62
SECTION 23 50 00 HVAC EQUIPMENT Display hidden notes to specifier. (Don't know how? Click Here ) Copyright 2018 - 2019 ARCAT, Inc. - All rights reserved PART 1 GENERAL 1.1 SECTION INCLUDES A. Gas Furnaces. B. Central Air Conditioners. C. Central Heat Pumps. D. Packaged Heating Units E. Ductless Heat Pumps and Air Conditioners F. Condo Pack Heating and Cooling Systems. G. Hybrid Heating Systems. H. High Efficiency Air Cleaners 1.2 RELATED SECTIONS A. Section 22 11 13 - Facility Water Distribution Piping. B. Section 26 05 00 - Common Work Results for Electrical 1.3 REFERENCES A. CSA B140.4-04 - Oil-fired warm air furnaces B. CSA B149.1 - Natural Gas and Propane Installation Code. C. CSA B149.2 - Propane Storage and Handling Code. D. CSA B212-00 - Energy Utilization Efficiencies of Oil-Fired Furnaces and Boilers. E. CSA C222.1 - Canadian Electrical Code. 23 50 00-1

Transcript of €¦ · Web viewNapoleon Ductless Multi-Zone Heat Pumps and Air Conditioners: General: Multi-zone...

Page 1: €¦ · Web viewNapoleon Ductless Multi-Zone Heat Pumps and Air Conditioners: General: Multi-zone offers up to 4 indoor units that operate from one, outdoor air condenser. Indoor

SECTION 23 50 00HVAC EQUIPMENT

Display hidden notes to specifier. (Don't know how? Click Here)

Copyright 2018 - 2019 ARCAT, Inc. - All rights reserved

PART 1 GENERAL

1.1 SECTION INCLUDES

A. Gas Furnaces.

B. Central Air Conditioners.

C. Central Heat Pumps.

D. Packaged Heating Units

E. Ductless Heat Pumps and Air Conditioners

F. Condo Pack Heating and Cooling Systems.

G. Hybrid Heating Systems.

H. High Efficiency Air Cleaners

1.2 RELATED SECTIONS

A. Section 22 11 13 - Facility Water Distribution Piping.

B. Section 26 05 00 - Common Work Results for Electrical

1.3 REFERENCES

A. CSA B140.4-04 - Oil-fired warm air furnaces

B. CSA B149.1 - Natural Gas and Propane Installation Code.

C. CSA B149.2 - Propane Storage and Handling Code.

D. CSA B212-00 - Energy Utilization Efficiencies of Oil-Fired Furnaces and Boilers.

E. CSA C222.1 - Canadian Electrical Code.

F. CSA B366.1 - Solid-fuel-fired central heating appliances

G. CSA B415.1-10 - Performance testing of solid-fuel-burning heating appliances.

H. NFPA 54 - National Fuel Gas Code.

23 50 00-1

Page 2: €¦ · Web viewNapoleon Ductless Multi-Zone Heat Pumps and Air Conditioners: General: Multi-zone offers up to 4 indoor units that operate from one, outdoor air condenser. Indoor

I. NFPA - 70 - National Electric Code.

J. UL 391 - Standard for Solid-Fuel and Combination-Fuel Central and Supplementary Furnaces.

K. UL 727 - Standard for Oil fired Furnaces.

L. UL 1995/CSA C22.2 No.236 - Standard for Heating and Cooling Equipment

1.4 SUBMITTALS

A. Submit under provisions of Section 01 30 00 - Administrative Requirements.

B. Product Data: Manufacturer's data sheets on each product to be used, including:1. Preparation instructions and recommendations.2. Storage and handling requirements and recommendations.3. Installation methods. I

C. Shop Drawings: Overall dimensions and required clearances including detail of architectural enclosing requirements. Detailed schematics of electrical control wiring and power rough-in.

D. Manufacturer's Certificates: Certify products meet or exceed specified requirements.

E. Closeout Submittals: Provide manufacturer's maintenance instructions that include recommendations for periodic checking and adjustment and periodic cleaning and maintenance of all components.

1.5 QUALITY ASSURANCE

A. Manufacturer Qualifications: Manufacturer with a minimum of 5 years documented experience with the types of products specified.

B. Installer Qualifications: Installer with a minimum 2 years documented experience with the type of products specified.

C. Mock-Up: Provide a mock-up for evaluation of surface preparation techniques and application workmanship.1. Finish areas designated by Architect.2. Do not proceed with remaining work until workmanship, color, and sheen are

approved by Architect.3. Refinish mock-up area as required to produce acceptable work.

1.6 DELIVERY, STORAGE, AND HANDLING

A. Store products in manufacturer's unopened packaging until ready for installation.

B. Store products in covered area, well protected from weather.

1.7 SEQUENCING

A. Ensure that locating templates and other information required for installation of products of this section are furnished to affected trades in time to prevent interruption of construction progress.

B. Ensure that products of this section are supplied to affected trades in time to prevent interruption of construction progress.

1.8 PROJECT CONDITIONS

23 50 00-2

Page 3: €¦ · Web viewNapoleon Ductless Multi-Zone Heat Pumps and Air Conditioners: General: Multi-zone offers up to 4 indoor units that operate from one, outdoor air condenser. Indoor

A. Maintain environmental conditions (temperature, humidity, and ventilation) within limits recommended by manufacturer for optimum results. Do not install products under environmental conditions outside manufacturer's absolute limits.

1.9 WARRANTY

A. Gas Furnaces: Provide with the Manufacturers 10 year Limited Unit Replacement Heat Exchanger, Life Time Limited Heat Exchanger and 10 Year Limited Parts Warranty.

B. Gas Furnaces: Provide with the Manufacturers 20 year Limited Unit Replacement Heat Exchanger, Life Time Limited Heat Exchanger and 10 Year Limited Parts Warranty.

C. Gas Furnaces: Provide with the Manufacturers 15 year Limited Unit Replacement Heat Exchanger, Life Time Limited Heat Exchanger and 10 Year Limited Parts Warranty.

D. Ductless Heat Pumps and Air Conditioners: Provide Heat Pumps and Multi-Zone Heat Pumps with the Manufacturers 6 year Limited Compressor, and 6 year Limited Parts Warranty.

E. Condo-Pack: Provide with the Manufacturers 20 year Limited Heat Exchanger, 10 year Limited Furnace Module, and 5 year Limited Parts Warranty. Provide NC15 Air Conditioner with the Manufacturers 5 year compressor, and 1 year Limited Parts Warranty.

F. Central A/C: Provide with the Manufacturers 10 Year Limited Compressor Warranty and 10 Year Limited Parts Warranty.

G. Hybrid Heating Systems: Provide with the Manufacturers Limited Lifetime Warranty.

H. Whole House High Efficiency Media Air Cleaners: Provide with the Manufacturers 10 Year Limited Parts Warranty.

PART 2 PRODUCTS

2.1 MANUFACTURERS

A. Substitutions: Not permitted.

B. Requests for substitutions will be considered in accordance with provisions of Section 01 60 00 - Product Requirements.

2.2 GAS FURNACES

A. Napoleon 9500 Series Gas Furnace:1. Features:

a. Installation options for Upflow, Horizontal Left and Horizontal Right.b. Single Stagec. Secondary Stainless Steel Heat Exchanger

2. Series: NPX030S2B with Endura Pro Motor:a. Heating Capacity:

1) Efficiency (AFUE): 95 percent2) Input BTU/hr 0-4500': 30,0003) Output BTU/hr 0-4500': 28,500

b. Cabinet Dimensions: 17-1/2 inches wide by 29-1/2 inches deep by 32-7/8 inches high.

c. Venting:1) Clearance to Combustibles: 02) Minimum Vent Size: 1-1/2 inches3) Maximum Vent Size: 2 inches

23 50 00-3

Page 4: €¦ · Web viewNapoleon Ductless Multi-Zone Heat Pumps and Air Conditioners: General: Multi-zone offers up to 4 indoor units that operate from one, outdoor air condenser. Indoor

4) Minimum Vent Length: 15 feet5) Maximum Vent Length: 75 feet

d. Airflow and Cooling1) Motor Type and Size ECM: 1/3 hp2) Recommended AC Tonnage: 1-1/2, 2 and 2-1/2

3. Series: NPX040S2B with Endura Pro Motor:a. Heating Capacity:

1) Efficiency (AFUE): 95 percent2) Input BTU/hr 0-4500': 40,0003) Output BTU/hr 0-4500': 38,000

b. Cabinet Dimensions: 17-1/2 inches wide by 29-1/2 inches deep by 32-7/8 inches high.

c. Venting:1) Clearance to Combustibles: 02) Minimum Vent Size: 1-1/2 inches3) Maximum Vent Size: 2 inches4) Minimum Vent Length: 15 feet5) Maximum Vent Length: 75 feet

d. Airflow and Cooling1) Motor Type and Size ECM: 1/3 hp2) Recommended AC Tonnage: 1-1/2, 2 and 2-1/2

4. Series: NPX060S3B with Endura Pro Motor:a. Heating Capacity:

1) Efficiency (AFUE): 95 percent2) Input BTU/hr 0-4500': 60,0003) Output BTU/hr 0-4500': 57,000

b. Cabinet Dimensions: 17-1/2 inches wide by 29-1/2 inches deep by 32-7/8 inches high.

c. Venting:1) Clearance to Combustibles: 02) Minimum Vent Size: 1-1/2 inches3) Maximum Vent Size: 3 inches4) Minimum Vent Length: 15 feet5) Maximum Vent Length: 100 feet

d. Airflow and Cooling1) Motor Type and Size ECM: 1/2 hp2) Recommended AC Tonnage: 1.5, 2, 2-1/2 and 3

5. Series: NPX080S3B with Endura Pro Motor:a. Heating Capacity:

1) Efficiency (AFUE): 95 percent2) Input BTU/hr 0-4500': 80,0003) Output BTU/hr 0-4500': 76,000

b. Cabinet Dimensions: 17-1/2 inches wide by 29-1/2 inches deep by 32-7/8 inches high.

c. Venting:1) Clearance to Combustibles: 02) Minimum Vent Size: 2 inches3) Maximum Vent Size: 3 inches4) Minimum Vent Length: 15 feet5) Maximum Vent Length: 100 feet

d. Airflow and Cooling1) Motor Type and Size ECM: 1/2 hp2) Recommended AC Tonnage: 1-1/2, 2, 2-1/2 and 3

6. Series: NPX080S4B with Endura Pro Motor:a. Heating Capacity:

1) Efficiency (AFUE): 95 percent

23 50 00-4

Page 5: €¦ · Web viewNapoleon Ductless Multi-Zone Heat Pumps and Air Conditioners: General: Multi-zone offers up to 4 indoor units that operate from one, outdoor air condenser. Indoor

2) Input BTU/hr 0-4500': 80,0003) Output BTU/hr 0-4500': 76,000

b. Cabinet Dimensions: 22-1/2 inches wide by 29-1/2 inches deep by 32-7/8 inches high.

c. Venting:1) Clearance to Combustibles: 02) Minimum Vent Size: 2 inches3) Maximum Vent Size: 3 inches4) Minimum Vent Length: 15 feet5) Maximum Vent Length: 100 feet

d. Airflow and Cooling1) Motor Type and Size ECM: 3/4 hp2) Recommended AC Tonnage: 2, 3, and 4

7. Series: NPX100S5B with Endura Pro Motor:a. Heating Capacity:

1) Efficiency (AFUE): 95 percent2) Input BTU/hr 0-4500': 100,0003) Output BTU/hr 0-4500': 95,000

b. Cabinet Dimensions: 22-1/2 inches wide by 29-1/2 inches deep by 32-7/8 inches high.

c. Venting:1) Clearance to Combustibles: 02) Minimum Vent Size: 2 inches3) Maximum Vent Size: 3 inches4) Minimum Vent Length: 15 feet5) Maximum Vent Length: 100 feet

d. Airflow and Cooling1) Motor Type and Size ECM: 3/4 hp2) Recommended AC Tonnage: 2, 3, 4, and 5

8. Series: NPX120S5B with Endura Pro Motor:a. Heating Capacity:

1) Efficiency (AFUE): 95 percent2) Input BTU/hr 0-4500': 120,0003) Output BTU/hr 0-4500': 114,000

b. Cabinet Dimensions: 22-1/2 inches wide by 29-1/2 inches deep by 32-7/8 inches high.

c. Venting:1) Clearance to Combustibles: 02) Minimum Vent Size: 2 inches3) Maximum Vent Size: 3 inches4) Minimum Vent Length: 15 feet5) Maximum Vent Length: 100 feet

d. Airflow and Cooling1) Motor Type and Size ECM: 1 hp2) Recommended AC Tonnage: 2, 3, 4, and 5

9. Series: NSM030S2B with PSC Motor:a. Heating Capacity:

1) Efficiency (AFUE): 95 percent2) Input BTU/hr 0-4500': 30,0003) Output BTU/hr 0-4500': 28,500

b. Cabinet Dimensions: 17-1/2 inches wide by 29-1/2 inches deep by 32-7/8 inches high.

c. Venting:1) Clearance to Combustibles: 02) Minimum Vent Size: 1-1/2 inches3) Maximum Vent Size: 2 inches

23 50 00-5

Page 6: €¦ · Web viewNapoleon Ductless Multi-Zone Heat Pumps and Air Conditioners: General: Multi-zone offers up to 4 indoor units that operate from one, outdoor air condenser. Indoor

4) Minimum Vent Length: 15 feet5) Maximum Vent Length: 75 feet

d. Airflow and Cooling1) Motor Type and Size PSC: 1/3 hp2) Recommended AC Tonnage: 1-1/2, 2 and 2.5

10. Series: NSM040S2B with PSC Motor:a. Heating Capacity:

1) Efficiency (AFUE): 95 percent2) Input BTU/hr 0-4500': 40,0003) Output BTU/hr 0-4500': 38,000

b. Cabinet Dimensions: 17-1/2 inches wide by 29-1/2 inches deep by 32-7/8 inches high.

c. Venting:1) Clearance to Combustibles: 02) Minimum Vent Size: 1-1/2 inches3) Maximum Vent Size: 2 inches4) Minimum Vent Length: 15 feet5) Maximum Vent Length: 75 feet

d. Airflow and Cooling1) Motor Type and Size ECM: 1/3 hp2) Recommended AC Tonnage: 1-1/2, 2 and 2.5

11. Series: NSM060S3B with PSC Motor:a. Heating Capacity:

1) Efficiency (AFUE): 95 percent2) Input BTU/hr 0-4500': 60,0003) Output BTU/hr 0-4500': 57,000

b. Cabinet Dimensions: 17-1/2 inches wide by 29-1/2 inches deep by 32-7/8 inches high.

c. Venting:1) Clearance to Combustibles: 02) Minimum Vent Size: 1-1/2 inches3) Maximum Vent Size: 3 inches4) Minimum Vent Length: 15 feet5) Maximum Vent Length: 100 feet

d. Airflow and Cooling1) Motor Type and Size ECM: 1/2 hp2) Recommended AC Tonnage: 1.5, 2, 2-1/2 and 3

12. Series: NSM080S3B with PSC Motor:a. Heating Capacity:

1) Efficiency (AFUE): 95 percent2) Input BTU/hr 0-4500': 80,0003) Output BTU/hr 0-4500': 76,000

b. Cabinet Dimensions: 17-1/2 inches wide by 29-1/2 inches deep by 32-7/8 inches high.

c. Venting:1) Clearance to Combustibles: 02) Minimum Vent Size: 2 inches3) Maximum Vent Size: 3 inches4) Minimum Vent Length: 15 feet5) Maximum Vent Length: 100 feet

d. Airflow and Cooling1) Motor Type and Size ECM: 1/2 hp2) Recommended AC Tonnage: 2, 2-1/2 and 3

