Walkair OMN

46
Operation and Maintenance WALKair V2.0 UMN:OMN A50010-Z3-C100-1-7619

description

Manual de Operacion y Mantenimiento del Walkair V2.0

Transcript of Walkair OMN

Page 1: Walkair OMN

Operation and Maintenance

WALKair V2.0

UMN:OMN

A50010-Z3-C100-1-7619

Page 2: Walkair OMN

UMN:OMN Operation and MaintenanceWALKair™ V2.0

2 A50010-Z3-C100-1-7619

U Important Note on Product Safety

Elevated voltages are inevitably present at specific points in this electrical equipment. Some of theparts can also have elevated operating temperatures.Non-observance of these conditions and the safety instructions can result in personal injury or inproperty damage.Therefore only trained and qualified personnel may install and maintain the system.The system complies with the standard EN 60950 / IEC 60950. All equipment connected has tocomply with the applicable safety standards.Safety Warnings:

• Protective earth must be securely fixed (GND STUD) and installed prior to TNV (TelecomNetwork Voltage) connections.

• AC power must be disconnected prior to changing the Power Supply fuse.

• DC cable shield must be connected to ground on both sides. A secure connection to the BUcase should be provided via the D-type connector.

• Powering off the indoor units is performed by disconnecting the DC power supply cable.

• When disconnecting the DC power supply cable from the Main Distribution Power, firstdisconnect the +/-48V supply, and only then the DC cable shield.

• E1 output cables should be installed within the same building as the Base Station BU.

Copyright (C) Siemens AG 1999

Issued by the Information and Communication Networks GroupHofmannstraße 51D-81359 Munich

Technical modifications possible.Technical specifications and features are binding only insofar asthey are specifically and expressly agreed upon in a written contract.

Page 3: Walkair OMN

Operation and Maintenance UMN:OMNWALKair™ V2.0

A50010-Z3-C100-1-7619 3

Contents1 Introduction ........................................................................................................ 51.1 General .............................................................................................................. 51.2 System Components.......................................................................................... 51.3 Management Features....................................................................................... 61.3.1 Element Management........................................................................................ 61.3.2 Service Management ......................................................................................... 61.4 Interfaces for Operation and Maintenance......................................................... 6

2 Starting and Ending an LCI Session .................................................................. 72.1 Requirements..................................................................................................... 72.2 Starting an LCI Session ..................................................................................... 72.2.1 Accessing the Main Menu.................................................................................. 82.2.2 Accessing the Previous Menu............................................................................ 82.2.3 Refreshing the Screen ....................................................................................... 82.2.4 Toggling the Error Message Display.................................................................. 82.2.5 Adjusting the Print Level .................................................................................... 92.3 Ending an LCI Session ...................................................................................... 92.4 LCI Structure...................................................................................................... 9

3 Monitoring the System ..................................................................................... 123.1 Equipment Status Indications .......................................................................... 123.1.1 BU-TS LEDs .................................................................................................... 133.2 Viewing System Alarms via the LCI ................................................................. 143.2.1 Displaying Error Log ........................................................................................ 143.2.2 Displaying Current Active Alarms .................................................................... 143.2.3 Alarm Display State ......................................................................................... 153.2.4 Alarm Descriptions........................................................................................... 15

4 Configuration Tasks......................................................................................... 214.1 Configuring Customer Parameters .................................................................. 214.1.1 Defining and Commissioning New Terminal Stations ...................................... 214.1.2 Adding a New Service...................................................................................... 234.2 Viewing Configuration Data ............................................................................. 264.2.1 BS Parameters................................................................................................. 264.2.2 TS Parameters................................................................................................. 28

5 E1 Card............................................................................................................ 305.1 Overview.......................................................................................................... 305.2 Configuration.................................................................................................... 315.3 Maintenance .................................................................................................... 34

6 Performing System Test .................................................................................. 356.1 General ............................................................................................................ 356.2 Loopback Types............................................................................................... 356.3 Setting Loopbacks ........................................................................................... 35

7 System Reset................................................................................................... 37

8 Viewing Inventory Data .................................................................................... 38

9 Software Download.......................................................................................... 41

10 Troubleshooting ............................................................................................... 4310.1 Base Station Troubleshooting.......................................................................... 4310.2 Terminal Station Troubleshooting .................................................................... 44

11 Abbreviations ................................................................................................... 45

Page 4: Walkair OMN

UMN:OMN Operation and MaintenanceWALKair™ V2.0

4 A50010-Z3-C100-1-7619

Figures

Fig. 1.1 Basic WALKair Components ........................................................................... 5Fig. 2.1 LCI Menus Prefix............................................................................................. 8Fig. 2.2 BU-BS LCI Main Menu.................................................................................... 8Fig. 2.3 BU-BS LCI Tree ............................................................................................ 10Fig. 2.4 BU-TS LCI Tree ............................................................................................ 11Fig. 3.1 BU-BS Front Panel........................................................................................ 12Fig. 3.2 BU-TS Front Panel ........................................................................................ 13Fig. 3.3 Maintenance Management Menu.................................................................. 14Fig. 3.4 Alarms and Errors Menu ............................................................................... 14Fig. 4.1 Configuration Management Menu................................................................. 21Fig. 4.2 Administrative Parameters Menu .................................................................. 21Fig. 4.3 Administrative Parameters Menu .................................................................. 22Fig. 4.4 Service Menu ................................................................................................ 23Fig. 4.5 E1 Leased Line Service Menu ...................................................................... 23Fig. 4.6 Administrative Parameters Menu .................................................................. 26Fig. 4.7 BS Parameters Menu.................................................................................... 26Fig. 4.8 TS Parameters Menu .................................................................................... 28Fig. 5.1 E1 Physical Interface..................................................................................... 30Fig. 5.2 Configuration Management Menu................................................................. 31Fig. 5.3 Telecom Interface Parameters Menu............................................................ 31Fig. 5.4 E1 Interface Parameters Menu ..................................................................... 31Fig. 5.5 Functional Diagram Loopbacks..................................................................... 34Fig. 6.1 System Tests Menu....................................................................................... 36Fig. 8.1 Version Control Menu.................................................................................... 38Fig. 9.1 Maintenance Management Menu.................................................................. 41Fig. 9.2 Version Control Menu.................................................................................... 42

Tables

Tab. 2.1 LCI Cable Pin-out........................................................................................... 7Tab. 2.2 LCI Print Levels.............................................................................................. 9Tab. 3.1 Base Station BU LED Indications................................................................. 12Tab. 3.2 Terminal Station BU LED Indications........................................................... 13Tab. 3.3 LED Table .................................................................................................... 13

This document consists of a total of 46 pages. All pages are issue 1.

Page 5: Walkair OMN

Operation and Maintenance UMN:OMNWALKair™ V2.0

A50010-Z3-C100-1-7619 5

1 Introduction

1.1 GeneralThe Operation and Maintenance Manual contains all the procedures and informationfor eliminating faults that can be indicated and located via the operating facilities(LCI and/or operator PC).

1.2 System ComponentsThe following is a basic description of the system main components (refer to Fig. 1.1).

Business CustomerApplication

Base Station

Micro Cell FeedingApplication

Terminal Station

120o Sector

60o Sector

Radio To The Building (RTTB) Application

10-km Radius

Fig. 1.1 Basic WALKair Components

Base Station(BS)

Located at the network side, the base station provides serviceto a cell (a circular coverage area of up to 10-km radius). Thebase station provides the interfaces to the Telecom switches.

Terminal Station(TS)

Located at the customer premises, the terminal stationinterfaces with the Customer Premises Equipment (CPE),including LAN bridges/routers and PBXs.

The Air Protocol The air protocol is a patent-pending; proprietary protocoldeveloped to optimize the air traffic between the exchange andCPE sides.

Page 6: Walkair OMN

UMN:OMN Operation and MaintenanceWALKair™ V2.0

6 A50010-Z3-C100-1-7619

1.3 Management FeaturesThe following sections describe the LCI management features. Most managementcapabilities are via the Base Station, which configures the Terminal Stations. TerminalStation configuration is required only for initial air link establishment.

1.3.1 Element Management

The LCI provides the user with the capability to configure the network elements and toobtain status and provisioning information regarding network elements.• The operator can obtain a detailed overview of each BU-BS and BU-TS

configuration.• Equipment Setup. The operator can set and configure each Telecom port

according to the required specification.• System Testing. The operator can perform loopback tests on each of the Telecom

and air interfaces.• Interface management. The operator can configure interface types and

parameters.• Current Status• Collects alarms from network elements.

1.3.2 Service Management

Communication services management enables service configuration and provides theuser with status information concerning the telecommunication services provided byWALKair system, including the air links between the BSs and the TSs.

