Zelio and Altivar Pushbuttons and Lights System User … Automatyka przemyslowa/Aplikacje... ·...

20
Zelio and Altivar Pushbuttons and Lights System User Guide 33003483.01

Transcript of Zelio and Altivar Pushbuttons and Lights System User … Automatyka przemyslowa/Aplikacje... ·...

Page 1: Zelio and Altivar Pushbuttons and Lights System User … Automatyka przemyslowa/Aplikacje... · Zelio and Altivar Pushbuttons and Lights System User ... Also the tool can help in

Zelio and Altivar Pushbuttons and Lights

System User Guide

3300

3483

.01

Page 2: Zelio and Altivar Pushbuttons and Lights System User … Automatyka przemyslowa/Aplikacje... · Zelio and Altivar Pushbuttons and Lights System User ... Also the tool can help in

Zelio and Altivar Pushbuttons and Lights_EN.doc - Oct-04

Schneider Electric

1

Table of Content

Typical Applications ...............................................................................................................3 System .....................................................................................................................................4

Architecture.............................................................................................................................4 Installation...............................................................................................................................5

Hardware.............................................................................................................................................................6 Software ..............................................................................................................................................................8 Communication ...................................................................................................................................................8

Implementation .......................................................................................................................9 HMI ....................................................................................................................................................................10 PLC....................................................................................................................................................................10 Devices..............................................................................................................................................................13

Addendum .............................................................................................................................15 Detailed Component list........................................................................................................15 Component Features ............................................................................................................16

Contact ..................................................................................................................................19

Introduction This document is intended to provide a quick introduction to the described System.

It is not intended to replace any specific product documentation. On the contrary, it offers additional information to the product documentation, for installing, configuring and starting up the system. A detailed functional description or the specification for a specific user application is not part of this document. Nevertheless, the document outlines some typical applications where the system might be implemented.

Page 3: Zelio and Altivar Pushbuttons and Lights System User … Automatyka przemyslowa/Aplikacje... · Zelio and Altivar Pushbuttons and Lights System User ... Also the tool can help in

Zelio and Altivar Pushbuttons and Lights_EN.doc - Oct-04

Schneider Electric

2

Abbreviations

Word / Expression Signification PLC Programmable Logic Controller HMI Human Machine Interface VVD Variable Velocity Drive PC Personal Computer AC Alternating current DC Direct current PS Power supply I/O Input / Output CB Circuit Breaker ESTOP Emergency Stop Zelio Family product name for a Schneider midrange PLC Phaseo Family product name for Schneider power supply devices Altivar Family product name for Schneider VVD devices Telefast Family product name for the Schneider distributed I/O devices

Page 4: Zelio and Altivar Pushbuttons and Lights System User … Automatyka przemyslowa/Aplikacje... · Zelio and Altivar Pushbuttons and Lights System User ... Also the tool can help in

Zelio and Altivar Pushbuttons and Lights_EN.doc - Oct-04

Schneider Electric

3

Typical Applications

Introduction Typical applications or sub-applications which use systems as outlined in the

following chapters are seen in the following market sectors: Industry • Small machinery automation systems • Decentralised automation systems supplementary to large and medium size

machinery Buildings/Services • Lighting management • Access, control and surveillance management • Heating and air conditioning management

Application Description Example Mobile Pump Station The application controls the

filling or emptying of fluid tanks. With a VVD the speed of pumping is adjustable and , allows for adaptation based on the fluidity of the liquid and the volume of the tank.

Control of a roll gate The application allows opening and closing of gates protecting the entry of a plant or cordonned off area.

Window mover in a greenhouse

The application regulate sthe air conditioning in a greenhouse.

Page 5: Zelio and Altivar Pushbuttons and Lights System User … Automatyka przemyslowa/Aplikacje... · Zelio and Altivar Pushbuttons and Lights System User ... Also the tool can help in

Zelio and Altivar Pushbuttons and Lights_EN.doc - Oct-04

Schneider Electric

4

System

Introduction The system chapter describes the architecture, the components, the dimensions and

the number of components used within this system.

Architecture

Overview The system is built up with a low end PLC with pushbutton control and visualization via

pilot lights and illuminated beacon to control a connected VVD – AC motor unit. Safety protection is provided in the form of an emergency stop and a mains switch. All application variables (time, speed or control logic) can be changed by the integrated PLC or VVD panel.