13. Series: NSM080S4B with PSC Motor:a. Heating Capacity:

1) Efficiency (AFUE): 95 percent

23 50 00-6

Page 7: €¦ · Web viewNapoleon Ductless Multi-Zone Heat Pumps and Air Conditioners: General: Multi-zone offers up to 4 indoor units that operate from one, outdoor air condenser. Indoor

2) Input BTU/hr 0-4500': 80,0003) Output BTU/hr 0-4500': 76,000

b. Cabinet Dimensions: 22-1/2 inches wide by 29-1/2 inches deep by 32-7/8 inches high.

c. Venting:1) Clearance to Combustibles: 02) Minimum Vent Size: 2 inches3) Maximum Vent Size: 3 inches4) Minimum Vent Length: 15 feet5) Maximum Vent Length: 100 feet

d. Airflow and Cooling1) Motor Type and Size ECM: 3/4 hp2) Recommended AC Tonnage: 3, 4 and 5

14. Series: NSM100S5B with PSC Motor:a. Heating Capacity:

1) Efficiency (AFUE): 95 percent2) Input BTU/hr 0-4500': 100,0003) Output BTU/hr 0-4500': 95,000

b. Cabinet Dimensions: 22-1/2 inches wide by 29-1/2 inches deep by 32-7/8 inches high.

c. Venting:1) Clearance to Combustibles: 02) Minimum Vent Size: 2 inches3) Maximum Vent Size: 3 inches4) Minimum Vent Length: 15 feet5) Maximum Vent Length: 100 feet

d. Airflow and Cooling1) Motor Type and Size ECM: 3/4 hp2) Recommended AC Tonnage: 3, 4 and 5

15. Series: NSM120S5B with PSC Motor:a. Heating Capacity:

1) Efficiency (AFUE): 95 percent2) Input BTU/hr 0-4500': 120,0003) Output BTU/hr 0-4500': 114,000

b. Cabinet Dimensions: 22-1/2 inches wide by 29-1/2 inches deep by 32-7/8 inches high.

c. Venting:1) Clearance to Combustibles: 02) Minimum Vent Size: 2 inches3) Maximum Vent Size: 3 inches4) Minimum Vent Length: 15 feet5) Maximum Vent Length: 100 feet

d. Airflow and Cooling1) Motor Type and Size ECM: 3/4 hp2) Recommended AC Tonnage: 3, 4 and 5

B. Napoleon 9600 Series Gas Furnace:1. Features:

a. Installation options for Upflow, Horizontal Left and Horizontal Right.b. Two Stagec. Sure-View Windowd. Secondary Stainless Steel Heat Exchanger

2. Series NPV040T2B with ECM EON Motor:a. Heating Capacity:

1) Efficiency (AFUE): 96 percent2) Input BTU/hr 0-4500': 40,000

23 50 00-7

Page 8: €¦ · Web viewNapoleon Ductless Multi-Zone Heat Pumps and Air Conditioners: General: Multi-zone offers up to 4 indoor units that operate from one, outdoor air condenser. Indoor

3) Output BTU/hr 0-4500': 38,000b. Cabinet Dimensions: 17-1/2 inches wide by 29-1/2 inches deep by 32-7/8

inches h.c. Venting:

1) Clearance to Combustibles: 02) Minimum Vent Size: 1-1/2 inches3) Maximum Vent Size: 2 inches4) Minimum Vent Length: 15 feet5) Maximum Vent Length: 75 feet

d. Airflow and Cooling1) Motor Type and Size ECM: 1/3 hp2) Recommended AC Tonnage: 1-1/2, 2 and 2-1/2

3. Series NPV060T3B with ECM EON Motor:a. Heating Capacity:

1) Efficiency (AFUE): 96 percent2) Input BTU/hr 0-4500': 60,0003) Output BTU/hr 0-4500': 57,000

b. Cabinet Dimensions: 17-1/2 inches wide by 29-1/2 inches deep by 32-7/8 inches h.

c. Venting:1) Clearance to Combustibles: 02) Minimum Vent Size: 1-1/2 inches3) Maximum Vent Size: 2 inches4) Minimum Vent Length: 15 feet5) Maximum Vent Length: 100 feet

d. Airflow and Cooling1) Motor Type and Size ECM: 1/2 hp2) Recommended AC Tonnage: 1-1/2, 2, 2-1/2 and 3

4. Series NPV080T3B with ECM EON Motor:a. Heating Capacity:

1) Efficiency (AFUE): 96 percent2) Input BTU/hr 0-4500': 80,0003) Output BTU/hr 0-4500': 76,000

b. Cabinet Dimensions: 17-1/2 inches wide by 29-1/2 inches deep by 32-7/8 inches h.

c. Venting:1) Clearance to Combustibles: 02) Minimum Vent Size: 2 inches3) Maximum Vent Size: 3 inches4) Minimum Vent Length: 15 feet5) Maximum Vent Length: 100 feet

d. Airflow and Cooling1) Motor Type and Size ECM: 1/2 hp2) Recommended AC Tonnage: 1-1/2, 2, 2-1/2 and 3

5. Series NPV080T4B with ECM EON Motor:a. Heating Capacity:

1) Efficiency (AFUE): 96 percent2) Input BTU/hr 0-4500': 80,0003) Output BTU/hr 0-4500': 76,000

b. Cabinet Dimensions: 22-1/2 inches wide by 29-1/2 inches deep by 32-7/8 inches h.

c. Venting:1) Clearance to Combustibles: 02) Minimum Vent Size: 2 inches3) Maximum Vent Size: 3 inches4) Minimum Vent Length: 15 feet

23 50 00-8

Page 9: €¦ · Web viewNapoleon Ductless Multi-Zone Heat Pumps and Air Conditioners: General: Multi-zone offers up to 4 indoor units that operate from one, outdoor air condenser. Indoor

5) Maximum Vent Length: 100 feetd. Airflow and Cooling

1) Motor Type and Size ECM: 3/4 hp2) Recommended AC Tonnage: 2, 3, 4 and 5

6. Series NPV100T5B with ECM EON Motor:a. Heating Capacity:

1) Efficiency (AFUE): 96 percent2) Input BTU/hr 0-4500': 100,0003) Output BTU/hr 0-4500': 95,000

b. Cabinet Dimensions: 22-1/2 inches wide by 29-1/2 inches deep by 32-7/8 inches h.

c. Venting:1) Clearance to Combustibles: 02) Minimum Vent Size: 2 inches3) Maximum Vent Size: 3 inches4) Minimum Vent Length: 15 feet5) Maximum Vent Length: 100 feet

d. Airflow and Cooling1) Motor Type and Size ECM: 3/4 hp2) Recommended AC Tonnage: 2, 3, 4 and 5

7. Series NPV120T5B with ECM EON Motor:a. Heating Capacity:

1) Efficiency (AFUE): 96 percent2) Input BTU/hr 0-4500': 120,0003) Output BTU/hr 0-4500': 114,000

b. Cabinet Dimensions: 22-1/2 inches wide by 29-1/2 inches deep by 32-7/8 inches h.

c. Venting:1) Clearance to Combustibles: 02) Minimum Vent Size: 3 inches3) Maximum Vent Size: 3 inches4) Minimum Vent Length: 15 feet5) Maximum Vent Length: 100 feet

d. Airflow and Cooling1) Motor Type and Size ECM: 1 hp2) Recommended AC Tonnage: 2, 3, 4 and 5

8. Series NSX040T2B with Endura Pro ECM Motora. Heating Capacity:

1) Efficiency (AFUE): 96 percent2) Input BTU/hr 0-4500': 40,0003) Output BTU/hr 0-4500': 24,000

b. Cabinet Dimensions: 17-1/2 inches wide by 29-1/2 inches deep by 32-7/8 inches h.

c. Venting:1) Clearance to Combustibles: 02) Minimum Vent Size: 1-1/2 inches3) Maximum Vent Size: 2 inches4) Minimum Vent Length: 15 feet5) Maximum Vent Length: 75 feet

d. Airflow and Cooling1) Motor Type and Size ECM: 1/3 hp2) Recommended AC Tonnage: 1-1/2, 2 and 2-1/2

9. Series NSX060T3B with Endura Pro ECM Motoa. Heating Capacity:

1) Efficiency (AFUE): 96 percent2) Input BTU/hr 0-4500': 60,000

23 50 00-9

Page 10: €¦ · Web viewNapoleon Ductless Multi-Zone Heat Pumps and Air Conditioners: General: Multi-zone offers up to 4 indoor units that operate from one, outdoor air condenser. Indoor

3) Output BTU/hr 0-4500': 36,000b. Cabinet Dimensions: 17-1/2 inches wide by 29-1/2 inches deep by 32-7/8

inches h.c. Venting:

1) Clearance to Combustibles: 02) Minimum Vent Size: 1-1/2 inches3) Maximum Vent Size: 3 inches4) Minimum Vent Length: 15 feet5) Maximum Vent Length: 100 feet

d. Airflow and Cooling1) Motor Type and Size ECM: 1/2 hp2) Recommended AC Tonnage: 2, 2-1/2 and 3

10. Series NSX080T3B with Endura Pro ECM Motoa. Heating Capacity:

1) Efficiency (AFUE): 96 percent2) Input BTU/hr 0-4500': 80,0003) Output BTU/hr 0-4500': 48,000

b. Cabinet Dimensions: 17-1/2 inches wide by 29-1/2 inches deep by 32-7/8 inches h.

c. Venting:1) Clearance to Combustibles: 02) Minimum Vent Size: 2 inches3) Maximum Vent Size: 3 inches4) Minimum Vent Length: 15 feet5) Maximum Vent Length: 100 feet

d. Airflow and Cooling1) Motor Type and Size ECM: 1/2 hp2) Recommended AC Tonnage: 2, 2-1/2 and 3

11. Series NSX080T4B with Endura Pro ECM Motoa. Heating Capacity:

1) Efficiency (AFUE): 96 percent2) Input BTU/hr 0-4500': 80,0003) Output BTU/hr 0-4500': 48,000

b. Cabinet Dimensions: 22-1/2 inches wide by 29-1/2 inches deep by 32-7/8 inches h.

c. Venting:1) Clearance to Combustibles: 02) Minimum Vent Size: 2 inches3) Maximum Vent Size: 3 inches4) Minimum Vent Length: 15 feet5) Maximum Vent Length: 100 feet

d. Airflow and Cooling1) Motor Type and Size ECM: 3/4 hp2) Recommended AC Tonnage: 2, 3 and 4

12. Series NSX100T5B with Endura Pro ECM Motoa. Heating Capacity:

1) Efficiency (AFUE): 96 percent2) Input BTU/hr 0-4500': 100,0003) Output BTU/hr 0-4500': 60,000

b. Cabinet Dimensions: 22-1/2 inches wide by 29-1/2 inches deep by 32-7/8 inches h.

c. Venting:1) Clearance to Combustibles: 02) Minimum Vent Size: 2 inches3) Maximum Vent Size: 3 inches4) Minimum Vent Length: 15 feet

23 50 00-10

Page 11: €¦ · Web viewNapoleon Ductless Multi-Zone Heat Pumps and Air Conditioners: General: Multi-zone offers up to 4 indoor units that operate from one, outdoor air condenser. Indoor

5) Maximum Vent Length: 100 feetd. Airflow and Cooling

1) Motor Type and Size ECM: 3/4 hp2) Recommended AC Tonnage: 3, 4 and 5

13. Series NSX120T5B with Endura Pro ECM Motoa. Heating Capacity:

1) Efficiency (AFUE): 96 percent2) Input BTU/hr 0-4500': 120,0003) Output BTU/hr 0-4500': 72,000

b. Cabinet Dimensions: 22-1/2 inches wide by 29-1/2 inches deep by 32-7/8 inches h.

c. Venting:1) Clearance to Combustibles: 02) Minimum Vent Size: 3 inches3) Maximum Vent Size: 3 inches4) Minimum Vent Length: 15 feet5) Maximum Vent Length: 100 feet

d. Airflow and Cooling1) Motor Type and Size ECM: 1 hp2) Recommended AC Tonnage: 3, 4 and 5

C. Napoleon 9600Q Series Gas Furnace:1. Features:

a. Installation options: Multi-fit: upflow and horizontal right. May be installed in two positions, alcove or closet installations that require zero clearance.

b. Two Stagec. Secondary Stainless Steel Heat Exchanger

2. Series WSX040T2AA-N with Multispeed Motor:a. Heating Capacity:

1) Efficiency (AFUE): 96 percent2) Input BTU/hr 0-2000': 40,0003) Output BTU/hr 0-2000': 38,000

b. Cabinet Dimensions: 17-1/2 inches wide by 29-1/2 inches deep by 34 inches h.c. Venting:

1) Clearance to Combustibles: 02) Minimum Vent Size: 1-1/2 inches3) Maximum Vent Size: 2-1/2 inches4) Minimum Vent Length: 15 feet5) Maximum Vent Length: 75 feet

d. Airflow and Cooling1) Motor Type and Size: 1/3 hp2) Recommended AC Tonnage: 1-1/2, 2 and 2-1/2

3. Series WSX060T3AA-N with Multispeed Motor:a. Heating Capacity:

1) Efficiency (AFUE): 96 percent2) Input BTU/hr 0-2000': 60,0003) Output BTU/hr 0-2000': 58,000

b. Cabinet Dimensions: 17-1/2 inches wide by 29-1/2 inches deep by 34 inches h.c. Venting:

1) Clearance to Combustibles: 02) Minimum Vent Size: 1-1/2 inches3) Maximum Vent Size: 3 inches4) Minimum Vent Length: 15 feet5) Maximum Vent Length: 100 feet

d. Airflow and Cooling1) Motor Type and Size: 1/ 2 hp

23 50 00-11

Page 12: €¦ · Web viewNapoleon Ductless Multi-Zone Heat Pumps and Air Conditioners: General: Multi-zone offers up to 4 indoor units that operate from one, outdoor air condenser. Indoor

2) Recommended AC Tonnage: 1-1/2, 2 and 2-1/24. Series WSX080T3AA-N with Multispeed Motor:

a. Heating Capacity:1) Efficiency (AFUE): 96 percent2) Input BTU/hr 0-2000': 80,0003) Output BTU/hr 0-2000': 77,000

b. Cabinet Dimensions: 17-1/2 inches wide by 29-1/2 inches deep by 34 inches h.c. Venting:

1) Clearance to Combustibles: 02) Minimum Vent Size: 2 inches3) Maximum Vent Size: 3 inches4) Minimum Vent Length: 15 feet5) Maximum Vent Length: 100 feet

d. Airflow and Cooling1) Motor Type and Size: 1/2 hp2) Recommended AC Tonnage: 1-1/2, 2, 2-1/2 and 3

D. Napoleon Ultimate 9700 Gas Furnace:1. Features:

a. Upflow onlyb. Two-Stagec. SureView Windowd. EON ECM Motore. Primary Stainless Steel Heat Exchangerf. Secondary Stainless Steel Heat Exchangerg. LED Cabinet Lightsh. Built-In UV Light Air Purifieri. Four-Sided Insulated Cabinet

2. Series: NUV040T2B with ECM EON Motor:a. Heating Capacity

1) Efficiency (AFUE): 97 percent2) Input BTU/hr 0-4500': 40,0003) Output BTU/hr 0-4500': 38,800

b. Cabinet Dimensions: 17-1/2 inches wide by 29-1/2 inches deep by 32-7/8 inches h.

