1 VSC - HVDC Protection Requirements 6 th HVDC Colloquium DTU, Roskilde - Denmark Ataollah Mokhberdoran PhD Candidate at University of Porto Researcher at Automation & Switchgear Unit of EFACEC Company, Portugal

Transcript of VSC-HVDC Protection Requirements - Cardiff...

Page 1: VSC-HVDC Protection Requirements - Cardiff Universitysites.cardiff.ac.uk/medow/files/2013/09/Denmark_6th_HVDC_20150917... · VSC-HVDC Protection Requirements 6th HVDC Colloquium –DTU,

1

VSC-HVDC

Protection

Requirements

6th HVDC Colloquium – DTU, Roskilde - Denmark

Ataollah Mokhberdoran

PhD Candidate at University of Porto

Researcher at Automation & Switchgear

Unit of EFACEC Company, Portugal

Page 2: VSC-HVDC Protection Requirements - Cardiff Universitysites.cardiff.ac.uk/medow/files/2013/09/Denmark_6th_HVDC_20150917... · VSC-HVDC Protection Requirements 6th HVDC Colloquium –DTU,

Offshore Wind Industry

Installed Capacity and Average Wind Farm Size

Source:EWEA

Page 3: VSC-HVDC Protection Requirements - Cardiff Universitysites.cardiff.ac.uk/medow/files/2013/09/Denmark_6th_HVDC_20150917... · VSC-HVDC Protection Requirements 6th HVDC Colloquium –DTU,

Onshore wind sites are almost rareOnshore wind sites are in northern partsSolar sites are in the southern parts

Offshore Wind Industry

Generation moves to borders

Population is far from generation

Demand for transmitting bulk amount of the energy over long distances

Point to point transmission lines

Multi-terminal and meshed grid

EWEA Target

2030

Offshore:

150GWOnshore:

250GW

Page 4: VSC-HVDC Protection Requirements - Cardiff Universitysites.cardiff.ac.uk/medow/files/2013/09/Denmark_6th_HVDC_20150917... · VSC-HVDC Protection Requirements 6th HVDC Colloquium –DTU,

Multi-Terminal HVDC Grid

Page 5: VSC-HVDC Protection Requirements - Cardiff Universitysites.cardiff.ac.uk/medow/files/2013/09/Denmark_6th_HVDC_20150917... · VSC-HVDC Protection Requirements 6th HVDC Colloquium –DTU,

Multi-Terminal HVDC Grid

VSC

VSC

VSCVSC

VSC

AC

Grid

AC

AC DC

Bus

LineInternal

Protective Issues:

AC Side:

Loss of Synchronism

Frequency Deviation

Symmetric Faults

Asymmetric Faults

DC Side:HVDC Line Faults:

Pole to Ground

Pole to Pole

DC Bus Faults:

Pole to Ground

Pole to Pole

Component Level:

Capacitors, Switches,

Diodes, …

Page 6: VSC-HVDC Protection Requirements - Cardiff Universitysites.cardiff.ac.uk/medow/files/2013/09/Denmark_6th_HVDC_20150917... · VSC-HVDC Protection Requirements 6th HVDC Colloquium –DTU,

Multi-Terminal HVDC Grid

VSC

VSC

VSCVSC

VSC

AC Side Faults Can be Handled because of full control

on VSC at AC side fault.

Handling DC side faults is challenging!

DC Line Parameters

Converter Main Circuit Topology

Diodes Overload Capability

IGBTs Surge Capability

DC Grid Stability Issues

DC Link Capacitors Voltage Limitation

Bypass Circuit Capability

Fault Current Contribution

Page 7: VSC-HVDC Protection Requirements - Cardiff Universitysites.cardiff.ac.uk/medow/files/2013/09/Denmark_6th_HVDC_20150917... · VSC-HVDC Protection Requirements 6th HVDC Colloquium –DTU,

What do we want to save!?