Layout

Components Hardware:

• ZELIO Logic Compact (PLC) • Phaseo power supply (PS) • Altivar ATV 11 (VVD) • Tesys circuit breaker GV2 (CB) • Harmony Style 5 pushbutton XB5 (PB), pilot light XB5 (PL) and emergency stop • Illuminated beacon Style XVB (LT) • Vario switch-disconnect VCF • Standard AC-Motor Software: • Zeliosoft Version 2.0 • PowerSuite Version 1.5

Numbers of Components

For this stand-alone application you require only one of each component.

Dimension The compact size of the PLC, power supply, and ATV11 allows the use cabinet with

a size of 300x200x200mm (BxHxW). The pushbuttons and pilot lights can be integrated into the front door of the cabinet.

Page 6: Zelio and Altivar Pushbuttons and Lights System User … Automatyka przemyslowa/Aplikacje... · Zelio and Altivar Pushbuttons and Lights System User ... Also the tool can help in

Zelio and Altivar Pushbuttons and Lights_EN.doc - Oct-04

Schneider Electric

5

Installation

Introduction This chapter describes the steps necessary to install the hardware and to setup the

software to attain the following application architecture.

Layout

Page 7: Zelio and Altivar Pushbuttons and Lights System User … Automatyka przemyslowa/Aplikacje... · Zelio and Altivar Pushbuttons and Lights System User ... Also the tool can help in

Zelio and Altivar Pushbuttons and Lights_EN.doc - Oct-04

Schneider Electric

6

Hardware

General • All devices, with the exception of the GV2 circuit breaker can be mounted on the

rear wall of the cabinet.

• The GV2 needs a DIN rail for mounting.

• The illuminated beacon is delivered as single parts. The user has to assemble the beacon before installation. This allows the user to define the position of the different coloured elements.

• There are two possibilities for mounting the XB5 pushbutton or pilot light. In the 1st case, the user drills a 22mm hole in the correct position in the front side of the cabinet. The 2nd case is to mount the parts in an XALD housing which can take up to 5 push buttons or lights. The XALD could also be mounted on a surface on or in the cabinet.

• Mainly need of M5*18mm screws and nuts and 35mm DIN rail for fixing

• 230VAC wiring between main switch, emergency stop and VVD

• 24VDC wiring between power supply, PLC, pushbutton, light and control circuits of the VVD

Main switch VCF-02GE

Emergency Stop

XALK174G

Power supply ABL7RM24011

Page 8: Zelio and Altivar Pushbuttons and Lights System User … Automatyka przemyslowa/Aplikacje... · Zelio and Altivar Pushbuttons and Lights System User ... Also the tool can help in

Zelio and Altivar Pushbuttons and Lights_EN.doc - Oct-04

Schneider Electric

7

Zelio Logic SR2121BD

Motor protection

GV2-M08

VVD

Altivar ATV11HU18M2E

Illuminated Beacon XVB

Page 9: Zelio and Altivar Pushbuttons and Lights System User … Automatyka przemyslowa/Aplikacje... · Zelio and Altivar Pushbuttons and Lights System User ... Also the tool can help in

Zelio and Altivar Pushbuttons and Lights_EN.doc - Oct-04

Schneider Electric

8

Software

General To implement the system a user does not necessarily need a software tool.

The Zelio Logic CPU and the Altivar 11 can be started or programmed using the front panel on both devices. However, for more comfort and the possibility of data storage, simulation and multiple usage of the application it is recommended that you install and use Zeliosoft to configure the PLC and / or PowerSuite for the VVD. Your PC needs to have a Microsoft Windows operating system installed - either Windows 98, Windows 2000, or Windows NT. To start the installation, place the CDs in the CD or DVD drive of your PC. The CDs usually starts automatically due to the "Auto-Start" functionality of the PC. Please follow the installation routine. In case of problems please check the installation guidelines delivered with the product. The Software installation path on your harddisk is by default: • Zeliosoft \Program Files\Schneider Electric\Zeliosoft

• PowerSuite \Program Files\Schneider Electric\PowerSuite

Communication

General This is a hardwired configuration with no communication via bus system.

The HMI functionality is implemented using pushbuttons and pilot lights.

Page 10: Zelio and Altivar Pushbuttons and Lights System User … Automatyka przemyslowa/Aplikacje... · Zelio and Altivar Pushbuttons and Lights System User ... Also the tool can help in

Zelio and Altivar Pushbuttons and Lights_EN.doc - Oct-04

Schneider Electric

9

Implementation

Introduction The implementation chapter describes all steps necessary to initialize, parameterize,

program and to start-up the system.

