET
52
53
54
55
56
57
58
59
* BY VENDOR
* * * *
* * * *
* * * *
* * * *
* * * *
12 12 12 12
API RP 520 API RP 520 API RP 520
FL
UID
DA
TA
LIQUID LIQUID HOT OIL LIQUID
REQUIRED CAPACITY (VAPOUR/LIQUID)
SS 316 SS 316
OP
TIO
NS
SCREWED SCREWED SCREWED SCREWED
N/A N/A N/A N/A
REQUIRED
THERMAL EXPANSION THERMAL EXPANSION THERMAL EXPANSION THERMAL EXPANSION
TBA TBA TBA TBA
REQUIRED REQUIRED REQUIRED
API RP 520
MA
TE
RIA
L
CS, ASTM A105 CS, ASTM A105 CS, ASTM A105 CS, ASTM A105
CARBON STEEL CARBON STEEL CARBON STEEL CARBON STEEL
CS with Nickle Plate CS with Nickle Plate CS with Nickle Plate CS with Nickle Plate
N/A N/A N/A N/A
SS 316 SS 316 SS 316 SS 316
SS 316 SS 316
RF RF RF
CLOSED BONNET CLOSED BONNET CLOSED BONNET CLOSED BONNET
SS 316 SS 316 SS 316 SS 316
CO
NN
EC
TIO
N 2" 2" 2" 2"
OUTLET
SAFETY RELIEF SAFETY RELIEF SAFETY RELIEF SAFETY RELIEF
CONVENTIONAL CONVENTIONAL CONVENTIONAL CONVENTIONAL
GE
NE
RA
L
41-PSV-3729A 41-PSV-3729B 41-PSV-0121A 41-PSV-0121B
300# 300# 300# 300#
RF
17039-ND-P-DW-0203-11 17039-ND-P-DW-0203-11 17039-ND-P-DW-0203-14 17039-ND-P-DW-0203-14
FULL NOZZLE, FULL LIFT FULL NOZZLE, FULL LIFT FULL NOZZLE, FULL LIFT FULL NOZZLE, FULL LIFT
- - - -
2"-HM-41-3737-BC01-1N 2"-HM-41-3737A-BC01-1N 2"-HM-41-3671-BC01-1N 2"-HM-41-3671A-BC01-1N
Hot oil to Hot Oil Drain Tank
(ND-MBD-3320)
Hot oil to Hot Oil Drain Tank
(ND-MBD-3320) Bypass
Hot oil return to Hot Oil Drain Drum
(ND-MBD-3320)
HotHot oil return to Hot Oil Drain Drum
(ND-MBD-3320) Bypass
barg MMSCMD kg/hr
kg/hr BLPD
IMR
CKD DESCRIPTION
MV ISSUED FOR REVIEW
REFER BELOW OIL-100-ND-I-DS-0808
KIP-17039
- -
TITLE ITEM/TAG No. DATA SHEET No.
PRESSURE SAFETY VALVE
PROJECT DESCRIPTION PROJECT No. SHEET REV
CREATION OF SURFACE PRODUCTION FACILITIES (OCS) AT NADUA 07 OF 07 A0
MPC CONTRACTOR PURCHASE ORDER No. REQUISITION NO. SPECIFICATION No.
TBA
CLIENT NAME REV No. BY DATE DATE APP. DATE
OIL INDIA LIMITED / TEC LIMITED A0 IMR 28-Nov-18 28-Nov-18 MSR/ VSR 28-Nov-18
CLIENT DOCUMENT No.
