Page 1: VRV systems - daikin.mcquay.hudaikin.mcquay.hu/1_VRV/2_Kültéri_Egységek/RTSYQ-P_VRVIII-C... · 4. installation & maintenance Friendly design 14 outdoor unitS 19 1. VrV ... VrV

VRV® systems

www.da ik in .eu

Superior heating under low temperature conditionS

Page 2: VRV systems - daikin.mcquay.hudaikin.mcquay.hu/1_VRV/2_Kültéri_Egységek/RTSYQ-P_VRVIII-C... · 4. installation & maintenance Friendly design 14 outdoor unitS 19 1. VrV ... VrV

ENVIRONMENTAL AWARENESSAir Conditioning and the Environmentair conditioning systems provide a significant level of indoor comfort, making possible optimum working and living conditions in the most extreme climates. in recent years, motivated by a global awareness of the need to reduce the burdens on the environment, some manufacturers including daikin have invested enormous efforts in limiting the negative effects associated with the production and the operation of air conditioners. hence, models with energy saving features and improved eco-production techniques have seen the light of day, making a significant contribution to limiting the impact on the environment.

ABOUT DAIKINdaikin has a worldwide reputation based on over 80 years’ experience in the successful manufacture of high quality air conditioning equipment for industrial, commercial and residential use.

daikin europe n.V.

2

Page 3: VRV systems - daikin.mcquay.hudaikin.mcquay.hu/1_VRV/2_Kültéri_Egységek/RTSYQ-P_VRVIII-C... · 4. installation & maintenance Friendly design 14 outdoor unitS 19 1. VrV ... VrV

TABLE OF CONTENTSintroduction on VrV®iii-c 4

FeatureS 5

1. wide application range 52. high comfort levels 113. environmental awareness 124. installation & maintenance Friendly design 14

outdoor unitS 19

1. VrV®iii-c technologY 192. specifications 223. accessories 23

indoor unitS 24

1. Features 242. Specifications & accessories 31

Ventilation 44

1. hrV-heat reclaim Ventilation 442. FXmQ-mFV1 - outdoor air processing unit 463. VrV®+eXV-kit - VrV® air handling applications 47

powerFul Selection programmeS 48

1. VrV® Xpress 482. VrV® pro 49

uSer FriendlY control SYStemS 50

1. individual control Systems 502. centralised control Systems 523. network Solutions 534. accessories 58

3

Page 4: VRV systems - daikin.mcquay.hudaikin.mcquay.hu/1_VRV/2_Kültéri_Egységek/RTSYQ-P_VRVIII-C... · 4. installation & maintenance Friendly design 14 outdoor unitS 19 1. VrV ... VrV

INTRODUCTION ON VRV®III-C

daikin europe has extended its range of VrV® air conditioning systems with the technologically advanced VrV®iii-c inverter controlled heat pump system, designed specifically for installation in colder climates.

available in 10, 14, 16 and 20hp versions, VrV®iii-c is the first heat pump system on the market able to provide year round heating in outdoor temperatures down to -25°c without the need for any supplementary heating. in low ambient conditions, VrV®iii-c offers 30% more heating capacity compared to a standard VrV®iii heat pump.* cooling is also available in ambient temperatures down to -5°c.

System heating is extremely stable – a 10hp system for example, operating in an ambient of -10°c, has a capacity reduction ratio of just 11%. – less than 50% of that of a standard VrV®iii heat pump of comparable size.*

VrV®iii-c comprises a newly designed outdoor unit and ‘function unit’, featuring two stage compression technology, which provides its outstanding performance characteristics by creating the higher pressures necessary for efficient operation under low ambient conditions.

energy saving potential is excellent with a cop at -10°c of over 3.0 for all models, with rapid heat up to 40°c discharge temperature at low ambient achievable in only 8 minutes. also, the short defrost cycle of 4 minutes ensures a more stable interior temperature, resulting in considerably improved comfort levels. performance figures such as these lead to annual power costs around 20% lower than those of VrV®iii hp models.

the system can be linked to the complete range of daikin ceiling mounted, concealed, ducted, corner, cassette, wall mounted and floor mounted indoor fan coil units.

* Field test data akita city ‘06/Jan, Japan

> newly developed 2-stage Compress ion technology

> powerful heat ing even in Cold c l imates

> enhanced Comfort through quick-start heat ing

> higher COP under low temperature condit ions

> Cuts defrost ing t ime

4

Page 5: VRV systems - daikin.mcquay.hudaikin.mcquay.hu/1_VRV/2_Kültéri_Egységek/RTSYQ-P_VRVIII-C... · 4. installation & maintenance Friendly design 14 outdoor unitS 19 1. VrV ... VrV

rtSYQ10pY1 rtSYQ20pY1

1. VRV®III-C OutdOOR unIt RAngE

VRVIII®- C n° of outdoor

units

n° ofcompressors

Maximum n° of connectable indoor units

Minimum capacity

index - 50%

Maximum capacity

index - 130% *

RTSYQ10PY1 1 + function unit 2+1 16 125 325

RTSYQ14PY1 1 + function unit 3+1 22 175 455

RTSYQ16PY1 1 + function unit 3+1 26 200 520

RTSYQ20PY1 2 + function unit 3+1 32 250 650

FEATURES

1. WIDE AppLICATION RANgE

* please contact you local dealer for more information

Model 20 25 32 40 50 63 71 80 100 125 200 250 Capacity index 20 25 31.25 40 50 62.5 71 80 100 125 200 250

2. IndOOR unIt CApACIty IndEx

eg. Selected indoor units: FXcQ25 + FXFQ100 + FXmQ200 + FXSQ40 + FXFQ40connection ratio: 25 + 100 + 200 +40 = 405> possible outdoor unit rtSYQ16pY1

5

Page 6: VRV systems - daikin.mcquay.hudaikin.mcquay.hu/1_VRV/2_Kültéri_Egységek/RTSYQ-P_VRVIII-C... · 4. installation & maintenance Friendly design 14 outdoor unitS 19 1. VrV ... VrV

3. WIdE RAngE Of IndOOR unIts

VrV® air conditioning brings summer freshness and winter warmth to offices, hotels, department stores and

many other commercial premises. it enhances the indoor environment and creates a basis for increased business

prosperity and whatever the air conditioning requirement, a daikin indoor unit will provide the answer. VrV®

air conditioning can be supplied via 13 DIFFERENT INDOOR UNIT MODELS in a total of

75 VARIATIONS.

roundflow ceiling mounted cassette

4-way blow ceiling mounted cassette

2-way blow ceiling mounted cassette

ceiling mounted corner cassette

Small concealed ceiling unit

Slim concealed ceiling unit

FEATURES WIDE AppLICATION RANgE

6

Page 7: VRV systems - daikin.mcquay.hudaikin.mcquay.hu/1_VRV/2_Kültéri_Egységek/RTSYQ-P_VRVIII-C... · 4. installation & maintenance Friendly design 14 outdoor unitS 19 1. VrV ... VrV

20 25 32 40 50 63 71 80 100 125 200 250

8 8 8 8 8 8 8 8 8

8 8 8 8 8

8 8 8 8 8 8 8 8

8 8 8 8

8 8

8 8 8 8 8 8

8 8 8 8 8 8 8 8 8

8 8 8 8 8 8 8 8

8 8 8 8 8 8

8 8 8

8 8 8

8 8 8 8 8 8

8 8 8 8 8 8

NEW

Indoor units

Roundflow ceiling mounted cassette

4-way blow ceiling mounted cassette

2-way blow ceiling mounted cassette

Ceiling mounted corner cassette

Small concealed ceiling unit

Slim concealed ceiling unit

Concealed ceiling unit

Concealed ceiling unit

Wall mounted unit

Ceiling suspended unit

4-way blow ceiling suspended unit

Floor standing unit

Concealed floor standing unit

fxfQfxZQfxCQfxKQfxdQfxdQfxsQfxMQfxAQfxHQfxuQfxLQfxnQ

concealed ceiling unit

concealed ceiling unit

wall mounted unit

ceiling suspended unit

4-way blow ceiling suspended unit

(concealed) Floor Standing unit

7

Page 8: VRV systems - daikin.mcquay.hudaikin.mcquay.hu/1_VRV/2_Kültéri_Egységek/RTSYQ-P_VRVIII-C... · 4. installation & maintenance Friendly design 14 outdoor unitS 19 1. VrV ... VrV

4. IntEgRAtEd VEntILAtIOn

daikin offers a variety of solutions for the provision of fresh air ventilation to offices, hotels, stores and other commercial outlets – each one complementary to and as flexible as the VrV® system itself.

HRV - Heat Reclaim Ventilationheat and humidity are exchanged between supply and exhaust air, which ›- Brings outdoor air close to indoor air conditions- recovers energy loss- realises considerable reduction of air conditioning capacity.the heat exchanger modulates the humidity and temperature of incoming fresh air to match indoor conditions. ›the cooling/heating load placed on the air conditioning system is reduced. (heat and humidity are exchanged). ›most energy saving solution as smaller indoor units can be selected: ›- Size down of indoor units down to 40 %- payback total Vam system: ±2.5 years*

*conditions:

- outside cooling conditions: 30°C / outside heating conditions: - 8°C

- Inside cooling conditions: 24°C / inside heating conditions: 22°C

- Ventilation per room: 150m3/h

ideal modular concept to cope with the fresh air requirements ›

fxMQ-MfV1 – Outdoor Air processing unit100% fresh air intake possible ›leaves maximum floor and wall space for furniture, decorations and fittings ›operation range: -5°c to 43°c ›225 pa external static pressure allows extensive ductwork runs and flexible application: ›ideal for use in large areasdrain pump kit available as accessory ›

FEATURES WIDE AppLICATION RANgE

8

Page 9: VRV systems - daikin.mcquay.hudaikin.mcquay.hu/1_VRV/2_Kültéri_Egységek/RTSYQ-P_VRVIII-C... · 4. installation & maintenance Friendly design 14 outdoor unitS 19 1. VrV ... VrV

7. fLExIbLE pIpIng dEsIgn

VrV®iii-c offers an extended piping length of 165m (190m equivalent piping length) with a total system piping length of 500m. if the outdoor unit is located above the indoor unit, the height difference is 50m. if the outdoor unit is located below the indoor unit, the height difference is 40m. the distance between the outdoor unit and the function unit should be a maximum of 10m (13m equivalent piping length). after the first branch, the difference between the longest piping length and the shortest piping length can be a maximum 40m, provided that the longest piping length amounts to a maximum of 90m.

165m

Actu

al pip

ing le

ngth

50m

Level

diffe

rence

betw

een i

ndoo

r and

outdo

or un

its

15m

Level

diffe

rence

betw

een i

ndoo

r unit

s

90m

m

aximu

m

Actual piping

length 165 mEquivalent piping

length 190 m

6. WIdE HEAtIng OpERAtIOn RAngE

VrV®iii-c is the first system on the market with a standard operation range down to -25 °c outdoor ambient in heating and can also provide cooling down to - 5 °c outdoor ambient

5. stAbLE HEAtIng CApACIty

VrV®iii-c has a stable heating capacity, even in low ambients, making it suitable for single source heating. the heating capacity is 130% in comparison with the standard VrV®iii heating capacity under similar conditions

-25 -20 -15 -10 -5 0 5 10

VRV® III-C+15.5 °CDB

Heating capacity 10HP outdoor unit

Outdoor temp. (°CWB)

(kW)

-25 °CDB

VRV® III+15.5 °CDB

VRV III®-C+43 °CWB

VRV III®+43 °CWB

-20 °CDB

-5 °CWB -5 °CWB

35

30

25

20

15

10

5

0

50

40

30

20

10

-5

-10

-15

-20

-25

COOLINGHEATING

OpERAtIOn RAngE

outdo

or tem

perat

ure

standard heat pump

9

Page 10: VRV systems - daikin.mcquay.hudaikin.mcquay.hu/1_VRV/2_Kültéri_Egységek/RTSYQ-P_VRVIII-C... · 4. installation & maintenance Friendly design 14 outdoor unitS 19 1. VrV ... VrV

db(A) perceived loudness sound

0 Treshold of hearing - 20 Extremely soft Rustling leaves40 Very soft Quiet room60 Moderately loud Normal conversation80 Very loud City traffic noise100 Extremely loud Symphonic orchestra120 Threshold of feeling Jet taking off

Daikin indoor units

Peak in the outdoor temperature

Night mode starts Night mode ends

Max. -8dB (10 HP)

8 hrs 9 hrs

— Capacity* %

— Operation Sound dBA

notes: this function is available for on site setting. › the relationship between outdoor temperature (load) and time shown in ›the graph is merely an example.

8. supER sILEnt OpERAtIOn

Outdoor unitsQuietness is another important feature. to reduce noise and ensure comfortable operation, the latest technologies and features have been applied to the outdoor units.

night quiet function (max. -8dbA)

during the night the sound level of the outdoor unit can be reduced for a certain period: starting time and ending time can be input

2 modes(*1) with low sound level at night:

Mode 1 Automatic mode › Set on the outdoor pcB. time of maximum temperature is memorised. the low operating mode will become active 8 hours(*2) after the peak temperature in the daytime and operation will return to normal after 9 hours(*3).

Mode 2 Customized mode › Starting and ending times can be input. (external control adapter for outdoor unit, dta104a61 or dta104a62 and a separately ordered timer are necessary.)

notes:(*1). determine which mode to select depending on the climatic characteristics of each country.(*2). initial setting. can be selected from 6, 8 and 10 hours.(*3). initial setting. can be selected from 8, 9 and 10 hours.

Indoor unitsdaikin indoor units operate at sound levels as low as 25 dbA

FEATURES WIDE AppLICATION RANgE

10

Page 11: VRV systems - daikin.mcquay.hudaikin.mcquay.hu/1_VRV/2_Kültéri_Egységek/RTSYQ-P_VRVIII-C... · 4. installation & maintenance Friendly design 14 outdoor unitS 19 1. VrV ... VrV

35

30

25

20

15

60

50

40

30

20

10

0

-10

-20

positie blauwe lijnen:X +10

-5 0 5 6 10 14 15 20

50% REduCtIOn

2. HIgH COMFORT LEVELS

1. HIgH HEAt up spEEd

heat up speed is dramatically reduced, particularly under low ambient conditions. the required time for discharge temperature to reach 40°c has been reduced by 50%.