1.4 Interfaces for Operation and MaintenanceOperation and maintenance for the system is provided via a Local Craft Interface (LCI)which can be connected to any network element via an RS232 interface for elementmanagement.

Page 7: Walkair OMN

Operation and Maintenance UMN:OMNWALKair™ V2.0

A50010-Z3-C100-1-7619 7

2 Starting and Ending an LCI Session

2.1 RequirementsThe Local Craft Terminal is connected to BU-BSs and BU-TSs via RS232 interface. Atthe base station side, the LCI will typically be connected and running at all times inorder to provide reporting on system alarms and to provide system performancemonitoring.

In order to run the LCI the following is required:• PC platform as local craft terminal• Serial cable, TP4 wires, flat with RJ45 to a 9-pin D-type or 25-pin D-type

connectors. Refer to Tab. 2.1 for the cable pin-out.• Communications software (e.g., ProComm, PCPlus)

RJ45 (DCE) Signal Name D-type 25 D-type 9

1

2 RXD 2 3

3 TXD 3 2

4

5 GND 7 5

6

7

8

Tab. 2.1 LCI Cable Pin-out

2.2 Starting an LCI SessionAttach the Local Craft Terminal to the BU-BS LCI port, using an available COM portwith the following settings:• 9600 bps baud rate• no Parity• 8 data bits• 1 stop bits.

The LCI software embedded in the BU RAM assumes a VT100 terminal compatible,RS232 interface.

After making the LCI connection, run the communications software (e.g., ProComm).Make sure to set the terminal type to ANSI in the communications software.

While the BU-BS is initializing, a number of messages are displayed on the Craftterminal.

After the initialization has completed, the main menu, shown in Fig. 2.1 is displayed onthe Craft terminal screen.

Page 8: Walkair OMN

UMN:OMN Operation and MaintenanceWALKair™ V2.0

8 A50010-Z3-C100-1-7619

In order to re-display the LCI menu screen, press <Enter>.

The following lines, shown in Fig. 2.1, are attached to each LCI screen. Each of thesekeys can be typed at any time in order to perform the requested function.

BASE STATION -------------------------------------

Type the <symbol ><enter> at any time:

* Main Menu % Toggle Error Messages Display

^ Previous Menu + Increment Print Level

= Refresh Menu Screen - Decrement Print Level

Fig. 2.1 LCI Menus Prefix

2.2.1 Accessing the Main Menu

Press * <Enter> to access the main menu shown in Fig. 2.2. The main menu allowsaccess to all other LCI functions.

Main Menu

1. Configuration Management

2. Maintenance Management

BS>Enter option no:

Fig. 2.2 BU-BS LCI Main Menu

2.2.2 Accessing the Previous Menu

From any of the LCI screens, you can access the previous menu in the LCI screenhierarchy by pressing ^ <Enter>. For a description of the LCI screen hierarchy,see section 2.4.

2.2.3 Refreshing the Screen

You can refresh the LCI monitor screen at any time by pressing <Enter>. When youactivate the screen refresh, all information that was on the screen is erased, and thecurrent menu is re-displayed at the top of the screen.

2.2.4 Toggling the Error Message Display

By default, the LCI displays real-time error messages. The following is an example of atypical error message. You can toggle the display mode of these messages ON/OFFby pressing % <Enter>.

Page 9: Walkair OMN

Operation and Maintenance UMN:OMNWALKair™ V2.0

A50010-Z3-C100-1-7619 9

2.2.5 Adjusting the Print Level

The LCI reports system alarms and events by displaying messages on the terminalmonitor. The type of messages that are printed depends on the set print level.

Õ To adjust the print level:

Click + <Enter> to advance the print level, or - <Enter> to reduce the print level.As you change the print level, it is displayed on the LCI monitor.

The following table lists the print levels in descending order. Note that each print levelincludes the lower level messages.

Print Level Description

Info The default level. Displays all alarm and event messages, including status message(e.g., scanning frequencies)

Warning Displays alarms that are the Warning level

Error Displays alarms that are the Error level

Fatal Displays alarms that are the Fatal level

Display Displays no alarms or events, only the LCI menus

None Displays no alarms, events or LCI menus (displays a blank screen). If your LCI monitordisplays a blank screen, press + <Enter> to display the Display print level messages.

Tab. 2.2 LCI Print Levels

2.3 Ending an LCI SessionAs previously mentioned, the LCI is intended for continuous operation in order toprovide alarm reporting and performance monitoring. The LCI is connected to the basestation and provides reporting on system-wide events/alarms (including those thatoccur at the terminal stations).

Õ To end an LCI session:

Disconnect the serial cable from the base station port.

2.4 LCI StructureLCI parameters in the Base Station and Terminal Station are grouped into two groups,according to their functionality, as shown in the main menu (see Fig. 2.2):

• Configuration Parameters include all parameters required for the system’s initialconfiguration:

⇒ Radio Link Parameters include all parameters required to establish radioconnections.

⇒ Administrative Parameters include all parameters required to set theoperational status.

⇒ Telecom Interface Parameters include physical interface configuration.⇒ Service Parameters (Base Station only) include all parameters required for

establishing a service between Base Station and Terminal Station.

Page 10: Walkair OMN

UMN:OMN Operation and MaintenanceWALKair™ V2.0

10 A50010-Z3-C100-1-7619

• Maintenance Parameters include all parameters required for the system’s ongoingactivation:

⇒ System Tests include all parameters required to determine the equipmentoperational status.

⇒ Alarms and Errors include all parameters required to indicate system events.⇒ Version Control Information includes all parameters required keeping track

of equipment version.

The following diagrams depict the LCI program tree.

Radio Link Parameters

Administrative Parameters

Interface Parameters

Service Parameters

Configuration

Cable LengthCable Type"Other" Cable Type

Gain TableFrequency Index

BS Parameters

TS Parameters

Serial No.Administrative StatusSystem TimeSystem Clock

Info. ParametersAdministrative Status

Maintenance E1 LoopbackReset

Error LogCurrent Active AlarmsAlarm Display State

System Tests

System Alarms and Errors

Version Control Information

E1 Leased LineService

E1 Parameters

Display ServiceAdd serviceUpdate ServiceDelete serviceService State

Show VersionSwitch Version

Fig. 2.3 BU-BS LCI Tree

Page 11: Walkair OMN

Operation and Maintenance UMN:OMNWALKair™ V2.0

A50010-Z3-C100-1-7619 11

ConfigurationRadio Link Parameters

Administrative Parameters

Interface Parameters

Cable LengthCable Type"Other" Cable Type Gain TableFrequency

TS Serial No.Administrative StatusCustomer IdSystem Time

Maintenance System Tests

System Alarms and Errors

Version Control Information

E1 LoopbackReset

Error LogCurrent Active AlarmsAlarm Display State

Show VersionSwitch version

Fig. 2.4 BU-TS LCI Tree

Page 12: Walkair OMN

UMN:OMN Operation and MaintenanceWALKair™ V2.0

12 A50010-Z3-C100-1-7619

3 Monitoring the SystemThe operator can monitor system and equipment status locally by observing the LEDindications or via the LCI terminal.

3.1 Equipment Status IndicationsLED status indications are present on both the BU-BS and the BU-TS. These LEDsprovide visual indications as to the functioning of the equipment and report existence ofequipment and system alarms.

Fig. 3.1 shows the BU-BS front panel LEDs.

ETHEXTINT

XXXXXXXXE1/P-ISDNE1/P-ISDNE1/P-ISDNE1/P-ISDNE1/P-ISDN E1/P-ISDN

XXXXXXXXTx

Rx

Rx

TxRx Tx TxRx

ETHEXTINT

Fig. 3.1 BU-BS Front Panel

The front panel of the BU houses 3 LED indicators, listed in Tab. 3.1.

LED Description

EXT (Outdoor) Indicates the status of the outdoor equipment and radio link(e.g., failure in the RFU or a lost connection with one of the TSs)

INT (Indoor) Indicates the status of the indoor equipment

ETH Ethernet) Indicates the status of the Ethernet port. For future use.

Telecom LEDs Indicate the status of the Telecom card and service provided by the card(e.g., Loss of Signal on one of the E1s connected to the BU)

Tab. 3.1 Base Station BU LED Indications

Telecom LED; one perTelecom card

Page 13: Walkair OMN

Operation and Maintenance UMN:OMNWALKair™ V2.0

A50010-Z3-C100-1-7619 13

3.1.1 BU-TS LEDs

EXTINT

E1/P-ISDNTxRx

E1/P-ISDNTxRx

E1/P-ISDNTxRx

E1/P-ISDNE1/P-ISDNE1/P-ISDNE1/P-ISDNTxRx

E1/P-ISDNRx Tx

LCI

xxxxxxxx

xxxxxxxx

Fig. 3.2 BU-TS Front Panel

The front panel of the BU-TS houses 2 LED indicators, listed in Tab. 3.2.

