WMZ Circuit Breakers - WESCO International · 2015-05-22 · 9 UL 489 Cable-In / Cable-Out Branch...

10
9 UL 489 Cable-In / Cable-Out Branch Circuit Breaker WMZ Circuit Breakers PRODUCT OVERVIEW EATON CORPORATION Cable-in / cable-out circuit breakers and protectors Optimum and Efficient Protection Optimum product quality, tested reliability and safety standards for best protection of personnel, installations and plant Eaton’s WMZ DIN rail mountable circuit breaker is designed for use in branch service applications Powerful Offering for Machine and System Builders The WMZ is available with C and D characteristics in accordance with UL 489, CSA C222 No5; UL 1077, CSA C222 No235 and IEC 60947-2 These devices are CE marked Typical Applications Feeder and Branch Circuit Protection Convenience receptacle circuits (internal/external) Motor control circuits Load circuits leaving the equipment (external) HACR equipment (heating, air conditioning, refrigeration) (internal/external) PLC I/O points Computers Power supplies Control instrumentation Relays UPS Power conditioners Features Complete range of UL 489 listed DIN rail mounted miniature circuit breakers up to 40A current rating Standard ratings of 10 kAIC at 277/480 Vac Select amperages available at 14 kAIC at 277/480 Vac and 10 kAIC at 125 Vdc Current limiting design provides fast short-circuit interruption that reduces the let-through energy, which can damage the circuit Suitable for branch circuit device protection Thermal-magnetic overcurrent protection Two levels of short-circuit protection, categorized by C and D curves Trip-free design—breaker can not be defeated by holding the handle in the ON position Captive screws cannot be lost SWD (switching duty)—suitable for switching fluorescent lighting loads (I n ≤ 20A) Fulfill UL 489, CSA C222 No5 and also IEC 60947-2 Standard For use in applications for which UL 1077 or CSA C222 No235 are also allowed Field-installable shunt trip and auxiliary switch subsequent mounting Separate version for ring-tongue connection (Type WMZT…T), terminal screws can be removed (on both sides) Module width of only 177 mm (per pole) Contact Position Indicator (red/green) Easy installation on DIN rail Possibility for sealing the toggle in ON or OFF position WMZ Complies with the Latest National and International Standards Standards—Feeder and Branch Circuit Protection UL 489 Standard for molded-case circuit breakers (MCCB) for feeder and branch circuit protection. Products meet the requirements of the National Electrical Code ® (NEC ® ). CSA C22.2 No.5 Standard for molded-case circuit breakers (MCCB) for feeder and branch circuit protection (corresponds closely to UL 489 Standard). Products meet the requirements of the Canadian Electrical Code (CEC). RoHS These devices are RoHS compliant. WMZ Circuit Breakers Product Overview

Transcript of WMZ Circuit Breakers - WESCO International · 2015-05-22 · 9 UL 489 Cable-In / Cable-Out Branch...

Page 1: WMZ Circuit Breakers - WESCO International · 2015-05-22 · 9 UL 489 Cable-In / Cable-Out Branch Circuit Breaker WMZ Circuit Breakers PRODUCT OVERVIEW EATON CORPORATION Cable-in

9

UL 489 Cable-In / Cable-Out Branch Circuit BreakerWMZ Circuit Breakers

PRODUCT OVERVIEW

EATON CORPORATION Cable-in / cable-out circuit breakers and protectors

Optimum and Efficient Protection

Optimum product quality, tested reliability and safety standards for best protection of personnel, installations and plant . Eaton’s WMZ DIN rail mountable circuit breaker is designed for use in branch service applications .

Powerful Offering for Machine and System Builders

The WMZ is available with C and D characteristics in accordance with UL 489, CSA C22 .2 No .5; UL 1077, CSA C22 .2 No .235 and IEC 60947-2 . These devices are CE marked .