2. sHORt dEfROst tIME

the time required for defrost is reduced to 4 minutes – less than half that of the standard VrV®iii system (10 minutes), leading to a more stable interior indoor temperature and considerably improved comfort levels.* Field test data in Japan with 10 HP unit (Akita City Jan 2006)

Indoor heat exchanger temperature VRV®III-C

Indoor temperature VRV®III-C

Indoor heat exchanger temperature standard heat pump

Indoor temperature standard heat pump

Start heating operation

Elapsed time (min.)

* Field test data in Japan with 14 HP unit (Akita City Jan 2006)

standard heat pump Indo

or t

empe

ratu

re °

C

Disc

harg

e te

mpe

ratu

re (°

C)

11

Page 12: VRV systems - daikin.mcquay.hudaikin.mcquay.hu/1_VRV/2_Kültéri_Egységek/RTSYQ-P_VRVIII-C... · 4. installation & maintenance Friendly design 14 outdoor unitS 19 1. VrV ... VrV

3. ENVIRONMENTAL AWARENESS

1. HIgH COp (VRV III®-C)

the use of two stage compression technology results in improved energy saving performance at low ambients, with a cop of more than 3.0 at -10°c outdoor ambient. annual power costs are therefore, considerably lower than those of the standard heat pump.

COP (10HP)

CO

P

4.00

3.00

2.00

1.00

0.00

-25 -20 -15 -10 -5 0 5 10

Standard VRVIII heat pump

Outdoor temp. (WB°)

12

Page 13: VRV systems - daikin.mcquay.hudaikin.mcquay.hu/1_VRV/2_Kültéri_Egységek/RTSYQ-P_VRVIII-C... · 4. installation & maintenance Friendly design 14 outdoor unitS 19 1. VrV ... VrV

2. InVERtER tECHnOLOgy

the linear VrV® system makes use of a Variable proportional integral (pi) control system, which uses refrigerant pressure sensors to provide added control over inverter and on/oFF control compressors. this reduces the control steps into smaller units, providing precise control in both small and larger areas.

energy efficiency is also higher under part load conditions. Since less

capacity is required, the compressor rotates more slowly and the coil becomes virtually oversized. Superior efficiencies can therefore, be achieved with inverter compressors, rather than with non inverter compressors, which always run at the same speed.

Temperature remains stable

Slow start

Air conditioning without Inverter

Air conditioning with Inverter

Frequency

30 116 30+on 116+on

Cap

acity

50%

60%

55%

65%

3. LEss fREQuEnt stARt/stOp CyCLE

the technique adopted by daikin, of regulating the capacity using ›multiple compressors clearly results in minimum switching losses and power surges because of the overlap in capacity and frequency Since daikin utilises small 5hp inverter compressors, the influence of ›harmonics is less than that generated by a single large compressorthe use of multiple compressors by daikin also ensures a 50 % ›standby facility Smaller compressors are cheaper and faster to replace ›

T

t

13

Page 14: VRV systems - daikin.mcquay.hudaikin.mcquay.hu/1_VRV/2_Kültéri_Egységek/RTSYQ-P_VRVIII-C... · 4. installation & maintenance Friendly design 14 outdoor unitS 19 1. VrV ... VrV

32°C

10°C

43°C 0°C

4. INSTALLATION & MAINTENANCE FRIENDLy DESIgN

1. AutOMAtIC CHARgE funCtIOn

Conventional Way:1. calculation of additional refrigerant charging volume2. charging the unit with additional refrigerant3. measuring the weight of the cylinder4. judgment based on pressure (test operation)

VRV®III-C with VrV®iii-c however, these 4 steps are omitted since VrV®iii-c unit

can be charged with the necessary amount of refrigerant automatically via a push button on the pcB. automatic charging will cease once the appropriate amount of refrigerant has been transferred.

if temperature drops below 10°c manual charging is necessary. after having switched to heating and once the indoor temperature rises above 10°c, push the auto charge button to activate auto charge function. refrigerant containment is only available after performing the automatic charge function.

2. AutOMAtIC tEst

when refrigerant charging has ceased, pushing the test operation button on the pcB will initiate a check on the wiring, shut off valves, sensors and refrigerant volume. this test ceases automatically when completed.

3. EAsy MAIntEnAnCE

Automatic refrigerant containment check Simply activated by pressing a button on the pcB, the system calculates if

any refrigerant has been lost, ensuring optimum performance of the VrV® system.

self diagnostic function this function operated via push button on the pcB, speeds up

troubleshooting and should be used for start-up and maintenance. disconnected thermistors, faulty solenoid valves or motor operated valves, compressor malfunctions, communication errors, etc can be diagnosed quickly.

Automatic Information storage during unit operation, storage of data from the last 5 minutes occurs

automatically. in cases of malfunction, analysis of data from the last 5 minutes will be carried out to identify the location of the problem and cause of malfunction. measures to eliminate the cause of malfunction then be implemented.

Outdoor temperature

Indoor temperature

Automaticcharge

function

Manualcharge

FEATURES

14

Page 15: VRV systems - daikin.mcquay.hudaikin.mcquay.hu/1_VRV/2_Kültéri_Egységek/RTSYQ-P_VRVIII-C... · 4. installation & maintenance Friendly design 14 outdoor unitS 19 1. VrV ... VrV

Front

Left

Bottom

Right

4. sHORt InstALLAtIOn tIME

thanks to small refrigerant pipes and reFnet piping options, the VrV® piping system can be installed very easily and quickly.

installation of the VrV®iii-c system can also be implemented floor by floor, so that sections of the building can be put into use very quickly, or enabling the air conditioning system to be commissioned and operated in stages, rather than on final completion of the project.

5. MOduLAR & LIgHtWEIgHt

modular design enables units to be joined together in rows with an outstanding degree of uniformity.

the design of the outdoor units is sufficiently compact to allow them to be taken up to the top of a building in a commercial elevator, overcoming site transportation problem, particularly when outdoor units need to be installed on each floor.

6. nO stRuCtuRAL REInfORCEMEnt nECEssARy

thanks to the lightweight and vibration-free construction of the outdoor units, floors do not need to be reinforced, reducing the overall cost of the building.

7. REfRIgERAnt pIpIng

Reduced piping diametersuse of high efficiency r-410a enables the VrV®iii-c to operate on a smaller refrigerant charge to be used, leading to a reduction in liquid and gas pipe diameters.

Reduced piping costs thanks to modular designSmaller diameter liquid and gas piping contributes to a reduction in installation space and installation costs.

4-way piping ConnectionVrV®iii-c series not only offer the possibility to run piping from the front, but also from the left, right or bottom, thus providing greater freedom of layout.

15

Page 16: VRV systems - daikin.mcquay.hudaikin.mcquay.hu/1_VRV/2_Kültéri_Egységek/RTSYQ-P_VRVIII-C... · 4. installation & maintenance Friendly design 14 outdoor unitS 19 1. VrV ... VrV

8. unIfIEd REfnEt pIpIng

the unified daikin reFnet piping system is especially designed for simple installation.

the use of reFnet piping in combination with electronic expansion valves, results in a dramatic reduction in imbalance in refrigerant flowing between indoor units, despite the small diameter of the piping.

reFnet joints and headers (both accessories) can cut down on installation work and increase system reliability.

compared to regular t-joints, where refrigerant distribution is far from optimal, the daikin reFnet joints have specifically been designed to optimise refrigerant flow.

9. CROss WIRIng CHECK

the cross wiring check facility available on the VrV® is the first of its type in the industry to warn operatives of connection errors in inter unit wiring and piping. this function identifies and alerts system errors by means of on/off leds on the outdoor unit’s pc boards.

REFNET joint T-joint

Attached insulators for REFNET joint

Attached insulators for REFNET header

REFNET header

REFNET joint

10. sIMpLIfIEd WIRIng

a simple 2-wire non-shielded multiplex transmission system links each outdoor unit to multiple indoor units using one 2-core wire, thus simplifying the wiring operation.Furthermore, outdoor units have power connection outlets on side and front, resulting in easier installation and maintenance and saving space when rows of units are connected together.

FEATURES INSTALLATION & MAINTENANCE FRIENDLy DESIgN

16

Page 17: VRV systems - daikin.mcquay.hudaikin.mcquay.hu/1_VRV/2_Kültéri_Egységek/RTSYQ-P_VRVIII-C... · 4. installation & maintenance Friendly design 14 outdoor unitS 19 1. VrV ... VrV

11. “supER WIRIng” systEM

a Super wiring system is used to enable the shared use of wiring between indoor units, outdoor units and the centralised remote control.

this system makes it easy for the user to retrofit the existing system with a centralised remote control, simply by connecting it to the outdoor units.

thanks to a non polarity wiring system, incorrect connections become impossible and installation time is reduced.

12. 4-WAy WIRIng COnnECtIOn

wiring can be fed from the front panel, both left and right side panels and bottom panel of the outdoor unit.

13. AutO AddREss sEttIng funCtIOn

allows wiring between indoor and outdoor units, as well as group control wiring of multiple indoor units, to be performed without the bothersome task of manually setting each address.

Front

Left

Bottom

Right

17

Page 18: VRV systems - daikin.mcquay.hudaikin.mcquay.hu/1_VRV/2_Kültéri_Egységek/RTSYQ-P_VRVIII-C... · 4. installation & maintenance Friendly design 14 outdoor unitS 19 1. VrV ... VrV

18

Page 19: VRV systems - daikin.mcquay.hudaikin.mcquay.hu/1_VRV/2_Kültéri_Egységek/RTSYQ-P_VRVIII-C... · 4. installation & maintenance Friendly design 14 outdoor unitS 19 1. VrV ... VrV

OUTDOOR UNITS

1. VRV®III-C TECHNOLOgy

1. tWO stAgE COMpREssIOn

two stage compression technology enables the system to create higher pressures resulting in a higher heating capacity under low ambient conditions.the second inverter compressor (located in the function unit) is specially designed to provide higher pressures. after heat is exchanged in the indoor unit, gas and liquid are separated at the gas-liquid separator. this enables the refrigerant in gas condition to be recovered and transmitted direct to the high pressure compressor.

Heating capacity

Enthalpy

pres

sure

Evaporator capacity

Gas injection

Gas-liquidseparator

Input power

High

Middle

Low

Liquid injection

19

Page 20: VRV systems - daikin.mcquay.hudaikin.mcquay.hu/1_VRV/2_Kültéri_Egységek/RTSYQ-P_VRVIII-C... · 4. installation & maintenance Friendly design 14 outdoor unitS 19 1. VrV ... VrV

1

2

3

4

5

1

2

3

4

5

2 sine Wave dC Inverteroptimizing the sine wave curve, results in smoother motor rotation and improved motor efficiency.

2. VRV®III tECHnOLOgy

1 Reluctance brushless dC Compressor

the reluctance brushless dc motor provides significant increases in ›efficiency compared to conventional ac inverter motors, simultaneously using 2 different forms of torque (normal and reluctance torque) to produce extra power from small electric currents.the motor comprises powerful neodymium magnets, that create ›the reluctance torque. these magnets are approximately 12 times stronger than ferrite magnets and make a major contribution to its energy saving characteristics.

High thrust mechanism (VRV › ®III cooling only/heat pump)By introducing high pressure oil, the reactive force from the fixed scroll is added to the internal force, thereby reducing thrust losses. this results in improved efficiency and suppressed sound level.

OUTDOOR UNITS VRVIII-C TECHNOLOgy

20

Ferrite magnet

Neodymium magnet

Page 21: VRV systems - daikin.mcquay.hudaikin.mcquay.hu/1_VRV/2_Kültéri_Egységek/RTSYQ-P_VRVIII-C... · 4. installation & maintenance Friendly design 14 outdoor unitS 19 1. VrV ... VrV

> >

5

0 VrV®ii VrV®iii

43°C

60°C

55°C

55°C

50°C

27°C

27°C

27°C

27°C

27°C

27°C

55°C55°C 37°C

3 dC fan Motor

the use of a dc fan motor offers substantial improvements in operating efficiency compared to conventional ac motors, especially during low speed rotation.

DC fan motor structure

DC motor efficiency(comparison with a conventional AC motor)

Motor speed (rpm)

Efficie

ncy (%

)

AC motor

200 300 400 500 600 700 800 900 1000

100

80

60

40

20

0

4 dual dC fans

maximum 10% increase in airflow (16 hp) due to ›dual dc fans

5 e-pass Heat Exchanger

optimization of the path layout of the heat exchanger prevents heat transferring from the overheated gas section towards the sub cooled liquid section - a more efficient use of the heat exchanger.

In cooling mode, the heat exchanger of the condensor is improved. This means an improvement of COP by 3%.

Current Model HD Type

Fans optimized for their casings (increased air flow without sound increase)

10 HP: 3 blades, ø700 --> 4 blades, ø680

blade area increased by 25%, uneven pitch: No NZ noise

18 HP: ø700 --> ø540 x 2blade area increased by 20%,

sound reduced by 0.7 dB

increased output and reduced pressure loss together ›with increased external static pressure and reduced rated fan input.

