NJRA Architects, Inc. 5272 S. College Drive, Suite 104 | Murray, Utah 84123 | 801.364.9259 | www.njraarchitects.com
Page 1 of 1
Item
Number Description
1 As requested by the Owner main entrance door window system A101A & W1 to the dialysis
suite has been revised to match the storefront system at the main building hallway in
appearance and color. Field verify adjacent existing to match. This will be a 45-minute fire
rated glazed Hollow metal door window system as indicated in the attached revised
sheets. As an alternate- also provide price to fabricate this glazed door window system in
45-minute fire rated Aluminum storefront system. See attached revised sheets with revisions
shown clouded for more information.
2 See attached Plumbing ASI #8 from VBFA Engineers prepared in response to RFI #04 to
revise piping at three island sinks. See attached revised plumbing sheets PP100 & PP101 with
revisions shown clouded for more information.
Attachments:
ASI #8 Memo from VBFA Engineers,
Drawings: Revised sheets A113, A252, A601A, PP100 & PP101.
ARCHITECT’S SUPPLEMENTAL INSTRUCTIONS
Date Issued:
May 29, 2020
Project: Intermountain Healthcare
Tooele Valley Dialysis Clinic Expansion
2356 North 400 East, Suite #102
Tooele, Utah 84074
Architect’s Supplemental
Instructions:
ASI #8
To: Saunders Construction
1113 South 500 West
Bountiful, Utah 84010
The Work shall be revised in accordance with the following supplemental instructions, and shall be
carried out in accordance with the Contract Documents. Prior to proceeding with the work described,
the Contractor is to determine if the work is to affect the contract amount. If additional costs are to be
incurred, the Contractor shall submit an itemized cost breakdown showing time, material and other
items affected by the change. After acceptance of this work and associated costs, a change order
will be prepared for signatures to affect a change to the contract.
M E M O R A N D U M
DATE: May 29, 2020
TO: Sourabh Sinha, LEED AP
NJRA Architects, Inc.
FROM: Dallen Romriell, P.E.
PROJECT NO. 19605
PROJECT: Intermountain Healthcare Tooele Dialysis Clinic
RE: ASI-008 – Domestic Piping to Sinks -Ref RFI-004
ASI-008 adds clarification to the contract documents to coordinate domestic water to sinks where wall did not go to ceiling. The ASI relocates the hot water main to run underneath the slab in order to serve sinks that do not have walls going to ceiling.
SHEET - PP100 – BELOW GRADE PLUMBING PLAN 1. 1” DHW main dropped to go below grade to run to sinks in the following locations: Room
A116, Room A122, and Corridor A145. 2. 3/4” DCW branch dropped to go below grade to run to sinks in the following locations:
Room A116, Room A122, and Corridor A145.
SHEET - PP101 – LEVEL PLUMBING PLAN 1. Vent lines can be common vented per code to the sinks in the following locations: Room
A116, Room A122, and Corridor A145. 2. Thermostatic mixing valves for EW-1 need to be relocated from the ceiling to underneath
the cabinetry in the following locations: Room A122, and Corridor A145. 3. Keyed note 21 added.
RE
F.
FD
FD
FDPRIVATE/ISOLATION
A129
TDR
A126
WAITING
A101
PUBLICTOILET
A102 BAY #7
A113
BAY #2
A107
BAY #1
A106
(E)ELEVATOR
(E)ELEVATORMACHINE
ROOM
(E) HSKP
BAY #3
A108
STAFFBREAK/CONFERENCE
ROOM
A134 STORAGE
A132
MANAGEROFFICE
A130
LABALCOVE
A116
SHAREDOFFICE
A104
B
A
1 3
92 SFBAY #5
BAY #10
A118
BAY #6
A112
4
EXAM/HOME
TRAININGROOM
A136
HOMETRAINING
ROOM
A138
CLEANSUPPLY
A131
BAY #8
A114
BAY #4
A110
BAY #9
A117
BAY #11
A119
BAY #12
A120
BAY #13
A121
BAY #14
A122
PATIENTTOILET
A123
HSKP
A127
SOILEDWORKROOM
A128
FUTUREEXAM/HOME
TRAININGROOM
A141
STAFF TOILET
A139BIO MED
A137
ELEC
A135
MED ROOM
A124
MECH
A140
MECH
A133
NOURISHMENT
A105
MECH
A103
LABALCOVE
WHEELCHAIRALCOVE
A125
A401
1
NURSESTATION
EAST
A115
NURSESTATION
WEST
A109
BID ALTERNATE #1
CORRIDOR
A143
CORRIDOR
A142
CORRIDOR
A145
CORRIDOR
A144
CORRIDOR
A146
CORRIDOR
A145
TYP.
08.01
08.08 26.14
11.08
06.21
11.06
26.14
11.08
06.21
11.06
10.18
12.01
12.01
11.06
10.19
06.21
11.1522.04
22.05
12.01
11.0211.08 06.17 11.08
11.05
11.08
12.01
26.14
11.06
08.05
11.16
11.17
12.01
11.03
08.07
11.08
06.2122.05
06.21
11.0212.02TYP.
09.04
09.04
09.04 09.04
06.21
12.02TYP.
26.14
10.0610.06
22.02
22.01
22.04
22.05
06.2109.0809.08TYP.
12.02TYP.
11.02
06.21
22.05
11.02
09.04
09.04
26.06
11.02
09.04TYP.
12.02TYP.
11.02
11.0811.08TYP. TYP.
22.02
26.06
11.14
10.18
11.12
11.13
06.21
26.17
12.0112.01TYP.
10.06
10.06
22.01
26.14
22.02
26.16
08.09
08.03TYP.
11.06
11.18 11.18
01.14
26.14
12.03
09.27
TYP.
12.03
09.27TYP.
12.02
12.02
12.03
09.27TYP.
12.03
09.27TYP.
12.03
09.27TYP.
26.19
10.11
11.07 11.07
11.07
26.04
TYP.
08.03
08.04
06.17
06.17
06.17
06.17
06.17
06.17
TYP.
02.39
08.01
06.01
08.01
06.01
08.01
08.01
08.01
06.01
08.01
06.01
12.01
12.01
08.01
11.08
11.03
06.01
06.01
08.01
02.39
02.39
08.01
06.01
06.17
02.39
06.01
06.01
11.0306.01
12.01
06.01
11.0806.17
06.01
06.01
12.01
08.01
08.01
12.01 11.08
01.0801.16
11.03
12.01
06.01
06.01
11.03
11.08
06.17
11.08
06.0111.03
11.03
06.01
12.01
02.39
02.26
02.2402.24
TYP.
TYP.
TYP.
TYP.
TYP.
TYP.
TYP.
TYP.
TYP.
TYP.
TYP.
TYP.
TYP.
TYP.
TYP.
TYP.
TYP.
TYP.
TYP.
12.01
TYP.
06.01
TYP.
TYP.
08.01
22.03
22.01
10.06
08.01
22.02
12.01
08.10
08.01
11.02
11.0211.02
11.02
5
SELVAM
RAJAVELU
267857-0301
NJRA Architects, Inc.
