ZEPHYR - TEKADOOR€¦ · Multilingual, menu-driven electronic control unit for TEKADOOR air...
Transcript of ZEPHYR - TEKADOOR€¦ · Multilingual, menu-driven electronic control unit for TEKADOOR air...
INDIVIDUALINNOVATIVEENERGY-SAVING
THE SHOP CLASSICZEPHYR EC
ZEPHYRZEPHYR
ZEPHYR
Attractive intake grillewith micro-intake grille behind it
Access panelwith hidden screws
+
+
+ Self-supporting sheet steelhigh-quality powder coated
ApplicationsZephyr EC is the classic model for use in shops. Installation-ready unit which can be used for many applications, with 4 installation variants. Free-hanging, flush with the ceiling as a cassette, installation in suspended ceilings with sliding supports, and, on request also available as a floor-mounted vertical unit.
The housingSelf-supporting sheet steel. Screws are not visible.High-quality powder coating, RAL 9016 as standard (traffic white). Other colours are available. Access panel hidden behind the intake grille. Aerodynamically-optimised aluminium dis-charge fin (naturally anodised), flush with the underside of the unit and adjustable in 5 stages. Perforated metal intake grille (same colour as the unit) with micro grille behind it as an intake filter.
Heating mediaHeat exchangers for different heating mediaLPHW – for normal temperature LPHW 70/50°C and low-tem-perature LPHW 60/40°C, other temperatures available on request. DX – DX register soldered under nitrogen for operation with heat pumps. High-quality heat exchanger made from copper tubes, with pressed-on, extra-strong aluminium fins. ELECTRO: Series M : Ceramic 400V PTC elements Series L: 3-stage heat exchanger 400V, spiral form, corrosion resistant, with thermal overheating protection and switch-off delay.
MaintenanceEasy to clean (micro grille) without opening the unitby simply vacuuming the intake grille. Discreet secured access panel hidden on the lower side of the unit (hinges on one side) – easy to open.
THE SHOP CLASSICZEPHYR EC
Discharge fincan be adjusted in 5 stages
+
2
Advantages at a glanceMade in Germany
ErP conform / EC fans
Certified by TÜV-Süd
Robust, self-supporting sheet steel
Individual colours available
4 installation variants
Individual unit lengths up to 3000 mm
Service friendly thanks to filterless micro-intake grille
Simple to install
Aerodynamically optimised discharge fin
Different heating media possible
+
+
+
+
+
+
+
++
+
+
EC fansThe efficiency of the EC fans used by TEKADOOR is > 90% under partial load operation. This is 30–35% higher than for conventional AC fans. This does not just increase the efficiency, but also reduces the operating costs. The individually-driven EC fans with integrated motor protection can intake air in both directions. They have vibration-free bearings and are controlled by a PWM signal (pulse width modulation) – and for the DX with 0-10 V. They do not just comply with Directive ErP, but actually exceed this standard.
MountingSimple mounting thanks to the rivet nuts (M8) incorporated on the upper side of the unit and optionally-available assembly materials. In the standard version, the unit does not need to be opened for electrical connection. Connection terminals for the voltage supply, as well as the connectors for the control unit and parallel operation can be accessed from the outside.
Control Electronic TEKADOOR GTC EC control unit, multifunctional with touch display, including an optional ModBus interface A GTC 1 EC control unit is used as standard for models with LPHW heating. A GTC E EC or a GTC PTC EC control unit is used for models with electrical heating. The units come with 20 m preassembled and shielded data cable. The GTC 1 EC 5-stage control unit includes the ability to switch from manual to automatic and from summer mode to winter mode as standard. A solenoid valve of up to 2.5 A can be connected as an option for the winter mode. With the standard GTC E EC control unit, the airflow can be selected manually in 5 stages and the heating capacity – depending on the fan level – can be selected manually in 3 stages. The GTC PTC EC control unit for PTC heating elements switches the heating level automatically to the preselected fan level. Each control unit includes a manual to automatic mode switch and a potential-free contact for enabling via any on-site BMS or BEMS. A choice of 5-stage or stepless fan operation is offered as standard.A maximum of 10 units can be connected in parallel. 3
Connections
Heating connections – flow and return - on top of the unit as standard for easy connection to the on-site heating system. Op-tionally, the connections can also be to move - top right or side
Connection box (LPHW)
Simple electrical connection via connection box (voltage supply 230V/50Hz on the top of the unit); Optionally, the connections can also be to move
Exception:Electrical units with a heating capacity greater than 22,5 kW.
