WATERLOO LIFT STATION DESIGN. BUILD. OPERATE. …
Transcript of WATERLOO LIFT STATION DESIGN. BUILD. OPERATE. …
MECOSTA COUNTY
WATERLOO
LIFT STATION
CITY OF BIG RAPIDS
MECOSTA COUNTY, MICHIGAN
DECEMBER 2019
VICINITY MAP
LOCATION MAP
CIT
Y O
F B
IG
R
AP
ID
S
WA
TE
RL
OO
L
IF
T S
TA
TIO
N IM
PR
OV
EM
EN
TS
Know what's below.before you dig.Call
R
CS
841250
2960 Lucerne Drive SE
P: 616.977.1000
F: 616.977.1005
Grand Rapids, MI 49546
F&V PROJECT NO.
INDEX OF DRAWINGS
DESCRIPTION SHEET NO.
COVER SHEET CS
LIFT STATION SITE PLAN C1
LIFT STATION DEMOLITION D1
LIFT STATION PLAN & SECTION LS1
ELECTRICAL PLANS, DETAILS & SCHEDULES
E1
DESIGN. BUILD. OPERATE.
N
WATERLOO LIFT STATION
IMPROVEMENTS
MARK GIFFORD CITY MANAGER
CITY OF BIG RAPIDS
226 NORTH MICHIGAN AVENUE
BIG RAPIDS, MI 49307
(231) 592-4020
HEATHER BOWMAN DIRECTOR OF PUBLIC WORKS
CITY OF BIG RAPIDS WATER/SEWER
226 NORTH MICHIGAN AVENUE
BIG RAPIDS, MI 49307
(231) 592-4018
DAVE CUSHWAY WASTEWATER TREATMENT PLANT SUPERINTENDENT
CITY OF BIG RAPIDS
531 RIVER STREET
BIG RAPIDS, MI 49307
(231) 796-8483
LINDA DENNISUK TELEPHONE/FIBER OPTIC/CABLE
ATT
54 N. MILL ST, 4TH FLOOR
PONTIAC, MI 48342
(248) 456-8256
KURT GOLDING ELECTRIC
CONSUMERS ENERGY
530 W WILLOW ST
LANSING, MI 48906
(231) 929-6242
BARBARA SAUNDERS GAS
DTE GAS
ONE ENERGY PLAZA
DETROIT, MI 48226
(313) 235-5111
PROJECT AND PUBLIC UTILITY CONTACTS
F&V PROJECT NO.
DESIGN TEAM:
DRAWING INFORMATION:
CHECK BY:
REVISION:
CIT
Y O
F B
IG
R
AP
ID
S
ME
CO
ST
A C
OU
NT
Y, M
IC
HIG
AN
WA
TE
RL
OO
L
IF
T S
TA
TIO
N IM
PR
OV
EM
EN
TS
DECEMBER 2019
841250
2960 Lucerne Drive SE
P: 616.977.1000
F: 616.977.1005
Grand Rapids, MI 49546
DESIGN. BUILD. OPERATE.
EXISTING SITE PLAN
SCALE: NONE
NORTH
841250_C1
121219 scotth
LIF
T S
TA
TIO
N S
IT
E P
LA
N
RWW SFH DCT
C1
1Issu
ed
F
or P
art 41 P
erm
it
12/2019
RW
W
E
X
. 4
"
C
I F
O
R
C
E
M
A
IN
EX. WATER TREATMENT
PLANT FENCE
PROP. SILT FENCE
EX. SANITARY MH
RIM=907.32
INVERT = 903.67 (4" NE)
INVERT = 902.62 (10" NW)
INVERT = 902.57 (10" S)
EX. SANITARY MH
RIM=900.47
INVERT = 893.87 (8" N)
INVERT = 894.07 (6" SW)
INVERT = 893.87 (10" S)
EX. LS WET WELL
RIM=899.79
INVERT = 893.09 (10" N)
INVERT = 893.18 (8" E)
INVERT = 893.87 (8" S)
EX. GUADRAIL
CITY OF BIG RAPIDS
WATER TREATMENT PLANT
EX. WATERLOO LS
BUILDING
2Issu
ed
F
or B
id
12/2019
RW
W
LIFT STATION LOWER LEVEL PLAN
SCALE: 1/2" = 1'-0"
NORTH
2
LIFT STATION UPPER LEVEL PLAN
SCALE: 1/2" = 1'-0"
NORTH
1
PHOTO 1 PHOTO 2
PHOTO 3
1
2
3
REMOVE EX. PUMP (TYP. OF 2)
REMOVE EX. 4" PIPING
AND VALVES
REMOVE EX. 4" VALVES
REMOVE EX. 4" PIPING
AND VALVES
REMOVE EX. SUMP PUMP
AND DISCHARGE PIPING
REMOVE EX. STEEL PLATE, CUT AND CAP PIPE BELOW
PROPOSED CONCRETE. SEE SHEET LS1 FOR CONCRETE
REPAIR. SEE SHEET E1 FOR MODIFICATIONS TO
ELECTRICAL CONDUIT AND CABLES THROUGH THE FLOOR.