NJRA Project #
5272 S. College Drive, Suite104Murray, Utah 84123
801.364.9259www.njraarchitects.com
5/2
8/2
020 1
2:4
5:2
5 P
M
A113
Floor PlanLevel 1
Inte
rmo
un
tain
He
alth
ca
re
No
rth
po
inte
Me
dic
al P
ark
, B
ldg
B
2356 N
ort
h 4
00 E
ast
, Su
ite
#102
Too
ele
, U
tah
84074
19230.00
Construction Documents Feb 4, 2020
Too
ele
Va
lley D
ialy
sis
Clin
ic E
xp
an
sio
n
KEYED NOTES
01.08 CLEAN GOWN STORAGE.
01.14 DASHED LINE INDICATES AREA OF FUTURE TRAINING ROOM A141 TO BE BIDUNDER BID ALTERNATE #1. THE ROOM SHALL HAVE WALLS AND DOOR IN BASEBID ALONG WITH PLUMBING PIPING, HVAC ITEMS NOTED IN CONSTRUCTIONDOCUMENTS. NEW FINISHES, CEILING, MILLWORK, LIGHTING, PLUMBING
FIXTURE ETC TO BE BID UNDER ALTERNATE #1.
01.16 SOILED GOWN STORAGE.
02.24 UPGRADE EXISTING WALL TO TYPE-Q BY REPLACING GYPSUM BOARD TOTYPE-X GYPSUM AND EXTENDING WALL TO DECK ABOVE FOR A ONE-HR FIRERATING.
02.26 EXISTING FIRE RATED DOOR AND HARDWARE TO REMAIN. PROTECT DURINGCONSTRUCTION.
02.39 EXISTING DOOR AND HARDWARE TO REMAIN. PROTECT DURINGCONSTRUCTION.
06.01 NEW CASEWORK. SEE INTERIOR ELEVATIONS AND FINISH PLANS.
06.17 PLUMBING CHASE WALL. SEE INTERIOR ELEVATIONS AND DETAILS ON SHEETA505C. ALSO SEE ELECTRICAL AND PLUMBING DRAWINGS.
06.21 SOLID SURFACE INTEGRAL SINK. BASIS OF DESIGN: SAMSUNG, STARON A1181SINK, COLOR "BRIGHT WHITE" BW010. ALSO SEE PLUMBING DRAWINGS.
08.01 NEW DOOR. SEE DOOR SCHEDULE FOR MORE INFORMATION. WOOD DOORAT THE BUILDING HALLWAY SHALL MATCH COLOR AND FINISH OF THEADJACENT EXISTING WOOD DOORS IN THE HALLWAY. WOOD DOORS INSIDETHE REMODEL SUITE SHALL BE CLEAR MAPLE FINISH.
08.03 CARD ACCESS, TYPICAL. SEE ELECTRICAL DRAWINGS.
08.04 CARD ACCESS AND AUTOMATED DOOR OPENER. SEE ELECTRICALDRAWINGS.
08.05 PUSH PAD FOR AUTO DOOR ACTIVATION. SEE ELECTRICAL DRAWINGS.
08.07 OVERHEAD CONCEALED FULL BREAKOUT TRACKLESS UL 1784 SMOKE RATEDNARROW STILE SINGLE SLIDE ALUMINUM AND GLASS DOOR. BASIS OF DESIGN:ASSA ABLOY VERSAMAX ICU DOOR SYSTEM. GLAZING TO BE 1/4" CLEARTEMPERED. SEE DETAIL 8/A601A & 10/A601A.
08.08 EXISTING EXTERIOR WINDOWS TO REMAIN. PROTECT DURING CONSTRUCTION.
08.09 ALUMINUM AND GLASS MANUAL SLIDING WINDOW. BASIS OF DESIGN C. R.LAURENCE DW 4200 A TWO PANEL MANUAL DELUXE LOCKABLE SLIDINGWINDOW. FINISH: SATIN ANODIZED. SEE SHEET A601A.
08.10 INTERIOR WINDOW . SEE SCHEDULE. HM WINDOW FRAME AND GLAZING TOBE 1-HR FIRE RATED.
09.04 PARTIAL HEIGHT WALL WITH SOLID SURFACE CAP. SEE WALL TYPE 'P' ON SHEETA501.
09.08 3/4" THICK FIRE TREATED PLYWOOD FROM TOP OF BASE TO 7'-0" ABOVE BASE-ALL WALLS, TYPICAL, PAINT PLYWOOD TO MATCH WALL COLOR
09.27 PROVIDE SOLID SURFACE WINDOW SILL AT ALL EXTERIOR WINDOWS TYPICAL.SEE FINISH SCHEDULE AND DETAIL 5/A602A.
10.06 GRAB BARS. SEE SPECIFICATIONS. PROVIDE 'TYPE 1' METAL STUD BACKING PERDETAIL 5/A502A. SEE SHEET G003 FOR MOUNTING HEIGHTS.
10.11 METAL LOCKERS, 15" W X 18" D X 2 TIER. TOTAL 10 LOCKERS. SEESPECIFICATIONS. SEE DETAIL 6/A506A FOR LOCKER BASE DETAIL.
10.18 COFFEE POT, OFCI. SEE ELECTRICAL DRAWINGS.
10.19 REFRIGERATOR, OFCI. SEE ELECTRICAL DRAWINGS.
11.02 NURSE CHARTING STATION. SEE DETAIL 1/A504A. ALSO SEE DETAIL 13/A502AFOR BACKING REQUIREMENTS. SEE ELECTRICAL DRAWINGS FOR POWER ANDDATA.
11.03 PATIENT CHAIR/ RECLINER, OFOI.
11.05 METAL SHELVING, OFOI.
11.06 WALL MOUNTED MONITOR OFCI. SEE ELECTRICAL DRAWINGS. PROVIDE 3'-0"W X 2'-0" H X 18 GA SHEET METAL BACKING.
11.07 DIALYSIS HOSE AND SUPPLY BOX. SEE PLUMBING DRAWINGS. VERIFYLOCATION AND HEIGHT WITH OWNER BEFORE INSTALLATION.
11.08 TABLO HEMODIALYSIS SYSTEM. PROVIDED AND INSTALLED BY OWNERSVENDOR.
11.12 VENDING MACHINE, OFOI. SEE ELECTRICAL DRAWINGS
11.13 ICE AND WATER DISPENSER ON STAND, OFCI. SEE PLUMBING DRAWINGS.
11.14 FLUSH MOUNTED IN- FLOOR SCALE, OFCI. CONCRETE FLOOR TO HAVE A 3"RECESS FOR IN-FLOOR SCALE. RECESS TO BE 3'-0" W X 3'-4" D. PROVIDE 10"MINIMUM CLEARANCE FROM BACK WALL AND 6" MINIM CLEARANCE FROMSIDE WALL AS SHOWN. ALSO PROVIDE 3" RECESS FOR CONDUIT CENTERED ON
THE RECESSED SLAB/IN-FLOOR SCALE FROM THE FLOOR SCALE TO WALLBEHIND. COORDINATE WITH IN-FLOOR SCALE MANUFACTURER. SEE DETAIL2/A504A. POUR NEW THICKENED SLAB AFTER REMOVAL OF CONCRETE.
11.15 HIGH DENSITY WIRE SHELVING, OFOI
11.16 FLOOR MOUNTED BLANKET WARMER, OFCI. SEE ELECTRICAL DRAWINGS FORPOWER REQUIREMENTS.
11.17 LINEN CART, OFOI.
11.18 EXAM TABLE, OFOI. SEE ELECTRICAL DRAWINGS FOR POWER REQUIREMENTS.
12.01 FURNITURE, TO BE PROVIDED AND INSTALLED BY OWNERS VENDOR (MIDWESTCOMMERCIAL INTERIORS - MWCI)
12.02 PRIVACY CURTAIN AND TRACK. SEE FINISH SCHEDULE AND PROJECT MANUAL. SEE DETAIL 13/A503A
12.03 PROVIDE AND INSTALL 1" ALUMINUM BLINDS AT ALL EXTERIOR WINDOWS,TYPICAL THROUGHOUT THE PROJECT. FIELD VERIFY WINDOW SIZE BEFOREINSTALLATION.