c. Venting:1) Clearance to Combustibles: 02) Minimum Vent Size: 1-1/2 inches3) Maximum Vent Size: 2 inches4) Minimum Vent Length: 15 feet5) Maximum Vent Length: 75 feet

d. Airflow and Cooling1) Motor Type and Size ECM EON: 1/3 hp2) Recommended AC Tonnage: 1-1/2, 2, and 2-1/2

3. Series: NUV060T3B with ECM EON Motor:a. Heating Capacity

1) Efficiency (AFUE): 97 percent2) Input BTU/hr 0-4500': 60,0003) Output BTU/hr 0-4500': 58,260

b. Cabinet Dimensions: 17-1/2 inches wide by 29-1/2 inches deep by 32-7/8 inches h.

c. Venting:1) Clearance to Combustibles: 02) Minimum Vent Size: 1-1/2 inches3) Maximum Vent Size: 3 inches4) Minimum Vent Length: 15 feet

23 50 00-12

Page 13: €¦ · Web viewNapoleon Ductless Multi-Zone Heat Pumps and Air Conditioners: General: Multi-zone offers up to 4 indoor units that operate from one, outdoor air condenser. Indoor

5) Maximum Vent Length: 100 feetd. Airflow and Cooling

1) Motor Type and Size ECM EON: 1/2 hp2) Recommended AC Tonnage: 1-1/2, 2, 2-1/2 and 3

4. Series: NUV080T3B with ECM EON Motor:a. Heating Capacity

1) Efficiency (AFUE): 97 percent2) Input BTU/hr 0-4500': 80,0003) Output BTU/hr 0-4500': 77,600

b. Cabinet Dimensions: 17-1/2 inches wide by 29-1/2 inches deep by 32-7/8 inches h.

c. Venting:1) Clearance to Combustibles: 02) Minimum Vent Size: 2 inches3) Maximum Vent Size: 3 inches4) Minimum Vent Length: 15 feet5) Maximum Vent Length: 100 feet

d. Airflow and Cooling1) Motor Type and Size ECM EON: 1/2 hp2) Recommended AC Tonnage: 1-1/2, 2, 2-1/2 and 3

5. Series: NUV080T4B with ECM EON Motor:a. Heating Capacity

1) Efficiency (AFUE): 97 percent2) Input BTU/hr 0-4500': 80,0003) Output BTU/hr 0-4500': 77,600

b. Cabinet Dimensions: 22-1/2 inches wide by 31 inches deep by 32-7/8 inches h.c. Venting:

1) Clearance to Combustibles: 02) Minimum Vent Size: 2 inches3) Maximum Vent Size: 3 inches4) Minimum Vent Length: 15 feet5) Maximum Vent Length: 100 feet

d. Airflow and Cooling1) Motor Type and Size ECM EON: 3/4 hp2) Recommended AC Tonnage: 2, 3, 4 and 5

6. Series: NUV100T5B with ECM EON Motor:a. Heating Capacity

1) Efficiency (AFUE): 97 percent2) Input BTU/hr 0-4500': 100,0003) Output BTU/hr 0-4500': 97,000

b. Cabinet Dimensions: 22-1/2 inches wide by 29-1/2 inches deep by 32-7/8 inches h.

c. Venting:1) Clearance to Combustibles: 02) Minimum Vent Size: 2 inches3) Maximum Vent Size: 3 inches4) Minimum Vent Length: 15 feet5) Maximum Vent Length: 100 feet

d. Airflow and Cooling1) Motor Type and Size ECM EON: 3/4 hp2) Recommended AC Tonnage: 2, 3, 4 and 5

7. Series: NUV120T5B with ECM EON Motor:a. Heating Capacity (NG)

1) Efficiency (AFUE): 97 percent2) Input BTU/hr 0-4500': 120,0003) Output BTU/hr 0-4500': 116,000

23 50 00-13

Page 14: €¦ · Web viewNapoleon Ductless Multi-Zone Heat Pumps and Air Conditioners: General: Multi-zone offers up to 4 indoor units that operate from one, outdoor air condenser. Indoor

b. Cabinet Dimensions: 22-1/2 inches wide by 29-1/2 inches deep by 32-7/8 inches h.

c. Venting:1) Clearance to Combustibles: 02) Minimum Vent Size: 3 inches3) Maximum Vent Size: 3 inches4) Minimum Vent Length: 15 feet5) Maximum Vent Length: 100 feet

d. Airflow and Cooling1) Motor Type and Size ECM EON: 1 hp2) Recommended AC Tonnage: 2, 3, 4 and 5

8. Series: WUV040T2AA-N with ECM CC Motor:a. Heating Capacity

1) Efficiency (AFUE): 97 percent2) High Fire Input BTU/hr: 40,0003) Low Fire Input BTU/hr: 24,000

b. Cabinet Dimensions: 17-1/2 inches wide by 31 inches deep by 34 inches h.c. Venting:

1) Clearance to Combustibles: 02) Minimum Vent Size: 1-1/2 inches3) Maximum Vent Size: 2 inches4) Minimum Vent Length: 15 feet5) Maximum Vent Length: 75 feet

d. Airflow and Cooling1) Motor Type and Size ECM CC: 1/3 hp2) Recommended AC Tonnage: 1-1/2, 2, and 2-1/2

9. Series: WUV060T3AA-N with ECM CC Motor:a. Heating Capacity

1) Efficiency (AFUE): 97 percent2) High Fire Input BTU/hr: 60,0003) High Fire Input BTU/hr: 36,000

b. Cabinet Dimensions: 17-1/2 inches wide by 31 inches deep by 34 inches h.c. Venting:

1) Clearance to Combustibles: 02) Minimum Vent Size: 1-1/2 inches3) Maximum Vent Size: 3 inches4) Minimum Vent Length: 15 feet5) Maximum Vent Length: 100 feet

d. Airflow and Cooling1) Motor Type and Size ECM CC: 1/2 hp2) Recommended AC Tonnage: 1-1/2, 2, 2-1/2 and 3

10. Series: WUV080T3AA-N with ECM CC Motor:a. Heating Capacity

1) Efficiency (AFUE): 97 percent2) High Fire Input BTU/hr: 80,0003) High Fire Input BTU/hr: 48,000

b. Cabinet Dimensions: 17-1/2 inches wide by 31 inches deep by 34 inches h..c. Venting:

1) Clearance to Combustibles: 02) Minimum Vent Size: 2 inches3) Maximum Vent Size: 3 inches4) Minimum Vent Length: 15 feet5) Maximum Vent Length: 100 feet

d. Airflow and Cooling1) Motor Type and Size ECM CC: 1/2 hp2) Recommended AC Tonnage: 1-1/2, 2, 2-1/2 and 3

23 50 00-14

Page 15: €¦ · Web viewNapoleon Ductless Multi-Zone Heat Pumps and Air Conditioners: General: Multi-zone offers up to 4 indoor units that operate from one, outdoor air condenser. Indoor

11. Series: WUV080T4BA-N with ECM CC Motor:a. Heating Capacity

1) Efficiency (AFUE): 97 percent2) High Fire Input BTU/hr: 80,0003) High Fire Input BTU/hr: 48,000

b. Cabinet Dimensions: 22-1/2 inches wide by 31 inches deep by 34 inches h.c. Venting:

1) Clearance to Combustibles: 02) Minimum Vent Size: 2 inches3) Maximum Vent Size: 3 inches4) Minimum Vent Length: 15 feet5) Maximum Vent Length: 100 feet

d. Airflow and Cooling1) Motor Type and Size ECM CC: 3/4 hp2) Recommended AC Tonnage: 2, 2-1/2, 3 and 4

12. Series: WUV100T5B-N with ECM CC Motor:a. Heating Capacity

1) Efficiency (AFUE): 97 percent2) High Fire Input BTU/hr: 100,0003) High Fire Input BTU/hr: 60,000

b. Cabinet Dimensions: 22-1/2 inches wide by 31 inches deep by 34 inches h.c. Venting:

1) Clearance to Combustibles: 02) Minimum Vent Size: 2 inches3) Maximum Vent Size: 3 inches4) Minimum Vent Length: 15 feet5) Maximum Vent Length: 100 feet

d. Airflow and Cooling1) Motor Type and Size ECM CC: 3/4 hp2) Recommended AC Tonnage: 2-1/2, 3, 4 and 5

13. Series: WUV120T5BA-N with ECM CC Motor:a. Heating Capacity (NG)

1) Efficiency (AFUE): 97 percent2) High Fire Input BTU/hr: 120,0003) High Fire Input BTU/hr: 72,000

b. Cabinet Dimensions: 22-1/2 inches wide by 31 inches deep by 34 inches h.c. Venting:

1) Clearance to Combustibles: 02) Minimum Vent Size: 3 inches3) Maximum Vent Size: 3 inches4) Minimum Vent Length: 15 feet5) Maximum Vent Length: 100 feet

d. Airflow and Cooling1) Motor Type and Size ECM CC: 1 hp2) Recommended AC Tonnage: 2-/2, 3, 4 and 5

2.3 CENTRAL AIR CONDITIONERS

A. Napoleon Central Air Conditioner (13 SEER):1. General:

a. Motor: Permanently lubricated PSC - Permanent Split Capacitor motorb. Compressor: Copland scroll compressor with built-in temperature and pressure

protectionc. Refrigerant: R-410Ad. Coils: All aluminum micro-channel coilse. Cabinet: Powder coated louvered cabinet tested to withstand 1000 hour salt

23 50 00-15

Page 16: €¦ · Web viewNapoleon Ductless Multi-Zone Heat Pumps and Air Conditioners: General: Multi-zone offers up to 4 indoor units that operate from one, outdoor air condenser. Indoor

spray testing.2. Model NT13A018A:

a. Cooling Capacity:1) Nominal Size. 1.5 T2) Capacity BTU/H: 18,9003) Power: 208/230V, 60 Hz, 1 Phase,4) Fan Blade Diameter/Quantity: 18 inch/45) Condenser/Fan: 0.7 FLA, 1/8 HP, 1075 RPM.6) MCA: 12.07) Maximum Fuse/Breaker: 20 amp8) Liquid Line: 3/8 inch9) Suction Line: 3/4 inch

b. Dimensions: 24 inches wide by 27 inches high by 24 inches deep.3. Model NT13A024A:

a. Cooling Capacity:1) Nominal Size. 2.0 T2) Capacity BTU/H: 23,4003) Power: 208/230V, 60 Hz, 1 Phase,4) Fan Blade Diameter/Quantity: 18 inch/45) Condenser/Fan: 0.7 FLA, 1/8 HP, 1075 RPM.6) MCA: 17.67) Maximum Fuse/Breaker: 30 amp8) Liquid Line: 3/8 inch9) Suction Line: 3/4 inch

b. Dimensions: 24 inches wide by 27 inches high by 24 inches deep.4. Model NT13A030A:

a. Cooling Capacity:1) Nominal Size. 2.5 T2) Capacity BTU/H: 27,2003) Power: 208/230V, 60 Hz, 1 Phase,4) Fan Blade Diameter/Quantity: 24 inch/25) Condenser/Fan: 0.8 FLA, 1/6 HP, 850 RPM.6) MCA: 16.87) Maximum Fuse/Breaker: 25 amp8) Liquid Line: 3/8 inch9) Suction Line: 3/4 inch

b. Dimensions: 29.5 inches wide by 27 inches high by 29.5 inches deep.5. Model NT13A036A:

a. Cooling Capacity:1) Nominal Size. 3.0 T2) Capacity BTU/H: 34,6003) Power: 208/230V, 60 Hz, 1 Phase,4) Fan Blade Diameter/Quantity: 24 inch/25) Condenser/Fan: 0.8 FLA, 1/6 HP, 850 RPM.6) MCA: 21.77) Maximum Fuse/Breaker: 35 amp8) Liquid Line: 3/8 inch9) Suction Line: 3/4 inch

b. Dimensions: 29.5 inches wide by 27 inches high by 29.5 inches deep.6. Model NT13A042A:

a. Cooling Capacity:1) Nominal Size. 3.5 T2) Capacity BTU/H: 40,0003) Power: 208/230V, 60 Hz, 1 Phase,4) Fan Blade Diameter/Quantity: 24 inch/25) Condenser/Fan: 0.8 FLA, 1/6 HP, 850 RPM.

23 50 00-16

Page 17: €¦ · Web viewNapoleon Ductless Multi-Zone Heat Pumps and Air Conditioners: General: Multi-zone offers up to 4 indoor units that operate from one, outdoor air condenser. Indoor

6) MCA: 23.27) Maximum Fuse/Breaker: 40 amp8) Liquid Line: 3/8 inch9) Suction Line: 7/8 inch

b. Dimensions: 29.5 inches wide by 38-7/8 inches high by 29.5 inches deep.7. Model NT13A048A:

a. Cooling Capacity:1) Nominal Size. 4.0 T2) Capacity BTU/H: 44,5003) Power: 208/230V, 60 Hz, 1 Phase,4) Fan Blade Diameter/Quantity: 24 inch/25) Condenser/Fan: 0.8 FLA, 1/6 HP, 850 RPM.6) MCA: 25.77) Maximum Fuse/Breaker: 45 amp8) Liquid Line: 3/8 inch9) Suction Line: 7/8 inch

b. Dimensions: 29.5 inches wide by 38-7/8 inches high by 29.5 inches deep.8. Model NT13A060A:

a. Cooling Capacity:1) Nominal Size. 5.0 T2) Capacity BTU/H: 54,5003) Power: 208/230V, 60 Hz, 1 Phase,4) Fan Blade Diameter/Quantity: 24 inch/25) Condenser/Fan: 1.1 FLA, 1/5 HP, 850 RPM.6) MCA: 34.17) Maximum Fuse/Breaker: 60 amp8) Liquid Line: 3/8 inch9) Suction Line: 7/8 inch

b. Dimensions: 29.5 inches wide by 38-7/8 inches high by 29.5 inches deep.