10

Intern

al res

istance

(mmH

2O)@

185

m3 /min

10HP

Substantial reduction in pressure loss

Three-dimensional integrated woven soft steel grilles with plastic coating• High strength (withstands weight of 60 kg)• Increased outflow area opening ratio

Increased heat exchange area• Increase in heat exchange effectiveness

8.1

3.2

4.9

3.8

1.3

2.5

OUT 45°CIN 85°C

OUT 45°CIN 85°C

OUT 45°C

21

Page 22: VRV systems - daikin.mcquay.hudaikin.mcquay.hu/1_VRV/2_Kültéri_Egységek/RTSYQ-P_VRVIII-C... · 4. installation & maintenance Friendly design 14 outdoor unitS 19 1. VrV ... VrV

2. SpECIFICATIONS

Independent unit

Outdoor UnitOutdoor UnitFunction unit

Capacity Cooling kW

Heating kWHeating kW

Casing ColourDimensions Unit Height mm

Width mmDepth mm

Function unit Height mmWidth mmDepth mm

Weight Unit kgFunction unit kg

Heat Exchanger Tube typeFan Type

Piston displacement m

Air Flow Rate (nominal at 230V)

Cooling m3/minHeating m3/min

Motor DriveOutput motor W

Compressor Motor TypeSound level Cooling Starting method

Sound Pressure (Maximum)

dBA

Sound Pressure (Nominal)

dBA

Starting MethodRefrigerant Name

Charge kgControl

Piping connections Liquid (OD) TypeDiameter (OD) mm

Gas TypeDiameter (OD) mm

Oil equalizing TypeDiameter (OD) mm

Defrost MethodCapacity ControlSafety devicesPower Supply Name, Phase, Frequency, Voltage

RtsyQ10py1 RtsyQ14py1 RtsyQ16py1 RtsyQ20py1

rtSQ10pY1 rtSQ14pY1 rtSQ16pY1 rtSQ8pY1rtSQ12pY1

BtSQ20pY1 BtSQ20pY1 BtSQ20pY1 BtSQ20pY1

28.0 (1) 40.0 (4) 45.0 (7) 56.0 (10)

31.5 (2) 45.0 (5) 50.0 (8) 63.0 (11)28.0 (3) 40.0 (6) 45.0 (9) 56.0 (12)

Ivory white (5Y7,5/1) Ivory white (5Y7,5/1) Ivory white (5Y7,5/1) Ivory white (5Y7,5/1)1,680 1,680 1,680 1,680930 1,24 1,24 930 + 930765 765 765 765

1,570 1,570 1,570 1,570460 460 460 460765 765 765 765257 338 344 205 + 257110 110 110 110

Cross fin coil Cross fin coil Cross fin coil Cross fin coilPropeller Propeller Propeller Propeller

(13.72+10.53) + 16.9 (13.72+10.53+10.53)+16.9 (13.72+10.53+10.53) + 16.9 16.9+(13.72+10.53)+16.9185 233 239 (185+200)185 233 239 (185+200)

Direct drive Direct drive Direct drive Direct drive0.75x1 0.35x2 0.75x2 (0.75)+ (0.75)

Hermetically sealed scroll compressorSoft start

62 63 65 65

60 61 63 63

Soft startR-410A R-410A R-410A R-410A10.5 11.7 11.7 9.4+10.9

Expansion valve (electronic type) Expansion valve (electronic type) Expansion valve (electronic type) Expansion valve (electronic type)Braze connection Braze connection Braze connection Braze connection

9.52 12.7 12.7 15.9Braze connection Braze connection Braze connection Braze connection

22.2 28.6 28.6 28.6- - - Braze connection- - - 19.1

Deicer Deicer Deicer Deicer9 to 100 7 to 100 7 to 100 6 to 100

HPS - Fan motor driver overload protector - Over current relay - Inverter overload protectorY1, 3~, 50, 380-415

(1) indoor temperature: 27°CDB, 19°CWB; outdoor temperature 35°CDB; equivalent piping length: 7.5m; level difference 0m; function unit length: 6m; combined indoor unit: FXFQ50P x 5 units(2) indoor temperature: 20°CDB; outdoor temperature 7°CDB,6°CWB; equivalent piping length: 7.5m; level difference 0m; function unit length: 6m; combined indoor unit: FXFQ50P x 5 units(3) indoor temperature: 20°CDB; outdoor temperature -10°CWB; equivalent piping length: 7.5m; level difference 0m; function unit length: 6m; combined indoor unit: FXFQ50P x 5 units(4) indoor temperature: 27°CDB, 19°CWB; outdoor temperature 35°CDB; equivalent piping length: 7.5m; level difference 0m; function unit length: 6m; combined indoor unit: FXFQ50P x 7 units(5) indoor temperature: 20°CDB; outdoor temperature 7°CDB,6°CWB; equivalent piping length: 7.5m; level difference 0m; function unit length: 6m; combined indoor unit: FXFQ50P x 7 units(6) indoor temperature: 20°CDB; outdoor temperature -10°CWB; equivalent piping length: 7.5m; level difference 0m; function unit length: 6m; combined indoor unit: FXFQ50P x 7 units(7) indoor temperature: 27°CDB, 19°CWB; outdoor temperature 35°CDB; equivalent piping length: 7.5m; level difference 0m; function unit length: 6m; combined indoor unit: FXFQ50P x 8 units(8) indoor temperature: 20°CDB; outdoor temperature 7°CDB,6°CWB; equivalent piping length: 7.5m; level difference 0m; function unit length: 6m; combined indoor unit: FXFQ50P x 8 units(9) indoor temperature: 20°CDB; outdoor temperature -10°CWB; equivalent piping length: 7.5m; level difference 0m; function unit length: 6m; combined indoor unit: FXFQ50P x 8 units(10) indoor temperature: 27°CDB, 19°CWB; outdoor temperature 35°CDB; equivalent piping length: 7.5m; level difference 0m; function unit length: 6m; combined indoor unit: FXFQ50P x 10 units(11) indoor temperature: 20°CDB; outdoor temperature 7°CDB,6°CWB; equivalent piping length: 7.5m; level difference 0m; function unit length: 6m; combined indoor unit: FXFQ50P x 10 units(12) indoor temperature: 20°CDB; outdoor temperature -10°CWB; equivalent piping length: 7.5m; level difference 0m; function unit length: 6m; combined indoor unit: FXFQ50P x 10 units

OUTDOOR UNITS

2222

Page 23: VRV systems - daikin.mcquay.hudaikin.mcquay.hu/1_VRV/2_Kültéri_Egységek/RTSYQ-P_VRVIII-C... · 4. installation & maintenance Friendly design 14 outdoor unitS 19 1. VrV ... VrV

3. ACCESSORIES

Optional accessories

Distributive piping

Refnet header

Refnet joint

Snowbreak hood*

Kit (inlet + outlet)Air outletLeft side air inlet Right side air inletBack side air inlet

Outdoor unit multi connection piping kit

RtsyQ10py1 RtsQ14py1 RtsyQ20py1

RtsyQ16py1

KHRP26M22H (max.4 branch) KHRP26M22H (max.4 branch)KHRP26M33H (max.8 branch) KHRP26M33H (max.8 branch)

- KHRP26M72H (max.8 branch)KHRP26A22T KHRP26A22T KHRP26A22TKHRP26A33T KHRP26A33T KHRP26A33T

- KHRP26A72T KHRP26A72T- - KHRP26A73T

KPS26C280 KPS26C504 KPS26C280*KPS26C280T KPS26C504T KPS26C280T*KPS26C504L KPS26C504L KPS26C504L*KPS26C504R KPS26C504R KPS26C504R*KPS26C280B KPS26C504B KPS26C280B*

- - BHFP30A36

Note:* Snowbreak hoods are field supply. For technical drawings and more information contact your local Daikin dealer. Snowbreak hoods are advised to be installed when regular snowfall occurs.

23

Page 24: VRV systems - daikin.mcquay.hudaikin.mcquay.hu/1_VRV/2_Kültéri_Egységek/RTSYQ-P_VRVIII-C... · 4. installation & maintenance Friendly design 14 outdoor unitS 19 1. VrV ... VrV

850 mm

FXFQ-P

FXZQ-M820-25-32-40-50

20-25-32-40-50-63-80-100-125

60°

Ceiling void is 295 mm

Indoor UnIts

1. FeatUres

Round Flow ceiling mounted cassette

comfort�Modern�style�decoration�panel�in�white�(RAL9010)�›�360°� air� discharge� ensures� uniform� air� flow� and� temperature��›distributionAir�discharge�from�the�corners�avoids�dead�zones�that�may�be�subject��›to�temperature�differences�Comfortable� horizontal� air� discharge� ensures� draughtfree� operation��›and�prevents�ceiling�soiling�23�different�air�flow�patterns�possible��›Fresh�air�intake:�up�to�20%�›

Flexible installation and easy maintenance�Reduced�installation�height:�214mm�for�class�20-63��›Easy�visible�drain�check�thanks�to�clear�drain�socket����›Drain-up�pump�with�850�mm�lift�fitted�as�standard�›

360° Round Flow 4-Way Flow 3-Way Flow 2-Way Flow

Examples of Airflow Patterns

4-way blow ceiling mounted cassette (600mmx600mm)

comfort�Modern�style�decoration�panel�in�white�(RAL9010)�›Extremely�quiet�in�operation�›Excellent�low�draught�characteristics.��Since�the�flaps�can�move�to�a�0°��›position,�virtually�no�draught�can�be�experienced�Any�one�of�5�different�air�flow�patterns�can�be�freely�selected�between��›0°�and�60°�and�will�then�be�maintained�during�the�operational�cycle�of�the�air�conditioner

Flexible installation and easy maintenanceThanks� to� the� compact� casing,� it� matches� standard� architectural��›modules� of� 600x600mm,� therefore� ceiling� tile� cutting� is� no� longer�necessary�Air�can�be�discharged�in�any�of�4�directions�›�Possibility�to�shut�1�or�2�flaps�for�easy�installation�in�corners��›Since�the�switch�box�is�located�within�the�unit,�it�is�easy�to�access�from��›below�for�maintenance�without�removing�ceiling�tilesDrain-up�pump�with�500mm�lift�fitted�as�standard�›

500 mm

24

Page 25: VRV systems - daikin.mcquay.hudaikin.mcquay.hu/1_VRV/2_Kültéri_Egységek/RTSYQ-P_VRVIII-C... · 4. installation & maintenance Friendly design 14 outdoor unitS 19 1. VrV ... VrV

FXCQ-M8

FXKQ-Ma20-32-40-63

20-25-32-40-50-63-80-125

2-way blow ceiling mounted cassette

comfortQuiet�in�operation�›Leaves�maximum�floor�and�wall�space�for�furniture,�decorations�and��›fittingsAutomatic�air�flow�director�ensures�uniform�air�flow�and�temperature��›distributionAnti-ceiling�soiling�technology�›

�Filter

�Standard�long�life�filter�›�

Flexible installation and easy maintenance�Easy�installation�in�false�ceilings�of�only�355mm�›Drain-up�pump�with�600mm�lift�fitted�as�standard�›Maintenance�can�be�performed�by�simply�removing��›the�front�panel�Easy�to�clean�flat�suction�grille�›�Detachable�swing�flaps�›

ceiling mounted coRneR cassette

comfort�Equipped� with� special� draught� prevention� and� anti-ceiling� soiling��›technology

�Automatic�air�flow�director�ensures�uniform�air�flow�and�temperature��›distributionAir� flow� by� either� downward� air� discharge,� frontal� discharge� or� a��›combination�of�both

Flexible installation�Compact�dimensions,�can�easily�be�mounted�in�a�narrow�ceiling�void��›(only�220mm�ceiling�space�required,�195�with��spacer,�available�as�accessory)

Drain-up�pump�with�500mm�lift�fitted�as�standard�›

1Standard

Note: Standard setting when shipped.

2Draughtprevention

3Anti-ceiling soiling technology

minimum ceiling height is 355mm

600mm

CombinationFrontal discharge

Closed by the decoration panel

Downward discharge

Min. 195 mm

Panel spacer

20 mm 500 mm

25

Page 26: VRV systems - daikin.mcquay.hudaikin.mcquay.hu/1_VRV/2_Kültéri_Egységek/RTSYQ-P_VRVIII-C... · 4. installation & maintenance Friendly design 14 outdoor unitS 19 1. VrV ... VrV

Indoor UnIts FeatUres

26

FXdQ-M8

20-25-32-40-50-63

20-25

small concealed ceiling unit

comfortDesigned�for�hotel�bedrooms�›Blends� unobtrusively� with� any� interior� décor:� only� the� suction� and��›discharge�grilles�are�visible�Extremely�quiet�in�operation��›

Filter�Air�suction�filter�fitted�as�standard���›�

Flexible installation�Compact� dimensions� (230mm� high� &� 652mm� deep),� can� easily� be��›mounted�in�a�ceiling�void�The�air�suction�direction�can�be�altered�from�rear� to�bottom�suction��›�For� easy� mounting,� the� drain� pan� can� be� located� to� the� left� or� the��›right�of�the�unit

slim concealed ceiling unit

comfortQuiet�in�operation�›Blends�unobtrusively�with�any�interior�décor��›�Leaves�maximum�floor�and�wall�space�for�furniture,�decorations�and��›fittings�

200mm

Ceiling

Suction Chamber[Duct connection]

Air filter

FXdQ-P/na

Can�be�installed�in�both�new�and�existing�buildings�›Medium�external�static�pressure�facilitates�unit�use�with�flexible�ducts��›of�varying�lengths�Drain-up�pump�with�750mm�lift�fitted�as�standard�›

Flexible installation Slim�design,�can�easily�be�mounted�in�a�ceiling�void�of�only�240mm�›

Page 27: VRV systems - daikin.mcquay.hudaikin.mcquay.hu/1_VRV/2_Kültéri_Egységek/RTSYQ-P_VRVIII-C... · 4. installation & maintenance Friendly design 14 outdoor unitS 19 1. VrV ... VrV

FXsQ-M8

FXMQ-P/Ma

20-25-32-40-50-63-80-100-125

40-50-63-80-100-125-200-250

concealed ceiling unit

comfortHigh�flexibility�for�a�wide�variety�of�applications�›Quiet�in�operation�›Blends�unobtrusively�with�any�interior�décor�›

Filter�Long�life�filter�fitted�as�standard�›�High�efficiency�filters�(65%�and�95%)�available�as�accessory�›

Flexible installation and easy maintenanceHigh�external�static�pressure�facilitates�unit�use�with�flexible�ducts�of��›varying�lengths��When�using�suction�panel,�unit� requires�only��›350mm�of�ceiling�space�Drain-up� pump� with� 625mm� lift� fitted� as��›standardThe�air�suction�direction�can�be�altered�from��›rear�to�bottom�suction�The�switch�box�can�be�reached�from�the�side��›or�from�the�bottom�side�of�the�unit�for�easy�servicing

concealed ceiling unit

comfortLeaves� maximum� floor� and� wall� space� for� furniture,� decorations��›and�fittings�

Flexible installationCompact�unit�(a�height�of�300�mm),�allows�installation�in�narrow��›ceiling�voids�More�than�200�Pa�external�static�pressure�allows�extensive�ductwork��›runs�and�flexible�application:�ideal�for�use�in�large�areasBuilt-in�drain�pump�(standard�for�sizes�40�to�125)�increases�reliability�of��›the�drain�systemComplete�range�of�models�(FXMQ-PVE:�4.5�-�14�kW)���›(FXMQ-MAVE:�22.40�-�28�kW)Possibility� to� change� ESP� through� wired� remote� control� allows��›optimisation�of�the�supply�air�volumeReduction�of�power�consumption�of�20�%�(compared�to�FXMQ-MAVE��›series)�through�use�of�new�DC�Fan

Min.350mm

625mm

NEW

27

Page 28: VRV systems - daikin.mcquay.hudaikin.mcquay.hu/1_VRV/2_Kültéri_Egységek/RTSYQ-P_VRVIII-C... · 4. installation & maintenance Friendly design 14 outdoor unitS 19 1. VrV ... VrV

