Zte Bts Manual
-
Upload
diwakar-mishra -
Category
Documents
-
view
692 -
download
64
description
Transcript of Zte Bts Manual
-
ZXG10-BTS (V1A) Base Transceiver Station
Maintenance Manual
ZTE Corporation
-
ZTE Corporation. 2002, Shenzhen, P. R. China
All rights reserved. No part of this publication may be excerpted, reproduced, translated, annotated or edited, in any form or by any means, without the prior written permission of the copyright owner.
ZXG10-BTS (V1A)
Maintenance Manual
* * * *
3/F., A Wing, ZTE Plaza, Hi-Tech Industrial Park, Shenzhen, P. R. China
Tel: (0086) 75526790192
Fax: (0086) 75526790160
Post-code: 518057
* * * *
August, 2002 First Edition, First Print
-
Preface
ZXG10, a GSM mobile communication system independently developed by ZTE Corporation, is
composed of the switching sub-system ZXG10-MSS and the base station sub-system ZXG10-BSS.
The ZXG10-BSS is in charge of providing and managing wireless transmission in GSM, and is
composed of the base station controller ZXG10-BSC and the base station transceiver ZXG10-BTS,
etc. The reliable running of the ZXG10-BSS on the network is closely related to correct operation
and maintenance. Therefore, it is very important to handle problems properly with correct methods.
The ZXG10-BTS (V1A) Maintenance Manual serves as a guide for the user to perform daily
maintenance and fault handling on ZXG10-BTS (V1A). This manual primarily introduces the daily
maintenance, alarm handling and operation information processing of ZXG10-BTS (V1A).
In this Manual, ZXG10-BTS (V1A) is abbreviated as BTS (V1A) or BTS; ZXG10-BTS (V1A) local
management terminal as LMT; ZXG10-BSS (V1A) as BSS; and ZXG10-BSC (V1A) as BSC (V1A)
or BSC.
This Manual includes three chapters: Chapter 1 introduces the routine maintenance and emergent
maintenance of the ZXG10-BTS (V1A) as well as frequently used maintenance methods. Chapter 2
introduces the alarm classification of the LMT of ZXG10-BTS (V1A) and describes in detail the
alarm code, alarm content, alarm level, alarm cause, alarm impact, time limit of handling, and
handling process. Chapter 3 itemizes the operation information and handling methods of the boards
such as OMU and TRU. Appendix A introduces the procedures and precautions for replacing parts
and boards. Appendix B gives a list of abbreviations used in this document for the convenience of
users in reading this Manual.
This set of manuals also consists of the following documents:
Technical Manual for ZXG10-BTS (V1A)
Installation Manual for ZXG10-BTS (V1A)
Operation Manual for ZXG10-BTS (V1A)
Statement: The actual product may differ from what is described in this manual due to
frequent updates of ZTE products and fast development of technologies. Please contact our
local office for updating/upgrading information of the product.
-
Contents
1 EQUIPMENT MAINTENANCE .......................................................................................................... 1
1.1 MAINTENANCE DESCRIPTION ....................................................................................................................... 1
1.2 ROUTINE MAINTENANCE ............................................................................................................................. 2
1.2.1 Daily routine maintenance ........................................................................................................... 2
1.2.2 Regular routine maintenance ....................................................................................................... 4
1.3 EMERGENT MAINTENANCE .......................................................................................................................... 5
1.4 TYPICAL MAINTENANCE METHODS ............................................................................................................... 6
1.5 RELEVANT MAINTENANCE TABLES ................................................................................................................ 7
1.5.1 Routine maintenance and operation record table ....................................................................... 7
1.5.2 Emergent maintenance and operation record table .................................................................. 10
2 ALARM HANDLING ........................................................................................................................... 11
2.1 ALARM INFORMATION AND CLASSIFICATION ................................................................................................. 11
2.2 LEVEL-1 ALARM .................................................................................................................................... 18
2.3 LEVEL- 2 ALARM ................................................................................................................................... 18
2.3.1 Alarm of the main clock signal of the BS CKU ......................................................................... 18
2.3.2 Software version error of the BIE .............................................................................................. 19
2.3.3 Major alarm of the standing wave ratio of the transmitter combiner ....................................... 19
2.3.4 Communication interruption of the OMU .................................................................................. 20
2.4 LEVEL- 3 ALARM ................................................................................................................................... 21
2.4.1 Check error of the uplink data from the receiving processor to the channel processor ............ 21
2.4.2 Frame unit fault .......................................................................................................................... 24
2.4.3 Inconsistency of software versions ............................................................................................. 27
2.4.4 Out-of-lock of the transmitting RF self oscillator ...................................................................... 28
2.4.5 Error of software versions .......................................................................................................... 29
2.4.6 Fault of the BS clock unit (CKU) ............................................................................................... 31
2.4.7 Fault of BIE switching chips ...................................................................................................... 33
2.4.8 Faults of the BIE E1 interface .................................................................................................... 35
2.4.9 Alarm of fans of the BIE ............................................................................................................. 41
2.4.10 Alarm of temperature sensor ................................................................................................... 47
2.4.11 Fault of buses ........................................................................................................................... 52
2.4.12 Alarm of power amplifiers (PAs) .............................................................................................. 53
2.4.13 Alarm of low-noise amplifiers of the receiver multi-coupler .................................................. 55
-i-
-
2.4.14 Power alarm ............................................................................................................................. 57
2.4.15 Interruption of board communications .................................................................................... 58
2.4.16 Timeout of board unreported .................................................................................................... 61
2.4.17 Alarm of the 80W power amplifier (PA) ................................................................................... 62
2.4.18 Other alarm information .......................................................................................................... 63
2.5 LEVEL 4 ALARM ..................................................................................................................................... 67
2.5.1 Digital processor fault in the transceiver .................................................................................. 67
2.5.2 Check error of the uplink data from the RPP to the CHP .......................................................... 72
2.5.3 Cross-threshold of the flash memory programming times in the frame unit controller ............. 75
2.5.4 Channel parameter configuration error .................................................................................... 75
2.5.5 Out-of-lock of receiving RF self oscillator ................................................................................. 79
2.5.6 Alarm for out-of-lock of the phase-locked loop of the BS CKU ................................................. 80
2.5.7 No response of layer-3 software ................................................................................................. 81
2.5.8 Slide code indication of the BIE E1 interface signal ................................................................. 83
2.5.9 BS OMU fault ............................................................................................................................. 88
2.5.10 Minor alarm of PA over-temperature ....................................................................................... 89
2.5.11 Board communication interruption .......................................................................................... 90
2.5.12 Boards are unreported till timeout .......................................................................................... 94
2.5.13 80W PA link alarm .................................................................................................................. 101
3 RUNNING INFORMATION PROCESSING .................................................................................. 102
3.1 CLASSIFICATION OF RUNNING INFORMATION ............................................................................................... 102
3.2 OMU OPERATION INFORMATION ............................................................................................................. 106
3.2.1 OMU board not powered on ..................................................................................................... 106
3.2.2 OMU board powered on ........................................................................................................... 106
3.2.3 OMU BOOT starting ................................................................................................................ 106
3.2.4 OMU in active status ................................................................................................................ 107
3.2.5 OMU in standby status ............................................................................................................. 107
3.2.6 OMU procedure initially launched .......................................................................................... 107
3.2.7 OMU clock fault ....................................................................................................................... 108
3.2.8 OMU LAPD link disconnected. ................................................................................................ 108
3.2.9 OMU system in the initialization status .................................................................................. 108