LED Description

EXT (Outdoor) Indicates the status of the outdoor equipment(e.g., failure in the RFU or a lost connection with one of the TSs)

INT (Indoor) Indicates the status of the indoor equipment

Telecom LEDs Indicate the status of the Telecom card and service provided by the card(e.g., Loss of Signal on one of the E1s connected to the BU)

Tab. 3.2 Terminal Station BU LED Indications

LED State LED

Internal External Ethernet Telecom

Blinking RED Disable Major Disable

RED Major Major Major

Blinking Yellow Loopback

Yellow Minor Minor Minor

Blinking Green Software Download

Green OK OK OK OK

Tab. 3.3 LED Table

At startup, all LEDs are displayed in three different colors, then LEDs turn to green inorder to verify that they are operational.

Page 14: Walkair OMN

UMN:OMN Operation and MaintenanceWALKair™ V2.0

14 A50010-Z3-C100-1-7619

3.2 Viewing System Alarms via the LCIThe system alarm status can be viewed from the System Alarms and Error menu.

Õ To access the System Alarms and Error menu:

1. From the Main Menu, type 2 <Enter> to access the Maintenance Managementmenu, shown in Fig. 3.3.

Maintenance Management Menu

1. System Tests Menu

2. System Alarms And Error Menu

3. Version Menu

BS>Enter option no:

Fig. 3.3 Maintenance Management Menu

2. From the Maintenance Management menu, type 2 <Enter> to access theSystem Alarms and Error menu, shown in Fig. 3.4.

Alarms and Errors Menu

1. Display Error Log

2. Display Current Active Alarms

3. Alarm Display State

BS>Enter option no:

Fig. 3.4 Alarms and Errors Menu

3.2.1 Displaying Error Log

This option displays a log of the last 100 error messages intended for the Servicepersonnel.

3.2.2 Displaying Current Active Alarms

This option displays all currently active alarms. Any change in Alarm State (ON/OFF)will trigger an LCI message.

Õ To view the current alarms:

From the Alarms and Errors menu, type 2 <Enter>. The LCI displays the typicalalarm messages, as shown in the following example:

Alarm: TS LNK DN Source: TS00 Severity: Minor ON Date:10/05/98 03:23

Page 15: Walkair OMN

Operation and Maintenance UMN:OMNWALKair™ V2.0

A50010-Z3-C100-1-7619 15

The Active Alarms message displays the following alarm parameters:

• Alarm String: short string that describes the alarm.• Alarm Source: the source that originated the alarm.• Alarm Severity: Warning, Minor, and Major.• Alarm State: ON/OFF - alarm is active/inactive.• Alarm Date: The time of day when the alarm state changed between ON/OFF.

Each alarm is reflected on the front BU LEDs.

Any state change (ON/OFF) of an alarm will trigger a message to the LCI. Forexample, when more than 50% of the BS links is lost, the following message isdisplayed:

Alarm: MST TS LOS Source: BU Severity: Major ON Date:10/12/1997 08:31

3.2.3 Alarm Display State

You can disable the alarm reporting mechanism so that no alarms are reported at thebase station.

Õ To disable alarms reporting:

Type 3 <Enter> from the Alarms and Errors menu.

To toggle the state back to report enable, type 3 <Enter> again. The active state isdisplayed on the LCI screen as you change the state.

3.2.4 Alarm Descriptions

The following is a list of the possible alarms. Each alarm is listed with a full name, shortname (in parentheses) as it appears in the alarm display, description of the alarm, thepossible sources for the alarm, the alarm severity and the various LEDs that indicatethe alarm presence.

Alarm: LoopbackLoopback local (E1 LBK LCL)Local loopback disconnects the receive lines from the receiver. The dataprovided by the system interface is routed through the analog receiver back tothe system interface. This loopback is used to check the FALC.

Loopback remote (E1 LBK RMT)In remote loopback, the clock and data recovered from the line inputs are routedback to the line outputs via the analog or digital transmitter. This loopback isused for the remote side to check itself.

Payload Loopback (E1 LBK PYLD)Payload loopback will loop the data stream from the receiver section back to thetransmitter section. The looped data will pass the complete receiver includingthe wander and jitter compensation in the receive elastic store. Instead of thedata an AIS could be sent to the system interface.

Page 16: Walkair OMN

UMN:OMN Operation and MaintenanceWALKair™ V2.0

16 A50010-Z3-C100-1-7619

Channel Loopback (E1 LBK CHAN)Single channel loopback loops one channel at a time from the system PCMinput to the system PCM output. During channel loopback an idle channel istransmitted to the remote end in the corresponding PCM channel.Source: Telecom cardSeverity: WarningLED Type: Telecom LEDLED Indications: Blinking Yellow

Alarm: E1 Disabled (E1 DISABLED)Description: FALC disabled (deactivated). The E1 FALC PCM is deactivated. Inthis mode an AIS will be transmitted toward the remote end.Source: Telecom cardSeverity: WarningLED Type: Telecom LEDLED Indications: Blinking Red

Alarm: Alarm Indication Signal (E1 AIS)Description: An AIS is detected when the following two conditions existsimultaneously:• Loss of frame alignment• Receipt of 512 bits containing less than 3 binary zerosSource: Telecom cardSeverity: MajorLED Type: Indoor LED and Telecom LEDsLED Indications: Red

Alarm: Loss of Frame Alignment (E1 LFA)Description: Loss of Frame Alignment alarm becomes active after detecting3 or 4 consecutive incorrect FAS or service words.Source: Telecom cardSeverity: MajorLED Type: Indoor LED and Telecom LEDsLED Indications: Red

Alarm: Loss Of Signal (E1 LOS)Description: Loss of signal is detected when the incoming signal has“no transition” or logical zeros. “No transition” is when signal amplitude is morethan 20 dB below the nominal output amplitude during more than 1 msec asdefined in ITU-T Recommendation G.703.Source: Telecom cardSeverity: MajorLED Type: Indoor LED and Telecom LEDsLED Indications: Red

Page 17: Walkair OMN

Operation and Maintenance UMN:OMNWALKair™ V2.0

A50010-Z3-C100-1-7619 17

Alarm: Loss of Multi-Frame Alignment (E1 LMFA)Description: Loss of Multi-frame Alignment is detected when pulseframealignment has been lost.Source: Telecom cardSeverity: MajorLED Type: Indoor LED and Telecom LEDsLED Indications: Red

Alarm: Remote Alarm Indication and CRC (E1 CRC&RAI)Description: RAI and CRC4 errors are detected.Source: Telecom cardSeverity: MinorLED Type: Indoor LED and Telecom LEDs.LED Indications: Yellow

Alarm: Receive Remote Alarm Indication (E1 RAI)Description: An RAI is detected when the following two conditions occursimultaneously:• Frame alignment condition• Reception of one bit A (E bit) with binary content ONESource: Telecom cardSeverity: MinorLED Type: Indoor LED and Telecom LEDsLED Indications: Yellow

Alarm: Radio Link Loss (RLNK LOSS)Description: If this alarm occurs at the BS, the down link radio link is down. Ifthis alarm occurs at the TS, the radio link between the BS and TS is lost.Source: BS/TSSeverity: MajorLED Type: Outdoor LEDLED Indications: Red

Alarm: BU Disabled (BU DISABLED)Description: Administrative status of the BS/TS BU is disabled. There will be noattempt to connect the radio link.Source: BS/TSSeverity: WarningLED Type: Indoor LED, Outdoor LEDLED Indications: Blinking Red

Alarm: Radio Link Loss (RLNK LOSS)Description: If this alarm occurs at the BS, the down link radio link is down. Ifthis alarm occurs at the TS, the radio link between the BS and TS is lost.Source: BS/TSSeverity: MajorLED Type: Outdoor LEDLED Indications: Red

Page 18: Walkair OMN

UMN:OMN Operation and MaintenanceWALKair™ V2.0

18 A50010-Z3-C100-1-7619

Alarm: Terminal Station Radio Link Loss (TS RLNK LOS)Description: Base station detected loss of TS00-TS15 radio link.Source: BSSeverity: WarningLED Type: Telecom LEDLED Indications: Blinking Red

Alarm: More than 50% of TS Links Loss (MOST TS LOS)Description: Base station detected loss of more than 50% of the TS radio links.Source: BSSeverity: MajorLED Type: Outdoor LEDLED Indications: Red

Alarm: Radio Link Interference (RLNK INTRFR)Description: Radio Link InterferenceSource: BSSeverity: MajorLED Type: Outdoor LEDLED Indications: Red