22.01 FLOOR MOUNTED WATER CLOSET. SEE PLUMBING DRAWINGS.
22.02 WALL MOUNTED HAND WASH SINK. SEE PLUMBING DRAWINGS.
22.03 MOP SINK. SEE PLUMBING DRAWINGS.
22.04 COUNTER MOUNTED STAINLESS STEEL DEEP SINK. SEE PLUMBING DRAWINGS.
22.05 COUNTER MOUNTED EYE WASH. SEE PLUMBING DRAWINGS.
26.04 WALL MOUNTED PLUG STRIP. SEE ELECTRICAL DRAWINGS.
26.06 DOOR RELEASE BUTTON. SEE ELECTRICAL DRAWINGS.
26.14 NURSE CALL WITH PILLOW SPEAKER. SEE ELECTRICAL DRAWINGS.
26.16 WALL PHONE. SEE ELECTRICAL DRAWINGS.
26.17 FLOOR MOUNTED MULTI FUNCTION PRINTER/COPIER. SEE ELECTRICALDRAWINGS FOR POWER AND DATA.
26.19 SEE ELECTRICAL DRAWINGS FOR FLOOR BOX RECESSED IN CONCRETE TOPROVIDE POWER AND DATA CONNECTION TO THE TABLE. COORDINATE WITHOWNERS VENDOR MIDWEST FURNITURE FOR LOCATION OF THE TABLE LEGS TORUN ELECTRICAL CONNECTIONS TO THE TABLE.
GENERAL NOTES
A. SEE SHEET G003 AND G005 FOR SYMBOLS, GENERAL NOTES AND LEGEND.
B. SEE SHEET A505A FOR CABINET LEGEND.
C. SEE SHEET A601A FOR DOOR SCHEDULE AND WINDOW SCHEDULE
E. SEE SHEET A602A FOR FINISH SCHEDULE AND GENERAL NOTES.
NORTH
SCALE: 1/4" = 1'-0"1Floor Plan Level 1
5 ASI #8 May 28, 2020
4' -
0"
2' - 6" 2' - 6" 2' - 6"
7' -
2"
T1 T1 T1
TYP.
06.04
06.14
26.04
09.01
CLR.
2' - 6" 2' - 4 1/2" 2' - 4 1/2" 2' - 4 1/2"
2' - 6" 2' - 4 1/2" 2' - 4 1/2" 2' - 4 1/2" 2' - 4 1/2"
3' -
0"
1' -
10
"2
' -
10
"
B4 B4 B4
W2 W2 W2 W2
06.21
10.02
10.01
06.13
06.20
11.11
TYP.
06.06
06.14
B1
Op
en
6"
2' -
10
"
E N N E
D
06.25
06.24
06.27
11.03
26.22
11.08
22.11
26.23
06.10
06.26
2' -
10
"1
' -
10
"3
' -
0"
1' - 6" 2' - 6" 2' - 6"
2' - 6"2' - 6"
W2 W2
B3 B4 B2
06.14
08.02
06.20
22.05
06.21
10.0110.02
09.01
06.06
06.05
2' -
10
"
08.07
08.02
11.10
2' -
10
"
1' - 8" 1' - 8"
B3 B3
09.39 09.38
08.02
06.20
06.0706.07
01.0801.16
3' -
7 1
/2"
1' - 6" 2' - 6" 2' - 6" 2' - 6" 2' - 6"
B3 B4 B4 B2
06.20
09.04
06.21
TYP.
06.08
11.11 2' -
10
"
09.39
3' -
0"
1' - 4"
2' -
6"
B6
09.04
06.20
4' - 0" 1' - 4" 4' - 0" 1' - 4"
2' -
6"
3' -
0"
B6 B6
09.0406.20
3' -
0"
2' -
6"
1' - 4"
B6
09.04
06.20
3' -
0"
1' - 4" 3' - 6" 1' - 4"
2' -
6"
B6 B6
3' - 6"
09.04
06.20
3' -
4"
2' - 9" 2' - 3" 2' - 3" 1' - 4"
2' -
10
"
B2 B4 B4 B3
TYP.
06.05
06.08
06.2122.05 09.04 06.20
3' -
4"
2' -
10
"
2' - 9" 2' - 3" 2' - 3"
B2 B4 B4
1' - 4"
B3
06.2109.04
TYP.
06.05
22.05 06.20
06.08
1' - 8"
10.02 10.01
22.02
10.12
12.02
Open
4' -
0"3 1/8" 3' - 0"
2' -
10
"
09.38
11.09
10.0609.16
26.0510.12
U.C.
REF.
2' -
10
"
MIN.
2' - 6" CLR. 2' - 3" 1' - 2"
B4 B5
2' - 6" 3' - 0"
W1 W2
B1
3"
1' -
10
"3
' - 0
"
FE
06.20
06.21
10.02
10.0110.20
06.14
11.11
06.11
6"
5' -
6"
9" W3
AC-1
W3
FC09.01
22.02
10.05
22.01
10.0610.06
09.23
09.24
NC
6"
5' -
6"
9"
W3
FC
W3
AC-1
10.06
22.01 09.01
10.06 26.14
09.23
09.24
10.01
09.01
08.01
09.01
10.02
09.01
9' -
0"
10' - 8"
08.115
CR
08.09
11.06
08.01
09.01
11.12 11.13
2' - 6" 2' - 6" 2' - 6" 2' - 6"
T1 T1 T1 T1
7' -
0"
06.14
09.38
3' -
6"
06.20
06.09
2' -
10
"
3' - 1"
09.04
3' -
6"
2' -
10
"
09.04
06.20
3' - 1"
06.09
SELVAM
RAJAVELU
267857-0301
NJRA Architects, Inc.
