WHCA / WiCAL 2017

20
WHCA / WiCAL 2017 DHS DQA 1 Life Safety Code Update April 7, 2017 WHCA / WiCAL 55 th Annual Conference David Soens, PE, RA Life Safety Fire Authority Add C 2 Overview Introduction Federal updates LSC data – Top 10 Systems approach Correction 3 Resources Internet: DQA construction 4 Priorities #1 Federal surveyor Centers for Medicare & Medicaid Services #2 State plan reviewer Verification #3 State inspector Validation 5 QUALITY vs RISK Direct relationship Role of the Facility 6 Motivation Regulations exist to avoid negative outcomes or Regulations exist to ensure the right things happen

Transcript of WHCA / WiCAL 2017

Page 1: WHCA / WiCAL 2017

WHCA / WiCAL 2017

DHS DQA

1

Life Safety Code Update

April 7, 2017

WHCA / WiCAL 55th Annual Conference

David Soens, PE, RALife Safety Fire Authority

Add C

2

Overview

• Introduction

• Federal updates

• LSC data – Top 10

• Systems approach

• Correction

3

Resources

Internet: DQA construction4

Priorities

#1 Federal surveyorCenters for Medicare & Medicaid Services

#2 State plan reviewerVerification

#3 State inspectorValidation

5

QUALITY vs RISK

Direct relationship

Role of the Facility

6

Motivation

Regulations exist to avoid negative outcomes

or

Regulations exist to ensure the right things happen

Page 2: WHCA / WiCAL 2017

WHCA / WiCAL 2017

DHS DQA

7

Ground Rules

Read code

Understand use

Code in effect remains

Nothing guarantees success

Code is not a design manual

10,000 rule

8

Question

Is there one answer for every code question

(a) True

(b) I don’t know

(c) False

9

Data

Fatalities / Year Healthcare (fire) 5

Airline Passengers 520

Motor Vehicle 41,800

Hospital Infections 100,000

Lung Cancer 124,000

Heart Disease 125,000

Source: ASHE Training Seminar

10

Fire Data

Leading Causes of FireCooking 41%

Clothes dryer 14%

Heating equip. 9%

Smoking 7%

Electrical 6%

Intentional 4%

Trash 2%Source: NFPA Fire Analysis and Research

11

Federal Policy

Life safety survey process• Entrance • Building observations• Document review• Exit

12

Federal Prep

Accurate life safety plans

• Legible 11 x 17 or larger

• Building & department names

• Year constructed

• Construction type I, II, III …

• Sprinkler status : full, partial, or none

• Occupancy : health, ambulatory, clinic

• Smoke compartment : name & area

Page 3: WHCA / WiCAL 2017

WHCA / WiCAL 2017

DHS DQA

13

Federal Prep

Organized testing records

• Dated documents

• Who completed the testing

• What did they do

• How where problems corrected

• Scope of the system

• Operational / procedures / equipment

• Historical archives

• Contacts14

Life Safety Plan

15

Question

Is the LSC survey process changing …

a) Yes

b) It depends

c) No

16

CMS

Active

Operations

Total Concept

Passive

17

2012 Edition of NFPA 101

Life Safety Code (LSC)

18

LSC Policy

Facility agrees to be certified and follow NFPA 101 ….

LSC rules apply to the resident regardless of their location

customary accessLSC 18.1.3.3

Page 4: WHCA / WiCAL 2017

WHCA / WiCAL 2017

DHS DQA

19

2012 Life Safety Code

• New Health Care Facilities– Approved after July 5, 2016

LSC chapter 18

• Existing Health Care Facilities– Approved or built prior to July 5, 2016

LSC chapter 19

20

Codes vs Standards

NFPA

NFPA

NFPA

NFPANFPA

NFPA

NFPA

NFPA

NFPA

NFPA

NFPANFPA

NFPA

101101

21

Updated Standards

• NFPA 13 Sprinkler systems 2010

• NFPA 70 Electrical 2011

• NFPA 72 Fire Alarm 2010

• NFPA 80 Fire Doors 2010

• NFPA 90A Ventilation 2012

• NFPA 96 Cooking 2011

• NFPA 99 Health Care 2012

• NFPA 110 Emergency power 201022

Health Care

Subsection19.1 19.219.319.419.519.719.X

Chapter 19 Organization

DescriptionGeneralEgress

ProtectionSpecialUtilities

OperationsNFPA 99

23

Health Care

SubsetK- 100 seriesK- 200 seriesK- 300 seriesK- 400 seriesK- 500 seriesK- 700 seriesK- 900 series