Indoor UnIts FeatUres

28

100°

10° Cooling

70° Heating

FXaQ-Ma

32-63-100

20-25-32-40-50-63

wall mounted unit

comfortCompact�and�stylish�design�blends�unobtrusively�in�any�interior�décor��›Automatic�air�flow�director�ensures�efficient�air�distribution�via�louvers��›that�close�automatically�when�the�unit�is�switched�off�5� different� discharge� angles� can� be� programmed� via� the� remote��›control�Discharge�angle�automatically�returns�to�its�previous�position�on�restart��›(initial�setting�10�degrees�for�cooling�and�70�degrees�for�heating)

FilterMildew�proof�polystyrene�filter�and�drain�pan�›

Flexible installation and easy maintance Both� horizontal� flaps� and� front� panel� can� easily� be� removed� and��›washedAll� maintenance� operations� can� be� carried� out� from� the� front� of��›the�unit��Drain-up�pump�with�1,000mm�lift�available�as�accessory�›Drain�pipe�can�be�fitted�either�to�the�left�or�right�side�of�the�unit�›

slim concealed ceiling unit

comfortQuiet�in�operation��›Leaves�maximum�floor�and�wall�space�for�furniture,�decorations�and��›fittingsEnhanced�horizontal�and�vertical�air�circulation�in�all�directions�thanks��›to�an�air�flow�pattern�of�100°

FilterLong�life�filter�fitted�as�standard���›

Flexible installation and easy maintance Can�be�installed�in�both�new�and�existing�buildings�›The�ideal�solution�for�installation�without�false�ceilings�›Drain-up�pump�with�600mm�lift�available�as�accessory�›

�Maintenance�can�be�performed�easily�from�below�the�unit�›�Bristle�free�flap�makes�cleaning�easier�›

Drain-up kit(built inside main unit)

Drain-up kit(built inside main unit)

10° Cooling

70° Heating

1,000mm

Height of drain-up

Drain-up kit

Indoor unitDrain-up kit

1,000mm

Height of drain-up

Indoor unitDrain-up kit

32-63-100

20-25-32-40-50-63

FXHQ-Ma

Page 29: VRV systems - daikin.mcquay.hudaikin.mcquay.hu/1_VRV/2_Kültéri_Egységek/RTSYQ-P_VRVIII-C... · 4. installation & maintenance Friendly design 14 outdoor unitS 19 1. VrV ... VrV

FXUQ-Ma71-100-125

4-way blow ceiling suspended unit

comfortGroup�control�with�other�VRV�› ®�indoor�units�possible�Cool�heat�selection��›Prevention� of� cold� draught� at� hot� start,� defrost� and� oil� return� in��›heating�Air�can�be�discharged�in�any�of�4�directions�›Air� can� be� discharged� at� 5� different� angles� between� 0� and��›60�degrees

Automatic� air� flow� director� ensures� efficient� air� and� temperature��›distribution.�Air� flow� distribution� for� ceiling� heights� up� to� 3.5m� without� loss� of��›capacity.�

FilterAir�filter,�drain�pan�and�heat�exchanger�fin�are�mildew�proof�and�anti-�›bacterial�treated

Flexible installation Ideal�for�installation�in�new�and�existing�buildings�›5m�maximum�distance�between�FXUQ�unit�and�junction�box��›Possibility�to�shut�1�or�2�flaps�for�easy�installation�in�corners�›Drain-up�pump�with�500mm�lift�fitted�as�standard�›

29

Page 30: VRV systems - daikin.mcquay.hudaikin.mcquay.hu/1_VRV/2_Kültéri_Egységek/RTSYQ-P_VRVIII-C... · 4. installation & maintenance Friendly design 14 outdoor unitS 19 1. VrV ... VrV

Indoor UnIts FeatUres

30

Wall mounted Floor standing

FXLQ-Ma

20-25-32-40-50-63

20-25-32-40-50-63

FlooR standing unit

comfortIdeal�for�installation�beneath�a�window��›Compact�dimensions�(only�222mm�deep�and�600mm�high)��›All�models�are�available�with�remote�control�›

FilterLong�life�filter�fitted�as�standard�›

Flexible installation and easy maintance Running�the�pipes�from�connections�at�the�back,�enables�the�unit�to��›be�wall�mounted�

concealed FlooR standing unit

comfortIdeal�for�perimeter�air�conditioning�›�Ideal�for�installation�below�a�window��›�All�models�are�available�with�remote�control�›

FilterLong�life�filter�fitted�as�standard��›

Flexible installation and easy maintance On�site�connection�during�installation�is�easier�›�The�connecting�port�faces�downward,�eliminating�the�need�to�attach��›auxiliary�piping

FXnQ-Ma

Connecting port

Refrigerantpiping

�On�site�connection�during�installation�is�easier�›�The� fibreless� discharge� grille� prevents� condensation� and� staining�›

Page 31: VRV systems - daikin.mcquay.hudaikin.mcquay.hu/1_VRV/2_Kültéri_Egységek/RTSYQ-P_VRVIII-C... · 4. installation & maintenance Friendly design 14 outdoor unitS 19 1. VrV ... VrV

FXFQ-PR o u n d f l o w � c e i l i n g � m o u n t e d � c a s s e t t e

FxFQ20p FxFQ25p FxFQ32p FxFQ40p FxFQ50p FxFQ63p FxFQ80p FxFQ100p FxFQ125p

FxFQ20p FxFQ25p FxFQ32p FxFQ40p FxFQ50p FxFQ63p FxFQ80p FxFQ100p FxFQ125p

FxFQ-p

Capacitycooling kWheating kW

Power inputcooling kWheating kW

Dimensions (H x W x D) mmWeight unit kgCasing

Air Flow Ratecooling high / low m3 /minheating high / low m3 /min

Sound power (nominal) cooling dB(A)

Sound pressurecooling high / low dB(A)heating high / low dB(A)

Refrigerant namePower SupplyPiping Connections L / G / D diameter mmAir FilterDrain-up Height mm

Decoration Panel

modelcolour(H x W x D) mmweight kg

2.2 2.8 3.6 4.5 5.6 7.1 9.0 11.2 14.02.5 3.2 4.0 5.0 6.3 8.0 10.0 12.5 16.0

0.053 0.063 0.083 0.095 0.120 0.173 0.2580.045 0.055 0.067 0.114 0.108 0.176 0.246

204 x 840 x 840 246 x 840 x 840 288 x 840 x84020.0 21.0 24.0 26.0

Galvanised steel12.5 / 9.0 13.5 / 9.0 15.5 / 10.0 16.5 / 11.0 23.5 / 14.5 26.5 / 17.0 33.0 / 20.012.5 / 9.0 13.5 / 9.0 15.0 / 9.5 17.5 / 12.0 23.5 / 14.5 28.0 / 17.5 33.0 / 20.0

49 50 51 52 55 58 6131 / 28 32 / 28 33 / 28 34 / 29 38 / 32 41 / 33 44 / 3431 / 28 32 / 28 33 / 28 36 / 30 38 / 32 42 / 34 44 / 34

R-410A1~ / 220-240V / 50Hz

6.35 / 12.7 / 32 6.4 / 12.7 / 32 9.5 / 15.9 / 32Resin net with mold resistance

750BYCQ140CW1

RAL901050x950x950

5.5

Notes:The�sound�pressure�values�are�mentioned�for�a�unit�installed�with�rear�suctionThe�sound�power�level�is�an�absolute�value�indicating�the�power�wich�a�sound�source�generates.Nominal�cooling�capacities�are�based�on:�indoor�temperature:�270CDB,�190CWB,�outdoor�temperature:�350CDB,�equivalent�refrigerant�piping:�5m,�level�difference:�0m.Nominal�heating�capacities�are�based�on:�indoor�temperature:�20°CDB,�outdoor�temperature:�7°CDB,�6°CWB,�equivalent�refrigerant�piping:�5m,�level�difference:�0m.Capacities�are�net,�including�a�deduction�for�cooling�(an�addition�for�heating)�for�indoor�fan�motor�heat.

accessoRies

speciFications

Wired remote controlInfrared remote control cooling only

heat pumpDecoration panelReplacement long life filter (non-woven type)Fresh air intake kit (20 % fresh air intake) (chamber type)Air discharge outlet sealing member

BRC1D52BRC7F533FBRC7F532F

BYCQ140CW1KAFP551K160KDDQ5C140

KDBHQ55C140

FxFQ-p

2. sPeCIFICatIons & aCCessorIes

31

Page 32: VRV systems - daikin.mcquay.hudaikin.mcquay.hu/1_VRV/2_Kültéri_Egységek/RTSYQ-P_VRVIII-C... · 4. installation & maintenance Friendly design 14 outdoor unitS 19 1. VrV ... VrV

FXZQ-M84 - w a y b l o w c e i l i n g m o u n t e d c a s s e t t e ( 6 0 0 m m x 6 0 0 m m )

Notes:Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB • outdoor temperature: 35°CDB • equivalent piping length: 7.5m (horizontal).Nominal heating capacities are based on: indoor temperature: 20°CDB • outdoor temperature: 7°CDB, 6°CWB • equivalent piping length: 7.5m (horizontal).Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.

2.2 2.8 3.6 4.5 5.62.5 3.2 4.0 5.0 6.373 73 76 89 11564 64 68 80 107

286 x 575 x 57518

galvanised steel plate9.0 / 7.0 9.0 / 7.0 9.5 / 7.5 11.0 / 8.0 14.0 / 10.030 / 25 30 / 25 32 / 26 36 / 28 41 / 33

47 47 49 53 58R-410A

ø6.4 / ø12.7resin net with mold resistant

5001~, 50Hz, 220-240V

55 x 700 x 7002.7

white (RAL 9010)

Cooling capacity kWHeating capacity kWNominal input  cooling W

heating WDimensions (H x W x D) mmWeight kgCasingAir flow rate (H / L) m3 /minSound pressure level (H / L) (220V) dB(A)Sound power level dB(A)Refrigerant typePiping connections liquid / gas mmAir filterDrain-up height mmPower supply V1Decoration panel dimensions (H x W x D) mm

weight kgcolour

   

FXZQ20M8 FXZQ25M8 FXZQ32M8 FXZQ40M8 FXZQ50M8FXZQ-M8

FXZQ20M8 FXZQ25M8 FXZQ32M8 FXZQ40M8 FXZQ50M8FXZQ-M8

BRC1D52BRC7E531BRC7E530BYFQ60B

KDBH44B60KDBQ44B60KAFQ441B60KDDQ44X60

Wired remote controlInfrared remote control cooling only

heat pumpDecoration panelSealing member of air discharge outletPanel spacerReplacement long life filterFresh air intake kit direct installation type

Accessories

speciFicAtions

32

OutdOOr units spciFicatiOns & accessOries

Page 33: VRV systems - daikin.mcquay.hudaikin.mcquay.hu/1_VRV/2_Kültéri_Egységek/RTSYQ-P_VRVIII-C... · 4. installation & maintenance Friendly design 14 outdoor unitS 19 1. VrV ... VrV

FXcQ-M82 - w a y b l o w c e i l i n g m o u n t e d c a s s e t t e

Notes:Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB • outdoor temperature: 35°CDB • equivalent refrigerant piping: 8m • level difference: 0m.Nominal heating capacities are based on: indoor temperature: 20°CDB • outdoor temperature: 7°CDB, 6°CWB • equivalent refrigerant piping: 8m • level difference: 0m.Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.

Cooling capacity kWHeating capacity kWNominal input  cooling W

heating WDimensions (H x W x D) mmWeight kgCasingAir flow rate (H / L) m3 /minSound pressure level (H / L) dB(A)Sound power level dB(A)Refrigerant typePiping connections liquid / gas mmAir filterDrain-up height mmPower supply V3Decoration panel dimensions (H x W x D) mm

weight kgcolour

FXcQ-M8 FXcQ20M8 FXcQ25M8 FXcQ32M8 FXcQ40M8 FXcQ50M8 FXcQ63M8 FXcQ80M8 FXcQ125M8

2.2 2.8 3.6 4.5 5.6 7.1 9.0 14.02.5 3.2 4.0 5.0 6.3 8.0 10.0 16.077 92 92 130 130 161 209 25644 59 59 97 97 126 176 223

305 x 780 x 600 305 x 995 x 600 305 x 1,180 x 600 305 x 1,670 x 60026 31 32 35 47 48

galvanised steel plate7 / 5 9 / 6.5 9 / 6.5 12 / 9 12 / 9 16.5 / 13 26 / 21 33 / 25

33 / 28 35 / 29 35 / 29 35.5 / 30.5 35.5 / 30.5 38 / 33 40 / 35 45 / 3945 50 50 50 50 52 54 60

R-410Aø6.4 / ø12.7 ø9.5 / ø15.9

resin net with mold resistant600

1~, 50Hz, 230V53 x 1,030 x 680 53 x 1,245 x 680 53 x 1,430 x 680 53 x 1,920 x 680

8 8.5 9.5 12ivory white

Wired remote controlInfrared remote control cooling only

heat pumpDecoration panelHigh efficiency filter 65% *1High efficiency filter 90% *1Filter  chamber for bottom suctionReplacement long life filter

BRC1D52BRC7C67BRC7C62

BYBC32G BYBC50G BYBC63G BYBC125GKAFJ532G36 KAFJ532G56 KAFJ532G80 KAFJ532G160KAFJ533G36 KAFJ533G56 KAFJ533G80 KAFJ533G160KDDFJ53G36 KDDFJ53G56 KDDFJ53G80 KDDFJ53G160KAFJ531G36 KAFJ531G56 KAFJ531G80 KAFJ531G160

FXcQ20M8 FXcQ25M8 FXcQ32M8 FXcQ40M8 FXcQ50M8 FXcQ63M8 FXcQ80M8 FXcQ125M8FXcQ-M8

Note:*1. Filter chamber is required when installing a high efficiency filter.

Accessories

speciFicAtions

33

Page 34: VRV systems - daikin.mcquay.hudaikin.mcquay.hu/1_VRV/2_Kültéri_Egységek/RTSYQ-P_VRVIII-C... · 4. installation & maintenance Friendly design 14 outdoor unitS 19 1. VrV ... VrV

FXKQ-Ma

C e i l i n g m o u n t e d c o r n e r c a s s e t t e

Notes:Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB • outdoor temperature: 35°CDB • equivalent refrigerant piping: 7.5m (horizontal).Nominal heating capacities are based on: indoor temperature: 20°CDB • outdoor temperature: 7°CDB, 6°CWB • equivalent refrigerant piping: 7.5m (horizontal).Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.*Data were not available at time of publication.