-
ORIGINATOR ORIG. DATE
19-Sep-18
UNITS:- Pressure psig kg/cm2 g kPag Flow : Gas MMscfd Sm
3/hr
Temp O C O F Liquid: m3/hr USgpm
1 TAG No.
2 SERVICE
3 VESSEL No.
4 LINE No.
5 P &ID NUMBER
6 FULL NOZZLE/SEMI-NOZZLE
7 SAFETY / RELIEF / SAFETY RELIEF
8 CONV., BELLOWS, PILOT OP.
9 BONNET TYPE
10 SIZE INLET OUTLET 1" 1"
11 FL. RATING INLET 300# 300#
12 FL. FACE INLET OUTLET RF RF
13 BODY
14 BONNET
15 NOZZLE, SEAT and DISC
16 RESILIENT SEAT SEAL
17 GUIDE AND RINGS
18 SPRING
19 BELLOWS
20 CAP: SCREWED or BOLTED
21 LEVER: OPEN or PACKED
22 TEST GAG
23 CODE
24 BASIS
25 VESSEL SIZE DIA X T/T
26 FLUID STATE HOT OIL HOT OIL
27
28 OPERATING S.G MOL. WEIGHT
29 OPER. PRESS SET PRESS
30 OPER. TEMP REL. TEMP AMB AMB
31 CONSTANT
32 BACK PRESSURE VARIABLE
33 TOTAL
34 % ALLOWABLE OVER PRESSURE
35 OVER PRESSURE FACTOR
36 COMPRESSIBILITY FACTOR
37 LATENT HEAT OF VAPORIZATION (KJ/Kg)
38 RATIO OF SPECIFIC HEATS Cp / Cv
39 OPERATING VISCOSITY cP
40 VAPOUR GAS MASS FRACTION
41 BAROMETRIC PRESSURE
42 ENVIRONMENTAL FACTOR
43 VESSEL / WETTED
44 RATED CAPACITY
45 CALCULATED AREA inch2
46 SELECTED AREA inch2
47 ORIFICE DESIGNATION
48 MANUFACTURER
49 MODEL No.
50 NOTES:-
51 REFER NOTES SHEET
52
53
54
55
56
57
58
59
* BY VENDOR
* *
* *
* *
* *
* *
12 12
API RP 520
FL
UID
DA
TA
LIQUID LIQUID
REQUIRED CAPACITY (VAPOUR/LIQUID)
OP
TIO
NS
SCREWED SCREWED
N/A N/A
REQUIRED
THERMAL EXPANSION THERMAL EXPANSION
TBA TBA
REQUIRED
API RP 520
MA
TE
RIA
L
CS, ASTM A105 CS, ASTM A105
CARBON STEEL CARBON STEEL
CS with Nickle Plate CS with Nickle Plate
N/A N/A
SS 316 SS 316
SS 316 SS 316
RF
CLOSED BONNET CLOSED BONNET
SS 316 SS 316
CO
NN
EC
TIO
N 2" 2"
OUTLET
SAFETY RELIEF SAFETY RELIEF
CONVENTIONAL CONVENTIONAL
GE
NE
RA
L
41-PSV-6624A 41-PSV-6624B
300# 300#
RF
17039-ND-P-DW-0206-04 17039-ND-P-DW-0206-04
FULL NOZZLE, FULL LIFT FULL NOZZLE, FULL LIFT
- -
2"-HM-41-6637-BC01-1N 2"-HM-41-6856-BC01-1N
Hot oil retrun to Hot Oil Drain
Tank (ND-MBD-3320)
Hot oil retrun to Hot Oil Drain Tank
(ND-MBD-3320) By Pass
barg MMSCMD kg/hr
kg/hr BLPD
IMR
CKD DESCRIPTION
MV ISSUED FOR REVIEW
REFER BELOW OIL-100-ND-I-DS-0808
KIP-17039
- -
Datasheet NumberRev
Code
OIL-100-ND-I-DS-0814 A0 Sheet No.: 02 of 06
SHEET No.
1 COVER SHEET
2 INDEX SHEET
3 REVISION SHEET
4 NOTES SHEET
5 DS - SDV
6 SDV- LIST
INDEX SHEET
TITLE
CREATION OF SURFACE PRODUCTION
FACILITIES (OCS) AT NADUA
Revision Index
DATA SHEET FOR ACTUATED ON OFF VALVES
Datasheet NumberRev
Code
OIL-100-ND-I-DS-0814 A0 Sheet No: 03 of 06
REV No. LIST OF PAGES OF UPDATED / MODIFIED SECTIONS, IF ANY
A0 FIRST ISSUE
REVISION RECORD SHEET
PURPOSE
ISSUED FOR REVIEW
CREATION OF SURFACE PRODUCTION
FACILITIES (OCS) AT NADUA
Revision Index
DATA SHEET FOR ACTUATED ON OFF VALVES
Datasheet Number Rev Code
OIL-100-ND-I-DS-0814 A0 Sheet No: 04 of 06
4. Orientation of the actuator will be along the pipe axis.
5. Valve body thickness shall be as per ASME B16.34 plus C.A.
6. All instrument painting shall be as per Painting Specification
7. All fastners including stud-bolts and nuts material shall be ASTM A193 Gr. B7/B7M & Heavy hex nuts shall be ASTM A194 Gr. 2H/2HM
with Zinc coated ( hot dipped ) according to ASME B16.5.
