MCBs or Miniature Circuit Breakers are electromechanical devices which protect an electrical circuit from an overcurrent. The overcurrent, in an electrical circuit, may result from short circuit, overload or faulty design. An MCB is a better alternative to a Fuse since it does not require replacement once an overload is detected. Unlike fuse, an MCB can be easily reset and thus offers improved operational safety and greater convenience without incurring large operating cost

Page 4: Welcome to Electric Dept. Rajkot Division. How MCB works.

• The principal of operation is simple. An MCB functions by interrupting the continuity of electrical flow through the circuit once a fault is detected. In simple terms MCB is a switch which automatically turns off when the current flowing through it passes the maximum allowable limit. Generally MCB are designed to protect against over current and over temperature faults (over heating).

 • There are two contacts one is fixed and the other moveable. When the current

exceeds the predefined limit a solenoid forces the moveable contact to open (i.e., disconnect from the fixed contact) and the MCB turns off thereby stopping the current to flow in the circuit. In order to restart the flow of current the MCB is manually turned on. This mechanism is used to protect from the faults arising due to over current or over load. 

• To protect against fault arising due to over heating or increase in temperature a bi-metallic strip is used. MCBs are generally designed to trip within 2.5 millisecond when an over current fault arises. In case of temperature rise or over heating it may take 2 seconds to 2 minutes for the MCB to trip.

• This article covers the insight of a single pole MCB commonly used in the house hold. The following image shows the different internal parts of an MCB with top casing removed. The subsequent sections will examine each part and its function.

Page 5: Welcome to Electric Dept. Rajkot Division. How MCB works.
Page 6: Welcome to Electric Dept. Rajkot Division. How MCB works.

Tripping mechanism of MCB

Page 7: Welcome to Electric Dept. Rajkot Division. How MCB works.

The following image illustrates the tripping mechanism of the MCB. The circuit breaker contacts and the position of the knob can easily be seen in both, ON and OFF, state. In the ON state the moveable contact touches the fixed contact as shown in the image.

Page 8: Welcome to Electric Dept. Rajkot Division. How MCB works.

• The path of the current in the ON state is shown in the image below. The live wire is screwed at the input terminal. From the input terminal the current flows to the fixed contact which is touching the input terminal. The current then moves to the moving contact (since in the ON state it is touching the fixed contact). The moving contact is connected to the electromagnetic coil of the solenoid by means of a thick wire. The current from the moving contacts enters the electromagnetic coil. The current from the coil goes to the bimetallic strip by means of another thick wire and finally to the output terminal where it is collected by the neutral wire of the line.

Page 9: Welcome to Electric Dept. Rajkot Division. How MCB works.
Page 10: Welcome to Electric Dept. Rajkot Division. How MCB works.

•Connections of the coil

Page 11: Welcome to Electric Dept. Rajkot Division. How MCB works.
Page 12: Welcome to Electric Dept. Rajkot Division. How MCB works.

Switching Mechanism

Page 13: Welcome to Electric Dept. Rajkot Division. How MCB works.

The switching or the tripping mechanism can be closely observed in the following images. This mechanism is used to automatically cut off the supply of the current when the current exceeds the permissible

limits thereby preventing any damage to the appliances.

Let us understand this system in further detail. The image below shows a closure look of the different parts of the tripping mechanism. The moving part of the solenoid is called the plunger. It is like a solid semi cylinder connected to a hammer at one end. The moveable contact is positioned slightly above the plunger and moves axially along the plunger. It does not touch the plunger.

Page 14: Welcome to Electric Dept. Rajkot Division. How MCB works.
Page 15: Welcome to Electric Dept. Rajkot Division. How MCB works.

Role of Plunger

Page 16: Welcome to Electric Dept. Rajkot Division. How MCB works.

The heart of this mechanism is the solenoid which works on the principle of electro mechanism. As mentioned earlier one end of the coil is connected to the moveable contact by means of a thick wire for current to pass through it in the ON state. The coil of the solenoid is designed in such a way that when current passing through it is within the permissible value, the magnetic force produced is not enough to pull the plunger. When the current exceeds the permissible value, the magnetic force also increases and this magnetic force pulls the plunger inside towards the center of the coil.

Page 17: Welcome to Electric Dept. Rajkot Division. How MCB works.

• When the plunger moves it also pulls the moveable contact and forces it to separate from the fixed contact thereby tripping the circuit. The moveable contact is connected to the knob by means of mechanical arrangement and forces the MCB knob to fall down. The plunger is connected to a spring from inside the electromagnetic coil and as the plunger moves towards the center of the coil, the spring gets loaded. After the MCB trips (i.e., the moveable contact separates from the fixed contact and the current stops flowing) the spring forces the plunger back to its normal state without disturbing the moveable contact.

Page 18: Welcome to Electric Dept. Rajkot Division. How MCB works.

Mechanical Assembly

Page 19: Welcome to Electric Dept. Rajkot Division. How MCB works.

On further disassembling, different parts of this mechanical system can be seen. The images below shows all the parts of the switching

mechanism which are further detailed in the subsequent images

Page 20: Welcome to Electric Dept. Rajkot Division. How MCB works.

