B0405Room Data SheetADB
Project: 7857 7857 Nottingham Uni Medical Centre
Department: PRI Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
Room: B0405 Patient Obs. Bays for no. 4 (based on Multi-bed room: 4 beds)
Room Number: Revision Date: 01/03/2017
1) User may undress and dress in privacy.
2) Rest and relaxation or sleeping.
3) Patient may take meals or refreshments in bed, by the bed or in the sitting space.
4) Entertainment services system may be used.
5) Patient may receive visitors.
6) Clinical wash-hand basin may be used.
7) Patient records may be reviewed and recorded.
8) Electronic patient records (EPRs) may be accessed and updated.
9) Medicines for use by patients (self-medication) is stored securely in a 'personal' locker.
10) A working supply of linen and amenities is stored.
11) A working supply of consumables may be held/stored.
12) Personal belongings and clothing are stored.
13) Mobile hoist may be used.
14) Patient will receive therapeutic and clinical attention from healthcare staff .
15) Patient may be ambulant, in a wheelchair or on a trolley or bed
16) Carrying out examinations and assessment of patient.
17) Piped medical gases, vacuum and associated equipment may be used.
Activities:
Personnel: 4 x patients.
8 x others (staff and/or visitors).
Planning
Relationships:
Close to social space.
En-suite sanitary facilities.
Space Data: Height (mm): 64.00 2,700Area (m²):
Notes: This room is based on the use of a trolley with a worktop.
It is assumed that computers will be handheld or brought into the room on a trolley.
The call repeat lamp is situated over the door outside the room.
The following items may be provided:
- a ceiling-mounted hoist;
- when used for maternity post-natal provision of a cot(s) will be required.
Separate data and voice outlets may be used where structure cabling solutions are not
available.
ADB Group Definitions:
1. Contractor supply and install.
2. Supply by others, contractor install.
3. UoN supply – loose equipment and specialist equipment (chairs, drawer units,
non-fixed medical equipment).
4. NHS IT equipment (nil cost to the project).
5. Dental supply and install.
6. Pharmacy supply and install.
7. UoN IT support and install.
8. UoN supply and install (tacks and blinds; fire extinguishers; UoN signage.
9. UoN F.O.C.
Activity DataBase 01/03/2017
7857 Nottingham Uni Medical Centre7857Project:
Room Environmental Data B0405ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: B0405 Patient Obs. Bays for no. 4 (based on Multi-bed room: 4 beds)
Room Number: Revision Date: 01/03/2017
Permissible Space Temerature Range(dry bulb) (degC):
TEMPERATURE AND VENTILATION Requirements Notes
18 - 28
Heating Design Temperature (dry bulb)(degC): 22
Minimum Air Changes (AC/hr): 6
Ventilation Type: S/E/N
Bal or -vePressure Relative to Adjoining Space:
G4Supply Air: Final Filter Class
Permisiible Relative Humidity Range (%): Uncontrolled
General Notes:
LIGHTINGType Of Control: S/N/EM
Daytime General Service Illuminance (Lux): 100
Daytime Specific Service Illuminance (Lux): 300
Nighttime General Service Illuminance (Lux): 5
Nighttime Specific Service Illuminance (Lux): 0.5
Local Task Illuminance (Lux): 300
Colour Rendering Required: Y
Colour Rendering Required Characteristics (Ra): 80
Unified Glare Rating Limit (UGRL): 19
Emergency Escape Route Lighting Required: In accordance with BS 5266 and Health Technical
MemorandumsY
Standby Lighting Grade - General Lighting: A
AStandby Lighting Grade - Local Lighting:
General Notes: Refer to SLL Lighting Guide 2 for more detailed guidance
RISKClinical Risk Category:
Non-clinical Business Continuity Risk Category:
General Notes:
Noise Intrusion (dB) 1hr day:
NOISE
Noise Intrusion (dB) 1hr night:
Noise Intrusion (dB) f night:
45
35
45
The LAmax,f dB noise limit applies only at night 23:00 to
07:00 hours.
Maximum Internal Noise from M&E Services (NR): 30 Total noise of MEP services under normal operation across
the range 63Hz to 4kHz inclusive.
Room Sound-insulation Parameters - Privacy:
Room Sound-insulation Parameters - Noise Generation:
Moderate
Typical
Reference to Table 3 of the Department of Health 'Acoustics:
Technical design manual 4032:0.6:England'.
Noise Sensitiviy: Medium
Sound-insulation Rating (dB D nT,w):
General Notes:
Maximum Surface Temperature (DegC):
SAFETY/FIRE
43
Domestic Hot Water Discharge Temperature (DegC): 41
Maximum Cold Water Discharge Temperature (DegC): <20
General Notes:
Type of Automatic Fire Detection: Smoke
General Notes:
Activity DataBase 01/03/2017
ADB Room Design Character B0405
Project: 7857 7857 Nottingham Uni Medical Centre
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Patient Obs. Bays for no. 4 (based on Multi-bed room: 4 beds)B0405Room:
01/03/2017Revision Date:Room Number:
Walls: Wall finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Wall finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Floor: Floor finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Floor finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Ceiling: Ceiling finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Ceiling finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Doorsets: Configuration, glazing, fire rating, security, etc. to be determined by Project Team.
HTM 58 (Mar-2005)
Refer to HBN 00-04 (May-2007) for effective clear door widths.
3 sets of doors:
1 x personnel, wheelchair & equipment access (1000mm);
1 x personnel, trolley, wheelchair & equipment access (1300mm)
1 x personnel, bed, trolley, wheelchair & equipment access (1500mm)
Windows: Essential
Clear glass with solar and privacy control
Designation to be validated against current documentation (HTM 55 archived).
Internal Glazing: Non-essential - Project Option
Designation to be validated against current documentation. HTM 57 (Mar-2005)
Hatch: Not required
Notes: All finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
All finishes selected must have an appropriate risk assessment to accompany the design
decision.
Infection Control must be consulted as described in Performance Requirements for Building
Elements Used in Healthcare Facilities 8941:0.6 England.
Activity DataBase 01/03/2017
Schedule of Components by Room
Project: 7857 7857 Nottingham Uni Medical Centre
B0405ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: B0405 Patient Obs. Bays for no. 4 (based on Multi-bed room: 4 beds)
Room Number: Revision Date: 01/03/2017
Key: (n-old qty) Deletions m-new qty Additions m (n) Quantity changes since audit dateAudit Date: 2-Mar-2017
DescriptionCodeTotalTransNew
GrpAlt. CodeQuantity
1BASIN, medium, hospital pattern, vitreous china, no
tap holes, no overflow, integral back outlet, 500W
400D.
BAS10111
1BED HEAD BUFFER/DOCKING device, bed and wall
protection, horizontal, wall mounted, (internal
clearance 1000-1400)
BED04033
1LAMP, repeat call, patient/staff or staff emergency or
cardiac call
CAL03411
1HOOK, single, small, wall mountedHOO01944
1LUMINAIRE, bedhead, dimmable, patient reading
and general nursing care/examination
LIG00533
1SOCKET outlet, switched, 13 amp, singleOUT00522
1SOCKET outlet, switched, 13 amp, twinOUT01055
1CONNECTION UNIT, switched, 13 amp, flex outletOUT04911
1SOCKET outlet data/voice, double.OUT13122
1RAIL, clinical equipment, wall mounted, 600mmRAI13022
1CABINET, base, modular storage, for 400 facing
inserts, with door, on plinth, 900H
SMC01311
1CABINET, upper, modular storage, for 400 facing
inserts, with door, 750H
SMC02333
1WORKTOP, clinical, for 3 x 400 facing modular
storage cabinets, 1365W 700D
SMW05311
1SWITCH, lightSWC02511
1TAP, bib, 2x8 mm thermostatic mixer, automatic
action, sensor operated, non-touch,
TAP89211
1TRAP, bottle, 1.1/4 in, plastic resealing.WAS10711
2DISPENSER, barrier cream, disposable single
cartridge, wall mounted
DIS01111
2DISPENSER, paper towel, wall mountedDIS01311
2DISPENSER, Medical hand sanitizer, lever action,
wall mounted
DIS02611
2DISPENSER, soap, disposable single cartridge, lever
action, wall mounted
DIS03011
2DISPENSER, disposable gloves set of 3 and
disposable apron, wall mounted
DIS43811
3BED variable height, two-way tilt, adjustable backrest
and knee-break, built-in bed extension with mattress
retainer, electrically operated, on castors, 380-780H
2260/2430L 1010W
BED01544
3CHAIR, easy, high back, with open arms,
upholstered, wipeable
CHA30744
3HOLDER, sack, with lid foot operated, medium,
freestanding, 875H 430W 385D
HOL00622
3MATTRESS, suitable for BED015MAT00844
3TABLE, overbed, cantileveredTAB07344
3ROBE-LOCKER combined, with lockable
section/drawer, towel rail at rear, on castors, 1430H
610W 530D
WAR02144
Activity DataBase 01/03/2017
Schedule of Components by Room
Project: 7857 7857 Nottingham Uni Medical Centre
B0405ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: B0405 Patient Obs. Bays for no. 4 (based on Multi-bed room: 4 beds)
Room Number: Revision Date: 01/03/2017
Key: (n-old qty) Deletions m-new qty Additions m (n) Quantity changes since audit dateAudit Date: 2-Mar-2017
DescriptionCodeTotalTransNew
GrpAlt. CodeQuantity
8TRACK, blinds for windowsTRA90033
Activity DataBase 01/03/2017
C0237Room Data SheetADB
Project: 7857 7857 Nottingham Uni Medical Centre
Department: PRI Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
Room: C0237 Consult / Exam (based on Consulting/examination room: double-sided couch
access)
Room Number: Revision Date: 01/03/2017
1) Consultations may take place.
2) Sterile supplies and consumables are stored on a trolley.
3) User may undress and dress in privacy.
4) Electronic patient records (EPRs) may be accessed and updated.
5) Clinical hand washing.
6) Discussions and interviews may take place.
7) Carrying out examinations and assessment of patient.
8) Patient may arrive on foot or in a wheelchair.
9) Examinations of the patient may be carried out from one or both sides of the couch.
10) Minimally invasive clinical procedures may be undertaken from one or both sides of the
couch.
11) Call systems may be used.
Activities:
Personnel: 1 x patient.
1-2 x staff.
1 x other (escort).
Planning
Relationships:
Space Data: Height (mm): 16.00 2,700Area (m²):
Activity DataBase 01/03/2017
Notes: This room includes a 3-section couch, alternatively, it may accommodate a 2-section
couch or specialist couch.
The call repeat lamp is situated over the door outside the room.
The following items are shown on the room layout but are optional:
- patient/staff call (although expected where a patient will be left unattended);
- room in use switch and indicator.
The following items may be provided:
- a small printer;
- a small lockable drawer;
- dimming switch.
Piped medical gases may be required for some clinical specialties.
Workstations have been placed in Consult/ exam rooms at 900mmm. Local policy may
prefer a desk up to 1200mm to facilitate working practice.
.
Separate data and voice outlets may be used where structure cabling solutions are not
available.
ADB Group Definitions:
1. Contractor supply and install.
2. Supply by others, contractor install.
3. UoN supply – loose equipment and specialist equipment (chairs, drawer units,
non-fixed medical equipment).
4. NHS IT equipment (nil cost to the project).
5. Dental supply and install.
6. Pharmacy supply and install.
7. UoN IT support and install.
8. UoN supply and install (tacks and blinds; fire extinguishers; UoN signage.
9. UoN F.O.C.
Activity DataBase 01/03/2017
7857 Nottingham Uni Medical Centre7857Project:
Room Environmental Data C0237ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: C0237 Consult / Exam (based on Consulting/examination room: double-sided couch
access)
Room Number: Revision Date: 01/03/2017
Permissible Space Temerature Range(dry bulb) (degC):
TEMPERATURE AND VENTILATION Requirements Notes
18 - 28
Heating Design Temperature (dry bulb)(degC): 22
Minimum Air Changes (AC/hr): 6
Ventilation Type: S/E/N
Bal or -vePressure Relative to Adjoining Space:
G4Supply Air: Final Filter Class
Permisiible Relative Humidity Range (%): Uncontrolled
General Notes:
LIGHTINGType Of Control: N
Daytime General Service Illuminance (Lux): 300 WP
Daytime Specific Service Illuminance (Lux):
Nighttime General Service Illuminance (Lux):
Nighttime Specific Service Illuminance (Lux):
Local Task Illuminance (Lux): 1000 Bed level (provided by the mobile examinantion lamp)
Colour Rendering Required: Y
Colour Rendering Required Characteristics (Ra): 80
Unified Glare Rating Limit (UGRL): 19
Emergency Escape Route Lighting Required: In accordance with BS 5266 and Health Technical
MemorandumsY
Standby Lighting Grade - General Lighting: B
Standby Lighting Grade - Local Lighting:
General Notes: Refer to SLL Lighting Guide 2 for more detailed guidance
RISKClinical Risk Category:
Non-clinical Business Continuity Risk Category:
General Notes:
Noise Intrusion (dB) 1hr day:
NOISE
Noise Intrusion (dB) 1hr night:
Noise Intrusion (dB) f night:
40
-
-
Maximum Internal Noise from M&E Services (NR): 35 Total noise of MEP services under normal operation across
the range 63Hz to 4kHz inclusive.
Room Sound-insulation Parameters - Privacy:
Room Sound-insulation Parameters - Noise Generation:
Confidential
Typical
Reference to Table 3 of the Department of Health 'Acoustics:
Technical design manual 4032:0.6:England'.
Noise Sensitiviy: Medium
Sound-insulation Rating (dB D nT,w):
General Notes:
Maximum Surface Temperature (DegC):
SAFETY/FIRE
43
Domestic Hot Water Discharge Temperature (DegC): 41
Maximum Cold Water Discharge Temperature (DegC): <20
General Notes:
Type of Automatic Fire Detection: Smoke
General Notes:
Activity DataBase 01/03/2017
ADB Room Design Character C0237
Project: 7857 7857 Nottingham Uni Medical Centre
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Consult / Exam (based on Consulting/examination room: double-sided couch
access)
C0237Room:
01/03/2017Revision Date:Room Number:
Walls: Wall finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Wall finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Floor: Floor finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Floor finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Ceiling: Ceiling finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Ceiling finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Doorsets: Configuration, glazing, fire rating, security, etc. to be determined by Project Team.
HTM 58 (Mar-2005)
Refer to HBN 00-04 (May-2007) for effective clear door widths.
1 doorset:
1 x personnel, wheelchair & equipment access (1000mm)
Requirement for hinge protection when areas used by children
Windows: Desirable - Project Option
Clear glass with solar and privacy control
Designation to be validated against current documentation (HTM 55 archived).
Internal Glazing: Not required
Hatch: Not required
Notes: All finishes selected must have an appropriate risk assessment to accompany the design
decision.
Infection Control must be consulted as described in Performance Requirements for Building
Elements Used in Healthcare Facilities 8941:0.6 England.
Activity DataBase 01/03/2017
Schedule of Components by Room
Project: 7857 7857 Nottingham Uni Medical Centre
C0237ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: C0237 Consult / Exam (based on Consulting/examination room: double-sided couch
access)
Room Number: Revision Date: 01/03/2017
Key: (n-old qty) Deletions m-new qty Additions m (n) Quantity changes since audit dateAudit Date: 2-Mar-2017
DescriptionCodeTotalTransNew
GrpAlt. CodeQuantity
1BASIN, medium, hospital pattern, vitreous china, no
tap holes, no overflow, integral back outlet, 500W
400D.
BAS10111
1PUSH BUTTON, patient/staff call (help) with socket
for patient hand-held unit
CAL00311
1PULL/PUSH BUTTON, staff emergency call, reset
and integral/adjacent indicator lamp
CAL00711
1LAMP, repeat call, patient/staff or staff emergency or
cardiac call
CAL03411
1DESK, cantilever, single pedestal 3 drawer, cable
management, modesty panel, 1800W 800D
DES02011
1HOOK, single, small, wall mountedHOO01955
1LUMINAIRE, examination, ceiling, adjustable, 1000
lux
LIG05311
1SOCKET outlet, switched, 13 amp, singleOUT00511
1SOCKET outlet, switched, 13 amp, twinOUT01055
1CONNECTION UNIT, switched, 13 amp, flex outletOUT04911
1SOCKET outlet data/voice, double.OUT13122
1CABINET, base, modular storage, for 400 facing
inserts, with door, on plinth, 900H
SMC01311
1CABINET, upper, modular storage, for 400 facing
inserts, with door, 750H
SMC02333
1WORKTOP, clinical, for 3 x 400 facing modular
storage cabinets, 1365W 700D
SMW05311
1SWITCH, lightSWC02511
1TAP, bib, 2x8 mm thermostatic mixer, automatic
action, sensor operated, non-touch,
TAP89211
1TRAP, bottle, 1.1/4 in, plastic resealing.WAS10711
2DISPENSER, barrier cream, disposable single
cartridge, wall mounted
DIS01111
2DISPENSER, paper towel, wall mountedDIS01311
2DISPENSER, Medical hand sanitizer, lever action,
wall mounted
DIS02611
2DISPENSER, soap, disposable single cartridge, lever
action, wall mounted
DIS03011
2DISPENSER, disposable gloves set of 3 and
disposable apron, wall mounted
DIS43811
3CHAIR, swivel, height adjustable, high back, with
arms, wipeable, 5 star base, on castors
CHA30111
3CHAIR, upright, with arms, upholstered, stacking,
wipeable
CHA31822
3COUCH, examination/treatment, (3 section), variable
height, retractable wheels, with paper roll holder
COU01011
3HOLDER, sack, with lid foot operated, medium,
freestanding, 875H 430W 385D
HOL00622
3HOLDER, sharps box, up to 7 litre capacity,
rail/trolley hang or wall mounted, 170H 125W 100D
HOL02011
Activity DataBase 01/03/2017
Schedule of Components by Room
Project: 7857 7857 Nottingham Uni Medical Centre
C0237ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: C0237 Consult / Exam (based on Consulting/examination room: double-sided couch
access)
Room Number: Revision Date: 01/03/2017
Key: (n-old qty) Deletions m-new qty Additions m (n) Quantity changes since audit dateAudit Date: 2-Mar-2017
DescriptionCodeTotalTransNew
GrpAlt. CodeQuantity
3REFRIGERATOR, capacity 160 litre, automatic
defrost, stainless steel, underbench, external
temperature gauge, lockable, on castors, 850H
610W 600D
REF05811
3TROLLEY, modular storage, single open frame,
including handle and worktop, with up to 5 sets of
runners for 600 facing inserts, 850H 730W 450D
SMT00211
3TRACK, curtain, two sided, to suite room dimensionsTRA90111
4COMPUTER KEYBOARDCOM93311
4COMPUTER PRINTER, laser, A4, 250H 380W 385DCOM93811
4COMPUTER MONITOR, 17"; TFT, digital flat panel
display, high-resolution screens, desk top
COM94911
4PRINTER, for labels, desk mountedPRI90022
8TRACK, blinds for windowsTRA90011
Activity DataBase 01/03/2017
C0515Room Data SheetADB
Project: 7857 7857 Nottingham Uni Medical Centre
Department: PRI Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
Room: C0515 Patient Test (based on Testing room: audiometric booth)
Room Number: Revision Date: 01/03/2017
1) Audiometric examination and test procedures may take place.
2) Recording patient data/notes.
3) Patient may be ambulant with/without walking aids, in a wheelchair or requiring assistance.
4) Recording equipment may be used.
5) Computer workstation(s) may be used.
6) Monitoring/diagnostic or therapeutic equipment may be used.
7) Specialised visual aids and multi-media equipment may be used.
8) Clinical hand washing may be undertaken.
Activities:
Personnel: 1 x patient.
1 x staff.
2 x others (escorts).
Planning
Relationships:
Easy access from waiting area.
Clinical handwash to be located outside of the room/booth.
Space Data: Height (mm): 8.00 2,000Area (m²):
Height is the nominal internal dimension of a standard booth and is subject to
design/local decision.
Room area includes booth wall thickness but excludes surrounding void and space for
basin.
Notes: Specialist equipment and associated services are a project team option.
Computer CPU, if provided, to be within an acoustic housing or situated within an
adjoining space.
The call repeat lamp is situated over the door outside the room.
Separate data and voice outlets may be used where structure cabling solutions are not
available.
ADB Group Definitions:
1. Contractor supply and install.
2. Supply by others, contractor install.
3. UoN supply – loose equipment and specialist equipment (chairs, drawer units,
non-fixed medical equipment).
4. NHS IT equipment (nil cost to the project).
5. Dental supply and install.
6. Pharmacy supply and install.
7. UoN IT support and install.
8. UoN supply and install (tacks and blinds; fire extinguishers; UoN signage.
9. UoN F.O.C.
Activity DataBase 01/03/2017
7857 Nottingham Uni Medical Centre7857Project:
Room Environmental Data C0515ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: C0515 Patient Test (based on Testing room: audiometric booth)
Room Number: Revision Date: 01/03/2017
Permissible Space Temerature Range(dry bulb) (degC):
TEMPERATURE AND VENTILATION Requirements Notes
18 - 28
Heating Design Temperature (dry bulb)(degC): 22
Minimum Air Changes (AC/hr): 6
Ventilation Type: S/E
Bal or -vePressure Relative to Adjoining Space:
G4Supply Air: Final Filter Class
Permisiible Relative Humidity Range (%): Uncontrolled
General Notes:
LIGHTINGType Of Control: S/V
Daytime General Service Illuminance (Lux): 300 WP
Daytime Specific Service Illuminance (Lux): 150 During test
Nighttime General Service Illuminance (Lux):
Nighttime Specific Service Illuminance (Lux):
Local Task Illuminance (Lux):
Colour Rendering Required: Y
Colour Rendering Required Characteristics (Ra): 80
Unified Glare Rating Limit (UGRL): 19
Emergency Escape Route Lighting Required: In accordance with BS 5266 and Health Technical
MemorandumsY
Standby Lighting Grade - General Lighting: B
Standby Lighting Grade - Local Lighting:
General Notes: Refer to SLL Lighting Guide 2 for more detailed guidance
RISKClinical Risk Category:
Non-clinical Business Continuity Risk Category:
General Notes:
Noise Intrusion (dB) 1hr day:
NOISE
Noise Intrusion (dB) 1hr night:
Noise Intrusion (dB) f night:
35
-
-
Specialist advice required.
Maximum Internal Noise from M&E Services (NR): 30 Total noise of MEP services under normal operation across
the range 63Hz to 4kHz inclusive.
Room Sound-insulation Parameters - Privacy:
Room Sound-insulation Parameters - Noise Generation:
Confidential
Low
Reference to Table 3 of the Department of Health 'Acoustics:
Technical design manual 4032:0.6:England'.
Noise Sensitiviy: Sensitive
Sound-insulation Rating (dB D nT,w):
General Notes:
Maximum Surface Temperature (DegC):
SAFETY/FIRE
43
Domestic Hot Water Discharge Temperature (DegC): 41
Maximum Cold Water Discharge Temperature (DegC): <20
General Notes:
Type of Automatic Fire Detection: Smoke
General Notes:
Activity DataBase 01/03/2017
ADB Room Design Character C0515
Project: 7857 7857 Nottingham Uni Medical Centre
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Patient Test (based on Testing room: audiometric booth)C0515Room:
01/03/2017Revision Date:Room Number:
Walls: Wall finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Wall finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Floor: Floor finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Floor finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Ceiling: Ceiling finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Ceiling finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Doorsets: Configuration, glazing, fire rating, security, etc. to be determined by Project Team.
HTM 58 (Mar-2005)
Refer to HBN 00-04 (May-2007) for effective clear door widths.
1 doorset - sound attenuating steel doors by specialist:
1 x personnel, wheelchair & equipment access (1000mm)
Requirement for hinge protection when areas used by children
Windows: Not required
Internal Glazing: Not required
Hatch: Not required
Notes: All finishes selected must have an appropriate risk assessment to accompany the design
decision.
Infection Control must be consulted as described in Performance Requirements for Building
Elements Used in Healthcare Facilities 8941:0.6 England.
Activity DataBase 01/03/2017
Schedule of Components by Room
Project: 7857 7857 Nottingham Uni Medical Centre
C0515ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: C0515 Patient Test (based on Testing room: audiometric booth)
Room Number: Revision Date: 01/03/2017
Key: (n-old qty) Deletions m-new qty Additions m (n) Quantity changes since audit dateAudit Date: 2-Mar-2017
DescriptionCodeTotalTransNew
GrpAlt. CodeQuantity
1LAMP INDICATING fire alarm initiation, wall mountedALA02011
1BASIN, medium, hospital pattern, vitreous china, no
tap holes, no overflow, integral back outlet, 500W
400D.
BAS10111
1PULL/PUSH BUTTON, staff emergency call, reset
and integral/adjacent indicator lamp
CAL00711
1LAMP, repeat call, patient/staff or staff emergency or
cardiac call
CAL03411
1HOOK, single, small, wall mountedHOO01922
1SOCKET outlet, switched, 13 amp, singleOUT00511
1SOCKET outlet, switched, 13 amp, twinOUT01044
1CONNECTION UNIT, switched, 13 amp, flex outletOUT04911
1SOCKET outlet data/voice, double.OUT13133
1SWITCH, lightSWC02511
1SWITCH, dimmer, modulatingSWC03411
1TAP, bib, 2x8 mm thermostatic mixer, automatic
action, sensor operated, non-touch,
TAP89211
1TRAP, bottle, 1.1/4 in, plastic resealing.WAS10711
2DISPENSER, barrier cream, disposable single
cartridge, wall mounted
DIS01111
2DISPENSER, paper towel, wall mountedDIS01311
2DISPENSER, Medical hand sanitizer, lever action,
wall mounted
DIS02611
2DISPENSER, soap, disposable single cartridge, lever
action, wall mounted
DIS03011
3TYMPANOMETER, audiometrec testingAUD00611
3COMPUTER with built-in keyboard, 130H 465W
372D
AUD01511
3CHAIR, swivel, height adjustable, high back, with
arms, wipeable, 5 star base, on castors
CHA30122
3CHAIR, upright, upholstered, stacking, wipeableCHA31722
3HOLDER, sack, with lid foot operated, medium,
freestanding, 875H 430W 385D
HOL00611
3TABLE, 710H 600W 450DTAB00311
3TABLE, 720H 900W 700DTAB17711
4COMPUTER KEYBOARDCOM03311
4COMPUTER MONITOR, 17"; TFT, digital flat panel
display, high-resolution screens, desk top
COM04911
Activity DataBase 01/03/2017
C0522-04Room Data SheetADB
Project: 7857 7857 Nottingham Uni Medical Centre
Department: PRI Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
Room: C0522-04 Patient Recovery (based on Recovery room: 1 place)
Room Number: Revision Date: 01/03/2017
1) Examinations of the patient may be carried out from one or both sides of the couch.
2) Electronic patient records (EPRs) may be accessed and updated.
3) Clinical hand washing.
4) Call systems may be used.
5) Patient may be ambulant, in a wheelchair or on a trolley or bed
6) Patient may undress/dress in privacy.
7) Telephone(s) may be used.
8) Piped medical gases, vacuum and associated equipment may be used.
Activities:
Personnel: 1x Patient
1-2x Staff
1x Other (escort)
Planning
Relationships:
Space Data: Height (mm): 12.00 2,700Area (m²):
Notes: The call repeat lamp is situated over the door outside the room.
The following items are shown on the room layout but are optional:
- patient/staff call (although expected where a patient will be left unattended);
- room in use switch and indicator;
- clinical workstation;
- location of the privacy curtain (may be at door entrance, as shown, or between couch
and clinical workstation, see HBN 00-03).
Workstations have been placed in at 900mmm. Local policy may prefer a worktop up to
1200mm to facilitate working practice.
.
Separate data and voice outlets may be used where structure cabling solutions are not
available.
ADB Group Definitions:
1. Contractor supply and install.
2. Supply by others, contractor install.
3. UoN supply – loose equipment and specialist equipment (chairs, drawer units,
non-fixed medical equipment).
4. NHS IT equipment (nil cost to the project).
5. Dental supply and install.
6. Pharmacy supply and install.
7. UoN IT support and install.
8. UoN supply and install (tacks and blinds; fire extinguishers; UoN signage.
9. UoN F.O.C.
Activity DataBase 01/03/2017
7857 Nottingham Uni Medical Centre7857Project:
Room Environmental Data C0522-04ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: C0522-04 Patient Recovery (based on Recovery room: 1 place)
Room Number: Revision Date: 01/03/2017
Permissible Space Temerature Range(dry bulb) (degC):
TEMPERATURE AND VENTILATION Requirements Notes
18 - 25
Heating Design Temperature (dry bulb)(degC): 22
Minimum Air Changes (AC/hr): 15
Ventilation Type: S/E
BalPressure Relative to Adjoining Space:
F7Supply Air: Final Filter Class
Permisiible Relative Humidity Range (%): Uncontrolled
General Notes:
LIGHTINGType Of Control: N/S
Daytime General Service Illuminance (Lux): 500 WP
Daytime Specific Service Illuminance (Lux): 500 WP
Nighttime General Service Illuminance (Lux):
Nighttime Specific Service Illuminance (Lux):
Local Task Illuminance (Lux):
Colour Rendering Required: Y
Colour Rendering Required Characteristics (Ra): 90
Unified Glare Rating Limit (UGRL): 19
Emergency Escape Route Lighting Required: In accordance with BS 5266 and Health Technical
MemorandumsY
Standby Lighting Grade - General Lighting: A
AStandby Lighting Grade - Local Lighting:
General Notes:
RISKClinical Risk Category:
Non-clinical Business Continuity Risk Category:
General Notes:
Noise Intrusion (dB) 1hr day:
NOISE
Noise Intrusion (dB) 1hr night:
Noise Intrusion (dB) f night:
40
35
45
The LAmax,f dB noise limit applies only at night 23:00 to
07:00 hours.
Maximum Internal Noise from M&E Services (NR): 35 Total noise of MEP services under normal operation across
the range 63Hz to 4kHz inclusive.
Room Sound-insulation Parameters - Privacy:
Room Sound-insulation Parameters - Noise Generation:
Confidential
Typical
Reference to Table 3 of the Department of Health 'Acoustics:
Technical design manual 4032:0.6:England'.
Noise Sensitiviy: Medium
Sound-insulation Rating (dB D nT,w):
General Notes:
Maximum Surface Temperature (DegC):
SAFETY/FIRE
43
Domestic Hot Water Discharge Temperature (DegC): 41
Maximum Cold Water Discharge Temperature (DegC): <20
General Notes:
Type of Automatic Fire Detection: Smoke
General Notes:
Activity DataBase 01/03/2017
ADB Room Design Character C0522-04
Project: 7857 7857 Nottingham Uni Medical Centre
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Patient Recovery (based on Recovery room: 1 place)C0522-04Room:
01/03/2017Revision Date:Room Number:
Walls: Wall finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Wall finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Floor: Floor finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Floor finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Ceiling: Ceiling finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Ceiling finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Doorsets: Configuration, glazing, fire rating, security, etc. to be determined by Project Team.
HTM 58 (Mar-2005)
Refer to HBN 00-04 (May-2007) for effective clear door widths.
1 doorset:
1 x personnel, wheelchair & equipment access (1000mm)
Requirement for hinge protection when areas used by children
Windows: Desirable - Project Option
Clear glass with solar and privacy control
Designation to be validated against current documentation (HTM 55 archived).
Internal Glazing: Not required
Hatch: Not required
Notes: All finishes selected must have an appropriate risk assessment to accompany the design
decision.
Infection Control must be consulted as described in Performance Requirements for Building
Elements Used in Healthcare Facilities 8941:0.6 England.
Activity DataBase 01/03/2017
Schedule of Components by Room
Project: 7857 7857 Nottingham Uni Medical Centre
C0522-04ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: C0522-04 Patient Recovery (based on Recovery room: 1 place)
Room Number: Revision Date: 01/03/2017
Key: (n-old qty) Deletions m-new qty Additions m (n) Quantity changes since audit dateAudit Date: 2-Mar-2017
DescriptionCodeTotalTransNew
GrpAlt. CodeQuantity
1BASIN, medium, hospital pattern, vitreous china, no
tap holes, no overflow, integral back outlet, 500W
400D.
BAS10111
1PUSH BUTTON, patient/staff call (help) with socket
for patient hand-held unit
CAL00311
1PULL/PUSH BUTTON, staff emergency call, reset
and integral/adjacent indicator lamp
CAL00711
1LAMP, repeat call, patient/staff or staff emergency or
cardiac call
CAL03411
1HOOK, single, small, wall mountedHOO01955
1ILLUMINATED SIGN, 'Room in use'LIG07311
1SOCKET outlet, switched, 13 amp, singleOUT00511
1SOCKET outlet, switched, 13 amp, twinOUT01077
1CONNECTION UNIT, switched, 13 amp, flex outletOUT04911
1SOCKET outlet data/voice, double.OUT13144
1WORKTOP, clinical, for 400 facing modular storage
cabinets, 900W 700D
SMW06911
1SWITCH, lightSWC02511
1SWITCH, 'Room in use' illuminated sign.SWC07611
1TAP, bib, 2x8 mm thermostatic mixer, automatic
action, sensor operated, non-touch,
TAP89211
1TRACK, curtain, door, C-shapeTRA14711
1TRAP, bottle, 1.1/4 in, plastic resealing.WAS10711
2BRACKET, holder, suction unit.BRA00311
2DISPENSER, barrier cream, disposable single
cartridge, wall mounted
DIS01111
2DISPENSER, paper towel, wall mountedDIS01311
2DISPENSER, Medical hand sanitizer, lever action,
wall mounted
DIS02611
2DISPENSER, soap, disposable single cartridge, lever
action, wall mounted
DIS03011
2DISPENSER, disposable gloves set of 3 and
disposable apron, wall mounted
DIS43811
3CHAIR, swivel, height adjustable, medium back,
wipeable, 5 star base, on castors
CHA30211
3CHAIR, upright, upholstered, stacking, wipeableCHA31711
3CHAIR, easy, reclining, wipeableCHA39111
3HOLDER, sack, with lid foot operated, medium,
freestanding, 875H 430W 385D
HOL00622
3HOLDER, sharps box, up to 7 litre capacity,
rail/trolley hang or wall mounted, 170H 125W 100D
HOL02011
3LOCKER, bedside, 4 compartment with lockable
section /drawer, towel rail at rear, on castors, 902H
485W 485D
LOC00411
3TROLLEY, modular storage, single open frame,
including handle and worktop, with up to 5 sets of
runners for 600 facing inserts, 850H 730W 450D
SMT00211
3STOOL, height adjustable, swivel, mobileSTO00411
Activity DataBase 01/03/2017
Schedule of Components by Room
Project: 7857 7857 Nottingham Uni Medical Centre
C0522-04ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: C0522-04 Patient Recovery (based on Recovery room: 1 place)
Room Number: Revision Date: 01/03/2017
Key: (n-old qty) Deletions m-new qty Additions m (n) Quantity changes since audit dateAudit Date: 2-Mar-2017
DescriptionCodeTotalTransNew
GrpAlt. CodeQuantity
4COMPUTER KEYBOARDCOM03311
4COMPUTER MONITOR, 17"; TFT, digital flat panel
display, high-resolution screens, desk top
COM04911
8TRACK, blinds for windowsTRA90011
Activity DataBase 01/03/2017
C1023Room Data SheetADB
Project: 7857 7857 Nottingham Uni Medical Centre
Department: PRI Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
Room: C1023 Ophthalmic test room
Room Number: Revision Date: 01/03/2017
1) Interviewing and consultation.
2) Assessment for error of refraction when test type is situated behind the patient and viewed
by patient in a mirror sited 3 metres in front.
3) Examine the eye by means of a slit lamp.
4) Clinical hand washing.
5) Electronic patient records (EPRs) may be accessed and updated.
6) Computer workstation(s) may be used.
7) Telephone(s) may be used.
8) A working supply of stationery is held.
9) Patient to undergo optometry examination, (low vision assessment).
Activities:
Personnel: 1 x Patient
1 x Staff
1 x Other (escort)
Planning
Relationships:
Within ophthalmic clinic.
Space Data: Height (mm): 12.00 2,700Area (m²):
Notes: This room will accommodate: Vision Testing, Low Vision Assessment and Ophthalmic
Technical Consultation and can be used by Ophthalmology Consultants or Nurses ,
Orthoptists or Optometrists depending on the Project and local policy.
Separate data and voice outlets may be used where structure cabling solutions are not
available.
ADB Group Definitions:
1. Contractor supply and install.
2. Supply by others, contractor install.
3. UoN supply – loose equipment and specialist equipment (chairs, drawer units,
non-fixed medical equipment).
4. NHS IT equipment (nil cost to the project).
5. Dental supply and install.
6. Pharmacy supply and install.
7. UoN IT support and install.
8. UoN supply and install (tacks and blinds; fire extinguishers; UoN signage.
9. UoN F.O.C.
Activity DataBase 01/03/2017
7857 Nottingham Uni Medical Centre7857Project:
Room Environmental Data C1023ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: C1023 Ophthalmic test room
Room Number: Revision Date: 01/03/2017
Permissible Space Temerature Range(dry bulb) (degC):
TEMPERATURE AND VENTILATION Requirements Notes
18 - 28
Heating Design Temperature (dry bulb)(degC): 22
Minimum Air Changes (AC/hr): 6
Ventilation Type: S/E/N
Bal or -vePressure Relative to Adjoining Space:
G4Supply Air: Final Filter Class
Permisiible Relative Humidity Range (%): Uncontrolled
General Notes:
LIGHTINGType Of Control: N
Daytime General Service Illuminance (Lux): 300 WP
Daytime Specific Service Illuminance (Lux):
Nighttime General Service Illuminance (Lux):
Nighttime Specific Service Illuminance (Lux):
Local Task Illuminance (Lux):
Colour Rendering Required: Y
Colour Rendering Required Characteristics (Ra): 80
Unified Glare Rating Limit (UGRL): 19
Emergency Escape Route Lighting Required: In accordance with BS 5266 and Health Technical
MemorandumsY
Standby Lighting Grade - General Lighting: B
Standby Lighting Grade - Local Lighting:
General Notes: 6500K Colour Temperature - Refer to SLL Lighting Guide 2 for more detailed guidance
RISKClinical Risk Category:
Non-clinical Business Continuity Risk Category:
General Notes:
Noise Intrusion (dB) 1hr day:
NOISE
Noise Intrusion (dB) 1hr night:
Noise Intrusion (dB) f night:
40
-
-
Maximum Internal Noise from M&E Services (NR): 35 Total noise of MEP services under normal operation across
the range 63Hz to 4kHz inclusive.
Room Sound-insulation Parameters - Privacy:
Room Sound-insulation Parameters - Noise Generation:
Confidential
Typical
Reference to Table 3 of the Department of Health 'Acoustics:
Technical design manual 4032:0.6:England'.
Noise Sensitiviy: Medium
Sound-insulation Rating (dB D nT,w):
General Notes:
Maximum Surface Temperature (DegC):
SAFETY/FIRE
43
Domestic Hot Water Discharge Temperature (DegC): 41
Maximum Cold Water Discharge Temperature (DegC): <20
General Notes:
Type of Automatic Fire Detection: Smoke
General Notes:
Activity DataBase 01/03/2017
ADB Room Design Character C1023
Project: 7857 7857 Nottingham Uni Medical Centre
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Ophthalmic test roomC1023Room:
01/03/2017Revision Date:Room Number:
Walls: Wall finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Wall finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Floor: Floor finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Floor finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Ceiling: Ceiling finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Ceiling finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Doorsets: Configuration, glazing, fire rating, security, etc. to be determined by Project Team.
HTM 58 (Mar-2005)
Refer to HBN 00-04 (May-2007) for effective clear door widths.
1 doorset:
1 x personnel, wheelchair & equipment access (1000mm)
Requirement for hinge protection when areas used by children
Windows: Non-essential - Project Option
Clear glass with solar and privacy control. Blackout
Designation to be validated against current documentation (HTM 55 archived).
Internal Glazing: Not required
Hatch: Not required
Notes: All finishes selected must have an appropriate risk assessment to accompany the design
decision.
Infection Control must be consulted as described in Performance Requirements for Building
Elements Used in Healthcare Facilities 8941:0.6 England.
Activity DataBase 01/03/2017
Schedule of Components by Room
Project: 7857 7857 Nottingham Uni Medical Centre
C1023ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: C1023 Ophthalmic test room
Room Number: Revision Date: 01/03/2017
Key: (n-old qty) Deletions m-new qty Additions m (n) Quantity changes since audit dateAudit Date: 2-Mar-2017
DescriptionCodeTotalTransNew
GrpAlt. CodeQuantity
1BASIN, medium, hospital pattern, vitreous china, no
tap holes, no overflow, integral back outlet, 500W
400D.
BAS10111
1PULL/PUSH BUTTON, staff emergency call, reset
and integral/adjacent indicator lamp
CAL00711
1LAMP, repeat call, patient/staff or staff emergency or
cardiac call
CAL03411
1CHAIR, treatment, reclining, height adjustable,
wipeable.
CHA37211
1HOOK, single, small, wall mountedHOO01933
1MIRROR, optical glass, 700H 400WMIR03111
1SOCKET outlet, switched, 13 amp, singleOUT00511
1SOCKET outlet, switched, 13 amp, twinOUT01033
1CONNECTION UNIT, switched, 13 amp, flex outletOUT04944
1SOCKET outlet data/voice, double.OUT13122
1WORKTOP, clinical, for 400 facing modular storage
cabinets, 1200W 700D
SMW07211
1SWITCH, lightSWC02511
1SWITCH, dimmer, modulatingSWC03411
1TAP, bib, 2x8 mm thermostatic mixer, automatic
action, sensor operated, non-touch,
TAP89211
1TRAP, bottle, 1.1/4 in, plastic resealing.WAS10711
2DIAGNOSTIC SET, ophthalmoscope/auriscope with
handle, wall mounted
DIA03011
2DISPENSER, barrier cream, disposable single
cartridge, wall mounted
DIS01111
2DISPENSER, paper towel, wall mountedDIS01311
2DISPENSER, Medical hand sanitizer, lever action,
wall mounted
DIS02611
2DISPENSER, soap, disposable single cartridge, lever
action, wall mounted
DIS03011
2TEST Snellen, with controls, wall mountedTES00411
3CASE, trial lens, for use with electric
ophthalmoscope
CAS01111
3CHAIR, swivel, height adjustable, medium back,
wipeable, 5 star base, on castors
CHA30211
3CHAIR, swivel, height adjustable, medium back,
wipeable, 5 star base, on glides
CHA30411
3CHAIR, upright, upholstered, stacking, wipeableCHA31711
3HOLDER, sack, with lid foot operated, medium,
freestanding, 875H 430W 385D
HOL00622
3TEST LogMAR visual acuity chartOPH01511
3SLIT LAMP, with accessories and height adjustable
stand
OPH02611
4COMPUTER KEYBOARDCOM03311
4COMPUTER MONITOR, 17"; TFT, digital flat panel
display, high-resolution screens, desk top
COM04911
Activity DataBase 01/03/2017
D0434-01Room Data SheetADB
Project: 7857 7857 Nottingham Uni Medical Centre
Department: PRI Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
Room: D0434-01 Dental Staff Rest (based on Rest room with beverages and snack preparation
bay: 10 places)
Room Number: Revision Date: 01/03/2017
1) Rest and relaxation or sleeping.
2) Small amounts of dry goods are stored in cupboard(s).
3) Holding/ storing food in refrigerator.
4) Crockery and cutlery are washed mechanically.
5) Hand-rinse basin may be used.
6) Consuming beverages, meals and snacks.
7) People preparing beverages, meals and snacks.
8) Telephone may be used and messages taken.
9) Laptop computer(s) may be used.
Activities:
Personnel: 10 x persons..
Planning
Relationships:
Staff use - located away from public areas.
Space Data: Height (mm): 20.50 2,700Area (m²):
Notes: The following items are shown on the room layout but are optional:
- telephone outlet;
- mini kitchen water boiler;
- mini kitchen microwave.
The following items may be provided:
- cube lockers for personal belongings;
- television, radio - generally not in staff rest areas;
- water cooler, or access.
.
Separate data and voice outlets may be used where structure cabling solutions are not
available.
ADB Group Definitions:
1. Contractor supply and install.
2. Supply by others, contractor install.
3. UoN supply – loose equipment and specialist equipment (chairs, drawer units,
non-fixed medical equipment).
4. NHS IT equipment (nil cost to the project).
5. Dental supply and install.
6. Pharmacy supply and install.
7. UoN IT support and install.
8. UoN supply and install (tacks and blinds; fire extinguishers; UoN signage.
9. UoN F.O.C.
Activity DataBase 01/03/2017
7857 Nottingham Uni Medical Centre7857Project:
Room Environmental Data D0434-01ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: D0434-01 Dental Staff Rest (based on Rest room with beverages and snack preparation
bay: 10 places)
Room Number: Revision Date: 01/03/2017
Permissible Space Temerature Range(dry bulb) (degC):
TEMPERATURE AND VENTILATION Requirements Notes
18 – 28
Heating Design Temperature (dry bulb)(degC): 22
Minimum Air Changes (AC/hr): 6
Ventilation Type: S/E/N
-vePressure Relative to Adjoining Space:
G4Supply Air: Final Filter Class
Permisiible Relative Humidity Range (%): Uncontrolled
General Notes:
LIGHTINGType Of Control: S/V/EM
Daytime General Service Illuminance (Lux): 50 Floor
Daytime Specific Service Illuminance (Lux): 200 On tables
Nighttime General Service Illuminance (Lux):
Nighttime Specific Service Illuminance (Lux):
Local Task Illuminance (Lux): 300 At servery counter
Colour Rendering Required: Y
Colour Rendering Required Characteristics (Ra): 90
Unified Glare Rating Limit (UGRL): 22
Emergency Escape Route Lighting Required: In accordance with BS 5266 and Health Technical
MemorandumsY
Standby Lighting Grade - General Lighting: B
Standby Lighting Grade - Local Lighting:
General Notes: Refer to SLL Lighting Guide 2 for more detailed guidance
RISKClinical Risk Category:
Non-clinical Business Continuity Risk Category:
General Notes:
Noise Intrusion (dB) 1hr day:
NOISE
Noise Intrusion (dB) 1hr night:
Noise Intrusion (dB) f night:
50
-
-
Maximum Internal Noise from M&E Services (NR): 40 Total noise of MEP services under normal operation across
the range 63Hz to 4kHz inclusive.
Room Sound-insulation Parameters - Privacy:
Room Sound-insulation Parameters - Noise Generation:
Moderate
High
Reference to Table 3 of the Department of Health 'Acoustics:
Technical design manual 4032:0.6:England'.
Noise Sensitiviy: Medium
Sound-insulation Rating (dB D nT,w):
General Notes:
Maximum Surface Temperature (DegC):
SAFETY/FIRE
43
Domestic Hot Water Discharge Temperature (DegC): 41
Maximum Cold Water Discharge Temperature (DegC): <20
General Notes:
Type of Automatic Fire Detection: Smoke
General Notes:
Activity DataBase 01/03/2017
ADB Room Design Character D0434-01
Project: 7857 7857 Nottingham Uni Medical Centre
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Dental Staff Rest (based on Rest room with beverages and snack
preparation bay: 10 places)
D0434-01Room:
01/03/2017Revision Date:Room Number:
Walls: Wall finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Wall finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Floor: Floor finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Floor finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Ceiling: Ceiling finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Ceiling finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Doorsets: Configuration, glazing, fire rating, security, etc. to be determined by Project Team.
HTM 58 (Mar-2005)
Refer to HBN 00-04 (May-2007) for effective clear door widths.
1 doorset:
1 x personnel, wheelchair & equipment access (1000mm)
Windows: Desirable - Project Option
Clear glass with solar control
Designation to be validated against current documentation (HTM 55 archived).
Internal Glazing: Not required
Hatch: Not required
Notes: All finishes selected must have an appropriate risk assessment to accompany the design
decision.
Infection Control must be consulted as described in Performance Requirements for Building
Elements Used in Healthcare Facilities 8941:0.6 England.
Activity DataBase 01/03/2017
Schedule of Components by Room
Project: 7857 7857 Nottingham Uni Medical Centre
D0434-01ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: D0434-01 Dental Staff Rest (based on Rest room with beverages and snack preparation
bay: 10 places)
Room Number: Revision Date: 01/03/2017
Key: (n-old qty) Deletions m-new qty Additions m (n) Quantity changes since audit dateAudit Date: 2-Mar-2017
DescriptionCodeTotalTransNew
GrpAlt. CodeQuantity
1BASIN, small, general pattern, vitreous china, 1 tap
right hand hole, no overflow, bottom outlet, 400W
300D
BAS10511
1BOARD, display/notice, wall mounted, 900H 600WBOA01211
1CUPBOARD, 2 adjustable shelves, wall mounted,
750H 600W 300D
CUP25211
1CUPBOARD, space for built in microwave, wall
mounted, 750H 600W 300D
CUP25911
1CUPBOARD, base, including sink panel, with door,
on plinth, 900H 600W 500D
CUP71511
1CUPBOARD/DRAWER UNIT, base, with door, on
plinth, 900H 600W 500D
CUP73111
1OUTLET cable, 13 ampOUT00233
1SOCKET outlet, switched, 13 amp, singleOUT00511
1SOCKET outlet, switched, 13 amp, twinOUT01033
1CONNECTION UNIT, switched, 13 ampOUT05233
1SOCKET outlet data/voice, double.OUT13122
1OUTLET, cold water for equipmentOUT30111
1SWITCH, lightSWC02511
1TAP, monobloc, pillar mixer, integral thermostatic,
short lever.
TAP28911
1TAP, pillar, high neck, long lever, pair hot and cold,
1/2 in.
TAP35911
1WASTE, unslotted flush-grated, metal, 1.1/4 in. .WAS10011
1WASTE, unslotted recessed grated, metal, 1.1/2 in,
with plug and chain
WAS10311
1TRAP, bottle, 1.1/4 in, plastic resealing.WAS10711
1TRAP, bottle, 1.1/2 in, plastic resealing.WAS10811
1WATER BOILER, 2.5 litre, electric, wall mountedWAT00311
1WORKTOP, dished, stainless steel, with integral
centre sink bowl and 2 tap holes, 2100W 600D
WRT22111
5CHAIR, easy, low back, upholstered, wipeableCHA40566
5CHAIR, upright, upholstered, stacking, wipeableCHA41733
5DISPENSER, soap, wall mountedDIS12411
5HOLDER, sack, with lid foot operated, medium,
freestanding, 875H 430W 385D
HOL10611
5OVEN, microwave, capacity 18 litre, build in, (suitable
for CUP259)
OVE11611
5REFRIGERATOR, capacity 160 litre, automatic
defrost, stainless steel, underbench, external
temperature gauge, lockable, on castors, 850H
610W 600D
REF15811
5TABLE, 710H 900W 900DTAB10711
5TABLE, occasional, square, 415H 610W 610DTAB15333
5TRACK, blinds for windowsTRA90211
Activity DataBase 01/03/2017
D0434-03Room Data SheetADB
Project: 7857 7857 Nottingham Uni Medical Centre
Department: PRI Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
Room: D0434-03 Health Centre Rest Room (based on Rest room with beverages and snack
preparation bay: 20 places)
Room Number: Revision Date: 01/03/2017
1) Rest and relaxation or sleeping.
2) Small amounts of dry goods are stored in cupboard(s).
3) Holding/ storing food in refrigerator.
4) Crockery and cutlery are washed mechanically.
5) Hand-rinse basin may be used.
6) Consuming beverages, meals and snacks.
7) People preparing beverages, meals and snacks.
8) Telephone may be used and messages taken.
9) Laptop computer(s) may be used.
Activities:
Personnel: 20 x persons..
Planning
Relationships:
Staff use - located away from public areas.
Space Data: Height (mm): 35.50 2,700Area (m²):
Notes: The following items are shown on the room layout but are optional:
- telephone outlet;
- mini kitchen water boiler;
- mini kitchen microwave.
The following items may be provided:
- cube lockers for personal belongings;
- television, radio - generally not in staff rest areas;
- water cooler, or access.
.
Separate data and voice outlets may be used where structure cabling solutions are not
available.
ADB Group Definitions:
1. Contractor supply and install.
2. Supply by others, contractor install.
3. UoN supply – loose equipment and specialist equipment (chairs, drawer units,
non-fixed medical equipment).
4. NHS IT equipment (nil cost to the project).
5. Dental supply and install.
6. Pharmacy supply and install.
7. UoN IT support and install.
8. UoN supply and install (tacks and blinds; fire extinguishers; UoN signage.
9. UoN F.O.C.
Activity DataBase 01/03/2017
7857 Nottingham Uni Medical Centre7857Project:
Room Environmental Data D0434-03ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: D0434-03 Health Centre Rest Room (based on Rest room with beverages and snack
preparation bay: 20 places)
Room Number: Revision Date: 01/03/2017
Permissible Space Temerature Range(dry bulb) (degC):
TEMPERATURE AND VENTILATION Requirements Notes
18 – 28
Heating Design Temperature (dry bulb)(degC): 22
Minimum Air Changes (AC/hr): 6
Ventilation Type: S/E/N
-vePressure Relative to Adjoining Space:
G4Supply Air: Final Filter Class
Permisiible Relative Humidity Range (%): Uncontrolled
General Notes:
LIGHTINGType Of Control: S/V/EM
Daytime General Service Illuminance (Lux): 50 Floor
Daytime Specific Service Illuminance (Lux): 200 On tables
Nighttime General Service Illuminance (Lux):
Nighttime Specific Service Illuminance (Lux):
Local Task Illuminance (Lux): 300 At servery counter
Colour Rendering Required: Y
Colour Rendering Required Characteristics (Ra): 90
Unified Glare Rating Limit (UGRL): 22
Emergency Escape Route Lighting Required: In accordance with BS 5266 and Health Technical
MemorandumsY
Standby Lighting Grade - General Lighting: B
Standby Lighting Grade - Local Lighting:
General Notes: Refer to SLL Lighting Guide 2 for more detailed guidance
RISKClinical Risk Category:
Non-clinical Business Continuity Risk Category:
General Notes:
Noise Intrusion (dB) 1hr day:
NOISE
Noise Intrusion (dB) 1hr night:
Noise Intrusion (dB) f night:
50
-
-
Maximum Internal Noise from M&E Services (NR): 40 Total noise of MEP services under normal operation across
the range 63Hz to 4kHz inclusive.
Room Sound-insulation Parameters - Privacy:
Room Sound-insulation Parameters - Noise Generation:
Moderate
High
Reference to Table 3 of the Department of Health 'Acoustics:
Technical design manual 4032:0.6:England'.
Noise Sensitiviy: Medium
Sound-insulation Rating (dB D nT,w):
General Notes:
Maximum Surface Temperature (DegC):
SAFETY/FIRE
43
Domestic Hot Water Discharge Temperature (DegC): 41
Maximum Cold Water Discharge Temperature (DegC): <20
General Notes:
Type of Automatic Fire Detection: Smoke
General Notes:
Activity DataBase 01/03/2017
ADB Room Design Character D0434-03
Project: 7857 7857 Nottingham Uni Medical Centre
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Health Centre Rest Room (based on Rest room with beverages and snack
preparation bay: 20 places)
D0434-03Room:
01/03/2017Revision Date:Room Number:
Walls: Wall finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Wall finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Floor: Floor finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Floor finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Ceiling: Ceiling finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Ceiling finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Doorsets: Configuration, glazing, fire rating, security, etc. to be determined by Project Team.
HTM 58 (Mar-2005)
Refer to HBN 00-04 (May-2007) for effective clear door widths.
1 doorset:
1 x personnel, wheelchair & equipment access (1000mm)
Windows: Desirable - Project Option
Clear glass with solar control
Designation to be validated against current documentation (HTM 55 archived).
Internal Glazing: Not required
Hatch: Not required
Notes: All finishes selected must have an appropriate risk assessment to accompany the design
decision.
Infection Control must be consulted as described in Performance Requirements for Building
Elements Used in Healthcare Facilities 8941:0.6 England.
Activity DataBase 01/03/2017
Schedule of Components by Room
Project: 7857 7857 Nottingham Uni Medical Centre
D0434-03ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: D0434-03 Health Centre Rest Room (based on Rest room with beverages and snack
preparation bay: 20 places)
Room Number: Revision Date: 01/03/2017
Key: (n-old qty) Deletions m-new qty Additions m (n) Quantity changes since audit dateAudit Date: 2-Mar-2017
DescriptionCodeTotalTransNew
GrpAlt. CodeQuantity
1BASIN, small, general pattern, vitreous china, 1 tap
right hand hole, no overflow, bottom outlet, 400W
300D
BAS10511
1BOARD, display/notice, wall mounted, 900H 600WBOA01211
1CUPBOARD, 2 adjustable shelves, wall mounted,
750H 600W 300D
CUP25222
1CUPBOARD, space for built in microwave, wall
mounted, 750H 600W 300D
CUP25911
1CUPBOARD, base, including sink panel, with door,
on plinth, 900H 600W 500D
CUP71533
1OUTLET cable, 13 ampOUT00255
1SOCKET outlet, switched, 13 amp, singleOUT00511
1SOCKET outlet, switched, 13 amp, twinOUT01044
1CONNECTION UNIT, switched, 13 ampOUT05222
1SOCKET outlet data/voice, double.OUT13133
1OUTLET, cold water for equipmentOUT30111
1SWITCH, lightSWC02511
1TAP, monobloc, pillar mixer, integral thermostatic,
short lever.
TAP28911
1TAP, pillar, high neck, long lever, pair hot and cold,
1/2 in.
TAP35922
1WASTE, unslotted flush-grated, metal, 1.1/4 in. .WAS10011
1WASTE, unslotted recessed grated, metal, 1.1/2 in,
with plug and chain
WAS10311
1TRAP, bottle, 1.1/4 in, plastic resealing.WAS10711
1TRAP, bottle, 1.1/2 in, plastic resealing.WAS10822
1WATER BOILER, 2.5 litre, electric, wall mountedWAT00311
1WORKTOP, plain, stainless steel, with 2 sink bowls
& drainers, cantilevered from wall, 2400W
650D, HTM63
WKT52011
2DISPENSER, paper towel, wall mountedDIS01311
2DISPENSER, soap, wall mountedDIS02411
3CHAIR, easy, low back, upholstered, wipeableCHA3051010
3CHAIR, upright, upholstered, stacking, wipeableCHA3171616
3HOLDER, sack, with lid foot operated, medium,
freestanding, 875H 430W 385D
HOL00611
3OVEN, microwave, light duty, 1000watt, capacity 26
litres, 295H 295W 410D
OVE01422
3REFRIGERATOR, capacity 385 litre, automatic
defrost, stainless steel, external temperature gauge,
lockable, on castors, 1995H 600W 700D
REF06722
3TABLE, circular, 760H 1100mm dia.TAB03044
3TABLE, occasional, square, 415H 610W 610DTAB05333
8TRACK, blinds for windowsTRA90022
Activity DataBase 01/03/2017
G0180-01Room Data SheetADB
Project: 7857 7857 Nottingham Uni Medical Centre
Department: PRI Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
Room: G0180-01 Parking bay: resusitation trolley
Room Number: Revision Date: 01/03/2017
1) Mobile equipment may be parked and stored and/or recharged.
2) Equipment is placed on charge.
3) Carrying out routine checks on equipment.
Activities:
Personnel: Intermittent use.
Planning
Relationships:
Space Data: Height (mm): 2.00 2,400Area (m²):
2400 mm is the anticipated minimum ceiling height. Should be sized to suit surrounding
area/design.
Notes: ADB Group Definitions:
1. Contractor supply and install.
2. Supply by others, contractor install.
3. UoN supply – loose equipment and specialist equipment (chairs, drawer units,
non-fixed medical equipment).
4. NHS IT equipment (nil cost to the project).
5. Dental supply and install.
6. Pharmacy supply and install.
7. UoN IT support and install.
8. UoN supply and install (tacks and blinds; fire extinguishers; UoN signage.
9. UoN F.O.C.
Activity DataBase 01/03/2017
7857 Nottingham Uni Medical Centre7857Project:
Room Environmental Data G0180-01ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: G0180-01 Parking bay: resusitation trolley
Room Number: Revision Date: 01/03/2017
Permissible Space Temerature Range(dry bulb) (degC):
TEMPERATURE AND VENTILATION Requirements Notes
18 - 28
Heating Design Temperature (dry bulb)(degC): 18
Minimum Air Changes (AC/hr): See HVAC notes 2
Ventilation Type: N
BalPressure Relative to Adjoining Space:
G4Supply Air: Final Filter Class
Permisiible Relative Humidity Range (%):
General Notes: Part of corridor space
LIGHTINGType Of Control: N
Daytime General Service Illuminance (Lux): 200
Daytime Specific Service Illuminance (Lux):
Nighttime General Service Illuminance (Lux):
Nighttime Specific Service Illuminance (Lux):
Local Task Illuminance (Lux):
Colour Rendering Required: Y
Colour Rendering Required Characteristics (Ra): 80
Unified Glare Rating Limit (UGRL): 22
Emergency Escape Route Lighting Required: In accordance with BS 5266 and Health Technical
MemorandumsY
Standby Lighting Grade - General Lighting:
Standby Lighting Grade - Local Lighting:
General Notes:
RISKClinical Risk Category:
Non-clinical Business Continuity Risk Category:
General Notes:
Noise Intrusion (dB) 1hr day:
NOISE
Noise Intrusion (dB) 1hr night:
Noise Intrusion (dB) f night:
55
-
-
Maximum Internal Noise from M&E Services (NR): 40 Total noise of MEP services under normal operation across
the range 63Hz to 4kHz inclusive.
Room Sound-insulation Parameters - Privacy:
Room Sound-insulation Parameters - Noise Generation:
Not Private
Typical
Reference to Table 3 of the Department of Health 'Acoustics:
Technical design manual 4032:0.6:England'.
Noise Sensitiviy: Not Sensitive
Sound-insulation Rating (dB D nT,w):
General Notes:
Maximum Surface Temperature (DegC):
SAFETY/FIRE
43
Domestic Hot Water Discharge Temperature (DegC): 41
Maximum Cold Water Discharge Temperature (DegC): <20
General Notes:
Type of Automatic Fire Detection: Smoke
General Notes:
Activity DataBase 01/03/2017
ADB Room Design Character G0180-01
Project: 7857 7857 Nottingham Uni Medical Centre
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Parking bay: resusitation trolleyG0180-01Room:
01/03/2017Revision Date:Room Number:
Walls: Wall finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Wall finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Floor: Floor finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Floor finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Ceiling: Ceiling finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Ceiling finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Doorsets: Not required - open to circulation area or part of another space
Windows: Not required
Internal Glazing: Not required
Hatch: Not required
Notes: All finishes selected must have an appropriate risk assessment to accompany the design
decision.
Infection Control must be consulted as described in Performance Requirements for Building
Elements Used in Healthcare Facilities 8941:0.6 England.
Activity DataBase 01/03/2017
Schedule of Components by Room
Project: 7857 7857 Nottingham Uni Medical Centre
G0180-01ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: G0180-01 Parking bay: resusitation trolley
Room Number: Revision Date: 01/03/2017
Key: (n-old qty) Deletions m-new qty Additions m (n) Quantity changes since audit dateAudit Date: 2-Mar-2017
DescriptionCodeTotalTransNew
GrpAlt. CodeQuantity
1SOCKET outlet, switched, 13 amp, twinOUT01022
3TROLLEY, Stirling Medical - LX34RES5,
emergency/resuscitation, 1010H 690W 540D
TRO90011
Activity DataBase 01/03/2017
G0400-03Room Data SheetADB
Project: 7857 7857 Nottingham Uni Medical Centre
Department: PRI Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
Room: G0400-03 Corridor
Room Number: Revision Date: 01/03/2017
1) Patients, relatives and escorts wait to be seen.
2) Displaying information.
Activities:
Personnel:
Planning
Relationships:
General circulation.
Close to clinical or work area.
Close to WC facilities.
Space Data: Height (mm): 2,500Area (m²):
Notes: General circulation.
ADB Group Definitions:
1. Contractor supply and install.
2. Supply by others, contractor install.
3. UoN supply – loose equipment and specialist equipment (chairs, drawer units,
non-fixed medical equipment).
4. NHS IT equipment (nil cost to the project).
5. Dental supply and install.
6. Pharmacy supply and install.
7. UoN IT support and install.
8. UoN supply and install (tacks and blinds; fire extinguishers; UoN signage.
9. UoN F.O.C.
Activity DataBase 01/03/2017
7857 Nottingham Uni Medical Centre7857Project:
Room Environmental Data G0400-03ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: G0400-03 Corridor
Room Number: Revision Date: 01/03/2017
Permissible Space Temerature Range(dry bulb) (degC):
TEMPERATURE AND VENTILATION Requirements Notes
18 - 28
Heating Design Temperature (dry bulb)(degC): 21
Minimum Air Changes (AC/hr): 4
Ventilation Type: S/E/N
Bal or -vePressure Relative to Adjoining Space:
G4Supply Air: Final Filter Class
Permisiible Relative Humidity Range (%): Uncontrolled
General Notes:
LIGHTINGType Of Control: S/N
Daytime General Service Illuminance (Lux): 200
Daytime Specific Service Illuminance (Lux):
Nighttime General Service Illuminance (Lux):
Nighttime Specific Service Illuminance (Lux):
Local Task Illuminance (Lux):
Colour Rendering Required: Y
Colour Rendering Required Characteristics (Ra): 80
Unified Glare Rating Limit (UGRL): -
Emergency Escape Route Lighting Required: In accordance with BS 5266 and Health Technical
MemorandumsY
Standby Lighting Grade - General Lighting: B
Standby Lighting Grade - Local Lighting:
General Notes: Refer to SLL Lighting Guide 2 for more detailed guidance
RISKClinical Risk Category:
Non-clinical Business Continuity Risk Category:
General Notes:
Noise Intrusion (dB) 1hr day:
NOISE
Noise Intrusion (dB) 1hr night:
Noise Intrusion (dB) f night:
63
-
-
Maximum Internal Noise from M&E Services (NR): 63 Total noise of MEP services under normal operation across
the range 63Hz to 4kHz inclusive.
Room Sound-insulation Parameters - Privacy:
Room Sound-insulation Parameters - Noise Generation:
Not Private
Typical
Reference to Table 3 of the Department of Health 'Acoustics:
Technical design manual 4032:0.6:England'.
Noise Sensitiviy: Not Sensitive
Sound-insulation Rating (dB D nT,w):
General Notes:
Maximum Surface Temperature (DegC):
SAFETY/FIRE
43
Domestic Hot Water Discharge Temperature (DegC): 41
Maximum Cold Water Discharge Temperature (DegC): <20
General Notes:
Type of Automatic Fire Detection: Smoke
General Notes:
Activity DataBase 01/03/2017
ADB Room Design Character G0400-03
Project: 7857 7857 Nottingham Uni Medical Centre
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
CorridorG0400-03Room:
01/03/2017Revision Date:Room Number:
Walls: Wall finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Wall finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Floor: Floor finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Floor finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Ceiling: Ceiling finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Ceiling finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Doorsets: Not required - open to circulation area or part of another space
Windows: Non-essential - Project Option
Clear glass with solar control or Not applicable
Designation to be validated against current documentation (HTM 55 archived).
Internal Glazing: Not required
Hatch: Not required
Notes: All finishes selected must have an appropriate risk assessment to accompany the design
decision.
Infection Control must be consulted as described in Performance Requirements for Building
Elements Used in Healthcare Facilities 8941:0.6 England.