Typical Applications

Feeder and Branch Circuit Protection

• Convenience receptacle circuits (internal/external)

• Motor control circuits

• Load circuits leaving the equipment (external)

• HACR equipment (heating, air conditioning, refrigeration) (internal/external)

• PLC I/O points

• Computers

• Power supplies

• Control instrumentation

• Relays

• UPS

• Power conditioners

Features

• Complete range of UL 489 listed DIN rail mounted miniature circuit breakers up to 40A current rating

• Standard ratings of 10 kAIC at 277/480 Vac

• Select amperages available at 14 kAIC at 277/480 Vac and 10 kAIC at 125 Vdc

• Current limiting design provides fast short-circuit interruption that reduces the let-through energy, which can damage the circuit

• Suitable for branch circuit device protection

• Thermal-magnetic overcurrent protection

— Two levels of short-circuit protection, categorized by C and D curves

• Trip-free design—breaker can not be defeated by holding the handle in the ON position

• Captive screws cannot be lost

• SWD (switching duty)—suitable for switching fluorescent lighting loads (In ≤ 20A)

• Fulfill UL 489, CSA C22 .2 No .5 and also IEC 60947-2 Standard

• For use in applications for which UL 1077 or CSA C22 .2 No .235 are also allowed

• Field-installable shunt trip and auxiliary switch subsequent mounting

• Separate version for ring-tongue connection (Type WMZT… .T), terminal screws can be removed (on both sides)

• Module width of only 17 .7 mm (per pole)

• Contact Position Indicator (red/green)

• Easy installation on DIN rail

• Possibility for sealing the toggle in ON or OFF position

WMZ Complies with the Latest National and International Standards

Standards—Feeder and Branch Circuit Protection

UL 489

Standard for molded-case circuit breakers (MCCB) for feeder and branch circuit protection.

Products meet the requirements of the National Electrical Code® (NEC®).

CSA C22.2 No.5

Standard for molded-case circuit breakers (MCCB) for feeder and branch circuit protection (corresponds closely to UL 489 Standard).

Products meet the requirements of the Canadian Electrical Code (CEC).

RoHS

These devices are RoHS compliant.

WMZ Circuit BreakersProduct Overview

Page 2: WMZ Circuit Breakers - WESCO International · 2015-05-22 · 9 UL 489 Cable-In / Cable-Out Branch Circuit Breaker WMZ Circuit Breakers PRODUCT OVERVIEW EATON CORPORATION Cable-in

10

UL 489 Cable-In / Cable-Out Branch Circuit BreakerWMZ Circuit BreakersPRODUCT SELECTION

EATON CORPORATION Cable-in / cable-out circuit breakers and protectors

Tripping Curves to Choose From

Eaton WMZ branch circuit breakers are available with “C” and “D” tripping characteristics .

C-curve devices are suitable for applications where medium levels of inrush current are expected . Applications include small transformers, lighting, pilot devices, control circuits and coils . C-curve devices provide a medium magnetic trip point .

D-curve devices are suitable for applications where high levels of inrush current are expected . The high magnetic trip point prevents nuisance tripping in high inductive applications such as motors, transformers and power supplies .

Eaton WMZ devices are current limiting, which means they interrupt fault currents within one half cycle of the fault . Current limiting devices offer superior protection by reducing peak let-through current and energy .

Catalog Numbering System

Device Printing on Front and Side

Installation options

These branch circuit breakers are available in two terminal configurations: standard box terminals that accept multiple conductors and ring-tongue terminals, ideally suited to demanding requirements of the semi-conductor industry . All breakers mount on standard 35 mm DIN rail . Bus connectors and feeder terminal facilitate mounting and wiring of multiple miniature circuit breaker arrays in control panel assemblies . These circuit breakers can also be reverse feed .

tripping characteristic acc . to UL 489 conventional non-tripping

current Int = 1.0 IN (T=40°)

conventional tripping current It = 1.35 IN: t < 1 h (T=25°)