3.2.10 OMU file downloading ........................................................................................................... 109
3.3 TRU OPERATION INFORMATION ............................................................................................................... 109
3.3.1 TRU board not powered on ...................................................................................................... 109
3.3.2 TRU board powered on ............................................................................................................ 109
3.3.3 BOOT starting .......................................................................................................................... 110
ii
-
3.3.4 Process initially started ............................................................................................................ 110
3.3.5 OMU clock fault ....................................................................................................................... 110
3.3.6 LAPD link disconnected ........................................................................................................... 111
3.3.7 TRU HDLC link disconnected .................................................................................................. 111
3.3.8 TRU system in the initialization status ..................................................................................... 112
3.3.9 TRU file downloading ............................................................................................................... 112
3.3.10 TRU BCCH carrier indication ............................................................................................... 112
3.4 BIE RUNNING INFORMATION ................................................................................................................... 113
3.4.1 BIE board not powered on ........................................................................................................ 113
3.4.2 BIE program out of service ...................................................................................................... 113
3.4.3 BIE HDLC link not established ................................................................................................ 113
3.4.4 BIE working normally .............................................................................................................. 114
3.4.5 BIE in the active status ............................................................................................................. 114
3.5 EBIE RUNNING INFORMATION ................................................................................................................ 114
3.5.1 EBIE board not powered on ..................................................................................................... 114
3.5.2 EBIE program out of service .................................................................................................... 115
3.5.3 EBIE 8K and E1 alarm ............................................................................................................. 115
3.5.4 EBIE HDLC link not established .............................................................................................. 115
3.5.5 EBIE working normally ............................................................................................................ 116
3.5.6 EBIE in active status ................................................................................................................ 116
3.5.7 EBIE parameter configuration ................................................................................................ 116
3.6 CKU RUNNING INFORMATION ................................................................................................................. 117
3.6.1 CKU board not powered on ...................................................................................................... 117
3.6.2 CKU initialization .................................................................................................................... 117
3.6.3 CKU program out of service .................................................................................................... 117
3.6.4 CKU working normally ............................................................................................................ 118
3.6.5 CKU in the active status ........................................................................................................... 118
3.6.6 CKU in the phase lock status .................................................................................................... 118
3.6.7 CKU in the locked status .......................................................................................................... 118
3.6.8 Asynchronization of the whole CKU network .......................................................................... 119
3.6.9 The CKU clock frame number abnormal ................................................................................. 119
3.6.10 CKU HDLC link not established ............................................................................................ 119
3.6.11 The CKU 8K clock abnormal ................................................................................................. 120
3.7 EAM RUNNING INFORMATION ................................................................................................................ 120
3.7.1 EAM board not powered on ..................................................................................................... 120
3.7.2 EAM initialization .................................................................................................................... 120
3.7.3 EAM working normally ............................................................................................................ 121
-iii-
-
3.7.4 EAM HDLC link disconnected ................................................................................................. 121
3.7.5 The EAM system clock severely abnormal ............................................................................... 121
APPENDIX A REPLACEMENT OF BOARDS AND PARTS .......................................................... 123
A.1 OVERVIEW ........................................................................................................................................ 123
A.2 REPLACEMENT OF THE PUBLIC SHELF BOARD .......................................................................................... 124
A.3 REPLACEMENT OF THE CARRIER SHELF BOARD ........................................................................................ 125
APPENDIX B ABBREVIATIONS ....................................................................................................... 127
iv
-
1 Equipment Maintenance
1.1Maintenance description
The objective of daily maintenance is to ensure an optimized working condition of the product, so
that the whole network runs properly. The classification of the daily maintenance of the ZXG10-BTS
(V1A), together with the maintenance requirements and recommendations will be described below.
1. Maintenance classification
Daily maintenance of ZXG10-BTS (V1A) can be classified into routine maintenance and emergent
maintenance.
The routine maintenance refers to periodical maintenance, which is divided into daily routine
maintenance and regular routine maintenance by their maintenance periods. Emergent maintenance
refers to the maintenance tasks to be immediately executed as required by sudden failures of the
ZXG10-BTS (V1A) equipment and network adjustment, e.g., equipment failure, user-reported fault,
and the emergent problems found out in routine maintenance. Emergent failures are characterized by
abrupt occurrence and serious influences on the QoS, so the maintenance personnel in the equipment
room are required to handle them decisively, cautiously and in-time. A detailed record must be made
afterward so as to eliminate potential faults.
2. Maintenance requirements and recommendations
The daily maintenance of ZXG10-BTS (V1A) equipment is a major task for the maintenance
personnel in the equipment room. Excellent daily maintenance is a key factor to ensure long-term
stable running of the equipment. Therefore, a set of equipment room maintenance regulations should
be formulated to regulate and guide the work of the maintenance personnel. The followings are some
basic requirements and recommendations for daily maintenance:
1) The maintenance personnel should implement the daily and regular routine check strictly and
keep a detailed record without any omission.
2) The maintenance personnel must keep the equipment room safe and tidy, with proper
temperature and humidity.
3) The maintenance personnel should follow the equipment operation specifications strictly,
-1-
-
avoid any operations on the equipment beyond the daily maintenance specifications, e.g.,
arbitrarily plugging/unplugging, resetting, starting and switching over the equipment, or
changing the data; and should wear an anti-static wrist strap when accessing the hardware
system, and store the damaged parts and the spare parts in anti-static bags, which should be
labeled of the category and stored properly.
4) The person in charge of the equipment room should keep the user accounts, passwords and
the user authorities for login to the local operation & maintenance console and to the network
management system, and distribute them to relevant persons according to their specific
authorities, so as to define the responsibility and authority clearly.
5) The maintenance personnel should handle detected problems and faults in time, report major
problems to relevant supervisors in time and contact the local office of ZTE to get an early
solution, which should be recorded in detail afterward.
6) Before on-duty, the maintenance personnel must undergo necessary training. Different
maintenance positions should be assumed by persons of the corresponding technical levels.
7) The frequently used tools and instruments should be checked, repaired and calibrated before
use to ensure their proper conditions. Generally, the following tools and instruments are
recommended to be prepared in the equipment room.
A. Tools and auxiliary materials: screwdriver (flat-head and Phillips), diagonal pliers, cable
stripper, unpacking pliers, electric iron, chip-extractor, programmer, eraser, tweezers,
spanner, electrical drill, tape, anti-static wrist strap, insulating tape and cable tie.
B. Instruments: Multimeter, thermometer, humidity meter, optical power meter and earth
resistance tester.
8) The power supply of the system should be kept stable and reliable, and the grounding of the
system should be checked regularly.
1.2Routine maintenance
1.2.1Daily routine maintenance
Daily routine maintenance includes the following items:
1. Equipment room environment
1) Temperature requirements:
-2-
Maintenance Manual for ZXG10-BTS (V1A)
-
Ambient temperature requirements: -5C ~ +45C; recommended to be always kept between
15C ~ 30C. A thermometer should be available in the equipment room, and the maintenance
personnel should check it daily and make a record in detail; an air conditioner is recommended
to be installed in the equipment room to meet the temperature requirements for long-term stable
running of the equipment.
