HIGH DENSITY EQUIPMENT PANEL (HDEP) ORDERING GUIDE

24-Fiber MPO System10/40/100 GbE Migration Solution

Page 2: 24-Fiber MPO System · 10 Gigabit Interconnect Introduction The 10 Gigabit Interconnect solution, like all of the planned migration designs, begins with a 24-fiber optical trunk with

Table of Contents

HDEP System Overview 3

HDEP 24-Fiber Interconnect System10 Gigabit Interconnect

Introduction ............................................................................................................................ 42-Fiber LC- A-B Patch Cord ........................................................................................................ 41x24 Fiber MPO to 12 x duplex LC Module, Straight A-A/B-B ........................................................ 4MPO Trunk, Polarity A .............................................................................................................. 41x24 Fiber MPO to 12 x duplex LC Module, Flipped A B/B-A ........................................................ 41 and 4 RU Chassis (not shown in system diagram) ....................................................................... 4Ordering Information ................................................................................................................ 5Specifications ......................................................................................................................... 5

HD 10 Gigabit Interconnect

8-Fiber HD Array ..................................................................................................................... 62x6 MPO Module .................................................................................................................. 6MPO Trunk, Polarity A .............................................................................................................. 640G MPO Patch Cord, Polarity A .............................................................................................. 61 and 4 RU Chassis (not shown in system diagram) ....................................................................... 6Ordering Information ................................................................................................................ 7Specifications ......................................................................................................................... 7

40 Gigabit Interconnect

1x3 MPO Array ..................................................................................................................... 8MPO Module ......................................................................................................................... 8MPO Trunk, Polarity A .............................................................................................................. 81 and 4 RU Chassis (not shown in system diagram) ....................................................................... 8Ordering Information ................................................................................................................ 9Specifications ......................................................................................................................... 9

100 Gigabit Interconnect

Introduction .......................................................................................................................... 10MPO Patch Cord, Polarity A .................................................................................................... 10MPO Module ....................................................................................................................... 10MPO Patch Cord, Polarity B .................................................................................................... 101 and 4 RU Chassis (not shown in system diagram) ..................................................................... 10Ordering Information .............................................................................................................. 11Specifications ....................................................................................................................... 11

Page 3: 24-Fiber MPO System · 10 Gigabit Interconnect Introduction The 10 Gigabit Interconnect solution, like all of the planned migration designs, begins with a 24-fiber optical trunk with

HDEP Cross-Connect System10 Gigabit Cross-Connect

Introduction .......................................................................................................................... 122-Fiber LC A-B-Patch Cord ....................................................................................................... 121x24 Fiber MPO to 12 x duplex LC Module, Straight A-A/B-B ...................................................... 12MPO Trunk, Polarity A ............................................................................................................ 121x24 Fiber MPO to 12 x duplex LC Module, Flipped A-B/B-A ...................................................... 121 and 4 RU Chassis (not shown in system diagram) ..................................................................... 12Ordering Information .............................................................................................................. 13Specifications ....................................................................................................................... 13

HD 10/40 Gigabit Cross-Connect

Introduction .......................................................................................................................... 148-Fiber HD Array ................................................................................................................... 142x6 MPO Module ................................................................................................................. 14MPO Trunk, Polarity A ............................................................................................................ 1440G MPO Patch Cord, Polarity B ............................................................................................ 1440G MPO Patch Cord, Polarity A ............................................................................................ 141 and 4 RU Chassis (not shown in system diagram) ..................................................................... 14Ordering Information .............................................................................................................. 15Specifications ....................................................................................................................... 15

40 Gigabit Cross-Connect

Introduction .......................................................................................................................... 1640G MPO Patch Cord, Polarity A ............................................................................................ 162x6 MPO Module ................................................................................................................. 16MPO Trunk, Polarity A ......................................................................................................... 1640G MPO Patch Cord, Polarity B ............................................................................................ 161 and 4 RU Chassis (not shown in system diagram) ..................................................................... 16Ordering Information .............................................................................................................. 17Specifications ....................................................................................................................... 17

100 Gigabit Cross-Connect

Introduction .......................................................................................................................... 18MPO Patch Cord, Polarity A .................................................................................................... 18MPO Module ....................................................................................................................... 18MPO Trunk, Polarity A ............................................................................................................ 18MPO Patch Cord, Polarity B .................................................................................................... 181 and 4 RU Chassis (not shown in system diagram) ..................................................................... 18Ordering Information .............................................................................................................. 19Specifications ....................................................................................................................... 19