2.0 IN: t = 12–120 s (T=25°)

instantaneous tripping acc . to IEC 60898-1 type C: 5 IN: t > 0.1 s

10 IN: t < 0.1 se type D: 10 IN: t > 0.1 s

20 IN: t < 0.1 s

Conductor Type

Calibration Temperature UL/CSA

Rated Voltage UL/CSA

Breaker Status Indicator

Catalog Number

Rated Current

WMZ T 1 C 16 T

Breaker Family

WMZ = WMZ UL circuit breaker Number of Poles

1 = Single-pole2 = Two-pole3 = Three-pole

Terminal

T = Ring terminals[blank] = Standard box terminals

Breaker Type

T = 10 kAICH = 14 kAIC D = 10 kAIC/DC

Protective Curve

C = C Curve (5–10X In)D = D Curve (10–20X In)

Ampere Rating

X0 = 0.5A01 = 1AX1 = 1.5A02 = 2A03 = 3A04 = 4A05 = 5A06 = 6A07 = 7A08 = 8A

10 = 10A13 = 13A15 = 15A16 = 16A20 = 20A25 = 25A30 = 30A32 = 32A40 = 40A

Limited curve and ampere offerings. 125 Vdc for single-pole, 250 Vdc for two-pole in series. Not offered for Type WMZD.

WMZ Circuit BreakersProduct Selection

Page 3: WMZ Circuit Breakers - WESCO International · 2015-05-22 · 9 UL 489 Cable-In / Cable-Out Branch Circuit Breaker WMZ Circuit Breakers PRODUCT OVERVIEW EATON CORPORATION Cable-in

11

UL 489 Cable-In / Cable-Out Branch Circuit BreakerWMZ Circuit Breakers

PRODUCT SELECTION

EATON CORPORATION Cable-in / cable-out circuit breakers and protectors

WMZT Product Selection

• UL approved (UL 489) and CSA Certified (CSA C22 .2 No . 5-02) as branch circuit breakers

• Interrupting capacity: 10 kA UL/CSA; 15 kA IEC 60947

• Current limiting device

• Optional connections for ring-tongue terminals

WMZT UL 489 Circuit Breakers—10 kAIC

AmperesSingle-Pole Catalog Number

Two-Pole Catalog Number

Three-Pole Catalog Number

C Curve (5–10X In Current Rating)

0.511.523

WMZT1CX0WMZT1C01WMZT1CX1WMZT1C02WMZT1C03

WMZT2CX0WMZT2C01WMZT2CX1WMZT2C02WMZT2C03

WMZT3CX0WMZT3C01WMZT3CX1WMZT3C02WMZT3C03

45678

WMZT1C04WMZT1C05WMZT1C06WMZT1C07WMZT1C08

WMZT2C00WMZT2C05WMZT2C06WMZT2C07WMZT2C08

WMZT3C04WMZT3C05WMZT3C06WMZT3C07WMZT3C08

1013151620

WMZT1C10WMZT1C13WMZT1C15WMZT1C16WMZT1C20

WMZT2C10WMZT2C13WMZT2C15WMZT2C16WMZT2C20

WMZT3C10WMZT3C13WMZT3C15WMZT3C16WMZT3C20

25303240

WMZT1C25WMZT1C30WMZT1C32WMZT1C40

WMZT2C25WMZT2C30WMZT2C32WMZT2C40

WMZT3C25WMZT3C30WMZT3C32WMZT3C40

D Curve (10–20X In Current Rating)