Alarm: IF Lock Detect (IF NO LOCK)Description: IF synthesizer (LMX) failed to lock on the frequency set to thesynthesizer.Source: BS/TSSeverity: MajorLED Type: Indoor LEDLED Indications: Red

Alarm: RFU Power Loss (RFU PWR LOS)Description: RFU power sense detected no power.Source: BS/TSSeverity: MajorLED Type: Outdoor LEDLED Indications: Red

Alarm: Accumulated Links BER > Threshold 1 (PM LBER1)Description: Accumulated Links BER > Threshold 1.Source: BSSeverity: MinorLED Type: Outdoor LEDLED Indications: Yellow

Alarm: Accumulated Links BER > Threshold 2 (PM LBER2)Description: Accumulated Links BER > Threshold 2.Source: BSSeverity: MajorLED Type: Outdoor LEDLED Indications: Yellow

Page 19: Walkair OMN

Operation and Maintenance UMN:OMNWALKair™ V2.0

A50010-Z3-C100-1-7619 19

Alarm: Radio Link BER > Threshold 1 (PM RBER1)Description: Radio Link BER > Threshold 1.Source: TSSeverity: MinorLED Type: Outdoor LEDLED Indications: Yellow

Alarm: Radio Link BER > Threshold 2 (PM RBER2)Description: Radio Link BER > Threshold 2.Source: TSSeverity: MajorLED Type: Outdoor LEDLED Indications: Yellow

Alarm: Illegal Service Configuration (SRVC CONFIG)Description: Illegal Service ConfigurationSource: BSSeverity: MinorLED Type: Indoor LEDLED Indications: Yellow

Alarm: Authentication Fail (TS AUTHENTC)Description: TS Authentication FailSource: BSSeverity: MinorLED Type: Indoor LEDLED Indications: Yellow

Alarm: Diagnostics RAM Fault (RAM FAULT)Description: Diagnosed RAM faultSource: BS/TSSeverity: MajorLED Type: Indoor LEDLED Indications: Red

Alarm: Diagnostics E2PROM Fault (EEPR FAULT)Description: Diagnosed E2PROM faultSource: BS/TSSeverity: MajorLED Indications: Indoor LEDLED Indications: Red

Alarm: Diagnostics Flash Fault ( FLASH FAULT)Description: Diagnosed FLASH faultSource: BS/TSSeverity: MajorLED Indications: Indoor LEDLED Indications: Red

Page 20: Walkair OMN

UMN:OMN Operation and MaintenanceWALKair™ V2.0

20 A50010-Z3-C100-1-7619

Alarm: Diagnostics Matrix Fault ( MATRX FAULT)Description: Diagnosed Telecom MATRIX faultSource: BS/TSSeverity: MajorLED Indications: Indoor LEDLED Indications: Red

Alarm: Diagnostics SW Version Fault (BU SW VER)Description: Diagnosed invalid SW versionSource: BS/TSSeverity: MajorLED Indications: Indoor LEDLED Indications: Red

Alarm: Diagnostics ORCA Fault (ORCA FAULT)Description: Diagnosed ORCA faultSource: BS/TSSeverity: MajorLED Indications: Indoor LEDLED Indications: Red

Alarm: Diagnostics DSP Fault (DSP FAULT)Description: DSP is not responding to periodic status request from QUICC.Source: BS/TSSeverity: MajorLED Indications: Indoor LEDLED Indications: Red

Alarm: Service Not Responding (SVE NO ACK)Description: Base station detects that a service is not respondingSource: BSSeverity: MinorLED Indications: Outdoor LEDLED Indications: Yellow

Page 21: Walkair OMN

Operation and Maintenance UMN:OMNWALKair™ V2.0

A50010-Z3-C100-1-7619 21

4 Configuration Tasks

4.1 Configuring Customer Parameters

4.1.1 Defining and Commissioning New Terminal Stations

Defining and assigning new terminal stations to a base station is done by specifying theterminal station customer ID numbers using the Administrative Parameters menu.

Õ To access the Administrative Parameters menu:

1. From the Main Menu, type 1 <Enter> to access the Configuration Managementmenu, shown in Fig. 4.1.

Configuration Management Menu

1. Radio Link Parameters Menu

2. Administrative Parameters Menu

3. Telecom Interfaces Parameters Menu

3. Service Parameters Menu

BS>Enter option no:

Fig. 4.1 Configuration Management Menu

2. From the Configuration Management, type 2 <Enter> to access theAdministrative Parameters menu, shown in Fig. 4.2.

Administrative Parameters Menu

1. BS Parameters Menu

2. TS parameters Menu

BS>Enter option no:

Fig. 4.2 Administrative Parameters Menu

3. From the Administrative Parameters menu, type 2 <Enter> to access theTS Parameters menu, shown in Fig. 4.3.

Page 22: Walkair OMN

UMN:OMN Operation and MaintenanceWALKair™ V2.0

22 A50010-Z3-C100-1-7619

TS Parameters

1. Get List of TS Information Parameters

2. Set List of TS Information Parameters

3. Add Single TS Information Parameters

4. Update Single TS Information Parameters

5. Get TS Administrative Status

6. Set TS Administrative Status

BS> Enter option no.

Fig. 4.3 Administrative Parameters Menu

Õ To specify the terminal station customer ID numbers:

1. From the TS Parameters menu, enter 2-<Enter>.The following is displayed:All defined TS info will be erased.

Are you sure ? [Yes/No]: N -

2. In order to erase all existing services and start de-defined the services enterY <Enter>. In order to add a single service enters N <Enter> and then enter3 <Enter>.

Type Q to quit

Enter TS# Information Parameters:

Customer ID (No.)

Distance [km] (0 if less than 10 km)

The TS index is automatically generated by the system, and is incremented by 1each time you specify a new customer ID.

3. Enter the following two parameters separated by spaces:• TS customer ID - This must be an 8 digit decimal number• Distance of the TS from the BS

Note: WALKair measures the distance automatically if it is less than or equal to10 km (distance ≤ 10 km). Insert 0 when the distance is smaller than orequal to 10 km. If the distance is greater than 10 km, enter the estimateddistance in km.

4. Repeat for all serviced TSs, press q for termination.

Õ To set administrative status:

1. From the TS Parameters menu, enter 6 <Enter>. The following is displayed:TS index [0-15]:

2. Type the TS index followed by <Enter>. The following is displayed:Administrative Status [Enable/Disable]: current status is

3. Type E <Enter> to enable TS.By default, all TSs are disabled. When disabled, TS will not communicate with itsBU-BS, e.g., the base station will not look for its customer ID.

Page 23: Walkair OMN

Operation and Maintenance UMN:OMNWALKair™ V2.0

A50010-Z3-C100-1-7619 23

4.1.2 Adding a New Service

In this part of the commissioning process, you define the types of service supported bythe system per terminal station port. The WALKair system supports two types ofservices:

• E1 transparent mode

• Fractional E1 mode

The service parameters used in the system are entered from the Service menu.

Õ To access the Service menu:

1. From the Main Menu, type 1 <Enter> to access the Configuration Managementmenu.

2. From the Configuration Management menu, type 4 <Enter> to access theService Parameters menu, shown in Fig. 4.4.

Service Parameters Menu

1. E1 Leased Line Services

BS>Enter option no:

Fig. 4.4 Service Menu

3. From the Service menu type 1 <Enter> to access the E1 Leased Line Servicemenu, shown in Fig. 4.5.

E1 Leased Line Service Menu

1. Get List of E1 Service Parameters

2. Set list of E1 Service Parameters

3. Add E1 Service

4. Get E1 Service Parameters

5. Update E1 Service Parameters

6. Get E1 Service State

7. Set E1 Service State

8. Delete E1 Services

BS>Enter option no:

Fig. 4.5 E1 Leased Line Service Menu

Page 24: Walkair OMN

UMN:OMN Operation and MaintenanceWALKair™ V2.0

24 A50010-Z3-C100-1-7619

Õ To view all existing services

Type 1 <Enter> from the E1 Leased Line Service menu. The following isdisplayed:Number of services: 2

Service # 01Bandwidth : 3 * 64KbpsBase Station Channels : E1#0 0-2Terminal Station Customer ID : #1234Terminal Station Channels : E1#0 0-2Terminal Station Administrative Status : ENABLEDTerminal Station Operational Status : CONNECTEDService Administrative Status : ENABLEDService Operational Status : CONNECTED

Service # 02Bandwidth : 5 * 64KbpsBase Station Channels : E1#2 0-4Terminal Station Customer ID : #4567Terminal Station Channels : E1#2 0-4Terminal Station Administrative Status : ENABLEDTerminal Station Operational Status : CONNECTEDService Administrative Status : ENABLEDService Operational Status : CONNECTED

Õ To add list of new service:

Note: This option erases all existing services and enables the insertion of new ones.