Activity DataBase 01/03/2017
Schedule of Components by Room
Project: 7857 7857 Nottingham Uni Medical Centre
G0400-03ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: G0400-03 Corridor
Room Number: Revision Date: 01/03/2017
Key: (n-old qty) Deletions m-new qty Additions m (n) Quantity changes since audit dateAudit Date: 2-Mar-2017
DescriptionCodeTotalTransNew
GrpAlt. CodeQuantity
1OUTLET cable, 13 ampOUT00211
9DISPENSER, cooler, drinking water, (fountain),
(capacity 63.3 l/hr), floor standing
DIS00211
9DISPENSER, disposable cup, wall mountedDIS01211
Activity DataBase 01/03/2017
G0400-05Room Data SheetADB
Project: 7857 7857 Nottingham Uni Medical Centre
Department: PRI Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
Room: G0400-05 Corridor
Room Number: Revision Date: 01/03/2017
1) Patients, relatives and escorts wait to be seen.
2) Displaying information.
Activities:
Personnel:
Planning
Relationships:
General circulation.
Close to clinical or work area.
Close to WC facilities.
Space Data: Height (mm): 2,500Area (m²):
Notes: General circulation.
ADB Group Definitions:
1. Contractor supply and install.
2. Supply by others, contractor install.
3. UoN supply – loose equipment and specialist equipment (chairs, drawer units,
non-fixed medical equipment).
4. NHS IT equipment (nil cost to the project).
5. Dental supply and install.
6. Pharmacy supply and install.
7. UoN IT support and install.
8. UoN supply and install (tacks and blinds; fire extinguishers; UoN signage.
9. UoN F.O.C.
Activity DataBase 01/03/2017
7857 Nottingham Uni Medical Centre7857Project:
Room Environmental Data G0400-05ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: G0400-05 Corridor
Room Number: Revision Date: 01/03/2017
Permissible Space Temerature Range(dry bulb) (degC):
TEMPERATURE AND VENTILATION Requirements Notes
18 - 28
Heating Design Temperature (dry bulb)(degC): 21
Minimum Air Changes (AC/hr): 4
Ventilation Type: S/E/N
Bal or -vePressure Relative to Adjoining Space:
G4Supply Air: Final Filter Class
Permisiible Relative Humidity Range (%): Uncontrolled
General Notes:
LIGHTINGType Of Control: S/N
Daytime General Service Illuminance (Lux): 200
Daytime Specific Service Illuminance (Lux):
Nighttime General Service Illuminance (Lux):
Nighttime Specific Service Illuminance (Lux):
Local Task Illuminance (Lux):
Colour Rendering Required: Y
Colour Rendering Required Characteristics (Ra): 80
Unified Glare Rating Limit (UGRL): -
Emergency Escape Route Lighting Required: In accordance with BS 5266 and Health Technical
MemorandumsY
Standby Lighting Grade - General Lighting: B
Standby Lighting Grade - Local Lighting:
General Notes: Refer to SLL Lighting Guide 2 for more detailed guidance
RISKClinical Risk Category:
Non-clinical Business Continuity Risk Category:
General Notes:
Noise Intrusion (dB) 1hr day:
NOISE
Noise Intrusion (dB) 1hr night:
Noise Intrusion (dB) f night:
63
-
-
Maximum Internal Noise from M&E Services (NR): 63 Total noise of MEP services under normal operation across
the range 63Hz to 4kHz inclusive.
Room Sound-insulation Parameters - Privacy:
Room Sound-insulation Parameters - Noise Generation:
Not Private
Typical
Reference to Table 3 of the Department of Health 'Acoustics:
Technical design manual 4032:0.6:England'.
Noise Sensitiviy: Not Sensitive
Sound-insulation Rating (dB D nT,w):
General Notes:
Maximum Surface Temperature (DegC):
SAFETY/FIRE
43
Domestic Hot Water Discharge Temperature (DegC): 41
Maximum Cold Water Discharge Temperature (DegC): <20
General Notes:
Type of Automatic Fire Detection: Smoke
General Notes:
Activity DataBase 01/03/2017
ADB Room Design Character G0400-05
Project: 7857 7857 Nottingham Uni Medical Centre
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
CorridorG0400-05Room:
01/03/2017Revision Date:Room Number:
Walls: Wall finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Wall finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Floor: Floor finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Floor finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Ceiling: Ceiling finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Ceiling finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Doorsets: Not required - open to circulation area or part of another space
Windows: Non-essential - Project Option
Clear glass with solar control or Not applicable
Designation to be validated against current documentation (HTM 55 archived).
Internal Glazing: Not required
Hatch: Not required
Notes: All finishes selected must have an appropriate risk assessment to accompany the design
decision.
Infection Control must be consulted as described in Performance Requirements for Building
Elements Used in Healthcare Facilities 8941:0.6 England.
Activity DataBase 01/03/2017
Schedule of Components by Room
Project: 7857 7857 Nottingham Uni Medical Centre
G0400-05ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: G0400-05 Corridor
Room Number: Revision Date: 01/03/2017
Key: (n-old qty) Deletions m-new qty Additions m (n) Quantity changes since audit dateAudit Date: 2-Mar-2017
DescriptionCodeTotalTransNew
GrpAlt. CodeQuantity
3SCALE, measuring machine, height weight and blood
pressure measure
SCA90011
Activity DataBase 01/03/2017
G0400-06Room Data SheetADB
Project: 7857 7857 Nottingham Uni Medical Centre
Department: PRI Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
Room: G0400-06 Corridor
Room Number: Revision Date: 01/03/2017
1) Patients, relatives and escorts wait to be seen.
2) Displaying information.
Activities:
Personnel:
Planning
Relationships:
General circulation.
Close to clinical or work area.
Close to WC facilities.
Space Data: Height (mm): 2,500Area (m²):
Notes: General circulation.
ADB Group Definitions:
1. Contractor supply and install.
2. Supply by others, contractor install.
3. UoN supply – loose equipment and specialist equipment (chairs, drawer units,
non-fixed medical equipment).
4. NHS IT equipment (nil cost to the project).
5. Dental supply and install.
6. Pharmacy supply and install.
7. UoN IT support and install.
8. UoN supply and install (tacks and blinds; fire extinguishers; UoN signage.
9. UoN F.O.C.
Activity DataBase 01/03/2017
7857 Nottingham Uni Medical Centre7857Project:
Room Environmental Data G0400-06ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: G0400-06 Corridor
Room Number: Revision Date: 01/03/2017
Permissible Space Temerature Range(dry bulb) (degC):
TEMPERATURE AND VENTILATION Requirements Notes
18 - 28
Heating Design Temperature (dry bulb)(degC): 21
Minimum Air Changes (AC/hr): 4
Ventilation Type: S/E/N
Bal or -vePressure Relative to Adjoining Space:
G4Supply Air: Final Filter Class
Permisiible Relative Humidity Range (%): Uncontrolled
General Notes:
LIGHTINGType Of Control: S/N
Daytime General Service Illuminance (Lux): 200
Daytime Specific Service Illuminance (Lux):
Nighttime General Service Illuminance (Lux):
Nighttime Specific Service Illuminance (Lux):
Local Task Illuminance (Lux):
Colour Rendering Required: Y
Colour Rendering Required Characteristics (Ra): 80
Unified Glare Rating Limit (UGRL): -
Emergency Escape Route Lighting Required: In accordance with BS 5266 and Health Technical
MemorandumsY
Standby Lighting Grade - General Lighting: B
Standby Lighting Grade - Local Lighting:
General Notes: Refer to SLL Lighting Guide 2 for more detailed guidance
RISKClinical Risk Category:
Non-clinical Business Continuity Risk Category:
General Notes:
Noise Intrusion (dB) 1hr day:
NOISE
Noise Intrusion (dB) 1hr night:
Noise Intrusion (dB) f night:
63
-
-
Maximum Internal Noise from M&E Services (NR): 63 Total noise of MEP services under normal operation across
the range 63Hz to 4kHz inclusive.
Room Sound-insulation Parameters - Privacy:
Room Sound-insulation Parameters - Noise Generation:
Not Private
Typical
Reference to Table 3 of the Department of Health 'Acoustics:
Technical design manual 4032:0.6:England'.
Noise Sensitiviy: Not Sensitive
Sound-insulation Rating (dB D nT,w):
General Notes:
Maximum Surface Temperature (DegC):
SAFETY/FIRE
43
Domestic Hot Water Discharge Temperature (DegC): 41
Maximum Cold Water Discharge Temperature (DegC): <20
General Notes:
Type of Automatic Fire Detection: Smoke
General Notes:
Activity DataBase 01/03/2017
ADB Room Design Character G0400-06
Project: 7857 7857 Nottingham Uni Medical Centre
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
CorridorG0400-06Room:
01/03/2017Revision Date:Room Number:
Walls: Wall finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Wall finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Floor: Floor finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Floor finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Ceiling: Ceiling finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Ceiling finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Doorsets: Not required - open to circulation area or part of another space
Windows: Non-essential - Project Option
Clear glass with solar control or Not applicable
Designation to be validated against current documentation (HTM 55 archived).
Internal Glazing: Not required
Hatch: Not required
Notes: All finishes selected must have an appropriate risk assessment to accompany the design
decision.
Infection Control must be consulted as described in Performance Requirements for Building
Elements Used in Healthcare Facilities 8941:0.6 England.
Activity DataBase 01/03/2017
Schedule of Components by Room
Project: 7857 7857 Nottingham Uni Medical Centre
G0400-06ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: G0400-06 Corridor
Room Number: Revision Date: 01/03/2017
Key: (n-old qty) Deletions m-new qty Additions m (n) Quantity changes since audit dateAudit Date: 2-Mar-2017
DescriptionCodeTotalTransNew
GrpAlt. CodeQuantity
1CUPBOARD, 2 adjustable shelves, wall mounted,
750H 600W 300D
CUP25222
1CUPBOARD, base, including sink panel, with door,
on plinth, 900H 600W 500D
CUP71522
1OUTLET cable, 13 ampOUT00211
1OUTLET, cold water for equipmentOUT30111
1SINK UNIT, 1 bowl and drainer, stainless steel,
variable height, motorised system, 650/910H 1200W
580D
SIN10511
1TAP, pillar, high neck, long lever, pair hot and cold,
1/2 in.
TAP35911
1WASTE, unslotted recessed grated, metal, 1.1/2 in,
with plug and chain
WAS10311
1TRAP, bottle, 1.1/2 in, plastic resealing.WAS10811
1WATER BOILER, 2.5 litre, electric, wall mountedWAT00311
3UNIT CHAIR, 1 seater, with arms, upholstered,
wipeable
CHA36733
8TRACK, blinds for windowsTRA90011
Activity DataBase 01/03/2017
H1304-001Room Data SheetADB
Project: 7857 7857 Nottingham Uni Medical Centre
Department: PRI Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
Room: H1304-001 Seminar room: 20 places (including 1 wheelchair place)
Room Number: Revision Date: 01/03/2017
1) Seminars/conferences are held.
2) Multimedia equipment may be used.
3) Laptop computer(s) may be used.
4) Telephone(s) may be used.
Activities:
Personnel: 21 x persons (including lecturer).
Intermittent use.
Planning
Relationships:
Space Data: Height (mm): 28.00 2,700Area (m²):
Notes: For flexibility in use, direct access to a store is required.
The call repeat lamp is situated over the door outside the room.
The following items may be provided:
- a TV;
- an overhead projector;
- video-conferencing facilities;
- an induction loop hearing system;
- a public address system (in larger seminar rooms);
- a clinical wash-hand basin and gel dispenser to allow for clinical use of the room;
- audiovisual links to clinical areas for training purposes;
- shelving, desks/tables and computers for training use.
.
Separate data and voice outlets may be used where structure cabling solutions are not
available.
ADB Group Definitions:
1. Contractor supply and install.
2. Supply by others, contractor install.
3. UoN supply – loose equipment and specialist equipment (chairs, drawer units,
non-fixed medical equipment).
4. NHS IT equipment (nil cost to the project).
5. Dental supply and install.
6. Pharmacy supply and install.
7. UoN IT support and install.
8. UoN supply and install (tacks and blinds; fire extinguishers; UoN signage.
9. UoN F.O.C.
Activity DataBase 01/03/2017
7857 Nottingham Uni Medical Centre7857Project:
Room Environmental Data H1304-001ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: H1304-001 Seminar room: 20 places (including 1 wheelchair place)
Room Number: Revision Date: 01/03/2017
Permissible Space Temerature Range(dry bulb) (degC):
TEMPERATURE AND VENTILATION Requirements Notes
18 - 25
Heating Design Temperature (dry bulb)(degC): 21
Minimum Air Changes (AC/hr): 6
Ventilation Type: S/E/N
BalPressure Relative to Adjoining Space:
G4Supply Air: Final Filter Class
Permisiible Relative Humidity Range (%): Uncontrolled
General Notes:
LIGHTINGType Of Control: S/V
Daytime General Service Illuminance (Lux): 100-150 On floor
Daytime Specific Service Illuminance (Lux): 300 Over working plane
Nighttime General Service Illuminance (Lux):
Nighttime Specific Service Illuminance (Lux):
Local Task Illuminance (Lux):
Colour Rendering Required: Y
Colour Rendering Required Characteristics (Ra): 80
Unified Glare Rating Limit (UGRL): 19
Emergency Escape Route Lighting Required: In accordance with BS 5266 and Health Technical
MemorandumsY
Standby Lighting Grade - General Lighting: B
Standby Lighting Grade - Local Lighting:
General Notes: Refer to SLL Lighting Guide 2 for more detailed guidance
RISKClinical Risk Category:
Non-clinical Business Continuity Risk Category:
General Notes:
Noise Intrusion (dB) 1hr day:
NOISE
Noise Intrusion (dB) 1hr night:
Noise Intrusion (dB) f night:
53
-
-
Maximum Internal Noise from M&E Services (NR): 53 Total noise of MEP services under normal operation across
the range 63Hz to 4kHz inclusive.
Room Sound-insulation Parameters - Privacy:
Room Sound-insulation Parameters - Noise Generation:
Not Private
Typical
Reference to Table 3 of the Department of Health 'Acoustics:
Technical design manual 4032:0.6:England'.
Noise Sensitiviy: Not Sensitive
Sound-insulation Rating (dB D nT,w):
General Notes:
Maximum Surface Temperature (DegC):
SAFETY/FIRE
43
Domestic Hot Water Discharge Temperature (DegC): 41
Maximum Cold Water Discharge Temperature (DegC): <20
General Notes:
Type of Automatic Fire Detection: Smoke
General Notes:
Activity DataBase 01/03/2017
ADB Room Design Character H1304-001
Project: 7857 7857 Nottingham Uni Medical Centre
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Seminar room: 20 places (including 1 wheelchair place)H1304-001Room:
01/03/2017Revision Date:Room Number:
Walls: Wall finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Wall finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Floor: Floor finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Floor finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Ceiling: Ceiling finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Ceiling finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Doorsets: Configuration, glazing, fire rating, security, etc. to be determined by Project Team.
HTM 58 (Mar-2005)
Refer to HBN 00-04 (May-2007) for effective clear door widths.
2 sets of doors:
2 x personnel, wheelchair & equipment access (1500mm)
Windows: Desirable - Project Option
Clear glass with solar and privacy control.
Blinds will be required to darken room, full blackout is rarely required
Designation to be validated against current documentation (HTM 55 archived).
Internal Glazing: Not required
Hatch: Not required
Notes: All finishes selected must have an appropriate risk assessment to accompany the design
decision.
Infection Control must be consulted as described in Performance Requirements for Building
Elements Used in Healthcare Facilities 8941:0.6 England.
Activity DataBase 01/03/2017
Schedule of Components by Room
Project: 7857 7857 Nottingham Uni Medical Centre
H1304-001ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: H1304-001 Seminar room: 20 places (including 1 wheelchair place)
Room Number: Revision Date: 01/03/2017
Key: (n-old qty) Deletions m-new qty Additions m (n) Quantity changes since audit dateAudit Date: 2-Mar-2017
DescriptionCodeTotalTransNew
GrpAlt. CodeQuantity
1BOARD, display/notice, wall mounted, 900H 1200WBOA01311
1HOOK, single, small, wall mountedHOO0191515
1OUTLET cable, fused, 13 amp, ceiling mountedOUT00411
1SOCKET outlet, switched, 13 amp, twinOUT0101010
1SOCKET outlet, computer data, doubleOUT13366
1SOCKET outlet, computer data, single, ceiling
mounted
OUT13511
1SOCKET outlet, telephoneOUT21511
1SWITCH, lightSWC02511
1SWITCH, dimmer, modulatingSWC03411
1THERMOSTATTHE00511
3BOARD, flip chart, height adjustable, freestandingBOA05111
3CHAIR, upright, with arms, upholstered, stacking,
wipeable
CHA3182020
3CUPBOARD, steel, 2 adjustable shelves, 2 door,
lockable, 900H 900W 420D
CUP03611
3TABLE, 710H 1200W 600DTAB00833
770 inch screen to be controlled by local laptopSCR90111
8TRACK, blinds for windowsTRA90033
Activity DataBase 01/03/2017
H1304-002Room Data SheetADB
Project: 7857 7857 Nottingham Uni Medical Centre
Department: PRI Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
Room: H1304-002 Seminar room: 20 places (including 1 wheelchair place)
Room Number: Revision Date: 01/03/2017
1) Seminars/conferences are held.
2) Multimedia equipment may be used.
3) Laptop computer(s) may be used.
4) Telephone(s) may be used.
Activities:
Personnel: 21 x persons (including lecturer).
Intermittent use.
Planning
Relationships:
Space Data: Height (mm): 28.00 2,700Area (m²):
Notes: For flexibility in use, direct access to a store is required.
The call repeat lamp is situated over the door outside the room.
The following items may be provided:
- a TV;
- an overhead projector;
- video-conferencing facilities;
- an induction loop hearing system;
- a public address system (in larger seminar rooms);
- a clinical wash-hand basin and gel dispenser to allow for clinical use of the room;
- audiovisual links to clinical areas for training purposes;
- shelving, desks/tables and computers for training use.
.
Separate data and voice outlets may be used where structure cabling solutions are not
available.
ADB Group Definitions:
1. Contractor supply and install.
2. Supply by others, contractor install.
3. UoN supply – loose equipment and specialist equipment (chairs, drawer units,
non-fixed medical equipment).
4. NHS IT equipment (nil cost to the project).
5. Dental supply and install.
6. Pharmacy supply and install.
7. UoN IT support and install.
8. UoN supply and install (tacks and blinds; fire extinguishers; UoN signage.
9. UoN F.O.C.
Activity DataBase 01/03/2017
7857 Nottingham Uni Medical Centre7857Project:
Room Environmental Data H1304-002ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: H1304-002 Seminar room: 20 places (including 1 wheelchair place)
Room Number: Revision Date: 01/03/2017
Permissible Space Temerature Range(dry bulb) (degC):
TEMPERATURE AND VENTILATION Requirements Notes
18 - 25
Heating Design Temperature (dry bulb)(degC): 21
Minimum Air Changes (AC/hr): 6
Ventilation Type: S/E/N
BalPressure Relative to Adjoining Space:
G4Supply Air: Final Filter Class
Permisiible Relative Humidity Range (%): Uncontrolled
General Notes:
LIGHTINGType Of Control: S/V
Daytime General Service Illuminance (Lux): 100-150 On floor
Daytime Specific Service Illuminance (Lux): 300 Over working plane
Nighttime General Service Illuminance (Lux):
Nighttime Specific Service Illuminance (Lux):
Local Task Illuminance (Lux):
Colour Rendering Required: Y
Colour Rendering Required Characteristics (Ra): 80
Unified Glare Rating Limit (UGRL): 19
Emergency Escape Route Lighting Required: In accordance with BS 5266 and Health Technical
MemorandumsY
Standby Lighting Grade - General Lighting: B
Standby Lighting Grade - Local Lighting:
General Notes: Refer to SLL Lighting Guide 2 for more detailed guidance
RISKClinical Risk Category:
Non-clinical Business Continuity Risk Category:
General Notes:
Noise Intrusion (dB) 1hr day:
NOISE
Noise Intrusion (dB) 1hr night:
Noise Intrusion (dB) f night:
53
-
-
Maximum Internal Noise from M&E Services (NR): 53 Total noise of MEP services under normal operation across
the range 63Hz to 4kHz inclusive.
Room Sound-insulation Parameters - Privacy:
Room Sound-insulation Parameters - Noise Generation:
Not Private
Typical
Reference to Table 3 of the Department of Health 'Acoustics:
Technical design manual 4032:0.6:England'.
Noise Sensitiviy: Not Sensitive
Sound-insulation Rating (dB D nT,w):
General Notes:
Maximum Surface Temperature (DegC):
SAFETY/FIRE
43
Domestic Hot Water Discharge Temperature (DegC): 41
Maximum Cold Water Discharge Temperature (DegC): <20
General Notes:
Type of Automatic Fire Detection: Smoke
General Notes:
Activity DataBase 01/03/2017
ADB Room Design Character H1304-002
Project: 7857 7857 Nottingham Uni Medical Centre
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Seminar room: 20 places (including 1 wheelchair place)H1304-002Room:
01/03/2017Revision Date:Room Number:
Walls: Wall finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Wall finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Floor: Floor finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Floor finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Ceiling: Ceiling finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Ceiling finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Doorsets: Configuration, glazing, fire rating, security, etc. to be determined by Project Team.
HTM 58 (Mar-2005)
Refer to HBN 00-04 (May-2007) for effective clear door widths.
2 sets of doors:
2 x personnel, wheelchair & equipment access (1500mm)
Windows: Desirable - Project Option
Clear glass with solar and privacy control.
Blinds will be required to darken room, full blackout is rarely required
Designation to be validated against current documentation (HTM 55 archived).
Internal Glazing: Not required
Hatch: Not required
Notes: All finishes selected must have an appropriate risk assessment to accompany the design
decision.
Infection Control must be consulted as described in Performance Requirements for Building
Elements Used in Healthcare Facilities 8941:0.6 England.
Activity DataBase 01/03/2017
Schedule of Components by Room
Project: 7857 7857 Nottingham Uni Medical Centre
H1304-002ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: H1304-002 Seminar room: 20 places (including 1 wheelchair place)
Room Number: Revision Date: 01/03/2017
Key: (n-old qty) Deletions m-new qty Additions m (n) Quantity changes since audit dateAudit Date: 2-Mar-2017
DescriptionCodeTotalTransNew
GrpAlt. CodeQuantity
1BOARD, display/notice, wall mounted, 900H 1200WBOA01322
1HOOK, single, small, wall mountedHOO0191717
1OUTLET cable, fused, 13 amp, ceiling mountedOUT00411
1SOCKET outlet, switched, 13 amp, twinOUT0101010
1SOCKET outlet, computer data, doubleOUT13355
1SOCKET outlet, computer data, single, ceiling
mounted
OUT13511
1SOCKET outlet, telephoneOUT21511
1SWITCH, lightSWC02511
1SWITCH, dimmer, modulatingSWC03411
1THERMOSTATTHE00511
3BOARD, flip chart, height adjustable, freestandingBOA05111
3CHAIR, upright, with arms, upholstered, stacking,
wipeable
CHA3182020
3CUPBOARD, steel, 2 adjustable shelves, 2 door,
lockable, 900H 900W 420D
CUP03611
3TABLE, 710H 1200W 600DTAB00833
770 inch screen to be controlled by local laptopSCR90111
8TRACK, blinds for windowsTRA90011
Activity DataBase 01/03/2017
J0232-001Room Data SheetADB
Project: 7857 7857 Nottingham Uni Medical Centre
Department: PRI Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
Room: J0232-001 Reception Dental Area (based on Reception: 2 person)
Room Number: Revision Date: 01/03/2017
1) Reception and registration of patients.
2) Maintaining appointments and attendance register.
3) Computer workstation(s) may be used.
4) Dealing with enquiries.
5) Telephone(s) may be used.
6) Controlling access to clinical or work area.
7) Staff notices, information and/or messages may be displayed.
Activities:
Personnel: 2 x staff.
2 x patients/visitors.
Planning
Relationships:
Close to, with clear view of, entrance and waiting area.
Close to self-registration point when provided.
Close to clinical or work area(s).
Easy access to records store when paper records are still used.
Access to a "safe haven" area.
Space Data: Height (mm): 11.00 2,400Area (m²):
2400 mm is the anticipated minimum ceiling height. Should be sized to suit surrounding
area/design.
Notes: The reception desk should be accessible to all users and provide security for staff .
In facilities for children and young people it should be child friendly.
The following items may be provided:
- a printer;
- a "controlled entry" system;
- a "next patient" call system;
.
Separate data and voice outlets may be used where structure cabling solutions are not
available.
ADB Group Definitions:
1. Contractor supply and install.
2. Supply by others, contractor install.
3. UoN supply – loose equipment and specialist equipment (chairs, drawer units,
non-fixed medical equipment).
4. NHS IT equipment (nil cost to the project).
5. Dental supply and install.
6. Pharmacy supply and install.
7. UoN IT support and install.
8. UoN supply and install (tacks and blinds; fire extinguishers; UoN signage.
9. UoN F.O.C.
Activity DataBase 01/03/2017
7857 Nottingham Uni Medical Centre7857Project:
Room Environmental Data J0232-001ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: J0232-001 Reception Dental Area (based on Reception: 2 person)
Room Number: Revision Date: 01/03/2017
Permissible Space Temerature Range(dry bulb) (degC):
TEMPERATURE AND VENTILATION Requirements Notes
18 - 28
Heating Design Temperature (dry bulb)(degC): 21
Minimum Air Changes (AC/hr): 4
Ventilation Type: S/E/N
BalPressure Relative to Adjoining Space:
G4Supply Air: Final Filter Class
Permisiible Relative Humidity Range (%): Uncontrolled
General Notes:
LIGHTINGType Of Control: S/N
Daytime General Service Illuminance (Lux): 300
Daytime Specific Service Illuminance (Lux):
Nighttime General Service Illuminance (Lux):
Nighttime Specific Service Illuminance (Lux):
Local Task Illuminance (Lux): 500 Over desk task area
Colour Rendering Required: Y
Colour Rendering Required Characteristics (Ra): 80
Unified Glare Rating Limit (UGRL): 19
Emergency Escape Route Lighting Required: In accordance with BS 5266 and Health Technical
MemorandumsY
Standby Lighting Grade - General Lighting: B
Standby Lighting Grade - Local Lighting:
General Notes: Refer to SLL Lighting Guide 2 for more detailed guidance
RISKClinical Risk Category:
Non-clinical Business Continuity Risk Category:
General Notes:
Noise Intrusion (dB) 1hr day:
NOISE
Noise Intrusion (dB) 1hr night:
Noise Intrusion (dB) f night:
58
-
-
Maximum Internal Noise from M&E Services (NR): 58 Total noise of MEP services under normal operation across
the range 63Hz to 4kHz inclusive.
Room Sound-insulation Parameters - Privacy:
Room Sound-insulation Parameters - Noise Generation:
Not Private
Typical
Reference to Table 3 of the Department of Health 'Acoustics:
Technical design manual 4032:0.6:England'.
Noise Sensitiviy: Not Sensitive
Sound-insulation Rating (dB D nT,w):
General Notes:
Maximum Surface Temperature (DegC):
SAFETY/FIRE
43
Domestic Hot Water Discharge Temperature (DegC): 41
Maximum Cold Water Discharge Temperature (DegC): <20
General Notes:
Type of Automatic Fire Detection: Smoke
General Notes:
Activity DataBase 01/03/2017
ADB Room Design Character J0232-001
Project: 7857 7857 Nottingham Uni Medical Centre
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Reception Dental Area (based on Reception: 2 person)J0232-001Room:
01/03/2017Revision Date:Room Number:
Walls: Wall finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Wall finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Floor: Floor finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Floor finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Ceiling: Ceiling finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Ceiling finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Doorsets: Configuration, glazing, fire rating, security, etc. to be determined by Project Team.
HTM 58 (Mar-2005)
Refer to HBN 00-04 (May-2007) for effective clear door widths.
1 doorset:
1 x personnel, wheelchair & equipment access (1000mm)
Windows: Not required
Internal Glazing: Not required
Hatch: Not required
Notes: All finishes selected must have an appropriate risk assessment to accompany the design
decision.
Infection Control must be consulted as described in Performance Requirements for Building
Elements Used in Healthcare Facilities 8941:0.6 England.
Activity DataBase 01/03/2017
Schedule of Components by Room
Project: 7857 7857 Nottingham Uni Medical Centre
J0232-001ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: J0232-001 Reception Dental Area (based on Reception: 2 person)
Room Number: Revision Date: 01/03/2017
Key: (n-old qty) Deletions m-new qty Additions m (n) Quantity changes since audit dateAudit Date: 2-Mar-2017
DescriptionCodeTotalTransNew
GrpAlt. CodeQuantity
1BESPOKE RECEPTION DESK, console top, Custom
fit
COU90111
1SOCKET outlet, switched, 13 amp, singleOUT00522
1SOCKET outlet, switched, 13 amp, twinOUT01066
1SOCKET outlet data/voice, double.OUT13133
1PANEL, indicatorPAN06311
1SWITCH, lightSWC02522
3CHAIR, swivel, height adjustable, high back, with
arms, wipeable, 5 star base, on castors
CHA30133
3DRAWER UNIT, 2 drawer, lockable, on castors,
600H 410W 600D
DRA05611
4COMPUTER KEYBOARDCOM93333
4COMPUTER MONITOR, 17"; TFT, digital flat panel
display, high-resolution screens, desk top
COM94933
Activity DataBase 01/03/2017
J0232-002Room Data SheetADB
Project: 7857 7857 Nottingham Uni Medical Centre
Department: PRI Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
Room: J0232-002 Reception: 2 person
Room Number: Revision Date: 01/03/2017
1) Reception and registration of patients.
2) Maintaining appointments and attendance register.
3) Computer workstation(s) may be used.
4) Dealing with enquiries.
5) Telephone(s) may be used.
6) Controlling access to clinical or work area.
7) Staff notices, information and/or messages may be displayed.
Activities:
Personnel: 2 x staff.
2 x patients/visitors.
Planning
Relationships:
Close to, with clear view of, entrance and waiting area.
Close to self-registration point when provided.
Close to clinical or work area(s).
Easy access to records store when paper records are still used.
Access to a "safe haven" area.
Space Data: Height (mm): 11.00 2,400Area (m²):
2400 mm is the anticipated minimum ceiling height. Should be sized to suit surrounding
area/design.
Notes: The reception desk should be accessible to all users and provide security for staff .
In facilities for children and young people it should be child friendly.
The following items may be provided:
- a printer;
- a "controlled entry" system;
- a "next patient" call system;
.
Separate data and voice outlets may be used where structure cabling solutions are not
available.
ADB Group Definitions:
1. Contractor supply and install.
2. Supply by others, contractor install.
3. UoN supply – loose equipment and specialist equipment (chairs, drawer units,
non-fixed medical equipment).
4. NHS IT equipment (nil cost to the project).
5. Dental supply and install.
6. Pharmacy supply and install.
7. UoN IT support and install.
8. UoN supply and install (tacks and blinds; fire extinguishers; UoN signage.
9. UoN F.O.C.
Activity DataBase 01/03/2017
7857 Nottingham Uni Medical Centre7857Project:
Room Environmental Data J0232-002ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: J0232-002 Reception: 2 person
Room Number: Revision Date: 01/03/2017
Permissible Space Temerature Range(dry bulb) (degC):
TEMPERATURE AND VENTILATION Requirements Notes
18 - 28
Heating Design Temperature (dry bulb)(degC): 21
Minimum Air Changes (AC/hr): 4
Ventilation Type: S/E/N
BalPressure Relative to Adjoining Space:
G4Supply Air: Final Filter Class
Permisiible Relative Humidity Range (%): Uncontrolled
General Notes:
LIGHTINGType Of Control: S/N
Daytime General Service Illuminance (Lux): 300
Daytime Specific Service Illuminance (Lux):
Nighttime General Service Illuminance (Lux):
Nighttime Specific Service Illuminance (Lux):
Local Task Illuminance (Lux): 500 Over desk task area
Colour Rendering Required: Y
Colour Rendering Required Characteristics (Ra): 80
Unified Glare Rating Limit (UGRL): 19
Emergency Escape Route Lighting Required: In accordance with BS 5266 and Health Technical
MemorandumsY
Standby Lighting Grade - General Lighting: B
Standby Lighting Grade - Local Lighting:
General Notes: Refer to SLL Lighting Guide 2 for more detailed guidance
RISKClinical Risk Category:
Non-clinical Business Continuity Risk Category:
General Notes:
Noise Intrusion (dB) 1hr day:
NOISE
Noise Intrusion (dB) 1hr night:
Noise Intrusion (dB) f night:
58
-
-
Maximum Internal Noise from M&E Services (NR): 58 Total noise of MEP services under normal operation across
the range 63Hz to 4kHz inclusive.
Room Sound-insulation Parameters - Privacy:
Room Sound-insulation Parameters - Noise Generation:
Not Private
Typical
Reference to Table 3 of the Department of Health 'Acoustics:
Technical design manual 4032:0.6:England'.
Noise Sensitiviy: Not Sensitive
Sound-insulation Rating (dB D nT,w):
General Notes:
Maximum Surface Temperature (DegC):
SAFETY/FIRE
43
Domestic Hot Water Discharge Temperature (DegC): 41
Maximum Cold Water Discharge Temperature (DegC): <20
General Notes:
Type of Automatic Fire Detection: Smoke
General Notes:
Activity DataBase 01/03/2017
ADB Room Design Character J0232-002
Project: 7857 7857 Nottingham Uni Medical Centre
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Reception: 2 personJ0232-002Room:
01/03/2017Revision Date:Room Number:
Walls: Wall finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Wall finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Floor: Floor finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Floor finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Ceiling: Ceiling finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Ceiling finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Doorsets: Configuration, glazing, fire rating, security, etc. to be determined by Project Team.
HTM 58 (Mar-2005)
Refer to HBN 00-04 (May-2007) for effective clear door widths.
1 doorset:
1 x personnel, wheelchair & equipment access (1000mm)
Windows: Not required
Internal Glazing: Not required
Hatch: Not required
Notes: All finishes selected must have an appropriate risk assessment to accompany the design
decision.
Infection Control must be consulted as described in Performance Requirements for Building
Elements Used in Healthcare Facilities 8941:0.6 England.
Activity DataBase 01/03/2017
Schedule of Components by Room
Project: 7857 7857 Nottingham Uni Medical Centre
J0232-002ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: J0232-002 Reception: 2 person
Room Number: Revision Date: 01/03/2017
Key: (n-old qty) Deletions m-new qty Additions m (n) Quantity changes since audit dateAudit Date: 2-Mar-2017
DescriptionCodeTotalTransNew
GrpAlt. CodeQuantity
1BESPOKE RECEPTION DESK, console top, Custom
fit
COU90211
1SOCKET outlet, switched, 13 amp, singleOUT00511
1SOCKET outlet, switched, 13 amp, twinOUT01066
1SOCKET outlet data/voice, double.OUT13133
1PANEL, indicatorPAN06311
1SWITCH, lightSWC02511
5CHAIR, swivel, height adjustable, high back, with
arms, wipeable, 5 star base, on castors
CHA40133
5COMPUTER KEYBOARDCOM13333
5COMPUTER MONITOR, 17"; TFT, digital flat panel
display, high-resolution screens, desk top
COM14933
5DRAWER UNIT, 2 drawer, lockable, on castors,
600H 410W 600D
DRA15611
5PRINTER multifunction, network, floor standing, zone
1800W 750D
PRI21011
Activity DataBase 01/03/2017
J1155-01ARoom Data SheetADB
Project: 7857 7857 Nottingham Uni Medical Centre
Department: PRI Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
Room: J1155-01A Waiting area: 20 places (including 2 wheelchair places)
Room Number: Revision Date: 01/03/2017
1) Patients, relatives and escorts wait to be seen.
2) Displaying information.
Activities:
Personnel: 20 x persons, including 2 x wheelchair user
Planning
Relationships:
Adjacent to reception area.
Close to clinical or work area.
Close to WC facilities.
Space Data: Height (mm): 10.00 2,700Area (m²):
Notes: Type of seating to be suitable for patient profile.
Method for calling patients into clinical rooms to be decided locally.
The following items may be provided:
- an enclosed noticeboard;
- background music and other entertainment facilities;
- television and internet access.
ADB Group Definitions:
1. Contractor supply and install.
2. Supply by others, contractor install.
3. UoN supply – loose equipment and specialist equipment (chairs, drawer units,
non-fixed medical equipment).
4. NHS IT equipment (nil cost to the project).
5. Dental supply and install.
6. Pharmacy supply and install.
7. UoN IT support and install.
8. UoN supply and install (tacks and blinds; fire extinguishers; UoN signage.
9. UoN F.O.C.
Activity DataBase 01/03/2017
7857 Nottingham Uni Medical Centre7857Project:
Room Environmental Data J1155-01AADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: J1155-01A Waiting area: 20 places (including 2 wheelchair places)
Room Number: Revision Date: 01/03/2017
Permissible Space Temerature Range(dry bulb) (degC):
TEMPERATURE AND VENTILATION Requirements Notes
18 - 28
Heating Design Temperature (dry bulb)(degC): 21
Minimum Air Changes (AC/hr): 4
Ventilation Type: S/E/N
Bal or -vePressure Relative to Adjoining Space:
G4Supply Air: Final Filter Class
Permisiible Relative Humidity Range (%): Uncontrolled
General Notes:
LIGHTINGType Of Control: S/N
Daytime General Service Illuminance (Lux): 200
Daytime Specific Service Illuminance (Lux):
Nighttime General Service Illuminance (Lux):
Nighttime Specific Service Illuminance (Lux):
Local Task Illuminance (Lux):
Colour Rendering Required: Y
Colour Rendering Required Characteristics (Ra): 80
Unified Glare Rating Limit (UGRL): -
Emergency Escape Route Lighting Required: In accordance with BS 5266 and Health Technical
MemorandumsY
Standby Lighting Grade - General Lighting: B
Standby Lighting Grade - Local Lighting:
General Notes: Refer to SLL Lighting Guide 2 for more detailed guidance
RISKClinical Risk Category:
Non-clinical Business Continuity Risk Category:
General Notes:
Noise Intrusion (dB) 1hr day:
NOISE
Noise Intrusion (dB) 1hr night:
Noise Intrusion (dB) f night:
63
-
-
Maximum Internal Noise from M&E Services (NR): 63 Total noise of MEP services under normal operation across
the range 63Hz to 4kHz inclusive.
Room Sound-insulation Parameters - Privacy:
Room Sound-insulation Parameters - Noise Generation:
Not Private
Typical
Reference to Table 3 of the Department of Health 'Acoustics:
Technical design manual 4032:0.6:England'.
Noise Sensitiviy: Not Sensitive
Sound-insulation Rating (dB D nT,w):
General Notes:
Maximum Surface Temperature (DegC):
SAFETY/FIRE
43
Domestic Hot Water Discharge Temperature (DegC): 41
Maximum Cold Water Discharge Temperature (DegC): <20
General Notes:
Type of Automatic Fire Detection: Smoke
General Notes:
Activity DataBase 01/03/2017
ADB Room Design Character J1155-01A
Project: 7857 7857 Nottingham Uni Medical Centre
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Waiting area: 20 places (including 2 wheelchair places)J1155-01ARoom:
01/03/2017Revision Date:Room Number:
Walls: Wall finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Wall finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Floor: Floor finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Floor finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Ceiling: Ceiling finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Ceiling finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Doorsets: Not required - open to circulation area or part of another space
Windows: Non-essential - Project Option
Clear glass with solar control or Not applicable
Designation to be validated against current documentation (HTM 55 archived).
Internal Glazing: Not required
Hatch: Not required
Notes: All finishes selected must have an appropriate risk assessment to accompany the design
decision.
Infection Control must be consulted as described in Performance Requirements for Building
Elements Used in Healthcare Facilities 8941:0.6 England.
Activity DataBase 01/03/2017
Schedule of Components by Room
Project: 7857 7857 Nottingham Uni Medical Centre
J1155-01AADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: J1155-01A Waiting area: 20 places (including 2 wheelchair places)
Room Number: Revision Date: 01/03/2017
Key: (n-old qty) Deletions m-new qty Additions m (n) Quantity changes since audit dateAudit Date: 2-Mar-2017
DescriptionCodeTotalTransNew
GrpAlt. CodeQuantity
3UNIT CHAIR, 1 seater, with arms, upholstered,
wipeable
CHA36733
3UNIT CHAIR, 2 seater, with arms, upholstered,
wipeable
CHA3681111
3UNIT CHAIR, 3 seater, with arms, upholstered,
wipeable
CHA36955
Activity DataBase 01/03/2017
J1155-01BRoom Data SheetADB
Project: 7857 7857 Nottingham Uni Medical Centre
Department: PRI Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
Room: J1155-01B Waiting area: 20 places (including 2 wheelchair places)
Room Number: Revision Date: 01/03/2017
Activities:
Personnel:
Planning
Relationships:
Space Data: Height (mm): 10.00 2,700Area (m²):
Notes: ADB Group Definitions:
1. Contractor supply and install.
2. Supply by others, contractor install.
3. UoN supply – loose equipment and specialist equipment (chairs, drawer units,
non-fixed medical equipment).
4. NHS IT equipment (nil cost to the project).
5. Dental supply and install.
6. Pharmacy supply and install.
7. UoN IT support and install.
8. UoN supply and install (tacks and blinds; fire extinguishers; UoN signage.
9. UoN F.O.C.
Activity DataBase 01/03/2017
7857 Nottingham Uni Medical Centre7857Project:
Room Environmental Data J1155-01BADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: J1155-01B Waiting area: 20 places (including 2 wheelchair places)
Room Number: Revision Date: 01/03/2017
Permissible Space Temerature Range(dry bulb) (degC):
TEMPERATURE AND VENTILATION Requirements Notes
Heating Design Temperature (dry bulb)(degC):
Minimum Air Changes (AC/hr):
Ventilation Type:
Pressure Relative to Adjoining Space:
Supply Air: Final Filter Class
Permisiible Relative Humidity Range (%):
General Notes:
LIGHTINGType Of Control:
Daytime General Service Illuminance (Lux):
Daytime Specific Service Illuminance (Lux):
Nighttime General Service Illuminance (Lux):
Nighttime Specific Service Illuminance (Lux):
Local Task Illuminance (Lux):
Colour Rendering Required: N
Colour Rendering Required Characteristics (Ra):
Unified Glare Rating Limit (UGRL):
Emergency Escape Route Lighting Required: N
Standby Lighting Grade - General Lighting:
Standby Lighting Grade - Local Lighting:
General Notes:
RISKClinical Risk Category:
Non-clinical Business Continuity Risk Category:
General Notes:
Noise Intrusion (dB) 1hr day:
NOISE
Noise Intrusion (dB) 1hr night:
Noise Intrusion (dB) f night:
Maximum Internal Noise from M&E Services (NR):
Room Sound-insulation Parameters - Privacy:
Room Sound-insulation Parameters - Noise Generation:
Noise Sensitiviy:
Sound-insulation Rating (dB D nT,w):
General Notes:
Maximum Surface Temperature (DegC):
SAFETY/FIRE
Domestic Hot Water Discharge Temperature (DegC):
Maximum Cold Water Discharge Temperature (DegC):
General Notes:
Type of Automatic Fire Detection:
General Notes:
Activity DataBase 01/03/2017
ADB Room Design Character J1155-01B
Project: 7857 7857 Nottingham Uni Medical Centre
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Waiting area: 20 places (including 2 wheelchair places)J1155-01BRoom:
01/03/2017Revision Date:Room Number:
Walls:
Floor:
Ceiling:
Doorsets:
Windows:
Internal Glazing:
Hatch:
Notes:
Activity DataBase 01/03/2017
Schedule of Components by Room
Project: 7857 7857 Nottingham Uni Medical Centre
J1155-01BADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: J1155-01B Waiting area: 20 places (including 2 wheelchair places)
Room Number: Revision Date: 01/03/2017
Key: (n-old qty) Deletions m-new qty Additions m (n) Quantity changes since audit dateAudit Date: 2-Mar-2017
DescriptionCodeTotalTransNew
GrpAlt. CodeQuantity
1OUTLET cable, 13 ampOUT00233
1SOCKET outlet data/voice, double.OUT13122
2TELEVISION monitor, colour, flat panel, large, wall
mounted
TVM00311
3RACK, magazine, 3 shelves, floor standing, fixed to
the wall, 1400H 900W 300D
RAC09111
4SCREEN, colour, check-in, required specialist socketSCR90033
9DISPENSER, cooler, drinking water, (fountain),
(capacity 63.3 l/hr), floor standing
DIS00211
Activity DataBase 01/03/2017
J1155-01CRoom Data SheetADB
Project: 7857 7857 Nottingham Uni Medical Centre
Department: PRI Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
Room: J1155-01C Waiting area: 20 places (including 2 wheelchair places)
Room Number: Revision Date: 01/03/2017
Activities:
Personnel:
Planning
Relationships:
Space Data: Height (mm): 10.00 2,700Area (m²):
Notes: ADB Group Definitions:
1. Contractor supply and install.
2. Supply by others, contractor install.
3. UoN supply – loose equipment and specialist equipment (chairs, drawer units,
non-fixed medical equipment).
4. NHS IT equipment (nil cost to the project).
5. Dental supply and install.
6. Pharmacy supply and install.
7. UoN IT support and install.
8. UoN supply and install (tacks and blinds; fire extinguishers; UoN signage.
9. UoN F.O.C.
Activity DataBase 01/03/2017
7857 Nottingham Uni Medical Centre7857Project:
Room Environmental Data J1155-01CADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: J1155-01C Waiting area: 20 places (including 2 wheelchair places)
Room Number: Revision Date: 01/03/2017
Permissible Space Temerature Range(dry bulb) (degC):
TEMPERATURE AND VENTILATION Requirements Notes
Heating Design Temperature (dry bulb)(degC):
Minimum Air Changes (AC/hr):
Ventilation Type:
Pressure Relative to Adjoining Space:
Supply Air: Final Filter Class
Permisiible Relative Humidity Range (%):
General Notes:
LIGHTINGType Of Control:
Daytime General Service Illuminance (Lux):
Daytime Specific Service Illuminance (Lux):
Nighttime General Service Illuminance (Lux):
Nighttime Specific Service Illuminance (Lux):
Local Task Illuminance (Lux):
Colour Rendering Required: N
Colour Rendering Required Characteristics (Ra):
Unified Glare Rating Limit (UGRL):
Emergency Escape Route Lighting Required: N
Standby Lighting Grade - General Lighting:
Standby Lighting Grade - Local Lighting:
General Notes:
RISKClinical Risk Category:
Non-clinical Business Continuity Risk Category:
General Notes:
Noise Intrusion (dB) 1hr day:
NOISE
Noise Intrusion (dB) 1hr night:
Noise Intrusion (dB) f night:
Maximum Internal Noise from M&E Services (NR):
Room Sound-insulation Parameters - Privacy:
Room Sound-insulation Parameters - Noise Generation:
Noise Sensitiviy:
Sound-insulation Rating (dB D nT,w):
General Notes:
Maximum Surface Temperature (DegC):
SAFETY/FIRE
Domestic Hot Water Discharge Temperature (DegC):
Maximum Cold Water Discharge Temperature (DegC):
General Notes:
Type of Automatic Fire Detection:
General Notes:
Activity DataBase 01/03/2017
ADB Room Design Character J1155-01C
Project: 7857 7857 Nottingham Uni Medical Centre
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Waiting area: 20 places (including 2 wheelchair places)J1155-01CRoom:
01/03/2017Revision Date:Room Number:
Walls:
Floor:
Ceiling:
Doorsets:
Windows:
Internal Glazing:
Hatch:
Notes:
Activity DataBase 01/03/2017
Schedule of Components by Room
Project: 7857 7857 Nottingham Uni Medical Centre
J1155-01CADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: J1155-01C Waiting area: 20 places (including 2 wheelchair places)
Room Number: Revision Date: 01/03/2017
Key: (n-old qty) Deletions m-new qty Additions m (n) Quantity changes since audit dateAudit Date: 2-Mar-2017
DescriptionCodeTotalTransNew
GrpAlt. CodeQuantity
1OUTLET, drinking water for equipmentOUT31511
3UNIT CHAIR, 2 seater, with arms, upholstered,
wipeable
CHA36822
3UNIT CHAIR, 3 seater, with arms, upholstered,
wipeable
CHA36922
Activity DataBase 01/03/2017
J1155-02Room Data SheetADB
Project: 7857 7857 Nottingham Uni Medical Centre
Department: PRI Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
Room: J1155-02 Sub-Wait 01 (based on Waiting area: 20 places (including 2 wheelchair
places))
Room Number: Revision Date: 01/03/2017
1) Patients, relatives and escorts wait to be seen.
2) Displaying information.
Activities:
Personnel: 20 x persons, including 2 x wheelchair user
Planning
Relationships:
Adjacent to reception area.
Close to clinical or work area.
Close to WC facilities.
Space Data: Height (mm): 30.00 2,700Area (m²):
Notes: Type of seating to be suitable for patient profile.
Method for calling patients into clinical rooms to be decided locally.
The following items may be provided:
- an enclosed noticeboard;
- background music and other entertainment facilities;
- television and internet access.
ADB Group Definitions:
1. Contractor supply and install.
2. Supply by others, contractor install.
3. UoN supply – loose equipment and specialist equipment (chairs, drawer units,
non-fixed medical equipment).
4. NHS IT equipment (nil cost to the project).
5. Dental supply and install.
6. Pharmacy supply and install.
7. UoN IT support and install.
8. UoN supply and install (tacks and blinds; fire extinguishers; UoN signage.
9. UoN F.O.C.
Activity DataBase 01/03/2017
7857 Nottingham Uni Medical Centre7857Project:
Room Environmental Data J1155-02ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: J1155-02 Sub-Wait 01 (based on Waiting area: 20 places (including 2 wheelchair
places))
Room Number: Revision Date: 01/03/2017
Permissible Space Temerature Range(dry bulb) (degC):
TEMPERATURE AND VENTILATION Requirements Notes
18 - 28
Heating Design Temperature (dry bulb)(degC): 21
Minimum Air Changes (AC/hr): 4
Ventilation Type: S/E/N
Bal or -vePressure Relative to Adjoining Space:
G4Supply Air: Final Filter Class
Permisiible Relative Humidity Range (%): Uncontrolled
General Notes:
LIGHTINGType Of Control: S/N
Daytime General Service Illuminance (Lux): 200
Daytime Specific Service Illuminance (Lux):
Nighttime General Service Illuminance (Lux):
Nighttime Specific Service Illuminance (Lux):
Local Task Illuminance (Lux):
Colour Rendering Required: Y
Colour Rendering Required Characteristics (Ra): 80
Unified Glare Rating Limit (UGRL): -
Emergency Escape Route Lighting Required: In accordance with BS 5266 and Health Technical
MemorandumsY
Standby Lighting Grade - General Lighting: B
Standby Lighting Grade - Local Lighting:
General Notes: Refer to SLL Lighting Guide 2 for more detailed guidance
RISKClinical Risk Category:
Non-clinical Business Continuity Risk Category:
General Notes:
Noise Intrusion (dB) 1hr day:
NOISE
Noise Intrusion (dB) 1hr night:
Noise Intrusion (dB) f night:
63
-
-
Maximum Internal Noise from M&E Services (NR): 63 Total noise of MEP services under normal operation across
the range 63Hz to 4kHz inclusive.
Room Sound-insulation Parameters - Privacy:
Room Sound-insulation Parameters - Noise Generation:
Not Private
Typical
Reference to Table 3 of the Department of Health 'Acoustics:
Technical design manual 4032:0.6:England'.
Noise Sensitiviy: Not Sensitive
Sound-insulation Rating (dB D nT,w):
General Notes:
Maximum Surface Temperature (DegC):
SAFETY/FIRE
43
Domestic Hot Water Discharge Temperature (DegC): 41
Maximum Cold Water Discharge Temperature (DegC): <20
General Notes:
Type of Automatic Fire Detection: Smoke
General Notes:
Activity DataBase 01/03/2017
ADB Room Design Character J1155-02
Project: 7857 7857 Nottingham Uni Medical Centre
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Sub-Wait 01 (based on Waiting area: 20 places (including 2 wheelchair
places))
J1155-02Room:
01/03/2017Revision Date:Room Number:
Walls: Wall finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Wall finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Floor: Floor finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Floor finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Ceiling: Ceiling finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Ceiling finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Doorsets: Not required - open to circulation area or part of another space
Windows: Non-essential - Project Option
Clear glass with solar control or Not applicable
Designation to be validated against current documentation (HTM 55 archived).
Internal Glazing: Not required
Hatch: Not required
Notes: All finishes selected must have an appropriate risk assessment to accompany the design
decision.
Infection Control must be consulted as described in Performance Requirements for Building
Elements Used in Healthcare Facilities 8941:0.6 England.
Activity DataBase 01/03/2017
Schedule of Components by Room
Project: 7857 7857 Nottingham Uni Medical Centre
J1155-02ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: J1155-02 Sub-Wait 01 (based on Waiting area: 20 places (including 2 wheelchair places))
Room Number: Revision Date: 01/03/2017
Key: (n-old qty) Deletions m-new qty Additions m (n) Quantity changes since audit dateAudit Date: 2-Mar-2017
DescriptionCodeTotalTransNew
GrpAlt. CodeQuantity
1BOARD, display/notice, wall mounted, 900H 1200WBOA01311
2RACK, leaflet, wall mounted, 915H 250W 105DRAC44011
2TELEVISION monitor, colour, flat panel, large, wall
mounted
TVM00311
3UNIT CHAIR, 1 seater, with arms, upholstered,
wipeable
CHA3671010
3TABLE, occasional, square, 415H 610W 610DTAB05322
8TRACK, blinds for windowsTRA90011
Activity DataBase 01/03/2017
J1155-03Room Data SheetADB
Project: 7857 7857 Nottingham Uni Medical Centre
Department: PRI Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
Room: J1155-03 Sub-Wait 02 (based on Waiting area: 20 places (including 2 wheelchair
places))
Room Number: Revision Date: 01/03/2017
1) Patients, relatives and escorts wait to be seen.
2) Displaying information.
Activities:
Personnel: 20 x persons, including 2 x wheelchair user
Planning
Relationships:
Adjacent to reception area.
Close to clinical or work area.
Close to WC facilities.
Space Data: Height (mm): 30.00 2,700Area (m²):
Notes: Type of seating to be suitable for patient profile.
Method for calling patients into clinical rooms to be decided locally.
The following items may be provided:
- an enclosed noticeboard;
- background music and other entertainment facilities;
- television and internet access.
ADB Group Definitions:
1. Contractor supply and install.
2. Supply by others, contractor install.
3. UoN supply – loose equipment and specialist equipment (chairs, drawer units,
non-fixed medical equipment).
4. NHS IT equipment (nil cost to the project).
5. Dental supply and install.
6. Pharmacy supply and install.
7. UoN IT support and install.
8. UoN supply and install (tacks and blinds; fire extinguishers; UoN signage.
9. UoN F.O.C.
Activity DataBase 01/03/2017
7857 Nottingham Uni Medical Centre7857Project:
Room Environmental Data J1155-03ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: J1155-03 Sub-Wait 02 (based on Waiting area: 20 places (including 2 wheelchair
places))
Room Number: Revision Date: 01/03/2017
Permissible Space Temerature Range(dry bulb) (degC):
TEMPERATURE AND VENTILATION Requirements Notes
18 - 28
Heating Design Temperature (dry bulb)(degC): 21
Minimum Air Changes (AC/hr): 4
Ventilation Type: S/E/N
Bal or -vePressure Relative to Adjoining Space:
G4Supply Air: Final Filter Class
Permisiible Relative Humidity Range (%): Uncontrolled
General Notes:
LIGHTINGType Of Control: S/N
Daytime General Service Illuminance (Lux): 200
Daytime Specific Service Illuminance (Lux):
Nighttime General Service Illuminance (Lux):
Nighttime Specific Service Illuminance (Lux):
Local Task Illuminance (Lux):
Colour Rendering Required: Y
Colour Rendering Required Characteristics (Ra): 80
Unified Glare Rating Limit (UGRL): -
Emergency Escape Route Lighting Required: In accordance with BS 5266 and Health Technical
MemorandumsY
Standby Lighting Grade - General Lighting: B
Standby Lighting Grade - Local Lighting:
General Notes: Refer to SLL Lighting Guide 2 for more detailed guidance
RISKClinical Risk Category:
Non-clinical Business Continuity Risk Category:
General Notes:
Noise Intrusion (dB) 1hr day:
NOISE
Noise Intrusion (dB) 1hr night:
Noise Intrusion (dB) f night:
63
-
-
Maximum Internal Noise from M&E Services (NR): 63 Total noise of MEP services under normal operation across
the range 63Hz to 4kHz inclusive.
Room Sound-insulation Parameters - Privacy:
Room Sound-insulation Parameters - Noise Generation:
Not Private
Typical
Reference to Table 3 of the Department of Health 'Acoustics:
Technical design manual 4032:0.6:England'.
Noise Sensitiviy: Not Sensitive
Sound-insulation Rating (dB D nT,w):
General Notes:
Maximum Surface Temperature (DegC):
SAFETY/FIRE
43
Domestic Hot Water Discharge Temperature (DegC): 41
Maximum Cold Water Discharge Temperature (DegC): <20
General Notes:
Type of Automatic Fire Detection: Smoke
General Notes:
Activity DataBase 01/03/2017
ADB Room Design Character J1155-03
Project: 7857 7857 Nottingham Uni Medical Centre
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Sub-Wait 02 (based on Waiting area: 20 places (including 2 wheelchair
places))
J1155-03Room:
01/03/2017Revision Date:Room Number:
Walls: Wall finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Wall finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Floor: Floor finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Floor finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Ceiling: Ceiling finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Ceiling finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Doorsets: Not required - open to circulation area or part of another space
Windows: Non-essential - Project Option
Clear glass with solar control or Not applicable
Designation to be validated against current documentation (HTM 55 archived).
Internal Glazing: Not required
Hatch: Not required
Notes: All finishes selected must have an appropriate risk assessment to accompany the design
decision.
Infection Control must be consulted as described in Performance Requirements for Building
Elements Used in Healthcare Facilities 8941:0.6 England.
Activity DataBase 01/03/2017
Schedule of Components by Room
Project: 7857 7857 Nottingham Uni Medical Centre
J1155-03ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: J1155-03 Sub-Wait 02 (based on Waiting area: 20 places (including 2 wheelchair places))
Room Number: Revision Date: 01/03/2017
Key: (n-old qty) Deletions m-new qty Additions m (n) Quantity changes since audit dateAudit Date: 2-Mar-2017
DescriptionCodeTotalTransNew
GrpAlt. CodeQuantity
1BOARD, display/notice, wall mounted, 900H 1200WBOA01311
1OUTLET cable, 13 ampOUT00211
2RACK, leaflet, wall mounted, 915H 250W 105DRAC44011
2TELEVISION monitor, colour, flat panel, large, wall
mounted
TVM00311
3CHAIR, upright, with arms, upholstered, stacking,
wipeable
CHA31844
3UNIT CHAIR, 1 seater, with arms, upholstered,
wipeable
CHA3671010
3DRAWER UNIT, 3 drawer, lockable, on castors, desk
height 715H 430W 600D
DRA05722
3TABLE, circular, 760H 1100mm dia.TAB03011
3TABLE, occasional, square, 415H 610W 610DTAB05322
8TRACK, blinds for windowsTRA90011
9DISPENSER, cooler, drinking water, (fountain),
(capacity 63.3 l/hr), floor standing
DIS00211
9DISPENSER, disposable cup, wall mountedDIS01211
Activity DataBase 01/03/2017
J1155-04Room Data SheetADB
Project: 7857 7857 Nottingham Uni Medical Centre
Department: PRI Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
Room: J1155-04 Sub-Wait 03 (based on Waiting area: 20 places (including 2 wheelchair
places))
Room Number: Revision Date: 01/03/2017
1) Patients, relatives and escorts wait to be seen.
2) Displaying information.
Activities:
Personnel: 20 x persons, including 2 x wheelchair user
Planning
Relationships:
Adjacent to reception area.
Close to clinical or work area.
Close to WC facilities.
Space Data: Height (mm): 30.00 2,700Area (m²):
Notes: Type of seating to be suitable for patient profile.
Method for calling patients into clinical rooms to be decided locally.
The following items may be provided:
- an enclosed noticeboard;
- background music and other entertainment facilities;
- television and internet access.
ADB Group Definitions:
1. Contractor supply and install.
2. Supply by others, contractor install.
3. UoN supply – loose equipment and specialist equipment (chairs, drawer units,
non-fixed medical equipment).
4. NHS IT equipment (nil cost to the project).
5. Dental supply and install.
6. Pharmacy supply and install.
7. UoN IT support and install.
8. UoN supply and install (tacks and blinds; fire extinguishers; UoN signage.
9. UoN F.O.C.
Activity DataBase 01/03/2017
7857 Nottingham Uni Medical Centre7857Project:
Room Environmental Data J1155-04ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: J1155-04 Sub-Wait 03 (based on Waiting area: 20 places (including 2 wheelchair
places))
Room Number: Revision Date: 01/03/2017
Permissible Space Temerature Range(dry bulb) (degC):
TEMPERATURE AND VENTILATION Requirements Notes
18 - 28
Heating Design Temperature (dry bulb)(degC): 21
Minimum Air Changes (AC/hr): 4
Ventilation Type: S/E/N
Bal or -vePressure Relative to Adjoining Space:
G4Supply Air: Final Filter Class
Permisiible Relative Humidity Range (%): Uncontrolled
General Notes:
LIGHTINGType Of Control: S/N
Daytime General Service Illuminance (Lux): 200
Daytime Specific Service Illuminance (Lux):
Nighttime General Service Illuminance (Lux):
Nighttime Specific Service Illuminance (Lux):
Local Task Illuminance (Lux):
Colour Rendering Required: Y
Colour Rendering Required Characteristics (Ra): 80
Unified Glare Rating Limit (UGRL): -
Emergency Escape Route Lighting Required: In accordance with BS 5266 and Health Technical
MemorandumsY
Standby Lighting Grade - General Lighting: B
Standby Lighting Grade - Local Lighting:
General Notes: Refer to SLL Lighting Guide 2 for more detailed guidance
RISKClinical Risk Category:
Non-clinical Business Continuity Risk Category:
General Notes:
Noise Intrusion (dB) 1hr day:
NOISE
Noise Intrusion (dB) 1hr night:
Noise Intrusion (dB) f night:
63
-
-
Maximum Internal Noise from M&E Services (NR): 63 Total noise of MEP services under normal operation across
the range 63Hz to 4kHz inclusive.
Room Sound-insulation Parameters - Privacy:
Room Sound-insulation Parameters - Noise Generation:
Not Private
Typical
Reference to Table 3 of the Department of Health 'Acoustics:
Technical design manual 4032:0.6:England'.
Noise Sensitiviy: Not Sensitive
Sound-insulation Rating (dB D nT,w):
General Notes:
Maximum Surface Temperature (DegC):
SAFETY/FIRE
43
Domestic Hot Water Discharge Temperature (DegC): 41
Maximum Cold Water Discharge Temperature (DegC): <20
General Notes:
Type of Automatic Fire Detection: Smoke
General Notes:
Activity DataBase 01/03/2017
ADB Room Design Character J1155-04
Project: 7857 7857 Nottingham Uni Medical Centre
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Sub-Wait 03 (based on Waiting area: 20 places (including 2 wheelchair
places))
J1155-04Room:
01/03/2017Revision Date:Room Number:
Walls: Wall finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Wall finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Floor: Floor finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Floor finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Ceiling: Ceiling finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Ceiling finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Doorsets: Not required - open to circulation area or part of another space
Windows: Non-essential - Project Option
Clear glass with solar control or Not applicable
Designation to be validated against current documentation (HTM 55 archived).
Internal Glazing: Not required
Hatch: Not required
Notes: All finishes selected must have an appropriate risk assessment to accompany the design
decision.
Infection Control must be consulted as described in Performance Requirements for Building
Elements Used in Healthcare Facilities 8941:0.6 England.
Activity DataBase 01/03/2017
Schedule of Components by Room
Project: 7857 7857 Nottingham Uni Medical Centre
J1155-04ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: J1155-04 Sub-Wait 03 (based on Waiting area: 20 places (including 2 wheelchair places))
Room Number: Revision Date: 01/03/2017
Key: (n-old qty) Deletions m-new qty Additions m (n) Quantity changes since audit dateAudit Date: 2-Mar-2017
DescriptionCodeTotalTransNew
GrpAlt. CodeQuantity
1BOARD, display/notice, wall mounted, 900H 1200WBOA01322
1SOCKET outlet, switched, 13 amp, twinOUT01011
3UNIT CHAIR, 1 seater, with arms, upholstered,
wipeable
CHA36744
Activity DataBase 01/03/2017
J1155-05Room Data SheetADB
Project: 7857 7857 Nottingham Uni Medical Centre
Department: PRI Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
Room: J1155-05 First Floor Sub Wait (based on Waiting area: 20 places (including 2
wheelchair places))
Room Number: Revision Date: 01/03/2017
1) Patients, relatives and escorts wait to be seen.
2) Displaying information.
Activities:
Personnel: 20 x persons, including 2 x wheelchair user
Planning
Relationships:
Space Data: Height (mm): 42.80 2,700Area (m²):
Notes: Type of seating to be suitable for patient profile.
Method for calling patients into clinical rooms to be decided locally.
The following items may be provided:
- an enclosed noticeboard;
- background music and other entertainment facilities;
- television and internet access.
ADB Group Definitions:
1. Contractor supply and install.
2. Supply by others, contractor install.
3. UoN supply – loose equipment and specialist equipment (chairs, drawer units,
non-fixed medical equipment).
4. NHS IT equipment (nil cost to the project).
5. Dental supply and install.
6. Pharmacy supply and install.
7. UoN IT support and install.
8. UoN supply and install (tacks and blinds; fire extinguishers; UoN signage.
9. UoN F.O.C.
Activity DataBase 01/03/2017
7857 Nottingham Uni Medical Centre7857Project:
Room Environmental Data J1155-05ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: J1155-05 First Floor Sub Wait (based on Waiting area: 20 places (including 2
wheelchair places))
Room Number: Revision Date: 01/03/2017
Permissible Space Temerature Range(dry bulb) (degC):
TEMPERATURE AND VENTILATION Requirements Notes
18 - 28
Heating Design Temperature (dry bulb)(degC): 21
Minimum Air Changes (AC/hr): 4
Ventilation Type: S/E/N
Bal or -vePressure Relative to Adjoining Space:
G4Supply Air: Final Filter Class
Permisiible Relative Humidity Range (%): Uncontrolled
General Notes:
LIGHTINGType Of Control: S/N
Daytime General Service Illuminance (Lux): 200
Daytime Specific Service Illuminance (Lux):
Nighttime General Service Illuminance (Lux):
Nighttime Specific Service Illuminance (Lux):
Local Task Illuminance (Lux):
Colour Rendering Required: Y
Colour Rendering Required Characteristics (Ra): 80
Unified Glare Rating Limit (UGRL): -
Emergency Escape Route Lighting Required: In accordance with BS 5266 and Health Technical
MemorandumsY
Standby Lighting Grade - General Lighting: B
Standby Lighting Grade - Local Lighting:
General Notes: Refer to SLL Lighting Guide 2 for more detailed guidance
RISKClinical Risk Category:
Non-clinical Business Continuity Risk Category:
General Notes:
Noise Intrusion (dB) 1hr day:
NOISE
Noise Intrusion (dB) 1hr night:
Noise Intrusion (dB) f night:
63
-
-
Maximum Internal Noise from M&E Services (NR): 63 Total noise of MEP services under normal operation across
the range 63Hz to 4kHz inclusive.
