EN Regulation VM iSystem C003674-B Installation and Service Manual 300028025-001-01

Transcript of VM iSystem - Akvedukts€¦ · 3 Technical description 3.1 Operating modes 3.1.1. Appliance set to...

Page 1: VM iSystem - Akvedukts€¦ · 3 Technical description 3.1 Operating modes 3.1.1. Appliance set to VM/MR VM iSystem module networked with one or more generators equipped with a DIEMATIC

EN

Regulation

VM iSystem

C003674-B

Installation andService Manual

300028025-001-01

Page 2: VM iSystem - Akvedukts€¦ · 3 Technical description 3.1 Operating modes 3.1.1. Appliance set to VM/MR VM iSystem module networked with one or more generators equipped with a DIEMATIC

Contents

1 Introduction ................................................................................................41.1 Symbols used .......................................................4

1.2 Abbreviations ........................................................4

1.3 General ..................................................................41.3.1 Manufacturer's liability .............................................41.3.2 Installer's liability .....................................................5

1.4 Certifications .........................................................5

2 Safety instructions and recommendations ..............................................62.1 Recommendations ................................................6

3 Technical description ................................................................................73.1 Operating modes ..................................................7

3.1.1 Appliance set to VM/MR ..........................................73.1.2 Appliance set to 3WV+ ............................................73.1.3 Appliance set to OTH+3WV ....................................83.1.4 Appliance set to 0/1+V3V ........................................8

3.2 Description of the keys ........................................9

3.3 Description of the display ..................................103.3.1 Key functions .........................................................103.3.2 Flame symbol ........................................................103.3.3 Solar (If connected) ...............................................103.3.4 Operating modes ...................................................113.3.5 Domestic Hot Water override ................................113.3.6 Other information ..................................................12

3.4 Technical specifications ....................................12

4 Installation ................................................................................................134.1 Package list .........................................................13

4.2 Mounting ..............................................................13

4.3 Electrical connections ........................................144.3.1 Recommendations ................................................144.3.2 Access to the connection terminal ........................144.3.3 Description of the connection terminal block .........15

1 19/03/2012 - 300028025-001-01

Page 3: VM iSystem - Akvedukts€¦ · 3 Technical description 3.1 Operating modes 3.1.1. Appliance set to VM/MR VM iSystem module networked with one or more generators equipped with a DIEMATIC

4.4 Installation and connection examples - Applianceset to VM/MR .......................................................164.4.1 VM iSystem module networked with one or more

generators equipped with a DIEMATIC controlpanel .....................................................................16

4.5 Installation and connection examples - Applianceset to 3WV+ .........................................................184.5.1 Independent control system ..................................184.5.2 VM iSystem module networked with one or more

generators equipped with a DIEMATIC-m3 /DIEMATIC iSystem control panel ..........................25

4.5.3 VM iSystem module controlling a gas absorption heatpump (PGA) ..........................................................26

4.6 Installation and connection examples - Applianceset to OTH+3WV ..................................................274.6.1 Independent control system ..................................274.6.2 Cascade of boilers equipped with OTH bus ..........35

4.7 Installation and connection examples - Applianceset to 0/1+V3V .....................................................394.7.1 Independent control system ..................................394.7.2 Slave control system in cascade ...........................45

5 Operating the appliance ..........................................................................475.1 Powering up for the first time ............................47

5.2 Access to the various browsing levels .............485.2.1 User level ..............................................................485.2.2 Installer level .........................................................485.2.3 After Sales level ....................................................49

5.3 Browsing in the menus ......................................49

5.4 Reading out measured values ...........................50

5.5 Settings after powering up for the firsttime ......................................................................515.5.1 Displaying the parameters in extended

mode .....................................................................515.5.2 Setting the parameters specific to the

installation .............................................................525.5.3 Naming the circuits and generators ......................545.5.4 Setting the heating curve ......................................55

5.6 Changing the settings ........................................575.6.1 Language selection ...............................................575.6.2 Defining the configuration mode ...........................585.6.3 Calibrating the sensors .........................................585.6.4 Professional settings .............................................595.6.5 Configuring the network ........................................665.6.6 Return to the factory settings ................................69

Contents

2 19/03/2012 - 300028025-001-01

Page 4: VM iSystem - Akvedukts€¦ · 3 Technical description 3.1 Operating modes 3.1.1. Appliance set to VM/MR VM iSystem module networked with one or more generators equipped with a DIEMATIC

6 Switching off the appliance .....................................................................716.1 Installation shutdown .........................................71

6.2 Frost protection ..................................................71

7 Troubleshooting .......................................................................................727.1 Installer's contact details ...................................72

7.2 Messages (type code Mxx) ................................73

7.3 Message history ..................................................73

7.4 Faults ...................................................................747.4.1 Deletion of sensors from the memory in the

PCB .......................................................................76

7.5 Failure history .....................................................77

7.6 Parameter and input/output check (modetests) ....................................................................77

3 19/03/2012 - 300028025-001-01

Page 5: VM iSystem - Akvedukts€¦ · 3 Technical description 3.1 Operating modes 3.1.1. Appliance set to VM/MR VM iSystem module networked with one or more generators equipped with a DIEMATIC

1 Introduction

1.1 Symbols used

In these instructions, various danger levels are employed to draw theuser's attention to particular information. In so doing, we wish tosafeguard the user's safety, obviate hazards and guarantee correctoperation of the appliance.

DANGER

Risk of a dangerous situation causing serious physicalinjury.

WARNING

Risk of a dangerous situation causing slight physicalinjury.

CAUTION

Risk of material damage.

Signals important information.

¼ Signals a referral to other instructions or other pages in theinstructions.

1.2 Abbreviations

4 DHW: Domestic hot water4 3WV: 3-way valve

1.3 General

1.3.1. Manufacturer's liability

Our products are manufactured in compliance with the requirementsof the various applicable European Directives. They are therefore

delivered with [ marking and all relevant documentation.

VM iSystem 1. Introduction

19/03/2012 - 300028025-001-01 4

Page 6: VM iSystem - Akvedukts€¦ · 3 Technical description 3.1 Operating modes 3.1.1. Appliance set to VM/MR VM iSystem module networked with one or more generators equipped with a DIEMATIC

In the interest of customers, we are continuously endeavouring tomake improvements in product quality. All the specifications stated inthis document are therefore subject to change without notice.

Our liability as the manufacturer may not be invoked in the followingcases:

4 Failure to abide by the instructions on using the appliance.4 Faulty or insufficient maintenance of the appliance.4 Failure to abide by the instructions on installing the appliance.

1.3.2. Installer's liability

The installer is responsible for the installation and inital start up of theappliance. The installer must respect the following instructions:

4 Read and follow the instructions given in the manuals providedwith the appliance.

4 Carry out installation in compliance with the prevailing legislationand standards.

4 Perform the initial start up and carry out any checks necessary.4 Explain the installation to the user.4 If a maintenance is necessary, warn the user of the obligation to

check the appliance and maintain it in good working order.4 Give all the instruction manuals to the user.

1.4 Certifications

This product complies to the requirements to the european directivesand following standards:

4 2006/95/EC Low Voltage Directive. Reference Standard:EN60.335.1.

4 2004/108/EC Electromagnetic Compatibility Directive. Genericstandards: EN1000-6-3 , EN 61000-6-1.

1. Introduction VM iSystem

5 19/03/2012 - 300028025-001-01

Page 7: VM iSystem - Akvedukts€¦ · 3 Technical description 3.1 Operating modes 3.1.1. Appliance set to VM/MR VM iSystem module networked with one or more generators equipped with a DIEMATIC

2 Safety instructions andrecommendations

2.1 Recommendations

WARNING

Only qualified professionals are authorised to work on theappliance and the installation.