Organization

DescriptionGeneralEgress

ProtectionSpecialUtilities

OperationsNFPA 99

Subsection19.1 19.219.319.419.519.719.X

24

LSC Surveyor Form

CMS-2786R 2016 version

Page 5: WHCA / WiCAL 2017

WHCA / WiCAL 2017

DHS DQA

25

Wisconsin Top 10

1 sprinkler testing K-3532 hazardous areas K-3213 fire drills K-7124 corridor doors K-3635 fire alarm testing K-3456 utilities K-5117 generator testing K-9188 exit access K-2119 fire alarm installation K-34110 sprinkler installation K-351

26

Corridor Doors K363

• Gap between leafs• 1/8 inch allowance

• Corridor doors

• Smoke barrier doors

• Hazardous room doors

• Fire wall doors

• Exceed 1/8 inch = “astragal”

• Avoid gaskets

27

Corridor Doors K363

• Inactive leafs• Auto flush bolts

• Corridor doors

• Sleeping room

• Therapy room

• Occupied rooms

28

Walls

• Common Deficiencies– Holes

– Cracks

– Concrete block removed

– Improper materials

– Reception Window

– None latching doors

– Door clearances

29

Wall Lessons

• Lessons Learnedo Life Safety Plan

o Contract requirements

o Proactive maintenance• Suggestion: 1-wing per quarter

– Door latching manual testing

– Above ceiling visual inspection

30

Hazard Classification

Hazard of contents shall be classified by the registered design professional

(RDP)

LSC 6.2.1.2

Page 6: WHCA / WiCAL 2017

WHCA / WiCAL 2017

DHS DQA

31

Hazards

Degree of hazard greater than normal shall provide one of the following(1) Enclose area with 1-hour fire rating,(2) Protect the area with automatic extinguishment, or(3) Apply both (1) and (2) where the hazard is severe

LSC 8.7.1.1

32

• Hazardous Areaso Boiler and fuel-fire heater rooms

o Laundries (greater than 100 sq feet)

o Repair, maintenance and paint shops

o Combustible storage (> 50 sq feet)

o Trash collection rooms (> 64 gallon)

o Soiled linen rooms (> 64 gallon)