Room Sound-insulation Parameters - Privacy:
Room Sound-insulation Parameters - Noise Generation:
Not Private
Typical
Reference to Table 3 of the Department of Health
'Acoustics: Technical design manual
4032:0.6:England'.
Noise Sensitiviy: Not Sensitive
Sound-insulation Rating (dB D nT,w):
General Notes:
Maximum Surface Temperature (DegC):
SAFETY/FIRE
43
Domestic Hot Water Discharge Temperature (DegC): 41
Maximum Cold Water Discharge Temperature (DegC): <20
General Notes:
Type of Automatic Fire Detection: Smoke
General Notes:
Activity DataBase 01/03/2017
ADB Room Design Character J1155-05
Project: 7857 7857 Nottingham Uni Medical Centre
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
First Floor Sub Wait (based on Waiting area: 20 places (including 2
wheelchair places))
J1155-05Room:
01/03/2017Revision Date:Room Number:
Walls: Wall finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Wall finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Floor: Floor finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Floor finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Ceiling: Ceiling finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Ceiling finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Doorsets: Not required - open to circulation area or part of another space
Windows: Non-essential - Project Option
Clear glass with solar control or Not applicable
Designation to be validated against current documentation (HTM 55 archived).
Internal Glazing: Not required
Hatch: Not required
Notes: All finishes selected must have an appropriate risk assessment to accompany the design
decision.
Infection Control must be consulted as described in Performance Requirements for Building
Elements Used in Healthcare Facilities 8941:0.6 England.
Activity DataBase 01/03/2017
Schedule of Components by Room
Project: 7857 7857 Nottingham Uni Medical Centre
J1155-05ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: J1155-05 First Floor Sub Wait (based on Waiting area: 20 places (including 2 wheelchair
places))
Room Number: Revision Date: 01/03/2017
Key: (n-old qty) Deletions m-new qty Additions m (n) Quantity changes since audit dateAudit Date: 2-Mar-2017
DescriptionCodeTotalTransNew
GrpAlt. CodeQuantity
1SOCKET outlet, switched, 13 amp, singleOUT00511
1SOCKET outlet, switched, 13 amp, twinOUT01033
1SWITCH, lightSWC02511
2TELEVISION monitor, colour, flat panel, large, wall
mounted
TVM00311
3UNIT CHAIR, 1 seater, with arms, upholstered,
wipeable
CHA36788
3UNIT CHAIR, 2 seater, with arms, upholstered,
wipeable
CHA36855
3RACK, leaflet/pamphlet, 4 sections, with adjustable
dividers, wall mounted, 300H 805W 215D
RAC08911
3RACK, magazine, 3 shelves, floor standing, fixed to
the wall, 1400H 900W 300D
RAC09111
3TABLE, occasional, square, 415H 610W 610DTAB05344
9DISPENSER, cooler, drinking water, (fountain),
(capacity 63.3 l/hr), floor standing
DIS00211
Activity DataBase 01/03/2017
J1155-06Room Data SheetADB
Project: 7857 7857 Nottingham Uni Medical Centre
Department: PRI Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
Room: J1155-06 Dental Waiting Area (based on Waiting area: 20 places (including 2
wheelchair places))
Room Number: Revision Date: 01/03/2017
1) Patients, relatives and escorts wait to be seen.
2) Displaying information.
Activities:
Personnel: 20 x persons, including 2 x wheelchair user
Planning
Relationships:
Adjacent to reception area.
Close to clinical or work area.
Close to WC facilities.
Space Data: Height (mm): 30.00 2,700Area (m²):
Notes: Type of seating to be suitable for patient profile.
Method for calling patients into clinical rooms to be decided locally.
The following items may be provided:
- an enclosed noticeboard;
- background music and other entertainment facilities;
- television and internet access.
ADB Group Definitions:
1. Contractor supply and install.
2. Supply by others, contractor install.
3. UoN supply – loose equipment and specialist equipment (chairs, drawer units,
non-fixed medical equipment).
4. NHS IT equipment (nil cost to the project).
5. Dental supply and install.
6. Pharmacy supply and install.
7. UoN IT support and install.
8. UoN supply and install (tacks and blinds; fire extinguishers; UoN signage.
9. UoN F.O.C.
Activity DataBase 01/03/2017
7857 Nottingham Uni Medical Centre7857Project:
Room Environmental Data J1155-06ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: J1155-06 Dental Waiting Area (based on Waiting area: 20 places (including 2
wheelchair places))
Room Number: Revision Date: 01/03/2017
Permissible Space Temerature Range(dry bulb) (degC):
TEMPERATURE AND VENTILATION Requirements Notes
18 - 28
Heating Design Temperature (dry bulb)(degC): 21
Minimum Air Changes (AC/hr): 4
Ventilation Type: S/E/N
Bal or -vePressure Relative to Adjoining Space:
G4Supply Air: Final Filter Class
Permisiible Relative Humidity Range (%): Uncontrolled
General Notes:
LIGHTINGType Of Control: S/N
Daytime General Service Illuminance (Lux): 200
Daytime Specific Service Illuminance (Lux):
Nighttime General Service Illuminance (Lux):
Nighttime Specific Service Illuminance (Lux):
Local Task Illuminance (Lux):
Colour Rendering Required: Y
Colour Rendering Required Characteristics (Ra): 80
Unified Glare Rating Limit (UGRL): -
Emergency Escape Route Lighting Required: In accordance with BS 5266 and Health Technical
MemorandumsY
Standby Lighting Grade - General Lighting: B
Standby Lighting Grade - Local Lighting:
General Notes: Refer to SLL Lighting Guide 2 for more detailed guidance
RISKClinical Risk Category:
Non-clinical Business Continuity Risk Category:
General Notes:
Noise Intrusion (dB) 1hr day:
NOISE
Noise Intrusion (dB) 1hr night:
Noise Intrusion (dB) f night:
63
-
-
Maximum Internal Noise from M&E Services (NR): 63 Total noise of MEP services under normal operation across
the range 63Hz to 4kHz inclusive.
Room Sound-insulation Parameters - Privacy:
Room Sound-insulation Parameters - Noise Generation:
Not Private
Typical
Reference to Table 3 of the Department of Health 'Acoustics:
Technical design manual 4032:0.6:England'.
Noise Sensitiviy: Not Sensitive
Sound-insulation Rating (dB D nT,w):
General Notes:
Maximum Surface Temperature (DegC):
SAFETY/FIRE
43
Domestic Hot Water Discharge Temperature (DegC): 41
Maximum Cold Water Discharge Temperature (DegC): <20
General Notes:
Type of Automatic Fire Detection: Smoke
General Notes:
Activity DataBase 01/03/2017
ADB Room Design Character J1155-06
Project: 7857 7857 Nottingham Uni Medical Centre
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Dental Waiting Area (based on Waiting area: 20 places (including 2
wheelchair places))
J1155-06Room:
01/03/2017Revision Date:Room Number:
Walls: Wall finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Wall finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Floor: Floor finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Floor finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Ceiling: Ceiling finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Ceiling finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Doorsets: Not required - open to circulation area or part of another space
Windows: Non-essential - Project Option
Clear glass with solar control or Not applicable
Designation to be validated against current documentation (HTM 55 archived).
Internal Glazing: Not required
Hatch: Not required
Notes: All finishes selected must have an appropriate risk assessment to accompany the design
decision.
Infection Control must be consulted as described in Performance Requirements for Building
Elements Used in Healthcare Facilities 8941:0.6 England.
Activity DataBase 01/03/2017
Schedule of Components by Room
Project: 7857 7857 Nottingham Uni Medical Centre
J1155-06ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: J1155-06 Dental Waiting Area (based on Waiting area: 20 places (including 2 wheelchair
places))
Room Number: Revision Date: 01/03/2017
Key: (n-old qty) Deletions m-new qty Additions m (n) Quantity changes since audit dateAudit Date: 2-Mar-2017
DescriptionCodeTotalTransNew
GrpAlt. CodeQuantity
1SOCKET outlet, switched, 13 amp, singleOUT00511
1SOCKET outlet, switched, 13 amp, twinOUT01022
1SWITCH, lightSWC02511
5UNIT CHAIR, 1 seater, with arms, upholstered,
wipeable
CHA46733
5UNIT CHAIR, 3 seater, with arms, upholstered,
wipeable
CHA4691010
5RACK, leaflet/pamphlet, 4 sections, with adjustable
dividers, wall mounted, 300H 805W 215D
RAC18911
5RACK, magazine, 3 shelves, floor standing, fixed to
the wall, 1400H 900W 300D
RAC29111
Activity DataBase 01/03/2017
J1414Room Data SheetADB
Project: 7857 7857 Nottingham Uni Medical Centre
Department: PRI Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
Room: J1414 Play area: 3 children
Room Number: Revision Date: 01/03/2017
1) Children accompanying relatives or waiting to be seen are able to play.
2) Toys, books and games are stored.
Activities:
Personnel: 3 x children
Planning
Relationships:
Off, and observable from, the waiting area.
Space Data: Height (mm): 4.50 2,400Area (m²):
2400 is the anticipated minimum ceiling height. Should be sized to suit surrounding
area/design.
Notes: ADB Group Definitions:
1. Contractor supply and install.
2. Supply by others, contractor install.
3. UoN supply – loose equipment and specialist equipment (chairs, drawer units,
non-fixed medical equipment).
4. NHS IT equipment (nil cost to the project).
5. Dental supply and install.
6. Pharmacy supply and install.
7. UoN IT support and install.
8. UoN supply and install (tacks and blinds; fire extinguishers; UoN signage.
9. UoN F.O.C.
Activity DataBase 01/03/2017
7857 Nottingham Uni Medical Centre7857Project:
Room Environmental Data J1414ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: J1414 Play area: 3 children
Room Number: Revision Date: 01/03/2017
Permissible Space Temerature Range(dry bulb) (degC):
TEMPERATURE AND VENTILATION Requirements Notes
18 - 28
Heating Design Temperature (dry bulb)(degC): 21
Minimum Air Changes (AC/hr): 4
Ventilation Type: S/E/N
Bal or -vePressure Relative to Adjoining Space:
G4Supply Air: Final Filter Class
Permisiible Relative Humidity Range (%): Uncontrolled
General Notes:
LIGHTINGType Of Control: N/EM
Daytime General Service Illuminance (Lux): 300
Daytime Specific Service Illuminance (Lux):
Nighttime General Service Illuminance (Lux):
Nighttime Specific Service Illuminance (Lux):
Local Task Illuminance (Lux):
Colour Rendering Required: Y
Colour Rendering Required Characteristics (Ra): 80
Unified Glare Rating Limit (UGRL): 22
Emergency Escape Route Lighting Required: In accordance with BS 5266 and Health Technical
MemorandumsY
Standby Lighting Grade - General Lighting: B
Standby Lighting Grade - Local Lighting:
General Notes: Refer to SLL Lighting Guide 2 for more detailed guidance
RISKClinical Risk Category:
Non-clinical Business Continuity Risk Category:
General Notes:
Noise Intrusion (dB) 1hr day:
NOISE
Noise Intrusion (dB) 1hr night:
Noise Intrusion (dB) f night:
68
-
-
Maximum Internal Noise from M&E Services (NR): 68 Total noise of MEP services under normal operation across
the range 63Hz to 4kHz inclusive.
Room Sound-insulation Parameters - Privacy:
Room Sound-insulation Parameters - Noise Generation:
Not Private
Typical
Reference to Table 3 of the Department of Health 'Acoustics:
Technical design manual 4032:0.6:England'.
Noise Sensitiviy: Not Sensitive
Sound-insulation Rating (dB D nT,w):
General Notes:
Maximum Surface Temperature (DegC):
SAFETY/FIRE
43
Domestic Hot Water Discharge Temperature (DegC): 41
Maximum Cold Water Discharge Temperature (DegC): <20
General Notes:
Type of Automatic Fire Detection: Smoke
General Notes:
Activity DataBase 01/03/2017
ADB Room Design Character J1414
Project: 7857 7857 Nottingham Uni Medical Centre
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Play area: 3 childrenJ1414Room:
01/03/2017Revision Date:Room Number:
Walls: Wall finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Wall finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Floor: Floor finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Floor finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Ceiling: Ceiling finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Ceiling finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Doorsets: Not required - open to circulation area or part of another space
Windows: Non-essential - Project Option
Clear glass with solar control. Window opening restrictors max 100mm at bottom
Designation to be validated against current documentation (HTM 55 archived).
Internal Glazing: Desirable - Project Option
Clear safety glass when provided
Designation to be validated against current documentation. HTM 57 (Mar-2005)
Hatch: Not required
Notes: All finishes selected must have an appropriate risk assessment to accompany the design
decision.
Infection Control must be consulted as described in Performance Requirements for Building
Elements Used in Healthcare Facilities 8941:0.6 England.
Activity DataBase 01/03/2017
Schedule of Components by Room
Project: 7857 7857 Nottingham Uni Medical Centre
J1414ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: J1414 Play area: 3 children
Room Number: Revision Date: 01/03/2017
Key: (n-old qty) Deletions m-new qty Additions m (n) Quantity changes since audit dateAudit Date: 2-Mar-2017
DescriptionCodeTotalTransNew
GrpAlt. CodeQuantity
Activity DataBase 01/03/2017
L1308Room Data SheetADB
Project: 7857 7857 Nottingham Uni Medical Centre
Department: PRI Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
Room: L1308 Near patient testing room
Room Number: Revision Date: 01/03/2017
1) Electronic patient records (EPRs) may be accessed and updated.
2) Clinical wash-hand basin may be used.
3) Patient records may be reviewed and recorded.
4) Performing electrolyte analysis.
5) Performing blood gas analysis.
6) Performing glucose analysis.
7) Computer workstation(s) may be used.
8) Displaying information.
9) Printer may be used.
Activities:
Personnel: 2 x staff.
Intermittent use.
Planning
Relationships:
This room is based on the use of an outward opening entrance door, where an entrance door
is not provided, the entrance must be within a secure staff area.
Space Data: Height (mm): 8.00 2,700Area (m²):
Notes: Type of analyser provided to suit range of tests to be undertaken .
The following items are shown on the room layout but are optional:
- door to room;
- a specimen fridge;
- a sink and demineralised water supply.
The following items may be provided:
- a pneumatic tube to/from pathology.
.
Separate data and voice outlets may be used where structure cabling solutions are not
available.
ADB Group Definitions:
1. Contractor supply and install.
2. Supply by others, contractor install.
3. UoN supply – loose equipment and specialist equipment (chairs, drawer units,
non-fixed medical equipment).
4. NHS IT equipment (nil cost to the project).
5. Dental supply and install.
6. Pharmacy supply and install.
7. UoN IT support and install.
8. UoN supply and install (tacks and blinds; fire extinguishers; UoN signage.
9. UoN F.O.C.
Activity DataBase 01/03/2017
7857 Nottingham Uni Medical Centre7857Project:
Room Environmental Data L1308ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: L1308 Near patient testing room
Room Number: Revision Date: 01/03/2017
Permissible Space Temerature Range(dry bulb) (degC):
TEMPERATURE AND VENTILATION Requirements Notes
18 - 28
Heating Design Temperature (dry bulb)(degC): 21
Minimum Air Changes (AC/hr): 6
Ventilation Type: S/E
Bal or -vePressure Relative to Adjoining Space:
F7Supply Air: Final Filter Class
Permisiible Relative Humidity Range (%): Uncontrolled
General Notes:
LIGHTINGType Of Control: S/N
Daytime General Service Illuminance (Lux): 300
Daytime Specific Service Illuminance (Lux):
Nighttime General Service Illuminance (Lux):
Nighttime Specific Service Illuminance (Lux):
Local Task Illuminance (Lux):
Colour Rendering Required: Y
Colour Rendering Required Characteristics (Ra): 90
Unified Glare Rating Limit (UGRL): 19
Emergency Escape Route Lighting Required: In accordance with BS 5266 and Health Technical
MemorandumsY
Standby Lighting Grade - General Lighting: B
Standby Lighting Grade - Local Lighting:
General Notes:
RISKClinical Risk Category:
Non-clinical Business Continuity Risk Category:
General Notes:
Noise Intrusion (dB) 1hr day:
NOISE
Noise Intrusion (dB) 1hr night:
Noise Intrusion (dB) f night:
40
-
-
Maximum Internal Noise from M&E Services (NR): 35 Total noise of MEP services under normal operation across
the range 63Hz to 4kHz inclusive.
Room Sound-insulation Parameters - Privacy:
Room Sound-insulation Parameters - Noise Generation:
Confidential
Typical
Reference to Table 3 of the Department of Health 'Acoustics:
Technical design manual 4032:0.6:England'.
Noise Sensitiviy: Medium
Sound-insulation Rating (dB D nT,w):
General Notes:
Maximum Surface Temperature (DegC):
SAFETY/FIRE
43
Domestic Hot Water Discharge Temperature (DegC): 41
Maximum Cold Water Discharge Temperature (DegC): <20
General Notes:
Type of Automatic Fire Detection: Smoke
General Notes:
Activity DataBase 01/03/2017
ADB Room Design Character L1308
Project: 7857 7857 Nottingham Uni Medical Centre
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Near patient testing roomL1308Room:
01/03/2017Revision Date:Room Number:
Walls: Wall finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Wall finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Floor: Floor finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Floor finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Ceiling: Ceiling finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Ceiling finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Doorsets: Configuration, glazing, fire rating, security, etc. to be determined by Project Team.
HTM 58 (Mar-2005)
Refer to HBN 00-04 (May-2007) for effective clear door widths.
Not applicable or 1 doorset:
1 x personnel & equipment access (1000mm)
Windows: Not required
Internal Glazing: Not required
Hatch: Not required
Notes: All finishes selected must have an appropriate risk assessment to accompany the design
decision.
Infection Control must be consulted as described in Performance Requirements for Building
Elements Used in Healthcare Facilities 8941:0.6 England.
Activity DataBase 01/03/2017
Schedule of Components by Room
Project: 7857 7857 Nottingham Uni Medical Centre
L1308ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: L1308 Near patient testing room
Room Number: Revision Date: 01/03/2017
Key: (n-old qty) Deletions m-new qty Additions m (n) Quantity changes since audit dateAudit Date: 2-Mar-2017
DescriptionCodeTotalTransNew
GrpAlt. CodeQuantity
1BASIN, medium, hospital pattern, vitreous china, no
tap holes, no overflow, integral back outlet, 500W
400D.
BAS10111
1BOARD, display/notice, wall mounted, 900H 600WBOA01211
1HOOK, single, small, wall mountedHOO01911
1WORKBENCH laboratory, C-frame, freestanding,
920H 2000W 750D.
LWB08011
1WORKTOP, with right hand sink bowl (sink size
200x450x365), 920H 3000W 750D.
LWS19011
1OUTLET cable, 13 ampOUT00222
1SOCKET outlet, switched, 13 amp, singleOUT00511
1SOCKET outlet, switched, 13 amp, twinOUT01044
1CONNECTION UNIT, switched, 13 amp, flex outletOUT04911
1CONNECTION UNIT, switched, 13 ampOUT05211
1SOCKET outlet data/voice, double.OUT13144
1CABINET, upper, modular storage, for 400 facing
inserts, with door, 750H
SMC02322
1SWITCH, lightSWC02511
1TAP, laboratory, cold waterTAP02211
1TAP, laboratory, hot waterTAP02311
1TAP, bib, 2x8 mm thermostatic mixer, automatic
action, sensor operated, non-touch,
TAP89211
1WASTE, unslotted recessed grated, metal, 1.1/2 in,
with plug and chain
WAS10311
1TRAP, bottle, 1.1/4 in, plastic resealing.WAS10711
1TRAP, bottle, 1.1/2 in, plastic resealing.WAS10811
2DISPENSER, barrier cream, disposable single
cartridge, wall mounted
DIS01111
2DISPENSER, paper towel, wall mountedDIS01322
2DISPENSER, soap, wall mountedDIS02411
2DISPENSER, soap, disposable single cartridge, lever
action, wall mounted
DIS03011
3CHAIR, swivel, height adjustable 540-790, tilting
back, adjustable footrest, wipeable, 5 star base, on
castors/glides
CHA30311
3HOLDER, sack, with lid foot operated, medium,
freestanding, 875H 430W 385D
HOL00611
4COMPUTER KEYBOARDCOM03311
4COMPUTER MONITOR, 17"; TFT, digital flat panel
display, high-resolution screens, desk top
COM04911
8TRACK, blinds for windowsTRA90011
Activity DataBase 01/03/2017
M0251-001Room Data SheetADB
Project: 7857 7857 Nottingham Uni Medical Centre
Department: PRI Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
Room: M0251-001 Office: 1 person
Room Number: Revision Date: 01/03/2017
1) Clinical administration.
2) Computer workstation(s) may be used.
3) Telephone(s) may be used.
4) Discussions and interviews may take place.
5) Files and records are stored.
6) Hanging outdoor clothing.
7) Secure holding/storing of clothing and personal belongings.
8) Printer may be used.
9) Electronic patient records (EPRs) may be accessed and updated.
10) Staff notices, information and/or messages may be displayed.
11) Dealing with enquiries.
12) Information on computers may be accessed.
Activities:
Personnel: 1 x staff
Up to x 2 others.
Planning
Relationships:
Space Data: Height (mm): 8.00 2,400Area (m²):
Activity DataBase 01/03/2017
Notes: The following equipment is shown on the room layout but is optional:
- call repeat lamps for controlled drugs cupboards (but required if the office is used for
clinical control).
The following items may provided;
- shelving;
- printer.
The following items may be provided if the office is used for clinical control :
- a small safe;
- a key cupboard;
- an alarm panel, see HTM 08-03;
- a dimming switch - recommended if the room is used for viewing digital images.
.
Separate data and voice outlets may be used where structure cabling solutions are not
available.
ADB Group Definitions:
1. Contractor supply and install.
2. Supply by others, contractor install.
3. UoN supply – loose equipment and specialist equipment (chairs, drawer units,
non-fixed medical equipment).
4. NHS IT equipment (nil cost to the project).
5. Dental supply and install.
6. Pharmacy supply and install.
7. UoN IT support and install.
8. UoN supply and install (tacks and blinds; fire extinguishers; UoN signage.
9. UoN F.O.C.
Activity DataBase 01/03/2017
7857 Nottingham Uni Medical Centre7857Project:
Room Environmental Data M0251-001ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: M0251-001 Office: 1 person
Room Number: Revision Date: 01/03/2017
Permissible Space Temerature Range(dry bulb) (degC):
TEMPERATURE AND VENTILATION Requirements Notes
18 - 28
Heating Design Temperature (dry bulb)(degC): 21
Minimum Air Changes (AC/hr): 4
Ventilation Type: S/E/N
Bal or -vePressure Relative to Adjoining Space:
G4Supply Air: Final Filter Class
Permisiible Relative Humidity Range (%):
General Notes:
LIGHTINGType Of Control: S/N
Daytime General Service Illuminance (Lux): 300 Over workstations
Daytime Specific Service Illuminance (Lux):
Nighttime General Service Illuminance (Lux):
Nighttime Specific Service Illuminance (Lux):
Local Task Illuminance (Lux):
Colour Rendering Required: Y
Colour Rendering Required Characteristics (Ra): 80
Unified Glare Rating Limit (UGRL): 19
Emergency Escape Route Lighting Required: In accordance with BS 5266 and Health Technical
MemorandumsY
Standby Lighting Grade - General Lighting: B
Standby Lighting Grade - Local Lighting:
General Notes: Refer to CIBSE Lighting Guide LG3 for areas with VDT’s
RISKClinical Risk Category:
Non-clinical Business Continuity Risk Category:
General Notes:
Noise Intrusion (dB) 1hr day:
NOISE
Noise Intrusion (dB) 1hr night:
Noise Intrusion (dB) f night:
40
-
-
Maximum Internal Noise from M&E Services (NR): 35 Total noise of MEP services under normal operation across
the range 63Hz to 4kHz inclusive.
Room Sound-insulation Parameters - Privacy:
Room Sound-insulation Parameters - Noise Generation:
Private
Typical
Reference to Table 3 of the Department of Health 'Acoustics:
Technical design manual 4032:0.6:England'.
Noise Sensitiviy: Medium
Sound-insulation Rating (dB D nT,w):
General Notes:
Maximum Surface Temperature (DegC):
SAFETY/FIRE
82
Domestic Hot Water Discharge Temperature (DegC): 60
Maximum Cold Water Discharge Temperature (DegC): <20
General Notes:
Type of Automatic Fire Detection: Smoke
General Notes:
Activity DataBase 01/03/2017
ADB Room Design Character M0251-001
Project: 7857 7857 Nottingham Uni Medical Centre
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Office: 1 personM0251-001Room:
01/03/2017Revision Date:Room Number:
Walls: Wall finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Wall finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Floor: Floor finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Floor finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Ceiling: Ceiling finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Ceiling finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Doorsets: Configuration, glazing, fire rating, security, etc. to be determined by Project Team.
HTM 58 (Mar-2005)
Refer to HBN 00-04 (May-2007) for effective clear door widths.
1 doorset:
1 x personnel, wheelchair & equipment access (1000mm)
Windows: Desirable - Project Option
Clear glass with solar and privacy control
Designation to be validated against current documentation (HTM 55 archived).
Internal Glazing: Non-essential - Project Option
Designation to be validated against current documentation. HTM 57 (Mar-2005)
Hatch: Not required
Notes: All finishes selected must have an appropriate risk assessment to accompany the design
decision.
Infection Control must be consulted as described in Performance Requirements for Building
Elements Used in Healthcare Facilities 8941:0.6 England.
Activity DataBase 01/03/2017
Schedule of Components by Room
Project: 7857 7857 Nottingham Uni Medical Centre
M0251-001ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: M0251-001 Office: 1 person
Room Number: Revision Date: 01/03/2017
Key: (n-old qty) Deletions m-new qty Additions m (n) Quantity changes since audit dateAudit Date: 2-Mar-2017
DescriptionCodeTotalTransNew
GrpAlt. CodeQuantity
1BOARD, display/notice, wall mounted, 900H 1200WBOA01311
1DESK UNIT, cantilever, cable management,
adjustable legs, modesty panel, 1400W 700D
DES02611
1HOOK, single, small, wall mountedHOO01933
1SOCKET outlet, switched, 13 amp, singleOUT00511
1SOCKET outlet, switched, 13 amp, twinOUT01033
1SOCKET outlet data/voice, double.OUT13133
1SWITCH, lightSWC02511
3CABINET, lateral filing, 6 rails, 2 door, 1970H 1000W
470D
CAB04911
3CHAIR, swivel, height adjustable, high back, with
arms, wipeable, 5 star base, on castors
CHA30111
3CHAIR, upright, with arms, upholstered, stacking,
wipeable
CHA31844
3DRAWER UNIT, 2 drawer, lockable, on castors,
600H 410W 600D
DRA05611
3DRAWER UNIT, 3 drawer, lockable, on castors, desk
height 715H 430W 600D
DRA05711
3TABLE, circular, 760H 1100mm dia.TAB03011
4COMPUTER KEYBOARDCOM03311
4COMPUTER MONITOR, 17"; TFT, digital flat panel
display, high-resolution screens, desk top
COM04922
8TRACK, blinds for windowsTRA90011
Activity DataBase 01/03/2017
M0251-002Room Data SheetADB
Project: 7857 7857 Nottingham Uni Medical Centre
Department: PRI Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
Room: M0251-002 Office: 1 person
Room Number: Revision Date: 01/03/2017
1) Clinical administration.
2) Computer workstation(s) may be used.
3) Telephone(s) may be used.
4) Discussions and interviews may take place.
5) Files and records are stored.
6) Hanging outdoor clothing.
7) Secure holding/storing of clothing and personal belongings.
8) Printer may be used.
9) Electronic patient records (EPRs) may be accessed and updated.
10) Staff notices, information and/or messages may be displayed.
11) Dealing with enquiries.
12) Information on computers may be accessed.
Activities:
Personnel: 1 x staff
Up to x 2 others.
Planning
Relationships:
Space Data: Height (mm): 8.00 2,400Area (m²):
Activity DataBase 01/03/2017
Notes: The following equipment is shown on the room layout but is optional:
- call repeat lamps for controlled drugs cupboards (but required if the office is used for
clinical control).
The following items may provided;
- shelving;
- printer.
The following items may be provided if the office is used for clinical control :
- a small safe;
- a key cupboard;
- an alarm panel, see HTM 08-03;
- a dimming switch - recommended if the room is used for viewing digital images.
.
Separate data and voice outlets may be used where structure cabling solutions are not
available.
ADB Group Definitions:
1. Contractor supply and install.
2. Supply by others, contractor install.
3. UoN supply – loose equipment and specialist equipment (chairs, drawer units,
non-fixed medical equipment).
4. NHS IT equipment (nil cost to the project).
5. Dental supply and install.
6. Pharmacy supply and install.
7. UoN IT support and install.
8. UoN supply and install (tacks and blinds; fire extinguishers; UoN signage.
9. UoN F.O.C.
Activity DataBase 01/03/2017
7857 Nottingham Uni Medical Centre7857Project:
Room Environmental Data M0251-002ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: M0251-002 Office: 1 person
Room Number: Revision Date: 01/03/2017
Permissible Space Temerature Range(dry bulb) (degC):
TEMPERATURE AND VENTILATION Requirements Notes
18 - 28
Heating Design Temperature (dry bulb)(degC): 21
Minimum Air Changes (AC/hr): 4
Ventilation Type: S/E/N
Bal or -vePressure Relative to Adjoining Space:
G4Supply Air: Final Filter Class
Permisiible Relative Humidity Range (%):
General Notes:
LIGHTINGType Of Control: S/N
Daytime General Service Illuminance (Lux): 300 Over workstations
Daytime Specific Service Illuminance (Lux):
Nighttime General Service Illuminance (Lux):
Nighttime Specific Service Illuminance (Lux):
Local Task Illuminance (Lux):
Colour Rendering Required: Y
Colour Rendering Required Characteristics (Ra): 80
Unified Glare Rating Limit (UGRL): 19
Emergency Escape Route Lighting Required: In accordance with BS 5266 and Health Technical
MemorandumsY
Standby Lighting Grade - General Lighting: B
Standby Lighting Grade - Local Lighting:
General Notes: Refer to CIBSE Lighting Guide LG3 for areas with VDT’s
RISKClinical Risk Category:
Non-clinical Business Continuity Risk Category:
General Notes:
Noise Intrusion (dB) 1hr day:
NOISE
Noise Intrusion (dB) 1hr night:
Noise Intrusion (dB) f night:
40
-
-
Maximum Internal Noise from M&E Services (NR): 35 Total noise of MEP services under normal operation across
the range 63Hz to 4kHz inclusive.
Room Sound-insulation Parameters - Privacy:
Room Sound-insulation Parameters - Noise Generation:
Private
Typical
Reference to Table 3 of the Department of Health 'Acoustics:
Technical design manual 4032:0.6:England'.
Noise Sensitiviy: Medium
Sound-insulation Rating (dB D nT,w):
General Notes:
Maximum Surface Temperature (DegC):
SAFETY/FIRE
82
Domestic Hot Water Discharge Temperature (DegC): 60
Maximum Cold Water Discharge Temperature (DegC): <20
General Notes:
Type of Automatic Fire Detection: Smoke
General Notes:
Activity DataBase 01/03/2017
ADB Room Design Character M0251-002
Project: 7857 7857 Nottingham Uni Medical Centre
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Office: 1 personM0251-002Room:
01/03/2017Revision Date:Room Number:
Walls: Wall finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Wall finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Floor: Floor finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Floor finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Ceiling: Ceiling finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Ceiling finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Doorsets: Configuration, glazing, fire rating, security, etc. to be determined by Project Team.
HTM 58 (Mar-2005)
Refer to HBN 00-04 (May-2007) for effective clear door widths.
1 doorset:
1 x personnel, wheelchair & equipment access (1000mm)
Windows: Desirable - Project Option
Clear glass with solar and privacy control
Designation to be validated against current documentation (HTM 55 archived).
Internal Glazing: Non-essential - Project Option
Designation to be validated against current documentation. HTM 57 (Mar-2005)
Hatch: Not required
Notes: All finishes selected must have an appropriate risk assessment to accompany the design
decision.
Infection Control must be consulted as described in Performance Requirements for Building
Elements Used in Healthcare Facilities 8941:0.6 England.
Activity DataBase 01/03/2017
Schedule of Components by Room
Project: 7857 7857 Nottingham Uni Medical Centre
M0251-002ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: M0251-002 Office: 1 person
Room Number: Revision Date: 01/03/2017
Key: (n-old qty) Deletions m-new qty Additions m (n) Quantity changes since audit dateAudit Date: 2-Mar-2017
DescriptionCodeTotalTransNew
GrpAlt. CodeQuantity
1BOARD, display/notice, wall mounted, 900H 1200WBOA01311
1PULL/PUSH BUTTON, staff emergency call, reset
and integral/adjacent indicator lamp
CAL00711
1LAMP, repeat call, patient/staff or staff emergency or
cardiac call
CAL03411
1DESK, cantilever, single pedestal 3 drawer, cable
management, modesty panel, 1800W 800D
DES02011
1HOOK, single, small, wall mountedHOO01933
1SOCKET outlet, switched, 13 amp, singleOUT00511
1SOCKET outlet, switched, 13 amp, twinOUT01022
1SOCKET outlet data/voice, double.OUT13122
1SWITCH, lightSWC02511
3CABINET, lateral filing, 6 rails, 2 door, 1970H 1000W
470D
CAB04911
3CHAIR, swivel, height adjustable, high back, with
arms, wipeable, 5 star base, on castors
CHA30111
3CHAIR, upright, upholstered, stacking, wipeableCHA31722
3DRAWER UNIT, 2 drawer, lockable, on castors,
600H 410W 600D
DRA05611
3DRAWER UNIT, 3 drawer, lockable, on castors, desk
height 715H 430W 600D
DRA05711
7COMPUTER KEYBOARDCOM83311
7COMPUTER MONITOR, 17"; TFT, digital flat panel
display, high-resolution screens, desk top
COM84922
8TRACK, blinds for windowsTRA90011
Activity DataBase 01/03/2017
M0251-003Room Data SheetADB
Project: 7857 7857 Nottingham Uni Medical Centre
Department: PRI Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
Room: M0251-003 Office: 1 person
Room Number: Revision Date: 01/03/2017
1) Clinical administration.
2) Computer workstation(s) may be used.
3) Telephone(s) may be used.
4) Discussions and interviews may take place.
5) Files and records are stored.
6) Hanging outdoor clothing.
7) Secure holding/storing of clothing and personal belongings.
8) Printer may be used.
9) Electronic patient records (EPRs) may be accessed and updated.
10) Staff notices, information and/or messages may be displayed.
11) Dealing with enquiries.
12) Information on computers may be accessed.
Activities:
Personnel: 1 x staff
Up to x 2 others.
Planning
Relationships:
Space Data: Height (mm): 8.00 2,400Area (m²):
Activity DataBase 01/03/2017
Notes: The following equipment is shown on the room layout but is optional:
- call repeat lamps for controlled drugs cupboards (but required if the office is used for
clinical control).
The following items may provided;
- shelving;
- printer.
The following items may be provided if the office is used for clinical control :
- a small safe;
- a key cupboard;
- an alarm panel, see HTM 08-03;
- a dimming switch - recommended if the room is used for viewing digital images.
.
Separate data and voice outlets may be used where structure cabling solutions are not
available.
ADB Group Definitions:
1. Contractor supply and install.
2. Supply by others, contractor install.
3. UoN supply – loose equipment and specialist equipment (chairs, drawer units,
non-fixed medical equipment).
4. NHS IT equipment (nil cost to the project).
5. Dental supply and install.
6. Pharmacy supply and install.
7. UoN IT support and install.
8. UoN supply and install (tacks and blinds; fire extinguishers; UoN signage.
9. UoN F.O.C.
Activity DataBase 01/03/2017
7857 Nottingham Uni Medical Centre7857Project:
Room Environmental Data M0251-003ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: M0251-003 Office: 1 person
Room Number: Revision Date: 01/03/2017
Permissible Space Temerature Range(dry bulb) (degC):
TEMPERATURE AND VENTILATION Requirements Notes
18 - 28
Heating Design Temperature (dry bulb)(degC): 21
Minimum Air Changes (AC/hr): 4
Ventilation Type: S/E/N
Bal or -vePressure Relative to Adjoining Space:
G4Supply Air: Final Filter Class
Permisiible Relative Humidity Range (%):
General Notes:
LIGHTINGType Of Control: S/N
Daytime General Service Illuminance (Lux): 300 Over workstations
Daytime Specific Service Illuminance (Lux):
Nighttime General Service Illuminance (Lux):
Nighttime Specific Service Illuminance (Lux):
Local Task Illuminance (Lux):
Colour Rendering Required: Y
Colour Rendering Required Characteristics (Ra): 80
Unified Glare Rating Limit (UGRL): 19
Emergency Escape Route Lighting Required: In accordance with BS 5266 and Health Technical
MemorandumsY
Standby Lighting Grade - General Lighting: B
Standby Lighting Grade - Local Lighting:
General Notes: Refer to CIBSE Lighting Guide LG3 for areas with VDT’s
RISKClinical Risk Category:
Non-clinical Business Continuity Risk Category:
General Notes:
Noise Intrusion (dB) 1hr day:
NOISE
Noise Intrusion (dB) 1hr night:
Noise Intrusion (dB) f night:
40
-
-
Maximum Internal Noise from M&E Services (NR): 35 Total noise of MEP services under normal operation across
the range 63Hz to 4kHz inclusive.
Room Sound-insulation Parameters - Privacy:
Room Sound-insulation Parameters - Noise Generation:
Private
Typical
Reference to Table 3 of the Department of Health 'Acoustics:
Technical design manual 4032:0.6:England'.
Noise Sensitiviy: Medium
Sound-insulation Rating (dB D nT,w):
General Notes:
Maximum Surface Temperature (DegC):
SAFETY/FIRE
82
Domestic Hot Water Discharge Temperature (DegC): 60
Maximum Cold Water Discharge Temperature (DegC): <20
General Notes:
Type of Automatic Fire Detection: Smoke
General Notes:
Activity DataBase 01/03/2017
ADB Room Design Character M0251-003
Project: 7857 7857 Nottingham Uni Medical Centre
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Office: 1 personM0251-003Room:
01/03/2017Revision Date:Room Number:
Walls: Wall finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Wall finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Floor: Floor finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Floor finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Ceiling: Ceiling finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Ceiling finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Doorsets: Configuration, glazing, fire rating, security, etc. to be determined by Project Team.
HTM 58 (Mar-2005)
Refer to HBN 00-04 (May-2007) for effective clear door widths.
1 doorset:
1 x personnel, wheelchair & equipment access (1000mm)
Windows: Desirable - Project Option
Clear glass with solar and privacy control
Designation to be validated against current documentation (HTM 55 archived).
Internal Glazing: Non-essential - Project Option
Designation to be validated against current documentation. HTM 57 (Mar-2005)
Hatch: Not required
Notes: All finishes selected must have an appropriate risk assessment to accompany the design
decision.
Infection Control must be consulted as described in Performance Requirements for Building
Elements Used in Healthcare Facilities 8941:0.6 England.
Activity DataBase 01/03/2017
Schedule of Components by Room
Project: 7857 7857 Nottingham Uni Medical Centre
M0251-003ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: M0251-003 Office: 1 person
Room Number: Revision Date: 01/03/2017
Key: (n-old qty) Deletions m-new qty Additions m (n) Quantity changes since audit dateAudit Date: 2-Mar-2017
DescriptionCodeTotalTransNew
GrpAlt. CodeQuantity
1HOOK, single, small, wall mountedHOO01922
1LUMINAIRE, indicating controlled drugs cupboard
repeat
LIG13811
1SOCKET outlet, switched, 13 amp, singleOUT00511
1SOCKET outlet, switched, 13 amp, twinOUT01022
1SOCKET outlet data/voice, double.OUT13122
1SWITCH, lightSWC02511
5BOARD, display/notice, wall mounted, 900H 1200WBOA11311
5CABINET, lateral filing, 6 rails, 2 door, 1970H 1000W
470D
CAB14911
5CHAIR, swivel, height adjustable, high back, with
arms, wipeable, 5 star base, on castors
CHA40111
5CHAIR, upright, upholstered, stacking, wipeableCHA41722
5COMPUTER KEYBOARDCOM13311
5COMPUTER MONITOR, 17"; TFT, digital flat panel
display, high-resolution screens, desk top
COM14911
5Stand Alone Desk, cantilever, cable management,
adjustable legs, modesty panel, 1400W 700D
DES12611
5DRAWER UNIT, 2 drawer, lockable, on castors,
600H 410W 600D
DRA15611
5DRAWER UNIT, 3 drawer, lockable, on castors, desk
height 715H 430W 600D
DRA15711
5HOOK, single, small, wall mountedHOO11911
5TRACK, blinds for windowsTRA90211
Activity DataBase 01/03/2017
M0252-001Room Data SheetADB
Project: 7857 7857 Nottingham Uni Medical Centre
Department: PRI Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
Room: M0252-001 Admin (based on Office: 2 person)
Room Number: Revision Date: 01/03/2017
1) Clinical administration.
2) Computer workstation(s) may be used.
3) Telephone(s) may be used.
4) Discussions and interviews may take place.
5) Files and records are stored.
6) Hanging outdoor clothing.
7) Staff notices, information and/or messages may be displayed.
8) Printer may be used.
9) Dealing with enquiries.
10) Information on computers may be accessed.
Activities:
Personnel: 2 x staff.
Up to 2 x others.
Planning
Relationships:
Space Data: Height (mm): 12.00 2,400Area (m²):
Notes: The following equipment is shown on the room layout but is optional:
- call repeat lamps for controlled drugs cupboards (but required if the office is used for
clinical control).
The following items may be provided if the office is used for clinical control :
- a dimming switch - recommended if the room is used for viewing digital images.
.
Separate data and voice outlets may be used where structure cabling solutions are not
available.
ADB Group Definitions:
1. Contractor supply and install.
2. Supply by others, contractor install.
3. UoN supply – loose equipment and specialist equipment (chairs, drawer units,
non-fixed medical equipment).
4. NHS IT equipment (nil cost to the project).
5. Dental supply and install.
6. Pharmacy supply and install.
7. UoN IT support and install.
8. UoN supply and install (tacks and blinds; fire extinguishers; UoN signage.
9. UoN F.O.C.
Activity DataBase 01/03/2017
7857 Nottingham Uni Medical Centre7857Project:
Room Environmental Data M0252-001ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: M0252-001 Admin (based on Office: 2 person)
Room Number: Revision Date: 01/03/2017
Permissible Space Temerature Range(dry bulb) (degC):
TEMPERATURE AND VENTILATION Requirements Notes
18 - 28
Heating Design Temperature (dry bulb)(degC): 21
Minimum Air Changes (AC/hr): 4
Ventilation Type: S/E/N
Bal or -vePressure Relative to Adjoining Space:
G4Supply Air: Final Filter Class
Permisiible Relative Humidity Range (%):
General Notes:
LIGHTINGType Of Control: S/N
Daytime General Service Illuminance (Lux): 300 Over workstations
Daytime Specific Service Illuminance (Lux):
Nighttime General Service Illuminance (Lux):
Nighttime Specific Service Illuminance (Lux):
Local Task Illuminance (Lux):
Colour Rendering Required: Y
Colour Rendering Required Characteristics (Ra): 80
Unified Glare Rating Limit (UGRL): 19
Emergency Escape Route Lighting Required: In accordance with BS 5266 and Health Technical
MemorandumsY
Standby Lighting Grade - General Lighting: B
Standby Lighting Grade - Local Lighting:
General Notes: Refer to CIBSE Lighting Guide LG3 for areas with VDT’s
RISKClinical Risk Category:
Non-clinical Business Continuity Risk Category:
General Notes:
Noise Intrusion (dB) 1hr day:
NOISE
Noise Intrusion (dB) 1hr night:
Noise Intrusion (dB) f night:
40
-
-
Maximum Internal Noise from M&E Services (NR): 35 Total noise of MEP services under normal operation across
the range 63Hz to 4kHz inclusive.
Room Sound-insulation Parameters - Privacy:
Room Sound-insulation Parameters - Noise Generation:
Moderate
Typical
Reference to Table 3 of the Department of Health 'Acoustics:
Technical design manual 4032:0.6:England'.
Noise Sensitiviy: Medium
Sound-insulation Rating (dB D nT,w):
General Notes:
Maximum Surface Temperature (DegC):
SAFETY/FIRE
82
Domestic Hot Water Discharge Temperature (DegC): 60
Maximum Cold Water Discharge Temperature (DegC): <20
General Notes:
Type of Automatic Fire Detection: Smoke
General Notes:
Activity DataBase 01/03/2017
ADB Room Design Character M0252-001
Project: 7857 7857 Nottingham Uni Medical Centre
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Admin (based on Office: 2 person)M0252-001Room:
01/03/2017Revision Date:Room Number:
Walls: Wall finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Wall finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Floor: Floor finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Floor finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Ceiling: Ceiling finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Ceiling finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Doorsets: Configuration, glazing, fire rating, security, etc. to be determined by Project Team.
HTM 58 (Mar-2005)
Refer to HBN 00-04 (May-2007) for effective clear door widths.
1 doorset:
1 x personnel, wheelchair & equipment access (1000mm)
Windows: Desirable - Project Option
Clear glass with solar and privacy control
Designation to be validated against current documentation (HTM 55 archived).
Internal Glazing: Non-essential - Project Option
Designation to be validated against current documentation. HTM 57 (Mar-2005)
Hatch: Not required
Notes: All finishes selected must have an appropriate risk assessment to accompany the design
decision.
Infection Control must be consulted as described in Performance Requirements for Building
Elements Used in Healthcare Facilities 8941:0.6 England.
Activity DataBase 01/03/2017
Schedule of Components by Room
Project: 7857 7857 Nottingham Uni Medical Centre
M0252-001ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: M0252-001 Admin (based on Office: 2 person)
Room Number: Revision Date: 01/03/2017
Key: (n-old qty) Deletions m-new qty Additions m (n) Quantity changes since audit dateAudit Date: 2-Mar-2017
DescriptionCodeTotalTransNew
GrpAlt. CodeQuantity
1BOARD, display/notice, wall mounted, 900H 1200WBOA01311
1DESK UNIT, cantilever, L shape, cable management,
wall fixed, modesty panel, 2837W 2220L 750D
DES90111
1SOCKET outlet, switched, 13 amp, singleOUT00522
1SOCKET outlet, switched, 13 amp, twinOUT01044
1SOCKET outlet data/voice, double.OUT13133
1SHELF, custom to fit, L shape corner, 2837W 2220L
300D
SHE90011
1SWITCH, lightSWC02522
3CHAIR, swivel, height adjustable, high back, with
arms, wipeable, 5 star base, on castors
CHA30122
3DRAWER UNIT, 2 drawer, lockable, on castors,
600H 410W 600D
DRA05622
4COMPUTER KEYBOARDCOM03322
4COMPUTER MONITOR, 17"; TFT, digital flat panel
display, high-resolution screens, desk top
COM94922
Activity DataBase 01/03/2017
M0252-002Room Data SheetADB
Project: 7857 7857 Nottingham Uni Medical Centre
Department: PRI Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
Room: M0252-002 Office: 2 person
Room Number: Revision Date: 01/03/2017
1) Clinical administration.
2) Computer workstation(s) may be used.
3) Telephone(s) may be used.
4) Discussions and interviews may take place.
5) Files and records are stored.
6) Hanging outdoor clothing.
7) Staff notices, information and/or messages may be displayed.
8) Printer may be used.
9) Dealing with enquiries.
10) Information on computers may be accessed.
Activities:
Personnel: 2 x staff.
Up to 2 x others.
Planning
Relationships:
Space Data: Height (mm): 12.00 2,400Area (m²):
Notes: The following equipment is shown on the room layout but is optional:
- call repeat lamps for controlled drugs cupboards (but required if the office is used for
clinical control).
The following items may be provided if the office is used for clinical control :
- a dimming switch - recommended if the room is used for viewing digital images.
.
Separate data and voice outlets may be used where structure cabling solutions are not
available.
ADB Group Definitions:
1. Contractor supply and install.
2. Supply by others, contractor install.
3. UoN supply – loose equipment and specialist equipment (chairs, drawer units,
non-fixed medical equipment).
4. NHS IT equipment (nil cost to the project).
5. Dental supply and install.
6. Pharmacy supply and install.
7. UoN IT support and install.
8. UoN supply and install (tacks and blinds; fire extinguishers; UoN signage.
9. UoN F.O.C.
Activity DataBase 01/03/2017
7857 Nottingham Uni Medical Centre7857Project:
Room Environmental Data M0252-002ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: M0252-002 Office: 2 person
Room Number: Revision Date: 01/03/2017
Permissible Space Temerature Range(dry bulb) (degC):
TEMPERATURE AND VENTILATION Requirements Notes
18 - 28
Heating Design Temperature (dry bulb)(degC): 21
Minimum Air Changes (AC/hr): 4
Ventilation Type: S/E/N
Bal or -vePressure Relative to Adjoining Space:
G4Supply Air: Final Filter Class
Permisiible Relative Humidity Range (%):
General Notes:
LIGHTINGType Of Control: S/N
Daytime General Service Illuminance (Lux): 300 Over workstations
Daytime Specific Service Illuminance (Lux):
Nighttime General Service Illuminance (Lux):
Nighttime Specific Service Illuminance (Lux):
Local Task Illuminance (Lux):
Colour Rendering Required: Y
Colour Rendering Required Characteristics (Ra): 80
Unified Glare Rating Limit (UGRL): 19
Emergency Escape Route Lighting Required: In accordance with BS 5266 and Health Technical
MemorandumsY
Standby Lighting Grade - General Lighting: B
Standby Lighting Grade - Local Lighting:
General Notes: Refer to CIBSE Lighting Guide LG3 for areas with VDT’s
RISKClinical Risk Category:
Non-clinical Business Continuity Risk Category:
General Notes:
Noise Intrusion (dB) 1hr day:
NOISE
Noise Intrusion (dB) 1hr night:
Noise Intrusion (dB) f night:
40
-
-
Maximum Internal Noise from M&E Services (NR): 35 Total noise of MEP services under normal operation across
the range 63Hz to 4kHz inclusive.
Room Sound-insulation Parameters - Privacy:
Room Sound-insulation Parameters - Noise Generation:
Moderate
Typical
Reference to Table 3 of the Department of Health 'Acoustics:
Technical design manual 4032:0.6:England'.
Noise Sensitiviy: Medium
Sound-insulation Rating (dB D nT,w):
General Notes:
Maximum Surface Temperature (DegC):
SAFETY/FIRE
82
Domestic Hot Water Discharge Temperature (DegC): 60
Maximum Cold Water Discharge Temperature (DegC): <20
General Notes:
Type of Automatic Fire Detection: Smoke
General Notes:
Activity DataBase 01/03/2017
ADB Room Design Character M0252-002
Project: 7857 7857 Nottingham Uni Medical Centre
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Office: 2 personM0252-002Room:
01/03/2017Revision Date:Room Number:
Walls: Wall finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Wall finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Floor: Floor finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Floor finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Ceiling: Ceiling finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Ceiling finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Doorsets: Configuration, glazing, fire rating, security, etc. to be determined by Project Team.
HTM 58 (Mar-2005)
Refer to HBN 00-04 (May-2007) for effective clear door widths.
1 doorset:
1 x personnel, wheelchair & equipment access (1000mm)
Windows: Desirable - Project Option
Clear glass with solar and privacy control
Designation to be validated against current documentation (HTM 55 archived).
Internal Glazing: Non-essential - Project Option
Designation to be validated against current documentation. HTM 57 (Mar-2005)
Hatch: Not required
Notes: All finishes selected must have an appropriate risk assessment to accompany the design
decision.
Infection Control must be consulted as described in Performance Requirements for Building
Elements Used in Healthcare Facilities 8941:0.6 England.
Activity DataBase 01/03/2017
Schedule of Components by Room
Project: 7857 7857 Nottingham Uni Medical Centre
M0252-002ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: M0252-002 Office: 2 person
Room Number: Revision Date: 01/03/2017
Key: (n-old qty) Deletions m-new qty Additions m (n) Quantity changes since audit dateAudit Date: 2-Mar-2017
DescriptionCodeTotalTransNew
GrpAlt. CodeQuantity
1LUMINAIRE, indicating controlled drugs cupboard
repeat
LIG13811
1SOCKET outlet, switched, 13 amp, singleOUT00511
1SOCKET outlet, switched, 13 amp, twinOUT01044
1SOCKET outlet data/voice, double.OUT13144
1SWITCH, lightSWC02511
5BOARD, display/notice, wall mounted, 900H 1200WBOA11322
5CABINET, lateral filing, 6 rails, 2 door, 1970H 1000W
470D
CAB14911
5CHAIR, swivel, height adjustable, high back, with
arms, wipeable, 5 star base, on castors
CHA40122
5CHAIR, upright, upholstered, stacking, wipeableCHA41722
5COMPUTER KEYBOARDCOM13322
5COMPUTER MONITOR, 17"; TFT, digital flat panel
display, high-resolution screens, desk top
COM14922
5Stand Alone Desk, cantilever, cable management,
adjustable legs, modesty panel, 1400W 700D
DES12622
5DRAWER UNIT, 2 drawer, lockable, on castors,
600H 410W 600D
DRA15622
5DRAWER UNIT, 3 drawer, lockable, on castors, desk
height 715H 430W 600D
DRA15722
5HOOK, single, small, wall mountedHOO11933
5TRACK, blinds for windowsTRA90211
Activity DataBase 01/03/2017
M0252-003Room Data SheetADB
Project: 7857 7857 Nottingham Uni Medical Centre
Department: PRI Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
Room: M0252-003 Office: 2 person
Room Number: Revision Date: 01/03/2017
1) Clinical administration.
2) Computer workstation(s) may be used.
3) Telephone(s) may be used.
4) Discussions and interviews may take place.
5) Files and records are stored.
6) Hanging outdoor clothing.
7) Staff notices, information and/or messages may be displayed.
8) Printer may be used.
9) Dealing with enquiries.
10) Information on computers may be accessed.
Activities:
Personnel: 2 x staff.
Up to 2 x others.
Planning
Relationships:
Space Data: Height (mm): 12.00 2,400Area (m²):
Notes: The following equipment is shown on the room layout but is optional:
- call repeat lamps for controlled drugs cupboards (but required if the office is used for
clinical control).
The following items may be provided if the office is used for clinical control :
- a dimming switch - recommended if the room is used for viewing digital images.
.
Separate data and voice outlets may be used where structure cabling solutions are not
available.
ADB Group Definitions:
1. Contractor supply and install.
2. Supply by others, contractor install.
3. UoN supply – loose equipment and specialist equipment (chairs, drawer units,
non-fixed medical equipment).
4. NHS IT equipment (nil cost to the project).
5. Dental supply and install.
6. Pharmacy supply and install.
7. UoN IT support and install.
8. UoN supply and install (tacks and blinds; fire extinguishers; UoN signage.
9. UoN F.O.C.
Activity DataBase 01/03/2017
7857 Nottingham Uni Medical Centre7857Project:
Room Environmental Data M0252-003ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: M0252-003 Office: 2 person
Room Number: Revision Date: 01/03/2017
Permissible Space Temerature Range(dry bulb) (degC):
TEMPERATURE AND VENTILATION Requirements Notes
18 - 28
Heating Design Temperature (dry bulb)(degC): 21
Minimum Air Changes (AC/hr): 4
Ventilation Type: S/E/N
Bal or -vePressure Relative to Adjoining Space:
G4Supply Air: Final Filter Class
Permisiible Relative Humidity Range (%):
General Notes:
LIGHTINGType Of Control: S/N
Daytime General Service Illuminance (Lux): 300 Over workstations
Daytime Specific Service Illuminance (Lux):
Nighttime General Service Illuminance (Lux):
Nighttime Specific Service Illuminance (Lux):
Local Task Illuminance (Lux):
Colour Rendering Required: Y
Colour Rendering Required Characteristics (Ra): 80
Unified Glare Rating Limit (UGRL): 19
Emergency Escape Route Lighting Required: In accordance with BS 5266 and Health Technical
MemorandumsY
Standby Lighting Grade - General Lighting: B
Standby Lighting Grade - Local Lighting:
General Notes: Refer to CIBSE Lighting Guide LG3 for areas with VDT’s
RISKClinical Risk Category:
Non-clinical Business Continuity Risk Category:
General Notes:
Noise Intrusion (dB) 1hr day:
NOISE
Noise Intrusion (dB) 1hr night:
Noise Intrusion (dB) f night:
40
-
-
Maximum Internal Noise from M&E Services (NR): 35 Total noise of MEP services under normal operation across
the range 63Hz to 4kHz inclusive.
Room Sound-insulation Parameters - Privacy:
Room Sound-insulation Parameters - Noise Generation:
Moderate
Typical
Reference to Table 3 of the Department of Health 'Acoustics:
Technical design manual 4032:0.6:England'.
Noise Sensitiviy: Medium
Sound-insulation Rating (dB D nT,w):
General Notes:
Maximum Surface Temperature (DegC):
SAFETY/FIRE
82
Domestic Hot Water Discharge Temperature (DegC): 60
Maximum Cold Water Discharge Temperature (DegC): <20
General Notes:
Type of Automatic Fire Detection: Smoke
General Notes:
Activity DataBase 01/03/2017
ADB Room Design Character M0252-003
Project: 7857 7857 Nottingham Uni Medical Centre
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Office: 2 personM0252-003Room:
01/03/2017Revision Date:Room Number:
Walls: Wall finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Wall finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Floor: Floor finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Floor finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Ceiling: Ceiling finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Ceiling finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Doorsets: Configuration, glazing, fire rating, security, etc. to be determined by Project Team.
HTM 58 (Mar-2005)
Refer to HBN 00-04 (May-2007) for effective clear door widths.
1 doorset:
1 x personnel, wheelchair & equipment access (1000mm)
Windows: Desirable - Project Option
Clear glass with solar and privacy control
Designation to be validated against current documentation (HTM 55 archived).
Internal Glazing: Non-essential - Project Option
Designation to be validated against current documentation. HTM 57 (Mar-2005)
Hatch: Not required
Notes: All finishes selected must have an appropriate risk assessment to accompany the design
decision.
Infection Control must be consulted as described in Performance Requirements for Building
Elements Used in Healthcare Facilities 8941:0.6 England.
Activity DataBase 01/03/2017
Schedule of Components by Room
Project: 7857 7857 Nottingham Uni Medical Centre
M0252-003ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: M0252-003 Office: 2 person
Room Number: Revision Date: 01/03/2017
Key: (n-old qty) Deletions m-new qty Additions m (n) Quantity changes since audit dateAudit Date: 2-Mar-2017
DescriptionCodeTotalTransNew
GrpAlt. CodeQuantity
1BOARD, display/notice, wall mounted, 900H 1200WBOA01322
1DESK UNIT, cantilever, cable management,
adjustable legs, modesty panel, 1400W 700D
DES02622
1HOOK, single, small, wall mountedHOO01933
1SOCKET outlet, switched, 13 amp, singleOUT00511
1SOCKET outlet, switched, 13 amp, twinOUT01044
1SOCKET outlet data/voice, double.OUT13144
1SWITCH, lightSWC02511
3CABINET, filing, 4 drawer, 1320H 465W 620DCAB02544
3CHAIR, swivel, height adjustable, high back, with
arms, wipeable, 5 star base, on castors
CHA30122
3CHAIR, upright, upholstered, stacking, wipeableCHA31722
3DRAWER UNIT, 2 drawer, lockable, on castors,
600H 410W 600D
DRA05633
4COMPUTER KEYBOARDCOM03322
4COMPUTER MONITOR, 17"; TFT, digital flat panel
display, high-resolution screens, desk top
COM04922
8TRACK, blinds for windowsTRA90011
Activity DataBase 01/03/2017
M0278-001Room Data SheetADB
Project: 7857 7857 Nottingham Uni Medical Centre
Department: PRI Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
Room: M0278-001 GPs' Admin Area (based on Administration area: shared use: 8 workstations *
2)
Room Number: Revision Date: 01/03/2017
1) Clinical administration.
2) Computer workstation(s) may be used.
3) Telephone(s) may be used.
4) Files and records are stored.
5) Secure holding/storing of clothing and personal belongings.
6) Hanging outdoor clothing.
7) Electronic patient records (EPRs) may be accessed and updated.
8) Dealing with enquiries.
9) Information on computers may be accessed.
10) Staff notices, information and/or messages may be displayed.
11) Patient records may be reviewed and recorded.
Activities:
Personnel: 8 x staff.
Up to 4 x others.
Planning
Relationships:
Space Data: Height (mm): 40.00 2,700Area (m²):
Notes: The layout illustrates socket outlets at desk height because they should be easily
accessible to enable equipment to be switched off for energy conservation .
Floor box services are discouraged as they make it harder to convert the space into a
clinical room in the future. It is therefore assumed that the workstations are wire
managed.
.
Separate data and voice outlets may be used where structure cabling solutions are not
available.
ADB Group Definitions:
1. Contractor supply and install.
2. Supply by others, contractor install.
3. UoN supply – loose equipment and specialist equipment (chairs, drawer units,
non-fixed medical equipment).
4. NHS IT equipment (nil cost to the project).
5. Dental supply and install.
6. Pharmacy supply and install.
7. UoN IT support and install.
8. UoN supply and install (tacks and blinds; fire extinguishers; UoN signage.
9. UoN F.O.C.
Activity DataBase 01/03/2017
7857 Nottingham Uni Medical Centre7857Project:
Room Environmental Data M0278-001ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: M0278-001 GPs' Admin Area (based on Administration area: shared use: 8 workstations *
2)
Room Number: Revision Date: 01/03/2017
Permissible Space Temerature Range(dry bulb) (degC):
TEMPERATURE AND VENTILATION Requirements Notes
18 - 28
Heating Design Temperature (dry bulb)(degC): 21
Minimum Air Changes (AC/hr): 6
Ventilation Type: S/E/N
Bal or -vePressure Relative to Adjoining Space:
G4Supply Air: Final Filter Class
Permisiible Relative Humidity Range (%):
General Notes:
LIGHTINGType Of Control: S/N
Daytime General Service Illuminance (Lux): 300 Over workstations
Daytime Specific Service Illuminance (Lux):
Nighttime General Service Illuminance (Lux):
Nighttime Specific Service Illuminance (Lux):
Local Task Illuminance (Lux):
Colour Rendering Required: Y
Colour Rendering Required Characteristics (Ra): 80
Unified Glare Rating Limit (UGRL): 19
Emergency Escape Route Lighting Required: In accordance with BS 5266 and Health Technical
MemorandumsY
Standby Lighting Grade - General Lighting: B
Standby Lighting Grade - Local Lighting:
General Notes: Refer to CIBSE Lighting Guide LG3 for areas with VDT’s
RISKClinical Risk Category:
Non-clinical Business Continuity Risk Category:
General Notes:
Noise Intrusion (dB) 1hr day:
NOISE
Noise Intrusion (dB) 1hr night:
Noise Intrusion (dB) f night:
45
-
-
Maximum Internal Noise from M&E Services (NR): 35 Total noise of MEP services under normal operation across
the range 63Hz to 4kHz inclusive.
Room Sound-insulation Parameters - Privacy:
Room Sound-insulation Parameters - Noise Generation:
Not Private
Typical
Reference to Table 3 of the Department of Health 'Acoustics:
Technical design manual 4032:0.6:England'.
Noise Sensitiviy: Medium
Sound-insulation Rating (dB D nT,w):
General Notes:
Maximum Surface Temperature (DegC):
SAFETY/FIRE
82
Domestic Hot Water Discharge Temperature (DegC): 60
Maximum Cold Water Discharge Temperature (DegC): <20
General Notes:
Type of Automatic Fire Detection: Smoke
General Notes:
Activity DataBase 01/03/2017
ADB Room Design Character M0278-001
Project: 7857 7857 Nottingham Uni Medical Centre
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
GPs' Admin Area (based on Administration area: shared use: 8 workstations *
2)
M0278-001Room:
01/03/2017Revision Date:Room Number:
Walls: Wall finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Wall finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Floor: Floor finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Floor finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Ceiling: Ceiling finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Ceiling finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Doorsets: Not required - open to circulation area or part of another space
Windows: Desirable - Project Option
Clear glass with solar and privacy control
Designation to be validated against current documentation (HTM 55 archived).
Internal Glazing: Non-essential - Project Option
Designation to be validated against current documentation. HTM 57 (Mar-2005)
Hatch: Not required
Notes: All finishes selected must have an appropriate risk assessment to accompany the design
decision.
Infection Control must be consulted as described in Performance Requirements for Building
Elements Used in Healthcare Facilities 8941:0.6 England.
Activity DataBase 01/03/2017
Schedule of Components by Room
Project: 7857 7857 Nottingham Uni Medical Centre
M0278-001ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: M0278-001 GPs' Admin Area (based on Administration area: shared use: 8 workstations *
2)
Room Number: Revision Date: 01/03/2017
Key: (n-old qty) Deletions m-new qty Additions m (n) Quantity changes since audit dateAudit Date: 2-Mar-2017
DescriptionCodeTotalTransNew
GrpAlt. CodeQuantity
1BOARD, display/notice, wall mounted, 900H 600WBOA01222
1BOARD, display/notice, wall mounted, 900H 1200WBOA01311
1BOARD, marker, whiteboard, dry-wipe, with pen
holder, wall mounted, 1200H1800W
BOA10611
1DESK UNIT, cantilever, cable management,
adjustable legs, modesty panel, 1400W 700D
DES0261919
1SOCKET outlet, switched, 13 amp, singleOUT00533
1SOCKET outlet, switched, 13 amp, twinOUT0103333
1SOCKET outlet data/voice, double.OUT1311515
1SHELF, 900W 300DSHE21111
1WORKTOP, clinical, for 2 x 400 facing modular
storage cabinets, 910W 700D
SMW05211
1SWITCH, lightSWC02511
3CHAIR, swivel, height adjustable, high back, with
arms, wipeable, 5 star base, on castors
CHA3011818
3CHAIR, upright, with arms, upholstered, stacking,
wipeable
CHA31866
3DRAWER UNIT, 2 drawer, lockable, on castors,
600H 410W 600D
DRA0561212
3DRAWER UNIT, 3 drawer, lockable, on castors, desk
height 715H 430W 600D
DRA0571616
3SCREEN, dividing, 1500H 2000WSCR02666
3TABLE, 710H 1800W 900DTAB01411
4COMPUTER PRINTER, laser, A4, 250H 380W 385DCOM03833
4COMPUTER KEYBOARDCOM9331818
4COMPUTER MONITOR, 17"; TFT, digital flat panel
display, high-resolution screens, desk top
COM9491717
4PRINTER multifunction, network, floor standing, zone
1800W 750D
PRI91011
8TRACK, blinds for windowsTRA90011
Activity DataBase 01/03/2017
M0278-01Room Data SheetADB
Project: 7857 7857 Nottingham Uni Medical Centre
Department: PRI Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
Room: M0278-01 Dental Admin Area (based on Administration area: shared use: 4
workstations)
Room Number: Revision Date: 01/03/2017
1) Clinical administration.
2) Computer workstation(s) may be used.
3) Telephone(s) may be used.
4) Files and records are stored.
5) Secure holding/storing of clothing and personal belongings.
Activities:
Personnel: 4 x staff.
Up to 2 x others.
Planning
Relationships:
Space Data: Height (mm): 20.00 2,700Area (m²):
Notes: The layout illustrates socket outlets at desk height because they should be easily
accessible to enable equipment to be switched off for energy conservation .