DETAILSZEPHYR EC
4
Data cable connection/interface
Simple, standard plug and play connection of the data cable and an optional solenoid valve on the top side of the unit. The connection can be offset on request.
Control:Input for the data cable to the control unit.
Auxiliary:Output for parallel operation with other units.
Discharge fin
The shielding performance of the door air curtain system is opti-mised by adjusting the discharge fin. The fin can be adjusted in 5 stages. During the heating period, the discharge fin should be tilted outwards by 10 to 15 degrees to prevent cold air coming in from the outside. In contrast, during operation in the summer, the fin is tilted inwards, so that the cooled indoor air cannot escape.
5
ZEPHYR
ZEPHYR ECINSTALLATION VARIANTS
6
ZEPHYR
Free-hanging
A = VARIABLE UNIT LENGTH
FRONT VIEW
BOTTOM VIEW
SIDE VIEW
TOP VIEW
Connection-ready free-hanging door air curtain unit for visible installation directly above the door.Ambient air intake is at the front, on the room side.
* WE RESERVE THE RIGHT TO MAKE TECHNICAL CHANGES
Optional:side connections
connection box60
in
out
30
60
85
50
25
30
70
A
46035 295
Vorbereitung fürVerschraubung M 20
Platinein
out
Einnietmuttern M8
75 45
60100
40
260
Anschlussboxconnection box
provision for screwconnection 20 mm
circuit board
rivetting nut M8Attention! Measure will change for model Zephyr LX / LXX from 260 mm to 450 mm and from 460 mm to 715 mm and revetting nut M8 will change to M10.
**
*
*
7
ZEPHYR
Cassette
FRONT VIEW
BOTTOM VIEW
TOP VIEW
SIDE VIEW
* WE RESERVE THE RIGHT TO MAKE TECHNICAL CHANGES
Connection-ready door air curtain unit with integrated intake chamber on the underside and surrounding frame for installation flush with the ceiling. Ambient air intake is from the underside, on the room side. Freely accessible maintenance panel.
connection box
9 mm Langlochfür Befestigung
verschiebbar
80
50
M8
40
Befestigung nur bei über 2m GeräteM8 Einnietmutter unter der Lasche35
25
700
260
AA+50
LuftaustrittRevision
650
LuftaustrittRevision
OUT
IN
Platine
80
260
365390
12540
Vorberei-tungVerschrau-bung M20
DurchführungTemperatur-fühler
80700
MEASURE A:
950 mm
1450 mm
1950 mm
2450 mm
A = VARIABLE UNIT LENGTH
hidden fixing screw for inspection
prepared for using in a suspended ceiling
fitting for units bigger than 2m
9 mm long hole for fitting
movable
air outlet
air outlet
inspection panel
inspection panel
circuit board
provision for screw connection20 mm
performancefor temperaturesensor
Attention! Measure will change for model Zephyr Cassette LX / LXX from 260 mm to 440 mm and from 700 mm to 1270 mm and revetting nut M8 will change to M10.
*
8
ZEPHYR
Suspended ceiling unitFRONT VIEW
BOTTOM VIEW
TOP VIEW
SIDE VIEW
* WE RESERVE THE RIGHT TO MAKE TECHNICAL CHANGES
Connection-ready door air curtain unit with integrated intake chamber on the underside. Intake and discharge sliding supports for installation in a suspended ceiling. Only the intake and discharge grilles are visible from below. Ambient air intake is from the under-side, on the room side.CAUTION: The maintenance panel is on the underside of the unit. Therefore, it is essential that the suspended ceiling in which the unit is installed can be disassembled.
Optional:side connection
connection box
A = VARIABLE UNIT LENGTH
130-210
60
out
in
60
50
85
M25 + M20
351
26015
210 260 25
3020 20
75120
Verschraubung
A
720
35 295Vorbereitung für
Verschraubung M 20
Platine
Einnietmuttern M8
inout
75 50
60100
40Anschlussboxconnection box
circuit board
provision for screwconnection 20 mmrivetting nut M8
Attention! Measure will change for model Zephyr LX / LXX from 260 mm to 580 mm and from 720 mm to 1100 mm and revet-ting nut M8 will change to M10.