2.8 3.6 4.5 7.13.2 4.0 5.0 8.066 66 76 10546 46 56 85

215 x 1,110 x 710 215 x 1,310 x 71031 34

galvanised steel plate11 / 9 11 / 9 13 / 10 18 / 1538 / 33 38 / 33 40 / 34 42 / 37

* * * *R-410A

ø6.4 / ø12.7 ø9.5 / ø15.9resin net with mold resistant

5001~, 50Hz, 220-240V

70 x 1,240 x 800 70 x 1,440 x 8008.5 9.5

ivory white

Cooling capacity kWHeating capacity kWNominal input  cooling W

heating WDimensions (H x W x D) mmWeight kgCasingAir flow rate (H / L) m3 /minSound pressure level (H / L) (220V) dB(A)Sound power level dB(A)Refrigerant typePiping connections liquid / gas mmAir filterDrain-up height mmPower supply VEDecoration panel dimensions (H x W x D) mm

weight kgcolour

FXKQ-MA FXKQ25MA FXKQ32MA FXKQ40MA FXKQ63MA

BRC1D52BRC4C63BRC4C61

BYK45F BYK71FKPBJ52F56 KPBJ52F80KAFJ521F56 KAFJ521F80K-HV7AW K-HV9AW

KDBJ52F56W KDBJ52F80WKFDJ52F56 KFDJ52F80

FXKQ-MA

Wired remote controlInfrared remote control cooling only

heat pumpDecoration panelPanel spacerReplacement long life filterAir discharge grilleAir discharge blind panelFlexible duct (with shutter)

FXKQ25MA FXKQ32MA FXKQ40MA FXKQ63MA

Accessories

speciFicAtions

34

OutdOOr units spciFicatiOns & accessOries

Page 35: VRV systems - daikin.mcquay.hudaikin.mcquay.hu/1_VRV/2_Kültéri_Egységek/RTSYQ-P_VRVIII-C... · 4. installation & maintenance Friendly design 14 outdoor unitS 19 1. VrV ... VrV

FXdQ-M8S m a l l c o n c e a l e d c e i l i n g u n i t

Notes :Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB • outdoor temperature: 35°CDB • equivalent refrigerant piping: 8m • level difference : 0mNominal heating capacities are based on: indoor air temperature: 20°CDB • outdoor temperature: 7°CDB, 6°CWB • equivalent refrigerant piping: 8m • level difference : 0mCapacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.

FXDQ20M8 FXDQ25M8

2.2 2.82.5 3.2

5050

230x502x65217

galvanised steel plate6.7/5.2 7.4/5.8

37/3250

R-410Aø6.4/ø12.7

resin net with mold resistant1~, 50Hz, 230V

FXDQ-M8

Cooling capacity kWHeating capacity kWNominal input  cooling W

heating WDimensions (HxWxD) mmWeight kgCasingAir flow rate (H/L) m3/minSound pressure level (H/L) dB(A)Sound power level dB(A)Refrigerant typePiping connections liquid/gas mmAir filterPower supply V3

FXDQ20M8 FXDQ25M8FXDQ-M8

Wired remote controlInfrared remote control cooling 

heating

BRC1D52, BRC2C51, BRC3A61BRC4C64BRC4C62

Accessories

speciFicAtions

35

Page 36: VRV systems - daikin.mcquay.hudaikin.mcquay.hu/1_VRV/2_Kültéri_Egységek/RTSYQ-P_VRVIII-C... · 4. installation & maintenance Friendly design 14 outdoor unitS 19 1. VrV ... VrV

FXdQ-p / naS l i m c o n c e a l e d c e i l i n g u n i t

2.2 2.8 3.6 4.5 5.6 7.12.5 3.2 4.0 5.0 6.3 8.086 86 89 160 165 18167 67 70 70 152 168

200 x 700 x 620 200 x 900 x 620 200 x 1,100 x 62023 23 23 27 28 31

galvanised steel plate8.0 / 6.4 8.0 / 6.4 8.0 / 6.4 10.5 / 8.5 12.5 / 10.0 16.5 / 13.033 / 29 33 / 29 33 / 29 34 / 30 35 / 31 36 / 32

* * * * * *R-410A

750ø6.4 / ø12.7 ø9.5 / ø15.9

removable, washable, mildew proof1~, 50Hz, 220-240V

Cooling capacity kWHeating capacity kWNominal input  cooling W

heating WDimensions (H x W x D) mmWeight kgCasingAir flow rate (H / L) m3 /minSound pressure level (H / L) dB(A)Sound power level dB(A)Refrigerant typeDrain-up height mmPiping connections liquid / gas mmAir filterPower supply VE

FXDQ20p FXDQ25p FXDQ32p FXDQ40nA FXDQ50nA FXDQ63nAFXDQ-p / nA

FXDQ-p / nA

BRC1D52BRC4C64BRC4C62 

Wired remote controlInfrared remote control cooling only

heat pump

FXDQ20p FXDQ25p FXDQ32p FXDQ40nA FXDQ50nA FXDQ63nA

Notes:Nominal cooling capacities are based on: • Indoor temperature: 27°CDB, 19°CWB • Outdoor temperature: 35°CDB • Equivalent piping length: 7.5m (horizontal).Nominal heating capacities are based on: • Indoor temperature: 20°CDB • Outdoor temperature: 7°CDB, 6°CWB • Equivalent piping length: 7.5m (horizontal).Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.The sound pressure values are mentioned for a unit installed with rear suction.* Data were not available at time of publication.

Accessories

speciFicAtions

36

OutdOOr units spciFicatiOns & accessOries

Page 37: VRV systems - daikin.mcquay.hudaikin.mcquay.hu/1_VRV/2_Kültéri_Egységek/RTSYQ-P_VRVIII-C... · 4. installation & maintenance Friendly design 14 outdoor unitS 19 1. VrV ... VrV

FXsQ-M8C o n c e a l e d c e i l i n g u n i t

Cooling capacity kWHeating capacity kWNominal input  cooling W

heating WDimensions (H x W x D) mmWeight kgCasingAir flow rate (H / L) m3 /minSound pressure level (H / L) dB(A)Sound power level dB(A)Refrigerant typePiping connections liquid / gas mmAir filterDrain-up height mmPower supply V3Decoration panel dimensions (H x W x D)

weight kgcolour

2.2 2.8 3.6 4.5 5.6 7.1 9.0 11.2 14.02.5 3.2 4.0 5.0 6.3 8.0 10.0 12.5 16.0110 110 114 127 143 189 234 242 32190 90 94 107 123 169 214 222 301

300 x 550 x 800 300 x 700 x 800 300 x 1,000 x 800 300 x 1,400 x 80030 30 30 30 31 41 51 51 52

galvanised steel plate9 / 6.5 9 / 6.5 9.5 / 7 11.5 / 9 15 / 11 21 / 15.5 27 / 20 28 / 20.5 38 / 2832 / 28 32 / 28 33 / 28 33 / 29 35 / 31 35 / 30 37 / 31 38 / 33 40 / 35

50 50 51 56 58 56 55 56 65R-410A

ø6.4 / ø12.7 ø9.5 / ø15.9resin net with mold resistant

6251~, 50Hz, 230V

55 x 650 x 500 55 x 800 x 500 55 x 1,100 x 500 55 x 1,500 x 5003 3.5 4.5 6.5

ivory white

FXsQ20M8 FXsQ25M8 FXsQ32M8 FXsQ40M8 FXsQ50M8 FXsQ63M8 FXsQ80M8 FXsQ100M8 FXsQ125M8FXsQ-M8

Wired remote controlInfrared remote control cooling only

heat pumpDecoration panelService access panelHigh efficiency filter 65% *1High efficiency filter 90% *1Filter  chamber for bottom suctionFilter chamber rear suctionAir suction canvasScreening door / blind boardAir discharge adapter for round duct

BRC1D52, BRC2C51, BRC3A61BRC4C64BRC4C62

BYBS32D BYBS45D BYB571D BYBS125DKTBJ25K36W KTBJ25K56W KTBJ25K80W KTBJ25K160WKAFJ252L36 KAFJ252L56 KAFJ252L80 KAFJ252L160KAFJ253L36 KAFJ253L56 KAFJ253L80 KAFJ253L160KAJ25L36D KAJ25L56D KAJ25L80D KAJ25L160DKAJ25L36B KAJ25L56B KAJ25L80B KAJ25L160BKSA-25K36 KSA-25K56 KSA-25K80 KSA-25K160KBBJ25K36 KBBJ25K56 KBBJ25K80 KBBJ25K160KDAJ25K36 KDAJ25K56 KDAJ25K71 KDAJ25K140

FXsQ20M8 FXsQ25M8 FXsQ32M8 FXsQ40M8 FXsQ50M8 FXsQ63M8 FXsQ80M8 FXsQ100M8FXsQ125M8FXsQ-M8

Notes:Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB • outdoor temperature: 35°CDB • equivalent refrigerant piping: 8m • level difference: Om.Nominal heating capacities are based on: indoor temperature: 20°CDB • outdoor temperature: 7°CDB, 6°CWB • equivalent refrigerant piping: 8m • level difference: Om.Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. The sound pressure values are mentioned for a unit installed with rear suction.

Notes:*1. If installing a high efficiency filter in the unit, an assembly chamber for either bottom or rear suction is required.

Accessories

speciFicAtions

37

Page 38: VRV systems - daikin.mcquay.hudaikin.mcquay.hu/1_VRV/2_Kültéri_Egységek/RTSYQ-P_VRVIII-C... · 4. installation & maintenance Friendly design 14 outdoor unitS 19 1. VrV ... VrV

FXMQ-p/MaC o n c e a l e d c e i l i n g u n i t

4.5 5.6 7.1 9.0 11.2 14.0 22,4 28,05.0 6.3 8.0 10.0 12.5 16.0 25,0 31,5

0.194(1) / 0.193(2) 0.215(1) / 0.214(2) 0.230(1) / 0.229(2) 0.298(1) / 0.297(2) 0.376(1) / 0.375(2) 0.461(1) / 0.460(2) 1.294 1.4650.182 0.203 0.218 0.286 0.364 0.449 1.294 1.465

300 x 700 x 700 300 x 1,000 x 700 300 x 1,400 x 700 470x1.380x1.10028 36 36 36 46 46 137 137

galvanised steel plate16/13/11 18/16.5/15 19.5/17.5/16 25/22.5/20 32/27/23 39/33/28 58/50 72/62

* * * * * * 48/45 48/45* * * * * * * *

R-410Aø6.4 / ø12.7 ø9.5 / ø15.9 ø9,5/ø19,1 ø9,5/ø22,2

cf. note 41~, 50Hz, 220-240V / 1~, 60Hz, 220V

Cooling capacity kWHeating capacity kWNominal input  cooling W

heating WDimensions (H x W x D) mmWeight kgCasingAir flow rate (HH / H / L) m3 /minSound pressure level dB(A)Sound power level dB(A)Refrigerant typePiping connections liquid / gas mmAir filterPower supply VE

FXMQ-p/MA FXMQ40p FXMQ50p FXMQ63p FXMQ80p FXMQ100p FXMQ125p FXMQ200MA FXMQ250MA

Notes:Nominal cooling (static pressure).Nominal heating (static pressure).Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.The air filter is not standard accessory, but please mount it in the duct system at the suction side. Select its colorimetric method (gravity method) 50% or more.(1) 50Hz, 220-240V(2) 60Hz, 220V(3) Data were not available at time of publication.(4) The air filter is not standard accessory, but please mount it in the duct system at the suction side. Select its colorimetric method (gravity method) 50% or more.*Data were not available at time of publication.

FXMQ40p FXMQ50p FXMQ63p FXMQ80p FXMQ100p FXMQ125p FXMQ200MA FXMQ250MA

BRC1D52BRC4C66

BRC4C65 KDU-30L250KAF372AA56 KAF372AA80 KAF372AA160 KAFJ372L280KAF373AA56 KAF373AA80 KAF373AA160 KAFJ373L280KDDF3AA56 KDDF37AA80 KDDF37AA160 KDJ3705L280KAF371AA56 KAF371AA80 KAF371AA160 KAFJ371L280

Wired remote controlInfrared remote control cooling only

heat pumpHigh efficiency filter 65%High efficiency filter 90%Filter chamberLonglife replacement filter

FXMQ-p/MA

Accessories

speciFicAtions

NEW

38

OutdOOr units spciFicatiOns & accessOries

Page 39: VRV systems - daikin.mcquay.hudaikin.mcquay.hu/1_VRV/2_Kültéri_Egységek/RTSYQ-P_VRVIII-C... · 4. installation & maintenance Friendly design 14 outdoor unitS 19 1. VrV ... VrV

FXaQ-MaW a l l m o u n t e d u n i t

FXAQ20MA FXAQ25MA FXAQ32MA FXAQ40MA FXAQ50MA FXAQ63MAFXAQ-MA

Cooling capacity kWcapacity kWNominal input  cooling W

heating WDimensions (HxWxD) mmWeight kgColourAir flow rate (H / L) m3 /minSound pressure level (H / L) (220V) dB(A)Sound power level dB(A)Refrigerant typePiping connections liquid / gas mmAir filterPower supply VE

2.2 2.8 3.6 4.5 5.6 7.12.5 3.2 4.0 5.0 6.3 8.016 22 27 20 27 5024 27 32 20 32 60

290 x 795 x 230 290 x 1,050 x 23011 14

white7.5 / 4.5 8 / 5 9 / 5.5 12 / 9 15 / 12 19 / 1435 / 29 36 / 29 37 / 29 39 / 34 42 / 36 46 / 39

* * * * * *R-410A

ø6.4 / ø12.7 ø9.5 / ø15.9resin net washable

1~, 50Hz, 220-240V

Notes:Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB • outdoor temperature: 35°CDB • equivalent refrigerant piping: 5m (horizontal). Nominal heating capacities are based on: indoor temperature: 20°CDB • outdoor temperature: 7°CDB, 6°CWB • equivalent refrigerant piping: 5m (horizontal).Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.*Data were not available at time of publication.