The following image shows the connection of the moveable contact with the coil. A thick wire carries the current from the movable contact to the coil.

Page 21: Welcome to Electric Dept. Rajkot Division. How MCB works.

Structure of Plunger

Page 22: Welcome to Electric Dept. Rajkot Division. How MCB works.

The image shows how the spring loaded mechanism works. The spring which is connected to the rod of the plunger pushes the plunger back

to its rest position once the tripping has taken place.

Page 23: Welcome to Electric Dept. Rajkot Division. How MCB works.

The image below shows the structure and arrangement of plunger, the moveable contact and the spring.

Page 24: Welcome to Electric Dept. Rajkot Division. How MCB works.

Arrangement of mechanical parts

Page 25: Welcome to Electric Dept. Rajkot Division. How MCB works.

The dismantled mechanical parts used to pull the knob when the tripping takes place. When the MCB gets tripped the moveable contact which is connected to the knob using these mechanical parts pulls the knob to the off position.

Page 26: Welcome to Electric Dept. Rajkot Division. How MCB works.

The following image shows the arrangement of the plunger, coil and the spring.

Page 27: Welcome to Electric Dept. Rajkot Division. How MCB works.

Parts of MCB

Page 28: Welcome to Electric Dept. Rajkot Division. How MCB works.

The outgoing and incoming terminals have been shown in the following image.

Page 29: Welcome to Electric Dept. Rajkot Division. How MCB works.

All the parts of this single pole MCB have been shown together in the following image.

Page 30: Welcome to Electric Dept. Rajkot Division. How MCB works.

Arc quenching

Page 31: Welcome to Electric Dept. Rajkot Division. How MCB works.

Arc quenching in MCB (Miniature Circuit Breakers)Another important point to be considered in the design of circuit

breakers is Arc quenching. To understand how MCB carries out the arc quenching, it is important to know about the electric arc and how is it

produced. When an overcurrent is interrupted by the circuit breaker by opening its contacts, current tries to bridge the gap. In an attempt to maintain the circuit, the air heats up and becomes a conductor. As a result an arc forms. In general, when air and gases are heated, they

become electric conductors. The hotter they get, the better they conduct. The following image shows how an electric arc looks like.

Page 32: Welcome to Electric Dept. Rajkot Division. How MCB works.

• The heat from an uncontrolled arc in a circuit breaker can cause a rapid and violent expansion of the nearby air and could severely damage the circuit breaker. Therefore, besides separating the electrical contacts, a circuit breaker also has to quickly extinguish the arc. A number of factors can be employed for quenching the arc, such as, speed, distance, dielectric strength, cooling etc.

• a)      Speed : When the contacts separate rapidly, there is less time for the arc to form and maintain itself.

• b)      Distance : When the distance between opened contacts is more, the arc has to stretch more to maintain the current flow which requires more voltage.

• c)      Cooling : When the arc is forced against a cold material, it absorbs and dissipates the heat.

• d)     Dielectric Strength : When the arc is submerged in a medium with higher dielectric strength than air (sulfur hexafluoride, SF6), the insulating nature of the medium helps in quenching the arc. 

• In an MCB, arc chutes or arc dividers are used for arc quenching. When the contacts of an MCB separate, generating an electrical arc between them through air, the arc is moved into the arch chute where it is divided into small segments. The overall energy level of the arc gets split up which is not sufficient to sustain the arc and therefore it gets dissipated.

Page 33: Welcome to Electric Dept. Rajkot Division. How MCB works.

Arc Chutes

Page 34: Welcome to Electric Dept. Rajkot Division. How MCB works.

The image below shows the arc chute used in the MCB for arc quenching purposes.

Page 35: Welcome to Electric Dept. Rajkot Division. How MCB works.

• Finally the next images shows how the arc chute is positioned in the MCB. The fixed contact is extended to the arc chute. This is done so as to transfer the arc to the interior of the breaker. The arc is broken into smaller arc by the arc chute. These segmented smaller arc have a very small potential and hence get naturally dissipated.

Page 36: Welcome to Electric Dept. Rajkot Division. How MCB works.

• On removing the holder which holds the arc chute, the mechanical structure and arrangement of the arc chute is visible in the next image.

Page 37: Welcome to Electric Dept. Rajkot Division. How MCB works.

Over heat protection

Page 38: Welcome to Electric Dept. Rajkot Division. How MCB works.

• Over heat protection• The MCB’s also provide protection against overheating. It uses a

bimetallic strip for the same. The arrangement of the bimetallic strip is shown in the image below. The bimetallic strip is made up of two metals with different temperature coefficients. When the current flows through the bimetallic strip, it gets heated. The heating results in bending of the bimetallic strip. The more is the heating, the more is the bending. The bimetallic strip is mechanically connected to the tripping mechanism by means of a metal strip as shown in the image. When the bimetallic strip bends it forces the metal strip to pull the plastic flap which in turn triggers the tripping mechanism after certain allowed temperature limit for which the bimetallic strip is designed.