Floor box services are discouraged as they make it harder to convert the space into a
clinical room in the future. It is therefore assumed that the workstations are wire
managed.
.
Separate data and voice outlets may be used where structure cabling solutions are not
available.
ADB Group Definitions:
1. Contractor supply and install.
2. Supply by others, contractor install.
3. UoN supply – loose equipment and specialist equipment (chairs, drawer units,
non-fixed medical equipment).
4. NHS IT equipment (nil cost to the project).
5. Dental supply and install.
6. Pharmacy supply and install.
7. UoN IT support and install.
8. UoN supply and install (tacks and blinds; fire extinguishers; UoN signage.
9. UoN F.O.C.
Activity DataBase 01/03/2017
7857 Nottingham Uni Medical Centre7857Project:
Room Environmental Data M0278-01ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: M0278-01 Dental Admin Area (based on Administration area: shared use: 4
workstations)
Room Number: Revision Date: 01/03/2017
Permissible Space Temerature Range(dry bulb) (degC):
TEMPERATURE AND VENTILATION Requirements Notes
18 - 28
Heating Design Temperature (dry bulb)(degC): 21
Minimum Air Changes (AC/hr): 6
Ventilation Type: S/E/N
Bal or -vePressure Relative to Adjoining Space:
G4Supply Air: Final Filter Class
Permisiible Relative Humidity Range (%):
General Notes:
LIGHTINGType Of Control: S/N
Daytime General Service Illuminance (Lux): 300 Over workstations
Daytime Specific Service Illuminance (Lux):
Nighttime General Service Illuminance (Lux):
Nighttime Specific Service Illuminance (Lux):
Local Task Illuminance (Lux):
Colour Rendering Required: Y
Colour Rendering Required Characteristics (Ra): 80
Unified Glare Rating Limit (UGRL): 19
Emergency Escape Route Lighting Required: In accordance with BS 5266 and Health Technical
MemorandumsY
Standby Lighting Grade - General Lighting: B
Standby Lighting Grade - Local Lighting:
General Notes: Refer to CIBSE Lighting Guide LG3 for areas with VDT’s
RISKClinical Risk Category:
Non-clinical Business Continuity Risk Category:
General Notes:
Noise Intrusion (dB) 1hr day:
NOISE
Noise Intrusion (dB) 1hr night:
Noise Intrusion (dB) f night:
45
-
-
Maximum Internal Noise from M&E Services (NR): 35 Total noise of MEP services under normal operation across
the range 63Hz to 4kHz inclusive.
Room Sound-insulation Parameters - Privacy:
Room Sound-insulation Parameters - Noise Generation:
Moderate
Typical
Reference to Table 3 of the Department of Health 'Acoustics:
Technical design manual 4032:0.6:England'.
Noise Sensitiviy: Medium
Sound-insulation Rating (dB D nT,w):
General Notes:
Maximum Surface Temperature (DegC):
SAFETY/FIRE
82
Domestic Hot Water Discharge Temperature (DegC): 60
Maximum Cold Water Discharge Temperature (DegC): <20
General Notes:
Type of Automatic Fire Detection: Smoke
General Notes:
Activity DataBase 01/03/2017
ADB Room Design Character M0278-01
Project: 7857 7857 Nottingham Uni Medical Centre
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Dental Admin Area (based on Administration area: shared use: 4
workstations)
M0278-01Room:
01/03/2017Revision Date:Room Number:
Walls: Wall finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Wall finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Floor: Floor finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Floor finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Ceiling: Ceiling finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Ceiling finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Doorsets: Not required - open to circulation area or part of another space
Windows: Desirable - Project Option
Clear glass with solar and privacy control
Designation to be validated against current documentation (HTM 55 archived).
Internal Glazing: Non-essential - Project Option
Designation to be validated against current documentation. HTM 57 (Mar-2005)
Hatch: Not required
Notes: All finishes selected must have an appropriate risk assessment to accompany the design
decision.
Infection Control must be consulted as described in Performance Requirements for Building
Elements Used in Healthcare Facilities 8941:0.6 England.
Activity DataBase 01/03/2017
Schedule of Components by Room
Project: 7857 7857 Nottingham Uni Medical Centre
M0278-01ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: M0278-01 Dental Admin Area (based on Administration area: shared use: 4 workstations)
Room Number: Revision Date: 01/03/2017
Key: (n-old qty) Deletions m-new qty Additions m (n) Quantity changes since audit dateAudit Date: 2-Mar-2017
DescriptionCodeTotalTransNew
GrpAlt. CodeQuantity
1SOCKET outlet, switched, 13 amp, singleOUT00511
1SOCKET outlet, switched, 13 amp, twinOUT01088
1SOCKET outlet data/voice, double.OUT13144
1SWITCH, lightSWC02511
5BOARD, display/notice, wall mounted, 900H 1200WBOA11311
5CHAIR, swivel, height adjustable, high back, with
arms, wipeable, 5 star base, on castors
CHA40144
5COMPUTER KEYBOARDCOM13344
5COMPUTER MONITOR, 17"; TFT, digital flat panel
display, high-resolution screens, desk top
COM14944
5Stand Alone Desk, cantilever, cable management,
adjustable legs, modesty panel, 1400W 700D
DES12644
5DRAWER UNIT, 2 drawer, lockable, on castors,
600H 410W 600D
DRA15666
5TRACK, blinds for windowsTRA90211
Activity DataBase 01/03/2017
M0278-02Room Data SheetADB
Project: 7857 7857 Nottingham Uni Medical Centre
Department: PRI Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
Room: M0278-02 Reception Combined (based on Administration area: shared use: 6
workstations)
Room Number: Revision Date: 01/03/2017
1) Clinical administration.
2) Computer workstation(s) may be used.
3) Telephone(s) may be used.
4) Files and records are stored.
5) Secure holding/storing of clothing and personal belongings.
6) Hanging outdoor clothing.
7) Information on computers may be accessed.
8) Printer may be used.
9) Electronic patient records (EPRs) may be accessed and updated.
10) Staff notices, information and/or messages may be displayed.
11) Dealing with enquiries.
12) Patient records may be reviewed and recorded.
13) Shredding documents.
Activities:
Personnel: 6 x staff.
Up to 3 x others.
Planning
Relationships:
Space Data: Height (mm): 30.00 2,700Area (m²):
Notes: The layout illustrates socket outlets at desk height because they should be easily
accessible to enable equipment to be switched off for energy conservation .
Floor box services are discouraged as they make it harder to convert the space into a
clinical room in the future. It is therefore assumed that the workstations are wire
managed.
.
Separate data and voice outlets may be used where structure cabling solutions are not
available.
ADB Group Definitions:
1. Contractor supply and install.
2. Supply by others, contractor install.
3. UoN supply – loose equipment and specialist equipment (chairs, drawer units,
non-fixed medical equipment).
4. NHS IT equipment (nil cost to the project).
5. Dental supply and install.
6. Pharmacy supply and install.
7. UoN IT support and install.
8. UoN supply and install (tacks and blinds; fire extinguishers; UoN signage.
9. UoN F.O.C.
Activity DataBase 01/03/2017
7857 Nottingham Uni Medical Centre7857Project:
Room Environmental Data M0278-02ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: M0278-02 Reception Combined (based on Administration area: shared use: 6
workstations)
Room Number: Revision Date: 01/03/2017
Permissible Space Temerature Range(dry bulb) (degC):
TEMPERATURE AND VENTILATION Requirements Notes
18 - 28
Heating Design Temperature (dry bulb)(degC): 21
Minimum Air Changes (AC/hr): 6
Ventilation Type: S/E/N
Bal or -vePressure Relative to Adjoining Space:
G4Supply Air: Final Filter Class
Permisiible Relative Humidity Range (%):
General Notes:
LIGHTINGType Of Control: S/N
Daytime General Service Illuminance (Lux): 300 Over workstations
Daytime Specific Service Illuminance (Lux):
Nighttime General Service Illuminance (Lux):
Nighttime Specific Service Illuminance (Lux):
Local Task Illuminance (Lux):
Colour Rendering Required: Y
Colour Rendering Required Characteristics (Ra): 80
Unified Glare Rating Limit (UGRL): 19
Emergency Escape Route Lighting Required: In accordance with BS 5266 and Health Technical
MemorandumsY
Standby Lighting Grade - General Lighting: B
Standby Lighting Grade - Local Lighting:
General Notes: Refer to CIBSE Lighting Guide LG3 for areas with VDT’s
RISKClinical Risk Category:
Non-clinical Business Continuity Risk Category:
General Notes:
Noise Intrusion (dB) 1hr day:
NOISE
Noise Intrusion (dB) 1hr night:
Noise Intrusion (dB) f night:
45
-
-
Maximum Internal Noise from M&E Services (NR): 35 Total noise of MEP services under normal operation across
the range 63Hz to 4kHz inclusive.
Room Sound-insulation Parameters - Privacy:
Room Sound-insulation Parameters - Noise Generation:
Not Private
Typical
Reference to Table 3 of the Department of Health 'Acoustics:
Technical design manual 4032:0.6:England'.
Noise Sensitiviy: Medium
Sound-insulation Rating (dB D nT,w):
General Notes:
Maximum Surface Temperature (DegC):
SAFETY/FIRE
82
Domestic Hot Water Discharge Temperature (DegC): 60
Maximum Cold Water Discharge Temperature (DegC): <20
General Notes:
Type of Automatic Fire Detection: Smoke
General Notes:
Activity DataBase 01/03/2017
ADB Room Design Character M0278-02
Project: 7857 7857 Nottingham Uni Medical Centre
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Reception Combined (based on Administration area: shared use: 6
workstations)
M0278-02Room:
01/03/2017Revision Date:Room Number:
Walls: Wall finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Wall finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Floor: Floor finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Floor finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Ceiling: Ceiling finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Ceiling finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Doorsets: Not required - open to circulation area or part of another space
Windows: Desirable - Project Option
Clear glass with solar and privacy control
Designation to be validated against current documentation (HTM 55 archived).
Internal Glazing: Non-essential - Project Option
Designation to be validated against current documentation. HTM 57 (Mar-2005)
Hatch: Not required
Notes: All finishes selected must have an appropriate risk assessment to accompany the design
decision.
Infection Control must be consulted as described in Performance Requirements for Building
Elements Used in Healthcare Facilities 8941:0.6 England.
Activity DataBase 01/03/2017
Schedule of Components by Room
Project: 7857 7857 Nottingham Uni Medical Centre
M0278-02ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: M0278-02 Reception Combined (based on Administration area: shared use: 6
workstations)
Room Number: Revision Date: 01/03/2017
Key: (n-old qty) Deletions m-new qty Additions m (n) Quantity changes since audit dateAudit Date: 2-Mar-2017
DescriptionCodeTotalTransNew
GrpAlt. CodeQuantity
1BOARD, display/notice, wall mounted, 900H 1200WBOA01311
1DESK UNIT, cantilever, cable management,
adjustable legs, modesty panel, 1400W 700D
DES02666
1SOCKET outlet, switched, 13 amp, twinOUT0101010
1SOCKET outlet data/voice, double.OUT1311010
3CHAIR, swivel, height adjustable, high back, with
arms, wipeable, 5 star base, on castors
CHA30166
3CHAIR, upright, upholstered, stacking, wipeableCHA31722
3DRAWER UNIT, 2 drawer, lockable, on castors,
600H 410W 600D
DRA05666
3DRAWER UNIT, 3 drawer, lockable, on castors, desk
height 715H 430W 600D
DRA05711
4COMPUTER KEYBOARDCOM93366
4COMPUTER MONITOR, 17"; TFT, digital flat panel
display, high-resolution screens, desk top
COM94966
8TRACK, blinds for windowsTRA90011
Activity DataBase 01/03/2017
M0281Room Data SheetADB
Project: 7857 7857 Nottingham Uni Medical Centre
Department: PRI Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
Room: M0281 Quiet workspace
Room Number: Revision Date: 01/03/2017
1) Clinical administration.
2) Laptop computer(s) may be used.
3) Telephone(s) may be used.
4) Carrying out administration and clerical duties.
5) Electronic patient records (EPRs) may be accessed and updated.
6) Information on computers may be accessed.
7) Staff notices, information and/or messages may be displayed.
Activities:
Personnel: 1 x staff.
Intermittent use.
Planning
Relationships:
Close to open plan workstation area.
Space Data: Height (mm): 6.00 2,400Area (m²):
Notes: The room has been sized to discourage users from feeling too comfortable and wishing
to monopolise the space.
.
Separate data and voice outlets may be used where structure cabling solutions are not
available.
ADB Group Definitions:
1. Contractor supply and install.
2. Supply by others, contractor install.
3. UoN supply – loose equipment and specialist equipment (chairs, drawer units,
non-fixed medical equipment).
4. NHS IT equipment (nil cost to the project).
5. Dental supply and install.
6. Pharmacy supply and install.
7. UoN IT support and install.
8. UoN supply and install (tacks and blinds; fire extinguishers; UoN signage.
9. UoN F.O.C.
Activity DataBase 01/03/2017
7857 Nottingham Uni Medical Centre7857Project:
Room Environmental Data M0281ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: M0281 Quiet workspace
Room Number: Revision Date: 01/03/2017
Permissible Space Temerature Range(dry bulb) (degC):
TEMPERATURE AND VENTILATION Requirements Notes
18 - 28
Heating Design Temperature (dry bulb)(degC): 21
Minimum Air Changes (AC/hr): 6
Ventilation Type: S/E/N
Bal or -vePressure Relative to Adjoining Space:
G4Supply Air: Final Filter Class
Permisiible Relative Humidity Range (%):
General Notes:
LIGHTINGType Of Control: S/N
Daytime General Service Illuminance (Lux): 300 Over workstations
Daytime Specific Service Illuminance (Lux):
Nighttime General Service Illuminance (Lux):
Nighttime Specific Service Illuminance (Lux):
Local Task Illuminance (Lux):
Colour Rendering Required: Y
Colour Rendering Required Characteristics (Ra): 80
Unified Glare Rating Limit (UGRL): 19
Emergency Escape Route Lighting Required: In accordance with BS 5266 and Health Technical
MemorandumsY
Standby Lighting Grade - General Lighting: B
Standby Lighting Grade - Local Lighting:
General Notes: Refer to CIBSE Lighting Guide LG3 for areas with VDT’s
RISKClinical Risk Category:
Non-clinical Business Continuity Risk Category:
General Notes:
Noise Intrusion (dB) 1hr day:
NOISE
Noise Intrusion (dB) 1hr night:
Noise Intrusion (dB) f night:
40
-
-
Maximum Internal Noise from M&E Services (NR): 35 Total noise of MEP services under normal operation across
the range 63Hz to 4kHz inclusive.
Room Sound-insulation Parameters - Privacy:
Room Sound-insulation Parameters - Noise Generation:
Confidential
Typical
Reference to Table 3 of the Department of Health 'Acoustics:
Technical design manual 4032:0.6:England'.
Noise Sensitiviy: Medium
Sound-insulation Rating (dB D nT,w):
General Notes:
Maximum Surface Temperature (DegC):
SAFETY/FIRE
82
Domestic Hot Water Discharge Temperature (DegC): 60
Maximum Cold Water Discharge Temperature (DegC): <20
General Notes:
Type of Automatic Fire Detection: Smoke
General Notes:
Activity DataBase 01/03/2017
ADB Room Design Character M0281
Project: 7857 7857 Nottingham Uni Medical Centre
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Quiet workspaceM0281Room:
01/03/2017Revision Date:Room Number:
Walls: Wall finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Wall finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Floor: Floor finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Floor finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Ceiling: Ceiling finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Ceiling finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Doorsets: Configuration, glazing, fire rating, security, etc. to be determined by Project Team.
HTM 58 (Mar-2005)
Refer to HBN 00-04 (May-2007) for effective clear door widths.
Not applicable or 1 doorset:
1 x personnel, wheelchair & equipment access (1000mm)
Windows: Desirable - Project Option
Clear glass with solar and privacy control
Designation to be validated against current documentation (HTM 55 archived).
Internal Glazing: Non-essential - Project Option
Designation to be validated against current documentation. HTM 57 (Mar-2005)
Hatch: Not required
Notes: All finishes selected must have an appropriate risk assessment to accompany the design
decision.
Infection Control must be consulted as described in Performance Requirements for Building
Elements Used in Healthcare Facilities 8941:0.6 England.
Activity DataBase 01/03/2017
Schedule of Components by Room
Project: 7857 7857 Nottingham Uni Medical Centre
M0281ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: M0281 Quiet workspace
Room Number: Revision Date: 01/03/2017
Key: (n-old qty) Deletions m-new qty Additions m (n) Quantity changes since audit dateAudit Date: 2-Mar-2017
DescriptionCodeTotalTransNew
GrpAlt. CodeQuantity
1SOCKET outlet, switched, 13 amp, singleOUT00511
1SOCKET outlet, switched, 13 amp, twinOUT01022
1SOCKET outlet data/voice, double.OUT13122
1SWITCH, lightSWC02511
5BOARD, display/notice, wall mounted, 900H 1200WBOA11311
5CHAIR, swivel, height adjustable, high back, with
arms, wipeable, 5 star base, on castors
CHA40122
5HOOK, single, small, wall mountedHOO11933
5SHELF, custom to fit, L shape corner, Width to fit,
300D
SHE90211
5WORKTOP, clinical, for 6 x 400 facing modular
storage cabinets, 2730W 700D
SMW15611
Activity DataBase 01/03/2017
M0330-01Room Data SheetADB
Project: 7857 7857 Nottingham Uni Medical Centre
Department: PRI Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
Room: M0330-01 Library/GP training room
Room Number: Revision Date: 01/03/2017
1) Computer workstation(s) may be used.
2) Telephone(s) may be used.
3) Holding meetings.
4) Colleagues/visitors may be received for training/observation purposes
5) Library and reference material may be accessed.
6) Holding food trolleys (heated and unheated).
7) Instruction is undertaken with the aid of multimedia equipment.
Activities:
Personnel: Up to 10 x persons (meeting function).
Planning
Relationships:
Space Data: Height (mm): 16.00 2,400Area (m²):
Notes:
Separate data and voice outlets may be used where structure cabling solutions are not
available.
ADB Group Definitions:
1. Contractor supply and install.
2. Supply by others, contractor install.
3. UoN supply – loose equipment and specialist equipment (chairs, drawer units,
non-fixed medical equipment).
4. NHS IT equipment (nil cost to the project).
5. Dental supply and install.
6. Pharmacy supply and install.
7. UoN IT support and install.
8. UoN supply and install (tacks and blinds; fire extinguishers; UoN signage.
9. UoN F.O.C.
Activity DataBase 01/03/2017
7857 Nottingham Uni Medical Centre7857Project:
Room Environmental Data M0330-01ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: M0330-01 Library/GP training room
Room Number: Revision Date: 01/03/2017
Permissible Space Temerature Range(dry bulb) (degC):
TEMPERATURE AND VENTILATION Requirements Notes
18 - 28
Heating Design Temperature (dry bulb)(degC): 21
Minimum Air Changes (AC/hr): 6
Ventilation Type: S/E/N
Bal or -vePressure Relative to Adjoining Space:
G4Supply Air: Final Filter Class
Permisiible Relative Humidity Range (%):
General Notes:
LIGHTINGType Of Control: S/N
Daytime General Service Illuminance (Lux): 300 Provide good vertical illumination
Daytime Specific Service Illuminance (Lux):
Nighttime General Service Illuminance (Lux):
Nighttime Specific Service Illuminance (Lux):
Local Task Illuminance (Lux):
Colour Rendering Required: Y
Colour Rendering Required Characteristics (Ra): 80
Unified Glare Rating Limit (UGRL): 19
Emergency Escape Route Lighting Required: In accordance with BS 5266 and Health Technical
MemorandumsY
Standby Lighting Grade - General Lighting: B
Standby Lighting Grade - Local Lighting:
General Notes: Refer to CIBSE Lighting Guide LG3 for areas with VDT’s
RISKClinical Risk Category:
Non-clinical Business Continuity Risk Category:
General Notes:
Noise Intrusion (dB) 1hr day:
NOISE
Noise Intrusion (dB) 1hr night:
Noise Intrusion (dB) f night:
35
-
-
Maximum Internal Noise from M&E Services (NR): 35 Total noise of MEP services under normal operation across
the range 63Hz to 4kHz inclusive.
Room Sound-insulation Parameters - Privacy:
Room Sound-insulation Parameters - Noise Generation:
Private
Typical
Reference to Table 3 of the Department of Health 'Acoustics:
Technical design manual 4032:0.6:England'.
Noise Sensitiviy: Medium
Sound-insulation Rating (dB D nT,w):
General Notes:
Maximum Surface Temperature (DegC):
SAFETY/FIRE
82
Domestic Hot Water Discharge Temperature (DegC): 60
Maximum Cold Water Discharge Temperature (DegC): <20
General Notes:
Type of Automatic Fire Detection: Smoke
General Notes:
Activity DataBase 01/03/2017
ADB Room Design Character M0330-01
Project: 7857 7857 Nottingham Uni Medical Centre
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Library/GP training roomM0330-01Room:
01/03/2017Revision Date:Room Number:
Walls: Wall finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Wall finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Floor: Floor finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Floor finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Ceiling: Ceiling finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Ceiling finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Doorsets: Configuration, glazing, fire rating, security, etc. to be determined by Project Team.
HTM 58 (Mar-2005)
Refer to HBN 00-04 (May-2007) for effective clear door widths.
1 doorset:
1 x personnel, wheelchair & equipment access (1000mm)
Windows: Desirable - Project Option
Clear glass with solar and privacy control
Designation to be validated against current documentation (HTM 55 archived).
Internal Glazing: Non-essential - Project Option
Designation to be validated against current documentation. HTM 57 (Mar-2005)
Hatch: Not required
Notes: All finishes selected must have an appropriate risk assessment to accompany the design
decision.
Infection Control must be consulted as described in Performance Requirements for Building
Elements Used in Healthcare Facilities 8941:0.6 England.
Activity DataBase 01/03/2017
Schedule of Components by Room
Project: 7857 7857 Nottingham Uni Medical Centre
M0330-01ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: M0330-01 Library/GP training room
Room Number: Revision Date: 01/03/2017
Key: (n-old qty) Deletions m-new qty Additions m (n) Quantity changes since audit dateAudit Date: 2-Mar-2017
DescriptionCodeTotalTransNew
GrpAlt. CodeQuantity
1BOARD, display/notice, wall mounted, 900H 1200WBOA01311
1DESK UNIT, cantilever, cable management,
adjustable legs, modesty panel, 1400W 700D
DES02633
1HOOK, single, small, wall mountedHOO01933
1SOCKET outlet, switched, 13 amp, singleOUT00511
1SOCKET outlet, switched, 13 amp, twinOUT01055
1SOCKET outlet data/voice, double.OUT13133
1SHELF, custom to fit, L shape corner, Width to fit,
300D
SHE90111
1SWITCH, lightSWC02511
3CHAIR, swivel, height adjustable, high back, with
arms, wipeable, 5 star base, on castors
CHA30133
3CHAIR, upright, upholstered, stacking, wipeableCHA31733
4COMPUTER KEYBOARDCOM93333
4COMPUTER MONITOR, 17"; TFT, digital flat panel
display, high-resolution screens, desk top
COM94933
8TRACK, blinds for windowsTRA90011
Activity DataBase 01/03/2017
M0410Room Data SheetADB
Project: 7857 7857 Nottingham Uni Medical Centre
Department: PRI Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
Room: M0410 Photocoping/printing room
Room Number: Revision Date: 01/03/2017
1) Carrying out printing activities.
2) Carrying out photocopying activities.
3) Shredding documents.
4) Stationery/paper is stored.
Activities:
Personnel: 1 x staff.
Intermittent use.
Planning
Relationships:
Within an administration space.
Space Data: Height (mm): 6.00 2,400Area (m²):
Notes: One photocopy/printing room, with multifunctional printer/copier and storage for
paper/printing supplies, for every 32 workstations.
.
Separate data and voice outlets may be used where structure cabling solutions are not
available.
ADB Group Definitions:
1. Contractor supply and install.
2. Supply by others, contractor install.
3. UoN supply – loose equipment and specialist equipment (chairs, drawer units,
non-fixed medical equipment).
4. NHS IT equipment (nil cost to the project).
5. Dental supply and install.
6. Pharmacy supply and install.
7. UoN IT support and install.
8. UoN supply and install (tacks and blinds; fire extinguishers; UoN signage.
9. UoN F.O.C.
Activity DataBase 01/03/2017
7857 Nottingham Uni Medical Centre7857Project:
Room Environmental Data M0410ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: M0410 Photocoping/printing room
Room Number: Revision Date: 01/03/2017
Permissible Space Temerature Range(dry bulb) (degC):
TEMPERATURE AND VENTILATION Requirements Notes
18 - 28
Heating Design Temperature (dry bulb)(degC): 21
Minimum Air Changes (AC/hr): 6
Ventilation Type: S/E
Bal or -vePressure Relative to Adjoining Space:
G4Supply Air: Final Filter Class
Permisiible Relative Humidity Range (%):
General Notes:
LIGHTINGType Of Control: S/N
Daytime General Service Illuminance (Lux): 300
Daytime Specific Service Illuminance (Lux):
Nighttime General Service Illuminance (Lux):
Nighttime Specific Service Illuminance (Lux):
Local Task Illuminance (Lux):
Colour Rendering Required: Y
Colour Rendering Required Characteristics (Ra): 80
Unified Glare Rating Limit (UGRL): 19
Emergency Escape Route Lighting Required: In accordance with BS 5266 and Health Technical
MemorandumsY
Standby Lighting Grade - General Lighting: B
Standby Lighting Grade - Local Lighting:
General Notes:
RISKClinical Risk Category:
Non-clinical Business Continuity Risk Category:
General Notes:
Noise Intrusion (dB) 1hr day:
NOISE
Noise Intrusion (dB) 1hr night:
Noise Intrusion (dB) f night:
50
-
-
Maximum Internal Noise from M&E Services (NR): 35 Total noise of MEP services under normal operation across
the range 63Hz to 4kHz inclusive.
Room Sound-insulation Parameters - Privacy:
Room Sound-insulation Parameters - Noise Generation:
Not Private
High
Reference to Table 3 of the Department of Health 'Acoustics:
Technical design manual 4032:0.6:England'.
Noise Sensitiviy: Not Sensitive
Sound-insulation Rating (dB D nT,w):
General Notes:
Maximum Surface Temperature (DegC):
SAFETY/FIRE
82
Domestic Hot Water Discharge Temperature (DegC): 60
Maximum Cold Water Discharge Temperature (DegC): <20
General Notes:
Type of Automatic Fire Detection: Smoke
General Notes:
Activity DataBase 01/03/2017
ADB Room Design Character M0410
Project: 7857 7857 Nottingham Uni Medical Centre
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Photocoping/printing roomM0410Room:
01/03/2017Revision Date:Room Number:
Walls: Wall finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Wall finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Floor: Floor finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Floor finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Ceiling: Ceiling finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Ceiling finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Doorsets: Configuration, glazing, fire rating, security, etc. to be determined by Project Team.
HTM 58 (Mar-2005)
Refer to HBN 00-04 (May-2007) for effective clear door widths.
1 doorset:
1 x personnel, wheelchair & equipment access (1000mm)
Windows: Not required
Internal Glazing: Not required
Hatch: Not required
Notes: All finishes selected must have an appropriate risk assessment to accompany the design
decision.
Infection Control must be consulted as described in Performance Requirements for Building
Elements Used in Healthcare Facilities 8941:0.6 England.
Activity DataBase 01/03/2017
Schedule of Components by Room
Project: 7857 7857 Nottingham Uni Medical Centre
M0410ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: M0410 Photocoping/printing room
Room Number: Revision Date: 01/03/2017
Key: (n-old qty) Deletions m-new qty Additions m (n) Quantity changes since audit dateAudit Date: 2-Mar-2017
DescriptionCodeTotalTransNew
GrpAlt. CodeQuantity
1BOARD, display/notice, wall mounted, 900H 1200WBOA01311
1SOCKET outlet, switched, 13 amp, twinOUT01011
1SOCKET outlet data/voice, double.OUT13111
1SHELF, 600W 300DSHE20111
1SHELF, 900W 300DSHE21111
1WORKTOP, clinical, for 400 facing modular storage
cabinets, 600W 700D
SMW06611
1STORAGE UNIT, pigeon holes, 48 people, to
specialist design
STF90011
4PRINTER multifunction, network, floor standing, zone
1800W 750D
PRI91011
Activity DataBase 01/03/2017
M0724-01Room Data SheetADB
Project: 7857 7857 Nottingham Uni Medical Centre
Department: PRI Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
Room: M0724-01 Interview room: 4 places (including 1 wheelchair place)
Room Number: Revision Date: 01/03/2017
1) Discussions and interviews may take place.
2) Telephone(s) may be used.
3) Laptop computer(s) may be used.
4) Call systems may be used.
Activities:
Personnel: Up to 4 x persons.
Planning
Relationships:
Space Data: Height (mm): 8.00 2,400Area (m²):
Notes: The call repeat lamp is situated over the door outside the room.
The following items are shown on the room layout but are optional:
- staff emergency call (not required if the room is for staff use only);
- telephone (should not be provided in rooms intended as quiet spaces);
- room in use switch and indicator.
The following items may be provided:
- a clinical wash-hand basin and gel dispenser to allow for clinical use of the room;
.
Separate data and voice outlets may be used where structure cabling solutions are not
available.
ADB Group Definitions:
1. Contractor supply and install.
2. Supply by others, contractor install.
3. UoN supply – loose equipment and specialist equipment (chairs, drawer units,
non-fixed medical equipment).
4. NHS IT equipment (nil cost to the project).
5. Dental supply and install.
6. Pharmacy supply and install.
7. UoN IT support and install.
8. UoN supply and install (tacks and blinds; fire extinguishers; UoN signage.
9. UoN F.O.C.
Activity DataBase 01/03/2017
7857 Nottingham Uni Medical Centre7857Project:
Room Environmental Data M0724-01ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: M0724-01 Interview room: 4 places (including 1 wheelchair place)
Room Number: Revision Date: 01/03/2017
Permissible Space Temerature Range(dry bulb) (degC):
TEMPERATURE AND VENTILATION Requirements Notes
18 - 28
Heating Design Temperature (dry bulb)(degC): 21
Minimum Air Changes (AC/hr): 6
Ventilation Type: S/E/N
Bal or -vePressure Relative to Adjoining Space:
G4Supply Air: Final Filter Class
Permisiible Relative Humidity Range (%):
General Notes:
LIGHTINGType Of Control: N
Daytime General Service Illuminance (Lux): 300
Daytime Specific Service Illuminance (Lux):
Nighttime General Service Illuminance (Lux):
Nighttime Specific Service Illuminance (Lux):
Local Task Illuminance (Lux):
Colour Rendering Required: Y
Colour Rendering Required Characteristics (Ra): 80
Unified Glare Rating Limit (UGRL): 19
Emergency Escape Route Lighting Required: In accordance with BS 5266 and Health Technical
MemorandumsY
Standby Lighting Grade - General Lighting: B
Standby Lighting Grade - Local Lighting:
General Notes:
RISKClinical Risk Category:
Non-clinical Business Continuity Risk Category:
General Notes:
Noise Intrusion (dB) 1hr day:
NOISE
Noise Intrusion (dB) 1hr night:
Noise Intrusion (dB) f night:
40
-
-
Maximum Internal Noise from M&E Services (NR): 35 Total noise of MEP services under normal operation across
the range 63Hz to 4kHz inclusive.
Room Sound-insulation Parameters - Privacy:
Room Sound-insulation Parameters - Noise Generation:
Confidential
Typical
Reference to Table 3 of the Department of Health 'Acoustics:
Technical design manual 4032:0.6:England'.
Noise Sensitiviy: Medium
Sound-insulation Rating (dB D nT,w):
General Notes:
Maximum Surface Temperature (DegC):
SAFETY/FIRE
43
Domestic Hot Water Discharge Temperature (DegC): 43
Maximum Cold Water Discharge Temperature (DegC): <20
General Notes:
Type of Automatic Fire Detection: Smoke
General Notes:
Activity DataBase 01/03/2017
ADB Room Design Character M0724-01
Project: 7857 7857 Nottingham Uni Medical Centre
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Interview room: 4 places (including 1 wheelchair place)M0724-01Room:
01/03/2017Revision Date:Room Number:
Walls: Wall finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Wall finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Floor: Floor finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Floor finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Ceiling: Ceiling finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Ceiling finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Doorsets: Configuration, glazing, fire rating, security, etc. to be determined by Project Team.
HTM 58 (Mar-2005)
Refer to HBN 00-04 (May-2007) for effective clear door widths.
1 doorset:
1 x personnel, wheelchair & equipment access (1000mm)
Windows: Non-essential - Project Option
Clear glass with solar and privacy control
Designation to be validated against current documentation (HTM 55 archived).
Internal Glazing: Not required
Hatch: Not required
Notes: All finishes selected must have an appropriate risk assessment to accompany the design
decision.
Infection Control must be consulted as described in Performance Requirements for Building
Elements Used in Healthcare Facilities 8941:0.6 England.
Activity DataBase 01/03/2017
Schedule of Components by Room
Project: 7857 7857 Nottingham Uni Medical Centre
M0724-01ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: M0724-01 Interview room: 4 places (including 1 wheelchair place)
Room Number: Revision Date: 01/03/2017
Key: (n-old qty) Deletions m-new qty Additions m (n) Quantity changes since audit dateAudit Date: 2-Mar-2017
DescriptionCodeTotalTransNew
GrpAlt. CodeQuantity
1BOARD, display/notice, wall mounted, 900H 1200WBOA01311
1PULL/PUSH BUTTON, staff emergency call, reset
and integral/adjacent indicator lamp
CAL00711
1LAMP, repeat call, patient/staff or staff emergency or
cardiac call
CAL03411
1DESK UNIT, cantilever, cable management,
adjustable legs, modesty panel, 1400W 700D
DES02611
1HOOK, single, small, wall mountedHOO01944
1ILLUMINATED SIGN, 'Room in use'LIG07311
1SOCKET outlet, switched, 13 amp, singleOUT00511
1SOCKET outlet, switched, 13 amp, twinOUT01033
1SOCKET outlet data/voice, double.OUT13122
1SWITCH, lightSWC02511
1SWITCH, 'Room in use' illuminated sign.SWC07611
3CHAIR, swivel, height adjustable, high back, with
arms, wipeable, 5 star base, on castors
CHA30111
3CHAIR, upright, with arms, upholstered, stacking,
wipeable
CHA31833
3DRAWER UNIT, 3 drawer, lockable, on castors, desk
height 715H 430W 600D
DRA05711
3TABLE, occasional, circular, 415H 600mm dia.TAB90011
4COMPUTER KEYBOARDCOM03311
4COMPUTER MONITOR, 17"; TFT, digital flat panel
display, high-resolution screens, desk top
COM04922
Activity DataBase 01/03/2017
M0724-02Room Data SheetADB
Project: 7857 7857 Nottingham Uni Medical Centre
Department: PRI Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
Room: M0724-02 Interview room: 4 places (including 1 wheelchair place)
Room Number: Revision Date: 01/03/2017
1) Discussions and interviews may take place.
2) Telephone(s) may be used.
3) Laptop computer(s) may be used.
4) Call systems may be used.
Activities:
Personnel: Up to 4 x persons.
Planning
Relationships:
Space Data: Height (mm): 8.00 2,400Area (m²):
Notes: The call repeat lamp is situated over the door outside the room.
The following items are shown on the room layout but are optional:
- staff emergency call (not required if the room is for staff use only);
- telephone (should not be provided in rooms intended as quiet spaces);
- room in use switch and indicator.
The following items may be provided:
- a clinical wash-hand basin and gel dispenser to allow for clinical use of the room;
.
Separate data and voice outlets may be used where structure cabling solutions are not
available.
ADB Group Definitions:
1. Contractor supply and install.
2. Supply by others, contractor install.
3. UoN supply – loose equipment and specialist equipment (chairs, drawer units,
non-fixed medical equipment).
4. NHS IT equipment (nil cost to the project).
5. Dental supply and install.
6. Pharmacy supply and install.
7. UoN IT support and install.
8. UoN supply and install (tacks and blinds; fire extinguishers; UoN signage.
9. UoN F.O.C.
Activity DataBase 01/03/2017
7857 Nottingham Uni Medical Centre7857Project:
Room Environmental Data M0724-02ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: M0724-02 Interview room: 4 places (including 1 wheelchair place)
Room Number: Revision Date: 01/03/2017
Permissible Space Temerature Range(dry bulb) (degC):
TEMPERATURE AND VENTILATION Requirements Notes
18 - 28
Heating Design Temperature (dry bulb)(degC): 21
Minimum Air Changes (AC/hr): 6
Ventilation Type: S/E/N
Bal or -vePressure Relative to Adjoining Space:
G4Supply Air: Final Filter Class
Permisiible Relative Humidity Range (%):
General Notes:
LIGHTINGType Of Control: N
Daytime General Service Illuminance (Lux): 300
Daytime Specific Service Illuminance (Lux):
Nighttime General Service Illuminance (Lux):
Nighttime Specific Service Illuminance (Lux):
Local Task Illuminance (Lux):
Colour Rendering Required: Y
Colour Rendering Required Characteristics (Ra): 80
Unified Glare Rating Limit (UGRL): 19
Emergency Escape Route Lighting Required: In accordance with BS 5266 and Health Technical
MemorandumsY
Standby Lighting Grade - General Lighting: B
Standby Lighting Grade - Local Lighting:
General Notes:
RISKClinical Risk Category:
Non-clinical Business Continuity Risk Category:
General Notes:
Noise Intrusion (dB) 1hr day:
NOISE
Noise Intrusion (dB) 1hr night:
Noise Intrusion (dB) f night:
40
-
-
Maximum Internal Noise from M&E Services (NR): 35 Total noise of MEP services under normal operation across
the range 63Hz to 4kHz inclusive.
Room Sound-insulation Parameters - Privacy:
Room Sound-insulation Parameters - Noise Generation:
Confidential
Typical
Reference to Table 3 of the Department of Health 'Acoustics:
Technical design manual 4032:0.6:England'.
Noise Sensitiviy: Medium
Sound-insulation Rating (dB D nT,w):
General Notes:
Maximum Surface Temperature (DegC):
SAFETY/FIRE
43
Domestic Hot Water Discharge Temperature (DegC): 43
Maximum Cold Water Discharge Temperature (DegC): <20
General Notes:
Type of Automatic Fire Detection: Smoke
General Notes:
Activity DataBase 01/03/2017
ADB Room Design Character M0724-02
Project: 7857 7857 Nottingham Uni Medical Centre
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Interview room: 4 places (including 1 wheelchair place)M0724-02Room:
01/03/2017Revision Date:Room Number:
Walls: Wall finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Wall finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Floor: Floor finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Floor finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Ceiling: Ceiling finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Ceiling finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Doorsets: Configuration, glazing, fire rating, security, etc. to be determined by Project Team.
HTM 58 (Mar-2005)
Refer to HBN 00-04 (May-2007) for effective clear door widths.
1 doorset:
1 x personnel, wheelchair & equipment access (1000mm)
Windows: Non-essential - Project Option
Clear glass with solar and privacy control
Designation to be validated against current documentation (HTM 55 archived).
Internal Glazing: Not required
Hatch: Not required
Notes: All finishes selected must have an appropriate risk assessment to accompany the design
decision.
Infection Control must be consulted as described in Performance Requirements for Building
Elements Used in Healthcare Facilities 8941:0.6 England.
Activity DataBase 01/03/2017
Schedule of Components by Room
Project: 7857 7857 Nottingham Uni Medical Centre
M0724-02ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: M0724-02 Interview room: 4 places (including 1 wheelchair place)
Room Number: Revision Date: 01/03/2017
Key: (n-old qty) Deletions m-new qty Additions m (n) Quantity changes since audit dateAudit Date: 2-Mar-2017
DescriptionCodeTotalTransNew
GrpAlt. CodeQuantity
1CUPBOARD, 1 shelf, lockable, on plinth, 750H 600W
500D
CUP02144
1OUTLET cable, fused, 13 amp, ceiling mountedOUT00411
1SOCKET outlet, switched, 13 amp, twinOUT01033
1SOCKET outlet data/voice, double.OUT13122
1SOCKET outlet, computer data, single, ceiling
mounted
OUT13511
1WORKTOP, non-clinical, 2400W 600DWRT02411
2BOARD, marker, whiteboard, dry-wipe, with pen
holder, wall mounted, 1200H1800W
BOA00611
3CHAIR, upright, with arms, upholstered, stacking,
wipeable
CHA31866
3TABLE, 710H 1800W 900DTAB01411
770 inch screen to be controlled by local laptopSCR90111
8TRACK, blinds for windowsTRA90033
Activity DataBase 01/03/2017
M0724-03Room Data SheetADB
Project: 7857 7857 Nottingham Uni Medical Centre
Department: PRI Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
Room: M0724-03 MH Interview (based on Interview room: 4 places (including 1 wheelchair
place))
Room Number: Revision Date: 01/03/2017
1) Discussions and interviews may take place.
2) Telephone(s) may be used.
3) Laptop computer(s) may be used.
4) Call systems may be used.
Activities:
Personnel: Up to 4 x persons.
Planning
Relationships:
Space Data: Height (mm): 8.00 2,400Area (m²):
Notes: The call repeat lamp is situated over the door outside the room.
The following items are shown on the room layout but are optional:
- staff emergency call (not required if the room is for staff use only);
- telephone (should not be provided in rooms intended as quiet spaces);
- room in use switch and indicator.
The following items may be provided:
- a clinical wash-hand basin and gel dispenser to allow for clinical use of the room;
.
Separate data and voice outlets may be used where structure cabling solutions are not
available.
ADB Group Definitions:
1. Contractor supply and install.
2. Supply by others, contractor install.
3. UoN supply – loose equipment and specialist equipment (chairs, drawer units,
non-fixed medical equipment).
4. NHS IT equipment (nil cost to the project).
5. Dental supply and install.
6. Pharmacy supply and install.
7. UoN IT support and install.
8. UoN supply and install (tacks and blinds; fire extinguishers; UoN signage.
9. UoN F.O.C.
Activity DataBase 01/03/2017
7857 Nottingham Uni Medical Centre7857Project:
Room Environmental Data M0724-03ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: M0724-03 MH Interview (based on Interview room: 4 places (including 1 wheelchair
place))
Room Number: Revision Date: 01/03/2017
Permissible Space Temerature Range(dry bulb) (degC):
TEMPERATURE AND VENTILATION Requirements Notes
18 - 28
Heating Design Temperature (dry bulb)(degC): 21
Minimum Air Changes (AC/hr): 6
Ventilation Type: S/E/N
Bal or -vePressure Relative to Adjoining Space:
G4Supply Air: Final Filter Class
Permisiible Relative Humidity Range (%):
General Notes:
LIGHTINGType Of Control: N
Daytime General Service Illuminance (Lux): 300
Daytime Specific Service Illuminance (Lux):
Nighttime General Service Illuminance (Lux):
Nighttime Specific Service Illuminance (Lux):
Local Task Illuminance (Lux):
Colour Rendering Required: Y
Colour Rendering Required Characteristics (Ra): 80
Unified Glare Rating Limit (UGRL): 19
Emergency Escape Route Lighting Required: In accordance with BS 5266 and Health Technical
MemorandumsY
Standby Lighting Grade - General Lighting: B
Standby Lighting Grade - Local Lighting:
General Notes:
RISKClinical Risk Category:
Non-clinical Business Continuity Risk Category:
General Notes:
Noise Intrusion (dB) 1hr day:
NOISE
Noise Intrusion (dB) 1hr night:
Noise Intrusion (dB) f night:
40
-
-
Maximum Internal Noise from M&E Services (NR): 35 Total noise of MEP services under normal operation across
the range 63Hz to 4kHz inclusive.
Room Sound-insulation Parameters - Privacy:
Room Sound-insulation Parameters - Noise Generation:
Confidential
Typical
Reference to Table 3 of the Department of Health 'Acoustics:
Technical design manual 4032:0.6:England'.
Noise Sensitiviy: Medium
Sound-insulation Rating (dB D nT,w):
General Notes:
Maximum Surface Temperature (DegC):
SAFETY/FIRE
43
Domestic Hot Water Discharge Temperature (DegC): 43
Maximum Cold Water Discharge Temperature (DegC): <20
General Notes:
Type of Automatic Fire Detection: Smoke
General Notes:
Activity DataBase 01/03/2017
ADB Room Design Character M0724-03
Project: 7857 7857 Nottingham Uni Medical Centre
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
MH Interview (based on Interview room: 4 places (including 1 wheelchair
place))
M0724-03Room:
01/03/2017Revision Date:Room Number:
Walls: Wall finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Wall finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Floor: Floor finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Floor finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Ceiling: Ceiling finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Ceiling finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Doorsets: Configuration, glazing, fire rating, security, etc. to be determined by Project Team.
HTM 58 (Mar-2005)
Refer to HBN 00-04 (May-2007) for effective clear door widths.
1 doorset:
1 x personnel, wheelchair & equipment access (1000mm)
Windows: Non-essential - Project Option
Clear glass with solar and privacy control
Designation to be validated against current documentation (HTM 55 archived).
Internal Glazing: Not required
Hatch: Not required
Notes: All finishes selected must have an appropriate risk assessment to accompany the design
decision.
Infection Control must be consulted as described in Performance Requirements for Building
Elements Used in Healthcare Facilities 8941:0.6 England.
Activity DataBase 01/03/2017
Schedule of Components by Room
Project: 7857 7857 Nottingham Uni Medical Centre
M0724-03ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: M0724-03 MH Interview (based on Interview room: 4 places (including 1 wheelchair
place))
Room Number: Revision Date: 01/03/2017
Key: (n-old qty) Deletions m-new qty Additions m (n) Quantity changes since audit dateAudit Date: 2-Mar-2017
DescriptionCodeTotalTransNew
GrpAlt. CodeQuantity
1BOARD, display/notice, wall mounted, 900H 1200WBOA01311
1BOARD, marker, whiteboard, dry-wipe, with pen
holder, wall mounted, 600H 900W
BOA13411
1PULL/PUSH BUTTON, staff emergency call, reset
and integral/adjacent indicator lamp
CAL00711
1LAMP, repeat call, patient/staff or staff emergency or
cardiac call
CAL03411
1DESK UNIT, cantilever, cable management,
adjustable legs, modesty panel, 1400W 700D
DES02611
1HOOK, single, small, wall mountedHOO01977
1ILLUMINATED SIGN, 'Room in use'LIG07311
1SOCKET outlet, switched, 13 amp, singleOUT00511
1SOCKET outlet, switched, 13 amp, twinOUT01033
1SOCKET outlet data/voice, double.OUT13133
1SWITCH, lightSWC02511
1SWITCH, 'Room in use' illuminated sign.SWC07611
3CABINET, filing, 2 drawer, 710H 800W 470DCAB02711
3CHAIR, swivel, height adjustable, high back, with
arms, wipeable, 5 star base, on castors
CHA30111
3CHAIR, upright, with arms, upholstered, stacking,
wipeable
CHA31822
3DRAWER UNIT, 3 drawer, lockable, on castors, desk
height 715H 430W 600D
DRA05711
3TABLE, occasional, circular, 415H 600mm dia.TAB90011
4COMPUTER KEYBOARDCOM03311
4COMPUTER MONITOR, 17"; TFT, digital flat panel
display, high-resolution screens, desk top
COM04922
8TRACK, blinds for windowsTRA90011
Activity DataBase 01/03/2017
M0724-04Room Data SheetADB
Project: 7857 7857 Nottingham Uni Medical Centre
Department: PRI Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
Room: M0724-04 UofN Service Area (based on Interview room: 4 places (including 1
wheelchair place))
Room Number: Revision Date: 01/03/2017
1) Discussions and interviews may take place.
2) Telephone(s) may be used.
3) Laptop computer(s) may be used.
4) Call systems may be used.
Activities:
Personnel: Up to 4 x persons.
Planning
Relationships:
Space Data: Height (mm): 8.00 2,400Area (m²):
Notes: The call repeat lamp is situated over the door outside the room.
The following items are shown on the room layout but are optional:
- staff emergency call (not required if the room is for staff use only);
- telephone (should not be provided in rooms intended as quiet spaces);
- room in use switch and indicator.
The following items may be provided:
- a clinical wash-hand basin and gel dispenser to allow for clinical use of the room;
.
Separate data and voice outlets may be used where structure cabling solutions are not
available.
ADB Group Definitions:
1. Contractor supply and install.
2. Supply by others, contractor install.
3. UoN supply – loose equipment and specialist equipment (chairs, drawer units,
non-fixed medical equipment).
4. NHS IT equipment (nil cost to the project).
5. Dental supply and install.
6. Pharmacy supply and install.
7. UoN IT support and install.
8. UoN supply and install (tacks and blinds; fire extinguishers; UoN signage.
9. UoN F.O.C.
Activity DataBase 01/03/2017
7857 Nottingham Uni Medical Centre7857Project:
Room Environmental Data M0724-04ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: M0724-04 UofN Service Area (based on Interview room: 4 places (including 1
wheelchair place))
Room Number: Revision Date: 01/03/2017
Permissible Space Temerature Range(dry bulb) (degC):
TEMPERATURE AND VENTILATION Requirements Notes
18 - 28
Heating Design Temperature (dry bulb)(degC): 21
Minimum Air Changes (AC/hr): 6
Ventilation Type: S/E/N
Bal or -vePressure Relative to Adjoining Space:
G4Supply Air: Final Filter Class
Permisiible Relative Humidity Range (%):
General Notes:
LIGHTINGType Of Control: N
Daytime General Service Illuminance (Lux): 300
Daytime Specific Service Illuminance (Lux):
Nighttime General Service Illuminance (Lux):
Nighttime Specific Service Illuminance (Lux):
Local Task Illuminance (Lux):
Colour Rendering Required: Y
Colour Rendering Required Characteristics (Ra): 80
Unified Glare Rating Limit (UGRL): 19
Emergency Escape Route Lighting Required: In accordance with BS 5266 and Health Technical
MemorandumsY
Standby Lighting Grade - General Lighting: B
Standby Lighting Grade - Local Lighting:
General Notes:
RISKClinical Risk Category:
Non-clinical Business Continuity Risk Category:
General Notes:
Noise Intrusion (dB) 1hr day:
NOISE
Noise Intrusion (dB) 1hr night:
Noise Intrusion (dB) f night:
40
-
-
Maximum Internal Noise from M&E Services (NR): 35 Total noise of MEP services under normal operation across
the range 63Hz to 4kHz inclusive.
Room Sound-insulation Parameters - Privacy:
Room Sound-insulation Parameters - Noise Generation:
Confidential
Typical
Reference to Table 3 of the Department of Health 'Acoustics:
Technical design manual 4032:0.6:England'.
Noise Sensitiviy: Medium
Sound-insulation Rating (dB D nT,w):
General Notes:
Maximum Surface Temperature (DegC):
SAFETY/FIRE
43
Domestic Hot Water Discharge Temperature (DegC): 43
Maximum Cold Water Discharge Temperature (DegC): <20
General Notes:
Type of Automatic Fire Detection: Smoke
General Notes:
Activity DataBase 01/03/2017
ADB Room Design Character M0724-04
Project: 7857 7857 Nottingham Uni Medical Centre
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
UofN Service Area (based on Interview room: 4 places (including 1
wheelchair place))
M0724-04Room:
01/03/2017Revision Date:Room Number:
Walls: Wall finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Wall finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Floor: Floor finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Floor finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Ceiling: Ceiling finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Ceiling finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Doorsets: Configuration, glazing, fire rating, security, etc. to be determined by Project Team.
HTM 58 (Mar-2005)
Refer to HBN 00-04 (May-2007) for effective clear door widths.
1 doorset:
1 x personnel, wheelchair & equipment access (1000mm)
Windows: Non-essential - Project Option
Clear glass with solar and privacy control
Designation to be validated against current documentation (HTM 55 archived).
Internal Glazing: Not required
Hatch: Not required
Notes: All finishes selected must have an appropriate risk assessment to accompany the design
decision.
Infection Control must be consulted as described in Performance Requirements for Building
Elements Used in Healthcare Facilities 8941:0.6 England.
Activity DataBase 01/03/2017
Schedule of Components by Room
Project: 7857 7857 Nottingham Uni Medical Centre
M0724-04ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: M0724-04 UofN Service Area (based on Interview room: 4 places (including 1 wheelchair
place))
Room Number: Revision Date: 01/03/2017
Key: (n-old qty) Deletions m-new qty Additions m (n) Quantity changes since audit dateAudit Date: 2-Mar-2017
DescriptionCodeTotalTransNew
GrpAlt. CodeQuantity
1BOARD, display/notice, wall mounted, 900H 1200WBOA01311
1BOARD, marker, whiteboard, dry-wipe, with pen
holder, wall mounted, 600H 900W
BOA13411
1PULL/PUSH BUTTON, staff emergency call, reset
and integral/adjacent indicator lamp
CAL00711
1LAMP, repeat call, patient/staff or staff emergency or
cardiac call
CAL03411
1DESK UNIT, cantilever, cable management,
adjustable legs, modesty panel, 1400W 700D
DES02611
1HOOK, single, small, wall mountedHOO01944
1ILLUMINATED SIGN, 'Room in use'LIG07311
1SOCKET outlet, switched, 13 amp, singleOUT00511
1SOCKET outlet, switched, 13 amp, twinOUT01011
1SOCKET outlet data/voice, double.OUT13111
1SWITCH, lightSWC02511
1SWITCH, 'Room in use' illuminated sign.SWC07611
3CABINET, filing, 2 drawer, 710H 800W 470DCAB02711
3CHAIR, upright, with arms, upholstered, stacking,
wipeable
CHA31833
3DRAWER UNIT, 2 drawer, lockable, on castors,
600H 410W 600D
DRA05611
3TABLE, occasional, circular, 415H 600mm dia.TAB90011
7COMPUTER KEYBOARDCOM83311
7COMPUTER MONITOR, 17"; TFT, digital flat panel
display, high-resolution screens, desk top
COM84911
8TRACK, blinds for windowsTRA90011
Activity DataBase 01/03/2017
N0111Room Data SheetADB
Project: 7857 7857 Nottingham Uni Medical Centre
Department: PRI Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
Room: N0111 Enhanced procedures room
Room Number: Revision Date: 01/03/2017
1) Patient is positioned on the operating table.
2) Surgical instruments on instrument trolley may be used.
3) Medical and surgical supplies are stored.
4) Viewing diagnostic images on VDT.
5) Used swabs may be checked, weighed and recorded.
6) Operating lists may be displayed.
7) Patient records may be reviewed and recorded.
8) Patient is transferred from operating table to bed/trolley.
9) Computer workstation(s) may be used.
10) Telephone(s) may be used.
11) Administration of sedation.
12) Minor surgical procedures may be performed under local anaesthetic.
13) Patient may arrive on foot or in a wheelchair.
14) Administration of sedation.
Activities:
Personnel: 1 x patient
4 x staff
Planning
Relationships:
Access to a separate preparation facility is optional depending on the nature/volume of
procedures to be undertaken
Space Data: Height (mm): 20.00 3,000Area (m²):
Notes: Separate data and voice outlets may be used where structure cabling solutions are not
available.
ADB Group Definitions:
1. Contractor supply and install.
2. Supply by others, contractor install.
3. UoN supply – loose equipment and specialist equipment (chairs, drawer units,
non-fixed medical equipment).
4. NHS IT equipment (nil cost to the project).
5. Dental supply and install.
6. Pharmacy supply and install.
7. UoN IT support and install.
8. UoN supply and install (tacks and blinds; fire extinguishers; UoN signage.
9. UoN F.O.C.
Activity DataBase 01/03/2017
7857 Nottingham Uni Medical Centre7857Project:
Room Environmental Data N0111ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: N0111 Enhanced procedures room
Room Number: Revision Date: 01/03/2017
Permissible Space Temerature Range(dry bulb) (degC):
TEMPERATURE AND VENTILATION Requirements Notes
18 - 25
Heating Design Temperature (dry bulb)(degC): 22
Minimum Air Changes (AC/hr): 10
Ventilation Type: S
+vePressure Relative to Adjoining Space:
F7Supply Air: Final Filter Class
Permisiible Relative Humidity Range (%):
General Notes:
LIGHTINGType Of Control: S/V
Daytime General Service Illuminance (Lux): 1000
Daytime Specific Service Illuminance (Lux): 500
Nighttime General Service Illuminance (Lux):
Nighttime Specific Service Illuminance (Lux):
Local Task Illuminance (Lux): 30000 to 60000
Colour Rendering Required: Y
Colour Rendering Required Characteristics (Ra): 90
Unified Glare Rating Limit (UGRL): 19
Emergency Escape Route Lighting Required: In accordance with BS 5266 and Health Technical
MemorandumsY
Standby Lighting Grade - General Lighting: A
AStandby Lighting Grade - Local Lighting:
General Notes: Refer to SLL Lighting Guide 2 for more detailed guidance
RISKClinical Risk Category:
Non-clinical Business Continuity Risk Category:
General Notes:
Noise Intrusion (dB) 1hr day:
NOISE
Noise Intrusion (dB) 1hr night:
Noise Intrusion (dB) f night:
40
40
50
The LAmax,f dB noise limit applies at any time.
Maximum Internal Noise from M&E Services (NR): 40 Total noise of MEP services under normal operation across
the range 63Hz to 4kHz inclusive.
Room Sound-insulation Parameters - Privacy:
Room Sound-insulation Parameters - Noise Generation:
Private
Typical
Reference to Table 3 of the Department of Health 'Acoustics:
Technical design manual 4032:0.6:England'.
Noise Sensitiviy: Sensitive
Sound-insulation Rating (dB D nT,w):
General Notes:
Maximum Surface Temperature (DegC):
SAFETY/FIRE
43
Domestic Hot Water Discharge Temperature (DegC): 43
Maximum Cold Water Discharge Temperature (DegC): <20
General Notes:
Type of Automatic Fire Detection: Smoke Duct mounted on Supply
General Notes:
Activity DataBase 01/03/2017
ADB Room Design Character N0111
Project: 7857 7857 Nottingham Uni Medical Centre
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Enhanced procedures roomN0111Room:
01/03/2017Revision Date:Room Number:
Walls: Wall finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Wall finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Floor: Floor finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Floor finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Ceiling: Ceiling finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Ceiling finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Doorsets: Configuration, glazing, fire rating, security, etc. to be determined by Project Team.
HTM 58 (Mar-2005)
Refer to HBN 00-04 (May-2007) for effective clear door widths.
2 sets of doors:
1 x personnel, wheelchair & equipment access (1000mm);
1 x personnel, bed, trolley, wheelchair & equipment access (1500mm)
Windows: Non-essential - Project Option
Obscured glass with solar control
Designation to be validated against current documentation (HTM 55 archived).
Internal Glazing: Not required
Hatch: Not required
Notes: All finishes selected must have an appropriate risk assessment to accompany the design
decision.
Infection Control must be consulted as described in Performance Requirements for Building
Elements Used in Healthcare Facilities 8941:0.6 England.
Activity DataBase 01/03/2017
Schedule of Components by Room
Project: 7857 7857 Nottingham Uni Medical Centre
N0111ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: N0111 Enhanced procedures room
Room Number: Revision Date: 01/03/2017
Key: (n-old qty) Deletions m-new qty Additions m (n) Quantity changes since audit dateAudit Date: 2-Mar-2017
DescriptionCodeTotalTransNew
GrpAlt. CodeQuantity
1BASIN, medium, hospital pattern, vitreous china, no
tap holes, no overflow, integral back outlet, 500W
400D.
BAS10111
1BOARD, marker, whiteboard, dry-wipe, with pen
holder, wall mounted, 600H 900W
BOA13422
1PULL/PUSH BUTTON, staff emergency call, reset
and integral/adjacent indicator lamp
CAL00711
1LAMP, repeat call, patient/staff or staff emergency or
cardiac call
CAL03411
1DESK UNIT, cantilever, cable management,
adjustable legs, modesty panel, 1400W 700D
DES02611
1LUMINAIRE operating (minor)LIG05011
1ILLUMINATED SIGN, 'Room in use'LIG07311
1SOCKET outlet, switched, 13 amp, singleOUT00511
1SOCKET outlet, switched, 13 amp, twinOUT01066
1CONNECTION UNIT, switched, 13 amp, flex outletOUT04911
1SOCKET outlet data/voice, double.OUT13111
1CABINET, base, modular storage, for 400 facing
inserts, with door, on plinth, 900H
SMC01311
1CABINET, upper, modular storage, for 400 facing
inserts, with door, 750H
SMC02333
1WORKTOP, clinical, for 3 x 400 facing modular
storage cabinets, 1365W 700D
SMW05311
1SWITCH, lightSWC02511
1SWITCH, 'Room in use' illuminated sign.SWC07611
1TAP, bib, 2x8 mm thermostatic mixer, automatic
action, sensor operated, non-touch,
TAP89211
1TRAP, bottle, 1.1/4 in, plastic resealing.WAS10711
2DISPENSER, barrier cream, disposable single
cartridge, wall mounted
DIS01111
2DISPENSER, paper towel, wall mountedDIS01311
2DISPENSER, soap, disposable single cartridge, lever
action, wall mounted
DIS03011
2DISPENSER, disposable gloves set of 3 and
disposable apron, wall mounted
DIS43811
3CHAIR, swivel, height adjustable, medium back,
wipeable, 5 star base, on castors
CHA30211
3CHAIR, upright, upholstered, stacking, wipeableCHA31711
3HOLDER, sack, with lid foot operated, medium,
freestanding, 875H 430W 385D
HOL00622
3HOLDER, sharps box, up to 7 litre capacity,
rail/trolley hang or wall mounted, 170H 125W 100D
HOL02011
3KICKABOUT, bowl stand, stainless steel, 360mm
dia.
KIC00122
3REFRIGERATOR, capacity 160 litre, automatic
defrost, stainless steel, underbench, external
temperature gauge, lockable, on castors, 850H
610W 600D
REF05811
Activity DataBase 01/03/2017
Schedule of Components by Room
Project: 7857 7857 Nottingham Uni Medical Centre
N0111ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: N0111 Enhanced procedures room
Room Number: Revision Date: 01/03/2017
Key: (n-old qty) Deletions m-new qty Additions m (n) Quantity changes since audit dateAudit Date: 2-Mar-2017
DescriptionCodeTotalTransNew
GrpAlt. CodeQuantity
3TROLLEY, modular storage, single open frame,
including handle and worktop, with up to 5 sets of
runners for 600 facing inserts, 850H 730W 450D
SMT00211
3STAND, infusion, twin hook, breaks, mobileSTA14211
3STOOL, surgeon/anaesthetist, height adjustable,
includes anti-static seat pads
STO00622
3TABLE, surgical procedures, radiotranslucen,t o/a
1005H 2100W 835D
TAB07711
3TROLLEY, dressing/instrument, stainless steel,
buffered, 870H 750W 450D
TRO13311
3TROLLEY diathermy equipment, 1 shelf, 870H 490W
650D
TRO14011
4COMPUTER KEYBOARDCOM93311
4COMPUTER MONITOR, 17"; TFT, digital flat panel
display, high-resolution screens, desk top
COM94911
8TRACK, blinds for windowsTRA90022
Activity DataBase 01/03/2017
P0625Room Data SheetADB
Project: 7857 7857 Nottingham Uni Medical Centre
Department: PRI Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
Room: P0625 Pantry/refreshment area
Room Number: Revision Date: 01/03/2017
1) Preparing beverages/snacks with patients.
2) Microwave oven may be used.
3) Small amounts of dry goods are stored in cupboard(s).
4) Provision of refrigerated storage.
5) Trays, crockery and cutlery are stored.
6) Disposal of waste and contaminated materials.
7) Hand-rinse basin may be used.
Activities:
Personnel: 1 - 2 x persons.
Intermittent use.
Planning
Relationships:
Located in staff, patient or visitors areas as appropriate.
Space Data: Height (mm): 8.00 2,400Area (m²):
Notes: The following items are included on the room layout but are optional:
- a microwave oven;
- a dishwasher.
The layout is suitable for ambulant/semi-ambulant users, consideration must be given to
wheelchair user provision.
ADB Group Definitions:
1. Contractor supply and install.
2. Supply by others, contractor install.
3. UoN supply – loose equipment and specialist equipment (chairs, drawer units,
non-fixed medical equipment).
4. NHS IT equipment (nil cost to the project).
5. Dental supply and install.
6. Pharmacy supply and install.
7. UoN IT support and install.
8. UoN supply and install (tacks and blinds; fire extinguishers; UoN signage.
9. UoN F.O.C.
Activity DataBase 01/03/2017
7857 Nottingham Uni Medical Centre7857Project:
Room Environmental Data P0625ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: P0625 Pantry/refreshment area
Room Number: Revision Date: 01/03/2017
Permissible Space Temerature Range(dry bulb) (degC):
TEMPERATURE AND VENTILATION Requirements Notes
18 - 28
Heating Design Temperature (dry bulb)(degC): 21
Minimum Air Changes (AC/hr): 6
Ventilation Type: E
-vePressure Relative to Adjoining Space:
-Supply Air: Final Filter Class
Permisiible Relative Humidity Range (%):
General Notes:
LIGHTINGType Of Control: N
Daytime General Service Illuminance (Lux): 300
Daytime Specific Service Illuminance (Lux):
Nighttime General Service Illuminance (Lux):
Nighttime Specific Service Illuminance (Lux):
Local Task Illuminance (Lux):
Colour Rendering Required: Y
Colour Rendering Required Characteristics (Ra): 80
Unified Glare Rating Limit (UGRL): 22
Emergency Escape Route Lighting Required: In accordance with BS 5266 and Health Technical
MemorandumsY
Standby Lighting Grade - General Lighting: B
Standby Lighting Grade - Local Lighting:
General Notes:
RISKClinical Risk Category:
Non-clinical Business Continuity Risk Category:
General Notes:
Noise Intrusion (dB) 1hr day:
NOISE
Noise Intrusion (dB) 1hr night:
Noise Intrusion (dB) f night:
55
-
-
Maximum Internal Noise from M&E Services (NR): 40 Total noise of MEP services under normal operation across
the range 63Hz to 4kHz inclusive.
Room Sound-insulation Parameters - Privacy:
Room Sound-insulation Parameters - Noise Generation:
Not Private
Typical
Reference to Table 3 of the Department of Health 'Acoustics:
Technical design manual 4032:0.6:England'.
Noise Sensitiviy: Not Sensitive
Sound-insulation Rating (dB D nT,w):
General Notes:
Maximum Surface Temperature (DegC):
SAFETY/FIRE
43
Domestic Hot Water Discharge Temperature (DegC): 60
Maximum Cold Water Discharge Temperature (DegC): <20
General Notes:
Type of Automatic Fire Detection: Heat
General Notes:
Activity DataBase 01/03/2017
ADB Room Design Character P0625
Project: 7857 7857 Nottingham Uni Medical Centre
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Pantry/refreshment areaP0625Room:
01/03/2017Revision Date:Room Number:
Walls: Wall finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Wall finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Floor: Floor finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Floor finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Ceiling: Ceiling finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Ceiling finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Doorsets: Configuration, glazing, fire rating, security, etc. to be determined by Project Team.
HTM 58 (Mar-2005)
Refer to HBN 00-04 (May-2007) for effective clear door widths.
1 doorset:
1 x personnel, wheelchair & equipment access (1000mm)
Requirement for hinge protection when areas used by children
Windows: Not required
Internal Glazing: Not required
Hatch: Not required
Notes: All finishes selected must have an appropriate risk assessment to accompany the design
decision.