FXAQ20MA FXAQ25MA FXAQ32MA FXAQ40MA FXAQ50MA FXAQ63MAFXAQ-MA

Wired remote controlInfrared remote control cooling only

heat pumpDrain pump kit

BRC1D52BRC7E619BRC7E618

K-KDU572DVE

Accessories

speciFicAtions

39

Page 40: VRV systems - daikin.mcquay.hudaikin.mcquay.hu/1_VRV/2_Kültéri_Egységek/RTSYQ-P_VRVIII-C... · 4. installation & maintenance Friendly design 14 outdoor unitS 19 1. VrV ... VrV

FXHQ-MaC e i l i n g s u s p e n d e d u n i t

FXHQ32MA FXHQ63MA FXHQ100MAFXHQ-MA

3.6 7.1 11.24.0 8.0 12.5111 115 135111 115 135

195 x 960 x 680 195 x 1,160 x 680 195 x 1,400 x 68024 28 33

Ivory white12 / 10 17.5 / 14 25 / 19.536 / 31 39 / 34 45 / 37

* * *R-410A

ø6.4 / ø12.7 ø9.5 / ø15.9Resin net with mold resistant

1~, 50Hz, 220-240V

Cooling capacity kWHeating capacity kWNominal input  cooling W

heating WDimensions (HxWxD) mmWeight kgColourAir flow rate (H / L) m3 /minSound pressure level (H / L) (220V) dB(A)Sound power level dB(A)Refrigerant typePiping connections liquid / gas mmAir filterPower supply VE

Notes:Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB • outdoor temperature: 35°CDB • equivalent refrigerant piping: 7.5m (horizontal).Nominal heating capacities are based on: indoor temperature: 20°CDB • outdoor temperature: 7°CDB, 6°CWB • equivalent refrigerant piping: 7.5m (horizontal).Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.*Data were not available at time of publication.

FXHQ32MA FXHQ63MA FXHQ100MAFXHQ-MA

BRC1D52BRC7E66BRC7E63

KDU50M60 KDU50M125 KDU50M125KAFJ501DA56 KAFJ501DA80 KAFJ501DA112KHFP5M35 KHFP5M63 KHFP5M63

Wired remote controlInfrared remote control cooling only

heat pumpDrain pump kitReplacement long life filter resin netL-type piping kit for upward direction

Accessories

speciFicAtions

40

OutdOOr units spciFicatiOns & accessOries

Page 41: VRV systems - daikin.mcquay.hudaikin.mcquay.hu/1_VRV/2_Kültéri_Egységek/RTSYQ-P_VRVIII-C... · 4. installation & maintenance Friendly design 14 outdoor unitS 19 1. VrV ... VrV

FXuQ-Ma4 - w a y b l o w c e i l i n g s u s p e n d e d u n i t

FXUQ71MA FXUQ100MA FXUQ125MAFXUQ-MA

8.0 11.2 14.09.0 12.5 14.0180 289 289160 269 269

165 x 895 x 895 230 x 895 x 895   230 x 895 x 89525 31  31

white19 / 14 29 / 21 32 / 2340 / 35 43 / 38 44 / 39

56 59 60R-410A

ø9.5 / ø15.9 ø9.5 / ø15.9 ø9.5 / ø15.9resin net with mold resistant

1~, 50Hz, 230VBEVQ71MA BEVQ100MA BEVQ125MA

Cooling capacity kWHeating capacity kWNominal input cooling W

heating WDimensions (HxWxD) mmWeight kgColourAir flow rate (H / L)Sound pressure level (H / L) (220V) dB(A)Sound power level (H) dB(A)Refrigerant typePiping connections liquid / gas mmAir filterPower supply  V1Combination with junction box

Notes:Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB • outdoor temperature: 35°CDB, 24° CWB. Nominal heating capacities are based on: indoor temperature: 20°CDB, 15° CWB • outdoor temperature: 7°CDB, 6°CWB.Capacities are net including a deduction for cooling (an addition for heating) for indoor fan motor heat.

FXUQ71MA FXUQ100MA FXUQ125MAFXUQ-MA

BRC1D52BRC7C529BRC7C528

KDBHJ49F80 KDBHJ49F140KDBTJ49F80 KDBTJ49F140KDGJ49F80 KDGJ49F140

KAFJ495F140KHFP49M63 KHFP49M140

Wired remote controlInfrared remote control cooling only

heat pumpSealing member of air discharge outletAir discharge decoration panelVertical flap kitReplacement long life filterL-type connection piping kit

JUnction BoX For connection to VrV®

BeVQ71MA BeVQ100MA BeVQ125MABeVQ-MA

100x350x225  x   3.0 3.5

galvanised steel plate1~, 50Hz, 220-240V

Dimensions H x W x D mmWeight kgCasingPower supply VE

BEVQ-MA

Accessories

speciFicAtions

41

Page 42: VRV systems - daikin.mcquay.hudaikin.mcquay.hu/1_VRV/2_Kültéri_Egységek/RTSYQ-P_VRVIII-C... · 4. installation & maintenance Friendly design 14 outdoor unitS 19 1. VrV ... VrV

FXLQ-MaF l o o r s t a n d i n g u n i t

Notes:Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB • outdoor temperature: 35°CDB • equivalent refrigerant piping: 7.5m (horizontal).Nominal heating capacities are based on: indoor temperature: 20°CDB • outdoor temperature: 7°CDB, 6°CWB • equivalent refrigerant piping: 7.5m (horizontal).Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.*Data were not available at time of publication.

2.2 2.8 3.6 4.5 5.6 7.12.5 3.2 4.0 5.0 6.3 8.049 49 90 90 110 11049 49 90 90 110 110

600 x 1,000 x 222 600 x 1,140 x 222 600 x 1,420 x 22225 30 36

ivory white7/6 7/6 8/6 11/8.5 14/11 16/12

35/32 35/32 35/32 38/33 39/34 40/35* * * * * *

R-410Aø6.4/ø12.7 ø9.5/ø15.9

resin net with mold resistant1~, 50Hz, 220-240V

Cooling capacity kWHeating capacity kWNominal input  cooling W

heating WDimensions (H x W x D) mmWeight kgColourAir flow rate (H/L) m3 /minSound pressure level (H/L) (220V) dB(A)Sound power level dB(A)Refrigerant typePiping connections liquid/gas mmAir filterPower supply VE

Accessories

speciFicAtions

FXLQ-MA

FXLQ-MA

BRC1D52, BRC2C51, BRC3A61BRC4C64BRC4C62

KAFJ361K28 KAFJ361K45 KAFJ361K71

Wired remote controlInfrared remote control cooling only

heat pumpLong life replacement filter

FXLQ20MA FXLQ25MA FXLQ32MA FXLQ40MA FXLQ50MA FXLQ63MA

FXLQ20MA FXLQ25MA FXLQ32MA FXLQ40MA FXLQ50MA FXLQ63MA

42

OutdOOr units spciFicatiOns & accessOries

Page 43: VRV systems - daikin.mcquay.hudaikin.mcquay.hu/1_VRV/2_Kültéri_Egységek/RTSYQ-P_VRVIII-C... · 4. installation & maintenance Friendly design 14 outdoor unitS 19 1. VrV ... VrV

FXnQ-MaC o n c e a l e d f l o o r s t a n d i n g u n i t

Notes:Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB • outdoor temperature: 35°CDB • equivalent refrigerant piping: 8m • level difference: Om.Nominal heating capacities are based on: indoor temperature: 20°CDB • outdoor temperature: 7°CDB, 6°CWB • equivalent refrigerant piping: 8m • level difference: Om.Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.The sound pressure values are mentioned for a unit installed with rear suction.

BRC1D52, BRC2C51, BRC3A61BRC4C64BRC4C62

KAFJ361K28 KAFJ361K45 KAFJ361K71

Wired remote controlInfrared remote control cooling only

heat pumpReplacement long life filter

FXnQ20MA FXnQ25MA FXnQ32MA FXnQ40MA FXnQ50MA FXnQ63MAFXnQ-MA

Cooling capacity kWHeating capacity kWNominal input  cooling W

heating WDimensions (HxWxD) mmWeight kgCasingAir flow rate (H/L) m3/minSound pressure level (H/L)(220V) dB(A)Sound power level dB(A)Refrigerant typePiping connections liquid/gas mmAir filterPower supply VE

2.2 2.8 3.6 4.5 5.6 7.12.5 3.2 4.0 5.0 6.3 8.049 49 90 90 110 11049 49 90 90 110 110

600 x 1,00 x 222 600 x 1,140 x 222 600 x 1,420 x 22225 30 36

Ivory white7/6 7/6 8/6 11/8.5 14/11 16/12

35/32 35/32 35/32 38/33 39/34 40/35* * * * * *

R-410Aø6.4/ø12.7 ø9.5/ø15.9

Resin net with mold resistant1~, 50Hz, 220-240V 

Accessories

speciFicAtions

FXnQ20MA FXnQ25MA FXnQ32MA FXnQ40MA FXnQ50MA FXnQ63MAFXnQ-MA

43

Page 44: VRV systems - daikin.mcquay.hudaikin.mcquay.hu/1_VRV/2_Kültéri_Egységek/RTSYQ-P_VRVIII-C... · 4. installation & maintenance Friendly design 14 outdoor unitS 19 1. VrV ... VrV

VentiLatiOn

1. HrV-Heat recLaiM VentiLatiOn

1. VAM-FA8

The Daikin heat recovery ventilation system modulates the temperature and humidity of incoming fresh air to match indoor conditions. A balance is thus achieved between in-door and outdoor ambients, enabling the cooling or heating load placed on the air conditioning system to be reduced significantly. HRV units can be controlled individually or in-tegral with the air conditioning system Daikin VRV® or Sky Air series)

9 models to choose from ›Compact, energy saving ventilation ›Specially developed heat exchange element with HEP ›(High Efficiency Paper)Easy integration into the VRV › ® systemConnectable to current Daikin control systems: ›

Total heat exchanged foul air

Clean outdoor air

Total heat exchanged clean airFoul indoor air

(1) Sound pressure level is measured in heat exchange mode.

VAM150FA VAM250FA VAM350FA VAM500FA VAM650FA VAM800FA VAM1000FA VAM1500FA VAM2000FA150 250 350 500 650 800 1,000 1,500 2,000

27/28.5 28/29 32/34 33/34.5 34.5/35.5 36/37 36/37 39.5/41.5 40/42.569 64 98 98 93 137 157 137 13774 72 75 74 74 74 75 75 7558 58 61 58 58 60 61 61 6164 64 65 62 63 65 66 66 66269 269 285 285 348 348 348 710 710760 760 812 812 988 988 988 1,498 1,498509 509 800 800 852 852 1,140 852 1,14024 24 33 33 48 48 61 132 158

Ø 100 Ø 150 Ø 150 Ø 200 Ø 200 Ø 250 Ø 250 Ø 350 Ø 3501~, 50Hz, 220-240V

VAM-FA

VENTILATIONAir flow rate m3/hSound pressure level (max.) (1) dBAExternal static pressure (max.) PaTemperature exchange efficiency %Enthalpy exchange efficiency

 heating %cooling %

Dimensions H mmW mmD mm

Weight kgDuct diameter mmPower supply VE

44

Page 45: VRV systems - daikin.mcquay.hudaikin.mcquay.hu/1_VRV/2_Kültéri_Egységek/RTSYQ-P_VRVIII-C... · 4. installation & maintenance Friendly design 14 outdoor unitS 19 1. VrV ... VrV

VKM50GAM VKM80GAM VKM100GAM4.71 7.46 9.125.58 8.79 10.69

500 - 500 - 440 750 - 750 - 640 950 - 950 - 82037 - 35.5 - 32 38.5 - 36 - 33 39 - 37 - 3438 - 36 - 34 40 - 37.5 - 35.5 40 - 38 - 35.5

160 - 120 - 100 140 - 90 - 70 110 - 70 - 6076 - 76 - 77.5  78 - 78 - 79 74 - 74 - 76.564 - 64 - 67 66 - 66 - 68 62 - 62 - 6667 - 67- 69 71 - 71 - 73 65 - 65 -69

natural evaporating humdifier2.70 4.00 5.40387 387 387

1,764 1,764 1,764832 1,214 1,214102 120 125

1~, 220-240V, 50Hz

VentiLAtion, DX coiL & HUMiDiFierFresh air conditioning load cooling kW

heating kWAir flow rate ultra high - high - low m3/hSound pressure level - 220V ultra high - high - low dBASound pressure level - 240V ultra high - high - low dBAStatic pressure ultra high - high - low PaTemperature exchange efficiency ultra high - high - low %Enthalpy exchange efficiency - cooling ultra high - high - low %Enthalpy exchange efficiency - heating ultra high - high - low %Humidifier typeHumidification capacity kg/hDimensions height mm

width mmdepth mm

Weight kgPower supply V1

VKM-GAM

VKM-GA

VKM50GA VKM80GA VKM100GA4.71 7.46 9.125.58 8.79 10.69

500 - 500 - 440 750 - 750 - 640 950 - 950 - 82038 - 36 - 33.5 40 - 37.5 - 34.5 40 - 38 - 3539 - 37 - 35.5 41.5 - 39 - 37 41 - 39 - 36.5

180 - 150 - 110 170 - 120 - 80 150 - 100 - 7076 - 76 - 77.5  78 - 78 - 79 74 - 74 - 76.564 - 64 - 67 66 - 66 - 68 62 - 62 - 6667 - 67- 69 71 - 71 - 73 65 - 65 -69

387 387 3871,764 1,764 1,764832 1,214 1,214 96 109 114

1~, 220-240V, 50Hz

VentiLAtion & DX coiLFresh air conditioning load cooling kW

heating kWAir flow rate ultra high - high - low m3/hSound pressure level - 220V ultra high - high - low dBASound pressure level - 240V ultra high - high - low dBAStatic pressure ultra high - high - low PaTemperature exchange efficiency ultra high - high - low %Enthalpy exchange efficiency - cooling ultra high - high - low %Enthalpy exchange efficiency - heating ultra high - high - low %Dimensions height mm

width mmdepth mm

Weight kgPower supply V1

2. VKM-GA / VKM-GAM

Heat purge (economiser): heat accumulated indoors ›is discharged at night Integration of humidification and air conditioning into ›HRV unit Increased static pressure thanks to improved fan ›performance Individual control via HRV remote control › Connectable to current Daikin control systems: ›

45

Page 46: VRV systems - daikin.mcquay.hudaikin.mcquay.hu/1_VRV/2_Kültéri_Egységek/RTSYQ-P_VRVIII-C... · 4. installation & maintenance Friendly design 14 outdoor unitS 19 1. VrV ... VrV

2. FXMQ-MFV1 - OutdOOr air prOcessing unit

cOMbined FresH air treatMent and air cOnditiOning Via a singLe systeM.