The appliance should be on Summer or Antrifreeze mode rather thanswitched off to guarantee the following functions:

4 Anti blocking of pumps.4 Frost protection.

VM iSystem 2. Safety instructions and recommendations

19/03/2012 - 300028025-001-01 6

Page 8: VM iSystem - Akvedukts€¦ · 3 Technical description 3.1 Operating modes 3.1.1. Appliance set to VM/MR VM iSystem module networked with one or more generators equipped with a DIEMATIC

3 Technical description

3.1 Operating modes

3.1.1. Appliance set to VM/MR

VM iSystem module networked with one or more generatorsequipped with a DIEMATIC control panel

VM iSense Pro module networked with one or more generatorsequipped with a DIEMATIC / iSense Pro control panel

4 Primary circuit control.4 Circuits B, C, DHW and AUX available.4 Does not require an outside temperature sensor.4 1 to 20VM iSystem modules + 1 to 10 generators equipped with a

DIEMATIC control panel.4 DHW priority is only activated on the secondary circuits connected

to the same VM iSystem module

3.1.2. Appliance set to 3WV+

Independent control system

4 No primary circuit control.4 Circuits B, C, DHW and AUX available.4 Requires an outside temperature sensor.VM iSystem module networked with one or more generatorsequipped with a DIEMATIC-m3 / DIEMATIC iSystem control panel

4 Primary circuit control.4 Circuits B, C, DHW and AUX available.4 Does not require an outside temperature sensor.4 1 to 10VM iSystem modules configured as 3WV+ or generators

equipped with a DIEMATIC control panel + 20VM iSystemmodules configured as VM/MR.

4 DHW priority is activated on all of the system's secondary circuits.VM iSystem module controlling a gas absorption heat pump(PGA)

4 Control of one gas absorption heat pump.4 Circuits B, C, DHW and AUX available.4 Requires an outside temperature sensor.

Generator

equipped with

DIEMATIC (Master)

VM iSystemNumber 20

Bus VM iSystem

Number 39

C00

3723

-A-0

4

Generator equipped with DIEMATIC /

iSense Pro (Master)

VM iSense Pro

Number 20

VM iSense Pro

Number 39

Bus

C00

3776

-A-0

4

VM iSystem

C00

3722

-A

Generator equipped with

DIEMATIC-m3 / DIEMATIC iSystem

(Master)

VM iSystemNumber 2

Bus VM iSystemNumber 10

C00

3724

-A-0

4

VM iSystem

Master

PGA mit RS485/RS432

interfaceNumber 2

PGA mit RS485/RS432

interfaceNumber 10

Bus

C00

3725

-A-0

4

3. Technical description VM iSystem

7 19/03/2012 - 300028025-001-01

Page 9: VM iSystem - Akvedukts€¦ · 3 Technical description 3.1 Operating modes 3.1.1. Appliance set to VM/MR VM iSystem module networked with one or more generators equipped with a DIEMATIC

4 VM iSystem module configured as bus master.4 1 to 10 groups of 3 gas absorption heat pumps.

3.1.3. Appliance set to OTH+3WV

Independent control system

4 ON/OFF and temperature control of the boiler.4 Circuits B, C, DHW and AUX available.4 Requires an outside temperature sensor.

Cascade of boilers equipped with OTH bus

4 ON/OFF and temperature control of the boiler.4 Circuits B, C, DHW and AUX available.4 Requires an outside temperature sensor.4 1 to 10VM iSystem modules configured as OTH+3WV or

generators equipped with a DIEMATIC-m3 / DIEMATIC iSystemcontrol panel or an OTH MODBUS interface + 20VM iSystemmodules configured as VM/MR.

4 DHW priority is activated on all of the system's secondary circuits.

3.1.4. Appliance set to 0/1+V3V

Independent control system

4 Control of the boiler with an ON/OFF inlet.4 Circuits B, C and DHW available.4 S.AUX used for the ON/OFF command.4 The LAUX outlet provides 230V.4 Requires an outside temperature sensor.Slave control system in cascade

4 Circuits B, C and DHW available.4 S.AUX used for the ON/OFF command.4 Does not require an outside temperature sensor.4 The VM iSystem module is always a slave in a cascade

installation.4 DHW priority is activated on all of the system's secondary circuits.

VM iSystem

Boiler equipped

with a OTH bus

OTH

C00

3726

-A-0

4

VM iSystem - Number 2

or

Modbus/OTH interface

VM iSystem - Number 10

or

Modbus/OTH interface

OTH

VM iSystemMaster

Boiler equipped

with a OTH bus

Boiler equipped

with a OTH bus

Boiler equipped

with a OTH bus

OTH

Bus

OTH

C00

3727

-A-0

4

VM iSystem

Boiler

0/1

C00

3728

-A-0

4

Generator equipped with

DIEMATIC-m3 / DIEMATIC iSystem

(Master)

VM iSystemNumber 2

Bus VM iSystemNumber 10

Boiler Boiler

0/1 0/1

C00

3729

-A-0

4

VM iSystem 3. Technical description

19/03/2012 - 300028025-001-01 8

Page 10: VM iSystem - Akvedukts€¦ · 3 Technical description 3.1 Operating modes 3.1.1. Appliance set to VM/MR VM iSystem module networked with one or more generators equipped with a DIEMATIC

3.2 Description of the keys

A Temperature setting key (heating, DHW, swimming pool)B Operating mode selection keyC DHW override keyD Key to access the parameters reserved for the installerE Keys on which the function varies as and when selections

are madeF Rotary setting button:

4 Turn the rotary button to scroll through the menus ormodify a value

4 Press the rotary button to access the menu selectedor confirm a value modification

G Button AUTO/MANUH FuseJ Button ON/OFF

C003672-B

bar

STD

0 2 4 6 8 10 12 14 16 18 22 2420

AUTO

A

B

C

D E F

J

H

G

3. Technical description VM iSystem

9 19/03/2012 - 300028025-001-01

Page 11: VM iSystem - Akvedukts€¦ · 3 Technical description 3.1 Operating modes 3.1.1. Appliance set to VM/MR VM iSystem module networked with one or more generators equipped with a DIEMATIC

3.3 Description of the display

3.3.1. Key functions

> Access to the various menus

( Used to scroll through the menus

' Used to scroll through the parameters? The symbol is displayed when help is available

f Used to display the curve of the parameter selectedSTD Reset of the time programmes

b Selection of comfort mode or selection of the days to beprogrammed

v Selection of reduced mode or deselection of the days tobe programmed

j Back to the previous levelESC Back to the previous level without saving the

modifications made

3.3.2. Flame symbol

4 The symbol is displayed: The burner is operating.4 The symbol is not displayed: The burner is off.

3.3.3. Solar (If connected)

u The solar load pump is running

L000200-A The top part of the tank is reheated to the tank set point

L000201-A The entire tank is reheated to the tank set point

L000198-A The entire tank is reheated to the solar tank set point

L000199-A The tank is not loaded - Presence of the solar control

system

bar

r

STD( ' t

0 2 4 6 8 10 12 14 16 18 22 2420

C002696-A

pb AUTOx c rjLg m

bar

STD t

0 2 4 6 8 10 12 14 16 18 22 2420

C002701-B

pb AUTOx c rjMg m

bar

STD t

0 2 4 6 8 10 12 14 16 18 22 2420

L000197-A

pb AUTOx c rjMg m

VM iSystem 3. Technical description

19/03/2012 - 300028025-001-01 10

Page 12: VM iSystem - Akvedukts€¦ · 3 Technical description 3.1 Operating modes 3.1.1. Appliance set to VM/MR VM iSystem module networked with one or more generators equipped with a DIEMATIC

3.3.4. Operating modes

p Summer mode: The heating is off. Domestic hot watercontinues to be produced

b WINTER mode: Heating and domestic hot water working

AUTO Operation in automatic mode according to the timerprogramme

x Comfort mode: The symbol is displayed when a DAYoverride (comfort) is activated

4 Flashing symbol: Temporary override4 Steady symbol: Permanent override

m Reduced mode: The symbol is displayed when a NIGHToverride (reduced) is activated

4 Flashing symbol: Temporary override4 Steady symbol: Permanent override

g Holiday mode: The symbol is displayed when a HOLIDAYoverride (antifreeze) is activated

4 Flashing symbol: Holiday mode programmed4 Steady symbol: Holiday mode active

m Manual mode

3.3.5. Domestic Hot Water override

A bar is displayed when a DHW override is activated:

4 Flashing bar: Temporary override4 Steady bar: Permanent override

bar

STD t

0 2 4 6 8 10 12 14 16 18 22 2420

C002697-B

pb AUTOx c rjMg m

bar

STD t

0 2 4 6 8 10 12 14 16 18 22 2420C002698-B

pb AUTOx c rjMg m

bar

STD t

0 2 4 6 8 10 12 14 16 18 22 2420

C002707-A

pb AUTOx c rjMg m

3. Technical description VM iSystem

11 19/03/2012 - 300028025-001-01

Page 13: VM iSystem - Akvedukts€¦ · 3 Technical description 3.1 Operating modes 3.1.1. Appliance set to VM/MR VM iSystem module networked with one or more generators equipped with a DIEMATIC

3.3.6. Other information

r The symbol is displayed when domestic hot waterproduction is running.

w Valve indicator: The symbol is displayed when a 3-wayvalve is connected.