8. Air Filter Regulators shall be provided with manual drainage facility, an integral pressure gauge calibrated in barg. Body material shall be
SS316 and filter element is 5 micron size.
9. Flange finish shall be in accordance with ASNI B16.5, for Raised Face (RF) flanges and shall be smooth finish to 125-250 AARH
10. All actuator valves accessories like solenoid valve, filter regulator, etc. shall be mounted on the valve actuator and tubed by vendor
using bright annealed SS316 (ASTM A269) tubing, tube size shall be 10mm O.D. X 1mm W.T.minimum. All tube fittings shall be imperial
and 316 SS double compression type, SWAGELOK.
11. All components such as air filter regulators, limit switches, solenoid valve shall be factory mounted, tubed / wired in completely assemble
condition and bolted to a SS 316 mounting plate which is fixed to a support with SS316 bolts.
13. Spare cable entry shall be plugged with SS316 Ex'd' certified plug.
14. Actuator to be sized for maximum pressure drop equal to the valve design pressure with minimum instrument air supply pressure (5.5 barg).
15. Actuator shall be sized for 1.5 times the required seating torque of the valve when the valve is closed against maximum differential pressure.
16. Actuator shall be supplied with a pressure relief valve to protect the actuator from overpressure if the actuator design pressure is lower
than the maximum instrument air pressure indicated in the datasheet.
17. The valve stem and linkage mechanism shall be consistance with actuator torque characteristic. The maximum torque developed by actuator shall not exceed that
which can be safely sustained by the valve stem. Valve stem or shaft and its trim shall be of blowout proof design and be capable of withstanding the maximum
actuator torque/thrust.
18. The mounting of the actuator shall be suitable for supporting the actuator without external attachments and shall be capable of
resisting actuator's maximum torque force.
19. Limit switches shall be supplied with hermetically sealed NAMUR Inductive proximity switches.
All valves shall be provided with an integral open/close mechanical position indicator(yellow/black) which shall be clearly visible from all angles.
20. Solenoid valve shall have SS 316 body, trim with viton or equal resilient seat (to be anti-explosion decompression type) and surge
suppression diode integrally mounted in enclosure. Open port of solenoid valve shall fitted with a bug screen.
All valves shall be provided with an integral open/close mechanical position indicator(yellow/black) which shall be clearly visible from all angles.
20. Solenoid valve shall have SS 316 body, trim with viton or equal resilient seat (to be anti-explosion decompression type) and surge
suppression diode integrally mounted in enclosure. Open port of solenoid valve shall fitted with a bug screen.
21. Flying leads termination cable are not acceptable for solenoid valve and limit switches.
23. Hydrotest pressure and seat test pressure shall be as per ASME code requirement.
24. Vendor shall verify all sizing calculations to confirm datasheets, selection and shall conform with his quotation. Vendor is responsible to confirm that the
specified pneumatic ON/OFF valve will operate satisfactorily for the given service conditions.
25. Stroke time should not exceed 3 times body size (inches) in seconds or be less than body size (inches) in seconds. Maximum stroke time of any valve is 30 sec.
26. All electrical components shall be suitable for hazardous area with ingress protection IP 65 (min).
27. All Actuated ON/OFF Valve assemblies (valve, actuator, solenoid valve, air pressure regulator and valve position switches) shall be SIL- 2 certified.
28. The Valves above 25Kgs shall be provided with eye bolts as per the requirements for site handling.
29. Valve actuators assemblies shall be equipped with adjustable controls to regulate their stroking speed.
30. All ball valves over 2” shall incorporate anti-static feature ensuring electrical continuity between ball, stem and body.
31. Actuator colour coding shall be fail open valve-Green and fail close valve-Red.
32. All Casting & Welding shall be 100% Radio graphed.
the required stroke-speed, fail safe action.
35. Other auxiliary devices such as air lock relay, pilot relay, booster relay volume tank etc. shall be provided as parts of the actuating system in order to achieve
34. Stem for ball valves shall be anti-blowout type and for floating ball valves, seat spring shall be provided.
CREATION OF SURFACE PRODUCTION FACILITIES (OCS)
AT NADUA
Revision Index
DATA SHEET FOR ACTUATED ON OFF VALVES
Notes:
1. Documentation required :- Calibration Certificate , Ingress Protection Certificate, Material Certificates to 3.1 as per EN 10204, Hydro test ,
operating & Maintenance Instructions & Spare Parts List.
