Wiring Power Meters Ben Kemink. FORESIGHT INNOVATION QUALITY Subjects covered: to re-wire an...

25
Wiring Power Meters Ben Kemink

Transcript of Wiring Power Meters Ben Kemink. FORESIGHT INNOVATION QUALITY Subjects covered: to re-wire an...

Page 1: Wiring Power Meters Ben Kemink. FORESIGHT INNOVATION QUALITY Subjects covered: to re-wire an incorrect NEGATIVE average power situation. to connect Single-Phase,

Wiring Power Meters

Ben Kemink

Page 2: Wiring Power Meters Ben Kemink. FORESIGHT INNOVATION QUALITY Subjects covered: to re-wire an incorrect NEGATIVE average power situation. to connect Single-Phase,

FORESIGHTINNOVATION

QUALITY

Subjects covered:

to re-wire an incorrect NEGATIVE average power situation.

to connect Single-Phase, Two-Phase , Three-Phase-Three-Three-Wire and Three-Phase-Four-Wire loads.

to connect safely measurement transformers between the loads and power meters.

more about the magic of the virtual ground box

Page 3: Wiring Power Meters Ben Kemink. FORESIGHT INNOVATION QUALITY Subjects covered: to re-wire an incorrect NEGATIVE average power situation. to connect Single-Phase,

FORESIGHTINNOVATION

QUALITY

Why ring?

Page 4: Wiring Power Meters Ben Kemink. FORESIGHT INNOVATION QUALITY Subjects covered: to re-wire an incorrect NEGATIVE average power situation. to connect Single-Phase,

FORESIGHTINNOVATION

QUALITY

Page 5: Wiring Power Meters Ben Kemink. FORESIGHT INNOVATION QUALITY Subjects covered: to re-wire an incorrect NEGATIVE average power situation. to connect Single-Phase,

FORESIGHTINNOVATION

QUALITY

i

u

Source Wiring Load

Make a drawing

Page 6: Wiring Power Meters Ben Kemink. FORESIGHT INNOVATION QUALITY Subjects covered: to re-wire an incorrect NEGATIVE average power situation. to connect Single-Phase,

FORESIGHTINNOVATION

QUALITY

Positive “DC”

+

-

I

U

Page 7: Wiring Power Meters Ben Kemink. FORESIGHT INNOVATION QUALITY Subjects covered: to re-wire an incorrect NEGATIVE average power situation. to connect Single-Phase,

FORESIGHTINNOVATION

QUALITY

Negative “DC”

-

+U

I

Page 8: Wiring Power Meters Ben Kemink. FORESIGHT INNOVATION QUALITY Subjects covered: to re-wire an incorrect NEGATIVE average power situation. to connect Single-Phase,

FORESIGHTINNOVATION

QUALITY

Always: First Connect the Current !

i

u

i

v

+

-

Wiring Sequence

Page 9: Wiring Power Meters Ben Kemink. FORESIGHT INNOVATION QUALITY Subjects covered: to re-wire an incorrect NEGATIVE average power situation. to connect Single-Phase,

FORESIGHTINNOVATION

QUALITY

Correct Connection

The sign of the current is positive, when the current flows from [I] terminal to [±] terminal inside the powermeter shunt.

The sign of the voltage is positive when the voltage of the [V] terminal is higher than [±] terminal.

I

V

i

v

+

-

I

V

i

v

+

-

Page 10: Wiring Power Meters Ben Kemink. FORESIGHT INNOVATION QUALITY Subjects covered: to re-wire an incorrect NEGATIVE average power situation. to connect Single-Phase,

FORESIGHTINNOVATION

QUALITY

v

i

p

Pavg

v

i

p

Pavg

The voltage source increases and the current also

Page 11: Wiring Power Meters Ben Kemink. FORESIGHT INNOVATION QUALITY Subjects covered: to re-wire an incorrect NEGATIVE average power situation. to connect Single-Phase,

FORESIGHTINNOVATION

QUALITY

Incorrect Voltmeter connection

v

i

p

Pactive

The power meter displays negative value for average power.

I

V

i

v

+

-

The source voltage decreases but the current increases.