1. Press 2 <Enter> from the E1 Leased Line Service menu. The following isdisplayed:All defined services will be erased.

Are you sure ? [Yes/No] Y

Type q to quit

Enter Service # 00 Information:

The service index is automatically generated by the system, and is incremented by1 each time you specify a new service.Service Bandwidth (N x 64 Kbps) [N = 1-64]: 0 -

2. Enter the bandwidth in units of 64 Kbps; for example: 2 <Enter> will define2 x 64 Kbps.Base Station First E1 channel:

E1 #[0/1/2] ts#[0-31]: <E1#0 ts#0> -

3. Enter the BU-BS port number (0-2) originating the service path:• Port no. 0 is located near the LEDs• Port no. 1 is middle port• Port no. 2 is located The IF connectors

Enter the first E1 time slot to be allocated followed by <Enter>.

The system will reserve n x E1 consecutive time slots starting from the firstallocated time slot. For example, if no. of E1 time slots = 2 and first allocated timeslot is 10, the system will reserve time slots 10 and 11.

Terminal Station Customer ID: <0> -

Page 25: Walkair OMN

Operation and Maintenance UMN:OMNWALKair™ V2.0

A50010-Z3-C100-1-7619 25

4. Enter the destination customer ID no.(8 digits),Terminal Station First E1 channel:

E1#[0/1/2] ts#[0-31]: <E1#0 ts#0> -

5. Enter the number of E1 port and the first time slot, for example, 0 2 <Enter>

6. Repeat for all services, press q for termination.

Õ To add a single new service:

1. Press 3 <Enter> from the E1 Leased Line Service menu. The following isdisplayed:Enter Service # Info :

Service Bandwidth (N x 64 Kbps) [N = 1-64]: 0 -

2. Repeat steps 3-6 to specify Single Service parameters (for example, a newcustomer service), if required.

Õ To enable a service:

By default, all services are disabled.

1. From E1 Leased Line Service Menu enter 7 <Enter>. In order to enable theservice. The following is displayed:Enter Service Index:

2. Type the index of the service to be enabled. The following is displayed:Administrative Status [Enable/Disable]: current statusdisplayed

Type E<Enter> to enable the service.

Õ To delete E1 Service:

1. From the E1 Leased Line Service Menu, enter 8 <Enter>. The following isdisplayed:Enter Service Index:

2. Enter the service index to be deleted. Service index can be retrieved using option 1in the E1 leased Line Service menu.Are you sure you want to delete service #00 [Yes/No]

Press Y <Enter> in order to delete the service.

Page 26: Walkair OMN

UMN:OMN Operation and MaintenanceWALKair™ V2.0

26 A50010-Z3-C100-1-7619

4.2 Viewing Configuration DataFrom the Main Menu, type 1 <Enter> to access the Configuration Managementmenu, shown in Fig. 4.1.

From the Configuration Management menu, type 2 <Enter> to access theAdministrative Parameters menu shown in Fig. 4.6.

Administrative Parameters

1. BS Parameters Menu

2. TS parameters Menu

BS>Enter option no:

Fig. 4.6 Administrative Parameters Menu

4.2.1 BS Parameters

From the Administrative Parameters menu, type 1 <Enter> to access the BSParameters menu, shown in Fig. 4.7.

BS Parameters Menu

1. Get BS Serial Number

2. Get BS Administrative Status

3. Set BS Administrative Status

4. Get System Time

5. Set System Time

6. Get System Clock Source

7. Set System Clock Source

BS>Enter option no:

Fig. 4.7 BS Parameters Menu

Õ To view the BS serial number:

From the BS Parameters menu, type 1 <Enter>. The LCI returns:Serial Number: 0,0 [Dec]

Õ To view the BU-BS administrative status:

From the BS Parameters menu, type 2 <Enter>. The LCI returns:Administrative Status: Enabled

orAdministrative Status: Disabled

Page 27: Walkair OMN

Operation and Maintenance UMN:OMNWALKair™ V2.0

A50010-Z3-C100-1-7619 27

4.2.1.1 Setting System Time and DateNote: This is the time and date of the LCI program; this option controls the time and

date stamps that the LCI puts on reported events and alarms. (It has nothing todo with the date and time of the network elements).

Õ To view the currently set date and time:

From the BS Parameters menu, type 4 <Enter>. The LCI displays:Date: 10/6/1998 Time: 08:32:27

Õ To set the time and date:

1. From the Administrative Parameters menu, type 1 to access the BS Parametersmenu, shown in Fig. 4.7.

2. From the BS Parameters menu, enter 5 <Enter>. The current system date andtime is displayed, followed by a date request:Date: dd/mm/yyyy Time: hh:mm:ss

Insert Date [dd mm yyyy] :

3. Insert the day, month and year, separated with spaces.Insert Time [hh mm]:

4. Insert the time, separating hours and minutes with space.Note: The time is local and is used for error and alarm notification only.

4.2.1.2 Setting System Synchronization Source

System synchronization source is set using the Administrative Parameters menu.

1. From the Main Menu, type 1 <Enter> to access the Configuration Managementmenu, shown in Fig. 4.1.

2. From the Configuration Management, type 2 <Enter> to access theAdministrative Parameters menu, shown in Fig. 4.2.

3. From the Administrative Parameters menu, type 1 to access the BS Parametersmenu, shown in Fig. 4.7.

4. From the BS Parameters menu, type 7 to define the system synchronizationsource options. The following is displayed:System clock Source[Internal/0/1/2/Automatic]:

Type the appropriate synchronization source:• Internal - Type I <Enter> for Internal clock.• 0/1/2 - Type 0, 1 or 2 <Enter> to get System Clock from the specific E1

interface.• Automatic - Type A <Enter> to choose System Clock automatically from the

available E1 interface.

Page 28: Walkair OMN

UMN:OMN Operation and MaintenanceWALKair™ V2.0

28 A50010-Z3-C100-1-7619

4.2.2 TS Parameters

From the Administrative Parameters menu (Fig. 4.6), type 2 <Enter>. The TSParameters menu is displayed as shown in Fig. 4.8.

TS Parameters

1. Get List of TS Information Parameters

2. Set List of TS Information Parameters

3. Add Single TS Information Parameters

4. Update Single TS Information Parameters

5. Get TS Administrative Status

6. Set TS Administrative Status

BS> Enter option no.

Fig. 4.8 TS Parameters Menu

Õ To obtain a list of the TS parameters:

From the TS Parameters menu, type 1 <Enter>. The LCI displays a general list ofthe TS parameters for all terminal stations associated with the base station.

The following example shows a list of TS parameters for a typical system:

Õ To set a list of TS parameters:

1. From the TS Parameters menu, enter 2 <Enter>. The following is displayed:All Defined TS info will be erasedAre you sure ? [Yes/No]: N -

2. This option erases all existing services. Confirmation is required.TS index 01 information parameters:Customer ID (No.)

The TS index is automatically generated by the system, and is incremented by 1each time you specify a new customer ID.

3. Enter TS customer ID - It must be an 8 digit decimal number. This no. identifies thecustomer in all system displays.Distance [km] (0 if less than 10 km)

4. Enter the distance of the TS from the BS

Note: WALKair measures the distance automatically if it is less than or equal to10 km (distance ≤10 km). Insert 0 when the distance is smaller or equal to10 km. If the distance is greater than 10 km, enter the estimated distancein km.

5. Repeat for all serviced TSs, press q for termination.

Page 29: Walkair OMN

Operation and Maintenance UMN:OMNWALKair™ V2.0

A50010-Z3-C100-1-7619 29

Õ To set administrative status:

1. From the TS Parameters menu, enter 5 <Enter>. The following is displayed:TS index [0-15]:

2. Type the TS index to be enabled <Enter>. The following is displayed:Administrative Status [Enable/Disable]:current status is displayed -

3. Type E <Enter> to enable the TS.

Note: By default, all TSs are disabled. When disabled, TS will not communicatewith its BU-BS, e.g., the base station will not look for its customer ID.

Page 30: Walkair OMN

UMN:OMN Operation and MaintenanceWALKair™ V2.0

30 A50010-Z3-C100-1-7619

5 E1 Card

5.1 OverviewThe E1 card allows for N x 64 or full 2.048 Mbps service. Each BS or TS basic unit canbe configured with up to 3 E1 interfaces.

The E1 card configuration and maintenance is performed via Local Craft Interfaceconnected locally on the front panel of the TS/BS BU.