2. All instruments to be supplied with a SS 316 Name plate with Tag no. permanently inscribed. Tags shall be Permanently secured.
TITLE ITEM/TAG No. DATA SHEET No.
DATA SHEET FOR ACTUATED ON OFF VALVES
PROJECT DESCRIPTION VME PROJECT No SPECIFICATION No.
CREATION OF SURFACE PRODUCTION FACILITIES (OCS) AT NADUA
MPC CONTRACTOR SUPPLIER DOC.NO REQUISITION No. SHEET REV
TBA A0
CLIENT NAME REV No. BY DATE CKD DATE APP. DATE
OIL INDIA LIMITED / TEC LIMITED A0 IMR 28-Nov-18 MV 28-Nov-18 MSR/ VSR 28-Nov-18
CLIENT DOC .No
ORIGINATOR ORIG. DATE
14-Sep-18
UNITS:- Pressure barg kg/cm2 g kPa g psi g Flow : Gas MMscfd SCMH Sm3/hr kg/hr
Temp 0 C 0 F Liquid: m3/hr kg./hr bpd USgpm
1 55
2 FLUID REFER ANNEXURE-1 56 TYPE
3 LINE No. REFER ANNEXURE-1 57 MFR *
4 P&ID No. REFER ANNEXURE-1 58 SIZE REFER ANNEXURE-1
5 LINE SIZE AND SCHEDULE REFER ANNEXURE-1 59 SPRING ACTION OPEN / CLOSE REFER ANNEXURE-1
6 CORROSION ALLOWANCE REFER ANNEXURE-1 60 MAX ALLOWABLE PRESSURE *
7 61 MIN REQUIRED PRESSURE *
8 FLOW RATE 62 AIR FLUID PRESSURE -
9 OP. PRESSURE / OP. TEMP. ( barg/ OC) 63 AVAILABLE AIR PR. MIN / NOR / MAX. 6 / 8 / 10 barg
10 SPEC. GRAV. 64 BREAK TORQUE RUN TORQUE
11 LIQ. DENSITY AT OP. PR & TEMP (kg/m3) 65 TIME OPEN CLOSE
12 VISCOSITY cP 66 ACTUATOR COLOUR YES
13 DESIGN TEMPERATURE (OC) REFER ANNEXURE-1 67 ACT ORIENTATION PARALLEL TO FLOW
14 DESIGN PRESSURE (barg) REFER ANNEXURE-1 68 HANDWHEEL TYPE -
15 Dp SHUT-OFF PRESSURE (bar) REFER ANNEXURE-1 69 AIR FAILURE VALVE SET AT -
16 70 AIR CONSUMPTION *
17 DESIGN CODE API 6D 71 POSITION INDICATION (LOCAL) YES
18 FIRE-SAFE API-6FA /API 607/ BS 6755 72 POSITION INDICATION (REMOTE) YES - SEE LINES 75~83
19 SEAT LEAKAGE CLASS ANSI FCI 70.2, Class VI or Equal 73 ACCUMULATOR NOTE-35
20 74 PNEUMATIC CONNECTION 1/4" NPTF
21 TYPE BALL VALVE 75
22 SIZE / RATING (in) NB REFER ANNEXURE-1 76 TAG No. REFER ANNEXURE-1
23 FLANGE FACE FINISH REFER ANNEXURE-1 77 TYPE
24 CONFIGURATION REFER ANNEXURE-1 78 MFR & MODEL *
25 MATERIAL BODY 79 CONTACTS / RATING 24VDC @ 2 A
26 BALL 80 ACTUATION POINTS OPEN / CLOSE
27 STEM 81 ENCLOSURE
28 SEAT RING 82 ENCLOSURE MATERIAL SS316
29 SEAT INSERT 83 CABLE ENTRY ISO M20 X 1.5 mm (2 nos)
30 FIRE SEAL 84
31 PACKING 85 TAG No.
32 BOLT / NUT 86 TYPE
33 OTHER SPECIFICATIONS - 87 AIR SUPPLY SIGNAL
34 RUN TORQUE BREAK TORQUE 88 MFR & MODEL
