Application Data 29-167C Page 1 Cutler-Hammer Westinghouse & Cutler-Hammer Products Five Parkway Center Pittsburgh, Pennsylvania, U.S.A. 15220 October 1997 Mailed to: E/29-100A Breaker Description Curve No. Page Current Limit-R ® Circuit Breakers Type FCL 15 Amperes ................................................................................ SC-4340-80A 2 Type FCL 20 Amperes ................................................................................ SC-4341-80A 3 Type FCL 25 Amperes ................................................................................ SC-4342-80A 4 Type FCL 30 Amperes ................................................................................ SC-4343-80A 5 Type FCL 35 Amperes ................................................................................ SC-4344-80A 6 Type FCL 40 Amperes ................................................................................ SC-4345-80A 7 Type FCL 45 Amperes ................................................................................ SC-4346-80A 8 Type FCL 50 Amperes ................................................................................ SC-4347-80A 9 Type FCL 60 Amperes ................................................................................ SC-4348-80A 10 Type FCL 70 Amperes ................................................................................ SC-4349-80A 11 Type FCL 80 Amperes ................................................................................ SC-4350-80A 12 Type FCL 90 Amperes ................................................................................ SC-4351-80A 13 Type FCL 100 Amperes .............................................................................. SC-4352-80A 14 Types LCL and LCLG 125-250 Amperes ................................................... SC-3624-81A 15 Types LCLA and LCLGA 125-250 Amperes .............................................. SC-3625-81A 16 Types LCL and LCLG 200-400 Amperes ................................................... SC-3626-81A 17 Types LCLA and LCLGA 200-400 Amperes .............................................. SC-3627-81A 18 Ground Fault Pick-up Curves for Types LCLG and LCLGA .................... SC-3906-86A 19 Tri-Pac ® Current Limiting Circuit Breakers Type FB 15 Amperes .................................................................................. SC-3572-76A 20 Type FB 20 Amperes .................................................................................. SC-3573-76A 21 Type FB 30 Amperes .................................................................................. SC-3574-76A 22 Type FB 40 Amperes .................................................................................. SC-3575-76A 23 Type FB 50 Amperes .................................................................................. SC-3576-76A 24 Type FB 70 Amperes .................................................................................. SC-3577-76A 25 Type FB 90 Amperes .................................................................................. SC-3578-76A 26 Type FB 100 Amperes ................................................................................ SC-3579-76A 27 Time/Current Characteristic Curves for Westinghouse Current Limit-R ® Circuit Breakers and Tri-Pac ® Circuit Breakers Westinghouse AB DE-ION ® Current Limiting Circuit Breakers Individual oversize copies of curves listed above printed on onion-skin paper are available in limited quantity from: Cutler-Hammer Westinghouse & Cutler-Hammer Products Five Parkway Center Pittsburgh, PA 15220 When ordering onion-skin curves, use num- ber at bottom of page where curve appears, i.e., SC-4340-80. Requests for full sets of curves will not be honored. Voltages shown in curve headings are maximum at which the breaker may be applied. Interrupting capacity of individual breaker is tabulated on each curve. Type LA 70 Amperes .................................................................................. SC-3580-76A 28 Type LA 90 Amperes .................................................................................. SC-3581-76A 29 Type LA 100 Amperes ................................................................................ SC-3582-76A 30 Type LA 125 Amperes ................................................................................ SC-3583-76A 31 Type LA 150 Amperes ................................................................................ SC-3584-76A 32 Type LA 175 Amperes ................................................................................ SC-3585-76A 33 Type LA 200 Amperes ................................................................................ SC-3586-76A 34 Type LA 225 Amperes ................................................................................ SC-3587-76A 35 Type LA 250 Amperes ................................................................................ SC-3588-76A 36 Type LA 300 Amperes ................................................................................ SC-3589-76A 37 Type LA 350 Amperes ................................................................................ SC-3590-76A 38 Type LA 400 Amperes ................................................................................ SC-3591-76A 39 Type NB 300 Amperes ............................................................................... SC-3592-76B 40 Type NB 350 Amperes ............................................................................... SC-3593-76B 41 Type NB 400 Amperes ............................................................................... SC-3594-76B 42 Type NB 500 Amperes ............................................................................... SC-3595-76B 43 Type NB 600 Amperes ............................................................................... SC-3596-76B 44 Type NB 700 Amperes ............................................................................... SC-3597-76B 45 Type NB 800 Amperes ............................................................................... SC-3598-76B 46 Type PB 600 Amperes ................................................................................ SC-3599-76B 47 Type PB 800 Amperes ................................................................................ SC-3600-76B 48 Type PB 1000 Amperes .............................................................................. SC-3601-76B 49 Type PB 1200 Amperes .............................................................................. SC-3602-76B 50 Type PB 1400 Amperes .............................................................................. SC-3603-76B 51 Type PB 1600 Amperes .............................................................................. SC-3604-76B 52

Transcript of Westinghouse AB DE-ION Current Limiting Circuit Breakerspub/@electrical/... · Application Data...

Page 1: Westinghouse AB DE-ION Current Limiting Circuit Breakerspub/@electrical/... · Application Data 29-167C Page 3 October 1997 AB DE-ION Current Limit-R® Circuit Breakers Type FCL,

Application Data29-167C

Page 1

Cutler-HammerWestinghouse &Cutler-Hammer ProductsFive Parkway CenterPittsburgh, Pennsylvania, U.S.A. 15220

October 1997Mailed to: E/29-100A

Breaker Description Curve No. Page

Current Limit-R® Circuit BreakersType FCL 15 Amperes ................................................................................ SC-4340-80A 2Type FCL 20 Amperes ................................................................................ SC-4341-80A 3Type FCL 25 Amperes ................................................................................ SC-4342-80A 4Type FCL 30 Amperes ................................................................................ SC-4343-80A 5Type FCL 35 Amperes ................................................................................ SC-4344-80A 6Type FCL 40 Amperes ................................................................................ SC-4345-80A 7Type FCL 45 Amperes ................................................................................ SC-4346-80A 8Type FCL 50 Amperes ................................................................................ SC-4347-80A 9Type FCL 60 Amperes ................................................................................ SC-4348-80A 10Type FCL 70 Amperes ................................................................................ SC-4349-80A 11Type FCL 80 Amperes ................................................................................ SC-4350-80A 12Type FCL 90 Amperes ................................................................................ SC-4351-80A 13Type FCL 100 Amperes .............................................................................. SC-4352-80A 14Types LCL and LCLG 125-250 Amperes ................................................... SC-3624-81A 15Types LCLA and LCLGA 125-250 Amperes .............................................. SC-3625-81A 16Types LCL and LCLG 200-400 Amperes ................................................... SC-3626-81A 17Types LCLA and LCLGA 200-400 Amperes .............................................. SC-3627-81A 18Ground Fault Pick-up Curves for Types LCLG and LCLGA .................... SC-3906-86A 19

Tri-Pac® Current Limiting Circuit BreakersType FB 15 Amperes .................................................................................. SC-3572-76A 20Type FB 20 Amperes .................................................................................. SC-3573-76A 21Type FB 30 Amperes .................................................................................. SC-3574-76A 22Type FB 40 Amperes .................................................................................. SC-3575-76A 23Type FB 50 Amperes .................................................................................. SC-3576-76A 24Type FB 70 Amperes .................................................................................. SC-3577-76A 25Type FB 90 Amperes .................................................................................. SC-3578-76A 26Type FB 100 Amperes ................................................................................ SC-3579-76A 27

Time/Current Characteristic Curves forWestinghouse Current Limit-R® CircuitBreakers and Tri-Pac® Circuit Breakers

WestinghouseAB DE-ION®

Current LimitingCircuit Breakers

Individual oversize copies of curves listedabove printed on onion-skin paper areavailable in limited quantity from:

Cutler-HammerWestinghouse &Cutler-Hammer ProductsFive Parkway CenterPittsburgh, PA 15220

When ordering onion-skin curves, use num-ber at bottom of page where curve appears,i.e., SC-4340-80. Requests for full sets ofcurves will not be honored.

Voltages shown in curve headings aremaximum at which the breaker may beapplied. Interrupting capacity of individualbreaker is tabulated on each curve.

Type LA 70 Amperes .................................................................................. SC-3580-76A 28Type LA 90 Amperes .................................................................................. SC-3581-76A 29Type LA 100 Amperes ................................................................................ SC-3582-76A 30Type LA 125 Amperes ................................................................................ SC-3583-76A 31Type LA 150 Amperes ................................................................................ SC-3584-76A 32Type LA 175 Amperes ................................................................................ SC-3585-76A 33Type LA 200 Amperes ................................................................................ SC-3586-76A 34Type LA 225 Amperes ................................................................................ SC-3587-76A 35Type LA 250 Amperes ................................................................................ SC-3588-76A 36Type LA 300 Amperes ................................................................................ SC-3589-76A 37Type LA 350 Amperes ................................................................................ SC-3590-76A 38Type LA 400 Amperes ................................................................................ SC-3591-76A 39

Type NB 300 Amperes ............................................................................... SC-3592-76B 40Type NB 350 Amperes ............................................................................... SC-3593-76B 41Type NB 400 Amperes ............................................................................... SC-3594-76B 42Type NB 500 Amperes ............................................................................... SC-3595-76B 43Type NB 600 Amperes ............................................................................... SC-3596-76B 44Type NB 700 Amperes ............................................................................... SC-3597-76B 45Type NB 800 Amperes ............................................................................... SC-3598-76B 46

Type PB 600 Amperes ................................................................................ SC-3599-76B 47Type PB 800 Amperes ................................................................................ SC-3600-76B 48Type PB 1000 Amperes .............................................................................. SC-3601-76B 49Type PB 1200 Amperes .............................................................................. SC-3602-76B 50Type PB 1400 Amperes .............................................................................. SC-3603-76B 51Type PB 1600 Amperes .............................................................................. SC-3604-76B 52

Page 2: Westinghouse AB DE-ION Current Limiting Circuit Breakerspub/@electrical/... · Application Data 29-167C Page 3 October 1997 AB DE-ION Current Limit-R® Circuit Breakers Type FCL,

Application Data29-167C

Page 2

October 1997

Type FCL, 15 Amperes, 2 and 3 Poles

AB DE-ION Current Limit-R® Circuit Breakers

Curve No. SC-4340-80A

1,00

0

800

600

900

700

500

400

300

200

100

8060 9070504030201086 975 10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

Maximum TotalClearing Time

Minimum TotalClearing Time

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

TIME IN

SECONDS

1,000

500

300

200

5,000

3,000

2,000

1 HOUR1 M

INUTE

2 HOURS

TIM

E IN

SEC

ONDS

10,000

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

1,000

500

300

200

5,000

3,000

2,000

1 HO

UR1

MIN

UTE

2 HO

URS

CURRENT IN AMPERES

CURRENT IN AMPERES

10,000

1,00

0

800

600

900

700

500

400

300

200

1008060 9070504030201086 975

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

100,

000

80,0

00

60,0

00

90,0

00

70,0

00

50,0

00

40,0

00

30,0

00

200,

000

150,

000

1 CYCLE

1 CY

CLE

Maximum InterruptingTime at 240 Volts Ac

Current LimitingThreshold

Interrupting Rating (UL Listed)Symmetrical RMS AmperesBreaker

Frame

Fixed InstantaneousTrip Amperes

200,000

15 600 - 1000

150,000FCL240 Volts 480 Volts

Circuit Breaker Time/Current Curves

Current Limit-R Circuit Breakers

Catalog Type FCL Breakers, 2 and 3 Poles

Application and coordination curves based on 40°Cambient cold start, connected with four (4) feet of60/75°C rated wire size and tested in the open airwith current in all poles.

Maximum Ac Volts480, 60 Hertz

Breaker RatingContinuous Ratingin Amperes

Maximum InterruptingTime at 480 Volts Ac

Page 3: Westinghouse AB DE-ION Current Limiting Circuit Breakerspub/@electrical/... · Application Data 29-167C Page 3 October 1997 AB DE-ION Current Limit-R® Circuit Breakers Type FCL,

Application Data29-167C

Page 3

October 1997

AB DE-ION Current Limit-R® Circuit BreakersType FCL, 20 Amperes, 2 and 3 Poles

Curve No. SC-4341-80A

1,00

0

800

600

900

700

500

400

300

200

100

8060 9070504030201086 975 10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

Maximum TotalClearing Time

Minimum TotalClearing Time

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

TIME IN

SECONDS

1,000

500

300

200

5,000

3,000

2,000

1 HOUR1 M

INUTE

2 HOURS

TIM

E IN

SEC

ONDS

10,000

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

1,000

500

300

200

5,000

3,000

2,000

1 HO

UR1

MIN

UTE

2 HO

URS

CURRENT IN AMPERES

CURRENT IN AMPERES

10,000

1,00

0

800

600

900

700

500

400

300

200

1008060 9070504030201086 975

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

100,

000

80,0

00

60,0

00

90,0

00

70,0

00

50,0

00

40,0

00

30,0

00

200,

000

150,

000

1 CYCLE

1 CY

CLE

Interrupting Rating (UL Listed)Symmetrical RMS AmperesBreaker

Frame

Fixed InstantaneousTrip Amperes

200,000

20 600 - 1000

150,000FCL240 Volts 480 Volts

Circuit Breaker Time/Current Curves

Current Limit-R Circuit Breakers

Catalog Type FCL Breakers, 2 and 3 Poles

Application and coordination curves based on 40°Cambient cold start, connected with four (4) feet of60/75°C rated wire size and tested in the open airwith current in all poles.

Maximum Ac Volts480, 60 Hertz

Breaker RatingContinuous Ratingin Amperes

Maximum InterruptingTime at 240 Volts Ac

Current LimitingThreshold Maximum Interrupting

Time at 480 Volts Ac

Page 4: Westinghouse AB DE-ION Current Limiting Circuit Breakerspub/@electrical/... · Application Data 29-167C Page 3 October 1997 AB DE-ION Current Limit-R® Circuit Breakers Type FCL,

Application Data29-167C

Page 4

October 1997

Type FCL, 25 Amperes, 2 and 3 Poles

AB DE-ION Current Limit-R® Circuit Breakers

Curve No. SC-4342-80A

1,00

0

800

600

900

700

500

400

300

200

100

8060 9070504030201086 975 10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

Maximum TotalClearing Time

Minimum TotalClearing Time

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

TIME IN

SECONDS

1,000

500

300

200

5,000

3,000

2,000

1 HOUR1 M

INUTE

2 HOURS

TIM

E IN

SEC

ONDS

10,000

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

1,000

500

300

200

5,000

3,000

2,000

1 HO

UR1

MIN

UTE

2 HO

URS

CURRENT IN AMPERES

CURRENT IN AMPERES

10,000

1,00

0

800

600

900

700

500

400

300

200

1008060 9070504030201086 975

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

100,

000

80,0

00

60,0

00

90,0

00

70,0

00

50,0

00

40,0

00

30,0

00

200,

000

150,

000

1 CYCLE

1 CY

CLE

Interrupting Rating (UL Listed)Symmetrical RMS AmperesBreaker

Frame

Fixed InstantaneousTrip Amperes

200,000

25 600 - 1000

150,000FCL240 Volts 480 Volts

Circuit Breaker Time/Current Curves

Current Limit-R Circuit Breakers

Catalog Type FCL Breakers, 2 and 3 Poles

Application and coordination curves based on 40°Cambient cold start, connected with four (4) feet of60/75°C rated wire size and tested in the open airwith current in all poles.

