Westfalia Control Unit C7-623

download Westfalia Control Unit C7-623

of 148

description

westfalia separator control unit

Transcript of Westfalia Control Unit C7-623

  • 8164-9001-400

    1198

    Control Unit

    C7-623

    WMS01

    Program0

    Program1

    L-Test SMS36

    SMS96

    7 8 9

    4 5 6

    1 2 3

    . 0

    ESCINSDEL

    DIR

    HARDCOPY

    SHIFT

    HELP ENTER

    SFBAF FRCE

    DC5VSTOPRUN

    D E F

    A B C

    SIMATIC C7-623

    ACK

    DOWN ALARMS

    SERIES

    1 2

    CHECK

    Sep. FEED SLUDG

    E

    PARTIAL HEATERRELEASE

    UP

  • III

    8164-9001-400 / 1198

    Subject to modification!

  • IV

    8164-9001-400 / 1198

    For your safety

    Strictly adhere to instructions marked with this symbol.This avoids damage to the separator and other units.

    Take special care when carrying out operations marked withthis symbol -otherwise danger to life.

    Observe accident prevention regulations.The local safety and accident prevention regulations apply uncondi-tionally to the operation of the separator.

    When operating electrical apparatus, certain parts carrydangerously high voltage.Non-compliance with the protective measures can therefore result inserious injury or damage.For this reason, only suitably qualified specialists are allowed to workon the units.Protective measures should be taken in line with national and local reg-ulations.

    Instruction manualsFollow the instructions given in this manual and the separator manual.Proper and safe operation is conditional on appropriate transport andstorage conditions, correct operation and assembly as well as carefuloperation and maintenance.

    Operate the separator only in accordance with agreed pro-cess and operating parameters.

    Maintain the separator as specified -in the separator manual.

    Carry out safety checks on the separator -as described in chapter Safety in the separator manual.

  • V

    8164-9001-400 / 1198

    Liability for the function of the unit passes to the owner.Liability for the function of the unit passes unconditionally to the owneror operator irrespective of existing warranty periods in so far as the unitis improperly maintained or serviced by persons other than WestfaliaSeparator service personnel or if the machine is not applied in accor-dance with the intended use.Westfalia Separator AG shall not be liable for damage which occurs asa result of non-compliance with the above. Warranty and liability condi-tions in the Conditions of Sale and Delivery of Westfalia Separator AGare not extended by the above.

  • VI

    8164-9001-400 / 1198

    ForewordThis instruction manual is primarily intended for persons assigned the taskof operating and maintaining the control unit. To assure safe operation it istherefore imperative that the manual is indeed handed over to these per-sons.

    In the event of any queries please state the model designation and the se-rial number (see nameplate inside the control unit).When ordering spare parts, it aids the rapid and correct processing of yourorder if you also state the circuit diagram number specified.

    Typenschild / Name plate

  • VII

    8164-9001-400 / 1198

    1 General description 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.1 Application 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.2 Equipment 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.3 Control cabinet 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.4 General layout plan 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    2 Control system 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2.1 Design 9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2.2 Classification specifications 9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2.3 Special designs 10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2.4 Assembly 10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2.4.1 Control unit 10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2.4.2 Electrical connection 11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2.4.3 Fuse terminals 11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2.5 Installing the control unit in the control cabinet 12. . . . . . . . . . . . . . . . . 2.5.1 Loosening the fixing bracket 15. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    3 Control unit 17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3.1 Technical specifications 18. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3.2 Getting acquainted with the operating elements 19. . . . . . . . . . . . . . . . 3.2.1 Function keys 20. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3.2.2 Softkeys 22. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3.2.3 System keyboard 23. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3.3 Overview of display pages 25. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3.4 Selecting operating modes 26. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3.4.1 Calling up the system function menu 26. . . . . . . . . . . . . . . . . . . . . . . . . . 3.4.2 Calling up the system function menu 27. . . . . . . . . . . . . . . . . . . . . . . . . . 3.4.3 Exiting the system function menu 28. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3.5 Password protection 29. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3.5.1 Entering the password 29. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3.6 The start screen 30. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3.7 Interfaces 31. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    4 Operation 33. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.1 Switching on the control unit 34. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.2 Start screen 35. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.3 Calling up separator data 36. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.4 Calling up the process text page 38. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.5 Calling up the separator data page 41. . . . . . . . . . . . . . . . . . . . . . . . . . . 4.6 Calling up system times 44. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.6.1 Determining the separating time 46. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.7 Timer overview 48. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.8 Calling up the timer table 50. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.9 Calling up digital inputs 51. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.10 Calling up digital outputs 52. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.11 Calling up analog inputs 53. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.12 Calling up analog outputs 53. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.13 Calling up service addresses 54. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.14 Calling up operator times 56. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.15 Calling up the system settings 57. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.16 Loading a new program 60. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.16.1 The UD 700 60. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.16.2 Loading data from the UD 700 to the C7-623 61. . . . . . . . . . . . . . . . . .

  • VIII

    8164-9001-400 / 1198

    4.16.3 Text transfer OP-part 64. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.16.4 Loading configured data from the programming device into

    the UD 700 66. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    5 Programs and settings 71. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.1 Separator-specific operating modes 72. . . . . . . . . . . . . . . . . . . . . . . . . . 5.1.1 OSA-/OSB separators with VARIZONE system 72. . . . . . . . . . . . . . . . . 5.1.2 OSA-/OSB separators with UNITROL system WMS function 73. . . 5.1.3 OSA-/OSB separators with UNITROL system SMS function

    for HFO 74. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.1.4 OSC separators in -02- design 76. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.1.5 OSC separators with UNITROL system WMS system 79. . . . . . . . . 5.1.6 OSC separators with UNITROL system SMS function 82. . . . . . . . . 5.1.7 OSC separators with UNITROL system SMS function for

    lube oil treatment 85. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.2 Setting the counters 89. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.2.1 Flush ejection (counter 1) 89. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.2.2 Partial ejections (counter 2) 89. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.3 Entering freely assignable times 90. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    6 Error messages / maintenance 91. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6.1 Error messages 92. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6.1.1 Status and error indicators 92. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6.2 Alarm descriptions 93. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6.2.1 Separator motor protection (input 0.1) 93. . . . . . . . . . . . . . . . . . . . . . . . . 6.2.2 PSL Clean oil discharge (input 0.2) 95. . . . . . . . . . . . . . . . . . . . . . . . . . . 6.2.3 PSH Clean oil discharge (input 0.3) (special design) 97. . . . . . . . . . . . 6.2.4 FSH water discharge (input 0.4) (special design) 99. . . . . . . . . . . . . . . 6.2.5 LSHH Sludge tank (input 0.7) 100. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6.2.6 Fault feed pump (input 1.1) (optional) 102. . . . . . . . . . . . . . . . . . . . . . . . . 6.2.7 Fault sludge pump (input 1.3) (optional) 103. . . . . . . . . . . . . . . . . . . . . . . 6.2.8 Vibration monitoring stage 1 (input 1.6) (additional equipment) 105. . . 6.2.9 Vibration monitoring stage 2 (input 1.7) (additional equipment) 107. . . 6.2.10 SMS System errors (input 0.6) 109. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6.2.11 SMS Minimum separating time not exceeded (Input 0.6) 111. . . . . . . 6.2.12 HFO series operation: Selection errors 113. . . . . . . . . . . . . . . . . . . . . . . . 6.2.13 Ejection monitoring (analog output 0.0) 115. . . . . . . . . . . . . . . . . . . . . . . . 6.2.14 Temperature monitoring (analog output 0.2) 119. . . . . . . . . . . . . . . . . . . 6.3 Causes and action 124. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6.3.1 Separator monitoring systems 124. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6.3.2 Separator optional auxiliaries 126. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6.3.3 Separator 128. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6.3.4 Control unit C7-623 129. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6.4 Maintenance 131. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6.4.1 Storing batteries 131. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6.4.2 Changing the battery 131. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    7 Appendix 135. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

  • 1 General description

    1

    8164-9001-400 / 1198

    1.1 Application 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.2 Equipment 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.3 Control cabinet 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.4 General layout plan 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

  • 2

    8164-9001-400 / 1198

    The C7-623 control unit is used for the automatic ejection control and conditionmonitoring of mineral oil separators of the series OSA OSB OSCWith the electronic C7-623/A control unit total ejections of the centrifuge bowl, withor without previous displacement of the product, are triggered at preset intervals.The following ejection modes can be selected on the OSC separators: partial ejections total ejections preselectable partial ejections followed by total ejectionWith the time-dependent program cycle it is important in respect of high clarifyingefficiency and avoiding desludging losses that the separable solids content in theproduct does not fluctuate widely.The centrifuges with UNITROL system are provided with two basic monitoring sys-tems: Water content monitoring system - WMS Sludge space monitoring system - SMSSeries operation is also available for two-stage HFO treatment.Software assignment to the specific separator is carried out in the factory using apassword function.Detailed information on the special functions is given in the respective chapters ofthis manual.The illuminated four-line LC display provides information about the operating andmalfunction condition of the separator and, depending on the programming, dis-plays relevant process data.

    The control system comprises, in addition to the control cabinet, all complete linefittings incorporating electrical components which are controlled or monitored bythe control unit.These include: the dirty oil connection, the water connection, the operating water connection, additionally on UNITROL centrifuges:

    - the circuit and water discharge valve- the water sensor- and/or the pressure switch for the bypass line in SMS function.