NJRA Project #
5272 S. College Drive, Suite104Murray, Utah 84123
801.364.9259www.njraarchitects.com
5/2
8/2
020 1
2:4
5:3
0 P
M
A252
InteriorElevations
Inte
rmo
un
tain
He
alth
ca
re
No
rth
po
inte
Me
dic
al P
ark
, B
ldg
B
2356 N
ort
h 4
00 E
ast
, Su
ite
#102
Too
ele
, U
tah
84074
19230.00
Construction Documents Feb 4, 2020
Too
ele
Va
lley D
ialy
sis
Clin
ic E
xp
an
sio
n
SCALE: 3/8" = 1'-0"1A124 Med Room - North
SCALE: 3/8" = 1'-0"2A124 Med Room - South
SCALE: 3/8" = 1'-0"4A129 Private/ Isolation - South
SCALE: 3/8" = 1'-0"5A129 Private/ Isolation - West
SCALE: 3/8" = 1'-0"6A129 Private/ Isolation - North
SCALE: 3/8" = 1'-0"7A116 Lab Alcove - East
SCALE: 3/8" = 1'-0"8A116 Lab Alcove - West
SCALE: 3/8" = 1'-0"9A115 Nurse Station - East
SCALE: 3/8" = 1'-0"10A109 Nurse Station - South
SCALE: 3/8" = 1'-0"11A109 Nurse Station - West
SCALE: 3/8" = 1'-0"12A115 Nurse Station - North
SCALE: 3/8" = 1'-0"13A143 Corridor - South
SCALE: 3/8" = 1'-0"14A143 Corridor - North
SCALE: 3/8" = 1'-0"15A142 Hand Wash Sink - North
SCALE: 3/8" = 1'-0"3A142 Floor Scale Alcove - West
SCALE: 3/8" = 1'-0"17A105 Nourishment - South
SCALE: 3/8" = 1'-0"18A102 Public Toilet - East
SCALE: 3/8" = 1'-0"19A102 Public Toilet - South
SCALE: 3/8" = 1'-0"20A102 Public Toilet - West
SCALE: 3/8" = 1'-0"21A102 Public Toilet - North
SCALE: 3/8" = 1'-0"22A101 Waiting - North
SCALE: 3/8" = 1'-0"23A101 Waiting - South
KEYED NOTES
GENERAL NOTES
A. SEE SHEET G003 AND G005 FOR SYMBOLS, GENERAL NOTES AND LEGEND.
B. SEE SHEET A505A FOR CABINET LEGEND.
C. SEE SHEET A601A FOR DOOR SCHEDULE AND WINDOW SCHEDULE
E. SEE SHEET A602A FOR FINISH SCHEDULE AND GENERAL NOTES.
01.08 CLEAN GOWN STORAGE.
01.16 SOILED GOWN STORAGE.
06.04 PLASTIC LAMINATE TALL CABINET FILLER PANEL AS REQUIRED. FILLER PANEL TOMATCH PROFILE AND FINISH OF ADJACENT CABINETS.
06.05 PLASTIC LAMINATE BASE CABINET FILLER PANEL AS REQUIRED. FILLER PANEL TOMATCH PROFILE AND FINISH OF ADJACENT CABINETS.
06.06 PLASTIC LAMINATE WALL CABINET FILLER PANEL AS REQUIRED. FILLER PANELTO MATCH PROFILE AND FINISH OF ADJACENT CABINETS.
06.07 CABINETS TO BE LOCKABLE.
06.08 ALL SINK CABINETS TO BE LOCKABLE, TYPICAL.
06.09 PROVIDE P-LAM FINISHED PANEL AT SIDE OF CABINET.
06.10 30" WIDE P-LAM LIFT UP ACCESS PANEL WITH STAINLESS STEEL CONTINUOUSCONCEALED PIANO HINGE AND MOUNTING BRACKET. CENTER ACCESSPANEL ON WALL BOX BELOW.
06.11 P-LAM END PANEL.
06.13 GLASS PARTITION BETWEEN DIRTY AND CLEAN SIDE. GLASS TO BE 1/2" THICK XDEPTH OF COUNTERTOP. GLASS TO SPAN FROM TOP OF COUNTERTOP TOBOTTOM OF UPPER/WALL CABINET. PROVIDE 3" RADIUSED EDGE ON THEEXPOSED EDGE. PROVIDE POLISHED EDGES AT ALL/TWO EXPOSED EDGES.
PROVIDE 1/2" X 1/2" X CONT, STAINLESS STEEL RECEIVING CHANNEL TOHOLD THE GLASS IN PLACE. CUT COUNTER BACKSPLASH TO ANCHOR GLASSTO WALL BEHIND.
06.14 P-LAM CLOSER PANEL TO CEILING ABOVE. SEE DETAIL 2/A505B
06.20 SOLID SURFACE COUNTER WITH FULL BULLNOSE EDGE AND INTEGRALBACKSPLASH. SEE DETAIL 5/A505B AND 8/A505B. PROVIDE INTEGRAL SIDESPLASH WHERE COUNTER ABUTS PERPENDICULAR WALL/CABINET.
06.21 SOLID SURFACE INTEGRAL SINK. BASIS OF DESIGN: SAMSUNG, STARON A1181SINK, COLOR "BRIGHT WHITE" BW010. ALSO SEE PLUMBING DRAWINGS.
06.24 TALL CABINET. SEE CASEWORK LEGEND.
06.25 P-LAM LOCKABLE ACCESS PANEL WITH STAINLESS STEEL CONTINUOUSCONCEALED PIANO HINGE AND MOUNTING BRACKET.
06.26 P-LAM LOCKABLE STORAGE CABINET WITH DOOR TO STORE PATIENTBELONGINGS. SEE DETAILS ON SHEET A505C.
06.27 BUILT IN CASEWORK FOR CHASE WALL WITH PLASTIC LAMINATE FASCIA PANELAND MELAMINE BACK. USE MARINE GRADE PLYWOOD THROUGHOUT. SEEDETAILS ON SHEET A505C.
08.01 NEW DOOR. SEE DOOR SCHEDULE FOR MORE INFORMATION. WOOD DOORAT THE BUILDING HALLWAY SHALL MATCH COLOR AND FINISH OF THEADJACENT EXISTING WOOD DOORS IN THE HALLWAY. WOOD DOORS INSIDETHE REMODEL SUITE SHALL BE CLEAR MAPLE FINISH.
08.02 CORNER ALUMINUM WINDOW. BASIS OF DESIGN KAWNEER VG TRIFAB 451.SEE WINDOW SCHEDULE. GLAZING TO BE 1/4" THICK, CLEAR, TEMPERED.
08.07 OVERHEAD CONCEALED FULL BREAKOUT TRACKLESS UL 1784 SMOKE RATEDNARROW STILE SINGLE SLIDE ALUMINUM AND GLASS DOOR. BASIS OF DESIGN:ASSA ABLOY VERSAMAX ICU DOOR SYSTEM. GLAZING TO BE 1/4" CLEARTEMPERED. SEE DETAIL 8/A601A & 10/A601A.
08.09 ALUMINUM AND GLASS MANUAL SLIDING WINDOW. BASIS OF DESIGN C. R.LAURENCE DW 4200 A TWO PANEL MANUAL DELUXE LOCKABLE SLIDINGWINDOW. FINISH: SATIN ANODIZED. SEE SHEET A601A.
08.11 NEW 45 MINUTE FIRE RATED GLAZED HOLLOW METAL DOOR WINDOW FRAMESYSTEM TO MATCH LOOK OF THE STOREFRONT SYSTEM OF OTHER ADJACENTSUITES AT THE BUILDING HALLWAY. SEE DOOR SCHEDULE ON SHEET A601A FORMORE INFORMATION.
09.01 WALL BASE. SEE FINISH SCHEDULE.
09.04 PARTIAL HEIGHT WALL WITH SOLID SURFACE CAP. SEE WALL TYPE 'P' ON SHEETA501.
09.16 CORNER GUARD, 2" X 2" X 4'-0". SEE FINISH SCHEDULE. SEE DETAIL 11/A601B.TOP OF CORNER GUARD TO ALIGN WITH TOP OF WALL PROTECTIONWAINSCOT. TYP.
09.23 WALL FIELD TILE. SEE FINISH SCHEDULE
09.24 WALL ACCENT TILE. SEE FINISH SCHEDULE
09.38 GYPSUM BOARD SOFFIT. SEE DETAIL 9/A503A.
09.39 GYPSUM BOARD HEADER. SEE DETAIL 6/A503A.
10.01 SOAP DISPENSER. OFCI. SEE SHEET G004 FOR MOUNTING HEIGHT.
10.02 PAPER TOWEL DISPENSER. OFCI. SEE SHEET G003 FOR MOUNTING HEIGHT.
10.05 MIRROR. 24 INCHES WIDE X 36" HIGH. SEE SPECIFICATIONS. MOUNT MIRRORSUCH THAT THE REFLECTIVE SURFACE OF MIRROR IS NO MORE THAN 40 INCHESAFF. SEE SHEET G003 FOR MOUNTING HEIGHT.