*
**
*
9
STANDARD CIRCUIT DIAGRAM FOR LPHW (PUMPED WARM WATER)
ZEPHYR EC
230V/ 50Hz
3
CONTROL
F 16 AT
L N PE
Platine EC
Anschlußbox
bauseitig
Erdung, Nullung oderSchutzschaltung nachden Vorschriften desVDE und des zuständ.EVU ausführen.
Technische Änderungen vorbehalten
Störun
g pot.
-frei
Betrie
b pot.
-frei
1 211 12 133 4 514 15
0
zum Steuerteil (CONTROL)Adresse 1-9
8
AUXILIARNL2 PE
230V / 50Hz
Magnetventil(OPTIONAL)
L PEN
8
PENL2
internAUX MON
07.03.2017lagezeichnet/signet
TeileGruppevonPos.
Werkstoff Maßstab
Blatt
Erstelldatum
GTM EC MOD Bus 170307Kunde
BenennungName
Kundenzeichnung Nr.:
DatumName
1 von 1
6 716 17 8 9 10 1918 20
CPU
AdressSchalter0 = MASTER1 - 9 = SLAVE
5
1 23
4
9
87 6
nicht
beleg
t
nicht
beleg
t
nicht
beleg
t
nicht
beleg
t
Fros
tschu
tzthe
rmos
tatop
tiona
l
Standard Anschlusskabel(20 m) mitRJ-45 Stecker
1M
PENL1
zu weiterenVentilatoren
blau/blue
gelb/yellow
weiss/white
rot/red
4
321
RJ 45
MOD Bus 1 2 3 4
ON
optio
nal
ext. S
ignalg
eber
DDC-
Fre
igab
e op
tiona
l
Y PWM
0 V
+10 V
imp.
ModBusinterface(optional)
230V/ 50Hz
3
CONTROL
F 16 AT
L N PE
PCB EC
Connecting box
Main switch and fusesto be installed by thirdparties must complyto all applicable rules andrequirements!
Technical changes reserved
1 211 12 133 4 514 15
0
to input (CONTROL) next PCBAddress 1-9
8
AUXILIARNL2 PE
230V / 50Hz
Magnetic valve(OPTIONAL)
L PEN
8
PENL2
internAUX MON
02.01.2019lagezeichnet/signet
TeileGruppevonPos.
Werkstoff Maßstab
Blatt
Erstelldatum
GTC I EC 190102Kunde
BenennungName
Kundenzeichnung Nr.:
DatumName
1 von 1
6 716 17 8 9 10 1918 20
CPU
Addressswitch0 = MASTER1 - 9 = SLAVE
5
1 23
4
9
87 6
ext. C
ontac
t
fault
Opera
tion
Fros
t prot
ectio
n the
rmos
tat
not u
sed
not u
sed
nicht
beleg
t
optio
nal
optio
nal
Standard suppledshielded datacable(20 m) withRJ-45 connectors
1M
PENL1
next Fan
blau/blue
gelb/yellow
weiss/white
rot/red
4
Room
temp.
sens
orop
tiona
l
Room temperature. Sensor installed
q
BMS
On/O
ff
Y 0-10 V
0 V
+10 V
imp.
Timeroff
Fr 21.09.201807:52
Heat level0 / 0
AutomaticHand
Room Temp10°C
Fan level0 / 0
CONTROL UNIT GTC 1 ECMultilingual, menu-driven electronic control unit for TEKADOOR air curtains with LPHW heating and energy-saving EC fans. A standard feature of the control unit with touch display is a choice between 5-stage or stageless fan control, which can be selected individually by the operator. The relevant operating modes and symbols are arranged clearly on the colour display. The date, time and room temperature are shown as standard. The room temperature is monitored via an internal temperature sensor in the control unit as standard.