The E1 interface comply with ETS 300 011, and is in accordance with ITU-TRec. G.703, §6. It is a symmetrical-pair 120-ohm balanced interface. The signal bit rateinput should be 2048 kbit/s ±50 ppm. The line code is HDB3.

Frame Structure is according to ITU-T G.704 §5 and §2.3 with or without CRC4,according to operator selection.

The jitter performance is in accordance with ITU-T G.823, and the parameters given inITU-T Rec. G.736 and I.431.

Each E1 interface in the Base Station and Terminal Station has two shielded RJ45connectors for G.703, 120 ohm. One for transmit pair and the second for receive. Bothconnectors have the same pin arrangement, as shown in Fig. 5.1.

18 34

TIP

RIN

G

SHIELD GROUND

Front View

Fig. 5.1 E1 Physical Interface

The E1 module front panel has a single LED, which displays the status of the interface.The color codes for the LED is:

• Green - Normal operation• Yellow - Minor alarm• Blinking Yellow - Under test• Red - Major alarm• Blinking Red - Interface Disabled

Page 31: Walkair OMN

Operation and Maintenance UMN:OMNWALKair™ V2.0

A50010-Z3-C100-1-7619 31

5.2 ConfigurationBasically, E1 interface is pre-configured and can be activated without additionalconfiguration. In case default values are not appropriate, the E1 interface can beconfigured using the following menus.

Õ To access E1 configuration menu:

1. From the Main Menu, type 1 <Enter> to access the Configuration Managementmenu, shown in Fig. 5.2.

Configuration Management Menu

1. Radio Link Parameters Menu

2. Administrative Parameters Menu

3. Telecom Interfaces Parameters Menu

3. Service Parameters Menu

BS>Enter option no:

Fig. 5.2 Configuration Management Menu

2. From the Configuration Management, type 3 <Enter> to access the TelecomInterface Parameters menu, shown in Fig. 5.3.

Telecom Interfaces Parameters Menu

1. -E1 Interface Parameters Menu.

BS>Enter option no:

Fig. 5.3 Telecom Interface Parameters Menu

3. From the Telecom Interface Parameters menu, type 1 <Enter> to access the E1Interface Parameters menu, shown in Fig. 5.4.

E1 Interface Parameters Menu

1. Get E1 Physical Configuration.

2. Set E1 Physical Configuration.

3. Get E1 Administrative Status.

4. Set E1 Administrative Status.

5. Get E1 Other Parameters.

6. Set E1 Other Parameters

Fig. 5.4 E1 Interface Parameters Menu

Page 32: Walkair OMN

UMN:OMN Operation and MaintenanceWALKair™ V2.0

32 A50010-Z3-C100-1-7619

Õ To view E1 physical configuration:

1. From the E1 Interface Parameters menu, type 1 <Enter>. The following isdisplayed:Configuration parameters of the E1:Line Coding (Transmit & Receive) : HDB3Framing format (Transmit & Receive): MFF_CRC4

(CRC4 MultiFrame Format)Alarm mode (AIS alarm mode) : ETSI (ETS_300233)

Õ To update E1 physical configuration:

When updating E1 physical parameters, all ports are updated and set to DisableState.

1. From the E1 Interface Parameters menu, type 2 <Enter>. The following isdisplayed:Update Configuration parameters of the E1 :Line Coding : HDB3 [NRZ,CMI,AMI,HDB3] -

2. This parameter should not be changed. Type <Enter> to keep default value. Thefollowing is displayed:Framing format : MFF_CRC4 [DDF,MFF_CRC4,MFF_CRC4_EXT] -

3. Frame format should be one of the following values:• DDF - Double Frame Format (No CRC)• MFF - Multi Frame Format CRC4• MFF - Multi Frame Format CRC4 with extension

Type the appropriate frame format and <Enter>. The following if displayed:Alarm mode : ETSI [ETSI,ITU_T] -

4. This parameter should not be changed. Type <Enter> to keep default value. Thefollowing is displayed:WARNING - All E1 will be disabled after configuration.Update Configuration parameters to E1 [Y/N] ? - n

5. Type Y <Enter> to confirm the update of all E1 interfaces.

Note: The interfaces will be disabled.

Õ To view Other E1 parameters:

1. From the E1 Interface Parameters menu, type 5 <Enter>. The following isdisplayed:From Port [0-2] - To Port [0-2] : 0 2 -

2. Type the range of interface to be displayed <from> <to>. E1 transmission modeand jitter are displayed:PortNum 0 :

E1 Mode [Transparent (no signaling)/Unframed]:TRANSPARENTTransmit Jitter Attenuator [Enable/Disable] :ENABLE

PortNum 1 :

E1 Mode [Transparent (no signaling)/Unframed]:UNFRAMEDTransmit Jitter Attenuator [Enable/Disable] :ENABLE

PortNum 2 :

E1 Mode [Transparent (no signaling)/Unframed]:TRANSPARENTTransmit Jitter Attenuator [Enable/Disable] :ENABLE

Page 33: Walkair OMN

Operation and Maintenance UMN:OMNWALKair™ V2.0

A50010-Z3-C100-1-7619 33

Õ To change Other E1 parameters:

1. From the E1 Interface Parameters menu, type 6 <Enter>. The following isdisplayed:From Port [0-2] - To Port [0-2] : 0 2 -

2. Type the range of interface to be displayed <from> <to>. The following isdisplayed:PortNum 0 :E1 Mode [Transparent (no signaling)/Unframed]:TRANSPARENT

3. E1 mode should be one of the following values:• Transparent - Type T for Transparent 16 time slot• Unframed - Type U for Transparent 0 time slot (2 Mbps only)

Type the appropriate E1 mode and <Enter>. The following if displayed:Transmit Jitter Attenuator [Enable/Disable] :ENABLE

4. Type E < Enter>.

5. Repeat steps 2 to 4 for all ports in the range.

Õ To change administrative status:

1. From the E1 Interface Parameters menu, type 6 <Enter>. The following isdisplayed:From Port [0-2] - To Port [0-2] : 0 2 -

2. Type the range of interface to be displayed <from> <to>. The following isdisplayed:PortNum 0 -> E1 Status [Enable/Disable]: ENABLE -

3. Type E < Enter> to enable the E1 interface.

4. Repeat steps 2 to 3 for all ports in the range.

Page 34: Walkair OMN

UMN:OMN Operation and MaintenanceWALKair™ V2.0

34 A50010-Z3-C100-1-7619

5.3 MaintenanceThe following loopbacks are available for maintenance and fault isolation:

Line BU main card

RemoteLPB

LocalLPB

PayloadLPB

Fig. 5.5 Functional Diagram Loopbacks

• Remote (E1) loopback transmit the received 2M-stream back to the line, withoutany framing actions. This loopback is used to check the E1 lines.

• Payload loopback transmit the payload of the received 2M-stream back to the line,using the framing options as configured for the port (e.g. CRC calculation, Alarm bithandling etc.) The timing of the transmitted 2M stream is Jitter attenuated. Thenetwork to check the path to the E1 interface including the E1 interface itself usespayload loopback.

• Local (E1) loopback replaces the incoming 2M stream, with the transmitted stream.Local loopback is used to check a full WALKair path including the air link.

When in loopback, the LED indicator will show as follows:

Loopback E1 Cable Connected E1 Cable Disconnected

Local Blinking Yellow Blinking Yellow

Remote RED RED

Payload Blinking Yellow RED

Loopback activation is described in Section 6.

Page 35: Walkair OMN

Operation and Maintenance UMN:OMNWALKair™ V2.0

A50010-Z3-C100-1-7619 35

6 Performing System Test

6.1 GeneralThis section describes the types of the loopbacks supported by the system. Thepresence of a loopback is considered as an alarm with Warning severity (seeSection 3.2.4). When there is a loopback on a certain port, the Telecom LED blinks inyellow color.

Note:• Loopback functionality remains active until it is disabled.• Loopback cannot be performed on port I disable mode.

6.2 Loopback TypesLoopback local (E1 LBK LCL)

Local loopback disconnects the receive lines from the receiver. The data provided bythe system interface is routed through the analog receiver back to the system interface.This loopback is used to check the FALC.

Loopback remote (E1 LBK RMT)

In remote loopback, the clock and data recovered from the line inputs are routed backto the line outputs via the analog or digital transmitter. This loopback is used for theremote side to check itself.

Payload Loopback (E1 LBK PYLD)

Payload loopback will loop the data stream from the receiver section back to thetransmitter section. The looped data will pass the complete receiver including thewander and jitter compensation in the receive elastic store. Instead of the data an AIScould be sent to the system interface.

Channel Loopback (E1 LBK CHAN)

Single channel loopback loops one channel at a time from the system PCM input to thesystem PCM output. During channel loopback an idle channel is transmitted to theremote end in the corresponding PCM channel.

