WINS H-TEC FIRE PROTECTION PANEL (Calcium Silicate)

Transcript of WINS H-TEC FIRE PROTECTION PANELwinsconsultants.com/wp-content/uploads/2018/06/E-Brochure_Web.pdfBS...

  • WINS H-TECFIRE PROTECTION

    PANEL(Calcium Silicate)

  • Page 1

    WINS H-TEC FIRE PROTECTION PANELPHYSICAL AND MECHANICAL PROPERTIES

    Test Description Standard Test Result

    Density

    Resistance to impact

    Moisture content

    Dimension

    Surface condition

    Sound transmission loss

    BS EN 1170-6:1998

    BS 5669 :Part 1:1989, Clause 21

    BS EN 772:1993

    BS 5669:Part1:1989, Clause 8

    By direct measurement

    1.05g/cm3

    Class A

    12.35%

    Average thickness: 8.87mm

    No visible damage

    13.98MPa

    Dimensional changesassociated with changesin relative humidity

    Tensile strength andelongation at break

    BS 2782:Part 10:Method 1003:1977

    BS EN 318:2002

    BS 5669 :Part 1:1989,Clause 19

    Increase in mass(water absorption)& thickness(swelling)

    Microscopic examinationof bulk materials

    In-house methodsG-T-023 & G-T-028

    BS 2782:Part 10:Method 1005:1997

    BS 2750 Part 3:1995

    Flexural strength

    Water absorption: 34.99%;Swelling: 0.08%

    55dB

    Non-asbestos

    Length change:generally within 0.02%

    Tensile strength: 6.98MPa

    Elongation at break: 0.14%

    Thickness change:generally within 0.12%

  • WINS H-TEC FIRE PROTECTION PANEL9mm THICK ENCLOSURE SYSTEM

    FIG. NO.1:FOUR-SIDED WINS H-TEC FIRE PROTECTION PANEL

    HORIZONTAL ENCLOSURE SYSTEM FOR :4 HOURS INTEGRITY

    4 HOURS INSULATIONIN ACCORDANCE WITH BS EN 1364-2:1999, BS EN 1364-1:1999

    Page 2

    1 1 layer of WINS H-TEC FIRE PROTECTION PANEL of 9mm thick

    2 1 layer of WINS H-TEC FIRE PROTECTION PANEL FILLET 100mm width of 9mm thick positioned all board joints, except the corner longitudinal joints.

    3 Enclosure support, steel C-channel or L-angles

    4 Steel hanger rod at nominal 1000mm centres sizes according to limiting stress

    5 Steel channel collar, 32mmx50mmx32mmx0.5mm thick at butt joints at nominal 1220mm.

    6 Steel cable tray

    7 Rock wool 1 layer of 100mm thick with nominal density of 80Kg/m3

    8 Steel angle minimum 25mmx25mmx0.6mm thick

    Legend :

    1

    35

    4

    2

    7

    8

    6

    7

  • WINS H-TEC FIRE PROTECTION PANEL9mm THICK ENCLOSURE SYSTEM

    FIG. NO.2:THREE-SIDED WINS H-TEC FIRE PROTECTION PANEL

    HORIZONTAL ENCLOSURE SYSTEM FOR :4 HOURS INTEGRITY

    4 HOURS INSULATIONIN ACCORDANCE WITH BS EN 1364-2:1999, BS EN 1364-1:1999

    Page 3

    9

    7

    1 2 7

    3

    57

    48

    6

    6

    1 2 4

    7

    5

    107

    978

    1 1 layer of WINS H-TEC FIRE PROTECTION PANEL of 9mm thick

    2 1 layer of WINS H-TEC FIRE PROTECTION PANEL FILLET 100mm width of 9mm thick positioned all board joints, except the corner longitudinal joints.

    3 Steel hanger rod at nominal 1000mm centres sizes according to limiting stress

    4 Steel channel collar, 32mmx50mmx32mmx0.5mm thick at butt joints at nominal 1220mm.

    5 M4 Self-tapping screw at nominal 200mm centers

    6 M6 all steel expanding �xing at 500mm nominal centers

    7 Rock wool 1 layer of 100mm thick with nominal density of 80Kg/m3

    8 Steel angle minimum 25mmx25mmx0.6mm thick

    9 General E&M services. e.g. cable trucking and steel pipe etc.

    Cantilever arm at maximum 1250mm centers

    Legend :

    10

  • WINS H-TEC FIRE PROTECTION PANEL9mm THICK ENCLOSURE SYSTEM

    FIG. NO.3:TWO-SIDED WINS H-TEC FIRE PROTECTION PANEL

    ENCLOSURE SYSTEM FOR :4 HOURS INTEGRITY

    4 HOURS INSULATIONIN ACCORDANCE WITH BS EN 1364-2:1999, BS EN 1364-1:1999

    Page 4

    1 1 layer of WINS H-TEC FIRE PROTECTION PANEL of 9mm thick

    2 1 layer of WINS H-TEC FIRE PROTECTION PANEL FILLET 100mm width of 9mm thick positioned all board joints, except the corner longitudinal joints.