10.06 GRAB BARS. SEE SPECIFICATIONS. PROVIDE 'TYPE 1' METAL STUD BACKING PERDETAIL 5/A502A. SEE SHEET G003 FOR MOUNTING HEIGHTS.
10.12 WALL PROTECTION WAINSCOT, 0.06 INCH THICK. SEE FINISH SCHEDULE. ALIGNTOP OF WAINSCOT WITH TOP OF CORNER GUARD WHERE OCCURS. SEEDETAIL 4/A602A.
10.20 MICROWAVE, OFCI. SEE ELECTRICAL DRAWINGS. FOR MICROWAVE IN WALLCABINET PROVIDE OUTLET IN THE CABINET ABOVE WITH A GROMMETOPENING AT THE BASE OF THIS CABINET.
11.03 PATIENT CHAIR/ RECLINER, OFOI.
11.06 WALL MOUNTED MONITOR OFCI. SEE ELECTRICAL DRAWINGS. PROVIDE 3'-0"W X 2'-0" H X 18 GA SHEET METAL BACKING.
11.08 TABLO HEMODIALYSIS SYSTEM. PROVIDED AND INSTALLED BY OWNERSVENDOR.
11.09 WALL MOUNTED READOUT PANEL FOR SCALE, O.F.C.I. SEE ELECTRICALDRAWINGS FOR POWER AND DATA. INSTALL PER MANUFACTURESRECOMMENDATION. CONTACT OWNER FOR MORE INFORMATION.
11.10 CEILING MOUNTED TV. OFCI. PROVIDE 3" STAINLESS STEEL GROMMET ATOPENING IN CEILING TILE AT ALL CEILING MOUNTED TV LOCATIONS, TYPICAL.
11.11 UNDERCOUNTER REFRIGERATOR. OFOI. SEE ELECTRICAL DRAWINGS FORPOWER AND DATA.
11.12 VENDING MACHINE, OFOI. SEE ELECTRICAL DRAWINGS
11.13 ICE AND WATER DISPENSER ON STAND, OFCI. SEE PLUMBING DRAWINGS.
12.02 PRIVACY CURTAIN AND TRACK. SEE FINISH SCHEDULE AND PROJECT MANUAL. SEE DETAIL 13/A503A
22.01 FLOOR MOUNTED WATER CLOSET. SEE PLUMBING DRAWINGS.
22.02 WALL MOUNTED HAND WASH SINK. SEE PLUMBING DRAWINGS.
22.05 COUNTER MOUNTED EYE WASH. SEE PLUMBING DRAWINGS.
22.11 DIALYSIS HOSE AND SUPPLY BOX. SEE PLUMBING DRAWINGS. VERIFYLOCATION AND HEIGHT WITH OWNER BEFORE INSTALLATION.
26.04 WALL MOUNTED PLUG STRIP. SEE ELECTRICAL DRAWINGS.
26.05 IN WALL CONDUIT FOR LOAD CELL CABLE. SEE MANUFACTURER ANDELECTRICAL DRAWINGS.
26.14 NURSE CALL WITH PILLOW SPEAKER. SEE ELECTRICAL DRAWINGS.
26.22 LIGHT SWITCH. SEE ELECTRICAL DRAWINGS.
26.23 DEDICATED OUTLET FOR DIALYSIS MACHINE. SEE ELECTRICAL DRAWINGS.
SCALE: 3/8" = 1'-0"16A105 Nourishment - North
SCALE: 3/8" = 1'-0"24A145 Corridor - North
SCALE: 3/8" = 1'-0"25Bay #11
SCALE: 3/8" = 1'-0"26Bay #12
5 ASI #8 May 28, 2020
DOOR OPENING
1/4"
7'-0"
1/4"
1. PRE MANUFACTURED ALUMINUM AND GLASS SLIDINGDOOR. SEE PROJECT MANUAL FOR DETAILS.
2. PROVIDE CLEAR SILICON SEALANT ALL AROUND DOORFRAME- BOTH SIDES OF DOOR.
3. (2) TYP. TRACK PINS AT DECK ABOVE AND FLOOR SLABBELOW.
4. DOUBLE METAL STUDS, SEAM WELD AT 12" O.C. TYP., USE16 GA STUDS.
5. 5/8" THICK, TYPE 'X' GYP. BD. ALL AROUND.
6. 1/4" SHIM SPACE AT EACH JAMB.
KEYED NOTES
12345
6
1. GLAZING SHALL BE CLEAR, TEMPERED, AND 1/4" THICK.
2. DOOR FRAME, SEE DOOR SCHEDULE.
3. WHERE DOOR OCCURS AT MASONRY WALL (8" HIGH, C.M.U. BLOCKS),
AND WITH A TYPICAL DOOR HEIGHT OF 7' - 0", USE 4" FRAME AS FRAME
HEAD INSTEAD OF THE STANDARD 2" FRAME.
KEYED NOTES
1
2"
SEE DOORSCHEDULE 2"
2"
SEE D
OO
R S
CH
ED
ULE
2
2"
SEE DOORSCHEDULE
2"1' - 2"
2"
SEE D
OO
R S
CH
ED
ULE
2"
4"
4
2"
SEE DOORSCHEDULE 2" 3' - 0" 2"
SEE D
OO
R S
CH
ED
ULE
2"
3' -
4"
2"
5
2"
SEE DOORSCHEDULE 2"
2"
SEE D
OO
R S
CH
ED
ULE
2"
6
2"
SEE DOORSCHEDULE 2"
1' - 2"
2"
2"
SEE D
OO
R S
CH
ED
ULE
2"
2 2 2
2 2
1
1
1 1 1
1
1' -
4"
1' -
4"
NOTE: REFER TO "DOOR SCHEDULE" FOR FRAME TYPES REQUIRED FOR THIS PROJECT. SOME FRAME TYPE
ELEVATIONS INDICATED ABOVE MAY NOT BE APPLICABLE TO THIS PROJECT.
DASHED LINE DENOTES
FINISH FLOOR
3 3
3
2"
SEE DOORSCHEDULE
2"1' - 2"
2"
SEE D
OO
R S
CH
ED
ULE
2"
4"
2' -
8"
2"
2
1
3 3
7
2"
SEE DOORSCHEDULE 2"
1' - 2"
2"
2"
SEE D
OO
R S
CH
ED
ULE
2"
2
1 1
1
1' -
4"
4"2
' -
8"
2"
DASHED LINE DENOTES
FINISH FLOOR
1. VISION PANEL. GLAZING IN VISION PANEL SHALL BE 1/4" THICK, CLEAR,
TEMPERED, GLAZING. FOR WOOD DOOR, PROVIDE WOOD TRIM FRAME
FLUSH WITH THE FACE OF THE DOOR, AROUND THE VISION PANEL
OPENING. STAIN AND SPECIES OF WOOD TRIM SHALL MATCH WOOD
DOOR. FOR HOLLOW METAL DOOR, PROVIDE METAL TRIM AROUND
VISION PANEL. GLAZING SHALL BE FIRE RATED IF DOORS ARE REQUIRED
TO BE FIRE RATED.
2. FOR EXTERIOR DOORS OF THIS TYPE, GLAZING SHALL BE TINTED,
INSULATED, TEMPERED, LOW E, AND 1" THICK. FOR INTERIOR DOORS OF
THIS TYPE, GLAZING SHALL BE CLEAR, TEMPERED AND 1/4" THICK.
3. STAINLESS STEEL WELDED WIRE MESH (15 GAUGE) ATTACHED TO DOOR.
PROVIDE FRAME AROUND THE OPENING IN DOOR TO SECURE THE MESH
IN PLACE.