0.511.523

WMZT1DX0WMZT1D01WMZT1DX1WMZT1D02WMZT1D03

WMZT2DX0WMZT2D01WMZT2DX1WMZT2D02WMZT2D03

WMZT3DX0WMZT3D01WMZT3DX1WMZT3D02WMZT3D03

45678

WMZT1D04WMZT1D05WMZT1D06WMZT1D07WMZT1D08

WMZT2D04WMZT2D05WMZT2D06WMZT2D07WMZT2D08

WMZT3D04WMZT3D05WMZT3D06WMZT3D07WMZT3D08

1013151620

WMZT1D10WMZT1D13WMZT1D15WMZT1D16WMZT1D20

WMZT2D10WMZT2D13WMZT2D15WMZT2D16WMZT2D20

WMZT3D10WMZT3D13WMZT3D15WMZT3D16WMZT3D20

25303240

WMZT1D25WMZT1D30WMZT1D32WMZT1D40

WMZT2D25WMZT2D30WMZT2D32WMZT2D40

WMZT3D25WMZT3D30WMZT3D32WMZT3D40z

WMZT UL 489 Circuit Breakers with Ring-Tongue Terminals—10 kAIC

AmperesSingle-Pole Catalog Number

Two-Pole Catalog Number

Three-Pole Catalog Number

C Curve with Ring-Tongue Terminals (5–10X In Current Rating)

0.511.523

WMZT1CX0TWMZT1C01TWMZT1CX1TWMZT1C02TWMZT1C03T

WMZT2CX0TWMZT2C01TWMZT2CX1TWMZT2C02TWMZT2C03T

WMZT3CX0TWMZT3C01TWMZT3CX1TWMZT3C02TWMZT3C03T

45678

WMZT1C04TWMZT1C05TWMZT1C06TWMZT1C07TWMZT1C08T

WMZT2C04TWMZT2C05TWMZT2C06TWMZT2C07TWMZT2C08T

WMZT3C04TWMZT3C05TWMZT3C06TWMZT3C07TWMZT3C08T

1013151620

WMZT1C10TWMZT1C13TWMZT1C15TWMZT1C16TWMZT1C20T

WMZT2C10TWMZT2C13TWMZT2C15TWMZT2C16TWMZT2C20T

WMZT3C10TWMZT3C13TWMZT3C15TWMZT3C16TWMZT3C20T

25303240

WMZT1C25TWMZT1C30TWMZT1C32TWMZT1C40T

WMZT2C25TWMZT2C30TWMZT2C32TWMZT2C40T

WMZT3C25TWMZT3C30TWMZT3C32TWMZT3C40T

D Curve with Ring-Tongue Terminals (10–20X In Current Rating)

0.511.523

WMZT1DX0TWMZT1D01TWMZT1DX1TWMZT1D02TWMZT1D03T

WMZT2DX0TWMZT2D01TWMZT2DX1TWMZT2D02TWMZT2D03T

WMZT3DX0TWMZT3D01TWMZT3DX1TWMZT3D02TWMZT3D03T

45678

WMZT1D04TWMZT1D05TWMZT1D06TWMZT1D07TWMZT1D08T

WMZT2D04TWMZT2D05TWMZT2D06TWMZT2D07TWMZT2D08T

WMZT3D04TWMZT3D05TWMZT3D06TWMZT3D07TWMZT3D08T

1013151620

WMZT1D10TWMZT1D13TWMZT1D15TWMZT1D16TWMZT1D20T

WMZT2D10TWMZT2D13TWMZT2D15TWMZT2D16TWMZT2D20T

WMZT3D10TWMZT3D13TWMZT3D15TWMZT3D16TWMZT3D20T

25303240

WMZT1D25TWMZT1D30TWMZT1D32TWMZT1D40T

WMZT2D25TWMZT2D30TWMZT2D32TWMZT2D40T

WMZT3D25TWMZT3D30TWMZT3D32TWMZT3D40T

For our complete product offering, see the Distribution Products Catalog (CA08101001E) .

