Download - BPL Introduction

Transcript
Page 1: BPL Introduction

| January 17, 2006 | 1

Distribution Automation Project – BPL Network Design

© Copyright IBM Corporation 2006

BPL Introduction

CNP is installing a Broadband over Power Line (BPL) communications infrastructure to facilitate distribution system automation. The BPL equipment injects/receives a high frequency (3-30 Mhz) data signal into/from one phase of an existing distribution ckt. There is an injector unit at or near the substation that is connected to a high speed data communication path fiber/ethernet). Then there are repeaters installed along the circuit to amplify and re-broadcast the signal. The BPL equipment will be connected to utility devices to provide a communication path.

Page 2: BPL Introduction

| January 17, 2006 | 2

Distribution Automation Project – BPL Network Design

© Copyright IBM Corporation 2006

BPL Introduction

For 2006, 41 12kV ckts are scheduled to have BPL equipment installed.

IBM has been hired as the BPL system integrator, and they will be doing the BPL design. The design consists of determining how many devices will be required per ckt and approximately where the devices should be located.

Page 3: BPL Introduction

Distribution Automation Project

© Copyright IBM Corporation 2006

BPL Network DesignBellaire BI01 Circuit

March 12th, 2006

V1.9

Page 4: BPL Introduction

| January 17, 2006 | 4

Distribution Automation Project – BPL Network Design

© Copyright IBM Corporation 2006

Table of Contents

Overall circuit map

GIS map of individual installation point

Injection Point + Sensor (comfort stn) design

BPL + CCU design

RF design

Logical network design

Network address design

Page 5: BPL Introduction

| January 17, 2006 | 5

Distribution Automation Project – BPL Network Design

© Copyright IBM Corporation 2006

The BI01 circuit will have two BPL nodes at the pole locations shown below.

Node #1

TP-Bi01

Node #2

Node Type Notes

Node #1 BPL Injection + comfort stn

HE point

Node #2 BPL + CCU

Page 6: BPL Introduction

| January 17, 2006 | 6

Distribution Automation Project – BPL Network Design

© Copyright IBM Corporation 2006

Node #1 is the BPL injection point + sensor station for BI01, it is the first pole past the Terminal Pole of BI01.

Page 7: BPL Introduction

| January 17, 2006 | 7

Distribution Automation Project – BPL Network Design

© Copyright IBM Corporation 2006

Node #2 is a BPL + CCU installation point

Page 8: BPL Introduction

| January 17, 2006 | 8

Distribution Automation Project – BPL Network Design

© Copyright IBM Corporation 2006

The injector node (Node #1) will be connected with multimode fiber to the backhaul network at the Bellaire substation control-house.

CNP Backhaul Network

BPL/AMM ServersCheckpoint Firewall

IBM Server Rack

Cisco 6509 Switch

Cisco 2960 SwitchFujitsu FW4100

Centerpoint ECDC

Fujitsu FW4020-1

Cisco 3750 Switch

Bellaire Substation Controlhouse

Fiber Dist. Panel

BPL MV Coupler

BPL MV Gateway

LV 120V

12 KV MV Tap

Cat5e

Fiber –MM 50/125RG-58

Ground

AC 120V

MV 12KV

C-Phase

Comfort Station

Page 9: BPL Introduction

| January 17, 2006 | 9

Distribution Automation Project – BPL Network Design

© Copyright IBM Corporation 2006

Cat5e

Fiber –MM 50/125

RG-58

Ground

AC 120V

12 KV MV Tap

BPL Repeater Node With RF Meter Collector

BPL MV Coupler

BPL MV Gateway

CCU

RF Diplexer*

The second node (Node #2) will also a have an AMR Collector Unit (CCU).

C - Phase

Node #2

Page 10: BPL Introduction

| January 17, 2006 | 10

Distribution Automation Project – BPL Network Design

© Copyright IBM Corporation 2006

RF Band allocation for BI01 Frequency Mode: 1 for Node #1 and Node #2 Frequency range 3MHz – 13 MHz Frequency notching will be used to notch out the amateur radio bands

Node #1 Node #2

MV Coupler MV CouplerMode 1 Filter

“next” port

“Previous” port

12 KV line, C-Phase

Page 11: BPL Introduction

| January 17, 2006 | 11

Distribution Automation Project – BPL Network Design

© Copyright IBM Corporation 2006

BI01 network logical diagram

Page 12: BPL Introduction

| January 17, 2006 | 12

Distribution Automation Project – BPL Network Design

© Copyright IBM Corporation 2006

This table shows the BPL IP addressing for BI01.

Site Type Network Addr Address Range Subnet Mask Assigned To

Bellaire 10.144.0.0 10.144.0.1 - 10.144.31.254 255.255.240.0 -or- /19 Bellaire Substation

         

Bellaire Circuits   Address Range Mask Assigned to

Bi01 10.144.0.X /24 10.144.0.1 - 10.144.0.254 255.255.255.0 VLAN Bi01

AMM Collectors Meter collectors 10.144.0.10 - 10.144.0.29 255.255.255.0  

Sensors Sensors 10.144.0.30 - 10.144.0.59 255.255.255.0  

BPL Gateways BPL devices 10.144.0.60 - 10.144.0.99 255.255.255.0  

Reserved   10.144.0.100 - 10.144.0.254 255.255.255.0  

Page 13: BPL Introduction

| January 17, 2006 | 13

Distribution Automation Project – BPL Network Design

© Copyright IBM Corporation 2006

Page 14: BPL Introduction

| January 17, 2006 | 14

Distribution Automation Project – BPL Network Design

© Copyright IBM Corporation 2006

Page 15: BPL Introduction

| January 17, 2006 | 15

Distribution Automation Project – BPL Network Design

© Copyright IBM Corporation 2006

Page 16: BPL Introduction

| January 17, 2006 | 16

Distribution Automation Project – BPL Network Design

© Copyright IBM Corporation 2006