Infection Control must be consulted as described in Performance Requirements for Building
Elements Used in Healthcare Facilities 8941:0.6 England.
Activity DataBase 01/03/2017
Schedule of Components by Room
Project: 7857 7857 Nottingham Uni Medical Centre
P0625ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: P0625 Pantry/refreshment area
Room Number: Revision Date: 01/03/2017
Key: (n-old qty) Deletions m-new qty Additions m (n) Quantity changes since audit dateAudit Date: 2-Mar-2017
DescriptionCodeTotalTransNew
GrpAlt. CodeQuantity
1BASIN, small, stainless steel, apron front, 1 tap hole,
500W 400D
BAS01511
1CUPBOARD, base, with door, on plinth, 900H 400W
500D
CUP70311
1CUPBOARD, base, including sink panel, with door,
on plinth, 900H 600W 500D
CUP71511
1CUPBOARD/DRAWER UNIT, base, with door, on
plinth, 900H 600W 500D
CUP73122
1CUPBOARD, upper, with door, 600H 600W 300DCUP75322
1OUTLET cable, 13 ampOUT00222
1SOCKET outlet, switched, 13 amp, singleOUT00511
1SOCKET outlet, switched, 13 amp, twinOUT01022
1CONNECTION UNIT, switched, 13 amp, flex outletOUT04911
1CONNECTION UNIT, switched, 13 ampOUT05222
1OUTLET, cold water for equipmentOUT30122
1OUTLET, drainage, anti-syphonOUT34111
1SWITCH, lightSWC02511
1TAP, monobloc, pillar mixer, integral thermostatic,
short lever.
TAP28911
1TAP, pillar, high neck, long lever, pair hot and cold,
1/2 in.
TAP35911
1WASTE, unslotted flush-grated, metal, 1.1/4 in. .WAS10011
1WASTE, unslotted recessed grated, metal, 1.1/2 in,
with plug and chain
WAS10311
1TRAP, bottle, 1.1/4 in, plastic resealing.WAS10711
1TRAP, bottle, 1.1/2 in, plastic resealing.WAS10811
1WATER BOILER, 2.5 litre, electric, wall mountedWAT00311
1WORKTOP, dished, stainless steel, with integral left
of centre sink bowl and 2 tap holes, 3500W 600D
WRT23711
2DISPENSER, paper towel roll, wall mountedDIS00711
2DISPENSER, paper towel, wall mountedDIS01311
2DISPENSER, soap, wall mountedDIS02411
2DISHWASHER, under bench, high temperatureWAS06511
3HOLDER, sack, with lid foot operated, medium,
freestanding, 875H 430W 385D
HOL00622
3OVEN, microwave, heavy duty, 1600watt, capacity 26
litre, 370H 465W 560D
OVE01311
3REFRIGERATOR, capacity 160 litre, automatic
defrost, stainless steel, underbench, external
temperature gauge, lockable, on castors, 850H
610W 600D
REF05811
Activity DataBase 01/03/2017
R0902Room Data SheetADB
Project: 7857 7857 Nottingham Uni Medical Centre
Department: PRI Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
Room: R0902 Decontamination room: dirty instruments
Room Number: Revision Date: 01/03/2017
1) Soiled instruments may be cleansed, disinfected and sterilised
2) Sterilizer is loaded/unloaded.
3) Loading of medical devices into ultrasonic.
4) Cleaning endoscopes.
5) Automatic washing, disinfecting and sterilizing endoscopes.
6) Holding supplies of endoscope processing chemicals.
7) Sterilizing instruments and equipment.
8) Instruments or equipment are washed by hand.
9) Clinical wash-hand basin may be used.
10) Dispensing disposable aprons.
11) Dispensing disposable gloves.
Activities:
Personnel: Up to 2 staff.
Planning
Relationships:
Adjacent to decontamination suite clean instruments room
Space Data: Height (mm): 12.00 2,400Area (m²):
Notes: Reference should be made to HTM 01-01 and HTM 01-05 Decontamination in primary
care dental practices, figure 3 although it is believed that this room is suitable for other
similar decontamination purposes.
The room includes stainless steel worktops, where cleaning agents are used that may
damage stainless steel a solid core surface is recommended, subject to manufactures
and infection control recommendations.
Consideration must be given to COSHH requirements, appropriate PPE and any
necessary storage of cleaning supplies.
The following items are shown on the room layout but are optional:
- Ultrasonic cleaner. When not provided wash and rinse sinks should be located nearer
to each other to avoid manual handling risks.
The following items may be provided:
- COSHH cupboard for cleaning supplies.
ADB Group Definitions:
1. Contractor supply and install.
2. Supply by others, contractor install.
3. UoN supply – loose equipment and specialist equipment (chairs, drawer units,
non-fixed medical equipment).
4. NHS IT equipment (nil cost to the project).
5. Dental supply and install.
6. Pharmacy supply and install.
7. UoN IT support and install.
8. UoN supply and install (tacks and blinds; fire extinguishers; UoN signage.
9. UoN F.O.C.
Activity DataBase 01/03/2017
7857 Nottingham Uni Medical Centre7857Project:
Room Environmental Data R0902ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: R0902 Decontamination room: dirty instruments
Room Number: Revision Date: 01/03/2017
Permissible Space Temerature Range(dry bulb) (degC):
TEMPERATURE AND VENTILATION Requirements Notes
18 - 28
Heating Design Temperature (dry bulb)(degC): 21
Minimum Air Changes (AC/hr): 15
Ventilation Type: S/E
-vePressure Relative to Adjoining Space:
F9Supply Air: Final Filter Class
Permisiible Relative Humidity Range (%):
General Notes:
LIGHTINGType Of Control: N
Daytime General Service Illuminance (Lux): 300
Daytime Specific Service Illuminance (Lux):
Nighttime General Service Illuminance (Lux):
Nighttime Specific Service Illuminance (Lux):
Local Task Illuminance (Lux):
Colour Rendering Required: Y
Colour Rendering Required Characteristics (Ra): 80
Unified Glare Rating Limit (UGRL): 22
Emergency Escape Route Lighting Required: In accordance with BS 5266 and Health Technical
MemorandumsY
Standby Lighting Grade - General Lighting: B
Standby Lighting Grade - Local Lighting:
General Notes:
RISKClinical Risk Category:
Non-clinical Business Continuity Risk Category:
General Notes:
Noise Intrusion (dB) 1hr day:
NOISE
Noise Intrusion (dB) 1hr night:
Noise Intrusion (dB) f night:
45
-
-
Maximum Internal Noise from M&E Services (NR): 40 Total noise of MEP services under normal operation across
the range 63Hz to 4kHz inclusive.
Room Sound-insulation Parameters - Privacy:
Room Sound-insulation Parameters - Noise Generation:
Moderate
Typical
Reference to Table 3 of the Department of Health 'Acoustics:
Technical design manual 4032:0.6:England'.
Noise Sensitiviy: Medium
Sound-insulation Rating (dB D nT,w):
General Notes:
Maximum Surface Temperature (DegC):
SAFETY/FIRE
82
Domestic Hot Water Discharge Temperature (DegC): 41
Maximum Cold Water Discharge Temperature (DegC): <20
General Notes:
Type of Automatic Fire Detection: Smoke
General Notes:
Activity DataBase 01/03/2017
ADB Room Design Character R0902
Project: 7857 7857 Nottingham Uni Medical Centre
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Decontamination room: dirty instrumentsR0902Room:
01/03/2017Revision Date:Room Number:
Walls: Wall finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Wall finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Floor: Floor finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Floor finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Ceiling: Ceiling finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Ceiling finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Doorsets: Configuration, glazing, fire rating, security, etc. to be determined by Project Team.
HTM 58 (Mar-2005)
Refer to HBN 00-04 (May-2007) for effective clear door widths.
1 doorset:
1 x personnel & equipment access (1000mm)
Windows: Desirable - Project Option
Clear glass with solar control, sealed
Designation to be validated against current documentation (HTM 55 archived).
Internal Glazing: Not required
Hatch: Not required
Notes: All finishes selected must have an appropriate risk assessment to accompany the design
decision.
Infection Control must be consulted as described in Performance Requirements for Building
Elements Used in Healthcare Facilities 8941:0.6 England.
Activity DataBase 01/03/2017
Schedule of Components by Room
Project: 7857 7857 Nottingham Uni Medical Centre
R0902ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: R0902 Decontamination room: dirty instruments
Room Number: Revision Date: 01/03/2017
Key: (n-old qty) Deletions m-new qty Additions m (n) Quantity changes since audit dateAudit Date: 2-Mar-2017
DescriptionCodeTotalTransNew
GrpAlt. CodeQuantity
1BASIN, medium, hospital pattern, vitreous china, no
tap holes, no overflow, integral back outlet, 500W
400D.
BAS10111
1SOCKET outlet, switched, 13 amp, singleOUT00511
1SOCKET outlet, switched, 13 amp, twinOUT01011
1CONNECTION UNIT, switched, 13 amp, flex outletOUT04911
1CONNECTION UNIT switched 13amp, flex, indicator
light
OUT05911
1OUTLET isolator, equipment manufacturer's
specification
OUT07922
1SOCKET outlet data/voice, double.OUT13111
1SWITCH, lightSWC02511
1TAP, bib, lever, hospital pattern, pair hot and cold,
1/2 in.
TAP80922
1TAP, bib, 2x8 mm thermostatic mixer, automatic
action, sensor operated, non-touch,
TAP89211
1WASTE, unslotted flush-grated, metal, 1.1/2 in.WAS10222
1TRAP, bottle, 1.1/4 in, plastic resealing.WAS10711
1TRAP, bottle, 1.1/2 in, plastic resealing.WAS10822
1WORKTOP, plain, stainless steel, with 2 sink bowls
& drainer, 3000W 700D
WKT52711
5BOTTLE, eye irrigation, emergency, with internal
application, fix panel
BOT10111
5DISPENSER, barrier cream, disposable single
cartridge, wall mounted
DIS21111
5DISPENSER, disposable mask, wall mountedDIS53711
5HOLDER, sack, with lid foot operated, medium,
freestanding, 875H 430W 385D
HOL10622
5SCANNER: Bar-codeSCN10111
5REPROCESSOR, endoscope, pass throughSTE13311
5STERILIZER, built-in, pass-through autoclave, small
load
STE13511
5TRACK, blinds for windowsTRA90211
5TROLLEY, dressing/instrument, stainless steel,
buffered, 870H 450W 450D
TRO23122
5ULTRASONIC CLEANER, bench top, (tank size
150x495x280mm), Includes basket and stainless
steel lid, heated, 280H 535W 355D
ULT10611
Activity DataBase 01/03/2017
R0904Room Data SheetADB
Project: 7857 7857 Nottingham Uni Medical Centre
Department: PRI Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
Room: R0904 Decontamination room: clean instruments
Room Number: Revision Date: 01/03/2017
1) Clinical wash-hand basin may be used.
2) Sterilizer is loaded/unloaded.
3) Storage of flexible endoscopes in a security cupboard.
4) Processes and tests are recorded.
5) Secure storage of instruments.
Activities:
Personnel: Up to 2 x staff.
Planning
Relationships:
Adjacent to dirty instruments room
Space Data: Height (mm): 12.00 2,400Area (m²):
Notes: Reference should be made to HTM 01-01 and HTM 01-05 Decontamination in primary
care dental practices, figure 3 although it is believed that this room is suitable for other
similar decontamination purposes.
The room includes stainless steel worktops, where cleaning agents are used that may
damage stainless steel a solid core surface is recommended, subject to manufactures
and infection control recommendations.
Consideration must be given to COSHH requirements, appropriate PPE and any
necessary storage of cleaning supplies.
The following items may be provided:
- COSHH cupboard for cleaning supplies.
ADB Group Definitions:
1. Contractor supply and install.
2. Supply by others, contractor install.
3. UoN supply – loose equipment and specialist equipment (chairs, drawer units,
non-fixed medical equipment).
4. NHS IT equipment (nil cost to the project).
5. Dental supply and install.
6. Pharmacy supply and install.
7. UoN IT support and install.
8. UoN supply and install (tacks and blinds; fire extinguishers; UoN signage.
9. UoN F.O.C.
Activity DataBase 01/03/2017
7857 Nottingham Uni Medical Centre7857Project:
Room Environmental Data R0904ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: R0904 Decontamination room: clean instruments
Room Number: Revision Date: 01/03/2017
Permissible Space Temerature Range(dry bulb) (degC):
TEMPERATURE AND VENTILATION Requirements Notes
18 - 28
Heating Design Temperature (dry bulb)(degC): 21
Minimum Air Changes (AC/hr): 15
Ventilation Type: S/E
-vePressure Relative to Adjoining Space:
F9Supply Air: Final Filter Class
Permisiible Relative Humidity Range (%):
General Notes:
LIGHTINGType Of Control: N
Daytime General Service Illuminance (Lux): 300
Daytime Specific Service Illuminance (Lux):
Nighttime General Service Illuminance (Lux):
Nighttime Specific Service Illuminance (Lux):
Local Task Illuminance (Lux):
Colour Rendering Required: Y
Colour Rendering Required Characteristics (Ra): 80
Unified Glare Rating Limit (UGRL): 22
Emergency Escape Route Lighting Required: In accordance with BS 5266 and Health Technical
MemorandumsY
Standby Lighting Grade - General Lighting: B
Standby Lighting Grade - Local Lighting:
General Notes:
RISKClinical Risk Category:
Non-clinical Business Continuity Risk Category:
General Notes:
Noise Intrusion (dB) 1hr day:
NOISE
Noise Intrusion (dB) 1hr night:
Noise Intrusion (dB) f night:
45
-
-
Maximum Internal Noise from M&E Services (NR): 40 Total noise of MEP services under normal operation across
the range 63Hz to 4kHz inclusive.
Room Sound-insulation Parameters - Privacy:
Room Sound-insulation Parameters - Noise Generation:
Moderate
Typical
Reference to Table 3 of the Department of Health 'Acoustics:
Technical design manual 4032:0.6:England'.
Noise Sensitiviy: Medium
Sound-insulation Rating (dB D nT,w):
General Notes:
Maximum Surface Temperature (DegC):
SAFETY/FIRE
82
Domestic Hot Water Discharge Temperature (DegC): 41
Maximum Cold Water Discharge Temperature (DegC): <20
General Notes:
Type of Automatic Fire Detection: Smoke
General Notes:
Activity DataBase 01/03/2017
ADB Room Design Character R0904
Project: 7857 7857 Nottingham Uni Medical Centre
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Decontamination room: clean instrumentsR0904Room:
01/03/2017Revision Date:Room Number:
Walls: Wall finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Wall finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Floor: Floor finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Floor finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Ceiling: Ceiling finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Ceiling finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Doorsets: Configuration, glazing, fire rating, security, etc. to be determined by Project Team.
HTM 58 (Mar-2005)
Refer to HBN 00-04 (May-2007) for effective clear door widths.
1 doorset:
1 x personnel & equipment access (1000mm)
Windows: Desirable - Project Option
Clear glass with solar control, sealed
Designation to be validated against current documentation (HTM 55 archived).
Internal Glazing: Not required
Hatch: Not required
Notes: All finishes selected must have an appropriate risk assessment to accompany the design
decision.
Infection Control must be consulted as described in Performance Requirements for Building
Elements Used in Healthcare Facilities 8941:0.6 England.
Activity DataBase 01/03/2017
Schedule of Components by Room
Project: 7857 7857 Nottingham Uni Medical Centre
R0904ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: R0904 Decontamination room: clean instruments
Room Number: Revision Date: 01/03/2017
Key: (n-old qty) Deletions m-new qty Additions m (n) Quantity changes since audit dateAudit Date: 2-Mar-2017
DescriptionCodeTotalTransNew
GrpAlt. CodeQuantity
1BASIN, medium, hospital pattern, vitreous china, no
tap holes, no overflow, integral back outlet, 500W
400D.
BAS10111
1SOCKET outlet, switched, 13 amp, singleOUT00511
1SOCKET outlet, switched, 13 amp, twinOUT01022
1CONNECTION UNIT, switched, 13 amp, flex outletOUT04911
1CONNECTION UNIT switched 13amp, flex, indicator
light
OUT05911
1SOCKET outlet data/voice, double.OUT13111
1WORKTOP, clinical, for 400 facing modular storage
cabinets, 3000W 700D
SMW09011
1SWITCH, lightSWC02511
1TAP, bib, 2x8 mm thermostatic mixer, automatic
action, sensor operated, non-touch,
TAP89211
1TRAP, bottle, 1.1/4 in, plastic resealing.WAS10711
5CABINET, endoscopy, 8 scopesCAB40111
5DISPENSER, barrier cream, disposable single
cartridge, wall mounted
DIS21111
5HOLDER, sack, with lid foot operated, medium,
freestanding, 875H 430W 385D
HOL10622
5SCANNER: Bar-codeSCN10111
5TRACK, blinds for windowsTRA90211
5TROLLEY, dressing/instrument, stainless steel,
buffered, 870H 450W 450D
TRO23122
Activity DataBase 01/03/2017
S0012Room Data SheetADB
Project: 7857 7857 Nottingham Uni Medical Centre
Department: PRI Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
Room: S0012 Infant feeding room
Room Number: Revision Date: 01/03/2017
1) Mother breast or bottle feeding her baby.
2) Mother to express milk using breast pump.
3) Wash-hand basin may be used.
Activities:
Personnel: 1 x infant.
1 x parent/carer.
Planning
Relationships:
Easy access from waiting area.
Space Data: Height (mm): 6.00 2,400Area (m²):
Notes: Expressed milk must be stored elsewhere.
ADB Group Definitions:
1. Contractor supply and install.
2. Supply by others, contractor install.
3. UoN supply – loose equipment and specialist equipment (chairs, drawer units,
non-fixed medical equipment).
4. NHS IT equipment (nil cost to the project).
5. Dental supply and install.
6. Pharmacy supply and install.
7. UoN IT support and install.
8. UoN supply and install (tacks and blinds; fire extinguishers; UoN signage.
9. UoN F.O.C.
Activity DataBase 01/03/2017
7857 Nottingham Uni Medical Centre7857Project:
Room Environmental Data S0012ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: S0012 Infant feeding room
Room Number: Revision Date: 01/03/2017
Permissible Space Temerature Range(dry bulb) (degC):
TEMPERATURE AND VENTILATION Requirements Notes
18 - 28
Heating Design Temperature (dry bulb)(degC): 22
Minimum Air Changes (AC/hr): 3
Ventilation Type: E/N
-vePressure Relative to Adjoining Space:
Supply Air: Final Filter Class
Permisiible Relative Humidity Range (%):
General Notes:
LIGHTINGType Of Control: N
Daytime General Service Illuminance (Lux): 300
Daytime Specific Service Illuminance (Lux):
Nighttime General Service Illuminance (Lux):
Nighttime Specific Service Illuminance (Lux):
Local Task Illuminance (Lux):
Colour Rendering Required: Y
Colour Rendering Required Characteristics (Ra): 80
Unified Glare Rating Limit (UGRL):
Emergency Escape Route Lighting Required: In accordance with BS 5266 and Health Technical
MemorandumsY
Standby Lighting Grade - General Lighting: B
Standby Lighting Grade - Local Lighting:
General Notes:
RISKClinical Risk Category:
Non-clinical Business Continuity Risk Category:
General Notes:
Noise Intrusion (dB) 1hr day:
NOISE
Noise Intrusion (dB) 1hr night:
Noise Intrusion (dB) f night:
40
-
-
Maximum Internal Noise from M&E Services (NR): 35 Total noise of MEP services under normal operation across
the range 63Hz to 4kHz inclusive.
Room Sound-insulation Parameters - Privacy:
Room Sound-insulation Parameters - Noise Generation:
Confidential
High
Reference to Table 3 of the Department of Health 'Acoustics:
Technical design manual 4032:0.6:England'.
Noise Sensitiviy: Medium
Sound-insulation Rating (dB D nT,w):
General Notes:
Maximum Surface Temperature (DegC):
SAFETY/FIRE
43
Domestic Hot Water Discharge Temperature (DegC): 41
Maximum Cold Water Discharge Temperature (DegC): <20
General Notes:
Type of Automatic Fire Detection: Smoke
General Notes:
Activity DataBase 01/03/2017
ADB Room Design Character S0012
Project: 7857 7857 Nottingham Uni Medical Centre
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Infant feeding roomS0012Room:
01/03/2017Revision Date:Room Number:
Walls: Wall finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Wall finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Floor: Floor finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Floor finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Ceiling: Ceiling finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Ceiling finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Doorsets: Configuration, glazing, fire rating, security, etc. to be determined by Project Team.
HTM 58 (Mar-2005)
Refer to HBN 00-04 (May-2007) for effective clear door widths.
1 doorset:
1 x personnel, wheelchair & equipment access (1000mm) - see HBN 00-02
Requirement for hinge protection when areas used by children
Windows: Not required
Internal Glazing: Not required
Hatch: Not required
Notes: All finishes selected must have an appropriate risk assessment to accompany the design
decision.
Infection Control must be consulted as described in Performance Requirements for Building
Elements Used in Healthcare Facilities 8941:0.6 England.
Activity DataBase 01/03/2017
Schedule of Components by Room
Project: 7857 7857 Nottingham Uni Medical Centre
S0012ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: S0012 Infant feeding room
Room Number: Revision Date: 01/03/2017
Key: (n-old qty) Deletions m-new qty Additions m (n) Quantity changes since audit dateAudit Date: 2-Mar-2017
DescriptionCodeTotalTransNew
GrpAlt. CodeQuantity
1BASIN, medium, general pattern, vitreous china, 2
tap holes, no overflow, bottom outlet, 500W 400D.
BAS10711
1HOOK, single, small, wall mountedHOO01933
1SOCKET outlet, switched, 13 amp, singleOUT00511
1SOCKET outlet, switched, 13 amp, twinOUT01011
1CONNECTION UNIT, switched, 13 amp, flex outletOUT04911
1OUTLET, floor drainage and grating, 150 mm dia.
hospital pattern.
OUT34511
1SHELF, raised edge, non-breakable, 300W 150DSHE10111
1SHELF, 1200W 400DSHE22211
1SWITCH, dimmer, modulatingSWC03411
1TAP, bib, 2x8 mm thermostatic mixer, automatic
action, sensor operated, non-touch,
TAP89211
1WASTE, unslotted recessed grated, metal, 1.1/4 in,
with plug and chain.
WAS10111
1TRAP, bottle, 1.1/4 in, plastic resealing.WAS10711
2DISPENSER, paper towel, wall mountedDIS01311
2DISPENSER, soap, wall mountedDIS02411
3CHAIR, easy, low back, upholstered, wipeableCHA30511
3CHAIR, upright, upholstered, stacking, wipeableCHA31711
3HOLDER, sack, with lid foot operated, medium,
freestanding, 875H 430W 385D
HOL00611
3OVEN, microwave, light duty, 1000watt, capacity 26
litres, 295H 295W 410D
OVE01411
3RAIL for shower curtain, Width to fitRAI90011
3TABLE, occasional, square, 415H 610W 610DTAB05311
Activity DataBase 01/03/2017
T0211-001Room Data SheetADB
Project: 7857 7857 Nottingham Uni Medical Centre
Department: PRI Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
Room: T0211-001 Staff communication base: 3 places
Room Number: Revision Date: 01/03/2017
1) Electronic patient records (EPRs) may be accessed and updated.
2) Computer workstation(s) may be used.
3) Dealing with enquiries.
4) Telephone(s) may be used.
5) Staff supervise and observe patients.
6) Carrying out administration and clerical duties.
7) Information may be provided to patients, carers and visitors.
8) Clinical administration.
9) Call systems may be used.
Activities:
Personnel: 3 x staff.
2 x other staff or patients/visitors.
Planning
Relationships:
Situated to allow easy access and good observation of the areas served.
Access to a "safe haven" area.
Space Data: Height (mm): 14.50 2,400Area (m²):
2400 mm is the anticipated minimum ceiling height. Should be sized to suit surrounding
area/design.
Notes: Clear access space around the staff communication base should be maintained even
when someone is standing at the front of the base.
The following items are shown on the room layout but are optional:
- call system alarm panel, see HTM 08-03;
The following items may be provided:
- controlled drugs cupboard alarm;
- departmental controlled entry system.
.
Separate data and voice outlets may be used where structure cabling solutions are not
available.
ADB Group Definitions:
1. Contractor supply and install.
2. Supply by others, contractor install.
3. UoN supply – loose equipment and specialist equipment (chairs, drawer units,
non-fixed medical equipment).
4. NHS IT equipment (nil cost to the project).
5. Dental supply and install.
6. Pharmacy supply and install.
7. UoN IT support and install.
8. UoN supply and install (tacks and blinds; fire extinguishers; UoN signage.
9. UoN F.O.C.
Activity DataBase 01/03/2017
7857 Nottingham Uni Medical Centre7857Project:
Room Environmental Data T0211-001ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: T0211-001 Staff communication base: 3 places
Room Number: Revision Date: 01/03/2017
Permissible Space Temerature Range(dry bulb) (degC):
TEMPERATURE AND VENTILATION Requirements Notes
18 - 28
Heating Design Temperature (dry bulb)(degC): 21
Minimum Air Changes (AC/hr): 6
Ventilation Type: S/E
Bal or -vePressure Relative to Adjoining Space:
G4Supply Air: Final Filter Class
Permisiible Relative Humidity Range (%):
General Notes:
LIGHTINGType Of Control: S/V/N
Daytime General Service Illuminance (Lux): 300
Daytime Specific Service Illuminance (Lux):
Nighttime General Service Illuminance (Lux): 30-200
Nighttime Specific Service Illuminance (Lux):
Local Task Illuminance (Lux):
Colour Rendering Required: Y
Colour Rendering Required Characteristics (Ra): 80
Unified Glare Rating Limit (UGRL): 19
Emergency Escape Route Lighting Required: In accordance with BS 5266 and Health Technical
MemorandumsY
Standby Lighting Grade - General Lighting: A
AStandby Lighting Grade - Local Lighting:
General Notes: Refer to SLL Lighting Guide 2 for guidance
RISKClinical Risk Category:
Non-clinical Business Continuity Risk Category:
General Notes:
Noise Intrusion (dB) 1hr day:
NOISE
Noise Intrusion (dB) 1hr night:
Noise Intrusion (dB) f night:
40
-
-
Maximum Internal Noise from M&E Services (NR): 35 Total noise of MEP services under normal operation across
the range 63Hz to 4kHz inclusive.
Room Sound-insulation Parameters - Privacy:
Room Sound-insulation Parameters - Noise Generation:
Confidential
Typical
Reference to Table 3 of the Department of Health 'Acoustics:
Technical design manual 4032:0.6:England'.
Noise Sensitiviy: Medium
Sound-insulation Rating (dB D nT,w):
General Notes:
Maximum Surface Temperature (DegC):
SAFETY/FIRE
43
Domestic Hot Water Discharge Temperature (DegC): 41
Maximum Cold Water Discharge Temperature (DegC): <20
General Notes:
Type of Automatic Fire Detection: Smoke
General Notes:
Activity DataBase 01/03/2017
ADB Room Design Character T0211-001
Project: 7857 7857 Nottingham Uni Medical Centre
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Staff communication base: 3 placesT0211-001Room:
01/03/2017Revision Date:Room Number:
Walls: Wall finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Wall finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Floor: Floor finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Floor finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Ceiling: Ceiling finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Ceiling finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Doorsets: Configuration, glazing, fire rating, security, etc. to be determined by Project Team.
HTM 58 (Mar-2005)
Refer to HBN 00-04 (May-2007) for effective clear door widths.
1 doorset:
1 x personnel, wheelchair & equipment access (1000mm)
Windows: Non-essential - Project Option
Clear glass with solar control
Designation to be validated against current documentation (HTM 55 archived).
Internal Glazing: Not required
Hatch: Not required
Notes: All finishes selected must have an appropriate risk assessment to accompany the design
decision.
Infection Control must be consulted as described in Performance Requirements for Building
Elements Used in Healthcare Facilities 8941:0.6 England.
Activity DataBase 01/03/2017
Schedule of Components by Room
Project: 7857 7857 Nottingham Uni Medical Centre
T0211-001ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: T0211-001 Staff communication base: 3 places
Room Number: Revision Date: 01/03/2017
Key: (n-old qty) Deletions m-new qty Additions m (n) Quantity changes since audit dateAudit Date: 2-Mar-2017
DescriptionCodeTotalTransNew
GrpAlt. CodeQuantity
8TRACK, blinds for windowsTRA90011
Activity DataBase 01/03/2017
T0211-002Room Data SheetADB
Project: 7857 7857 Nottingham Uni Medical Centre
Department: PRI Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
Room: T0211-002 IT Communication Room
Room Number: Revision Date: 01/03/2017
1) Electronic patient records (EPRs) may be accessed and updated.
2) Computer workstation(s) may be used.
3) Dealing with enquiries.
4) Telephone(s) may be used.
5) Staff supervise and observe patients.
6) Carrying out administration and clerical duties.
7) Information may be provided to patients, carers and visitors.
8) Clinical administration.
9) Patient records may be reviewed and recorded.
10) Information on computers may be accessed.
11) Call systems may be used.
Activities:
Personnel: 2 x staff.
2 x other staff or patients/visitors.
Planning
Relationships:
Situated to allow easy access and good observation of the areas served.
Access to a "safe haven" area.
Space Data: Height (mm): 11.00 2,400Area (m²):
2400 mm is the anticipated minimum ceiling height. Should be sized to suit surrounding
area/design.
Notes: Clear access space around the staff communication base should be maintained even
when someone is standing at the front of the base.
The following items are shown on the room layout but are optional:
- call system alarm panel, see HTM 08-03;
The following items may be provided:
- controlled drugs cupboard alarm;
- departmental controlled entry system.
.
Separate data and voice outlets may be used where structure cabling solutions are not
available.
ADB Group Definitions:
1. Contractor supply and install.
2. Supply by others, contractor install.
3. UoN supply – loose equipment and specialist equipment (chairs, drawer units,
non-fixed medical equipment).
4. NHS IT equipment (nil cost to the project).
5. Dental supply and install.
6. Pharmacy supply and install.
7. UoN IT support and install.
8. UoN supply and install (tacks and blinds; fire extinguishers; UoN signage.
9. UoN F.O.C.
Activity DataBase 01/03/2017
7857 Nottingham Uni Medical Centre7857Project:
Room Environmental Data T0211-002ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: T0211-002 IT Communication Room
Room Number: Revision Date: 01/03/2017
Permissible Space Temerature Range(dry bulb) (degC):
TEMPERATURE AND VENTILATION Requirements Notes
18 - 28
Heating Design Temperature (dry bulb)(degC): 21
Minimum Air Changes (AC/hr): 6
Ventilation Type: S/E
Bal or -vePressure Relative to Adjoining Space:
G4Supply Air: Final Filter Class
Permisiible Relative Humidity Range (%):
General Notes:
LIGHTINGType Of Control: S/V/N
Daytime General Service Illuminance (Lux): 300
Daytime Specific Service Illuminance (Lux):
Nighttime General Service Illuminance (Lux): 30-200
Nighttime Specific Service Illuminance (Lux):
Local Task Illuminance (Lux):
Colour Rendering Required: Y
Colour Rendering Required Characteristics (Ra): 80
Unified Glare Rating Limit (UGRL): 19
Emergency Escape Route Lighting Required: In accordance with BS 5266 and Health Technical
MemorandumsY
Standby Lighting Grade - General Lighting: A
AStandby Lighting Grade - Local Lighting:
General Notes: Refer to SLL Lighting Guide 2 for guidance
RISKClinical Risk Category:
Non-clinical Business Continuity Risk Category:
General Notes:
Noise Intrusion (dB) 1hr day:
NOISE
Noise Intrusion (dB) 1hr night:
Noise Intrusion (dB) f night:
40
-
-
Maximum Internal Noise from M&E Services (NR): 35 Total noise of MEP services under normal operation across
the range 63Hz to 4kHz inclusive.
Room Sound-insulation Parameters - Privacy:
Room Sound-insulation Parameters - Noise Generation:
Confidential
Typical
Reference to Table 3 of the Department of Health 'Acoustics:
Technical design manual 4032:0.6:England'.
Noise Sensitiviy: Medium
Sound-insulation Rating (dB D nT,w):
General Notes:
Maximum Surface Temperature (DegC):
SAFETY/FIRE
43
Domestic Hot Water Discharge Temperature (DegC): 41
Maximum Cold Water Discharge Temperature (DegC): <20
General Notes:
Type of Automatic Fire Detection: Smoke
General Notes:
Activity DataBase 01/03/2017
ADB Room Design Character T0211-002
Project: 7857 7857 Nottingham Uni Medical Centre
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
IT Communication RoomT0211-002Room:
01/03/2017Revision Date:Room Number:
Walls: Wall finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Wall finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Floor: Floor finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Floor finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Ceiling: Ceiling finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Ceiling finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Doorsets: Configuration, glazing, fire rating, security, etc. to be determined by Project Team.
HTM 58 (Mar-2005)
Refer to HBN 00-04 (May-2007) for effective clear door widths.
1 doorset:
1 x personnel, wheelchair & equipment access (1000mm)
Windows: Non-essential - Project Option
Clear glass with solar control
Designation to be validated against current documentation (HTM 55 archived).
Internal Glazing: Not required
Hatch: Not required
Notes: All finishes selected must have an appropriate risk assessment to accompany the design
decision.
Infection Control must be consulted as described in Performance Requirements for Building
Elements Used in Healthcare Facilities 8941:0.6 England.
Activity DataBase 01/03/2017
Schedule of Components by Room
Project: 7857 7857 Nottingham Uni Medical Centre
T0211-002ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: T0211-002 IT Communication Room
Room Number: Revision Date: 01/03/2017
Key: (n-old qty) Deletions m-new qty Additions m (n) Quantity changes since audit dateAudit Date: 2-Mar-2017
DescriptionCodeTotalTransNew
GrpAlt. CodeQuantity
Activity DataBase 01/03/2017
T0531Room Data SheetADB
Project: 7857 7857 Nottingham Uni Medical Centre
Department: PRI Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
Room: T0531 Preparation room: catheter laboratories/enhanced procedures
Room Number: Revision Date: 01/03/2017
1) Holding/storing working supply of clean and sterile materials for immediate use.
2) Sterile pre-set trays are held/stored
3) A working supply of consumables is held/stored.
4) Operating lists may be displayed.
5) Sterile fluids are stored.
6) Trays are prepared and trolleys laid up for surgical /clinical procedures.
7) Instrument trolleys are held/stored.
Activities:
Personnel: 1-2 staff intermittently
Planning
Relationships:
Adjacent to enhanced procedures room.
Goods to be delivered from corridor.
Space Data: Height (mm): 9.00 2,700Area (m²):
Notes: The number and size of dressing/instrument trolleys is a project team option.
The following items may be provided:
- heated lotion cabinet which could be provided in a central store instead of within the
preparation room.
Separate data and voice outlets may be used where structure cabling solutions are not
available.
ADB Group Definitions:
1. Contractor supply and install.
2. Supply by others, contractor install.
3. UoN supply – loose equipment and specialist equipment (chairs, drawer units,
non-fixed medical equipment).
4. NHS IT equipment (nil cost to the project).
5. Dental supply and install.
6. Pharmacy supply and install.
7. UoN IT support and install.
8. UoN supply and install (tacks and blinds; fire extinguishers; UoN signage.
9. UoN F.O.C.
Activity DataBase 01/03/2017
7857 Nottingham Uni Medical Centre7857Project:
Room Environmental Data T0531ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: T0531 Preparation room: catheter laboratories/enhanced procedures
Room Number: Revision Date: 01/03/2017
Permissible Space Temerature Range(dry bulb) (degC):
TEMPERATURE AND VENTILATION Requirements Notes
18 - 25
Heating Design Temperature (dry bulb)(degC): 22
Minimum Air Changes (AC/hr): 10
Ventilation Type: S
+vePressure Relative to Adjoining Space:
F7Supply Air: Final Filter Class
Permisiible Relative Humidity Range (%):
General Notes:
LIGHTINGType Of Control: N
Daytime General Service Illuminance (Lux): 500
Daytime Specific Service Illuminance (Lux):
Nighttime General Service Illuminance (Lux):
Nighttime Specific Service Illuminance (Lux):
Local Task Illuminance (Lux):
Colour Rendering Required: Y
Colour Rendering Required Characteristics (Ra): 80
Unified Glare Rating Limit (UGRL): 19
Emergency Escape Route Lighting Required: In accordance with BS 5266 and Health Technical
MemorandumsY
Standby Lighting Grade - General Lighting: B
Standby Lighting Grade - Local Lighting:
General Notes: Refer to SLL Lighting Guide 2 for guidance
RISKClinical Risk Category:
Non-clinical Business Continuity Risk Category:
General Notes:
Noise Intrusion (dB) 1hr day:
NOISE
Noise Intrusion (dB) 1hr night:
Noise Intrusion (dB) f night:
40
-
50
The LAmax,f dB noise limit applies at any time.
Maximum Internal Noise from M&E Services (NR): 40 Total noise of MEP services under normal operation across
the range 63Hz to 4kHz inclusive.
Room Sound-insulation Parameters - Privacy:
Room Sound-insulation Parameters - Noise Generation:
Private
Typical
Reference to Table 3 of the Department of Health 'Acoustics:
Technical design manual 4032:0.6:England'.
Noise Sensitiviy: Medium
Sound-insulation Rating (dB D nT,w):
General Notes:
Maximum Surface Temperature (DegC):
SAFETY/FIRE
82
Domestic Hot Water Discharge Temperature (DegC): 41
Maximum Cold Water Discharge Temperature (DegC): <20
General Notes:
Type of Automatic Fire Detection: Smoke
General Notes:
Activity DataBase 01/03/2017
ADB Room Design Character T0531
Project: 7857 7857 Nottingham Uni Medical Centre
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Preparation room: catheter laboratories/enhanced proceduresT0531Room:
01/03/2017Revision Date:Room Number:
Walls: Wall finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Wall finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Floor: Floor finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Floor finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Ceiling: Ceiling finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Ceiling finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Doorsets: Configuration, glazing, fire rating, security, etc. to be determined by Project Team.
HTM 58 (Mar-2005)
Refer to HBN 00-04 (May-2007) for effective clear door widths.
2 sets of doors:
2 x personnel & equipment access (1000mm)
Windows: Non-essential - Project Option
Obscured glass with solar control, security control as necessary, see BS2881
Designation to be validated against current documentation (HTM 55 archived).
Internal Glazing: Not required
Hatch: Not required
Notes: All finishes selected must have an appropriate risk assessment to accompany the design
decision.
Infection Control must be consulted as described in Performance Requirements for Building
Elements Used in Healthcare Facilities 8941:0.6 England.
Activity DataBase 01/03/2017
Schedule of Components by Room
Project: 7857 7857 Nottingham Uni Medical Centre
T0531ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: T0531 Preparation room: catheter laboratories/enhanced procedures
Room Number: Revision Date: 01/03/2017
Key: (n-old qty) Deletions m-new qty Additions m (n) Quantity changes since audit dateAudit Date: 2-Mar-2017
DescriptionCodeTotalTransNew
GrpAlt. CodeQuantity
1SOCKET outlet, switched, 13 amp, singleOUT00511
1SOCKET outlet, switched, 13 amp, twinOUT01011
1SOCKET outlet data/voice, double.OUT13111
1CABINET, base, modular storage, for 400 facing
inserts, with door, on plinth, 900H
SMC01322
1WORKTOP, clinical, for 400 facing modular storage
cabinets, 2700W 700D
SMW08711
1SWITCH, lightSWC02511
2BOARD, marker, whiteboard, dry-wipe, with pen
holder, wall mounted, 600H 900W
BOA03411
3HOLDER, sack, with lid foot operated, medium,
freestanding, 875H 430W 385D
HOL00611
3STAND, 2 lotion bowls, stainless steel, (Bowls not
included).
STA10211
3TROLLEY, dressing/instrument, stainless steel,
buffered, 870H 450W 450D
TRO13122
3TROLLEY, dressing/instrument, stainless steel,
buffered, 870H 750W 450D
TRO13322
3TROLLEY, instruments, stainless steel, buffered,
870H 920W 620D
TRO20111
Activity DataBase 01/03/2017
T0538Room Data SheetADB
Project: 7857 7857 Nottingham Uni Medical Centre
Department: PRI Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
Room: T0538 Clean utility room: without controlled drugs cupboard
Room Number: Revision Date: 01/03/2017
1) Dressing/instrument trolleys are held and prepared.
2) Sterile supplies and consumables are held.
3) Non-controlled medicines and pharmaceuticals are stored securely.
4) Provision of refrigerated storage.
5) Flammable medicines are stored.
6) Supplies trolleys are held/stored.
7) Clinical wash-hand basin may be used.
8) Bar coded items may be tracked.
9) Trolleys for clinical procedures are prepared and laid up .
10) Sterile packs, lotions and drugs may be prepared for immediate use.
11) Medication is prepared for administration.
12) Contrast media, I.V. injections and other sterile procedures may be prepared.
13) Computer workstation(s) may be used.
14) Telephone(s) may be used.
15) Infusion fluids are stored.
Activities:
Personnel: 2 x staff.
Planning
Relationships:
Close to clinical area, particularly treatment rooms.
Space Data: Height (mm): 8.00 2,400Area (m²):
Notes: See BS 2881 for requirements for medicines storage. This room does not include
controlled drugs cupboards.
The following items may be provided:
- a barcode reader and charger.
.
Separate data and voice outlets may be used where structure cabling solutions are not
available.
ADB Group Definitions:
1. Contractor supply and install.
2. Supply by others, contractor install.
3. UoN supply – loose equipment and specialist equipment (chairs, drawer units,
non-fixed medical equipment).
4. NHS IT equipment (nil cost to the project).
5. Dental supply and install.
6. Pharmacy supply and install.
7. UoN IT support and install.
8. UoN supply and install (tacks and blinds; fire extinguishers; UoN signage.
9. UoN F.O.C.
Activity DataBase 01/03/2017
7857 Nottingham Uni Medical Centre7857Project:
Room Environmental Data T0538ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: T0538 Clean utility room: without controlled drugs cupboard
Room Number: Revision Date: 01/03/2017
Permissible Space Temerature Range(dry bulb) (degC):
TEMPERATURE AND VENTILATION Requirements Notes
18 - 28
Heating Design Temperature (dry bulb)(degC): 21
Minimum Air Changes (AC/hr): 6
Ventilation Type: S
+vePressure Relative to Adjoining Space:
G4Supply Air: Final Filter Class
Permisiible Relative Humidity Range (%):
General Notes:
LIGHTINGType Of Control: N
Daytime General Service Illuminance (Lux): 150
Daytime Specific Service Illuminance (Lux):
Nighttime General Service Illuminance (Lux):
Nighttime Specific Service Illuminance (Lux):
Local Task Illuminance (Lux):
Colour Rendering Required: Y
Colour Rendering Required Characteristics (Ra): 80
Unified Glare Rating Limit (UGRL): 19
Emergency Escape Route Lighting Required: In accordance with BS 5266 and Health Technical
MemorandumsY
Standby Lighting Grade - General Lighting: B
Standby Lighting Grade - Local Lighting:
General Notes: Refer to SLL Lighting Guide 2 for guidance
RISKClinical Risk Category:
Non-clinical Business Continuity Risk Category:
General Notes:
Noise Intrusion (dB) 1hr day:
NOISE
Noise Intrusion (dB) 1hr night:
Noise Intrusion (dB) f night:
50
-
-
Maximum Internal Noise from M&E Services (NR): 40 Total noise of MEP services under normal operation across
the range 63Hz to 4kHz inclusive.
Room Sound-insulation Parameters - Privacy:
Room Sound-insulation Parameters - Noise Generation:
Not Private
Low
Reference to Table 3 of the Department of Health 'Acoustics:
Technical design manual 4032:0.6:England'.
Noise Sensitiviy: Not Sensitive
Sound-insulation Rating (dB D nT,w):
General Notes:
Maximum Surface Temperature (DegC):
SAFETY/FIRE
82
Domestic Hot Water Discharge Temperature (DegC): 41/>55
Maximum Cold Water Discharge Temperature (DegC): <20
General Notes:
Type of Automatic Fire Detection: Smoke
General Notes:
Activity DataBase 01/03/2017
ADB Room Design Character T0538
Project: 7857 7857 Nottingham Uni Medical Centre
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Clean utility room: without controlled drugs cupboardT0538Room:
01/03/2017Revision Date:Room Number:
Walls: Wall finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Wall finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Floor: Floor finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Floor finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Ceiling: Ceiling finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Ceiling finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Doorsets: Configuration, glazing, fire rating, security, etc. to be determined by Project Team.
HTM 58 (Mar-2005)
Refer to HBN 00-04 (May-2007) for effective clear door widths.
1 doorset:
1 x personnel & equipment access (1000mm)
Windows: Non-essential - Project Option
Obscured glass with solar control, security control as necessary, see BS2881
Designation to be validated against current documentation (HTM 55 archived).
Internal Glazing: Not required
Hatch: Not required
Notes: All finishes selected must have an appropriate risk assessment to accompany the design
decision.
Infection Control must be consulted as described in Performance Requirements for Building
Elements Used in Healthcare Facilities 8941:0.6 England.
Activity DataBase 01/03/2017
Schedule of Components by Room
Project: 7857 7857 Nottingham Uni Medical Centre
T0538ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: T0538 Clean utility room: without controlled drugs cupboard
Room Number: Revision Date: 01/03/2017
Key: (n-old qty) Deletions m-new qty Additions m (n) Quantity changes since audit dateAudit Date: 2-Mar-2017
DescriptionCodeTotalTransNew
GrpAlt. CodeQuantity
1BASIN, medium, hospital pattern, vitreous china, no
tap holes, no overflow, integral back outlet, 500W
400D.
BAS10111
1CUPBOARD, flammable material, metal, adjustable
spillage tray and sump, lockable, 712H 355W 305D
CUP55011
1OUTLET cable, 13 ampOUT00211
1SOCKET outlet, switched, 13 amp, singleOUT00511
1SOCKET outlet, switched, 13 amp, twinOUT01011
1CONNECTION UNIT, switched, 13 amp, flex outletOUT04911
1CONNECTION UNIT, switched, 13 ampOUT05211
1SOCKET outlet data/voice, double.OUT13122
1CABINET, tall, modular storage, for 400 facing
inserts, open, on plinth, 2100H
SMC00133
1CABINET, base, modular storage, for 400 facing
inserts, with door, on plinth, 900H
SMC01322
1CABINET, upper, modular storage, for 400 facing
inserts, with door, 750H
SMC02344
1WORKTOP, clinical, for 400 facing modular storage
cabinets, 2100W 700D
SMW08111
1SWITCH, lightSWC02511
1TAP, bib, 2x8 mm thermostatic mixer, automatic
action, sensor operated, non-touch,
TAP89211
1TRAP, bottle, 1.1/4 in, plastic resealing.WAS10711
2DISPENSER, barrier cream, disposable single
cartridge, wall mounted
DIS01111
2DISPENSER, paper towel, wall mountedDIS01311
2DISPENSER, soap, disposable single cartridge, lever
action, wall mounted
DIS03011
2DISPENSER, disposable gloves set of 3 and
disposable apron, wall mounted
DIS43811
3HOLDER, sack, with lid foot operated, medium,
freestanding, 875H 430W 385D
HOL00622
Activity DataBase 01/03/2017
V0554Room Data SheetADB
Project: 7857 7857 Nottingham Uni Medical Centre
Department: PRI Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
Room: V0554 Staff communal changing room: 20 lockers
Room Number: Revision Date: 01/03/2017
1) User may undress and dress.
2) Changing into clean uniforms (including blues or greens).
3) Changing footwear.
4) Secure hanging of wet outdoor clothing.
5) Secure holding/storing of clothing and personal belongings.
6) Secure holding/storage of motorcycle and bicycle helmets.
7) Hanging outdoor clothing.
8) Disposal of dirty uniforms.
Activities:
Personnel: Up to 6 x staff.
Intermittent use.
Planning
Relationships:
Direct access to showers and/or individual changing room(s).
Close to WCs.
Close to uniform exchange, if provided.
Space Data: Height (mm): 20.00 2,700Area (m²):
Notes: It is assumed that this space is supported by one individual changing room. See V0725
for details of semi-ambulant individual changing room and V0276 for independent
wheelchair individual changing room.
The room layout illustrates space for all users but includes lockers for generally
ambulant users. A suitable number of lockers must comply with the requirements of
BS8300/ADM for wheelchair users depending upon the expected user group.
The following items may be provided:
- cube lockers for personal belongings will be required if staff are not allocated their own
changing lockers;
- shaver sockets, shelves and lights associated with mirrors.
ADB Group Definitions:
1. Contractor supply and install.
2. Supply by others, contractor install.
3. UoN supply – loose equipment and specialist equipment (chairs, drawer units,
non-fixed medical equipment).
4. NHS IT equipment (nil cost to the project).
5. Dental supply and install.
6. Pharmacy supply and install.
7. UoN IT support and install.
8. UoN supply and install (tacks and blinds; fire extinguishers; UoN signage.
9. UoN F.O.C.
Activity DataBase 01/03/2017
7857 Nottingham Uni Medical Centre7857Project:
Room Environmental Data V0554ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: V0554 Staff communal changing room: 20 lockers
Room Number: Revision Date: 01/03/2017
Permissible Space Temerature Range(dry bulb) (degC):
TEMPERATURE AND VENTILATION Requirements Notes
18 - 28
Heating Design Temperature (dry bulb)(degC): 22
Minimum Air Changes (AC/hr): 6
Ventilation Type: S/E
Bal or -vePressure Relative to Adjoining Space:
G4Supply Air: Final Filter Class
Permisiible Relative Humidity Range (%): Uncontrolled
General Notes:
LIGHTINGType Of Control: N
Daytime General Service Illuminance (Lux): 200
Daytime Specific Service Illuminance (Lux):
Nighttime General Service Illuminance (Lux):
Nighttime Specific Service Illuminance (Lux):
Local Task Illuminance (Lux):
Colour Rendering Required: Y
Colour Rendering Required Characteristics (Ra): 80
Unified Glare Rating Limit (UGRL): 22
Emergency Escape Route Lighting Required: In accordance with BS 5266 and Health Technical
MemorandumsY
Standby Lighting Grade - General Lighting:
Standby Lighting Grade - Local Lighting:
General Notes:
RISKClinical Risk Category:
Non-clinical Business Continuity Risk Category:
General Notes:
Noise Intrusion (dB) 1hr day:
NOISE
Noise Intrusion (dB) 1hr night:
Noise Intrusion (dB) f night:
55
-
-
Maximum Internal Noise from M&E Services (NR): 45 Total noise of MEP services under normal operation across
the range 63Hz to 4kHz inclusive.
Room Sound-insulation Parameters - Privacy:
Room Sound-insulation Parameters - Noise Generation:
Moderate
Typical
Reference to Table 3 of the Department of Health 'Acoustics:
Technical design manual 4032:0.6:England'.
Noise Sensitiviy: Not Sensitive
Sound-insulation Rating (dB D nT,w):
General Notes:
Maximum Surface Temperature (DegC):
SAFETY/FIRE
82
Domestic Hot Water Discharge Temperature (DegC): 41
Maximum Cold Water Discharge Temperature (DegC): <20
General Notes:
Type of Automatic Fire Detection: Smoke heat to be considered if adjacent to shower rooms
General Notes:
Activity DataBase 01/03/2017
ADB Room Design Character V0554
Project: 7857 7857 Nottingham Uni Medical Centre
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Staff communal changing room: 20 lockersV0554Room:
01/03/2017Revision Date:Room Number:
Walls: Wall finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Wall finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Floor: Floor finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Floor finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Ceiling: Ceiling finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Ceiling finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Doorsets: Configuration, glazing, fire rating, security, etc. to be determined by Project Team.
HTM 58 (Mar-2005)
Refer to HBN 00-04 (May-2007) for effective clear door widths.
2 sets of doors:
2 x personnel, wheelchair & equipment access (1000mm)
Windows: Non-essential - Project Option
Obscured glass with solar control
Designation to be validated against current documentation (HTM 55 archived).
Internal Glazing: Not required
Hatch: Not required
Notes: All finishes selected must have an appropriate risk assessment to accompany the design
decision.
Infection Control must be consulted as described in Performance Requirements for Building
Elements Used in Healthcare Facilities 8941:0.6 England.
Activity DataBase 01/03/2017
Schedule of Components by Room
Project: 7857 7857 Nottingham Uni Medical Centre
V0554ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: V0554 Staff communal changing room: 20 lockers
Room Number: Revision Date: 01/03/2017
Key: (n-old qty) Deletions m-new qty Additions m (n) Quantity changes since audit dateAudit Date: 2-Mar-2017
DescriptionCodeTotalTransNew
GrpAlt. CodeQuantity
1BASIN, small, general pattern, vitreous china, 1 tap
right hand hole, no overflow, bottom outlet, 400W
300D
BAS10511
1DISH, soap, wall mountedDIS20011
1LUMINAIRE, single fluorescent lamp, wall, 8 watt,
300 mm
LIG06311
1MIRROR, wall mounted, 900H 300WMIR00211
1MIRROR, unbreakable, wall mounted, 1300H 500WMIR02633
1SOCKET outlet, switched, 13 amp, singleOUT00511
1SOCKET outlet, switched, 13 amp, twinOUT01022
1SOCKET outlet, shaverOUT02511
1RAIL for shower curtain, 1200mmRAI26211
1SEAT, bench, wall mounted, 480H 1300W 400DSEA00411
1SHOWER, slip resistant floor, with drainage outlet,
1000W 1200D
SHO00422
1SHOWER, valve, thermostatic mixer (associated with
SHO020).
SHO01811
1SHOWER, adjustable shower head hand spray
(associated with SHO018).
SHO02011
1SWITCH, lightSWC02511
1TAP, monobloc, pillar mixer, integral thermostatic,
short lever.
TAP28911
1WASTE, unslotted flush-grated, metal, 1.1/4 in. .WAS10022
1TRAP, bottle, 1.1/4 in, plastic resealing.WAS10711
1WC/toilet pan with seat, 520-550 projection, hospital
pattern, rimless pan, vitreous china.
WCH00111
5DISPENSER, soap, wall mountedDIS12411
5HOOK, single, small, wall mountedHOO11922
5LOCKER clothes, triple, 1800H 300W 550DLOC8001313
5SHELF, raised edge, non-breakable, 300W 150DSHE30111
5TRACK, blinds for windowsTRA90211
Activity DataBase 01/03/2017
V0554-03Room Data SheetADB
Project: 7857 7857 Nottingham Uni Medical Centre
Department: PRI Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
Room: V0554-03 Staff communal changing room: 30 lockers
Room Number: Revision Date: 01/03/2017
1) User may undress and dress.
2) Changing into clean uniforms (including blues or greens).
3) Changing footwear.
4) Secure hanging of wet outdoor clothing.
5) Secure holding/storing of clothing and personal belongings.
6) Secure holding/storage of motorcycle and bicycle helmets.
7) Hanging outdoor clothing.
8) Disposal of dirty uniforms.
Activities:
Personnel: Up to 12 x staff.
Intermittent use.
Planning
Relationships:
Direct access to showers and/or individual changing room(s).
Close to WCs.
Close to uniform exchange, if provided.
Space Data: Height (mm): 30.00 2,700Area (m²):
Notes: It is assumed that this space is supported by one individual changing room. See V0725
for details of semi-ambulant individual changing room and V0276 for independent
wheelchair individual changing room.
The room layout illustrates space for all users but includes lockers for generally
ambulant users. A suitable number of lockers must comply with the requirements of
BS8300/ADM for wheelchair users depending upon the expected user group.
The following items may be provided:
- cube lockers for personal belongings will be required if staff are not allocated their own
changing lockers;
- shaver sockets, shelves and lights associated with mirrors.
ADB Group Definitions:
1. Contractor supply and install.
2. Supply by others, contractor install.
3. UoN supply – loose equipment and specialist equipment (chairs, drawer units,
non-fixed medical equipment).
4. NHS IT equipment (nil cost to the project).
5. Dental supply and install.
6. Pharmacy supply and install.
7. UoN IT support and install.
8. UoN supply and install (tacks and blinds; fire extinguishers; UoN signage.
9. UoN F.O.C.
Activity DataBase 01/03/2017
7857 Nottingham Uni Medical Centre7857Project:
Room Environmental Data V0554-03ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: V0554-03 Staff communal changing room: 30 lockers
Room Number: Revision Date: 01/03/2017
Permissible Space Temerature Range(dry bulb) (degC):
TEMPERATURE AND VENTILATION Requirements Notes
18 - 28
Heating Design Temperature (dry bulb)(degC): 22
Minimum Air Changes (AC/hr): 6
Ventilation Type: S/E
Bal or -vePressure Relative to Adjoining Space:
G4Supply Air: Final Filter Class
Permisiible Relative Humidity Range (%): Uncontrolled
General Notes:
LIGHTINGType Of Control: N
Daytime General Service Illuminance (Lux): 200
Daytime Specific Service Illuminance (Lux):
Nighttime General Service Illuminance (Lux):
Nighttime Specific Service Illuminance (Lux):
Local Task Illuminance (Lux):
Colour Rendering Required: Y
Colour Rendering Required Characteristics (Ra): 80
Unified Glare Rating Limit (UGRL): 22
Emergency Escape Route Lighting Required: In accordance with BS 5266 and Health Technical
MemorandumsY
Standby Lighting Grade - General Lighting:
Standby Lighting Grade - Local Lighting:
General Notes:
RISKClinical Risk Category:
Non-clinical Business Continuity Risk Category:
General Notes:
Noise Intrusion (dB) 1hr day:
NOISE
Noise Intrusion (dB) 1hr night:
Noise Intrusion (dB) f night:
55
-
-
Maximum Internal Noise from M&E Services (NR): 45 Total noise of MEP services under normal operation across
the range 63Hz to 4kHz inclusive.
Room Sound-insulation Parameters - Privacy:
Room Sound-insulation Parameters - Noise Generation:
Moderate
Typical
Reference to Table 3 of the Department of Health 'Acoustics:
Technical design manual 4032:0.6:England'.
Noise Sensitiviy: Not Sensitive
Sound-insulation Rating (dB D nT,w):
General Notes:
Maximum Surface Temperature (DegC):
SAFETY/FIRE
82
Domestic Hot Water Discharge Temperature (DegC): 41
Maximum Cold Water Discharge Temperature (DegC): <20
General Notes:
Type of Automatic Fire Detection: Smoke heat to be considered if adjacent to shower rooms
General Notes:
Activity DataBase 01/03/2017
ADB Room Design Character V0554-03
Project: 7857 7857 Nottingham Uni Medical Centre
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Staff communal changing room: 30 lockersV0554-03Room:
01/03/2017Revision Date:Room Number:
Walls: Wall finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Wall finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Floor: Floor finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Floor finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Ceiling: Ceiling finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Ceiling finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Doorsets: Configuration, glazing, fire rating, security, etc. to be determined by Project Team.
HTM 58 (Mar-2005)
Refer to HBN 00-04 (May-2007) for effective clear door widths.
1 doorset:
1 x personnel, wheelchair & equipment access (1000mm) - see HBN 00-02
Windows: Non-essential - Project Option
Obscured glass with solar control
Designation to be validated against current documentation (HTM 55 archived).
Internal Glazing: Not required
Hatch: Not required
Notes: All finishes selected must have an appropriate risk assessment to accompany the design
decision.
Infection Control must be consulted as described in Performance Requirements for Building
Elements Used in Healthcare Facilities 8941:0.6 England.
Activity DataBase 01/03/2017
Schedule of Components by Room
Project: 7857 7857 Nottingham Uni Medical Centre
V0554-03ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: V0554-03 Staff communal changing room: 30 lockers
Room Number: Revision Date: 01/03/2017
Key: (n-old qty) Deletions m-new qty Additions m (n) Quantity changes since audit dateAudit Date: 2-Mar-2017
DescriptionCodeTotalTransNew
GrpAlt. CodeQuantity
1BASIN, small, general pattern, vitreous china, 1 tap
right hand hole, no overflow, bottom outlet, 400W
300D
BAS10522
1BENCH, transfer, fixed, 300H 1200W 700DBEN00633
1DISH, soap, wall mountedDIS20022
1HOOK, single, small, wall mountedHOO01944
1LUMINAIRE, single fluorescent lamp, wall, 8 watt,
300 mm
LIG06322
1MIRROR, wall mounted, 900H 300WMIR00222
1MIRROR, unbreakable, wall mounted, 1300H 500WMIR02622
1SOCKET outlet, switched, 13 amp, singleOUT00511
1SOCKET outlet, switched, 13 amp, twinOUT01033
1SOCKET outlet, shaverOUT02522
1RAIL for shower curtain, 1200mmRAI26222
1SHELF, raised edge, non-breakable, 300W 150DSHE10122
1SHOWER, slip resistant floor, with drainage outlet,
1000W 1200D
SHO00444
1SHOWER, valve, thermostatic mixer (associated with
SHO020).
SHO01822
1SHOWER, adjustable shower head hand spray
(associated with SHO018).
SHO02022
1SWITCH, lightSWC02511
1TAP, monobloc, pillar mixer, integral thermostatic,
short lever.
TAP28922
1WASTE, unslotted flush-grated, metal, 1.1/4 in. .WAS10044
1TRAP, bottle, 1.1/4 in, plastic resealing.WAS10722
1WC/toilet pan with seat, 520-550 projection, hospital
pattern, rimless pan, vitreous china.
WCH00122
2DISPENSER, paper towel, wall mountedDIS01322
2DISPENSER, soap, wall mountedDIS02422
3LOCKER clothes, triple, 1800H 300W 550DLOC9001717
8TRACK, blinds for windowsTRA90022
Activity DataBase 01/03/2017
V0653Room Data SheetADB
Project: 7857 7857 Nottingham Uni Medical Centre
Department: PRI Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
Room: V0653 Locker bay: 12 small lockers
Room Number: Revision Date: 01/03/2017
1) Secure holding/storing of clothing and personal belongings.Activities:
Personnel: Intermittent use.
Planning
Relationships:
Convenient to circulation route.
Space Data: Height (mm): 1.50 2,400Area (m²):
2400 mm is the anticipated minimum ceiling height. Should be sized to suit surrounding
area/design.
Notes: Lockers included for generally ambulant users. A suitable number of lockers must
comply with the requirements of BS8300/ADM for wheelchair users depending upon the
expected user group.
ADB Group Definitions:
1. Contractor supply and install.
2. Supply by others, contractor install.
3. UoN supply – loose equipment and specialist equipment (chairs, drawer units,
non-fixed medical equipment).
4. NHS IT equipment (nil cost to the project).
5. Dental supply and install.
6. Pharmacy supply and install.
7. UoN IT support and install.
8. UoN supply and install (tacks and blinds; fire extinguishers; UoN signage.
9. UoN F.O.C.
Activity DataBase 01/03/2017
7857 Nottingham Uni Medical Centre7857Project:
Room Environmental Data V0653ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: V0653 Locker bay: 12 small lockers
Room Number: Revision Date: 01/03/2017
Permissible Space Temerature Range(dry bulb) (degC):
TEMPERATURE AND VENTILATION Requirements Notes
18 - 28
Heating Design Temperature (dry bulb)(degC): 21
Minimum Air Changes (AC/hr): 6
Ventilation Type: E
-vePressure Relative to Adjoining Space:
Supply Air: Final Filter Class
Permisiible Relative Humidity Range (%): Uncontrolled
General Notes:
LIGHTINGType Of Control: N
Daytime General Service Illuminance (Lux): 100-150
Daytime Specific Service Illuminance (Lux):
Nighttime General Service Illuminance (Lux):
Nighttime Specific Service Illuminance (Lux):
Local Task Illuminance (Lux):
Colour Rendering Required: Y
Colour Rendering Required Characteristics (Ra): 80
Unified Glare Rating Limit (UGRL): 22
Emergency Escape Route Lighting Required: In accordance with BS 5266 and Health Technical
MemorandumsY
Standby Lighting Grade - General Lighting:
Standby Lighting Grade - Local Lighting:
General Notes:
RISKClinical Risk Category:
Non-clinical Business Continuity Risk Category:
General Notes:
Noise Intrusion (dB) 1hr day:
NOISE
Noise Intrusion (dB) 1hr night:
Noise Intrusion (dB) f night:
55
-
-
Maximum Internal Noise from M&E Services (NR): 45 Total noise of MEP services under normal operation across
the range 63Hz to 4kHz inclusive.
Room Sound-insulation Parameters - Privacy:
Room Sound-insulation Parameters - Noise Generation:
Moderate
Typical
Reference to Table 3 of the Department of Health 'Acoustics:
Technical design manual 4032:0.6:England'.
Noise Sensitiviy: Not Sensitive
Sound-insulation Rating (dB D nT,w):
General Notes:
Maximum Surface Temperature (DegC):
SAFETY/FIRE
82
Domestic Hot Water Discharge Temperature (DegC): 41
Maximum Cold Water Discharge Temperature (DegC): <20
General Notes:
Type of Automatic Fire Detection: Smoke
General Notes:
Activity DataBase 01/03/2017
ADB Room Design Character V0653
Project: 7857 7857 Nottingham Uni Medical Centre
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Locker bay: 12 small lockersV0653Room:
01/03/2017Revision Date:Room Number:
Walls: Wall finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Wall finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Floor: Floor finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Floor finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Ceiling: Ceiling finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Ceiling finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Doorsets: Not required - open to circulation area or part of another space
Windows: Not required
Internal Glazing: Not required
Hatch: Not required
Notes: All finishes selected must have an appropriate risk assessment to accompany the design
decision.
Infection Control must be consulted as described in Performance Requirements for Building
Elements Used in Healthcare Facilities 8941:0.6 England.
Activity DataBase 01/03/2017
Schedule of Components by Room
Project: 7857 7857 Nottingham Uni Medical Centre
V0653ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: V0653 Locker bay: 12 small lockers
Room Number: Revision Date: 01/03/2017
Key: (n-old qty) Deletions m-new qty Additions m (n) Quantity changes since audit dateAudit Date: 2-Mar-2017
DescriptionCodeTotalTransNew
GrpAlt. CodeQuantity
3LOCKER, 4 compartments, 1800H 300W 450DLOC01433
Activity DataBase 01/03/2017
V0725-01Room Data SheetADB
Project: 7857 7857 Nottingham Uni Medical Centre
Department: PRI Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
Room: V0725-01 Changing room: semi-ambulant
Room Number: Revision Date: 01/03/2017
1) Semi-ambulant person may undress/dress in privacy.
2) Hanging outdoor clothing.
3) Call systems may be used.
Activities:
Personnel: 1 x person.
Intermittent use.
Planning
Relationships:
Adjacent to sub-waiting area (if provided).
Close to WC facilities.
May be use in conjunction with staff changing area.
Space Data: Height (mm): 2.00 2,400Area (m²):
Notes: The call repeat lamp is situated over the door outside the room.
The following items are shown on the room layout but are optional:
- patient/staff call (although required when for patient use);
The following items may be provided:
- a tip-up seat
ADB Group Definitions:
1. Contractor supply and install.
2. Supply by others, contractor install.
3. UoN supply – loose equipment and specialist equipment (chairs, drawer units,
non-fixed medical equipment).