VSC

VSC

VSCVSC

VSC

Large I2t Capability

Diodes: Limited Surge Current

IGBT or IGCT: Limited Surge Current

Capacitors: Limited Voltage

Capacitors: Limited di/dt

(1) Core

(3) Sheath(4) Insulater(5) Armor

(6) Insulator(2) Insulator

VSC

2Cdc

2Cdc

+

_

Page 8: VSC-HVDC Protection Requirements - Cardiff Universitysites.cardiff.ac.uk/medow/files/2013/09/Denmark_6th_HVDC_20150917... · VSC-HVDC Protection Requirements 6th HVDC Colloquium –DTU,

Power IGBTs

Realized by Soft Punch Through Chip Technology

3 Standard Isolation Voltages (4, 6 and 10.2kVRMS)

Low Forward Voltage Drop Then Low Losses

AlSiC Base-plate (Good thermal cycling capability)

AlN isolation (Low thermal resistance)

Soft Switching behavior, Large Safe Operation Area

RBSOA

Page 9: VSC-HVDC Protection Requirements - Cardiff Universitysites.cardiff.ac.uk/medow/files/2013/09/Denmark_6th_HVDC_20150917... · VSC-HVDC Protection Requirements 6th HVDC Colloquium –DTU,

Power IGBTs

Reduced Pressure Uniformity Requirement

Optimized for Series Connections: Mechanically & Electrically

Multi-level Converters with 6 or More Devices Mechanically in series

Stable Short-circuit Failure Mode (SCFM)

Reduced Flatness of Heat Sink Tolerance

Chips contacted by common pole-piece Chips contacted by individual springs

Page 10: VSC-HVDC Protection Requirements - Cardiff Universitysites.cardiff.ac.uk/medow/files/2013/09/Denmark_6th_HVDC_20150917... · VSC-HVDC Protection Requirements 6th HVDC Colloquium –DTU,

Power IGBTs

FZ500R65KE3

V_CES = 6500V

I_Cnom = 500A

A High Power IGBT

Page 11: VSC-HVDC Protection Requirements - Cardiff Universitysites.cardiff.ac.uk/medow/files/2013/09/Denmark_6th_HVDC_20150917... · VSC-HVDC Protection Requirements 6th HVDC Colloquium –DTU,

Power IGBTs

FZ500R65KE3

V_CES = 6500V

I_Cnom = 500A

A High Power IGBT

Page 12: VSC-HVDC Protection Requirements - Cardiff Universitysites.cardiff.ac.uk/medow/files/2013/09/Denmark_6th_HVDC_20150917... · VSC-HVDC Protection Requirements 6th HVDC Colloquium –DTU,

Power Diodes

FZ500R65KE3

V_CES = 6500V

I_Cnom = 500A

A High Power IGBT

Page 13: VSC-HVDC Protection Requirements - Cardiff Universitysites.cardiff.ac.uk/medow/files/2013/09/Denmark_6th_HVDC_20150917... · VSC-HVDC Protection Requirements 6th HVDC Colloquium –DTU,

Topologies

fR

cableR cableL

dcC

dcC

chokeL

Large Capacitor Contribution

AC Grid Contribution

Anti-parallel Diodes Stressed

Pole to Pole Fault

Capacitor Contribution

AC Grid Contribution

Anti-parallel Diodes Stressed

Pole to Ground Fault

Page 14: VSC-HVDC Protection Requirements - Cardiff Universitysites.cardiff.ac.uk/medow/files/2013/09/Denmark_6th_HVDC_20150917... · VSC-HVDC Protection Requirements 6th HVDC Colloquium –DTU,

Topologies

Large Capacitor Contribution

AC Grid Contribution

Anti-parallel Diodes Stressed

Pole to Pole Fault

Page 15: VSC-HVDC Protection Requirements - Cardiff Universitysites.cardiff.ac.uk/medow/files/2013/09/Denmark_6th_HVDC_20150917... · VSC-HVDC Protection Requirements 6th HVDC Colloquium –DTU,