2) Humidity requirement
Relative humidity requirement: 15%~85%; recommended to be kept at 40%~65%. A humidity
meter should be available in the equipment room, and the maintenance personnel should check
it daily and keep a record in detail. A humidity conditioning device is recommended to be
installed in the areas where the humidity is seriously improper, especially, a damp-proof device
is recommended in areas of high humidity and anti-static floor is recommended in areas of low
humidity.
3) Working status of the air conditioner
Check whether the air conditioner (or other humidity conditioning devices) can work normally
according to the preset temperature (humidity) requirements, and handle the faults in time if
any.
4) Dust-proof
During the daily maintenance, the equipment should be kept free from dust or contamination. It
is recommended to apply dust-proof sealing rubber strips around the windows and doors of the
equipment room, adopt double-layered-glass sealed windows and wear union suits and special
shoes in the equipment room to diminish dust. In addition, strong magnetic, electrical or
corrosive materials should not be present inside or around the equipment room so as to prevent
from harmful particles.
2. Equipment running status
1) Querying the alarm information
Check the site alarms and rack alarms in the alarm query window of the operation &
maintenance center (OMCR) of the BSS or the LMT of the BTS, keep a detailed record of the
alarm information, and contact the technical personnel in time to locate and eliminate faults.
A. In the OMCR of the BSS, the current alarms are displayed in real time, and the rack
diagram and the alarm statuses of boards are displayed dynamically in the main interface
-3-
Chapter 1 Equipment MaintenanceAlarm Handling
-
of alarms. The recovered history alarms, current alarms and ordinary notifications can be
queried as needed. For the procedure of querying alarms, please see ZXG10-BSS (V1A)
Operation Manual; for the alarm causes and handling process, please see ZXG10-BSS
(V1A) Maintenance Manual.
B. Whether the Abis link is connected through or not, the LMT system of the BTS permits
the maintenance personnel to query the alarm status of boards in the site, including alarm
mode, alarm location, alarm content, fan running condition and rack temperature. Multiple
alarms may exist on the same board at a time, and the board color on the alarm viewing
interface represents the top alarm level existing on this board. Click the board, and all
alarm information on this board will be displayed. For the procedure of querying alarms,
please see ZXG10-BTS (V1A) Operation Manual; for alarm causes and handling process,
please see Chapter 2 of this Manual.
2) Running status of boards
Check whether the indication of the indicators for each board in the rack is normal. If any alarm
indicator is on, contact the technical personnel in time to locate and eliminate the fault.
The running information of the ZXG10-BTS (V1A) mainly comes from the indicators on the
panels of modules such as OMU and TRU. By the different flashing meanings of the indicators,
you can determine the running status of the equipment basically. For the meanings, causes and
handling of various indicator statuses, please see Section 3.1 of this Manual.
1.2.2Regular routine maintenance
Regular routine maintenance includes the following items:
1. Checking the BTS modules
Check the amount, model and version of spare modules once a week, and make sure that the spare
modules are stored in compliance with the requirements, with adequate amount and the convenience
to find. Check the back-to-fix conditions of faulty modules once a week.
2. Hardware checking: once a month.
1) Cleaning the rack
Clean the surface of the cabinet, clean and dry the air filter at the bottom of the cabinet; check
whether the cabinet is rusted, and whether there is any unrelated article in the cabinet. Report
any difficult problems in time if any, so as to get an early repair.
-4-
Maintenance Manual for ZXG10-BTS (V1A)
-
2) Checking the connection of power cables
Check whether the power cables are connected tightly, and whether there is rust.
3) Checking the connection of grounding cables
Check whether the grounding cables are connected tightly, and whether there is rust.
4) Checking the power modules
Check whether the power supply of each shelf can work independently. Contact the technical
personnel in time for any problem so as to fix the problem.
3. Transmission
Check the connector tightness of the transmission cables from the optical terminal/microwave rack
to the BTS rack once every quarter, and keep the transmission cables free from twisting, pressing,
deforming and over-tightness; and test the spare ports.
4. Antenna and feeder system
Adjust and calibrate the direction and pitch angle of the antenna once half a year; tighten the
antenna, outdoor jumper, feeder cable and indoor jumper; apply rust-proof treatment to the antenna
pole, feeder cable rack and grounding bar which are subject to getting rusty; test the VSWR of the
antenna and feeder system, the transmitting power of the PA; and perform a general test on all
frequencies of all cells of each BS.
1.3Emergent maintenance
Emergent maintenance refers to the maintenance task which needs to be handled immediately in
response to the emergent fault of ZXG10-BTS (V1A) equipment. Emergent faults are characterized
by abrupt occurrence and serious influence on the QoS, so the maintenance personnel of the
equipment room are required to handle them decisively, cautiously and in-time. A detailed record
should be made afterward so as to eliminate potential faults.
Generally, the emergent handling process and measures for emergent faults can be summarized
based on the following two types of faults:
1. Emergent faults and disasters in the environment of the equipment room
1) Major faults: Fault of the power supply system; floods, fires; faults of the air conditioner
system which cause the temperature and humidity severely beyond the specifications.
-5-
Chapter 1 Equipment MaintenanceAlarm Handling
-
2) Maintenance measures: When any alarm information is observed from the OMCR of the
BSS or the LMT system of the BTS, perform an immediate inspection on the environment of
the equipment room, locate the fault cause, and eliminate the fault quickly. Afterward, report to
the superior leaders and keep a detailed record to eliminate potential faults.
2. Emergent fault of the equipment
1) Major faults: including hardware faults, e.g., damage of boards and modules, not-in-position,
poor contact, and software faults, e.g., disorder of data and program, and improper upgrading.
2) Maintenance measures:
A. Through plugging/unplugging, some faults such as not-in-position and poor contact of
the hardware system can be solved; through the replacing or isolation method, the faults
such as hardware damage can be located; the data disorder can be queried and corrected
through operations in the OMCR of the BSS or the LMT system of the BTS.
B. Faults of the software and hardware are numerous and complicated. If the above simple
methods fail to solve the problem, please contact the technical personnel or the regional
office of ZTE Corporation, report to the relevant leaders, and keep a detailed record
afterward so as to eliminate potential faults.
1.4Typical maintenance methods
In daily maintenance, several typical maintenance methods can be used as follows:
1. Observation method
Locating the fault by viewing the alarm information of the LMT of the BTS. The observation
method is the first method the maintenance personnel should use in case of fault occurrence. Making
a correct judgement on the observation result is a key step for correct analysis and handling of the
fault. Therefore, the maintenance personnel must be very familiar with the indicator statuses of the
boards, and fully aware of the meanings of the alarm information of different levels on the LMT of
the BTS.
2. Plugging/unplugging method
When a circuit board is initially found faulty, plug/unplug the circuit board and the external interface
connector to eliminate such faults as poor contact or processor abnormality. Make sure that the board
must be hot-swappable when this method is applied.
-6-
Maintenance Manual for ZXG10-BTS (V1A)
-
3. Replacing method
The replacing method is to check the fault by replacing the circuit board in question with a normal
circuit board. When the plugging/unplugging method fails, the replacing method can be applied.