4. METAL LOUVER IN DOOR FOR VENTILATION.
KEYED NOTES
TYPE - A
SEE D
OO
R S
CH
ED
ULE
SEE DOORSCHEDULE
TYPE - B
SEE D
OO
R S
CH
ED
ULE
SEE DOORSCHEDULE
3' -
6"
2' -
9"
1
TYPE - C
SEE D
OO
R S
CH
ED
ULE
SEE DOORSCHEDULE
8"
6"
6' -
0"
6"
1
TYPE - D
SEE D
OO
R S
CH
ED
ULE
SEE DOOR SCHEDULE
1
NOTE: REFER TO "DOOR SCHEDULE" TABLE FOR DOOR TYPES REQUIRED FOR THIS PROJECT. SOME DOOR TYPE ELEVATIONS
INDICATED ABOVE, MAY NOT BE APPLICABLE TO THIS PROJECT.
2' -
6"
3' -
6"
DASHED LINE DENOTES
FINISH FLOOR
8"
6"
SEE DOORSCHEDULE
SEE D
OO
R S
CH
ED
ULE
TYPE - E
DASHED LINE DENOTES
FINISH FLOOR
5"
5"
5"
10
"
1
TYPE - F
2
7
A506A
8
A506A
410' - 8"
2"
8"
2"
6' -
6"
2"
1' -
2"
2"
2" 4' - 0" 2" 3' - 0" 2" 3' - 0" 2"
9' -
0"
6
2
2 2
2
2 2
2' -
10
"4
' - 4
"
4' - 0"
1
1
3' -
0"
4' -
2"
2' - 9 1/4"
9
A506A
9
A506A
3' -
0"
4' -
2"
1
1' - 5 7/8"
SEE D
OO
R S
CH
ED
ULE
SEE DOOR SCHEDULE
1
10
A601A
8
A601A
1. GLAZING SHALL BE CLEAR, TEMPERED, AND 1/4" THICK.
2. 45 MINUTE FIRE RATED GLAZING REQUIRED AT THIS
DOOR WINDOW SYSTEM.
3. MITER GLASS AT CORNER.
4. 45 MINUTE FIRE RATED HOLLOW METAL DOOR WINDOW
FRAME SYSTEM. COLOR TO MATCH ADJACENT EXISTING.
5. ALUMINUM AND GLASS MANUAL SLIDING WINDOW. CR
LAWRENCE DW 4200 A TWO PANEL MANUAL DELUXE
LOCKABLE SLIDING WINDOW. FINISH: SATIN ANODIZED.
6. 45 MINUTE FIRE FATED HOLLOW METAL GLAZED DOOR.
KEYED NOTES
2' - 11 3/8"
1' -
8"
PLAN
3
SC
HED
ULE
SEE
DO
OR
FRAME DEPTH
STUD SIZE
HEAD DETAIL - SECTION VIEW
1. CONTINUOUS SEALANT ON BOTH SIDES OF
THE FRAME.
2. DOOR FRAME SEEN BEYOND.
3. DOOR, SEE DOOR SCHEDULE FOR DOOR
TYPE.
4. GYPSUM BOARD, 5/8" THICK, TYPE 'X'. ATTACH
TO METAL STUD FRAMING. SEE WALL TYPES.
5. STEEL RUNNER (18 GAUGE) FASTENED WITH
SCREWS TO STRUT STUDS AT EACH END. SEE
DETAIL
6. HOLLOW METAL DOOR FRAME. FRAME
THICKNESS VARIES WITH WALL THICKNESS. SEE
FLOOR PLAN AND WALL SECTIONS. PAINT
FRAME.
7. SEE WALL TYPES FOR WALL WIDTH AND STUD
SIZE.
8. FRAME DEPTH SHALL BE WALL WIDTH PLUS 1".
9. LINE OF WALL, AS OCCURS.
10. PROVIDE DOUBLE METAL STUDS AT FRAME
JAMBS, WALL ENDS, ETC. PROVIDE STEEL
STRAPS (6" HIGH 16 GAUGE STRAPS AT 2'-0"
O.C.) SEE DETAIL
11. DOOR HINGE AS OCCURS. SEE DOOR AND
HARDWARE SCHEDULE. SEE FLOOR PLAN FOR
DOOR SWING.
1
5
2
3
1
4
SC
HED
ULE
SEE
DO
OR
FRAME DEPTH
STUD SIZE
1
5
2
3
1
4 4
8
8
WALL WIDTHWALL WIDTH
77
1/2" 1/2"
6
6
4
1/2"1/2"
KEYED NOTES
2"FR
AM
E D
EP
TH
STU
D S
IZE
614
4
10
9 11 31
2"
2"
FR
AM
E D
EP
TH
STU
D S
IZE
614
4
10
9 11 31
JAMB DETAIL - PLAN VIEW
2"
1/2
"1
/2"
7"
WA
LL W
IDTH
WA
LL W
IDTH
77 8 81/2
"1
/2"
/6 A502A
/7 A502A
SP
AC
E1
/4"
SH
IM
PA
CK
AG
E H
EIG
HT:
89
3/4
"
RO
UG
H O
PEN
ING
: 9
0"
1. SEE DETAIL 6/A502A FOR FRAMING AT DOOR
HEADER.
2. MANUAL SLIDING DOOR ALUMINUM AND GLASS
DOOR AS SCHEDULED.
3. PROVIDE CLEAR SILICON CAULKING ALL AROUND
DOOR - BOTH SIDES.
4. GYP. BD. SOFFIT AS SCHEDULED.
5. SHIM AS REQUIRED.
KEYED NOTES
1
3
3
2
5
SELVAM
RAJAVELU
267857-0301
NJRA Architects, Inc.
