Model: WN-NL-0327

Non-Locating Liquid Sensing Controller

Model: WN-L-0328

Locating & Non-Locating Liquid Sensing Cables C/N Leading Wire

Locating Liquid Sensing Controller

The Leading Brand of Water Detection System

WERNER Liquid Leakage Alarm System is widely used for Under-floor Air Conditioning Units, Over-head Fan Coil Units,

Hot Water Radiator Units, Sump Tanks, Drip Trays, etc.

Zone-Type Liquid Leakage Alarm System can be used with Water Sensing Cable or Spot Type Water Leakage Detector to

detect the presence of water on a horizontal surface.

Applications: Server Rooms, Offices, Ships, etcApplications: Server Rooms, Offices, Ships, etc

Basic characteristics

Product characteristics

Locating Liquid Sensing Controller

Environment rating

Power supply

Serial interface

Relay contacts

Compatibility :

Sensor cables max length :Accuracy :

P-LFP1000 sensor cable and TraceTek leakdetecting sensing cables or the same typesensing cables

1500MSensor cable’s length of 0.5% 0.5m

- 40°C ~ 60°C ( 0°F ~ 140°F )- 20°C ~ 50°C ( 32°F ~ 122°F )5% ~ 95% (No condensation)

RS-485 communication mode, baud ratecan be chosen, optional address for 0 to247, the factory default baud is 9600, andaddress is 0

0.24 in (6.0mm) nominal2*26 AWG with insulation of �uoropolymer2*30 AWG with jacket of conductive �uoropolymer

Fluoropolymer2.3 Ib (1kg)High-visibility yellow

Cable only:160 , Ib(72kg) Including connectors: 70 Ib(32kg)

>50Ib with 0.005(>22kg with 0.13mm) in blade; crosshead speed 0.2in/min

>65 cycles per UL71970degree

0.24 in (6.0mm) nominalNone2*30 AWG with jacket of conductive �uoropolymer

Fluoropolymer500gHigh-visibility yellow

12VDC, 3A

MODBUS RTU

AC125V, 0.5A, DC24V, 1A. to often open, closed can be chosen.

12VDC, 3W

P-LFP1B/C sensor cable and the same type tow line sensing cables

500M100%

Storage temperature :Operating temperature :Operating humidity :

Cable diameter :Continuity & signal wires :Sensing wires:

Carrier :Cable weight (50ft/15m Length) :Cable colour

Breaking strength :

Cut-through force :

Abrasion resistance :Max continuous operting temp :

Leak size to alarm(tap water):

Drying time :

Standard cleaning method :

2 in (50mm) max at any point along sensing cable, up to 5000ft max system length

Cable dries & resets within 15s after removal from standing water