Water Treatment Plant P&ID Reference

17
Drawing Set for Project Number: 500408 The Forsyth County Water Treatment Plant Expansion 12.0 MGD - ZEEWEED 1000

Transcript of Water Treatment Plant P&ID Reference

Page 1: Water Treatment Plant P&ID Reference

Drawing Set for

Project Number: 500408

The Forsyth County

Water Treatment Plant Expansion

12.0 MGD - ZEEWEED 1000

Page 2: Water Treatment Plant P&ID Reference

07/09/13 0 I.B. M.D. ISSUED FOR APPROVAL

EQUIPMENT SYMBOLS

MUFFLER

MEMBRANE MODULES

& HOUSING

(IF REQ’D)

PLC ALARM FUNCTION WITH

MULTIPLE TRIGGER POINTS

INSTRUMENTS SHARING

COMMON HOUSING

PILOT LIGHT

UNDEFINED

INTERLOCK LOGIC

SYSTEMS WITH

MULTIPLE PLC’S

F

WATER SOFTENER

CAPILLARY TUBING

PNEUMATIC SIGNAL

SOFTWARE LINK

INSTRUMENT CONNECTION

TERMINATION TAG

REVISION TRIANGLE

FLEXIBLE HOSE

FLOOR DRAIN

CALCULATED VALUE

THERMOWELL

MECHANICAL LINK

I

P

ULTRASONIC/ELECTROMAGNETIC

PI

PIG TAIL

RT

T

EX.

SKID BOUNDARY

EQUIPMENT/LINE

SUPPLIED BY OTHERS

OPTIONAL ITEM

FUTURE EQUIPMENT

PIPING SPOOL TAG

MAIN PROCESS LINE

PROCESS LINE

CONTINUATION SYMBOLS

DIAPHRAGM

SEAL

CALIBRATION

COLUMN

ROTAMETER

(VARIABLE AREA

FLOWMETERS)

PORTABLE

EXCHANGE TANK

CAMLOCK CONNECTION

XXXXXX-D-XXX

PERMEATE

TO STORAGE TANK TK-XX

XX USGPM

INJECTION QUILL

NORMALLY

CLOSEDNORMALLY

OPEN

DIAPHRAGM

BUTTERFLY

BALL

GATE OR OTHER

IN-LINE TYPE

NOT OTHERWISE

IDENTIFIED

GLOBE

NEEDLE

CHECK

KNIFE GATE

THREE WAY

RUPTURE DISC

(PRESSURE)

RUPTURE DISC

(VACUUM)

VACUUM BREAKER

AUTOMATIC AIR VENT

PRESSURE REGULATOR

PRESSURE RELIEF/

MULTI FUNCTION VALVE

FLOAT CONTROLLED

SLIDING GATE

VALVE & GATE ACTUATOR SYMBOLS

VALVE & GATE SYMBOLS

UV STERILIZER

CARTRIDGE

FILTER

GRANULAR ACTIVATED

CARBON FILTER (GAC)

OR MULTI MEDIA

FILTER (MMF)

HEAT

EXCHANGER HEATER

FLOW

STRAIGHTENING

DEVICE

STATIC MIXER

PULSATION

DAMPENER

MIXER

BACKFLOW

PREVENTER

DIFFUSER GRID

HH

H

L

LL

LA

I/P CONVERTER

(ELECTRIC ANALOG TO

PNEUMATIC SIGNAL CONVERTER)

RESIN TRAP

Y STRAINER

STEAM TRAP

CYLINDRICAL STRAINER

BACK PRESSURE REGULATOR

VENT AND

FILTER

LINE SYMBOLS & MISC.

PLC-X

PNEUMATIC DIAPHRAGM

SPRING CLOSE PNEUMATIC

CYLINDER (INST.AIR LINES

NOT ALWAYS SHOWN)

SPRING OPEN PNEUMATIC

CYLINDER (INST.AIR LINES

NOT ALWAYS SHOWN)

SOLENOID

ELECTRIC MOTOR

(ANALOG - CONTROL)

VALVE POSITIONER

ELECTRIC MOTOR

(DIGITAL- OPEN/CLOSED)

NOTE: ON LOSS OF PRIMARY POWER

(PNEUMATIC, ELECTRICAL OR HYDRAULIC)

XX: FC = FAIL CLOSED

FO = FAIL OPEN

FL = FAIL TO LAST POSITION

IF NOT SPECIFIED ASSUME FC.

DOUBLE ACTING PNEUMATIC

CYLINDER (INST.AIR LINES

NOT ALWAYS SHOWN)

TRAVEL STOP

DISCRETE

INSTRUMENTS

FIELD

MOUNTED

AUXILIARY

LOCATION

NORMALLY

ACCESSIBLE TO

OPERATOR

PROGRAMMABLE

LOGIC CONTROL

COMPUTER/DCS

FUNCTION

LOCATED ON

SKID CONTROL

PANEL

PINCH

VENTURI

FLOWMETER

FLOWMETER

VORTEX OR

MAGNETIC

(TYPE INDICATED)

PADDLEWHEEL

FLOWMETER

POSITIVE-

DISPLACEMENT-

TYPE FLOW

TOTALIZING

INDICATOR

FLUME

FIXED

SCREEN

VICTAULIC CONNECTION

FLANGED CONNECTION

BLIND FLANGE

NON-FLEX CONNECTION

INSTRUMENTATION LINES

P&ID TIE - INS

HEATING/

COOLING

COIL

ORIFICE PLATE

ORIFICE PLATE

IN QUICK-CHANGE

FITTING

GENERAL INSTRUMENT AND FUNCTION SYMBOLS

SEE INSTRUMENT LETTERS

SUMMING

AVERAGING

LOW

SELECTING

HIGH

SELECTING

S

S/n

I

PLUG OR ANGLE

SEAT

SILENCER

OR FILTER

P&ID LINE TYPES

LOCAL PANEL

CONICAL OR

TEMPORARY STRAINER

REVISED ITEM

FOUR WAY

MUD

WASHPACTOR

WPR-

M-

M-

GRIT WASHER/

CLASSIFIER

M- M-

PERFORATED

TRAVELLING

BAND SCREEN

M- M-

f(x)

HUMAN MACHINE

INTERFACE HMI

OTHER COMBINATIONS OF ANALOG/DIGITAL & DATA HIGHWAY

COMMUNICATION MUST ALSO BE SHOWN AS REQUIRED

SIGNAL

FROM

SIGNAL

TO

CLIENT INTERFACE SIGNALS

(SIZE,SCHEDULE,MATERIAL)

LINE DESIGNATION

SIZE (x"), SCHEDULE, MATERIAL

EX.4", SCH.80, PVC

SCH.80, PVC

SCH.80, CPVC

SCH.40, C.S.

P.E. TUBING

SCH.10, 316L SS

SCH.40, 316L SS

SS TUBING

SCH.10, 304L SS

SCH.40, 304L SS

MOST COMMON MATERIAL’S

NYLON TUBING

COMMON ABBREVIATIONS

MCC MOTOR CONTROL CENTER

MAG MAGNETIC

LOR LOCAL-OFF REMOTE

E-STOP EMERGENCY STOP

AI ANALOG INPUT

DO DIGITAL OUTPUT

FF FOUNDATION FIELD BUS

D.NET DEVICE NET

KK

BALL (MANUAL)

R

CAPPED CONNECTION

BASKET STRAINER

(MOTOR OPTIONAL)

ROTAMETER WITH

BUILT-IN HAND

CONTROL VALVE

EDUCTOR/

EJECTOR

UNSPECIFIED

FUNCTION

ELECTRIC SIGNAL (ANALOG OR

DIGITAL)

ELECTRIC TRACE

& INSULATION

S

M

M

HAND OVERRIDE

ACTUATOR WITH

TRAVEL STOP

SAMPLE VALVE

SSOLENOID VALVE

S

M M

IAS INSTRUMENT AIR SUPPLY

SP SET POINT

HOA HAND-OFF AUTO

DI DIGITAL INPUT

AO ANALOG OUTPUT

AIR DRYER

TURBINE

LOBE BLOWER

CENTRIFUGAL

BLOWER

CENTRIFUGAL

PUMP

POSITIVE

DISPLACEMENT

PUMP

REGENERATIVE

BLOWER

DIAPHRAGM

PUMP

VACUUM PUMP

(WET OR DRY)

TURBINE

PUMP

METERING

PUMP

COMPRESSOR

ROTARY SCREW

COMPRESSOR

PISTON

CAN

PUMP

DESICCANT

DRYER

AXIAL FLOW

PUMP

SUBMERSIBLE

PUMP

BLOWER

(GENERIC)

PUMP

(GENERIC)

07/04/20

0

07/04/20

07/09/12

07/09/12

A.P.L.

1:1

THE FORSYTH COUNTY - 12.0 MGD WTP

K.S.

N.K.

M.D. ISA SYMBOLOGY COVER SHEET

500408-L-001

500408L1 1.DGN

SHEET

1 OF 2

789101112D (24x36)

D

DATEREV. DESCRIPTION

REV.

DATEAPPROVAL

SCALE: DRAWING NO.

TITLE:

CUSTOMER:

(Y/M/D)

DSGNZONE APPD

SIZE:

CADD FILE:

6 5 4 3 2 1

B

A

C

D

G

H

F

E

B

A

C

D

G

H

F

E

789101112 6 5 4 3 2 1

DRWN:

DSGN:

CHKD:

APPD:

THIS DOCUMENT EMBODIES DESIGNS AND INFORMATION PROPRIETARY TO GE ZENON ULC.