NJRA Project #
5272 S. College Drive, Suite104Murray, Utah 84123
801.364.9259www.njraarchitects.com
5/2
8/2
020 1
2:4
5:3
2 P
M
A601A
Door &Window
Schedule
Inte
rmo
un
tain
He
alth
ca
re
No
rth
po
inte
Me
dic
al P
ark
, B
ldg
B
2356 N
ort
h 4
00 E
ast
, Su
ite
#102
Too
ele
, U
tah
84074
19230.00
Construction Documents Feb 4, 2020
Too
ele
Va
lley D
ialy
sis
Clin
ic E
xp
an
sio
n
DOOR #
DOOR FRAME DETAILS
DOOR #
FIRE
RATING
(MINUTES)
HARDWARE
GROUPCOMMENTS# OF
PANELS
WIDTH SIZE TYPE
(2/A601A)DEPTH MATERIAL JAMB HEAD THRESHOLD
W1 W2 HEIGHT THICKNESS MATERIAL
TYPE
(1/A601A)
A101A 1 4' - 0" 8' - 0" 1 3/4" HM E W1 7 3/4" HM 9/A601A 9/A601A A101A 45 1 6
A101B 1 4' - 0" 7' - 0" 1 3/4" WD E 1 8 1/4" HM 9/A601A 9/A601A A101B 2 1,2
A102 1 3' - 0" 7' - 0" 1 3/4" WD A 1 5 7/8" HM 9/A601A 9/A601A A102 11
A103 1 3' - 0" 7' - 0" 1 3/4" WD A 1 5 7/8" HM 9/A601A 9/A601A A103 13
A104 1 3' - 0" 7' - 0" 1 3/4" WD D 1 5 7/8" HM 9/A601A 9/A601A A104 10
A123 1 3' - 0" 7' - 0" 1 3/4" WD A 1 5 7/8" HM 9/A601A 9/A601A A123 11
A124 1 3' - 0" 7' - 0" 1 3/4" WD D 1 5 7/8" HM 9/A601A 9/A601A A124 7 1
A126 1 3' - 0" 7' - 0" 1 3/4" WD A 1 5 7/8" HM 9/A601A 9/A601A A126 7 1
A127 1 3' - 0" 7' - 0" 1 3/4" WD A 1 5 7/8" HM 9/A601A 9/A601A A127 9
A128 1 3' - 6" 7' - 0" 1 3/4" WD A 1 5 7/8" HM 9/A601A 9/A601A A128 5 1,3
A129 7' - 0" 7' - 6" AL F MFR. AL 8/A601A 10/A601A A129 12 5
A130 1 3' - 0" 7' - 0" 1 3/4" WD A 1 5 7/8" HM 9/A601A 9/A601A A130 10
A131 1 4' - 0" 7' - 0" 1 3/4" HM A 1 5 7/8" HM 9/A601A 9/A601A A131 4 1
A132A 1 4' - 0" 7' - 0" 1 3/4" HM A 1 5 7/8" HM 9/A601A 9/A601A A132A 6
A133 2 2' - 6" 7' - 0" 1 3/4" WD A 1 5 7/8" HM 9/A601A 9/A601A A133 8
A134 1 3' - 0" 7' - 0" 1 3/4" WD A 1 5 7/8" HM 9/A601A 9/A601A A134 10
A135 1 3' - 0" 7' - 0" 1 3/4" WD A 1 5 7/8" HM 9/A601A 9/A601A A135 9
A136 1 3' - 0" 7' - 0" 1 3/4" WD A 1 5 7/8" HM 9/A601A 9/A601A A136 10
A137 1 4' - 0" 7' - 0" 1 3/4" WD A 1 5 7/8" HM 9/A601A 9/A601A A137 4 1
A138 1 3' - 0" 7' - 0" 1 3/4" WD A 1 5 7/8" HM 9/A601A 9/A601A A138 10
A139 1 3' - 0" 7' - 0" 1 3/4" WD A 1 5 7/8" HM 9/A601A 9/A601A A139 11
A140 1 3' - 0" 7' - 0" 1 3/4" WD A 1 5 7/8" HM 9/A601A 9/A601A A140 9
A141 1 3' - 0" 7' - 0" 1 3/4" WD A 1 5 7/8" HM 9/A601A 9/A601A A141 10
A142 1 4' - 0" 7' - 0" 1 3/4" WD A 1 7 3/4" HM 9/A601A 9/A601A A142 45 3 1,4
COMMENTS
DOOR SCHEDULE
SCALE: 1/4" = 1'-0"2Frame Types
SCALE: 1/4" = 1'-0"1Door Types
SCALE: 1/4" = 1'-0"3Window Legend
W2 W3W1
NOTES:
1. CARD READER REQUIRED AT THIS DOOR.
2. DOOR RELEASE REQUIRED AT THIS DOOR FROM THE NURSE STATION AND SHARED OFFICE.
3. PROVIDE SAFE ZONE CLOSER AT THIS DOOR.
4. PROVIDE AUTO-OPENER AT THIS DOOR.
5. BREAKOUT SLIDING ALUM. GLASS DOOR. SEE SPECIFICATIONS.
6. 45 MINUTE FIRE RATED HOLLOW METAL DOOR AND WINDOW FRAME REQUIRED.
CONTRACTOR SHALL FEILD VERIFY ADJACENT EXISTING STOREFRONT AT THE BUILDING
HALLWAY TO MATCH WITH THE DOOR WINDOW SYSTEM IN APPEARANCE AND COLOR.
SCALE: 3" = 1'-0"9Door Frame in Stud Wall
5 ASI #8 May 28, 2020
SCALE: 3" = 1'-0"8Manual Sliding Breakout Door at Isolation Rooms
SCALE: 3" = 1'-0"10Sliding Door Head Detail
MFR. MFR.
45 MIN. - FIRE RATED (H.M.) SLIDING WINDOW (ALUMINUM) ALUMINUM WINDOW
5
5
5
5
5
1
1
2
2
4
4
A A
B B
S-1
S-1 S-1
S-2
SS-1
SB-1 SB-1 SB-1
L-1
FD-1
SB-1
FD-1
WC-1
S-2
WC-1
4"
4"
3"
S-1
SB-1SB-1
S-1
S-1
SB-1
3"
3"
S-1
SB-1
SB-1
SB-1
SB-1
S-1
SB-1
S-1
WC-1
FD-1
L-1
SB-1
SB-1SB-1SB-1
SB-1SB-1
L-2
FS-1
3"
FS-1
3"S-1
WO-1
2" V UP
1 1/2" V UP
1 1/2" V UP
3"
FS-1
FS-1
1 1/2" V UP
3" V UP
3" V UP
3" V UP
2"3"
3"
2" W UP
3"
2" W UP
2" W UP
3"
3"
2" W UP
2
1
SB-1 SB-1
1
PP301
3
SB-1
3"4"
L-12" V UP
5
4
4
6
W UP
W UP
W UPW UP
6
3"
DCW UP
DCW UP
DHW UPDHW UP
3/4" DCW UP
1" DHW UP
DCW UP
DHW UP
DHW UP
1" DHW UP3/4" DCW UP
RE
GIS
TER
E
DPROFESSIONA
L
EN
GIN
EE
R
No. 11599476-2202
S
TA
T E OF UTAH
DALLEN BLAIR
ROMRIELL
02.03.2020
W W W . V B F A . C O M
ASSOCIATES, INC.
VAN BOERUM& FRANK
801.530.3148 T
801.530.3150 F
CONSULTING ENGINEERS
330 South 300 East
Salt Lake City, UT 84111
Salt Lake City▪ Logan ▪ St. George ▪ Tempe
VBFA Project Number: 19605
NJRA Architects, Inc.
NJRA Project #
5272 S. College Drive, Suite104Murray, Utah 84123
801.364.9259www.njraarchitects.com
5/2
9/2
020 1
0:3
4:4
0 A
M
PP100
BELOWGRADE
PLUMBINGPLAN
Inte
rmo
un
tain
He
alth
ca
re
40
0 E
ast
240
0 S
ou
th
Too
ele
, U
tah
84
07
4
19230.00
Construction Documents February 03, 2020
Dia
lysi
s C
linic
Exp
an
sio
n
SCALE: 1/4" = 1'-0"1BELOW GRADE PLUMBING PLAN
NORTH
KEYED NOTES#
1. EXISTING ELEMENTS SHOWN LIGHT, TYPICAL.
2. CONTRACTOR RESPONSIBLE FOR COORDINATING AND LOCATING ALL CLEANOUTS PER CODE IN ADDITION TO CLEANOUTS CALLED OUT ON PLANS, TYPICAL.