4 x : 3-way valve opens4 c : 3-way valve closes

M The symbol is displayed when the pump is operating.

Name of the circuit for which the parameters aredisplayed.

3.4 Technical specifications

4 Electricity supply: 230 V - 50 Hz4 Output: 10 - 1450 W

Outside sensorTemperature in °C -20 -16 -12 -8 -4 0 4 8 12 16 20 24Resistance in Ω 2392 2088 1811 1562 1342 1149 984 842 720 616 528 454

Outlet sensor circuit B+CDomestic hot water sensorSystem sensorTemperature in °C 0 10 20 25 30 40 50 60 70 80 90Resistance in Ω 32014 19691 12474 10000 8080 5372 3661 2535 1794 1290 941

bar

STD t

0 2 4 6 8 10 12 14 16 18 22 2420

C002699-B

pb AUTOx c rjMg m

VM iSystem 3. Technical description

19/03/2012 - 300028025-001-01 12

Page 14: VM iSystem - Akvedukts€¦ · 3 Technical description 3.1 Operating modes 3.1.1. Appliance set to VM/MR VM iSystem module networked with one or more generators equipped with a DIEMATIC

4 Installation

4.1 Package list

The delivery includes:

4 The VM iSystem module4 Quick installation guide4 USB key with the installation and service manual and the user

guide

4.2 Mounting

The VM iSystem module can be affixed to the wall or in an electricalcabinet.

1. Drill 3 holes.(1) Drilling template

2. Affix the module.3. Open the protective hood.4. Secure the unit with the 3 screws.

CAUTION

4 Do not fit a power relay or a power circuit at a distanceof less than 10 cm from the box.

4 Failure to comply with these instructions could leadto interference and control unit malfunctioning oreven damage to the electronic circuitry.

C003570-C

(1)

4. Installation VM iSystem

13 19/03/2012 - 300028025-001-01

Page 15: VM iSystem - Akvedukts€¦ · 3 Technical description 3.1 Operating modes 3.1.1. Appliance set to VM/MR VM iSystem module networked with one or more generators equipped with a DIEMATIC

4.3 Electrical connections

4.3.1. Recommendations

WARNING

4 Only qualified professionnals may carry out electricalconnections, always with the power off.

4 The appliance is fully pre-wired. Do not modify theconnections inside the control panel.

4 Earth the appliance before making any electricalconnections.

Make the electrical connections of the appliance according to:

4 The instructions of the prevailing standards.4 The instructions on the electrical diagrams provided with the

boiler.4 The recommendations in the instructions.

CAUTION

4 Separate the sensor cables from the 230 V cables.4 Use 2 pipes or cable guides at least 10 cm apart.4 Keep to the polarity shown on the terminals: phase

(L), neutral (N) and earth *.

CAUTION

Failure to comply with these instructions could lead tointerference and control unit malfunctioning or evendamage to the electronic circuitry.

4.3.2. Access to the connection terminal

1. Unscrew the 2 screws.2. Open the protective hood.

C003571-B

VM iSystem 4. Installation

19/03/2012 - 300028025-001-01 14

Page 16: VM iSystem - Akvedukts€¦ · 3 Technical description 3.1 Operating modes 3.1.1. Appliance set to VM/MR VM iSystem module networked with one or more generators equipped with a DIEMATIC

4.3.3. Description of the connection terminalblock

Connecting the BUS cascadeBUS cable - Package AD124 / AD134 / DB119

S.SYST System sensor - Package AD250

CDI C O Remote control (Circuit C) - Package AD254 / AD285 r BF DHW sensor - Package AD212CDI B / CDR Remote control (Circuit B) - Package AD254 / AD285

Radio remote control - Circuit B/C - Package AD253 /AD284

I AF Outside sensor - Package FM46Outside radio-controlled temperaturesensor - Package AD251

kC C Outlet sensor circuit C - Package AD199 0-10 V / E.TEL Inlet 0-10 Voltsvoice remote monitoring module -Package AD152

kC B Outlet sensor circuit B - Package AD199 OT OpenTherm

N L

CSC

N

M C

N L

CSB

N

M B

N L L

AUX

N L

ALIM

230V/50Hz

C003567-C

L C Heating pump circuit C A B 3 way valve circuit BCS Safety contact - Factory fitted bridge(1) Lr D.H.W. load pumpA C 3 way valve circuit C L AUX Auxiliary pumpL B Heating pump circuit B ALIM 230 V/50Hz Electricity supplyCS Safety contact - Factory fitted bridge(1) (1) If using underfloor heating, remove the bridge CS and connect a safety thermostat.

To connect a wire to the terminal block, proceed as follows:

1. Strip 8 mm of wire.Maximum cross section of the wire: 1.5 mm2

2. Press the spring in the terminal block with a screwdriver.3. Insert the wire into the terminal block.

OT

0V +

AFBF0-10V/

E.TELS.SYST

C BCDI C CDI B/

CDR

C003730-A

N

M

B

N

L

LAUX

N

LALIM

230V/50H

z

1

2 L000577-A

4. Installation VM iSystem

15 19/03/2012 - 300028025-001-01

Page 17: VM iSystem - Akvedukts€¦ · 3 Technical description 3.1 Operating modes 3.1.1. Appliance set to VM/MR VM iSystem module networked with one or more generators equipped with a DIEMATIC

4.4 Installation and connection examples - Appliance set to VM/MR

4.4.1. VM iSystem module networked with one ormore generators equipped with aDIEMATIC control panel

n Connecting 2 x 2 valve circuits and a DHW tank

DHW priority is only activated on the secondarycircuits connected to the same VM iSystemmodule.

A Master boiler equipped with a Diematic 3 / Diematic m3 /Diematic iSystem / Diematic m-Delta control panel

Z Secondary boiler

E Low loss header

R BUS cable

T 3 way valve circuit B

Y Heating pump circuit B

U Outlet sensor circuit B

I Heating circuit B

O 3 way valve circuit C

P Heating pump circuit C

a Outlet sensor circuit C

z Heating circuit C

e D.H.W. load pump

r DHW sensor (Package AD212)

t DHW storage tank

4

1

N L

CSC

N

M C

N L

CSB

N

M B

N L L

AUX

NN L

ALIM

230V/50HzOT

0V +

AFBF0-10V/

E.TELS.SYST

C BCDI C CDI B/

CDR

17

1 2

3

4

4

5

6

7

9

10

11

128

13

15

14

16

5

6

7

9

10

11

128

13

15

14

16

N°1 N°2

N L

CSC

N

M C

N L

CSB

N

M B

N L L

AUX

NN L

ALIM

230V/50HzOT

0V +

AFBF0-10V/

E.TELS.SYST

C BCDI C CDI B/

CDR

17

C003689-D

VM N°20

VM N°21

VM iSystem 4. Installation

19/03/2012 - 300028025-001-01 16

Page 18: VM iSystem - Akvedukts€¦ · 3 Technical description 3.1 Operating modes 3.1.1. Appliance set to VM/MR VM iSystem module networked with one or more generators equipped with a DIEMATIC

y Domestic circulation loop pump (Optional)

u Outside temperature sensor (optional) for control perzone. Otherwise, the outside temperature of the boilertaken into account.

4 It is possible to connect up to 20 appliancesconfigured as VM/MR (address of 20 to 39).

4 Connect a safety thermostat if the heating circuit is forunderfloor heating.

Settings to be made for this type of installation: Appliance set to VM/MRParameters Access Settings to be made See chapterINSTALLATION Installer level

Menu #SYSTEMEXTENDED ¼ "Displaying the parameters in extended mode",

page 51VM NUMBER Installer level

Menu #NETWORK20, 21, 22, ... ¼ "Configuring the network", page 66

¼ For setting master and slave boilers, refer to the boiler'sinstallation and service manual.

n Connecting the options

For example: TELCOM remote vocal monitoring module, remotecontrols for circuits B and C, second DHW tank

N L

CSC

N

M C

N L

CSB

N

M B

N NL L

AUX

N L

ALIM

230V/50HzOT

0V +

AFBF0-10V/

E.TELS.SYST

C BCDI C CDI B/

CDR

V

PRG

TELCOM 2

ALPAL2AL1

321

SET#09

V8765

4321 4

3

5

1

MODE

0 2 4 6 8 10 12 14 16 18 22 2420

MODE

0 2 4 6 8 10 12 14 16 18 22 2420

2

C003688-B

A Connect the remote control (Package AD254/FM52).