Hazards K321

33

Hazards K321

34

• Common Deficiencies– Enclosure penetrations

– Door with no closing device

– Door won’t close and latch

– Combustible storage outside of a hazardous room enclosure

Hazards K321

35

Hazard Lessons

• Seal all enclosure penetrations

• Ensure door closing is working

• Ensure door latches into frame

• Inventory combustible storage

36

Sprinklers

Page 7: WHCA / WiCAL 2017

WHCA / WiCAL 2017

DHS DQA

37

Sprinkler Credits

Full building sprinkler credits• Construction type

• Travel distance

• Delayed-egress door locking

• Hazardous room enclosure

• Corridor walls & doors

• Smoke dampers

• Window sizes

38

Sprinkler Testing K353

• Weekly / monthly inspections

• Quarterly tests

• Annual tests

• Five year internal inspections

• Twenty year fast response testing

• Fifty year sprinkler test

2011 NFPA 25 Table 5.1.1.2

39

Clean Agent Testing

• Semi-annual agent test

• Annual enclosure inspection

• Supervised by fire alarm system

• Existing elevator applications

• Limited coverage

2012 NFPA 2001

LSC 9.7.3

40

Sprinklers K353

41

• Common Deficiencies– Obstructions

– Missing quarterly tests

– Dirt buildup on sprinkler head

– Spare heads for each sprinkler type

– Lacking supervision by fire alarm system

Sprinklers K353

42

Sprinkler Lessons

• Perform all tests – weekly, monthly, quarterly, and annual

• Remove lint or dust from sprinklers

• Replace broken or damaged sprinklers

• Supply sufficient number of spares– two per each type

Page 8: WHCA / WiCAL 2017

WHCA / WiCAL 2017

DHS DQA

43

Fire Drill K712

Written plan for the protection of all residents and for their evacuation in

the event of an emergency

Drills are held at unexpected times under varying conditions

44

(1) Use of alarms

(2) Transmission of alarms to fire department

(3) Emergency phone call to fire department

(4) Response to alarms

(5) Isolation of fire

(6) Evacuation of immediate area

(7) Evacuation of smoke compartment

(8) Preparation of floors and building for evacuation

(9) Extinguishment of fire

LSC 19.7.2.2

Fire Drill K712

45

Fire Drill Planning

46

Fire Drill K712

• Common Deficiencies– Lack of staff participation

– Missing smoke compartment

– Pattern of drills

47

Staff Participation Example

Fire Drills

48

Fire Drill Lessons

• Maximize staff involvement

• Include smoke compartment

• Distribute drills within shift

• Train new staff promptly

• Staff are your best detectors

Page 9: WHCA / WiCAL 2017

WHCA / WiCAL 2017

DHS DQA

49

Fire Alarm System Documentation

50

Smoke entry test is requiredListed aerosol

2010 NFPA 72Table 14.4.2.2 Item 14 g

Magnets can not fulfill this testThis test is required for all systems

Functional Test K345

51

One year after installationTwo year thereafter

Five year if within range

Factory range, measured, pass / fail

2010 NFPA 72 – 14.4.5.3

Sensitivity Test K345

52

• Test all interface connectionso Main to remote panelo Kitchen hoodo Delayed egress doorso Elevatorso Fan shut-downo Smoke damperso Door hold-openso Fire pumps

Fire Alarm Testing K345

53

Fire Alarm Lessons

• Perform quarterly off-premises transmission and document

• Maintain entire system

• Test all components

• One record in one location

Integrate facility systems

54

Functional testing and inspection1 year after installation

4 year cycle thereafterHospitals permitted every 6 years

2010 NFPA 80 – 19.4 2010 NFPA 105 - 6.5

Damper Testing

Page 10: WHCA / WiCAL 2017

WHCA / WiCAL 2017

DHS DQA

55

Access shall be verified and corrected

Fusible links shall be removed to ensure full closure

Document location, date, inspector name, and deficiencies discovered

Document how deficiencies were corrected

2010 NFPA 80 – 19.4 2010 NFPA 105 - 6.5

Damper Testing

56

Damper Fusible Link

57

Culture Change

58

Culture Change

59

Culture Change

60

Private Room

Page 11: WHCA / WiCAL 2017

WHCA / WiCAL 2017

DHS DQA

61

ComparisonInstitutional (facility) Culture Change (resident)

Locked exit doors No locks

Group feedings on facility schedule

Private dining experiences on resident’s schedule

Large group activities chosen by facility activity director

Variety of activities chosen by resident

Staff assigned to specific tasks Universal worker assigned to household

Double loaded corridors Households with up to 10-12

Shared rooms Private rooms

62

Cooking Options

I. Central

II. Limited• No grease or smoke vapors

III. Decentralized• 30 or less• NFPA 96 full effect

63

Central

64

Suppression

65

Limited Cooking

Residential equipment used for food warming shall not be required to be protected as a

hazard

Annex: Intended to permit small appliances used for reheating, such as microwave ovens, hot plates, toasters, and nourishment centers

LSC 18.3.2.5.2

66

Limited Cooking

Page 12: WHCA / WiCAL 2017

WHCA / WiCAL 2017

DHS DQA

67

Limited Cooking

No grease or smoke vapors68

Limited Cooking

Steam table

69

Decentralized Cooking

Staff supervision70

Decentralized Cooking

Stainless & seamless

71

Decentralized Cooking

Permitted open to the corridor

• Limited capacity of 30 beds

• Smoke barrier separated cooking area

• Type I grease hood– Minimum 500 CFM exhaust

– No corridor plenums IBC 1018.5

– Makeup air required IMC 508

– No flex duct

LSC 18.3.2.5.3

72

• Fire suppression UL 300 or UL 300A

• Manual release of the extinguishing system per NFPA 96

• Interlock turns off all sources of fuel and electrical when fire suppression is activated

LSC 18.3.2.5.3 continued

Decentralized Cooking

Page 13: WHCA / WiCAL 2017

WHCA / WiCAL 2017

DHS DQA

73

• Portable fire extinguishers are located in all kitchen areas

• Kill switch deactivates all equipment, restricted access and defaults on a 120 minute timeframe