3. WALLS SHOWN FROM ABOVE, TYPICAL.
4. CAP IN FLOOR.
5. FLOOR CUT FOR EXISTING WASTE DROP. TIE INTO NEAREST WASTE LINE.
6. FLOOR CUT TO TIE INTO EXISTING DROP LOCATIONS.
1 Addendum #1 02/17/20
2 Addendum #2 02/18/20
3 ASI-001 03/02/20
4 ASI-006 05/14/20
5 ASI-008 05/29/20
5
1 2 4
A
B
BAY #11
A119
PRIVATE/ISOLATION
A129
TDR
A126
SHARED OFFICE
A104
WAITING
A101
PUBLIC TOILET
A102
BAY #7
A113
BAY #5
A111
BAY #3
A108
BAY #2
A107
BAY #1
A106
(E) ELEVATOR
A140
(E) ELEVATOR MACHINEROOM
A141
(E) HSKP
A142
STAFF
BREAK/CONFERENCEROOM
A134STORAGE
A132
MANAGER OFFICE
A130
LAB ALCOVE
A116
BAY #10
A118
BAY #6
A112
EXAM/ HOME TRAININGROOM
A136HOME TRAINING ROOM
A138
CLEAN SUPPLY
A131
BAY #8
A114
BAY #4
A110
BAY #9
A117
BAY #12
A120
BAY #13
A121
BAY #14
A122
PATIENT TOILET
A123HSKP
A127
SOILED WORKROOM
A128
FUTURE EXAM/ HOMETRAINING ROOM
A141
STAFF TOILET
A139BIO MED
A137
ELEC
A135
MED ROOM
A124
MECH
A140
MECH
A133
NOURISHMENT
A105
MECH
A103
WHEELCHAIR ALCOVE
A125
WC-1
S-2WC-1
WC-1L-1
S-1
L-1
S-2
S-1 S-1
S-1
S-1
S-1
S-1
S-1
L-2
WH
1
FUR
3
FUR
1
S-1
SS-1
FS-1
FD-1
FD-1
FD-1
FS-1
FS-1
1
SB-1 SB-1 SB-1
SB-1
SB-1
SB-1
SB-1
SB-1SB-1SB-1
SB-1SB-1
FS-1
2
3
FUR
2
3
3
4
FUR
4
3/4" PC
5SB-1 SB-1 SB-1
SB-1
SB-1
SB-1
3/4" G
EW-1
EW-1
21
21
WO-1
1 1/4"
2"
2"3/4"
DET
1
3/4"
1 1/4"
6
7
7
7
3/4"1"
1 1/4" 1"
1 1/4"
7
2"
1 1/4"
1 1/4" 3/4"
3"
3" V UP
3" V UP
3"3" V UP 8
2"3"
3" V UP 8
3" V UP8
2"
3"
3" V UP
8
3"
3" V UP
3" V UP 8
1 1/2" V UP
3" V UP 8
3" V UP
3" V UP3"
3" V UP
3"
8
3" V UP8
S-1
IU
1B
IU
1A
3"
10
12
13 11
13 14
3"
EW-1
6
SB-1
SB-1
SB-1
14
3" V UP
3"
8
1" DWS
1 1/2" DWS
14
3"
3"
1 1/2" DWS
3/4"
9 3/4" DWR
1 1/2"
GPM0.5
GPM2.0
6
RCP
2
RCP
1
15
16
EW-1
EW-1
WO-2
1
PP301
17
3"
1 1/4"3/4"
2" V DN
L-1
3"
19
20
20
W DN
W DN20
20
W DN
W DN
W DN
1" DHW DN3/4" DCW DN
DHW DN
DHW DN
DHW DN
DHW DN
3/4" DCW DN
DCW DN
1" DHW DN3/4" DCW DN
RE
GIS
TER
E
DPROFESSIONA
L
EN
GIN
EE
R
No. 11599476-2202
S
TA
T E OF UTAH
DALLEN BLAIR
ROMRIELL
02.03.2020
W W W . V B F A . C O M
ASSOCIATES, INC.
VAN BOERUM& FRANK
801.530.3148 T
801.530.3150 F
CONSULTING ENGINEERS
330 South 300 East
Salt Lake City, UT 84111
Salt Lake City▪ Logan ▪ St. George ▪ Tempe
VBFA Project Number: 19605
NJRA Architects, Inc.
NJRA Project #
5272 S. College Drive, Suite104Murray, Utah 84123
801.364.9259www.njraarchitects.com
5/2
9/2
020 1
0:3
4:4
4 A
M
PP101
LEVEL 1PLUMBING
PLAN
Inte
rmo
un
tain
He
alth
ca
re
40
0 E
ast
240
0 S
ou
th
Too
ele
, U
tah
84
07
4
19230.00
Construction Documents February 03, 2020
Dia
lysi
s C
linic
Exp
an
sio
n
KEYED NOTES#
1. EXISTING ELEMENTS SHOWN LIGHT TO REMAIN, TYPICAL.
2. INSTALL NEW FIRE SPRINKLERS.
3. RELOCATE EXISTING PRV
4. INSTALL NEW 4 OZ PRV.
5. DROP DOWN WALL AND TERMINATE IN SERVICE SINK.
6. THERMOSTATIC MIXING VALVE INSTALLED IN CEILING.
7. PROVIDE HAMMER ARRESTOR ON ALL FAST ACTING VALVES, TYPICAL.
8. FIELD VERIFY LOCATION OF EXISTING VENT LINES PENETRATING LEVEL 2 FLOOR. CONNECT NEW VENT LINES TO EXISTING VENT LINES PENETRATING LEVEL 2 FLOOR. RUN ADDITIONAL PIPING AS NECESSARY.
9. OWNER PROVIDED WATER SOFTENER.
10. CONNECT TO OWNER PROVIDED WATER SOFTENER.
11. ALL SPRINKLER HEADS SHALL BE QUICK RESPONSE THROUGHOUT EACH REMODELED COMPARTMENT, TYPICAL. FIRE SPRINKLERS SHALL BE INSTALLED TO MEET NFPA 13-2016 REQUIREMENTS, TYPICAL.
12. INSTALL THERMOSTATIC MIXING VALVE FOR REVERSE OSMOSIS APPLICATIONS.
13. INSTALL FIRE SPRINKLER SPRINKLERS AND PIPING AS NECESSARY FOR THE REMODELED SPACE, INCLUDING NEW FLOOR PLAN, CEILING PLAN, AND CEILING HEIGHT ADJUSTMENTS. REFER TO THE ARCHITECTURAL SHEETS FOR COMPLETE SCOPE OF THE PROJECT.
14. VALVE AND CAP FOR OWNER TO CHLORINATE LINE.
15. CONNECT RETURN LINE TO WATER HEATER PER MANUFACTURER RECOMMENDATIONS.
16. SEE ARCHITECTURAL PLANS FOR ELEVATION AND EXACT LOCATION OF SUPPLY BOX, TYPICAL.
17. TYPICAL CLEANOUT, SEE PP301 FOR SECTION.
18. DISASSEMBLE GAS PIPING FOR SHEETROCK INSTALLATION TO JOISTS.
19. DISCONNECT WASTE PIPING IN CEILING AND DROP WASTE DOWN EXTERIOR WALL CAVITY. MAKE SURE THAT PIPE IS COMPLETELY COVERED WITH INSULATION ON THE EXTERIOR SIDE OF PIPE. ONCE WASTE PIPING IS BELOW THE CABINET CONTRACTOR CAN JOG BACK TO WHERE THE EXISTING DROP IS LOCATED IN ORDER TO AVOID BREAKING UP CONCRETE.
20. DISCONNECT PIPING IN CEILING AND ROUTE AS SHOWN.
21. INSTALL THERMOSTATIC MIXING VALVE UNDERNEATH COUNTER. RUN HOT AND COLD LINES NEATLY THROUGH CABINETRY.
NORTH
SCALE: 1/4" = 1'-0"1LEVEL 1 PLUMBING PLAN
1 Addendum #1 02/17/20
2 Addendum #2 02/18/20
3 ASI-001 03/02/20
4 ASI-006 05/14/20
5 ASI-008 05/29/20