Product Selection

Page 4: WMZ Circuit Breakers - WESCO International · 2015-05-22 · 9 UL 489 Cable-In / Cable-Out Branch Circuit Breaker WMZ Circuit Breakers PRODUCT OVERVIEW EATON CORPORATION Cable-in

12

UL 489 Cable-In / Cable-Out Branch Circuit BreakerWMZ Circuit BreakersPRODUCT SELECTION

EATON CORPORATION Cable-in / cable-out circuit breakers and protectors

WMZH Product Selection

• UL approved (UL 489) and CSA Certified (CSA C22 .2 No . 5-02) as branch circuit breakers

• Interrupting capacity: 14 kA UL/CSA; 15 kA IEC 60947

WMZH UL 489 Circuit Breakers—14 kAIC

AmperesSingle-Pole Catalog Number

Two-Pole Catalog Number

Three-Pole Catalog Number

C Curve (5–10X In Current Rating)

15162025

WMZH1C15WMZH1C16WMZH1C20WMZH1C25

WMZH2C15WMZH2C16WMZH2C20WMZH2C25

WMZH3C15WMZH3C16WMZH3C20WMZH3C25

D Curve (10–20X In Current Rating)

13151620

WMZH1D13WMZH1D15WMZH1D16WMZH1D20

WMZH2D13WMZH2D15WMZH2D16WMZH2D20

WMZH3D13WMZH3D15WMZH3D16WMZH3D20

WMZD Product Selection

• UL approved (UL 489) and CSA Certified (CSA C22 .2 No . 5-02) as branch circuit breakers

• Interrupting capacity: 10 kA at 125 Vdc UL/CSA

• 125 Vdc for single-pole, 250 Vdc for two-pole in series

• Current limiting device

• Current limiting device

• Optional connections for ring-tongue terminals

WMZH UL 489 Circuit Breakers with Ring-Tongue Terminals

AmperesSingle-Pole Catalog Number

Two-Pole Catalog Number

Three-Pole Catalog Number

C Curve (5–10X In Current Rating)

15162025

WMZH1C15TWMZH1C16TWMZH1C20TWMZH1C25T

WMZH2C15TWMZH2C16TWMZH2C20TWMZH2C25T

WMZH3C15TWMZH3C16TWMZH3C20TWMZH3C25T

D Curve (10–20X In Current Rating)

13151620

WMZH1D13TWMZH1D15TWMZH1D16TWMZH1D20T

WMZH2D13TWMZH2D15TWMZH2D16TWMZH2D20T

WMZH3D13TWMZH3D15TWMZH3D16TWMZH3D20T

WMZD UL 489 Circuit Breakers— 10 kAIC at 125 Vdc per pole

AmperesSingle-Pole Catalog Number

Two-Pole Catalog Number

C Curve (5–10X In Current Rating)

2345

WMZD1C02WMZD1C03WMZD1C04WMZD1C05

WMZD2C02WMZD2C03WMZD2C04WMZD2C05

67810

WMZD1C06WMZD1C07WMZD1C08WMZD1C10

WMZD2C06WMZD2C07WMZD2C08WMZD2C10

13151620

WMZD1C13WMZD1C15WMZD1C16WMZD1C20

WMZD2C13WMZD2C15WMZD2C16WMZD2C20

25303240

WMZD1C25WMZD1C30WMZD1C32WMZD1C40

WMZD2C25WMZD2C30WMZD2C32WMZD2C40

Page 5: WMZ Circuit Breakers - WESCO International · 2015-05-22 · 9 UL 489 Cable-In / Cable-Out Branch Circuit Breaker WMZ Circuit Breakers PRODUCT OVERVIEW EATON CORPORATION Cable-in

13

UL 489 Cable-In / Cable-Out Branch Circuit BreakerWMZ Circuit Breakers

PRODUCT SELECTION

EATON CORPORATION Cable-in / cable-out circuit breakers and protectors

WMZ UL 489 BreakersAccessory/Description Catalog Number

Two-pole contact or auxiliary contact/ Trip indicating contact

WMZSAUXTRIP

Auxiliary contact WMZTAUX

Shunt trip 110–415 VacShunt trip 12–110 Vac

WMZTST415WMZTST110

Padlock hasp WMZPLK

Busbar—single-pole 6 terminalsBusbar—single-pole 12 terminalsBusbar—single-pole 18 terminalsBusbar—two-pole 6 terminalsBusbar—two-pole 12 terminalsBusbar—two-pole 18 terminalsBusbar—three-pole 6 terminalsBusbar—three-pole 12 terminalsBusbar—three-pole 18 terminals