Page 4: 24-Fiber MPO System · 10 Gigabit Interconnect Introduction The 10 Gigabit Interconnect solution, like all of the planned migration designs, begins with a 24-fiber optical trunk with

For more information, visit commscope.com

High Density Equipment Panel System Overview

3

24-Fiber Trunking SolutionsBandwidth and storage demand is expanding at a breathtaking rate. The environment is rapidly evolving. The impact on data center design and management is profound. Networks will migrate from 10 to 40 to 100 Gigabit/second Ethernet speeds dynamically, and data center managers and designers need to be able to manage this migration to maximize efficiency and responsiveness while minimizing cost.

This dynamic migration demands a simple yet robust migration pathway, and successful migration starts with a simple yet robust plan. This guide presents just such a concise and manageable plan to allow migration of infrastructure, whether it be core switching, aggregation, end of row, top of rack or hybrid network architectures.

Centered around 24-fiber trunks and optical connectivity, this roadmap provides the following advantages:

• A single trunking format that can be replicated and upgraded simply and flexibly

• Unified solutions for 10, 40 and 100 GbE applications

• Pre-engineered paths and polarity

• Higher fiber utilization versus 12-fiber systems

• Fewer trunks

• Fewer connections

• Fewer components

• Standardized practices for design, installation, documentation and troubleshooting

• Component and trunk re-use

• Minimized waste of space, time and money

The following pages provide this plan--designs and products for each step of your network’s evolution to 100 GbE, allowing your data center strategy to become a dynamic business advantage.

40Gor 100G*

100G† 100G†

*100G implemented as 4x25G †100G implemented as 10x10G

10G

40Gor 100G*

10G

Page 5: 24-Fiber MPO System · 10 Gigabit Interconnect Introduction The 10 Gigabit Interconnect solution, like all of the planned migration designs, begins with a 24-fiber optical trunk with

For more information, visit commscope.com4

High Density Equipment Panel 10 Gigabit Interconnect

Introduction

The 10 Gigabit Interconnect solution, like all of the planned migration designs, begins with a 24-fiber optical trunk with a single, two-row MPO-type connector at each end. Trunks interface with the rear of a 1 or 4 rack unit (RU) high HDEP chassis, which contains up to six 24-fiber MPO to LC modules per RU. These 24-fiber modules break out the trunk fibers into 12 duplex LC connections at the front of each module, supporting 144-fibers per RU.

Modules reside in a multi-featured HDEP chassis which provides superior cable management for both the MPOs at the rear and LC cords at the front. HDEP chassis are stackable and available in 1 and 4 RU versions in both unmanaged and managed formats. They can be populated all at once, or added to or upgraded a module at a time in the future. The HDEP chassis also supports high density 10 Gigabit modules, as well as 40 and 100 GbE versions, allowing an upgrade path by changing the module at the front and employing existing and additional 24-fiber trunks at the rear.

Fiber Module 24-Fiber Trunk

1 RU Chassis

11

24-Fiber MPO Trunk A-Polarity (Type A)

MPO MPO

LC-Duplex A-B Patch Cord

LC-Duplex A-B Patch Cord

LC-Duplex LC-Duplex

2 4

3

24-Fiber MPO-LC Modules

24-Fiber MPO-LC Modules

4 RU Chassis

Page 6: 24-Fiber MPO System · 10 Gigabit Interconnect Introduction The 10 Gigabit Interconnect solution, like all of the planned migration designs, begins with a 24-fiber optical trunk with

For more information, visit commscope.com5

High Density Equipment Panel 10 Gigabit Interconnect

Specifications

MPOptimate Performance: Factory assembled and tested, 0.35 dB maximum insertion loss per module

Traceable: Each module is uniquely identified and linked to factory measurement data

Standard Fiber Path: Compatible with TIA 568-C.0-2 draft standard for polarity method “A”

24-Fiber Trunk: Fiber path supports 24-fiber deployment

Pinned Module: MPO alignment pins are maintained inside the module, reducing risk of damage during installation and use

Module used in Pairs: Provides proper fiber map, polarity and location of MPO alignment pins