An easy-to-navigate menu offers a selection of different operating modes:Hand – manual operationAuto AS – automatic operation via cool down protectionAuto RT – automatic operation via room temperatureAuto TK – automatic operation via door contactAuto Kombi – option to combine all individual automatic modes
An enabling contact and potential-free operation and malfunction signals are provided for control via an on-site BMS or BEMS. Errors and faults are displayed with a red „warning“ sign. By coding the control boards differently, up to 10 door air curtains can also be operated in parallel with 1 control unit, using the Master/Slave principle. The control board is preinstalled in the door air curtain unit and 20 m of preassembled data cable (connection between the door air curtain and control unit) are included as standard.
* WE RESERVE THE RIGHT TO MAKE TECHNICAL CHANGES
10
CIRCUIT DIAGRAM FOR ELECTRICAL HEAT EXCHANGER
ZEPHYR E EC
* WE RESERVE THE RIGHT TO MAKE TECHNICAL CHANGES
230V/ 50Hz
3
CONTROL
F 16 AT
L N PE
Platine EC
Anschlußbox
bauseitig
Erdung, Nullung oderSchutzschaltung nachden Vorschriften desVDE und des zuständ.EVU ausführen.
Technische Änderungen vorbehalten
Störun
g pot.
-frei
Betrie
b pot.
-frei
1 211 12 133 4 514 15
0
zum Steuerteil (CONTROL)Adresse 1-9
8
AUXILIARNL2 PE
230V / 50Hz
Magnetventil(OPTIONAL)
L PEN
8
PENL2
internAUX MON
07.03.2017lagezeichnet/signet
TeileGruppevonPos.
Werkstoff Maßstab
Blatt
Erstelldatum
GTM EC MOD Bus 170307Kunde
BenennungName
Kundenzeichnung Nr.:
DatumName
1 von 1
6 716 17 8 9 10 1918 20
CPU
AdressSchalter0 = MASTER1 - 9 = SLAVE
5
1 23
4
9
87 6
nicht
beleg
t
nicht
beleg
t
nicht
beleg
t
nicht
beleg
t
Fros
tschu
tzthe
rmos
tatop
tiona
l
Standard Anschlusskabel(20 m) mitRJ-45 Stecker
1M
PENL1
zu weiterenVentilatoren
blau/blue
gelb/yellow
weiss/white
rot/red
4
321
RJ 45
MOD Bus 1 2 3 4
ON
optio
nal
ext. S
ignalg
eber
DDC-
Fre
igab
e op
tiona
l
Y PWM
0 V
+10 V
imp.
ModBusinterface(optional)
GTM I PTC ECCircuit diagram for 400V PTC heating elements (only for M Series)
Blow
out T
emp s
enso
r
CONTROL
PCB EC
Technical changes reserved
1 211 12 133 4 514 15
0
to inputCONTROLnext PCB
8
AUXILIAR
8
AUX MON
02.01.2019Sagezeichnet/signet
TeileGruppevonPos.
Werkstoff Maßstab
Blatt
Erstelldatum
GTC E EC UK 190201Kunde
BenennungName
Kundenzeichnung Nr.:
DatumName
1 von 1
6 716 17 8 9 10 1918 20
CPU
Adressswitch0 = MASTER1 - 9 = SLAVE
5
1 23
4
9
87 6
Failu
re
Oper
ation
free
Standard supplied shielded datacable (20 m)1:1 straight wired RJ-45 Stecker
S 50°K1
K1 K2 K3
S 80°
S 60°
q q
q
q
K1
Connecting box
Mains switch and fusesto be installed by thirdparties must complyto all applicable rules andrequirements!
BMS
On/O
ff
1M
PENL1
nextFan
blau/blue
gelb/yellow
weiss/white
rot/red
optio
nal
4
free
step 2step 3 = step 1 + step 2
step 1
NL2 PE
PENL2intern
230V / 50Hz
K3 K2
230V/ 50Hz
3
3~400V/ 50Hz4
K0
q
ext.
Sign
alop
tiona
l
Fros
t the
rmos
tat
optio
nal
Room
Tem
p se
nsor
q q
Room temperature. Sensor installed
S 45°
YPWM
0 V
+10 V
imp.