6.3 Setting LoopbacksLoopbacks are set using the System Tests menu.

Õ To access the System Tests menu:

1. From the Mainn Menu, type 2 >Enter< to access the Management menu, shownin Fig. 3.3.

2. From the Maintenance Management menu, type 1 <Enter> to access theSystem Tests menu, shown in Fig. 6.1.

Page 36: Walkair OMN

UMN:OMN Operation and MaintenanceWALKair™ V2.0

36 A50010-Z3-C100-1-7619

System Tests Menu

1. Get E1 Loopback

2. Set E1 Loopback

3. Display Last Reset Date and Cause

4. System Reset

BS>Enter option no:

Fig. 6.1 System Tests Menu

Õ To set a loopback:

1. Type 2 <Enter> to set an E1 loopback. The LCI displays the following:From Port [0-2] - To Port [0-2]:

2. Enter the range of BU-BS port numbers for which you wish to set the loopback,with a space separating the first and last entry.For example:• To set a loopback on port 0, type 0 0 <Enter>.• To set a loopbacks on port 0 to 1, type 0 1 <Enter>.

The LCI displays the following:Insert Loopback Mode Requested -(C-Channel, L-Local, R-Remote, P-Payload, N-None)

3. Enter the type of loopback to set for the specified port(s) followed by <Enter>.For example, type L <Enter> to set a local loopback.

An alarm is issued regarding the loopback activation.

Alarm:E1 LBK LCL Source: Telecom: #0 Severity: Major ONDate: 10/12/1997 08:34

Õ To cancel a loopback:

Use the None option. The loopback cancellation alarm is issued:

Alarm:E1 LBK LCL Source: Telecom: #0 Severity: Major OFFDate: 10/12/1997 08:34

Õ To view loopbacks currently set at the BU:

1. From the System Tests menu, type 1 <Enter>. The LCI displays the following:From Port [0-2] - To Port [0-2]:

2. Enter the range of BU-BS port numbers for which you wish to view the loopbacksettings, with the first and last entry separated with a space.For example, to set a loopback on port 0, enter 0 0 <Enter>.The LCI displays the loopback state:PortNum 0 -> LocalPortNum 1 -> Port 0 is not configured as E1PortNum 2 -> Port 0 is not configured as E1

Page 37: Walkair OMN

Operation and Maintenance UMN:OMNWALKair™ V2.0

A50010-Z3-C100-1-7619 37

7 System ResetYou reset the system from the System Tests menu. For information on accessing theSystem Tests menu, refer to Section 6.3.

Õ To reset the system:

1. From the System Tests menu, type 4 <Enter>. The LCI displays the following:

Attention: after reset, the LCI baud rate will be 9600.Are you sure you want to reset the BU [Y/N]? N -

2. Type Y <Enter> to confirm. The following message is displayed:Wdog WALKair reset! Date 10/12/1997 - 08:35:10

The reset is executed.

Õ To display the date and reason for the last system reset:

From the System Tests menu, type 3 <Enter>. The LCI displays the following:

Wdog Last Reset Cause: User Request Date: 10/12/199804:23:10

The following is a list of the possible messages which display the system reset causes:• First Reset - the first reset is done after the commissioning process.• Task Request - the LCI software initiated the reset for internal reasons.• CPU Overload• Unknown - the cause for reset is unknown.• User Request - the operator used the System Reset command as described in

Section 7.

Page 38: Walkair OMN

UMN:OMN Operation and MaintenanceWALKair™ V2.0

38 A50010-Z3-C100-1-7619

8 Viewing Inventory DataViewing version information is required mainly foe maintenance reasons such asupgrades. The current BU version can be identified in each component following the“Product Version".

Õ To view Base Station Version information

1. From the Main Menu, type 2 <Enter> to access the Maintenance Managementmenu, shown in Fig. 3.3.

2. From the Maintenance Management menu type 3 <Enter> to access the VersionControl menu, shown in Fig. 8.1.

Version Control Menu

1. Show Version Information

2. Switch Loaded Version (Current Ø Backup)

BS>Enter option no:

Fig. 8.1 Version Control Menu

The following information is displayed:

Display Version Information Of [Current/Backup] : C -Current version of all BU Components :

BOOT Header : Flash Num - 0 Address - 0Source Path :F:\FLOWARE\FRZ_VER\02.07\INTEG\BS\FILE\BBTIN005.HEXSource Date : 05/01/1999 18:01Convert Date : 12/01/1999 17:47Product Version : 02.07Component Version : BS BOOT - bbtin005Code Crc : 0x00009D84Code Length : 0x00019678 (104056 Bytes)

SW Header : Flash Num - 0 Address - 20000Source Path :F:\FLOWARE\FRZ_VER\02.07\INTEG\BS\FILE\BRMIN006.HEXSource Date : 12/01/1999 17:35Convert Date : 12/01/1999 17:47Product Version : 02.07Component Version : BS SW - brmin006Code Crc : 0x0000C62ACode Length : 0x0012833F (1213247 Bytes)

DSP Kernel Header : Flash Num - 0 Address - 1a0000Source Path :F:\FLOWARE\FRZ_VER\02.07\INTEG\BS\FILE\GKRNL001.S2QSource Date : 26/11/1998 10:34Convert Date : 12/01/1999 17:49Product Version : 02.07Component Version : BS DSP Kernel - gkrnl001Code Crc : 0x0000F8A2Code Length : 0x0000163B (5691 Bytes)

Page 39: Walkair OMN

Operation and Maintenance UMN:OMNWALKair™ V2.0

A50010-Z3-C100-1-7619 39

DSP Application Header : Flash Num - 0 Address - 1b0000Source Path :F:\FLOWARE\FRZ_VER\02.07\INTEG\BS\FILE\BAPRN066.S2QSource Date : 02/12/1998 18:28Convert Date : 12/01/1999 17:49Product Version : 02.07Component Version : BS DSP Application - baprn066Code Crc : 0x0000DB46Code Length : 0x0000BAC6 (47814 Bytes)

Omas Header : Flash Num - 0 Address - 1e0000Source Path :F:\FLOWARE\FRZ_VER\02.07\INTEG\BS\FILE\BS_OM1_C.RBTSource Date : 26/11/1998 10:34Convert Date : 12/01/1999 17:49Product Version : 02.07Component Version : BS OMAS - bs_om1_cCode Crc : 0x0000935DCode Length : 0x00009608 (38408 Bytes)

Omeq Header : Flash Num - 0 Address - 1f0000Source Path :F:\FLOWARE\FRZ_VER\02.07\INTEG\BS/FILE/BS_OM2_Z.RBTSource Date : 26/11/1998 10:34Convert Date : 12/01/1999 17:49Product Version : 02.07Component Version : BS OMEQ - bs_om2_zCode Crc : 0x0000EABECode Length : 0x0000E7AC (59308 Bytes)

Taf Header : Flash Num - 0 Address - 1d0000Source Path :F:\FLOWARE\FRZ_VER\02.07\INTEG\BS\FILE\BSTAF12F.RBTSource Date : 08/12/1998 14:50Convert Date : 12/01/1999 17:49Product Version : 02.07Component Version : BS TAF - bstaf12fCode Crc : 0x00007285Code Length : 0x0000E7AC (59308 Bytes)

Õ To view Terminal Station Version information

From the Terminal Station LCI type:

1. From the Main Menu, type 2 <Enter> to access the Maintenance Managementmenu, shown Fig. 3.3.

2. From the Maintenance Management menu type 3<Enter> to access the VersionControl menu, shown in Fig. 4.7.

The following information is displayed:Current version of all BU Components :

BOOT Header : Flash Num - 0 Address - 0Source Path :F:\FLOWARE\FRZ_VER\02.07\INTEG\TS\FILE\TBTIN005.HEXSource Date : 05/01/1999 18:02Convert Date : 12/01/1999 17:08Product Version : 02.07Component Version : TS BOOT - tbtin005Code Crc : 0x0000DB8ECode Length : 0x00019672 (104050 Bytes)

Page 40: Walkair OMN

UMN:OMN Operation and MaintenanceWALKair™ V2.0

40 A50010-Z3-C100-1-7619

SW Header : Flash Num - 0 Address - 20000Source Path :F:\FLOWARE\FRZ_VER\02.07\INTEG\TS\FILE\TRMIN006.HEXSource Date : 12/01/1999 16:55Convert Date : 12/01/1999 17:08Product Version : 02.07Component Version : TS SW - trmin006Code Crc : 0x0000BCEBCode Length : 0x000D0B3F (854847 Bytes)

