Voltage Control of Microgrid Systems Connected to Power Network System in Fault Condition(1)

download Voltage Control of Microgrid Systems Connected to Power Network System in Fault Condition(1)

of 11

description

microgrid

Transcript of Voltage Control of Microgrid Systems Connected to Power Network System in Fault Condition(1)

  • International Electrical Engineering Journal (IEEJ) Vol. 4 (2013) No. 3, pp. 1087-1097 ISSN 2078-2365 http://www.ieejournal.com/

    1087

    Mehdi and Majid Voltage Control of Microgrid Systems Connected to Power Network System in Fault Condition

    Voltage Control of Microgrid Systems

    Connected to Power Network System in Fault

    Condition

    Abstract: In today's world, according as interest about renewable

    energy source rises, many researches are progressing about

    energy source development and power distribution system

    configuration for improving renewable energy source's

    efficiency. The microgrid is small power system that consists

    of several consumers' loads and small size Distributed

    resources and accomplishes one independent system. It is

    operated by interconnecting with power distribution system

    and could be islanding operation according to situation.

    Therefore, the control of microgrid makes microgrid can be

    connected to the power distribution system without

    equipment correction of power distribution system, and can

    compensate voltage quality and must satisfy dynamic

    request of loads as active and reactive power are controlled

    independently. Specially, when consumer's load includes

    sensitive loads, consumer is going to expect very high

    reliability from microgrid. In this paper, we studied about

    effects that get to power distribution system relationship

    fault condition this microgird using EMTP modeling and

    simulation. And we proposed microsource's control

    algorithm and simulated to improve voltage quality that is

    supplied in microgird interior load in fault condition of

    power distribution system. This shows that microgird can

    provide local high quality power supply or voltage

    compensation ability.

    Keywords: Microgrid, Voltage control, power quality,

    EMTP

    I. INTRODUCTION The microgrid is defined as one independent grid

    providing continuous power to loads on grid and

    compromising two or more microsources with enough

    capacity so as to operate independently, storage assets

    and loads [5], [11].

    Any energy sources should be connected on microgrid

    and not affect operations of the existing grid including

    protection coordination, reliability, power quality

    problem, voltage control and so on correspond to

    adding of new energy sources. And when microgrid are

    separated from grid operating protection devices by

    faults of the grid side, microsources should charge

    electrical power needs of loads in microgrid and

    operate maintaining power and voltage quality [5].

    But in case of instantaneous fault or voltage or power quality deteriorations, not permanent faults of the grid

    side, microgrid should operate economic and effective

    compensation over a falling-off in quality maintaining

    connection to grid.

    It is similar to compensating voltage drop changes in

    emergency conditions by interconnecting DVR

    (Dynamic Voltage Restorer) which is custom power

    device to the existing to distribution system. But in case

    of microsources, unlike DVR, it has no limitation of

    energy capacity on direct current side. So there is a

    need of many studies over improvement of voltage

    Mehdi Hadinezhad Islamic Azad University, Saveh Branch

    Saveh, Iran

    [email protected]

    Majid Gandomkar

    Department of Electrical Engineering Islamic Azad University, Saveh Branch

    Saveh, Iran

    [email protected]

  • International Electrical Engineering Journal (IEEJ) Vol. 4 (2013) No. 3, pp. 1087-1097 ISSN 2078-2365 http://www.ieejournal.com/

    1088

    Mehdi and Majid Voltage Control of Microgrid Systems Connected to Power Network System in Fault Condition

    quality controlling micro sources, not custom power

    devices.

    In this paper, we designed and simulated distribution

    system interconnected to micro sources and microgrid

    using Electro Magnetic Transient Program. And we

    figured out dynamic characteristics of microgrid in

    emergency conditions of distribution system and made

    a comparative study between the proposed control

    algorithm of microsources and the existing control

    algorithm.

