WaterCooledvs AirCooledChiller
1.Compressorenergycost
2.Makeupwatercosts
3.Sewer
charges
4.Chemicalcosts
5.Towerprocesspump
6.Towerpump
7.Towerfan
8.Aircooledcondenserfans
AirCooledvs.WaterCooledChillersOperatingCosts
Conventionalthinkinghasbeenthatwatercooledchillersaremoreefficientthanaircooledchillers. Ifweonlylookatcompressor
costs,thismaybetrue. However,usingstateofthearttechnologywithcentrifugalcompressorsandvariablespeedcontrol,air
cooledchillersareoftenthebetterchoice
-
8/13/2019 Water Cooled Air Cooled Comparison
2/3
Total
OperatingCosts
1.Compressor
2.MakeUpWater
7.TowerFan
5./6.Tower
Pumps
8.Condenser
Fans
3.Sewer
Charges
4.
Chemicals
-
8/13/2019 Water Cooled Air Cooled Comparison
3/3
System System Operating Operating TotalUnit TotalChiller
Loading Cooling Profile Time Energy EnergyCost
(%) Load (%) (Hrs/Yr) Consumption ($/Yr)(Tons) (kW/Ton)
100% 140 1% 60 0.614 $361
75% 105 42% 2,520 0.591 $10,940
50% 70 45% 2,700 0.619 $8,192
25% 35 12% 720 0.619 $1,092
100% $20,585
Coolingtowersystemwatercost(evaporation) $4,699
Coolingtowersystemwatercost(bleedoff) $940
Coolingtowersystemchemcialtreatmentcost $2,268
Coolingtowersystempumpenergy(process&
recirculationpumps) $8,428
Coolingtower
system
cooling
tower
fan
energy
cost $1,094
Coolingtoweroperatingcosttotal $17,429
Typicalcoolingtowerannualoperatingcost $17,429
TypicalR134Awatercooledrotaryscrewchillerannual
energycost $20,585
Totalfor
Typical
R
134A
water
cooled
rotary
screw
compressor $38,014
TypicalR134Awatercooledrotaryscrewchillerannual
operatingcost $38,014
ThermalCareR134Aaircooledcentrifugalchiller
annualoperatingcost ($15,828)
58%totalannual
savings $22,186
Itisimportanttolookatthetotaloperatingcostsinvolved
withthechillers,notjustthecompressorcosts. Asthe
graphicindicates,coolingtoweroperatingcostsshouldbe
addedtotheoperatingcostsofawatercooledchiller. A
coolingtowersystem'scostsincludethetowerfan,water
andsewer
costs,
chemical
costs
and
pumping
costs. In
processapplications,towersystemsgenerallyhaveprocess
pumpsandrecirculationpumpswhichcanaddasignificant
cost. Theillustrationbelowcomparestheoperatingcostof
anaircooledvariablespeedcentrifugalchillerversusa
watercooledscrewchiller. Thiscomparisonisbasedupon
a140
ton
load,
Chicago
weather
data,
$.07/kwh electrical
costs,$5.00/1000gallonwaterandsewercostsand6,000
hrs/yearoperation.
Becausetheaircooledchillerusesfloatingheadpressure
control,thecompressorenergycostsareactuallylessthan
thewatercooledchiller'scompressorcostsa$4,757
difference($20,585
$15,585). Adding
the
tower
system's
operatingcostof$17,429resultsina$22,186/year
operatingcostsavings. Amoreefficientvariablespeed
watercooledcentrifugalchillerreducesthecostdifference
to$16,725stillasignificantannualcostpenalty.