Maximum Ac Volts480, 60 Hertz

Breaker RatingContinuous Ratingin Amperes

Maximum InterruptingTime at 240 Volts Ac

Current LimitingThreshold Maximum Interrupting

Time at 480 Volts Ac

Page 5: Westinghouse AB DE-ION Current Limiting Circuit Breakerspub/@electrical/... · Application Data 29-167C Page 3 October 1997 AB DE-ION Current Limit-R® Circuit Breakers Type FCL,

Application Data29-167C

Page 5

October 1997

AB DE-ION Current Limit-R® Circuit Breakers

Curve No. SC-4343-80A

Type FCL, 30 Amperes, 2 and 3 Poles

1,00

0

800

600

900

700

500

400

300

200

100

8060 9070504030201086 975 10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

Maximum TotalClearing Time

Minimum TotalClearing Time

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

TIME IN

SECONDS

1,000

500

300

200

5,000

3,000

2,000

1 HOUR1 M

INUTE

2 HOURS

TIM

E IN

SEC

ONDS

10,000

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

1,000

500

300

200

5,000

3,000

2,000

1 HO

UR1

MIN

UTE

2 HO

URS

CURRENT IN AMPERES

CURRENT IN AMPERES

10,000

1,00

0

800

600

900

700

500

400

300

200

1008060 9070504030201086 975

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

100,

000

80,0

00

60,0

00

90,0

00

70,0

00

50,0

00

40,0

00

30,0

00

200,

000

150,

000

1 CYCLE

1 CY

CLE

Interrupting Rating (UL Listed)Symmetrical RMS AmperesBreaker

Frame

Fixed InstantaneousTrip Amperes

200,000

30 600 - 1000

150,000FCL240 Volts 480 Volts

Circuit Breaker Time/Current Curves

Current Limit-R Circuit Breakers

Catalog Type FCL Breakers, 2 and 3 Poles

Application and coordination curves based on 40°Cambient cold start, connected with four (4) feet of60/75°C rated wire size and tested in the open airwith current in all poles.

Maximum Ac Volts480, 60 Hertz

Breaker RatingContinuous Ratingin Amperes

Maximum InterruptingTime at 240 Volts Ac

Current LimitingThreshold Maximum Interrupting

Time at 480 Volts Ac

Page 6: Westinghouse AB DE-ION Current Limiting Circuit Breakerspub/@electrical/... · Application Data 29-167C Page 3 October 1997 AB DE-ION Current Limit-R® Circuit Breakers Type FCL,

Application Data29-167C

Page 6

October 1997

Type FCL, 35 Amperes, 2 and 3 Poles

AB DE-ION Current Limit-R® Circuit Breakers

Curve No. SC-4344-80A

1,00

0

800

600

900

700

500

400

300

200

100

8060 9070504030201086 975 10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

Maximum TotalClearing Time

Minimum TotalClearing Time

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

TIME IN

SECONDS

1,000

500

300

200

5,000

3,000

2,000

1 HOUR1 M

INUTE

2 HOURS

TIM

E IN

SEC

ONDS

10,000

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

1,000

500

300

200

5,000

3,000

2,000

1 HO

UR1

MIN

UTE

2 HO

URS

CURRENT IN AMPERES

CURRENT IN AMPERES

10,000

1,00

0

800

600

900

700

500

400

300

200

1008060 9070504030201086 975

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

100,

000

80,0

00

60,0

00

90,0

00

70,0

00

50,0

00

40,0

00

30,0

00

200,

000

150,

000

1 CYCLE

1 CY

CLE

Interrupting Rating (UL Listed)Symmetrical RMS AmperesBreaker

Frame

Fixed InstantaneousTrip Amperes

200,000

35 600 - 1000

150,000FCL240 Volts 480 Volts

Circuit Breaker Time/Current Curves

Current Limit-R Circuit Breakers

Catalog Type FCL Breakers, 2 and 3 Poles

Application and coordination curves based on 40°Cambient cold start, connected with four (4) feet of60/75°C rated wire size and tested in the open airwith current in all poles.

Maximum Ac Volts480, 60 Hertz

Breaker RatingContinuous Ratingin Amperes

Maximum InterruptingTime at 240 Volts Ac

Current LimitingThreshold Maximum Interrupting

Time at 480 Volts Ac

Page 7: Westinghouse AB DE-ION Current Limiting Circuit Breakerspub/@electrical/... · Application Data 29-167C Page 3 October 1997 AB DE-ION Current Limit-R® Circuit Breakers Type FCL,

Application Data29-167C

Page 7

October 1997

AB DE-ION Current Limit-R® Circuit Breakers

Curve No. SC-4345-80A

Type FCL, 40 Amperes, 2 and 3 Poles

1,00

0

800

600

900

700

500

400

300

200

100

8060 9070504030201086 975 10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

Maximum TotalClearing Time

Minimum TotalClearing Time

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

TIME IN

SECONDS

1,000

500

300

200

5,000

3,000

2,000

1 HOUR1 M

INUTE

2 HOURS

TIM

E IN

SEC

ONDS

10,000

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

1,000

500

300

200

5,000

3,000

2,000

1 HO

UR1

MIN

UTE

2 HO

URS

CURRENT IN AMPERES

CURRENT IN AMPERES

10,000

1,00

0

800

600

900

700

500

400

300

200

1008060 9070504030201086 975

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

100,

000

80,0

00

60,0

00

90,0

00

70,0

00

50,0

00

40,0

00

30,0

00

200,

000

150,

000

1 CYCLE

1 CY

CLE

Interrupting Rating (UL Listed)Symmetrical RMS AmperesBreaker

Frame

Fixed InstantaneousTrip Amperes

200,000

40 600 - 1000

150,000FCL240 Volts 480 Volts

Circuit Breaker Time/Current Curves

Current Limit-R Circuit Breakers

Catalog Type FCL Breakers, 2 and 3 Poles

Application and coordination curves based on 40°Cambient cold start, connected with four (4) feet of60/75°C rated wire size and tested in the open airwith current in all poles.

Maximum Ac Volts480, 60 Hertz

Breaker RatingContinuous Ratingin Amperes

Maximum InterruptingTime at 240 Volts Ac

Current LimitingThreshold Maximum Interrupting

Time at 480 Volts Ac

Page 8: Westinghouse AB DE-ION Current Limiting Circuit Breakerspub/@electrical/... · Application Data 29-167C Page 3 October 1997 AB DE-ION Current Limit-R® Circuit Breakers Type FCL,

Application Data29-167C

Page 8

October 1997

Type FCL, 45 Amperes, 2 and 3 Poles

AB DE-ION Current Limit-R® Circuit Breakers

Curve No. SC-4346-80A

1,00

0

800

600

900

700

500

400

300

200

100

8060 9070504030201086 975 10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

Maximum TotalClearing Time

Minimum TotalClearing Time

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

TIME IN

SECONDS

1,000

500

300

200

5,000

3,000

2,000

1 HOUR1 M

INUTE

2 HOURS

TIM

E IN

SEC

ONDS

10,000

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

1,000

500

300

200

5,000

3,000

2,000

1 HO

UR1

MIN

UTE

2 HO

URS

CURRENT IN AMPERES

CURRENT IN AMPERES

10,000

1,00

0

800

600

900

700

500

400

300

200

1008060 9070504030201086 975

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

100,

000

80,0

00

60,0

00

90,0

00

70,0

00

50,0

00

40,0

00

30,0

00

200,

000

150,

000

1 CYCLE

1 CY

CLE

Interrupting Rating (UL Listed)Symmetrical RMS AmperesBreaker

Frame

Fixed InstantaneousTrip Amperes

200,000

45 800 - 1300

150,000FCL240 Volts 480 Volts

Circuit Breaker Time/Current Curves

Current Limit-R Circuit Breakers

Catalog Type FCL Breakers, 2 and 3 Poles

Application and coordination curves based on 40°Cambient cold start, connected with four (4) feet of60/75°C rated wire size and tested in the open airwith current in all poles.

Maximum Ac Volts480, 60 Hertz

Breaker RatingContinuous Ratingin Amperes

Maximum InterruptingTime at 240 Volts Ac

Current LimitingThreshold Maximum Interrupting

Time at 480 Volts Ac

Page 9: Westinghouse AB DE-ION Current Limiting Circuit Breakerspub/@electrical/... · Application Data 29-167C Page 3 October 1997 AB DE-ION Current Limit-R® Circuit Breakers Type FCL,

Application Data29-167C

Page 9

October 1997

AB DE-ION Current Limit-R® Circuit Breakers

Curve No. SC-4347-80A

Type FCL, 50 Amperes, 2 and 3 Poles

Maximum TotalClearing Time

Minimum TotalClearing Time

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

TIME IN

SECONDS

1,000

500

300

200

5,000

3,000

2,000

1 HOUR1 M

INUTE

2 HOURS

TIM

E IN

SEC

ONDS

10,000

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

1,000

500

300

200

5,000

3,000

2,000

1 HO

UR1

MIN

UTE

2 HO

URS

CURRENT IN AMPERES

CURRENT IN AMPERES

10,000

1 CYCLE

1 CY

CLE

Interrupting Rating (UL Listed)Symmetrical RMS AmperesBreaker

Frame

Fixed InstantaneousTrip Amperes

200,000

50 800 - 1300

150,000FCL240 Volts 480 Volts

Circuit Breaker Time/Current Curves

Current Limit-R Circuit Breakers

Catalog Type FCL Breakers, 2 and 3 Poles

Application and coordination curves based on 40°Cambient cold start, connected with four (4) feet of60/75°C rated wire size and tested in the open airwith current in all poles.

Maximum Ac Volts480, 60 Hertz

Breaker RatingContinuous Ratingin Amperes

Maximum InterruptingTime at 240 Volts Ac

Current LimitingThreshold

Maximum InterruptingTime at 480 Volts Ac

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

100,

000

80,0

00

60,0

00

90,0

00

70,0

00

50,0

00

40,0

00

30,0

00

200,

000

20,0

00

1,00

0

800

600

900

700

500

400

300

200

1008060 907050

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

100,

000

80,0

00

60,0

00

90,0

00

70,0

00

50,0

00

40,0

00

30,0

00

20,0

00

1,00

0

800

600

900

700

500

400

300

200

100

8060 907050

Page 10: Westinghouse AB DE-ION Current Limiting Circuit Breakerspub/@electrical/... · Application Data 29-167C Page 3 October 1997 AB DE-ION Current Limit-R® Circuit Breakers Type FCL,

Application Data29-167C

Page 10

October 1997

Type FCL, 60 Amperes, 2 and 3 Poles

AB DE-ION Current Limit-R® Circuit Breakers

Curve No. SC-4348-80A

Maximum TotalClearing Time

Minimum TotalClearing Time

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

TIME IN

SECONDS

1,000

500

300

200

5,000

3,000

2,000

1 HOUR1 M

INUTE

2 HOURS

TIM

E IN

SEC

ONDS

10,000

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

1,000

500

300

200

5,000

3,000

2,000

1 HO

UR1

MIN

UTE

2 HO

URS

CURRENT IN AMPERES

CURRENT IN AMPERES

10,000

1 CYCLE

1 CY

CLE

Interrupting Rating (UL Listed)Symmetrical RMS AmperesBreaker

Frame

Fixed InstantaneousTrip Amperes

200,000

60 800 - 1300

150,000FCL240 Volts 480 Volts

Circuit Breaker Time/Current Curves

Current Limit-R Circuit Breakers

Catalog Type FCL Breakers, 2 and 3 Poles

Application and coordination curves based on 40°Cambient cold start, connected with four (4) feet of60/75°C rated wire size and tested in the open airwith current in all poles.

Maximum Ac Volts480, 60 Hertz

Breaker RatingContinuous Ratingin Amperes

Maximum InterruptingTime at 240 Volts Ac

Current LimitingThreshold

Maximum InterruptingTime at 480 Volts Ac

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

100,

000

80,0

00

60,0

00

90,0

00

70,0

00

50,0

00

40,0

00

30,0

00

200,

000

20,0

00

1,00

0

800

600

900

700

500

400

300

200

1008060 907050

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

100,

000

80,0

00

60,0

00

90,0

00

70,0

00

50,0

00

40,0

00

30,0

00

20,0

00

1,00

0

800

600

900

700

500

400

300

200

100

8060 907050

Page 11: Westinghouse AB DE-ION Current Limiting Circuit Breakerspub/@electrical/... · Application Data 29-167C Page 3 October 1997 AB DE-ION Current Limit-R® Circuit Breakers Type FCL,

Application Data29-167C

Page 11

October 1997

AB DE-ION Current Limit-R® Circuit Breakers

Curve No. SC-4349-80A

Type FCL, 70 Amperes, 2 and 3 Poles

Maximum TotalClearing Time

Minimum TotalClearing Time

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

TIME IN

SECONDS

1,000

500

300

200

5,000

3,000

2,000

1 HOUR1 M

INUTE

2 HOURS

TIM

E IN

SEC

ONDS

10,000

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

1,000

500

300

200

5,000

3,000

2,000

1 HO

UR1

MIN

UTE

2 HO

URS

CURRENT IN AMPERES

CURRENT IN AMPERES

10,000

1 CYCLE

1 CY

CLE

Interrupting Rating (UL Listed)Symmetrical RMS AmperesBreaker

Frame

Fixed InstantaneousTrip Amperes

200,000

70 800 - 1300

150,000FCL240 Volts 480 Volts

Circuit Breaker Time/Current Curves

Current Limit-R Circuit Breakers

Catalog Type FCL Breakers, 2 and 3 Poles

Application and coordination curves based on 40°Cambient cold start, connected with four (4) feet of60/75°C rated wire size and tested in the open airwith current in all poles.