B. Napoleon Central Air Conditioner (14 SEER):1. General:

a. Motor: Permanently lubricated PSC - Permanent Split Capacitor motorb. Compressor: Copland scroll compressor with built-in temperature and pressure

protectionc. Refrigerant: R-410Ad. Coils: All aluminum micro-channel coilse. Cabinet: Powder coated louvered cabinet tested to withstand 1000 hour salt

spray testing.2. Model NT14A018A:

a. Cooling Capacity:1) Nominal Size. 1.5 T2) Capacity BTU/H: 18,8003) Power: 208/230V, 60 Hz, 1 Phase,4) Fan Blade Diameter/Quantity: 18 inch/45) Condenser/Fan: 0.7 FLA, 1/8 HP, 1075 RPM.6) MCA: 12.07) Maximum Fuse/Breaker: 20 amp8) Liquid Line: 3/8 inch9) Suction Line: 3/4 inch

b. Dimensions: 24 inches wide by 27 inches high by 24 inches deep.3. Model NT14A024B:

a. Cooling Capacity:1) Nominal Size. 2.0 T2) Capacity BTU/H: 23,4003) Power: 208/230V, 60 Hz, 1 Phase,

23 50 00-17

Page 18: €¦ · Web viewNapoleon Ductless Multi-Zone Heat Pumps and Air Conditioners: General: Multi-zone offers up to 4 indoor units that operate from one, outdoor air condenser. Indoor

4) Fan Blade Diameter/Quantity: 18 inch/45) Condenser/Fan: 0.7 FLA, 1/8 HP, 1075 RPM.6) MCA: 14.37) Maximum Fuse/Breaker: 25 amp8) Liquid Line: 3/8 inch9) Suction Line: 3/4 inch

b. Dimensions: 24 inches wide by 27 inches high by 24 inches deep.4. Model NT14A030B: (14.5 SEER)

a. Cooling Capacity:1) Nominal Size. 2.5 T2) Capacity BTU/H: 28,6003) Power: 208/230V, 60 Hz, 1 Phase,4) Fan Blade Diameter/Quantity: 24 inch/25) Condenser/Fan: 0.8 FLA, 1/6 HP, 850 RPM.6) MCA: 16.87) Maximum Fuse/Breaker: 25 amp8) Liquid Line: 3/8 inch9) Suction Line: 3/4 inch

b. Dimensions: 29.5 inches wide by 27 inches high by 29.5 inches deep.5. Model NT14A036B:

a. Cooling Capacity:1) Nominal Size. 3.0 T2) Capacity BTU/H: 33,8003) Power: 208/230V, 60 Hz, 1 Phase,4) Fan Blade Diameter/Quantity: 24 inch/25) Condenser/Fan: 0.8 FLA, 1/6 HP, 850 RPM.6) MCA: 18.47) Maximum Fuse/Breaker: 30 amp8) Liquid Line: 3/8 inch9) Suction Line: 3/4 inch

b. Dimensions: 29.5 inches wide by 27 inches high by 29.5 inches deep.6. Model NT14A042B:

a. Cooling Capacity:1) Nominal Size. 3.5 T2) Capacity BTU/H: 38,0003) Power: 208/230V, 60 Hz, 1 Phase,4) Fan Blade Diameter/Quantity: 24 inch/25) Condenser/Fan: 0.8 FLA, 1/6 HP, 850 RPM.6) MCA: 21.77) Maximum Fuse/Breaker: 35 amp8) Liquid Line: 3/8 inch9) Suction Line: 7/8 inch

b. Dimensions: 29.5 inches wide by 38-7/8 inches high by 29.5 inches deep.7. Model NT14A048B:

a. Cooling Capacity:1) Nominal Size. 4.0 T2) Capacity BTU/H: 44,0003) Power: 208/230V, 60 Hz, 1 Phase,4) Fan Blade Diameter/Quantity: 24 inch/25) Condenser/Fan: 0.8 FLA, 1/6 HP, 850 RPM.6) MCA: 22.17) Maximum Fuse/Breaker: 35 amp8) Liquid Line: 3/8 inch9) Suction Line: 7/8 inch

b. Dimensions: 29.5 inches wide by 38-7/8 inches high by 29.5 inches deep.8. Model NT14A060B:

23 50 00-18

Page 19: €¦ · Web viewNapoleon Ductless Multi-Zone Heat Pumps and Air Conditioners: General: Multi-zone offers up to 4 indoor units that operate from one, outdoor air condenser. Indoor

a. Cooling Capacity:1) Nominal Size. 5.0 T2) Capacity BTU/H: 53,5003) Power: 208/230V, 60 Hz, 1 Phase,4) Fan Blade Diameter/Quantity: 24 inch/25) Condenser/Fan: 1.1 FLA, 1/5 HP, 850 RPM.6) MCA: 30.77) Maximum Fuse/Breaker: 50 amp8) Liquid Line: 3/8 inch9) Suction Line: 7/8 inch

b. Dimensions: 29.5 inches wide by 47-3/4 inches high by 29.5 inches deep.

C. Napoleon Central Air Conditioner (15 SEER):1. General:

a. Motor: Permanently lubricated PSC - Permanent Split Capacitor motorb. Compressor: Copland scroll compressor with built-in temperature and pressure

protectionc. Refrigerant: R-410Ad. Coils: All aluminum micro-channel coilse. Cabinet: Powder coated louvered cabinet tested to withstand 1000 hour salt

spray testing.2. Model NT16A018B:

a. Cooling Capacity:1) Nominal Size. 1.5 T2) Capacity BTU/H: 19,1003) Power: 208/230V, 60 Hz, 1 Phase,4) Fan Blade Diameter/Quantity: 24 inch/25) Condenser/Fan: 0.65 FLA, 1/8 HP, 850 RPM.6) MCA: 11.97) Maximum Fuse/Breaker: 20 amp8) Liquid Line: 3/8 inch9) Suction Line: 3/4 inch

b. Dimensions: 29 inches wide by 27 inches high by 29.5 inches deep.3. Model NT16A024B:

a. Cooling Capacity:1) Nominal Size. 2.0 T2) Capacity BTU/H: 24,0003) Power: 208/230V, 60 Hz, 1 Phase,4) Fan Blade Diameter/Quantity: 24 inch/25) Condenser/Fan: 0.65 FLA, 1/8 HP, 85 RPM.6) MCA: 14.37) Maximum Fuse/Breaker: 25 amp8) Liquid Line: 3/8 inch9) Suction Line: 3/4 inch

b. Dimensions: 29.5 inches wide by 27 inches high by 29.5 inches deep.4. Model NT16A030B:

a. Cooling Capacity:1) Nominal Size. 2.5 T2) Capacity BTU/H: 29,4003) Power: 208/230V, 60 Hz, 1 Phase,4) Fan Blade Diameter/Quantity: 24 inch/25) Condenser/Fan: 0.8 FLA, 2/16 HP, 850 RPM.6) MCA: 16.87) Maximum Fuse/Breaker: 25 amp8) Liquid Line: 3/8 inch9) Suction Line: 3/4 inch

23 50 00-19

Page 20: €¦ · Web viewNapoleon Ductless Multi-Zone Heat Pumps and Air Conditioners: General: Multi-zone offers up to 4 indoor units that operate from one, outdoor air condenser. Indoor

b. Dimensions: 29.5 inches wide by 27 inches high by 29.5 inches deep.5. Model NT16A036B:

a. Cooling Capacity:1) Nominal Size. 3.0 T2) Capacity BTU/H: 35,8003) Power: 208/230V, 60 Hz, 1 Phase,4) Fan Blade Diameter/Quantity: 24 inch/25) Condenser/Fan: 0.8 FLA, 1/6 HP, 850 RPM.6) MCA: 18.47) Maximum Fuse/Breaker: 30 amp8) Liquid Line: 3/8 inch9) Suction Line: 3/4 inch

b. Dimensions: 29.5 inches wide by 38-7/8 inches high by 29.5 inches deep.6. Model NT16A042B:

a. Cooling Capacity:1) Nominal Size. 3.5 T2) Capacity BTU/H: 41,0003) Power: 208/230V, 60 Hz, 1 Phase,4) Fan Blade Diameter/Quantity: 24 inch/25) Condenser/Fan: 0.8 FLA, 1/6 HP, 850 RPM.6) MCA: 21.77) Maximum Fuse/Breaker: 35 amp8) Liquid Line: 3/8 inch9) Suction Line: 7/8 inch

b. Dimensions: 29.5 inches wide by 38-7/8 inches high by 29.5 inches deep.7. Model NT16A048B:

a. Cooling Capacity:1) Nominal Size. 4.0 T2) Capacity BTU/H: 45,0003) Power: 208/230V, 60 Hz, 1 Phase,4) Fan Blade Diameter/Quantity: 24 inch/25) Condenser/Fan: 1.1 FLA, 1/5 HP, 850 RPM.6) MCA: 22.47) Maximum Fuse/Breaker: 35 amp8) Liquid Line: 3/8 inch9) Suction Line: 7/8 inch

b. Dimensions: 29.5 inches wide by 47-3/4 inches high by 29.5 inches deep.8. Model NT16A060B:

a. Cooling Capacity:1) Nominal Size. 5.0 T2) Capacity BTU/H: 56,5003) Power: 208/230V, 60 Hz, 1 Phase,4) Fan Blade Diameter/Quantity: 24 inch/25) Condenser/Fan: 1.1 FLA, 1/5 HP, 850 RPM.6) MCA: 30.77) Maximum Fuse/Breaker: 50 amp8) Liquid Line: 3/8 inch9) Suction Line: 7/8 inch

b. Dimensions:1) 27-7/8 inches wide by 44-7/8 inches high2) 29.5 inches deep.

D. Element Central Air Conditioner (13 SEER):1. General:

a. Compressor: High efficiency scroll compressor with built-in temperature and pressure protection

23 50 00-20

Page 21: €¦ · Web viewNapoleon Ductless Multi-Zone Heat Pumps and Air Conditioners: General: Multi-zone offers up to 4 indoor units that operate from one, outdoor air condenser. Indoor

b. Refrigerant: R-410Ac. Coils: All aluminum fin coilsd. Cabinet: Powder coated louvered galvanized steel cabinet.

2. Model WOVA-18CN1-M13T-N:a. Cooling Capacity:

1) Nominal Size. 1.5 T2) Capacity BTU/H: 18,0003) Power: 208/230V, 60 Hz, 1 Phase,4) MOP: 20 amp5) Liquid Line: 3/8 inch6) Suction Line: 3/4 inch7) Dimensions: 21-7/8 inches wide by 24-15/16 inches high by 21-7/8

inches deep.3. Model WOVA-24CN1-M13T-N:

a. Cooling Capacity:1) Nominal Size. 2 T2) Capacity BTU/H: 24,0003) Power: 208/230V, 60 Hz, 1 Phase,4) MOP: 30 amp5) Liquid Line: 3/8 inch6) Suction Line: 3/4 inch7) Dimensions: 23-5/8 inches wide by 24-15/16 inches high by 23-5/8

inches deep.4. Model WOVA-30CN1-M13T-N:

a. Cooling Capacity:1) Nominal Size. 2.5 T2) Capacity BTU/H: 30,0003) Power: 208/230V, 60 Hz, 1 Phase,4) MOP: 30 amp5) Liquid Line: 3/8 inch6) Suction Line: 3/4 inch7) Dimensions: 28 inches wide by 24-15/16 inches high by 28 inches deep.

5. Model WOVA-36CN1-M13T-N:a. Cooling Capacity:

1) Nominal Size. 3 T2) Capacity BTU/H: 36,0003) Power: 208/230V, 60 Hz, 1 Phase,4) MOP: 35 amp5) Liquid Line: 3/8 inch6) Suction Line: 3/4 inch7) Dimensions: 29-1/8 inches wide by 24-15/16 inches high by 29-1/8

inches deep.6. Model WOVA-42CN1-M13T-N:

a. Cooling Capacity:1) Nominal Size. 3.5 T2) Capacity BTU/H: 42,0003) Power: 208/230V, 60 Hz, 1 Phase,4) MOP: 40 amp5) Liquid Line: 3/8 inch6) Suction Line: 3/4 inch7) Dimensions: 28 inches wide by 33-3/16 inches high by 28 inches deep.

7. Model WOVA-48CN1-M13T-N:a. Cooling Capacity:

1) Nominal Size. 4 T2) Capacity BTU/H: 48,0003) Power: 208/230V, 60 Hz, 1 Phase,

23 50 00-21

Page 22: €¦ · Web viewNapoleon Ductless Multi-Zone Heat Pumps and Air Conditioners: General: Multi-zone offers up to 4 indoor units that operate from one, outdoor air condenser. Indoor

4) MOP: 50 amp5) Liquid Line: 3/8 inch6) Suction Line: 7/8 inch7) Dimensions: 28 inches wide by 33-3/16 inches high by 28 inches deep.

8. Model WOVA-60CN1-M13T-N:a. Cooling Capacity:

1) Nominal Size. 5 T2) Capacity BTU/H: 60,0003) Power: 208/230V, 60 Hz, 1 Phase,4) MOP: 60 amp5) Liquid Line: 3/8 inch6) Suction Line: 7/8 inch7) Dimensions: 29-1/8 inches wide by 33-3/16 inches high by 29-1/8 inches

deep.

E. Element Central Air Conditioner (14 SEER):1. General:

a. Compressor: High efficiency scroll compressor with built-in temperature and pressure protection

b. Refrigerant: R-410Ac. Coils: All aluminum fin coilsd. Cabinet: Powder coated louvered galvanized steel cabinet.

2. Model WOVA-18CN1-M14T-N:a. Cooling Capacity:

1) Nominal Size. 1.5 T2) Capacity BTU/H: 18,0003) Power: 208/230V, 60 Hz, 1 Phase,4) MOP: 20 amp5) Liquid Line: 3/8 inch6) Suction Line: 3/4 inch7) Dimensions: 21-7/8 inches wide by 24-15/16 inches high by 21-7/8

inches deep.3. Model WOVA-24CN1-M14T-N:

a. Cooling Capacity:1) Nominal Size. 2 T2) Capacity BTU/H: 24,0003) Power: 208/230V, 60 Hz, 1 Phase,4) MOP: 30 amp5) Liquid Line: 3/8 inch6) Suction Line: 3/4 inch7) Dimensions: 23-5/8 inches wide by 24-15/16 inches high by 23-5/8

inches deep.4. Model WOVA-30CN1-M14T-N:

a. Cooling Capacity:1) Nominal Size. 2.5 T2) Capacity BTU/H: 30,0003) Power: 208/230V, 60 Hz, 1 Phase,4) MOP: 30 amp5) Liquid Line: 3/8 inch6) Suction Line: 3/4 inch7) Dimensions: 28 inches wide by 24-15/16 inches high by 28 inches deep.

5. Model WOVA-36CN1-M14T-N:a. Cooling Capacity:

1) Nominal Size. 3 T2) Capacity BTU/H: 36,0003) Power: 208/230V, 60 Hz, 1 Phase,

23 50 00-22

Page 23: €¦ · Web viewNapoleon Ductless Multi-Zone Heat Pumps and Air Conditioners: General: Multi-zone offers up to 4 indoor units that operate from one, outdoor air condenser. Indoor

4) MOP: 35 amp5) Liquid Line: 3/8 inch6) Suction Line: 3/4 inch7) Dimensions: 29-1/8 inches wide by 24-15/16 inches high by 29-1/8

inches deep.6. Model WOVA-42CN1-M14T-N:

a. Cooling Capacity:1) Nominal Size. 3.5 T2) Capacity BTU/H: 42,0003) Power: 208/230V, 60 Hz, 1 Phase,4) MOP: 40 amp5) Liquid Line: 3/8 inch6) Suction Line: 3/4 inch7) Dimensions: 28 inches wide by 33-3/16 inches high by 28 inches deep.

7. Model WOVA-48CN1-M14T-N:a. Cooling Capacity:

1) Nominal Size. 4 T2) Capacity BTU/H: 48,0003) Power: 208/230V, 60 Hz, 1 Phase,4) MOP: 50 amp5) Liquid Line: 3/8 inch6) Suction Line: 7/8 inch7) Dimensions: 28 inches wide by 33-3/16 inches high by 28 inches deep.

8. Model WOVA-60CN1-M14T-N:a. Cooling Capacity:

1) Nominal Size. 5 T2) Capacity BTU/H: 60,0003) Power: 208/230V, 60 Hz, 1 Phase,4) MOP: 60 amp5) Liquid Line: 3/8 inch6) Suction Line: 7/8 inch7) Dimensions: 29-1/8 inches wide by 33-3/16 inches high by 29-1/8 inches

deep.

F. Element Central Air Conditioner (16 SEER):1. General:

a. Compressor: High efficiency scroll compressor with built-in temperature and pressure protection

b. Refrigerant: R-410Ac. Coils: All aluminum fin coilsd. Cabinet: Powder coated louvered galvanized steel cabinet.

2. Model WOVA-18CN1-M16T-N:a. Cooling Capacity:

1) Nominal Size. 1.5 T2) Capacity BTU/H: 18,0003) Power: 208/230V, 60 Hz, 1 Phase,4) MOP: 20 amp5) Liquid Line: 3/8 inch6) Suction Line: 3/4 inch7) Dimensions: 28 inches wide by 24-15/16 inches high by 28 inches deep.