Z Connect the TELCOM remote vocal monitoring module.The remote monitoring module can also be connected tothe S.SYST inlet (if available).

E Connect the DHW sensor of the second tank.

R Second domestic hot water tank.

T Connect the load pump of the second tank.

4. Installation VM iSystem

17 19/03/2012 - 300028025-001-01

Page 19: VM iSystem - Akvedukts€¦ · 3 Technical description 3.1 Operating modes 3.1.1. Appliance set to VM/MR VM iSystem module networked with one or more generators equipped with a DIEMATIC

Settings to be made for this type of installationParameters Access Settings to be made See chapterINSTALLATION Installer level

Menu #SYSTEMEXTENDED ¼ "Displaying the parameters in

extended mode", page 51If second tank connected:S.AUX:(1)

Installer levelMenu #SYSTEM

DHW ¼ "Setting the parameters specificto the installation", page 52

If a remote monitoring module isconnected to the 0-10V inlet on theterminal block:IN 0-10V

Installer levelMenu #SYSTEM

NO ¼ "Setting the parameters specificto the installation", page 52

If a remote monitoring module isconnected to the 0-10V inlet on theterminal block:I.TEL:(2)

Installer levelMenu #SYSTEM

ANTIFR ¼ "Setting the parameters specificto the installation", page 52

I.SYST Installer levelMenu #SYSTEM

To be customised ¼ "Setting the parameters specificto the installation", page 52

CTC.I.SYST Installer levelMenu #SYSTEM

To be customised ¼ "Setting the parameters specificto the installation", page 52

(1) The parameter is only displayed if INSTALLATION parameter is set to EXTENDED.(2) The parameter is only displayed if the parameter IN 0-10V is set to OFF.

4.5 Installation and connection examples - Appliance set to 3WV+

4.5.1. Independent control system

n 1 mixed heating circuit

2

4

6

3

7

1

5

N L

CSC

N

M C

N L

CSB

N

M B

N L L N

AUX

N L

ALIM

230V/50HzOT

0V +

AFBF0-10V/

E.TELS.SYST

C BCDI C CDI B/

CDR

C003684-C

A 3 way valve circuit B

Z Heating pump circuit B

E Outlet sensor circuit B

R Heating circuit B

T Outside sensor

VM iSystem 4. Installation

19/03/2012 - 300028025-001-01 18

Page 20: VM iSystem - Akvedukts€¦ · 3 Technical description 3.1 Operating modes 3.1.1. Appliance set to VM/MR VM iSystem module networked with one or more generators equipped with a DIEMATIC

Y Primary

U Connect a safety thermostat if the heating circuit is forunderfloor heating

Earth the various pumps and 3-way valves.

Settings to be made for this type of installationParameters Access Settings to be made See chapterCIRC.CURVE B Installer level

Menu #SECONDARY INSTAL.PTo be customised ¼ "Setting the heating curve", page 55

MAX. CIRC. B Installer levelMenu #SECONDARY LIMITS

To be customised ¼ "Professional settings", page 59

n 2 mixed heating circuits and 1 DHW circuit

12

14

13

11

5

N L

CSC

N

M C

N L

CSB

N

M B

N L L N

AUX

N L

ALIM

230V/50HzOT

0V +

AFBF0-10V/

E.TELS.SYST

C BCDI C CDI B/

CDR

107

8

9

2

4

6

3

1

C003685-D

A 3 way valve circuit B

Z Heating pump circuit B

E Outlet sensor circuit B

R Heating circuit B

T Outside sensor

Y Primary

U DHW storage tank

I DHW sensor (Package AD212)

Do not use the simulation connector delivered with theDHW sensor.

O Domestic circulation loop pump (Optional)

P D.H.W. load pump

a 3 way valve circuit C

z Heating pump circuit C

4. Installation VM iSystem

19 19/03/2012 - 300028025-001-01

Page 21: VM iSystem - Akvedukts€¦ · 3 Technical description 3.1 Operating modes 3.1.1. Appliance set to VM/MR VM iSystem module networked with one or more generators equipped with a DIEMATIC

e Outlet sensor circuit C

r Heating circuit C

If using underfloor heating, remove the bridge CS andconnect a safety thermostat.

Settings to be made for this type of installationParameters Access Settings to be made See chapterCIRC.CURVE B Installer level

Menu #SECONDARY INSTAL.PTo be customised ¼ "Setting the heating curve", page 55

MAX. CIRC. B Installer levelMenu #SECONDARY LIMITS

To be customised ¼ "Professional settings", page 59

CIRC.CURVE C Installer levelMenu #SECONDARY INSTAL.P

To be customised ¼ "Setting the heating curve", page 55

MAX. CIRC. C Installer levelMenu #SECONDARY LIMITS

To be customised ¼ "Professional settings", page 59

S.AUX Installer levelMenu SYSTEM

DHW LOOP ¼ "Setting the parameters specific to theinstallation", page 52

n 1 direct heating circuit + 1 mixed heating circuit + 1 DHWcircuit

12

14

5

N L

CSC

N

M C

N L

CSB

N

M B

N L L N

AUX

N L

ALIM

230V/50HzOT

0V +

AFBF0-10V/

E.TELS.SYST

C BCDI C CDI B/

CDR

107

8

9

2

4

6

3

1

C003733-B

A 3 way valve circuit B

Z Heating pump circuit B

E Outlet sensor circuit B

R Heating circuit B

T Outside sensor

Y Primary

U DHW storage tank

I DHW sensor

O Domestic circulation loop pump (Optional)

VM iSystem 4. Installation

19/03/2012 - 300028025-001-01 20

Page 22: VM iSystem - Akvedukts€¦ · 3 Technical description 3.1 Operating modes 3.1.1. Appliance set to VM/MR VM iSystem module networked with one or more generators equipped with a DIEMATIC

P D.H.W. load pump

z Heating pump circuit C

r Heating circuit C

If using underfloor heating, remove the bridge CS andconnect a safety thermostat.

Settings to be made for this type of installationParameters Access Settings to be made See chapterINSTALLATION Installer level

Menu #SYSTEMEXTENDED ¼ "Displaying the parameters

in extended mode", page 51CIRC.CURVE B Installer level

Menu #SECONDARYINSTAL.P

To be customised ¼ "Setting the heating curve",page 55

MAX. CIRC. B Installer levelMenu #SECONDARY LIMITS

To be customised ¼ "Professional settings",page 59

If circuit C is a direct circuitwithout a flow sensor:CIRC. C:(1)

Installer levelMenu #SYSTEM

DIRECT ¼ "Setting the parametersspecific to the installation", page52

CIRC.CURVE C Installer levelMenu #SECONDARYINSTAL.P

To be customised ¼ "Setting the heating curve",page 55

(1) The parameter is only displayed if INSTALLATION parameter is set to EXTENDED.

n Pool connection

N L

CSC

N

M C

N L

CSB

N

M B

N L L N

AUX

N L

ALIM

230V/50HzOT

0V +

AFBF0-10V/

E.TELS.SYST

C BCDI C CDI B/

CDR

44

1

35

2

C003686-B

A Connect the secondary swimming pool pump.

Z Connect the swimming pool sensor.

E Plate heat exchanger.

R Pool heating cut-off control

When the parameter I.TEL: or S.SYST is set to0/1 B, the swimming pool is no longer heatedwhen the contact is open (factory setting); onlythe antifreeze function continues to run.The contact direction can still be adjusted withparameter CT.TEL or CT.SYST.

T Connect the primary swimming pool pump.

4. Installation VM iSystem

21 19/03/2012 - 300028025-001-01

Page 23: VM iSystem - Akvedukts€¦ · 3 Technical description 3.1 Operating modes 3.1.1. Appliance set to VM/MR VM iSystem module networked with one or more generators equipped with a DIEMATIC

Settings to be made for this type of installationParameters Access Settings to be made See chapterINSTALLATION Installer level

Menu #SYSTEMEXTENDED ¼ "Displaying the

parameters in extendedmode", page 51

MAX. CIRC. B Installer levelMenu #SECONDARYLIMITS

Set the value of MAX.CIRC. B to the temperaturecorresponding to the needsof the exchanger

¼ "Professional settings",page 59

CIRC. B:(1) Installer levelMenu #SYSTEM

SWIM.P. ¼ "Setting the parametersspecific to the installation",page 52

If a heating shutdown commandis connected to the 0-10V inlet onthe terminal block:IN 0-10V

Installer levelMenu #SYSTEM

NO ¼ "Setting the parametersspecific to the installation",page 52

If a heating shutdown commandis connected to the 0-10V inlet onthe terminal block:I.TEL:(2)

Installer levelMenu #SYSTEM

0/1 B ¼ "Setting the parametersspecific to the installation",page 52

(1) The parameter is only displayed if INSTALLATION parameter is set to EXTENDED.(2) The parameter is only displayed if the parameter IN 0-10V is set to OFF.