Maximum Ac Volts480, 60 Hertz

Breaker RatingContinuous Ratingin Amperes

Maximum InterruptingTime at 240 Volts Ac

Current LimitingThreshold

Maximum InterruptingTime at 480 Volts Ac

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

100,

000

80,0

00

60,0

00

90,0

00

70,0

00

50,0

00

40,0

00

30,0

00

200,

000

20,0

00

1,00

0

800

600

900

700

500

400

300

200

1008060 907050

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

100,

000

80,0

00

60,0

00

90,0

00

70,0

00

50,0

00

40,0

00

30,0

00

20,0

00

1,00

0

800

600

900

700

500

400

300

200

100

8060 907050

Page 12: Westinghouse AB DE-ION Current Limiting Circuit Breakerspub/@electrical/... · Application Data 29-167C Page 3 October 1997 AB DE-ION Current Limit-R® Circuit Breakers Type FCL,

Application Data29-167C

Page 12

October 1997

Type FCL, 80 Amperes, 2 and 3 Poles

AB DE-ION Current Limit-R® Circuit Breakers

Curve No. SC-4350-80A

Maximum TotalClearing Time

Minimum TotalClearing Time 100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

TIME IN

SECONDS

1,000

500

300

200

5,000

3,000

2,000

1 HOUR1 M

INUTE

2 HOURS

TIM

E IN

SEC

ONDS

10,000

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

1,000

500

300

200

5,000

3,000

2,000

1 HO

UR1

MIN

UTE

2 HO

URS

CURRENT IN AMPERES

CURRENT IN AMPERES

10,000

1 CYCLE

1 CY

CLE

Interrupting Rating (UL Listed)Symmetrical RMS AmperesBreaker

Frame

Fixed InstantaneousTrip Amperes

200,000

80 800 - 1300

150,000FCL240 Volts 480 Volts

Circuit Breaker Time/Current Curves

Current Limit-R Circuit Breakers

Catalog Type FCL Breakers, 2 and 3 Poles

Application and coordination curves based on 40°Cambient cold start, connected with four (4) feet of60/75°C rated wire size and tested in the open airwith current in all poles.

Maximum Ac Volts480, 60 Hertz

Breaker RatingContinuous Ratingin Amperes

Maximum InterruptingTime at 240 Volts Ac

Current LimitingThreshold

Maximum InterruptingTime at 480 Volts Ac

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

100,

000

80,0

00

60,0

00

90,0

00

70,0

00

50,0

00

40,0

00

30,0

00

20,0

00

1,00

0

800

600

900

700

500

400

300

200

100

8060 907050

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

100,

000

80,0

00

60,0

00

90,0

00

70,0

00

50,0

00

40,0

00

30,0

00

200,

000

20,0

00

1,00

0

800

600

900

700

500

400

300

200

1008060 907050

Page 13: Westinghouse AB DE-ION Current Limiting Circuit Breakerspub/@electrical/... · Application Data 29-167C Page 3 October 1997 AB DE-ION Current Limit-R® Circuit Breakers Type FCL,

Application Data29-167C

Page 13

October 1997

AB DE-ION Current Limit-R® Circuit Breakers

Curve No. SC-4351-80A

Type FCL, 90 Amperes, 2 and 3 Poles

Maximum TotalClearing Time

Minimum TotalClearing Time 100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

TIME IN

SECONDS

1,000

500

300

200

5,000

3,000

2,000

1 HOUR1 M

INUTE

2 HOURS

TIM

E IN

SEC

ONDS

10,000

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

1,000

500

300

200

5,000

3,000

2,000

1 HO

UR1

MIN

UTE

2 HO

URS

CURRENT IN AMPERES

CURRENT IN AMPERES

10,000

1 CYCLE

1 CY

CLE

Interrupting Rating (UL Listed)Symmetrical RMS AmperesBreaker

Frame

Fixed InstantaneousTrip Amperes

200,000

90 800 - 1300

150,000FCL240 Volts 480 Volts

Circuit Breaker Time/Current Curves

Current Limit-R Circuit Breakers

Catalog Type FCL Breakers, 2 and 3 Poles

Application and coordination curves based on 40°Cambient cold start, connected with four (4) feet of60/75°C rated wire size and tested in the open airwith current in all poles.

Maximum Ac Volts480, 60 Hertz

Breaker RatingContinuous Ratingin Amperes

Maximum InterruptingTime at 240 Volts Ac

Current LimitingThreshold

Maximum InterruptingTime at 480 Volts Ac

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

100,

000

80,0

00

60,0

00

90,0

00

70,0

00

50,0

00

40,0

00

30,0

00

200,

000

20,0

00

1,00

0

800

600

900

700

500

400

300

200

1008060 907050

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

100,

000

80,0

00

60,0

00

90,0

00

70,0

00

50,0

00

40,0

00

30,0

00

20,0

00

1,00

0

800

600

900

700

500

400

300

200

100

8060 907050

Page 14: Westinghouse AB DE-ION Current Limiting Circuit Breakerspub/@electrical/... · Application Data 29-167C Page 3 October 1997 AB DE-ION Current Limit-R® Circuit Breakers Type FCL,

Application Data29-167C

Page 14

October 1997

Type FCL, 100 Amperes, 2 and 3 Poles

AB DE-ION Current Limit-R® Circuit Breakers

Curve No. SC-4352-80A

Maximum TotalClearing Time

Minimum TotalClearing Time 100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

TIME IN

SECONDS

1,000

500

300

200

5,000

3,000

2,000

1 HOUR1 M

INUTE

2 HOURS

TIM

E IN

SEC

ONDS

10,000

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

1,000

500

300

200

5,000

3,000

2,000

1 HO

UR1

MIN

UTE

2 HO

URS

CURRENT IN AMPERES

CURRENT IN AMPERES

10,000

1 CYCLE

1 CY

CLE

Interrupting Rating (UL Listed)Symmetrical RMS AmperesBreaker

Frame

Fixed InstantaneousTrip Amperes

200,000

100 800 - 1300

150,000FCL240 Volts 480 Volts

Circuit Breaker Time/Current Curves

Current Limit-R Circuit Breakers

Catalog Type FCL Breakers, 2 and 3 Poles

Application and coordination curves based on 40°Cambient cold start, connected with four (4) feet of60/75°C rated wire size and tested in the open airwith current in all poles.

Maximum Ac Volts480, 60 Hertz

Breaker RatingContinuous Ratingin Amperes

Maximum InterruptingTime at 240 Volts Ac

Current LimitingThreshold

Maximum InterruptingTime at 480 Volts Ac

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

100,

000

80,0

00

60,0

00

90,0

00

70,0

00

50,0

00

40,0

00

30,0

00

200,

000

20,0

00

1,00

0

800

600

900

700

500

400

300

200

1008060 907050

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

100,

000

80,0

00

60,0

00

90,0

00

70,0

00

50,0

00

40,0

00

30,0

00

20,0

00

1,00

0

800

600

900

700

500

400

300

200

100

8060 907050

Page 15: Westinghouse AB DE-ION Current Limiting Circuit Breakerspub/@electrical/... · Application Data 29-167C Page 3 October 1997 AB DE-ION Current Limit-R® Circuit Breakers Type FCL,

Application Data29-167C

Page 15

October 1997

AB DE-ION Current Limit-R® Circuit Breakers

Curve No. SC-3624-81A

Types LCL and LCLG, 125-250 Amperes, 2 and 3 Poles

60.0

50.0

40.0

30.0

20.01.0

0.8

0.6

0.9

0.7

0.5

10.08.0

6.0

9.0

7.0

5.0

4.0

3.0

2.0

60.0

50.0

40.0

30.0

20.0

1.0

0.8

0.6

0.9

0.7

0.5

10.0

8.0

6.0

9.0

7.0

5.0

4.0

3.0

2.0

Maximum TotalClearing Time

Minimum TotalClearing Time

4 X

5 X

6 X

7 X

8 X

225

A

175

A15

0 A

125

A

250

A

200

A

.05

.03

.02

.01

.005

.003

.002

.001

TIME IN SECONDS

TIM

E IN

SEC

ONDS

10,000

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

1,000

500

300

200

5,000

3,000

2,000

1 H

OU

R1

MIN

UT

E2

HO

UR

S

CURRENT IN MULTIPLES OF RATING PLUG ➀

1008060 9070504030

CURRENT IN MULTIPLES OF RATING PLUG ➀

When adjustable rating plugs are used, short delay pickup settingstrack the selected position of the adjustable rating plug. Forexample, with an adjustable 250 amp rating plug set at 50% andthe short delay pickup set at 4X, the short delay pickup is250 X 50% X 4 - 500 amps.

The threshold point changes with the ampere value of the ratingplug.

For ground fault time-current characteristics of LCLG, see CurveNo. SC-3906-86.

Circuit Breaker Time/Current Curves

Current Limit-R Circuit Breakers

Catalog Type LCL, LCLG Breakers, 2 and 3 Poles

Curve accuracy applies from -20°C to +55°C ambient. For possiblecontinuous ampere derating for ambients above +40°C refer toCutler-Hammer.

Maximum Ac Volts600, 50/60 Hertz

Breaker RatingsContinuous Amperes Short Delay Pickup Settings

3X to 9X rating plug valuewith calibration settingsas shown on curve (Tol. ±10%)

125-250

Frame 240 Volts

Rating Plugs AvailableContinuous Amperes Range of Adjustment

250 Amp250 Amp225 Amp225 Amp200 Amp200 Amp175 Amp175 Amp150 Amp125 Amp

Fixed 100%50-100%➀Fixed 100%70-100%➀Fixed 100%70-100%➀Fixed 100%75-100%➀Fixed 100%Fixed 100%

AMPERES X 100

Short DelayPickup Settings

200

300

400

500

600

800

1000

2000

3000700

900

Current LimitingThreshold ➁

Expanded View in Current Limiting Area

Maximum ClearingTime at 600 Volts Ac

Maximum ClearingTime at 480 Volts Ac

Maximum ClearingTime at 240 Volts Ac

3 X

9 X

Interrupting Rating (UL/CSA Listed)480 Volts 600 Volts

LCL, LCLG➂ 200,000 200,000 100,000

Optional Adjustable Rating Plug ➀

Standard Fixed Rating Plug

Page 16: Westinghouse AB DE-ION Current Limiting Circuit Breakerspub/@electrical/... · Application Data 29-167C Page 3 October 1997 AB DE-ION Current Limit-R® Circuit Breakers Type FCL,

Application Data29-167C

Page 16

October 1997

Types LCLA and LCLGA, 125-250 Amperes, 2 and 3 Poles

AB DE-ION Current Limit-R® Circuit Breakers

Curve No. SC-3625-81A

60.0

50.0

40.0

30.0

20.01.0

0.8

0.6

0.9

0.7

0.5

10.08.0

6.0

9.0

7.0

5.0

4.0

3.0

2.0

60.0

50.0

40.0

30.0

20.0

1.0

0.8

0.6

0.9

0.7

0.5

10.0

8.0

6.0

9.0

7.0

5.0

4.0

3.0

2.0

.05

.03

.02

.01

.005

.003

.002

.001

TIME IN SECONDS

TIM

E IN

SEC

ONDS

10,000

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

1,000

500

300

200

5,000

3,000

2,000

1 H

OU

R1

MIN

UT

E2

HO

UR

S

CURRENT IN MULTIPLES OF RATING PLUG ➀

1008060 9070504030

CURRENT IN MULTIPLES OF RATING PLUG ➀

When adjustable rating plugs are used, short delay pickup settingstrack the selected position of the adjustable rating plug. Forexample, with an adjustable 250 amp rating plug set at 50% andthe short delay pickup set at 4X, the short delay pickup is250 X 50% X 4 - 500 amps.

The threshold point changes with the ampere value of the ratingplug.

For ground fault time-current characteristics of LCLGA, see CurveNo. SC-3906-86.

Circuit Breaker Time/Current Curves

Current Limit-R Circuit Breakers

Catalog Type LCLA, LCLGA Breakers, 2 and 3 Poles

Curve accuracy applies from -20°C to +55°C ambient. For possiblecontinuous ampere derating for ambients above +40°C refer toCutler-Hammer.

Maximum Ac Volts600, 50/60 Hertz

Breaker RatingsContinuous Amperes Short Delay Pickup Settings

Rating Plugs AvailableContinuous Amperes Range of Adjustment

250 Amp250 Amp225 Amp225 Amp200 Amp200 Amp175 Amp175 Amp150 Amp125 Amp

Fixed 100%50-100%➀Fixed 100%70-100%➀Fixed 100%70-100%➀Fixed 100%75-100%➀Fixed 100%Fixed 100%

AMPERES X 100

Maximum TotalClearing Time

Minimum TotalClearing Time

Short DelayPickup Settings

200

300

400

500

600

800

1000

2000

3000700

900

Current LimitingThreshold ➁

Expanded View in Current Limiting Area

Maximum ClearingTime at 600 Volts Ac

Maximum ClearingTime at 480 Volts Ac

Maximum ClearingTime at 240 Volts Ac

3 X

250

A

Interrupting Rating (UL/CSA Listed)Frame 240 Volts 480 Volts 600 VoltsLCLA, LCLGA➂ 200,000 200,000 100,000

3X to 9X rating plug valuewith calibration settingsas shown on curve (Tol. ±10%)

125-250

225

A

175

A15

0 A

125

A

200

A

9 X

4 X

5 X

6 X

7 X

8 X

Optional Adjustable Rating Plug ➀

Standard Fixed Rating Plug

Page 17: Westinghouse AB DE-ION Current Limiting Circuit Breakerspub/@electrical/... · Application Data 29-167C Page 3 October 1997 AB DE-ION Current Limit-R® Circuit Breakers Type FCL,

Application Data29-167C

Page 17

October 1997

AB DE-ION Current Limit-R® Circuit Breakers

Curve No. SC-3626-81A

Types LCL and LCLG, 200-400 Amperes, 2 and 3 Poles

60.0

50.0

40.0

30.0

20.01.0

0.8

0.6

0.9

0.7

0.5

10.08.0

6.0

9.0

7.0

5.0

4.0

3.0

2.0

60.0

50.0

40.0

30.0

20.0

1.0

0.8

0.6

0.9

0.7

0.5

10.0

8.0

6.0

9.0

7.0

5.0

4.0

3.0

2.0

8 X

350

A

225

A27

5 A

200

A

300

A25

0 A

.05

.03

.02

.01

.005

.003

.002

.001

TIME IN SECONDS

TIM

E IN

SEC

ONDS

10,000

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

1,000

500

300

200

5,000

3,000

2,000

1 H

OU

R1

MIN

UT

E2

HO

UR

S

CURRENT IN MULTIPLES OF RATING PLUG ➀

1008060 9070504030

CURRENT IN MULTIPLES OF RATING PLUG ➀

When adjustable rating plugs are used, short delay pickup settingstrack the selected position of the adjustable rating plug. Forexample, with an adjustable 400 amp rating plug set at 50% andthe short delay pickup set at 4X, the short delay pickup is400 X 50% X 4 - 800 amps.