3. Model WOVA-24CN1-M16T-N:a. Cooling Capacity:

1) Nominal Size. 2 T2) Capacity BTU/H: 24,0003) Power: 208/230V, 60 Hz, 1 Phase,4) MOP: 30 amp

23 50 00-23

Page 24: €¦ · Web viewNapoleon Ductless Multi-Zone Heat Pumps and Air Conditioners: General: Multi-zone offers up to 4 indoor units that operate from one, outdoor air condenser. Indoor

5) Liquid Line: 3/8 inch6) Suction Line: 3/4 inch7) Dimensions: 29-1/8 inches wide by 24-15/16 inches high by 29-1/8

inches deep.4. Model WOVA-30CN1-M16T-N:

a. Cooling Capacity:1) Nominal Size. 2.5 T2) Capacity BTU/H: 30,0003) Power: 208/230V, 60 Hz, 1 Phase,4) MOP: 30 amp5) Liquid Line: 3/8 inch6) Suction Line: 3/4 inch7) Dimensions: 28 inches wide by 24-15/16 inches high by 28 inches deep.

5. Model WOVA-36CN1-M16T-N:a. Cooling Capacity:

1) Nominal Size. 3 T2) Capacity BTU/H: 36,0003) Power: 208/230V, 60 Hz, 1 Phase,4) MOP: 35 amp5) Liquid Line: 3/8 inch6) Suction Line: 3/4 inch7) Dimensions: 29-1/8 inches wide by 24-15/16 inches high by 29-1/8

inches deep.6. Model WOVA-42CN1-M16T-N:

a. Cooling Capacity:1) Nominal Size. 3.5 T2) Capacity BTU/H: 42,0003) Power: 208/230V, 60 Hz, 1 Phase,4) MOP: 40 amp5) Liquid Line: 3/8 inch6) Suction Line: 3/4 inch7) Dimensions: Dimensions: 29-1/8 inches wide by 24-15/16 inches high by

29-1/8 inches deep.7. Model WOVA-48CN1-M16T-N:

a. Cooling Capacity:1) Nominal Size. 4 T2) Capacity BTU/H: 48,0003) Power: 208/230V, 60 Hz, 1 Phase,4) MOP: 50 amp5) Liquid Line: 3/8 inch6) Suction Line: 7/8 inch7) Dimensions: Dimensions: 29-1/8 inches wide by 24-15/16 inches high by

29-1/8 inches deep.8. Model WOVA-60CN1-M16T-N:

a. Cooling Capacity:1) Nominal Size. 5 T2) Capacity BTU/H: 60,0003) Power: 208/230V, 60 Hz, 1 Phase,4) MOP: 60 amp5) Liquid Line: 3/8 inch6) Suction Line: 7/8 inch7) Dimensions: 29-1/8 inches wide by 24-15/16 inches high by 29-1/8

inches deep.

2.4 CENTRAL HEAT PUMPS

23 50 00-24

Page 25: €¦ · Web viewNapoleon Ductless Multi-Zone Heat Pumps and Air Conditioners: General: Multi-zone offers up to 4 indoor units that operate from one, outdoor air condenser. Indoor

A. Element Central Heat Pumps: (14 SEER)1. General:

a. Compressor: High efficiency scroll compressorb. Refrigerant: R-410Ac. Coils: All aluminum fin coilsd. Compressor Crankcase heatere. High and low pressure switchf. Low pressure inspect valveg. Cabinet: Powder coated galvanized steel louvered cabinet.

2. Model WOVA-18HN1-M14C-N:a. Cooling Capacity: BTU/H: 18,000b. Heating Capacity: BTU/H: 18,000c. HSPF: 7.8d. Power: 208/230V, 60 Hz, 1 Phase,e. MOP: 20 ampf. Liquid Line: 3/8 inchg. Suction Line: 3/4 inchh. Dimensions: 21-7/8 inches wide by 24-15/16 inches high by 21-7/8 inches

deep.3. Model WOVA-24HN1-M14C-N:

a. Cooling Capacity: BTU/H: 23,800b. Heating Capacity: BTU/H: 23,800c. HSPF: 7.8d. Power: 208/230V, 60 Hz, 1 Phase,e. MOP: 30 ampf. Liquid Line: 3/8 inchg. Suction Line: 3/4 inchh. Dimensions: 23-5/8 inches wide by 24-15/16 inches high by 23-5/8 inches

deep.4. Model WOVA-30CH1-M14C-N:

a. Cooling Capacity: BTU/H: 30,000b. Heating Capacity: BTU/H: 30,000c. HSPF: 8.3d. Power: 208/230V, 60 Hz, 1 Phase,e. MOP: 30 ampf. Liquid Line: 3/8 inchg. Suction Line: 3/4 inchh. Dimensions: 28 inches wide by 24-15/16 inches high by 28 inches deep.

5. Model WOVA-36HN1-M14-N:a. Cooling Capacity: BTU/H: 36,000b. Heating Capacity: BTU/H: 36,000c. HSPF: 8.3d. Power: 208/230V, 60 Hz, 1 Phase,e. MOP: 35 ampf. Liquid Line: 3/8 inchg. Suction Line: 3/4 inchh. Dimensions: 29-1/8 inches wide by 24-15/16 inches high by 29-1/8 inches

deep.6. Model WOVA-42HN1-M14-N:

a. Cooling Capacity: BTU/H: 42,000b. Heating Capacity: BTU/H: 40,000c. HSPF: 8.3d. Power: 208/230V, 60 Hz, 1 Phase,e. MOP: 40 ampf. Liquid Line: 3/8 inchg. Suction Line: 3/4 inch

23 50 00-25

Page 26: €¦ · Web viewNapoleon Ductless Multi-Zone Heat Pumps and Air Conditioners: General: Multi-zone offers up to 4 indoor units that operate from one, outdoor air condenser. Indoor

h. Dimensions: 28 inches wide by 33-3/16 inches high by 28 inches deep.7. Model WOVA-48HN1-M14-N:

a. Cooling Capacity: BTU/H: 48,000b. Heating Capacity: BTU/H: 48,000c. HSPF: 8.3d. Power: 208/230V, 60 Hz, 1 Phase,e. MOP: 50 ampf. Liquid Line: 3/8 inchg. Suction Line: 7/8 inchh. Dimensions: 28 inches wide by 33-3/16 inches high by 28 inches deep.

8. Model WOVA-60HN1-M14-N:a. Cooling Capacity: BTU/H: 57,000b. Heating Capacity: BTU/H: 56,000c. HSPF: 8.3d. Power: 208/230V, 60 Hz, 1 Phase,e. MOP: 60 ampf. Liquid Line: 3/8 inchg. Suction Line: 7/8 inchh. Dimensions: 29-1/8 inches wide by 33-3/16 inches high by 29-1/8 inches deep.

B. Element Central Heat Pumps: (16 SEER)1. General:

a. Compressor: High efficiciency scroll compressorb. Refrigerant: R-410Ac. Coils: All aluminum fin coilsd. Compressor Crankcase heatere. High and low pressure switchf. Low pressure inspect valveg. Cabinet: Powder coated galvanized steel louvered cabinet.

2. Model WOVA-18HN1-M16-N:a. Cooling Capacity: BTU/H: 18,000b. Heating Capacity: BTU/H: 17,500c. HSPF: 9d. Power: 208/230V, 60 Hz, 1 Phase,e. MOP: 20 ampf. Liquid Line: 3/8 inchg. Suction Line: 3/4 inchh. Dimensions: 28 inches wide by 24-15/16 inches high by 28 inches deep.

3. Model WOVA-24HN1-M16-N:a. Cooling Capacity: BTU/H: 24,000b. Heating Capacity: BTU/H: 23,000c. HSPF: 9d. Power: 208/230V, 60 Hz, 1 Phase,e. MOP: 30 ampf. Liquid Line: 3/8 inchg. Suction Line: 3/4 inchh. Dimensions: 29-1/8 inches wide by 24-15/16 inches high by 29-1/8 inches

deep.4. Model WOVA-30HN1-M16-N:

a. Cooling Capacity: BTU/H: 30,000b. Heating Capacity: BTU/H: 29,000c. HSPF: 9d. Power: 208/230V, 60 Hz, 1 Phase,e. MOP: 30 ampf. Liquid Line: 3/8 inchg. Suction Line: 3/4 inch

23 50 00-26

Page 27: €¦ · Web viewNapoleon Ductless Multi-Zone Heat Pumps and Air Conditioners: General: Multi-zone offers up to 4 indoor units that operate from one, outdoor air condenser. Indoor

h. Dimensions: 28 inches wide by 24-15/16 inches high by 28 inches deep.5. Model WOVA-36HN1-M16-N:

a. Cooling Capacity: BTU/H: 36,000b. Heating Capacity: BTU/H: 35,000c. HSPF: 9d. Power: 208/230V, 60 Hz, 1 Phase,e. MOP: 35 ampf. Liquid Line: 3/8 inchg. Suction Line: 3/4 inchh. Dimensions: 29-1/8 inches wide by 24-15/16 inches high by 29-1/8 inches

deep.6. Model WOVA-42HN1-M16-N:

a. Cooling Capacity: BTU/H: 42,000b. Heating Capacity: BTU/H: 42,000c. HSPF: 9d. Power: 208/230V, 60 Hz, 1 Phase,e. MOP: 40 ampf. Liquid Line: 3/8 inchg. Suction Line: 3/4 inchh. Dimensions: Dimensions: 29-1/8 inches wide by 24-15/16 inches high by 29-1/8

inches deep.7. Model WOVA-48HN1-M16-N:

a. Cooling Capacity: BTU/H: 48,000b. Heating Capacity: BTU/H: 45,000c. HSPF: 9d. Power: 208/230V, 60 Hz, 1 Phase,e. MOP: 50 ampf. Liquid Line: 3/8 inchg. Suction Line: 7/8 inchh. Dimensions: Dimensions: 29-1/8 inches wide by 24-15/16 inches high by 29-1/8

inches deep.8. Model WOVA-60HN1-M16-N:

a. Cooling Capacity: BTU/H: 60,000b. Heating Capacity: BTU/H: 55,000c. HSPF: 9d. Power: 208/230V, 60 Hz, 1 Phase,e. MOP: 60 ampf. Liquid Line: 3/8 inchg. Suction Line: 7/8 inchh. Dimensions: 29-1/8 inches wide by 24-15/16 inches high by 29-1/8 inches

deep.

2.5 PACKAGED HEATING SYSTEMS

A. Element Mid-Efficiency Gas Furnace:1. General:

a. Multi speed PSC motor.b. Single-stage designc. Natural gas and propaned. Hot surface ignitione. Flex Fit installation options: horizontal left and right, upflow and downflow

2. Model WGS80M050A3A-Na. BTU /h: 50,000b. AFUE: 80 percentc. Dimensions: 14-1/2 inches wide by 28-1/2 inches high by 33-3/4 inches deep.d. Motor Type: PSC

23 50 00-27

Page 28: €¦ · Web viewNapoleon Ductless Multi-Zone Heat Pumps and Air Conditioners: General: Multi-zone offers up to 4 indoor units that operate from one, outdoor air condenser. Indoor

3. Model WGS80M070A3A-Na. BTU /h: 70,000b. AFUE: 80 percentc. Dimensions: 14-1/2 inches wide by 28-1/2 inches high by 33-3/4 inches deep.d. Motor Type: PSC

4. Model WGS80M080B4A-Na. BTU /h: 80,000b. AFUE: 80 percentc. Dimensions: 17-1/2 inches wide by 28-1/2 inches high by 33-3/4 inches deep.d. Motor Type: PSC

5. Model WGS80M090B4A-Na. BTU /h: 90,000b. AFUE: 80 percentc. Dimensions: 17-1/2 inches wide by 28-1/2 inches high by 33-3/4 inches deep.d. Motor Type: PSC

6. Model WGS80M110C5A-Na. BTU /h: 110,000b. AFUE: 80 percentc. Dimensions: 21 inches wide by 28-1/2 inches high by 33-3/4 inches deep.d. Motor Type: PSC

7. Model WGS80M135D5A-Na. BTU /h: 135,000b. AFUE: 80 percentc. Dimensions: 24-1/2 inches wide by 28-1/2 inches high by 33-3/4 inches deep.d. Motor Type: PSC

B. Element Gas Furnace Packaged Unit:1. General:

a. Single-stage gas (NG/LP) heatingb. Bottom or side air returnc. Aluminized steel tubular heat exchangerd. Quiet Multi-speed circulation blowere. Direct spark ignitionf. Secondary drain pipeg. AHRI Certified and ET Llisted

2. Model WRB24S060GWN1-M14-Na. SEER: 14b. Heating Capacity BTU/H: 60,000c. Cooling Capacity BTU/H: 22,700d. EER BTU/H: 11.1e. Compressor Type: GMCC-Rotaryf. Indoor Fan Motor: 1/3 HPg. Outdoor Fan Motor: 1/12 HPh. Dimensions: 57 inches wide by 44 inches high by 41 inches deep.

3. Model WRB30S060GWN1-M14-Na. SEER: 14b. Heating Capacity BTU/H: 60,000c. Cooling Capacity BTU/H: 29,000d. EER BTU/H: 11.4e. Compressor Type: GMCC-Rotaryf. Indoor Fan Motor: 1/3 HPg. Outdoor Fan Motor: 1/6 HPh. Dimensions: 57 inches wide by 44 inches high by 41 inches deep.

4. Model WRB36S090GWN1-M14-Na. SEER: 14b. Heating Capacity BTU/H: 90,000

23 50 00-28

Page 29: €¦ · Web viewNapoleon Ductless Multi-Zone Heat Pumps and Air Conditioners: General: Multi-zone offers up to 4 indoor units that operate from one, outdoor air condenser. Indoor

c. Cooling Capacity BTU/H: 35,000d. EER BTU/H: 11.9e. Compressor Type: LG - Scrollf. Indoor Fan Motor: 3/4 HPg. Outdoor Fan Motor: 1/6 HPh. Dimensions: 57 inches wide by 44 inches high by 41 inches deep.

5. Model WRB42S090GWN1-M14-Na. SEER: 14b. Heating Capacity BTU/H: 90,000c. Cooling Capacity BTU/H: 41,000d. EER BTU/H: 11.5e. Compressor Type: Copland Scrollf. Indoor Fan Motor: 3/4 HPg. Outdoor Fan Motor: 1/3 HPh. Dimensions: 57 inches wide by 44 inches high by 41 inches deep.

6. Model WRB48S090GWN1-M14-Na. SEER: 14b. Heating Capacity BTU/H: 110,000c. Cooling Capacity BTU/H: 47,000d. EER BTU/H: 11.2e. Compressor Type: LG-Scrollf. Indoor Fan Motor: 3/4 HPg. Outdoor Fan Motor: 1/3 HPh. Dimensions: 57 inches wide by 44 inches high by 41 inches deep.

7. Model WRB60S090GWN1-M14-Na. SEER: 14b. Heating Capacity BTU/H: 90,000c. Cooling Capacity BTU/H: 56,000d. EER BTU/H: 10.9e. Compressor Type: Copeland Scrollf. Indoor Fan Motor: 1HPg. Outdoor Fan Motor: 1/3 HPh. Dimensions: 57 inches wide by 44 inches high by 41 inches deep.

8. Model WRB60S130GWN1-M14-Na. SEER: 14b. Heating Capacity BTU/H: 1300,000c. Cooling Capacity BTU/H: 56,000d. EER BTU/H: 10.9e. Compressor Type: Copeland Scrollf. Indoor Fan Motor: 1 HPg. Outdoor Fan Motor: 1/3HPh. Dimensions: 57 inches wide by 44 inches high by 41 inches deep.

C. Element Air Handlers:1. General:

a. Anti-rust cabinet spray painted galvanized steel withstanding 500 hours of salt spray testing

b. Fully insulated design minimizes indoor noise levelc. Removable front panel allows blower and coil assemblies to slide-out for easy

service ability.d. Filter rack located at bottom for maintenance and installatione. Electric heaterf. Flex Fit installation options: horizontal left and right, vertical.