    II. Voltage and Power Quality Lately, as the equipment using micro-processor and

    semiconductor, high sensitive and large load etc.

    increase, about high quality electric power is increasing. The reason is that voltage sag or distortion

    influence quality of product, result in information

    damage, and consequently these bring big economic

    loss. Existent analog signal was not influenced by

    voltage sag caused by successful open/close result for

    instantaneous system fault.

    However, control element, speed control appliances

    and computer etc are influence easily by voltage sag.

    Especially, in case of computer, power loss caused by

    voltage sag can influence seriously to the computer

    processing or information etc.

    Fig. 1. IEEE Std. 1100-1992 The CBEMA curve [13].

    Like above the CBEMA curve, the computer can

    perform the normal operation within +6% ~ -13% of

    normal voltage. And the permissible limitation of

    voltage is big in condition of momentary voltage

    variation within 0.5cycle. Therefore the compensation

    for the magnitude of voltage variation according to

    loads and time is necessary.

    III. MICROSOURCE CONTROLLER The inverter converts DC into AC and this is the key

    element of micro source operation. The inverter

    controller should be designed to response effectively in

    Microgrid loads variations. According to Microgrid

    operation modes especially, as micro source operate by

    voltage source, in order to be connected into microgrid,

    it need inductor (XL) for interconnecting to the power

    distribution system. [3].

  • International Electrical Engineering Journal (IEEJ) Vol. 4 (2013) No. 3, pp. 1087-1097 ISSN 2078-2365 http://www.ieejournal.com/

    1089

    Mehdi and Majid Voltage Control of Microgrid Systems Connected to Power Network System in Fault Condition

    Fig. 2. Micro source control structure.

    where P : power angle, V : output voltage of inverter, E

    : Grid voltage Like (1) ~ (3) and active power in the

    load angle, reactive power depend in magnitude of

    output voltage V of the inverter.

    Therefore output voltage magnitude of voltage source

    inverters and phase control will lead and will be able to

    control micro source outputs.

    A. Active power control

    Fig. 3. Active power versus Frequency droop controller.

    Microgrid system with distribution system

    interconnection in case is driven being done each Micro

    source must do fixed output according to the Active

    Power output direction amount, must decide the

    readjustment amount of output automatically in

    Islanding mode.

    Fig. 3 is active power control block diagram that use power-frequency droop [3]. This block is that apply

    power frequency droop control principle that is used to

    existent synchronous generator to inverter control.

    Equation (4), (5) describes input/output of power-

    frequency droop controller.

    Where Pm is Micro source active power output

    reference, PL is calculated active power, 0 is phase angle of grid.

    While microgrid is supplied active power in

    distribution system, by islanding mode operation because microgrid gets into overload in case is done

    frequency drop. Is proportional and increase fuel

  • International Electrical Engineering Journal (IEEJ) Vol. 4 (2013) No. 3, pp. 1087-1097 ISSN 2078-2365 http://www.ieejournal.com/

    1090

    Mehdi and Majid Voltage Control of Microgrid Systems Connected to Power Network System in Fault Condition

    control standard signal in droop set point in control

    system. Droop control has special quality that

    frequency decreases about output increase.

    B. Q versus E Droop and Voltage Control

    Fig. 4. Q versus E droop and voltage controller.

    Fig. 4. is voltage control block that use Q-E droop

    control.

    where Ereq is voltage reference of node. applying Q-E

    droop control, make new voltage reference and voltage

    control [3]. This can be possible to reduce large output

    of reactive power by allowing some voltage changes (

    V/Qmax) from reference voltage. voltage controller and Active power model in droop control using EMTP

    is illustrated in Fig. 5.

    Fig. 5. EMTP/RV module development for P and Voltage magnitude.

    (Droop)

  • International Electrical Engineering Journal (IEEJ) Vol. 4 (2013) No. 3, pp. 1087-1097 ISSN 2078-2365 http://www.ieejournal.com/

    1091

    Mehdi and Majid Voltage Control of Microgrid Systems Connected to Power Network System in Fault Condition

    Fig. 6. Proposed active power controller.