Controlling the pool circuit

The control system can be used to manage a swimming pool circuitin both cases:

Case 1: The control system regulates the primary circuit (boiler/exchanger) and the secondary circuit (exchanger/pool).

4 Connect the primary circuit pump (boiler/exchanger) to thepump B outlet. The temperature MAX. CIRC. B is then guaranteedduring comfort periods on programme B in summer and winteralike.

4 Connect the pool sensor (package AD212) to the S OUTL B input.4 Set the set point of the pool sensor using key C in the range 5 -

39°C.

Case 2: The pool has already a regulation system that is to bekept. The control system only regulates the primary circuit(boiler/exchanger).

4 Connect the primary circuit pump (boiler/exchanger) to thepump B outlet.The temperature MAX. CIRC. B is then guaranteed during comfortperiods on programme B in summer and winter alike.

The swimming pool can also be connected to circuit C:

4 Make the connection to the terminal blocks markedC.

4 Set the parameters for circuit C.

Hourly programming of the secondary circuit pump

The secondary pump operates during programme B comfort periodsin summer and winter alike.Stopping

VM iSystem 4. Installation

19/03/2012 - 300028025-001-01 22

Page 24: VM iSystem - Akvedukts€¦ · 3 Technical description 3.1 Operating modes 3.1.1. Appliance set to VM/MR VM iSystem module networked with one or more generators equipped with a DIEMATIC

To prepare your pool for winter, consult your pool specialist.

n Connecting a mixed tank

A Connect the electric tank

Z Power control relay to the electrical resistor

E DHW sensor (Package AD212)

Do not use the simulation connector delivered with theDHW sensor.

R Connect the outside temperature sensor

T D.H.W. load pump

Y Primary

Settings to be made for this type of installationParameters Access Settings to be made See chapterINSTALLATION Installer level

Menu #SYSTEMEXTENDED ¼ "Displaying the parameters in extended mode", page

51S.AUX:(1) Installer level

Menu #SYSTEMDHW ELEC ¼ "Setting the parameters specific to the installation",

page 52(1) The parameter is only displayed if INSTALLATION parameter is set to EXTENDED.

n Connecting the options

For example: TELCOM remote vocal monitoring module, remotecontrols for circuits B and C, second DHW tank

N L

CSC

N

M C

N L

CSB

N

M B

N NL L

AUX

N L

ALIM

230V/50HzOT

0V +

AFBF0-10V/

E.TELS.SYST

C BCDI C CDI B/

CDR

3

5

6

41

2

C003687-C

4. Installation VM iSystem

23 19/03/2012 - 300028025-001-01

Page 25: VM iSystem - Akvedukts€¦ · 3 Technical description 3.1 Operating modes 3.1.1. Appliance set to VM/MR VM iSystem module networked with one or more generators equipped with a DIEMATIC

N L

CSC

N

M C

N L

CSB

N

M B

N NL L

AUX

N L

ALIM

230V/50HzOT

0V +

AFBF0-10V/

E.TELS.SYST

C BCDI C CDI B/

CDR

V

PRG

TELCOM 2

ALPAL2AL1

321

SET#09

V8765

4321 4

3

5

1

MODE

0 2 4 6 8 10 12 14 16 18 22 2420

MODE

0 2 4 6 8 10 12 14 16 18 22 2420

2

C003688-B

A Connect the remote control (Package AD254/FM52).

Z Connect the TELCOM remote vocal monitoring module.The remote monitoring module can also be connected tothe S.SYST inlet (if available).

E Connect the DHW sensor of the second tank.

R Second domestic hot water tank.

T Connect the load pump of the second tank.

Settings to be made for this type of installationParameters Access Settings to be made See chapterINSTALLATION Installer level

Menu #SYSTEMEXTENDED ¼ "Displaying the parameters in

extended mode", page 51If second tank connected:S.AUX:(1)

Installer levelMenu #SYSTEM

DHW ¼ "Setting the parameters specificto the installation", page 52

If a remote monitoring module isconnected to the 0-10V inlet on theterminal block:IN 0-10V

Installer levelMenu #SYSTEM

NO ¼ "Setting the parameters specificto the installation", page 52

If a remote monitoring module isconnected to the 0-10V inlet on theterminal block:I.TEL:(2)

Installer levelMenu #SYSTEM

ANTIFR ¼ "Setting the parameters specificto the installation", page 52

I.SYST Installer levelMenu #SYSTEM

To be customised ¼ "Setting the parameters specificto the installation", page 52

CTC.I.SYST Installer levelMenu #SYSTEM

To be customised ¼ "Setting the parameters specificto the installation", page 52

(1) The parameter is only displayed if INSTALLATION parameter is set to EXTENDED.(2) The parameter is only displayed if the parameter IN 0-10V is set to OFF.

4.5.2. VM iSystem module networked with one ormore generators equipped with a

VM iSystem 4. Installation

19/03/2012 - 300028025-001-01 24

Page 26: VM iSystem - Akvedukts€¦ · 3 Technical description 3.1 Operating modes 3.1.1. Appliance set to VM/MR VM iSystem module networked with one or more generators equipped with a DIEMATIC

DIEMATIC-m3 / DIEMATIC iSystem controlpanel

n Connecting 2 x 2 valve circuits and a DHW tank

DHW priority is activated on all of the system'ssecondary circuits.

A Master boiler equipped with a Diematic m3 / DiematiciSystem control panel

Z Secondary boiler

E Low loss header

R BUS cable

T 3 way valve circuit B

Y Heating pump circuit B

U Outlet sensor circuit B

I Heating circuit B

O 3 way valve circuit C

P Heating pump circuit C

a Outlet sensor circuit C

z Heating circuit C

e D.H.W. load pump

r DHW sensor (Package AD212)

t DHW storage tank

y Domestic circulation loop pump (Optional)

u Outside temperature sensor (optional) for control perzone. Otherwise, the outside temperature of the boilertaken into account.

4

1

N L

CSC

N

M C

N L

CSB

N

M B

N L L

AUX

NN L

ALIM

230V/50HzOT

0V +

AFBF0-10V/

E.TELS.SYST

C BCDI C CDI B/

CDR

17

1 2

3

45

6

7

9

10

11

128

13

15

14

16

5

6

7

9

10

11

128

13

15

14

16

4

N°1 N°2

N L

CSC

N

M C

N L

CSB

N

M B

N L L

AUX

NN L

ALIM

230V/50HzOT

0V +

AFBF0-10V/

E.TELS.SYST

C BCDI C CDI B/

CDR

17

C003734-D

VM N°3

VM N°4

4. Installation VM iSystem

25 19/03/2012 - 300028025-001-01

Page 27: VM iSystem - Akvedukts€¦ · 3 Technical description 3.1 Operating modes 3.1.1. Appliance set to VM/MR VM iSystem module networked with one or more generators equipped with a DIEMATIC

Connect a safety thermostat if the heating circuit is forunderfloor heating.

Settings to be made for this type of installation: VM iSystem slave moduleParameters Access Settings to be made See chapterINSTALLATION Installer level

Menu #SYSTEMEXTENDED ¼ "Displaying the parameters in extended

mode", page 51CASCADE:(1) Installer level

Menu #NETWORKON ¼ "Configuring the network", page 66

MASTER CONTROLLER(1) Installer levelMenu #SYSTEM

OFF

SLAVE NUMBER(1) Installer levelMenu #SYSTEM

2, 3, ...

(1) The parameter is only displayed if INSTALLATION parameter is set to EXTENDED

4.5.3. VM iSystem module controlling a gasabsorption heat pump (PGA)

n 1 mixed heating circuit and 1 DHW circuit

7

8

9

2

4

6

232 485

3

1 10

5

N L

CSC

N

M C

N L

CSB

N

M B

N L L

AUX

NN L

ALIM

230V/50HzOT

0V +

AFBF0-10V/

E.TELS.SYST

C BCDI C CDI B/

CDR

C003749-D

11

A 3 way valve circuit B

Z Heating pump circuit B

E Outlet sensor circuit B

R Heating circuit B

T Outside sensor

Y Gas absorption heat pump

U DHW storage tank

I DHW sensor (Package AD212)

Do not use the simulation connector delivered with theDHW sensor.