Flexible: Chassis enables superior cable management and can be stacked in standard 19-inch racks or cabinets

Ordering Information

Number Component Part Number

1 2-Fiber LC A-B Patch Cord FPCTB-MDLC-D-xM

2Unmanaged Module, LC-MPO Aqua, 24 fibers (1x24F MPO rear port), straight fiber path, Optimate performance

N5MP-24DLMR4AP (Right)

N5MP-24DLML4AP (Left)

3 24-Fiber Trunk, Polarity A OM4 MPT-2C2CM40xxxF-FF

4Unmanaged Module, LC-MPO Aqua, 24 fibers (1x24F MPO rear port), flipped fiber path, Optimate performance

N5MP-24DLMR4BP (Right)

N5MP-24DLML4AP (Left)

N/S Chassis 1 RU N5CHU-1RU

N/S Chassis 4 RU N5CHU-4RU

Note: x or xxx denotes length F = feet or M = meters and may be changed accordingly based on ordering preference

10 Gigabit LC-MPO Solution

Page 7: 24-Fiber MPO System · 10 Gigabit Interconnect Introduction The 10 Gigabit Interconnect solution, like all of the planned migration designs, begins with a 24-fiber optical trunk with

For more information, visit commscope.com6

High Density Equipment Panel High Density 10 Gigabit Interconnect

Introduction

HDEP High Density 10 Gigabit Fiber modules also utilize 24-fiber MPO trunks and support interconnection from 40 Gigabit switch ports that have been remotely enabled as four 10 Gigabit independent paths. QSFP ports on the switch interface via a 1x3 MPO array to a 24 fiber trunk. This trunk connects to a 24 fiber (12 duplex LC) array at the other end, physically dividing the 10 gigabit paths to individual ports which provide LC connectivity.

This component set maintains fiber paths and polarity, and provide proper fiber mapping from transmit at one end to receive at the other over a total of twelve 10 Gigabit paths. All modules are compatible with HDEP chassis, frames and hardware, and feature a highly engineered, and highly effective, cable management system. Chassis are stackable and available in managed and unmanaged versions, supporting 144 fibers per RU in a usable cabling system.

24-Fiber High Density Array

1x3 MPO Array 24-Fiber Trunk

4 RU Chassis1 RU Chassis

24-Fiber MPO Trunk A-Polarity (Type A)

40G array 3 single row MPO to one

dual row 24 fiber MPO.

3

22

1 4

MPO MPO

MPO MPO

Fiber Module

8-Way MPO Adaptor Module

8-Way MPO Adaptor Module

Page 8: 24-Fiber MPO System · 10 Gigabit Interconnect Introduction The 10 Gigabit Interconnect solution, like all of the planned migration designs, begins with a 24-fiber optical trunk with

For more information, visit commscope.com7

High Density Equipment Panel High Density 10 Gigabit Interconnect

Specifications

MPOptimate Performance: Factory measured maximum 0.35 dB insertion loss per module (LC-MPO) or 0.5 dB (MPO-MPO)

Traceable: Each module is uniquely identified and linked to factory measurement data

Standard Fiber Path: Compatible with TIA 568-C.0-2 draft standard for polarity method “A” trunks for 40 GbE

24-Fiber Trunk: Fiber path supports dual-fiber 10 Gigabit deployment via 40 Gigabit equipment connections (4x10Gbit paths per QSFP port)

Pinned Module: MPO alignment pins are maintained inside the module, reducing risk of damage

Module used in Pairs: Provides proper fiber map, polarity and location of MPO alignment pins

Flexible: Chassis enables superior cable management regardless of module type

Ordering Information

Number Component Part Number

1 1x3 MPO array MPG-1CNC240xxxF-NC

2HDEP Unmanaged Adapter Pack, MPO-MPO Aqua, (8x24F MPO ports)

N5AP-192MPOMMS

3 24-Fiber Trunk, Polarity A OM4 MPT-2C2CM40xxxF-FF

4 Array; one 24 fiber MPO to 12 duplex LC, OM4 MPL-1CLC240xxxF-NC

N/S Chassis 1 RU N5CHU-1RU

N/S Chassis 4 RU N5CHU-4RU

Note: x or xxx denotes length F = Feet and M = Meters and may be changed accordingly based on ordering preference