The threshold point changes with the ampere value of the ratingplug.

For ground fault time-current characteristics of LCLG, see CurveNo. SC-3906-86.

Circuit Breaker Time/Current Curves

Current Limit-R Circuit Breakers

Catalog Type LCL, LCLG Breakers, 2 and 3 Poles

Curve accuracy applies from -20°C to +55°C ambient. For possiblecontinuous ampere derating for ambients above +40°C refer toCutler-Hammer.

Maximum Ac Volts600, 50/60 Hertz

Breaker RatingsContinuous Amperes Short Delay Pickup Settings

2X to 8X rating plug valuewith calibration settingsas shown on curve (Tol. ±10%)

200-400

Interrupting Rating (UL/CSA Listed)Frame 240 Volts 480 Volts 600 VoltsLCL, LCLG➂ 200,000 200,000 100,000

Rating Plugs AvailableContinuous Amperes Range of Adjustment

400 Amp400 Amp350 Amp350 Amp300 Amp300 Amp275 Amp250 Amp225 Amp200 Amp

Fixed 100%50-100%➀Fixed 100%70-100%➀Fixed 100%75-100%➀Fixed 100%Fixed 100%Fixed 100%Fixed 100%

AMPERES X 100

3 X

4 X

5 X

6 X

7 X

400

A

Optional Adjustable Rating Plug ➀

Standard Fixed Rating Plug

Maximum TotalClearing Time

Minimum TotalClearing Time

Short DelayPickup Settings

200

300

400

500

600

800

2000

3000700

900

Current LimitingThreshold ➁

Expanded View in Current Limiting Area

Maximum ClearingTime at 600 Volts Ac

Maximum ClearingTime at 480 Volts Ac

Maximum ClearingTime at 240 Volts Ac

Page 18: Westinghouse AB DE-ION Current Limiting Circuit Breakerspub/@electrical/... · Application Data 29-167C Page 3 October 1997 AB DE-ION Current Limit-R® Circuit Breakers Type FCL,

Application Data29-167C

Page 18

October 1997

Type LCLA and LCLGA, 200-400 Amperes, 2 and 3 Poles

AB DE-ION Current Limit-R® Circuit Breakers

Curve No. SC-3627-81A

60.0

50.0

40.0

30.0

20.01.0

0.8

0.6

0.9

0.7

0.5

10.08.0

6.0

9.0

7.0

5.0

4.0

3.0

2.0

60.0

50.0

40.0

30.0

20.0

1.0

0.8

0.6

0.9

0.7

0.5

10.0

8.0

6.0

9.0

7.0

5.0

4.0

3.0

2.0

8 X

.05

.03

.02

.01

.005

.003

.002

.001

TIME IN SECONDS

TIM

E IN

SEC

ONDS

10,000

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

1,000

500

300

200

5,000

3,000

2,000

1 H

OU

R1

MIN

UT

E2

HO

UR

S

CURRENT IN MULTIPLES OF RATING PLUG ➀

1008060 9070504030

CURRENT IN MULTIPLES OF RATING PLUG ➀

When adjustable rating plugs are used, short delay pickup settingstrack the selected position of the adjustable rating plug. Forexample, with an adjustable 400 amp rating plug set at 50% andthe short delay pickup set at 4X, the short delay pickup is400 X 50% X 4 - 800 amps.

The threshold point changes with the ampere value of the ratingplug.

For ground fault time-current characteristics of LCLGA, see CurveNo. SC-3906-86.

Circuit Breaker Time/Current Curves

Current Limit-R Circuit Breakers

Catalog Type LCLA, LCLGA Breakers, 2 and 3 Poles

Curve accuracy applies from -20°C to +55°C ambient. For possiblecontinuous ampere derating for ambients above +40°C refer toCutler-Hammer.

Maximum Ac Volts600, 50/60 Hertz

Breaker RatingsContinuous Amperes Short Delay Pickup Settings

2X to 8X rating plug valuewith calibration settingsas shown on curve (Tol. ±10%)

200-400

Interrupting Rating (UL/CSA Listed)Frame 240 Volts 480 Volts 600 VoltsLCLA, LCLGA➂ 200,000 200,000 100,000

Rating Plugs AvailableContinuous Amperes Range of Adjustment

400 Amp400 Amp350 Amp350 Amp300 Amp300 Amp275 Amp250 Amp225 Amp200 Amp

Fixed 100%50-100%➀Fixed 100%70-100%➀Fixed 100%70-100%➀Fixed 100%Fixed 100%Fixed 100%Fixed 100%

AMPERES X 100

350

A30

0 A

225

A27

5 A

4 X

5 X

6 X

7 X

Maximum TotalClearing Time

Minimum TotalClearing Time

Short DelayPickup Settings

250

A

200

300

400

500

600

800

1000

2000

3000700

900

Current LimitingThreshold ➁

Expanded View in Current Limiting Area

Maximum ClearingTime at 600 Volts Ac

Maximum ClearingTime at 480 Volts Ac

Maximum ClearingTime at 240 Volts Ac

3 X

400

A

200

A

Optional Adjustable Rating Plug ➀

Standard Fixed Rating Plug

Page 19: Westinghouse AB DE-ION Current Limiting Circuit Breakerspub/@electrical/... · Application Data 29-167C Page 3 October 1997 AB DE-ION Current Limit-R® Circuit Breakers Type FCL,

Application Data29-167C

Page 19

October 1997

AB DE-ION Current Limit-R® Circuit BreakersGround Fault Pick-up Curves for Types LCLG and LCLGA

Curve No. SC-3906-86A

Minimum Pick-Up➀

(± 20%)Maximum Pick-Up➀

+0 %)(

Maximum Time (±20%)

Minimum Time (±20%)

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

TIME IN

SECONDS

1,000

500

300

200

5,000

3,000

2,000

1 HOUR1 M

INUTE

2 HOURS

TIM

E IN

SEC

ONDS

10,000

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

1,000

500

300

200

5,000

3,000

2,000

1 HO

UR1

MIN

UTE

2 HO

URS

CURRENT IN PERCENT OF FRAME RATING

10,000

1 CYCLE

1 CY

CLE

CURRENT IN PERCENT OF FRAME RATING

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

1,00

0

800

600

900

700

500

400

300

200

1008060 9070504030201086 975

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

1,00

0

800

600

900

700

500

400

300

200

100

8060 9070504030201086 975

Page 20: Westinghouse AB DE-ION Current Limiting Circuit Breakerspub/@electrical/... · Application Data 29-167C Page 3 October 1997 AB DE-ION Current Limit-R® Circuit Breakers Type FCL,

Application Data29-167C

Page 20

October 1997

Type FB, 15 Amperes, 2 and 3 Poles

Curve No. SC-3572-76A

1000

800

600

900

700

500

400

300

200

Fixed Instantaneous Trip AmperesSee Curve

Symmetrical RMS Amperes240 Volts200,000

480 Volts200,000

600 Volts200,000

Dc Amperes250 Volts10,000

Instantaneous TripRating in Amperes15

Interrupting Rating (UL Listed)BreakerFrame

FB Tri-Pac

Circuit Breaker Time/Current Curves

Tri-Pac Circuit Breakers

Catalog Type FB Circuit Breakers, 15 Amperes, 2 and 3 Poles,600 Volts Ac Max., 250 Volts Dc

Application and coordination curves based on 40°C ambientcold start, connected with four (4) feet of 60°C rated wiresize and tested in open air with current in all poles.

Single (1) pole test data at 25°C based on NEMA procedures forverifying performance of molded case circuit breakers.

Maximum

Maximum Single PoleTrip Times at 25°C ➀

Limiter 100 FBP06

Minimum 100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

TIME IN

SECONDS

1,000

500

300

200

5,000

3,000

2,000

1 HOUR1 M

INUTE

2 HOURS

TIM

E IN

SEC

ONDS

10,000

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

1,000

500

300

200

5,000

3,000

2,000

1 HO

UR1

MIN

UTE

2 HO

URS

CURRENT IN AMPERES

CURRENT IN AMPERES

10,000

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

100

8060 9070504030201086 975

1 CYCLE

1 CY

CLE

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

100080

0

600

900

700

500

400

300

200

1008060 907050

100,

000

80,0

00

60,0

00

90,0

00

70,0

00

50,0

00

40,0

00

30,0

00

20,0

004030201086 975

AB DE-ION Tri-Pac® Circuit Breakers

Page 21: Westinghouse AB DE-ION Current Limiting Circuit Breakerspub/@electrical/... · Application Data 29-167C Page 3 October 1997 AB DE-ION Current Limit-R® Circuit Breakers Type FCL,

Application Data29-167C

Page 21

October 1997

Type FB, 20 Amperes, 2 and 3 Poles

Curve No. SC-3573-76A

1000

800

600

900

700

500

400

300

200

Maximum Single PoleTrip Times at 25°C ➀

Fixed Instantaneous Trip AmperesSee Curve

Symmetrical RMS Amperes240 Volts200,000

480 Volts200,000

600 Volts200,000

Dc Amperes250 Volts10,000

Instantaneous TripRating in Amperes20

Interrupting Rating (UL Listed)BreakerFrame

FB Tri-Pac

Maximum

Limiter 100 FBP06

Minimum

Circuit Breaker Time/Current Curves

Tri-Pac Circuit Breakers

Catalog Type FB Circuit Breakers, 20 Amperes, 2 and 3 Poles,600 Volts Ac Max., 250 Volts Dc

Application and coordination curves based on 40°C ambientcold start, connected with four (4) feet of 60°C rated wiresize and tested in open air with current in all poles.

Single (1) pole test data at 25°C based on NEMA procedures forverifying performance of molded case circuit breakers.

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

TIME IN

SECONDS

1,000

500

300

200

5,000

3,000

2,000

1 HOUR1 M

INUTE

2 HOURS

TIM

E IN

SEC

ONDS

10,000

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

1,000

500

300

200

5,000

3,000

2,000

1 HO

UR1

MIN

UTE

2 HO

URS

CURRENT IN AMPERES

CURRENT IN AMPERES

10,000

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

100

8060 9070504030201086 975

1 CYCLE

1 CY

CLE

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

100080

0

600

900

700

500

400

300

200

1008060 907050

100,

000

80,0

00

60,0

00

90,0

00

70,0

00

50,0

00

40,0

00

30,0

00

20,0

004030201086 975

AB DE-ION Tri Pac® Circuit Breakers

Page 22: Westinghouse AB DE-ION Current Limiting Circuit Breakerspub/@electrical/... · Application Data 29-167C Page 3 October 1997 AB DE-ION Current Limit-R® Circuit Breakers Type FCL,

Application Data29-167C

Page 22

October 1997

Type FB, 30 Amperes, 2 and 3 Poles

Curve No. SC-3574-76A

1000

800

600

900

700

500

400

300

200

Maximum Single PoleTrip Times at 25°C ➀

Fixed Instantaneous Trip AmperesSee Curve

Symmetrical RMS Amperes240 Volts200,000

480 Volts200,000

600 Volts200,000

Dc Amperes250 Volts10,000

Instantaneous TripRating in Amperes30

Interrupting Rating (UL Listed)BreakerFrame

FB Tri-Pac

Maximum

Limiter 100 FBP06

Minimum

Circuit Breaker Time/Current Curves

Tri-Pac Circuit Breakers

Catalog Type FB Circuit Breakers, 30 Amperes, 2 and 3 Poles,600 Volts Ac Max., 250 Volts Dc

Application and coordination curves based on 40°C ambientcold start, connected with four (4) feet of 60°C rated wiresize and tested in open air with current in all poles.

Single (1) pole test data at 25°C based on NEMA procedures forverifying performance of molded case circuit breakers.

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

TIME IN

SECONDS

1,000

500

300

200

5,000

3,000

2,000

1 HOUR1 M

INUTE

2 HOURS

TIM

E IN

SEC

ONDS

10,000

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

1,000

500

300

200

5,000

3,000

2,000

1 HO

UR1

MIN

UTE

2 HO

URS

CURRENT IN AMPERES

CURRENT IN AMPERES

10,000

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

100

8060 9070504030201086 975

1 CYCLE

1 CY

CLE

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

100080

0

600

900

700

500

400

300

200

1008060 907050

100,

000

80,0

00

60,0

00

90,0

00

70,0

00

50,0

00

40,0

00

30,0

00

20,0

004030201086 975

AB DE-ION Tri-Pac® Circuit Breakers

Page 23: Westinghouse AB DE-ION Current Limiting Circuit Breakerspub/@electrical/... · Application Data 29-167C Page 3 October 1997 AB DE-ION Current Limit-R® Circuit Breakers Type FCL,

Application Data29-167C

Page 23

October 1997

Type FB, 40 Amperes, 2 and 3 Poles

Curve No. SC-3575-76A

1000

800

600

900

700

500

400

300

200

Fixed Instantaneous Trip Amperes500-1000

Symmetrical RMS Amperes240 Volts200,000

480 Volts200,000

600 Volts200,000

Dc Amperes250 Volts10,000

Instantaneous TripRating in Amperes40

Interrupting Rating (UL Listed)BreakerFrame

FB Tri-Pac

Maximum

Limiter 100 FBP06

Minimum

Maximum Single PoleTrip Times at 25°C ➀

Circuit Breaker Time/Current Curves

Tri-Pac Circuit Breakers

Catalog Type FB Circuit Breakers, 40 Amperes, 2 and 3 Poles,600 Volts Ac Max., 250 Volts Dc

Application and coordination curves based on 40°C ambientcold start, connected with four (4) feet of 60°C rated wiresize and tested in open air with current in all poles.

Single (1) pole test data at 25°C based on NEMA procedures forverifying performance of molded case circuit breakers.

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

TIME IN

SECONDS

1,000

500

300

200

5,000

3,000

2,000

1 HOUR1 M

INUTE

2 HOURS

TIM

E IN

SEC

ONDS

10,000

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

1,000

500

300

200

5,000

3,000

2,000

1 HO

UR1

MIN

UTE

2 HO

URS

CURRENT IN AMPERES

CURRENT IN AMPERES

10,000

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

100

8060 9070504030201086 975

1 CYCLE

1 CY

CLE

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

100080

0

600

900

700

500

400

300

200

1008060 907050

100,

000

80,0

00

60,0

00

90,0

00

70,0

00

50,0

00

40,0

00

30,0

00

20,0

004030201086 975

AB DE-ION Tri Pac® Circuit Breakers

Page 24: Westinghouse AB DE-ION Current Limiting Circuit Breakerspub/@electrical/... · Application Data 29-167C Page 3 October 1997 AB DE-ION Current Limit-R® Circuit Breakers Type FCL,

Application Data29-167C

Page 24

October 1997

Type FB, 50 Amperes, 2 and 3 Poles

Curve No. SC-3576-76A

1000

800

600

900

700

500

400

300

200

Fixed Instantaneous Trip Amperes600-1200

Symmetrical RMS Amperes240 Volts200,000

480 Volts200,000

600 Volts200,000

Dc Amperes250 Volts10,000

Instantaneous TripRating in Amperes50

Interrupting Rating (UL Listed)BreakerFrame

FB Tri-Pac

Maximum

Limiter 100 FBP06

Minimum

Maximum Single PoleTrip Times at 25°C ➀

Circuit Breaker Time/Current Curves

Tri-Pac Circuit Breakers

Catalog Type FB Circuit Breakers, 50 Amperes, 2 and 3 Poles,600 Volts Ac Max., 250 Volts Dc

Application and coordination curves based on 40°C ambientcold start, connected with four (4) feet of 60°C rated wiresize and tested in open air with current in all poles.