COORDINATE ALL WORK w/ELECTRICAL CONTRACTOR.
EX. GRADE
EX. GRADE
EX. PUMP CONTROLS
EX. WET
WELL
EX. WET WELL
ACCESS MH. CASTING
EX. WET WELL
REMOVE EX. PUMPS
2
1
EX. CONTROL ROOM
EX. PUMPING ROOM
REMOVE STEEL PLATE.
SEE PHOTO 2
EX. WET WELL
EX. PUMPING ROOM
EX. CONTROL ROOM
F&V PROJECT NO.
DESIGN TEAM:
DRAWING INFORMATION:
CHECK BY:
REVISION:
CIT
Y O
F B
IG
R
AP
ID
S
ME
CO
ST
A C
OU
NT
Y, M
IC
HIG
AN
WA
TE
RL
OO
L
IF
T S
TA
TIO
N IM
PR
OV
EM
EN
TS
DECEMBER 2019
841250
2960 Lucerne Drive SE
P: 616.977.1000
F: 616.977.1005
Grand Rapids, MI 49546
DESIGN. BUILD. OPERATE.
841250_D1
121219 scotth
LIF
T S
TA
TIO
N D
EM
OL
IT
IO
N
RWW SFH DCT
D1
REMOVE EX. 4" PIPING AND VALVES
REMOVE EX. SUMP PUMP
DISCHARGE
DEMOLITION NOTES:
1. UPON REMOVAL RETURN THE FOLLOWING ITEMS TO THE OWNER: TWO (2) SEWAGE
PUMPS, CONTROL PANEL, DISCONNECTS, AND MOTOR STARTERS. EXCEPT FOR ITEMS
SALVAGED FOR OWNER, CONTRACTOR RESPONSIBLE FOR DISPOSAL OF ALL DEMOLITION
MATERIALS AND EQUIPMENT.
2. REMOVE AND DISPOSE OF ALL INSTRUMENTATION AND ANCILLARY EQUIPMENT WITHIN
THE WET WELL.
REMOVE AND DISPOSE OF ALL
ELECTRICAL CONDUIT, WIRING,
RECEPTACLES, AND LIGHTING IN
LOWER LEVEL.
DO NOT REMOVE 2" CONDUIT AND
WEATHERHEAD. LEAVE IN PLACE FOR
REUSE.
REMOVE ALL ELECTRICAL GEAR,
CONTROL PANEL, CONDUITS AND
WIRING.
REMOVE AND DISPOSE OF CEILING
MOUNTED LIGHT FIXTURES, CONDUIT AND
WIRING
3'-0" MIN.
REMOVE AND REPLACE EX. GUARDRAIL
AND ASPHALT (HMA) AS REQUIRED TO
COMPLETE PIPING REPLACEMENT.
REFER TO TYPICAL HMA PAVEMENT
SECTION, THIS SHEET.
REMOVE EX. 4" PVC VENT
REMOVE EX. HATCH AND FRAME.
SAW CUT EX. FLOOR. DRILL OUT ANY
EXPOSED REBAR TO A DEPTH OF 6"
AND FILL WITH EPOXY GROUT.
3'-5"
3'-1
"
FILL EX. HOLES
w/NON-SHRINK GROUT
1
SECTION2
SECTION
REMOVE LOOSE
CONCRETE AND DEBIS IN
EX. SUMP
EX. INLET SEWER
INV. EL. 893.08±
EX. INLET SEWER
INV. EL. 893.18±
FROM WATER PLANT
EX. ABANDONED WET
WELL OVER FLOW
INV. EL. 893.78±
SPACING 6-10' MAX.
ROLL JOINT
SILT FENCE
FENCE POSTS DRIVEN
INTO GROUND 1' MIN.