4. NHS IT equipment (nil cost to the project).
5. Dental supply and install.
6. Pharmacy supply and install.
7. UoN IT support and install.
8. UoN supply and install (tacks and blinds; fire extinguishers; UoN signage.
9. UoN F.O.C.
Activity DataBase 01/03/2017
7857 Nottingham Uni Medical Centre7857Project:
Room Environmental Data V0725-01ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: V0725-01 Changing room: semi-ambulant
Room Number: Revision Date: 01/03/2017
Permissible Space Temerature Range(dry bulb) (degC):
TEMPERATURE AND VENTILATION Requirements Notes
18 - 28
Heating Design Temperature (dry bulb)(degC): 22
Minimum Air Changes (AC/hr): 6
Ventilation Type: E
-vePressure Relative to Adjoining Space:
Supply Air: Final Filter Class
Permisiible Relative Humidity Range (%): Uncontrolled
General Notes:
LIGHTINGType Of Control: N
Daytime General Service Illuminance (Lux): 200
Daytime Specific Service Illuminance (Lux):
Nighttime General Service Illuminance (Lux):
Nighttime Specific Service Illuminance (Lux):
Local Task Illuminance (Lux):
Colour Rendering Required: Y
Colour Rendering Required Characteristics (Ra): 80
Unified Glare Rating Limit (UGRL): 22
Emergency Escape Route Lighting Required: In accordance with BS 5266 and Health Technical
MemorandumsY
Standby Lighting Grade - General Lighting: B
Standby Lighting Grade - Local Lighting:
General Notes:
RISKClinical Risk Category:
Non-clinical Business Continuity Risk Category:
General Notes:
Noise Intrusion (dB) 1hr day:
NOISE
Noise Intrusion (dB) 1hr night:
Noise Intrusion (dB) f night:
55
-
-
Maximum Internal Noise from M&E Services (NR): 45 Total noise of MEP services under normal operation across
the range 63Hz to 4kHz inclusive.
Room Sound-insulation Parameters - Privacy:
Room Sound-insulation Parameters - Noise Generation:
Moderate
Typical
Reference to Table 3 of the Department of Health 'Acoustics:
Technical design manual 4032:0.6:England'.
Noise Sensitiviy: Not Sensitive
Sound-insulation Rating (dB D nT,w):
General Notes:
Maximum Surface Temperature (DegC):
SAFETY/FIRE
43
Domestic Hot Water Discharge Temperature (DegC): 41
Maximum Cold Water Discharge Temperature (DegC): <20
General Notes:
Type of Automatic Fire Detection: Smoke heat to be considered if adjacent to shower rooms
General Notes:
Activity DataBase 01/03/2017
ADB Room Design Character V0725-01
Project: 7857 7857 Nottingham Uni Medical Centre
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Changing room: semi-ambulantV0725-01Room:
01/03/2017Revision Date:Room Number:
Walls: Wall finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Wall finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Floor: Floor finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Floor finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Ceiling: Ceiling finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Ceiling finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Doorsets: Configuration, glazing, fire rating, security, etc. to be determined by Project Team.
HTM 58 (Mar-2005)
Refer to HBN 00-04 (May-2007) for effective clear door widths.
1 doorset:
1 x personnel access (1000mm) - see HBN 00-02
Requirement for hinge protection when areas used by children
Windows: Not required
Internal Glazing: Not required
Hatch: Not required
Notes: All finishes selected must have an appropriate risk assessment to accompany the design
decision.
Infection Control must be consulted as described in Performance Requirements for Building
Elements Used in Healthcare Facilities 8941:0.6 England.
Activity DataBase 01/03/2017
Schedule of Components by Room
Project: 7857 7857 Nottingham Uni Medical Centre
V0725-01ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: V0725-01 Changing room: semi-ambulant
Room Number: Revision Date: 01/03/2017
Key: (n-old qty) Deletions m-new qty Additions m (n) Quantity changes since audit dateAudit Date: 2-Mar-2017
DescriptionCodeTotalTransNew
GrpAlt. CodeQuantity
1PULL CORD, patient/staff call (help) with
reassurance lamp
CAL00611
1RESET UNIT, with repeat lamp, patient/staff callCAL01211
1LAMP, repeat call, patient/staff or staff emergency or
cardiac call
CAL03411
1HOOK, single, small, wall mountedHOO01922
1MIRROR, unbreakable, wall mounted, 1300H 500WMIR02611
1SEAT, bench, wall mounted, 480H 1300W 400DSEA00411
1SHELF, raised edge, non-breakable, 300W 150DSHE10111
1SWITCH, lightSWC02511
8TRACK, blinds for windowsTRA90011
Activity DataBase 01/03/2017
V0725-02Room Data SheetADB
Project: 7857 7857 Nottingham Uni Medical Centre
Department: PRI Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
Room: V0725-02 Changing room: semi-ambulant
Room Number: Revision Date: 01/03/2017
1) Semi-ambulant person may undress/dress in privacy.
2) Hanging outdoor clothing.
3) Call systems may be used.
Activities:
Personnel: 1 x person.
Intermittent use.
Planning
Relationships:
Adjacent to sub-waiting area (if provided).
Close to WC facilities.
May be use in conjunction with staff changing area.
Space Data: Height (mm): 2.00 2,400Area (m²):
Notes: The call repeat lamp is situated over the door outside the room.
The following items are shown on the room layout but are optional:
- patient/staff call (although required when for patient use);
The following items may be provided:
- a tip-up seat
ADB Group Definitions:
1. Contractor supply and install.
2. Supply by others, contractor install.
3. UoN supply – loose equipment and specialist equipment (chairs, drawer units,
non-fixed medical equipment).
4. NHS IT equipment (nil cost to the project).
5. Dental supply and install.
6. Pharmacy supply and install.
7. UoN IT support and install.
8. UoN supply and install (tacks and blinds; fire extinguishers; UoN signage.
9. UoN F.O.C.
Activity DataBase 01/03/2017
7857 Nottingham Uni Medical Centre7857Project:
Room Environmental Data V0725-02ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: V0725-02 Changing room: semi-ambulant
Room Number: Revision Date: 01/03/2017
Permissible Space Temerature Range(dry bulb) (degC):
TEMPERATURE AND VENTILATION Requirements Notes
18 - 28
Heating Design Temperature (dry bulb)(degC): 22
Minimum Air Changes (AC/hr): 6
Ventilation Type: E
-vePressure Relative to Adjoining Space:
Supply Air: Final Filter Class
Permisiible Relative Humidity Range (%): Uncontrolled
General Notes:
LIGHTINGType Of Control: N
Daytime General Service Illuminance (Lux): 200
Daytime Specific Service Illuminance (Lux):
Nighttime General Service Illuminance (Lux):
Nighttime Specific Service Illuminance (Lux):
Local Task Illuminance (Lux):
Colour Rendering Required: Y
Colour Rendering Required Characteristics (Ra): 80
Unified Glare Rating Limit (UGRL): 22
Emergency Escape Route Lighting Required: In accordance with BS 5266 and Health Technical
MemorandumsY
Standby Lighting Grade - General Lighting: B
Standby Lighting Grade - Local Lighting:
General Notes:
RISKClinical Risk Category:
Non-clinical Business Continuity Risk Category:
General Notes:
Noise Intrusion (dB) 1hr day:
NOISE
Noise Intrusion (dB) 1hr night:
Noise Intrusion (dB) f night:
55
-
-
Maximum Internal Noise from M&E Services (NR): 45 Total noise of MEP services under normal operation across
the range 63Hz to 4kHz inclusive.
Room Sound-insulation Parameters - Privacy:
Room Sound-insulation Parameters - Noise Generation:
Moderate
Typical
Reference to Table 3 of the Department of Health 'Acoustics:
Technical design manual 4032:0.6:England'.
Noise Sensitiviy: Not Sensitive
Sound-insulation Rating (dB D nT,w):
General Notes:
Maximum Surface Temperature (DegC):
SAFETY/FIRE
43
Domestic Hot Water Discharge Temperature (DegC): 41
Maximum Cold Water Discharge Temperature (DegC): <20
General Notes:
Type of Automatic Fire Detection: Smoke heat to be considered if adjacent to shower rooms
General Notes:
Activity DataBase 01/03/2017
ADB Room Design Character V0725-02
Project: 7857 7857 Nottingham Uni Medical Centre
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Changing room: semi-ambulantV0725-02Room:
01/03/2017Revision Date:Room Number:
Walls: Wall finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Wall finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Floor: Floor finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Floor finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Ceiling: Ceiling finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Ceiling finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Doorsets: Configuration, glazing, fire rating, security, etc. to be determined by Project Team.
HTM 58 (Mar-2005)
Refer to HBN 00-04 (May-2007) for effective clear door widths.
1 doorset:
1 x personnel access (1000mm) - see HBN 00-02
Requirement for hinge protection when areas used by children
Windows: Not required
Internal Glazing: Not required
Hatch: Not required
Notes: All finishes selected must have an appropriate risk assessment to accompany the design
decision.
Infection Control must be consulted as described in Performance Requirements for Building
Elements Used in Healthcare Facilities 8941:0.6 England.
Activity DataBase 01/03/2017
Schedule of Components by Room
Project: 7857 7857 Nottingham Uni Medical Centre
V0725-02ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: V0725-02 Changing room: semi-ambulant
Room Number: Revision Date: 01/03/2017
Key: (n-old qty) Deletions m-new qty Additions m (n) Quantity changes since audit dateAudit Date: 2-Mar-2017
DescriptionCodeTotalTransNew
GrpAlt. CodeQuantity
1PULL CORD, patient/staff call (help) with
reassurance lamp
CAL00611
1RESET UNIT, with repeat lamp, patient/staff callCAL01211
1LAMP, repeat call, patient/staff or staff emergency or
cardiac call
CAL03411
1HOOK, single, small, wall mountedHOO01922
1MIRROR, unbreakable, wall mounted, 1300H 500WMIR02611
1SEAT, bench, wall mounted, 480H 1300W 400DSEA00411
1SHELF, raised edge, non-breakable, 300W 150DSHE10111
1SWITCH, lightSWC02511
Activity DataBase 01/03/2017
V0726Room Data SheetADB
Project: 7857 7857 Nottingham Uni Medical Centre
Department: PRI Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
Room: V0726 Changing room: independent wheelchair
Room Number: Revision Date: 01/03/2017
1) Wheelchair user may undress/dress independently in privacy.
2) Hanging clothing whilst seated.
3) Call systems may be used.
Activities:
Personnel: 1 x person.
Intermittent use.
Planning
Relationships:
Adjacent to sub-waiting area (if provided).
Close to WC facilities.
Space Data: Height (mm): 4.50 2,400Area (m²):
Notes: The call repeat lamp is situated over the door outside the room.
The following items may be provided:
- a bench (instead of the tip-up seat shown on the room layout).
ADB Group Definitions:
1. Contractor supply and install.
2. Supply by others, contractor install.
3. UoN supply – loose equipment and specialist equipment (chairs, drawer units,
non-fixed medical equipment).
4. NHS IT equipment (nil cost to the project).
5. Dental supply and install.
6. Pharmacy supply and install.
7. UoN IT support and install.
8. UoN supply and install (tacks and blinds; fire extinguishers; UoN signage.
9. UoN F.O.C.
Activity DataBase 01/03/2017
7857 Nottingham Uni Medical Centre7857Project:
Room Environmental Data V0726ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: V0726 Changing room: independent wheelchair
Room Number: Revision Date: 01/03/2017
Permissible Space Temerature Range(dry bulb) (degC):
TEMPERATURE AND VENTILATION Requirements Notes
18 - 28
Heating Design Temperature (dry bulb)(degC): 22
Minimum Air Changes (AC/hr): 6
Ventilation Type: E
-vePressure Relative to Adjoining Space:
Supply Air: Final Filter Class
Permisiible Relative Humidity Range (%): Uncontrolled
General Notes:
LIGHTINGType Of Control: N
Daytime General Service Illuminance (Lux): 200
Daytime Specific Service Illuminance (Lux):
Nighttime General Service Illuminance (Lux):
Nighttime Specific Service Illuminance (Lux):
Local Task Illuminance (Lux):
Colour Rendering Required: Y
Colour Rendering Required Characteristics (Ra): 80
Unified Glare Rating Limit (UGRL): 22
Emergency Escape Route Lighting Required: In accordance with BS 5266 and Health Technical
MemorandumsY
Standby Lighting Grade - General Lighting: B
Standby Lighting Grade - Local Lighting:
General Notes:
RISKClinical Risk Category:
Non-clinical Business Continuity Risk Category:
General Notes:
Noise Intrusion (dB) 1hr day:
NOISE
Noise Intrusion (dB) 1hr night:
Noise Intrusion (dB) f night:
55
-
-
Maximum Internal Noise from M&E Services (NR): 45 Total noise of MEP services under normal operation across
the range 63Hz to 4kHz inclusive.
Room Sound-insulation Parameters - Privacy:
Room Sound-insulation Parameters - Noise Generation:
Moderate
Typical
Reference to Table 3 of the Department of Health 'Acoustics:
Technical design manual 4032:0.6:England'.
Noise Sensitiviy: Not Sensitive
Sound-insulation Rating (dB D nT,w):
General Notes:
Maximum Surface Temperature (DegC):
SAFETY/FIRE
43
Domestic Hot Water Discharge Temperature (DegC): 41
Maximum Cold Water Discharge Temperature (DegC): <20
General Notes:
Type of Automatic Fire Detection: Smoke heat to be considered if adjacent to shower rooms
General Notes:
Activity DataBase 01/03/2017
ADB Room Design Character V0726
Project: 7857 7857 Nottingham Uni Medical Centre
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Changing room: independent wheelchairV0726Room:
01/03/2017Revision Date:Room Number:
Walls: Wall finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Wall finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Floor: Floor finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Floor finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Ceiling: Ceiling finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Ceiling finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Doorsets: Configuration, glazing, fire rating, security, etc. to be determined by Project Team.
HTM 58 (Mar-2005)
Refer to HBN 00-04 (May-2007) for effective clear door widths.
1 doorset:
1 x personnel, wheelchair & equipment access (1000mm) - see HBN 00-02
Requirement for hinge protection when areas used by children
Windows: Not required
Internal Glazing: Not required
Hatch: Not required
Notes: All finishes selected must have an appropriate risk assessment to accompany the design
decision.
Infection Control must be consulted as described in Performance Requirements for Building
Elements Used in Healthcare Facilities 8941:0.6 England.
Activity DataBase 01/03/2017
Schedule of Components by Room
Project: 7857 7857 Nottingham Uni Medical Centre
V0726ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: V0726 Changing room: independent wheelchair
Room Number: Revision Date: 01/03/2017
Key: (n-old qty) Deletions m-new qty Additions m (n) Quantity changes since audit dateAudit Date: 2-Mar-2017
DescriptionCodeTotalTransNew
GrpAlt. CodeQuantity
1PULL CORD, patient/staff call (help) with
reassurance lamp
CAL00611
1RESET UNIT, with repeat lamp, patient/staff callCAL01222
1LAMP, repeat call, patient/staff or staff emergency or
cardiac call
CAL03411
1HOOK, single, small, wall mountedHOO01922
1MIRROR, unbreakable, wall mounted, 1300H 500WMIR02611
1RAIL, grab, horizontal, wall mounted, 600mmRAI16122
1RAIL, grab, hinged, wall mounted, 650mmRAI17211
1SEAT, tip-up, fixed heightSEA02211
1SHELF, raised edge, non-breakable, 300W 150DSHE10111
1SWITCH, lightSWC02511
Activity DataBase 01/03/2017
V0922-01Room Data SheetADB
Project: 7857 7857 Nottingham Uni Medical Centre
Department: PRI Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
Room: V0922-01 WC: independent wheelchair
Room Number: Revision Date: 01/03/2017
1) Independent wheelchair accessible toilet and adjacent hand-rinse basin may be used.
2) Call systems may be used.
Activities:
Personnel: 1 x person.
Intermittent use.
Planning
Relationships:
Space Data: Height (mm): 4.50 2,400Area (m²):
Notes: The call repeat lamp is situated over the door outside the room.
The following items are shown on the drawing but are optional:
- the bin for the disposal of sanitary towels is only required in female WCs;
ADB Group Definitions:
1. Contractor supply and install.
2. Supply by others, contractor install.
3. UoN supply – loose equipment and specialist equipment (chairs, drawer units,
non-fixed medical equipment).
4. NHS IT equipment (nil cost to the project).
5. Dental supply and install.
6. Pharmacy supply and install.
7. UoN IT support and install.
8. UoN supply and install (tacks and blinds; fire extinguishers; UoN signage.
9. UoN F.O.C.
Activity DataBase 01/03/2017
7857 Nottingham Uni Medical Centre7857Project:
Room Environmental Data V0922-01ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: V0922-01 WC: independent wheelchair
Room Number: Revision Date: 01/03/2017
Permissible Space Temerature Range(dry bulb) (degC):
TEMPERATURE AND VENTILATION Requirements Notes
18 - 28
Heating Design Temperature (dry bulb)(degC): 20
Minimum Air Changes (AC/hr): 10
Ventilation Type: E
-vePressure Relative to Adjoining Space:
Supply Air: Final Filter Class
Permisiible Relative Humidity Range (%): Uncontrolled
General Notes:
LIGHTINGType Of Control: N
Daytime General Service Illuminance (Lux): 200
Daytime Specific Service Illuminance (Lux):
Nighttime General Service Illuminance (Lux):
Nighttime Specific Service Illuminance (Lux):
Local Task Illuminance (Lux):
Colour Rendering Required: Y
Colour Rendering Required Characteristics (Ra): 80
Unified Glare Rating Limit (UGRL): 22
Emergency Escape Route Lighting Required: In accordance with BS 5266 and Health Technical
MemorandumsY
Standby Lighting Grade - General Lighting: B
Standby Lighting Grade - Local Lighting:
General Notes:
RISKClinical Risk Category:
Non-clinical Business Continuity Risk Category:
General Notes:
Noise Intrusion (dB) 1hr day:
NOISE
Noise Intrusion (dB) 1hr night:
Noise Intrusion (dB) f night:
55
-
-
Maximum Internal Noise from M&E Services (NR): 45 Total noise of MEP services under normal operation across
the range 63Hz to 4kHz inclusive.
Room Sound-insulation Parameters - Privacy:
Room Sound-insulation Parameters - Noise Generation:
Moderate
Typical
Reference to Table 3 of the Department of Health 'Acoustics:
Technical design manual 4032:0.6:England'.
Noise Sensitiviy: Not Sensitive
Sound-insulation Rating (dB D nT,w):
General Notes:
Maximum Surface Temperature (DegC):
SAFETY/FIRE
43
Domestic Hot Water Discharge Temperature (DegC): 41
Maximum Cold Water Discharge Temperature (DegC): <20
General Notes:
Type of Automatic Fire Detection: Omitted via risk assessment
General Notes:
Activity DataBase 01/03/2017
ADB Room Design Character V0922-01
Project: 7857 7857 Nottingham Uni Medical Centre
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
WC: independent wheelchairV0922-01Room:
01/03/2017Revision Date:Room Number:
Walls: Wall finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Wall finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Floor: Floor finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Floor finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Ceiling: Ceiling finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Ceiling finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Doorsets: Configuration, glazing, fire rating, security, etc. to be determined by Project Team.
HTM 58 (Mar-2005)
Refer to HBN 00-04 (May-2007) for effective clear door widths.
1 doorset:
1 x personnel, wheelchair & equipment access (1000mm) - see HBN 00-02
Requirement for hinge protection when areas used by children
Windows: Not required
Internal Glazing: Not required
Hatch: Not required
Notes: All finishes selected must have an appropriate risk assessment to accompany the design
decision.
Infection Control must be consulted as described in Performance Requirements for Building
Elements Used in Healthcare Facilities 8941:0.6 England.
Activity DataBase 01/03/2017
Schedule of Components by Room
Project: 7857 7857 Nottingham Uni Medical Centre
V0922-01ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: V0922-01 WC: independent wheelchair
Room Number: Revision Date: 01/03/2017
Key: (n-old qty) Deletions m-new qty Additions m (n) Quantity changes since audit dateAudit Date: 2-Mar-2017
DescriptionCodeTotalTransNew
GrpAlt. CodeQuantity
1BACKREST, WC/toilet, padded, wall mountedBAC00211
1BASIN, small, general pattern, vitreous china, 1 tap
right hand hole, no overflow, bottom outlet, 400W
300D
BAS10511
1PULL CORD, patient/staff call (help) with
reassurance lamp
CAL00611
1PULL/PUSH BUTTON, staff emergency call, reset
and integral/adjacent indicator lamp
CAL00711
1RESET UNIT, with repeat lamp, patient/staff callCAL01222
1LAMP, repeat call, patient/staff or staff emergency or
cardiac call
CAL03411
1CISTERN WC/toilet, concealed, reversible. To suit
WC
CIS00511
1HOOK, single, small, wall mountedHOO01922
1MIRROR, unbreakable, wall mounted, 1300H 500WMIR02611
1RAIL, grab, vertical, wall mounted, 600mmRAI04833
1RAIL, grab, horizontal, with supports, wall mounted,
600mm
RAI15911
1RAIL, grab, hinged, wall mounted, 650mmRAI17211
1SHELF, raised edge, non-breakable, 600W 200DSHE10011
1SHELF, raised edge, non-breakable, 200W 150DSHE10211
1SWITCH, lightSWC02511
1TAP, monobloc, pillar mixer, integral thermostatic,
short lever.
TAP28911
1WASTE, unslotted flush-grated, metal, 1.1/4 in. .WAS10011
1TRAP, bottle, 1.1/4 in, plastic resealing.WAS10711
1WC/toilet pan with seat, 700 mm projection, hospital
pattern, rimless pan, vitreous china.
WCH00511
2DISPENSER, paper towel, wall mountedDIS01311
2DISPENSER, toilet paper, dispense individual
sheets, wall mounted
DIS01511
2DISPENSER, soap, wall mountedDIS02411
3BIN, disposal, sealed, operated with one hand,
nominal 420H 155W 490D
BIN02811
3HOLDER, sack, small, freestandingHOL00311
Activity DataBase 01/03/2017
V0922-02Room Data SheetADB
Project: 7857 7857 Nottingham Uni Medical Centre
Department: PRI Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
Room: V0922-02 WC: independent wheelchair
Room Number: Revision Date: 01/03/2017
1) Independent wheelchair accessible toilet and adjacent hand-rinse basin may be used.
2) Call systems may be used.
Activities:
Personnel: 1 x person.
Intermittent use.
Planning
Relationships:
Space Data: Height (mm): 4.50 2,400Area (m²):
Notes: The call repeat lamp is situated over the door outside the room.
The following items are shown on the drawing but are optional:
- the bin for the disposal of sanitary towels is only required in female WCs;
ADB Group Definitions:
1. Contractor supply and install.
2. Supply by others, contractor install.
3. UoN supply – loose equipment and specialist equipment (chairs, drawer units,
non-fixed medical equipment).
4. NHS IT equipment (nil cost to the project).
5. Dental supply and install.
6. Pharmacy supply and install.
7. UoN IT support and install.
8. UoN supply and install (tacks and blinds; fire extinguishers; UoN signage.
9. UoN F.O.C.
Activity DataBase 01/03/2017
7857 Nottingham Uni Medical Centre7857Project:
Room Environmental Data V0922-02ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: V0922-02 WC: independent wheelchair
Room Number: Revision Date: 01/03/2017
Permissible Space Temerature Range(dry bulb) (degC):
TEMPERATURE AND VENTILATION Requirements Notes
18 - 28
Heating Design Temperature (dry bulb)(degC): 20
Minimum Air Changes (AC/hr): 10
Ventilation Type: E
-vePressure Relative to Adjoining Space:
Supply Air: Final Filter Class
Permisiible Relative Humidity Range (%): Uncontrolled
General Notes:
LIGHTINGType Of Control: N
Daytime General Service Illuminance (Lux): 200
Daytime Specific Service Illuminance (Lux):
Nighttime General Service Illuminance (Lux):
Nighttime Specific Service Illuminance (Lux):
Local Task Illuminance (Lux):
Colour Rendering Required: Y
Colour Rendering Required Characteristics (Ra): 80
Unified Glare Rating Limit (UGRL): 22
Emergency Escape Route Lighting Required: In accordance with BS 5266 and Health Technical
MemorandumsY
Standby Lighting Grade - General Lighting: B
Standby Lighting Grade - Local Lighting:
General Notes:
RISKClinical Risk Category:
Non-clinical Business Continuity Risk Category:
General Notes:
Noise Intrusion (dB) 1hr day:
NOISE
Noise Intrusion (dB) 1hr night:
Noise Intrusion (dB) f night:
55
-
-
Maximum Internal Noise from M&E Services (NR): 45 Total noise of MEP services under normal operation across
the range 63Hz to 4kHz inclusive.
Room Sound-insulation Parameters - Privacy:
Room Sound-insulation Parameters - Noise Generation:
Moderate
Typical
Reference to Table 3 of the Department of Health 'Acoustics:
Technical design manual 4032:0.6:England'.
Noise Sensitiviy: Not Sensitive
Sound-insulation Rating (dB D nT,w):
General Notes:
Maximum Surface Temperature (DegC):
SAFETY/FIRE
43
Domestic Hot Water Discharge Temperature (DegC): 41
Maximum Cold Water Discharge Temperature (DegC): <20
General Notes:
Type of Automatic Fire Detection: Omitted via risk assessment
General Notes:
Activity DataBase 01/03/2017
ADB Room Design Character V0922-02
Project: 7857 7857 Nottingham Uni Medical Centre
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
WC: independent wheelchairV0922-02Room:
01/03/2017Revision Date:Room Number:
Walls: Wall finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Wall finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Floor: Floor finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Floor finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Ceiling: Ceiling finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Ceiling finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Doorsets: Configuration, glazing, fire rating, security, etc. to be determined by Project Team.
HTM 58 (Mar-2005)
Refer to HBN 00-04 (May-2007) for effective clear door widths.
1 doorset:
1 x personnel, wheelchair & equipment access (1000mm) - see HBN 00-02
Requirement for hinge protection when areas used by children
Windows: Not required
Internal Glazing: Not required
Hatch: Not required
Notes: All finishes selected must have an appropriate risk assessment to accompany the design
decision.
Infection Control must be consulted as described in Performance Requirements for Building
Elements Used in Healthcare Facilities 8941:0.6 England.
Activity DataBase 01/03/2017
Schedule of Components by Room
Project: 7857 7857 Nottingham Uni Medical Centre
V0922-02ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: V0922-02 WC: independent wheelchair
Room Number: Revision Date: 01/03/2017
Key: (n-old qty) Deletions m-new qty Additions m (n) Quantity changes since audit dateAudit Date: 2-Mar-2017
DescriptionCodeTotalTransNew
GrpAlt. CodeQuantity
1BACKREST, WC/toilet, padded, wall mountedBAC00211
1BASIN, small, general pattern, vitreous china, 1 tap
right hand hole, no overflow, bottom outlet, 400W
300D
BAS10511
1PULL CORD, patient/staff call (help) with
reassurance lamp
CAL00611
1PULL/PUSH BUTTON, staff emergency call, reset
and integral/adjacent indicator lamp
CAL00711
1RESET UNIT, with repeat lamp, patient/staff callCAL01222
1LAMP, repeat call, patient/staff or staff emergency or
cardiac call
CAL03411
1CISTERN WC/toilet, concealed, reversible. To suit
WC
CIS00511
1HOOK, single, small, wall mountedHOO01922
1MIRROR, unbreakable, wall mounted, 1300H 500WMIR02611
1RAIL, grab, vertical, wall mounted, 600mmRAI04833
1RAIL, grab, horizontal, with supports, wall mounted,
600mm
RAI15911
1RAIL, grab, hinged, wall mounted, 650mmRAI17211
1SHELF, raised edge, non-breakable, 600W 200DSHE10011
1SHELF, raised edge, non-breakable, 200W 150DSHE10211
1SWITCH, lightSWC02511
1TAP, monobloc, pillar mixer, integral thermostatic,
short lever.
TAP28911
1WASTE, unslotted flush-grated, metal, 1.1/4 in. .WAS10011
1TRAP, bottle, 1.1/4 in, plastic resealing.WAS10711
1WC/toilet pan with seat, 700 mm projection, hospital
pattern, rimless pan, vitreous china.
WCH00511
2DISPENSER, paper towel, wall mountedDIS01311
2DISPENSER, toilet paper, dispense individual
sheets, wall mounted
DIS01511
2DISPENSER, soap, wall mountedDIS02411
3BIN, disposal, sealed, operated with one hand,
nominal 420H 155W 490D
BIN02811
3HOLDER, sack, small, freestandingHOL00311
Activity DataBase 01/03/2017
V0922-03Room Data SheetADB
Project: 7857 7857 Nottingham Uni Medical Centre
Department: PRI Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
Room: V0922-03 WC: independent wheelchair
Room Number: Revision Date: 01/03/2017
1) Independent wheelchair accessible toilet and adjacent hand-rinse basin may be used.
2) Call systems may be used.
Activities:
Personnel: 1 x person.
Intermittent use.
Planning
Relationships:
Space Data: Height (mm): 4.50 2,400Area (m²):
Notes: The call repeat lamp is situated over the door outside the room.
The following items are shown on the drawing but are optional:
- the bin for the disposal of sanitary towels is only required in female WCs;
ADB Group Definitions:
1. Contractor supply and install.
2. Supply by others, contractor install.
3. UoN supply – loose equipment and specialist equipment (chairs, drawer units,
non-fixed medical equipment).
4. NHS IT equipment (nil cost to the project).
5. Dental supply and install.
6. Pharmacy supply and install.
7. UoN IT support and install.
8. UoN supply and install (tacks and blinds; fire extinguishers; UoN signage.
9. UoN F.O.C.
Activity DataBase 01/03/2017
7857 Nottingham Uni Medical Centre7857Project:
Room Environmental Data V0922-03ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: V0922-03 WC: independent wheelchair
Room Number: Revision Date: 01/03/2017
Permissible Space Temerature Range(dry bulb) (degC):
TEMPERATURE AND VENTILATION Requirements Notes
18 - 28
Heating Design Temperature (dry bulb)(degC): 20
Minimum Air Changes (AC/hr): 10
Ventilation Type: E
-vePressure Relative to Adjoining Space:
Supply Air: Final Filter Class
Permisiible Relative Humidity Range (%): Uncontrolled
General Notes:
LIGHTINGType Of Control: N
Daytime General Service Illuminance (Lux): 200
Daytime Specific Service Illuminance (Lux):
Nighttime General Service Illuminance (Lux):
Nighttime Specific Service Illuminance (Lux):
Local Task Illuminance (Lux):
Colour Rendering Required: Y
Colour Rendering Required Characteristics (Ra): 80
Unified Glare Rating Limit (UGRL): 22
Emergency Escape Route Lighting Required: In accordance with BS 5266 and Health Technical
MemorandumsY
Standby Lighting Grade - General Lighting: B
Standby Lighting Grade - Local Lighting:
General Notes:
RISKClinical Risk Category:
Non-clinical Business Continuity Risk Category:
General Notes:
Noise Intrusion (dB) 1hr day:
NOISE
Noise Intrusion (dB) 1hr night:
Noise Intrusion (dB) f night:
55
-
-
Maximum Internal Noise from M&E Services (NR): 45 Total noise of MEP services under normal operation across
the range 63Hz to 4kHz inclusive.
Room Sound-insulation Parameters - Privacy:
Room Sound-insulation Parameters - Noise Generation:
Moderate
Typical
Reference to Table 3 of the Department of Health 'Acoustics:
Technical design manual 4032:0.6:England'.
Noise Sensitiviy: Not Sensitive
Sound-insulation Rating (dB D nT,w):
General Notes:
Maximum Surface Temperature (DegC):
SAFETY/FIRE
43
Domestic Hot Water Discharge Temperature (DegC): 41
Maximum Cold Water Discharge Temperature (DegC): <20
General Notes:
Type of Automatic Fire Detection: Omitted via risk assessment
General Notes:
Activity DataBase 01/03/2017
ADB Room Design Character V0922-03
Project: 7857 7857 Nottingham Uni Medical Centre
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
WC: independent wheelchairV0922-03Room:
01/03/2017Revision Date:Room Number:
Walls: Wall finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Wall finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Floor: Floor finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Floor finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Ceiling: Ceiling finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Ceiling finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Doorsets: Configuration, glazing, fire rating, security, etc. to be determined by Project Team.
HTM 58 (Mar-2005)
Refer to HBN 00-04 (May-2007) for effective clear door widths.
1 doorset:
1 x personnel, wheelchair & equipment access (1000mm) - see HBN 00-02
Requirement for hinge protection when areas used by children
Windows: Not required
Internal Glazing: Not required
Hatch: Not required
Notes: All finishes selected must have an appropriate risk assessment to accompany the design
decision.
Infection Control must be consulted as described in Performance Requirements for Building
Elements Used in Healthcare Facilities 8941:0.6 England.
Activity DataBase 01/03/2017
Schedule of Components by Room
Project: 7857 7857 Nottingham Uni Medical Centre
V0922-03ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: V0922-03 WC: independent wheelchair
Room Number: Revision Date: 01/03/2017
Key: (n-old qty) Deletions m-new qty Additions m (n) Quantity changes since audit dateAudit Date: 2-Mar-2017
DescriptionCodeTotalTransNew
GrpAlt. CodeQuantity
1BACKREST, WC/toilet, padded, wall mountedBAC00211
1BASIN, small, general pattern, vitreous china, 1 tap
right hand hole, no overflow, bottom outlet, 400W
300D
BAS10511
1PULL CORD, patient/staff call (help) with
reassurance lamp
CAL00611
1PULL/PUSH BUTTON, staff emergency call, reset
and integral/adjacent indicator lamp
CAL00711
1RESET UNIT, with repeat lamp, patient/staff callCAL01222
1LAMP, repeat call, patient/staff or staff emergency or
cardiac call
CAL03411
1HOOK, single, small, wall mountedHOO01922
1MIRROR, unbreakable, wall mounted, 1300H 500WMIR02611
1RAIL, grab, vertical, wall mounted, 600mmRAI04833
1RAIL, grab, horizontal, with supports, wall mounted,
600mm
RAI15911
1RAIL, grab, horizontal, wall mounted, 600mmRAI16111
1RAIL, grab, hinged, wall mounted, 650mmRAI17211
1SHELF, raised edge, non-breakable, 600W 200DSHE10011
1SHELF, raised edge, non-breakable, 200W 150DSHE10211
1SWITCH, lightSWC02511
1TAP, monobloc, pillar mixer, integral thermostatic,
short lever.
TAP28911
1WASTE, unslotted flush-grated, metal, 1.1/4 in. .WAS10011
1TRAP, bottle, 1.1/4 in, plastic resealing.WAS10711
1WC/toilet pan with seat, 700 mm projection, hospital
pattern, rimless pan, vitreous china.
WCH00511
2DISPENSER, paper towel, wall mountedDIS01311
2DISPENSER, toilet paper, dispense individual
sheets, wall mounted
DIS01511
2DISPENSER, soap, wall mountedDIS02411
3BIN, disposal, sealed, operated with one hand,
nominal 420H 155W 490D
BIN02811
3HOLDER, sack, small, freestandingHOL00311
Activity DataBase 01/03/2017
V1010Room Data SheetADB
Project: 7857 7857 Nottingham Uni Medical Centre
Department: PRI Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
Room: V1010 WC: ambulant
Room Number: Revision Date: 01/03/2017
1) Toilet may be used by ambulant person.
2) Hand-rinse basin may be used.
Activities:
Personnel: 1 x staff.
Intermittent use.
Planning
Relationships:
Space Data: Height (mm): 2.00 2,400Area (m²):
Notes: The following items are shown on the drawing but are optional:
- the bin for the disposal of sanitary towels is only required in female WCs;
- the shelf next to the basin.
ADB Group Definitions:
1. Contractor supply and install.
2. Supply by others, contractor install.
3. UoN supply – loose equipment and specialist equipment (chairs, drawer units,
non-fixed medical equipment).
4. NHS IT equipment (nil cost to the project).
5. Dental supply and install.
6. Pharmacy supply and install.
7. UoN IT support and install.
8. UoN supply and install (tacks and blinds; fire extinguishers; UoN signage.
9. UoN F.O.C.
Activity DataBase 01/03/2017
7857 Nottingham Uni Medical Centre7857Project:
Room Environmental Data V1010ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: V1010 WC: ambulant
Room Number: Revision Date: 01/03/2017
Permissible Space Temerature Range(dry bulb) (degC):
TEMPERATURE AND VENTILATION Requirements Notes
18 - 28
Heating Design Temperature (dry bulb)(degC): 20
Minimum Air Changes (AC/hr): 10
Ventilation Type: E
-vePressure Relative to Adjoining Space:
Supply Air: Final Filter Class
Permisiible Relative Humidity Range (%): Uncontrolled
General Notes:
LIGHTINGType Of Control: N
Daytime General Service Illuminance (Lux): 200
Daytime Specific Service Illuminance (Lux):
Nighttime General Service Illuminance (Lux):
Nighttime Specific Service Illuminance (Lux):
Local Task Illuminance (Lux):
Colour Rendering Required: Y
Colour Rendering Required Characteristics (Ra): 80
Unified Glare Rating Limit (UGRL): 22
Emergency Escape Route Lighting Required: In accordance with BS 5266 and Health Technical
MemorandumsY
Standby Lighting Grade - General Lighting: B
Standby Lighting Grade - Local Lighting:
General Notes:
RISKClinical Risk Category:
Non-clinical Business Continuity Risk Category:
General Notes:
Noise Intrusion (dB) 1hr day:
NOISE
Noise Intrusion (dB) 1hr night:
Noise Intrusion (dB) f night:
55
-
-
Maximum Internal Noise from M&E Services (NR): 45 Total noise of MEP services under normal operation across
the range 63Hz to 4kHz inclusive.
Room Sound-insulation Parameters - Privacy:
Room Sound-insulation Parameters - Noise Generation:
Moderate
Typical
Reference to Table 3 of the Department of Health 'Acoustics:
Technical design manual 4032:0.6:England'.
Noise Sensitiviy: Not Sensitive
Sound-insulation Rating (dB D nT,w):
General Notes:
Maximum Surface Temperature (DegC):
SAFETY/FIRE
43
Domestic Hot Water Discharge Temperature (DegC): 41
Maximum Cold Water Discharge Temperature (DegC): <20
General Notes:
Type of Automatic Fire Detection: Omitted via risk assessment
General Notes:
Activity DataBase 01/03/2017
ADB Room Design Character V1010
Project: 7857 7857 Nottingham Uni Medical Centre
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
WC: ambulantV1010Room:
01/03/2017Revision Date:Room Number:
Walls: Wall finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Wall finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Floor: Floor finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Floor finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Ceiling: Ceiling finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Ceiling finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Doorsets: Configuration, glazing, fire rating, security, etc. to be determined by Project Team.
HTM 58 (Mar-2005)
Refer to HBN 00-04 (May-2007) for effective clear door widths.
1 doorset:
1 x personnel access (900mm) - see HBN 00-02
Requirement for hinge protection when areas used by children
Windows: Not required
Internal Glazing: Not required
Hatch: Not required
Notes: All finishes selected must have an appropriate risk assessment to accompany the design
decision.
Infection Control must be consulted as described in Performance Requirements for Building
Elements Used in Healthcare Facilities 8941:0.6 England.
Activity DataBase 01/03/2017
Schedule of Components by Room
Project: 7857 7857 Nottingham Uni Medical Centre
V1010ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: V1010 WC: ambulant
Room Number: Revision Date: 01/03/2017
Key: (n-old qty) Deletions m-new qty Additions m (n) Quantity changes since audit dateAudit Date: 2-Mar-2017
DescriptionCodeTotalTransNew
GrpAlt. CodeQuantity
1BASIN, small, general pattern, vitreous china, 1 tap
right hand hole, no overflow, bottom outlet, 400W
300D
BAS10511
1CISTERN WC/toilet, concealed, reversible. To suit
WC
CIS00511
1TAP, monobloc, pillar mixer, integral thermostatic,
short lever.
TAP28911
1WASTE, unslotted flush-grated, metal, 1.1/4 in. .WAS10011
1TRAP, bottle, 1.1/4 in, plastic resealing.WAS10711
1WC/toilet pan with seat, 520-550 projection, hospital
pattern, rimless pan, vitreous china.
WCH00111
2DISPENSER, paper towel, wall mountedDIS01311
2DISPENSER, soap, wall mountedDIS02411
3HOLDER, sack, with lid foot operated, small,
freestanding
HOL00411
5BIN, disposal, sealed, operated with one hand,
nominal 420H 155W 490D
BIN12811
5HOLDER, toilet roll, multi, largeHOL11611
5SHELF, raised edge, non-breakable, 300W 150DSHE30111
Activity DataBase 01/03/2017
V1121Room Data SheetADB
Project: 7857 7857 Nottingham Uni Medical Centre
Department: PRI Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
Room: V1121 WC: semi-ambulant
Room Number: Revision Date: 01/03/2017
1) Toilet may be used by semi-ambulant person.
2) Hand-rinse basin may be used.
3) Call systems may be used.
Activities:
Personnel: 1 x person.
Intermittent use.
Planning
Relationships:
Space Data: Height (mm): 2.50 2,400Area (m²):
Notes: The call repeat lamp is situated over the door outside the room.
The following items are shown on the drawing but are optional:
- the bin for the disposal of sanitary towels is only required in female WCs;
- the shelf next to the basin.
ADB Group Definitions:
1. Contractor supply and install.
2. Supply by others, contractor install.
3. UoN supply – loose equipment and specialist equipment (chairs, drawer units,
non-fixed medical equipment).
4. NHS IT equipment (nil cost to the project).
5. Dental supply and install.
6. Pharmacy supply and install.
7. UoN IT support and install.
8. UoN supply and install (tacks and blinds; fire extinguishers; UoN signage.
9. UoN F.O.C.
The following items may be provided:
- mirror.
Activity DataBase 01/03/2017
7857 Nottingham Uni Medical Centre7857Project:
Room Environmental Data V1121ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: V1121 WC: semi-ambulant
Room Number: Revision Date: 01/03/2017
Permissible Space Temerature Range(dry bulb) (degC):
TEMPERATURE AND VENTILATION Requirements Notes
18 - 28
Heating Design Temperature (dry bulb)(degC): 20
Minimum Air Changes (AC/hr): 10
Ventilation Type: E
-vePressure Relative to Adjoining Space:
Supply Air: Final Filter Class
Permisiible Relative Humidity Range (%): Uncontrolled
General Notes:
LIGHTINGType Of Control: N
Daytime General Service Illuminance (Lux): 200
Daytime Specific Service Illuminance (Lux):
Nighttime General Service Illuminance (Lux):
Nighttime Specific Service Illuminance (Lux):
Local Task Illuminance (Lux):
Colour Rendering Required: Y
Colour Rendering Required Characteristics (Ra): 80
Unified Glare Rating Limit (UGRL): 22
Emergency Escape Route Lighting Required: In accordance with BS 5266 and Health Technical
MemorandumsY
Standby Lighting Grade - General Lighting: B
Standby Lighting Grade - Local Lighting:
General Notes:
RISKClinical Risk Category:
Non-clinical Business Continuity Risk Category:
General Notes:
Noise Intrusion (dB) 1hr day:
NOISE
Noise Intrusion (dB) 1hr night:
Noise Intrusion (dB) f night:
55
-
-
Maximum Internal Noise from M&E Services (NR): 45 Total noise of MEP services under normal operation across
the range 63Hz to 4kHz inclusive.
Room Sound-insulation Parameters - Privacy:
Room Sound-insulation Parameters - Noise Generation:
Moderate
Typical
Reference to Table 3 of the Department of Health 'Acoustics:
Technical design manual 4032:0.6:England'.
Noise Sensitiviy: Not Sensitive
Sound-insulation Rating (dB D nT,w):
General Notes:
Maximum Surface Temperature (DegC):
SAFETY/FIRE
43
Domestic Hot Water Discharge Temperature (DegC): 41
Maximum Cold Water Discharge Temperature (DegC): <20
General Notes:
Type of Automatic Fire Detection: Omitted via risk assessment
General Notes:
Activity DataBase 01/03/2017
ADB Room Design Character V1121
Project: 7857 7857 Nottingham Uni Medical Centre
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
WC: semi-ambulantV1121Room:
01/03/2017Revision Date:Room Number:
Walls: Wall finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Wall finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Floor: Floor finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Floor finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Ceiling: Ceiling finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Ceiling finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Doorsets: Configuration, glazing, fire rating, security, etc. to be determined by Project Team.
HTM 58 (Mar-2005)
Refer to HBN 00-04 (May-2007) for effective clear door widths.
1 doorset:
1 x personnel access (1000mm) - see HBN 00-02
Requirement for hinge protection when areas used by children
Windows: Not required
Internal Glazing: Not required
Hatch: Not required
Notes: All finishes selected must have an appropriate risk assessment to accompany the design
decision.
Infection Control must be consulted as described in Performance Requirements for Building
Elements Used in Healthcare Facilities 8941:0.6 England.
Activity DataBase 01/03/2017
Schedule of Components by Room
Project: 7857 7857 Nottingham Uni Medical Centre
V1121ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: V1121 WC: semi-ambulant
Room Number: Revision Date: 01/03/2017
Key: (n-old qty) Deletions m-new qty Additions m (n) Quantity changes since audit dateAudit Date: 2-Mar-2017
DescriptionCodeTotalTransNew
GrpAlt. CodeQuantity
1BASIN, small, general pattern, vitreous china, 1 tap
right hand hole, no overflow, bottom outlet, 400W
300D
BAS10511
1PULL CORD, patient/staff call (help) with
reassurance lamp
CAL00611
1PULL/PUSH BUTTON, staff emergency call, reset
and integral/adjacent indicator lamp
CAL00711
1RESET UNIT, with repeat lamp, patient/staff callCAL01211
1LAMP, repeat call, patient/staff or staff emergency or
cardiac call
CAL03411
1CISTERN WC/toilet, concealed, reversible. To suit
WC
CIS00511
1HOOK, single, small, wall mountedHOO01911
1MIRROR, wall mounted, 650H 300WMIR00111
1RAIL, grab, vertical, wall mounted, 600mmRAI04844
1RAIL, grab, horizontal, wall / door mounted, 500mmRAI15811
1RAIL, grab, horizontal, wall mounted, 600mmRAI16111
1RAIL, grab, hinged, wall mounted, 650mmRAI17211
1SHELF, raised edge, non-breakable, 300W 150DSHE10111
1SWITCH, lightSWC02511
1TAP, monobloc, pillar mixer, integral thermostatic,
short lever.
TAP28911
1WASTE, unslotted flush-grated, metal, 1.1/4 in. .WAS10011
1TRAP, bottle, 1.1/4 in, plastic resealing.WAS10711
1WC/toilet pan with seat, 520-550 projection, hospital
pattern, rimless pan, vitreous china.
WCH00111
2DISPENSER, paper towel, wall mountedDIS01311
2DISPENSER, toilet paper, dispense individual
sheets, wall mounted
DIS01511
2DISPENSER, soap, wall mountedDIS02411
3BIN, disposal, sealed, operated with one hand,
nominal 420H 155W 490D
BIN02811
3HOLDER, sack, with lid foot operated, small,
freestanding
HOL00411
Activity DataBase 01/03/2017
V1131Room Data SheetADB
Project: 7857 7857 Nottingham Uni Medical Centre
Department: PRI Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
Room: V1131 Nappy changing room
Room Number: Revision Date: 01/03/2017
1) Changing nappies.
2) Clinical waste may be disposed
3) Wash-hand basin may be used.
Activities:
Personnel: 1 x baby or infant.
1 x adult (ambulant).
Planning
Relationships:
Adjacent to waiting area and/or concourse
Space Data: Height (mm): 5.00 2,400Area (m²):
Notes: The call repeat lamp is situated over the door outside the room.
The room includes a wall-mounted fold-down changing table, alternatively, it can
accommodate a fixed or mobile table.
The layout is suitable for ambulant and semi-ambulant users, where access is required
for wheelchair users, consideration must be given to the space within the room and
fixing height of the changing table.
ADB Group Definitions:
1. Contractor supply and install.
2. Supply by others, contractor install.
3. UoN supply – loose equipment and specialist equipment (chairs, drawer units,
non-fixed medical equipment).
4. NHS IT equipment (nil cost to the project).
5. Dental supply and install.
6. Pharmacy supply and install.
7. UoN IT support and install.
8. UoN supply and install (tacks and blinds; fire extinguishers; UoN signage.
9. UoN F.O.C.
Activity DataBase 01/03/2017
7857 Nottingham Uni Medical Centre7857Project:
Room Environmental Data V1131ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: V1131 Nappy changing room
Room Number: Revision Date: 01/03/2017
Permissible Space Temerature Range(dry bulb) (degC):
TEMPERATURE AND VENTILATION Requirements Notes
18 - 28
Heating Design Temperature (dry bulb)(degC): 22
Minimum Air Changes (AC/hr): 10
Ventilation Type: E
-vePressure Relative to Adjoining Space:
Supply Air: Final Filter Class
Permisiible Relative Humidity Range (%): Uncontrolled
General Notes:
LIGHTINGType Of Control: N
Daytime General Service Illuminance (Lux): 200
Daytime Specific Service Illuminance (Lux):
Nighttime General Service Illuminance (Lux):
Nighttime Specific Service Illuminance (Lux):
Local Task Illuminance (Lux):
Colour Rendering Required: Y
Colour Rendering Required Characteristics (Ra): 80
Unified Glare Rating Limit (UGRL): 22
Emergency Escape Route Lighting Required: In accordance with BS 5266 and Health Technical
MemorandumsY
Standby Lighting Grade - General Lighting: B
Standby Lighting Grade - Local Lighting:
General Notes:
RISKClinical Risk Category:
Non-clinical Business Continuity Risk Category:
General Notes:
Noise Intrusion (dB) 1hr day:
NOISE
Noise Intrusion (dB) 1hr night:
Noise Intrusion (dB) f night:
45
-
-
Maximum Internal Noise from M&E Services (NR): 45 Total noise of MEP services under normal operation across
the range 63Hz to 4kHz inclusive.
Room Sound-insulation Parameters - Privacy:
Room Sound-insulation Parameters - Noise Generation:
Moderate
Typical
Reference to Table 3 of the Department of Health 'Acoustics:
Technical design manual 4032:0.6:England'.
Noise Sensitiviy: Not Sensitive
Sound-insulation Rating (dB D nT,w):
General Notes:
Maximum Surface Temperature (DegC):
SAFETY/FIRE
43
Domestic Hot Water Discharge Temperature (DegC): 41
Maximum Cold Water Discharge Temperature (DegC): <20
General Notes:
Type of Automatic Fire Detection: Smoke
General Notes:
Activity DataBase 01/03/2017
ADB Room Design Character V1131
Project: 7857 7857 Nottingham Uni Medical Centre
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Nappy changing roomV1131Room:
01/03/2017Revision Date:Room Number:
Walls: Wall finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Wall finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Floor: Floor finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Floor finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Ceiling: Ceiling finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Ceiling finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Doorsets: Configuration, glazing, fire rating, security, etc. to be determined by Project Team.
HTM 58 (Mar-2005)
Refer to HBN 00-04 (May-2007) for effective clear door widths.
1 doorset:
1 x personnel, wheelchair & equipment access (1000mm) - see HBN 00-02
Requirement for hinge protection when areas used by children
Windows: Not required
Internal Glazing: Not required
Hatch: Not required
Notes: All finishes selected must have an appropriate risk assessment to accompany the design
decision.
Infection Control must be consulted as described in Performance Requirements for Building
Elements Used in Healthcare Facilities 8941:0.6 England.
Activity DataBase 01/03/2017
Schedule of Components by Room
Project: 7857 7857 Nottingham Uni Medical Centre
V1131ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: V1131 Nappy changing room
Room Number: Revision Date: 01/03/2017
Key: (n-old qty) Deletions m-new qty Additions m (n) Quantity changes since audit dateAudit Date: 2-Mar-2017
DescriptionCodeTotalTransNew
GrpAlt. CodeQuantity
1BASIN, medium, general pattern, vitreous china, 2
tap holes, no overflow, bottom outlet, 500W 400D.
BAS10711
1HOOK, single, small, wall mountedHOO01922
1SOCKET outlet, switched, 13 amp, singleOUT00511
1CONNECTION UNIT, switched, 13 amp, flex outletOUT04911
1SHELF, raised edge, non-breakable, 300W 150DSHE10111
1SHELF, 600W 300DSHE20122
1WORKTOP, clinical, for 400 facing modular storage
cabinets, Width to fit, 700D
SMW90011
1SWITCH, lightSWC02511
1TAP, bib, 2x8 mm thermostatic mixer, automatic
action, sensor operated, non-touch,
TAP89211
1WASTE, unslotted recessed grated, metal, 1.1/4 in,
with plug and chain.
WAS10111
1TRAP, bottle, 1.1/4 in, plastic resealing.WAS10711
2DISPENSER, paper towel, wall mountedDIS01311
2DISPENSER, soap, wall mountedDIS02411
3HOLDER, sack, with lid foot operated, medium,
freestanding, 875H 430W 385D
HOL00611
3Counter Top Baby Changing Unit MT80, Magrini
LTD., 160H 780W 565D
NCU90111
Activity DataBase 01/03/2017
V1133Room Data SheetADB
Project: 7857 7857 Nottingham Uni Medical Centre
Department: PRI Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
Room: V1133 Changing room and toilet: accompanied: single-sided changing table access
Room Number: Revision Date: 01/03/2017
1) Independent wheelchair accessible toilet and adjacent hand-rinse basin may be used.
2) Adjustable height changing table with sides accessed from one side for changing nappies or
continence pads may be required.
3) Clinical waste may be disposed
4) Wash-hand basin may be used.
5) Call systems may be used.
Activities:
Personnel: 1 x young person (0-18 years) or adult with continence problems.
1 x accompanying carer (ambulant).
Planning
Relationships:
Adjacent to waiting area and/or concourse.
Space Data: Height (mm): 9.00 2,400Area (m²):
Notes: This room does not allow for the use of lifting aids for transfer to the toilet or changing
table. For guidance on public assisted changing spaces and the use of lifting aids go to
www.changingplaces.org. It is recommended that a risk assessment is carried out on the
use of public assisted changing spaces and the provision of lifting aids.
The call repeat lamp is situated over the door outside the room.
The following items are shown on the drawing but are optional:
- paper roll dispenser associated with couch.
The following items may be provided:
- mirror, light and shaver outlet.
ADB Group Definitions:
1. Contractor supply and install.
2. Supply by others, contractor install.
3. UoN supply – loose equipment and specialist equipment (chairs, drawer units,
non-fixed medical equipment).
4. NHS IT equipment (nil cost to the project).
5. Dental supply and install.
6. Pharmacy supply and install.
7. UoN IT support and install.
8. UoN supply and install (tacks and blinds; fire extinguishers; UoN signage.
9. UoN F.O.C.
Activity DataBase 01/03/2017
7857 Nottingham Uni Medical Centre7857Project:
Room Environmental Data V1133ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: V1133 Changing room and toilet: accompanied: single-sided changing table access
Room Number: Revision Date: 01/03/2017
Permissible Space Temerature Range(dry bulb) (degC):
TEMPERATURE AND VENTILATION Requirements Notes
18 - 28
Heating Design Temperature (dry bulb)(degC): 22
Minimum Air Changes (AC/hr): 6
Ventilation Type: E
-vePressure Relative to Adjoining Space:
Supply Air: Final Filter Class
Permisiible Relative Humidity Range (%): Uncontrolled
General Notes:
LIGHTINGType Of Control: N
Daytime General Service Illuminance (Lux): 200
Daytime Specific Service Illuminance (Lux):
Nighttime General Service Illuminance (Lux):
Nighttime Specific Service Illuminance (Lux):
Local Task Illuminance (Lux):
Colour Rendering Required: Y
Colour Rendering Required Characteristics (Ra): 80
Unified Glare Rating Limit (UGRL): 22
Emergency Escape Route Lighting Required: In accordance with BS 5266 and Health Technical
MemorandumsY
Standby Lighting Grade - General Lighting: B
Standby Lighting Grade - Local Lighting:
General Notes:
RISKClinical Risk Category:
Non-clinical Business Continuity Risk Category:
General Notes:
Noise Intrusion (dB) 1hr day:
NOISE
Noise Intrusion (dB) 1hr night:
Noise Intrusion (dB) f night:
45
-
-
Maximum Internal Noise from M&E Services (NR): 45 Total noise of MEP services under normal operation across
the range 63Hz to 4kHz inclusive.
Room Sound-insulation Parameters - Privacy:
Room Sound-insulation Parameters - Noise Generation:
Moderate
Typical
Reference to Table 3 of the Department of Health 'Acoustics:
Technical design manual 4032:0.6:England'.
Noise Sensitiviy: Not Sensitive
Sound-insulation Rating (dB D nT,w):
General Notes:
Maximum Surface Temperature (DegC):
SAFETY/FIRE
43
Domestic Hot Water Discharge Temperature (DegC): 41
Maximum Cold Water Discharge Temperature (DegC): <20
General Notes:
Type of Automatic Fire Detection: Smoke
General Notes:
Activity DataBase 01/03/2017
ADB Room Design Character V1133
Project: 7857 7857 Nottingham Uni Medical Centre
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Changing room and toilet: accompanied: single-sided changing table accessV1133Room:
01/03/2017Revision Date:Room Number:
Walls: Wall finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Wall finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Floor: Floor finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Floor finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Ceiling: Ceiling finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Ceiling finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Doorsets: Configuration, glazing, fire rating, security, etc. to be determined by Project Team.
HTM 58 (Mar-2005)
Refer to HBN 00-04 (May-2007) for effective clear door widths.
1 doorset:
1 x personnel, wheelchair & equipment access (1000mm) - see HBN 00-02
Requirement for hinge protection when areas used by children
Windows: Not required
Internal Glazing: Not required
Hatch: Not required
Notes: All finishes selected must have an appropriate risk assessment to accompany the design
decision.
Infection Control must be consulted as described in Performance Requirements for Building
Elements Used in Healthcare Facilities 8941:0.6 England.
Activity DataBase 01/03/2017
Schedule of Components by Room
Project: 7857 7857 Nottingham Uni Medical Centre
V1133ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: V1133 Changing room and toilet: accompanied: single-sided changing table access
Room Number: Revision Date: 01/03/2017
Key: (n-old qty) Deletions m-new qty Additions m (n) Quantity changes since audit dateAudit Date: 2-Mar-2017
DescriptionCodeTotalTransNew
GrpAlt. CodeQuantity
1BACKREST, WC/toilet, padded, wall mountedBAC00211
1BASIN, small, general pattern, vitreous china, 1 tap
right hand hole, no overflow, bottom outlet, 400W
300D
BAS10511
1BASIN, medium, general pattern, vitreous china, 2
tap holes, no overflow, bottom outlet, 500W 400D.
BAS10711
1PUSH BUTTON patient/staff call, wall mountedCAL00211
1PULL CORD, patient/staff call (help) with
reassurance lamp
CAL00611
1PULL/PUSH BUTTON, staff emergency call, reset
and integral/adjacent indicator lamp
CAL00711
1RESET UNIT, with repeat lamp, patient/staff callCAL01222
1LAMP, repeat call, patient/staff or staff emergency or
cardiac call
CAL03411
1CISTERN WC/toilet, concealed, reversible. To suit
WC
CIS00511
1HOOK, single, small, wall mountedHOO01922
1SOCKET outlet, switched, 13 amp, singleOUT00511
1CONNECTION UNIT, switched, 13 amp, flex outletOUT04911
1RAIL, grab, vertical, wall mounted, 600mmRAI04833
1RAIL, grab, horizontal, with supports, wall mounted,
600mm
RAI15911
1RAIL, grab, hinged, wall mounted, 650mmRAI17211
1SHELF, raised edge, non-breakable, 200W 150DSHE10211
1SHELF, 400W 300DSHE57711
1SWITCH, lightSWC02511
1TAP, monobloc, pillar mixer, integral thermostatic,
short lever.
TAP28911
1TAP, bib, 2x8 mm thermostatic mixer, automatic
action, sensor operated, non-touch,
TAP89211
1WASTE, unslotted flush-grated, metal, 1.1/4 in. .WAS10011
1WASTE, unslotted recessed grated, metal, 1.1/4 in,
with plug and chain.
WAS10111
1TRAP, bottle, 1.1/4 in, plastic resealing.WAS10722
1WC/toilet pan with seat, 700 mm projection, hospital
pattern, rimless pan, vitreous china.
WCH00511
2DISPENSER, paper towel, wall mountedDIS01322
2DISPENSER, toilet paper, dispense individual
sheets, wall mounted
DIS01511
2DISPENSER, soap, wall mountedDIS02422
2DISPENSER, wipes, door mountedDIS06411
3BIN, disposal, sealed, operated with one hand,
nominal 420H 155W 490D
BIN02811
3CHAIR, stacking, polypropylene, with back and seat
pads, wipeable.
CHA38311
3HOLDER, sack, with lid foot operated, medium,
freestanding, 875H 430W 385D
HOL00611
Activity DataBase 01/03/2017
Schedule of Components by Room
Project: 7857 7857 Nottingham Uni Medical Centre
V1133ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: V1133 Changing room and toilet: accompanied: single-sided changing table access
Room Number: Revision Date: 01/03/2017
Key: (n-old qty) Deletions m-new qty Additions m (n) Quantity changes since audit dateAudit Date: 2-Mar-2017
DescriptionCodeTotalTransNew
GrpAlt. CodeQuantity
3HOLDER, sack with lid foot operated, large,
freestanding, 960H 500W 415D
HOL00811
3TABLE/TROLLEY changing, variable height, with
sides and paper roll holder, on castors, 500-920H
1820W 700D
TAB09811
Activity DataBase 01/03/2017
V1321Room Data SheetADB
Project: 7857 7857 Nottingham Uni Medical Centre
Department: PRI Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
Room: V1321 Shower room: ambulant
Room Number: Revision Date: 01/03/2017
1) Shower may be used by ambulant person.
2) User may undress and dress in privacy.
3) Hanging outdoor clothing.
4) Hanging clothes and towels.
Activities:
Personnel: 1 x person (staff or visitor).
Intermittent use.
Planning
Relationships:
Associated with staff changing area.
Close to a WC.
Space Data: Height (mm): 2.50 2,400Area (m²):
Notes: This room is not recommended for patient use.
The following items may be provided:
- inward opening door;
- full length mirror.
ADB Group Definitions:
1. Contractor supply and install.
2. Supply by others, contractor install.
3. UoN supply – loose equipment and specialist equipment (chairs, drawer units,
non-fixed medical equipment).
4. NHS IT equipment (nil cost to the project).
5. Dental supply and install.
6. Pharmacy supply and install.
7. UoN IT support and install.
8. UoN supply and install (tacks and blinds; fire extinguishers; UoN signage.
9. UoN F.O.C.
Activity DataBase 01/03/2017
7857 Nottingham Uni Medical Centre7857Project:
Room Environmental Data V1321ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: V1321 Shower room: ambulant
Room Number: Revision Date: 01/03/2017
Permissible Space Temerature Range(dry bulb) (degC):
TEMPERATURE AND VENTILATION Requirements Notes
18 - 28
Heating Design Temperature (dry bulb)(degC): 22
Minimum Air Changes (AC/hr): 10
Ventilation Type: E
-vePressure Relative to Adjoining Space:
Supply Air: Final Filter Class
Permisiible Relative Humidity Range (%): Uncontrolled
General Notes:
LIGHTINGType Of Control: N
Daytime General Service Illuminance (Lux): 100-150
Daytime Specific Service Illuminance (Lux):
Nighttime General Service Illuminance (Lux):
Nighttime Specific Service Illuminance (Lux):
Local Task Illuminance (Lux):
Colour Rendering Required: Y
Colour Rendering Required Characteristics (Ra): 80
Unified Glare Rating Limit (UGRL): 22
Emergency Escape Route Lighting Required: In accordance with BS 5266 and Health Technical
MemorandumsY
Standby Lighting Grade - General Lighting: B
Standby Lighting Grade - Local Lighting:
General Notes:
RISKClinical Risk Category:
Non-clinical Business Continuity Risk Category:
General Notes:
Noise Intrusion (dB) 1hr day:
NOISE
Noise Intrusion (dB) 1hr night:
Noise Intrusion (dB) f night:
55
-
-
Maximum Internal Noise from M&E Services (NR): 45 Total noise of MEP services under normal operation across
the range 63Hz to 4kHz inclusive.
Room Sound-insulation Parameters - Privacy:
Room Sound-insulation Parameters - Noise Generation:
Moderate
Typical
Reference to Table 3 of the Department of Health 'Acoustics:
Technical design manual 4032:0.6:England'.
Noise Sensitiviy: Not Sensitive
Sound-insulation Rating (dB D nT,w):
General Notes:
Maximum Surface Temperature (DegC):
SAFETY/FIRE
43
Domestic Hot Water Discharge Temperature (DegC): 41
Maximum Cold Water Discharge Temperature (DegC): <20
General Notes:
Type of Automatic Fire Detection: Omitted via risk assessment
General Notes:
Activity DataBase 01/03/2017
ADB Room Design Character V1321
Project: 7857 7857 Nottingham Uni Medical Centre
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Shower room: ambulantV1321Room:
01/03/2017Revision Date:Room Number:
Walls: Wall finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Wall finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Floor: Floor finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Floor finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Ceiling: Ceiling finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Ceiling finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Doorsets: Configuration, glazing, fire rating, security, etc. to be determined by Project Team.
HTM 58 (Mar-2005)
Refer to HBN 00-04 (May-2007) for effective clear door widths.
1 doorset:
1 x personnel access (900mm) - see HBN 00-02
Requirement for hinge protection when areas used by children
Windows: Not required
Internal Glazing: Not required
Hatch: Not required
Notes: All finishes selected must have an appropriate risk assessment to accompany the design
decision.
Infection Control must be consulted as described in Performance Requirements for Building
Elements Used in Healthcare Facilities 8941:0.6 England.
Activity DataBase 01/03/2017
Schedule of Components by Room
Project: 7857 7857 Nottingham Uni Medical Centre
V1321ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: V1321 Shower room: ambulant
Room Number: Revision Date: 01/03/2017
Key: (n-old qty) Deletions m-new qty Additions m (n) Quantity changes since audit dateAudit Date: 2-Mar-2017
DescriptionCodeTotalTransNew
GrpAlt. CodeQuantity
1DISH, soap, wall mountedDIS20011
1HOOK, single, small, wall mountedHOO01933
1LUMINAIRE, single fluorescent lamp, wall, 8 watt,
300 mm
LIG06311
1MIRROR, wall mounted, 900H 300WMIR00211
1SOCKET outlet, shaverOUT02511
1RAIL for shower curtain, 1000mmRAI26011
1SEAT, tip-up, wall mounted, 400 W 400DSEA02411
1SHELF, raised edge, non-breakable, 300W 150DSHE10111
1SHOWER TRAY ceramic slip resistant base, with
drainage outlet, 800W 800D
SHO00911
1SHOWER, valve, thermostatic mixer (associated with
SHO020).
SHO01811
1SHOWER, adjustable shower head hand spray
(associated with SHO018).
SHO02011
1SWITCH 5amp ac single pole, 1 way, ceiling pull
cord
SWC01411
1WASTE, unslotted flush-grated, metal, 1.1/4 in. .WAS10011
Activity DataBase 01/03/2017
V1625Room Data SheetADB
Project: 7857 7857 Nottingham Uni Medical Centre
Department: PRI Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
Room: V1625 Shower, WC and wash: en-suite, assisted wheelchair accessible
Non-touch WC cistern
Room Number: Revision Date: 01/03/2017
1) Patient/user may be ambulant, or in a wheelchair.
2) Patient may arrive in sanitary chair.
3) Hanging clothes and towels.
4) Transfer patient to/from shower chair/seat.
5) Using shower.
6) Using WC.
7) Personal washing for a seated person.
8) Grooming for a seated person.
9) Using electric shaver.