WMZT1P6TWMZT1P12TWMZT1P18TWMZT2P6TWMZT2P12TWMZT2P18TWMZT3P6TWMZT3P12TWMZT3P18T

Three-pole busbar shroud WMZT3PSHROUD

Extension terminal—35 mm (2–14 AWG) WMZT35EXT

Bus connector—conductors up to 50 mm2 (~1/0 AWG) WMZTBCON

Contact sales office for availability.

Tripping Signal Switch WMZSAUXTRIP, WMZTAUX

• Design according to IEC/EN 60947-5-1, IEC/EN 62019

• Field installable

• The specified minimum voltages are per contact—take into account particularly in case of series connection

• Self-cleaning contacts

• Contact material and design particularly suitable for extra low voltage

• WMZSAUXTRIP: the function of one of the two change-over contacts can be switched from “auxiliary switch” to “tripping signal switch”

• Tripping signal contact transmits message of electric tripping, not mechanical switch-off

• Test key for contact function “electrical tripping”

• WMZTAUX: will allow for > 480Y/277 Vac rating

Connection Diagram

WMZSAUXTRIP

21

4.11

1.11

1.14

1.12

4.12/4.14

4.14/4.12

13

2214

Same Polarity

WMZTAUX

4.13(105.0)

Single-Pole Two-Pole Three-Pole

.70(17.7)

.70(17.7)1.39

(35.3)2.09

(53.1)

.70(17.7)

.70(17.7)

4.13(105.0)

4.13(105.0)

1.17(29.7)39°

1.42(36.1)

Dimensions

Miniature Circuit Breakers

WMZ

Page 6: WMZ Circuit Breakers - WESCO International · 2015-05-22 · 9 UL 489 Cable-In / Cable-Out Branch Circuit Breaker WMZ Circuit Breakers PRODUCT OVERVIEW EATON CORPORATION Cable-in

14

UL 489 Cable-In / Cable-Out Branch Circuit BreakerWMZ Circuit BreakersTECHNICAL DATA

EATON CORPORATION Cable-in / cable-out circuit breakers and protectors

Miniature Circuit Breakers WMZ

Connection Diagrams

Miniature Circuit Breakers WMZDescription Specification

Electrical

Design according to UL 489, CSA C22.2 No.5, IEC 60947-2

Rated voltage WMZT UL/CSA UL/CSA UL/CSA IEC 947-2

10 kAIC at 277/480V from 0.5A to 32A10 kAIC at 240 Vac for 40A10 kAIC at 48 Vdc per pole15 kAIC at 240/415 Vac

Rated voltage WMZD UL/CSA 10 kAIC at 125 Vdc per pole

(two poles maximum)10 kAIC at 250 Vdc with two poles connected in series

Rated voltage WMZH UL/CSA IEC 947-2

14 kAIC at 277/480V at listed amperages15 kAIC at 240/415 Vac

Rated frequency 50/60 Hz

Rated breaking capacity WMZT UL/CSA IEC 947-2

10 kA15 kA

Rated breaking capacity WMZH UL/CSA IEC 947-2

14 kA15 kA

Characteristic C, D

Endurance ≥ 20,000 operations

Line voltage connection Suitable for reverse feed

Mechanical

Frame size 45 mm

Device height 105 mm

Device width 17.7 mm per pole

Mounting Quick fastening with two lock-in positions on IEC/EN 60715

Upper and lower terminals Open mouth/lift terminals

Terminal capacity Single-wire Two-wire

AWG 18–6AWG 18–10

Terminal fastening torque AWG 18-21: 21 lb-inAWG 10-8: 25 lb-inAWG 6: 36 lb-in

Mounting Independent of position

Calibration temperatureUL 489, CSA C22.2 No.5IEC 60947-2

40°C30°C

Two-Pole Three-PoleSingle-Pole

Dimensions (mm)