• Prohibited solid fuel or deep-fat frying

LSC 18.3.2.5.3 continued

Decentralized Cooking

74

• Inspection, testing, and cleaning of every cooking station per NFPA 96

• Smoke detection in the corridor inspected, tested, and maintained NFPA 72

• Sprinkler protected smoke compartment inspected, tested, and maintained NFPA 25

LSC 18.3.2.5.3

Decentralized Cooking

75

Station Kill Switch

Concealed76

Semi-annual Inspection

Clean when dirty

77

Cooking K324

• Common Deficiencies– Not connected to fire alarm

– Missing semi-annual inspection

– Not cleaning when dirty

78

• Moderate volume operations• Semi-annual Inspections

• Suppression system links• Semi-annual replacement

• Clean when dirty• Hood to fan

2011 NFPA 96 – Chapter 11

Cooking K324

Page 14: WHCA / WiCAL 2017

WHCA / WiCAL 2017

DHS DQA

79

Cooking Lessons

• Staff trained

• Connected to fire alarm system

• Semi-annual inspection

• Access to equipment

• Fuel shut-off locations

80

Fireplaces

81

Fireplace Option

Direct-vent gas fireplaces are permitted

• Glass seal front with mesh screen

• Installed and maintenance per NFPA 54

• Quick response sprinkler protection

• Controls are locked or restrict access

• Carbon monoxide local detectors

• No fireplaces inside of a sleeping room

LSC 18.5.2.382

Solid fuel–burning fireplaces are permitted

• Fire separation of 1-hour fire resistance

• Fireplace installed and maintenance NFPA 211

• Hearth a minimum of 4 in height

• Heat tempered glass enclosure

• Supervised carbon monoxide detection

• AHJ input for other precautions

LSC 18.5.2.3

Fireplace Option

83

Question

Is staff supervision critical when a fire place is burning fuel ?

a) Yes

b) Don’t know

c) No

84

Medical Equipment

Page 15: WHCA / WiCAL 2017

WHCA / WiCAL 2017

DHS DQA

85

Medical Equipment

Wheeled equipment permitted in 8 foot corridors

• Maintain minimum 60 in. clear width• Fire plan and training relocate equipment• Permitted wheeled equipment

o Equipment in useo Medical emergency equipmento Patient lift and transport equipment

LSC 18.2.3.4 (4)

86

Fixed Furniture

87

Fixed Furniture

Fixed furniture permitted within 8 ft corridors

• furniture is attached to the floor or wall• maintains a minimum 72 in. clear width• located only on one side of the corridor• grouped in 50 ft2 areas or less • groupings separated by at least 10 ft• does not obstruct access to building / fire equipment• smoke detected corridors, or the furniture allows

direct supervision by facility staff at a staff station

LSC 18.2.3.4 (5)

88

Equipment & Furniture

89

Furnishings, Mattresses, and Decorations

Draperies, curtains, and other loosely hanging fabrics and films serving as furnishings or decorations in health care occupancies shall meet the flame propagation performance criteria contained in NFPA 701

LSC 18.7.5.1

Furnishings

90

Furnishings

Page 16: WHCA / WiCAL 2017

WHCA / WiCAL 2017

DHS DQA

91

Exempt flame propagation criteria

• shower curtains

• draperies at sleeping room windows

• draperies and curtains

• Individual panel less than 48 ft2 and

• total area is less than 20 percent of the wall area

LSC 18.7.5.1

Furnishings

92

Combustible decorations are permitted when treated with an approved fire-retardant coating that is listed and labeled for the intended application