    The Block diagram of the proposed active power

    controller is illustrated in Fig. 6, This can be expressed the following equation:

    The proposed controller, when many micro sources

    within microgrid in islanding operation operate in

    parallel, limits active power output of micro sources

    which operate in exceeding rated active power output

    of inverter and provides lack of active power from

    other micro sources.

  • International Electrical Engineering Journal (IEEJ) Vol. 4 (2013) No. 3, pp. 1087-1097 ISSN 2078-2365 http://www.ieejournal.com/

    1092

    Mehdi and Majid Voltage Control of Microgrid Systems Connected to Power Network System in Fault Condition

    Fig. 7. EMTP/RV module development for P and Voltage magnitude. (proposed)

    IV. MICROGRID AND FAULT MODELING A kind of faults in distribution system can classify into

    instantaneous fault, permanent fault as fault

    maintenance time and line to ground fault, line to line

    fault as fault conditions. Fault in distribution system the moment fault about 98% occupy and also, most of

    distribution line fault appear by line to ground fault.

    In this case, when recloser produces fault being

    engaged to protect distribution system, because fault is

    intercepted instantaneously, Causes a lot of short-cycle

    voltage sag.

    Therefore, the momentary voltage sag compensation

    micro source through the control effectively, the fault will be reduced by the loss.

  • International Electrical Engineering Journal (IEEJ) Vol. 4 (2013) No. 3, pp. 1087-1097 ISSN 2078-2365 http://www.ieejournal.com/

    1093

    Mehdi and Majid Voltage Control of Microgrid Systems Connected to Power Network System in Fault Condition

    Fig. 8. Model of a Microgrid.

    Microgrid modeling is a 15kW, 11.25kVar capacity is

    configured as three micro sources, and 10kW, 1kVar of

    the load capacity of the three places are located. Fig. 9,

    is active power output of proposed micro source

    controller.

    Fig. 9. Active power output of micro source controller.

    V. CASE STUDY

    Following Fig. 10. It shows the result of simulation that

    the micro source existing in the microgrid does not

    work. In this case, we simulated general distribution

  • International Electrical Engineering Journal (IEEJ) Vol. 4 (2013) No. 3, pp. 1087-1097 ISSN 2078-2365 http://www.ieejournal.com/

    1094

    Mehdi and Majid Voltage Control of Microgrid Systems Connected to Power Network System in Fault Condition

    system existing only loads except micro sources. And

    the condition of simulation is set to at 5 seconds from

    grid and restore at 6 sec.

    At this time, the internal voltage in microgrid is

    influenced by voltage variation caused by distribution

    system fault.. In this simulation, average voltage for

    fault period is 180V (RMS) as following Fig. 10

    Fig. 10. Voltage of the microgrid when micro source does not exist. (RMS)

    A. Droop control In the internal microgrid, three micro-source based on

    droop control is connected. At this time, voltage

    variation caused by distribution system fault is

    compensated partly. In simulation, average voltage for

    the fault period is 255V (RMS) as following Fig. 11,

    And when the system is recovered normally, voltage

    increase is very large according to the micro-source

    control.

  • International Electrical Engineering Journal (IEEJ) Vol. 4 (2013) No. 3, pp. 1087-1097 ISSN 2078-2365 http://www.ieejournal.com/

    1095

    Mehdi and Majid Voltage Control of Microgrid Systems Connected to Power Network System in Fault Condition

    Fig. 11. Microgrid internal voltage that is consisted of droop controller base micro source.

    B. Proposed control In the internal microgrid, three micro-source based on

    the proposed control is connected. Fig. 12, shows that

    the compensation for voltage variation of micro-source

    caused by distribution system fault is more developed

    than the compensation by micro-source based on droop

    control.