2. Model WVA-18HWN1-M13-Na. SEER: 14b. Dimensions: 18-1/8 inches wide by 20-1/2 inches high by 41-3/8 inches deep.

23 50 00-29

Page 30: €¦ · Web viewNapoleon Ductless Multi-Zone Heat Pumps and Air Conditioners: General: Multi-zone offers up to 4 indoor units that operate from one, outdoor air condenser. Indoor

c. Motor Type / Size: PSC - 1/8 HP3. Model WVA-24N1B-N

a. SEER: 14b. Dimensions: 19-5/8 inches wide by 22-5/8 inches high by 46-1/2inches deep.c. Motor Type / Size: PSC - 1/5 HP

4. Model WVA-30N1B-Na. SEER: 14b. Dimensions: 19-5/8 inches wide by 21-5/8 inches high by 46-1/2 inches deep.c. Motor Type / Size: PSC - 1/4 HP

5. Model WVA-36HWN1-M13-Na. SEER: 14b. Dimensions: 19-5/8 inches wide by 21-5/8 inches high by 46-1/2 inches deep.c. Motor Type / Size: PSC - 1/2 HP

6. Model WVA-42N1C-Na. SEER: 14b. Dimensions: 22 inches wide by 24 inches high by 54-1/2 inches deep.c. Motor Type / Size: PSC - 1/2 HP

7. Model WVA-48HWN1-M13-Na. SEER: 14b. Dimensions: 22 inches wide by 24 inches high by 54-1/2 inches deep.c. Motor Type / Size: PSC - 1/2 HP

8. Model WVA-60HWN1-M13-Na. SEER: 14b. Dimensions: 22 inches wide by 24 inches high by 54-1/2 inches deep.c. Motor Type / Size: PSC - 3/4 HP

9. Model WVA-18WN1-M16P-Na. SEER: 16b. Dimensions: 16-1/8 inches wide by 20-1/2 inches high by 41-3/8 inches deep.c. Motor Type / Size: PSC - 1/8 HP

10. Model WVA-24WN1-M16P-Na. SEER: 16b. Dimensions: 19-5/8 inches wide by 21-5/8 inches high by 46-1/2 inches deep.c. Motor Type: EMC

11. Model WVA-30WN1-M16P-Na. SEER: 16b. Dimensions: 19-5/8 inches wide by 21-5/8 inches high by 46-1/2 inches deep.c. Motor Type: EMC

12. Model WVA-36WN1-M16P-Na. SEER: 16b. Dimensions: 22 inches wide by 24 inches high by 54-1/2 inches deep.c. Motor Type: EMC

13. Model WVA-42WN1-M16P-Na. SEER: 16b. Dimensions: 22 inches wide by 24 inches high by 54-1/2 inches deep.c. Motor Type: EMC

14. Model WVA-48WN1-M16P-Na. SEER: 16b. Dimensions: 22 inches wide by 24 inches high by 54-1/2 inches deep.c. Motor Type: EMC

15. Model WVA-60WN1-M16P-Na. SEER: 16b. Dimensions: 22 inches wide by 24 inches high by 54-1/2 inches deep.c. Motor Type: EMC

D. Element Heat Pump (14 SEER) with Auxiliary Electric Heater:1. General:

23 50 00-30

Page 31: €¦ · Web viewNapoleon Ductless Multi-Zone Heat Pumps and Air Conditioners: General: Multi-zone offers up to 4 indoor units that operate from one, outdoor air condenser. Indoor

a. Auxiliary Electric Heaterb. Refrigerant: R-410Ac. Coils: All aluminum fin coilsd. High and low pressure switche. Low pressure inspect valvef. Cabinet: Powder coated galvanized steel louvered cabinet.

2. Model WRC-24HWN1-M14-N:a. Cooling Capacity: BTU/H: 22,400b. Heating Capacity: BTU/H: 22,800c. HSPF: 8.0d. Power: 208/230V, 60 Hz, 1 Phase,e. Dimensions: 52 inches wide by 25 inches high by 38 inches deep.

3. Model WRC -30HWN1-M14-N:a. Cooling Capacity: BTU/H: 30,000b. Heating Capacity: BTU/H: 30,000c. HSPF: 8.0d. Power: 208/230V, 60 Hz, 1 Phase,e. Dimensions: 52 inches wide by 25 inches high by 38 inches deep.

4. Model WRC -36HWN1-M14-N:a. Cooling Capacity: BTU/H: 34,200b. Heating Capacity: BTU/H: 34,200c. HSPF: 8.0d. Power: 208/230V, 60 Hz, 1 Phase,e. Dimensions: 52 inches wide by 25 inches high by 38 inches deep.

5. Model WRC -42HWN1-M14-N:a. Cooling Capacity: BTU/H: 42,000b. Heating Capacity: BTU/H: 40,500c. HSPF: 8.0d. Power: 208/230V, 60 Hz, 1 Phase,e. Dimensions: 58 inches wide by 33 inches high by 38 inches deep.

6. Model WRC -48HWN1-M14-N:a. Cooling Capacity: BTU/H: 46,500b. Heating Capacity: BTU/H: 46,500c. HSPF: 8.0d. Power: 208/230V, 60 Hz, 1 Phase,e. Dimensions: 58 inches wide by 33 inches high by 38 inches deep.

7. Model WRC -60HWN1-M14-N:a. Cooling Capacity: BTU/H: 57,000b. Heating Capacity: BTU/H: 57,000c. HSPF: 8.0d. Power: 208/230V, 60 Hz, 1 Phase,e. Dimensions: 58 inches wide by 33 inches high by 38 inches deep.

2.6 DUCTLESS HEAT PUMPS AND AIR CONDITIONERS

A. Napoleon Ductless Heat Pumps and Air Conditioners:1. General: Includes remote control for indoor unit and the following:

a. Designed to operate in temperatures as low as minus 30 degrees C / minus 22 degrees F.

b. Refrigeration leakage detection.c. Auto Defrostingd. Independent dehumidification.

2. Model: NC15-12Fa. Cooling Capacity: BTU/H: 12, 000b. Heating Capacity: BTU/H: -c. SEER: 15

23 50 00-31

Page 32: €¦ · Web viewNapoleon Ductless Multi-Zone Heat Pumps and Air Conditioners: General: Multi-zone offers up to 4 indoor units that operate from one, outdoor air condenser. Indoor

d. EER: 9e. HSPF4: -f. HSPF5: -g. Min. Amapacity: 10h. Max. Fuse: 15i. Power: 115V, 60 Hz, 1 Phase,j. Liquid Line: 1/4 inchk. Suction Line: 1/2 inchl. Indoor Dimensions: 30.31 inches wide by 7.4 inches high by 10.04 inches

deep.m. Outdoor Dimensions: 26 inches wide by 10.42 inches high by 21.3 inches deep.

3. Model: NC15-18Fa. Cooling Capacity: BTU/H: 18, 000b. Heating Capacity: BTU/H: -c. SEER: 15d. EER: 9e. HSPF4: -f. HSPF5: -g. Min. Amapacity: 20h. Max. Fuse: 15i. Power: 208/230V, 60 Hz, 1 Phasej. Liquid Line: 1/4 inchk. Suction Line: 1/2 inchl. Indoor Dimensions: 35.63 inches wide by 7.8 inches high by 10.83 inches

deep.m. Outdoor Dimensions: 29.92 inches wide by 11.22 inches high by 23.23 inches

deep.4. Model: NC15-24F

a. Cooling Capacity: BTU/H: 22, 000b. Heating Capacity: BTU/H: -c. SEER: 15d. EER: 9e. HSPF4: -f. HSPF5: -g. Min. Amapacity: 25h. Max. Fuse: 25i. Power: 208/230V, 60 Hz, 1 Phasej. Liquid Line: 3/8 inchk. Suction Line: 5/8 inchl. Indoor Dimensions: 40.55 inches wide by 8.58 inches high by 12.4 inches

deep.m. Outdoor Dimensions: 26 inches wide by 10.42 inches high by 21.3 inches deep.

5. Model: NLIS9F-Ba. Cooling Capacity: BTU/H: 9,000b. Heating Capacity: 10,700c. SEER: 16.4d. EER: 12.2e. HSPF4: 9.6f. HSPF5: 7.0g. Min. Amapacity: 15h. Max. Fuse: 20i. Power: 208/230V, 60 Hz, 1 Phase,j. Liquid Line: 1/4 inchk. Suction Line: 3/8 inchl. Indoor Dimensions: 31.1 inches wide by 7.8 inches high by 10.5 inches deep.m. Outdoor Dimensions: 30 inches wide by 11.25 inches high by 23.25 inches

23 50 00-32

Page 33: €¦ · Web viewNapoleon Ductless Multi-Zone Heat Pumps and Air Conditioners: General: Multi-zone offers up to 4 indoor units that operate from one, outdoor air condenser. Indoor

deep.6. Model: NLIS12F-C

a. Cooling Capacity: BTU/H: 12,000b. Heating Capacity: BTU/H: 11,800c. SEER: 17.5d. EER: 11e. HSPF4: 9f. HSPF5: 7.5g. Min. Amapacity: 15h. Max. Fuse: 15i. Power: 208/230V, 60 Hz, 1 Phase,j. Liquid Line: 1/4 inchk. Suction Line: 3/8 inchl. Indoor Dimensions: 31.57 inches wide by 7.44 inches high by 11.69 inches

deep.m. Outdoor Dimensions: 30.31 inches wide by 11.81 inches high by 21.85 inches

deep.7. Model: NLIS18F-C

a. Cooling Capacity: BTU/H: 18,000b. Heating Capacity: BTU/H: 18,000c. SEER: 17.7d. EER: 11e. HSPF4: 9.8f. HSPF5: 7.5g. Min. Amapacity: 15h. Max. Fuse: 20i. Power: 208/230V, 60 Hz, 1 Phase,j. Liquid Line: 1/4 inchk. Suction Line: 3/8 inchl. Indoor Dimensions: 37.99 inches wide by 8.46 inches high by 12.56 inches

deep.m. Outdoor Dimensions: 31.5 inches wide by 13.11 inches high by 21.81 inches

deep.8. Model: NLIS24F-C

a. Cooling Capacity: BTU/H: 24,000b. Heating Capacity: BTU/H: 25,000c. SEER: 16.4d. EER: 9.5e. HSPF4: 9f. HSPF5: 7.2g. Min. Amapacity: 18h. Max. Fuse: 25i. Power: 208/230V, 60 Hz, 1 Phase,j. Liquid Line: 3/8 inchk. Suction Line: 5/8 inchl. Indoor Dimensions: 42.52 inches wide by 8.90 inches high by 13.19 inches

deep.m. Outdoor Dimensions: 33.27 inches wide by 14.29 inches high by 27.64 inches

deep9. Model: NH21-12F

a. Cooling Capacity: BTU/H: 12,000b. Heating Capacity: BTU/H: 12,000c. SEER: 21.5d. EER: 13e. HSPF4: 9.8f. HSPF5: 7.7

23 50 00-33

Page 34: €¦ · Web viewNapoleon Ductless Multi-Zone Heat Pumps and Air Conditioners: General: Multi-zone offers up to 4 indoor units that operate from one, outdoor air condenser. Indoor

g. Min. Amapacity: 12h. Max. Fuse: 15i. Power: 208/230V, 60 Hz, 1 Phase,j. Liquid Line: 1/4 inchk. Suction Line: 1/2 inchl. Indoor Dimensions: 31.57 inches wide by 7.44 inches high by 11.69 inches

deep.m. Outdoor Dimensions: 31.50 inches wide by 31.11 inches high by 21.81 inches

deep10. Model: NH21-18F

a. Cooling Capacity: BTU/H: 18,000b. Heating Capacity: BTU/H: 18,000c. SEER: 21d. EER: 13e. HSPF4: 10f. HSPF5: 8g. Min. Amapacity: 15h. Max. Fuse: 20i. Power: 208/230V, 60 Hz, 1 Phase,j. Liquid Line: 1/4 inchk. Suction Line: 1/2 inchl. Indoor Dimensions: 42.52 inches wide by 8.90 inches high by 13.19 inches

deep.m. Outdoor Dimensions: 33.27 inches wide by 14.29 inches high by 27.54 inches

deep11. Model: NH21-24F

a. Cooling Capacity: BTU/H: 24,000b. Heating Capacity: BTU/H: 24,000c. SEER: 20.5d. EER: 12.5e. HSPF4: 10f. HSPF5: 8.3g. Min. Amapacity: 18h. Max. Fuse: 25i. Power: 208/230V, 60 Hz, 1 Phase,j. Liquid Line: 3/8 inchk. Suction Line: 5/8 inchl. Indoor Dimensions: 42.52 inches wide by 8.90 inches high by 13.19 inches

deep.m. Outdoor Dimensions: 37.24 inches wide by 15.14 inches high by 31.89 inches

deep12. Model: NH25-09F

a. Cooling Capacity: BTU/H: 9,000b. Heating Capacity: BTU/H: 10,900c. SEER: 25d. EER: 14.5e. HSPF4: 11.2f. HSPF5: 9g. Min. Amapacity: 9h. Max. Fuse: 15i. Power: 208/230V, 60 Hz, 1 Phase,j. Liquid Line: 1/4 inchk. Suction Line: 3/8 inchl. Indoor Dimensions: 32.87 inches wide by 7.80 inches high by 11.02 inches

deep.m. Outdoor Dimensions: 31.5 inches wide by 13.11 inches high by 21.81 inches

23 50 00-34

Page 35: €¦ · Web viewNapoleon Ductless Multi-Zone Heat Pumps and Air Conditioners: General: Multi-zone offers up to 4 indoor units that operate from one, outdoor air condenser. Indoor

deep13. Model: NH25-12F

a. Cooling Capacity: BTU/H: 12,000b. Heating Capacity: BTU/H: 11,800c. SEER: 25d. EER: 14.5e. HSPF4: 11.2f. HSPF5: 9g. Min. Amapacity: 9h. Max. Fuse: 15i. Power: 208/230V, 60 Hz, 1 Phase,j. Liquid Line: 1/4 inchk. Suction Line: 3/8 inchl. Indoor Dimensions: 32.87 inches wide by 7.80 inches high by 11.02 inches

deep.m. Outdoor Dimensions: 31.5 inches wide by 13.11 inches high by 21.81 inches

deep14. Model: NH25-18F

a. Cooling Capacity: BTU/H: 17,000b. Heating Capacity: BTU/H: 18,000c. SEER: 20d. EER: 12.5e. HSPF4: 10.3f. HSPF5: 8.8g. Min. Amapacity: 18h. Max. Fuse: 25i. Power: 208/230V, 60 Hz, 1 Phase,j. Liquid Line: 1/4 inchk. Suction Line: 3/8 inchl. Indoor Dimensions: 38.98 inches wide by 8.58 inches high by 12.4 inches

deep.m. Outdoor Dimensions: 33.27 inches wide by 14.29 inches high by 27.64 inches

deep15. Model: NH25-24F

a. Cooling Capacity: BTU/H: 24,000b. Heating Capacity: BTU/H: 24,000c. SEER: 20.5d. EER: 12.5e. HSPF4: 11.5f. HSPF5: 9.6g. Min. Amapacity: 20h. Max. Fuse: 30i. Power: 208/230V, 60 Hz, 1 Phase,j. Liquid Line: 3/8 inchk. Suction Line: 5/8 inchl. Indoor Dimensions: 46.69 inches wide by 10.16 inches high by 13.39 inches

deep.m. Outdoor Dimensions: 37.2 inches wide by 16.14 inches high by 31.89 inches

deep16. Model: NH25-30F

a. Cooling Capacity: BTU/H: 30,000b. Heating Capacity: BTU/H: 30,000c. SEER: 19.8d. EER: 11.5e. HSPF4: 9.4f. HSPF5: 8

23 50 00-35

Page 36: €¦ · Web viewNapoleon Ductless Multi-Zone Heat Pumps and Air Conditioners: General: Multi-zone offers up to 4 indoor units that operate from one, outdoor air condenser. Indoor

g. Min. Amapacity: 20h. Max. Fuse: 30i. Power: 208/230V, 60 Hz, 1 Phase,j. Liquid Line: 3/8 inchk. Suction Line: 5/8 inchl. Indoor Dimensions: 46.69 inches wide by 10.16 inches high by 13.39 inches

deep.m. Outdoor Dimensions: 37.2 inches wide by 16.14 inches high by 31.89 inches

deep17. Model: NH25-36F

a. Cooling Capacity: BTU/H: 36,000b. Heating Capacity: BTU/H: 36,000c. SEER: 16d. EER: 8.6e. HSPF4: 8.5f. HSPF5: 7g. Min. Amapacity: 25h. Max. Fuse: 35i. Power: 208/230V, 60 Hz, 1 Phase,j. Liquid Line: 3/8 inchk. Suction Line: 5/8 inchl. Indoor Dimensions: 46.69 inches wide by 10.16 inches high by 13.39 inches

deep.m. Outdoor Dimensions: 37.2 inches wide by 16.14 inches high by 31.89 inches

deep

B. Napoleon Ductless Multi-Zone Heat Pumps and Air Conditioners:1. General: Multi-zone offers up to 4 indoor units that operate from one, outdoor air

condenser. Indoor options include wall mount units or cassettes. Cassettes install flush into the ceiling and through the remote control.a. Remote control.b. Designed to operate in temperatures as low as minus 30 degrees C / minus 22

degrees F.c. Refrigeration leakage detection.d. Auto Defrostinge. Independent dehumidification.