SILT FENCE B
ROLL JOINTS
FABRIC TO BE WRAPPED
AROUND FENCE POST
GEOTEXTILE FILTER
FABRIC FASTENED ON
UPHILL SIDE, TOWARDS
EARTH DISRUPTION
1' MIN.
6"x6" ANCHOR TRENCH
RIDGE OF COMPACTED
EARTH ON UPHILL SIDE
OF FILTER FABRIC
UNDISTURBED
VEGETATION
6" ANCHOR TRENCH
SILT FENCE A
1' M
IN
.
NOT TO SCALE
PG 58-28
-
AWI
220
220 LBS/SYD
EST. YIELD
HMA, 13A
ITEM
HMA, 13A220 LBS/SYD
HMA APPLICATION TABLE
APPLICATION RATE 0.05 - 0.15 GAL/SYD SS-IH, AS DIRECTED BY ENGINEER.
COURSES OF HMA (PAYMENT INCLUDED IN HMA MIX).
PG 58-28
GRADE
BINDER
TYPE
LEVELING1
COURSE
TOP2
NOTE: BOND COAT SHALL BE APPLIED BETWEEN SUCCESSIVE
8" AGGREGATE BASE
2
1
12" SAND SUBBASE
PAVEMENT SECTION
TYPICAL HMA
NOT TO SCALE
1Issu
ed
F
or P
art 41 P
erm
it
12/2019
RW
W
REMOVE EX. HATCH, LADDER
AND FRAME.
2Issu
ed
F
or B
id
12/2019
RW
W
PROPOSED 4" DIP (TYP.)
PROPOSED 4" 1/4 TURN PLUG VALVE
(TYP. OF 5)
PROPOSED 4" DIP (TYP.)
PROPOSED 4" PLUG VALVE
(TYP. OF 3)
4" 90° BEND (TYP.)
4" TEE (TYP.)
LIFT STATION LOWER LEVEL PLAN VIEW
SCALE: 1/2" = 1'-0"
NORTH
LIFT STATION UPPER LEVEL PLAN VIEW
SCALE: 1/2" = 1'-0"
NORTH
PROPOSED BYPASS PUMP CONNECTION
SEE SHEET E1 AND D1 FOR
ELECTRICAL MODIFICATIONS
4
5
2
P-1
P-2
P-1
1
2
VALVE SCHEDULE
1
6
7
4
5
2
3
TAG
HANDWHEEL
HANDWHEEL
HANDWHEEL
HANDWHEEL
ACTUATOR
4" PLUG
PLUG
PLUG
CHECK
CHECK
PLUG
SIZE TYPE COMMENTS
PUMP P-1 SUCTION
LOCATION
4"
4"
4"
4"
4"
4" PLUG CHAINWHEEL
PUMP P-1 DISCHARGE
PUMP P-1 DISCHARGE
PUMP P-2 SUCTION
PUMP P-2 DISCHARGE
PUMP P-2 DISCHARGE
BYPASS PUMPING CONNECTION
2
PROPOSED 1-1/2" GSP SUMP PUMP
DISCHARGE. CONNECT TO
EXISTING PIPE AT WET WELL
2
1
PRECISION FIXED ALUMINUM LADDER. MODEL FL
OR APPROVED EQUAL. INSTALL IN ACCORDANCE
w/MANUFACTURERS RECOMMENDATIONS
w/EPOXY ANCHORS. CONTRACTOR TO FIELD
VERIFY DIMENSIONS PRIOR TO SUBMITTING
SHOP DRAWINGS
1-1/2" DIAMETER SAFETY
HANDRAIL MOUNTED
w/EPOXY ANCHORS
#4 BARS, TWO EACH FACE EVENLY SPACED
12" LONG w/4" EMBED. DRILL AND EPOXY
ANCHORS. COORDINATE WORK w/ENGINEER
PRIOR TO EMBEDDING BARS
TYPE 304 S.S. PAN. ANCHOR TO WALL
w/EPOXY ANCHORS. INSTALL NEOPRENE
GASKET BETWEEN PAN AND EXISTING
CONCRETE
1
PROPOSED 1/2" TAP AND BALL VALVE. ROUTE
PVC DRAIN PIPING TO FLOOR. (TYP. OF 2)
CONSTRUCTION NOTE:
1. CONTRACTOR TO FIELD VERIFY ALL DIMENSIONS AND EQUIPMENT
ORIENTATION PRIOR TO FABRICATION/INSTALLATION.