When plugging/unplugging and replacing the board, please see the precautions and operation
procedure for replacing the boards and parts as listed in Appendix A.
4. Isolation method
When a part of the system is faulty, the involved circuit board or racks can be isolated to check
whether the fault comes from mutual impact. For example, a typical application of the isolation
method is to self-loop the I/O interface of a circuit board so as to isolate and solve the problem of the
related system.
5. Self-test method
When the system or circuit board is powered on again judge if there is any fault by way of self-test.
Usually, when a circuit board is re-powered on for self-test, the indicators on its panel will flash
regularly, so that we can check whether the circuit board itself is faulty.
6. Pressing method
Such faults as poor contact can be removed by pressing the chips and cable connectors.
7. Comprehensive method
Any fault can be cleared by combining the above methods and taking advantage of ones
maintenance experience.
1.5Relevant maintenance tables
1.5.1Routine maintenance and operation record table
The daily maintenance record table is shown in Table 1-1. The regular maintenance table is shown in
Table 1-2. The maintenance item periodical summary table is shown in Table 1-3.
-7-
Chapter 1 Equipment MaintenanceAlarm Handling
-
Table 1-1 Daily maintenance record table
Items Operation item Equipment running status and
handling result
Operator Remarks
Equipment
room
environment
Temperature
Humidity
Working status of
the air conditioner
Dust-proof
Equipment
running status
Querying the alarm
information
Running status of
boards
Table 1-2 Regular maintenance record table
Items Operation item Equipment running status and
handling result
Operator Remarks
Check the
BTS module
Check the BTS
module
Hardware:
check
Clean the rack
Check the
connection of power
cables
Check the
connection of
grounding cables
Check the power
module
Transmission Transmission
Antenna and
feeder
System
Antenna and feeder
system
-8-
Maintenance Manual for ZXG10-BTS (V1A)
-
Table 1-3 Maintenance item periodical summary table
Items Operation item Maintenance
period
Equipment running status
and handling result
Operator Remarks
Equipment room
environment
Temperature Daily
Humidity Daily
Working status of
the air conditioner
Daily
Dust-proof Daily
Equipment
running status
Querying the
alarm information
Daily
Running status of
boards
Daily
BTS module
check
Check the BTS
module
Weekly
Hardware:
check
Clean the racks Monthly
Check the
connection of
power cables
Monthly
Check the
connection of
ground cables
Monthly
Check the power
module
Monthly
Transmission Transmission quarterly
Antenna and
feeder
System
Antenna and
feeder system
Half a year
-9-
Chapter 1 Equipment MaintenanceAlarm Handling
-
1.5.2Emergent maintenance and operation record table
The emergent fault handling record table is shown in Table 1-4.
Table 1-4 Emergent fault handling record table
Exchange name: Person to handle:
Time Time of fault resolved:
Fault source: informed by the user alarm system found in daily routine maintenance others
Fault category:
Fault description:
Handling method:
Result:
Remarks by the person in charge:
-10-
Maintenance Manual for ZXG10-BTS (V1A)
-
2 Alarm Handling
2.1Alarm information and classification
The alarm management of the LTM system is an important part of BTS local operation and
maintenance. The LMT system, after it is put into operation, can perform centralized monitoring on
the overall running condition of the BTS for the purpose of real-time maintenance and recovery.
Whether the Abis link is connected through or not, the LMT system permits the maintenance
personnel to query the alarm status of boards in the site, and view the site alarms and rack alarm
information on the LMT alarm viewing interface.
Boards that may send alarms include:
1. Boards in the public shelf: operation and maintenance unit (OMU), BS interface equipment (BIE),
clock unit (CKU), external alarm collection module (EAM), signaling distribution unit (SDU) and
power supply (PSA).
2. Boards in the carrier shelf: frame unit (FU), carrier unit (CU), power supply (PSB), power
amplifier (PA), combiner HYCOM and multi-coupler MUL.
3. Others: fan, temperature.
In terms of real-time handling, the alarms include ordinary notifications and alarms. Ordinary
notifications only indicate unrepeatable or transient faults during the system running. Usually, if a
notification is not frequently repeated, it may be caused accidentally by the environment, which
needs no handling; if a notification is frequently repeated, or even the alarm occurs for a long time, it
must be checked and solved in time.
An alarm usually lasts for a certain time. According to the severity in the system, alarms are divided
into four levels. Following is the division of the four alarm levels, as shown in Table 2-1.
-11-
-
Table 2-1 Division of alarm levels
Alarm
level
The scope of
services seriously
affected
The scope of
equipment safety
seriously affected
The scope of system
running reliability
seriously affected
The scope of
system
maintainability
seriously affected
1 The whole BSS The whole BSS
2 One or some sites BSC or a site The whole BSS The whole BSS
3 One or some carriers One or some carriers BSC or a site BSC or a site
4 One or some
channels
No influence One or some carriers One or some
carriers
Note: In the definition of the alarm levels, the affected scope only refers to one single index. That is,
if the affected scope of one single index, e.g., reliability, security reaches the specified scope, the
level of the alarm can be determined basically. If one alarm item has affected several indexes, the
alarm level should be raised.
The alarm information summary table of the LMT is shown in Table 2-2. For the detailed
information of the alarm, e.g., alarm cause, time limit of handling, handling process, please see
relevant contents of Section 2.2~2.5.
Table 2-2 Alarm information summary table
Alarm code Alarm name Alarm level
0xC00 Alarm of the main clock signal of the BS CKU 2
0xD00 Software version error of the BS interface equipment 2
0x1301 Major alarm of standing wave ratio of the transmitter
combiner
2
0x1701 Communication interruption of the OMU. 2
0xA08 Data check error of both the main-set and sub-set uplink
data from the receiving processor to the channel
processor (DSP0).
3
0xA09 Data check error of both the main-set and sub-set uplink
data from the receiving processor to the channel
processor (DSP1).
3
-12-
Maintenance Manual for ZXG10-BTS (V1A)
-
(continued)
Alarm code Alarm name Alarm level
0xA0A Data check error of both the main-set and sub-set uplink
data from the receiving processor to the channel
processor (DSP2).
3
0xA0B Data check error of both the main-set and sub-set uplink
data from the receiving processor to the channel
processor (DSP3).
3
0xA0D Fault of the interface clock between the frame unit
controller and the BS CKU.