O Domestic circulation loop pump (Optional)

VM iSystem 4. Installation

19/03/2012 - 300028025-001-01 26

Page 28: VM iSystem - Akvedukts€¦ · 3 Technical description 3.1 Operating modes 3.1.1. Appliance set to VM/MR VM iSystem module networked with one or more generators equipped with a DIEMATIC

P D.H.W. load pump

a RS232 / RS485 interface (Package AD277)

Connect a safety thermostat if the heating circuit is forunderfloor heating.

Settings to be made for this type of installationParameters Access Settings to be made See chapterINSTALLATION Installer level

Menu #SYSTEMEXTENDED ¼ "Displaying the parameters in extended

mode", page 51CASCADE:(1) Installer level

Menu #NETWORKON ¼ "Configuring the network", page 66

MASTER CONTROLLER(1) Installer levelMenu #SYSTEM

ON

SYSTEM NETWORK(1) Installer levelMenu #SYSTEM

ADD SLAVE

PERMUT (1) The parameter is only displayed if INSTALLATION parameter is set to EXTENDED

4.6 Installation and connection examples - Appliance set to OTH+3WV

4.6.1. Independent control system

n 1 mixed heating circuit

2

4

6

3

1

5

N L

CSC

N

M C

N L

CSB

N

M B

N L L

AUX

NN L

ALIM

230V/50HzOT

OT

0V +

AFBF0-10V/

E.TELS.SYST

C BCDI C CDI B/

CDR

C003736-C

A 3 way valve circuit B

Z Heating pump circuit B

E Outlet sensor circuit B

R Heating circuit B

T Outside sensor (optional)

Y Boiler with OpenTherm inlet

4. Installation VM iSystem

27 19/03/2012 - 300028025-001-01

Page 29: VM iSystem - Akvedukts€¦ · 3 Technical description 3.1 Operating modes 3.1.1. Appliance set to VM/MR VM iSystem module networked with one or more generators equipped with a DIEMATIC

4 Earth the various pumps and 3-way valves.4 Connect a safety thermostat if the heating circuit is for

underfloor heating.

Settings to be made for this type of installationParameters Access Settings to be made See chapterCIRC.CURVE B Installer level

Menu #SECONDARY INSTAL.PTo be customised ¼ "Setting the heating curve", page 55

MAX. CIRC. B Installer levelMenu #SECONDARY LIMITS

To be customised ¼ "Professional settings", page 59

n 2 mixed heating circuits and 1 DHW circuit

12

14

13

11

5

N L

CSC

N

M C

N L

CSB

N

M B

N L L N N

AUX

N L

ALIM

230V/50HzOT

0V +

AFBF0-10V/

E.TELS.SYST

C BCDI C CDI B/

CDR

107

8

9

2

4

6

15

3

1

C003737-B

A 3 way valve circuit B

Z Heating pump circuit B

E Outlet sensor circuit B

R Heating circuit B

T Outside sensor

Y Primary

U DHW storage tank

I DHW sensor (Package AD212)

Do not use the simulation connector delivered with theDHW sensor.

O Domestic circulation loop pump (Optional)

P D.H.W. load pump

a 3 way valve circuit C

z Heating pump circuit C

e Outlet sensor circuit C

r Heating circuit C

VM iSystem 4. Installation

19/03/2012 - 300028025-001-01 28

Page 30: VM iSystem - Akvedukts€¦ · 3 Technical description 3.1 Operating modes 3.1.1. Appliance set to VM/MR VM iSystem module networked with one or more generators equipped with a DIEMATIC

t Boiler's OT terminal block

Connect a safety thermostat if the heating circuit is forunderfloor heating.

Settings to be made for this type of installationParameters Access Settings to be made See chapterCIRC.CURVE B Installer level

Menu #SECONDARY INSTAL.PTo be customised ¼ "Setting the heating curve", page 55

MAX. CIRC. B Installer levelMenu #SECONDARY LIMITS

To be customised ¼ "Professional settings", page 59

n 1 direct heating circuit + 1 mixed heating circuit + 1 DHWcircuit

12

14

5

N L

CSC

N

M C

N L

CSB

N

M B

N L L

AUX

NN L

ALIM

230V/50HzOT

0V +

AFBF0-10V/

E.TELS.SYST

C BCDI C CDI B/

CDR

107

8

9

2

4

6

3

115

C003738-C

A 3 way valve circuit B

Z Heating pump circuit B

E Outlet sensor circuit B

R Heating circuit B

T Outside sensor

Y Primary

U DHW storage tank

I DHW sensor

O Domestic circulation loop pump (Optional)

P D.H.W. load pump

z Heating pump circuit C

r Heating circuit C

t Boiler's OT terminal block

4. Installation VM iSystem

29 19/03/2012 - 300028025-001-01

Page 31: VM iSystem - Akvedukts€¦ · 3 Technical description 3.1 Operating modes 3.1.1. Appliance set to VM/MR VM iSystem module networked with one or more generators equipped with a DIEMATIC

4 Earth the various pumps and 3-way valves.4 Connect a safety thermostat if the heating circuit is for

underfloor heating.

Settings to be made for this type of installationParameters Access Settings to be made See chapterINSTALLATION Installer level

Menu #SYSTEMEXTENDED ¼ "Displaying the parameters

in extended mode", page 51CIRC.CURVE B Installer level

Menu #SECONDARYINSTAL.P

To be customised ¼ "Setting the heating curve",page 55

MAX. CIRC. B Installer levelMenu #SECONDARY LIMITS

To be customised ¼ "Professional settings",page 59

If circuit C is a direct circuitwithout a flow sensor:CIRC. C:(1)

Installer levelMenu #SYSTEM

DIRECT ¼ "Setting the parametersspecific to the installation", page52

CIRC.CURVE C Installer levelMenu #SECONDARYINSTAL.P

To be customised ¼ "Setting the heating curve",page 55

(1) The parameter is only displayed if INSTALLATION parameter is set to EXTENDED.

n Hot water storage tank connection

QUADRO DU storage tankIn this installation example, the storage tank (type QUADRO DU)incorporates a domestic hot water zone. The boiler starts upsystematically to maintain the domestic hot water zone in the storagetank or to maintain the independent tank at temperature.

N L

CSC

N

M C

N L

CSB

N

M B

N L L N N

AUX

N L

ALIM

230V/50HzOT

0V +

AFBF0-10V/

E.TELS.SYST

C BCDI C CDI B/

CDR

C003739-A

3

4

5

7

6

21

M

VM iSystem 4. Installation

19/03/2012 - 300028025-001-01 30

Page 32: VM iSystem - Akvedukts€¦ · 3 Technical description 3.1 Operating modes 3.1.1. Appliance set to VM/MR VM iSystem module networked with one or more generators equipped with a DIEMATIC

This type of installation only works if the boilerincorporates a boiler pump managed by theboiler regulator.

A Boiler regulator

Z Connect the heating pump (Circuit B).

E DHW sensor (Package AD212)

Do not use the simulation connector delivered with theDHW sensor.

R Connect the sensor from the storage tank (PackageAD250).

T Buffer tank.

Y Solar sensor probe.

U Connect the solar station to the solar collectors.

Settings to be made for this type of installationParameters Access Settings to be made See chapterINSTALLATION Installer level

Menu #SYSTEMEXTENDED ¼ "Displaying the parameters in

extended mode", page 51I.SYST Installer level

Menu #SYSTEMSTORAGE TANK ¼ "Setting the parameters specific to

the installation", page 52If circuit B is a direct circuit without aflow sensor:CIRC. B:(1)

Installer levelMenu #SYSTEM

DIRECT ¼ "Setting the parameters specific tothe installation", page 52

(1) The parameter is only displayed if INSTALLATION parameter is set to EXTENDED.