IT IS TO BE USED ONLY FOR THE PURPOSE AND BY THE ENTITY FOR WHICH IT WAS ORIGINALLY SUPPLIED. THE

DOCUMENT MAY NOT BE DUPLICATED, DISCLOSED TO ANY OTHER PERSON OR ENTITY, OR USED FOR MANUFACTURE OF

THE ITEM IN PART OR IN WHOLE WITHOUT THE PRIOR WRITTEN PERMISSION OF GE ZENON ULC.

Page 3: Water Treatment Plant P&ID Reference

07/09/13 0 I.B. M.D. ISSUED FOR APPROVAL

HAND

POWER

MECHANICAL OR INSTRUMENT DEVICE TAG IDENTIFICATION PREFIX

AV AIR VENT

AIR DRIER

HAND VALVE

RESIN TRAP

STRAINER

WASHPACTOR

AC

B

CV

DR

F

FG

FI

FO

FV

FX

H

HC

HE

HV

LG

LI

MX

P

PD

PI

RT

SG

SV

TI

TK

UV

VB

YY

AIR COMPRESSOR

ANALYSIS ELEMENT WITH ANALYSIS INDICATING TRANSMITTER AE/AIT

AE/AT ANALYSIS ELEMENT WITH ANALYSIS TRANSMITTER

BLOWER

BPV BACK PRESSURE VALVE

CHECK VALVE/INJECTION QUILL

FILTER

FCV FLOW CONTROL VALVE

FLOW ELEMENT WITH FLOW INDICATING TRANSMITTERFE/FIT

FE/FT FLOW ELEMENT WITH FLOW TRANSMITTER

FLOW SIGHT GLASS

FLOW INDICATOR

ORIFICE PLATE

AUTOMATIC VALVE

FLOW STRAIGHTENING DEVICE

GWC GRIT WASHER/CLASSIFIER

HEATER

HEATING COIL

HCV HAND CONTROL VALVE

HEAT EXCHANGER

LCV LEVEL CONTROL VALVE

LE/LIT LEVEL ELEMENT WITH LEVEL INDICATING TRANSMITTER

LE/LT LEVEL ELEMENT WITH LEVEL TRANSMITTER

LEVEL SIGHT GLASS

LEVEL INDICATOR

LS* LEVEL SWITCH

MFV MULTI FUNCTION VALVE (COMBINATION RELIEF & BACKPRESSURE VALVE FOR METERING PUMPS)

MIXER

STATIC MIXERMXS

PUMP

PULSATION DAMPENER

PE/PIT PRESSURE ELEMENT WITH PRESSURE INDICATING TRANSMITTER

PE/PT PRESSURE ELEMENT WITH PRESSURE TRANSMITTER

PRESSURE INDICATOR

PRESSURE REGULATING VALVE

PRESSURE SWITCH

PRV

PS*

PSE RUPTURE DISC

PRESSURE RELIEF VALVEPSV

SCR SCREEN

SIGHT GLASS

STR

SAMPLE VALVE

TEMPERATURE CONTROL VALVETCV

TE/TIT TEMPERATURE ELEMENT WITH TEMPERATURE INDICATING TRANSMITTER

TE/TT TEMPERATURE ELEMENT WITH TEMPERATURE TRANSMITTER

TEMPERATURE INDICATOR

TANK

TEMPERATURE SWITCHTS*

TURBINETURB

UV STERILIZER

VACUUM BREAKER

VIBRATION SWITCHVS*

WPR

SOLENOID FOR PNEUMATIC CONTROL OF AUTOMATIC VALVE

* ADD THE SUFFIX HH (HIGH HIGH), H (HIGH), L (LOW), LL (LOW LOW) AS REQUIRED FOR THESE ITEMS.

ISA TEXT ABBREVIATIONS

MEASURED OR

INDICATING VARIABLEMODIFIER

READOUT OR

PASSIVE FUNCTIONMODIFIEROUTPUT FUNCTION

ANALYSIS

BURNER, COMBUSTION

USERS CHOICE

USERS CHOICE

VOLTAGE

FLOW RATE

USERS CHOICE

CURRENT (ELECTRICAL)

TIME, TIME SCHEDULE

LEVEL

LOG REMOVAL

USERS CHOICE

USERS CHOICE

PRESSURE, VACUUM

QUANTITY

RADIATION

SPEED, FREQUENCY

TEMPERATURE

MULTIVARIABLE

VIBRATION, MECHANICAL

ANALYSIS

WEIGHT, FORCE

UNCLASSIFIED

POSITION, DIMENSION

DIFFERENTIAL

RATIO (FRACTION)

SCAN

TIME RATE OF CHANGE

MOMENTARY

INTEGRATE, TOTALISE

SAFETY

X AXIS

Y AXIS

Z AXIS

AVERAGE

MULTIFUNCTION

WELL

RECORD

POINT (TEST)

CONNECTION

LIGHT

ORIFICE, RESTRICTION

USERS CHOICE USERS CHOICE USERS CHOICE

INDICATE

GLASS, VIEWING DEVICE

SENSOR

(PRIMARY ELEMENT)

USERS CHOICE

ALARM

USERS CHOICE USERS CHOICE

CONTROL

CONTROL STATION

SWITCH

TRANSMIT

MULTIFUNCTION

VALVE, DAMPER,

LOUVER

UNCLASSIFIED UNCLASSIFIED

MULTIFUNCTION

EVENT, STATE OR

PRESENTRELAY, COMPUTE,

CONVERT

DRIVER, ACTUATOR,

UNCLASSIFIED FINAL

CONTROL ELEMENT

HIGH

LOW

MIDDLE, INTERMEDIATE

Z

A

B

C

D

E

F

G

H

I

J

K

L

M

N

O

P

Q

R

S

T

U

V

W

X

Y

07/04/20

0

07/04/20

07/09/12

07/09/12

A.P.L.

1:1

THE FORSYTH COUNTY - 12.0 MGD WTP

K.S.

N.K.

M.D. ISA SYMBOLOGY COVER SHEET

500408-L-001

500408L1 2.DGN

SHEET

2 OF 2

789101112D (24x36)

D

DATEREV. DESCRIPTION

REV.

DATEAPPROVAL

SCALE: DRAWING NO.

TITLE:

CUSTOMER:

(Y/M/D)

DSGNZONE APPD

SIZE:

CADD FILE:

6 5 4 3 2 1

B

A

C

D

G

H

F

E

B

A

C

D

G

H

F

E

789101112 6 5 4 3 2 1

DRWN:

DSGN:

CHKD:

APPD:

THIS DOCUMENT EMBODIES DESIGNS AND INFORMATION PROPRIETARY TO GE ZENON ULC.

IT IS TO BE USED ONLY FOR THE PURPOSE AND BY THE ENTITY FOR WHICH IT WAS ORIGINALLY SUPPLIED. THE

DOCUMENT MAY NOT BE DUPLICATED, DISCLOSED TO ANY OTHER PERSON OR ENTITY, OR USED FOR MANUFACTURE OF

THE ITEM IN PART OR IN WHOLE WITHOUT THE PRIOR WRITTEN PERMISSION OF GE ZENON ULC.

Page 4: Water Treatment Plant P&ID Reference

07/04/27

0

07/04/20

07/09/12

07/09/12

I.B.

THE FORSYTH COUNTY - 12.0 MGD WTP

K.S.

N.K.

M.D. PROCESS FLOW DIAGRAM 500408A001.DGN

500408-A-001SHEET

1 OF 1 1:1

07/09/13 0 I.B. M.D. ISSUED FOR APPROVAL

CLARIFIED WATER

CLEARWELL

BACKWASH WASTE

TO BACKWASH

RECOVERY BASINS

ELECTRIC

WATER

HEATER

SODIUM

BISULFITE

SODIUM

HYDROXIDE

P-9700A/B

CIP PUMPS

FEED

CHANNEL

(BY OTHERS)

TK-3500-1 TO 6

(7 TO 11 FUTURE)

MEMBRANE TANK

(BY OTHERS)

B-8500A/B

NEUTRALIZED

CHEMICAL WASTE

TO RESIDUALS

HOLDING BASINS

TK-9700

CIP TANK

TK-8800

BACKPULSE TANK

P-3500-1 TO 6

(7 TO 11 FUTURE)

PROCESS PUMP

SEALWEIR

SODIUM

HYPOCHLORITE

CITRIC

ACID

STR-7600 A

STR-7600 B

STR-7600 C

STR-7600 A - SELF-CLEANING STRAINER

STR-7600 B - BASKET STRAINER

STR-7600 C - SELF-CLEANING STRAINER (FUTURE)

P-5300 A/B P-5500 A/B

P-5100 A/B P-6500 A/B

P-6600 A/B

789101112D (24x36)

D

DATEREV. DESCRIPTION

REV.

DATEAPPROVAL

SCALE: DRAWING NO.

TITLE:

CUSTOMER:

(Y/M/D)

DSGNZONE APPD

SIZE:

CADD FILE:

6 5 4 3 2 1

B

A

C

D

G

H

F

E

B

A

C

D

G

H

F

E

789101112 6 5 4 3 2 1

DRWN:

DSGN:

CHKD:

APPD:

THIS DOCUMENT EMBODIES DESIGNS AND INFORMATION PROPRIETARY TO GE ZENON ULC.

IT IS TO BE USED ONLY FOR THE PURPOSE AND BY THE ENTITY FOR WHICH IT WAS ORIGINALLY SUPPLIED. THE

DOCUMENT MAY NOT BE DUPLICATED, DISCLOSED TO ANY OTHER PERSON OR ENTITY, OR USED FOR MANUFACTURE OF

THE ITEM IN PART OR IN WHOLE WITHOUT THE PRIOR WRITTEN PERMISSION OF GE ZENON ULC.