    3 Steel hanger rod at nominal 1000mm centres sizes according to limiting stress

    4 Steel channel collar, 32mmx50mmx32mmx0.5mm thick at butt joints at nominal 1220mm. Sizes may be larger to suit board and rock wool thickness

    5 M4 Self-tapping screw at nominal 200mm centers

    6 M6 all steel expanding �xing at 500mm nominal centers

    7 Rock wool 1 layer of 100mm thick with nominal density of 80Kg/m3

    8 Steel angle minimum 25mmx25mmx0.6mm thick

    9 General E&M services. e.g. cable trucking and steel pipe etc.

    Legend :

    3

    9

    6

    8

    5

    7

    21

    7

    7

    4

  • WINS H-TEC FIRE PROTECTION PANEL9mm THICK ENCLOSURE SYSTEM

    FIG. NO.4:ONE-SIDED WINS H-TEC FIRE PROTECTION PANEL

    ENCLOSURE SYSTEM FOR :4 HOURS INTEGRITY

    4 HOURS INSULATIONIN ACCORDANCE WITH BS EN 1364-2:1999, BS EN 1364-1:1999

    Page 5

    1 1 layer of WINS H-TEC FIRE PROTECTION PANEL of 9mm thick

    2 1 layer of WINS H-TEC FIRE PROTECTION PANEL FILLET 100mm width of 9mm thick positioned all board joints, except the corner longitudinal joints.

    3 Steel hanger rod at nominal 1000mm centres sizes according to limiting stress

    4 Steel channel collar, 32mmx50mmx32mmx0.5mm thick at butt joints at nominal 1220mm. Sizes may be larger to suit board and rock wool thickness

    5 M4 Self-tapping screw at nominal 200mm centers

    6 M6 all steel expanding �xing at 500mm nominal centers

    7 Rock wool 1 layer of 100mm thick with nominal density of 80Kg/m3

    8 Steel angle minimum 25mmx25mmx0.6mm thick

    9 General E&M services. e.g. cable trucking and steel pipe etc.

    Legend :

    39

    4

    6

    51 2 87

  • WINS H-TEC FIRE PROTECTION PANEL9mm THICK ENCLOSURE SYSTEM

    FIG. NO.5:FOUR-SIDED WINS H-TEC FIRE PROTECTION PANEL

    VERTICAL ENCLOSURE SYSTEM FOR :4 HOURS INTEGRITY

    4 HOURS INSULATIONIN ACCORDANCE WITH BS EN 1364-2:1999, BS EN 1364-1:1999

    Page 6

    1 1 layer of WINS H-TEC FIRE PROTECTION PANEL of 9mm thick

    2 1 layer of WINS H-TEC FIRE PROTECTION PANEL FILLET 100mm width of 9mm thick positioned all board joints, except the corner longitudinal joints.

    3 Steel hanger rod at nominal 1000mm centres sizes according to limiting stress

    4 Steel channel collar, 32mmx50mmx32mmx0.5mm thick at butt joints at nominal 1220mm. Sizes may be larger to suit board and rock wool thickness

    5 Steel cable tray

    6 M4 Self-tapping screw at nominal 200mm centers

    7 Rock wool 1 layer of 100mm thick with nominal density of 80Kg/m3

    8 General E&M services. e.g. cable trucking and steel pipe etc.

    9 Steel angle minimum 25mmx25mmx0.9mm thick fasten the service duct to the wall at nominal 1220mm centers.

    Construction wall

    Concrete �oor

    Legend :

    10

    11

    7

    2

    1

    3

    10

    4

    6

    11

    39

    8

    7

    5

  • WINS H-TEC FIRE PROTECTION PANEL9mm THICK ENCLOSURE SYSTEM

    FIG. NO.6:FOUR-SIDED WINS H-TEC FIRE PROTECTION PANEL

    HORIZONTAL ENCLOSURE SYSTEM FOR :2 HOURS INTEGRITY

    2 HOURS INSULATIONIN ACCORDANCE WITH BS EN 1364-2:1999, BS EN 1364-1:1999

    Page 7

    1

    35

    4

    2

    7

    8

    6

    9

    1 1 layer of WINS H-TEC FIRE PROTECTION PANEL of 9mm thick

    2 1 layer of WINS H-TEC FIRE PROTECTION PANEL FILLET 100mm width of 9mm thick positioned all board joints, except the corner longitudinal joints.