    Optional extras: multi-purpose thermometer PT 100 for minimum / maximum monitoring in the

    dirty oil level switch for monitoring the water discharge process-dependent control of an external feed pump level switch for monitoring the sludge tank minimum and maximum level switch for controlling a sludge pump klaxon for audible alarmThe standard C7-623 control unit is designed for single operation of purifiers or clar-ifiers.If required, series operating mode can be pre-selected for two-stage HFO opera-tion after entering a password. The MPI interfaces (Multi Point Interface) must becabled accordingly (cf. chapter 6.2.12 page 113 ff.).

    1.1 Application

    1.2 Equipment

  • 3

    8164-9001-400 / 1198

    Fig. 2

    The C7-623 control unit is built into the door of the control cabinet ready for connec-tion.

    An order-specific drawing is in the appendix to this manual.

    1.3 Control cabinet

  • 4

    8164-9001-400 / 1198

    1.4 General layout plan

    Fig. 3

    9

    1

    8

    14111310

    127

    32

    A

    C6

    5

    4B

    D

    A WaterB Compressed airC Dirty oil feedD Clean oil discharge

    1 Control unit C7-623 and motor control for centrifugeMotor control feed pump

    Motor control sludge pump 2 Water pressure reducer

    3 Feed assembly with solenoid valve forfilling, displacement and operating water

    4 Compressed air control unit 5 Pneumatic 3/2-way valve with

    manual adjustment and solenoid valve for control air(fitted in the dirty oil line of the separator)

    6 PT 100 oil feed min./max. temperature monitoring 7 Pressure switch (for monitoring the clean oil discharge)8 Connections for electrical power supply 9 Klaxon

    10 Water discharge valve11 Circuit valve12 Pressure switch - sludge space monitoring13 Water sensor14 Terminal box (fitted to separator)

    On special order only.

  • 2 Control system

    5Westfalia Separator AG

    8164-9001-400 / 1198

    2.1 Design 9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2.2 Classification specifications 9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2.3 Special designs 10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2.4 Assembly 10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2.4.1 Control unit 10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2.4.2 Electrical connection 11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2.4.3 Fuse terminals 11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2.5 Installing the control unit in the control cabinet 12. . . . . . . . . . . . . . . . . 2.5.1 Loosening the fixing bracket 15. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

  • 6

    8164-9001-400 / 1198

    Fig. 4 - Front view of the C7-623 control unit

    1

    2

    3

    1 Electronic control unit C7-623/A

    2 Main switch

    3 Lock

  • 7

    8164-9001-400 / 1198

    Fig. 5 - Inside view of the C7-623 control unit

    1

    2

    3

    45678

    1 Power supply module2 Electronic control unit C7-623/A3 Main switch4 Measuring transducer 0-1 A / 4-20 mA5 Terminal strip6 Interface relay/collective alarm7 Circuit breaker8 Connecting terminals for lead

  • 8

    8164-9001-400 / 1198

    Fig. 6 - Rear view of the C7-623/A control unit - input/output definitions

  • 9

    8164-9001-400 / 1198

    The electronic control unit C7-623/A is installed in the front door.The foil-protected keyboard allows IP 65 protection.The control unit incorporates an illuminated LC display with 4 x 20 characters andcursor control.The display is equipped with continuous background illumination. The contrast ofthe LC display can be altered with the keyboard.

    ...

    + ... The contrast is adjusted by pressing the shift key and the +/- key.

    As the control units can be installed at various heights, it is advisable to adjust theLC display for optimum readability during commissioning.The main switch and the keyboard foil with the function keys and input/output defini-tions are mounted below the electronic unit.Installed on the mounting plate inside the control unit, above terminal strip X1 forconnection of all external lines, are the following devices: 24 VDC power supply unit Current measuring transducer for ejection monitoring and current indication Two-pole safety cut-out for the connected nominal voltage Measuring relay for water discharge in UNITROL operating mode Temperature/measuring transducer for product monitoringCable entry is from below through cable glands.The control unit is assembled ready for operation and is wired ready to hook up.

    The C7-623/A control unit complies with the VDE regulations (IEC) and has beengranted acceptance certificates by the following classification societies: Germanischer Lloyd (certificate No. 10050-98HH) Lloyds Register of Shipping (certificate No. 98/20058) Det Norske Veritas (certificate No. ...) American Bureau of Shipping (certificate No. 97-MU33558-X-A1) Bureau Veritas (certificate No. ...)

    2.1 Design

    SHIFT

    +/-

    2.2 Classification specifi-cations

  • 10

    8164-9001-400 / 1198

    Special versions differing from the one described in this manual are available: The electronic C7-623/A control unit can be integrated in a compact control cabi-

    net with separator motor controls, oil and water heater controls, vibration moni-toring system, pump controls etc. or in a central control room.

    For centrifuges installed in explosion-hazarded areas, operation can be carriedout by means of an explosion-proof control panel mounted in the vicinity of thecentrifuge. The control unit is then installed in a room outside the danger area.The supervisory equipment on the centrifuge such as pressure switch, flow de-tector and temperature switch is then connected to intrinsically safe EEx(i) cir-cuits.

    In accordance with US regulations, the C7-623/A control unit can be operatedaccording to FM in explosion-hazarded zones.

    Fig.7

    1 Gasket 10.5x23x5(Part-No. 0007-2278-750)

    2 Threaded bolt M 8(let into wall)

    3 Washer4 Rear panel of control unit5 Washer6 Wall

    The control unit must be fitted either to a wall (pillar) or a frame in the vicinity ofthe centrifuge.

    If possible, the installation site for land-based installations must be chosen sothat the sun cannot shine on the front panel impairing the readability of the dis-play. Heating of the electronic control unit by solar radiation must also beavoided.

    When mounting the control unit on a wall, a clearance of about 20 mm shouldbe maintained. The fixing dimensions are given in the dimensioned drawing inthe appendix.

    The fixing holes at the rear of the control unit must be sealed by means of thegaskets supplied.In case of shipboard installations, the unit should be mounted in a low-vibrationarrangement and must not be within the vicinity of hot pipelines.

    Although the electronic control unit is protected against moisture by the protec-tive foil and door seal, the cabinet must not, however, be installed in an exces-sively humid environment or damp area.

    In order to maintain a constant temperature inside the control unit, the mainswitch should be left on when the centrifuge is at a standstill.

    If the centrifuge is installed in an explosion-hazarded area, the control unit mustbe located outside the hazardous area.

    2.3 Special designs

    2.4 Assembly

    2.4.1 Control unit

  • 11

    8164-9001-400 / 1198

    The control unit is rated for a connection voltage of 220 VAC. It is also available fora 110 VAC connection voltage. When a motor starter is integrated, the operatingconnection voltage is stepped down correspondingly.

    Before operating the control unit, check the rated or connected voltage indicatedon the red rating plate inside the cabinet.Make sure that the solenoid valves for operating water and control air are rated for24 VDC.

    The electrical feed to the control unit must be protected by a 10 A slow-blow fuseor the rated currents of the motor starters must be adjusted in accordance with thedata in the circuit diagram.External voltagesThe potential-free contacts of the output modules carry external voltage (evenwhen the main switch is off!). They can be identified by the orange coloured wiring.They can be included in circuits with any voltage 250 VAC.For the switching capacity of the contacts: see 3.1A wire cross-section of 1.0 mm2, copper, is adequate for all cables. The arrange-ment of the terminals on terminal strip X1 is shown in the terminal diagram in theappendix.The screwed glands for the electrical cables should be properly tightened andpacked with sealing compound.

    Valve actuation is via fuse terminals with LED indicators.When there is a short-circuit in the valve electric circuit, the fuse in the terminal re-sponds which is indicated by the corresponding red LED. This single fuse arrange-ment guarantees the full functionality of the C7-623/A control unit, as the operatingvoltage 24 VDC is still available. The electronic fuse in the power supply module isnot activated.

    Attention!When the fuse monitoring responds, the function of the separator is limited (valvedoes not work).Eliminate the cause of trouble immediately!Spare fuses 0.5 A - semi-time lag are supplied with the control cabinet.

    2.4.2 Electrical connection

    2.4.3 Fuse terminals

  • 12

    8164-9001-400 / 1198

    The C7-623/A control unit has been prepared for fixed installation in a control panelor cabinet door.

    Housing dimensions 240 mm x 168 mm

    Mounting depth 69 mm

    Control panel cutout 230.5 mm x 158.5 mm

    Fig. 8

    168

    24069

    230,5+0,5

    158,5+0,51

    Proceed as follows: Preferably use a Torx screwdriver, size T10. Make a cutout in the control panel (1) (dimensions 230.5 x 158.5 mm).

    2.5 Installing the controlunit in the control cabi-net

  • 13

    8164-9001-400 / 1198

    Fig. 9

    2

    Insert the enclosed sealing ring behind the front panel (2)(see fig. 9). Insert the control unit into the cutout in the control panel.

    3

    Fig. 10 - Fixing bracket before engaging

    Insert the four fixing brackets (3) (see fig. 10) into the guides provided. Push the fixing brackets in until the spring engages.

  • 14

    8164-9001-400 / 1198

    4

    Fig. 11 - Fixing bracket engaged

    Screw the four fastening screws enclosed with the control unit into the four fixingbrackets enclosed (4) (see fig. 11).

    Tighten the four screws with the Torx screwdriver (torque 0.6 Nm).