Power Loss at ln Characteristic C Characteristic D

In [A]

Single-Pole

Two- Pole

Three-Pole

Single-Pole

Two- Pole

Three-Pole

P [W] P [W] P [W] P [W] P [W] P [W

0.511.52

1.61.11.31.4

3.22.22.62.8

4.73.43.94.3

1.60.81.01.0

3.21.52.12.1

4.82.33.13.1

3456

1.21.41.91.2

2.42.93.72.3

3.64.35.63.5

1.21.41.51.2

2.42.92.92.3

3.64.34.43.5

781013

1.41.41.82.4

2.82.83.64.7

4.34.25.37.1

1.41.21.52.0

2.82.43.04.1

4.33.74.56.1

15162025

1.92.12.93.1

3.84.35.86.2

5.66.48.79.3

1.51.71.82.6

3.13.53.75.1

4.65.25.57.7

30323540

3.03.43.74.0

6.06.87.48.1

9.010.211.012.1

2.73.13.83.9

5.46.27.67.8

8.19.311.311.6

17 .7

105

5 .5

45

10

44

60

Technical Data

Page 7: WMZ Circuit Breakers - WESCO International · 2015-05-22 · 9 UL 489 Cable-In / Cable-Out Branch Circuit Breaker WMZ Circuit Breakers PRODUCT OVERVIEW EATON CORPORATION Cable-in

15

UL 489 Cable-In / Cable-Out Branch Circuit BreakerWMZ Circuit Breakers

TECHNICAL DATA

EATON CORPORATION Cable-in / cable-out circuit breakers and protectors

Let-Through Energy

Characteristic C (0.5–32A), 277V

Characteristic D (0.5–32A), 277V

Characteristic C (40A), 240V

Characteristic D (40A), 240V

Page 8: WMZ Circuit Breakers - WESCO International · 2015-05-22 · 9 UL 489 Cable-In / Cable-Out Branch Circuit Breaker WMZ Circuit Breakers PRODUCT OVERVIEW EATON CORPORATION Cable-in

16

UL 489 Cable-In / Cable-Out Branch Circuit BreakerWMZ Circuit BreakersACCESSORIES

EATON CORPORATION Cable-in / cable-out circuit breakers and protectors

Dimensions (mm)

WMZT_ _ 6T WMZT_ _ 12T

WMZT_ _ 18T WMZT35EXT

WMZT3PSHROUD

517,6

5x17,6=88

517,6

17x17,6=299,2

5

717,6 17,6 3,55

17,611x17,6=193,6

310,2

204,6

24

1616

48.2

15,5

46

32,5

71,6

6

13,5

3

31,3

99

WMZT35EXTDescription UL 489 IEC/EN 60947-2

# 2–14 AWG60/75°C Cu

2.5–35 mm2

60/75°C Cu

0.56 in 14 mm

Tested according to Tightening torque of terminal screws

UL 486A # 14 AWG ≥ 2.3 Nm

UL 486B # 8–12 AWG ≥ 2.8 Nm

UL 486E # 6–1 AWG 4 Nm

Lockout Attachment

WMZPLK

Accessories

Page 9: WMZ Circuit Breakers - WESCO International · 2015-05-22 · 9 UL 489 Cable-In / Cable-Out Branch Circuit Breaker WMZ Circuit Breakers PRODUCT OVERVIEW EATON CORPORATION Cable-in