    3 Enclosure support, steel C-channel or L-angles

    4 Steel hanger rod at nominal 1000mm centres sizes according to limiting stress

    5 Steel channel collar, 32mmx50mmx32mmx0.5mm thick at butt joints at nominal 1220mm.

    6 Steel cable tray

    7 Rock wool 1 layer of 50mm thick with nominal density of 110Kg/m3

    8 Steel angle minimum 25mmx25mmx0.6mm thick

    Legend :

  • WINS H-TEC FIRE PROTECTION PANEL9mm THICK ENCLOSURE SYSTEM

    FIG. NO.7:THREE-SIDED WINS H-TEC FIRE PROTECTION PANEL

    ENCLOSURE SYSTEM FOR :2 HOURS INTEGRITY

    2 HOURS INSULATIONIN ACCORDANCE WITH BS EN 1364-2:1999, BS EN 1364-1:1999

    Page 8

    1 1 layer of WINS H-TEC FIRE PROTECTION PANEL of 9mm thick

    2 1 layer of WINS H-TEC FIRE PROTECTION PANEL FILLET 100mm width of 9mm thick positioned all board joints, except the corner longitudinal joints.

    3 Steel hanger rod at nominal 1000mm centres sizes according to limiting stress

    4 Steel channel collar, 32mmx50mmx32mmx0.5mm thick at butt joints at nominal 1220mm.

    5 M4 Self-tapping screw at nominal 200mm centers

    6 M6 all steel expanding �xing at 500mm nominal centers

    7 Rock wool 1 layer of 50mm thick with nominal density of 110Kg/m3

    8 Steel angle minimum 25mmx25mmx0.6mm thick

    9 General E&M services. e.g. cable trucking and steel pipe etc.

    Cantilever arm at maximum 1250mm centers

    Legend :

    10

    9

    7

    1 2 7

    3

    57

    48

    6

    6

    1 2 4

    7

    5

    107

    978

  • WINS H-TEC FIRE PROTECTION PANEL9mm THICK ENCLOSURE SYSTEM

    FIG. NO.8:TWO-SIDED WINS H-TEC FIRE PROTECTION PANEL

    ENCLOSURE SYSTEM FOR :2 HOURS INTEGRITY

    2 HOURS INSULATIONIN ACCORDANCE WITH BS EN 1364-2:1999, BS EN 1364-1:1999

    Page 9

    1 1 layer of WINS H-TEC FIRE PROTECTION PANEL of 9mm thick

    2 1 layer of WINS H-TEC FIRE PROTECTION PANEL FILLET 100mm width of 9mm thick positioned all board joints, except the corner longitudinal joints.

    3 Steel hanger rod at nominal 1000mm centres sizes according to limiting stress

    4 Steel channel collar, 32mmx50mmx32mmx0.5mm thick at butt joints at nominal 1220mm. Sizes may be larger to suit board and rock wool thickness

    5 M4 Self-tapping screw at nominal 200mm centers

    6 M6 all steel expanding �xing at 500mm nominal centers

    7 Rock wool 1 layer of 50mm thick with nominal density of 110Kg/m3

    8 Steel angle minimum 25mmx25mmx0.6mm thick

    9 General E&M services. e.g. cable trucking and steel pipe etc.

    Legend :

    3

    9

    6

    8

    5

    7

    21

    7

    7

    4

  • WINS H-TEC FIRE PROTECTION PANEL9mm THICK ENCLOSURE SYSTEM

    FIG. NO.9:ONE-SIDED WINS H-TEC FIRE PROTECTION PANEL

    ENCLOSURE SYSTEM FOR :2 HOURS INTEGRITY

    2 HOURS INSULATIONIN ACCORDANCE WITH BS EN 1364-2:1999, BS EN 1364-1:1999

    Page 10

    39

    4

    6

    51 2 87

    1 1 layer of WINS H-TEC FIRE PROTECTION PANEL of 9mm thick

    2 1 layer of WINS H-TEC FIRE PROTECTION PANEL FILLET 100mm width of 9mm thick positioned all board joints, except the corner longitudinal joints.