Function Functional description

1. Use the left or right pushbutton to select the direction of rotation.

2. Press ON to start the motor with the selected direction of rotation.

3. If you select the opposite direction of rotation while the motor is running, the

speed drops to zero before the motor changes to the new direction.

4. With the push button OFF the motor stops.

Page 11: Zelio and Altivar Pushbuttons and Lights System User … Automatyka przemyslowa/Aplikacje... · Zelio and Altivar Pushbuttons and Lights System User ... Also the tool can help in

Zelio and Altivar Pushbuttons and Lights_EN.doc - Oct-04

Schneider Electric

10

HMI

Introduction No HMI was implemented in this application.

PLC

Introduction The PLC section describes the different steps needed to initialize, parameterize and

program the PLC logic to fulfill the above description of the system functionality. The user application is written with the Zeliosoft tool.

When you start the Zeliosoft software for the first time, you are shown the welcome screen with choices to generate a new program or to work on an existing program. For a new PLC application select “new program”. You are shown the screen to select the Zelio modules - presented with their pictures. Please select your PLC then select the correct module type reference shown in the list in the lower half of the screen.

After selecting the appropriate module you can choose the programming language. The PLC logic can be written in two different programming languages: Ladder or FBD.

Page 12: Zelio and Altivar Pushbuttons and Lights System User … Automatyka przemyslowa/Aplikacje... · Zelio and Altivar Pushbuttons and Lights System User ... Also the tool can help in

Zelio and Altivar Pushbuttons and Lights_EN.doc - Oct-04

Schneider Electric

11

In our example we use FBD (Function Block Derived). The example shows the FBD screen including the logic program for this example.

Before you can transfer the logic program to the PLC, you have to configure the communication port of the PC. Open the menu “communication setup” under “Transfer” in the toolbar. The COM-port 1 and 3 are selectable. If you have connected the Zelio programming cable to the PC and the Zelio Logic controller you can test the connection with the Test button in the Port configure menu.

Page 13: Zelio and Altivar Pushbuttons and Lights System User … Automatyka przemyslowa/Aplikacje... · Zelio and Altivar Pushbuttons and Lights System User ... Also the tool can help in

Zelio and Altivar Pushbuttons and Lights_EN.doc - Oct-04

Schneider Electric

12

The logic program can be transferred to the controller now. Use the menu “Transfer – Transfer Program- PC Module.

Before you set the PLC in running mode, read the safety instructions for your system. After a successful transfer you can start the Zelio Logic controller. Select: Transfer-> RUN Module.

Page 14: Zelio and Altivar Pushbuttons and Lights System User … Automatyka przemyslowa/Aplikacje... · Zelio and Altivar Pushbuttons and Lights System User ... Also the tool can help in

Zelio and Altivar Pushbuttons and Lights_EN.doc - Oct-04

Schneider Electric

13

Devices

Introduction The devices section describes the different steps needed to initialize and

parameterize the device logic/behaviour to fulfill the described system functionality. The devices are initialized and parameterized using the Powersuite tool.

General The ATV 11 can be programmed using the front panel. The advantage of using the

PowerSuite software tool is to have the data storage on PC and the possibility to print out the documentation. Also the tool can help in online optimization of the parameters.

1st PowerSuite screen after program start: After reading the instructions press “Alt+F” to continue .

Select the device ATV 11 for our application example.

Select the exact device type of ATV 11 according to the catalog number for our application example.

Page 15: Zelio and Altivar Pushbuttons and Lights System User … Automatyka przemyslowa/Aplikacje... · Zelio and Altivar Pushbuttons and Lights System User ... Also the tool can help in

Zelio and Altivar Pushbuttons and Lights_EN.doc - Oct-04

Schneider Electric

14

Parameterizing the AC-Motor - for our example use the default settings.

After this procedure you can store the settings on the PC. Use the icon with the disk symbol. Check and establish the connection between the PC and the Altivar

Transfer the settings to the Altivar. Use the menu: Link->Transfer File.