17

UL 489 Cable-In / Cable-Out Branch Circuit BreakerWMZ Circuit Breakers

TECHNICAL DATA

EATON CORPORATION Cable-in / cable-out circuit breakers and protectors

Influence of Ambient Temperature T on Load Carrying Capacity

Device Market Current Rating In (A) at 40°C

In (A) at Higher Ambient Temperature

15°C 20°C 25°C 30°C 40°C 50°C 55°C 60°C

0.51.01.52.0

0.61.11.72.2

0.51.11.62.2

0.51.11.62.1

0.51.01.62.1

0.51.01.52.0

0.51.01.41.9

0.50.91.41.9

0.5 0.9 1.4 1.8

3.04.05.06.0

3.34.45.56.6

3.24.35.46.5

3.24.25.36.4

3.14.25.26.2

3.04.05.06.0

2.93.84.85.8

2.93.84.75.6

2.8 3.7 4.6 5.5

7.08.010.013.0

7.78.811.014.3

7.68.610.814.0

7.48.510.613.8

7.38.310.413.5

7.08.010.013.0

6.77.79.612.5

6.67.59.412.5

6.4 7.4 9.2 12.0

15.016.020.025.0

16.517.622.027.5

16.217.321.627.0

15.917.021.226.5

15.616.620.826.0

15.016.020.025.0

14.415.419.224.0

14.115.018.823.3

13.8 14.7 18.4 23.0

30.032.040.0

33.035.244.0

32.434.643.2

31.833.942.4

31.233.341.6

30.032.040.0

28.830.738.4

28.230.137.6

27.6 29.4 36.8

Ambient Temperature T [°C]Maximum Load IL at ambient temperature T: IL (T) = IN KT(T)

Load

Fac

tor

KT

[I/

I N]

Technical Data

Page 10: WMZ Circuit Breakers - WESCO International · 2015-05-22 · 9 UL 489 Cable-In / Cable-Out Branch Circuit Breaker WMZ Circuit Breakers PRODUCT OVERVIEW EATON CORPORATION Cable-in

18

UL 489 Cable-In / Cable-Out Branch Circuit BreakerWMZ Circuit BreakersACCESSORIES

EATON CORPORATION Cable-in / cable-out circuit breakers and protectors

AccessoriesDescription WMZSAUXTRIP WMZTAUX

Electrical

Contact function 2CO 1NO + 1NC

Rated voltage 230V 250V

Frequency 50/60 Hz 50/60 Hz

Rated current 2A 6A

Rated thermal current Ith 2A 6A

Utilization category AC13rated operational current Ie 3A/250 Vac 3A/250 Vac

Utilization category AC15rated operational current Ie 2A/250 Vac 2A/250 Vac

Utilization category DC12rated operational current Ie 0.5A/110 Vdc 0.5A/110 Vdc

0.25A/220 Vdc

Rated insulation voltage UI 250 Vac 250 Vac

Minimum operational voltage per contact Umin 5 Vdc 5 Vdc

Minimum operational current Imin 10 mA DC 10 mA AC/DC

Rated peak withstand voltage Uimp (1.2/50µ) 2.5 kV 4 kV

Conditional short-circuit current Ik with backup fuse 6A 1 kA 1 kA

Max. backup fuse, overload and short circuit 6A gL —

Mechanical

Tripping indicator “electrical tripping” Blue/white —

Frame size 45 mm 45 mm

Device height 80 mm 80 mm

Device width 8.8 mm (0.5MU) 8.8 mm (0.5MU)

Mounting Onto switching device —

Degree of protection, built-in IP40 IP40

Terminal protection Finger and hand touch safe according to BGV A3, ÖVE-EN 6

Finger and hand touch safeaccording to BGV A3, ÖVE-EN 6

Terminals Lift terminals Lift terminals

Terminal capacity 20–14 AWG 0.5–2.5 mm2

Terminal screws M3 (posidrive Z0) M3 (posidrive Z0)

Fastening torque of terminal screws 7 lb-in Max. 1.2 Nm