3
0xA0E Read/write error of the flash memory in the frame unit 3
0xA18 Overflow of the watchdog in the frame unit controller 3
0xA26 LAPD link disconnection of the frame unit controller and
the BSC
3
0xB00 Downlink check error between the frame unit and carrier
unit
3
0xA23 Inconsistency of the channel processor (CHP) software
version
3
0xA24 Inconsistency of the frame unit controller (FUC) software
version
3
0xB04 Out-of-lock of transmitting RF self oscillator 3 3
0xB05 Out-of-lock of transmitting RF self oscillator 4 3
0xB06 Out-of-lock of transmitting intermediate frequency self
oscillator 5
3
0xB0F Wrong carrier unit (CU) software version 3
0xC0C Wrong BS CKU software version 3
0xF2A Wrong BS environment alarm board layer-3 software
version
3
0xC01 Alarm of BS CKU frame numbers 3
0xC09 Error of the BS CKU parameter configuration 3
0xC0A Abnormality of the 8K clock signal between BS interface
equipment (BIE) and the BS CKU
3
0xD01 Fault of the BIE switching chip 1 3
0xD02 Fault of the BIE switching chip 2 3
Chapter 2 Alarm Handling
-13-
-
(contiued)
Alarm code Alarm name Alarm level
0xD03 Fault of the BIE switching chip 3 3
0xD04 Fault of the BIE switching chip 4 3
0xD05 Read/write fault of E1 interface chip 1 of the BIE 3
0xD06 Read/write fault of E1 interface chip 2 of the BIE 3
0xD07 Read/write fault of E1 interface chip 3 of the BIE 3
0xD08 Loss of E1 interface signal 1 of the BIE 3
0xD09 Loss of E1 interface signal 2 of the BIE 3
0xD0A Loss of E1 interface signal 3 of the BIE 3
0xD11 Alarm of out-of-frame of E1 interface signal 1 of the BIE 3
0xD12 Alarm of out-of-frame of E1 interface signal 2 of the BIE 3
0xD13 Alarm of out-of-frame of E1 interface signal 3 of the BIE 3
0xF01 Alarm of fan 1 3
0xF02 Alarm of fan 2 3
0xF03 Alarm of fan 3 3
0xF04 Alarm of fan 4 3
0xF05 Alarm of fan 5 3
0xF06 Alarm of fan 6 3
0xF07 Alarm of fan 7 3
0xF08 Alarm of fan 8 3
0xF09 Alarm of fan 9 3
0xF0D Alarm of temperature sensor 1 3
0xF0E Alarm of temperature sensor 2 3
0xF0F Alarm of temperature sensor 3 3
0xF10 Alarm of temperature sensor 4 3
0xF11 Alarm of temperature sensor 5 3
0xF12 Alarm of temperature sensor 6 3
0x1002 Fault of the frame unit bus 3
0x1003 Fault of the low-speed bus 3
(contiued)
-14-
Maintenance Manual for ZXG10-BTS (V1A)
-
Alarm code Alarm name Alarm level
0x1100 Alarm of the PA output power 3
0x1101 Alarm of the PA voltage standing wave ratio 3
0x1102 Alarm of the PA tube over-current 3
0x1103 Alarm of PA tube over-voltage 3
0x1105 Major alarm of PA over-temperature 3
0x1200 Alarm of low-noise amplifier 1 of the receiver multi-
coupler
3
0x1201 Alarm of low-noise amplifier 2 of the receiver multi-
coupler
3
0x1400 Alarm of the power supply of the carrier shelf 3
0x1500 Alarm of the power supply of the public shelf 3
0x1702 Communication interruption of the BS interface board 3
0x1703 Communication interruption of the BS CKU 3
0x1704 Communication interruption of the BS environment
alarm unit
3
0x1708 Communication link disconnection of the power board of
the public shelf
3
0x1801 BS OMU unreported till timeout 3
0x1804 BS environment alarm board unreported till timeout 3
0x1106 Alarm of the current, voltage and temperature of the 80W
PA
3
0x1107 Alarm of the consistency of the two 80W PAs in terms of
the forward power and type, and the standing wave ratio
of the PA on the left
3
0xA22 Inconsistent configuration of cell parameters 3
0xB08 Error of parameter configuration of the carrier unit 3
0xD14 Error of link parameter configuration of the BIE 3
0xF2B No response of the layer-3 software of the BS
environment alarm board
3
0x1300 Minor alarm of standing wave ratio of the transmitter
combiner
3
(contiued)
Chapter 2 Alarm Handling
-15-
-
Alarm code Alarm name Alarm level
0xA04 Initialization failure of the digital processor 0 in the
transceiver
4
0xA05 Initialization failure of digital processor 01 in the
transceiver
4
0xA06 Initialization failure of digital processor 02 in the
transceiver
4
0xA07 Initialization failure of digital processor 03 in the
transceiver
4
0xA10 Software overflow of digital processing unit 0 in the
transceiver
4
0xA11 Software overflow of digital processing unit 1 in the
transceiver
4
0xA12 Software overflow of digital processing unit 2 in the
transceiver
4
0xA13 Software overflow of digital processing unit 3 in the
transceiver
4
0xA14 Check error of one channel of the uplink data from the
RPP to the CHP (DSP0)
4
0xA15 Check error of one channel of the uplink data from the
RPP to the CHP (DSP1)
4
0xA16 Check error of one channel of the uplink data from the
RPP to the CHP (DSP2)
4
0xA17 Check error of one channel of the uplink data from the
RPP to the CHP (DSP3)
4
0xA19 Cross-threshold of the flash memory programming times
in the frame unit controller
4
0xA1A Channel 0 parameter configuration error 4
0xA1B Channel 1 parameter configuration error 4
0xA1C Channel 2 parameter configuration error 4
0xA1D Channel 3 parameter configuration error 4
0xA1E Channel 4 parameter configuration error 4
0xA1F Channel 5 parameter configuration error 4
(continued)
Alarm code Alarm name Alarm level
-16-
Maintenance Manual for ZXG10-BTS (V1A)
-
0xA20 Channel 6 parameter configuration error 4
0xA21 Channel 7 parameter configuration error 4
0xB02 Out-of-lock of receiving RF self oscillator 1 4
0xB03 Out-of-lock of receiving RF self oscillator 2 4
0xB07 Out-of-lock of receiving IF self oscillator 6 4
0xC08 Alarm for out-of-lock of phase-locked loop of the BS
CKU
4
0xC0D No response of layer-3 software of the BS CKU 4
0xD15 No response of the layer-3 software of the BS BIE 4
0xB10 No response of the layer-3 software of the carrier unit
(CU)
4
0xD0B Forward slide code indication of the BIE E1 interface
signal 1
4
0xD0C Forward slide code indication of the BIE E1 interface
signal 2
4
0xD0D Forward slide code indication of the BIE E1 interface
signal 3
4
0xD0E Backward slide code indication of the BIE E1 interface
signal 1
4
0xD0F Backward slide code indication of the BIE E1 interface
signal 2
4
0xD10 Backward slide code indication of the BIE E1 interface
signal 3
4
0x1000 Cross-threshold of the flash memory programming times
of the BS OMU
4
0x1001 Failure of flash memory programming of the BS OMU 4
0x1004 The standby board of the BS OMU not in position 4
0x1104 Minor alarm of PA over-temperature 4
0x1705 Communication interruption of the frame unit 4
0x1706 Communication link disconnection of the carrier unit 4
(continued)
Chapter 2 Alarm Handling
-17-
-
Alarm code Alarm name Alarm level
0x1709 Communication link disconnection of the power board of
the carrier shelf
4
0x170A Communication link disconnection of the PA 4
0x170B Communication link disconnection of the multi-coupler 4
0x170D Communication link disconnection of the combiner 4
0x1802 The BS interface board unreported till timeout 4
0x1803 The BS CKU unreported till timeout 4
0x1805 The frame unit unreported till timeout 4
0x1806 The carrier unit unreported till timeout 4
0x1808 The public shelf power board unreported till timeout 4
0x1809 The carrier shelf power board unreported till timeout 4
0x180A The PA unreported till timeout 4
0x180B The multi-coupler unreported till timeout 4
0x180D The hybrid combiner unreported till timeout 4
0x1108 80W PA link alarm 4
2.2Level-1 alarm
None.