L N PE31 2
S 100°
F 16 AT
Timeroff
Fr 21.09.201807:52
Heat level0 / 0
AutomaticHand
Room Temp10°C
Fan level0 / 0
CONTROL UNIT GTC E EC Multilingual, menu-driven electronic control unit for TEKADOOR air curtains with LPHW heating and energy-saving EC fans. 5-stage fan operation or stageless fan control – easy to adjust on the control unit using the touch display. The electric heater can be activated in 3 stages.The relevant operating modes and symbols are arranged clearly on the colour display. The date, time and room temperature are shown as standard. The room temperature is monitored via an internal temperature sensor in the control unit as standard. An easy-to-navigate menu offers a selection of different operating modes: Hand – manual operation Auto AS – automatic operation via cool down protection Auto RT – automatic operation via room temperature Auto TK – automatic operation via door contact Auto AT – automatic operation via constant discharge temperature Auto Kombi – option to combine all individual automatic modes An enabling contact and potential-free operation and malfunction signals are provided for control via an on-site BMS or BEMS. A constant discharge temperature can be set via an optional cable temperaturesensor. This enables optimisation of the shielding performance. A week timer is incorporated as standard, enabling up to 12 different switching times to be programmed per week. Errors and faults are displayed with a red „warning“ sign. By coding the control boards differently, up to 10 door air curtains can also be operated in parallel with 1 control unit, using the Master/Slave principle.The control board is preinstalled in the door air curtain unit and 20 m of preassembled data cable (connection between the door air curtain and control unit) are included as standard. 11
12
OPTIONAL ACCESSORIESZEPHYR EC
Thermostatic straight-way valve
(Setting range + 20 °C to + 35 °C) limits the discharge temperature (constant supply air temperature limitation). Also available as a 3-way valve.
Solenoid valve
Opens or closes the warm water circuit in the summer/winter setting of the control unit, in order to close the heating water circuit and save energy during summer operation or when the air curtain is not working (normally closed). Caution: If solenoid valves are used, it is expressly recommend-ed to install a frost protection thermostat (automatically actuat-ed) and a strainer.
Thermo-electric shut-off valve
230 V / 50 Hz, normally closed.On-site installation in theheating flow. Actuated bythe summer/ winter circuit. Summer function – closed. Winter function – opened.
Ceiling attachment set
For problem-free, vibration free ceiling attachment, consisting of M8 or M10 threaded rods, up to 1000 mm length, vibration dampers, turnbuckles and coun-ter nuts.
13
Frost protectionthermostat
For monitoring LPHW heat exchangers exposed to the risk of frost. As soon as the temper-ature falls below +7 °C, the fans are switched off and an optional solenoid valve is opened.
Control unitGTC 2 EC
Possibility of combination of various automatic operations. A constant discharge tempera-ture can be set via an optional electronic control valve, and a week timer is incorporated as standard, enabling up to 12 different switching times to be programmed per week.
Electronic control valve
Electronic valve with 0-10V im-pulse and blow-out temperature sensor completely installed and wired. In combi-nation with the GTC 2 control, a preselected blow-out tempera-ture is kept constant.
Door contact solenoid switch
In automatic mode switches on the door air curtain in the preselected stage
TECHNICAL DATAFREE HANGING / CASSETTE SUS-PENDED CEILING
ZEPHYR EC M
Model M 1 M 1.5 M 2 M 2.5 M 3
Air quantity max: m3/h 1800 2700 3600 4500 6300
Heating capacity rated1 LPHW 70 / 50 °C kW 8.5 12.7 17.0 21.2 29.7
LPHW 60 / 40 °C kW 8.5 12.7 17.0 21.2 29.7
Flow rate LPHW 70 / 50 °C m3/h 0.37 0.56 0.75 0.93 1.30
LPHW 60 / 40 °C m3/h 0.37 0.55 0.74 0.92 1.29
Water resistance LPHW 70 / 50 °C kPa 0.5 5.7 2.4 3.2 5.6
LPHW 60 / 40 °C kPa 3.8 7.0 4.5 3.2 5.6
Nominal connection sizes Internal thread Inches 2 x 3/4" 2 x 3/4" 2 x 3/4" 2 x 3/4" 2 x 3/4"
Flow/return DN 20 20 20 20 20
EC fans Voltage V 230 / 1 / N / PE
Frequency Hz 50
Max. current consump-tion
A 2.1 3.1 4.1 5.1 7.2
Max. motor power kW 0.3 0.5 0.6 0.8 0.9
400 V PTC Electric heater Voltage V 400 / 3 / N / PE
Frequency Hz 50
Heating capacity kW 7 10,5 14 17,5 on request
Sound pressure level 2 Highest setting dB (A) 58 59 60 61 62
Drawing dimension Unit length ( A ) mm 1000 1500 2000 2500 3000
Unit height 3 mm 260 260 260 260 260
Unit depth 4 mm 490 490 490 490 490
Weight Zephyr kg 45 60 75 80 100
Cassette kg 52 70 88 97 120
Zephyr-Z kg 62 85 107 122 149
Design based on: recommended operating pointIntake temperature tLE = +20 °C
Discharge temperature tLA = +34 °CDischarge height = up to 2.70 m
1. Rated operation based on operating point (see above), discharge temperature control recommended.2. measured at a lateral distance of 3 m. Sound pressure level may very depending on surrounding conditions.3. For the Zephyr Z (suspended ceiling version), this dimension changes to 390–470 mm.4. For the Zephyr Z this dimension changes to 720 mm and to 700 mm for the cassette (ceiling-flush version).