35 BODY TEST PRESSURE 1.5 TIMES OF THE DESIGN PRESSURE 89 MANUAL RESET
36 SEAT TEST PRESSURE 1.1 TIMES OF THE DESIGN PRESSURE 90 MATERIAL BODY/HOUSING
37 LIMIT STOPS NO 91 PILOT ACTION
38 MFR * 92 PILOT CONNECTION
39 MODEL * 93
40 94 MFR & MODEL *
41 a) PNEUMATIC TUBE SIZE ¼” O.D. X 0.035” W.T 95 MATERIAL ENCLOSURE 316 SS IP 65
42 b) ALL CABLE ENTRIES ISO M20 X 1.5 mm 96 INTEGRAL PRESSURE GAUGE YES
43 c) ALL TUBES AND FITTINGS MATERIAL 316 SS, SEE LINES 50 97 DESIGN PRESSURE SET PRESSURE 10 barg *
44 d) AREA CLASSIFICATION ZONE 2, GROUP IIA& IIB,TEMP.CL T3 98 PORT SIZE 1/4" NPTF
45 SPEED CONTROLLER LOCAL INDICATOR. 99
46 100 TAG No. REFER ANNEXURE-1
47 101 QTY REFER ANNEXURE-1
48 102 TYPE 3 / 2 -WAY, UNIVERSAL
49 LIMIT SWITCHES SHALL BE PROVIDED WITH INTEGRAL TERMINAL BLOCK 103 POWER SUPPLY 24 VDC, < 6 WATT, H COIL INSULATION
50 ALL TUBE FITTINGS SHALL BE IMPERIAL AND DOUBLE 104 ENCLOSURE TYPE EEx'd' / IP 65
51 FERRULE COMPRESSION TYPE. 105 MFR & MODEL *
52 VENT/EXHAUST CONNECTIONS TO BE PROVIDED WITH BUG SCREEN 106 MANUAL RESET YES
53 107 MATERIAL BODY/HOUSING 316 SS
54 108 PORT SIZE CABLE ENTRY 1/4'' NPTF ISO 1/2" NPT(F) X 1.5 mm
NOTES:- * BY VENDOR
Refer Notes sheet
REFER ANNEXURE-1 OIL-100-ND-I-DS-0814
KIP-17039 -
- - 05 of 06
NA
DESCRIPTION
-
IMR
GENERAL
QUARTER TURN, SPRING RETURN DOUBLE ACTING
PISTON
PROCESS CONDITIONS
NA
REFER ANNEXURE-1 VALVE CODE Ex'ia' / IP 65
NA REFER ANNEXURE-3
NA REFER ANNEXURE-3
NA
APPLICABLE CODES AND SPECIFICATIONS
VALVE (NOTE-30,31,32)
SWITCHES
INDUCTIVE PROXIMITY SWITCH WITH NAMUR
REFER ANNEXURE-1 VALVE CODE
REFER ANNEXURE-1 VALVE CODE
ZONE 2, GROUP IIA& IIB,TEMP.CL T3
ISSUED FOR REVIEW
ACTUATOR (PNEUMATIC)
ANNEXURE-2
FILTER REGULATOR (NOTE-8)
ADDITIONAL INFORMATION
YES YES SOLENOID VALVE (NOTE-20,21)
REFER ANNEXURE-1 VALVE CODE
REFER ANNEXURE-1 VALVE CODE
REFER ANNEXURE-1 VALVE CODE PNEUMATIC PILOT VALVE
REFER ANNEXURE-1 VALVE CODE
REFER ANNEXURE-1
A0
S.NO TAG NO P&ID No. LINE N0. FLUID VALVE SIZE (in) CONFIGURATION
LINE SIZE (in) / SCH
or WALL THK. / C.A
(mm)
RATING
FLANGE
FINISH
(AARH)
VALVE CODE
DESIGN
PRESSURE
(kg/cm2g)
DESIGN
TEMP. (OC)
ΔP SHUTOFF
PRESSURE (bar)FAIL POSITION LIMIT SWITCH TAG NO.
SOLENOID
VALVE TAG NO.
SOLENOID
VALVE QTYACTUATOR SIZE
NACE
REQUIREMENTBOLT / NUT MATERIAL VALVE MODEL NO
LIMIT SWITCH /
SOLENOID VALVE
MODEL NO
ACTUATOR
MODEL
VALVE
SCHEMATICS
NO.