Single (1) pole test data at 25°C based on NEMA procedures forverifying performance of molded case circuit breakers.

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

TIME IN

SECONDS

1,000

500

300

200

5,000

3,000

2,000

1 HOUR1 M

INUTE

2 HOURS

TIM

E IN

SEC

ONDS

10,000

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

1,000

500

300

200

5,000

3,000

2,000

1 HO

UR1

MIN

UTE

2 HO

URS

CURRENT IN AMPERES

CURRENT IN AMPERES

10,000

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

100

8060 9070504030201086 975

1 CYCLE

1 CY

CLE

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

100080

0

600

900

700

500

400

300

200

1008060 907050

100,

000

80,0

00

60,0

00

90,0

00

70,0

00

50,0

00

40,0

00

30,0

00

20,0

004030201086 975

AB DE-ION Tri-Pac® Circuit Breakers

Page 25: Westinghouse AB DE-ION Current Limiting Circuit Breakerspub/@electrical/... · Application Data 29-167C Page 3 October 1997 AB DE-ION Current Limit-R® Circuit Breakers Type FCL,

Application Data29-167C

Page 25

October 1997

Type FB, 70 Amperes, 2 and 3 Poles

Curve No. SC-3577-76A

1000

800

600

900

700

500

400

300

200

Fixed Instantaneous Trip Amperes600-1200

Symmetrical RMS Amperes240 Volts200,000

480 Volts200,000

600 Volts200,000

Dc Amperes250 Volts10,000

Instantaneous TripRating in Amperes70

Interrupting Rating (UL Listed)BreakerFrame

FB Tri-Pac

Maximum

Limiter 100 FBP06

MinimumMaximum Single PoleTrip Times at 25°C ➀

Circuit Breaker Time/Current Curves

Tri-Pac Circuit Breakers

Catalog Type FB Circuit Breakers, 70 Amperes, 2 and 3 Poles,600 Volts Ac Max., 250 Volts Dc

Application and coordination curves based on 40°C ambientcold start, connected with four (4) feet of 60°C rated wiresize and tested in open air with current in all poles.

Single (1) pole test data at 25°C based on NEMA procedures forverifying performance of molded case circuit breakers.

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

TIME IN

SECONDS

1,000

500

300

200

5,000

3,000

2,000

1 HOUR1 M

INUTE

2 HOURS

TIM

E IN

SEC

ONDS

10,000

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

1,000

500

300

200

5,000

3,000

2,000

1 HO

UR1

MIN

UTE

2 HO

URS

CURRENT IN AMPERES

CURRENT IN AMPERES

10,000

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

100

8060 9070504030201086 975

1 CYCLE

1 CY

CLE

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

100080

0

600

900

700

500

400

300

200

1008060 907050

100,

000

80,0

00

60,0

00

90,0

00

70,0

00

50,0

00

40,0

00

30,0

00

20,0

004030201086 975

AB DE-ION Tri Pac® Circuit Breakers

Page 26: Westinghouse AB DE-ION Current Limiting Circuit Breakerspub/@electrical/... · Application Data 29-167C Page 3 October 1997 AB DE-ION Current Limit-R® Circuit Breakers Type FCL,

Application Data29-167C

Page 26

October 1997

Type FB, 90 Amperes, 2 and 3 Poles

Curve No. SC-3578-76A

1000

800

600

900

700

500

400

300

200

Fixed Instantaneous Trip Amperes700-1400

Symmetrical RMS Amperes240 Volts200,000

480 Volts200,000

600 Volts200,000

Dc Amperes250 Volts10,000

Instantaneous TripRating in Amperes90

Interrupting Rating (UL Listed)BreakerFrame

FB Tri-Pac

Maximum

Limiter 100 FBP06

Minimum

Maximum Single PoleTrip Times at 25°C ➀

Circuit Breaker Time/Current Curves

Tri-Pac Circuit Breakers

Catalog Type FB Circuit Breakers, 90 Amperes, 2 and 3 Poles,600 Volts Ac Max., 250 Volts Dc

Application and coordination curves based on 40°C ambientcold start, connected with four (4) feet of 60°C rated wiresize and tested in open air with current in all poles.

Single (1) pole test data at 25°C based on NEMA procedures forverifying performance of molded case circuit breakers.

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

TIME IN

SECONDS

1,000

500

300

200

5,000

3,000

2,000

1 HOUR1 M

INUTE

2 HOURS

TIM

E IN

SEC

ONDS

10,000

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

1,000

500

300

200

5,000

3,000

2,000

1 HO

UR1

MIN

UTE

2 HO

URS

CURRENT IN AMPERES

CURRENT IN AMPERES

10,000

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

100

8060 9070504030201086 975

1 CYCLE

1 CY

CLE

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

100080

0

600

900

700

500

400

300

200

1008060 907050

100,

000

80,0

00

60,0

00

90,0

00

70,0

00

50,0

00

40,0

00

30,0

00

20,0

004030201086 975

AB DE-ION Tri-Pac® Circuit Breakers

Page 27: Westinghouse AB DE-ION Current Limiting Circuit Breakerspub/@electrical/... · Application Data 29-167C Page 3 October 1997 AB DE-ION Current Limit-R® Circuit Breakers Type FCL,

Application Data29-167C

Page 27

October 1997

Type FB, 100 Amperes, 2 and 3 Poles

Curve No. SC-3579-76A

1000

800

600

900

700

500

400

300

200

Fixed Instantaneous Trip Amperes700-1400

Symmetrical RMS Amperes240 Volts200,000

480 Volts200,000

600 Volts200,000

Dc Amperes250 Volts10,000

Instantaneous TripRating in Amperes100

Interrupting Rating (UL Listed)BreakerFrame

FB Tri-Pac

Maximum

Limiter 100 FBP06

Minimum

Maximum Single PoleTrip Times at 25°C ➀

Circuit Breaker Time/Current Curves

Tri-Pac Circuit Breakers

Catalog Type FB Circuit Breakers, 100 Amperes, 2 and 3 Poles,600 Volts Ac Max., 250 Volts Dc

Application and coordination curves based on 40°C ambientcold start, connected with four (4) feet of 60°C rated wiresize and tested in open air with current in all poles.

Single (1) pole test data at 25°C based on NEMA procedures forverifying performance of molded case circuit breakers.

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

TIME IN

SECONDS

1,000

500

300

200

5,000

3,000

2,000

1 HOUR1 M

INUTE

2 HOURS

TIM

E IN

SEC

ONDS

10,000

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

1,000

500

300

200

5,000

3,000

2,000

1 HO

UR1

MIN

UTE

2 HO

URS

CURRENT IN AMPERES

CURRENT IN AMPERES

10,000

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

100

8060 9070504030201086 975

1 CYCLE

1 CY

CLE

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

100080

0

600

900

700

500

400

300

200

1008060 907050

100,

000

80,0

00

60,0

00

90,0

00

70,0

00

50,0

00

40,0

00

30,0

00

20,0

004030201086 975

AB DE-ION Tri Pac® Circuit Breakers

Page 28: Westinghouse AB DE-ION Current Limiting Circuit Breakerspub/@electrical/... · Application Data 29-167C Page 3 October 1997 AB DE-ION Current Limit-R® Circuit Breakers Type FCL,

Application Data29-167C

Page 28

October 1997

Type LA, 70 Amperes, 2 and 3 Poles

Curve No. SC-3580-76A

1000

800

600

900

700

500

400

300

200

Adjustable Instantaneous Trip Amperes350-700

Symmetrical RMS Amperes240 Volts200,000

480 Volts200,000

600 Volts200,000

Dc Amperes250 Volts10,000

Instantaneous TripRating in Amperes70

Interrupting Rating (UL Listed)BreakerFrame

LA Tri-Pac

Maximum

Limiter 200 LAP08

Limiter 400 LAP10

Minimum

LO HI

Maximum Single PoleTrip Times at 25°C ➀

Circuit Breaker Time/Current Curves

Tri-Pac Circuit Breakers

Catalog Type LA Circuit Breakers, 70 Amperes, 2 and 3 Poles,600 Volts Ac Max., 250 Volts Dc

Application and coordination curves based on 40°C ambientcold start, connected with four (4) feet of 60°C rated wiresize and tested in open air with current in all poles.

Single (1) pole test data at 25°C based on NEMA procedures forverifying performance of molded case circuit breakers.

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

TIME IN

SECONDS

1,000

500

300

200

5,000

3,000

2,000

1 HOUR1 M

INUTE

2 HOURS

TIM

E IN

SEC

ONDS

10,000

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

1,000

500

300

200

5,000

3,000

2,000

1 HO

UR1

MIN

UTE

2 HO

URS

CURRENT IN AMPERES

CURRENT IN AMPERES

10,000

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

100

8060 9070504030201086 975

1 CYCLE

1 CY

CLE

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

100080

0

600

900

700

500

400

300

200

1008060 907050

100,

000

80,0

00

60,0

00

90,0

00

70,0

00

50,0

00

40,0

00

30,0

00

20,0

004030201086 975

AB DE-ION Tri-Pac® Circuit Breakers

Page 29: Westinghouse AB DE-ION Current Limiting Circuit Breakerspub/@electrical/... · Application Data 29-167C Page 3 October 1997 AB DE-ION Current Limit-R® Circuit Breakers Type FCL,

Application Data29-167C

Page 29

October 1997

Type LA, 90 Amperes, 2 and 3 Poles

Curve No. SC-3581-76A

1000

800

600

900

700

500

400

300

200

Adjustable Instantaneous Trip Amperes450-900

Symmetrical RMS Amperes240 Volts200,000

480 Volts200,000

600 Volts200,000

Dc Amperes250 Volts10,000

Instantaneous TripRating in Amperes90

Interrupting Rating (UL Listed)BreakerFrame

LA Tri-Pac

Maximum

Limiter 200 LAP08

Limiter 400 LAP10

Minimum

LO HI

Maximum Single PoleTrip Times at 25°C ➀

Circuit Breaker Time/Current Curves

Tri-Pac Circuit Breakers

Catalog Type LA Circuit Breakers, 90 Amperes, 2 and 3 Poles,600 Volts Ac Max., 250 Volts Dc

Application and coordination curves based on 40°C ambientcold start, connected with four (4) feet of 60°C rated wiresize and tested in open air with current in all poles.

Single (1) pole test data at 25°C based on NEMA procedures forverifying performance of molded case circuit breakers.

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

TIME IN

SECONDS

1,000

500

300

200

5,000

3,000

2,000

1 HOUR1 M

INUTE

2 HOURS

TIM

E IN

SEC

ONDS

10,000

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

1,000

500

300

200

5,000

3,000

2,000

1 HO

UR1

MIN

UTE

2 HO

URS

CURRENT IN AMPERES

CURRENT IN AMPERES

10,000

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

100

8060 9070504030201086 975

1 CYCLE

1 CY

CLE

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

100080

0

600

900

700

500

400

300

200

1008060 907050

100,

000

80,0

00

60,0

00

90,0

00

70,0

00

50,0

00

40,0

00

30,0

00

20,0

004030201086 975

AB DE-ION Tri Pac® Circuit Breakers

Page 30: Westinghouse AB DE-ION Current Limiting Circuit Breakerspub/@electrical/... · Application Data 29-167C Page 3 October 1997 AB DE-ION Current Limit-R® Circuit Breakers Type FCL,

Application Data29-167C

Page 30

October 1997

Type LA, 100 Amperes, 2 and 3 Poles

Curve No. SC-3582-76A

1000

800

600

900

700

500

400

300

200

Adjustable Instantaneous Trip Amperes500-1000

Symmetrical RMS Amperes240 Volts200,000

480 Volts200,000

600 Volts200,000

Dc Amperes250 Volts10,000

Instantaneous TripRating in Amperes100

Interrupting Rating (UL Listed)BreakerFrame

LA Tri-Pac

Maximum

Limiter 200 LAP08

Limiter 400 LAP10

Minimum

LO HI

Maximum Single PoleTrip Times at 25°C ➀

Circuit Breaker Time/Current Curves

Tri-Pac Circuit Breakers

Catalog Type LA Circuit Breakers, 100 Amperes, 2 and 3 Poles,600 Volts Ac Max., 250 Volts Dc

Application and coordination curves based on 40°C ambientcold start, connected with four (4) feet of 75°C rated wiresize and tested in open air with current in all poles.

Single (1) pole test data at 25°C based on NEMA procedures forverifying performance of molded case circuit breakers.

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

TIME IN

SECONDS

1,000

500

300

200

5,000

3,000

2,000

1 HOUR1 M

INUTE

2 HOURS

TIM

E IN

SEC

ONDS

10,000

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

1,000

500

300

200

5,000

3,000

2,000

1 HO

UR1

MIN

UTE

2 HO

URS

CURRENT IN AMPERES

CURRENT IN AMPERES

10,000

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

100

8060 9070504030201086 975

1 CYCLE

1 CY

CLE

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

100080

0

600

900

700

500

400

300

200

1008060 907050

100,

000

80,0

00

60,0

00

90,0

00

70,0

00

50,0

00

40,0

00

30,0

00

20,0

004030201086 975

AB DE-ION Tri-Pac® Circuit Breakers

Page 31: Westinghouse AB DE-ION Current Limiting Circuit Breakerspub/@electrical/... · Application Data 29-167C Page 3 October 1997 AB DE-ION Current Limit-R® Circuit Breakers Type FCL,

Application Data29-167C

Page 31

October 1997

Type LA, 125 Amperes, 2 and 3 Poles

Curve No. SC-3583-76A

1000

800

600

900

700

500

400

300

200

Adjustable Instantaneous Trip Amperes625-1250

Symmetrical RMS Amperes240 Volts200,000

480 Volts200,000

600 Volts200,000

Dc Amperes250 Volts10,000

Instantaneous TripRating in Amperes125

Interrupting Rating (UL Listed)BreakerFrame

LA Tri-Pac

Maximum

Limiter 200 LAP08

Limiter 400 LAP10

Minimum

LO HI

Maximum Single PoleTrip Times at 25°C ➀

Circuit Breaker Time/Current Curves

Tri-Pac Circuit Breakers

Catalog Type LA Circuit Breakers, 125 Amperes, 2 and 3 Poles,600 Volts Ac Max., 250 Volts Dc

Application and coordination curves based on 40°C ambientcold start, connected with four (4) feet of 75°C rated wiresize and tested in open air with current in all poles.