Page 5: Water Treatment Plant P&ID Reference

SCREEN WASH WATER

FROM PLANT SERVICE

CLARIFIED WATER

FROM SEDIMENTATION

TANK OR SUPERPULSATOR HV-7587

6"

500408-D-001 SHT.2

SCREENED CLARIFIED

WATER

500408-D-015

SCREENED CLARIFIED

SAMPLE

36", SCH.10, 304L SS

FV-7637

1/2"

S

DO

S

HIS

YS

TYP. SOLENOID VALVE CONTROL DETAIL

07/09/13 0 I.B. M.D. ISSUED FOR APPROVAL

07/04/27

3

07/04/20

07/09/12

07/09/12

I.B.

THE FORSYTH COUNTY - 12.0 MGD WTP

K.S.

N.K.

M.D. PIPING & INSTRUMENTATION DIAGRAM PRE-TREATMENT 500408D1 1.DGN

500408-D-001SHEET

1 OF 2 1:1

36" CLD1

08/03/11 1 G.C. M.D. REVISED AS NOTED

08/04/01 2 X.C. M.D. REVISED AS NOTED

12 MGD

24 MGD (FUTURE)

STR-A

STR-C

NOTES:

1. ALL DOTTED LINES/EQUIPMENT

BY OTHERS

2. STRAINER CONTROLLED BY LOCAL

PANEL, NOT ZENON PLC.

3. INCLUDED WITH STRAINER PACKAGE

4. 900 GPM @ 40 PSIG NEEDED FOR

BACK WASHING.

5. STRAINER SYSTEM SUPPLIED AND

CONTROLLED BY OTHERS.

09/11/04 3 X.C. M.D. REVISED AS NOTED

3

3

PI

7641B

HV-7641B

1

2"

2

HV-7680B

M-7600B

HV-7640B

1

2"

PI

7640B

HV-7660B

2"

30" 30"

STR-7600B

0.5mm

BASKET STRAINER

RATED FLOW: 9365 GPM

CLEAN PRESSURE DROP:

0.40 PSIG @ 12410 GPM

STANDBY

HV-7681B

(SEE NOTE 5)

(SEE NOTE 5)

789101112D (24x36)

D

DATEREV. DESCRIPTION

REV.

DATEAPPROVAL

SCALE: DRAWING NO.

TITLE:

CUSTOMER:

(Y/M/D)

DSGNZONE APPD

SIZE:

CADD FILE:

6 5 4 3 2 1

B

A

C

D

G

H

F

E

B

A

C

D

G

H

F

E

789101112 6 5 4 3 2 1

DRWN:

DSGN:

CHKD:

APPD:

THIS DOCUMENT EMBODIES DESIGNS AND INFORMATION PROPRIETARY TO GE ZENON ULC.

IT IS TO BE USED ONLY FOR THE PURPOSE AND BY THE ENTITY FOR WHICH IT WAS ORIGINALLY SUPPLIED. THE

DOCUMENT MAY NOT BE DUPLICATED, DISCLOSED TO ANY OTHER PERSON OR ENTITY, OR USED FOR MANUFACTURE OF

THE ITEM IN PART OR IN WHOLE WITHOUT THE PRIOR WRITTEN PERMISSION OF GE ZENON ULC.

Page 6: Water Treatment Plant P&ID Reference

07/04/20

2

07/04/20

07/09/12

07/09/12

A.P.L.

THE FORSYTH COUNTY - 12.0 MGD WTP

K.S.

N.K.

M.D. PIPING & INSTRUMENTATION DIAGRAM DISTRIBUTION CHANNEL 500408D1 2.DGN

500408-D-001SHEET

2 OF 2 1:1

OVERFLOW

TO BACKWASH

RECOVERY BASINS

LIT

7626

LE

7626

AI

LI

7626

MULTIPLE

LINES

LY

7626

500408-D-001,SHT.1

SCREENED CLARIFIED

WATER

TK-7600

FEED CHANNEL

30", SCH.10, 304L SS

18", SCH.10, 304L SS

42", SCH.10, 304L SS

NOTE:

1. ALL DOTTED LINES/EQUIPMENT

BY OTHERS

500408-D-003

SCREENED CLARIFIED

WATER

TO MEMBRANE TANKS

LA

7626

LL

7626

HV-7626

1�"

07/09/13 0 I.B. M.D. ISSUED FOR APPROVAL

2

08/03/11 1 G.C. M.D. REVISED AS NOTED

08/04/01 2 X.C. M.D. REVISED AS NOTED

10", SCH.10, 304 SS 500408-D-013

PERMEATE

BY OTHERS

RANGE: 0-60"

789101112D (24x36)

D

DATEREV. DESCRIPTION

REV.

DATEAPPROVAL

SCALE: DRAWING NO.

TITLE:

CUSTOMER:

(Y/M/D)

DSGNZONE APPD

SIZE:

CADD FILE:

6 5 4 3 2 1

B

A

C

D

G

H

F

E

B

A

C

D

G

H

F

E

789101112 6 5 4 3 2 1

DRWN:

DSGN:

CHKD:

APPD:

THIS DOCUMENT EMBODIES DESIGNS AND INFORMATION PROPRIETARY TO GE ZENON ULC.

IT IS TO BE USED ONLY FOR THE PURPOSE AND BY THE ENTITY FOR WHICH IT WAS ORIGINALLY SUPPLIED. THE

DOCUMENT MAY NOT BE DUPLICATED, DISCLOSED TO ANY OTHER PERSON OR ENTITY, OR USED FOR MANUFACTURE OF

THE ITEM IN PART OR IN WHOLE WITHOUT THE PRIOR WRITTEN PERMISSION OF GE ZENON ULC.

Page 7: Water Treatment Plant P&ID Reference

07/04/27

2

07/04/23

07/09/12

07/09/12

I.B.

THE FORSYTH COUNTY - 12.0 MGD WTP

K.S.

N.K.

M.D. PIPING & INSTRUMENTATION DIAGRAM P.D. BLOWERS & ASSOC. EQUIPMENT 500408D002.DGN

500408-D-002SHEET

1 OF 1 1:1

FLL

8506B

PI

8540A

FSL

8506B

PI

8540B

PSV-8582A

PSV-8582B

INLET FILTER

AND SILENCER

DI

HV-8580A

HV-8580B

CV-8585B

CV-8585A

INLET FILTER

AND SILENCERDISCHARGE

SILENCER

DISCHARGE

SILENCERMULTIPLE

LINES

DI

FAL

8506B

B-8500A

B-8500B

3", SCH.10, 304L SS

3", SCH.10, 304L SS

3", SCH.10, 304L SS

ACCUSTIC HOOD

ACCUSTIC HOOD

500408-D-003

AIR SCOUR

TO TK-3400

FLL

8506A

FSL

8506A

FAL

8506A

S.P.= 110 SCFM

DECREASING

S.P.= 110 SCFM

DECREASING

�"

�"

S.P.= 11 PSIG

(SEE NOTE 3)

S.P.= 11 PSIG

(SEE NOTE 3)

B-8500A/B

MEMBRANE BLOWERS

131-223 SCFM @ 5.32 TO 5.75 PSIG

10 HP 3600 RPM

480 V/ 3 PH/ 60 HZ

HV-8540A

1/2"

HV-8540B

1/2"

HOA

SMY

8500A

DI DO AODI

YS

8500A

YA

8500A

SC

8500A

HA

8500A

HIS

8500A

YL

8500A

M-8500A

JS

8500A

SC

8500A

HS

8500A

KQI

8500A

KQ

8500A

HOA

SMY

8500B

DI DO AODI

YS

8500B

YA

8500B

SC

8500B

HA

8500B

HIS

8500B

YL

8500B

M-8500B

JS

8500B

SC

8500B

HS

8500B

KQI

8500B

KQ

8500B

(SEE NOTE 4)

(SEE NOTE 4)

07/09/13 0 I.B. M.D. ISSUED FOR APPROVAL

3",SCH.10, 304L SS

3",SCH.10, 304L SS

2

08/03/11 1 G.C. M.D. REVISED AS NOTED

08/04/01 2 G.V.K. M.D. REVISED AS NOTED

NOTE:

1. ALL DOTTED LINES/EQUIPMENT

BY OTHERS.

2. ZENON TRAIN 1 TAGS SHOWN.

3. INCLUDED WITH BLOWER PACKAGE.

4. ESTIMATED BLOWER DISCHARGE AIR

TEMPERATURE IS 150^F. PROVIDE

PROTECTION ON PIPING IS NECESSARY

(BY OTHERS).

5. LOW POINT DRAINS & HIGH VENT POINTS

BY OTHERS.

789101112D (24x36)

D

DATEREV. DESCRIPTION

REV.

DATEAPPROVAL

SCALE: DRAWING NO.

TITLE:

CUSTOMER:

(Y/M/D)

DSGNZONE APPD

SIZE:

CADD FILE:

6 5 4 3 2 1

B

A

C

D

G

H

F

E

B

A

C

D

G

H

F

E

789101112 6 5 4 3 2 1

DRWN:

DSGN:

CHKD:

APPD:

THIS DOCUMENT EMBODIES DESIGNS AND INFORMATION PROPRIETARY TO GE ZENON ULC.

IT IS TO BE USED ONLY FOR THE PURPOSE AND BY THE ENTITY FOR WHICH IT WAS ORIGINALLY SUPPLIED. THE

DOCUMENT MAY NOT BE DUPLICATED, DISCLOSED TO ANY OTHER PERSON OR ENTITY, OR USED FOR MANUFACTURE OF

THE ITEM IN PART OR IN WHOLE WITHOUT THE PRIOR WRITTEN PERMISSION OF GE ZENON ULC.