A well-balanced pressure ratio is one of the prerequisites for perfect function.
* WE RESERVE THE RIGHT TO MAKE TECHNICAL CHANGES
14
TECHNICAL DATAFREE HANGING / SUSPENDED CEILING
ZEPHYR EC L
Model L 1 L 1.5 L 2 L 2.5 L 3
Air quantity max: m3/h 2700 3600 5400 6300 7200
Heating capacity rated1
LPHW 70 / 50 °C kW 12.7 17.0 25.5 29.7 34.0
LPHW 60 / 40 °C kW 12.7 17.0 25.5 29.7 34.0
Flow rate LPHW 70 / 50 °C m3/h 0.56 0.75 1.11 1.31 1.49
LPHW 60 / 40 °C m3/h 0.55 0.74 1.11 1.29 1.48
Water resistance LPHW 70 / 50 °C kPa 0.8 2.8 3.7 5.2 7.2
LPHW 60 / 40 °C kPa 1.7 3.7 4.2 6.1 7.2
Nominal connection sizes
Internal thread Inches 2 x 3/4" 2 x 3/4" 2 x 3/4" 2 x 3/4" 2 x 3/4"
Flow/return DN 20 20 20 20 20
EC fans Voltage V 230 / 1 / N / PE
Frequency Hz 50
Max. current consump-tion
A 3.1 4.1 6.2 7.2 8.2
Max. motor power kW 0.5 0.6 0.9 1.1 1.2
Electric heater3-stage
Voltage V 400 / 3 / N / PE
Frequency Hz 50
Heating capacity kW 5//10/15 7,5/15/22,5 10/20/30 10,7/21,4/32 10,7/21,4/32
Sound pressure level 2 Highest setting dB (A) 60 61 62 63 64
Drawing dimension Unit length ( A ) mm 1000 1500 2000 2500 3000
Unit height 3 mm 260 260 260 260 260
Unit depth 4 mm 490 490 490 490 490
Weight Zephyr kg 50 65 80 105 125
Cassette kg 57 75 93 122 145
Zephyr-Z kg 67 90 112 147 174
Design based on: recommended operating pointIntake temperature tLE = +20 °C
Discharge temperature tLA = +34 °CDischarge height = up to 3.00 m
1. Rated operation based on operating point (see above), discharge temperature control recommended.2. measured at a lateral distance of 3 m. Sound pressure level may very depending on surrounding conditions.3. For the Zephyr Z (suspended ceiling version), this dimension changes to 390–470 mm.4. For the Zephyr Z this dimension changes to 720 mm and to 700 mm for the cassette (ceiling-flush version).
A well-balanced pressure ratio is one of the prerequisites for perfect function.