2. Model: NCASSETTE12a. Cooling Capacity BTU/H: -b. Heating Capacity BTU/H: -c. SEER: -d. EER: -e. HSPF4: -f. HSPF5: -g. Min. Amapacity: 1.3h. Max. Fuse: 15i. Power: 208/230V, 60 Hz, 1 Phasej. Liquid Line: 1/4 inchk. Suction Line: 1/2 inchl. Indoor Dimensions: 22.44 inches wide by 22.24 inches high by 10.24 inches

deep.m. Outdoor Dimensions: -

3. Model: NCASSETTE18a. Cooling Capacity BTU/H: -b. Heating Capacity BTU/H: -c. SEER: -d. EER: -

23 50 00-36

Page 37: €¦ · Web viewNapoleon Ductless Multi-Zone Heat Pumps and Air Conditioners: General: Multi-zone offers up to 4 indoor units that operate from one, outdoor air condenser. Indoor

e. HSPF4: -f. HSPF5: -g. Min. Amapacity: 1.9h. Max. Fuse: 15i. Power: 208/230V, 60 Hz, 1 Phasej. Liquid Line: 1/4 inchk. Suction Line: 1/2 inchl. Indoor Dimensions: 22.44 inches wide by 22.24 inches high by 10.24 inches

deep.m. Outdoor Dimensions: -

4. Model: NH21-09F-Ia. Cooling Capacity BTU/H: -b. Heating Capacity BTU/H: -c. SEER: -d. EER: -e. HSPF4: -f. HSPF5: -g. Min. Amapacity: 0.25h. Max. Fuse: 15i. Power: 208/230V, 60 Hz, 1 Phasej. Liquid Line: 1/4 inchk. Suction Line: 3/8 inchl. Indoor Dimensions: 31.25 inches wide by 10.5 inches high by 7.75 inches

deep.m. Outdoor Dimensions: 33.27 inches wide by 27.56 inches high by 12.6 inches

deep.5. Model: NH21-12F-I

a. Cooling Capacity BTU/H: -b. Heating Capacity BTU/H: -c. SEER: -d. EER: -e. HSPF4: -f. HSPF5: -g. Min. Amapacity: 0.25h. Max. Fuse: 15i. Power: 208/230V, 60 Hz, 1 Phasej. Liquid Line: 1/4 inchk. Suction Line: 1/2 inchl. Indoor Dimensions: 31.25 inches wide by 10.5 inches high by 7.75 inches

deep.m. Outdoor Dimensions: 33.27 inches wide by 27.56 inches high by 12.6 inches

deep.6. Model: NH21-18F-I

a. Cooling Capacity BTU/H: -b. Heating Capacity BTU/H: -c. SEER: -d. EER: -e. HSPF4: -f. HSPF5: -g. Min. Amapacity: 0.4h. Max. Fuse: 15i. Power: 208/230V, 60 Hz, 1 Phasej. Liquid Line: 1/4 inchk. Suction Line: 1/2 inchl. Indoor Dimensions: 36.25 inches wide by 11.5 inches high by 8.75 inches

deep.

23 50 00-37

Page 38: €¦ · Web viewNapoleon Ductless Multi-Zone Heat Pumps and Air Conditioners: General: Multi-zone offers up to 4 indoor units that operate from one, outdoor air condenser. Indoor

m. Outdoor Dimensions: 38.98 inches wide by 37.99 inches high by 13.58 inches deep.

7. Model: NMZO-30F-Ba. Cooling Capacity BTU/H: 30,000b. Heating Capacity BTU/H: 30,000c. SEER: 16d. EER: 7.5e. HSPF4: 9f. HSPF5: 7.5g. Min. Amapacity: 18h. Max. Fuse: 30i. Power: 208/230V, 60 Hz, 1 Phasej. Liquid Line: 1/4 inchk. Suction Line: 3/8 inchl. Indoor Dimensions: -m. Outdoor Dimensions: 35.43 inches wide by 37.99 inches high by 12.40 inches

deep.8. Model: NMZO-36F-B

a. Cooling Capacity BTU/H: 36,000b. Heating Capacity BTU/H: 38,000c. SEER: 16.5d. EER: 8.9e. HSPF4: 9f. HSPF5: 7.9g. Min. Amapacity: 27h. Max. Fuse: 40i. Power: 208/230V, 60 Hz, 1 Phasej. Liquid Line: 1/4 inchk. Suction Line: 3/8 inchl. Indoor Dimensions: -m. Outdoor Dimensions: 38.98 inches wide by 37.99 inches high by 13.58 inches

deep.

2.7 CONDO PACK HEATING AND COOLING SYSTEMS

A. Napoleon Condo Pack Heating and Cooling System:1. General: Designed with wall sleeves and removable heating and cooling modules with

quick connect electrical fittings.a. Three piece design allows for individual component handling for easy

installation and serviceability.b. Appliance shell dimensions where penetrating exterior wall: 43-1/8 inches high

by 28 inches wide.c. Wall sleeve dimensions:

1) 44-7/8 inches high by 28-7/8 inches wide.2) 12.59 inches deep.3) 14.89 inches deep.4) 16.89 inches deep.5) 18.89 inches deep.

B. High Efficiency Condensing Gas Heating / Electric Cooling Modules1. Series P-C15A-A012A-A

a. Heating Capacity:1) Thermal Efficiency: 90 percent2) AFUE efficiency 96.8 percent3) Input BTU/hr: 15,0004) Output BTU/hr: 14,500

23 50 00-38

Page 39: €¦ · Web viewNapoleon Ductless Multi-Zone Heat Pumps and Air Conditioners: General: Multi-zone offers up to 4 indoor units that operate from one, outdoor air condenser. Indoor

b. Cooling Capacity:1) BTU/H: 12,0002) EER: 11.03) Refrigerant: R410A4) Weight (lbs): 323

2. Series P-C15A-A18A-Aa. Heating Capacity:

1) Thermal Efficiency: 90 percent2) AFUE efficiency 96.8 percent3) Input BTU/hr: 15,0004) Output BTU/hr: 14,500

b. Cooling Capacity:1) BTU/H: 17,0002) EER: 11.03) Refrigerant 410A4) Weight (lbs): 344

3. Series P-C15A-A24A-Aa. Heating Capacity:

1) Thermal Efficiency: 90 percent2) AFUE efficiency 96.8 percent3) Input BTU/hr: 15,0004) Output BTU/hr: 14,500

b. Cooling Capacity:1) BTU/H: 24,0002) EER: 11.03) Refrigerant: R410A4) Weight (lbs): 401

4. Series P-C030A-12A-Aa. Heating Capacity:

1) Thermal Efficiency: 90 percent2) AFUE efficiency 93 percent3) Input BTU/hr: 30,0004) Output BTU/hr: 27,900

b. Cooling Capacity:1) BTU/H: 12,0002) EER: 11.03) Refrigerant: R410A4) Weight (lbs): 328

5. Series P-C30A-A18A-Aa. Heating Capacity:

1) Thermal Efficiency: 90 percent2) AFUE efficiency 93 percent3) Input BTU/hr: 30,0004) Output BTU/hr: 27,900

b. Cooling Capacity:1) BTU/H: 17,0002) EER: 11.03) RefrigerantR410A4) Weight (lbs): 344

6. Series P-C30Q-A24A-Aa. Heating Capacity:

1) Thermal Efficiency: 90 percent2) AFUE efficiency 93 percent3) Input BTU/hr: 30,0004) Output BTU/hr: 27,900

b. Cooling Capacity:

23 50 00-39

Page 40: €¦ · Web viewNapoleon Ductless Multi-Zone Heat Pumps and Air Conditioners: General: Multi-zone offers up to 4 indoor units that operate from one, outdoor air condenser. Indoor

1) BTU/H: 24,0002) EER: 11.03) Refrigerant: R410A4) Weight (lbs): 401

7. Series P-C040A-A12A-Aa. Heating Capacity:

1) Thermal Efficiency: 90 percent2) AFUE efficiency 91.7 percent3) Input BTU/hr: 40,0004) Output BTU/hr: 36,700

b. Cooling Capacity:1) BTU/H: 12,0002) EER: 11.03) Refrigerant: R410A4) Weight (lbs): 328

8. Series P-C40A-A18A-Aa. Heating Capacity:

1) Thermal Efficiency: 90 percent2) AFUE efficiency 91.7 percent3) Input BTU/hr: 40,0004) Output BTU/hr: 36,700

b. Cooling Capacity:1) BTU/H: 17,0002) EER: 11.063) Refrigerant: R410A4) Weight (lbs): 349

9. Series P-C40A-A24A-Aa. Heating Capacity:

1) Thermal Efficiency: 90 percent2) AFUE efficiency 91.7 percent3) Input BTU/hr: 40,0004) Output BTU/hr: 36,700

b. Cooling Capacity:1) BTU/H: 24,05002) EER: 11.03) Refrigerant: R410A4) Weight (lbs): 401

10. Series P-C50A-A12A-Aa. Heating Capacity:

1) Thermal Efficiency: 90.6 percent2) AFUE efficiency 90.6 percent3) Input BTU/hr: 50,0004) Output BTU/hr: 45,300

b. Cooling Capacity:1) BTU/H: 12,0002) EER: 11.03) Refrigerant: R410A4) Weight (lbs): 328

11. Series P-C50A-A18A-Aa. Heating Capacity:

1) Thermal Efficiency: 90.6 percent2) AFUE efficiency 90.6 percent3) Input BTU/hr: 50,0004) Output BTU/hr: 45,300

b. Cooling Capacity:1) BTU/H: 17,000

23 50 00-40

Page 41: €¦ · Web viewNapoleon Ductless Multi-Zone Heat Pumps and Air Conditioners: General: Multi-zone offers up to 4 indoor units that operate from one, outdoor air condenser. Indoor

2) EER: 11.03) Refrigerant: R410A4) Weight (lbs): 329

12. Series P-C40A-A24A-Aa. Heating Capacity:

1) Thermal Efficiency: 90.6 percent2) AFUE efficiency 90.6 percent3) Input BTU/hr: 50,0004) Output BTU/hr: 45,300

b. Cooling Capacity:1) BTU/H: 24,0002) EER: 11.03) Refrigerant: R410A4) Weight (lbs): 401

C. Mid Efficiency Gas Heating / Electric Cooling Modules1. Series P-S26A-A12A-A

a. Heating Capacity:1) Thermal Efficiency: 80 percent2) AFUE efficiency 80 percent3) Input BTU/hr: 26,0004) Output BTU/hr: 20,800

b. Cooling Capacity:1) BTU/H: 12,0002) EER: 11.03) Refrigerant: R410A4) Weight (lbs): 323

2. Series P-S26A-A18A-Aa. Heating Capacity:

1) Thermal Efficiency: 80 percent2) AFUE efficiency 80 percent3) Input BTU/hr: 26,0004) Output BTU/hr: 20,800

b. Cooling Capacity:1) BTU/H: 17,0002) EER: 11.03) Refrigerant: R410A4) Weight (lbs): 344

3. Series P-S26A-A24A-Aa. Heating Capacity:

1) Thermal Efficiency: 80 percent2) AFUE efficiency 80 percent3) Input BTU/hr: 26,0004) Output BTU/hr: 20,800

b. Cooling Capacity:1) BTU/H: 24,0002) EER: 11.03) Refrigerant: R410A4) Weight (lbs): 401

4. Series P-SC38A-A12A-Aa. Heating Capacity:

1) Thermal Efficiency: 80 percent2) AFUE efficiency 80 percent3) Input BTU/hr: 38,0004) Output BTU/hr: 30,400

b. Cooling Capacity:

23 50 00-41

Page 42: €¦ · Web viewNapoleon Ductless Multi-Zone Heat Pumps and Air Conditioners: General: Multi-zone offers up to 4 indoor units that operate from one, outdoor air condenser. Indoor

1) BTU/H: 12,8002) EER: 11.03) Refrigerant: R410A4) Weight (lbs): 323

5. Series P-S38A-A18A-Aa. Heating Capacity:

1) Thermal Efficiency: 80 percent2) AFUE efficiency 80 percent3) Input BTU/hr: 38,0004) Output BTU/hr: 30,400

b. Cooling Capacity:1) BTU/H: 17,0002) EER: 11.03) Refrigerant: R410A4) Weight (lbs): 344

6. Series P-S38A-A24A-Aa. Heating Capacity:

1) Thermal Efficiency: 80 percent2) AFUE efficiency 80 percent3) Input BTU/hr: 38,0004) Output BTU/hr: 30,400

b. Cooling Capacity:1) BTU/H: 24,0002) EER: 11.03) Refrigerant: R410A4) Weight (lbs): 401

7. Series P-S51A-A12A-Aa. Heating Capacity:

1) Thermal Efficiency: 80 percent2) AFUE efficiency 80 percent3) Input BTU/hr: 51,0004) Output BTU/hr: 40,800

b. Cooling Capacity:1) BTU/H: 12,0002) EER: 11.03) Refrigerant: R410A4) Weight (lbs): 323

8. Series P-S51A-A18A-Aa. Heating Capacity:

1) Thermal Efficiency: 80 percent2) AFUE efficiency 80 percent3) Input BTU/hr: 51,0004) Output BTU/hr: 40,800

b. Cooling Capacity:1) BTU/H: 17,0002) EER: 11.03) Refrigerant: R410A4) Weight (lbs): 344

9. Series P-S51A-A24A-Aa. Heating Capacity:

1) Thermal Efficiency: 80 percent2) AFUE efficiency 80 percent3) Input BTU/hr: 510004) Output BTU/hr: 40,800

b. Cooling Capacity:1) BTU/H: 24,500

23 50 00-42

Page 43: €¦ · Web viewNapoleon Ductless Multi-Zone Heat Pumps and Air Conditioners: General: Multi-zone offers up to 4 indoor units that operate from one, outdoor air condenser. Indoor