Page 8: Water Treatment Plant P&ID Reference

07/04/27

2

07/04/23

07/09/12

07/09/12

I.B.

THE FORSYTH COUNTY - 12.0 MGD WTP

K.S.

N.K.

M.D. PIPING & INSTRUMENTATION DIAGRAM MEMBRANES & ASSOC. EQUIPEMENT 500408D003.DGN

500408-D-003SHEET

1 OF 1 1:1

PDIC

3423-1

PDIC

8823-1

PDL

8823-1

PDL

3423-1

H

L

LL

H

L

LL

H

PDL

8123-1

H

TMP

BACKWASH WASTE

TO BACKWASH

RECOVERY BASINS

CA

SS

ET

TE

B-1

CA

SS

ET

TE

A-1

HV-3484A-1

2"

HV-3484B-1

2"

FV-3473-1

HV-3426-1

1�"

AI

HH

H

L

LL

HH

H

L

LL

IASIP

AO

HIS

3463-1

ZC

3463-1

LIC

3426-1

LI

3426-1

LL

3426-1

LY

3426-1

LA

3426-1

LIT

3426-1

LE

3426-1

HV-3482A-1

10"

HV-3482B-1

10"

FV-9761C-1

2"

FV-9761B-1

FV-3467-1

PDC

3423-1

PDC

8823-1

PDA

8823-1

PDA

3423-1

PDA

8123-1

LC

3426-1

HV-3466-1

FV-9761A-1

FCV-3463-1

IASIP

AO

ZC

3463-1

HIS

3463-1

BAFFLE PLATE

(BY OTHERS)

TK-3400-1

MEMBRANE TANK

HIS

HIS

F.O.

3", SCH.10, 304L SS

6", SCH.80, CPVC

18", SCH.10, 304L SS

1", SCH.10, 304L SS

12", SCH.10, 304L SS

18", SCH.10, 304L SS

12", SCH.10, 304L SS

3", SCH.10, 304L SS

2 ZW-1000 v3 CASSETTES OF 51/60 MODULES PER TRAIN

CONCRETE CONSTRUCTION

HV-3887-1

1"

DO EXHAUST

IAS

S

YS

DO

S

YS

FC

ANGLE SEAT VALVE CONTROL DETAIL

TYP. PNEUMATIC ACTUATED VALVE CONTROL DETAIL

500408-D-010

CIP / DRAIN

RECIRCULATION RETURN/

TANK DRAIN FOR CLEAN

500408-D-001,SHT.2

SCREENED CLARIFIED

WATER

FROM DISTRIBUTION

CHANNEL

500408-D-005

PERMEATE/BACKPULSE

TO P-3500/FROM

BACKPULSE SYSTEM

RANGE:

4 TO 140 IN

(SEE NOTE 4)500408-D-002

AIR SCOUR

FROM B-8500 A/B

FCV-3863-1

07/09/13 0 I.B. M.D. ISSUED FOR APPROVAL

S

DO

YS

9267-1

FV-9267-1

�"

HV-9291-1

1"

FV-9268-1

1"

P-9200-1

VACUUM EJECTOR

(FOR PRIMING)

�",SCH.40, 304L SS

HV-9290-1

�"

EJECTOR ASSEMBLY AIR SUPPLY ASSEMBLY

EXHAUST

1" FLEX HOSE

OR PVC

(BY OTHERS)

F-9200-1

�"

AIR SUPPLY

�"

NPS-F

�" ODT,

PP TUBING

(BY OTHERS)PI

9240-1

1"

1",SCH.40,

304L SS

500408-D-012

MIT AIR

FROM AC-9100 A/B

500408-D-012

INSTRUMENT AIR

13.5 SCFM @ 80 PSIG

FROM AC-9100 A/B

NOTE 3

NOTES:

1. ALL DOTTED LINES/EQUIPMENT

BY OTHERS.

2. DRAWING TYPICAL FOR TRAINS 1 TO 6.

ZENON TRAIN 1 TAGS SHOWN.

3. EJECTORS TO BE LOCATED AT HIGH POINT

IN PIPING

4. A PORTION OF THE AIR HEADER NEEDS

TO BE LOCATED ABOVE THE HIGHEST

WATER LEVEL IN THE MEMBRANE TANK.

08/03/11 1 G.C. M.D. REVISED AS NOTED

08/04/01 2 G.V.K. M.D. REVISED AS NOTED

HV-3463-1

OVERFLOW TO

DISTRIBUTION

CHANNEL

2

2

2

2

2

789101112D (24x36)

D

DATEREV. DESCRIPTION

REV.

DATEAPPROVAL

SCALE: DRAWING NO.

TITLE:

CUSTOMER:

(Y/M/D)

DSGNZONE APPD

SIZE:

CADD FILE:

6 5 4 3 2 1

B

A

C

D

G

H

F

E

B

A

C

D

G

H

F

E

789101112 6 5 4 3 2 1

DRWN:

DSGN:

CHKD:

APPD:

THIS DOCUMENT EMBODIES DESIGNS AND INFORMATION PROPRIETARY TO GE ZENON ULC.

IT IS TO BE USED ONLY FOR THE PURPOSE AND BY THE ENTITY FOR WHICH IT WAS ORIGINALLY SUPPLIED. THE

DOCUMENT MAY NOT BE DUPLICATED, DISCLOSED TO ANY OTHER PERSON OR ENTITY, OR USED FOR MANUFACTURE OF

THE ITEM IN PART OR IN WHOLE WITHOUT THE PRIOR WRITTEN PERMISSION OF GE ZENON ULC.

Page 9: Water Treatment Plant P&ID Reference

07/04/27

2

07/04/23

07/09/12

07/09/12

I.B.

THE FORSYTH COUNTY - 12.0 MGD WTP

K.S.

N.K.

M.D. PIPING & INSTRUMENTATION DIAGRAM PROCESS PUMP & ASSOC. EQUIPMENT 500408D005.DGN

500408-D-005SHEET

1 OF 1 1:1

FV-3560-1

FV-8860-1

CV-3585-1

FV-8861-1

HV-3586-1

1" HV-3587-1

1"

PI

3541-1

PI

3540-1

HV-3541-1

�"

HV-3540-1

�"

PE

3523-1

PIT

3523-1

M-3500-1

FE

3520-1

H

L

H

L

FQJ

3522-1

FQM

3522-1

FC

3522-1

FQ

3522-1

FY

3522-1

FQJI

3522-1

FQMI

3522-1

FIC

3522-1

FQI

3522-1

FL

3522-1

FIC

8820-1

FL

8820-1

FQMI

8820-1

FQJI

8820-1

HH

H

L

LL

AI

FIC

3520-1

FL

3520-1

FJI

3520-1

FQI

3520-1

HH

H

L

LL

FIT

3520-1

FC

3520-1

FA

3520-1

FJ

3520-1

FFMY

3520-

FQ

3520-1

FQM

8820-1

FQJ

8820-1

FA

8820-1

FC

8820-1

H

L

H

L

MAG

PLH

8807-1

PAH

8807-1

PSH

8807-1

DI

AI

PY

3523-1

PI

3523-1

HH

H

L

LL

PL

3523-1

PA

3523-1

HH

H

L

LL

10", SCH.10, 304L SS 10", SCH.10, 304L SS

10", SCH.10, 304L SS

12", SCH.10, 304L SS

12", SCH.10, 304L SS

FV-3561-1

TYP. PNEUMATIC ACTUATED VALVE CONTROL DETAIL

DO EXHAUST

IAS

S

HIS

YS

500408-D-013

PERMEATE

TO COMMON PERMEATE

HEADER

500408-D-007

BACKPULSE WATER

FROM BACKPULSE TANK

500408-D-015

PERMEATE SAMPLE

500408-D-003

PERMEATE/

BACKPULSE

FROM/TO MEMBRANES

1/2", P.E. TUBING

(SEE NOTE 3)

8"10"

S.P.= 11 PSIG

INCREASINGRANGE:

-15 TO 15 PSIG

AO

P-3500-1

PROCESS PUMP

1871 GPM @ 41.2 FT

30HP, 880 RPM

480 V/ 3 PH/ 60 HZ

DO

S

HIS

YS

TYP. SOLENOID VALVE CONTROL DETAIL

S

FV-3536A

�"

NOTES:

1. ALL DOTTED LINES/EQUIPMENT

BY OTHERS

2. DRAWING TYPICAL FOR TRAINS 1 TO 6.

ZENON TRAIN 1 TAGS SHOWN.

3. 5 PIPE DIAMETERS UPSTREAM, 3 PIPE

DIAMETERS DOWNSTREAM, STRAIGHT PIPE

RUN RECOMMENDED FOR MAXIMUM ACCURACY.

07/09/13 0 I.B. M.D. ISSUED FOR APPROVAL

2

HIS

3500-1

YL

3500-1

YA

3500-1

YS

3500-1

SC

3500-1

I

HOA

JS

3500-1

DI DO DI

TLH

3500-1

SM

3500-1

HA

3500-1

KQI

3500-1

SC

3500-1

HS

3500-1

YL

3500-1

HOA

TAH

3500-1

JC

3500-1

TSH

3500-1 RANGE:

0 TO 2000 GPM

08/03/11 1 G.C. M.D. REVISED AS NOTED

08/04/01 2 G.V.K. M.D. REVISED AS NOTED

2

789101112D (24x36)

D

DATEREV. DESCRIPTION

REV.

DATEAPPROVAL

SCALE: DRAWING NO.