Single (1) pole test data at 25°C based on NEMA procedures forverifying performance of molded case circuit breakers.

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

TIME IN

SECONDS

1,000

500

300

200

5,000

3,000

2,000

1 HOUR1 M

INUTE

2 HOURS

TIM

E IN

SEC

ONDS

10,000

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

1,000

500

300

200

5,000

3,000

2,000

1 HO

UR1

MIN

UTE

2 HO

URS

CURRENT IN AMPERES

CURRENT IN AMPERES

10,000

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

100

8060 9070504030201086 975

1 CYCLE

1 CY

CLE

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

100080

0

600

900

700

500

400

300

200

1008060 907050

100,

000

80,0

00

60,0

00

90,0

00

70,0

00

50,0

00

40,0

00

30,0

00

20,0

004030201086 975

AB DE-ION Tri Pac® Circuit Breakers

Page 32: Westinghouse AB DE-ION Current Limiting Circuit Breakerspub/@electrical/... · Application Data 29-167C Page 3 October 1997 AB DE-ION Current Limit-R® Circuit Breakers Type FCL,

Application Data29-167C

Page 32

October 1997

Type LA, 150 Amperes, 2 and 3 Poles

Curve No. SC-3584-76A

1000

800

600

900

700

500

400

300

200

Adjustable Instantaneous Trip Amperes750-1500

Symmetrical RMS Amperes240 Volts200,000

480 Volts200,000

600 Volts200,000

Dc Amperes250 Volts10,000

Instantaneous TripRating in Amperes150

Interrupting Rating (UL Listed)BreakerFrame

LA Tri-Pac

Maximum

Limiter 200 LAP08

Limiter 400 LAP10

Minimum

LO HI

Maximum Single PoleTrip Times at 25°C ➀

Circuit Breaker Time/Current Curves

Tri-Pac Circuit Breakers

Catalog Type LA Circuit Breakers, 150 Amperes, 2 and 3 Poles,600 Volts Ac Max., 250 Volts Dc

Application and coordination curves based on 40°C ambientcold start, connected with four (4) feet of 75°C rated wiresize and tested in open air with current in all poles.

Single (1) pole test data at 25°C based on NEMA procedures forverifying performance of molded case circuit breakers.

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

TIME IN

SECONDS

1,000

500

300

200

5,000

3,000

2,000

1 HOUR1 M

INUTE

2 HOURS

TIM

E IN

SEC

ONDS

10,000

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

1,000

500

300

200

5,000

3,000

2,000

1 HO

UR1

MIN

UTE

2 HO

URS

CURRENT IN AMPERES

CURRENT IN AMPERES

10,000

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

100

8060 9070504030201086 975

1 CYCLE

1 CY

CLE

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

100080

0

600

900

700

500

400

300

200

1008060 907050

100,

000

80,0

00

60,0

00

90,0

00

70,0

00

50,0

00

40,0

00

30,0

00

20,0

004030201086 975

AB DE-ION Tri-Pac® Circuit Breakers

Page 33: Westinghouse AB DE-ION Current Limiting Circuit Breakerspub/@electrical/... · Application Data 29-167C Page 3 October 1997 AB DE-ION Current Limit-R® Circuit Breakers Type FCL,

Application Data29-167C

Page 33

October 1997

Type LA, 175 Amperes, 2 and 3 Poles

Curve No. SC-3585-76A

1000

800

600

900

700

500

400

300

200

Adjustable Instantaneous Trip Amperes875-1750

Symmetrical RMS Amperes240 Volts200,000

480 Volts200,000

600 Volts200,000

Dc Amperes250 Volts10,000

Instantaneous TripRating in Amperes175

Interrupting Rating (UL Listed)BreakerFrame

LA Tri-Pac

Maximum

Limiter 200 LAP08

Limiter 400 LAP10

Minimum

LO HI

Maximum Single PoleTrip Times at 25°C ➀

Circuit Breaker Time/Current Curves

Tri-Pac Circuit Breakers

Catalog Type LA Circuit Breakers, 175 Amperes, 2 and 3 Poles,600 Volts Ac Max., 250 Volts Dc

Application and coordination curves based on 40°C ambientcold start, connected with four (4) feet of 75°C rated wiresize and tested in open air with current in all poles.

Single (1) pole test data at 25°C based on NEMA procedures forverifying performance of molded case circuit breakers.

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

TIME IN

SECONDS

1,000

500

300

200

5,000

3,000

2,000

1 HOUR1 M

INUTE

2 HOURS

TIM

E IN

SEC

ONDS

10,000

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

1,000

500

300

200

5,000

3,000

2,000

1 HO

UR1

MIN

UTE

2 HO

URS

CURRENT IN AMPERES

CURRENT IN AMPERES

10,000

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

100

8060 9070504030201086 975

1 CYCLE

1 CY

CLE

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

100080

0

600

900

700

500

400

300

200

1008060 907050

100,

000

80,0

00

60,0

00

90,0

00

70,0

00

50,0

00

40,0

00

30,0

00

20,0

004030201086 975

AB DE-ION Tri Pac® Circuit Breakers

Page 34: Westinghouse AB DE-ION Current Limiting Circuit Breakerspub/@electrical/... · Application Data 29-167C Page 3 October 1997 AB DE-ION Current Limit-R® Circuit Breakers Type FCL,

Application Data29-167C

Page 34

October 1997

Type LA, 200 Amperes, 2 and 3 Poles

Curve No. SC-3586-76A

1000

800

600

900

700

500

400

300

200

Adjustable Instantaneous Trip Amperes1000-2000

Symmetrical RMS Amperes240 Volts200,000

480 Volts200,000

600 Volts200,000

Dc Amperes250 Volts10,000

Instantaneous TripRating in Amperes200

Interrupting Rating (UL Listed)BreakerFrame

LA Tri-Pac

Maximum

Limiter 200 LAP08

Limiter 400 LAP10

Minimum

LO HI

Maximum Single PoleTrip Times at 25°C ➀

Circuit Breaker Time/Current Curves

Tri-Pac Circuit Breakers

Catalog Type LA Circuit Breakers, 200 Amperes, 2 and 3 Poles,600 Volts Ac Max., 250 Volts Dc

Application and coordination curves based on 40°C ambientcold start, connected with four (4) feet of 75°C rated wiresize and tested in open air with current in all poles.

Single (1) pole test data at 25°C based on NEMA procedures forverifying performance of molded case circuit breakers.

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

TIME IN

SECONDS

1,000

500

300

200

5,000

3,000

2,000

1 HOUR1 M

INUTE

2 HOURS

TIM

E IN

SEC

ONDS

10,000

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

1,000

500

300

200

5,000

3,000

2,000

1 HO

UR1

MIN

UTE

2 HO

URS

CURRENT IN AMPERES

CURRENT IN AMPERES

10,000

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

100

8060 9070504030201086 975

1 CYCLE

1 CY

CLE

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

100080

0

600

900

700

500

400

300

200

1008060 907050

100,

000

80,0

00

60,0

00

90,0

00

70,0

00

50,0

00

40,0

00

30,0

00

20,0

004030201086 975

AB DE-ION Tri-Pac® Circuit Breakers

Page 35: Westinghouse AB DE-ION Current Limiting Circuit Breakerspub/@electrical/... · Application Data 29-167C Page 3 October 1997 AB DE-ION Current Limit-R® Circuit Breakers Type FCL,

Application Data29-167C

Page 35

October 1997

Type LA, 225 Amperes, 2 and 3 Poles

Curve No. SC-3587-76A

1000

800

600

900

700

500

400

300

200

Adjustable Instantaneous Trip Amperes1125-2250

Symmetrical RMS Amperes240 Volts200,000

480 Volts200,000

600 Volts200,000

Dc Amperes250 Volts10,000

Instantaneous TripRating in Amperes225

Interrupting Rating (UL Listed)BreakerFrame

LA Tri-Pac

Maximum

Limiter 400 LAP10

Minimum

LO HI

Maximum Single PoleTrip Times at 25°C ➀

Circuit Breaker Time/Current Curves

Tri-Pac Circuit Breakers

Catalog Type LA Circuit Breakers, 225 Amperes, 2 and 3 Poles,600 Volts Ac Max., 250 Volts Dc

Application and coordination curves based on 40°C ambientcold start, connected with four (4) feet of 75°C rated wiresize and tested in open air with current in all poles.

Single (1) pole test data at 25°C based on NEMA procedures forverifying performance of molded case circuit breakers.

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

TIME IN

SECONDS

1,000

500

300

200

5,000

3,000

2,000

1 HOUR1 M

INUTE

2 HOURS

TIM

E IN

SEC

ONDS

10,000

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

1,000

500

300

200

5,000

3,000

2,000

1 HO

UR1

MIN

UTE

2 HO

URS

CURRENT IN AMPERES

CURRENT IN AMPERES

10,000

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

100

8060 9070504030201086 975

1 CYCLE

1 CY

CLE

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

100080

0

600

900

700

500

400

300

200

1008060 907050

100,

000

80,0

00

60,0

00

90,0

00

70,0

00

50,0

00

40,0

00

30,0

00

20,0

004030201086 975

AB DE-ION Tri Pac® Circuit Breakers

Page 36: Westinghouse AB DE-ION Current Limiting Circuit Breakerspub/@electrical/... · Application Data 29-167C Page 3 October 1997 AB DE-ION Current Limit-R® Circuit Breakers Type FCL,

Application Data29-167C

Page 36

October 1997

Type LA, 250 Amperes, 2 and 3 Poles

Curve No. SC-3588-76A

1000

800

600

900

700

500

400

300

200

Adjustable Instantaneous Trip Amperes1250-2500

Symmetrical RMS Amperes240 Volts200,000

480 Volts200,000

600 Volts200,000

Dc Amperes250 Volts10,000

Instantaneous TripRating in Amperes250

Interrupting Rating (UL Listed)BreakerFrame

LA Tri-Pac

Maximum

Limiter 400 LAP10

Minimum

LO HI

Maximum Single PoleTrip Times at 25°C ➀

Circuit Breaker Time/Current Curves

Tri-Pac Circuit Breakers

Catalog Type LA Circuit Breakers, 250 Amperes, 2 and 3 Poles,600 Volts Ac Max., 250 Volts Dc

Application and coordination curves based on 40°C ambientcold start, connected with four (4) feet of 75°C rated wiresize and tested in open air with current in all poles.

Single (1) pole test data at 25°C based on NEMA procedures forverifying performance of molded case circuit breakers.

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

TIME IN

SECONDS

1,000

500

300

200

5,000

3,000

2,000

1 HOUR1 M

INUTE

2 HOURS

TIM

E IN

SEC

ONDS

10,000

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

1,000

500

300

200

5,000

3,000

2,000

1 HO

UR1

MIN

UTE

2 HO

URS

CURRENT IN AMPERES

CURRENT IN AMPERES

10,000

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

100

8060 9070504030201086 975

1 CYCLE

1 CY

CLE

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

100080

0

600

900

700

500

400

300

200

1008060 907050

100,

000

80,0

00

60,0

00

90,0

00

70,0

00

50,0

00

40,0

00

30,0

00

20,0

004030201086 975

AB DE-ION Tri-Pac® Circuit Breakers

Page 37: Westinghouse AB DE-ION Current Limiting Circuit Breakerspub/@electrical/... · Application Data 29-167C Page 3 October 1997 AB DE-ION Current Limit-R® Circuit Breakers Type FCL,

Application Data29-167C

Page 37

October 1997

Type LA, 300 Amperes, 2 and 3 Poles

Curve No. SC-3589-76A

1000

800

600

900

700

500

400

300

200

Adjustable Instantaneous Trip Amperes1500-3000

Symmetrical RMS Amperes240 Volts200,000

480 Volts200,000

600 Volts200,000

Dc Amperes250 Volts10,000

Instantaneous TripRating in Amperes300

Interrupting Rating (UL Listed)BreakerFrame

LA Tri-Pac

Maximum

Limiter 400 LAP10

Minimum

LO HI

Maximum Single PoleTrip Times at 25°C ➀

Circuit Breaker Time/Current Curves

Tri-Pac Circuit Breakers

Catalog Type LA Circuit Breakers, 300 Amperes, 2 and 3 Poles,600 Volts Ac Max., 250 Volts Dc

Application and coordination curves based on 40°C ambientcold start, connected with four (4) feet of 75°C rated wiresize and tested in open air with current in all poles.

Single (1) pole test data at 25°C based on NEMA procedures forverifying performance of molded case circuit breakers.

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

TIME IN

SECONDS

1,000

500

300

200

5,000

3,000

2,000

1 HOUR1 M

INUTE

2 HOURS

TIM

E IN

SEC

ONDS

10,000

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

1,000

500

300

200

5,000

3,000

2,000

1 HO

UR1

MIN

UTE

2 HO

URS

CURRENT IN AMPERES

CURRENT IN AMPERES

10,000

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

100

8060 9070504030201086 975

1 CYCLE

1 CY

CLE

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

100080

0

600

900

700

500

400

300

200

1008060 907050

100,

000

80,0

00

60,0

00

90,0

00

70,0

00

50,0

00

40,0

00

30,0

00

20,0

004030201086 975

AB DE-ION Tri Pac® Circuit Breakers

Page 38: Westinghouse AB DE-ION Current Limiting Circuit Breakerspub/@electrical/... · Application Data 29-167C Page 3 October 1997 AB DE-ION Current Limit-R® Circuit Breakers Type FCL,

Application Data29-167C

Page 38

October 1997

Type LA, 350 Amperes, 2 and 3 Poles

Curve No. SC-3590-76A

1000

800

600

900

700

500

400

300

200

Adjustable Instantaneous Trip Amperes1750-3500

Symmetrical RMS Amperes240 Volts200,000

480 Volts200,000

600 Volts200,000

Dc Amperes250 Volts10,000

Instantaneous TripRating in Amperes350

Interrupting Rating (UL Listed)BreakerFrame

LA Tri-Pac

Maximum

Limiter 400 LAP10

Minimum

LO

HI

Maximum Single PoleTrip Times at 25°C ➀

Circuit Breaker Time/Current Curves

Tri-Pac Circuit Breakers

Catalog Type LA Circuit Breakers, 350 Amperes, 2 and 3 Poles,600 Volts Ac Max., 250 Volts Dc

Application and coordination curves based on 40°C ambientcold start, connected with four (4) feet of 75°C rated wiresize and tested in open air with current in all poles.