2. PROVIDE PIPE SUPPORTS AS REQUIRED.
EX. 4" CONC. CURB
3
6
FILL WITH CONCRETE
1 1/2" GSP SUMP PUMP DISCHARGE.
CONNECT TO EXISTING PIPE AT
WET WELL
EX. 4" CONC. CURB
NEW CONCRETE
EX. WET WELL
EX. CONTROL
ROOM
EX. PUMPING
ROOM
EX. PUMPING
ROOM
EX. CONTROL
ROOM
EX. WET WELL
EX. WET WELL
EX. PUMPING
ROOM
EX. CONTROL ROOM
INSTALL 4" INLINE FAN IN EX. 4" PVC VENT
PIPE. FAN SHALL BE MIN. 150 CFM BY ACTIVE
AIR OR ENGINEER APPROVED EQUAL.
COORDINATE HEIGHT OF INSTALL W/ OWNER.
SUPPORT UNIT FROM THE WALL
RE-ROUTE EX. 4" PVC VENT PIPE
AND EXTEND TO 18" ABOVE
FINISHED FLOOR. SECURE TO
WALL w/S.S. PIPE CLAMPS AND
ANCHORS.
F&V PROJECT NO.
DESIGN TEAM:
DRAWING INFORMATION:
CHECK BY:
REVISION:
CIT
Y O
F B
IG
R
AP
ID
S
ME
CO
ST
A C
OU
NT
Y, M
IC
HIG
AN
WA
TE
RL
OO
L
IF
T S
TA
TIO
N IM
PR
OV
EM
EN
TS
DECEMBER 2019
841250
2960 Lucerne Drive SE
P: 616.977.1000
F: 616.977.1005
Grand Rapids, MI 49546
DESIGN. BUILD. OPERATE.
841250_LS1
121819 davet
LIF
T S
TA
TIO
N P
LA
N &
S
EC
TIO
N
RWW SFH DCT
LS1
NEW BUILDING PENETRATION
FOR PUMP LEVEL CONTROLS
3
1
3'-1
"
PROPOSED 18" DIAM.x24" SUMP BASIN.
JACKEL MODEL SF22A OR EQUAL.
GROUT LEVEL WITH EXISTING FLOOR
WALL PENETRATION DETAIL - TYPE 1
USE TYPE 1 WALL PENETRATION FOR ALL PIPING
PASSING THROUGH CORED HOLES IN EXISTING
CAST-IN-PLACE WALLS, UNLESS NOTED OTHERWISE.
NOTE:
1.
INTERIOR OR WATER
SOIL OR WATER
SCALE: NOT TO SCALE
CONCRETE WALL
MODULAR
MECHANICAL
SEAL
PIPE
1'-6
"
CONNECT TO EX.
FORCEMAIN
4" BYPASS CONNECTION
4'' CAMLOCK w/CAP
PS SAFETY ACCESS - 30-inch
LADDER SAFETY GATE OR
EQUAL.
CORE HOLE FOR PROPOSED 4" PVC VENT
PIPE. COORDINATE LOCATION wENGINEER
PROPOSED 4" CHECK VALVE
(TYP. OF 2)
7
7
3'-5"
ENLARGE PUMP SECTION
3'-0"
PROPOSED SUMP PUMP AND CHECK VALVE.
WAYNE MODEL CDU980E OR EQUAL
4" PVC VENT
PROPOSED 4" PRESSURE
GAUGE AND ISOLATION RING
(TYP. OF 2)
CONNECT TO EXISTING 4"
PUMP SUCTION.
PROPOSED PUMP (TYP. OF 2)
1Issu
ed
F
or P
art 41 P
erm
it
12/2019
RW
W
2
SECTION
1
SECTION
SEE ENLARGED PUMP SECTION,
THIS SHEET
1" LEVELING GROUT (TYP.)
EXCAVATION FOR BELLS
METHOD I METHOD II
DD
12"
12"
3" M
IN
.
BELL HOLE EXCAVATIONS
REQUIRED FOR METHODS I & II
GRANULAR BACKFILL
COMPACTED
GRANULAR BACKFILL
COMPACTED
SHAPE FOR
BARREL OF PIPE
NOTES:
1. METHOD I. IN AREAS OF UNCONSOLIDATED
SOILS (SAND, GRAVEL, ETC.)