TITLE:

CUSTOMER:

(Y/M/D)

DSGNZONE APPD

SIZE:

CADD FILE:

6 5 4 3 2 1

B

A

C

D

G

H

F

E

B

A

C

D

G

H

F

E

789101112 6 5 4 3 2 1

DRWN:

DSGN:

CHKD:

APPD:

THIS DOCUMENT EMBODIES DESIGNS AND INFORMATION PROPRIETARY TO GE ZENON ULC.

IT IS TO BE USED ONLY FOR THE PURPOSE AND BY THE ENTITY FOR WHICH IT WAS ORIGINALLY SUPPLIED. THE

DOCUMENT MAY NOT BE DUPLICATED, DISCLOSED TO ANY OTHER PERSON OR ENTITY, OR USED FOR MANUFACTURE OF

THE ITEM IN PART OR IN WHOLE WITHOUT THE PRIOR WRITTEN PERMISSION OF GE ZENON ULC.

Page 10: Water Treatment Plant P&ID Reference

HV-8884

HV-8895

4"

LY

8826

LA

8826

LL

8826

LI

8826

LE

8826

LIT

8826

HH

H

L

LL

F

CV-8898

FV-8870

POTABLE WATER

FROM PLANT SERVICE

WATER SOURCE

HV-8890

HH

H

L

LL

AI

MULTIPLE LINES

2"(50mm), SCH.80 PVC

HV-5696

FV-5677

CV-5685

VENT C/W

AIR FILTER

F-8800

STR-8800

6", SCH.10, 304L SS

12", SCH.10, 304L SS

�", SCH.80, CPVC

TYP. PNEUMATIC ACTUATED VALVE CONTROL DETAIL

DO EXHAUST

IAS

S

HIS

YS

NOTES:

1. ALL DOTTED LINES/EQUIPMENT

BY OTHERS

2. PIPE SPOOL FOR STRAINER MAINTENANCE/

REMOVAL AND ISOLATION VALVE ACTUATION.

500408-D-005

BACKPULSE WATER

TO MEMBRANES

500408-D-013

PERMEATE

FROM COMMON

PERMEATE HEADER

FROM P-5100

SODIUM HYPOCHLORITE

FOR BIOGROWTH PREVENTION

500408-D-011,SHT.1

(SEE NOTE 2)

HV-8826

1�"

RANGE:

12" TO 100"

07/04/27

2

07/04/23

07/09/12

07/09/12

I.B.

THE FORSYTH COUNTY - 12.0 MGD WTP

K.S.

N.K.

M.D. PIPING & INSTRUMENTATION DIAGRAM BACKPULSE TANK & ASSOC. EQUIPMENT 500408D007.DGN

500408-D-007SHEET

1 OF 1 1:1

07/09/13 0 I.B. M.D. ISSUED FOR APPROVAL

8",

SC

H.80,

PV

C

08/03/11 1 G.C. M.D. REVISED AS NOTED

HV-8871

HV-5697

�"

TK-8800

BACKPULSE TANK

2,000 USGAL

CT - 2000

PE CONSTRUCTION

08/04/01 2 G.V.K. M.D. REVISED AS NOTED

2

22

2

2

2

2

789101112D (24x36)

D

DATEREV. DESCRIPTION

REV.

DATEAPPROVAL

SCALE: DRAWING NO.

TITLE:

CUSTOMER:

(Y/M/D)

DSGNZONE APPD

SIZE:

CADD FILE:

6 5 4 3 2 1

B

A

C

D

G

H

F

E

B

A

C

D

G

H

F

E

789101112 6 5 4 3 2 1

DRWN:

DSGN:

CHKD:

APPD:

THIS DOCUMENT EMBODIES DESIGNS AND INFORMATION PROPRIETARY TO GE ZENON ULC.

IT IS TO BE USED ONLY FOR THE PURPOSE AND BY THE ENTITY FOR WHICH IT WAS ORIGINALLY SUPPLIED. THE

DOCUMENT MAY NOT BE DUPLICATED, DISCLOSED TO ANY OTHER PERSON OR ENTITY, OR USED FOR MANUFACTURE OF

THE ITEM IN PART OR IN WHOLE WITHOUT THE PRIOR WRITTEN PERMISSION OF GE ZENON ULC.

Page 11: Water Treatment Plant P&ID Reference

07/04/27

1

07/04/23

07/09/12

07/09/12

I.B.

THE FORSYTH COUNTY - 12.0 MGD WTP

K.S.

N.K.

M.D. PIPING & INSTRUMENTATION DIAGRAM VACUUM PUMPS & ASSOC. EQUIPMENT 500408D009.DGN

500408-D-009SHEET

1 OF 1 1:1

FV-9261A

TO

ATMOSPHERE

TO

ATMOSPHERE

PI

9241

HV-9241

�"

FV-9261B

HCV-9292A

FROM

ATMOSPHERE

MULTIPLE LINES

FROM ATM.

TO

ATMOSPHERE

FV-9261C

VACUUM PUMPS

LSH

9202-1

LAH

9202-1

LLH

9202-1

TK-9200

DI

P-9200A

M-9200A

M-9200B

M-9200C

P-9200C

P-9200B

S

FV-9292A

�"

S

FV-9292B

�"

S

FV-9292C

�"

SEE NOTE 2

(TYP.)

LIQUID

RESERVOIR

30 GAL

LG

92-1

PI

9243

HV-9243

�"

FV-9200A

FV-9200B

FV-9200C

1�", SCH.80, CPVC 3", SCH.80, CPVC 3", SCH.80, CPVC

2", SCH.80, CPVC 2", SCH.80, CPVC

2", SCH.80, CPVC 2", SCH.80, CPVC

2", SCH.80, CPVC 2", SCH.80, CPVC

TYP. PNEUMATIC ACTUATED VALVE CONTROL DETAIL

DO EXHAUST

IAS

S

HIS

YS

TYP. BLOWER CONTROL DETAIL

YS

YA

HA

DI DO DI

HIS

YL

M-

HOA

KQI

JS

HS

YL

DO

S

HIS

YS

TYP. SOLENOID VALVECONTROL DETAIL

500408-D-003

AIR/VACUUM

FROM AIR RELEASE VALVE

(SEE NOTE 5)

(TYP.)(SEE NOTE 6)

(TYP.)

(SEE NOTE 4)

(TYP.)

FV-9262A

FV-9262D

1"

FV-9262B

FV-9262C

2"

2"2"

�"

(SEE NOTE 3)

(TYP.)

(SEE NOTE 3)

(TYP.)

NOTES:

1. ALL DOTTED LINES/EQUIPMENT

BY OTHERS

2. DISCHARGE AIR MAY BE HOT AND HUMID, PROTECT

OPERATORS APPROPRIATELY.

3. TO BE INSTALLED AS CLOSE TO LIQUID RESERVOIR

AS POSSIBLE.

4. VACUUM LINES TO BE SLOPED DOWN TOWARDS TK-9200

SUCH THAT LIQUID IS NOT ALLOWED TO COLLECT IN LINES.

WHERE LOW POINTS IN PIPING CANNOT BE AVOIDED, AN

AUTOMATED DRAIN MUST BE INSTALLED. DISCUSS DESIGN

REQUIREMENTS WITH ZENON BEFORE INSTALLING.

5. FILTER TO BE INSTALLED IN HORIZONTAL ORIENTATION.

REFER TO VACUUM PUMP VENDOR DATA.

6. VACUUM PUMP MUST BE MOUNTED ON A STEEL FRAME FOR

ANCHOR BOLT ACCESS.

2 DUTY + 1 STANDBY

67 CFM @ 25.12" HG @ 1206 FASL

7.5 HP, 3600 RPM

480 V / 3 PH / 60 Hz

07/09/13 0 I.B. M.D. ISSUED FOR APPROVAL

08/04/01 1 G.V.K. M.D. REVISED AS NOTED

789101112D (24x36)

D

DATEREV. DESCRIPTION

REV.

DATEAPPROVAL

SCALE: DRAWING NO.

TITLE:

CUSTOMER:

(Y/M/D)

DSGNZONE APPD

SIZE:

CADD FILE:

6 5 4 3 2 1

B

A

C

D

G

H

F

E

B

A

C

D

G

H

F

E

789101112 6 5 4 3 2 1

DRWN:

DSGN:

CHKD:

APPD:

THIS DOCUMENT EMBODIES DESIGNS AND INFORMATION PROPRIETARY TO GE ZENON ULC.

IT IS TO BE USED ONLY FOR THE PURPOSE AND BY THE ENTITY FOR WHICH IT WAS ORIGINALLY SUPPLIED. THE

DOCUMENT MAY NOT BE DUPLICATED, DISCLOSED TO ANY OTHER PERSON OR ENTITY, OR USED FOR MANUFACTURE OF

THE ITEM IN PART OR IN WHOLE WITHOUT THE PRIOR WRITTEN PERMISSION OF GE ZENON ULC.

Page 12: Water Treatment Plant P&ID Reference

07/04/27

2

07/04/23

07/09/12

07/09/12

I.B.

THE FORSYTH COUNTY - 12.0 MGD WTP

K.S.

N.K.

M.D. PIPING & INSTRUMENTATION DIAGRAM CLEANING SYSTEM TK-97 500408D010.DGN

500408-D-010SHEET

1 OF 1 1:1

CV-9785A

HV-9781A

HV-9786A

HV-9787A

HV-9780A

CV-9785B

HV-9781B

HV-9786B

HV-9787B

HV-9780B

FIT

9720

HH

H

L

LL

HH

H

L

LL

AI

FV-9760

NEUTRALIZED

CHEMICAL WASTE

TO RESIDUALS

HOLDING BASINS

FV-9745

FV-9765

CV-9745

HV-9734

HCV-9734

HV-9732

HCV-9732

AE

9734

AIT

9734

AE

9732

AIT

9732

S

TIT

9730

TE

9730

RESIDUAL

CHLORINE

ANALYZERRANGE:

0 TO 14RANGE:

TO ppm

HH

H

L

LL

HH

H

L

LL

LIT

9726

LE

9726

FV-9770A

FV-9775

MAG

SEE NOTE 3

SEE NOTE 2

(MULTIPLE

LINES)

FV-9762

HH

H

L

LL

HH

H

L

LL

M-9700A

P-9700A

P-9700B

M-9700B

DIDODI

TSH

9709

IYL

9709

JS

9709

HS

9709

YLH

9709

HOA

YS

9709

HA

9709

YA

9709

YL

9709

HIS

9709

HK

9709

TEMP.