Topologies

Partial Capacitor Contribution

IGBTs Blocked

Anti-parallel Diodes Stressed

Pole to Pole Fault

Page 16: VSC-HVDC Protection Requirements - Cardiff Universitysites.cardiff.ac.uk/medow/files/2013/09/Denmark_6th_HVDC_20150917... · VSC-HVDC Protection Requirements 6th HVDC Colloquium –DTU,

Topologies

Page 17: VSC-HVDC Protection Requirements - Cardiff Universitysites.cardiff.ac.uk/medow/files/2013/09/Denmark_6th_HVDC_20150917... · VSC-HVDC Protection Requirements 6th HVDC Colloquium –DTU,

Topologies

Page 18: VSC-HVDC Protection Requirements - Cardiff Universitysites.cardiff.ac.uk/medow/files/2013/09/Denmark_6th_HVDC_20150917... · VSC-HVDC Protection Requirements 6th HVDC Colloquium –DTU,

Topologies

Possible Capacitor Contribution

SM Capacitor Charged up

DC Fault Blocked

Pole to Pole Fault

IGBTs Stressed Before Blocking

IGBTs Blocked

Page 19: VSC-HVDC Protection Requirements - Cardiff Universitysites.cardiff.ac.uk/medow/files/2013/09/Denmark_6th_HVDC_20150917... · VSC-HVDC Protection Requirements 6th HVDC Colloquium –DTU,

Topologies

Page 20: VSC-HVDC Protection Requirements - Cardiff Universitysites.cardiff.ac.uk/medow/files/2013/09/Denmark_6th_HVDC_20150917... · VSC-HVDC Protection Requirements 6th HVDC Colloquium –DTU,

Topologies

Almost the same circuit

topology as MMC but redrawn

Page 21: VSC-HVDC Protection Requirements - Cardiff Universitysites.cardiff.ac.uk/medow/files/2013/09/Denmark_6th_HVDC_20150917... · VSC-HVDC Protection Requirements 6th HVDC Colloquium –DTU,

Topologies

Page 22: VSC-HVDC Protection Requirements - Cardiff Universitysites.cardiff.ac.uk/medow/files/2013/09/Denmark_6th_HVDC_20150917... · VSC-HVDC Protection Requirements 6th HVDC Colloquium –DTU,

Topologies

Less Switch than F-Bridge

Less Smoothness

Higher Voltage Sub-modules

DC Fault Tolerant

More Switch than H-Bridge

Page 23: VSC-HVDC Protection Requirements - Cardiff Universitysites.cardiff.ac.uk/medow/files/2013/09/Denmark_6th_HVDC_20150917... · VSC-HVDC Protection Requirements 6th HVDC Colloquium –DTU,

Topologies

Source: Tim Green’s Presentation at University of Strathclyde, Dec 2014

Page 24: VSC-HVDC Protection Requirements - Cardiff Universitysites.cardiff.ac.uk/medow/files/2013/09/Denmark_6th_HVDC_20150917... · VSC-HVDC Protection Requirements 6th HVDC Colloquium –DTU,

Topologies

Source of Figures: Stephen Finney’s Presentation at University of Strathclyde, Dec 2014

Diode currents in an MMC converter under DC fault conditions

Page 25: VSC-HVDC Protection Requirements - Cardiff Universitysites.cardiff.ac.uk/medow/files/2013/09/Denmark_6th_HVDC_20150917... · VSC-HVDC Protection Requirements 6th HVDC Colloquium –DTU,

Topologies

Reduced Pressure Uniformity Requirement

Each One Has Its Pros and Cons

Fault Tolerant Topologies:

- Can Reduce the Need for DC Circuit Breaker

- Have Higher Power Losses

- What about the Selectivity?

Half- Bridge based Topologies:

- Good Efficiency

- Defenceless Against the DC side Faults

- Requires Fast DC Fault Current Breaking

Page 26: VSC-HVDC Protection Requirements - Cardiff Universitysites.cardiff.ac.uk/medow/files/2013/09/Denmark_6th_HVDC_20150917... · VSC-HVDC Protection Requirements 6th HVDC Colloquium –DTU,

Fault causes rapidly changing currents in all lines

Selectivity: Only the affected element must be switched

IGBTs cannot withstand high overloads

Diodes are More Vulnerable

Fast enough (DC: no inductance XL to limit the current)

Only in case of DC fault and not during load change or AC fault

Remarks on DC Grid Protections

Fault location (branch) detection within a few milliseconds

Too fast for communication between measurement devices

Independent detection systems

Opening at both sides of the faulted line

No opening of other branches?