2) EER: 11.03) Refrigerant: R410A4) Weight (lbs): 401

10. Series P-S64A-A12A-Aa. Heating Capacity:

1) Thermal Efficiency: 80 percent2) AFUE efficiency 80 percent3) Input BTU/hr: 64,0004) Output BTU/hr: 51,200

b. Cooling Capacity:1) BTU/H: 12,0002) EER: 11.03) Refrigerant: R410A4) Weight (lbs): 323

11. Series P-S64A-A18A-Aa. Heating Capacity:

1) Thermal Efficiency: 80 percent2) AFUE efficiency 80 percent3) Input BTU/hr: 64,0004) Output BTU/hr: 51,200

b. Cooling Capacity:1) BTU/H: 17,0002) EER: 11.03) Refrigerant: R410A4) Weight (lbs): 344

12. Series P-S64A-A24A-Aa. Heating Capacity:

1) Thermal Efficiency: 80 percent2) AFUE efficiency 80 percent3) Input BTU/hr: 64,0004) Output BTU/hr: 51,200

b. Cooling Capacity:1) BTU/H: 24,0002) EER: 11.03) Refrigerant: R410A4) Weight (lbs): 401

D. Electric Heating / Cooling Modules1. Series P-E05A-A12A-A

a. Heating Capacity:1) 240V

a) Kw/Hr: 4.8b) Btu/Hr: 16300

2) 208Va) Kw/Hr: 3.6b) Btu/Hr: 12300

b. Cooling Capacity:1) BTU/H: 12,0002) EER: 11.03) Refrigerant: R410A4) CFM: 540

2. Series P-E005A-A18A-Aa. Heating Capacity:

1) 240Va) Kw/Hr: 4.8b) Btu/Hr: 16300

23 50 00-43

Page 44: €¦ · Web viewNapoleon Ductless Multi-Zone Heat Pumps and Air Conditioners: General: Multi-zone offers up to 4 indoor units that operate from one, outdoor air condenser. Indoor

2) 208Va) Kw/Hr: 3.6b) Btu/Hr: 12300

b. Cooling Capacity:1) BTU/H: 17,0002) EER: 11.03) Refrigerant: R410A4) CFM: 600

3. Series P-E005A-A24A-Aa. Heating Capacity:

1) 240Va) Kw/Hr: 4.8b) Btu/Hr: 16300

2) 208Va) Kw/Hr: 3.6b) Btu/Hr: 12300

b. Cooling Capacity:1) BTU/H: 24,0002) EER: 11.03) Refrigerant: R410A4) CFM: 800

4. Series P-E07A-A12A-Aa. Heating Capacity:

1) 240Va) Kw/Hr: 7.3b) Btu/Hr: 24600

2) 208Va) Kw/Hr: 5.5b) Btu/Hr: 18400

b. Cooling Capacity:1) BTU/H: 12,0002) EER: 11.03) Refrigerant: R410A4) CFM: 450

5. Series P-E07A-A18A-Aa. Heating Capacity:

1) 240Va) Kw/Hr: 7.3b) Btu/Hr: 24600

2) 208Va) Kw/Hr: 5.5b) Btu/Hr: 18400

b. Cooling Capacity:1) BTU/H: 17,0002) EER: 11.03) Refrigerant:R410A4) CFM: 600

6. Series P-E07A-A24A-Aa. Heating Capacity:

1) 240Va) Kw/Hr: 7.3b) Btu/Hr: 24600

2) 208Va) Kw/Hr: 5.5b) Btu/Hr: 18400

b. Cooling Capacity:

23 50 00-44

Page 45: €¦ · Web viewNapoleon Ductless Multi-Zone Heat Pumps and Air Conditioners: General: Multi-zone offers up to 4 indoor units that operate from one, outdoor air condenser. Indoor

1) BTU/H: 24,0002) EER: 11.03) Refrigerant: R410A4) CFM: 800

7. Series P-E10A-A12A-Aa. Heating Capacity:

1) 240Va) Kw/Hr: 9.6b) Btu/Hr: 32700

2) 208Va) Kw/Hr: 7.2b) Btu/Hr: 24600

b. Cooling Capacity:1) BTU/H: 12,0002) EER: 11.03) Refrigerant: R410A4) CFM: 450

8. Series P-E10A-A18A-Aa. Heating Capacity:

1) 240Va) Kw/Hr: 9.6b) Btu/Hr: 32700

2) 208Va) Kw/Hr: 7.2b) Btu/Hr: 24600

b. Cooling Capacity:1) BTU/H: 17,0002) EER: 11.03) Refrigerant: R410A4) CFM: 600

9. Series P-E10A-A24A-Aa. Heating Capacity:

1) 240Va) Kw/Hr: 9.6b) Btu/Hr: 32700

2) 208Va) Kw/Hr: 7.2b) Btu/Hr: 24600

b. Cooling Capacity:1) BTU/H: 24,0002) EER: 11.03) Refrigerant: R 410A4) CFM: 800

10. Series P-E15A-A12A-Aa. Heating Capacity:

1) 240Va) Kw/Hr: 14.4b) Btu/Hr: 49100

2) 208Va) Kw/Hr: 10.8b) Btu/Hr: 36900

b. Cooling Capacity:1) BTU/H: 12,0002) EER: 11.03) Refrigerant: R410A4) CFM: 450

23 50 00-45

Page 46: €¦ · Web viewNapoleon Ductless Multi-Zone Heat Pumps and Air Conditioners: General: Multi-zone offers up to 4 indoor units that operate from one, outdoor air condenser. Indoor

11. Series P-E15A-A18A-Aa. Heating Capacity:

1) 240Va) Kw/Hr: 14.4b) Btu/Hr: 49100

2) 208Va) Kw/Hr: 10.8b) Btu/Hr: 36900

b. Cooling Capacity:1) BTU/H: 17,0002) EER: 11.03) Refrigerant:R410A4) CFM: 740

12. Series P-E15A-A24A-Aa. Heating Capacity:

1) 240Va) Kw/Hr: 14.2b) Btu/Hr: 49100

2) 208Va) Kw/Hr: 10.8b) Btu/Hr: 36900

b. Cooling Capacity:1) BTU/H: 24,0002) EER: 11.03) Refrigerant: R410A4) CFM: 800

E. Hydronic Heating Modules1. Series PSH030A012A-TP

a. Heating Capacity:1) 208V/230V

a) Model: CHHM030Ab) Btu/Hr: 30000

b. Cooling Capacity:1) BTU/H: 12,8002) EER: 10.83) Refrigerant: 410A4) CFM: 440

2. Series PSH030A018A-TPa. Heating Capacity:

1) 208V/230Va) Model: CHHM030Ab) Btu/Hr: 30000

b. Cooling Capacity:1) BTU/H: 16,5002) EER: 9.63) Refrigerant: 410A4) CFM: 740

3. Series PSH030A024A-TPa. Heating Capacity:

1) 208V/230Va) Model: CHHM030Ab) Btu/Hr: 30000

b. Cooling Capacity:1) BTU/H: 19,5002) EER: 9.0

23 50 00-46

Page 47: €¦ · Web viewNapoleon Ductless Multi-Zone Heat Pumps and Air Conditioners: General: Multi-zone offers up to 4 indoor units that operate from one, outdoor air condenser. Indoor

3) Refrigerant: 410A4) CFM: 740

4. Series PSH030A030A-TPa. Heating Capacity:

1) 208V/230Va) Model: CHHM030Ab) Btu/Hr: 30000

b. Cooling Capacity:1) BTU/H: 24,4002) EER: 9.03) Refrigerant: 410A4) CFM: 960

5. Series PSH042A012A-TPa. Heating Capacity:

1) 208V/230Va) Model: CHHM042Ab) Btu/Hr: 42000

b. Cooling Capacity:1) BTU/H: 12,8002) EER: 10.83) Refrigerant: 410A4) CFM: 450

6. Series PSE007A018A-TPa. Heating Capacity:

1) 208V/230Va) Model: CHHM042Ab) Btu/Hr: 42000

b. Cooling Capacity:1) BTU/H: 16,5002) EER: 9.63) Refrigerant: 410A4) CFM: 740

7. Series PSH042A024A-TPa. Heating Capacity:

1) 208V/230Va) Model: CHHM042Ab) Btu/Hr: 42000

b. Cooling Capacity:1) BTU/H: 19,5002) EER: 9.03) Refrigerant: 410A4) CFM: 740

8. Series PSH042A030A-TPa. Heating Capacity:

1) 208V/230Va) Model: CHHM042Ab) Btu/Hr: 42000

b. Cooling Capacity:1) BTU/H: 24,4002) EER: 9.03) Refrigerant: 410A4) CFM: 960

2.8 HYBRID HEATING SYSTEMS

A. General: Napoleon's Hybrid Series Furnaces are certified to CSA B366.1-M91, B140.4-04,

23 50 00-47

Page 48: €¦ · Web viewNapoleon Ductless Multi-Zone Heat Pumps and Air Conditioners: General: Multi-zone offers up to 4 indoor units that operate from one, outdoor air condenser. Indoor

B212-00, UL 1995/CSA C22.2 No.236, UL 391, UL 727, and CSA B415.1-10

B. Napoleon Hybrid Wood Furnace (HMF200):1. Description: Hybrid furnaces switch from wood to the secondary heat source

automatically. If the furnace runs out of wood, a second thermostat controlling the optional heating components will automatically engage. During power failures, the wood burning portion uses gravity air flow for emergency heating. Napoleon's Hybrid Series Furnaces are clean burning and certified to (CSA B415.1-10) with efficiency ratings as high as 77.2 percent.

2. Combustion System:a. Wood Furnace: Stainless steel tube combustion system with a secondary burn

cycle from the wood and from wood gases that achieves an extraordinary clean burn without a catalytic combustor. The system uses horizontal jets of super heated secondary air that are mixed with the fire's smoke to burn off released smoke particles.1) Maximum peak input capacity (wood): 200,000 BTU's2) Maximum peak output capacity (wood): 150,000 BTU's3) Low emissions: 4.5 g/h (wood)4) Firebox Capacity: 5 cubic foot5) Furnace Dimensions with Blower: 48 inches wide by 32 inches deep by

52 inches high6) Firebox Front Opening: 18 inches wide by 24 inches deep by 13-1/2

inches high.b. Electric Furnace:

1) Maximum Output: 70,000 - 85,000 BTU's (18 - 25 kW)2) Wood/Electric Furnace Dimensions with Blower: 60 inches wide by 32

inches deep by 52 inches highc. Gas Furnace:

1) Maximum Output:2) Wood/Gas Furnace Dimensions with Blower: __ inches wide by 32

inches deep by 52 inches highd. Oil Furnace: Stainless steel combustion chamber/heat exchanger of the oil

furnace module can be connected to your choice of Beckett or Riello high-efficiency burners.1) Maximum Output: 70,000 - 93,000 BTU's / Up to 85 percent AFUE2) Wood/Oil Furnace Dimensions with Blower: 48 inches wide by 42 inches

deep by 52 inches highe. Wood/Electric/Oil Furnace Dimensions with Blower: 60 inches wide by 42

inches deep by 52 inches high3. Blower: 4 speed - 1400 CFM4. Minimum Clearance to Combustibles: 14 inches sides by 24 inches back by 48 inches

front5. Venting:

a. Wood only 6 inch diameter.b. Wood/Oil combo 7 inch diameter.

2.9 HIGH EFFICENCY AIR CLEANERS

A. Whole House High Efficiency Media Air Cleaners:1. General:

a. High Efficiency MERV* 11 Media Filter, rated at 492 feet/minute, removes airborne contaminants down to 0.3 micron.

b. Filter material constructed of continuous hydrophobic polyolefin fibers that will not shred or absorb moisture. Cellulose free and will not sustain mold growth.

c. Extra deep, 5 1/4 inch filter.d. Heavy gauge galvanized steel cabinet with powder coat finish.

23 50 00-48

Page 49: €¦ · Web viewNapoleon Ductless Multi-Zone Heat Pumps and Air Conditioners: General: Multi-zone offers up to 4 indoor units that operate from one, outdoor air condenser. Indoor

2. Model NNA-NC1625-A:a. Power Consumption: 0b. House Size: Less than 3,000 sfc. Air Flow: Up to 1400 CFMd. Duct Size: 16 inches by 25 inchese. Intake Dimensions: 13.25 inches H by 23.7 inches Lf. Cabinet Dimensions: 7.5 inches W by 17.4 inches H by 26.5 inches Lg. Weight: 18 lbsh. Pressure Drop: .066 in/wg @ 246 fpmi. MERV Rating: 11

3. Model NNA-NC2025-A:a. Power Consumption: 0b. House Size: Greater than 3,000 sfc. Air Flow: Up to 2000 CFMd. Duct Size: 20 inches by 25 inchese. Intake Dimensions: 18.1 inches H by 23.25 inches Lf. Cabinet Dimensions: 7.5 inches W by 22.25 inches H by 26.1 inches Lg. Weight: 20 lbsh. Pressure Drop: .069 in/wg @ 246 fpmi. MERV Rating: 11

B. Home Shield Ultraviolet light Air Purifiers:1. General: HomeShield installed into the HVAC system to disinfect the air from harmful

microorganisms such as such as dust particles, mold spores, animal hair, dander, pollen, dust mites, viruses and bacteria.

2. Model Full Kit: Designed to purify the air entering and exiting your HVAC system. Lamps can be placed up to 6 ft apart.a. Medical Grade High Output 60-120 Watts Modulesb. Standard Grade 18-36 Watts Modules

3. Model Twin Lamp: Twin Lamp with adjustable bulbs allow for precise configurations around air conditioner coils.a. Medical Grade High Output 60-120 Watts Modulesb. Standard Grade 18-36 Watts Modules

4. Model Furnace Lamp: Kit fits inside your furnace to purify the air passing through.a. Standard Grade 18-36 Watts Modules

PART 3 EXECUTION

3.1 EXAMINATION

A. Do not begin installation until wall openings and rough-in have been properly prepared.

B. If preparation is the responsibility of another installer, notify Architect of unsatisfactory preparation before proceeding.

3.2 PREPARATION

A. Clean surfaces thoroughly prior to installation.

B. Prepare surfaces using the methods recommended by the manufacturer for achieving the best result for the substrate under the project conditions.

3.3 INSTALLATION

A. Install in accordance with manufacturer's instructions and the requirements of authorities having jurisdiction.

23 50 00-49

Page 50: €¦ · Web viewNapoleon Ductless Multi-Zone Heat Pumps and Air Conditioners: General: Multi-zone offers up to 4 indoor units that operate from one, outdoor air condenser. Indoor

B. Use manufacturer's guidelines for minimum clearances to combustibles, walls, and finishes.

C. Anchor all components firmly in position.

D. Connect to natural gas system in accordance with NFPA 54.

E. Connect to natural gas system in accordance with CSA B149.1.

F. Connect to propane system in accordance with NFPA 54.

G. Connect to propane system in accordance with CSA B149.1 and B149.2.

H. Connect to power supply and control wiring in accordance with NFPA 70.

I. Connect to power supply and control wiring in accordance with CSA C221.

J. Upon completion of installation, visually inspect all exposed surfaces. Touch up scratches and abrasions with touch up paint recommended by the manufacturer; make imperfections invisible to the unaided eye from a distance of 5 feet.

K. Test for proper operation and adjust until satisfactory results are obtained.

3.4 PROTECTION

A. Protect installed products until completion of project.

B. Touch-up, repair or replace damaged products before Substantial Completion.

END OF SECTION

23 50 00-50