8/8/2019 Volt Reg Cdvr Lehe3225
http://slidepdf.com/reader/full/volt-reg-cdvr-lehe3225 1/8
D I G I T A L
V O L T A G E R E G U L A T O R
W H E R E T H E W O R L D T U R N S F O R P O W E R
FEATURES
● Microprocessor based control featuring choiceof three control modes standard:
Automatic Voltage Regulation (AVR)
Power Factor Regulation (PF)
Reactive Power Regulation (Var)
● Programmable stability settings
● Soft start control with an adjustable timesetting in AVR control mode
● Dual Slope Underfrequency (volts/hertz)
regulation● Three-phase or single-phase generator voltage
(RMS) sensing/regulation in AVR mode
● Single-phase generator current sensing forregulation purposes
● Field current and field voltage sensing
● Five contact sensing inputs for system interface
● One common LED for visual indication ofAlarm and Shutdown fault conditions
● Fault Shutdown Driver and Alarm OutputDriver for indication of Alarm and Shutdownfault conditions
● Generator paralleling with reactive droopcompensation and reactive differentialcompensation
● Line drop compensation
● Remote communication interface via CAN 2.0B
● Ten generator protective functions
● UL 508A Recognized and CE certified
WORLDWIDE PRODUCT SUPPORT
● Worldwide parts availability through theCaterpillar dealer network
● Over 1,800 dealer branch stores operatingin 166 countries.
● 99.7% of parts orders filled within 24 hours.The best product support record in the industry.
● Caterpillar dealer service technicians aretrained to service every aspect of your electricpower generation system.
COMPLETE SYSTEM INTEGRATION
Fully designed and factory tested to workseamlessly with Cat Generator using Shunt,PMG, or AREP excitation systems andEMCP controls.
Caterpillar is leading the power generation
marketplace with Power Solutions engineered
to deliver unmatched flexibility, expandability,
reliability, and cost-effectiveness.
LEHE3225
The Cat Digital Voltage Regulator is a
microprocessor based control designed
to provide precise voltage control, robust
transient response, and generator protection
with industry leading features and versatility.
8/8/2019 Volt Reg Cdvr Lehe3225
http://slidepdf.com/reader/full/volt-reg-cdvr-lehe3225 2/8
D I G I T A L
V O L T A G E R E G U L A T O R
2
LEHE3225
SPECIFICATIONS
General Specifications
Voltage Regulation ±0.25% no load to full load
Temperature Drift ±1.0% for a 40° C change
Response Time Maximum of 10 millisecondsVariable Sensing Range 90 to 600 Volts
Control Power 24 Vdc Supply (18 to 30 Vdc, 5VA)
Regulator Filtering THF 3% per IEC34-1TIF of 50 NEMA MG1-22.43
Harmonic Tolerance 0.5% Voltage regulation with 40% THD
Weight 1.47 kg (3.25 lb)
Environmental
Operating Temperature –40° C to 70° C (–40° F to 158° F)
Storage Temperature –40° C to 85° C (–40° F to 185° F)
Relative Humidity 95% non-condensing 30° C to 60° C
Salt Spray 5% for 48 hrs at 38° C at 115% nominal operating voltage
Vibration 4.5G (peak) 18-2000 Hz in 3 perpendicular planes
Shock 20G
Certifications
CE Approved
UL Recognized
CSA Listed
PROTECTIVE FUNCTIONS● Generator Overvoltage
● Generator Undervoltage
● Loss of Excitation● Instantaneous Field Overcurrent
● Over Excitation
● Loss of Sensing
● Diode Fault Monitor
● Internal Watchdog Failure
● Internal Memory Failure
● Fault Reset Closed Too Long
8/8/2019 Volt Reg Cdvr Lehe3225
http://slidepdf.com/reader/full/volt-reg-cdvr-lehe3225 3/8
D I G I T A L
V O L T A G E R E G U L A T O R
3
LEHE3225
Programmable Variables Range of Adjustment
Voltage vs Frequency Characteristic Two slope ranges adjustable from 1 to 10 PU in 0.1 increments
Fine Voltage Level –10% to +10% in 0.1% increment