2. METHOD II: IN AREAS OF CONSOLIDATED SOILS
(CLAY, HARDPAN, ROCK, ETC.)
SCALE: NOT TO SCALE
METHODS OF BEDDING PIPE
GROUT EX. PIPE
PENETRATION
CORE EX. CONCRETE WALL FOR
NEW PIPE PENETRATION
T.O. SLAB
EL. 889.65'±
EX. 4" SUCTION
INV. EL. 890.00'±
EX. GRADE EL. 900.00'±
4" DISCHARGE
C/L EL. 897.40'±
4" DISCHARGE
C/L EL. 895.32'±
DIP = DUCTILE IRON
GSP = GALVANIZED STEEL PIPE
PVC = POLYVINYL CHLORIDE
S.S. = STAINLESS STEEL
ABBREVIATIONS:
FLOOR PENETRATION DETAIL
INTERIOR
SCALE: NOT TO SCALE
CONCRETE FLOOR
MODULAR
MECHANICAL
SEAL
INTERIOR
PROPOSED 1/2" TAP AND BALL VALVE.
ROUTE PVC DRAIN PIPING TO SUMP. SECURE
PIPING TO WALL. W/ S.S. PIPE CLAMPS.
2Issu
ed
F
or B
id
12/2019
RW
W
841250_E1
121819 davet
EL
EC
TR
IC
AL
P
LA
NS
, D
ET
AIL
S &
S
CH
ED
UL
ES
EEH DCT
E1
SHEET NOTES:
1 REFER TO ALL DIVISION 26 ELECTRICAL SPECIFICATIONS
FOR ADDITIONAL REQUIREMENTS.
2 MAIN CONTROL PANEL FURNISHED BY OWNERS
SYSTEMS INTERGRATOR, INSTALLED BY CONTRACTOR.
#14 THWN LIGHT
JUNCTION BOX
EQUAL (TYP.)
SPLICES. 3M OR
600V. WIRE NUT
NUTS
FLOAT CABLES (TYP.)
1-1/2" PVC COATED RIGID METAL CONDUIT TO WET WELL
NOTE:
WITHIN THIS JUNCTION BOX AND CONDUITS.
ONLY INTRINSICALLY SAFE CONDUCTORS SHALL BE PERMITTED
LEVEL CONTROL
JUNCTION BOX DETAIL
NEMA 7
BLUE CONDUCTORS
ON BOTH SIDE OF WIRE
PROVIDE WIRE NUMBER
EXPLOSIONPROOF
CONDUIT SEAL
FITTING
1
VOLTAGE
MAIN C.B.
BUS SIZE
DESCRIPTION
LOWER LEVEL LIGHTS/FAN
OUTSIDE RECEPTACLE
19
23
21
20
20
17
15
13
11
7
9
3
5
1
1 180
UPPER LEVEL RECEPTACLES
TOTALS
2
LOWER LEVEL RECEPTACLES
2
LTS.
SURFACE ENCLOSURE
LOAD CENTER
LOCATION
20
AMPSNO.
1
POLES
CIRCUIT
1
VA
30
CONTROL RM LIGHTS
CONTROL BUILDING
OUTLETS
REC. OTHER
"LP-A"
DESCRIPTION
VOLT AMP.
ØA ØB
180
20
24
22
18
16
14
12
1 20
10
8
4
6
POLES
120/240, 1Ø, 3W.
30 AMP
REC.
OUTLETS
LTS.
2
OTHER
VA
100
AMPS
CIRCUIT
1 20
100 AMP
NO.
2
1
260
360
820 2110
MAIN CONTROL PANEL
100
20
1 750
460
DEHUMIDIFIER RECEPTACLE
201
NEMA 1
LIGHTING FIXTURE SCHEDULE
TYPE DESCRIPTION
TOTAL
W
LAMP
MOUNTING
NO W TYPE
1 METALUX 4ILED-LD4-7-WG-120V-L840-CD1-U 28 1 28 120V LED CEILING MOUNT
2
EDWARDS 48FLEDR-N5. FLASHING RED
BEACON. SHATTER RESISTENT, NEMA 4
HOUSING.
10 1 10 120 V LED WALL MOUNT 7' ABOVE GRADE
CONDUIT BODY w/CONDUIT
AND CONDUCTORS TO MCP
CONTROL BUILDING EAST ELEVATION
SCALE: 1/4"=1'-0"
ALARM
LIGHT
WET WELL COVER
SEE LEVEL CONTROL JUNCTION
BOX DETAIL, THIS SHEET
LEVEL CONTROL JUNCTION BOX.