    3 Steel hanger rod at nominal 1000mm centres sizes according to limiting stress

    4 Steel channel collar, 32mmx50mmx32mmx0.5mm thick at butt joints at nominal 1220mm. Sizes may be larger to suit board and rock wool thickness

    5 M4 Self-tapping screw at nominal 200mm centers

    6 M6 all steel expanding �xing at 500mm nominal centers

    7 Rock wool 1 layer of 50mm thick with nominal density of 110Kg/m3

    8 Steel angle minimum 25mmx25mmx0.6mm thick

    9 General E&M services. e.g. cable trucking and steel pipe etc.

    Legend :

  • WINS H-TEC FIRE PROTECTION PANEL9mm THICK ENCLOSURE SYSTEM

    FIG. NO.10:FOUR-SIDED WINS H-TEC FIRE PROTECTION PANEL

    VERTICAL ENCLOSURE SYSTEM FOR :2 HOURS INTEGRITY

    2 HOURS INSULATIONIN ACCORDANCE WITH BS EN 1364-2:1999, BS EN 1364-1:1999

    Page 11

    1 1 layer of WINS H-TEC FIRE PROTECTION PANEL of 9mm thick

    2 1 layer of WINS H-TEC FIRE PROTECTION PANEL FILLET 100mm width of 9mm thick positioned all board joints, except the corner longitudinal joints.

    3 Steel hanger rod at nominal 1000mm centres sizes according to limiting stress

    4 Steel channel collar, 32mmx50mmx32mmx0.5mm thick at butt joints at nominal 1220mm. Sizes may be larger to suit board and rock wool thickness

    5 Steel cable tray

    6 M4 Self-tapping screw at nominal 200mm centers

    7 Rock wool 1 layer of 50mm thick with nominal density of 110Kg/m3

    8 General E&M services. e.g. cable trucking and steel pipe etc.

    9 Steel angle minimum 25mmx25mmx0.9mm thick fasten the service duct to the wall at nominal 1220mm centers.

    Construction wall

    Concrete �oor

    Legend :

    10

    11

    7

    2

    1

    3

    10

    4

    6

    11

    39

    8

    7

    5

  • WINS H-TEC FIRE PROTECTION PANEL9mm THICK ENCLOSURE SYSTEM WITH ACCESS PANEL

    4 hours �re rating, integrity in accordance withBS EN 1364-2:1999, BS EN 1364-1:2015

    FIG. NO. 1:FOUR-SIDED WINS H-TEC FIRE PROTECTION PANEL

    HORIZONTAL ENCLOSURE SYSTEM

    Page 12

    1 WINS H-Tec �re protection panel, 9mm thick

    2 WINS H-Tec �re protection �llet, 100mm width, 9mm thick (inside or outside) positioned all board joints, except the corner longitudinal joints

    3 Enclosure support, steel C-channel or L-angles

    4 Steel hanger rod at nominal 1000mm centres sizes according to limiting stress

    5 Steel channel collar, 32x50x0.5mm thick at butt joints at nominal 1220mm centers

    6 Steel cable tray

    7 Steel angle minimum 25x25x0.6mm thick

    8 M6 all steel expanding �xing at 500mm nominal centers

    9 M4 Self-tapping screw at nominal 200mm centers

    General E&M services. e.g. cable trucking and steel pipe etc.

    Cantilever arm at maximum 1250mm centers

    Steel angle minimum 50x50x0.9mm thick fasten the service duct to the wall at nominal 1200mm centers

    Construction wall

    Concrete �oor

    C-channel 50x50x50x0.6mm thick

    Access panel not exceeding 610mmx610mm

    Legend :

    10

    11

    12

    13

    14

    15

    16

    ACCESSPANEL

    (OPTIONAL)

    1

    15

    9

    16

    35

    4

    2 6

    7

  • WINS H-TEC FIRE PROTECTION PANEL9mm THICK ENCLOSURE SYSTEM WITH ACCESS PANEL

    4 hours �re rating, integrity in accordance withBS EN 1364-2:1999, BS EN 1364-1:2015

    FIG. NO. 2: THREE-SIDED CONSTRUCTION FROM FLOOR SOFFIT

    FIG. NO.2: THREE-SIDED CONSTRUCTION FROM SIDE WALL

    Page 13

    1 WINS H-Tec �re protection panel, 9mm thick

    2 WINS H-Tec �re protection �llet, 100mm width, 9mm thick (inside or outside) positioned all board joints, except the corner longitudinal joints

    3 Enclosure support, steel C-channel or L-angles

    4 Steel hanger rod at nominal 1000mm centres sizes according to limiting stress

    5 Steel channel collar, 32x50x0.5mm thick at butt joints at nominal 1220mm centers

    6 Steel cable tray

    7 Steel angle minimum 25x25x0.6mm thick

    8 M6 all steel expanding �xing at 500mm nominal centers

    9 M4 Self-tapping screw at nominal 200mm centers

    General E&M services. e.g. cable trucking and steel pipe etc.