Backup in case this fails

New superfast DC breakers are needed (≈ 5 ms)

Source: Dirk Van Hertem, Lecture at Strathclyd University, Glasgow, Scotland, Dec 2014

Page 27: VSC-HVDC Protection Requirements - Cardiff Universitysites.cardiff.ac.uk/medow/files/2013/09/Denmark_6th_HVDC_20150917... · VSC-HVDC Protection Requirements 6th HVDC Colloquium –DTU,

HVDC Circuit Breaker

HVDC Circuit Breaker

CB

Surge Arrestor

cCcL

cR

sIoI

aI

cI

L

Surge Arrestor Surge Arrestor

CB

IGBT IGBT

Small Size IGBT

Breaker

Surge Arrestor

Main Breaker

Surge Arrestor

IGBT IGBT

Ultra Fast

Disconnector

IsolatorL

Surge Arrestor

vR

dcL

LiT

Mechanical Circuit Breaker

Solid-state Circuit Breaker

Hybrid Circuit Breaker

Page 28: VSC-HVDC Protection Requirements - Cardiff Universitysites.cardiff.ac.uk/medow/files/2013/09/Denmark_6th_HVDC_20150917... · VSC-HVDC Protection Requirements 6th HVDC Colloquium –DTU,

Fast DC Circuit Breakers

Solid-state Circuit Breaker

• Ultra Fast

Interruption Time

• 800kV, 5kA expected

Maximum Ratings

• High, up to 30% of Related VSC

Conduction Losses

• Surge Arrestors

Energy Absorption

• Very High

Surge Voltage

• Fast

Interruption Time

• 320kV, 16kA Expected

Maximum Ratings

• Low, up to 1% of Related VSC

Conduction Losses

• Surge Arrestors

Energy Absorption

• Very High

Surge Voltage

Hybrid Circuit BreakerSmall Size IGBT

Breaker

Surge Arrestor

Main Breaker

Surge Arrestor

IGBT IGBT

Ultra Fast

Disconnector

IsolatorL

Main Breaker Unit

Page 29: VSC-HVDC Protection Requirements - Cardiff Universitysites.cardiff.ac.uk/medow/files/2013/09/Denmark_6th_HVDC_20150917... · VSC-HVDC Protection Requirements 6th HVDC Colloquium –DTU,

Fast DC Circuit Breakers

Hybrid Circuit Breaker

Solid-state Circuit Breaker Metal Contacts and Semiconductors

Conducting the current in

normal operation

Main interrupter in

fault condition

IGBT Breaker

Surge Arrestor

Main Breaker

IGBT IGBT

Ultra Fast

Disconnector

IsolatorL

Page 30: VSC-HVDC Protection Requirements - Cardiff Universitysites.cardiff.ac.uk/medow/files/2013/09/Denmark_6th_HVDC_20150917... · VSC-HVDC Protection Requirements 6th HVDC Colloquium –DTU,

Fast DC Circuit Breakers

f

sc n delay

diI I t

dt

. . scCB DC line sc line

diV V R i L

dt

DCV

1

lineR 1

lineL2

lineR 2

lineLBreaker

BRVLV

Short

Circuit

Fault

sci

Load

Page 31: VSC-HVDC Protection Requirements - Cardiff Universitysites.cardiff.ac.uk/medow/files/2013/09/Denmark_6th_HVDC_20150917... · VSC-HVDC Protection Requirements 6th HVDC Colloquium –DTU,