Both fresh air treatment and air conditioning can be achieved successfully in a single system via heat pump technology without the usual design problems associated with balancing air supply and discharge. Air conditioning fan coil units and an outdoor air treatment unit can be connected to the same refrigerant line, resulting in enhanced design flexibility and a significant reduction in total system costs.

100% fresh air intake possible ›Leaves maximum floor and wall space for furniture, decorations ›and fittingsOperation range: -5°C to 43°C ›225 Pa external static pressure allows extensive ductwork runs and ›flexible application: ideal for use in large areasDrain pump kit available as accessory ›

FXMQ-MFV1INdOOr UNITs FXMQ125MFV1 FXMQ200MFV1 FXMQ250MFV1

Capacitycooling kw 14.0 22.4 28.00heating kw 8.9 13.9 17.40

Power Inputcooling kw 0.359 0.548 0.638heating kw 0.359 0.548 0.638

Dimensions HxWxD mm 470x744x1,100 470x1380x1,100Weight kg 86 123

Air Flow Ratecooling medium m3/min 18.0 28.0 35.0heating medium m3/min 18.0 28.0 35.0

Refrigerant -Power Supply 220-240V/50HzPiping Connections liquid (od)/gas/drain mm 9.5 / 15.9 / PS1B 9.5 / 19.1 / PS1B 9.5 / 22.2 / PS1B

46

VentiLatiOn

Page 47: VRV systems - daikin.mcquay.hudaikin.mcquay.hu/1_VRV/2_Kültéri_Egységek/RTSYQ-P_VRVIII-C... · 4. installation & maintenance Friendly design 14 outdoor unitS 19 1. VrV ... VrV

3. VrV®+eXV-Kit - VrV® air HandLing appLicatiOns

Cooling onlyrXQ-P(A) 5 8 10 12 14 16 18Capacity range HP 5 8 10 12 14 16 18Capacity cooling kw 14.0 22.4 28.0 33.5 40.0 45.0 49.0Power input (Nominal) cooling kw 3.52 5.56 7.42 9.62 12.4 14.2 16.2Dimensions HxWxD mm 1,680x635x765 1,680x930x765 1,680x1,240x765Weight kg 157 185 238 315 323

Sound Levelsound power cooling dBA 72 78 80 83sound pressure cooling dBA 54 57 58 60 63

Air Flow Rate (nominal at 230V) cooling m³/min 95 171 185 196 233 239Operation Range cooling min~max °CDB -5.0~43.0Refrigerant R-410APower Supply 3N~/400V/50HzMax n° of indoor units to be connected 8 13 16 19 23 26 29Piping connections liquid (OD)/gas mm 9.5 / 15.9 9.5 / 19.1 9.5 / 22.2 12.7 / 22.2 12.7 / 28.6 15.9 / 28.6

Combination table

Outdoor unit

CONTrOL bOX EXPANsION VALVE kIT

CONTrOL z CLAss 50 CLAss 63 CLAss 80 CLAss 100 CLAss 125 CLAss 140 CLAss 200 CLAss 250

EkEXMCb EkEXV50 EkEXV63 EkEXV80 EkEXv100 EkEXV125 EkEXV140 EkEXV200 EkEXV250

3ph

RXQ5P x x x x x x x x xRXQ8P x x x x x x x x xRXQ10P x x x x x x x x xRXQ12P x x x x x x x x xRXQ14PA x x x x x x x x xRXQ16PA x x x x x x x x xRXQ18PA x x x x x x x x x

A new range of R-410A inverter condensing units ›for multi application with air handling units.Inverter controlled units ›Large capacity range (from 5 to 18HP) ›Cooling only ›R-410A ›

Control z: control of air temperature (suction ›temperature, room temperature) via Daikin control (no DDC controller needed)Large range of expansion valve kits available ›BRC1D52 is used to set the set point ›temperature (connected to the EKEXMCB).

EXV-kit

EKEXMCB

Air handling unit

gas pipe

liquid pipe

F1, F2 communication

47

Page 48: VRV systems - daikin.mcquay.hudaikin.mcquay.hu/1_VRV/2_Kültéri_Egységek/RTSYQ-P_VRVIII-C... · 4. installation & maintenance Friendly design 14 outdoor unitS 19 1. VrV ... VrV

1. VrV® Xpress

Daikin has developed a new user friendly, software tool that allows rapid VRV® selection and provides a professional result in the 7 following steps:

Select indoor units1. Connect outdoor units to indoor units2. Automatic receipt of piping diagram with joints3. Automatic receipt of wiring diagram4. Connect appropriate centralised control systems5. Visualise result in Microsoft Word, Microsoft Excel and AutoCAD6. ®

Save project7.

Using VRV® Xpress enables VRV® selection to be achieved in a simple, complete and professional manner.

Windows95®, Windows98®, WindowsNT®, Windows2000®, WindowsXP® and WindowsVista® are registered trademarks of Microsoft corporation.

pOwerFuL seLectiOn prOgraMMes

48

Page 49: VRV systems - daikin.mcquay.hudaikin.mcquay.hu/1_VRV/2_Kültéri_Egységek/RTSYQ-P_VRVIII-C... · 4. installation & maintenance Friendly design 14 outdoor unitS 19 1. VrV ... VrV

2. VrV® prO

FeAtUres:

The VRV® Pro selection programme offers 3 separate modes to accommodate different design formats according to customer requirements. Multi languages are possible.

expert mode:1. once the cooling and heating loads in the different rooms have been calculated, the software will select the most appropriate system plus an estimate of the power consumption.Quick mode: 2. based on calculated system loads, the software will select the most appropriate system.Drawing mode:3. selecting the indoor and outdoor units from a list enables the user to design a system in no time at all.

A simple to use, Daikin computerised selection programme, designed for use with Windows 95®, Windows 98®, WindowsNT®, Windows 2000®, Windows XP® and WindowsVista® systems, enables consulting engineers, design and build contractors, property developers and architects etc. to plan a Daikin air conditioning project on a step by step basis, complete with detailed drawings, bills of quantities and costs.The programme thus enables VRV® air conditioning systems to be engineered precisely and economically (without over-sizing units), thereby ensuring optimum operating cycles and maximum energy efficiency.

Windows95®, Windows98®, WindowsNT®, Windows2000®, WindowsXP® and WindowsVista® are registered trademarks of Microsoft corporation.

49

Page 50: VRV systems - daikin.mcquay.hudaikin.mcquay.hu/1_VRV/2_Kültéri_Egységek/RTSYQ-P_VRVIII-C... · 4. installation & maintenance Friendly design 14 outdoor unitS 19 1. VrV ... VrV

brc4*brc7*

brc2c51

brc3a61

user FriendLy cOntrOL systeMs

1. indiViduaL cOntrOL systeMs

inFrAreD reMote controL

operation buttons: ON / OFF, timer mode start / stop, timer mode on / off, programme time, temperature setting, air flow direction (FXHQ, FXFQ, FXCQ and FXAQ models only), operating mode, fan speed control, filter sign reset, inspection / test indication

Display: Operating mode, battery change, set temperature, air flow direction (FXHQ, FXFQ, FXCQ and FXAQ models only), programmed time, inspection / test operation, fan speed

siMpLiFieD reMote controL

Simple, compact and easy to operate unit, suitable for use in hotel bed-rooms

operation buttons: ON / OFF, operating mode selection, fan speed control, temperature setting

Display: Cool / heat changeover control, Heat Recovery Ventilation (HRV) in operation, set temperature, operating mode, centralised control indication, fan speed, defrost / hot start, malfunction adjustment, operating mode selection, fan speed control, filter sign reset, inspection test / operation

siMpLiFieD BUiLt-in reMote controL For HoteL AppLicAtions

Compact, user friendly unit, ideal for use in hotel bedrooms

operation buttons: ON / OFF, fan speed control, temperature setting

Display: Heat Recovery Ventilation (HRV) in operation, set temperature, operating mode, centralised control indication, fan speed, defrost / hot start, malfunction

50

Page 51: VRV systems - daikin.mcquay.hudaikin.mcquay.hu/1_VRV/2_Kültéri_Egységek/RTSYQ-P_VRVIII-C... · 4. installation & maintenance Friendly design 14 outdoor unitS 19 1. VrV ... VrV

brc1d52

WireD reMote controL

Limit operation (min/max): room temperature is controlled within ›adjustable upper and lower limits. Limit operation can be activated manually or by schedule timerReal time clock: indicates real time and day ›Schedule timer: ›- It is possible to programme a weekly schedule timer- It is possible to programme the remote control for each day of

the week. Five day actions can be set as follows:

· Set point: unit is switched ON and normal operation is maintained

· OFF: unit is switched OFF· Limits: unit is switched ON and min / max control (cf. limit

operation for more details)Home leave (frost protection): during occupants’ absence, the indoor ›temperature can be maintained at a certain level. This function can also switch the unit ON/OFFDifferent levels of disabled buttons can be selected as follows: ›- Level 1:all buttons are accessible- Level 2: all buttons are disabled except for: ON / OFF, set temper-

ature up / down, fan speed, cooling / heating mode, enable / dis-able schedule timer, air flow direction adjustment button

- Level 3: all buttons are disabled except for: ON / OFF, set temperature up / down, fan speed

User friendly HRV function, thanks to the introduction of a button for ›ventilation mode and fan speedConstantly monitoring of the system for malfunctions in a total of 80 ›componentsImmediate display of fault location and condition ›Reduction of maintenance time and costs ›

operation buttons: ON / OFF, timer mode start / stop, timer on / off, programmed time, temperature setting, air flow direction adjustment, operating mode selection, fan speed control, filter sign reset, inspection test / operation

Display: Operating mode, Heat Recovery Ventilation (HRV) in operation, cool / heat changeover control, centralised control indication, group control indication, set temperature, air flow direction, programmed time, inspection / test operation, fan speed, clean air filter, defrost / hot start, malfunction

51

Page 52: VRV systems - daikin.mcquay.hudaikin.mcquay.hu/1_VRV/2_Kültéri_Egységek/RTSYQ-P_VRVIII-C... · 4. installation & maintenance Friendly design 14 outdoor unitS 19 1. VrV ... VrV

dcs302c51

dcs301b51

dst301b51

UniFieD on/oFF controL

Providing simultaneous and individual control of 16 groups of indoor unitsA maximum of 16 groups (128 indoor units) can be controlled ›2 remote controls in separate locations can be used ›Operating status indication (normal operation, alarm) ›Centralised control indication ›Maximum wiring length of 1,000m (total: 2,000m) ›

2. centraLised cOntrOL systeMs

centrALiseD reMote controL

Providing individual control of 64 groups (zones) of indoor unitsA maximum of 64 groups (128 indoor units, max. 10 outdoor units) ›can be controlledA maximum of 128 groups (128 indoor units, max. 10 outdoor units) ›can be controlled via 2 centralised remote controls in separate locationsZone control ›Group control (up and down buttons are added for group selection) ›Control of HRV air flow direction and air flow rate ›Expanded timer function ›Malfunction code display ›Maximum wiring length of 1,000m (total: 2,000m) ›

scHeDULe tiMer

Enabling 64 groups to be programmedA maximum of 128 indoor units can be controlled ›8 types of weekly schedule ›A maximum of 48 hours back-up power supply ›Maximum wiring length of 1,000m (total: 2,000m) ›

52

user FriendLy cOntrOL systeMs

Page 53: VRV systems - daikin.mcquay.hudaikin.mcquay.hu/1_VRV/2_Kültéri_Egységek/RTSYQ-P_VRVIII-C... · 4. installation & maintenance Friendly design 14 outdoor unitS 19 1. VrV ... VrV

3. netwOrK sOLutiOns

The ideal solution for control and management up to 2,000 indoor units

AppLicAtion AreAA small commercial area of less than ›40 indoor units.Critical applications for centralized monitoring. ›

systeM LAyoUtAllows monitoring and control of up to up to 50 ›stores or sites and 2,000 indoor units with just one modem and phone line.Automates daily air conditioning operation in order ›to free users from the hassle of air conditioning operation / management.The daily schedule setting allows automatic ›operation afterward.Automates alarm (report messages) for any ›malfunctions / errors. Immediate report of any indoor unit breakdown to the servicing company.Automatic report of breakdown / malfunction ›information.Minimizes the inconvenience of not having air ›conditioning via rapid messages

FUnctionsSchedule setup (Daily schedule) ›- Start / stop

A / C malfunction report ›- Send message to monitoring system

Manual operation ›- Start / Stop, set temperature, operation mode,

fan speedStatus monitoring - Start / Stop, set temperature, - Operation mode, room temperature, operation

time, error code

Modem

Public phone line

PC for monitoring

Malfunction

DS-NETadapter

Max. of 10 DS-NET adapters

RS4

85R

S232

C

P1 - P2 F1 - F2

P1 - P2 F1 - F2

Modem

53

Page 54: VRV systems - daikin.mcquay.hudaikin.mcquay.hu/1_VRV/2_Kültéri_Egységek/RTSYQ-P_VRVIII-C... · 4. installation & maintenance Friendly design 14 outdoor unitS 19 1. VrV ... VrV

Allows detailed and easy monitoring and operation of VRV® systems (max. 2 x 64 control groups)

LAnGUAGesEnglish, French, German, Italian, Spanish ›

systeM LAyoUtUp to 2 x 64 indoor units can be controlled ›Onboard Ethernet port (web browser & e-mail) ›Digital i / o contacts (option) ›Touch panel (full colour LCD via icon display) ›

MAnAGeMentWeb application & internet compatibility ›- Monitoring & control according to user- Remote monitoring & control of more than one

building- Remote monitoring & control of more than one

building via internetPower Proportional Distribution (option) ›PPD data is available on the internet ›Easy management of electricity consumption ›Enhanced history function ›

controLIndividual control (set point, start / stop, fan speed) (max. ›2 x 64 indoor units / groups)Schedule control (8 schedules, 17 patterns) ›Flexible grouping in zones ›Yearly schedule ›Fire emergency stop control ›Interlocking control ›Increased HRV monitoring and control function ›Automatic cooling / heating changeover ›Quick selection and full control ›Simple navigation ›Heating optimization ›Temperature limit ›Password security: 3 levels ›(general, administration & service)

CSV output of PPD (option) result

Public line

Air Conditioning Network Service System

Onboard Ethernet

port

PCMCIAflash

memory

Onboard

modem

third party controller (domotics, BMS, etc.)