SEE DETAIL, THIS SHEET
1750
PROVIDE 1" C FROM MAIN CONTROL
PANEL FOR WIRELESS INTERNET
PROVIDER TO RUN ANTENNA WIRE.
CAP END.
F&V PROJECT NO.
DESIGN TEAM:
DRAWING INFORMATION:
CHECK BY:
REVISION:
CIT
Y O
F B
IG
R
AP
ID
S
ME
CO
ST
A C
OU
NT
Y, M
IC
HIG
AN
WA
TE
RL
OO
L
IF
T S
TA
TIO
N IM
PR
OV
EM
EN
TS
DECEMBER 2019
841250
2960 Lucerne Drive SE
P: 616.977.1000
F: 616.977.1005
Grand Rapids, MI 49546
DESIGN. BUILD. OPERATE.
GRADE
TEMPERATURE SWITCH
NORMALLY OPEN
TEMPERATURE SWITCH
NORMALLY CLOSED
CONTROL TRANSFORMER
TERMINAL BLOCK
RELAY CONTACT, NORMALLY CLOSED
RELAY CONTACT, NORMALLY OPEN
NORMALLY CLOSED
OFF-DELAY TIMING CONTACT,
NORMALLY OPEN
OFF-DELAY TIMING CONTACT,
NORMALLY CLOSED
ON-DELAY TIMING CONTACT,
NORMALLY OPEN
ON-DELAY TIMING CONTACT,
FLOW SWITCH, NORMALLY CLOSED
FLOW SWITCH, NORMALLY OPEN
PUSHBUTTON, NORMALLY CLOSED
PUSHBUTTON, NORMALLY OPEN
PUSH-TO-TEST PILOT LIGHT
3-POSITION SELECTOR SWITCH
R
HAND
OFF
AUTO
x
x
ELECTRICAL CONNECTION
FIELD WIRING
BELOW GRADE WIRING
OVERHEAD ELECTRICAL w/ POLES
GROUND ROD (SINGLE LINE DIAGRAM)
POWER TRANSFORMER
REMOVE
5
1
2SINGLE-PHASE MOTOR
THREE-PHASE MOTOR
THERMOSTAT, WALL MOUNTED, 5'-0" A.F.F.
T
FUSE
OCCUPANCY SENSOR..
JUNCTION BOX.
J
3P
30A
(1)
(2)
COMBINATION MOTOR STARTER, NEMA SIZE 1
DISCONNECT SWITCH, NON - FUSED
MOTOR STARTER, NEMA SIZE 2
LPA1
F
DISCONNECT SWITCH, "F" - FUSED
ELECTRICAL LEGEND
a,b
MANUAL MOTOR STARTING SWITCH, 42" A.F.F.
MS
S
A1,3
OCCUPANCY SENSOR W/MANUAL OVERRIDE
OS
DUPLEX RECEPTACLE, 16" AFF.
UNLESS OTHERWISE NOTED. NUMBER
INDICATES CIRCUIT FROM LPA W/2 #12
& 1 #12 GND IN
3
4
" C.
SINGLE-POLE SWITCH, 42" AFF. "ab"
INDICATES ONE SWITCH FOR EACH
CIRCUIT.
CIRCUIT BREAKER IN PANELBOARD, 30
AMP, 3 POLE
O
HOMERUN TO LIGHTINGPANEL LPA,
CIRCUIT 1. HASHMARKS INDICATE QTY.
OF #12 CONDUCTORS PLUS #12 GND. IF
NO HASH MARKS OR WIRES ARE
INDICATED CONDUIT IS SPARE
3
3 INDICATES FIXTURE TYPE FROM
SCHEDULE
1
PHOTO NUMBER 1 AND
DIRECTION OF PHOTO
LEVEL CONTROL MOUNTING
BRACKET INSTALLATION DETAIL
SCALE: NOT TO SCALE
WETWELL
MANHOLE
6 HOOK STAINLESS STEEL FLOAT SWTICH HOOK
MOUNT BRACKET BEND TO MATCH APPROXIMATE
RADIUS OF MANHOLE ATTACH TO MANHOLE
FRAME WITH 3/8" STAINLESS STEEL BOLTS.