10) Patient may require assistance during the activities.
Activities:
Personnel: 1 x Patient
1 x Staff
Planning
Relationships:
Easy access to/from patient bed areas.
En-suite to bedroom.
En-suite to overnight stay.
Space Data: Height (mm): 6.00 2,400Area (m²):
Notes: Adequate space should be allowed either or both sides of the WC for assist the patient.
Use of hoist/ceiling hoist.
For layout see HBN Hosp. acom for children and young people Appendix 4 sheet 1.
ADB Group Definitions:
1. Contractor supply and install.
2. Supply by others, contractor install.
3. UoN supply – loose equipment and specialist equipment (chairs, drawer units,
non-fixed medical equipment).
4. NHS IT equipment (nil cost to the project).
5. Dental supply and install.
6. Pharmacy supply and install.
7. UoN IT support and install.
8. UoN supply and install (tacks and blinds; fire extinguishers; UoN signage.
9. UoN F.O.C.
Activity DataBase 01/03/2017
7857 Nottingham Uni Medical Centre7857Project:
Room Environmental Data V1625ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: V1625 Shower, WC and wash: en-suite, assisted wheelchair accessible
Non-touch WC cistern
Room Number: Revision Date: 01/03/2017
Permissible Space Temerature Range(dry bulb) (degC):
TEMPERATURE AND VENTILATION Requirements Notes
18 - 28
Heating Design Temperature (dry bulb)(degC): 21
Minimum Air Changes (AC/hr): 6
Ventilation Type: E
-vePressure Relative to Adjoining Space:
Supply Air: Final Filter Class
Permisiible Relative Humidity Range (%): Uncontrolled
General Notes:
LIGHTINGType Of Control: N
Daytime General Service Illuminance (Lux): 200
Daytime Specific Service Illuminance (Lux):
Nighttime General Service Illuminance (Lux):
Nighttime Specific Service Illuminance (Lux):
Local Task Illuminance (Lux):
Colour Rendering Required: Y
Colour Rendering Required Characteristics (Ra): 80
Unified Glare Rating Limit (UGRL): 22
Emergency Escape Route Lighting Required: In accordance with BS 5266 and Health Technical
MemorandumsY
Standby Lighting Grade - General Lighting: B
Standby Lighting Grade - Local Lighting:
General Notes:
RISKClinical Risk Category:
Non-clinical Business Continuity Risk Category:
General Notes:
Noise Intrusion (dB) 1hr day:
NOISE
Noise Intrusion (dB) 1hr night:
Noise Intrusion (dB) f night:
45
-
-
Maximum Internal Noise from M&E Services (NR): 40 Total noise of MEP services under normal operation across
the range 63Hz to 4kHz inclusive.
Room Sound-insulation Parameters - Privacy:
Room Sound-insulation Parameters - Noise Generation:
Moderate
Typical
Reference to Table 3 of the Department of Health 'Acoustics:
Technical design manual 4032:0.6:England'.
Noise Sensitiviy: Not Sensitive
Sound-insulation Rating (dB D nT,w):
General Notes:
Maximum Surface Temperature (DegC):
SAFETY/FIRE
43
Domestic Hot Water Discharge Temperature (DegC): 41
Maximum Cold Water Discharge Temperature (DegC): <20
General Notes:
Type of Automatic Fire Detection: Omitted via risk assessment
General Notes:
Activity DataBase 01/03/2017
ADB Room Design Character V1625
Project: 7857 7857 Nottingham Uni Medical Centre
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Shower, WC and wash: en-suite, assisted wheelchair accessible
Non-touch WC cistern
V1625Room:
01/03/2017Revision Date:Room Number:
Walls: Wall finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Wall finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Floor: Floor finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Floor finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Ceiling: Ceiling finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Ceiling finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Doorsets: Configuration, glazing, fire rating, security, etc. to be determined by Project Team.
HTM 58 (Mar-2005)
Refer to HBN 00-04 (May-2007) for effective clear door widths.
1 doorset:
1 x personnel, wheelchair & equipment access (1000mm) - see HBN 00-02
Requirement for hinge protection when areas used by children
Windows: Not required
Internal Glazing: Not required
Hatch: Not required
Notes: All finishes selected must have an appropriate risk assessment to accompany the design
decision.
Infection Control must be consulted as described in Performance Requirements for Building
Elements Used in Healthcare Facilities 8941:0.6 England.
Activity DataBase 01/03/2017
Schedule of Components by Room
Project: 7857 7857 Nottingham Uni Medical Centre
V1625ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: V1625 Shower, WC and wash: en-suite, assisted wheelchair accessible
Non-touch WC cistern
Room Number: Revision Date: 01/03/2017
Key: (n-old qty) Deletions m-new qty Additions m (n) Quantity changes since audit dateAudit Date: 2-Mar-2017
DescriptionCodeTotalTransNew
GrpAlt. CodeQuantity
1BACKREST, WC/toilet, padded, wall mountedBAC00211
1BASIN, small, general pattern, vitreous china, 1 tap
right hand hole, no overflow, bottom outlet, 400W
300D
BAS10511
1PULL CORD, patient/staff call (help) with
reassurance lamp
CAL00622
1RESET UNIT, with repeat lamp, patient/staff callCAL01222
1CISTERN WC/toilet, concealed, reversible. To suit
WC
CIS00511
1DISH, soap, wall mountedDIS20011
1HOOK, single, small, wall mountedHOO01911
1RAIL, grab, vertical, wall mounted, 600mmRAI04855
1RAIL, towel, single stainless steel, 15mm dia.
450mm
RAI06111
1RAIL, grab, horizontal, with supports, wall mounted,
600mm
RAI15911
1RAIL, grab, horizontal, cranked, L-shape, wall
mounted, 1550W 450D
RAI16411
1RAIL, grab, hinged, wall mounted, 650mmRAI17211
1SEAT, tip-up, wall mounted, 400 W 400DSEA02411
1SHELF, raised edge, non-breakable, 200W 150DSHE10211
1SHOWER, slip resistant floor, with drainage outlet,
1600W 1100D
SHO00711
1SHOWER, valve, thermostatic mixer (associated with
SHO020).
SHO01811
1SHOWER, adjustable shower head hand spray
(associated with SHO018).
SHO02011
1STORAGE UNIT, mid, shelf, 150H 300W 150D,
HTM63
STF20011
1TAP, monobloc, pillar mixer, integral thermostatic,
short lever.
TAP28911
1WASTE, unslotted flush-grated, metal, 1.1/4 in. .WAS10011
1TRAP, bottle, 1.1/4 in, plastic resealing.WAS10711
1WC/toilet pan with seat, 700 mm projection, hospital
pattern, rimless pan, vitreous china.
WCH00511
2DISPENSER, paper towel, wall mountedDIS01322
2DISPENSER, toilet paper, dispense individual
sheets, wall mounted
DIS01511
2DISPENSER, soap, wall mountedDIS02411
3BIN, disposal, sealed, operated with one hand,
nominal 420H 155W 490D
BIN02811
3HOLDER, sack, small, freestandingHOL00311
3RAIL for shower curtain, Width to fitRAI90011
Activity DataBase 01/03/2017
V1631Room Data SheetADB
Project: 7857 7857 Nottingham Uni Medical Centre
Department: PRI Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
Room: V1631 Shower room: independent wheelchair
Room Number: Revision Date: 01/03/2017
1) Shower may be used by a person who is an independent wheelchair user.
2) Independent wheelchair accessible toilet and adjacent hand-rinse basin may be used.
3) User may undress and dress in privacy.
4) Hanging outdoor clothing.
5) Hanging clothes and towels.
6) Use of shower chair.
7) Personal grooming by an individual.
8) Call systems may be used.
9) Wheelchair accessible hand-wash basin may be used.
Activities:
Personnel: 1 x person.
Intermittent use.
Planning
Relationships:
Space Data: Height (mm): 7.00 2,400Area (m²):
Notes: The call repeat lamp is situated over the door outside the room.
The following items are shown on the drawing but are optional:
- the bin for the disposal of sanitary towels is only required in female WCs;
- mirror, light and shaver outlet.
The following items may be provided:
- modular shelf;
- fixed shower head.
ADB Group Definitions:
1. Contractor supply and install.
2. Supply by others, contractor install.
3. UoN supply – loose equipment and specialist equipment (chairs, drawer units,
non-fixed medical equipment).
4. NHS IT equipment (nil cost to the project).
5. Dental supply and install.
6. Pharmacy supply and install.
7. UoN IT support and install.
8. UoN supply and install (tacks and blinds; fire extinguishers; UoN signage.
9. UoN F.O.C.
Activity DataBase 01/03/2017
7857 Nottingham Uni Medical Centre7857Project:
Room Environmental Data V1631ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: V1631 Shower room: independent wheelchair
Room Number: Revision Date: 01/03/2017
Permissible Space Temerature Range(dry bulb) (degC):
TEMPERATURE AND VENTILATION Requirements Notes
18 - 28
Heating Design Temperature (dry bulb)(degC): 22
Minimum Air Changes (AC/hr): 10
Ventilation Type: E
-vePressure Relative to Adjoining Space:
Supply Air: Final Filter Class
Permisiible Relative Humidity Range (%): Uncontrolled
General Notes:
LIGHTINGType Of Control: N
Daytime General Service Illuminance (Lux): 200
Daytime Specific Service Illuminance (Lux):
Nighttime General Service Illuminance (Lux):
Nighttime Specific Service Illuminance (Lux):
Local Task Illuminance (Lux):
Colour Rendering Required: Y
Colour Rendering Required Characteristics (Ra): 80
Unified Glare Rating Limit (UGRL): 22
Emergency Escape Route Lighting Required: In accordance with BS 5266 and Health Technical
MemorandumsY
Standby Lighting Grade - General Lighting: B
Standby Lighting Grade - Local Lighting:
General Notes:
RISKClinical Risk Category:
Non-clinical Business Continuity Risk Category:
General Notes:
Noise Intrusion (dB) 1hr day:
NOISE
Noise Intrusion (dB) 1hr night:
Noise Intrusion (dB) f night:
55
-
-
Maximum Internal Noise from M&E Services (NR): 45 Total noise of MEP services under normal operation across
the range 63Hz to 4kHz inclusive.
Room Sound-insulation Parameters - Privacy:
Room Sound-insulation Parameters - Noise Generation:
Moderate
Typical
Reference to Table 3 of the Department of Health 'Acoustics:
Technical design manual 4032:0.6:England'.
Noise Sensitiviy: Not Sensitive
Sound-insulation Rating (dB D nT,w):
General Notes:
Maximum Surface Temperature (DegC):
SAFETY/FIRE
43
Domestic Hot Water Discharge Temperature (DegC): 41
Maximum Cold Water Discharge Temperature (DegC): <20
General Notes:
Type of Automatic Fire Detection: Omitted via risk assessment
General Notes:
Activity DataBase 01/03/2017
ADB Room Design Character V1631
Project: 7857 7857 Nottingham Uni Medical Centre
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Shower room: independent wheelchairV1631Room:
01/03/2017Revision Date:Room Number:
Walls: Wall finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Wall finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Floor: Floor finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Floor finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Ceiling: Ceiling finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Ceiling finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Doorsets: Configuration, glazing, fire rating, security, etc. to be determined by Project Team.
HTM 58 (Mar-2005)
Refer to HBN 00-04 (May-2007) for effective clear door widths.
1 doorset:
1 x personnel, wheelchair & equipment access (1000mm) - see HBN 00-02
Requirement for hinge protection when areas used by children
Windows: Not required
Internal Glazing: Not required
Hatch: Not required
Notes: All finishes selected must have an appropriate risk assessment to accompany the design
decision.
Infection Control must be consulted as described in Performance Requirements for Building
Elements Used in Healthcare Facilities 8941:0.6 England.
Activity DataBase 01/03/2017
Schedule of Components by Room
Project: 7857 7857 Nottingham Uni Medical Centre
V1631ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: V1631 Shower room: independent wheelchair
Room Number: Revision Date: 01/03/2017
Key: (n-old qty) Deletions m-new qty Additions m (n) Quantity changes since audit dateAudit Date: 2-Mar-2017
DescriptionCodeTotalTransNew
GrpAlt. CodeQuantity
1BACKREST, WC/toilet, padded, wall mountedBAC00211
1BASIN, small, general pattern, vitreous china, 1 tap
right hand hole, no overflow, bottom outlet, 400W
300D
BAS10511
1BASIN, large, general pattern, vitreous china, 2 tap
holes, no overflow, bottom outlet, 600W 500D.
BAS10911
1PULL CORD, patient/staff call (help) with
reassurance lamp
CAL00633
1PULL/PUSH BUTTON, staff emergency call, reset
and integral/adjacent indicator lamp
CAL00711
1RESET UNIT, with repeat lamp, patient/staff callCAL01222
1LAMP, repeat call, patient/staff or staff emergency or
cardiac call
CAL03411
1CISTERN WC/toilet, concealed, reversible. To suit
WC
CIS00511
1DISH, soap, wall mountedDIS20011
1HOOK, single, small, wall mountedHOO01922
1LUMINAIRE, single fluorescent lamp, wall, 8 watt,
300 mm
LIG06311
1MIRROR, wall mounted, 900H 300WMIR00211
1MIRROR, unbreakable, wall mounted, 1300H 500WMIR02611
1SOCKET outlet, shaverOUT02511
1OUTLET, floor drainage and grating, 150 mm dia.
hospital pattern.
OUT34511
1RAIL, grab, vertical, wall mounted, 600mmRAI04855
1RAIL, grab, horizontal, with supports, wall mounted,
600mm
RAI15911
1RAIL, grab, horizontal, wall mounted, 600mmRAI16133
1RAIL, grab, hinged, wall mounted, 650mmRAI17222
1RAIL for shower curtain, L-shape, 920W 920DRAI27011
1SEAT, tip-up, fixed heightSEA02211
1SEAT, tip-up, wall mounted, 400 W 400DSEA02411
1SHELF, raised edge, non-breakable, 300W 150DSHE10111
1SHELF, raised edge, non-breakable, 200W 150DSHE10211
1SHOWER, valve, thermostatic mixer (associated with
SHO020).
SHO01811
1SHOWER, adjustable shower head hand spray
(associated with SHO018).
SHO02011
1SHOWER, slip resistant floor, with drainage outlet,
1040W 1040D
SHO03611
1SWITCH 5amp ac single pole, 1 way, ceiling pull
cord
SWC01411
1TAP, monobloc, pillar mixer, integral thermostatic,
short lever.
TAP28911
1TAP, pillar, short lever, pair hot and cold, 1/2 in.TAP34711
1WASTE, unslotted flush-grated, metal, 1.1/4 in. .WAS10011
1WASTE, unslotted recessed grated, metal, 1.1/4 in,
with plug and chain.
WAS10111
Activity DataBase 01/03/2017
Schedule of Components by Room
Project: 7857 7857 Nottingham Uni Medical Centre
V1631ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: V1631 Shower room: independent wheelchair
Room Number: Revision Date: 01/03/2017
Key: (n-old qty) Deletions m-new qty Additions m (n) Quantity changes since audit dateAudit Date: 2-Mar-2017
DescriptionCodeTotalTransNew
GrpAlt. CodeQuantity
1TRAP, bottle, 1.1/4 in, plastic resealing.WAS10722
1WC/toilet pan with seat, 700 mm projection, hospital
pattern, rimless pan, vitreous china.
WCH00511
2DISPENSER, paper towel, wall mountedDIS01322
2DISPENSER, toilet paper, dispense individual
sheets, wall mounted
DIS01511
2DISPENSER, soap, wall mountedDIS02422
3BIN, disposal, sealed, operated with one hand,
nominal 420H 155W 490D
BIN02811
3HOLDER, sack, small, freestandingHOL00311
Activity DataBase 01/03/2017
V1635-01Room Data SheetADB
Project: 7857 7857 Nottingham Uni Medical Centre
Department: PRI Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
Room: V1635-01 Shower room: assisted: in-patient
Room Number: Revision Date: 01/03/2017
1) Use of shower requires assistance. The shower may have an adjustable or fixed tip-up
shower seat.
2) Use of toilet requires assistance.
3) Wheelchair accessible hand-wash basin may be used.
4) User may undress and dress in privacy.
5) Hanging outdoor clothing.
6) Hanging clothes and towels.
7) Sanitary chair/commode may be used.
8) Use of shower chair.
9) Mobile hoist may be used.
10) Call systems may be used.
Activities:
Personnel: 1 x patient.
1-2 x assistants.
Intermittent use.
Planning
Relationships:
Space Data: Height (mm): 6.50 2,400Area (m²):
Notes: The call repeat lamp is situated over the door outside the room.
The following items are shown on the drawing but are optional:
- the bin for the disposal of sanitary towels is only required in female WCs;
- mirror, light and shaver outlet.
The following items may be provided:
- modular shelf;
- fixed shower head;
- adjustable height basin;
- mobile shower chair in lieu of fixed seat;
ADB Group Definitions:
1. Contractor supply and install.
2. Supply by others, contractor install.
3. UoN supply – loose equipment and specialist equipment (chairs, drawer units,
non-fixed medical equipment).
4. NHS IT equipment (nil cost to the project).
5. Dental supply and install.
6. Pharmacy supply and install.
7. UoN IT support and install.
8. UoN supply and install (tacks and blinds; fire extinguishers; UoN signage.
9. UoN F.O.C.
Activity DataBase 01/03/2017
7857 Nottingham Uni Medical Centre7857Project:
Room Environmental Data V1635-01ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: V1635-01 Shower room: assisted: in-patient
Room Number: Revision Date: 01/03/2017
Permissible Space Temerature Range(dry bulb) (degC):
TEMPERATURE AND VENTILATION Requirements Notes
18 - 28
Heating Design Temperature (dry bulb)(degC): 22
Minimum Air Changes (AC/hr): 10
Ventilation Type: E
-vePressure Relative to Adjoining Space:
Supply Air: Final Filter Class
Permisiible Relative Humidity Range (%): Uncontrolled
General Notes:
LIGHTINGType Of Control: N
Daytime General Service Illuminance (Lux): 200
Daytime Specific Service Illuminance (Lux):
Nighttime General Service Illuminance (Lux):
Nighttime Specific Service Illuminance (Lux):
Local Task Illuminance (Lux):
Colour Rendering Required: Y
Colour Rendering Required Characteristics (Ra): 80
Unified Glare Rating Limit (UGRL): 22
Emergency Escape Route Lighting Required: In accordance with BS 5266 and Health Technical
MemorandumsY
Standby Lighting Grade - General Lighting: B
Standby Lighting Grade - Local Lighting:
General Notes:
RISKClinical Risk Category:
Non-clinical Business Continuity Risk Category:
General Notes:
Noise Intrusion (dB) 1hr day:
NOISE
Noise Intrusion (dB) 1hr night:
Noise Intrusion (dB) f night:
55
-
-
Maximum Internal Noise from M&E Services (NR): 45 Total noise of MEP services under normal operation across
the range 63Hz to 4kHz inclusive.
Room Sound-insulation Parameters - Privacy:
Room Sound-insulation Parameters - Noise Generation:
Moderate
Typical
Reference to Table 3 of the Department of Health 'Acoustics:
Technical design manual 4032:0.6:England'.
Noise Sensitiviy: Not Sensitive
Sound-insulation Rating (dB D nT,w):
General Notes:
Maximum Surface Temperature (DegC):
SAFETY/FIRE
43
Domestic Hot Water Discharge Temperature (DegC): 41
Maximum Cold Water Discharge Temperature (DegC): <20
General Notes:
Type of Automatic Fire Detection: Omitted via risk assessment
General Notes:
Activity DataBase 01/03/2017
ADB Room Design Character V1635-01
Project: 7857 7857 Nottingham Uni Medical Centre
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Shower room: assisted: in-patientV1635-01Room:
01/03/2017Revision Date:Room Number:
Walls: Wall finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Wall finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Floor: Floor finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Floor finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Ceiling: Ceiling finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Ceiling finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Doorsets: Configuration, glazing, fire rating, security, etc. to be determined by Project Team.
HTM 58 (Mar-2005)
Refer to HBN 00-04 (May-2007) for effective clear door widths.
1 doorset:
1 x personnel, wheelchair & equipment access (1500mm) - see HBN 00-02
Requirement for hinge protection when areas used by children
Windows: Not required
Internal Glazing: Not required
Hatch: Not required
Notes: All finishes selected must have an appropriate risk assessment to accompany the design
decision.
Infection Control must be consulted as described in Performance Requirements for Building
Elements Used in Healthcare Facilities 8941:0.6 England.
Activity DataBase 01/03/2017
Schedule of Components by Room
Project: 7857 7857 Nottingham Uni Medical Centre
V1635-01ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: V1635-01 Shower room: assisted: in-patient
Room Number: Revision Date: 01/03/2017
Key: (n-old qty) Deletions m-new qty Additions m (n) Quantity changes since audit dateAudit Date: 2-Mar-2017
DescriptionCodeTotalTransNew
GrpAlt. CodeQuantity
1BACKREST, WC/toilet, padded, wall mountedBAC00211
1BASIN, large, general pattern, vitreous china, 2 tap
holes, no overflow, bottom outlet, 600W 500D.
BAS10911
1PULL CORD, patient/staff call (help) with
reassurance lamp
CAL00633
1PULL/PUSH BUTTON, staff emergency call, reset
and integral/adjacent indicator lamp
CAL00711
1RESET UNIT, with repeat lamp, patient/staff callCAL01211
1LAMP, repeat call, patient/staff or staff emergency or
cardiac call
CAL03411
1CISTERN WC/toilet, concealed, reversible. To suit
WC
CIS00511
1HOOK, single, small, wall mountedHOO01922
1LUMINAIRE, single fluorescent lamp, wall, 8 watt,
300 mm
LIG06311
1MIRROR, wall mounted, 900H 300WMIR00211
1MIRROR, unbreakable, wall mounted, 1300H 500WMIR02611
1SOCKET outlet, shaverOUT02511
1OUTLET, floor drainage and grating, 150 mm dia.
hospital pattern.
OUT34511
1RAIL, grab, vertical, wall mounted, 600mmRAI04844
1RAIL, grab, horizontal, wall mounted, 600mmRAI16122
1RAIL, grab, hinged, wall mounted, 650mmRAI17233
1RAIL, grab, hinged, wall mounted, 650mm with toilet
roll holder
RAI17411
1RAIL for shower curtain, L-shape, 920W 1200DRAI27211
1SEAT, tip-up, fixed heightSEA02211
1SHOWER, valve, thermostatic mixer (associated with
SHO020).
SHO01811
1SHOWER, adjustable shower head hand spray
(associated with SHO018).
SHO02011
1SWITCH 5amp ac single pole, 1 way, ceiling pull
cord
SWC01411
1TAP, pillar, short lever, pair hot and cold, 1/2 in.TAP34711
1WASTE, unslotted recessed grated, metal, 1.1/4 in,
with plug and chain.
WAS10111
1TRAP, bottle, 1.1/4 in, plastic resealing.WAS10711
1WC/toilet pan with seat, 700 mm projection, hospital
pattern, rimless pan, vitreous china.
WCH00511
2DISPENSER, paper towel, wall mountedDIS01311
2DISPENSER, soap, wall mountedDIS02411
2SHELF, modular unitSHE10411
3BIN, disposal, sealed, operated with one hand,
nominal 420H 155W 490D
BIN02811
3HOLDER, sack, with lid foot operated, medium,
freestanding, 875H 430W 385D
HOL00611
Activity DataBase 01/03/2017
W0274Room Data SheetADB
Project: 7857 7857 Nottingham Uni Medical Centre
Department: PRI Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
Room: W0274 Store: medicines
Room Number: Revision Date: 01/03/2017
1) Non-controlled medicines and pharmaceuticals are stored securely.
2) Refrigerated storage of drugs/medicines.
Activities:
Personnel: 1 x staff.
Intermittent use.
Planning
Relationships:
Close to dispensary.
Space Data: Height (mm): 12.00 2,400Area (m²):
Notes: This is store is suitable for use as a:
- non-formulary drugs store;
- returned medicines store;
- clinical trials store;
- unlicensed medicines store.
The following items are shown on the room layout but are optional:
- freezer
The following items may be provided:
- Door alarm to provide access monitoring.
Separate data and voice outlets may be used where structure cabling solutions are not
available.
ADB Group Definitions:
1. Contractor supply and install.
2. Supply by others, contractor install.
3. UoN supply – loose equipment and specialist equipment (chairs, drawer units,
non-fixed medical equipment).
4. NHS IT equipment (nil cost to the project).
5. Dental supply and install.
6. Pharmacy supply and install.
7. UoN IT support and install.
8. UoN supply and install (tacks and blinds; fire extinguishers; UoN signage.
9. UoN F.O.C.
Activity DataBase 01/03/2017
7857 Nottingham Uni Medical Centre7857Project:
Room Environmental Data W0274ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: W0274 Store: medicines
Room Number: Revision Date: 01/03/2017
Permissible Space Temerature Range(dry bulb) (degC):
TEMPERATURE AND VENTILATION Requirements Notes
18 - 25
Heating Design Temperature (dry bulb)(degC): 21
Minimum Air Changes (AC/hr): 4
Ventilation Type: S/E
Bal or -vePressure Relative to Adjoining Space:
F7Supply Air: Final Filter Class
Permisiible Relative Humidity Range (%): Uncontrolled
General Notes:
LIGHTINGType Of Control: S/N
Daytime General Service Illuminance (Lux): 500
Daytime Specific Service Illuminance (Lux):
Nighttime General Service Illuminance (Lux):
Nighttime Specific Service Illuminance (Lux):
Local Task Illuminance (Lux):
Colour Rendering Required: Y
Colour Rendering Required Characteristics (Ra): 80
Unified Glare Rating Limit (UGRL): 19
Emergency Escape Route Lighting Required: In accordance with BS 5266 and Health Technical
MemorandumsY
Standby Lighting Grade - General Lighting: B
Standby Lighting Grade - Local Lighting:
General Notes:
RISKClinical Risk Category:
Non-clinical Business Continuity Risk Category:
General Notes:
Noise Intrusion (dB) 1hr day:
NOISE
Noise Intrusion (dB) 1hr night:
Noise Intrusion (dB) f night:
55
-
-
Maximum Internal Noise from M&E Services (NR): 40 Total noise of MEP services under normal operation across
the range 63Hz to 4kHz inclusive.
Room Sound-insulation Parameters - Privacy:
Room Sound-insulation Parameters - Noise Generation:
Not Private
Low
Reference to Table 3 of the Department of Health 'Acoustics:
Technical design manual 4032:0.6:England'.
Noise Sensitiviy: Not Sensitive
Sound-insulation Rating (dB D nT,w):
General Notes:
Maximum Surface Temperature (DegC):
SAFETY/FIRE
82
Domestic Hot Water Discharge Temperature (DegC): 41
Maximum Cold Water Discharge Temperature (DegC): <20
General Notes:
Type of Automatic Fire Detection: Smoke
General Notes:
Activity DataBase 01/03/2017
ADB Room Design Character W0274
Project: 7857 7857 Nottingham Uni Medical Centre
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Store: medicinesW0274Room:
01/03/2017Revision Date:Room Number:
Walls: Wall finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Wall finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Floor: Floor finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Floor finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Ceiling: Ceiling finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Ceiling finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Doorsets: Configuration, glazing, fire rating, security, etc. to be determined by Project Team.
HTM 58 (Mar-2005)
Refer to HBN 00-04 (May-2007) for effective clear door widths.
1 doorset:
1 x personnel & equipment access (1000mm)
Windows: Not required - windows not desirable
Internal Glazing: Not required
Hatch: Not required
Notes: All finishes selected must have an appropriate risk assessment to accompany the design
decision.
Infection Control must be consulted as described in Performance Requirements for Building
Elements Used in Healthcare Facilities 8941:0.6 England.
Activity DataBase 01/03/2017
Schedule of Components by Room
Project: 7857 7857 Nottingham Uni Medical Centre
W0274ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: W0274 Store: medicines
Room Number: Revision Date: 01/03/2017
Key: (n-old qty) Deletions m-new qty Additions m (n) Quantity changes since audit dateAudit Date: 2-Mar-2017
DescriptionCodeTotalTransNew
GrpAlt. CodeQuantity
Activity DataBase 01/03/2017
W0812Room Data SheetADB
Project: 7857 7857 Nottingham Uni Medical Centre
Department: PRI Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
Room: W0812 Store: records
Room Number: Revision Date: 01/03/2017
1) Secure storage.
2) Files and records are stored.
3) Rack(s) are used for storage.
4) Laptop computer(s) may be used.
5) Telephone(s) may be used.
Activities:
Personnel: 1-2 x staff.
Intermittent use.
Planning
Relationships:
Close to clinical area.
Space Data: Height (mm): 12.00 2,400Area (m²):
Notes: Separate data and voice outlets may be used where structure cabling solutions are not
available.
ADB Group Definitions:
1. Contractor supply and install.
2. Supply by others, contractor install.
3. UoN supply – loose equipment and specialist equipment (chairs, drawer units,
non-fixed medical equipment).
4. NHS IT equipment (nil cost to the project).
5. Dental supply and install.
6. Pharmacy supply and install.
7. UoN IT support and install.
8. UoN supply and install (tacks and blinds; fire extinguishers; UoN signage.
9. UoN F.O.C.
Activity DataBase 01/03/2017
7857 Nottingham Uni Medical Centre7857Project:
Room Environmental Data W0812ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: W0812 Store: records
Room Number: Revision Date: 01/03/2017
Permissible Space Temerature Range(dry bulb) (degC):
TEMPERATURE AND VENTILATION Requirements Notes
18 - 28
Heating Design Temperature (dry bulb)(degC): 21
Minimum Air Changes (AC/hr): 3
Ventilation Type: E
-vePressure Relative to Adjoining Space:
G4Supply Air: Final Filter Class
Permisiible Relative Humidity Range (%): Uncontrolled
General Notes:
LIGHTINGType Of Control: S/N
Daytime General Service Illuminance (Lux): 300
Daytime Specific Service Illuminance (Lux): 200 at workstation
Nighttime General Service Illuminance (Lux):
Nighttime Specific Service Illuminance (Lux):
Local Task Illuminance (Lux):
Colour Rendering Required: Y
Colour Rendering Required Characteristics (Ra): 80
Unified Glare Rating Limit (UGRL): 22
Emergency Escape Route Lighting Required: In accordance with BS 5266 and Health Technical
MemorandumsY
Standby Lighting Grade - General Lighting: B
Standby Lighting Grade - Local Lighting:
General Notes:
RISKClinical Risk Category:
Non-clinical Business Continuity Risk Category:
General Notes:
Noise Intrusion (dB) 1hr day:
NOISE
Noise Intrusion (dB) 1hr night:
Noise Intrusion (dB) f night:
55
-
-
Maximum Internal Noise from M&E Services (NR): 40 Total noise of MEP services under normal operation across
the range 63Hz to 4kHz inclusive.
Room Sound-insulation Parameters - Privacy:
Room Sound-insulation Parameters - Noise Generation:
Not Private
Low
Reference to Table 3 of the Department of Health 'Acoustics:
Technical design manual 4032:0.6:England'.
Noise Sensitiviy: Not Sensitive
Sound-insulation Rating (dB D nT,w):
General Notes:
Maximum Surface Temperature (DegC):
SAFETY/FIRE
82
Domestic Hot Water Discharge Temperature (DegC): 41
Maximum Cold Water Discharge Temperature (DegC): <20
General Notes:
Type of Automatic Fire Detection: Smoke
General Notes:
Activity DataBase 01/03/2017
ADB Room Design Character W0812
Project: 7857 7857 Nottingham Uni Medical Centre
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Store: recordsW0812Room:
01/03/2017Revision Date:Room Number:
Walls: Wall finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Wall finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Floor: Floor finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Floor finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Ceiling: Ceiling finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Ceiling finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Doorsets: Configuration, glazing, fire rating, security, etc. to be determined by Project Team.
HTM 58 (Mar-2005)
Refer to HBN 00-04 (May-2007) for effective clear door widths.
1 doorset:
1 x personnel & equipment access (1000mm)
Windows: Non-essential - Project Option
Obscured glass with solar control, security control as necessary, see BS2881
Designation to be validated against current documentation (HTM 55 archived).
Internal Glazing: Not required
Hatch: Not required
Notes: All finishes selected must have an appropriate risk assessment to accompany the design
decision.
Infection Control must be consulted as described in Performance Requirements for Building
Elements Used in Healthcare Facilities 8941:0.6 England.
Activity DataBase 01/03/2017
Schedule of Components by Room
Project: 7857 7857 Nottingham Uni Medical Centre
W0812ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: W0812 Store: records
Room Number: Revision Date: 01/03/2017
Key: (n-old qty) Deletions m-new qty Additions m (n) Quantity changes since audit dateAudit Date: 2-Mar-2017
DescriptionCodeTotalTransNew
GrpAlt. CodeQuantity
1SOCKET outlet, switched, 13 amp, singleOUT00511
1SOCKET outlet, switched, 13 amp, twinOUT01011
1SOCKET outlet data/voice, double.OUT13111
1SWITCH, lightSWC02511
2RACK, vertical, open front, wall mounted, 1800H
1200W 300D
RAC19122
2RACK, metal, 1 bay, 4 shelves, 1980H 900W 650DRAC4061515
2RACK, metal, 1 bay, 4 shelves, 1980H 1200W 600DRAC41077
3CHAIR, swivel, height adjustable, high back, with
arms, wipeable, 5 star base, on castors
CHA30111
3TABLE, 710H 900W 600DTAB00511
8TRACK, blinds for windowsTRA90022
Activity DataBase 01/03/2017
W1585Room Data SheetADB
Project: 7857 7857 Nottingham Uni Medical Centre
Department: PRI Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
Room: W1585 Store: general
Room Number: Revision Date: 01/03/2017
1) Miscellaneous equipment is stored.
2) Non-clinical supplies are stored.
Activities:
Personnel: 1 x staff.
Intermittent use.
Planning
Relationships:
Space Data: Height (mm): 12.00 2,400Area (m²):
Notes: ADB Group Definitions:
1. Contractor supply and install.
2. Supply by others, contractor install.
3. UoN supply – loose equipment and specialist equipment (chairs, drawer units,
non-fixed medical equipment).
4. NHS IT equipment (nil cost to the project).
5. Dental supply and install.
6. Pharmacy supply and install.
7. UoN IT support and install.
8. UoN supply and install (tacks and blinds; fire extinguishers; UoN signage.
9. UoN F.O.C.
Activity DataBase 01/03/2017
7857 Nottingham Uni Medical Centre7857Project:
Room Environmental Data W1585ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: W1585 Store: general
Room Number: Revision Date: 01/03/2017
Permissible Space Temerature Range(dry bulb) (degC):
TEMPERATURE AND VENTILATION Requirements Notes
18 - 28
Heating Design Temperature (dry bulb)(degC): 21
Minimum Air Changes (AC/hr): 3
Ventilation Type: E
-vePressure Relative to Adjoining Space:
Supply Air: Final Filter Class
Permisiible Relative Humidity Range (%): Uncontrolled
General Notes:
LIGHTINGType Of Control: S/N
Daytime General Service Illuminance (Lux): 200/300 Subject to perception of detail required
Daytime Specific Service Illuminance (Lux):
Nighttime General Service Illuminance (Lux):
Nighttime Specific Service Illuminance (Lux):
Local Task Illuminance (Lux):
Colour Rendering Required: Y
Colour Rendering Required Characteristics (Ra): 80
Unified Glare Rating Limit (UGRL): 22
Emergency Escape Route Lighting Required: In accordance with BS 5266 and Health Technical
MemorandumsY
Standby Lighting Grade - General Lighting: B
Standby Lighting Grade - Local Lighting:
General Notes:
RISKClinical Risk Category:
Non-clinical Business Continuity Risk Category:
General Notes:
Noise Intrusion (dB) 1hr day:
NOISE
Noise Intrusion (dB) 1hr night:
Noise Intrusion (dB) f night:
55
-
-
Maximum Internal Noise from M&E Services (NR): 45 Total noise of MEP services under normal operation across
the range 63Hz to 4kHz inclusive.
Room Sound-insulation Parameters - Privacy:
Room Sound-insulation Parameters - Noise Generation:
Not Private
Low
Reference to Table 3 of the Department of Health 'Acoustics:
Technical design manual 4032:0.6:England'.
Noise Sensitiviy: Not Sensitive
Sound-insulation Rating (dB D nT,w):
General Notes:
Maximum Surface Temperature (DegC):
SAFETY/FIRE
82
Domestic Hot Water Discharge Temperature (DegC): 41
Maximum Cold Water Discharge Temperature (DegC): <20
General Notes:
Type of Automatic Fire Detection: Smoke
General Notes:
Activity DataBase 01/03/2017
ADB Room Design Character W1585
Project: 7857 7857 Nottingham Uni Medical Centre
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Store: generalW1585Room:
01/03/2017Revision Date:Room Number:
Walls: Wall finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Wall finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Floor: Floor finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Floor finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Ceiling: Ceiling finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Ceiling finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Doorsets: Configuration, glazing, fire rating, security, etc. to be determined by Project Team.
HTM 58 (Mar-2005)
Refer to HBN 00-04 (May-2007) for effective clear door widths.
1 doorset:
1 x personnel & equipment access (1000mm)
Windows: Not required
Internal Glazing: Not required
Hatch: Not required
Notes: All finishes selected must have an appropriate risk assessment to accompany the design
decision.
Infection Control must be consulted as described in Performance Requirements for Building
Elements Used in Healthcare Facilities 8941:0.6 England.
Activity DataBase 01/03/2017
Schedule of Components by Room
Project: 7857 7857 Nottingham Uni Medical Centre
W1585ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: W1585 Store: general
Room Number: Revision Date: 01/03/2017
Key: (n-old qty) Deletions m-new qty Additions m (n) Quantity changes since audit dateAudit Date: 2-Mar-2017
DescriptionCodeTotalTransNew
GrpAlt. CodeQuantity
1SOCKET outlet, switched, 13 amp, singleOUT00511
1SHELVING FRAME, modular storage, 1 bay, with 5
shelves, 2130H 1000W 465D
SMF01188
1SWITCH, lightSWC02511
Activity DataBase 01/03/2017
W1585-001Room Data SheetADB
Project: 7857 7857 Nottingham Uni Medical Centre
Department: PRI Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
Room: W1585-001 Store: general
Room Number: Revision Date: 01/03/2017
1) Miscellaneous equipment is stored.
2) Non-clinical supplies are stored.
Activities:
Personnel: 1 x staff.
Intermittent use.
Planning
Relationships:
Space Data: Height (mm): 16.00 2,400Area (m²):
Notes: ADB Group Definitions:
1. Contractor supply and install.
2. Supply by others, contractor install.
3. UoN supply – loose equipment and specialist equipment (chairs, drawer units,
non-fixed medical equipment).
4. NHS IT equipment (nil cost to the project).
5. Dental supply and install.
6. Pharmacy supply and install.
7. UoN IT support and install.
8. UoN supply and install (tacks and blinds; fire extinguishers; UoN signage.
9. UoN F.O.C.
Activity DataBase 01/03/2017
7857 Nottingham Uni Medical Centre7857Project:
Room Environmental Data W1585-001ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: W1585-001 Store: general
Room Number: Revision Date: 01/03/2017
Permissible Space Temerature Range(dry bulb) (degC):
TEMPERATURE AND VENTILATION Requirements Notes
18 - 28
Heating Design Temperature (dry bulb)(degC): 21
Minimum Air Changes (AC/hr): 3
Ventilation Type: E
-vePressure Relative to Adjoining Space:
Supply Air: Final Filter Class
Permisiible Relative Humidity Range (%): Uncontrolled
General Notes:
LIGHTINGType Of Control: S/N
Daytime General Service Illuminance (Lux): 200/300 Subject to perception of detail required
Daytime Specific Service Illuminance (Lux):
Nighttime General Service Illuminance (Lux):
Nighttime Specific Service Illuminance (Lux):
Local Task Illuminance (Lux):
Colour Rendering Required: Y
Colour Rendering Required Characteristics (Ra): 80
Unified Glare Rating Limit (UGRL): 22
Emergency Escape Route Lighting Required: In accordance with BS 5266 and Health Technical
MemorandumsY
Standby Lighting Grade - General Lighting: B
Standby Lighting Grade - Local Lighting:
General Notes:
RISKClinical Risk Category:
Non-clinical Business Continuity Risk Category:
General Notes:
Noise Intrusion (dB) 1hr day:
NOISE
Noise Intrusion (dB) 1hr night:
Noise Intrusion (dB) f night:
55
-
-
Maximum Internal Noise from M&E Services (NR): 45 Total noise of MEP services under normal operation across
the range 63Hz to 4kHz inclusive.
Room Sound-insulation Parameters - Privacy:
Room Sound-insulation Parameters - Noise Generation:
Not Private
Low
Reference to Table 3 of the Department of Health 'Acoustics:
Technical design manual 4032:0.6:England'.
Noise Sensitiviy: Not Sensitive
Sound-insulation Rating (dB D nT,w):
General Notes:
Maximum Surface Temperature (DegC):
SAFETY/FIRE
82
Domestic Hot Water Discharge Temperature (DegC): 41
Maximum Cold Water Discharge Temperature (DegC): <20
General Notes:
Type of Automatic Fire Detection: Smoke
General Notes:
Activity DataBase 01/03/2017
ADB Room Design Character W1585-001
Project: 7857 7857 Nottingham Uni Medical Centre
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Store: generalW1585-001Room:
01/03/2017Revision Date:Room Number:
Walls: Wall finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Wall finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Floor: Floor finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Floor finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Ceiling: Ceiling finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Ceiling finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Doorsets: Configuration, glazing, fire rating, security, etc. to be determined by Project Team.
HTM 58 (Mar-2005)
Refer to HBN 00-04 (May-2007) for effective clear door widths.
1 doorset:
1 x personnel & equipment access (1000mm)
Windows: Not required
Internal Glazing: Not required
Hatch: Not required
Notes: All finishes selected must have an appropriate risk assessment to accompany the design
decision.
Infection Control must be consulted as described in Performance Requirements for Building
Elements Used in Healthcare Facilities 8941:0.6 England.
Activity DataBase 01/03/2017
Schedule of Components by Room
Project: 7857 7857 Nottingham Uni Medical Centre
W1585-001ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: W1585-001 Store: general
Room Number: Revision Date: 01/03/2017
Key: (n-old qty) Deletions m-new qty Additions m (n) Quantity changes since audit dateAudit Date: 2-Mar-2017
DescriptionCodeTotalTransNew
GrpAlt. CodeQuantity
1SOCKET outlet, switched, 13 amp, singleOUT00511
1SHELVING FRAME, modular storage, 1 bay, with 5
shelves, 2130H 1000W 665D
SMF0131010
1SWITCH, lightSWC02511
Activity DataBase 01/03/2017
W1585-002Room Data SheetADB
Project: 7857 7857 Nottingham Uni Medical Centre
Department: PRI Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
Room: W1585-002 Store: general
Room Number: Revision Date: 01/03/2017
1) Miscellaneous equipment is stored.
2) Non-clinical supplies are stored.
Activities:
Personnel: 1 x staff.
Intermittent use.
Planning
Relationships:
Space Data: Height (mm): 16.00 2,400Area (m²):
Notes: ADB Group Definitions:
1. Contractor supply and install.
2. Supply by others, contractor install.
3. UoN supply – loose equipment and specialist equipment (chairs, drawer units,
non-fixed medical equipment).
4. NHS IT equipment (nil cost to the project).
5. Dental supply and install.
6. Pharmacy supply and install.
7. UoN IT support and install.
8. UoN supply and install (tacks and blinds; fire extinguishers; UoN signage.
9. UoN F.O.C.
Activity DataBase 01/03/2017
7857 Nottingham Uni Medical Centre7857Project:
Room Environmental Data W1585-002ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: W1585-002 Store: general
Room Number: Revision Date: 01/03/2017
Permissible Space Temerature Range(dry bulb) (degC):
TEMPERATURE AND VENTILATION Requirements Notes
18 - 28
Heating Design Temperature (dry bulb)(degC): 21
Minimum Air Changes (AC/hr): 3
Ventilation Type: E
-vePressure Relative to Adjoining Space:
Supply Air: Final Filter Class
Permisiible Relative Humidity Range (%): Uncontrolled
General Notes:
LIGHTINGType Of Control: S/N
Daytime General Service Illuminance (Lux): 200/300 Subject to perception of detail required
Daytime Specific Service Illuminance (Lux):
Nighttime General Service Illuminance (Lux):
Nighttime Specific Service Illuminance (Lux):
Local Task Illuminance (Lux):
Colour Rendering Required: Y
Colour Rendering Required Characteristics (Ra): 80
Unified Glare Rating Limit (UGRL): 22
Emergency Escape Route Lighting Required: In accordance with BS 5266 and Health Technical
MemorandumsY
Standby Lighting Grade - General Lighting: B
Standby Lighting Grade - Local Lighting:
General Notes:
RISKClinical Risk Category:
Non-clinical Business Continuity Risk Category:
General Notes:
Noise Intrusion (dB) 1hr day:
NOISE
Noise Intrusion (dB) 1hr night:
Noise Intrusion (dB) f night:
55
-
-
Maximum Internal Noise from M&E Services (NR): 45 Total noise of MEP services under normal operation across
the range 63Hz to 4kHz inclusive.
Room Sound-insulation Parameters - Privacy:
Room Sound-insulation Parameters - Noise Generation:
Not Private
Low
Reference to Table 3 of the Department of Health 'Acoustics:
Technical design manual 4032:0.6:England'.
Noise Sensitiviy: Not Sensitive
Sound-insulation Rating (dB D nT,w):
General Notes:
Maximum Surface Temperature (DegC):
SAFETY/FIRE
82
Domestic Hot Water Discharge Temperature (DegC): 41
Maximum Cold Water Discharge Temperature (DegC): <20
General Notes:
Type of Automatic Fire Detection: Smoke
General Notes:
Activity DataBase 01/03/2017
ADB Room Design Character W1585-002
Project: 7857 7857 Nottingham Uni Medical Centre
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Store: generalW1585-002Room:
01/03/2017Revision Date:Room Number:
Walls: Wall finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Wall finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Floor: Floor finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Floor finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Ceiling: Ceiling finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Ceiling finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Doorsets: Configuration, glazing, fire rating, security, etc. to be determined by Project Team.
HTM 58 (Mar-2005)
Refer to HBN 00-04 (May-2007) for effective clear door widths.
1 doorset:
1 x personnel & equipment access (1000mm)
Windows: Not required
Internal Glazing: Not required
Hatch: Not required
Notes: All finishes selected must have an appropriate risk assessment to accompany the design
decision.
Infection Control must be consulted as described in Performance Requirements for Building
Elements Used in Healthcare Facilities 8941:0.6 England.
Activity DataBase 01/03/2017
Schedule of Components by Room
Project: 7857 7857 Nottingham Uni Medical Centre
W1585-002ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: W1585-002 Store: general
Room Number: Revision Date: 01/03/2017
Key: (n-old qty) Deletions m-new qty Additions m (n) Quantity changes since audit dateAudit Date: 2-Mar-2017
DescriptionCodeTotalTransNew
GrpAlt. CodeQuantity
1SOCKET outlet, switched, 13 amp, singleOUT00511
1SOCKET outlet, switched, 13 amp, twinOUT01022
1SOCKET outlet data/voice, double.OUT13122
1SHELVING FRAME, modular storage, 1 bay, with 5
shelves, 2130H 1000W 665D
SMF0131313
1SWITCH, lightSWC02511
3CHAIR, swivel, height adjustable, high back, with
arms, wipeable, 5 star base, on castors
CHA30111
3DESK RETURN UNIT, cantilever, cable
management, adjustable legs, modesty panel,
freestanding, 1200W 600D
DES02811
4COMPUTER KEYBOARDCOM93311
4COMPUTER MONITOR, 17"; TFT, digital flat panel
display, high-resolution screens, desk top
COM94911
Activity DataBase 01/03/2017
W1585-003Room Data SheetADB
Project: 7857 7857 Nottingham Uni Medical Centre
Department: PRI Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
Room: W1585-003 Store: general
Room Number: Revision Date: 01/03/2017
1) Miscellaneous equipment is stored.
2) Non-clinical supplies are stored.
Activities:
Personnel: 1 x staff.
Intermittent use.
Planning
Relationships:
Space Data: Height (mm): 16.00 2,400Area (m²):
Notes: ADB Group Definitions:
1. Contractor supply and install.
2. Supply by others, contractor install.
3. UoN supply – loose equipment and specialist equipment (chairs, drawer units,
non-fixed medical equipment).
4. NHS IT equipment (nil cost to the project).
5. Dental supply and install.
6. Pharmacy supply and install.
7. UoN IT support and install.
8. UoN supply and install (tacks and blinds; fire extinguishers; UoN signage.
9. UoN F.O.C.
Activity DataBase 01/03/2017
7857 Nottingham Uni Medical Centre7857Project:
Room Environmental Data W1585-003ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: W1585-003 Store: general
Room Number: Revision Date: 01/03/2017
Permissible Space Temerature Range(dry bulb) (degC):
TEMPERATURE AND VENTILATION Requirements Notes
18 - 28
Heating Design Temperature (dry bulb)(degC): 21
Minimum Air Changes (AC/hr): 3
Ventilation Type: E
-vePressure Relative to Adjoining Space:
Supply Air: Final Filter Class
Permisiible Relative Humidity Range (%): Uncontrolled
General Notes:
LIGHTINGType Of Control: S/N
Daytime General Service Illuminance (Lux): 200/300 Subject to perception of detail required
Daytime Specific Service Illuminance (Lux):
Nighttime General Service Illuminance (Lux):
Nighttime Specific Service Illuminance (Lux):
Local Task Illuminance (Lux):
Colour Rendering Required: Y
Colour Rendering Required Characteristics (Ra): 80
Unified Glare Rating Limit (UGRL): 22
Emergency Escape Route Lighting Required: In accordance with BS 5266 and Health Technical
MemorandumsY
Standby Lighting Grade - General Lighting: B
Standby Lighting Grade - Local Lighting:
General Notes:
RISKClinical Risk Category:
Non-clinical Business Continuity Risk Category:
General Notes:
Noise Intrusion (dB) 1hr day:
NOISE
Noise Intrusion (dB) 1hr night:
Noise Intrusion (dB) f night:
55
-
-
Maximum Internal Noise from M&E Services (NR): 45 Total noise of MEP services under normal operation across
the range 63Hz to 4kHz inclusive.
Room Sound-insulation Parameters - Privacy:
Room Sound-insulation Parameters - Noise Generation:
Not Private
Low
Reference to Table 3 of the Department of Health 'Acoustics:
Technical design manual 4032:0.6:England'.
Noise Sensitiviy: Not Sensitive
Sound-insulation Rating (dB D nT,w):
General Notes:
Maximum Surface Temperature (DegC):
SAFETY/FIRE
82
Domestic Hot Water Discharge Temperature (DegC): 41
Maximum Cold Water Discharge Temperature (DegC): <20
General Notes:
Type of Automatic Fire Detection: Smoke
General Notes:
Activity DataBase 01/03/2017
ADB Room Design Character W1585-003
Project: 7857 7857 Nottingham Uni Medical Centre
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Store: generalW1585-003Room:
01/03/2017Revision Date:Room Number:
Walls: Wall finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Wall finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Floor: Floor finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Floor finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Ceiling: Ceiling finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Ceiling finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Doorsets: Configuration, glazing, fire rating, security, etc. to be determined by Project Team.
HTM 58 (Mar-2005)
Refer to HBN 00-04 (May-2007) for effective clear door widths.
1 doorset:
1 x personnel & equipment access (1000mm)
Windows: Not required
Internal Glazing: Not required
Hatch: Not required
Notes: All finishes selected must have an appropriate risk assessment to accompany the design
decision.
Infection Control must be consulted as described in Performance Requirements for Building
Elements Used in Healthcare Facilities 8941:0.6 England.
Activity DataBase 01/03/2017
Schedule of Components by Room
Project: 7857 7857 Nottingham Uni Medical Centre
W1585-003ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: W1585-003 Store: general
Room Number: Revision Date: 01/03/2017
Key: (n-old qty) Deletions m-new qty Additions m (n) Quantity changes since audit dateAudit Date: 2-Mar-2017
DescriptionCodeTotalTransNew
GrpAlt. CodeQuantity
1SOCKET outlet, switched, 13 amp, singleOUT00511
1SOCKET outlet, switched, 13 amp, twinOUT01011
1SHELVING FRAME, modular storage, 1 bay, with 5
shelves, 2130H 1000W 665D
SMF01366
1SWITCH, lightSWC02511
7PRINTER multifunction, network, floor standing, zone
1800W 750D
PRI11011
Activity DataBase 01/03/2017
W1585-004Room Data SheetADB
Project: 7857 7857 Nottingham Uni Medical Centre
Department: PRI Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
Room: W1585-004 Store: general
Room Number: Revision Date: 01/03/2017
1) Miscellaneous equipment is stored.
2) Non-clinical supplies are stored.
Activities:
Personnel: 1 x staff.
Intermittent use.
Planning
Relationships:
Space Data: Height (mm): 16.00 2,400Area (m²):
Notes: ADB Group Definitions:
1. Contractor supply and install.
2. Supply by others, contractor install.
3. UoN supply – loose equipment and specialist equipment (chairs, drawer units,
non-fixed medical equipment).
4. NHS IT equipment (nil cost to the project).
5. Dental supply and install.
6. Pharmacy supply and install.
7. UoN IT support and install.
8. UoN supply and install (tacks and blinds; fire extinguishers; UoN signage.
9. UoN F.O.C.
Activity DataBase 01/03/2017
7857 Nottingham Uni Medical Centre7857Project:
Room Environmental Data W1585-004ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: W1585-004 Store: general
Room Number: Revision Date: 01/03/2017
Permissible Space Temerature Range(dry bulb) (degC):
TEMPERATURE AND VENTILATION Requirements Notes
18 - 28
Heating Design Temperature (dry bulb)(degC): 21
Minimum Air Changes (AC/hr): 3
Ventilation Type: E
-vePressure Relative to Adjoining Space:
Supply Air: Final Filter Class
Permisiible Relative Humidity Range (%): Uncontrolled
General Notes:
LIGHTINGType Of Control: S/N
Daytime General Service Illuminance (Lux): 200/300 Subject to perception of detail required
Daytime Specific Service Illuminance (Lux):
Nighttime General Service Illuminance (Lux):
Nighttime Specific Service Illuminance (Lux):
Local Task Illuminance (Lux):
Colour Rendering Required: Y
Colour Rendering Required Characteristics (Ra): 80
Unified Glare Rating Limit (UGRL): 22
Emergency Escape Route Lighting Required: In accordance with BS 5266 and Health Technical
MemorandumsY
Standby Lighting Grade - General Lighting: B
Standby Lighting Grade - Local Lighting:
General Notes:
RISKClinical Risk Category:
Non-clinical Business Continuity Risk Category:
General Notes:
Noise Intrusion (dB) 1hr day:
NOISE
Noise Intrusion (dB) 1hr night:
Noise Intrusion (dB) f night:
55
-
-
Maximum Internal Noise from M&E Services (NR): 45 Total noise of MEP services under normal operation across
the range 63Hz to 4kHz inclusive.
Room Sound-insulation Parameters - Privacy:
Room Sound-insulation Parameters - Noise Generation:
Not Private
Low
Reference to Table 3 of the Department of Health 'Acoustics:
Technical design manual 4032:0.6:England'.
Noise Sensitiviy: Not Sensitive
Sound-insulation Rating (dB D nT,w):
General Notes:
Maximum Surface Temperature (DegC):
SAFETY/FIRE
82
Domestic Hot Water Discharge Temperature (DegC): 41
Maximum Cold Water Discharge Temperature (DegC): <20
General Notes:
Type of Automatic Fire Detection: Smoke
General Notes:
Activity DataBase 01/03/2017
ADB Room Design Character W1585-004
Project: 7857 7857 Nottingham Uni Medical Centre
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Store: generalW1585-004Room:
01/03/2017Revision Date:Room Number:
Walls: Wall finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Wall finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Floor: Floor finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Floor finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Ceiling: Ceiling finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Ceiling finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Doorsets: Configuration, glazing, fire rating, security, etc. to be determined by Project Team.
HTM 58 (Mar-2005)
Refer to HBN 00-04 (May-2007) for effective clear door widths.
1 doorset:
1 x personnel & equipment access (1000mm)
Windows: Not required
Internal Glazing: Not required
Hatch: Not required
Notes: All finishes selected must have an appropriate risk assessment to accompany the design
decision.
Infection Control must be consulted as described in Performance Requirements for Building
Elements Used in Healthcare Facilities 8941:0.6 England.
Activity DataBase 01/03/2017
Schedule of Components by Room
Project: 7857 7857 Nottingham Uni Medical Centre
W1585-004ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: W1585-004 Store: general
Room Number: Revision Date: 01/03/2017
Key: (n-old qty) Deletions m-new qty Additions m (n) Quantity changes since audit dateAudit Date: 2-Mar-2017
DescriptionCodeTotalTransNew
GrpAlt. CodeQuantity
1SOCKET outlet, switched, 13 amp, singleOUT00511
1SWITCH, lightSWC02511
5SHELF, 1500W 300DSHE33188
5SHELVING FRAME, modular storage, 1 bay, with 5
shelves, 2130H 1000W 465D
SMF11199
5TRACK, blinds for windowsTRA90211
Activity DataBase 01/03/2017
W1585-005Room Data SheetADB
Project: 7857 7857 Nottingham Uni Medical Centre
Department: PRI Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
Room: W1585-005 Store: general
Room Number: Revision Date: 01/03/2017
1) Miscellaneous equipment is stored.
2) Non-clinical supplies are stored.
Activities:
Personnel: 1 x staff.
Intermittent use.
Planning
Relationships:
Space Data: Height (mm): 16.00 2,400Area (m²):
Notes: ADB Group Definitions:
1. Contractor supply and install.
2. Supply by others, contractor install.
3. UoN supply – loose equipment and specialist equipment (chairs, drawer units,
non-fixed medical equipment).
4. NHS IT equipment (nil cost to the project).
5. Dental supply and install.
6. Pharmacy supply and install.
7. UoN IT support and install.
8. UoN supply and install (tacks and blinds; fire extinguishers; UoN signage.
9. UoN F.O.C.
Activity DataBase 01/03/2017
7857 Nottingham Uni Medical Centre7857Project:
Room Environmental Data W1585-005ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: W1585-005 Store: general
Room Number: Revision Date: 01/03/2017
Permissible Space Temerature Range(dry bulb) (degC):
TEMPERATURE AND VENTILATION Requirements Notes
18 - 28
Heating Design Temperature (dry bulb)(degC): 21
Minimum Air Changes (AC/hr): 3
Ventilation Type: E
-vePressure Relative to Adjoining Space:
Supply Air: Final Filter Class
Permisiible Relative Humidity Range (%): Uncontrolled
General Notes:
LIGHTINGType Of Control: S/N
Daytime General Service Illuminance (Lux): 200/300 Subject to perception of detail required
Daytime Specific Service Illuminance (Lux):
Nighttime General Service Illuminance (Lux):
Nighttime Specific Service Illuminance (Lux):
Local Task Illuminance (Lux):
Colour Rendering Required: Y
Colour Rendering Required Characteristics (Ra): 80
Unified Glare Rating Limit (UGRL): 22
Emergency Escape Route Lighting Required: In accordance with BS 5266 and Health Technical
MemorandumsY
Standby Lighting Grade - General Lighting: B
Standby Lighting Grade - Local Lighting:
General Notes:
RISKClinical Risk Category:
Non-clinical Business Continuity Risk Category:
General Notes:
Noise Intrusion (dB) 1hr day:
NOISE
Noise Intrusion (dB) 1hr night:
Noise Intrusion (dB) f night:
55
-
-
Maximum Internal Noise from M&E Services (NR): 45 Total noise of MEP services under normal operation across
the range 63Hz to 4kHz inclusive.
Room Sound-insulation Parameters - Privacy:
Room Sound-insulation Parameters - Noise Generation:
Not Private
Low
Reference to Table 3 of the Department of Health 'Acoustics:
Technical design manual 4032:0.6:England'.
Noise Sensitiviy: Not Sensitive
Sound-insulation Rating (dB D nT,w):
General Notes:
Maximum Surface Temperature (DegC):
SAFETY/FIRE
82
Domestic Hot Water Discharge Temperature (DegC): 41
Maximum Cold Water Discharge Temperature (DegC): <20
General Notes:
Type of Automatic Fire Detection: Smoke
General Notes:
Activity DataBase 01/03/2017
ADB Room Design Character W1585-005
Project: 7857 7857 Nottingham Uni Medical Centre
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Store: generalW1585-005Room:
01/03/2017Revision Date:Room Number:
Walls: Wall finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Wall finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Floor: Floor finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Floor finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Ceiling: Ceiling finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Ceiling finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Doorsets: Configuration, glazing, fire rating, security, etc. to be determined by Project Team.
HTM 58 (Mar-2005)
Refer to HBN 00-04 (May-2007) for effective clear door widths.
1 doorset:
1 x personnel & equipment access (1000mm)
Windows: Not required
Internal Glazing: Not required
Hatch: Not required
Notes: All finishes selected must have an appropriate risk assessment to accompany the design
decision.
Infection Control must be consulted as described in Performance Requirements for Building
Elements Used in Healthcare Facilities 8941:0.6 England.
Activity DataBase 01/03/2017
Schedule of Components by Room
Project: 7857 7857 Nottingham Uni Medical Centre
W1585-005ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: W1585-005 Store: general
Room Number: Revision Date: 01/03/2017
Key: (n-old qty) Deletions m-new qty Additions m (n) Quantity changes since audit dateAudit Date: 2-Mar-2017
DescriptionCodeTotalTransNew
GrpAlt. CodeQuantity
1SOCKET outlet, switched, 13 amp, singleOUT00511
1SHELF, 900W 300DSHE2111010
1SHELF, 1500W 300DSHE23188
1SHELVING FRAME, modular storage, 1 bay, with 5
shelves, 2130H 1000W 465D
SMF01177
1SWITCH, lightSWC02511
Activity DataBase 01/03/2017
X0145Room Data SheetADB
Project: 7857 7857 Nottingham Uni Medical Centre
Department: PRI Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
Room: X0145 Treatment room: double-sided couch access
Room Number: Revision Date: 01/03/2017
1) Carrying out invasive clinical procedures from both sides of the couch.
2) User may undress and dress in privacy.
3) Trays/packs for clinical procedures are prepared.
4) Clinical wash-hand basin may be used.
5) Electronic patient records (EPRs) may be accessed and updated.
6) Sterile supplies and consumables are held/stored on a trolley.
7) Monitoring/diagnostic or therapeutic equipment may be used.
8) Use of mobile diagnostic and therapeutic equipment.
9) Patient may arrive on foot in a wheelchair or on a trolley
10) Preparation for clinical procedures is undertaken.
11) Dressing/instrument trolleys are held and prepared.
12) Sterile packs, lotions and drugs may be prepared for immediate use.
13) Piped medical gases, vacuum and associated equipment may be used.
14) Call systems may be used.
Activities:
Personnel: 1 x patient.
2 x staff.
Planning
Relationships:
Close to a clean utility room.
Close to a dirty utility room.
Space Data: Height (mm): 16.00 2,700Area (m²):
Activity DataBase 01/03/2017
Notes: This room includes a 3-section couch and is based on option 1 layout in HBN 00-03.
Alternatively, it may accommodate a 2-section couch or specialist treatment chair.
The room includes general engineering services for delivering treatments. For further
details see HTM 02-01 and HTM 08-03.
The call repeat lamp is situated over the door outside the room.
The following items are shown on the room layout but are optional:
- room in use switch and indicator.
- the location of the privacy curtain (may be at the door entrance instead of between the
couch and clinical workstation).
Where laser treatments are carried out, an illuminated "laser in use" sign must be
situated outside the room linked to a door locking mechanism.
Where the room includes a window, blackout blinds are recommended for flexibility in
use.
.
Separate data and voice outlets may be used where structure cabling solutions are not
available.
ADB Group Definitions:
1. Contractor supply and install.
2. Supply by others, contractor install.
3. UoN supply – loose equipment and specialist equipment (chairs, drawer units,
non-fixed medical equipment).
4. NHS IT equipment (nil cost to the project).
5. Dental supply and install.
6. Pharmacy supply and install.
7. UoN IT support and install.
8. UoN supply and install (tacks and blinds; fire extinguishers; UoN signage.
9. UoN F.O.C.
Activity DataBase 01/03/2017
7857 Nottingham Uni Medical Centre7857Project:
Room Environmental Data X0145ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: X0145 Treatment room: double-sided couch access
Room Number: Revision Date: 01/03/2017
Permissible Space Temerature Range(dry bulb) (degC):
TEMPERATURE AND VENTILATION Requirements Notes
18 - 25
Heating Design Temperature (dry bulb)(degC): 22
Minimum Air Changes (AC/hr): 10
Ventilation Type: S/E
+vePressure Relative to Adjoining Space:
F7Supply Air: Final Filter Class
Permisiible Relative Humidity Range (%): Uncontrolled
General Notes:
LIGHTINGType Of Control: S/V
Daytime General Service Illuminance (Lux): 500
Daytime Specific Service Illuminance (Lux):
Nighttime General Service Illuminance (Lux):
Nighttime Specific Service Illuminance (Lux):
Local Task Illuminance (Lux): 1000
Colour Rendering Required: Y
Colour Rendering Required Characteristics (Ra): 80/90 Ra 90 required for examination/treatment
Unified Glare Rating Limit (UGRL): 19
Emergency Escape Route Lighting Required: In accordance with BS 5266 and Health Technical
MemorandumsY
Standby Lighting Grade - General Lighting:
Standby Lighting Grade - Local Lighting:
General Notes:
RISKClinical Risk Category:
Non-clinical Business Continuity Risk Category:
General Notes:
Noise Intrusion (dB) 1hr day:
NOISE
Noise Intrusion (dB) 1hr night:
Noise Intrusion (dB) f night:
40
-
-
Maximum Internal Noise from M&E Services (NR): 35 Total noise of MEP services under normal operation across
the range 63Hz to 4kHz inclusive.
Room Sound-insulation Parameters - Privacy:
Room Sound-insulation Parameters - Noise Generation:
Confidential
Typical
Reference to Table 3 of the Department of Health 'Acoustics:
Technical design manual 4032:0.6:England'.
Noise Sensitiviy: Medium
Sound-insulation Rating (dB D nT,w):
General Notes:
Maximum Surface Temperature (DegC):
SAFETY/FIRE
43
Domestic Hot Water Discharge Temperature (DegC): 41
Maximum Cold Water Discharge Temperature (DegC): <20
General Notes:
Type of Automatic Fire Detection: Smoke
General Notes:
Activity DataBase 01/03/2017
ADB Room Design Character X0145
Project: 7857 7857 Nottingham Uni Medical Centre
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Treatment room: double-sided couch accessX0145Room:
01/03/2017Revision Date:Room Number:
Walls: Wall finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Wall finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Floor: Floor finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Floor finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Ceiling: Ceiling finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Ceiling finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Doorsets: Configuration, glazing, fire rating, security, etc. to be determined by Project Team.
HTM 58 (Mar-2005)
Refer to HBN 00-04 (May-2007) for effective clear door widths.
1 doorset:
1 x personnel, trolley, wheelchair & equipment access (1500mm)
Requirement for hinge protection when areas used by children
Windows: Desirable - Project Option
Clear glass, openable, privacy control
Designation to be validated against current documentation (HTM 55 archived).
Internal Glazing: Not required
Hatch: Not required
Notes: All finishes selected must have an appropriate risk assessment to accompany the design
decision.