Fast DC Circuit Breakers

SSCB

Short

Circuit

Fault

R line

L line

i sc

V DC Load

R v

Short

Circuit

Fault

R lineL

line

i sc

V DC Load

R v

SSCB

Two Main Solid-state DC Circuit Breaker Topologies

Main Breaker Unit

NP

G2

S2

D2

NP

G2

S2

D2

20131-Diode+Rv based2-SiC-BGSIT based

Main Breaker

IGBT IGBTL

L’

L’’

L’

L’’

20141-Coupled Inductors based

2-Seperated Rv based

N

P

G2 S2

D2

NP

G2 S2

D2

Surge Arrestor

Capacitor

2015SiC based

2010Thyristor based

Page 32: VSC-HVDC Protection Requirements - Cardiff Universitysites.cardiff.ac.uk/medow/files/2013/09/Denmark_6th_HVDC_20150917... · VSC-HVDC Protection Requirements 6th HVDC Colloquium –DTU,

General Requirements

• High rate of rise of fault current

• Save converters

• Protec. algorithms

• Footprint

• Surge arrestor

• Limitations as energy absorbers

• Reducing the Reliability of the Device

• Surge arrestor

• High overvoltage

• Insulation problem

• Increase the cost of devices

Quick

Interruption

Action

Stored

Energy

Dissipation

Surge

Voltage

Issue

Page 33: VSC-HVDC Protection Requirements - Cardiff Universitysites.cardiff.ac.uk/medow/files/2013/09/Denmark_6th_HVDC_20150917... · VSC-HVDC Protection Requirements 6th HVDC Colloquium –DTU,

Proposed Method

C

Short-Circuit

Fault

L iLicon

DC +

-

Auxiliary

Branch

Breaker

C

Short-Circuit

Fault

L iLicon

DC +

-

Auxiliary

Branch

Breaker

C

Short-Circuit

Fault

L iLicon

DC +

-

Auxiliary

Branch

Breaker

Pending Patent, No. 108775, 2015, Ataollah Mokhberdoran, Adriano Carvalho, Nuno Silva, Hélder Leite, António Carrapatoso

Page 34: VSC-HVDC Protection Requirements - Cardiff Universitysites.cardiff.ac.uk/medow/files/2013/09/Denmark_6th_HVDC_20150917... · VSC-HVDC Protection Requirements 6th HVDC Colloquium –DTU,

Proposed Method

Employs a pre-charged capacitorTo feed the fault current during and after main breaker unit interruption

Prevent the sudden reduction of voltage of beginning of the line

Change the final equivalent circuit to a RLC circuit

No surge VoltageNatural response of the RLC circuit

Ultra-fast actionThe converter current is interrupted very quickly (in the range of few hundred micro seconds)

C

Short-Circuit

Fault

L iLicon

DC +

-

Auxiliary

Branch

Breaker

Pending Patent, No. 108775, 2015, Ataollah Mokhberdoran, Adriano Carvalho, Nuno Silva, Hélder Leite, António Carrapatoso

Page 35: VSC-HVDC Protection Requirements - Cardiff Universitysites.cardiff.ac.uk/medow/files/2013/09/Denmark_6th_HVDC_20150917... · VSC-HVDC Protection Requirements 6th HVDC Colloquium –DTU,

SSCB in A System

Transmission

Line

VSC1

SSCB1

CCB

SSCB2

TF

LL

Rch

chL R L

Tch

CCB

TF Rch

Tch

chLR L

LL

VSC2

Pending Patent, No. 108775, 2015, Ataollah Mokhberdoran, Adriano Carvalho, Nuno Silva, Hélder Leite, António Carrapatoso

Page 36: VSC-HVDC Protection Requirements - Cardiff Universitysites.cardiff.ac.uk/medow/files/2013/09/Denmark_6th_HVDC_20150917... · VSC-HVDC Protection Requirements 6th HVDC Colloquium –DTU,

Aggregated Model

2 1

1 22

fault cable

cable

R R R C

L L L

1

2

max.