    Cantilever arm at maximum 1250mm centers

    Legend :

    10

    11

    4 HRS. INTEGRITY

    ACCESSPANEL

    (OPTIONAL)

    ACCESSPANEL

    (OPTIONAL)

    4

    487

    87

    10

    1 2 5 9

    410

    1 2 5 9 9

    4

    5

    4

    5

    4 HRS. INTEGRITY

    ACCESSPANEL

    (OPTIONAL)

    ACCESSPANEL

    (OPTIONAL)

    81 2

    5 7

    10911

    81

    5

    72

    4

    1 2 910

  • WINS H-TEC FIRE PROTECTION PANEL9mm THICK ENCLOSURE SYSTEM WITH ACCESS PANEL

    Page 14

    1 WINS H-Tec �re protection panel, 9mm thick

    2 WINS H-Tec �re protection �llet, 100mm width, 9mm thick (inside or outside) positioned all board joints, except the corner longitudinal joints

    3 Enclosure support, steel C-channel or L-angles

    4 Steel hanger rod at nominal 1000mm centres sizes according to limiting stress

    5 Steel channel collar, 32x50x0.5mm thick at butt joints at Fig nominal 1220mm centers

    6 Steel cable tray

    7 Steel angle minimum 25x25x0.6mm thick

    8 M6 all steel expanding �xing at 500mm nominal centers

    9 M4 Self-tapping screw at nominal 200mm centers

    General E&M services. e.g. cable trucking and steel pipe etc.

    Legend :

    10

    4 hours �re rating, integrity in accordance withBS EN 1364-2:1999, BS EN 1364-1:2015

    FIG. NO. 3:TWO-SIDED WINS H-TEC FIRE PROTECTION PANEL ENCLOSURE SYSTEM

    ACCESSPANEL

    (OPTIONAL)

    4

    10

    87

    5921

  • WINS H-TEC FIRE PROTECTION PANEL9mm THICK ENCLOSURE SYSTEM WITH ACCESS PANEL

    4 hours �re rating, integrity in accordance withBS EN 1364-2:1999, BS EN 1364-1:2015

    FIG. NO. 4:ONE-SIDED WINS H-TEC FIRE PROTECTION PANEL ENCLOSURE SYSTEM

    Page 15

    1 WINS H-Tec �re protection panel, 9mm thick

    2 WINS H-Tec �re protection �llet, 100mm width, 9mm thick (inside or outside) positioned all board joints, except the corner longitudinal joints

    3 Enclosure support, steel C-channel or L-angles

    4 Steel hanger rod at nominal 1000mm centres sizes according to limiting stress

    5 Steel channel collar, 32x50x0.5mm thick at butt joints at Fig nominal 1220mm centers

    6 Steel cable tray

    7 Steel angle minimum 25x25x0.6mm thick

    8 M6 all steel expanding �xing at 500mm nominal centers

    9 M4 Self-tapping screw at nominal 200mm centers

    General E&M services. e.g. cable trucking and steel pipe etc.

    Legend :

    10

    4

    10

    5

    8

    91 2 7

  • 1 WINS H-Tec �re protection panel, 9mm thick

    2 WINS H-Tec �re protection �llet, 100mm width, 9mm thick (inside or outside) positioned all board joints, except the corner longitudinal joints

    3 Enclosure support, steel C-channel or L-angles

    4 Steel hanger rod at nominal 1000mm centres sizes according to limiting stress

    5 Steel channel collar, 32x50x0.5mm thick at butt joints at nominal 1220mm centers

    6 Steel cable tray

    7 Steel angle minimum 25x25x0.6mm thick

    8 M6 all steel expanding �xing at 500mm nominal centers

    9 M4 Self-tapping screw at nominal 200mm centers

    General E&M services. e.g. cable trucking and steel pipe etc.