Ethernet

Links to the wattmeter when using the PPD (option) function

Remote monitoring / controlvia internet, e-mailPPD data is available on internet

Pi-port

Malfunction

54

user FriendLy cOntrOL systeMs

Page 55: VRV systems - daikin.mcquay.hudaikin.mcquay.hu/1_VRV/2_Kültéri_Egységek/RTSYQ-P_VRVIII-C... · 4. installation & maintenance Friendly design 14 outdoor unitS 19 1. VrV ... VrV

[iPU]

MonitorinGVisualisation via Graphical User Interface (GUI) ›Icon colour display change function ›Indoor units operation mode ›Error messages via e-mail & mobile phone (option) ›Indication filter replacement ›Multi PC ›

cost perForMAnceLabour saving ›Easy installation ›Compact design: limited installation space ›Overall energy saving ›

open interFAceCommunication to any third party controller ›(domotics, BMS, etc.) is possible via open interface.

connectABLe toVRV › ®

HRV ›Sky Air (via interface adapter) ›Split (via interface adapter) ›

Fire alarm

Forced OFF contact input

DIII-NET

Indoor units

Controls drain pump, lighting etc.

Monitoring of room enter/exit sign

HRV

DIO unit

RS-232C

DIII-NET PLUS adapter

DIII-NET Allows monitoring/control of up to 64 units (groups)

HRVIndoor unit

DI unit

55

Page 56: VRV systems - daikin.mcquay.hudaikin.mcquay.hu/1_VRV/2_Kültéri_Egységek/RTSYQ-P_VRVIII-C... · 4. installation & maintenance Friendly design 14 outdoor unitS 19 1. VrV ... VrV

~

~

The ideal solution for control and management of maximum 1,024 VRV® indoor units

systeM LAyoUtUp to 1,024 indoor units can be controlled ›(by 4 iPUs)Ethernet TCPIP / 10 base / T communication ›Integrated digital contacts on the Intelligent ›Processing Unit (iPU)- 19 general input ports- 2 digital outputsStand alone operation of the iPU ›for minimum 48 hoursCompatible with UPS shutdown software ›

MAnAGeMentWeb access function (option) ›Power Proportional Distribution ›Operational history management (start/stop, ›malfunction, operation hours) Generation of reports (graphics & tables) ›(daily, weekly, monthly)Peak load shedding ›Advanced tenant management ›Sliding temperature ›Eco mode (option) ›

controLIndividual control (setpoint, start / stop, fan speed) ›(max. 1,024 indoor units)Group control (100 groups) ›Schedule control (128 programs) › Fire emergency stop control (32 programs) ›Interlocking control ›Setpoint limitation › Automatic cooling heating changeover ›Power failure / release control ›Temperature limit (automatic start) ›Timer extension ›

MonitorinGVisualisation via a Graphical User Interface (GUI) ›featuring free layoutOperation mode of indoor & outdoor units ›Fault indication ›Indication filter replacement ›Setpoint indication ›Operation time monitoring ›Multi PC ›On-line help ›

Web Access

Sub PC

ETH

ERN

ET

Intranet/Internet Web Access

Malfunction report by E-Mail

Dio unitPower supply facility

Daikin Central Air Conditioning System

VRV® SystemLocal monitoring

& control

DMS502A51 BACnet Gateway(monitoring only)

Air Conditioning Network Service System (Optional Maintenance Service)

Electricity Measurement

(Via Internet)

Ai unit

HRV

DAM602B51/52

Fire alarm

DIII-NET

DIII-NET

DIII-NET

DIII-N

ET

56

user FriendLy cOntrOL systeMs

Page 57: VRV systems - daikin.mcquay.hudaikin.mcquay.hu/1_VRV/2_Kültéri_Egységek/RTSYQ-P_VRVIII-C... · 4. installation & maintenance Friendly design 14 outdoor unitS 19 1. VrV ... VrV

Lonworks Networks Compatible Gateway

Interface for connection to LonWorks › ® networksCommunication via Lon protocol ›(twisted pair wire)64 units connectable per DMS-IF ›Unlimited site size ›Quick and easy installation ›

Integrated control system connecting VRV® system with BMS system.

PPD data is available on BMS-system ›Interface for BMS system ›Communication via BACnet protocol ›(connection via Ethernet)256 units connectable per BACnet gateway ›

Unlimited site size ›Easy and fast installation ›

BUILDING CONTROL NETWORK

LON BMS

Fire alarm System

Security

adapter

LonTalk

LonTalk

LonPoint LonPoint

ETH

ERN

ET (T

CP/

IP)

adapter

DMS504B51

Local Control

DIII- NET

VRV® Outdoor unit

HRV

Remote Control

DAIKIN A / C INFRASTRUCTURE

DAIKIN A / C INFRASTRUCTURE

BMS

BAC

NET

/ ET

HER

NET

Fire alarm Security

DMS502A51

Local ControlDAM602B51 / 52 (Intelligent Manager)

Control and monitoring

DIII- NET

VRV® Outdoor unit

HRV

Remote Control

Power supply facility

Pump Lighting Elevator

BUILDING CONTROL NETWORK

57

Page 58: VRV systems - daikin.mcquay.hudaikin.mcquay.hu/1_VRV/2_Kültéri_Egységek/RTSYQ-P_VRVIII-C... · 4. installation & maintenance Friendly design 14 outdoor unitS 19 1. VrV ... VrV

4. accessOries

inDiViDUAL controL systeMs

BRC1D52BRC7F533 BRC7E531 BRC7C67 BRC4C63 BRC4C64 BRC4C64 BRC4C64 BRC4C66 BRC7C529 BRC7E66  BRC7E619 BRC4C64 BRC4C64BRC7F532 BRC7E530 BRC7C62 BRC4C61 BRC4C62 BRC4C62 BRC4C62 BRC4C65 BRC7C528 BRC7E63  BRC7E618 BRC4C62 BRC4C62

- - - - BRC2C51 BRC2C51 BRC2C51 BRC2C51 - - - BRC2C51 BRC2C51- - - - BRC3A61 BRC3A61 BRC3A61 BRC3A61 - - - BRC3A61 BRC3A61

Wired remote controlInfrared remote control cooling only

heat pumpSimplified remote controlSimplified remote control for hotel use

centrALiseD controL systeMs

DCS302C51DCS301B51DST301B51

Centralised remote controlUnified ON/OFF controlSchedule timer

Description

otHers

Description

Wiring adapterWiring adapter (hour meter)Wiring adapter for electrical appendices (1)Wiring adapter for electrical appendices (2)Remote sensorInstallation box for adapter PCBElectrical box with earth terminal (3 blocks)Electrical box with earth terminal (2 blocks)Noise filter (for electromagnetic interface only)External control adapterInterface adapter for Sky Air seriesConnector for forced on/forced off

- KRP1B57*1  - KRP1B61 KRP1B61 KRP1B56  - KRP1B61 KRP4A53 KRP1B3  - KRP1B61 KRP1B61EKRP1C11*1 - EKRP1B2  - EKRP1B2*2  - EKRP1B2  -  -  -  -  -KRP2A526*1 KRP2A526*1 KRP2A516*1 KRP2A61 KRP2A516 KRP2A53 KRP2A516 KRP2A61 KRP2A62* KRP2A51 KRP2A51 KRP2A51KRP4AA53*1 KRP4A536*1 KRP4A516*1 KRP4A51 KRP4A516 KRP4A54 KRP4A516 KRP4A51 KRP4A52* KRP4A51 KRP4A51 KRP4A51KRCS01-4 KRCS01-1KRP1H98 KRP1BA101 KRP1B96*3/4  -  - KRP1BA101  - KRP1B97 KRP1C93*3 KRP4A93*3/4  -  -

- KJB311AKJB212AA KJB212A

- KEK26-1A- DTA104A52 DTA104A51*1 DTA104A61 DTA104A51 DTA104A53 DTA104A51 DTA104A61 DTA104A62 DTA104A51 DTA104A61 DTA104A61-  -  -  -  -  -  -  - DTA102A52  -  -  -  --  -  -  -  -  -  -  - EKRORO  -  -  -  -

Notes:*1: Installation box is required *2: Fixing box is KRP1A90 *3: Up to 2 adapters can be fixed per installation box *4: Only 1 installation box can be installed per indoor unit

DS-net adapterSoftware

DTA113B51 4 units can be connected per adapter, 40 units when 10 adapters are connectedDPC001B1-B51 Monitoring panel software

DCS601C51 2x64 units can be connectedDCS002C51 Power Proportional Distribution (PPD) softwareDCS004A51 E-mail / Web softwareDCS601A52 DIII NET-Plus adapterKJB411A For wall mounted installation1264009 Spare part n° of Touch-Pen for Intelligent Touch Controller

KRP928A2S For connection to Split unitsDTA102A52 For connection to R-22 / R-407C Sky Air unitsDTA112B51 For connection to R-410A Sky Air unitsDEC101A51 Input contacts: 16 pointsDEC102A51 Input contacts: 8 points; output contacts: 4 points

Intelligent Touch ControllerSoftware

HardwareInstallation boxTouch-PenInterface adapters

Digital inputDigital input/output

Description

Description

reFerence coMMents

reFerence coMMents

Description FXFQ FXZQ FXcQ FXKQ FXDQ FXDQ-n FXsQ FXMQ FXUQ FXHQ FXAQ FXLQ FXnQ

FXFQ FXZQ FXcQ FXKQ FXDQ FXDQ-n FXsQ FXMQ FXUQ FXHQ FXAQ FXLQ FXnQ

FXFQ FXZQ FXcQ FXKQ FXDQ FXDQ-n FXsQ FXMQ FXUQ FXHQ FXAQ FXLQ FXnQ

58

user FriendLy cOntrOL systeMs

Page 59: VRV systems - daikin.mcquay.hudaikin.mcquay.hu/1_VRV/2_Kültéri_Egységek/RTSYQ-P_VRVIII-C... · 4. installation & maintenance Friendly design 14 outdoor unitS 19 1. VrV ... VrV

DAM602B51 256 indoor units per IPUDAM602B52 128 indoor units per IPU

IM3.XX Up to 1,024 indoor unitsKRP928A2S For connection to Split unitsDTA102A52 For connection to R-407C/R-22 Sky Air unitsDTA112B51 For connection to R-410A Sky Air units 

DAM101A51 Outdoor temperature sensorDEC10151* Input contacts: 16 pointsDEC10251* Input contacts: 8 points; output contacts: 4 points

DAM002A51DAM003A51DAM004A51

Intelligent Processing unit

SoftwareInterface adapters

DIII AiDigital inputDigital input / outputPower Proportional DistributionECO ModeWeb Acces Function

Description reFerence coMMents

DMS502B51 64 units per Gateway DAM411B51 Extension of 3 x DIII lines (3 x 64) indoor unitsDAM412B51 For forced shutdownKRP928A2S For connection to Split unitsDTA102A52 For connection to R-407C/R-22 Sky Air unitsDTA112B51 For connection to R-410A Sky Air units

BACnet GatewayDIII board Digital input/outputInterface adapters

Description reFerence coMMents

BMs: BUiLDinG MAnAGeMent systeM

Conta

ct / a

nalog

 sign

al

Parallel interface - Basic unitTemperature measurement unitsTemperature setting unitsUnification adapter for computerised control Wiring adapter for electrical appendices (1)

Wiring adapter for electrical appendices (2)External control adapter for outdoor unit

DIII-net expander adapter

Mounting kit

DPF201A51 enables ON/OFF command, operation and display of malfunction can be used in combination with up to 4 units.DPF201A52 enables temperature measurement output for 4 groups; 0~5VDC.»DPF201A53 enables temperature setting input for 16 groups; 0~5VDC.»DCS302A52 used for combining of air conditioning control computer and central remote controller (ON/OFF, display)KRP2A51 simultaneously controls air conditioning control computer and up to 64 groups of indoor units. KRP2A52

KRP4A51-53 to control the group of indoor units collectively, which are connected by the transmission wiring of remote controller.DTA104A51

cooling/heating mode change over, demand control and low noise control are available between the plural outdoor units.DTA104A52DTA109A51 a maximum of 10 outdoors or 128 indoors can be connected to 1 DTA109A51

a maximum of 8 DTA109A51 can be connected to DIII-netKRP4A92 for easy installation of the DTA109A51

Description reFerence coMMents

DMS504B51 Up to 64 units can be connected per DMS-IF KRP928A2S For connection to Split unitsDTA102A52 For connection to R-407C/R-22 Sky Air unitsDTA112B51 For connection to R-410A Sky Air units

LonWorks® networks compatible GatewayInterface adapters

Description reFerence coMMents

59

Page 60: VRV systems - daikin.mcquay.hudaikin.mcquay.hu/1_VRV/2_Kültéri_Egységek/RTSYQ-P_VRVIII-C... · 4. installation & maintenance Friendly design 14 outdoor unitS 19 1. VrV ... VrV

EPC

EN08

-205

• X

XX

X •

05/

08 •

Cop

yrig

ht ©

Dai

kin

The

pres

ent p

ublic

atio

n su

pers

edes

EPC

EN07

-200

.Pr

inte

d on

non

-chl

orin

ated

pap

er. P

repa

red

by L

a M

ovid

a, B

elgi

um

Resp

onsi

ble

Edito

r: D

aiki

n Eu

rope

N.V

., Za

ndvo

orde

stra

at 3

00, B

-840

0 O

oste

nde

FSC

The present leaflet is drawn up by way of information only and does not constitute an offer binding upon Daikin Europe N.V.. Daikin Europe N.V. has compiled the content of this leaflet to the best of its knowledge. No express or implied warranty is given for the completeness, accuracy, reliability or fitness for particular purpose of its content and the products and services presented therein. Specifications are subject to change without prior notice. Daikin Europe N.V. explicitly rejects any liability for any direct or indirect damage, in the broadest sense, arising from or related to the use and/or interpretation of this leaflet. All content is copyrighted by Daikin Europe N.V.

Daikin Europe N.V. is approved by LRQA for its Quality Management System in accordance with the ISO9001 standard. ISO9001 pertains to quality assurance regarding design, development, manufacturing as well as to services related to the product.

ISO14001 assures an effective environmental management system in order to help protect human health and the environment from the potential impact of our activities, products and services and to assist in maintaining and improving the quality of the environment.

Daikin units comply with the European regulations that guarantee the safety of the product.

VRV® products are not within the scope of the Eurovent certification programme.

Daikin’s unique position as a manufacturer of air conditioning equipment, compressors and refrigerants has led to its close involvement in environmental issues. For several years Daikin has had the intention to become a leader in the provision of products that have limited impact on the environment. This challenge demands the eco design and development of a wide range of products and an energy management system, resulting in energy conservation and a reduction of waste.