HV-5196

CV-5198

FV-5160

HV-6696

CV-6698

HV-6698

HV-5396

HV-5596

CV-5398

CV-5598

HV-5398

HV-5598

HV-6596

CV-6598

HV-6598

pH Cl

-

AI

AI

9734

AY

9734

AL

9734

AA

9734

HH

H

L

LL

HH

H

L

LL

AI

AI

9732

AY

9732

AL

9732

AA

9732

HH

H

L

LL

HH

H

L

LL

AI

TI

9730

TY

9730

TL

9730

TA

9730

AI

LL

9726

LA

9726

LI

9726

LY

9726

FL

9720

FI

9720

FA

9720

FY

9720

PI

9741A

PI

9740AFE

9720

PI

9740BPI

9741B

6", SCH.80, CPVC

6", SCH.10, 304L SS

6", SCH.80, CPVC

6", SCH.80, CPVC

6", SCH.80, CPVC

�", SCH.80, CPVC

�", SCH.80, CPVC

1", SCH.80, CPVC

�", SCH.80, CPVC

1", SCH.80, CPVC

8", SCH.10, 304L SS

CV-9798

HV-9795

HV-9799

POTABLE WATER

FROM PLANT SERVICE

WATER SOURCE

2", SCH.10, 304L SS

HV-9790

TYP. PNEUMATIC ACTUATED VALVE CONTROL DETAIL

DO EXHAUST

IAS

S

HIS

YS

500408-D-013

PERMEATE

FROM COMMON

PERMEATE HEADER

500408-D-003

CIP / DRAIN

TO/FROM TK-3400

500408-D-011,SHT.1

SOLUTION FOR

RECOVERY CLEANS

FROM P-6600

SODIUM HYPOCHLORITE

500408-D-011,SHT.1

SOLUTION FOR

MAINTENANCE CLEANS

FROM P-5100

SODIUM HYPOCHLORITE

CITRIC

500408-D-011,SHT.1

ACID SOLUTION

FOR CLEANS

FROM P-6500

500408-D-011,SHT.2

SODIUM BISULPHITE

FOR NEUTRALIZATION

FROM P-5300

500408-D-011,SHT.2

SODIUM HYDROXIDE

FOR NEUTRALIZATION

FROM P-5500

DO

S

YS

TYP. SOLENOID VALVECONTROL DETAIL

HIS

DI DO AO DI

HOA

KQI

9700A

JS

9700A

SC

9700A

HS

9700A

YL

9700A

YA

9700A

YS

9700A

SC

9700A

SMY

9700A

HA

9700A

HIS

9700A

YL

9700A

DI DO AO DI

HOA

KQI

9700B

JS

9700B

SC

9700B

HS

9700B

YL

9700B

YA

9700B

YS

9700B

SC

9700B

SMY

9700B

HA

9700B

HIS

9700B

YL

9700B

RANGE:

TO INHV-9726

RANGE:

TO ^F

HV-9741A

1/2" 6"4"

HV-9741B

1/2"

HV-9740B

1/2"6"

4"

CIP/RECIRC./NEUTRALIZATION PUMPS

1 DUTY + 1 STANDBY

306 GPM @ 22.5 FT

5 HP @ 1180 RPM

480 V / 3 PH / 60 Hz

FV-9732

1/2"

�", SCH.80, CPVC

HV-9740A

1/2"

RANGE:

0 TO 1000 GPM

07/09/13 0 I.B. M.D. ISSUED FOR APPROVAL

08/03/11 1 I.B. M.D. REVISED AS NOTED

8"

TK-9700

CIP TANK

2000 USGAL

PE CONSTRUCTION

CT-2000

08/04/01 2 X.C. M.D. REVISED AS NOTED

FV-9771

6"

VENT

HX-9700

ELECTRIC HEATER

37 KW

NO

TE 6

BPV-6594

BPV-5394

BPV-5594

BPV-5194

BPV-6694

HV-5198

PANEL

NOTES:

1. ALL DOTTED LINES/EQUIPMENT

BY OTHERS

2. PROVIDE AIR GAP.

3. 5 PIPE DIAMETERS UPSTREAM, 3 PIPE

DIAMETERS DOWNSTREAM, STRAIGHT PIPE

RUN RECOMMENDED FOR MAXIMUM ACCURACY.

4. ADD GOOSE NECK TO PREVENT DURING OF

CELLS PROBE.

5. DO NOT INSTALL PROBES UNTIL COMMISSIONING

BEGINS.

6. INJECTION LINES TO BE LOCATED ON UNDERSIDE

OF PIPES.

2

NOTE 5 NOTE 4

2

2

2

2

2

2

2

2

2

2

2

2

2 2

2NOTE 6

2

789101112D (24x36)

D

DATEREV. DESCRIPTION

REV.

DATEAPPROVAL

SCALE: DRAWING NO.

TITLE:

CUSTOMER:

(Y/M/D)

DSGNZONE APPD

SIZE:

CADD FILE:

6 5 4 3 2 1

B

A

C

D

G

H

F

E

B

A

C

D

G

H

F

E

789101112 6 5 4 3 2 1

DRWN:

DSGN:

CHKD:

APPD:

THIS DOCUMENT EMBODIES DESIGNS AND INFORMATION PROPRIETARY TO GE ZENON ULC.

IT IS TO BE USED ONLY FOR THE PURPOSE AND BY THE ENTITY FOR WHICH IT WAS ORIGINALLY SUPPLIED. THE

DOCUMENT MAY NOT BE DUPLICATED, DISCLOSED TO ANY OTHER PERSON OR ENTITY, OR USED FOR MANUFACTURE OF

THE ITEM IN PART OR IN WHOLE WITHOUT THE PRIOR WRITTEN PERMISSION OF GE ZENON ULC.

Page 13: Water Treatment Plant P&ID Reference

DO

S

HIS

YS

TYP. SOLENOID VALVE CONTROL DETAIL

HIS

6500B

YL

6500B

YA

6500B

YS

6500B

YY

6500B

YL

6500A

HIS

6500A

YS

6500A

YA

6500A

YY

6500A

DI DO DO DI

HIS

5100B

YL

5100B

YA

5100B

YS

5100B

YY

5100B

YL

5100A

HIS

5100A

YS

5100A

YA

5100A

YY

5100A

DI DO DO DI

HIS

6600B

YL

6600B

YA

6600B

YS

6600B

YY

6600B

YL

6600A

HIS

6600A

YS

6600A

YA

6600A

YY

6600A

DI DO DO DI

07/04/27

2

07/04/23

07/09/12

07/09/12

I.B.

THE FORSYTH COUNTY - 12.0 MGD WTP

K.S.

N.K.

M.D. PIPING & INSTRUMENTATION DIAGRAM CLEANING CHEMICALS 500408D11 1.DGN

500408-D-011SHEET

1 OF 2 1:1

500408-D-010

CITRIC ACID

FOR RECOVERY CLEANS

TO P-9700 DISCHARGE

500408-D-010

SODIUM HYPOCHLORITE

FOR MAINTENANCE CLEANS

TO P-9700 DISCHARGE

500408-D-010

SODIUM HYPOCHLORITE

FOR RECOVERY CLEANS

TO P-9700 DISCHARGE

500408-D-007

SODIUM HYPOCHLORITE

FOR BIOGROWTH PREVENTION

TO BACKPULSE TANK

TK-8800

AI

LI

5100

LY

5100

LIT

5100

LE

5100

LT-5100

RANGE: TBD

07/09/13 0 I.B. M.D. ISSUED FOR APPROVAL

08/03/11 1 G.C. M.D. REVISEE AS NOTED

CHEMICAL FILL LINE

FROM CHEMICAL

TRANSFER PUMPS

NOTES:

1. ALL DOTTED LINES/EQUIPMENT

BY OTHERS

2. VENT ALL CHEMICAL TANKS APPROPRIATELY

3. CHEMICAL PUMP SYSTEM WIRED TO LOCAL

JUNCTION BOX

4. TEMPORARY GAUGE CONNECTIONS FOR COMMISSSING

ONLY

08/04/01 2 G.V.K. M.D. REVISEE AS NOTED

2

2

2

2

2

2

2

2

2

2

2

(SEE NOTE 2)

CALIBRATION

COLUMN

FQMI-6548 P-6500B

HV-6581B

HV-6586B

PSV-6583B

HV-6587B

HV-6580BHV-6580A

HV-6587A

PSV-6583A

P-6500A

HV-6581A

HV-6586A

�", SCH.80, CPVC

",

SC

H.80,

CP

VC

�", SCH.80, CPVC

",

SC

H.80,

CP

VC

(SEE NOTE 2)