2.3Level- 2 alarm
2.3.1Alarm of the main clock signal of the BS CKU
Alarm code: 0xC00
Alarm content: Alarm of CKU main clock signal
Alarm level: 2
Alarm cause: hardware fault
Influence of the alarm: If the alarm occurs to an active CKU, this BS will fail to work normally; if
the alarm occurs to a standby CKU, the running reliability of the system will deteriorate.
Time limit of handling: Handle it at once.
-18-
Maintenance Manual for ZXG10-BTS (V1A)
-
Handling process: Replace the CKU board
Alarm type: Equipment alarm
2.3.2Software version error of the BIE
Alarm code: 0xD00
Alarm content: BIE (software version error)Alarm level: 2
Alarm cause: software version error, or wrong alarm caused by communication error
Influence of the alarm: The system fails to start normally.
Time limit of handling: Handle it at once.
Handling process:
1. Insert the board properly and reset it.
2. If the alarm still exists, the board may be faulty, please replace the board.
3. If the alarm still exists, the board software version may be inconsistent with the OMU background
database. Please contact the regional office of ZTE Corporation.
Alarm type: Wrong handling.
2.3.3Major alarm of the standing wave ratio of the transmitter combiner
Alarm code: 0x1301
Alarm content: Major alarm of the standing wave ratio of the transmitter combiner
Alarm level: 2
Alarm cause: The external terminal of the combiner is open-circuited or of high resistance, the EAM
receives interference signals or the EAM alarm line is wrongly connected.
Influence of the alarm: The PA transmitting power is off protectively, and the corresponding cell fails
to work.
Time limit of handling: Handle it at once.
Handling process:
Chapter 2 Alarm Handling
-19-
-
1. Check whether the EAM works normally.
2. Check whether the EAM alarm cable of the backplane is faulty. If the alarm occurs together with
the minor alarm of the standing wave ratio of the transmitter combiner, the backplane alarm line
may be faulty.
3. If the alarm indicator on the panel is on at the same time, it is required to check whether the
connectors between the set-top jumper, main feeder and antenna are poorly contacted, and check for
water leakage.
4. If none of the above measures works, please contact the regional office of ZTE Corporation.
Alarm type: Equipment alarm
2.3.4Communication interruption of the OMU
Alarm code: 0x1701
Alarm content: OMU communication interruption
Alarm level: 2
Alarm cause: LAPD link disconnection between OMU and BSC, OMU fault, BTS rack power-off,
fault of LAPD, SMB, T network board of the BSC, etc.
Influence of the alarm: Affecting the reset and startup of the BTS and the information transmission
between the BTS and the BSC, and the operation and maintenance of BTS will be interrupted.
Time limit of handling: Handle it at once.
Handling process:
1. Check whether the boards of BSC, e.g., LAPD, SMB, work normally, and whether there is any
alarm present, if there is, clear it first.
2. Check whether the LAPD timeslot of the OMU is allocated correctly.
3. Check whether the E1 line is connected through.
4. Check whether the BTS rack is powered on, and whether OMU is started normally.
5. Check whether the BIE of BTS works normally. Clear the alarms first if any.
-20-
Maintenance Manual for ZXG10-BTS (V1A)
-
6. If none of the above measures works, please contact the regional office of ZTE Corporation.
Alarm type: Communication alarm
2.4Level- 3 alarm
2.4.1Check error of the uplink data from the receiving processor to the channel processor
2.4.1.1Data check error of both the main-set and sub-set uplink data from the receiving
processor to the channel processor (DSP0)
Alarm code: 0xA08
Alarm content: Data check error of both the main-set and sub-set uplink data from the receiving
processor (RPP) to the channel processor (CHP) (DSP0)
Alarm level: 3
Alarm cause: Severe interference exists in the transmission channel from the RPP to the CHP (or the
lines are poorly contacted).
Influence of the alarm: The signal quality of the radio interface will deteriorate drastically, affecting
the voice quality and even the assignment will fail.
Time limit of handling: Handle it as soon as possible.
Handling process:
1. Check whether the CKU is properly inserted.
2. Check whether the backplane line gets loose.
3. Check whether the bit switch for the transmission matching resistance on the backplane is set
properly.
4. If none of the above operations works, reset the BTS to check if the fault still exists.
5. If none of the above measures works, please contact the regional office of ZTE Corporation.
Alarm type: Equipment alarm
Chapter 2 Alarm Handling
-21-
-
2.4.1.2Data check error of both the main-set and sub-set uplink data from the receiving
processor to the channel processor (DSP1).
Alarm code: 0xA09
Alarm content: Data check error of both the main-set and sub-set uplink data from the receiving
processor (RPP) to the channel processor (CHP) (DSP1)
Alarm level: 3
Alarm cause: Severe interference exists in the transmission channel from the RPP to the CHP (or the
lines are poorly contacted).
Influence of the alarm: The signal quality of the radio interface will deteriorate drastically, the uplink
bit error will occur in timeslot 1 and timeslot 5. In serious situations, the conversation will be
interrupted and the assignment will fail.
Time limit of handling: Handle it as soon as possible.
Handling process:
1. Check whether the CKU is properly inserted.
2. Check whether the backplane line gets loose.
3. Check whether the bit switch for the transmission matching resistance on the backplane is set
properly.
4. If none of the above operations works, reset the BTS to check if the fault still exists.
5. If none of the above measures works, please contact the regional office of ZTE Corporation.
Alarm type: Equipment alarm
2.4.1.3Data check error of both the main-set and sub-set uplink data from the receiving
processor to the channel processor (DSP2).
Alarm code: 0xA0A
Alarm content: Data check error of both the main-set and sub-set uplink data from the receiving
processor (RPP) to the channel processor (CHP) (DSP2)
Alarm level: 3
-22-
Maintenance Manual for ZXG10-BTS (V1A)
-
Alarm cause: Severe interference exists in the transmission channel from the RPP to the CHP (or the
lines are poorly contacted).
Influence of the alarm: The signal quality of the radio interface will deteriorate drastically, the uplink
bit error will occur in timeslot 2 and timeslot 6. In serious situations, the conversation will be
interrupted and the assignment will fail.
Time limit of handling: Handle it as soon as possible.
Handling process:
1. Check whether the CKU is properly inserted.
2. Check whether the backplane line gets loose.
3. Check whether the bit switch for the transmission matching resistance on the backplane is set
properly.
4. If none of the above operations works, reset the BTS to check if the fault still exists.
5. If none of the above measures works, please contact the regional office of ZTE Corporation.
Alarm type: Equipment alarm
2.4.1.4Data check error of both the main-set and sub-set uplink data from the receiving
processor to the channel processor (DSP3).
Alarm code: 0xA0B
Alarm content: Data check error of both the main-set and sub-set uplink data from the receiving
processor (RPP) to the channel processor (CHP) (DSP3)
Alarm level: 3
Alarm cause: Severe interference exists in the transmission channel from the RPP to the CHP (or the
lines are poorly contacted).