CVR

k I

1 2

1 2

2

4 cableL L LC

R

22

2

1 2 1 2 1

10

.

fault cable

cable cable

R R Rd i t di ti t

dt L L L dt L L L C

+_

C 1

t=0

R 2

R S

VDC

t=0

2L RCable CableL

R fault

sw1

sw21L

LiCBi

Ci

B

(t)

(t) (t)A

Page 37: VSC-HVDC Protection Requirements - Cardiff Universitysites.cardiff.ac.uk/medow/files/2013/09/Denmark_6th_HVDC_20150917... · VSC-HVDC Protection Requirements 6th HVDC Colloquium –DTU,

Aggregated Model

SSCB 2- Positive Pole

SSCB 4- Negative Pole

HVDC Cable

Short

Circuit Fault

HVDC Cable

SSCB1- Positive Pole

SSCB 3- Negative Pole

HVDC Cable

HVDC Cable

R6

L1

C3

L2 L3L4 T4

R8 L7

T2C2

C4

C1

L5 L6 L8

R2 R4

2 1

1 2

2 2 2

2 2

fault cable

cable

R R R C

L L L

1

2

max.

CVR

k I

1 2

1 2

2

4 cableL L LC

R

2 1

1 22

fault cable

cable

R R R C

L L L

Page 38: VSC-HVDC Protection Requirements - Cardiff Universitysites.cardiff.ac.uk/medow/files/2013/09/Denmark_6th_HVDC_20150917... · VSC-HVDC Protection Requirements 6th HVDC Colloquium –DTU,

Aggregated Model

Page 39: VSC-HVDC Protection Requirements - Cardiff Universitysites.cardiff.ac.uk/medow/files/2013/09/Denmark_6th_HVDC_20150917... · VSC-HVDC Protection Requirements 6th HVDC Colloquium –DTU,

SSCB in A System

SSCB1 XLPE Cable – 90km SSCB2

SSCB3 XLPE Cable – 90km SSCB4

A BC

VSC- 1 VSC-2

MMC

X R1 1 XR 22

T1T2

Ip1 I line,p

1

Ip2I line,p

2 VCB,2+

_+_

VCB, 1

Bus1 Bus2

MMC

In1

I line,n

1

_VCB, 3 + Ip2

I line,n2

VCB,4_+

(1) Core

(2) Insulator(3) Sheath

(4) Insulater

(5) Armor

(6) Insulator

Table I: Assumed system parametersMMC Power 1000MVA Cable Length 90km Transformer Y/D

Nominal

Voltage±320kV Smoothing Reactor 15mH AC source 230kV

Configuration Sym. monopole Fault Impedance 0.1Ω MMC Type Half-bridge

Table II: Designed SSCB parametersIth 3kA R1 3kΩ L1 50µH

C1 350µF R2 30Ω L2 10mH

TABLE III

DC CABLE DATA

LayerRadius

(mm)

Resistivity

(Ωm)

Rel.

permeability

Rel.

permittivity

(1) Core 25.2 1.72*10-8 1 1

(2) Insulator 40.2 - 1 2.3

(3) Sheath 43.0 2.20*10-7 1 1

(4) Insulator 48.0 - 1 2.3

(5) Armor 53.0 1.80*10-7 10 1

(6) Insulator 57.0 - 1 2.1

Page 40: VSC-HVDC Protection Requirements - Cardiff Universitysites.cardiff.ac.uk/medow/files/2013/09/Denmark_6th_HVDC_20150917... · VSC-HVDC Protection Requirements 6th HVDC Colloquium –DTU,

Point to Point MMC-HVDC

SSCB1 XLPE Cable – 90km SSCB2

SSCB3 XLPE Cable – 90km SSCB4

A BC

VSC- 1 VSC-2

MMC

X R1 1 XR 22

T1T2

Ip1 I line,p

1

Ip2I line,p

2 VCB,2+

_+_

VCB, 1

Bus1 Bus2

MMC

In1

I line,n

1

_VCB, 3 + Ip2

I line,n2

VCB,4_+

Page 41: VSC-HVDC Protection Requirements - Cardiff Universitysites.cardiff.ac.uk/medow/files/2013/09/Denmark_6th_HVDC_20150917... · VSC-HVDC Protection Requirements 6th HVDC Colloquium –DTU,