CALIBRATION

COLUMN

FQMI-5148 P-5100B

HV-5181B

HV-5186B

PSV-5183B

HV-5187B

HV-5180BHV-5180A

HV-5187A

PSV-5183A

P-5100A

HV-5181A

HV-5186A

SODIUM HYPOCHLORITE

�", SCH.80, CPVC

",

SC

H.80,

CP

VC

�", SCH.80, CPVC

",

SC

H.80,

CP

VC

CALIBRATION

COLUMN

FQMI-5248 P-5200B

HV-6681B

HV-6686B

PSV-6683B

HV-6687B

HV-6680BHV-6680A

HV-6687A

PSV-6683A

P-6600A

HV-6681A

HV-6686A

1", SCH.80, CPVC

1",

SC

H.80,

CP

VC

1",

SC

H.80,

CP

VC

PANEL LIMITS

PANEL LIMITS

PANEL LIMITS

CITRIC ACID TOTE

(BY OTHERS)

1", SCH.80, CPVC

TK-6500

P-6600A/B

SODIUM HYPOCHLORITE PUMPS

FOR RECOVERY CLEANS

1.27 GPM @ 58 PSIG MAX.

120 V/ 1 PH/ 60 HZ

TK-5100

�"

�"

�"

P-5100A/B

SODIUM HYPOCHLORITE PUMPS

FOR MAINTENANCE CLEANS

0.13 GPM @ 58 PSIG MAX.

120 V/ 1 PH/ 60 HZ

P-6500A/B

CITRIC ACID PUMPS

FOR RECOVERY CLEANS

0.1 GPM @ 58 PSIG MAX.

120 V/ 1 PH/ 60 HZ

(SEE NOTE 4)

( BY OTHERS )

NOTE 4

NOTE 4

NOTE 4

1"

1"

789101112D (24x36)

D

DATEREV. DESCRIPTION

REV.

DATEAPPROVAL

SCALE: DRAWING NO.

TITLE:

CUSTOMER:

(Y/M/D)

DSGNZONE APPD

SIZE:

CADD FILE:

6 5 4 3 2 1

B

A

C

D

G

H

F

E

B

A

C

D

G

H

F

E

789101112 6 5 4 3 2 1

DRWN:

DSGN:

CHKD:

APPD:

THIS DOCUMENT EMBODIES DESIGNS AND INFORMATION PROPRIETARY TO GE ZENON ULC.

IT IS TO BE USED ONLY FOR THE PURPOSE AND BY THE ENTITY FOR WHICH IT WAS ORIGINALLY SUPPLIED. THE

DOCUMENT MAY NOT BE DUPLICATED, DISCLOSED TO ANY OTHER PERSON OR ENTITY, OR USED FOR MANUFACTURE OF

THE ITEM IN PART OR IN WHOLE WITHOUT THE PRIOR WRITTEN PERMISSION OF GE ZENON ULC.

Page 14: Water Treatment Plant P&ID Reference

07/04/27

2

07/04/23

07/09/12

07/09/12

I.B.

THE FORSYTH COUNTY - 12.0 MGD WTP

K.S.

N.K.

M.D. PIPING & INSTRUMENTATION DIAGRAM NEUTRALIZATION CHEMICALS 500408D11 2.DGN

500408-D-011SHEET

2 OF 2 1:1

DO

S

HIS

YS

TYP. SOLENOID VALVE CONTROL DETAIL

HIS

5300B

YL

5300B

YA

5300B

YS

5300B

YY

5300B

YL

5300A

HIS

5300A

YS

5300A

YA

5300A

YY

5300A

DI DO

DO DI

HIS

5500B

YL

5500B

YA

5500B

YS

5500B

YY

5500B

YL

5500A

HIS

5500A

YS

5500A

YA

6400A

YY

5500A

DI DO

DO DI

NOTES:

1. ALL DOTTED LINES/EQUIPMENT

BY OTHERS

2. VENT ALL CHEMICAL TANKS APPROPRIATELY.

3. BACK PRESSURE VALVE WILL BE SHIPPED LOOSE

FOR INSTALLATION CLOSE TO INJECTION POINT.

4. CHEMICAL PUMP SYSTEM WIRED TO LOCAL

JUNCTION BOX.

500408-D-010

SODIUM BISULFITE

TO P-9700 DISCHARGE

500408-D-010

SODIUM HYDROXIDE

TO P-9700 DISCHARGE

LT-5100

RANGE: TBD

AI

LI

5500

LY

5500

LIT

5500

LE

5500

07/09/13 0 I.B. M.D. ISSUED FOR APPROVAL

08/03/11 1 G.C. M.D. REVISED AS NOTED

CHEMICAL FILL LINE

FROM CHEMICAL

TRANSFER PUMPS

(BY OTHERS)

08/04/01 2 G.V.K. M.D. REVISED AS NOTED

2

2

2

2

2

2

(SEE NOTE 2)

CALIBRATION

COLUMN

FQMI-5348 P-5300B

HV-5381B

HV-5386B

PSV-5383B

HV-5387B

HV-5380BHV-5380A

HV-5387A

PSV-5383A

P-5300A

HV-5381A

HV-5386A

�", SCH.80, CPVC

",

SC

H.

80,

CP

VC

�", SCH.80, CPVC

",

SC

H.

80,

CP

VC

(SEE NOTE 2)

SODIUM HYDROXIDE

�", SCH.80, CPVC

CALIBRATION

COLUMN

FQMI-5548 P-5500B

HV-5581B

HV-5386B

PSV-5583B

HV-5587B

HV-5580BHV-5580A

HV-5587A

PSV-5583A

P-5500A

HV-5581A

HV-5586A

�", SCH.80, CPVC

",

SC

H.80,

CP

VC

",

SC

H.80,

CP

VC

PANEL LIMITS

SODIUM BISULFITE TOTE(BY OTHERS)

PANEL LIMITS

TK-5500

TK-5300

�"

�"

P-5300A/B

SODIUM BISULFITE PUMPS

FOR NEUTRALIZATION

0.010-0.102 GPM @ 58 PSIG MAX.

120 V/ 1 PH/ 60 HZ

(SEE NOTE 4)

P-5500A/B

SODIUM HYDROXIDE PUMPS

FOR NEUTRALIZATION

0.005-0.235 GPM @ 58 PSIG MAX.

120 V/ 1 PH/ 60 HZ

(SEE NOTE 4)

1"

789101112D (24x36)

D

DATEREV. DESCRIPTION

REV.

DATEAPPROVAL

SCALE: DRAWING NO.

TITLE:

CUSTOMER:

(Y/M/D)

DSGNZONE APPD

SIZE:

CADD FILE:

6 5 4 3 2 1

B

A

C

D

G

H

F

E

B

A

C

D

G

H

F

E

789101112 6 5 4 3 2 1

DRWN:

DSGN:

CHKD:

APPD:

THIS DOCUMENT EMBODIES DESIGNS AND INFORMATION PROPRIETARY TO GE ZENON ULC.

IT IS TO BE USED ONLY FOR THE PURPOSE AND BY THE ENTITY FOR WHICH IT WAS ORIGINALLY SUPPLIED. THE

DOCUMENT MAY NOT BE DUPLICATED, DISCLOSED TO ANY OTHER PERSON OR ENTITY, OR USED FOR MANUFACTURE OF

THE ITEM IN PART OR IN WHOLE WITHOUT THE PRIOR WRITTEN PERMISSION OF GE ZENON ULC.

Page 15: Water Treatment Plant P&ID Reference

07/04/26

2

07/04/23

07/09/12

07/09/12

I.B.

THE FORSYTH COUNTY - 12.0 MGD WTP

K.S.

N.K.

M.D. PIPING & INSTRUMENTATION DIAGRAM AIR SYSTEM FOR PDT EQUIP. & VALVES 500408D012.DGN

500408-D-012SHEET

1 OF 1 1:1

PSL

9108

PLL

9108

I

PSL

9100A

PI

9140A

HOA

INSTRUMENT AIR

DI

HV-9183

PRV-9586

PSV-9564

CV-9580

HV-9580

PSV-9182A

M-9182A

S.P.= 110 PSIG

DECREASING

PI

9541

HV-9181A

HV-9182A

HV-9184

DPI

9141

HV-9185

DPI

9542

HV-9582

HV-9583

MULTIPLE LINES

(1 PER TRAIN)

(SEE NOTE 2)

REGULATOR

(SEE NOTE 3)

PSL

9100B

PI

9140B

YS

9100B

YA

9100B

YL

9100B

DI

PSV-9182A

M-9182B

HV-9181B

HV-9182B

AC-9100B

KQI

9100B

JS

9100B

HS

9100B

YL

9100B

AC-9100A

F-9100B

F-9100A

TK-9100B

TK-9100A

F-9100

PRIMARY COALESCING

FILTER W/ INTEGRAL

AUTO-DRAIN

F-9500

SECONDARY COALESCING

FILTER W/ INTEGRAL

AUTO-DRAIN

ACF-9500

ACTIVATED CARBON

FILTER W/ INTEGRAL

MANUAL DRAIN

I

HOAKQI

9100A

JS

9100A

HS

9100A

YL

9100A

LOCAL

DI

YS

9100A

YA

9100A

YL

9100A

DI DI

SEE NOTE 7

PAL

9108

500408-D-003

MIT AIR

TO MEMBRANES

S.P.= 70 PSIG

DECREASING

S.P.= 80 PSIG

S.P.= 10 PSIGS.P.= 11 PSIG

AUTO-DRAIN

INTEGRAL

TO DRYER

(SEE NOTE 6)

AUTO-DRAIN

INTEGRAL

TO DRYER

(SEE NOTE 6)

120USGAL

(SEE NOTE 6)

120USGAL

(SEE NOTE 6)

ELECTRICAL

AUTO-DRAIN

120 V/ 1 PH/ 60 HZ

(SEE NOTE 5)

S.P.= 90 PSIG

DECREASING

7.5 HP, 1034 RPM

22.6 ACFM @ 175 PSIG MAX.

480 V/ 3 PH/ 60HZ

(SEE NOTE 4,6,8)

AC-9100A/B

AIR COMPRESSORS

1 DUTY + 1 STANDBY

u 1 m

COMPRESSED AIR

RECEIVER TANK

COMPRESSED AIR

RECEIVER TANK

ELECTRICAL

AUTO-DRAIN

120 V/ 1 PH/ 60 HZ

(SEE NOTE 5)

u0.01 mu0.01 m

PRV-9182

1/2"

HV-9598

1/2"

HV-9541

1/2"

DRAIN

HV-9180A

3/4"

DR-9182 A/B

REFRIGERATED AIR DRYER

MAX. 35 CFM @ 100 PSIG

1/3 HP

120 V / 1 PH / 60 Hz

HV-9180B

3/4"

�" �"

�" �" �" �"

1" 304

L

S.