  • 15

    8164-9001-400 / 1198

    Proceed as follows when loosening the fixing bracket:

    1

    3

    2

    Fig. 12

    Loosen the screw (1). Lift the fixing bracket (2). Push the fixing bracket out of the guide (3).

    2.5.1 Loosening the fixingbracket

  • 16

    8164-9001-400 / 1198

    NoteNotes

    NotizenAnotaciones

    NotizenNotesNote

  • 3 Control unit

    17

    8164-9001-400 / 1198

    3.1 Technical specifications 18. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3.2 Getting acquainted with the operating elements 19. . . . . . . . . . . . . . . . 3.2.1 Function keys 20. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3.2.2 Softkeys 22. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3.2.3 System keyboard 23. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3.3 Overview of display pages 25. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3.4 Selecting operating modes 26. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3.4.1 Calling up the system function menu 26. . . . . . . . . . . . . . . . . . . . . . . . . . 3.4.2 Calling up the system function menu 27. . . . . . . . . . . . . . . . . . . . . . . . . . 3.4.3 Exiting the system function menu 28. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3.5 Password protection 29. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3.5.1 Entering the password 29. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3.6 The start screen 30. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3.7 Interfaces 31. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

  • 18

    8164-9001-400 / 1198

    Ordering number C7-623/AEWK: P4 623 A000 11 303

    WS-MS-No. 0005-4050-300Dimensions 240 x 168 x 69 mm (H x B x T)Installation/cutout dimensions 230.5 x 158.5+0.5 mmWeight 1 350 gDisplay STN LC display, 4 lines of 20 characters,LED background illumination 5 mm character heightKeyboard Film keypad with metal domes

    44 keys with 26 integrated LEDsInputs 16 digital, 24 VDC, range: 11-30 VDC

    4 analog 4-20 mA / 0-10 VDCOutputs 16 digital, 0.5 A each, max. total current 4 A

    4 analog 4-20 mASerial interface V.24 for printer connectionMPI interface Standard MPI interfaceBuffer battery Buffer time approx. 1 yearFlash memory / configuration memory

    128 KB

    RAM 128 KBConfiguration software Step 7B+B software ProTool / ProTool-LitePower supply 24 VDC, range: 20.4 to 30.2 VDCInput voltage with polarity re-versal protection

    yes

    Current consumption 2.4 A max.Safety standard DIN EN 61131-2/IEC 1131-2Enclosure Unit front: IP 65 as per IEC 529

    Unit housing: IP 20 as per IEC 529Electromagnetic compatibility EN 50081-2 / EN 50082-2Climatic conditionsOperation:

    Tested as per DIN IEC 68-2-1/ 68-2-20 oC to 55 oC, vertical installationO eration:

    Storage:Humidity:

    0 C to 55 C, vertical installation-20 oC to +70 oCTested as per DIN / IEC 68 2 3Humidity: Tested as er DIN / IEC 68-2-3Operation/storage: 5-95% at 25 oC

    Mechanical environmentalconditions

    Vibration: as per DIN IEC 68-2-6Operation: 10-58 Hz, amplitude 0.075 mm,58-500 Hz, acceleration 9.8 m/sStorage: 5-9 Hz, amplitude 3.5 mm, 9-500 Hz, acceleration 9.8 m/sShock: as per DIN IEC 68-2-29 Semi-sinusoidal 100 m/s2 (10 g), 16 ms,100 shocks

    3.1 Technical specifica-tions

  • 19

    8164-9001-400 / 1198

    3.2 Getting acquainted with the operating elements

    WMS01

    Program0

    Program1

    L-Test SMS36

    SMS96

    Fig. 13

    7 8 9

    4 5 6

    1 2 3

    . 0

    ESCINSDEL

    DIR

    HARDCOPY

    SHIFT

    HELP ENTER

    SFBAF FRCE

    DC5VSTOPRUN

    D E F

    A B C

    SIMATIC C7-623

    ACK

    1

    3

    5

    DOWN ALARMS UP

    2SERIES

    1 2

    CHECK

    Sep. FEED SLUDGE PARTIAL HEATERRELEASE

    4

    The operating interface consists of:1 Display2 Softkeys3 Status and fault indicator4 Function keys5 System keys

  • 20

    8164-9001-400 / 1198

    The function keys have a global function: The actions which can be triggered areindependent of the display. They each incorporate an LED which gives informationon the state of the respective function.

    Key Key designation Description

    Program0

    Separation program Off This key closes the feed valve in separating mode andempties the bowl.On the OSC separators two total ejections are triggeredautomatically.Ejections are indicated by the LED.

    Program1

    Separation program ON This key starts the separating program.When the ejection program has run the feed valve isopened.No start is possible if the separating temperature hasdropped below the minimum value.The LED lights up in ejection and separating mode.

    L-TestLamp test This key starts a function test of all key LEDs and any exter-

    nal pilot lamps.The following LEDs are not tested: SF DC5V RUN BAF FRCE STOP.

    WMS01

    Water Content Monitoring System(WMS)

    When commissioning a UNITROL centrifuge, the WMSfunction can be assigned to the centrifuge (-01-) after en-tering a password.The WMS function is visible in the display.For details see chapter 5.1.5, page 79.

    SMS36

    Sludge Monitoring System SMS-HFO When commissioning a UNITROL centrifuge, the SMSfunction can be assigned to the centrifuge (-36-) after en-tering a password.The SMS function is visible in the display.For details see chapter 5.1.6, page 82.

    SMS96

    Sludge Monitoring System SMS-LO When commissioning a UNITROL centrifuge, the SMSfunction can be assigned to the centrifuge (-96-) after en-tering a password.The SMS function is visible in the display.For details see chapter 5.1.7, page 85.

    SERIES1 2

    Series operation When operating HFO separators in series, two control sys-tems can be preselected within the MPI network for thistreatment mode.The SERIES key on each control unit must be activated.

    3.2.1 Function keys

  • 21

    8164-9001-400 / 1198

    Key DescriptionKey designation

    CHECKSystem test WMS or SMS In separating mode repeated pressing of this key will initi-

    ate a check of the water discharge (WMS) or ejection bymeans of SMS, depending on which of the functions hasbeen preselected.

    Sep. Separator status This key has no function.The LED in the key shows the actual status of the separa-tor: Permanent lighting: operation Slow flashing: fault from motor protection Rapid flashing: start-up phase

    FEEDStatus indication feed pump This key has no function.

    The LED in the key shows the actual status of the feedpump: Permanent lighting: operation Slow flashing: fault from motor protection Rapid flashing: pump post-running

    SLUDGEStatus indication sludge pump This key has no function.

    The LED in the key shows the actual status of the sludgepump: Permanent lighting: operation Slow flashing: fault from motor protection Rapid flashing: pump post-running

    PARTIALPreselection partial ejection OSC separators allow partial ejections.

    To do this, preselect the number of partial ejections on co-unter Z1 to be triggered before the total ejection and thenpress the key PARTIAL.

    Process screen This key calls up the process screen from any selected di-splay page (display page 3/1) and shows the current sepa-rating data.

    HEATERRELEASE

    Heater release Pressing this key releases an optional heating systemwhich is then process-dependently controlled.The function is signalled by the LED.Attention:Pay attention to minimum separating temperature!

    Special function This key is programmed specifically for the contract and isdescribed in the appendix.

    Special function This key is programmed specifically for the contract and isdescribed in the appendix.

  • 22

    8164-9001-400 / 1198

    The softkeys have a local function: The actions which can be triggered are depen-dent on the screen currently displayed and are shown by an icon on the screenabove the key.Example of triggering an action in the softkey menu:

    Fig. 14

    MODE: STOP

    MENU

    DOWN UPALARMS

    Press the UP key to execute the Menu function.

    The functionality of the individual softkeys is described in the corresponding dis-plays.

    Softkey DOWNThis key is normally used in the display to access the previous level.Other functions are picture-dependent and are shown in the display.

    Softkey ALARMSPicture-dependent function key as per display.On the process page (display page 3/1) you can use this key to callup the alarm message buffer.

    Picture-dependent function key as per display.

    Softkey UPThis key is normally used in the display to access the next level.Other functions are picture-dependent and are shown in the display.

    3.2.2 Softkeys

    UP

    DOWN

    ALARMS

    UP

  • 23

    8164-9001-400 / 1198

    Fig. 15

    7 8 9

    4 5 6

    1 2 3

    . 0

    ESCINSDEL

    DIR

    HARDCOPY

    SHIFT

    HELP ENTER

    D E F

    A B C

    ACK

    Note:Pressing several keys at the sametime may lead to incorrect entries.

    Moves cursor to the left

    Moves cursor to the right

    Moves cursor upwards

    Moves cursor downwards

    Note:The cursor keys have a repeat function: When the key is depressedthe entry is repeated after a short delay until the key is released.

    3.2.3 System keyboard

  • 24

    8164-9001-400 / 1198

    Numeric ....

    ...

    .... key block for inputting valuesWhen the SHIFT key is pressed you can enter alphanumeric charac-ters A to F.

    Change-sign keyThis key is used to alternate between the plus and minus sign.

    Shift keyThis key is used to activate the alternate function of double-functionkeys.The LED goes on when the change-over function is activated.

    Cancel key (Escape)This key cancels already started functions, deletes already entered characters for a value input, switches back to previous menu, changes operating levels.

    ConfirmThis key accepts and exits an entry, switches from message level to picture level.

    Acknowledgement keyAcknowledges the currently indicated alarm message or all mes-sages of an acknowledgement group; this does not eliminate thefault.The LED remains on as long as at least one unacknowledged alarmmessage is queued.