Page 16: Zelio and Altivar Pushbuttons and Lights System User … Automatyka przemyslowa/Aplikacje... · Zelio and Altivar Pushbuttons and Lights System User ... Also the tool can help in

Zelio and Altivar Pushbuttons and Lights_EN.doc - Oct-04

Schneider Electric

15

Addendum

Detailed Component list

Type / Software Revision/Version • ZELIO Logic Compact – SR2PACBD (PLC + Zeliosoft

+ Programming cable) • PowerSuite V2.0 - VW3A8104 • Phaseo power supply - ABL7RM2401 (PS) • Altivar ATV11 - ATV11HU18M2E (VVD) • ATV Connection Kit -VW3A8106 (cable) • Harmony Style 5 pushbuttonXB5AA3311 - green (PB) • Harmony Style 5 pushbuttonXB5AA3341 - white (PB) • Harmony Style 5 pushbuttonXB5AA3351 - black (PB) • Harmony Style 5 pushbuttonXB5AA4322 - red (PB) • Harmony Style 5 pilot light XB5AVB3 – green (PL) • Harmony Style 5 pilot light XB5AVB4 – red (PL) • Harmony Style 5 pilot light XB5AVB5 – orange (PL) • Harmony Style 5 pilot light XB5AVB6 – blue (PL) • Harmony Style 5 case XALD04H7 – for PB+PL • Illuminated beacon Style XB5AVB3 – green (LT) • Illuminated beacon Style XB5AVB4 – red (LT) • Illuminated beacon Style XB5AVB5 – orange (LT) • Illuminated beacon fixing bracket – XVBC12 (LT) • Illuminated beacon Unit base + cover – XVBC21 (LT) • Vario switch- disconnector VCF02GE – main switch • Harmony Style 5 emergency stop XALK174G (ESTOP) • Tesys circuit breaker GV2ME08 (CB) • Standard AC-Motor.

ALTEUM0040001 - 0,75Kw, 4-pol Form TE80 230VAC single phase

Optional: • SR-EEPROM Card - SR2ME01

Zelio Soft Powersuite Altivar 11

V2.0.7 V1.50

Page 17: Zelio and Altivar Pushbuttons and Lights System User … Automatyka przemyslowa/Aplikacje... · Zelio and Altivar Pushbuttons and Lights System User ... Also the tool can help in

Zelio and Altivar Pushbuttons and Lights_EN.doc - Oct-04

Schneider Electric

16

Component Features

Features PLC Zelio Logic: Zelio Logic Compact - SR1B121BD (Package including Software and Hardware): • 24VDC • 8 digital Input /4 Relay Output, • Front panel for Ladder and FBD programming no PC required or by using

Zeliosoft Software on a PC.

Page 18: Zelio and Altivar Pushbuttons and Lights System User … Automatyka przemyslowa/Aplikacje... · Zelio and Altivar Pushbuttons and Lights System User ... Also the tool can help in

Zelio and Altivar Pushbuttons and Lights_EN.doc - Oct-04

Schneider Electric

17

Features ctd. PLC Zelio ZelioSoft Functions - Ladder: • User-friendliness of the "free input" mode: LADDER or electrical symbols

• 120 rungs

• 5 contacts + 1 coil per programming line

16 textfunctionblocks,

16 timers,

16 up/downcounters,

1 fast counter,

16 analoguecomparators,

28 auxiliary relays,

8 counter comparators,

LCD screen with programmableback-lighting,

Automatic 1 hour clock change:summer/winter,

Diversity of coil functions; withmemory (set/reset), remoteswitch, contactor.

Zelio Soft Functions - FBD:

Page 19: Zelio and Altivar Pushbuttons and Lights System User … Automatyka przemyslowa/Aplikacje... · Zelio and Altivar Pushbuttons and Lights System User ... Also the tool can help in

Zelio and Altivar Pushbuttons and Lights_EN.doc - Oct-04

Schneider Electric

18

Features ctd.

Power supply Phaseo: ABL7RM2401 • 240VAC / 24 VDC

• 1,3 A

VVD Altivar : ATV11 HU18M2E • 0.75KW ,230VAC single phase

• Temperature range :- 10 ... + 50°C

• Speed range from 1 to 20 (0...200 Hz)

• Speed regulation by flux vector control

• Protection of drive and motor

• Compact, side by side mounting , DIN rail mounting possible

• Integrated class B EMC filter Circuit breaker : GV2ME08 • 2,5...4A

• Thermic and 51A magnetic tripping

Page 20: Zelio and Altivar Pushbuttons and Lights System User … Automatyka przemyslowa/Aplikacje... · Zelio and Altivar Pushbuttons and Lights System User ... Also the tool can help in

Schneider Electric GmbH Steinheimer Strasse 117 D - 63500 Seligenstadt Germany

Zelio and Altivar Pushbuttons and Lights_EN.doc

As standards, specifications and design change from time to time, please ask for confirmation of the information given in this publication

19

Contact

Author Telephone E-Mail Schneider Electric GmbH Customer & Market System & Architecture Architecture Definition Support

+49 6182 81 2555 [email protected]