S.

TU

BI

NG

�" �"

MULTIPLE LINES

(1 PER TRAIN)

NOTES:

1. ALL DOTTED LINES/EQUIPMENT

BY OTHERS

2. AT LEAST 1 ISOLATION VALVE PER

TRAIN (BY OTHERS).

3. HANDLE FOR BYPASS VALVE TO BE REMOVED

OR VALVE LOCKED IN CLOSED POSITION.

4. FOOD GRADE OIL TO BE USED.

5. AUTO-DRAIN PLUGS INTO LOCAL OUTLET.

WALL GFCI PLUG REQUIRED BY OTHERS.

6. NOT CONTROLLED BY PLC.

7. DRAIN VALVES TO BE LOCATED AT ANY LOW

POINTS IN PIPING WHERE MOISTURE MAY

ACCUMULATE. EXTRA VALVES BY OTHERS.

8. LOCAL CONTROL PANEL INCLUDED WITH

COMPRESSOR.

1" 304

L

S.

S.

TU

BI

NG

1" 304

L

S.

S.

TU

BI

NG

1" 304L S.S. TUBING

07/09/13 0 I.B. M.D. ISSUED FOR APPROVAL

2

08/03/11 1 G.C. M.D. REVISED AS NOTED

08/04/01 2 G.V.K. M.D. REVISED AS NOTED

2

2

789101112D (24x36)

D

DATEREV. DESCRIPTION

REV.

DATEAPPROVAL

SCALE: DRAWING NO.

TITLE:

CUSTOMER:

(Y/M/D)

DSGNZONE APPD

SIZE:

CADD FILE:

6 5 4 3 2 1

B

A

C

D

G

H

F

E

B

A

C

D

G

H

F

E

789101112 6 5 4 3 2 1

DRWN:

DSGN:

CHKD:

APPD:

THIS DOCUMENT EMBODIES DESIGNS AND INFORMATION PROPRIETARY TO GE ZENON ULC.

IT IS TO BE USED ONLY FOR THE PURPOSE AND BY THE ENTITY FOR WHICH IT WAS ORIGINALLY SUPPLIED. THE

DOCUMENT MAY NOT BE DUPLICATED, DISCLOSED TO ANY OTHER PERSON OR ENTITY, OR USED FOR MANUFACTURE OF

THE ITEM IN PART OR IN WHOLE WITHOUT THE PRIOR WRITTEN PERMISSION OF GE ZENON ULC.

Page 16: Water Treatment Plant P&ID Reference

07/04/27

1

07/04/23

07/09/12

07/09/12

A.P.L.

THE FORSYTH COUNTY - 12.0 MGD WTP

K.S.

N.K.

M.D. PIPING & INSTRUMENTATION DIAGRAM PERMEATE STORAGE TANK 500408D013.DGN

500408-D-013SHEET

1 OF 1 1:1

TI

7530

TY

7530

TIT

7530

TE

7530

MULTIPLE LINES

AI

AI

LE

7526

LY

7526

LI

7526

LL

7526

LA

7526

HH

H

L

LL

HH

H

L

LL

LIT

7526

VACUUM BREAKER

30", SCH.10, 316L SS

6", SCH.10, 304L SS

6", SCH.10, 304L SS

10", SCH.10, 316L SS

TK-7500

CLEARWELL

SEAL WEIR

NOTE:

1. ALL DOTTED LINES/EQUIPMENT

BY OTHERS

2. VACUUM BREAKER TO BE INSTALLED

AT HIGH POINT IN PIPING.

RANGE:

TO IN

TBD

(SEE NOTE 2)

RANGE: 32 TO 120^F

�"

500408-D-007

PERMEATE

TO TK-8800

500408-D-010

PERMEATE

TO TK-9700

500408-D-005

PERMEATE

FROM PERMEATE PUMPS

500408-D-015

COMMON PERMEATE

SAMPLE

FV-7537

1/2" S

DO

S

HIS

YS

TYP. SOLENOID VALVE CONTROL DETAIL

07/09/13 0 I.B. M.D. ISSUED FOR APPROVAL

08/04/01 1 X.C. M.D. REVISED AS NOTED

10", SCH.10, 304L SS

PERMEATE

500408-D-001,SHT.2

BYOTHERS

BYOTHERS

2

2

2

789101112D (24x36)

D

DATEREV. DESCRIPTION

REV.

DATEAPPROVAL

SCALE: DRAWING NO.

TITLE:

CUSTOMER:

(Y/M/D)

DSGNZONE APPD

SIZE:

CADD FILE:

6 5 4 3 2 1

B

A

C

D

G

H

F

E

B

A

C

D

G

H

F

E

789101112 6 5 4 3 2 1

DRWN:

DSGN:

CHKD:

APPD:

THIS DOCUMENT EMBODIES DESIGNS AND INFORMATION PROPRIETARY TO GE ZENON ULC.

IT IS TO BE USED ONLY FOR THE PURPOSE AND BY THE ENTITY FOR WHICH IT WAS ORIGINALLY SUPPLIED. THE

DOCUMENT MAY NOT BE DUPLICATED, DISCLOSED TO ANY OTHER PERSON OR ENTITY, OR USED FOR MANUFACTURE OF

THE ITEM IN PART OR IN WHOLE WITHOUT THE PRIOR WRITTEN PERMISSION OF GE ZENON ULC.

Page 17: Water Treatment Plant P&ID Reference

07/04/27

1

07/04/23

07/09/12

07/09/12

I.B.

THE FORSYTH COUNTY - 12.0 MGD WTP

K.S.

N.K.

M.D. PIPING & INSTRUMENTATION DIAGRAM PARTICLE COUNTER & TURBIDIMETER 500408D015.DGN

500408-D-015SHEET

1 OF 1 1:1

TO DRAIN

PARTICLE

COUNTER

VENT

HH

H

HH

H

F

HH

H

S

HH

H

L

LL

HH

H

L

LL

AI

�",P.E., TUBING

S

HH

H

L

LL

HH

H

L

LL

AI

TO DRAIN

�",P.E., TUBING500408-D-001,SHT.1

SCREENED CLARIFIED

SAMPLE

AE

7637

AIT

7637

7637

AY

7637

AA

AI

7637

AL

7637

TURB

TURB

PART

HH

H

L

LL

AI

TO DRAIN

�",P.E., TUBING

AE

7537

AIT

7537

7537

AY

7537

AA

TURB

500408-D-013

COMMON

PERMEATE SAMPLE

AE

3537-1

AIT

3537-1

AA

3537-1

AY

3537-1

AL

3537-1

AI

3537-1

1 -3536B-1

HCV-3536B-1

FE

3536B-1

TK-3536-1

DEGASSING

CYLINDER

HCV-3536A-1

FV-3536A-1

AE

3536-1

AJIT

3536-1

A1

3536-1

AA

3536-1

AJI

3536-1

AI1

3536-1

AJI

3536-1

AL1

3536-1

HV-3537-1

(NOTE 2)

AI

7537

HH

H

L

LL

AL

7537

DO

S

HIS

YS

TYP. SOLENOID VALVECONTROL DETAIL

500408-D-005

PERMEATE SAMPLE

(PER TRAIN)

RANGE:

0 - 1,000 mNTU

RANGE:

0 - 1,000 mNTU

RANGE:

0 - 1,000 mNTU

F-3536-1

HV-3536C-1

1/2"

�"

HV-7637

HV-7537

(SEE NOTE 2)

07/09/13 0 I.B. M.D. ISSUED FOR APPROVAL

NOTES:

1. ALL DOTTED LINES/EQUIPMENT

BY OTHERS

2. DRAWING TYPICAL FOR TRAINS 1 TO 6.

08/04/01 1 G.V.K. M.D. REVISED AS NOTED

PANEL

PANEL

PANEL

2

2

2

789101112D (24x36)

D

DATEREV. DESCRIPTION

REV.

DATEAPPROVAL

SCALE: DRAWING NO.

TITLE:

CUSTOMER:

(Y/M/D)

DSGNZONE APPD

SIZE:

CADD FILE:

6 5 4 3 2 1

B

A

C

D

G

H

F

E

B

A

C

D

G

H

F

E

789101112 6 5 4 3 2 1

DRWN:

DSGN:

CHKD:

APPD:

THIS DOCUMENT EMBODIES DESIGNS AND INFORMATION PROPRIETARY TO GE ZENON ULC.

IT IS TO BE USED ONLY FOR THE PURPOSE AND BY THE ENTITY FOR WHICH IT WAS ORIGINALLY SUPPLIED. THE

DOCUMENT MAY NOT BE DUPLICATED, DISCLOSED TO ANY OTHER PERSON OR ENTITY, OR USED FOR MANUFACTURE OF

THE ITEM IN PART OR IN WHOLE WITHOUT THE PRIOR WRITTEN PERMISSION OF GE ZENON ULC.