    Insert / delete keyThis key is used to enter a blank at the cursor position for alphanu-meric entries. All following characters are shifted to the right by oneposition.When you simultaneously press the SHIFT key, you can delete thecharacter at the cursor position for alphanumeric entries. All followingcharacters are shifted to the left by one position.

    Info keyOpens a help text for the selected object (e. g. message, input field).The LED only goes on when a help text is available for the selectedobject.

    Displays contentsThis key is used to call up the screen directory.

    Print (hardcopy)This key serves to output the content of the current display via a con-nected printer (optional).

    10

    9

    +/-

    SHIFT

    ESC

    ENTER

    ACK

    DELINS

    HELP

    DIR

    HARDCOPY

  • 25

    8164-9001-400 / 1198

    The control functions can be seen in the different display pages. Proceed as followsto view the display pages:

    Press the DIR key to get a display of all configured pages

    or ...

    ... select the desired screen.

    Open the desired screen.

    The following table gives an overview of the available display pages.

    Displaypage

    Main menu Displaypage

    Submenu

    1/1 Start menu 1/2 Program version

    2/1 Separator data 2/2 Pump status

    3/1 Process data total ejection 3/2 Process data partial ejection4/1 4/5 Separator operating data

    5/1 5/19 Timer table

    6/1 6/2 Counter table

    7/1 7/8 Digital inputs

    8/1 8/8 Digital outputs

    9/1 9/4 Analog inputs

    10/1 10/2 Analog outputs

    11/1 - 11/8 Service information

    12/1 12/8 Service information, operating hours

    13/1 Option for special function

    14/1 14/5 User times (setting without password)15/1 15/5 System settings, language, alarms,

    transfer

    Note:The process data on the display page 3/1 can be called up directly from every di-splay page by pressing the Process screen key.

    3.3 Overview of displaypages

    DIR

    ENTER

  • 26

    8164-9001-400 / 1198

    You can call up the system function menu from every operating level. The followingmenus are available in the system function menu: C7-CPU operating mode selection

    - RUN-P- RUN- STOP- MRES

    DI/DO status indication

    ...

    ... Simultaneously press the shift key and the help key.

    Note:The LED in the shift key goes out again when you press the help key.

    The display shows the system function menu:

    Fig. 16

    SYSTEM FUNCTIONS

    KEY DI/DO

    SIMATIC C7

    DOWN UPALARMS

    3.4 Selecting operatingmodes

    3.4.1 Calling up the systemfunction menu

    SHIFT

    HELP

  • 27

    8164-9001-400 / 1198

    Press the DOWN key.

    The display shows the menu C7-CPU operating modes:

    Fig. 17

    MODE: STOP

    RUNP RUN STOP MRES

    DOWN UPALARMS

    Key Operatingmode

    Description

    DOWN RUNP The CPU processes the user program.Using a programming device (PD) programs and datacan be uploaded from the C7-CPU (C7 PG), transferred to the C7-CPU (PG C7).

    ALARMS RUN The CPU processes the user program.Programs and data in the C7-CPU can be uploadedwith the PG/UD 700 (C7 PG/UD).The program and data can neither be loaded nor modi-fied.

    3.4.2 Calling up the systemfunction menu DOWN

  • 28

    8164-9001-400 / 1198

    Key DescriptionOperatingmode

    STOP The C7-CPU does not process a user program.Programs can be uploaded from the C7-CPU with the programming

    device (C7 PG), transferred to the C7-CPU (PG C7).Note:The operating mode STOP is valid only for theC7-CP, not for the C7-OP. Further processing with theC7-OP is possible.

    UP MRES Memory reset:Resetting the C7-CPU requires a special operatingsequence of the modes STOP and MRES. Thisfunction requires specialist knowledge.

    Press the ESC key to exit the system function menu or the menuC7-CPU operating modes.

    3.4.3 Exiting the systemfunction menu

    ESC

  • 29

    8164-9001-400 / 1198

    Certain entries and functions require prior entry of a password.You will be prompted to enter a password if you press a key to which a password-protected function is assigned, write in password-protected input fields.Note:You can obtain the password from Westfalia Separator AG.

    PASSWORD ENTRY

    ...

    ... Enter the password using the numerical keys.For security reasons, the entered digits are displayed as asterisks *.

    Confirm the entry or ...

    ... cancel the entry.

    After you have entered a valid password, you can use the password-protected func-tion for two minutes. After this time your access right is cancelled and the pass-word must be reentered if necessary.

    This symbol is used in the manual to refer to the procedure describedabove, that means:

    Enter the password as described above.Multiple password-protected entries during the 2 minute session do not requireyou to enter the password again.

    3.5 Password protection

    3.5.1 Entering the pass-word

    10

    9

    ENTER

    ESC

  • 30

    8164-9001-400 / 1198

    Fig. 18

    OSC-15/50

    >

    22.10.98 16:30:11

    Westfalia Separator

    1

    2

    3

    5 6

    7

    84 DOWN UPALARMS

    1 Current date2 Preselected separator model3 Company name4 Exit password level (DOWN key)5 Terminate password function (ALARMS key)6 Call up password (key )7 Call up password level (UP key)8 Current time

    3.6 The start screen

  • 31

    8164-9001-400 / 1198

    The plug and socket connectors (interfaces) required for connecting the various in-puts and outputs of the C7 are provided.

    Attention:Use only approved shielded cables for wiring the analog inputs and outputs as wellas the IM, V.24 and MPI interfaces.

    Fig. 19

    o

    u

    l

    r

    6

    2

    4

    5

    1

    78

    3

    1 IM port2 Analog inputs3 Analog outputs4 AUX digital inputs5 Serial interface V.24 (e. g. for printer)6 Digital inputs (top)7 Digital outputs (bottom)8 DI/DO 24 VDC power supply

    l lefto topu bottomr right

    3.7 Interfaces

  • 32

    8164-9001-400 / 1198

    Fig. 20

    1

    1 MPI interface

  • 4 Operation

    33

    8164-9001-400 / 1198

    4.1 Switching on the control unit 34. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.2 Start screen 35. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.3 Calling up separator data 36. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.4 Calling up the process text page 38. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.5 Calling up the separator data page 41. . . . . . . . . . . . . . . . . . . . . . . . . . . 4.6 Calling up system times 44. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.6.1 Determining the separating time 46. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.7 Timer overview 48. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.8 Calling up the timer table 50. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.9 Calling up digital inputs 51. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.10 Calling up digital outputs 52. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.11 Calling up analog inputs 53. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.12 Calling up analog outputs 53. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.13 Calling up service addresses 54. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.14 Calling up operator times 56. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.15 Calling up the system settings 57. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.16 Loading a new program 60. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.16.1 The UD 700 60. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.16.2 Loading data from the UD 700 to the C7-623 61. . . . . . . . . . . . . . . . . . 4.16.3 Text transfer OP-part 64. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.16.4 Loading configured data from the programming device into

    the UD 700 66. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

  • 34

    8164-9001-400 / 1198

    When you switch on the power supply the C7 control unit performs a self-test. Whenthe control unit has started correctly the following message is displayed:

    SIMATIC C7-623 V1.20 4 x 20 Characters 5 mm

    Press ENTER to switch to the start screen:

    22.11.97 16:30:11 OSC-15/10 Westfalia Separator>

    Display page 1/1 (start screen)

    Contrast adjustmentPress the shift key.The LED goes on.

    Press the +/- key to adjust the contrast.

    Press the shift key.The LED goes out.

    Calling up display pagesPress the DIR key to call up the directory.

    ...

    ... navigate to the desired display page using the cursor keys.

    Press ENTER to open the desired display page (overview see page 25).

    4.1 Switching on the con-trol unit

    ENTER

    SHIFT

    +/-

    SHIFT

    DIR

    ENTER

  • 35

    8164-9001-400 / 1198

    When the control unit has started correctly, you enter the start menu (displaypage 1/1):

    22.11.97 16:30:11 OSC-15/10 Westfalia Separator>

    Display page 1/1 (start screen)

    Press the Cursor down key to call up the next submenu:

    MINERAL OIL SYSTEMS Program version 8104-7623-700Version: 10/98 Da

    Display page 1/2 (Program version)

    Always state the current program version when contacting Westfalia Separator forsupport.

    Press the Cursor up key to return to the start menu.

    Press the UP key to access display page 2/1 (Separator data).

    4.2 Start screen

    UP

  • 36

    8164-9001-400 / 1198

    OSC 15/10 ready f. operationOP data: 12A/4800 rpmStarting time: 300 secMode: Single VARIZONE

    Display page 2/1 (separatordata)

    Line Description

    1 Separator modelThe separator model is entered at the factory.The current status of the separator is displayed. Possible states are: Off

    Separator is not switched on. Acceleration

    The separator is in the start-up phase; process start is not possible. Ready f. operation (ready for operation)

    The separator has reached its rated speed; the separating process canbegin.

    SeparationSeparator is in separating mode; the product feed is open or the ejectionprogram is running.

    PTC alarmThe motor protection has responded; power has been cut off to separa-tor and the feed valve closed.

    2 Operating data: Current

    The actual separator current is displayed. The current values are differ-ent in the start-up, ejection and operating cycles.

    Bowl speed (optional)If a proximity switch is retrofitted to the separator, the current bowlspeed is displayed.