* WE RESERVE THE RIGHT TO MAKE TECHNICAL CHANGES
15
TECHNICAL DATAFREE HANGING / SUSPENDED CEILING
ZEPHYR EC LX
Model LX 1 LX 1.5 LX 2 LX 2.5 LX 3
Air quantity max: m3/h 4500 5100 7300 9800 12000
Heating capacity rated1
LPHW 70 / 50 °C kW 21.2 24.0 34.4 46.2 56.6
LPHW 60 / 40 °C kW 21.2 24.0 34.4 46.2 56.6
Flow rate LPHW 70 / 50 °C m3/h 0.93 1.05 4.51 2.02 2.48
LPHW 60 / 40 °C m3/h 0.92 1.05 1.50 2.01 2.47
Water resistance LPHW 70 / 50 °C kPa 4.5 4.1 9.1 4.4 6.9
LPHW 60 / 40 °C kPa 3.2 4.1 3.7 4.5 7.0
Nominal connection sizes
Internal thread Inches 2 x 1“ 2 x 1" 2 x 1" 2 x 1" 2 x 1"
Flow/return DN 25 25 25 25 25
EC fans Voltage V 230 / 1 / N / PE
Frequency Hz 50
Max. current consump-tion
A 6.0 6.5 9.1 12.1 15.0
Max. motor power kW 1.1 1.4 2.1 2.7 3.5
Sound pressure level 2 Highest setting dB (A) 64 63 64 65 67
Drawing dimension Unit length ( A ) mm 1000 1500 2000 2500 3000
Unit height 3 mm 450 450 450 450 450
Unit depth 4 mm 715 715 715 715 715
Weight Zephyr kg 85 105 145 180 225
Cassette kg 97 123 168 213 260
Zephyr-Z kg 102 130 177 222 274
Design based on: recommended operating pointIntake temperature tLE = +20 °C
Discharge temperature tLA = +34 °CDischarge height = up to 3.20 m
1. Rated operation based on operating point (see above), discharge temperature control recommended.2. measured at a lateral distance of 3 m. Sound pressure level may very depending on surrounding conditions.3. For the Zephyr Z-LX/LXX (suspended ceiling version), this dimension changes to 580-680 mm.4. For the Zephyr Z-LX/LXX this dimension changes to 1100 mm.
A well-balanced pressure ratio is one of the prerequisites for perfect function.
* WE RESERVE THE RIGHT TO MAKE TECHNICAL CHANGES
16
TECHNICAL DATAFREE HANGING / SUSPENDED CEILING
ZEPHYR EC LXX
Model LXX 1 LXX 1.5 LXX 2 LXX 2.5 LXX 3
Air quantity max: m3/h 4900 7300 9800 12000 14200
Heating capacity rated1
LPHW 70 / 50 °C kW 23.1 34.4 46.2 56.6 67.0
LPHW 60 / 40 °C kW 23.1 34.4 46.2 56.6 67.0
Flow rate LPHW 70 / 50 °C m3/h 1.01 1.51 2.02 4.48 2.93
LPHW 60 / 40 °C m3/h 1.01 1.50 2.01 4.45 2.92
Water resistance LPHW 70 / 50 °C kPa 1.3 2.9 7.9 7.8 9.6
LPHW 60 / 40 °C kPa 3.8 2.4 4.7 7.8 9.7
Nominal connection sizes
Internal thread Inches 2 x 1 1/4" 2 x 1 1/4" 2 x 1 1/4" 2 x 1 1/4“ 2 x 1 1/4"
Flow/return DN 32 32 32 32 32
EC fans Voltage V 230 / 1 / N / PE
Frequency Hz 50
Max. current consump-tion
A 6.1 9.1 12.1 15.2 18.2
Max. motor power kW 1.4 2.1 2.8 3.5 4.1
Sound pressure level 2 Highest setting dB (A) 63 64 65 66 68
Drawing dimension Unit length ( A ) mm 1000 1500 2000 2500 3000
Unit height 3 mm 450 450 450 450 450
Unit depth 4 mm 715 715 715 715 715
Weight Zephyr kg 100 130 180 210 250
Cassette kg 112 148 203 238 285
Zephyr-Z kg 117 155 212 252 299
Design based on: recommended operating pointIntake temperature tLE = +20 °C
Discharge temperature tLA = +34 °CDischarge height = up to 3.60 m
1. Rated operation based on operating point (see above), discharge temperature control recommended.2. measured at a lateral distance of 3 m. Sound pressure level may very depending on surrounding conditions.3. For the Zephyr Z-LX/LXX (suspended ceiling version), this dimension changes to 580-680 mm.4. For the Zephyr Z-LX/LXX this dimension changes to 1100 mm.
A well-balanced pressure ratio is one of the prerequisites for perfect function.