Decorations shall not interfere with door operation

Decorations shall not be placed on fire-rated doors

LSC 18.7.5.6

Decorations

93

Decorations on non-fire-rated door, wall, or ceiling areas

• 20 percent allowance • per room not sprinkler protected

• 30 percent allowance • per room sprinkler protected

• 50 percent allowance • per sleeping room not exceeding a four person capacity

within a sprinkler protected smoke compartment

LSC 18.7.5.6

Decorations

94

Maintain Control

95

NFPA 99

Essential Electrical

Medical Gas

Ventilation

Fire Protection

Hyperbaric

96

Chapter 4 Fundamentals

Risk assessment categories

New systems

Category 1 – major injury or death

Category 2 – minor injury

Category 3 – no injury yet discomfort

Category 4 – no impact

NFPA 99

Page 17: WHCA / WiCAL 2017

WHCA / WiCAL 2017

DHS DQA

97

Emergency Power K918

• Common Deficiencies– Insufficient testing

– No task lighting

– No manual stop switch

– No block heater

98

Emergency Power

99

Diesel generators exercised monthly

30 minutes @ 30% of the nameplate

Diesel generators that can not load to 30%

Annual load bank for 1.5 hours

Level 1 EPSS 36 month full duration test

All EPSS fuel shall be tested annually

2010 NFPA 110

Section 8.3.8 and 8.4.2

Generators K918

100

Spark-ignited generators

Exercised monthly

Loading with available load

2010 NFPA 110 - 8.4.2.4

Generators K918

101

Power Lessons

• Inspect generators weekly

• Test generators monthly

• Always record a generator load

• Test battery lighting 30 seconds monthly / 90 minutes annually

• Save those records

102

Fire Watch

• Evacuate building or fire watch

• Fire protection outage

o Fire Alarm : More than 4 in 24 hours

o Sprinkler : More than 10 in 24 hours

• Contact DHS and local fire authority

• Dedicated staff

• Continuous

Page 18: WHCA / WiCAL 2017

WHCA / WiCAL 2017

DHS DQA

103

Fire Watch question

Question: How are staff going to alert the fire department when the fire alarm system is down ?

104

Fire Watch Lessons

• Initiation at 4 or 10 hours

• Accurate contacts

• Fire alarm outage is different than a sprinkler outage

• Log rounds

• Continuous

105

DQA Memo

DQA Memo 17-003

Fire Plan, Watch, and Fire Reporting

106

Fire Watch Record

107

Written records shall be signed and kept onsite

New and existing door assemblies

Testing shall be performed by individuals who can demonstrate knowledge and understanding

2010 NFPA 80 Chapter 5

LSC 7.2.1.15

Fire Door Inspections

108

Floor space on both sides

Force necessary to open doors

Door hardware is functional

No damage to door, frame, or hardware

No field modifications to assembly

Powered doors open upon power failure

Signage is installed, intact, and legible

Delayed locking device operation and timing

Security features do not circumvent operation

Fire Door Inspections

Page 19: WHCA / WiCAL 2017

WHCA / WiCAL 2017

DHS DQA

109

Door openings not in proper operating condition shall be repaired or replaced without delay

LSC 7.2.1.15

Door Repairs

110

Plan of Correction

I’m going to fix

I can’t fix

I don’t need to fix

111

Correction Option I

• I’m going to fix• POC 30 or less days

• Avoid 45 – 90 day window

• Temp Waiver 91 - 364 days

• Temp Waiver 365 +

112

I’m going to Fix

• Temporary Waivers – Timetable with milestone dates

• site mobilization, installation, certification, inspection, final cleaning, occupancy

– Increased fire safety awareness • Interim Life Safety Measures

• Additional detection / extinguishes

• Fire Watch

113

Safeguarding Construction

Temporary Separation Walls

Walls shall have at least a 1-hour fire rating

Opening at least a 45-minute fire rating

Non-sprinkler protected construction

2009 NFPA 241 - 8.6.2

Interim Life Safety

114

Correction Option II

• I can’t fix– Waiver

• Not automatic

• Reviewed each year

• Two key criteria

Page 20: WHCA / WiCAL 2017

WHCA / WiCAL 2017

DHS DQA

115

Waivers

• Process• Deficiency

• Plan of Correction

• State Recommendation

• Federal Decision

• Notification

116

Waivers

• Financial Hardship • Estimated cost of the installation

• Extent and duration of the disruption of normal use of resident areas resulting from the construction work

• Estimated period over which cost would be recovered

• Remaining useful life of the building

• Availability of financing

117

Waiver Factors

• No adverse impact to resident safety

• Financial burden statement

• Staffing levels, training, and drills

• Additional fire safety measures

• Letters are current

• Name and signature

SOM 2480118

Correction Option III

• I don’t need to fix– FSES

• Credits offset deficiencies

• Not automatic

• Reviewed each year

• Entire building analysis

• 2013 NFPA 101A

119

Summary

State resources

Federal updates

LSC data – Top 10

Systems approach

Correction

120

Thank You

Wisconsin Dept of Health Services www.dhs.wisconsin.gov

David Soens(608) 266-8016

[email protected]