Infection Control must be consulted as described in Performance Requirements for Building
Elements Used in Healthcare Facilities 8941:0.6 England.
Activity DataBase 01/03/2017
Schedule of Components by Room
Project: 7857 7857 Nottingham Uni Medical Centre
X0145ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: X0145 Treatment room: double-sided couch access
Room Number: Revision Date: 01/03/2017
Key: (n-old qty) Deletions m-new qty Additions m (n) Quantity changes since audit dateAudit Date: 2-Mar-2017
DescriptionCodeTotalTransNew
GrpAlt. CodeQuantity
1BASIN, medium, hospital pattern, vitreous china, no
tap holes, no overflow, integral back outlet, 500W
400D.
BAS10111
1LAMP, repeat call, patient/staff or staff emergency or
cardiac call
CAL03411
1HOOK, single, small, wall mountedHOO01922
1LUMINAIRE, examination, ceiling, adjustable, 1000
lux
LIG05311
1ILLUMINATED SIGN, 'Room in use'LIG07311
1SOCKET outlet, switched, 13 amp, singleOUT00511
1SOCKET outlet, switched, 13 amp, twinOUT01033
1CONNECTION UNIT, switched, 13 amp, flex outletOUT04911
1SOCKET outlet data/voice, double.OUT13122
1CABINET, base, modular storage, for 400 facing
inserts, with door, on plinth, 900H
SMC01311
1CABINET, upper, modular storage, for 400 facing
inserts, with door, 750H
SMC02333
1WORKTOP, clinical, for 3 x 400 facing modular
storage cabinets, 1365W 700D
SMW05311
1WORKTOP, clinical, for 400 facing modular storage
cabinets, 900W 700D
SMW06911
1SWITCH, lightSWC02511
1SWITCH, dimmer, modulatingSWC03411
1SWITCH, 'Room in use' illuminated sign.SWC07611
1TAP, bib, 2x8 mm thermostatic mixer, automatic
action, sensor operated, non-touch,
TAP89211
1TRACK, curtain, one sided, 3800LTRA17211
1TRAP, bottle, 1.1/4 in, plastic resealing.WAS10711
2BRACKET, holder, suction unit.BRA00311
2DISPENSER, barrier cream, disposable single
cartridge, wall mounted
DIS01111
2DISPENSER, paper towel, wall mountedDIS01311
2DISPENSER, Medical hand sanitizer, lever action,
wall mounted
DIS02611
2DISPENSER, soap, disposable single cartridge, lever
action, wall mounted
DIS03011
2DISPENSER, disposable gloves set of 3 and
disposable apron, wall mounted
DIS43811
3CHAIR, swivel, height adjustable, medium back,
wipeable, 5 star base, on glides
CHA30411
3CHAIR, upright, upholstered, stacking, wipeableCHA31711
3COUCH, examination/treatment, (3 section), variable
height, retractable wheels, with paper roll holder
COU01011
3HOLDER, sack, with lid foot operated, medium,
freestanding, 875H 430W 385D
HOL00622
3HOLDER, sharps box, up to 7 litre capacity,
rail/trolley hang or wall mounted, 170H 125W 100D
HOL02011
Activity DataBase 01/03/2017
Schedule of Components by Room
Project: 7857 7857 Nottingham Uni Medical Centre
X0145ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: X0145 Treatment room: double-sided couch access
Room Number: Revision Date: 01/03/2017
Key: (n-old qty) Deletions m-new qty Additions m (n) Quantity changes since audit dateAudit Date: 2-Mar-2017
DescriptionCodeTotalTransNew
GrpAlt. CodeQuantity
3REFRIGERATOR, capacity 160 litre, automatic
defrost, stainless steel, underbench, external
temperature gauge, lockable, on castors, 850H
610W 600D
REF05811
3TROLLEY, modular storage, single open frame,
including handle and worktop, with up to 5 sets of
runners for 600 facing inserts, 850H 730W 450D
SMT00211
3STOOL, surgeon/anaesthetist, height adjustable,
includes anti-static seat pads
STO00611
3TROLLEY, dressing/instrument, stainless steel,
buffered, 870H 750W 450D
TRO13311
4COMPUTER KEYBOARDCOM93311
4COMPUTER MONITOR, 17"; TFT, digital flat panel
display, high-resolution screens, desk top
COM94911
8TRACK, blinds for windowsTRA90011
Activity DataBase 01/03/2017
X0273Room Data SheetADB
Project: 7857 7857 Nottingham Uni Medical Centre
Department: PRI Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
Room: X0273 Consulting/ treatment room: multidisciplinary dental
Room Number: Revision Date: 01/03/2017
1) Dental procedures for all dental specialties (eg restorative, orthodontic, oral surgery, maxfax
etc) may be carried out by a practitioner.
2) Dental procedures for all dental specialties (eg restorative, orthodontic, oral surgery, maxfax
etc) may be carried out by a practitioner.
3) Imaging x-ray equipment may be used.
4) Diagnostic images are viewed on monitor.
5) Electronic patient records (EPRs) may be accessed and updated.
6) Preparation of moulds/casts
7) Clinical wash-hand basin may be used.
Activities:
Personnel: 1 x patient.
2 x staff.
2 x others (escorts).
Planning
Relationships:
Space Data: Height (mm): 20.10 2,700Area (m²):
Notes: This room includes a dental chair with attached cuspidor, separate dental light and
mobile dental unit.
Specific equipment requirements and arrangements for treating people in wheelchairs
should be determined locally.
The call repeat lamp is situated over the door outside the room.
An X-ray control panel is required for the intra-oral X-ray machine. It has not been shown
on the room layout as its location is subject to specialist advice.
Separate data and voice outlets may be used where structure cabling solutions are not
available.
ADB Group Definitions:
1. Contractor supply and install.
2. Supply by others, contractor install.
3. UoN supply – loose equipment and specialist equipment (chairs, drawer units,
non-fixed medical equipment).
4. NHS IT equipment (nil cost to the project).
5. Dental supply and install.
6. Pharmacy supply and install.
7. UoN IT support and install.
8. UoN supply and install (tacks and blinds; fire extinguishers; UoN signage.
9. UoN F.O.C.
Activity DataBase 01/03/2017
7857 Nottingham Uni Medical Centre7857Project:
Room Environmental Data X0273ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: X0273 Consulting/ treatment room: multidisciplinary dental
Room Number: Revision Date: 01/03/2017
Permissible Space Temerature Range(dry bulb) (degC):
TEMPERATURE AND VENTILATION Requirements Notes
18 - 25
Heating Design Temperature (dry bulb)(degC): 22
Minimum Air Changes (AC/hr): 10
Ventilation Type: S/E
+vePressure Relative to Adjoining Space:
F7Supply Air: Final Filter Class
Permisiible Relative Humidity Range (%): Uncontrolled
General Notes:
LIGHTINGType Of Control: S/V
Daytime General Service Illuminance (Lux): 500
Daytime Specific Service Illuminance (Lux):
Nighttime General Service Illuminance (Lux):
Nighttime Specific Service Illuminance (Lux):
Local Task Illuminance (Lux): 30000-60000
Colour Rendering Required: Y
Colour Rendering Required Characteristics (Ra): 90
Unified Glare Rating Limit (UGRL): 19
Emergency Escape Route Lighting Required: In accordance with BS 5266 and Health Technical
MemorandumsY
Standby Lighting Grade - General Lighting:
Standby Lighting Grade - Local Lighting:
General Notes:
RISKClinical Risk Category:
Non-clinical Business Continuity Risk Category:
General Notes:
Noise Intrusion (dB) 1hr day:
NOISE
Noise Intrusion (dB) 1hr night:
Noise Intrusion (dB) f night:
40
-
-
Maximum Internal Noise from M&E Services (NR): 35 Total noise of MEP services under normal operation across
the range 63Hz to 4kHz inclusive.
Room Sound-insulation Parameters - Privacy:
Room Sound-insulation Parameters - Noise Generation:
Confidential
Typical
Reference to Table 3 of the Department of Health
'Acoustics: Technical design manual
4032:0.6:England'.
Noise Sensitiviy: Medium
Sound-insulation Rating (dB D nT,w):
General Notes:
Maximum Surface Temperature (DegC):
SAFETY/FIRE
43
Domestic Hot Water Discharge Temperature (DegC): 41
Maximum Cold Water Discharge Temperature (DegC): <20
General Notes:
Type of Automatic Fire Detection: Smoke
General Notes:
Activity DataBase 01/03/2017
ADB Room Design Character X0273
Project: 7857 7857 Nottingham Uni Medical Centre
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Consulting/ treatment room: multidisciplinary dentalX0273Room:
01/03/2017Revision Date:Room Number:
Walls: Wall finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Wall finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Floor: Floor finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Floor finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Ceiling: Ceiling finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Ceiling finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Doorsets: Configuration, glazing, fire rating, security, etc. to be determined by Project Team.
HTM 58 (Mar-2005)
Refer to HBN 00-04 (May-2007) for effective clear door widths.
1 doorset:
1 x personnel, trolley, wheelchair & equipment access (1500mm)
Requirement for hinge protection when areas used by children
Windows: Non-essential - Project Option
Clear glass with solar and privacy control
Designation to be validated against current documentation (HTM 55 archived).
Internal Glazing: Not required
Hatch: Not required
Notes: All finishes selected must have an appropriate risk assessment to accompany the design
decision.
Infection Control must be consulted as described in Performance Requirements for Building
Elements Used in Healthcare Facilities 8941:0.6 England.
Activity DataBase 01/03/2017
Schedule of Components by Room
Project: 7857 7857 Nottingham Uni Medical Centre
X0273ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: X0273 Consulting/ treatment room: multidisciplinary dental
Room Number: Revision Date: 01/03/2017
Key: (n-old qty) Deletions m-new qty Additions m (n) Quantity changes since audit dateAudit Date: 2-Mar-2017
DescriptionCodeTotalTransNew
GrpAlt. CodeQuantity
1BASIN, medium, hospital pattern, vitreous china, no
tap holes, no overflow, integral back outlet, 500W
400D.
BAS10111
1CABINET, dental, 1 door, under bench, on plinth,
(internal fittings-project option), 890H 500W 450D
CAB16033
1CABINET, dental, 1 door, wash basin, on plinth,
890H 500W 450D
CAB16611
1PULL/PUSH BUTTON, staff emergency call, reset
and integral/adjacent indicator lamp
CAL00711
1LAMP, repeat call, patient/staff or staff emergency or
cardiac call
CAL03411
1SOCKET outlet, switched, 13 amp, singleOUT00511
1SOCKET outlet, switched, 13 amp, twinOUT01055
1CONNECTION UNIT, switched, 13 amp, flex outletOUT04922
1SOCKET outlet data/voice, double.OUT13144
1SWITCH, lightSWC02511
1SWITCH, dimmer, modulatingSWC03411
1TAP, monobloc, pillar mixer, integral thermostatic,
short lever.
TAP28911
1TAP, bib, 2x8 mm thermostatic mixer, automatic
action, sensor operated, non-touch,
TAP89211
1TRAP, bottle, 1.1/4 in, plastic resealing.WAS10711
1WORKTOP, with left of centre inset sink bowl, 30H
2000W 500D
WOR71111
1WORKTOP, 30H 1600W 500DWOR72111
1WORKTOP, 30H 1800W 500DWOR72311
5BRACKET, holder, suction unit.BRA10311
5CHAIR, swivel, height adjustable, high back, with
arms, wipeable, 5 star base, on castors
CHA40111
5CHAIR, upright, upholstered, stacking, wipeableCHA41722
5CHAIR, dental treatment, fully reclining with headrest,
electrically height adjustable, wipeable.
CHA47011
5COMPUTER KEYBOARDCOM13311
5DENTAL UNIT, with multi-services terminal, mobileDEN11211
5DISPENSER, barrier cream, disposable single
cartridge, wall mounted
DIS21111
5HOLDER, sack, with lid foot operated, small,
freestanding
HOL10411
5HOLDER, sack, with lid foot operated, medium,
freestanding, 875H 430W 385D
HOL10611
5HOLDER, sharps box, up to 7 litre capacity,
rail/trolley hang or wall mounted, 170H 125W 100D
HOL12011
5HOOK, single, small, wall mountedHOO11933
5MONITOR medical display 18 in.; digital image
viewer, wall mounted
IMG10211
5ILLUMINATED SIGN 'RADIATION ON', wall mountedLIG17111
5MICROSCOPE dentalMIC13811
Activity DataBase 01/03/2017
Schedule of Components by Room
Project: 7857 7857 Nottingham Uni Medical Centre
X0273ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: X0273 Consulting/ treatment room: multidisciplinary dental
Room Number: Revision Date: 01/03/2017
Key: (n-old qty) Deletions m-new qty Additions m (n) Quantity changes since audit dateAudit Date: 2-Mar-2017
DescriptionCodeTotalTransNew
GrpAlt. CodeQuantity
5TROLLEY, modular storage, single open frame,
including handle and worktop, with up to 5 sets of
runners for 600 facing inserts, 850H 730W 450D
SMT10211
5STOOL, dental, with back support, mobileSTO12422
5TABLE, 710H 1200W 600DTAB10811
5TRACK, blinds for windowsTRA90211
Activity DataBase 01/03/2017
X0325Room Data SheetADB
Project: 7857 7857 Nottingham Uni Medical Centre
Department: PRI Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
Room: X0325 Activity area: physiotherapy: 5 places
Room Number: Revision Date: 01/03/2017
1) Clinical wash-hand basin may be used.
2) Carrying out administration and clerical duties.
3) Information may be provided to patients, carers and visitors.
4) Clinical administration.
5) Patient records may be reviewed and recorded.
6) Telephone(s) may be used.
7) Information on computers may be accessed.
8) Electronic patient records (EPRs) may be accessed and updated.
9) Foot operated treadle and bicycle equipment is used.
10) Rehabilitation exercises are undertaken.
Activities:
Personnel: Up to 5 x patients.
2-3 x staff.
Planning
Relationships:
Near to individual treatment room area. (Are these included in HBN 11 SoA)
Direct access/close to equipment store.
Close to any associated changing/shower provision.
Space Data: Height (mm): 64.00 3,000Area (m²):
Notes: The call repeat lamp is situated over the door outside the room.
Separate data and voice outlets may be used where structure cabling solutions are not
available.
ADB Group Definitions:
1. Contractor supply and install.
2. Supply by others, contractor install.
3. UoN supply – loose equipment and specialist equipment (chairs, drawer units,
non-fixed medical equipment).
4. NHS IT equipment (nil cost to the project).
5. Dental supply and install.
6. Pharmacy supply and install.
7. UoN IT support and install.
8. UoN supply and install (tacks and blinds; fire extinguishers; UoN signage.
9. UoN F.O.C.
Activity DataBase 01/03/2017
7857 Nottingham Uni Medical Centre7857Project:
Room Environmental Data X0325ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: X0325 Activity area: physiotherapy: 5 places
Room Number: Revision Date: 01/03/2017
Permissible Space Temerature Range(dry bulb) (degC):
TEMPERATURE AND VENTILATION Requirements Notes
18 - 28
Heating Design Temperature (dry bulb)(degC): 21
Minimum Air Changes (AC/hr): 6
Ventilation Type: S/E/N
Bal or -vePressure Relative to Adjoining Space:
G4Supply Air: Final Filter Class
Permisiible Relative Humidity Range (%): Uncontrolled
General Notes:
LIGHTINGType Of Control: S/N
Daytime General Service Illuminance (Lux):
Daytime Specific Service Illuminance (Lux):
Nighttime General Service Illuminance (Lux):
Nighttime Specific Service Illuminance (Lux):
Local Task Illuminance (Lux):
Colour Rendering Required: Y
Colour Rendering Required Characteristics (Ra): 80
Unified Glare Rating Limit (UGRL): 19
Emergency Escape Route Lighting Required: In accordance with BS 5266 and Health Technical
MemorandumsY
Standby Lighting Grade - General Lighting:
Standby Lighting Grade - Local Lighting:
General Notes:
RISKClinical Risk Category:
Non-clinical Business Continuity Risk Category:
General Notes:
Noise Intrusion (dB) 1hr day:
NOISE
Noise Intrusion (dB) 1hr night:
Noise Intrusion (dB) f night:
40
-
-
Maximum Internal Noise from M&E Services (NR): 40 Total noise of MEP services under normal operation across
the range 63Hz to 4kHz inclusive.
Room Sound-insulation Parameters - Privacy:
Room Sound-insulation Parameters - Noise Generation:
Moderate
Typical
Reference to Table 3 of the Department of Health 'Acoustics:
Technical design manual 4032:0.6:England'.
Noise Sensitiviy: Medium
Sound-insulation Rating (dB D nT,w):
General Notes:
Maximum Surface Temperature (DegC):
SAFETY/FIRE
43
Domestic Hot Water Discharge Temperature (DegC): 41
Maximum Cold Water Discharge Temperature (DegC): <20
General Notes:
Type of Automatic Fire Detection: Smoke
General Notes:
Activity DataBase 01/03/2017
ADB Room Design Character X0325
Project: 7857 7857 Nottingham Uni Medical Centre
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Activity area: physiotherapy: 5 placesX0325Room:
01/03/2017Revision Date:Room Number:
Walls: Wall finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Wall finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Floor: Floor finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Floor finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Ceiling: Ceiling finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Ceiling finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Doorsets: Configuration, glazing, fire rating, security, etc. to be determined by Project Team.
HTM 58 (Mar-2005)
Refer to HBN 00-04 (May-2007) for effective clear door widths.
2 sets of doors:
2 x personnel, trolley, wheelchair & equipment access (1500mm);
Requirement for hinge protection when areas used by children
Windows: Essential
Clear glass with solar control, high level
Designation to be validated against current documentation (HTM 55 archived).
Internal Glazing: Not required
Hatch: Not required
Notes: All finishes selected must have an appropriate risk assessment to accompany the design
decision.
Infection Control must be consulted as described in Performance Requirements for Building
Elements Used in Healthcare Facilities 8941:0.6 England.
Activity DataBase 01/03/2017
Schedule of Components by Room
Project: 7857 7857 Nottingham Uni Medical Centre
X0325ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: X0325 Activity area: physiotherapy: 5 places
Room Number: Revision Date: 01/03/2017
Key: (n-old qty) Deletions m-new qty Additions m (n) Quantity changes since audit dateAudit Date: 2-Mar-2017
DescriptionCodeTotalTransNew
GrpAlt. CodeQuantity
1BASIN, medium, hospital pattern, vitreous china, no
tap holes, no overflow, integral back outlet, 500W
400D.
BAS10111
1BOARD, display/notice, wall mounted, 900H 600WBOA01211
1PULL/PUSH BUTTON, staff emergency call, reset
and integral/adjacent indicator lamp
CAL00722
1LAMP, repeat call, patient/staff or staff emergency or
cardiac call
CAL03411
1MIRROR, triple leaf, wall mounted, 1500H 1500WMIR00811
1OUTLET cable, 13 ampOUT00211
1SOCKET outlet, switched, 13 amp, singleOUT00511
1SOCKET outlet, switched, 13 amp, twinOUT01088
1CONNECTION UNIT, switched, 13 amp, flex outletOUT04911
1CONNECTION UNIT switched 13amp, indicatingOUT05811
1SOCKET outlet data/voice, double.OUT13122
1OUTLET, drinking water for equipmentOUT31511
1SWITCH, lightSWC02511
1TAP, bib, 2x8 mm thermostatic mixer, automatic
action, sensor operated, non-touch,
TAP89211
1TRACK, curtain, three sided, U-shape, 2900L 2700WTRA11622
1TRAP, bottle, 1.1/4 in, plastic resealing.WAS10711
2DISPENSER, barrier cream, disposable single
cartridge, wall mounted
DIS01111
2DISPENSER, paper towel, wall mountedDIS01311
2DISPENSER, Medical hand sanitizer, lever action,
wall mounted
DIS02622
2DISPENSER, soap, disposable single cartridge, lever
action, wall mounted
DIS03011
2DISPENSER, disposable gloves set of 3 and
disposable apron, wall mounted
DIS43822
2EXERCISE BARS, parallel, 3600mm longEXE00311
2PULLEY, exercise system, wall mounted, 1800H
560W
PUL01311
3CHAIR, swivel, height adjustable, high back, with
arms, wipeable, 5 star base, on castors
CHA30111
3CHAIR, upright, upholstered, stacking, wipeableCHA31722
3EXERCISE BENCH, 400H 2655W 300DEXE00811
3HOLDER, sack, with lid foot operated, medium,
freestanding, 875H 430W 385D
HOL00611
3MIRROR, unbreakable/safety glass, mobile, 1600H
500W
MIR01211
3PLINTH, Bobath centre, height adjustable
(380-910mm) and head section, 910H 1900W 1200D
PLI04022
3STOOL, height adjustable, 380H 480 dia.STO00222
3STOOL, wooden, 400H 400W 400DSTO01511
3TABLE, 710H 1200W 600DTAB00811
Activity DataBase 01/03/2017
Schedule of Components by Room
Project: 7857 7857 Nottingham Uni Medical Centre
X0325ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: X0325 Activity area: physiotherapy: 5 places
Room Number: Revision Date: 01/03/2017
Key: (n-old qty) Deletions m-new qty Additions m (n) Quantity changes since audit dateAudit Date: 2-Mar-2017
DescriptionCodeTotalTransNew
GrpAlt. CodeQuantity
3TABLE, therapy treatment, quadriceps, folding, 710H
1240W 610D
TAB09111
4COMPUTER KEYBOARDCOM03311
4COMPUTER MONITOR, 17"; TFT, digital flat panel
display, high-resolution screens, desk top
COM04911
5EXERCISE BICYCLE, ergometerEXE01411
5EXERCISE STEPSEXE01711
9DISPENSER, cooler, drinking water, (fountain),
(capacity 63.3 l/hr), floor standing
DIS00211
9DISPENSER, disposable cup, wall mountedDIS01211
Activity DataBase 01/03/2017
X0325-01Room Data SheetADB
Project: 7857 7857 Nottingham Uni Medical Centre
Department: PRI Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
Room: X0325-01 Activity area: physiotherapy: 5 places/2
Room Number: Revision Date: 01/03/2017
1) Clinical wash-hand basin may be used.
2) Carrying out administration and clerical duties.
3) Information may be provided to patients, carers and visitors.
4) Clinical administration.
5) Patient records may be reviewed and recorded.
6) Telephone(s) may be used.
7) Information on computers may be accessed.
8) Electronic patient records (EPRs) may be accessed and updated.
9) Foot operated treadle and bicycle equipment is used.
10) Rehabilitation exercises are undertaken.
Activities:
Personnel: Up to 5 x patients.
2-3 x staff.
Planning
Relationships:
Near to individual treatment room area. (Are these included in HBN 11 SoA)
Direct access/close to equipment store.
Close to any associated changing/shower provision.
Space Data: Height (mm): 32.00 3,000Area (m²):
Notes: The call repeat lamp is situated over the door outside the room.
Separate data and voice outlets may be used where structure cabling solutions are not
available.
ADB Group Definitions:
1. Contractor supply and install.
2. Supply by others, contractor install.
3. UoN supply – loose equipment and specialist equipment (chairs, drawer units,
non-fixed medical equipment).
4. NHS IT equipment (nil cost to the project).
5. Dental supply and install.
6. Pharmacy supply and install.
7. UoN IT support and install.
8. UoN supply and install (tacks and blinds; fire extinguishers; UoN signage.
9. UoN F.O.C.
Activity DataBase 01/03/2017
7857 Nottingham Uni Medical Centre7857Project:
Room Environmental Data X0325-01ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: X0325-01 Activity area: physiotherapy: 5 places/2
Room Number: Revision Date: 01/03/2017
Permissible Space Temerature Range(dry bulb) (degC):
TEMPERATURE AND VENTILATION Requirements Notes
18 - 28
Heating Design Temperature (dry bulb)(degC): 21
Minimum Air Changes (AC/hr): 6
Ventilation Type: S/E/N
Bal or -vePressure Relative to Adjoining Space:
G4Supply Air: Final Filter Class
Permisiible Relative Humidity Range (%): Uncontrolled
General Notes:
LIGHTINGType Of Control: S/N
Daytime General Service Illuminance (Lux):
Daytime Specific Service Illuminance (Lux):
Nighttime General Service Illuminance (Lux):
Nighttime Specific Service Illuminance (Lux):
Local Task Illuminance (Lux):
Colour Rendering Required: Y
Colour Rendering Required Characteristics (Ra): 80
Unified Glare Rating Limit (UGRL): 19
Emergency Escape Route Lighting Required: In accordance with BS 5266 and Health Technical
MemorandumsY
Standby Lighting Grade - General Lighting:
Standby Lighting Grade - Local Lighting:
General Notes:
RISKClinical Risk Category:
Non-clinical Business Continuity Risk Category:
General Notes:
Noise Intrusion (dB) 1hr day:
NOISE
Noise Intrusion (dB) 1hr night:
Noise Intrusion (dB) f night:
40
-
-
Maximum Internal Noise from M&E Services (NR): 40 Total noise of MEP services under normal operation across
the range 63Hz to 4kHz inclusive.
Room Sound-insulation Parameters - Privacy:
Room Sound-insulation Parameters - Noise Generation:
Moderate
Typical
Reference to Table 3 of the Department of Health 'Acoustics:
Technical design manual 4032:0.6:England'.
Noise Sensitiviy: Medium
Sound-insulation Rating (dB D nT,w):
General Notes:
Maximum Surface Temperature (DegC):
SAFETY/FIRE
43
Domestic Hot Water Discharge Temperature (DegC): 41
Maximum Cold Water Discharge Temperature (DegC): <20
General Notes:
Type of Automatic Fire Detection: Smoke
General Notes:
Activity DataBase 01/03/2017
ADB Room Design Character X0325-01
Project: 7857 7857 Nottingham Uni Medical Centre
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Activity area: physiotherapy: 5 places/2X0325-01Room:
01/03/2017Revision Date:Room Number:
Walls: Wall finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Wall finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Floor: Floor finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Floor finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Ceiling: Ceiling finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Ceiling finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Doorsets: Configuration, glazing, fire rating, security, etc. to be determined by Project Team.
HTM 58 (Mar-2005)
Refer to HBN 00-04 (May-2007) for effective clear door widths.
2 sets of doors:
2 x personnel, trolley, wheelchair & equipment access (1500mm);
Requirement for hinge protection when areas used by children
Windows: Essential
Clear glass with solar control, high level
Designation to be validated against current documentation (HTM 55 archived).
Internal Glazing: Not required
Hatch: Not required
Notes: All finishes selected must have an appropriate risk assessment to accompany the design
decision.
Infection Control must be consulted as described in Performance Requirements for Building
Elements Used in Healthcare Facilities 8941:0.6 England.
Activity DataBase 01/03/2017
Schedule of Components by Room
Project: 7857 7857 Nottingham Uni Medical Centre
X0325-01ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: X0325-01 Activity area: physiotherapy: 5 places/2
Room Number: Revision Date: 01/03/2017
Key: (n-old qty) Deletions m-new qty Additions m (n) Quantity changes since audit dateAudit Date: 2-Mar-2017
DescriptionCodeTotalTransNew
GrpAlt. CodeQuantity
1BASIN, medium, hospital pattern, vitreous china, no
tap holes, no overflow, integral back outlet, 500W
400D.
BAS10111
1PULL/PUSH BUTTON, staff emergency call, reset
and integral/adjacent indicator lamp
CAL00722
1LAMP, repeat call, patient/staff or staff emergency or
cardiac call
CAL03411
1OUTLET cable, 13 ampOUT00211
1SOCKET outlet, switched, 13 amp, twinOUT01066
1CONNECTION UNIT, switched, 13 amp, flex outletOUT04911
1SOCKET outlet data/voice, double.OUT13122
1OUTLET, drinking water for equipmentOUT31511
1TAP, bib, 2x8 mm thermostatic mixer, automatic
action, sensor operated, non-touch,
TAP89211
1TRACK, curtain, three sided, U-shape, 2900L 2700WTRA11611
1TRAP, bottle, 1.1/4 in, plastic resealing.WAS10711
2DISPENSER, barrier cream, disposable single
cartridge, wall mounted
DIS01111
2DISPENSER, paper towel, wall mountedDIS01311
2DISPENSER, Medical hand sanitizer, lever action,
wall mounted
DIS02611
2DISPENSER, soap, disposable single cartridge, lever
action, wall mounted
DIS03011
2DISPENSER, disposable gloves set of 3 and
disposable apron, wall mounted
DIS43811
3CHAIR, swivel, height adjustable, high back, with
arms, wipeable, 5 star base, on castors
CHA30111
3CHAIR, upright, upholstered, stacking, wipeableCHA31711
3HOLDER, sack, with lid foot operated, medium,
freestanding, 875H 430W 385D
HOL00611
3MIRROR, unbreakable/safety glass, mobile, 1600H
500W
MIR01211
3PLINTH, Bobath centre, height adjustable
(380-910mm) and head section, 910H 1900W 1200D
PLI04011
3STOOL, height adjustable, 380H 480 dia.STO00211
3TABLE, 710H 1200W 600DTAB00811
3TABLE, therapy treatment, quadriceps, folding, 710H
1240W 610D
TAB09111
4COMPUTER KEYBOARDCOM03311
4COMPUTER MONITOR, 17"; TFT, digital flat panel
display, high-resolution screens, desk top
COM04911
8TRACK, blinds for windowsTRA90033
9DISPENSER, cooler, drinking water, (fountain),
(capacity 63.3 l/hr), floor standing
DIS00211
9DISPENSER, disposable cup, wall mountedDIS01211
Activity DataBase 01/03/2017
X0325-02Room Data SheetADB
Project: 7857 7857 Nottingham Uni Medical Centre
Department: PRI Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
Room: X0325-02 Activity area: physiotherapy: 5 places/2
Room Number: Revision Date: 01/03/2017
1) Clinical wash-hand basin may be used.
2) Carrying out administration and clerical duties.
3) Information may be provided to patients, carers and visitors.
4) Clinical administration.
5) Patient records may be reviewed and recorded.
6) Telephone(s) may be used.
7) Information on computers may be accessed.
8) Electronic patient records (EPRs) may be accessed and updated.
9) Foot operated treadle and bicycle equipment is used.
10) Rehabilitation exercises are undertaken.
Activities:
Personnel: Up to 5 x patients.
2-3 x staff.
Planning
Relationships:
Near to individual treatment room area. (Are these included in HBN 11 SoA)
Direct access/close to equipment store.
Close to any associated changing/shower provision.
Space Data: Height (mm): 32.00 3,000Area (m²):
Notes: The call repeat lamp is situated over the door outside the room.
Separate data and voice outlets may be used where structure cabling solutions are not
available.
ADB Group Definitions:
1. Contractor supply and install.
2. Supply by others, contractor install.
3. UoN supply – loose equipment and specialist equipment (chairs, drawer units,
non-fixed medical equipment).
4. NHS IT equipment (nil cost to the project).
5. Dental supply and install.
6. Pharmacy supply and install.
7. UoN IT support and install.
8. UoN supply and install (tacks and blinds; fire extinguishers; UoN signage.
9. UoN F.O.C.
Activity DataBase 01/03/2017
7857 Nottingham Uni Medical Centre7857Project:
Room Environmental Data X0325-02ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: X0325-02 Activity area: physiotherapy: 5 places/2
Room Number: Revision Date: 01/03/2017
Permissible Space Temerature Range(dry bulb) (degC):
TEMPERATURE AND VENTILATION Requirements Notes
18 - 28
Heating Design Temperature (dry bulb)(degC): 21
Minimum Air Changes (AC/hr): 6
Ventilation Type: S/E/N
Bal or -vePressure Relative to Adjoining Space:
G4Supply Air: Final Filter Class
Permisiible Relative Humidity Range (%): Uncontrolled
General Notes:
LIGHTINGType Of Control: S/N
Daytime General Service Illuminance (Lux):
Daytime Specific Service Illuminance (Lux):
Nighttime General Service Illuminance (Lux):
Nighttime Specific Service Illuminance (Lux):
Local Task Illuminance (Lux):
Colour Rendering Required: Y
Colour Rendering Required Characteristics (Ra): 80
Unified Glare Rating Limit (UGRL): 19
Emergency Escape Route Lighting Required: In accordance with BS 5266 and Health Technical
MemorandumsY
Standby Lighting Grade - General Lighting:
Standby Lighting Grade - Local Lighting:
General Notes:
RISKClinical Risk Category:
Non-clinical Business Continuity Risk Category:
General Notes:
Noise Intrusion (dB) 1hr day:
NOISE
Noise Intrusion (dB) 1hr night:
Noise Intrusion (dB) f night:
40
-
-
Maximum Internal Noise from M&E Services (NR): 40 Total noise of MEP services under normal operation across
the range 63Hz to 4kHz inclusive.
Room Sound-insulation Parameters - Privacy:
Room Sound-insulation Parameters - Noise Generation:
Moderate
Typical
Reference to Table 3 of the Department of Health 'Acoustics:
Technical design manual 4032:0.6:England'.
Noise Sensitiviy: Medium
Sound-insulation Rating (dB D nT,w):
General Notes:
Maximum Surface Temperature (DegC):
SAFETY/FIRE
43
Domestic Hot Water Discharge Temperature (DegC): 41
Maximum Cold Water Discharge Temperature (DegC): <20
General Notes:
Type of Automatic Fire Detection: Smoke
General Notes:
Activity DataBase 01/03/2017
ADB Room Design Character X0325-02
Project: 7857 7857 Nottingham Uni Medical Centre
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Activity area: physiotherapy: 5 places/2X0325-02Room:
01/03/2017Revision Date:Room Number:
Walls: Wall finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Wall finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Floor: Floor finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Floor finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Ceiling: Ceiling finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Ceiling finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Doorsets: Configuration, glazing, fire rating, security, etc. to be determined by Project Team.
HTM 58 (Mar-2005)
Refer to HBN 00-04 (May-2007) for effective clear door widths.
2 sets of doors:
2 x personnel, trolley, wheelchair & equipment access (1500mm);
Requirement for hinge protection when areas used by children
Windows: Essential
Clear glass with solar control, high level
Designation to be validated against current documentation (HTM 55 archived).
Internal Glazing: Not required
Hatch: Not required
Notes: All finishes selected must have an appropriate risk assessment to accompany the design
decision.
Infection Control must be consulted as described in Performance Requirements for Building
Elements Used in Healthcare Facilities 8941:0.6 England.
Activity DataBase 01/03/2017
Schedule of Components by Room
Project: 7857 7857 Nottingham Uni Medical Centre
X0325-02ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: X0325-02 Activity area: physiotherapy: 5 places/2
Room Number: Revision Date: 01/03/2017
Key: (n-old qty) Deletions m-new qty Additions m (n) Quantity changes since audit dateAudit Date: 2-Mar-2017
DescriptionCodeTotalTransNew
GrpAlt. CodeQuantity
1BASIN, medium, hospital pattern, vitreous china, no
tap holes, no overflow, integral back outlet, 500W
400D.
BAS10111
1BOARD, display/notice, wall mounted, 900H 600WBOA01211
1PULL/PUSH BUTTON, staff emergency call, reset
and integral/adjacent indicator lamp
CAL00711
1LAMP, repeat call, patient/staff or staff emergency or
cardiac call
CAL03411
1MIRROR, triple leaf, wall mounted, 1500H 1500WMIR00811
1SOCKET outlet, switched, 13 amp, singleOUT00511
1SOCKET outlet, switched, 13 amp, twinOUT01066
1CONNECTION UNIT, switched, 13 amp, flex outletOUT04911
1CONNECTION UNIT switched 13amp, indicatingOUT05811
1SOCKET outlet data/voice, double.OUT13122
1SWITCH, lightSWC02511
1TAP, bib, 2x8 mm thermostatic mixer, automatic
action, sensor operated, non-touch,
TAP89211
1TRACK, curtain, three sided, U-shape, 2900L 2700WTRA11611
1TRAP, bottle, 1.1/4 in, plastic resealing.WAS10711
2DISPENSER, barrier cream, disposable single
cartridge, wall mounted
DIS01111
2DISPENSER, paper towel, wall mountedDIS01311
2DISPENSER, Medical hand sanitizer, lever action,
wall mounted
DIS02611
2DISPENSER, soap, disposable single cartridge, lever
action, wall mounted
DIS03011
2DISPENSER, disposable gloves set of 3 and
disposable apron, wall mounted
DIS43811
2PULLEY, exercise system, wall mounted, 1800H
560W
PUL01311
3CHAIR, swivel, height adjustable, high back, with
arms, wipeable, 5 star base, on castors
CHA30111
3CHAIR, upright, upholstered, stacking, wipeableCHA31711
3EXERCISE BENCH, 400H 2655W 300DEXE00811
3HOLDER, sack, with lid foot operated, medium,
freestanding, 875H 430W 385D
HOL00611
3PLINTH, Bobath centre, height adjustable
(380-910mm) and head section, 910H 1900W 1200D
PLI04011
3STOOL, height adjustable, 380H 480 dia.STO00211
3STOOL, wooden, 400H 400W 400DSTO01511
3TABLE, 710H 1200W 600DTAB00811
4COMPUTER KEYBOARDCOM03311
4COMPUTER MONITOR, 17"; TFT, digital flat panel
display, high-resolution screens, desk top
COM04911
5EXERCISE BICYCLE, ergometerEXE01411
5EXERCISE STEPSEXE01711
8TRACK, blinds for windowsTRA90011
Activity DataBase 01/03/2017
Y0431Room Data SheetADB
Project: 7857 7857 Nottingham Uni Medical Centre
Department: PRI Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
Room: Y0431 Dirty utility room
Room Number: Revision Date: 01/03/2017
1) Disposal of liquid waste.
2) Holding SHARPS in a container.
3) Items requiring disposal or reprocessing may be held/stored.
4) Clinical wash-hand basin may be used.
5) Urine specimens may be tested.
6) Clinical waste may be disposed
7) Disposal of waste and contaminated materials.
8) Disposal of used protective clothing.
9) Disposal of non-clinical waste.
Activities:
Personnel: 2 x staff.
Intermittent use.
Planning
Relationships:
Close to clinical area, particularly treatment rooms.
Space Data: Height (mm): 8.00 2,700Area (m²):
Notes: ADB Group Definitions:
1. Contractor supply and install.
2. Supply by others, contractor install.
3. UoN supply – loose equipment and specialist equipment (chairs, drawer units,
non-fixed medical equipment).
4. NHS IT equipment (nil cost to the project).
5. Dental supply and install.
6. Pharmacy supply and install.
7. UoN IT support and install.
8. UoN supply and install (tacks and blinds; fire extinguishers; UoN signage.
9. UoN F.O.C.
Activity DataBase 01/03/2017
7857 Nottingham Uni Medical Centre7857Project:
Room Environmental Data Y0431ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: Y0431 Dirty utility room
Room Number: Revision Date: 01/03/2017
Permissible Space Temerature Range(dry bulb) (degC):
TEMPERATURE AND VENTILATION Requirements Notes
18 - 28
Heating Design Temperature (dry bulb)(degC): 18
Minimum Air Changes (AC/hr): 6
Ventilation Type: E
-vePressure Relative to Adjoining Space:
Supply Air: Final Filter Class
Permisiible Relative Humidity Range (%): Uncontrolled
General Notes:
LIGHTINGType Of Control: N/S
Daytime General Service Illuminance (Lux): 200
Daytime Specific Service Illuminance (Lux):
Nighttime General Service Illuminance (Lux):
Nighttime Specific Service Illuminance (Lux):
Local Task Illuminance (Lux):
Colour Rendering Required: Y
Colour Rendering Required Characteristics (Ra): 80
Unified Glare Rating Limit (UGRL): 22
Emergency Escape Route Lighting Required: In accordance with BS 5266 and Health Technical
MemorandumsY
Standby Lighting Grade - General Lighting: B
Standby Lighting Grade - Local Lighting:
General Notes: Refer to SLL Lighting Guide 2 for more detailed guidance
RISKClinical Risk Category:
Non-clinical Business Continuity Risk Category:
General Notes:
Noise Intrusion (dB) 1hr day:
NOISE
Noise Intrusion (dB) 1hr night:
Noise Intrusion (dB) f night:
50
-
-
Maximum Internal Noise from M&E Services (NR): 40 Total noise of MEP services under normal operation across
the range 63Hz to 4kHz inclusive.
Room Sound-insulation Parameters - Privacy:
Room Sound-insulation Parameters - Noise Generation:
Not Private
High
Reference to Table 3 of the Department of Health 'Acoustics:
Technical design manual 4032:0.6:England'.
Noise Sensitiviy: Not Sensitive
Sound-insulation Rating (dB D nT,w):
General Notes:
Maximum Surface Temperature (DegC):
SAFETY/FIRE
82
Domestic Hot Water Discharge Temperature (DegC): 41/>55
Maximum Cold Water Discharge Temperature (DegC): <20
General Notes:
Type of Automatic Fire Detection: Smoke
General Notes:
Activity DataBase 01/03/2017
ADB Room Design Character Y0431
Project: 7857 7857 Nottingham Uni Medical Centre
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Dirty utility roomY0431Room:
01/03/2017Revision Date:Room Number:
Walls: Wall finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Wall finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Floor: Floor finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Floor finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Ceiling: Ceiling finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Ceiling finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Doorsets: Configuration, glazing, fire rating, security, etc. to be determined by Project Team.
HTM 58 (Mar-2005)
Refer to HBN 00-04 (May-2007) for effective clear door widths.
1 doorset:
1 x personnel & equipment access (1000mm)
Windows: Non-essential - Project Option
Clear glass with solar and privacy control
Designation to be validated against current documentation (HTM 55 archived).
Internal Glazing: Not required
Hatch: Not required
Notes: All finishes selected must have an appropriate risk assessment to accompany the design
decision.
Infection Control must be consulted as described in Performance Requirements for Building
Elements Used in Healthcare Facilities 8941:0.6 England.
Activity DataBase 01/03/2017
Schedule of Components by Room
Project: 7857 7857 Nottingham Uni Medical Centre
Y0431ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: Y0431 Dirty utility room
Room Number: Revision Date: 01/03/2017
Key: (n-old qty) Deletions m-new qty Additions m (n) Quantity changes since audit dateAudit Date: 2-Mar-2017
DescriptionCodeTotalTransNew
GrpAlt. CodeQuantity
1BASIN, medium, hospital pattern, vitreous china, no
tap holes, no overflow, integral back outlet, 500W
400D.
BAS10111
1LAMP, repeat call, patient/staff or staff emergency or
cardiac call
CAL03411
1DISPOSAL UNIT, plain top, right hand drainer, with
sink and hopper with flushing rim, 110mm outlet, no
tap holes no overflow, back inlet, stainless steel,
1600W 600D.
DSU00611
1SOCKET outlet, switched, 13 amp, singleOUT00511
1SOCKET outlet, switched, 13 amp, twinOUT01011
1CONNECTION UNIT, switched, 13 amp, flex outletOUT04911
1CABINET, base, modular storage, for 400 facing
inserts, with door, on plinth, 900H
SMC01322
1CABINET, upper, modular storage, for 400 facing
inserts, with door, 750H
SMC02322
1WORKTOP, clinical, for 2 x 400 facing modular
storage cabinets, 910W 700D
SMW05211
1SWITCH, lightSWC02511
1TAP, bib, lever, hospital pattern, pair hot and cold,
1/2 in.
TAP80911
1TAP, bib, 2x8 mm thermostatic mixer, automatic
action, sensor operated, non-touch,
TAP89211
1WASTE, unslotted flush-grated, metal, 1.1/2 in.WAS10211
1TRAP, bottle, 1.1/4 in, plastic resealing.WAS10711
1TRAP, bottle, 1.1/2 in, plastic resealing.WAS10811
2DISPENSER, paper towel roll, wall mountedDIS00711
2DISPENSER, barrier cream, disposable single
cartridge, wall mounted
DIS01111
2DISPENSER, paper towel, wall mountedDIS01311
2DISPENSER, soap, disposable single cartridge, lever
action, wall mounted
DIS03011
2DISPENSER, disposable gloves set of 3 and
disposable apron, wall mounted
DIS43811
3HOLDER, sack, with lid foot operated, medium,
freestanding, 875H 430W 385D
HOL00644
8TRACK, blinds for windowsTRA90011
Activity DataBase 01/03/2017
Y0642Room Data SheetADB
Project: 7857 7857 Nottingham Uni Medical Centre
Department: PRI Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
Room: Y0642 Disposal hold: 1700 litres
Room Number: Revision Date: 01/03/2017
1) Holding domestic, clinical and recyclable waste for disposal or reprocessingActivities:
Personnel: 1 x staff.
Intermittent use.
Planning
Relationships:
Adjacent to main circulation route.
Space Data: Height (mm): 8.00 2,700Area (m²):
Ceiling height must allow bin lids to open fully.
Notes: Separate bins/areas must be provided for:
- clinical waste;
- domestic waste;
- recyclable items;
- linen;
- equipment requiring reprocessing.
ADB Group Definitions:
1. Contractor supply and install.
2. Supply by others, contractor install.
3. UoN supply – loose equipment and specialist equipment (chairs, drawer units,
non-fixed medical equipment).
4. NHS IT equipment (nil cost to the project).
5. Dental supply and install.
6. Pharmacy supply and install.
7. UoN IT support and install.
8. UoN supply and install (tacks and blinds; fire extinguishers; UoN signage.
9. UoN F.O.C.
Activity DataBase 01/03/2017
7857 Nottingham Uni Medical Centre7857Project:
Room Environmental Data Y0642ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: Y0642 Disposal hold: 1700 litres
Room Number: Revision Date: 01/03/2017
Permissible Space Temerature Range(dry bulb) (degC):
TEMPERATURE AND VENTILATION Requirements Notes
18 - 28
Heating Design Temperature (dry bulb)(degC): 18
Minimum Air Changes (AC/hr): 3
Ventilation Type: E
-vePressure Relative to Adjoining Space:
Supply Air: Final Filter Class
Permisiible Relative Humidity Range (%): Uncontrolled
General Notes:
LIGHTINGType Of Control: N
Daytime General Service Illuminance (Lux): 200
Daytime Specific Service Illuminance (Lux):
Nighttime General Service Illuminance (Lux):
Nighttime Specific Service Illuminance (Lux):
Local Task Illuminance (Lux):
Colour Rendering Required: Y
Colour Rendering Required Characteristics (Ra): 80
Unified Glare Rating Limit (UGRL): 22
Emergency Escape Route Lighting Required: In accordance with BS 5266 and Health Technical
MemorandumsY
Standby Lighting Grade - General Lighting:
Standby Lighting Grade - Local Lighting:
General Notes:
RISKClinical Risk Category:
Non-clinical Business Continuity Risk Category:
General Notes:
Noise Intrusion (dB) 1hr day:
NOISE
Noise Intrusion (dB) 1hr night:
Noise Intrusion (dB) f night:
50
-
-
Maximum Internal Noise from M&E Services (NR): 40 Total noise of MEP services under normal operation across
the range 63Hz to 4kHz inclusive.
Room Sound-insulation Parameters - Privacy:
Room Sound-insulation Parameters - Noise Generation:
Not Private
Typical
Reference to Table 3 of the Department of Health 'Acoustics:
Technical design manual 4032:0.6:England'.
Noise Sensitiviy: Not Sensitive
Sound-insulation Rating (dB D nT,w):
General Notes:
Maximum Surface Temperature (DegC):
SAFETY/FIRE
82
Domestic Hot Water Discharge Temperature (DegC): 41/>55
Maximum Cold Water Discharge Temperature (DegC): <20
General Notes:
Type of Automatic Fire Detection: Smoke
General Notes:
Activity DataBase 01/03/2017
ADB Room Design Character Y0642
Project: 7857 7857 Nottingham Uni Medical Centre
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Disposal hold: 1700 litresY0642Room:
01/03/2017Revision Date:Room Number:
Walls: Wall finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Wall finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Floor: Floor finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Floor finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Ceiling: Ceiling finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Ceiling finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Doorsets: Configuration, glazing, fire rating, security, etc. to be determined by Project Team.
HTM 58 (Mar-2005)
Refer to HBN 00-04 (May-2007) for effective clear door widths.
1 doorset:
1 x personnel, trolley, & equipment access (1500mm)
Windows: Not required
Internal Glazing: Not required
Hatch: Not required
Notes: All finishes selected must have an appropriate risk assessment to accompany the design
decision.
Infection Control must be consulted as described in Performance Requirements for Building
Elements Used in Healthcare Facilities 8941:0.6 England.
Activity DataBase 01/03/2017
Schedule of Components by Room
Project: 7857 7857 Nottingham Uni Medical Centre
Y0642ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: Y0642 Disposal hold: 1700 litres
Room Number: Revision Date: 01/03/2017
Key: (n-old qty) Deletions m-new qty Additions m (n) Quantity changes since audit dateAudit Date: 2-Mar-2017
DescriptionCodeTotalTransNew
GrpAlt. CodeQuantity
1SOCKET outlet, switched, 13 amp, singleOUT00511
1SOCKET outlet, switched, 13 amp, twinOUT01011
1SHELVING FRAME, modular storage, 1 bay, with 5
shelves, 2130H 1000W 665D
SMF01311
1SWITCH, lightSWC02511
3BIN wheelie, 240 litre, 1060H 600W 730DBIN03411
3BIN wheelie, 1100 litre, 1470H1370W 1115DBIN03811
Activity DataBase 01/03/2017
Y1510-01Room Data SheetADB
Project: 7857 7857 Nottingham Uni Medical Centre
Department: PRI Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
Room: Y1510-01 Cleaners' room
Room Number: Revision Date: 01/03/2017
1) Disposal of liquid waste.
2) Filling and emptying cleaning equipment and containers.
3) Holding/storing cleaning equipment.
4) Cleaning equipment may be parked and/or stored.
5) Hand-rinse basin may be used.
6) Sink may be used.
7) Janitorial unit may be used.
Activities:
Personnel: 2 x staff.
Intermittent use.
Planning
Relationships:
Close to areas served.
Space Data: Height (mm): 8.00 2,400Area (m²):
If large equipment is stored elsewhere, the size of this room can be reduced.
Notes: This room represents a typical traditional cleaners' room with space for storing a vacuum
cleaner, scrubbing/polishing machine (for hard floors) and mop and bucket (stored on
the cleaners' trolley).
It includes a combined bucket sink and hand-rinse basin (janitorial unit) and separate
sink.
The following items are shown on the room layout but are optional:
- small cube lockers.
ADB Group Definitions:
1. Contractor supply and install.
2. Supply by others, contractor install.
3. UoN supply – loose equipment and specialist equipment (chairs, drawer units,
non-fixed medical equipment).
4. NHS IT equipment (nil cost to the project).
5. Dental supply and install.
6. Pharmacy supply and install.
7. UoN IT support and install.
8. UoN supply and install (tacks and blinds; fire extinguishers; UoN signage.
9. UoN F.O.C.
Activity DataBase 01/03/2017
7857 Nottingham Uni Medical Centre7857Project:
Room Environmental Data Y1510-01ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: Y1510-01 Cleaners' room
Room Number: Revision Date: 01/03/2017
Permissible Space Temerature Range(dry bulb) (degC):
TEMPERATURE AND VENTILATION Requirements Notes
18 - 28
Heating Design Temperature (dry bulb)(degC): 18
Minimum Air Changes (AC/hr): 3
Ventilation Type: E
-vePressure Relative to Adjoining Space:
Supply Air: Final Filter Class
Permisiible Relative Humidity Range (%): Uncontrolled
General Notes:
LIGHTINGType Of Control: N
Daytime General Service Illuminance (Lux): 200
Daytime Specific Service Illuminance (Lux):
Nighttime General Service Illuminance (Lux):
Nighttime Specific Service Illuminance (Lux):
Local Task Illuminance (Lux):
Colour Rendering Required: Y
Colour Rendering Required Characteristics (Ra): 22
Unified Glare Rating Limit (UGRL): 80
Emergency Escape Route Lighting Required: In accordance with BS 5266 and Health Technical
MemorandumsY
Standby Lighting Grade - General Lighting: B
Standby Lighting Grade - Local Lighting:
General Notes:
RISKClinical Risk Category:
Non-clinical Business Continuity Risk Category:
General Notes:
Noise Intrusion (dB) 1hr day:
NOISE
Noise Intrusion (dB) 1hr night:
Noise Intrusion (dB) f night:
50
-
-
Maximum Internal Noise from M&E Services (NR): 45 Total noise of MEP services under normal operation across
the range 63Hz to 4kHz inclusive.
Room Sound-insulation Parameters - Privacy:
Room Sound-insulation Parameters - Noise Generation:
Not Private
Typical
Reference to Table 3 of the Department of Health 'Acoustics:
Technical design manual 4032:0.6:England'.
Noise Sensitiviy: Not Sensitive
Sound-insulation Rating (dB D nT,w):
General Notes:
Maximum Surface Temperature (DegC):
SAFETY/FIRE
82
Domestic Hot Water Discharge Temperature (DegC): 41/>55
Maximum Cold Water Discharge Temperature (DegC): <20
General Notes:
Type of Automatic Fire Detection: Heat
General Notes:
Activity DataBase 01/03/2017
ADB Room Design Character Y1510-01
Project: 7857 7857 Nottingham Uni Medical Centre
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Cleaners' roomY1510-01Room:
01/03/2017Revision Date:Room Number:
Walls: Wall finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Wall finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Floor: Floor finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Floor finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Ceiling: Ceiling finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Ceiling finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Doorsets: Configuration, glazing, fire rating, security, etc. to be determined by Project Team.
HTM 58 (Mar-2005)
Refer to HBN 00-04 (May-2007) for effective clear door widths.
1 doorset:
1 x personnel & equipment access (1500mm)
Windows: Not required
Internal Glazing: Not required
Hatch: Not required
Notes: All finishes selected must have an appropriate risk assessment to accompany the design
decision.
Infection Control must be consulted as described in Performance Requirements for Building
Elements Used in Healthcare Facilities 8941:0.6 England.
Activity DataBase 01/03/2017
Schedule of Components by Room
Project: 7857 7857 Nottingham Uni Medical Centre
Y1510-01ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: Y1510-01 Cleaners' room
Room Number: Revision Date: 01/03/2017
Key: (n-old qty) Deletions m-new qty Additions m (n) Quantity changes since audit dateAudit Date: 2-Mar-2017
DescriptionCodeTotalTransNew
GrpAlt. CodeQuantity
1HOOK, single, large, wall mountedHOO02022
1SOCKET outlet, switched, 13 amp, singleOUT00511
1SHELF, 900W 300DSHE21111
1SINK and BASIN combination Janitorial unit, hinged
bucket grating to sink and monobloc mixer tap with
swivel nozzle, stainless steel, 900H 500W 600D.
SIN01311
1SWITCH, lightSWC02511
1TAP, bib, lever, hospital pattern, pair hot and cold,
1/2 in.
TAP80911
1WASTE, unslotted flush-grated, metal, 1.1/4 in. .WAS10011
1WASTE, unslotted flush-grated, metal, 1.1/2 in.WAS10222
1TRAP, bottle, 1.1/4 in, plastic resealing.WAS10711
1TRAP, bottle, 1.1/2 in, plastic resealing.WAS10811
2DISPENSER, paper towel, wall mountedDIS01311
2DISPENSER, soap, disposable single cartridge, lever
action, wall mounted
DIS03011
3HOLDER, sack, with lid foot operated, large, capacity
120 litre, mobile
HOL01411
8TRACK, blinds for windowsTRA90011
Activity DataBase 01/03/2017
Y1510-02Room Data SheetADB
Project: 7857 7857 Nottingham Uni Medical Centre
Department: PRI Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
Room: Y1510-02 Cleaners' room
Room Number: Revision Date: 01/03/2017
1) Disposal of liquid waste.
2) Filling and emptying cleaning equipment and containers.
3) Holding/storing cleaning equipment.
4) Cleaning equipment may be parked and/or stored.
5) Hand-rinse basin may be used.
6) Sink may be used.
7) Janitorial unit may be used.
Activities:
Personnel: 2 x staff.
Intermittent use.
Planning
Relationships:
Close to areas served.
Space Data: Height (mm): 8.00 2,400Area (m²):
If large equipment is stored elsewhere, the size of this room can be reduced.
Notes: This room represents a typical traditional cleaners' room with space for storing a vacuum
cleaner, scrubbing/polishing machine (for hard floors) and mop and bucket (stored on
the cleaners' trolley).
It includes a combined bucket sink and hand-rinse basin (janitorial unit) and separate
sink.
The following items are shown on the room layout but are optional:
- small cube lockers.
ADB Group Definitions:
1. Contractor supply and install.
2. Supply by others, contractor install.
3. UoN supply – loose equipment and specialist equipment (chairs, drawer units,
non-fixed medical equipment).
4. NHS IT equipment (nil cost to the project).
5. Dental supply and install.
6. Pharmacy supply and install.
7. UoN IT support and install.
8. UoN supply and install (tacks and blinds; fire extinguishers; UoN signage.
9. UoN F.O.C.
Activity DataBase 01/03/2017
7857 Nottingham Uni Medical Centre7857Project:
Room Environmental Data Y1510-02ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: Y1510-02 Cleaners' room
Room Number: Revision Date: 01/03/2017
Permissible Space Temerature Range(dry bulb) (degC):
TEMPERATURE AND VENTILATION Requirements Notes
18 - 28
Heating Design Temperature (dry bulb)(degC): 18
Minimum Air Changes (AC/hr): 3
Ventilation Type: E
-vePressure Relative to Adjoining Space:
Supply Air: Final Filter Class
Permisiible Relative Humidity Range (%): Uncontrolled
General Notes:
LIGHTINGType Of Control: N
Daytime General Service Illuminance (Lux): 200
Daytime Specific Service Illuminance (Lux):
Nighttime General Service Illuminance (Lux):
Nighttime Specific Service Illuminance (Lux):
Local Task Illuminance (Lux):
Colour Rendering Required: Y
Colour Rendering Required Characteristics (Ra): 22
Unified Glare Rating Limit (UGRL): 80
Emergency Escape Route Lighting Required: In accordance with BS 5266 and Health Technical
MemorandumsY
Standby Lighting Grade - General Lighting: B
Standby Lighting Grade - Local Lighting:
General Notes:
RISKClinical Risk Category:
Non-clinical Business Continuity Risk Category:
General Notes:
Noise Intrusion (dB) 1hr day:
NOISE
Noise Intrusion (dB) 1hr night:
Noise Intrusion (dB) f night:
50
-
-
Maximum Internal Noise from M&E Services (NR): 45 Total noise of MEP services under normal operation across
the range 63Hz to 4kHz inclusive.
Room Sound-insulation Parameters - Privacy:
Room Sound-insulation Parameters - Noise Generation:
Not Private
Typical
Reference to Table 3 of the Department of Health 'Acoustics:
Technical design manual 4032:0.6:England'.
Noise Sensitiviy: Not Sensitive
Sound-insulation Rating (dB D nT,w):
General Notes:
Maximum Surface Temperature (DegC):
SAFETY/FIRE
82
Domestic Hot Water Discharge Temperature (DegC): 41/>55
Maximum Cold Water Discharge Temperature (DegC): <20
General Notes:
Type of Automatic Fire Detection: Heat
General Notes:
Activity DataBase 01/03/2017
ADB Room Design Character Y1510-02
Project: 7857 7857 Nottingham Uni Medical Centre
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Cleaners' roomY1510-02Room:
01/03/2017Revision Date:Room Number:
Walls: Wall finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Wall finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Floor: Floor finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Floor finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Ceiling: Ceiling finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Ceiling finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Doorsets: Configuration, glazing, fire rating, security, etc. to be determined by Project Team.
HTM 58 (Mar-2005)
Refer to HBN 00-04 (May-2007) for effective clear door widths.
1 doorset:
1 x personnel & equipment access (1500mm)
Windows: Not required
Internal Glazing: Not required
Hatch: Not required
Notes: All finishes selected must have an appropriate risk assessment to accompany the design
decision.
Infection Control must be consulted as described in Performance Requirements for Building
Elements Used in Healthcare Facilities 8941:0.6 England.
Activity DataBase 01/03/2017
Schedule of Components by Room
Project: 7857 7857 Nottingham Uni Medical Centre
Y1510-02ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: Y1510-02 Cleaners' room
Room Number: Revision Date: 01/03/2017
Key: (n-old qty) Deletions m-new qty Additions m (n) Quantity changes since audit dateAudit Date: 2-Mar-2017
DescriptionCodeTotalTransNew
GrpAlt. CodeQuantity
1CLIP, spring, 32mm dia. 3, mounted on a wooden
batten, wall mounted
CLI01711
1HOOK, single, large, wall mountedHOO02022
1SOCKET outlet, switched, 13 amp, singleOUT00511
1SHELF, 1500W 300DSHE23111
1SINK and BASIN combination Janitorial unit, hinged
bucket grating to sink and monobloc mixer tap with
swivel nozzle, stainless steel, 900H 500W 600D.
SIN01311
1SWITCH, lightSWC02511
1WASTE, unslotted flush-grated, metal, 1.1/4 in. .WAS10011
1WASTE, unslotted flush-grated, metal, 1.1/2 in.WAS10222
1TRAP, bottle, 1.1/4 in, plastic resealing.WAS10711
1TRAP, bottle, 1.1/2 in, plastic resealing.WAS10811
2DISPENSER, paper towel, wall mountedDIS01311
2DISPENSER, soap, disposable single cartridge, lever
action, wall mounted
DIS03011
3HOLDER, sack, with lid foot operated, large, capacity
120 litre, mobile
HOL01411
3LADDER, 3 tread, platform type 750mm height,
folding
LAD00211
Activity DataBase 01/03/2017
Y1510-03Room Data SheetADB
Project: 7857 7857 Nottingham Uni Medical Centre
Department: PRI Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
Room: Y1510-03 Cleaners' room
Room Number: Revision Date: 01/03/2017
1) Disposal of liquid waste.
2) Filling and emptying cleaning equipment and containers.
3) Holding/storing cleaning equipment.
4) Cleaning equipment may be parked and/or stored.
5) Hand-rinse basin may be used.
6) Sink may be used.
7) Janitorial unit may be used.
Activities:
Personnel: 2 x staff.
Intermittent use.
Planning
Relationships:
Close to areas served.
Space Data: Height (mm): 8.00 2,400Area (m²):
If large equipment is stored elsewhere, the size of this room can be reduced.
Notes: This room represents a typical traditional cleaners' room with space for storing a vacuum
cleaner, scrubbing/polishing machine (for hard floors) and mop and bucket (stored on
the cleaners' trolley).
It includes a combined bucket sink and hand-rinse basin (janitorial unit) and separate
sink.
The following items are shown on the room layout but are optional:
- small cube lockers.
ADB Group Definitions:
1. Contractor supply and install.
2. Supply by others, contractor install.
3. UoN supply – loose equipment and specialist equipment (chairs, drawer units,
non-fixed medical equipment).
4. NHS IT equipment (nil cost to the project).
5. Dental supply and install.
6. Pharmacy supply and install.
7. UoN IT support and install.
8. UoN supply and install (tacks and blinds; fire extinguishers; UoN signage.
9. UoN F.O.C.
Activity DataBase 01/03/2017
7857 Nottingham Uni Medical Centre7857Project:
Room Environmental Data Y1510-03ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: Y1510-03 Cleaners' room
Room Number: Revision Date: 01/03/2017
Permissible Space Temerature Range(dry bulb) (degC):
TEMPERATURE AND VENTILATION Requirements Notes
18 - 28
Heating Design Temperature (dry bulb)(degC): 18
Minimum Air Changes (AC/hr): 3
Ventilation Type: E
-vePressure Relative to Adjoining Space:
Supply Air: Final Filter Class
Permisiible Relative Humidity Range (%): Uncontrolled
General Notes:
LIGHTINGType Of Control: N
Daytime General Service Illuminance (Lux): 200
Daytime Specific Service Illuminance (Lux):
Nighttime General Service Illuminance (Lux):
Nighttime Specific Service Illuminance (Lux):
Local Task Illuminance (Lux):
Colour Rendering Required: Y
Colour Rendering Required Characteristics (Ra): 22
Unified Glare Rating Limit (UGRL): 80
Emergency Escape Route Lighting Required: In accordance with BS 5266 and Health Technical
MemorandumsY
Standby Lighting Grade - General Lighting: B
Standby Lighting Grade - Local Lighting:
General Notes:
RISKClinical Risk Category:
Non-clinical Business Continuity Risk Category:
General Notes:
Noise Intrusion (dB) 1hr day:
NOISE
Noise Intrusion (dB) 1hr night:
Noise Intrusion (dB) f night:
50
-
-
Maximum Internal Noise from M&E Services (NR): 45 Total noise of MEP services under normal operation across
the range 63Hz to 4kHz inclusive.
Room Sound-insulation Parameters - Privacy:
Room Sound-insulation Parameters - Noise Generation:
Not Private
Typical
Reference to Table 3 of the Department of Health 'Acoustics:
Technical design manual 4032:0.6:England'.
Noise Sensitiviy: Not Sensitive
Sound-insulation Rating (dB D nT,w):
General Notes:
Maximum Surface Temperature (DegC):
SAFETY/FIRE
82
Domestic Hot Water Discharge Temperature (DegC): 41/>55
Maximum Cold Water Discharge Temperature (DegC): <20
General Notes:
Type of Automatic Fire Detection: Heat
General Notes:
Activity DataBase 01/03/2017
ADB Room Design Character Y1510-03
Project: 7857 7857 Nottingham Uni Medical Centre
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Cleaners' roomY1510-03Room:
01/03/2017Revision Date:Room Number:
Walls: Wall finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Wall finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Floor: Floor finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Floor finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Ceiling: Ceiling finishes to comply with Performance Requirements for Building Elements Used in
Healthcare Facilities 8941:0.6 England.
Ceiling finishes to be selected using the "Selection Procedure for Finishes" included in 8941:06:
England.
Doorsets: Configuration, glazing, fire rating, security, etc. to be determined by Project Team.
HTM 58 (Mar-2005)
Refer to HBN 00-04 (May-2007) for effective clear door widths.
1 doorset:
1 x personnel & equipment access (1500mm)
Windows: Not required
Internal Glazing: Not required
Hatch: Not required
Notes: All finishes selected must have an appropriate risk assessment to accompany the design
decision.
Infection Control must be consulted as described in Performance Requirements for Building
Elements Used in Healthcare Facilities 8941:0.6 England.
Activity DataBase 01/03/2017
Schedule of Components by Room
Project: 7857 7857 Nottingham Uni Medical Centre
Y1510-03ADB
Facilities for Primary and Community Care Design Guidance 1183: England -
list of rooms
PRIDepartment:
Room: Y1510-03 Cleaners' room
Room Number: Revision Date: 01/03/2017
Key: (n-old qty) Deletions m-new qty Additions m (n) Quantity changes since audit dateAudit Date: 2-Mar-2017
DescriptionCodeTotalTransNew
GrpAlt. CodeQuantity
1SOCKET outlet, switched, 13 amp, singleOUT00511
1SHELF, 1500W 300DSHE23122
1SINK and BASIN combination Janitorial unit, hinged
bucket grating to sink and monobloc mixer tap with
swivel nozzle, stainless steel, 900H 500W 600D.
SIN01311
1SWITCH, lightSWC02511
1WASTE, unslotted flush-grated, metal, 1.1/4 in. .WAS10011
1WASTE, unslotted flush-grated, metal, 1.1/2 in.WAS10222
1TRAP, bottle, 1.1/4 in, plastic resealing.WAS10711
1TRAP, bottle, 1.1/2 in, plastic resealing.WAS10811
3HOLDER, sack, with lid foot operated, large, capacity
120 litre, mobile
HOL01411
3Floor Standing LOCKER , single, 1800H 300W 550DLOC10522