    In this simulation, average voltage for the fault period

    is 261V(RMS) as like Fig. 12, And when the system is

    recovered normally, voltage increase caused by the

    micro source control is smaller than the increase caused by micro source based on droop control.

  • International Electrical Engineering Journal (IEEJ) Vol. 4 (2013) No. 3, pp. 1087-1097 ISSN 2078-2365 http://www.ieejournal.com/

    1096

    Mehdi and Majid Voltage Control of Microgrid Systems Connected to Power Network System in Fault Condition

    Fig. 12. Microgrid internal voltage that is consisted of proposed controller base micro source.

    VI. CONCLUSIONS If the fault of grid is not permanent but instantaneous or

    reduction of power quality, micro source can

    compensate voltage sag by similar principle that use to

    distribution system or custom power equipment.

    However, compensation rate is different from the control method of micro-source. The controller of

    micro-source proposed by simulation is more efficient

    than existent control method of micro-source for

    voltage sag compensation ability.

    And when micro-source based on the proposed

    controller transfer to the islanding operation, or the

    loads increase /decrease in islanding operation, it is

    operated normally within rating output range.

    This paper is the result of simulation in the ideal

    inverter model supposing three phase balance system,

    don't considered the economical operation of micro-

    source. In the next research, switching model of

    inverter including 3 phase unbalance system and

    modeling of real source would be simulated.

    VIII. REFERENCES

    [1] IEEE Standards Coordinating Committee 21, IEEE Std.1547.4-2011: IEEE Guide for Design, Operation,

    and Integration of Distributed.

    [2] I. Bae, J. Kim, Reliability Evaluation of Customers in a Microgrid, IEEE Transaction on Power Systems, Vol. 23, No. 3, pp. 1416-1422, Aug.

    2008.

    [3] M.Shao, R. L. Dianjun Lv, Control Strategy of Voltage and Frequency for Islanded Microgrid, 2012 IEEE 7th International Power Electronics and Motion

    Control Conference -ECCE Asia June 2-5, 2012,

    China.

    [4] R. H. Lasseter, MicroGrids, IEEE Power Engineering Society Winter Meeting, Vol. 1, pp. 305 -

    308, 2002.

    [5] R. J. Vijayan, S. Ch, R. Roy, Dynamic Modeling of Microgrid for Grid Connected and Intentional

    Islanding Operation, IEEE conference, 2012. [6] C.Cho, J-HongJeon, J-YulKim, S. Kwon, K. Park,

    S. Kim Active synchronizing control of a microgrid, IEEE Trans. power. Electron, vol. 26, no. 12, 2009, pp. 37073719.

  • International Electrical Engineering Journal (IEEJ) Vol. 4 (2013) No. 3, pp. 1087-1097 ISSN 2078-2365 http://www.ieejournal.com/

    1097

    Mehdi and Majid Voltage Control of Microgrid Systems Connected to Power Network System in Fault Condition

    [7] M.B. Delghavi, A. Yazdani, A control strategy for islanded operation of a Distributed Resource (DR)

    unit, Power & Energy Society General- Meeting, 2009, PES '09, IEEE 2009, pp. 18. [8] R. Caldon , F. Rossetto, A. Scala Reactive power control in distribution networks with dispersed

    generators: a cost based method Electric Power Systems Research 64 (2003) 209_/217

    [9] Robert H. Lasseter and Paolo Piagi, Control and Design of Microgrid Components. University of Wisconsin-Madison, 2006.

    [10] Ramon Zamora, anurag K. Srivastava Control for Microgrids storage: Review, challenges, and research

    needsElsevier, Volume 14, Issue 7,September 2010, Pages 2009-2018. [11] P. Yuan, L. PeiQiang, L. XinRan, L. Bo, X.

    ZhenHua, Strategy of Research and Application for the Microgrid Coordinated Control, The International IEEE Conference on Advanced Power System

    Automation and Protection,2011.