HD 10 Gigabit MPO-MPO Module

Page 9: 24-Fiber MPO System · 10 Gigabit Interconnect Introduction The 10 Gigabit Interconnect solution, like all of the planned migration designs, begins with a 24-fiber optical trunk with

For more information, visit commscope.com8

High Density Equipment Panel 40 Gigabit Interconnect

Introduction

For 40 GbE applications, HDEP 40 Gigabit modules provide connection from standard 24-fiber MPO trunks with 24-fiber dual row connectors to three single row 8-fiber MPO connectors via breakout array assemblies. Each trunk supports three 8-Fiber 40 Gigabit links, utilizing all 24 fibers of the trunk without abandoning any fibers in the trunk. Each module supports distribution of twenty-four 40 Gigabit Ethernet links. When used with pairs of arrays they provide proper fiber mapping and polarity from transmit at one end of the link to receive at the other.

Modules are compatible with HDEP chassis, frames and hardware, which feature a simple, yet highly engineered cable management system. Chassis support six modules per rack unit (1 RU) or 48 total 40 Gigabit connections per RU.

24-Fiber MPO Trunk A-Polarity (Type A)

1x3 MPO Array

3

22

1 1

24-Fiber Trunk1x3 MPO Array

1x3 MPO Array

MPO MPO

MPO MPO

4 RU Chassis1 RU Chassis

Fiber Module

8-Way MPO Adaptor Module

8-Way MPO Adaptor Module

Page 10: 24-Fiber MPO System · 10 Gigabit Interconnect Introduction The 10 Gigabit Interconnect solution, like all of the planned migration designs, begins with a 24-fiber optical trunk with

For more information, visit commscope.com9

High Density Equipment Panel 40 Gigabit Interconnect

Specifications

MPOptimate Performance: Compatible with MPOptimate trunks and patch cords. Maximum connection insertion loss 0.25dB for 24 fiber MPO

Standard Fiber Path: Compatible with TIA 568-C.0-2 draft standard for polarity method “A" trunks

24-Fiber Trunk: Fiber path supports 24-fiber deployment and 40 gigabit equipment connections. Each 24-fiber trunk supports three 8-fiber pathways without abandoning any trunk fibers

Module used in Pairs: Provides proper fiber map, polarity and location of MPO alignment pins

Flexible: System supports use of arrays or module and patch cords at either end of the trunk

Management capable: Managed modules and assemblies are available. Please contact CommScope for details

Note: Some proposed 100G transmission formats that employ 4X25G lanes employ this configuration

40 Gigabit MPO-MPO Module

Number Component Part Number

1 1x3 MPO Array MPG-1CNC240xxxF-NC

2Unmanaged Adapter Pack, MPO-MPO Aqua, 192 fibers (8, 24F MPO ports)

N5AP-192MPOMMS

3 24-Fiber Trunk, Polarity A OM4 MPT-2C2CM40xxxF-FF

N/S Chassis 1 RU N5CHU-1RU

N/S Chassis 4 RU N5CHU-4RU

Note: x or xxx denotes length F = Feet and M = Meters and may be changed accordingly based on ordering preference

Ordering Information

Page 11: 24-Fiber MPO System · 10 Gigabit Interconnect Introduction The 10 Gigabit Interconnect solution, like all of the planned migration designs, begins with a 24-fiber optical trunk with

For more information, visit commscope.com10

High Density Equipment Panel 100 Gigabit Interconnect

Introduction

HDEP 100 Gigabit fiber modules provide connection from eight MPO trunks with 24-fiber dual-row connectors to eight 24-fiber MPO equipment or patch cords. Each module supports distribution of eight 100 gigabit Ethernet links when configured in a 10X10G transmission format.

When used in pairs with 24-fiber MPO patch cord pairs they provide proper fiber mapping from transmit at one end to receive at the other of the link.

Modules are compatible with HDEP chassis, frames and hardware, and feature a simple, yet highly engineered, cable management system. Modules snap easily into existing or newly installed HDEP chassis support six modules per rack unit (1RU) or a total of 48 MPO connections per RU. Each module is fully assembled at the factory and can reside in a chassis with 10, High Density 10, 40, and 100 GbE modules. Chassis are available in 1 and 4 rack unit (RU) versions.