REV
1 41-SDV-3750 17039-ND-P-DW-0202-20 2"-HM-41-3762-BC01-HC-IN HOT OIL 2" GATE VALVE 2"/ XS/ 3 300# RF 125 - 250 GTBC01R FOW+0.07 108 FOW+0.07 FAIL CLOSE 41-ZSL/ZSH-3750 41-SDY-3750 1 * Not RequiredASTM A 193 Gr. B7 / ASTM A
194 Gr. 2H (ASME B16.5)* * * * A0
2 41-SDV-3727 17039-ND-P-DW-0203-10 4"-HM-41-3725-BC01-1N HOT OIL 3" GATE VALVE 4"/ STD/ 3 300# RF 125 - 250 GTBC01R 12/FV 250 12/FV FAIL CLOSE 41-ZSL/ZSH-3727 41-SXV-3727 1 * Not RequiredASTM A 193 Gr. B7 / ASTM A
194 Gr. 2H (ASME B16.5)* * * * A0
3 41-SDV-3730 17039-ND-P-DW-0203-11 3"-HM-41-3727-BC01-1N HOT OIL 3" GATE VALVE 3"/ STD/ 3 300# RF 125 - 250 GTBC01R FOW+0.07 90 FOW+0.07 FAIL CLOSE 41-ZSL/ZSH-3730 41-SXV-3730 1 * Not RequiredASTM A 193 Gr. B7 / ASTM A
194 Gr. 2H (ASME B16.5)* * * * A0
4 41-SDV-3668 17039-ND-P-DW-0203-14 3"-HM-41-8611-BC01-1N HOT OIL 3" GATE VALVE 3"/ STD/ 3 300# RF 125 - 250 GTBC01R FOW+0.07 90 FOW+0.07 FAIL CLOSE 41-ZSL/ZSH-3668 41-SXV-3668 1 * Not RequiredASTM A 193 Gr. B7 / ASTM A
194 Gr. 2H (ASME B16.5)* * * * A0
5 66-SDV-6643A 17039-ND-P-DW-0206-02 4"-TW-66-6604-AC01CLARIFIED/
TREATED WATER4" GATE VALVE 4"/ STD/ 3 150# RF 125 - 250 GTAC01R FOW+0.07 80 FOW+0.07 FAIL CLOSE 66-ZSL/ZSH-6643A 66-SXV-6643A 1 * Not Required
ASTM A 193 Gr. B7 / ASTM A
194 Gr. 2H (ASME B16.5)* * * * A0
6 66-SDV-6643B 17039-ND-P-DW-0206-02 4"-TW-66-6604-AC01CLARIFIED/
TREATED WATER4" GATE VALVE 4"/ STD/ 3 150# RF 125 - 250 GTAC01R FOW+0.07 80 FOW+0.07 FAIL CLOSE 66-ZSL/ZSH-6643B 66-SXV-6643B 1 * Not Required
ASTM A 193 Gr. B7 / ASTM A
194 Gr. 2H (ASME B16.5)* * * * A0
7 41-SDV-6623 17039-ND-P-DW-0206-04 2"-HM-41-3674-BC01-1N HOT OIL 2" GATE VALVE 2"/ XS/ 3 300# RF 125 - 250 GTBC01R 15 80 15 FAIL CLOSE 41-ZSL/ZSH-6623 41-SXV-6623 1 * Not RequiredASTM A 193 Gr. B7 / ASTM A
194 Gr. 2H (ASME B16.5)* * * * A0
8 66-SDV-6640 17039-ND-P-DW-0206-06 4"-WE-66-6605-AC01OFF-SPEC
EFFLUENT WATER4" GATE VALVE 4"/ STD/ 3 150# RF 125 - 250 GTAC01R FOW+0.07 80 FOW+0.07 FAIL CLOSE 66-ZSL/ZSH-6640 66-SXV-6640 1 * Not Required
ASTM A 193 Gr. B7 / ASTM A
194 Gr. 2H (ASME B16.5)* * * * A0
9 53-SDV-5516 17039-ND-P-DW-0212-01 4"-WP-53-5504-AC01 WATER 4" FULL BORE/ FLOATING BALL 4"/ STD/ 3 150# RF 125 - 250 BFAC01R 7/FV 80 7/FV FAIL CLOSE 53-ZSL/ZSH-5516 53-SXV-5516 1 * Not RequiredASTM A 193 Gr. B7 / ASTM A