    3 Elapsing start-up timeDuring the separator acceleration phase the elapsing start-up time is dis-played in seconds. The separator is ready for operation when the displayshows 0 sec. Preselection is made on timer 10.

    4.3 Calling up separatordata

  • 37

    8164-9001-400 / 1198

    Line Description

    4 Preselected mode (separator operating function)The separator operating mode is set at the factory. The following displaysare possible: Single VARIZONE

    The separator is run in single operation as VARIZONE (-02-). WMS (Water Content Monitoring System)

    The separator is run with activated water content monitoring system(-01-).(Further details are given in the separator manual.)

    SMS-HFO (Sludge Monitoring System)The separator is run with activated sludge space monitoring system(-36-).(Further details are given in the separator manual.)

    SMS-LO (Sludge Monitoring System)The separator is run with activated sludge space monitoring system(-96-).(Further details are given in the separator manual.)

    WMS seriesThe separator is operated as the first stage in series operation with aseparator equipped with SMS. Signal exchange is via the MPI interface.

    SMS seriesThe separator is run as the second stage in series operation with a se-parator equipped with WMS. Signal exchange is via the MPI interface.

    Press the key Cursor down to access the submenu which displaysthe current status of optional feed or sludge pumps.

    Feed pump statusOperationSludge pump statusOff

    Display page 2/2 (pump status)

    Possible displays for feed pump and sludge pump (in line 2 and 4): Off Operation Fault

    Press the Cursor up key to return to display page 2/1.

    Press the UP key to access display page 3/1 (process data totalejection).

    UP

  • 38

    8164-9001-400 / 1198

    Program: Ready f. operationStep: CirculationProduct temp.: 097 CSep. time: 3600 s

    Display page 3/1 (process datatotal ejection)

    Line Description

    1 The current status of the program cycle is displayed. Possible states are: Off

    Program cycle is not activated. Acceleration

    The program cycle is in the start-up phase; process start is not possible. Ready f. operation (ready for operation)

    Program cycle has reached operating speed; the separating processcan begin.

    SeparationSeparator is in process mode; the product feed is open or the ejectionprogram is running.

    PTC alarmThe motor protection has responded; power has been cut off to separa-tor and the feed valve closed.

    2 Depending on the operating status of the separator, the current programcycle (step) is shown in the display.The possible display texts are described below depending on operatingmode: Circulation

    The feed valve is in recirculation mode. The separator is in start-up orfault mode or the process has not been initiated.

    WaitingThe separating process has been initiated.

    DisplacementThe bowl contents are displaced without loss by opening the displace-ment water valve.

    Waiting after displacementThere is a delay time of 5 s after displacement.

    Total ejectionThe bowl sludge space is emptied by actuating the operating watervalve.

    Speed recoveryThe speed drop occurring during ejection is compensated for.

    FillingThe filling process creates the required water seal on the VARIZONEand UNITROL separators in 96 mode.

    Waiting after fillingAfter the filling process there is a delay time of 5 s.

    Feed - openThe separating process is activated.

    4.4 Calling up the processtext page

  • 39

    8164-9001-400 / 1198

    Line Description

    3 Product temperatureThe current product feed temperature is displayed in degrees Celsius.

    4 Separating timeThe elapsing separating time is displayed here in seconds. When a 0reading is displayed, an ejection cycle is triggered automatically.

    In partial ejection mode press the Cursor down key to call up thesubmenu:

    Partial ejection: 4Step: CirculationProduct temp.: 097 CSep. time: 3600 s

    Display page 3/2 (process data partialejection)

    Line Description

    1 Partial ejection counter (only for OSC separators)The number of partial ejections is displayed. When the display shows a0 reading, the next ejection is performed as a total ejection.

    2 Depending on the operating status of the separator, the current programcycle (step) is shown in the display.The possible display texts are described below depending on operatingmode: Circulation

    The feed valve is in recirculation mode. The separator is in start-up orfault mode or the process has not been initiated.

    WaitingThe separating process has been initiated.

    DisplacementThe bowl contents are displaced without loss by opening the displace-ment water valve.

    Waiting after displacementThere is a delay time of 5 s after displacement.

    Total ejectionThe bowl sludge space is emptied by actuating the operating watervalve.

    Speed recoveryThe speed drop occurring during ejection is compensated for.

    FillingThe filling process creates the required water seal on the VARIZONEand UNITROL separators in 96 mode.

    Waiting after fillingAfter the filling process there is a delay time of 5 s.

    Feed - openThe separating process is activated.

    3 Product temperatureThe current product feed temperature is displayed in degrees Celsius.

  • 40

    8164-9001-400 / 1198

    Line Description

    4 Separating timeThe elapsing separating time is displayed here in seconds. When a zeroreading is displayed, an ejection cycle is triggered automatically.

    ...

    ... On the counter display page you can use the numerical keys to pre-select the number of partial ejections until a total ejection within thesetpoint range.

    The counter registers each partial ejection and counts backwards until the valuezero is reached; the desired total ejection is then triggered.The preselected setpoint is then automatically reset.

    Press the Cursor up key to return to display page 3/1.

    Press the UP key to access display page 4/1 (separator operatingdata).

    10

    9

    UP

  • 41

    8164-9001-400 / 1198

    Sep. operating data:OP-h: 14567 hEjections: 1234Starts: 87

    Display page 4/1 (separator operatingdata)

    Line Description

    1 Header for the display page

    2 Operating hoursThe number of separator operating hours is displayed here. This hourcount is the basis for the required service actions (see separator manual).

    3 Number of ejectionsThe number of executed total ejections is shown in this line.

    4 Number of startsThe number of properly completed starts is shown in this line.

    Press the Cursor down key to call up the next submenu:

    WMS/per.: 11WMS/tot.: 123SMS/per.: 0SMS/tot.: 4

    Display page 4/2

    Line Description

    1 Number of WMS responses per separation unitOn UNITROL separators with activated water content monitoring system,the number of water discharges per preset separating time is registered.In the case of manual termination of the separation process, the displayedvalue is reset to zero.

    2 Number of WMS responsesOn UNITROL separators with activated water content monitoring system,the number of water discharges is continuously registered. The value dis-played cannot be reset.

    3 Number of SMS responses per separation unitOn UNITROL separators with activated sludge space monitoring systemthe number of ejections triggered by SMS per preset separating time isregistered. In the case of manual termination of the separation process,the displayed value is reset to zero.

    4 Number of SMS responsesOn UNITROL separators with activated sludge space monitoring systemthe number of ejections triggered by SMS is continuously registered. Thedisplayed value cannot be reset.

    4.5 Calling up the separa-tor data page

  • 42

    8164-9001-400 / 1198

    Press the Cursor down key to call up the next submenu:

    PTC alarms: 3PAL alarms: 5PAH alarms: 2FSH alarms: 5

    Display page 4/3

    Line Description

    1 PTC alarmsThis alarm is registered when the separator is shut down by the PTCthermistors integrated in the windings of the separator motor.

    2 PAL alarmsThis alarm is registered when the separation process is stopped by theminimum pressure switch installed in the clean oil discharge.

    3 PAH alarmsThis alarm is registered when the separation process is stopped by themaximum pressure switch installed in the clean oil discharge.(optional extra)

    4 FSH alarmsThis alarm is registered when the separation process is stopped by themax. level switch installed in the water discharge.(optional extra)

    Press the Cursor down key to call up the next submenu:

    LSHH alarms tank 33TSL alarm: 11TSH alarm: 9ISL eject. monit. 22

    Display page 4/4

    Line Description

    1 LSHH sludge tankThis alarm is registered when the separation process is stopped by thelevel limit switch high/high installed in the sludge tank.

    2 TSL product feed-temperatureThis alarm is registered when the separation process is stopped by thePT 100 temperature feelers (Multi-purpose thermometer) installed in thefeed.

  • 43

    8164-9001-400 / 1198

    Line Description

    3 TSH product feed-temperatureThis alarm is registered when the separation process is stopped by thePT 100 temperature feelers (Multi-purpose thermometer) installed in thefeed.

    4 Ejection monitoringThis alarm is registered when the ejection program is interrupted by re-sponse of the current monitoring device.

    Press the Cursor down key to call up the next submenu:

    Vibration stage 1 0Vibration stage 2 0

    Display page 4/5

    Line Description

    1 Vibration stage 1This alarm is registered when the separation process is stopped by theoptionally installed vibration switch.

    2 Vibration stage 2This alarm is registered when the separator is shut down by the optionallyinstalled vibration switch.

    Press the Cursor up key to scroll back to the previous display stage.

    Press the UP key to access display page 5/1 (timer table).UP

  • 44

    8164-9001-400 / 1198

    All times on display pages 5/1 to 5/19 are adjustable. These display pages arepassword-protected (for password entry see page 29)

    System timesT00: Partial ejectionP: 7200 sA: 4444 s

    Display page 5/1

    P: PresetA: Actual; run from the setpoint to 0

    Enter the password (cf. page 29).

    ...

    ... Enter the desired setpoints behind the preset value P using the nu-meric keyboard.

    Scroll through the timer table below by pressing the Cursor downkey.