    Cantilever arm at maximum 1250mm centers

    Steel angle minimum 50x50x0.9mm thick fasten the serviceduct to the wall at nominal 1200mm centers

    Construction wall

    Concrete �oor

    C-channel 50x50x50x0.6mm thick

    Access panel not exceeding 610mmx610mm

    Legend :

    10

    11

    12

    13

    14

    15

    16

    WINS H-TEC FIRE PROTECTION PANEL9mm THICK ENCLOSURE SYSTEM WITH ACCESS PANEL

    4 hours �re rating, integrity in accordance withBS EN 1364-2:1999, BS EN 1364-1:2015

    FIG. NO. 5:FOUR-SIDED WINS H-TEC FIRE PROTECTION PANEL

    VERTICAL ENCLOSURE SYSTEM

    Page 16

    ACCESSPANEL

    (OPTIONAL)

    6

    2

    1

    15

    13

    5

    9

    14

    4

    1216

    10

  • 1 WINS H-Tec �re protection panel, 9mm thick

    2 WINS H-Tec �re protection �llet, 100mm width, 9mm thick (inside or outside) positioned all board joints, except the corner longitudinal joints

    3 Enclosure support, steel C-channel or L-angles

    4 Steel hanger rod at nominal 1000mm centres sizes according to limiting stress

    5 Steel channel collar, 32x50x0.5mm thick at butt joints at nominal 1220mm centers

    6 Steel cable tray

    7 Steel angle minimum 25x25x0.6mm thick

    8 M6 all steel expanding �xing at 500mm nominal centers

    9 M4 Self-tapping screw at nominal 200mm centers

    General E&M services. e.g. cable trucking and steel pipe etc.

    Cantilever arm at maximum 1250mm centers

    Steel angle minimum 50x50x0.9mm thick fasten the serviceduct to the wall at nominal 1200mm centers

    Construction wall

    Concrete �oor

    C-channel 50x50x50x0.6mm thick

    Access panel not exceeding 610mmx610mm

    Steel stud channel 32x50x32x0.5mm thick

    Legend :

    10

    11

    12

    13

    14

    15

    16

    17

    WINS H-TEC FIRE PROTECTION PANEL9mm THICK ENCLOSURE SYSTEM WITH ACCESS PANEL

    4 hours �re rating, integrity in accordancewith BS EN 1364-2:1999, BS EN 1364-1:2015

    FIG. NO. 6:ACCESS PANEL DETAIL

    Page 17

    ACCESSPANEL

    OPTIONAL

    1

    15

    9

    163

    4

    2

    close open

    217

    15

    15

    171

    16

    9

    WINS ACCESS PANEL

    A.P. 16

    9

  • WINS H-TEC FIRE PROTECTION PANEL9mm THICK PARTITION SYSTEM WITH ACCESS PANEL

    4 hours �re rating, integrity in accordance with BS EN 1364-1:2015

    Page 18

    1 Wall

    2 Wins H-Tec Fire Protection Panel, 9mm thick

    3 Steel stud channel 32x50x32x0.5mm thick, @610mm c/c

    4 Ceiling �oor perimeter steel channel 24x50x24x0.5mm

    5 M4 Self-tapping screw, @200mm c/c

    6 M6 steel anchor bolt, @610mm c/c

    7 Board Joint, sealed with �re retardant sealant

    8 Wins H-Tec Fire Protection Panel Fillet, 9mm thick, 100mm width

    9 Access Panel (optional, any panel surface)

    Steel stud channel 50x50x50x0.6mm thick

    Legend :

    10

    close

    open

    5

    46

    8

    32

    7

    9

    8

    10

    1

    2

    5

    Access Port

    3

  • WINS H-TEC FIRE PROTECTION PANEL9mm THICK PARTITION SYSTEM

    4 hours �re rating, integrity in accordance with BS EN 1364-1:2015

    Page 19

    1 Wall

    2 Wins H-Tec Fire Protection Panel, 9mm thick

    3 Steel stud channel 32x50x32x0.5mm thick, @610mm c/c

    4 Ceiling �oor perimeter steel channel 24x50x24x0.5mm

    5 M4 Self-tapping screw, @200mm c/c

    6 M6 steel anchor bolt, @610mm c/c

    7 Board Joint, sealed with �re retardant sealant

    8 Wins H-Tec Fire Protection Panel Fillet, 9mm thick, 100mm width

    Legend :