STAINLESS STEEL BAR
SUPPORT USA BLUE BOOK
MD-47715 OR EQUAL
NYLON CABLE TIES (TYP.)
ALLOW 4' MIN. OF SLACK FOR
ADJUSTMENT
CONDUIT TO JUNCTION BOX
FLOAT AND TRANSDUCER CABLES
TO CONTROL PANEL (TYP.)
PROVIDE INSULATING BUSHING ON CONDUIT END
LIFT STATION UPPER PLAN
SCALE: 1/2"=1'-0"
NORTH
LIFT STATION LOWER PLAN
SCALE: 1/2"=1'-0"
NORTH
A1
1-1/2" C
MOUNT PHASE MONITOR
ON WALL OVER MCB
MD
TCB
LPA
MOUNT T1 ON WALL
OVER LPA
WET WELL COVER
WET WELL IS NEC
CLASS 1, DIV. 1
HAZARDOUS AREA
A5
A4
WP
GFI
GFI
A6
1 1
A2
A5
GFI
EXHAUST
FAN
TO LOWER
LEVEL LIGHTS
2
MCP
6"x6" SQUARE DUCT
(TYP.)
A3
GFI
11
A8A7
PROVIDE 2" CONDUIT SLEEVES TO MCP CORED
THROUGH FLOOR FOR PUMP CORDS. TERMINALS
3" BELOW LOWER LEVEL CEILING. SUPPORT PUMP
CORDS FROM CEILING w/STRAIN RELIEF
CONNECTORS OVER EACH PUMP
TO SWITCH ON
UPPER LEVEL
PUMP PORTABLE CORDS
TSL
MCP
4 #14 & 1 #14 GND-1/2"C
3/4" RGS CONDUIT
MAKE A LOOP IN TRANSDUCER
CORD TO ALLOW FOR FUTURE
SPLICING
180
1
1
2
SUMP PUMP
UPPER LEVEL LIGHTS
1000 1 20
50
201
100
1
WET WELL SET POINTS
SET POINTS
IN FEET
ELEVATION CONTROL POINT
3.8' 893.1BACK UP CONTROL ON/HIGH ALARM
3.5' 892.8LAG PUMP ON
3.3' 892.6LEAD PUMP ON
2.6' 891.9BOTH PUMPS OFF
2.3' 891.6BACK UP CONTROL OFF/LOW ALARM
1.0' 890.3TRANSDUCER - USE OFFSET ZERO CALIBRATION
0.0' 889.3WET WELL BOTTOM
TO ANCHOR,
TRANSDUCERS &
FLOATS
PROVIDE USA BLUEBOOK -
48447 STAINLESS STEEL CHAIN
AND ANCHOR
1Issu
ed
F
or P
art 41 P
erm
it
12/2019
RW
W
3.8' 893.1INFLUENT SEWER INVERT
LSH
J
SINGLE LINE DIAGRAM
480 VAC, 3 PH, 3W
FROM EX. WATER TREATMENT PLANT
PM
NEMA 1 ENCLOSURE
PHASE MONITOR
GROUNDING ELECTRODE SYSTEM
(2) GROUNDING ELECTRODES
(1) CONNECTION TO FORCEMAIN
LPA
T1-480 X 120/240
5 KVA
20A-2P
60A
SQUARE DUCT w/SPLIT BOLT
CONNECTORS OR 60 AMP
POWER DISTRIBUTION BLOCK
3FRS-
60
30A-3P
SQUARE DUCT WITH SPLIT BOLT
CONNECTORS OR 60 AMP POWER
DISTRIBUTION BLOCK
MCP
NEMA 1, 60AMP, 3P SE RATED
FUSED DISCONNECT (MD)
REUSE 2" C w/WEATHERHEAD
PROVIDE NEW 3 #4 & 1 #8 GND
3 #4 & 1 #8 GND-1 1/4"C
1 #8 GND-3/4"C
SECONDARY
SURGE ARRESTOR
3 #10 & 1 #12 GND-3/4"C
3 #12 & 1 #12 GND-3/4"C
2
MCP
MAIN CONTROL PANEL
(MCP)
2
2Issu
ed
F
or B
id
12/2019
RW
W
M:\P
roj841001-843000\841250 B
ig R
apids W
aterloo LS
Im
provem
ents 2019\C
ad\P
lns\841250_E
1.dw
g, 12/18/2019 1:38:27 P
M, davet, D
WG
T
o P
DF
.pc3