24-fiber MPO Patch Cord

A-Polarity (Type A)

24-fiber MPO Patch Cord B-Polarity (Type B)

1 4

24 Fiber Trunk

24-Fiber MPO Trunk A-Polarity (Type A)3

MPO MPO

4 RU Chassis1 RU Chassis

22

MPO MPO

Fiber Module

8-Way MPO Adaptor Module

8-Way MPO Adaptor Module

Page 12: 24-Fiber MPO System · 10 Gigabit Interconnect Introduction The 10 Gigabit Interconnect solution, like all of the planned migration designs, begins with a 24-fiber optical trunk with

For more information, visit commscope.com11

High Density Equipment Panel 100 Gigabit Interconnect

100 Gigabit MPO to MPO Modules

Ordering Information

Number Component Part Number

1 24-fiber MPO Patch Cord, Polarity A (Type A) MPT-1C2C240xxxF-NN

2Unmanaged Adapter Pack, MPO-MPO Aqua, 192 fibers (8, 24F MPO ports)

N5AP-192MPOMMS

3 24-Fiber Trunk, Polarity A OM4 MPT-2C2CM40xxxF-FF

4 24-Fiber MPO Patch Cord, Polarity B (Type B) MPF-1C2C240xxxF-NN

N/S Chassis 1 RU N5CHU-1RU

N/S Chassis 4 RU N5CHU-4RU

Note: x or xxx denotes length F = Feet and M = Meters and may be changed accordingly based on ordering preference

Specifications

MPOptimate Performance: Compatible with MPOptimate trunks and arrays

Standard Fiber Path: Compatible with TIA 568-C.0-2 draft standard for polarity method “A" trunks

24-Fiber Trunk: Up to eight 24-fiber MPO trunks per module

Patch Cords used in Pairs: Provides proper fiber map, polarity and location of MPO alignment pins

Page 13: 24-Fiber MPO System · 10 Gigabit Interconnect Introduction The 10 Gigabit Interconnect solution, like all of the planned migration designs, begins with a 24-fiber optical trunk with

For more information, visit commscope.com12

High Density Equipment Panel 10 Gigabit Cross-Connect

Introduction

The 10 Gigabit Cross-Connect Solution, like all of the planned migration designs, begins with a 24-fiber optical trunk with a single MPO-type connector at each end. A trunk interface with the rear of an HDEP module that breaks out the trunk fibers into twelve duplex LC connections (24 fibers) at the front. This module resides in a highly efficient HDEP chassis which provides superior cable management for both the MPOs at the rear and LC patch cords at the front. HDEP chassis are stackable and available in 1 and 4 RU versions. Either chassis supports 72 duplex LCs (144 fibers) per rack unit (1RU).

Chassis can be populated all at once, or added to or upgraded a module at a time in the future. The HDEP chassis also supports High Density 10 Gigabit modules, as well as 40 and 100 GbE versions, allowing an upgrade path by changing only the components at the front and using existing and additional 24-fiber trunks at the rear.

Chassis can be cascaded to form a half or full cross-connect layout. Cross-Connection can be implemented via LCs to maintain single channel flexibility. (Note: Some cross-connect architectures are treated as engineered links, and available power budget must be verified.)

24-Fiber Trunk

LC Duplex A-B Patch CordLC Duplex

A-B Patch CordLC Duplex

A-B Patch Cord

2 2

1 11

4 4

24-Fiber MPO Trunk A-Polarity (Type A) 24-Fiber MPO Trunk A-Polarity (Type A)

MPO

LC Duplex LC Duplex

MPO

3 3

4 RU Chassis1 RU Chassis

24-Fiber MPO-LC Modules

24-Fiber MPO-LC Modules

24-Fiber MPO-LC Modules

24-Fiber MPO-LC Modules

NEED IMAGE

Fiber Module

Page 14: 24-Fiber MPO System · 10 Gigabit Interconnect Introduction The 10 Gigabit Interconnect solution, like all of the planned migration designs, begins with a 24-fiber optical trunk with

For more information, visit commscope.com13

High Density Equipment Panel 10 Gigabit Cross-Connect

Specifications

MPOptimate Performance: Factory measured maximum measured 0.35 dB insertion loss per module

Traceable: Each module is uniquely identified and linked to factory measurement data