Influence of the alarm: The signal quality of the radio interface will deteriorate drastically, the uplink
bit error will occur in timeslot 3 and timeslot 7. In serious situations, the conversation will be
interrupted and the assignment will fail.
Time limit of handling: Handle it as soon as possible.
Chapter 2 Alarm Handling
-23-
-
Handling process:
1. Check whether the CKU is properly inserted.
2. Check whether the backplane line gets loose.
3. Check whether the bit switch for the transmission matching resistance on the backplane is set
properly.
4. If none of the above operations works, reset the BTS to check if the fault still exists.
5. If none of the above measures works, please contact the regional office of ZTE Corporation.
Alarm type: Equipment alarm
2.4.2Frame unit fault
2.4.2.1Fault of the interface clock between the frame unit controller and the BS CKU
Alarm code: 0xA0D
Alarm content: Fault of FUC_CKU interface clock
Alarm level: 3
Alarm cause: Fault of the BTS CKU, fault of the transmission clock line, or fault of the clock
interface on the FU.
Influence of the fault: Affecting the normal communication between the baseband processing unit
and OMU and CU, resulting in failure of normal operation of the whole CU.
Time limit of handling: Handle it at once.
Handling process:
1. Check whether alarms occur on the CKU board.
2. Check whether the line between the CKU and CU is connected reliably.
3. If none of above measures works, replace the TRU.
Alarm type: Equipment alarm
-24-
Maintenance Manual for ZXG10-BTS (V1A)
-
2.4.2.2Read/write error of the flash memory in the FU
Alarm code: 0xA0E
Alarm content: FLASH MEMORY error
Alarm level: 3
Alarm cause: Too many times of the FLASH programming, read/write error or the software
checksum error.
Influence of the alarm: The baseband processing unit fails to obtain the correct software version
from the flash memory, and the whole FU fails to work normally.
Time limit of handling: Handle it as soon as possible.
Handling process:
1. Reset the FU first to see whether the alarm can be recovered. If this alarm can be recovered, it
indicates this alarm is caused by external interference when the CPU reads the data from the flash
memory. This FU should be able to work normally after resetting.
2. If this alarm cannot be recovered by resetting, contact the regional office of ZTE Corporation as
soon as possible.
Alarm type: Equipment alarm
2.4.2.3Overflow of the watchdog in the FUC
Alarm code: 0xA18
Alarm content: Overflow of the WatchDog in the FUC.
Alarm level: 3
Alarm cause: The FUC program is out of service.
Influence of the alarm: No response of DSP or partial channels unavailable.
Time limit of handling: Handle it as soon as possible.
Handling process:
Chapter 2 Alarm Handling
-25-
-
1. Reset the FUC first to see whether this alarm can be recovered.
2. If this alarm cannot be recovered by resetting, contact the regional office of ZTE Corporation as
soon as possible.
Alarm type: Equipment alarm
2.4.2.4LAPD link disconnection of the FUC and the BSC
Alarm code: 0xA26
Alarm content: LAPD link disconnection of FU and BSC.
Alarm level: 3
Alarm cause: No connection between layer-2 software of the FUC and the BSC during a certain
period of time.
Influence of the alarm: This FUC fails to work. If this FUC is BCCH-TRX, services of the cell will
be affected.
Time limit of handling: Handle it as soon as possible.
Handling process:
1. Check whether this alarm occurs to other FUCs of this BS. If this alarm occurs to all FUCs of this
BS, check whether any alarm occurs to the BIE and whether the E1 line is connected properly, and
check whether any alarm occurs to the SMB, LAPD and DSN board of the BSC. If any, locate this
fault and clear it.
2. Check whether the BSC data is correct, especially the T network connection data and the SMB
timeslot connection data.
3. If only the LAPD of one layer TRU is disconnected, check whether the backplane cable is
connected properly.
4. If only the LAPD of one TRU is disconnected, reset the FUC.
5. If the problem still exists, please contact the regional office of ZTE Corporation.
Alarm type: Communication alarm
-26-
Maintenance Manual for ZXG10-BTS (V1A)
-
2.4.2.5Downlink check error between the FU and the CU
Alarm code: 0xB00
Alarm content: DLRC_AL downlink check error
Alarm level: 3
Alarm cause: Interference occurs to the link between the FU and CU.
Influence of the alarm: Numerous bit errors occur between CHP and CUI. The downlink is faulty,
and this TRU fails to provide normal conversation service.
Time limit of handling: Handle it at once.
Handling process:
1. Check whether the frequency-hopping cable on the backplane is connected properly. If not,
replace the frequency-hopping cable.
2. If the fault still exists, this TRU is faulty, please replace the board.
Alarm type: Equipment alarm
2.4.3Inconsistency of software versions
2.4.3.1Inconsistency of the channel processor (CHP) software versions
Alarm code: 0xA23
Alarm content: Inconsistency of the CHP software versions
Alarm level: 3
Alarm cause: Error loading of CHP software versions
Influence of the alarm: DSP fails to run normally over FU.
Time limit of handling: Handle it at once.
Handling process: Download a new CHP software version.
Alarm type: Error handling.
Chapter 2 Alarm Handling
-27-
-
2.4.3.2Inconsistency of the frame unit controller (FUC) software versions
Alarm code: 0xA24
Alarm content: Inconsistency of the FUC software versions
Alarm level: 3
Alarm cause: Error loading of FUC software versions
Influence of the alarm: FUC fails to run normally.
Time limit of handling: Handle it at once.
Handling process: Download a new FUC software version.
Alarm type: Error handling.
2.4.4Out-of-lock of the transmitting RF self oscillator
2.4.4.1Out-of-lock of the transmitting RF self oscillator 3
Alarm code: 0xB04
Alarm content: Out-of-lock of the transmitting RF self oscillator 3
Alarm level: 3
Alarm cause: Clock signal instability or TRU phrase-locked loop failure
Influence of the alarm: This TRU may fail to make a call.
Time limit of handling: Handle it at once.
Handling process: Replace the TRU.
Alarm type: Equipment alarm
2.4.4.2Out-of-lock of the transmitting RF self oscillator 4
Alarm code: 0xB05
Alarm content: Out-of-lock of the transmitting RF self oscillator 4
-28-
Maintenance Manual for ZXG10-BTS (V1A)
-
Alarm level: 3
Alarm cause: Clock signal instability or TRU phrase-locked loop failure
Influence of the alarm: This TRU may fail to make a call.
Time limit of handling: Handle it at once.
Handling process: Replace the TRU.
Alarm type: Equipment alarm
2.4.4.3Out-of-lock of the transmitting IF self oscillator 5
Alarm code: 0xB06
Alarm content: Out-of-lock of the transmitting IF self oscillator 5
Alarm level: 3
Alarm cause: Clock signal instability or TRU phrase-locked loop failure
Influence of the alarm: This TRU may fail to make a call.
Time limit of handling: Handle it at once.
Handling process: Replace the TRU.
Alarm type: Equipment alarm
2.4.5Error of software versions
2.4.5.1Error of the carrier unit (CU) software version
Alarm code: 0xB0F
Alarm content: The CU software version error
Alarm level: 3
Alarm cause: The CU software version error
Influence of the alarm: The CU fails to start normally, and this TRU cannot make a call.
Chapter 2 Alarm Handling
-29-
-
Time limit of handling: Handle it at once.