    Timer-No. Functions Setpoints Actualvalues

    T00 Partial ejectionT01 Displacement 0 s

    T01 (01)T01 (02)T01 (36)T01 (96)

    Displacement - UNITROL with WMSDisplacement - VARIZONEDisplacement - UNITROL with SMSDisplacement - UNITROL-LO with SMS

    0 s0 s0 s0 s

    T02 (01)T02 (02)T02 (36)T02 (96)

    Filling - UNITROL with WMSFilling - VARIZONEFilling - UNITROL with SMSFilling - UNITROL-LO with SMS

    0 s0 s0 s0 s

    T03 Waiting after start 5 s 0 s

    T04 Total ejectionT05 Speed recovery after total ejectionT06 Closing water pulse

    T07 Alarm delay

    T08 Waiting after displacement

    4.6 Calling up systemtimes

    10

    9

  • 45

    8164-9001-400 / 1198

    Timer-No. Actualvalues

    SetpointsFunctions

    T09 Waiting after filling

    T10 Separator acceleration

    T11 Bridging alarm after ejectionT12 Waiting after first ejection

    (only on OSC separators)T13 Speed recovery after partial ejectionT14 Pause closing water pulse

    T15 Circulation valve closed

    T16 Circulation valve open

    T17 System test WMS/SMS

    T18 LSHH sludge tank

    T19 not assigned

    T20 Separation

    T21 Minimum Separating time with active SMS

    T22 Monitoring time with active SMS

    T23 Post-run feed pump

    T24 Post-run sludge pump

    T25 not assigned

    T26 not assigned

    T27 PSL delay SMS

    T28 Ejection monitoringT29 Forced ejectionT30 not assigned

    T31 not assigned

    T32 not assigned

    The exact setpoints for the corresponding separator are given in the table onpage 48.Attention:Only alter the timers in passive state.In the active state the previously set time will first run down; the time change willonly become effective when next activated.All preset times run down from the entered setpoint to zero and activate the pro-grammed function.

  • 46

    8164-9001-400 / 1198

    Press the Cursor up key to scroll back to the previous display stage.

    Press the UP key to access display page 6/1 (counter function).

    When using time-dependent automatic control programs, accurate setting of theseparation time (time between ejection cycles) is only possible if the throughput ca-pacity and solids loading in the feed remain constant. If this is not the case, it maybe necessary to correct the settings during operation.The separating time depends on the preselected operating mode (partial or total ejection mode), the solids loading in the feed, the consistency of the solids, the effective sludge space volume in the bowl, the separator throughput and the desired bowl cleaning effect.The recommended time settings for the different separator models and their specialfunctions are given in the table in chapter 4.7 on page 48.Given constant conditions, the separating time can be determined by calculationor with the aid of the diagram (see overleaf).

    Example for calculating the separating time:Given: Solids loading p = 0.05%

    Sludge space volume V = 1.5 lSludge space with 75 % utilization V = 1.13 lThroughput capacity Vo = 2 000 l/h

    Wanted: Separating time t = ? min

    The separating time to be adjusted is calculated as follows:

    V 1.13t = 60 100 = 6 000 = 67.8 min = 1.1 h

    V p 2 000 0.05

    UP

    4.6.1 Determining the sep-arating time

  • 47

    8164-9001-400 / 1198

    Example for graphic determination of the separating time

    Fig. 21

    Sludge space V [l]

    Sepa

    rato

    r thr

    ough

    put V

    o [l/h

    ]So

    lids

    load

    ing

    in th

    e fe

    ed p

    [%]

    Running time of separator t [min]

  • 48W

    estfalia Separator AG4.7 Timer overview

    TimerNo Timer function

    Pass-word

    OSC 4/502 01 36 96

    OSC 15/1002 01 36 96

    OSC 30/2502 01 36 96

    OSC 50/4002 01 36 96

    OSA 702 01 36 96

    OSA 2002 01 36 96

    OSB 3502 01 36 96

    No. wordDB 20 DB 21 DB 22 DB 23 DB 24 DB 25 DB 26

    0 Partial ejection 1.5 2 3 3 - - -1 Displacement free 1.5 1 1.5 25 4 4 4 30 10 8 10 40 22 16 18 70 5 3 4 20 7 4 5 40 12 8 9 70

    2 Filling free 1 - - 0.3 3 - - 5 6 - - 15 16 - - 30 3 - - 5 4 - - 20 8 - - 30

    3 Waiting after program start 10 10 10 10 10 10 10

    4 Total ejection 2 2.5 3.5 3.5 10 10 10

    5 Speed recovery after totalejection 25 25 25 25 25 25 25

    6 Closing water pulse 0.08 0.18 0.18 0.18 0.18 0.18 0.18

    7 Alarm delay 20 20 20 20 20 20 20

    8 Waiting after displacement 10 10 10 10 10 10 10

    9 Waiting after filling 10 10 10 10 10 10 10

    10 Separator start-up free 240 240 480 600 360 480 600

    11 Bridging after ejection free 30 30 30 30 30 30 30

    12 Waiting after 1st ejection(OSC models) 10 10 10 10 - - -

    13 Speed recovery after partialejection 10 10 10 10 - - -

    14 Pause closing pulse 600 600 600 600 600 600 600

    15 Circulation valve closed 60 60 60 60 60 60 60

    16 Circulation valve open 15 15 15 15 15 15 15

    17 System check (SMS) 1 1 1 1 1 1 1

  • 49W

    estfalia Separator AG

    TimerNo.

    OSB 3502 01 36 96

    OSA 2002 01 36 96

    OSA 702 01 36 96

    OSC 50/4002 01 36 96

    OSC 30/2502 01 36 96

    OSC 15/1002 01 36 96

    OSC 4/502 01 36 96Pass-

    wordTimer functionTimerNo.

    DB 26DB 25DB 24DB 23DB 22DB 21DB 20

    Pass-wordTimer function

    18 LSHH sludge tank 10 10 10 10 10 10 10

    19 not assigned

    20 Separation free 7200 7200 7200 7200 7200 7200 7200

    21 Minimum separating time(SMS) 600 600 600 600 600 600 600

    22 not assigned

    23 Post-run feed pump 900 900 900 900 900 900 900

    24 Post-run sludge pump 10 10 10 10 10 10 -

    25 Vibro 1 2 2 2 2 2 2 2

    26 Vibro 2 2 2 2 2 2 2 2

    27 PSL delay (SMS) 10 10 10 10 10 10 1028 Ejection monitoring 1.5 2 3 3 5 5 529 not assigned

    30 not assigned

    31 not assigned

  • 50

    8164-9001-400 / 1198

    All times on display pages 6/1 to 6/2 are adjustable.

    Z1: Flush ejection P: 5 A: 2

    Display page 6/1 (counter table, Z1)

    Press the Cursor down key to call up the next submenu:

    Z2: Partial ejection on OSC models P: 5 A: 2

    Display page 6/2 (counter table, Z2)

    The elapsing actual values are behind A....

    ... Enter the desired setpoints behind the preset value P using the nu-meric keyboard.

    Timer-No. Functions Setpoints Actualvalues

    Z1 Number of total ejections to flush ejection 4Z2 Number of partial ejections to total ejec-

    tion(only on OSC separators)

    5

    Z3 vacant

    Z4 vacant

    Z5 vacant

    Z6 vacant

    Z7 vacant

    Z8 vacant

    Z9 vacant

    Press the Cursor up key to scroll back to the previous display page.

    Press the UP key to access display page 7/1 (digital inputs).

    4.8 Calling up the timertable

    10

    9

    UP

  • 51

    8164-9001-400 / 1198

    All digital inputs are shown on display pages 7/1 to 7/4.Scroll through the list below by pressing the Cursor down key.

    Input-No. Functions Terminalstrip

    Status

    DI 0.0 Separator in operation 1X2. 01/02 0

    DI 0.1 Separator malfunction 1X2. 03/04 0

    DI 0.2 PSL clean oil discharge 1X2. 05/06 0

    DI 0.3 PSH clean oil discharge 1X2. 07/08 0

    DI 0.4 FSH water discharge 1X2. 09/10 0

    DI 0.5 WMS - UNITROL 1X2. 11/12 0

    DI 0.6 SMS - UNITROL 1X2. 13/14 0

    DI 0.7 LSHH sludge tank 1X2. 15/16 0

    DI 1.0 Feed pump operation 0

    DI 1.1 Feed pump malfunction 0

    DI 1.2 Sludge pump operation 0

    DI 1.3 Sludge pump malfunction 0

    DI 1.4 LSH sludge tank for pump start 1X2. 27/28 0

    DI 1.5 LSL sludge tank for pump stop 1X2. 29/30 0

    DI 1.6 Vibration stage 1 1X2. 31/32 0

    DI 1.7 Vibration stage 2 1X2. 33/34 0

    Press the Cursor up key to scroll back to the previous display page.

    Press the UP key to access display page 8/1 (digital outputs).

    4.9 Calling up digital in-puts

    UP

  • 52

    8164-9001-400 / 1198

    All digital outputs are shown on display pages 8/1 to 8/4.Scroll through the list below by pressing the Cursor down key.

    Input-No. Functions Terminalstrip

    Status

    DO 0.0 Product valve 1X2. 39/40 0

    DO 0.1 Displacement and filling water valve 1X2. 41/42 0

    DO 0.2 Operating water valve 1X2. 43/44 0

    DO 0.3 Steam valve/heater interlocking(optional)

    1X2. 45/46 0

    DO 0.4 Circulation valve - UNITROL 1X2. 47/48 0

    DO 0.5 Water discharge valve - UNITROL 1X2. 49/50 0

    DO 0.6 Lamp test (optional) 1X2. 51/52 0DO 0.7 Collective alarm 1X2. 53/54 0

    DO 1.0 Separator off 0

    DO 1.1 Feed pump off 0

    DO 1.2 Sludge pump off 0

    DO 1.3 vacant 0

    DO 1.4 vacant 0

    DO 1.5 vacant 0

    DO 1.6 vacant 0

    DO 1.7 vacant 0

    Press the Cursor up key to scroll back to the previous display stage.