Standard Fiber Path: Compatible with TIA 568-C.0-2 draft standard for polarity method “A”

24-Fiber Trunk: Fiber path supports 24-fiber deployment

Pinned Module: MPO alignment pins are maintained inside the module, reducing risk of damage

Module used in Pairs: Provides proper fiber map, polarity and location of MPO alignment pins

Flexible: Chassis enables superior cable management and can be stacked in standard 19-inch racks or cabinets

Management capable: Managed modules and assemblies are available. Please contact CommScope for details

Ordering Information

Number Component Part Number

1 2-Fiber LC A-B Patch Cord FPCTB-MDLC-D-xM

2Unmanaged Module, LC-MPO Aqua, 24 fibers (1x24F MPO rear port), straight fiber path, Optimate performance

N5MP-24DLMR4AP (Right)

N5MP-24DLML4AP (Left)

3 24-Fiber Trunk, Polarity A OM4 MPT-2C2CM40xxxF-FF

4Unmanaged Module, LC-MPO Aqua, 24 fibers (1x24F MPO rear port), flipped fiber path, Optimate performance

N5MP-24DLMR4BP (Right)

N5MP-24DLML4AP (Left)

N/S Chassis 1 RU N5CHU-1RU

N/S Chassis 4 RU N5CHU-4RU

Note: x or xxx denotes length F = feet or M = meters and may be changed accordingly based on ordering preference

10 Gigabit LC-MPO Solution

Page 15: 24-Fiber MPO System · 10 Gigabit Interconnect Introduction The 10 Gigabit Interconnect solution, like all of the planned migration designs, begins with a 24-fiber optical trunk with

For more information, visit commscope.com14

High Density Equipment Panel HD 10/40 Gigabit Cross-Connect

Introduction

HDEP High Density 10 Gigabit Fiber Modules also utilize 24-fiber MPO trunks and support connection from 40 Gigabit switch ports that have been remotely enabled as four 10 Gigabit independent paths. MPO-based QSFP ports at the switch interface with an array at one end of the trunk, and a break-out array divides these signals into duplex LC pairs at the other end.

Chassis and modules can be cascaded to form half or full Cross-Connect architectures. Cross-Connection can be implemented via LCs to maintain single channel flexibility. (Note: Some Cross-Connect architectures are treated as engineered links, and available power budget must be verified.)

MPO modules have eight MPO ports that support trunks and patchcords with MPOptimate performance levels. Each module supports distribution of eight 40 Gigabit Ethernet paths, each containing four duplex 10 Gigabit links. When deployed according to recommendations in this design guide, the system maintains fiber paths and polarity and provides proper fiber mapping from transmit at one end to receive at the other - over a total of twenty-four 10 Gigabit paths per module. All modules are compatible with HDEP chassis, frames and hardware, and feature a simple, yet highly effective, cable management system. Modules are 1/3 RU high, can snap easily into existing or newly installed HDEP chassis, and can be replaced by 40 and 100 GbE module in the future.

4 RU Chassis1 RU Chassis

24-Fiber Trunk

3 3

4

24-Fiber MPO Patch Cord B-Polarity (Type B)

24-Fiber MPO Trunk A-Polarity (Type A)

24-Fiber MPO Trunk A-Polarity (Type A)

40G array 3 single row MPO to one dual row 24 fiber MPO.

2 2

1

MPO MPO

MPO MPO

8-Way MPO Adaptor Module

8-Way MPO Adaptor Module

8-Way MPO Adaptor Module

8-Way MPO Adaptor Module

Fiber Module

24-Fiber High Density Array

5

1x3 MPO Array

Page 16: 24-Fiber MPO System · 10 Gigabit Interconnect Introduction The 10 Gigabit Interconnect solution, like all of the planned migration designs, begins with a 24-fiber optical trunk with

For more information, visit commscope.com15

High Density Equipment Panel HD 10/40 Gigabit Cross-Connect

HD 10/40 Gigabit LC-MPO Cross-Connect Module

Number Component Part Number

1 1x3 MPO Array MPG-1CNC240xxxF-NC

2 HDEP Unmanaged Adapter Pack, MPO-MPO Aqua, (8x24F MPO ports) N5AP-192MPOMMS

3 24-Fiber Trunk, Polarity A OM4 MPT-2C2CM40xxxF-FF

4 24-Fiber MPO Patch Cord, Polarity B (Type B) MPF-1C1C240xxxF-NN

5 Array one 24 fiber MPO to 12 duplex LC, OM4 MPL-1CLC240xxxF-NC

N/S Chassis 1 RU N5CHU-1RU

N/S Chassis 4 RU N5CHU-4RU

Note: x or xxx denotes length F = Feet and M = Meters and may be changed accordingly based on ordering preference