Single (1) pole test data at 25°C based on NEMA procedures forverifying performance of molded case circuit breakers.

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

TIME IN

SECONDS

1,000

500

300

200

5,000

3,000

2,000

1 HOUR1 M

INUTE

2 HOURS

TIM

E IN

SEC

ONDS

10,000

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

1,000

500

300

200

5,000

3,000

2,000

1 HO

UR1

MIN

UTE

2 HO

URS

CURRENT IN AMPERES

CURRENT IN AMPERES

10,000

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

100

8060 9070504030201086 975

1 CYCLE

1 CY

CLE

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

100080

0

600

900

700

500

400

300

200

1008060 907050

100,

000

80,0

00

60,0

00

90,0

00

70,0

00

50,0

00

40,0

00

30,0

00

20,0

004030201086 975

AB DE-ION Tri-Pac® Circuit Breakers

Page 39: Westinghouse AB DE-ION Current Limiting Circuit Breakerspub/@electrical/... · Application Data 29-167C Page 3 October 1997 AB DE-ION Current Limit-R® Circuit Breakers Type FCL,

Application Data29-167C

Page 39

October 1997

Type LA, 400 Amperes, 2 and 3 Poles

Curve No. SC-3591-76A

1000

800

600

900

700

500

400

300

200

Adjustable Instantaneous Trip Amperes2000-4000

Symmetrical RMS Amperes240 Volts200,000

480 Volts200,000

600 Volts200,000

Dc Amperes250 Volts10,000

Instantaneous TripRating in Amperes400

Interrupting Rating (UL Listed)BreakerFrame

LA Tri-Pac

Maximum

Limiter 400 LAP10

Minimum

LO HI

Maximum Single PoleTrip Times at 25°C ➀

Circuit Breaker Time/Current Curves

Tri-Pac Circuit Breakers

Catalog Type LA Circuit Breakers, 400 Amperes, 2 and 3 Poles,600 Volts Ac Max., 250 Volts Dc

Application and coordination curves based on 40°C ambientcold start, connected with four (4) feet of 75°C rated wiresize and tested in open air with current in all poles.

Single (1) pole test data at 25°C based on NEMA procedures forverifying performance of molded case circuit breakers.

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

TIME IN

SECONDS

1,000

500

300

200

5,000

3,000

2,000

1 HOUR1 M

INUTE

2 HOURS

TIM

E IN

SEC

ONDS

10,000

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

1,000

500

300

200

5,000

3,000

2,000

1 HO

UR1

MIN

UTE

2 HO

URS

CURRENT IN AMPERES

CURRENT IN AMPERES

10,000

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

100

8060 9070504030201086 975

1 CYCLE

1 CY

CLE

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

100080

0

600

900

700

500

400

300

200

1008060 907050

100,

000

80,0

00

60,0

00

90,0

00

70,0

00

50,0

00

40,0

00

30,0

00

20,0

004030201086 975

AB DE-ION Tri Pac® Circuit Breakers

Page 40: Westinghouse AB DE-ION Current Limiting Circuit Breakerspub/@electrical/... · Application Data 29-167C Page 3 October 1997 AB DE-ION Current Limit-R® Circuit Breakers Type FCL,

Application Data29-167C

Page 40

October 1997

Type NB, 300 Amperes, 2 and 3 Poles

Curve No. SC-3592-76B

1000

800

600

900

700

500

400

300

200

Adjustable Instantaneous Trip Amperes1500-3000

Symmetrical RMS Amperes240 Volts200,000

480 Volts200,000

600 Volts200,000

Dc Amperes250 Volts10,000

Instantaneous TripRating in Amperes300

Interrupting Rating (UL Listed)BreakerFrame

NB Tri-Pac

Maximum

Limiter 500 NBP12

Minimum

LO HI

Limiter 800 NBP20

Maximum Single PoleTrip Times at 25°C ➀

Circuit Breaker Time/Current Curves

Tri-Pac Circuit Breakers

Catalog Type NB Circuit Breakers, 300 Amperes, 2 and 3 Poles,600 Volts Ac Max., 250 Volts Dc

Application and coordination curves based on 40°C ambientcold start, connected with four (4) feet of 75°C rated wiresize and tested in open air with current in all poles.

For single pole tests use dummy fuses or bypass the Tri-Pacfuses; otherwise, results may not agree with curve.

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

TIME IN

SECONDS

1,000

500

300

200

5,000

3,000

2,000

1 HOUR1 M

INUTE

2 HOURS

TIM

E IN

SEC

ONDS

10,000

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

1,000

500

300

200

5,000

3,000

2,000

1 HO

UR1

MIN

UTE

2 HO

URS

CURRENT IN AMPERES

CURRENT IN AMPERES

10,000

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

100

8060 9070504030201086 975

1 CYCLE

1 CY

CLE

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

100080

0

600

900

700

500

400

300

200

1008060 907050

100,

000

80,0

00

60,0

00

90,0

00

70,0

00

50,0

00

40,0

00

30,0

00

20,0

004030201086 975

AB DE-ION Tri-Pac® Circuit Breakers

Page 41: Westinghouse AB DE-ION Current Limiting Circuit Breakerspub/@electrical/... · Application Data 29-167C Page 3 October 1997 AB DE-ION Current Limit-R® Circuit Breakers Type FCL,

Application Data29-167C

Page 41

October 1997

Type NB, 350 Amperes, 2 and 3 Poles

Curve No. SC-3593-76B

1000

800

600

900

700

500

400

300

200

Adjustable Instantaneous Trip Amperes1750-3500

Symmetrical RMS Amperes240 Volts200,000

480 Volts200,000

600 Volts200,000

Dc Amperes250 Volts10,000

Instantaneous TripRating in Amperes350

Interrupting Rating (UL Listed)BreakerFrame

NB Tri-Pac

Maximum

Limiter 500 NBP12

Minimum

LO HI

Limiter 800 NBP20

Maximum Single PoleTrip Times at 25°C ➀

Circuit Breaker Time/Current Curves

Tri-Pac Circuit Breakers

Catalog Type NB Circuit Breakers, 350 Amperes, 2 and 3 Poles,600 Volts Ac Max., 250 Volts Dc

Application and coordination curves based on 40°C ambientcold start, connected with four (4) feet of 75°C rated wiresize and tested in open air with current in all poles.

For single pole tests use dummy fuses or bypass the Tri-Pacfuses; otherwise, results may not agree with curve.

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

TIME IN

SECONDS

1,000

500

300

200

5,000

3,000

2,000

1 HOUR1 M

INUTE

2 HOURS

TIM

E IN

SEC

ONDS

10,000

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

1,000

500

300

200

5,000

3,000

2,000

1 HO

UR1

MIN

UTE

2 HO

URS

CURRENT IN AMPERES

CURRENT IN AMPERES

10,000

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

100

8060 9070504030201086 975

1 CYCLE

1 CY

CLE

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

100080

0

600

900

700

500

400

300

200

1008060 907050

100,

000

80,0

00

60,0

00

90,0

00

70,0

00

50,0

00

40,0

00

30,0

00

20,0

004030201086 975

AB DE-ION Tri Pac® Circuit Breakers

Page 42: Westinghouse AB DE-ION Current Limiting Circuit Breakerspub/@electrical/... · Application Data 29-167C Page 3 October 1997 AB DE-ION Current Limit-R® Circuit Breakers Type FCL,

Application Data29-167C

Page 42

October 1997

Type NB, 400 Amperes, 2 and 3 Poles

Curve No. SC-3594-76B

1000

800

600

900

700

500

400

300

200

Adjustable Instantaneous Trip Amperes2000-4000

Symmetrical RMS Amperes240 Volts200,000

480 Volts200,000

600 Volts200,000

Instantaneous TripRating in Amperes400

Interrupting Rating (UL Listed)BreakerFrame

NB Tri-Pac

Maximum

Limiter 500 NBP12

Minimum

LO HI

Limiter 800 NBP20

Maximum Single PoleTrip Times at 25°C ➀

Circuit Breaker Time/Current Curves

Tri-Pac Circuit Breakers

Catalog Type NB Circuit Breakers, 400 Amperes, 2 and 3 Poles,600 Volts Ac Max.

Application and coordination curves based on 40°C ambientcold start, connected with four (4) feet of 75°C rated wiresize and tested in open air with current in all poles.

For single pole tests use dummy fuses or bypass the Tri-Pacfuses; otherwise, results may not agree with curve.

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

TIME IN

SECONDS

1,000

500

300

200

5,000

3,000

2,000

1 HOUR1 M

INUTE

2 HOURS

TIM

E IN

SEC

ONDS

10,000

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

1,000

500

300

200

5,000

3,000

2,000

1 HO

UR1

MIN

UTE

2 HO

URS

CURRENT IN AMPERES

CURRENT IN AMPERES

10,000

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

100

8060 9070504030201086 975

1 CYCLE

1 CY

CLE

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

100080

0

600

900

700

500

400

300

200

1008060 907050

100,

000

80,0

00

60,0

00

90,0

00

70,0

00

50,0

00

40,0

00

30,0

00

20,0

004030201086 975

AB DE-ION Tri-Pac® Circuit Breakers

Page 43: Westinghouse AB DE-ION Current Limiting Circuit Breakerspub/@electrical/... · Application Data 29-167C Page 3 October 1997 AB DE-ION Current Limit-R® Circuit Breakers Type FCL,

Application Data29-167C

Page 43

October 1997

Type NB, 500 Amperes, 2 and 3 Poles

Curve No. SC-3595-76B

1000

800

600

900

700

500

400

300

200

Adjustable Instantaneous Trip Amperes2500-5000

Symmetrical RMS Amperes240 Volts200,000

480 Volts200,000

600 Volts200,000

Instantaneous TripRating in Amperes500

Interrupting Rating (UL Listed)BreakerFrame

NB Tri-Pac

Maximum

Limiter 500 NBP12

Minimum

LO HI

Limiter 800 NBP20

Maximum Single PoleTrip Times at 25°C ➀

Circuit Breaker Time/Current Curves

Tri-Pac Circuit Breakers

Catalog Type NB Circuit Breakers, 500 Amperes, 2 and 3 Poles,600 Volts Ac Max.

Application and coordination curves based on 40°C ambientcold start, connected with four (4) feet of 75°C rated wiresize and tested in open air with current in all poles.

For single pole tests use dummy fuses or bypass the Tri-Pacfuses; otherwise, results may not agree with curve.

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

TIME IN

SECONDS

1,000

500

300

200

5,000

3,000

2,000

1 HOUR1 M

INUTE

2 HOURS

TIM

E IN

SEC

ONDS

10,000

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

1,000

500

300

200

5,000

3,000

2,000

1 HO

UR1

MIN

UTE

2 HO

URS

CURRENT IN AMPERES

CURRENT IN AMPERES

10,000

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

100

8060 9070504030201086 975

1 CYCLE

1 CY

CLE

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

100080

0

600

900

700

500

400

300

200

1008060 907050

100,

000

80,0

00

60,0

00

90,0

00

70,0

00

50,0

00

40,0

00

30,0

00

20,0

004030201086 975

AB DE-ION Tri Pac® Circuit Breakers

Page 44: Westinghouse AB DE-ION Current Limiting Circuit Breakerspub/@electrical/... · Application Data 29-167C Page 3 October 1997 AB DE-ION Current Limit-R® Circuit Breakers Type FCL,

Application Data29-167C

Page 44

October 1997

Type NB, 600 Amperes, 2 and 3 Poles

Curve No. SC-3596-76B

1000

800

600

900

700

500

400

300

200

Adjustable Instantaneous Trip Amperes3000-6000

Symmetrical RMS Amperes240 Volts200,000

480 Volts200,000

600 Volts200,000

Instantaneous TripRating in Amperes600

Interrupting Rating (UL Listed)BreakerFrame

NB Tri-Pac

Maximum

Minimum

LO HI

Limiter 800 NBP20

Maximum Single PoleTrip Times at 25°C ➀

Circuit Breaker Time/Current Curves

Tri-Pac Circuit Breakers

Catalog Type NB Circuit Breakers, 600 Amperes, 2 and 3 Poles,600 Volts Ac Max.

Application and coordination curves based on 40°C ambientcold start, connected with four (4) feet of 75°C rated wiresize and tested in open air with current in all poles.

For single pole tests use dummy fuses or bypass the Tri-Pacfuses; otherwise, results may not agree with curve.

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

TIME IN

SECONDS

1,000

500

300

200

5,000

3,000

2,000

1 HOUR1 M

INUTE

2 HOURS

TIM

E IN

SEC

ONDS

10,000

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

1,000

500

300

200

5,000

3,000

2,000

1 HO

UR1

MIN

UTE

2 HO

URS

CURRENT IN AMPERES

CURRENT IN AMPERES

10,000

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

100

8060 9070504030201086 975

1 CYCLE

1 CY

CLE

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

100080

0

600

900

700

500

400

300

200

1008060 907050

100,

000

80,0

00

60,0

00

90,0

00

70,0

00

50,0

00

40,0

00

30,0

00

20,0

004030201086 975

AB DE-ION Tri-Pac® Circuit Breakers

Page 45: Westinghouse AB DE-ION Current Limiting Circuit Breakerspub/@electrical/... · Application Data 29-167C Page 3 October 1997 AB DE-ION Current Limit-R® Circuit Breakers Type FCL,

Application Data29-167C

Page 45

October 1997

Type NB, 700 Amperes, 2 and 3 Poles

Curve No. SC-3597-76B

1000

800

600

900

700

500

400

300

200

Adjustable Instantaneous Trip Amperes3000-6000

Symmetrical RMS Amperes240 Volts200,000

480 Volts200,000

600 Volts200,000

Instantaneous TripRating in Amperes700

Interrupting Rating (UL Listed)BreakerFrame

NB Tri-Pac

Maximum

Minimum

LO HI

Limiter 800 NBP20

Maximum Single PoleTrip Times at 25°C ➀

Circuit Breaker Time/Current Curves

Tri-Pac Circuit Breakers

Catalog Type NB Circuit Breakers, 700 Amperes, 2 and 3 Poles,600 Volts Ac Max.

Application and coordination curves based on 40°C ambientcold start, connected with four (4) feet of 75°C rated wiresize and tested in open air with current in all poles.

For single pole tests use dummy fuses or bypass the Tri-Pacfuses; otherwise, results may not agree with curve.