* WE RESERVE THE RIGHT TO MAKE TECHNICAL CHANGES
17
Model DX-M 1 DX-M 1.5 DX-M 2 DX-M 2.5 DX-M 3
Air quantity max: m3/h 1800 2700 3600 4500 6300
Power 1 DX heating capacity kW 8.6 12.9 17.3 21.3 29.9
DX cooling capacity kW 8.1 12.5 16.9 21.3 29.9
Delivery and intake line Connections mm 10/16 10/16 10/18 10/22 10/22
EC fans 3 Voltage V 230 / 1 / N / PE
Frequency Hz 50
Max. current consump-tion
A 2.4 3.6 4.7 5.9 8.2
Max. motor power kW 0.3 0.5 0.7 0.8 1.2
Sound pressure level 2 Highest setting dB (A) 58 59 60 61 62
Drawing dimension Unit length ( A ) mm 1210 1710 2210 2710 3210
Unit height mm 260 260 260 260 260
Unit depth mm 490 490 490 490 490
Weight Zephyr DX kg 50 65 80 85 105
Cassette kg 57 75 93 102 125
Zephyr Z kg 67 92 112 127 154
ZEPHYR-DX M EC
Design based on:
recommended operating pointintake temperature = +20/27 °Cdischarge temperature = +34/18 °Cdischarge height = up to 2.70 m
heating gas temperature = 70 °Ccondensation temperature = 50 °Ccondensate exit temp. = 45 °Coperating pressure = max. 45bar
TECHNICAL DATAFREE HANGING/CASSETTE / SUSPENDED CEILING
1. Rated operation based on operating point (see above).2. measured at a lateral distance of 3 m. Sound pressure level may very depending on surrounding conditions.3. Control voltage 0-10 V.4. Only heating modus possible.
WARNING: in cooling mode the discharge temperature must not fall below 18 °C and the intake temperature must not rise above 27 °C! If these parameters are not adhered to, a higher level of condensate will form which cannot be re-moved by our optional condensate pump!
A well-balanced pressure ratio is one of the prerequisites for perfect function.
* WE RESERVE THE RIGHT TO MAKE TECHNICAL CHANGES
460
260
105
460
260
105
BOTTOM VIEW SIDE VIEW
rivetting nut M8
space for control (on site)
cable penetration
18
TECHNICAL DATAFREE HANGING/CASSETTE / SUSPENDED CEILING
ZEPHYR-DX L EC
Model DX-L 1 DX-L 1.5 DX-L 2 DX-L 2.5 DX-L 3
Air quantity max: m3/h 2700 3600 5400 6300 7200
Power 1 DX heating capacity kW 12.7 17.0 25.7 29.6 34
DX cooling capacity kW 12 16.6 25.2 29.7 34.2
Delivery and intake line Connections mm 10/16 10/18 10/22 10/22 10/22
EC fans 3 Voltage V 230 / 1 / N / PE
Frequency Hz 50
Max. current consump-tion
A 3.5 4.7 7.1 8.2 9.4
Max. motor power kW 0.5 0.7 1.0 1.2 1.4
Sound pressure level 2 Highest setting dB (A) 60 61 62 63 64
Drawing dimension Unit length ( A ) mm 1210 1710 2210 2710 3,210
Unit height mm 260 260 260 260 260
Unit depth mm 490 490 490 490 490
Weight Zephyr DX kg 55 65 85 110 130
Cassette kg 62 80 98 127 150
Zephyr Z kg 72 95 117 152 179
Design based on:
recommended operating pointintake temperature = +20/27 °Cdischarge temperature = +34/18 °Cdischarge height = up to 3.00 m
heating gas temperature = 70 °Ccondensation temperature = 50 °Ccondensate exit temp. = 45 °Coperating pressure = max. 45bar
1. Rated operation based on operating point (see above).2. measured at a lateral distance of 3 m. Sound pressure level may very depending on surrounding conditions.3. Control voltage 0-10 V.4. Only heating modus possible.
WARNING: in cooling mode the discharge temperature must not fall below 18 °C and the intake temperature must not rise above 27 °C! If these parameters are not adhered to, a higher level of condensate will form which cannot be re-moved by our optional condensate pump!
A well-balanced pressure ratio is one of the prerequisites for perfect function.
* WE RESERVE THE RIGHT TO MAKE TECHNICAL CHANGES