    5

    46

    83

    2

    7

    1

    3

  • WINS H-TEC FIRE PROTECTION PANEL9mm THICK PARTITION SYSTEM

    4 hours �re rating, integrity and insulation in accordance with BS EN 1364-1:2015

    Page 20

    1 Wall

    2 Wins H-Tec Fire Protection Panel, 9mm thick

    3 Steel stud channel 32x50x32x0.5mm thick, @610mm c/c

    4 Ceiling �oor perimeter steel channel 24x50x24x0.5mm

    5 M4 Self-tapping screw, @200mm c/c

    6 M6 steel anchor bolt, @610mm c/c

    7 Board Joint, sealed with �re retardant sealant

    8 Wins H-Tec Fire Protection Panel Fillet, 9mm thick, 100mm width

    9 Rock wool density 80kg/m3 by 50mm thick

    Legend :

    5

    46

    8

    32

    7

    1

    3

    9

    9

  • WINS H-TEC FIRE PROTECTION PANEL12mm THICK PARTITION SYSTEM WITH ACCESS PANEL

    4 hours �re rating, integrity in accordance with BS EN 1364-1:2015

    Page 21

    1 Wall

    2 Wins H-Tec Fire Protection Panel, 12mm thick

    3 Steel stud channel 32x50x32x0.5mm thick, @610mm c/c

    4 Ceiling �oor perimeter steel channel 24x50x24x0.5mm

    5 M4 Self-tapping screw, @200mm c/c

    6 M6 steel anchor bolt, @610mm c/c

    7 Board Joint, sealed with �re retardant sealant

    8 Wins H-Tec Fire Protection Panel Fillet, 12mm thick, 100mm width

    9 Access Panel (optional, any panel surface)

    Steel stud channel 50x50x50x0.6mm thick

    Legend :

    10

    close

    open

    5

    46

    8

    32

    7

    9

    8

    10

    1

    2

    5

    Access Port

    3

  • WINS H-TEC FIRE PROTECTION PANEL12mm THICK PARTITION SYSTEM

    4 hours �re rating, integrity in accordance with BS EN 1364-1:2015

    Page 22

    1 Wall

    2 Wins H-Tec Fire Protection Panel, 12mm thick

    3 Steel stud channel 32x50x32x0.5mm thick, @610mm c/c

    4 Ceiling �oor perimeter steel channel 24x50x24x0.5mm

    5 M4 Self-tapping screw, @200mm c/c

    6 M6 steel anchor bolt, @610mm c/c

    7 Board Joint, sealed with �re retardant sealant

    8 Wins H-Tec Fire Protection Panel Fillet, 12mm thick, 100mm width

    Legend :

    5

    46

    83

    2

    7

    1

    3

  • WINS H-TEC FIRE PROTECTION PANEL12mm THICK PARTITION SYSTEM

    4 hours �re rating, integrity and insulation in accordance with BS EN 1364-1:2015

    Page 23

    1 Wall

    2 Wins H-Tec Fire Protection Panel, 12mm thick

    3 Steel stud channel 32x50x32x0.5mm thick, @610mm c/c

    4 Ceiling �oor perimeter steel channel 24x50x24x0.5mm

    5 M4 Self-tapping screw, @200mm c/c

    6 M6 steel anchor bolt, @610mm c/c

    7 Board Joint, sealed with �re retardant sealant

    8 Wins H-Tec Fire Protection Panel Fillet, 12mm thick, 100mm width

    9 Rock wool density 80kg/m3 by 50mm thick

    Legend :

    5

    46

    8

    32

    7

    1

    3

    9

    9

  • 1 Wins H-Tec Fire Protection Panel 9mm Thick

    2 Steel C-channel At 610mm Spacing 50 X 32 X 0.5mm Thick

    3 Furring Channel / Perimeter Channel 50 X 25 X 0.5mm Thick

    4 Steel Wire Hanger @ 1000mm C/C

    5 Board Joints -all Gaps Sealed By Intumescent Sealant

    6 Wins H-Tec Fire Protection Fillet 100mm Width 9mm Thick

    7 Self Tapping Screws At Nominal 200mm Centres

    8 Rockwool,2 Layers Of 50mm Thick,Density 80kg/m³

    Legend :

    H-TEC FIRE PROTECTION PANEL4 HOURS FIRE RESISTANCE CEILING SYSTEM

    Page 24

    9mm WINS H-Tec Fire Protection Panel4 hours �re resistance, integrity and insulation in accordance with BS EN 1364-2:1999