Handling process:
1. Reset TRU.
2. If the resetting fails, contact the regional office of ZTE Corporation to replace the CU version.
Alarm type: Error handling.
2.4.5.2Error of the BS clock unit (CKU) software version
Alarm code: 0xC0C
Alarm content: The CKU software version error
Alarm level: 3
Alarm cause: The CKU software version error
Influence of the alarm: This BS can operate normally but is unable to be maintained and monitored.
Time limit of handling: Handle it as soon as possible.
Handling process:
1. Reset the CKU to see whether this alarm can be recovered.
2. If this alarm cannot be recovered, contact the regional office of ZTE Corporation as soon as
possible.
Alarm type: Error handling.
2.4.5.3Error of the BS external alarm module (EAM) layer3 software version
Alarm code: 0xF2A
Alarm content: The EAM layer3 software version error
Alarm level: 3
Alarm cause: The layer3 software version error or communication error
Influence of the alarm: OMU fails to monitor the running of EAM, and in-cabinet alarms and those
-30-
Maintenance Manual for ZXG10-BTS (V1A)
-
of external backbone nodes.
Time limit of handling: Handle it as soon as possible.
Handling process:
1. Insert the board properly and reset it.
2. In case that the alarm persists, contact the regional office of ZTE Corporation to replace the
version.
Alarm type: Error handling.
2.4.6Fault of the BS clock unit (CKU)
2.4.6.1Alarm of error BS CKU frame numbers
Alarm code: 0xC01
Alarm content: The CKU frame numbers error
Alarm level: 3
Alarm cause: Discontinuity or loss of frame numbers
Influence of the alarm: This BS fails to run normally.
Time limit of handling: Handle it at once.
Handling process:
1. Reset the CKU, and view whether the alarm occurs again.
2. If the alarm cannot be recovered, replace the CKU.
Alarm type: Equipment alarm
2.4.6.2Error of the BS CKU parameter configuration
Alarm code: 0xC09
Alarm content: The CKU parameter configuration error
Alarm level: 3
Chapter 2 Alarm Handling
-31-
-
Alarm cause: Parameter configuration error
Influence of the alarm: This BS can operate normally but fails to be synchronous over the entire
network.
Time limit of handling: Handle it at once.
Handling process: Re-configure the CKU parameters on the background and make the CKU
parameters synchronous with the BS.
Alarm type: Error handling.
2.4.6.3Abnormality of the 8K clock signal between BS interface equipment (BIE) and CKU
Alarm code: 0xC0A
Alarm content: Abnormality of the 8K clock signal between BIE and CKU
Alarm level: 3
Alarm cause: Abnormality of the 8K clock signal between BIE and CKU
Influence of the alarm: This BS can operate normally but fails to be synchronous over the entire
network.
Time limit of handling: Handle it as soon as possible.
Handling process:
1. Reinsert the CKU board or reset the CKU board.
2. Check the operation of the BIE board or reset the BIE board.
3. Check the connection of the E1 cable.
4. If the alarm exists still, set the synchronization mode of the CKU to the free-run mode, and then
contact the regional office of ZTE Corporation.
Alarm type: Equipment alarm
-32-
Maintenance Manual for ZXG10-BTS (V1A)
-
2.4.7Fault of BIE switching chips
2.4.7.1Fault of the BIE switching chip 1
Alarm code: 0xD01
Alarm content: Fault of the BIE switching chip 1
Alarm level: 3
Alarm cause: Faulty chip or abnormal clock signal
Influence of the alarm: The conversation is abnormal, or links between a part of TRUs and BSC
cannot be established, or the system fails to start normally.
Time limit of handling: Handle it at once.
Handling process:
1. Insert the board properly and reset it.
2. If the alarm persists, it indicates that the D401 chip on the board may be out of order, replace the
board.
3. If the alarm still exists, the system clock may be abnormal, then reset the CKU.
4. In case that the alarm still exists, contact the regional office of ZTE Corporation .
Alarm type: Equipment alarm
2.4.7.2Fault of the BIE switching chip 2
Alarm code: 0xD02
Alarm content: Fault of the BIE switching chip 2
Alarm level: 3
Alarm cause: Faulty chip or abnormal clock signal
Influence of the alarm: The conversation is abnormal, or links between a part of TRUs and BSC
cannot be established, or the system fails to start normally.
Time limit of handling: Handle it at once.
Chapter 2 Alarm Handling
-33-
-
Handling process:
1. Insert the board properly and reset it.
2. If the alarm appears again, it indicates that the D402 chip on the board may be out of order,
replace the board.
3. If the alarm still exists, the system clock may be abnormal, then reset the CKU.
4. In case that the alarm still exists, contact the regional office of ZTE Corporation.
Alarm type: Equipment alarm
2.4.7.3Fault of the BIE switching chip 3
Alarm code: 0xD03
Alarm content: Fault of the BIE switching chip 3
Alarm level: 3
Alarm cause: Faulty chip or abnormal clock signal
Influence of the alarm: The conversation is abnormal, or links between a part of TRUs and BSC
cannot be established, or the system fails to start normally.
Time limit of handling: Handle it at once.
Handling process:
1. Insert the board properly and reset it.
2. If the alarm appears again, it indicates that the D403 chip on the board may be out of order,
replace the board.
3. If the alarm still exists, the system clock may be abnormal, then reset the CKU.
4. In case that the alarm still exists, contact the regional office of ZTE Corporation.
Alarm type: Equipment alarm
2.4.7.4Fault of the BIE switching chip 4
Alarm code: 0xD04
-34-
Maintenance Manual for ZXG10-BTS (V1A)
-
Alarm content: Fault of the BIE switching chip 4
Alarm level: 3
Alarm cause: Faulty chip or abnormal clock signal
Influence of the alarm: The conversation is abnormal, or links between a part of TRUs and BSC
cannot be established, or the system fails to start normally.
Time limit of handling: Handle it at once.
Handling process:
1. Insert the board properly and reset it.
2. If the alarm persists, it indicates that the D404 chip on the board may be out of order, replace the
board.
3. If the alarm still exists, the system clock may be abnormal, then reset the CKU.
4. In case that the alarm still exists, contact the regional office of ZTE Corporation.
Alarm type: Equipment alarm
2.4.8Faults of the BIE E1 interface
2.4.8.1Read/write fault of the BIE E1 interface chip 1
Alarm code: 0xD05
Alarm content: Read/write fault of the BIE E1 interface chip 1
Alarm level: 3
Alarm cause: Chip or communication failure
Influence of the alarm: The conversation is abnormal, or links between a part of TRUs and BSC
cannot be established, or the system fails to start normally.
Time limit of handling: Handle it at once.
Handling process:
1. Insert the board properly and reset it.
Chapter 2 Alarm Handling
-35-
-
2. If the alarm appears again, it indicates that the D101 chip on the board may be out of order,
replace the board.
3. In case that the alarm still exists, contact the regional office of ZTE Corporation.
Alarm type: Equipment alarm
2.4.8.2Read/write fault of the BIE E1 interface chip 2
Alarm code: 0xD06
Alarm content: Read/write fault of the BIE E1 interface chip 2
Alarm level: 3
Alarm cause: Chip or communication failure
Influence of th