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

TIME IN

SECONDS

1,000

500

300

200

5,000

3,000

2,000

1 HOUR1 M

INUTE

2 HOURS

TIM

E IN

SEC

ONDS

10,000

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

1,000

500

300

200

5,000

3,000

2,000

1 HO

UR1

MIN

UTE

2 HO

URS

CURRENT IN AMPERES

CURRENT IN AMPERES

10,000

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

100

8060 9070504030201086 975

1 CYCLE

1 CY

CLE

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

100080

0

600

900

700

500

400

300

200

1008060 907050

100,

000

80,0

00

60,0

00

90,0

00

70,0

00

50,0

00

40,0

00

30,0

00

20,0

004030201086 975

AB DE-ION Tri Pac® Circuit Breakers

Page 46: Westinghouse AB DE-ION Current Limiting Circuit Breakerspub/@electrical/... · Application Data 29-167C Page 3 October 1997 AB DE-ION Current Limit-R® Circuit Breakers Type FCL,

Application Data29-167C

Page 46

October 1997

Type NB, 800 Amperes, 2 and 3 Poles

Curve No. SC-3598-76B

1000

800

600

900

700

500

400

300

200

Adjustable Instantaneous Trip Amperes3000-6000

Symmetrical RMS Amperes240 Volts200,000

480 Volts200,000

600 Volts200,000

Instantaneous TripRating in Amperes800

Interrupting Rating (UL Listed)BreakerFrame

NB Tri-Pac

Maximum

Minimum

LO HI

Limiter 800 NBP20

Maximum Single PoleTrip Times at 25°C ➀

Circuit Breaker Time/Current Curves

Tri-Pac Circuit Breakers

Catalog Type NB Circuit Breakers, 800 Amperes, 2 and 3 Poles,600 Volts Ac Max.

Application and coordination curves based on 40°C ambientcold start, connected with four (4) feet of 75°C rated wiresize and tested in open air with current in all poles.

For single pole tests use dummy fuses or bypass the Tri-Pacfuses; otherwise, results may not agree with curve.

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

TIME IN

SECONDS

1,000

500

300

200

5,000

3,000

2,000

1 HOUR1 M

INUTE

2 HOURS

TIM

E IN

SEC

ONDS

10,000

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

1,000

500

300

200

5,000

3,000

2,000

1 HO

UR1

MIN

UTE

2 HO

URS

CURRENT IN AMPERES

CURRENT IN AMPERES

10,000

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

100

8060 9070504030201086 975

1 CYCLE

1 CY

CLE

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

100080

0

600

900

700

500

400

300

200

1008060 907050

100,

000

80,0

00

60,0

00

90,0

00

70,0

00

50,0

00

40,0

00

30,0

00

20,0

004030201086 975

AB DE-ION Tri-Pac® Circuit Breakers

Page 47: Westinghouse AB DE-ION Current Limiting Circuit Breakerspub/@electrical/... · Application Data 29-167C Page 3 October 1997 AB DE-ION Current Limit-R® Circuit Breakers Type FCL,

Application Data29-167C

Page 47

October 1997

Type PB, 600 Amperes, 2 and 3 Poles

Curve No. SC-3599-76B

1000

800

600

900

700

500

400

300

200

Adjustable Instantaneous Trip Amperes1500-5000

Symmetrical RMS Amperes240 Volts200,000

480 Volts200,000

600 Volts200,000

Instantaneous TripRating in Amperes600

Interrupting Rating (UL Listed)BreakerFrame

PB Tri-Pac

Maximum

Minimum

LO HI

Limiter 1000 PBPR20

Limiter 1600 PBPR30

Maximum Single PoleTrip Times at 25°C ➀

Circuit Breaker Time/Current Curves

Tri-Pac Circuit Breakers

Catalog Type PB Circuit Breakers, 600 Amperes, 2 and 3 Poles,600 Volts Ac Max.

Application and coordination curves based on 40°C ambientcold start, connected with four (4) feet of 75°C rated wiresize and tested in open air with current in all poles.

For single pole tests use dummy fuses or bypass the Tri-Pacfuses; otherwise, results may not agree with curve.

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

TIME IN

SECONDS

1,000

500

300

200

5,000

3,000

2,000

1 HOUR1 M

INUTE

2 HOURS

TIM

E IN

SEC

ONDS

10,000

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

1,000

500

300

200

5,000

3,000

2,000

1 HO

UR1

MIN

UTE

2 HO

URS

CURRENT IN AMPERES

CURRENT IN AMPERES

10,000

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

100

8060 9070504030201086 975

1 CYCLE

1 CY

CLE

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

100080

0

600

900

700

500

400

300

200

1008060 907050

100,

000

80,0

00

60,0

00

90,0

00

70,0

00

50,0

00

40,0

00

30,0

00

20,0

004030201086 975

AB DE-ION Tri Pac® Circuit Breakers

Page 48: Westinghouse AB DE-ION Current Limiting Circuit Breakerspub/@electrical/... · Application Data 29-167C Page 3 October 1997 AB DE-ION Current Limit-R® Circuit Breakers Type FCL,

Application Data29-167C

Page 48

October 1997

Type PB, 800 Amperes, 2 and 3 Poles

Curve No. SC-3600-76B

1000

800

600

900

700

500

400

300

200

Adjustable Instantaneous Trip Amperes1500-5000

Symmetrical RMS Amperes240 Volts200,000

480 Volts200,000

600 Volts200,000

Instantaneous TripRating in Amperes800

Interrupting Rating (UL Listed)BreakerFrame

PB Tri-Pac

Maximum

Minimum

LO HI

Limiter 1000 PBPR20

Limiter 1600 PBPR30

Maximum Single PoleTrip Times at 25°C ➀

Circuit Breaker Time/Current Curves

Tri-Pac Circuit Breakers

Catalog Type PB Circuit Breakers, 800 Amperes, 2 and 3 Poles,600 Volts Ac Max.

Application and coordination curves based on 40°C ambientcold start, connected with four (4) feet of 75°C rated wiresize and tested in open air with current in all poles.

For single pole tests use dummy fuses or bypass the Tri-Pacfuses; otherwise, results may not agree with curve.

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

TIME IN

SECONDS

1,000

500

300

200

5,000

3,000

2,000

1 HOUR1 M

INUTE

2 HOURS

TIM

E IN

SEC

ONDS

10,000

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

1,000

500

300

200

5,000

3,000

2,000

1 HO

UR1

MIN

UTE

2 HO

URS

CURRENT IN AMPERES

CURRENT IN AMPERES

10,000

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

100

8060 9070504030201086 975

1 CYCLE

1 CY

CLE

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

100080

0

600

900

700

500

400

300

200

1008060 907050

100,

000

80,0

00

60,0

00

90,0

00

70,0

00

50,0

00

40,0

00

30,0

00

20,0

004030201086 975

AB DE-ION Tri-Pac® Circuit Breakers

Page 49: Westinghouse AB DE-ION Current Limiting Circuit Breakerspub/@electrical/... · Application Data 29-167C Page 3 October 1997 AB DE-ION Current Limit-R® Circuit Breakers Type FCL,

Application Data29-167C

Page 49

October 1997

Type PB, 1000 Amperes, 2 and 3 Poles

Curve No. SC-3601-76B

1000

800

600

900

700

500

400

300

200

Adjustable Instantaneous Trip Amperes1500-5000

Symmetrical RMS Amperes240 Volts200,000

480 Volts200,000

600 Volts200,000

Instantaneous TripRating in Amperes1000

Interrupting Rating (UL Listed)BreakerFrame

PB Tri-Pac

Maximum

Minimum

LO HI

Limiter 1000 PBPR20

Limiter 1600 PBPR30

Maximum Single PoleTrip Times at 25°C ➀

Circuit Breaker Time/Current Curves

Tri-Pac Circuit Breakers

Catalog Type PB Circuit Breakers, 1000 Amperes, 2 and 3 Poles,600 Volts Ac Max.

Application and coordination curves based on 40°C ambientcold start, connected with four (4) feet of 75°C rated wiresize and tested in open air with current in all poles.

For single pole tests use dummy fuses or bypass the Tri-Pacfuses; otherwise, results may not agree with curve.

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

TIME IN

SECONDS

1,000

500

300

200

5,000

3,000

2,000

1 HOUR1 M

INUTE

2 HOURS

TIM

E IN

SEC

ONDS

10,000

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

1,000

500

300

200

5,000

3,000

2,000

1 HO

UR1

MIN

UTE

2 HO

URS

CURRENT IN AMPERES

CURRENT IN AMPERES

10,000

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

100

8060 9070504030201086 975

1 CYCLE

1 CY

CLE

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

100080

0

600

900

700

500

400

300

200

1008060 907050

100,

000

80,0

00

60,0

00

90,0

00

70,0

00

50,0

00

40,0

00

30,0

00

20,0

004030201086 975

AB DE-ION Tri Pac® Circuit Breakers

Page 50: Westinghouse AB DE-ION Current Limiting Circuit Breakerspub/@electrical/... · Application Data 29-167C Page 3 October 1997 AB DE-ION Current Limit-R® Circuit Breakers Type FCL,

Application Data29-167C

Page 50

October 1997

Type PB, 1200 Amperes, 2 and 3 Poles

Curve No. SC-3602-76B

1000

800

600

900

700

500

400

300

200

Adjustable Instantaneous Trip Amperes2000-6000

Symmetrical RMS Amperes240 Volts200,000

480 Volts200,000

600 Volts200,000

Instantaneous TripRating in Amperes1200

Interrupting Rating (UL Listed)BreakerFrame

PB Tri-Pac

Maximum

Minimum

LO HI

Limiter 1600 PBPR30

Maximum Single PoleTrip Times at 25°C ➀

Circuit Breaker Time/Current Curves

Tri-Pac Circuit Breakers

Catalog Type PB Circuit Breakers, 1200 Amperes, 2 and 3 Poles,600 Volts Ac Max.

Application and coordination curves based on 40°C ambientcold start, connected with four (4) feet of 75°C rated wiresize and tested in open air with current in all poles.

For single pole tests use dummy fuses or bypass the Tri-Pacfuses; otherwise, results may not agree with curve.

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

TIME IN

SECONDS

1,000

500

300

200

5,000

3,000

2,000

1 HOUR1 M

INUTE

2 HOURS

TIM

E IN

SEC

ONDS

10,000

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

1,000

500

300

200

5,000

3,000

2,000

1 HO

UR1

MIN

UTE

2 HO

URS

CURRENT IN AMPERES

CURRENT IN AMPERES

10,000

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

100

8060 9070504030201086 975

1 CYCLE

1 CY

CLE

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

100080

0

600

900

700

500

400

300

200

1008060 907050

100,

000

80,0

00

60,0

00

90,0

00

70,0

00

50,0

00

40,0

00

30,0

00

20,0

004030201086 975

AB DE-ION Tri-Pac® Circuit Breakers

Page 51: Westinghouse AB DE-ION Current Limiting Circuit Breakerspub/@electrical/... · Application Data 29-167C Page 3 October 1997 AB DE-ION Current Limit-R® Circuit Breakers Type FCL,

Application Data29-167C

Page 51

October 1997

Type PB, 1400 Amperes, 2 and 3 Poles

Curve No. SC-3603-76B

1000

800

600

900

700

500

400

300

200

Adjustable Instantaneous Trip Amperes2500-7000

Symmetrical RMS Amperes240 Volts200,000

480 Volts200,000

600 Volts200,000

Instantaneous TripRating in Amperes1400

Interrupting Rating (UL Listed)BreakerFrame

PB Tri-Pac

Maximum

Minimum

LO HI

Limiter 1600 PBPR30

Maximum Single PoleTrip Times at 25°C ➀

Circuit Breaker Time/Current Curves

Tri-Pac Circuit Breakers

Catalog Type PB Circuit Breakers, 1400 Amperes, 2 and 3 Poles,600 Volts Ac Max.

Application and coordination curves based on 40°C ambientcold start, connected with four (4) feet of 75°C rated wiresize and tested in open air with current in all poles.

For single pole tests use dummy fuses or bypass the Tri-Pacfuses; otherwise, results may not agree with curve.

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

TIME IN

SECONDS

1,000

500

300

200

5,000

3,000

2,000

1 HOUR1 M

INUTE

2 HOURS

TIM

E IN

SEC

ONDS

10,000

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

1,000

500

300

200

5,000

3,000

2,000

1 HO

UR1

MIN

UTE

2 HO

URS

CURRENT IN AMPERES

CURRENT IN AMPERES

10,000

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

100

8060 9070504030201086 975

1 CYCLE

1 CY

CLE

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

100080

0

600

900

700

500

400

300

200

1008060 907050

100,

000

80,0

00

60,0

00

90,0

00

70,0

00

50,0

00

40,0

00

30,0

00

20,0

004030201086 975

AB DE-ION Tri Pac® Circuit Breakers

Page 52: Westinghouse AB DE-ION Current Limiting Circuit Breakerspub/@electrical/... · Application Data 29-167C Page 3 October 1997 AB DE-ION Current Limit-R® Circuit Breakers Type FCL,

Application Data29-167C

Page 52

October 1997

Type PB, 1600 Amperes, 2 and 3 Poles

Curve No. SC-3604-76B

1000

800

600

900

700

500

400

300

200

Adjustable Instantaneous Trip Amperes3000-8000

Symmetrical RMS Amperes240 Volts200,000

480 Volts200,000

600 Volts200,000

Instantaneous TripRating in Amperes1600

Interrupting Rating (UL Listed)BreakerFrame

PB Tri-Pac

Maximum

LO HI

Limiter 1600 PBPR30

Minimum

Maximum Single PoleTrip Times at 25°C ➀

Circuit Breaker Time/Current Curves

Tri-Pac Circuit Breakers

Catalog Type PB Circuit Breakers, 1600 Amperes, 2 and 3 Poles,600 Volts Ac Max.

Application and coordination curves based on 40°C ambientcold start, connected with four (4) feet of 75°C rated wiresize and tested in open air with current in all poles.

For single pole tests use dummy fuses or bypass the Tri-Pacfuses; otherwise, results may not agree with curve.

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

TIME IN

SECONDS

1,000

500

300

200

5,000

3,000

2,000

1 HOUR1 M

INUTE

2 HOURS

TIM

E IN

SEC

ONDS

10,000

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

1,000

500

300

200

5,000

3,000

2,000

1 HO

UR1

MIN

UTE

2 HO

URS

CURRENT IN AMPERES

CURRENT IN AMPERES

10,000

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

100

8060 9070504030201086 975

1 CYCLE

1 CY

CLE

10,0

00

8000

6000

9000

7000

5000

4000

3000

2000

100080

0

600

900

700

500

400

300

200

1008060 907050

100,

000

80,0

00

60,0

00

90,0

00

70,0

00

50,0

00

40,0

00

30,0

00

20,0

004030201086 975

AB DE-ION Tri-Pac® Circuit Breakers