The DHW part is maintained at the DHW set point by theboiler.The heating zone is maintained at the set temperaturecalculated according to the outside temperature. The zoneis reheated when the heating buffer temperature sensorT falls -6°C below the calculated set temperature.Reheating in the heating zone stops when the heatingbuffer temperature rises above the calculated settemperature.

n Pool connection

N L

CSC

N

M C

N L

CSB

N

M B

N L L N

AUX

N L

ALIM

230V/50HzOT

0V +

AFBF0-10V/

E.TELS.SYST

C BCDI C CDI B/

CDR

44

1

35

2

C003686-B

4. Installation VM iSystem

31 19/03/2012 - 300028025-001-01

Page 33: VM iSystem - Akvedukts€¦ · 3 Technical description 3.1 Operating modes 3.1.1. Appliance set to VM/MR VM iSystem module networked with one or more generators equipped with a DIEMATIC

A Connect the secondary swimming pool pump.

Z Connect the swimming pool sensor.

E Plate heat exchanger.

R Pool heating cut-off control

When the parameter I.TEL: or S.SYST is set to0/1 B, the swimming pool is no longer heatedwhen the contact is open (factory setting); onlythe antifreeze function continues to run.The contact direction can still be adjusted withparameter CT.TEL or CT.SYST.

T Connect the primary swimming pool pump.

Settings to be made for this type of installationParameters Access Settings to be made See chapterINSTALLATION Installer level

Menu #SYSTEMEXTENDED ¼ "Displaying the

parameters in extendedmode", page 51

MAX. CIRC. B Installer levelMenu #SECONDARYLIMITS

Set the value of MAX.CIRC. B to the temperaturecorresponding to the needsof the exchanger

¼ "Professional settings",page 59

CIRC. B:(1) Installer levelMenu #SYSTEM

SWIM.P. ¼ "Setting the parametersspecific to the installation",page 52

If a heating shutdown commandis connected to the 0-10V inlet onthe terminal block:IN 0-10V

Installer levelMenu #SYSTEM

NO ¼ "Setting the parametersspecific to the installation",page 52

If a heating shutdown commandis connected to the 0-10V inlet onthe terminal block:I.TEL:(2)

Installer levelMenu #SYSTEM

0/1 B ¼ "Setting the parametersspecific to the installation",page 52

(1) The parameter is only displayed if INSTALLATION parameter is set to EXTENDED.(2) The parameter is only displayed if the parameter IN 0-10V is set to OFF.

Controlling the pool circuit

The control system can be used to manage a swimming pool circuitin both cases:

Case 1: The control system regulates the primary circuit (boiler/exchanger) and the secondary circuit (exchanger/pool).

4 Connect the primary circuit pump (boiler/exchanger) to thepump B outlet. The temperature MAX. CIRC. B is then guaranteedduring comfort periods on programme B in summer and winteralike.

4 Connect the pool sensor (package AD212) to the S OUTL B input.4 Set the set point of the pool sensor using key C in the range 5 -

39°C.

VM iSystem 4. Installation

19/03/2012 - 300028025-001-01 32

Page 34: VM iSystem - Akvedukts€¦ · 3 Technical description 3.1 Operating modes 3.1.1. Appliance set to VM/MR VM iSystem module networked with one or more generators equipped with a DIEMATIC

Case 2: The pool has already a regulation system that is to bekept. The control system only regulates the primary circuit(boiler/exchanger).

4 Connect the primary circuit pump (boiler/exchanger) to thepump B outlet.The temperature MAX. CIRC. B is then guaranteed during comfortperiods on programme B in summer and winter alike.

The swimming pool can also be connected to circuit C:

4 Make the connection to the terminal blocks markedC.

4 Set the parameters for circuit C.

Hourly programming of the secondary circuit pump

The secondary pump operates during programme B comfort periodsin summer and winter alike.Stopping

To prepare your pool for winter, consult your pool specialist.

n Connecting a mixed tank

A Connect the electric tank

Z Power control relay to the electrical resistor

E DHW sensor (Package AD212)

Do not use the simulation connector delivered with theDHW sensor.

R Connect the outside temperature sensor

T D.H.W. load pump

Y Primary

U Boiler's OT terminal block

N L

CSC

N

M C

N L

CSB

N

M B

N L L

AUX

NN L

ALIM

230V/50HzOT

0V +

AFBF0-10V/

E.TELS.SYST

C BCDI C CDI B/

CDR

3

5

6

7

41

2

C003740-C

4. Installation VM iSystem

33 19/03/2012 - 300028025-001-01

Page 35: VM iSystem - Akvedukts€¦ · 3 Technical description 3.1 Operating modes 3.1.1. Appliance set to VM/MR VM iSystem module networked with one or more generators equipped with a DIEMATIC

Settings to be made for this type of installationParameters Access Settings to be made See chapterINSTALLATION Installer level

Menu #SYSTEMEXTENDED ¼ "Displaying the parameters in extended mode", page

51S.AUX:(1) Installer level

Menu #SYSTEMDHW ELEC ¼ "Setting the parameters specific to the installation",

page 52(1) The parameter is only displayed if INSTALLATION parameter is set to EXTENDED.

n Connecting the options

For example: TELCOM remote vocal monitoring module, remotecontrols for circuits B and C, second DHW tank

N L

CSC

N

M C

N L

CSB

N

M B

N NL L

AUX

N L

ALIM

230V/50HzOT

0V +

AFBF0-10V/

E.TELS.SYST

C BCDI C CDI B/

CDR

V

PRG

TELCOM 2

ALPAL2AL1

321

SET#09

V8765

4321 4

3

5

1

MODE

0 2 4 6 8 10 12 14 16 18 22 2420

MODE

0 2 4 6 8 10 12 14 16 18 22 2420

2

C003688-B

A Connect the remote control (Package AD254/FM52).

Z Connect the TELCOM remote vocal monitoring module.The remote monitoring module can also be connected tothe S.SYST inlet (if available).

E Connect the DHW sensor of the second tank.

R Second domestic hot water tank.

T Connect the load pump of the second tank.

Settings to be made for this type of installationParameters Access Settings to be made See chapterINSTALLATION Installer level

Menu #SYSTEMEXTENDED ¼ "Displaying the parameters in

extended mode", page 51If second tank connected:S.AUX:(1)

Installer levelMenu #SYSTEM

DHW ¼ "Setting the parameters specificto the installation", page 52

If a remote monitoring module isconnected to the 0-10V inlet on theterminal block:IN 0-10V

Installer levelMenu #SYSTEM

NO ¼ "Setting the parameters specificto the installation", page 52

(1) The parameter is only displayed if INSTALLATION parameter is set to EXTENDED.(2) The parameter is only displayed if the parameter IN 0-10V is set to OFF.

VM iSystem 4. Installation

19/03/2012 - 300028025-001-01 34

Page 36: VM iSystem - Akvedukts€¦ · 3 Technical description 3.1 Operating modes 3.1.1. Appliance set to VM/MR VM iSystem module networked with one or more generators equipped with a DIEMATIC

Settings to be made for this type of installationParameters Access Settings to be made See chapterIf a remote monitoring module isconnected to the 0-10V inlet on theterminal block:I.TEL:(2)

Installer levelMenu #SYSTEM

ANTIFR ¼ "Setting the parameters specificto the installation", page 52

I.SYST Installer levelMenu #SYSTEM

To be customised ¼ "Setting the parameters specificto the installation", page 52

CTC.I.SYST Installer levelMenu #SYSTEM

To be customised ¼ "Setting the parameters specificto the installation", page 52

(1) The parameter is only displayed if INSTALLATION parameter is set to EXTENDED.(2) The parameter is only displayed if the parameter IN 0-10V is set to OFF.

4.6.2. Cascade of boilers equipped with OTH bus

n Boiler cascade equipped with VM iSystem

DHW priority is activated on all of the system'ssecondary circuits.

A Master boiler equipped with a OpenTherm control panel

Secondary boiler

Z Low loss header

E BUS cable to make the link between boilers

R 3 way valve circuit B

T Heating pump circuit B

Y Outlet sensor circuit B

U Heating circuit B

I 3 way valve circuit C

O Heating pump circuit C

3

1

N L

CSC

N

M C

N L

CSB

N

M B

N L L

AUX

NN L

ALIM

230V/50HzOT

0V +

AFBF0-10V/

E.TELS.SYST

C BCDI C CDI B/

CDR

1617

1 1

2

34

5

6

8

9

10

117

12

14

13

15

4

5

6

8

9

10

117

12

14

13

15

N°1 N°2

N L

CSC

N

M C

N L

CSB

N

M B

N L L

AUX

NN L

ALIM

230V/50HzOT

0V +

AFBF0-10V/

E.TELS.SYST

C BCDI C CDI B/

CDR

16

C003741-C

VM N°1

VM N°2

4. Installation VM iSystem

35 19/03/2012 - 300028025-001-01

Page 37: VM iSystem - Akvedukts€¦ · 3 Technical description 3.1 Operating modes 3.1.1. Appliance set to VM/MR VM iSystem module networked with one or more generators equipped with a DIEMATIC

P Outlet sensor circuit C

a Heating circuit C

z D.H.W. load pump

e DHW sensor (Package AD212)

r DHW storage tank

t Domestic circulation loop pump (Optional)

y Outside sensor (Optional)

u System sensor

Connect a safety thermostat if the heating circuit is forunderfloor heating.