Page 12: Wiring Power Meters Ben Kemink. FORESIGHT INNOVATION QUALITY Subjects covered: to re-wire an incorrect NEGATIVE average power situation. to connect Single-Phase,

FORESIGHTINNOVATION

QUALITY

Incorrect Current meter connection

If the power meter displays a negative value for the average power, one should refers the voltage connection.

v

i

p

Pactive

I

V

i

v

+

-

Page 13: Wiring Power Meters Ben Kemink. FORESIGHT INNOVATION QUALITY Subjects covered: to re-wire an incorrect NEGATIVE average power situation. to connect Single-Phase,

FORESIGHTINNOVATION

QUALITY

Connect CURRENT METER if possible in RETURN WIRE

Return wire is at lower voltage than “HOT” wire,

after the voltage drop in the load.

Page 14: Wiring Power Meters Ben Kemink. FORESIGHT INNOVATION QUALITY Subjects covered: to re-wire an incorrect NEGATIVE average power situation. to connect Single-Phase,

FORESIGHTINNOVATION

QUALITY

Wiring Single-Phase Three-Wire

Page 15: Wiring Power Meters Ben Kemink. FORESIGHT INNOVATION QUALITY Subjects covered: to re-wire an incorrect NEGATIVE average power situation. to connect Single-Phase,

FORESIGHTINNOVATION

QUALITY

Wiring Three-Phase Four-Wire

Page 16: Wiring Power Meters Ben Kemink. FORESIGHT INNOVATION QUALITY Subjects covered: to re-wire an incorrect NEGATIVE average power situation. to connect Single-Phase,

FORESIGHTINNOVATION

QUALITY

Wiring Three-Phase Three-Wire

Page 17: Wiring Power Meters Ben Kemink. FORESIGHT INNOVATION QUALITY Subjects covered: to re-wire an incorrect NEGATIVE average power situation. to connect Single-Phase,

FORESIGHTINNOVATION

QUALITY

Wiring Yokogawa Three-Voltage Three-Current

Page 18: Wiring Power Meters Ben Kemink. FORESIGHT INNOVATION QUALITY Subjects covered: to re-wire an incorrect NEGATIVE average power situation. to connect Single-Phase,

FORESIGHTINNOVATION

QUALITY

The Only Correct Way to Measure the Phase Voltage!

Page 19: Wiring Power Meters Ben Kemink. FORESIGHT INNOVATION QUALITY Subjects covered: to re-wire an incorrect NEGATIVE average power situation. to connect Single-Phase,

FORESIGHTINNOVATION

QUALITY

THREE PHASE SYSTEMS Artificial Neutral

Justification that Ptotal correct is with Virtual Ground Box

Page 20: Wiring Power Meters Ben Kemink. FORESIGHT INNOVATION QUALITY Subjects covered: to re-wire an incorrect NEGATIVE average power situation. to connect Single-Phase,

FORESIGHTINNOVATION

QUALITY

Page 21: Wiring Power Meters Ben Kemink. FORESIGHT INNOVATION QUALITY Subjects covered: to re-wire an incorrect NEGATIVE average power situation. to connect Single-Phase,

FORESIGHTINNOVATION

QUALITY

Single-Phase Two-Wire, with PT & CT

Page 22: Wiring Power Meters Ben Kemink. FORESIGHT INNOVATION QUALITY Subjects covered: to re-wire an incorrect NEGATIVE average power situation. to connect Single-Phase,

FORESIGHTINNOVATION

QUALITY

Single-Phase Three-Wire, with PT & CT

Page 23: Wiring Power Meters Ben Kemink. FORESIGHT INNOVATION QUALITY Subjects covered: to re-wire an incorrect NEGATIVE average power situation. to connect Single-Phase,

FORESIGHTINNOVATION

QUALITY

Three-Phase Three-Wire, with PT & CT

Page 24: Wiring Power Meters Ben Kemink. FORESIGHT INNOVATION QUALITY Subjects covered: to re-wire an incorrect NEGATIVE average power situation. to connect Single-Phase,

FORESIGHTINNOVATION

QUALITY

Three-Phase Four-Wire, with PT & CT

Page 25: Wiring Power Meters Ben Kemink. FORESIGHT INNOVATION QUALITY Subjects covered: to re-wire an incorrect NEGATIVE average power situation. to connect Single-Phase,

FORESIGHTINNOVATION

QUALITY

Thank you and success!