    Press the UP key to access display page 9/1 (analog inputs).

    4.10 Calling up digital out-puts

    UP

  • 53

    8164-9001-400 / 1198

    All analog inputs are shown on display pages 9/1 to 9/4.Scroll through the list below by pressing the Cursor down key.

    Input-No. Functions Terminal strip

    AI 0.0 Motor current and ejection monitoring 1U3 6 / 7AI 0.1 Bowl speed (optional)AI 0.2 Product temperature min / max 1X2. 63 / 24W11

    AI 0.3 Vibration (optional) 1X2. 66 / 24W11

    Press the Cursor up key to scroll back to the previous display page.

    Press the UP key to access display page 10/1 (analog outputs).

    All analog outputs are shown on display pages 10/1 to 10/4.Scroll through the list below by pressing the Cursor down key.

    Input-No. Functions Terminal strip

    AO 0.0 vacant

    AO 0.1 vacant

    AO 0.2 vacant

    AO 0.3 vacant

    Press the Cursor up key to scroll back to the previous display page.

    Press the UP key to access display page 11/1 (Service ad-dresses).

    4.11 Calling up analog in-puts

    UP

    4.12 Calling up analog out-puts

    UP

  • 54

    8164-9001-400 / 1198

    The operating hours of the separator are shown on display page 11/1; the serviceaddresses with phone and fax numbers are shown on display pages 11/2 to 11/8.Further service information as well as spare parts orders are available in the MarineAfter-Sales Service Center, Hamburg on:Tel.: ++49 (0) 73 91 56Fax: ++49 (0) - 73 80 585

    ServiceSeparator operating hoursTotal-h: 123Interv.-h: 0

    Display page 11/1

    Line Description

    3 Registration of the operating hours as a function of the release contact ofthe motor starter via input 0.0.

    4 If the unit has to be exchanged for maintenance reasons the operatinghours of the separator can be transferred to the replacement unit; thisfunction is password-protected. (For password entry see page 29.)

    Press the Cursor down key to call up the next submenu:

    Marine After-Sales Service Center Hamburg: ++49 (0) 40 739156

    Display page 11/2

    Press the Cursor down key to call up the next submenu:

    Great Britain:Tel: ++4401908-313366Fax: ++4401908-221556

    Display page 11/3

    Press the Cursor down key to call up the next submenu:

    Netherlands:Tel: ++31 485 395911Fax: ++31 485 322211

    Display page 11/4

    4.13 Calling up service ad-dresses

  • 55

    8164-9001-400 / 1198

    Press the Cursor down key to call up the next submenu:

    Norway:Tel: ++47 22 183044Fax: ++47 22 182323

    Display page 11/5

    Press the Cursor down key to call up the next submenu:

    Singapore:Tel: ++65 4564805Fax: ++65 64576

    Display page 11/6

    Press the Cursor down key to call up the next submenu:

    Japan:Tel: ++81 5453 3761Fax: ++81 5453 3767

    Display page 11/7

    Press the Cursor down key to call up the next submenu:

    USA:Tel: ++01 201 7844 355Fax:++01 201 7844 409

    Display page 11/8

    Press the Cursor up key to scroll back to the previous display stage.

    Press the UP key to access display page 12/1 (Service informa-tion).

    UP

  • 56

    8164-9001-400 / 1198

    All times on display pages 14/1 to 14/5 can be overwritten by the operator. No pass-word is required.

    Operator times (without password)T20: SeparationP: 7200 s A: 4444 s

    Display page 14/1

    P: Preset

    A: ActualThe operator times may have to be optimized to suit system or product require-ments. The operator times are listed in the table below:

    Timer-No. Functions Setpoints Actual val-ues

    T20 Separation 7 200 s

    T01 (01)T01 (02)T01 (36)T01 (96)

    Displacement - UNITROL with WMSDisplacement - VARIZONEDisplacement - UNITROL with SMSDisplacement - UNITROL-LO withSMS

    0 s 0 s

    T 02 (01)T 02 (02)T 02 (36)T 02 (96)

    Filling - UNITROL with WMSFilling - VARIZONEFilling - UNITROL with SMSFilling - UNITROL-LO with SMS

    T10 Separator start-up 600 s 0 s

    T11 Bridging alarm min. 60 sfor 2-stageoperation

    Attention:Only alter the timers in passive state.In the active state the previously set time will first run down; the time change willonly become effective when next activated.All preset times run down from the entered setpoint to zero and activate the pro-grammed function.

    The operator times are part of the system times which are adjusted on the displaypages 5/1 to 5/19 (see chapter 4.6 on page 44).

    4.14 Calling up operatortimes

  • 57

    8164-9001-400 / 1198

    You can alter the system settings on display pages 15/1 to 15/5.

    System settingsLanguageAlarmsTransfer

    Display page 15/1 (System settings)

    Press the Cursor down key to call up the next submenu:

    Alarm message buffer | Text Amount

    Display page 15/2

    The following functions are password-protected (for password entrysee page 29).

    no function

    Viewing the alarm message bufferThe following information is displayed here: the alarm messages with code number date and time of the faults and acknowledgments.

    List of the programmed alarm messages with code number

    Overview of the number of faults

    Press the Cursor down key to call up the next submenu:

    4.15 Calling up the systemsettings

    DOWN

    ALARMS

    UP

  • 58

    8164-9001-400 / 1198

    Passwords Edit Logout | Login | Time Date

    Display page 15/3

    Define password level 0 to 9.

    Call up password entry.

    Back to start screen after password entry.

    Set time and date.

    Press the Cursor down key to call up the next submenu:

    German | English | | Spanish SELECT

    Display page 15/4

    Language selection German

    Language selection English

    Language selection Spanish or French

    Display of the selected language

    Press the Cursor down key to call up the next submenu:

    DOWN

    ALARMS

    UP

    DOWN

    ALARMS

    UP

  • 59

    8164-9001-400 / 1198

    MPI transfer | Offline | | Online

    Display page 15/5

    Transfer configured OP software into the control.

    Offline operation

    Online operation

    no function

    DOWN

    ALARMS

    UP

  • 60

    8164-9001-400 / 1198

    You can use the auxiliary device UD 700 (WS part number: 0005-4040-190) withoutprogramming device to load S7-user programs into the control unit. The UD 700replaces the previous EPROMs. In addition, new programs can be loaded into anexisting UD 700 via modem connection and be displayed.

    Fig. 22

    ESC OK

    UD 700SIEMENS

    1

    2

    3

    1 MPI connection (9-pole)2 RS232 interface (6-pole)3 24-VDC supply voltage

    exits current function, returns to next highest menu level.

    - confirms a setting, starts the selected function, selects the next lower menu level, acknowledges error messages.

    moves the cursor up.

    moves the cursor down.

    The symbol at the left in a display line marks the selected function.A power supply unit (220 mA) is required for operating the programming device.Download from the programming device to the UD 700 is normally via a RS232cable (C79451-A3437-B122).Download from the UD 700 to the C7-CPU is normally via an MPI cable(6ES7705-0AA00-7BA0).

    4.16 Loading a new pro-gram

    4.16.1 The UD 700

    ESC

    OK

  • 61

    8164-9001-400 / 1198

    The UD 700 is connected to the control unit via the MPI port (1).Attention:The following steps may only be carried out when the separator is at stand-still and with closed media feed.

    Proceed as follows on the control unit:

    SIMATIC C7 SYSTEM FUNCTIONS

    KEY DI/DA

    Switch to the menu C7-CPU operating modes.

    MODE: RUN

    RUNP RUN STOP MRES

    Select the operating mode STOP.

    Enter the password (cf. page 29).

    PASSWORD-LEVEL: 9

    ...

    Exit the password entry.The menu C7-CPU operating modes is displayed again:

    MODE: RUN

    RUNP RUN STOP MRES

    Switch the CPU to STOP mode.The CPU switches to Stop; the LED STOP goes on.The control unit is ready for data download.Switch to the MPI Transfer operating mode.Wait until MPI DOWNLOAD appears in the display:

    4.16.2 Loading data fromthe UD 700 to theC7-623

    DOWN

    ESC

    MPItransfer

  • 62

    8164-9001-400 / 1198

    Proceed as follows on the UD 700: Check the UD 700 for the software to be downloaded. The label specifies:

    Device type (must be C7-623 ) Software number to be downloaded, Configuration date of the program

    Fig. 23

    2

    Use the cable provided to connect the UD 700 to the jack MPI (2) on the rearpanel of the control unit (in the cabinet door).

    The UD 700 tests the function of RAM and EPROM. It then briefly displays the startscreen:

    SIMATIC S7 UD700V1.00

    It then displays the selection menu:

    UD --> S7/C7S7/C7 --> UD

    The transfer process UD --> S7/control unit (transfer from UD 700 to control unit)is marked by .

    Confirm the marked transfer process.The display shows the following selection menu:

    CPU download YESCPU download NO

    The selection item CPU Download YES is marked by .