    1

    7

    25

    6

    4

    83

  • 1 Wins H-Tec Fire Protection Panel 12mm Thick

    2 Steel C-channel At 610mm Spacing 50 X 32 X 0.5mm Thick

    3 Furring Channel / Perimeter Channel 50 X 25 X 0.5mm Thick

    4 Steel Wire Hanger @ 1000mm C/C

    5 Board Joints -all Gaps Sealed By Intumescent Sealant

    6 Wins H-Tec Fire Protection Fillet 100mm Width 9mm Thick

    7 Self Tapping Screws At Nominal 200mm Centres

    8 Rockwool,2 Layers Of 50mm Thick,Density 80kg/m³

    Legend :

    H-TEC FIRE PROTECTION PANEL4 HOURS FIRE RESISTANCE CEILING SYSTEM

    Page 25

    12mm WINS H-Tec Fire Protection Panel4 hours �re resistance, integrity and insulation in accordance with BS EN 1364-2:1999

    1

    7

    25

    6

    4

    83

  • H-TEC FIRE PROTECTION PANEL4 HOURS FIRE RESISTANCE CEILING SYSTEM

    Page 26

    9mm WINS H-Tec Fire Protection Panel4 hours �re resistance, integrity in accordance with BS EN 1364-2:1999

    1 Wins H-Tec Fire Protection Panel 9mm Thick

    2 Steel C-channel At 610mm Spacing 50 X 32 X 0.5mm Thick

    3 Furring Channel / Perimeter Channel 50 X 25 X 0.5mm Thick

    4 Steel Wire Hanger @ 1000mm C/C

    5 Board Joints -All Gaps Sealed By Intumescent Sealant

    6 Wins H-Tec Fire Protection Fillet, 100mm Width 9mm Thick

    7 Self Tapping Screws At Nominal 200mm Centres

    1 Wins H-Tec Fire Protection Panel 9mm Thick

    2 Steel C-channel At 610mm Spacing 50x32x0.5mm Thick

    3 Furring Channel/perimeter C-channel 50x25x0.5mm Thick

    4 Steel Wire Hanger @1000mm C/C

    5 Board Joints – All Gaps Sealed By Intumescent Sealant

    6 Wins H-Tec Fire Protection Fillet, 100mm Width 9mm Thick

    7 Self Tapping Screws At Nominal 200mm Centres

    4

    6

    3

    7

    21 5

    1

    7

    25

    6

    4

    3

  • Page 27

    1 Wins H-Tec Fire Protection Panel, 9mm thick

    2 Wins H-Tec Fire Protection Fillets 100mm wide x 9mm thick

    3 Top steel channel, 24mmx50mmx24mmx1mm thick

    4 Horizontal steel stud, 32mmx50mmx32mmx0.5mm thick

    5 Bottom steel channel, 24mmx50mmx24mmx0.5mm thick

    6 M8 anchor bolt, @610mm c/c

    7 M4x25mm self-tapping screw, @200mm c/c

    8 Furnace wall

    9 30mm free edge

    Board Joints with �re retardant sealant

    Vertical steel stud, 32mmx50mmx32mmx0.5mm thick, @610mm c/c

    Legend :

    10

    11

    7

    Detail A

    Detail B

    Detail C

    5

    2

    1

    1

    4

    3

    6

    Detail A Detail B Detail C

    WINS H-TEC FIRE PROTECTION PANEL9mm WINS H-TEC Smoke Barrier System

    2 hours �re rating, integrity in accordance with BS 476: Part 22: 1987

  • WINS H-TEC FIRE PROTECTION PANEL9mm WINS H-TEC Smoke Barrier System

    2 hours �re rating, integrity in accordance with BS 476: Part 22: 1987

    Page 28

    1 Wins H-Tec Fire Protection Panel, 9mm thick

    2 Wins H-Tec Fire Protection Fillets 100mm wide x 9mm thick

    3 Top steel channel, 24mmx50mmx24mmx1mm thick

    4 Horizontal steel stud, 32mmx50mmx32mmx0.5mm thick

    5 Bottom steel channel, 24mmx50mmx24mmx0.5mm thick

    6 M8 anchor bolt, @610mm c/c

    7 M4x25mm self-tapping screw, @200mm c/c

    8 Furnace wall

    9 30mm free edge

    Board Joints with �re retardant sealant

    Vertical steel stud, 32mmx50mmx32mmx0.5mm thick, @610mm c/c

    Legend :

    10

    11

    5

    4

    3

    10

    7

    1

    2

    11

    2

    1

    2

  • Website : www.winsconsultants.com