Ordering Information

Specifications

MPOptimate Performance: 24 fiber MPOptimate connectors are specified at 0.25dB insertion loss

Standard Fiber Path: Compatible with TIA 568-C.0-2 draft standard for polarity method "A" (for 40 Gigabit Ethernet)

24-Fiber Trunk: Fiber path supports dual-fiber 10 Gigabit deployment via 40 Gigabit equipment connections (4x10Gbit paths per QSFP port)

Flexible: Chassis enables superior cable management and can be stacked in a standard 19-inch rack or cabinet

Modules Used in Pairs: Provides proper fiber map, polarity and location of MPO alignment pins

Management capable: Managed modules and assemblies are available. Please contact CommScope for details

Page 17: 24-Fiber MPO System · 10 Gigabit Interconnect Introduction The 10 Gigabit Interconnect solution, like all of the planned migration designs, begins with a 24-fiber optical trunk with

For more information, visit commscope.com16

High Density Equipment Panel 40 Gigabit Cross-Connect

Introduction

For 40 GbE applications HDEP 40 Gigabit modules provide connection from standard 24-fiber MPO trunks with 24-fiber dual row connectors to three single row 8-fiber MPO connectors via breakout array assemblies. Each trunk supports three 8-Fiber 40 Gigabit links, utilizing all 24 fibers of the trunk without abandoning any fibers in the trunk. Each module supports distribution of twenty-four 40 Gigabit Ethernet links, for up to 144 links per RU.

When used with pairs of arrays they provide proper fiber mapping and polarity from transmit at one end of the link to receive at the other. (Note: Some Cross-Connect architectures are treated as engineered link and available power budget must be verified.)

Modules are compatible with HDEP chassis, frames and hardware, which feature a simple, yet highly engineered cable management system. Chassis support six modules per rack unit (1 RU) or 48 total 40 Gigabit connections per RU.

24-Fiber Trunk

4 RU Chassis1 RU Chassis

3 3

4

24-Fiber MPO Patch Cord B-Polarity (Type A)

24-Fiber MPO Trunk A-Polarity (Type A)

24-Fiber MPO Trunk A-Polarity (Type A)

40G array 3 single row MPO to one dual row 24 fiber MPO.

40G array 3 single row MPO to one dual

row 24 fiber MPO.

2 2

1 1

MPO MPO

MPO MPO

8-Way MPO Adaptor Module

8-Way MPO Adaptor Module

8-Way MPO Adaptor Module

8-Way MPO Adaptor Module

Fiber Module

Page 18: 24-Fiber MPO System · 10 Gigabit Interconnect Introduction The 10 Gigabit Interconnect solution, like all of the planned migration designs, begins with a 24-fiber optical trunk with

For more information, visit commscope.com17

High Density Equipment Panel 40 Gigabit Cross-Connect

40 Gigabit MPO to MPO Cross-Connect Modules

Ordering Information

Number Component Part Number

1 1x3 MPO Array MPG-1CNC240xxxF-NC

2Unmanaged Adapter Pack, MPO-MPO Aqua, 192 fibers (8, 24F MPO ports)

N5AP-192MPOMMS

3 24-Fiber Trunk, Polarity A OM4 MPT-2C2CM40xxxF-FF 

4 24-Fiber MPO Patch Cord, Polarity B (Type B) MPF-1C1C240xxxF-NN

N/S Chassis 1 RU N5CHU-1RU

N/S Chassis 4 RU N5CHU-4RU

Note: x or xxx denotes length F = Feet and M = Meters and may be changed accordingly based on ordering preference

Specifications

MPOptimate Performance: Compatible with MPOptimate trunks and patch cords. Maximum connection insertion loss 0.25dB for 24 fiber MPO

Standard Fiber Path: Compatible with TIA 568-C.0-2 draft standard for polarity method “A" trunks