Point to Point MMC-HVDC

SSCB1 XLPE Cable – 90km SSCB2

SSCB3 XLPE Cable – 90km SSCB4

A BC

VSC- 1 VSC-2

MMC

X R1 1 XR 22

T1T2

Ip1 I line,p

1

Ip2I line,p

2 VCB,2+

_+_

VCB, 1

Bus1 Bus2

MMC

In1

I line,n

1

_VCB, 3 + Ip2

I line,n2

VCB,4_+

Page 42: VSC-HVDC Protection Requirements - Cardiff Universitysites.cardiff.ac.uk/medow/files/2013/09/Denmark_6th_HVDC_20150917... · VSC-HVDC Protection Requirements 6th HVDC Colloquium –DTU,

Point to point MMC-HVDC

SSCB1 XLPE Cable – 90km SSCB2

SSCB3 XLPE Cable – 90km SSCB4

A BC

VSC- 1 VSC-2

MMC

X R1 1 XR 22

T1T2

Ip1 I line,p

1

Ip2I line,p

2 VCB,2+

_+_

VCB, 1

Bus1 Bus2

MMC

In1

I line,n

1

_VCB, 3 + Ip2

I line,n2

VCB,4_+

Page 43: VSC-HVDC Protection Requirements - Cardiff Universitysites.cardiff.ac.uk/medow/files/2013/09/Denmark_6th_HVDC_20150917... · VSC-HVDC Protection Requirements 6th HVDC Colloquium –DTU,

Multi-Terminal Model

Link 12

CB12

Link 34

Lin

k 1

3

Lin

k 2

4

CB21

CB14

CB41

CB

13

CB

24

CB

42

CB43CB34

CB

31

IGBT

Driver

Control

System

Current

Measurement

Circuit

Thyristor

Triger Cr.

Voltage

Measurement

CircuitThyristor

Triger Cr.

Main Breaker Unit

Page 44: VSC-HVDC Protection Requirements - Cardiff Universitysites.cardiff.ac.uk/medow/files/2013/09/Denmark_6th_HVDC_20150917... · VSC-HVDC Protection Requirements 6th HVDC Colloquium –DTU,

Multi-Terminal Model

Comparison

SSCBs are installed

Fault Close to Bus1

Page 45: VSC-HVDC Protection Requirements - Cardiff Universitysites.cardiff.ac.uk/medow/files/2013/09/Denmark_6th_HVDC_20150917... · VSC-HVDC Protection Requirements 6th HVDC Colloquium –DTU,

Developed Topology of SSCB

Main Breaker Unit

Page 46: VSC-HVDC Protection Requirements - Cardiff Universitysites.cardiff.ac.uk/medow/files/2013/09/Denmark_6th_HVDC_20150917... · VSC-HVDC Protection Requirements 6th HVDC Colloquium –DTU,

Developed Topology of SSCB

Main Breaker Unit

Main Breaker Unit Main Breaker Unit

loss sw sat CBP N V I

Page 47: VSC-HVDC Protection Requirements - Cardiff Universitysites.cardiff.ac.uk/medow/files/2013/09/Denmark_6th_HVDC_20150917... · VSC-HVDC Protection Requirements 6th HVDC Colloquium –DTU,

Fault Tolerant Converters can Reduce the Need for DCCB but not Eliminate

Summary

Pre-Block Current Stress Must be Considered in Sizing of IGBTs

Pre-Bypass Stress on Anti-Parallel Diodes, Specially Surge Current

Impact of VSC Control during the DC Fault should be Studied

New DC Fault Current Breaking Concept Proposed

Employs Common Components

Shows Improved Characteristics

Page 48: VSC-HVDC Protection Requirements - Cardiff Universitysites.cardiff.ac.uk/medow/files/2013/09/Denmark_6th_HVDC_20150917... · VSC-HVDC Protection Requirements 6th HVDC Colloquium –DTU,

Thank you for your attention

Questions?

Photo by: Ataollah Mokhberdoran