194 Gr. 2H (ASME B16.5)* * * * A0
10 53-SDV-5636 17039-ND-P-DW-0212-01 4"-WP-53-5508B-AC01 WATER 4" FULL BORE/ FLOATING BALL 4"/ STD/ 3 150# RF 125 - 250 BFAC01R 7/FV 80 7/FV FAIL CLOSE 53-ZSL/ZSH-5636 53-SXV-5636 1 * Not RequiredASTM A 193 Gr. B7 / ASTM A
194 Gr. 2H (ASME B16.5)* * * * A0
11 53-SDV-5607 17039-ND-P-DW-0212-04 3"-WD-53-5534-AS20FRESH POTABLE
WATER3" FULL BORE/ FLOATING BALL 3"/ STD/ 3 150# RF 125 - 250 BFAS20R FOW+0.07 80 FOW+0.07 FAIL CLOSE 53-ZSL/ZSH-5607 53-SXV-5607 1 * Not Required
ASTM A 193 Gr. B7 / ASTM A
194 Gr. 2H (ASME B16.5)* * * * A0
12 53-SDV-5630 17039-ND-P-DW-0212-04 4"-WD-53-5611B-AS20FRESH POTABLE
WATER4" FULL BORE/ FLOATING BALL 4"/ STD/ 3 150# RF 125 - 250 BFAS20R FOW+0.07 80 FOW+0.07 FAIL CLOSE 53-ZSL/ZSH-5630 53-SXV-5630 1 * Not Required
ASTM A 193 Gr. B7 / ASTM A
194 Gr. 2H (ASME B16.5)* * * * A0
13 71-SDV-7101 17039-ND-P-DW-0217-01 4"-WP-71-7101-AC01 WATER 4" GATE VALVE 4"/ STD/ 3 150# RF 125 - 250 GTAG01R FOW 80 FOW FAIL CLOSE 71-ZSL/ZSH-7101 71-SXV-7101 1 * Not RequiredASTM A 193 Gr. B7 / ASTM A
194 Gr. 2H (ASME B16.5)* * * * A0
14 56-XV-4010 17039-ND-P-DW-0207-01 4"-OW-56-5410-AC01 OILY WATER 4" GATE VALVE 4"/ STD/ 3 150# RF 125 - 250 GTAC01R 11/FV 100 11/FV FAIL CLOSE 56-ZSL/ZSH-4010 56-SXV-4010 1 * Not RequiredASTM A 193 Gr. B7 / ASTM A
194 Gr. 2H (ASME B16.5)* * * * A0
15 56-XV-4009 17039-ND-P-DW-0207-01 4"-OW-56-4019-AC01 OILY WATER 4" GATE VALVE 4"/ STD/ 3 150# RF 125 - 250 GTAC01R 11/FV 100 11/FV FAIL CLOSE 56-ZSL/ZSH-4009 56-SXV-4009 1 * Not RequiredASTM A 193 Gr. B7 / ASTM A
194 Gr. 2H (ASME B16.5)* * * * A0
16 71-XV-8008 17039-ND-P-DW-0217-01 2"-WP-53-4639A-AC01 WATER 2" GATE VALVE 2"/ STD/ 3 150# RF 125 - 250 GTAC01R FOW 80 FOW FAIL CLOSE 71-ZSL/ZSH-8008 71-SXV-8008 1 * Not RequiredASTM A 193 Gr. B7 / ASTM A
194 Gr. 2H (ASME B16.5)* * * * A0
17 71-XV-8009 17039-ND-P-DW-0217-01 2"-WP-53-4639B-AC01 WATER 2" GATE VALVE 2"/ STD/ 3 150# RF 125 - 250 GTAC01R FOW 80 FOW FAIL CLOSE 71-ZSL/ZSH-8009 71-SXV-8009 1 * Not RequiredASTM A 193 Gr. B7 / ASTM A
194 Gr. 2H (ASME B16.5)* * * * A0
REMARKS
* To be provided by vendor
OIL-100-ND-I-DS-0814 Sheet No.: 06 of 06
Document Title
DATA SHEET FOR ACTUATED ON OFF VALVES
CREATION OF SURFACE PRODUCTION FACILITIES (OCS) AT NADUA Document No. Rev.