Droop Adjustment 0 to 10% in 0.1% increment
Overvoltage Setpoint 105 to 135% of rated voltage in 1.0% incrementOvervoltage Time Delay 2 to 30 seconds in 1 second increments
Undervoltage Setpoint 60 to 95% of rated voltage in 1.0% incrementUndervoltage Time Delay 10 to 120 seconds in 1 second increments
Gain 1 to 20% in 0.1% increments
Single Phase or Three Phase Sensing
Under Frequency Point 20 to 40 Hz
Knee Frequency 45 to 65 Hz in 0.1 Hz increments
Minimum Voltage Setpoint 50 to 100% of rated voltage
Var Operating Mode 100% to –100% in 0.001 increments
PF Operating Mode 0.6 lead to 0.6 lag in 0.01 increments
Line Drop (IR) Compensation 0 to 10% in 0.1% increment
Loss of Excitation 0.1 to 1.0 PU leading varsLoss of Excitation Time Delay 0.1 to 9.9 seconds in 0.1 second increments
Over Excitation 0 to 12 Adc in 0.1 Adc incrementsTime Delay — Fixed Time Option 0 to 10 sec in 0.1 sec increments
Loss of Sensing Time Delay 0 to 25 sec in 1 sec increments
Diode Fault Monitor 1 to 10A rms field ripple current
Soft Start Function 1 to 120 sec
8/8/2019 Volt Reg Cdvr Lehe3225
http://slidepdf.com/reader/full/volt-reg-cdvr-lehe3225 4/8
D I G I T A L
V O L T A G E R E G U L A T O R
4
LEHE3225
REGULATION CHARACTERISTIC — FIGURE 1
Underfrequency Point (20-40 Hz)100
75
50
25
20 40 60 80 100
% of Nominal Frequency
Generator Output Voltage
Decreasing Slope 1 (1 – 10 V/HZ)
Decreasing Slope 2 (1 –10 V/HZ)
5 Hz (Fixed)
Minimum Voltage Setpoint (50-100%)
Knee Frequency
8/8/2019 Volt Reg Cdvr Lehe3225
http://slidepdf.com/reader/full/volt-reg-cdvr-lehe3225 5/8
D I G I T A L
V O L T A G E R E G U L A T O R
5
LEHE3225
OUTLINE DRAWING — FIGURE 2
0.16 (4.06)
0
0.59 (15.0)
2.81 (71.4)
2.87 (72.9)
5.50 typ.
(139.7)
0
0
6 .
3 8
( 1 6 2 .
1 )
10.88 (276.4)
7.50 typ.
(190.5)
P6
P12
P9 J4
8/8/2019 Volt Reg Cdvr Lehe3225
http://slidepdf.com/reader/full/volt-reg-cdvr-lehe3225 6/8
D I G I T A L
V O L T A G E R E G U L A T O R
6
LEHE3225
EXAMPLE CONNECTION DIAGRAM — FIGURE 3
10 9 10 8 7 PMG CTB
+ GEN
10 11
52 10
FIELD OUTPUT
P6-4 (F2,-) P6-5 (F1,+) P6-1 POWER INPUT
P6-2 P6-3 CURRENT SENSING
P12-1 P12-2 P12-10 VOLTAGE SENSING
P12-11 P12-12
P9-6 RAISE/LOWER INPUTS
P9-4 P9-5 +/-10 VDC CONTROL INPUT P12-6 (+) P12-3 (-) VAR/PF
CONTROL P9-9 EXCITATION
DISABLE P9-7 FAULT
RESETP9-8 P12-4 (-) ALARM
DRIVER
SHUTDOWN FAULT DRIVER
P12-9 (+) P12-5 (-) GROUND P6-6
24 Vdc + _
24 Vdc CONTROLPOWER
P12-8 (+) P12-7 (-)
1 52a 2 3 S1
4 10 5 5 6
A B C
Required only for Var/PF control. Var/PF is active with 52a closed, inactive with 52a open.
Excitation is disabled when closed, enabled when open.
Momentary closure resets any shutdown fault.
S1 (SPDT, spring -return to center-off position) adjusts regulator setpoint.
Normally-off, turns on for user alarm or trip.
Analog input voltage between -10 and +10 Vdc provides adjustment of operating setpoint.
External fuses should be sized to match the PMG and protect the field. Maximum fuse size
should be limited to Bussmann type KTK-12 or equivalent.
Three-phase PMG is shown. For single-phase PMG, omit P6-3 connection.
Sensing potential transformer is required if line voltage exceeds 660 Vac.
Item not supplied by Caterpillar.
When generator rotation is ACB, the connections shown for CTB should be reversed.
1 2 3 4 5 6 7 8 9 10 11
8/8/2019 Volt Reg Cdvr Lehe3225
http://slidepdf.com/reader/full/volt-reg-cdvr-lehe3225 7/8
D I G I T A L
V O L T A G E R E G U L A T O R
7
LEHE3225
8/8/2019 Volt Reg Cdvr Lehe3225
http://slidepdf.com/reader/full/volt-reg-cdvr-lehe3225 8/8
D I G I T A L
V O L T A G E R E G U L A T O R
www.CAT-ElectricPower.com
© 2003 CaterpillarAll rights reserved.
U.S. and European sourced Printed in U.S.A.