    OK

  • 63

    8164-9001-400 / 1198

    When you want to transfer the CPU program:

    Start the transfer process.The following message is briefly displayed:

    Preparing download

    Attention:Do not press any key on the UD 700 or on the control unit after you havestarted the transfer. Otherwise the transfer will be faulty.You can then no longer feed data to the control unit with the UD 700; youmust return the control unit to Westfalia Separator AG for reprogramming.The following messages are displayed:

    UD --> CPU FCB0019--------

    The number is counted during the transfer, the bar --- indicates the loading prog-ress.

    After completion of data transfer the C7 control unit must be switched back to oper-ating mode:

    Press the RUN key.

    If applicable, enter the password (cf. page 29).

    The control unit will start and signals proper functioning by means of the LEDRUN.

    Switch back to the process screen.

    OK

    ALARMS

  • 64

    8164-9001-400 / 1198

    On the control unit:

    Call up the directory.

    Scroll to the menu System setting (display page 15/1).

    System settingLanguageAlarmsTransfer

    Display page 15/1 (System settings)

    Scroll to the menu MPI transfer (display page 15/5).

    MPI transfer | Offline | | Online

    Display page 15/5

    Start the MPI transfer.The display switches over:

    MPI transferAddr. 1

    Attention:In the case of configured series operation, you must take into account differ-ent MPI addresses (3 / 5 / 7).

    4.16.3 Text transfer OP-part

    DIR

    DOWN

  • 65

    8164-9001-400 / 1198

    On the UD 700:

    CPU download YESCPU download NO

    Select the entry CPU download NO.

    Confirm your selection.The display switches to the following screen:

    OP download YESOP download NO

    The selection item OP download YES is marked by .

    Start the data transfer of the configured texts and graphics.

    The following messages are displayed:

    UD --> OP OPG0019--------

    The number is counted during the transfer, the bar --- indicates the loading prog-ress.

    When this program has been transferred, the UD 700 beeps.

    On the control unit:The control system restarts.

    Acknowledge the restart.The LED RUN goes on signalling that the control system is func-tional again.

    Disconnect the cable between UD 700 and control unit.

    OK

    OK

    ESC

  • 66

    8164-9001-400 / 1198

    You can load configured data from the programming device PG 740 into theUD 700.For this purpose you need the following connecting cables: RS 232 adapter cable (Part-No. C79451-A3437-B25) or RS 232 zero modem cable (Part-No. 6ES7901-1BF00-0XA0)In the following descriptions it is assumed that you know and can use MicrosoftWindows and that you are familiar with the SIMATIC Manager.

    Attention:Prior to the first transfer you must set the user parameters in the setup menu of theSIMATIC Manager.This procedure need not be repeated for subsequent transfers.

    Setting user parametersThe following description refers to the PC program SIMATIC Manager; the keysdescribed are the keys of the PC keyboard not the control unit or UD 700 keys. Press the Cursor down key 6 times until the cursor is positioned on Setup. Confirm with the OK button.

    The cursor is on Menu Setting. Confirm with the OK button.

    The cursor is on No Restrictions. Confirm with the OK button.

    The cursor jumps back to Menu Setting. Position the cursor with the Cursor down key on MPI-Parameter. Select the entry HSA = 15. Confirm with the OK button.

    The cursor jumps back to Modify HSA. Position the cursor with the Cursor down key on Modify CPU Address. Confirm with the OK button. In the case of standard configurations use the Cursor up or Cursor down keys

    to enter the value Address = 2.Exceptions:HFO series operation or integration in existing MPI networks.

    Confirm with the OK button.The cursor jumps back to Modify CPU address.

    Position the cursor with the Cursor down key on Modify OP address. Confirm with the OK button. In the case of standard configurations use the Cursor up or Cursor down keys

    to enter the value Address = 1.Exceptions:HFO series operation or integration in existing MPI networks.

    Confirm with the OK button.The cursor jumps back to Modify OP Address.

    Position the cursor with the Cursor down key on Modify UD Address. Confirm with the OK button. Always enter the value UD Address= 0.

    4.16.4 Loading configureddata from the pro-gramming device intothe UD 700

  • 67

    8164-9001-400 / 1198

    Confirm with the OK button. Press the ESC key to return to the main menu Setup.

    The MPI parameters are set. Use the Cursor down key to select the entry Target Device. Confirm with the OK button. Select the entry C7-623. Confirm with the OK button.

    The cursor jumps back to Target Device. Use the Cursor down key to position the cursor on CPU Memory. Confirm with the OK button.

    The cursor jumps to Clear before download. Confirm with the OK button.

    The cursor jumps back to CPU Memory. Use the Cursor down key to position the cursor on CPU RAM to ROM. Confirm with the OK button. Use the Cursor down key to position the cursor on Copy. Confirm with the OK button.

    The cursor jumps back to CPU RAM to ROM. Use the Cursor down key to position the cursor on Operating Language. Confirm with the OK button. Select the desired language. Confirm with the OK button.

    The cursor jumps back to Operating Language. Use the Cursor down key to position the cursor on Version Label. Confirm with the OK button. Select Label DB . Confirm with the OK button. Select the value Number = 0. Confirm with the OK button.

    The cursor jumps back to Version Label. Use the Cursor down key to position the cursor on RS232 Connection. Confirm with the OK button. Confirm the transmission speed Direct 38400 bit/s as per PG specification. Confirm with the OK button.

    The cursor jumps back to RS232 Connection. Press the ESC key to return to the main menu Setup. The modifications will be accepted by the UD 700. Setup is now complete. Press the ESC key to return to the main menu Communication

    UD ---> S7/C7.The programming device is ready for data transmission.

  • 68

    8164-9001-400 / 1198

    Transfer configuration dataWhen the user parameters have been saved you can transfer the configurationdata from the programming device to the UD 700 as follows:

    On the PG 740: Switch on the PG 740. Start Microsoft Windows until the start screen with the program overview ap-

    pears. Start the SIMATIC Manager. Open the desired file of configuration, e. g. SIMATIC 300-623_1. In the menu bar select Extras PG/PC-Interface Selection. Set the entry from MPI/ISA on Board to PC Adapter. Define the COM port and transmission speed under Properties, e.g. COM 2,

    38.400. Confirm with the OK button.

    You return to the main menu. Go to CPU-Program. Open the S7 program to be transferred, e. g. SIMATIC 300-623_1. Open the configuration S7-Program (1). Click on the display AP-off.

    The S7 configuration is available for download. Go to OP-Program. Open the OP program by double-clicking op623_1. Start the transfer mode via the menu File Transfer .

    The configuration data are synchronised.The Windows window Transfer MPI is opened.

    Start data transfer with the OK button.The transfer window is open and the data transfer shown as a block diagram.Correct transmission is indicated with the message Transfer completed suc-cessfully.

    On the UD 700: Connect the power supply unit for 24-VDC power supply.The display of the UD 700 lights up and the UD 700 tests the function of the RAMand EPROM. It then briefly displays the start screen:

    SIMATIC S7 UD700V1.00

    It then displays the selection menu:

    UD --> S7/C7S7/C7 --> UD

    Connect the serial data transmission cable to the serial interface of the PG 740and to the RS232 interface of the UD 700.

  • 69

    8164-9001-400 / 1198

    Use the Cursor down key to select the transfer mode PG/PC UD on the UD 700.

    Confirm your selection.

    If the connection is not correct, the display outputs the message:

    Waiting for connection

    On the PG 740: Click in the button bar on the Transfer button to start the download process at

    the programming device.The display of the UD 700 shows the following message:

    Connected

    The program is loaded into the UD 700.

    OK

  • 70

    8164-9001-400 / 1198

    NoteNotes

    NotizenAnotaciones

    NotizenNotesNote

  • 5 Programs and settings

    71

    8164-9001-400 / 1198

    5.1 Separator-specific operating modes 72. . . . . . . . . . . . . . . . . . . . . . . . . . 5.1.1 OSA-/OSB separators with VARIZONE system 72. . . . . . . . . . . . . . . . . 5.1.2 OSA-/OSB separators with UNITROL system WMS function 73. . . 5.1.3 OSA-/OSB separators with UNITROL system SMS function

    for HFO 74. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.1.4 OSC separators in -02- design 76. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.1.5 OSC separators with UNITROL system WMS system 79. . . . . . . . . 5.1.6 OSC separators with UNITROL system SMS function 82. . . . . . . . . 5.1.7 OSC separators with UNITROL system SMS function for

    lube oil treatment 85. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.2 Setting the counters 89. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.2.1 Flush ejection (counter 1) 89. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.2.2 Partial ejections (counter 2) 89. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.3 Entering freely assignable times 90. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

  • 72

    8164-9001-400 / 1198

    The control unit is assigned to the respective separator by means of a passwordin the factory. The possible variants are explained in the following sections.In the following explanations it is assumed that the separator motor is switched on, the starting time has elapsed, the separating time has been preselected and the minimum separating temperature has been exceeded.

    Sequence: ReadyStep: RecirculationProduct Temp.: 80 CSeparat. Time: 2400 s

    Display page 3/1 (process data)

    Compare the separator model shown on display page 2/1 with the installed separa-tor and adjust it if necessary. The time parameters are automatically set to suit thespecific separator.

    Start the separating program.The LED goes on.

    The program runs as follows:

    Program steps Function Timer No. Valve actuation

    1 2 3 4 5 6 7 8 9 PI&D-No.

    Waiting after program start 03

    Displacement 01 X9 790 02

    Waiting after displacement 08

    Total ejection 04 X9 790 01Speed recovery 05

    Filling 02 X9 790 02

    Waiting after filling 09

    Separation 20 X8 790 01

    Closing water pulses 06 X9 790 01