DSP Kernel Header : Flash Num - 0 Address - 1a0000Source Path :F:\FLOWARE\FRZ_VER\02.07\INTEG\TS\FILE\GKRNL001.S2QSource Date : 26/11/1998 10:47Convert Date : 12/01/1999 17:11Product Version : 02.07Component Version : TS DSP Kernel - gkrnl001Code Crc : 0x0000274DCode Length : 0x0000163B (5691 Bytes)

DSP Application Header : Flash Num - 0 Address -1b0000Source Path :F:\FLOWARE\FRZ_VER\02.07\INTEG\TS\FILE\TAPRN064.S2QSource Date : 26/11/1998 10:47Convert Date : 12/01/1999 17:11Product Version : 02.07Component Version : TS DSP Application - taprn064Code Crc : 0x00000062Code Length : 0x00006EE5 (28389 Bytes)

Omas Header : Flash Num - 0 Address - 1e0000Source Path :F:\FLOWARE\FRZ_VER\02.07\INTEG\TS\FILE\TS_OM1D2.RBTSource Date : 26/11/1998 10:47Convert Date : 12/01/1999 17:11Product Version : 02.07Component Version : TS OMAS - ts_om1d2Code Crc : 0x0000B60ACode Length : 0x0000E7AC (59308 Bytes)

Omeq Header : Flash Num - 0 Address - 1f0000Source Path :F:\FLOWARE\FRZ_VER\02.07\INTEG\TS/FILE/TS_OM2K1.RBTSource Date : 26/11/1998 10:47Convert Date : 12/01/1999 17:11Product Version : 02.07Component Version : TS OMEQ - ts_om2k1Code Crc : 0x00005DF0Code Length : 0x0000E7AC (59308 Bytes)

Taf Header : Flash Num - 0 Address - 1d0000Source Path :F:\FLOWARE\FRZ_VER\02.07\INTEG\TS\FILE\TSTAF12.RBTSource Date : 26/11/1998 10:47Convert Date : 12/01/1999 17:11Product Version : 02.07Component Version : TS TAF - tstaf12Code Crc : 0x000003EACode Length : 0x00009608 (38408 Bytes)

Page 41: Walkair OMN

Operation and Maintenance UMN:OMNWALKair™ V2.0

A50010-Z3-C100-1-7619 41

9 Software DownloadIt is possible to download new software versions to a BU-BS and BU-TS through alocally connected LCI. Downloading does not interrupt service. Software is resident ona Flash memory chip on the BU. Each Flash chip contains two sections: a primarysection and a backup section.

Software download is activated using a special script file, supplied with every newversion. The script file downloads all system software to the backup portion of theFlash. Once the software download is successfully completed, the user can switchbetween the active part of the Flash and the backup part (which has the new software).

Õ To download software to the backup area:

1. Activate script file option from ProWin or ProComm by pressing Alt F5, “WindowsASPECT Run Window” is presented.

2. Choose the appropriate script file named “load.wax”. The note field presented atthe top of this window displays the script description. Check that this is the SWdownload script for the appropriate version (currently 2.07). Click <OK>.

3. “WALKair program Loader” window is presented. Choose the Download files (with“.s19” suffix) location and choose required baud rate (57,600 is recommended).Click <OK>.

4. The loading process starts. LCI screen is starting to appear. A “Send New ASCIIFile” window appears for each component loading (7 for BS or TS). Multiple pointsdisplayed on the LCI indicate that the BU is still active.

5. The download process ids logged in the log file named:ProWin/capture/download.cap

Note: In case a checksum error appears during the download (can be detected vialog file or via version information), click once on the “running man” icon.Activate the script file again with a lower baud rate.

Õ To toggle between the current and backup software versions:

1. From the Main Menu, type 2 <Enter> to access the Maintenance Managementmenu, shown in Fig. 9.1.

Maintenance Management Menu

1. System Tests Menu

2. System Alarms And Error Menu

3. Version Menu

BS>Enter option no:

Fig. 9.1 Maintenance Management Menu

2. From the Maintenance Management menu, type 3 <Enter> to access theVersion Control menu, shown in Fig. 9.2.

Page 42: Walkair OMN

UMN:OMN Operation and MaintenanceWALKair™ V2.0

42 A50010-Z3-C100-1-7619

Version Control

1. Show Version Information

2. Switch Loaded Version (Current <=> Backup)

BS>Enter option no:

Fig. 9.2 Version Control Menu

3. Type 2 <Enter>. The LCI returns the following:

Are you sure you want to switch versions?(Backup <=> Current) [Yes/No] ? N -

4. Type Y <Enter> to perform the switch. The LCI returns the following.

Marked backup version as current version.BU must be reset in order to perform the switch.Reset the Bu [Yes/No]? N

In case of a download failure, the LCI returns the following:Error : Backup version is not valid (CRC Error)

Page 43: Walkair OMN

Operation and Maintenance UMN:OMNWALKair™ V2.0

A50010-Z3-C100-1-7619 43

10 Troubleshooting

10.1 Base Station Troubleshooting

Problem Description Action

LCI Display

LCI display is not responding • Adjust the baud rate to 9600

LCI Menu does not appear • Check Cable connection

• Type “-“ to change print level

BU LEDs

Do not operate on boot process • Check if the BU receives power

No RFU signals - External LED is red

Indoor/outdoor connection • Check the connection between IF-MUX and RFU

• Check if cable is connected to the IF-MUX N-typeconnector

• Check if cable is connected to the RFU N-typeconnector

IF MUX connection • Check the connection to the IF-MUX

• Check if both jumper cables are connected in theright direction

Wrong Cable Attenuation • Check the cable type and length. If other cable wasinserted, check the Gain table.

Link cannot be established with a TS

Enabling • Check if TS was enabled in the BS and TS

Wrong customer ID configuration • Check if the customer ID is correctly typed in the BSand TS

Wrong frequency configuration • In case the TS is the first commissioned TS for thisBU-BS, check the frequency index in the BS toensure that there is no collision with other BUfrequency

LEDs

LEDs, which are not green,indicate that an alarm was issued

• The alarm can be seen in the LCI

Page 44: Walkair OMN

UMN:OMN Operation and MaintenanceWALKair™ V2.0

44 A50010-Z3-C100-1-7619

10.2 Terminal Station Troubleshooting

Problem Description Action

LCI Display

LCI display is not responding • Adjust the baud rate to 9600

LCI Menu does not appear • Check Cable connection

• Type “-“ to change print level

BU LEDs

Do not operate on boot process • Check if the BU receives power

No RFU signals - External LED is red

Indoor/outdoor connection • Check the connection between IF interface and RFU

Wrong cable attenuation • Check the cable type and length. If other cable wasinserted, check the Gain table.

Link cannot be established with a BS

No frequency scanning • Check if TS was enabled in the BS and TS

No Synchronization • Authentication failure (Internal LED is Yellow). Check ifthe customer ID is correctly typed in the BS and TS.

LEDs

LEDs, which are not green,indicate that an alarm was issued

• The alarm can be seen in the LCI

Page 45: Walkair OMN

Operation and Maintenance UMN:OMNWALKair™ V2.0

A50010-Z3-C100-1-7619 45

11 Abbreviations

AC Alternating Current

ATM Asynchronous Transfer Mode

BER Bit Error Rate

BRI Basic Rate Interface

BS Base Station

BU-BS Base Station Basic Unit

BU Basic Unit

CPE Customer Premises Equipment

CPU Central Processing Unit

CRC Cyclic Redundant Check

DC Direct Current

DLC Data Link Control

EOC Embedded Operation Channel

ETSI European Telecommunications Standards Institute

FDD Frequency Duplexing Division

FMDA Frequency Division Multiple Access

GHz Giga Hertz

IF Intermediate Frequency

ISDN Integrated Services Digital Network

ITU-T International Telecommunications UnionTelecommunications Standardization Sector

LAN Local Area Network

LCI Local Craft Interface

LLC Logical Link Control

LOS Loss of Signal

MAC Media Access Control

Mbps Mega Bits per Second

MHz Mega Hertz

PBX Private Branch Exchange

PAD Packet Assembler/Disassembler

PC Personal Computer

PCM Pulse Code Modulation

PM Performance Monitoring

PMP Point-to-Multi-Point

PRI Primary Rate Interface

QAM Quadrature Amplitude Modulation

RF Radio Frequency

Page 46: Walkair OMN

UMN:OMN Operation and MaintenanceWALKair™ V2.0

46 A50010-Z3-C100-1-7619

RFU Radio Frequency Unit

SME Small/Medium Enterprise

TCP/IP Transmission Control Protocol/Internet Protocol

TDMA Time Division Multiple Access

TS Terminal Station

BU-TS Terminal Station Basic Unit

VAC Volts Alternating Current

VDC Volts Direct Current

WLL Wireless Local Loop