24-Fiber Trunk: Fiber path supports 24-fiber deployment and 40 gigabit equipment connections. Each 24-fiber trunk supports three 8-fiber pathways without abandoning any trunk fibers

Module used in Pairs: Provides proper fiber map, polarity and location of MPO alignment pins

Flexible: System supports use of modules or module and patch cords at either end of the trunk

Management capable: Managed modules and assemblies are available. Please contact CommScope for details

Note: Some proposed 100G transmission formats that employ 4X25G lanes employ this configuration

Page 19: 24-Fiber MPO System · 10 Gigabit Interconnect Introduction The 10 Gigabit Interconnect solution, like all of the planned migration designs, begins with a 24-fiber optical trunk with

For more information, visit commscope.com18

High Density Equipment Panel 100 Gigabit Cross-Connect

Introduction

HDEP 100 Gigabit fiber modules provide connection from eight MPO trunks with 24-fiber, dual-row connectors to eight 24-fiber MPO equipment or patch cords. Each module supports the distribution of eight 100 Gigabit Ethernet links when configured in a 10X10G transmission format. When used in pairs with 24-fiber MPO patch cord pairs they provide proper fiber mapping from transmit at one end to receive at the other of the link.

Modules can be cascaded to provide half or full cross-connect architectures. (Note: Some Cross-Connect architectures are treated as engineered links, and available power budget must be verified.)

Modules are compatible with HDEP chassis, frames and hardware, and feature a simple, yet highly engineered, cable management system. Chassis are available 1 and 4 rack unit (1RU and 4 RU) versions and support up to 48 x 100 Gigabit connections per RU. Each unit is fully assembled at the factory and can reside in a chassis with 10, High Density 10, 40 and 100 GbE modules to allow convenient, incremental upgrades.

24-Fiber Trunk

4 RU Chassis1 RU Chassis

3 3

2 2

MPO MPO

MPO MPO

8-Way MPO Adaptor Module

8-Way MPO Adaptor Module

8-Way MPO Adaptor Module

8-Way MPO Adaptor Module

24-Fiber MPO Patch Cord

B-Polarity (Type B)

24-Fiber MPO Patch Cord A-Polarity

(Type A)

24-Fiber MPO Patch Cord A-Polarity (Type A)

41 1

24-Fiber MPO Trunk A-Polarity (Type A) 24-Fiber MPO Trunk A-Polarity (Type A)

Fiber Module

Page 20: 24-Fiber MPO System · 10 Gigabit Interconnect Introduction The 10 Gigabit Interconnect solution, like all of the planned migration designs, begins with a 24-fiber optical trunk with

www.commscope.comVisit our website or contact your local CommScope representative for more information.

© 2015 CommScope, Inc. All rights reserved.

MPOptimate and all trademarks identified by ® or ™ are registered trademarks or trademarks, respectively, of CommScope, Inc. This document is for planning purposes only and is not intended to modify or supplement any specifications or warranties relating to CommScope products or services.

PS-318339.5-AE (12/15)

High Density Equipment Panel 100 Gigabit Cross-Connect

100 Gigabit MPO to MPO Modules

Ordering Information

Number Component Part Number

1 24-fiber MPO Patch Cord, Polarity A (Type A) MPT-1C2C240xxxF-NN

2Unmanaged Adapter Pack, MPO-MPO Aqua, 192 fibers (8, 24F MPO ports)

N5AP-192MPOMMS

3 24-Fiber Trunk, Polarity A OM4 MPT-2C2CM40xxxF-FF

4 24-Fiber MPO Patch Cord, Polarity B (Type B) MPF-1C1C240xxxF-NN

N/S Chassis 1 RU N5CHU-1RU

N/S Chassis 4 RU N5CHU-4RU

Note: x or xxx denotes length F = Feet and M = Meters and may be changed accordingly based on ordering preference

Specifications

MPOptimate Performance: 24 fiber MPOptimate connections are specified at 0.25dB insertion loss

Standard Fiber Path: Compatible with TIA 568-C.0-2 draft standard for polarity method "A" trunks

24-Fiber Trunk: Up to eight 24-fiber MPO trunks per module

Patch Cords and Modules used in Pairs: Provide proper fiber map, polarity and location of MPO alignment pins

Management capable: Managed modules and assemblies are available. Please contact CommScope for details