Settings to be made for this type of installation: VM iSystem master moduleParameters Access Settings to be made See chapterINSTALLATION Installer level

Menu #SYSTEMEXTENDED ¼ "Displaying the parameters in extended

mode", page 51CASCADE:(1) Installer level

Menu #NETWORKON ¼ "Configuring the network", page 66

MASTER CONTROLLER(1) Installer levelMenu #SYSTEM

ON

SYSTEM NETWORK(1) Installer levelMenu #SYSTEM

ADD GENE MANU

PERMUT (1) The parameter is only displayed if INSTALLATION parameter is set to EXTENDED

Settings to be made for this type of installation: VM iSystem slave moduleParameters Access Settings to be made See chapterINSTALLATION Installer level

Menu #SYSTEMEXTENDED ¼ "Displaying the parameters in extended

mode", page 51CASCADE:(1) Installer level

Menu #NETWORKON ¼ "Configuring the network", page 66

MASTER CONTROLLER(1) Installer levelMenu #SYSTEM

OFF

SLAVE NUMBER(1) Installer levelMenu #SYSTEM

2, 3, ...

(1) The parameter is only displayed if INSTALLATION parameter is set to EXTENDED

VM iSystem 4. Installation

19/03/2012 - 300028025-001-01 36

Page 38: VM iSystem - Akvedukts€¦ · 3 Technical description 3.1 Operating modes 3.1.1. Appliance set to VM/MR VM iSystem module networked with one or more generators equipped with a DIEMATIC

n Cascade of one boiler equipped with VM iSystem andone boiler equipped with an OTH Modbus interfaceboard

DHW priority is activated on all of the system'ssecondary circuits.

A Master boiler equipped with a OpenTherm control panel

Secondary boiler

Z Low loss header

E BUS cable to make the link between boilers

R 3 way valve circuit B

T Heating pump circuit B

Y Outlet sensor circuit B

U Heating circuit B

I 3 way valve circuit C

O Heating pump circuit C

P Outlet sensor circuit C

a Heating circuit C

z D.H.W. load pump

e DHW sensor (Package AD212)

r DHW storage tank

t Domestic circulation loop pump (Optional)

y Outside sensor (Optional)

u OTH Modbus interface board (Package AD286 / AD287)

u System sensor

1

N L

CSC

N

M C

N L

CSB

N

M B

N L L

AUX

NN L

ALIM

230V/50HzOT

OTBUS

0V +

AFBF0-10V/

E.TELS.SYST

C BCDI C CDI B/

CDR

16

17

17

1 1

2

34

5

6

8

9

10

117

12

14

13

15

N°1 N°2

C003742-E

VM N°1

4. Installation VM iSystem

37 19/03/2012 - 300028025-001-01

Page 39: VM iSystem - Akvedukts€¦ · 3 Technical description 3.1 Operating modes 3.1.1. Appliance set to VM/MR VM iSystem module networked with one or more generators equipped with a DIEMATIC

Connect a safety thermostat if the heating circuit is forunderfloor heating.

Settings to be made for this type of installation: VM iSystem master moduleParameters Access Settings to be made See chapterINSTALLATION Installer level

Menu #SYSTEMEXTENDED ¼ "Displaying the parameters in extended

mode", page 51CASCADE:(1) Installer level

Menu #NETWORKON ¼ "Configuring the network", page 66

MASTER CONTROLLER(1) Installer levelMenu #SYSTEM

ON

SYSTEM NETWORK(1) Installer levelMenu #SYSTEM

ADD SLAVE

PERMUT (1) The parameter is only displayed if INSTALLATION parameter is set to EXTENDED

Settings to be made for this type of installation: VM iSystem slave moduleParameters Access Settings to be made See chapterINSTALLATION Installer level

Menu #SYSTEMEXTENDED ¼ "Displaying the parameters in extended

mode", page 51CASCADE:(1) Installer level

Menu #NETWORKON ¼ "Configuring the network", page 66

MASTER CONTROLLER(1) Installer levelMenu #SYSTEM

OFF

SLAVE NUMBER(1) Installer levelMenu #SYSTEM

2, 3, ...

(1) The parameter is only displayed if INSTALLATION parameter is set to EXTENDED

VM iSystem 4. Installation

19/03/2012 - 300028025-001-01 38

Page 40: VM iSystem - Akvedukts€¦ · 3 Technical description 3.1 Operating modes 3.1.1. Appliance set to VM/MR VM iSystem module networked with one or more generators equipped with a DIEMATIC

4.7 Installation and connection examples - Appliance set to 0/1+V3V

4.7.1. Independent control system

n 1 mixed heating circuit

2

4

6

8

7

3

1

5

N L

CSC

N

M C

N

N

L

L

CSB

N

M B

N L L

AUX

NN L

ALIM

230V/50HzOT

0V +

AFBF0-10V/

E.TELS.SYST

C BCDI C CDI B/

CDR

C003743-C

A 3 way valve circuit B

Z Heating pump circuit B

E Outlet sensor circuit B

R Heating circuit B

T Outside sensor

Y Boiler

U Boiler control at 230 V

I System sensor used as boiler sensor

CAUTION

The VM iSystem module does not fulfil the boiler'soverheating safety functions.

4 Earth the various pumps and 3-way valves.4 Connect a safety thermostat if the heating circuit is for

underfloor heating.

Settings to be made for this type of installationParameters Access Settings to be made See chapterCIRC.CURVE B Installer level

Menu #SECONDARY INSTAL.PTo be customised ¼ "Setting the heating curve", page 55

MAX. CIRC. B Installer levelMenu #SECONDARY LIMITS

To be customised ¼ "Professional settings", page 59

4. Installation VM iSystem

39 19/03/2012 - 300028025-001-01

Page 41: VM iSystem - Akvedukts€¦ · 3 Technical description 3.1 Operating modes 3.1.1. Appliance set to VM/MR VM iSystem module networked with one or more generators equipped with a DIEMATIC

n 2 mixed heating circuits and 1 DHW circuit

13

15

14

12

10

11

5

N L

CSC

N

M C

N L

CSB

N

M B

N L L

AUX

NN L

ALIM

230V/50HzOT

0V +

AFBF0-10V/

E.TELS.SYST

C BCDI C CDI B/

CDR

9

2

4

3

1

6

8

7

N

L

C003744-D

A 3 way valve circuit B

Z Heating pump circuit B

E Outlet sensor circuit B

R Heating circuit B

T Outside sensor

Y Boiler

U Boiler control at 230 V

I System sensor used as boiler sensor

O DHW storage tank

P DHW sensor (Package AD212)

Do not use the simulation connector delivered with theDHW sensor.

a D.H.W. load pump

z 3 way valve circuit C

e Heating pump circuit C

r Outlet sensor circuit C

t Heating circuit C

CAUTION

The VM iSystem module does not fulfil the boiler'soverheating safety functions.

VM iSystem 4. Installation

19/03/2012 - 300028025-001-01 40

Page 42: VM iSystem - Akvedukts€¦ · 3 Technical description 3.1 Operating modes 3.1.1. Appliance set to VM/MR VM iSystem module networked with one or more generators equipped with a DIEMATIC

4 Earth the various pumps and 3-way valves.4 Connect a safety thermostat if the heating circuit is for

underfloor heating.

Settings to be made for this type of installationParameters Access Settings to be made See chapterCIRC.CURVE B Installer level

Menu #SECONDARY INSTAL.PTo be customised ¼ "Setting the heating curve", page 55

MAX. CIRC. B Installer levelMenu #SECONDARY LIMITS

To be customised ¼ "Professional settings", page 59

CIRC.CURVE C Installer levelMenu #SECONDARY INSTAL.P

To be customised ¼ "Setting the heating curve", page 55

MAX. CIRC. C Installer levelMenu #SECONDARY LIMITS

To be customised ¼ "Professional settings", page 59

n 1 direct heating circuit + 1 mixed heating circuit + 1 DHWcircuit

12

13

5

N L

CSC

N

M C

N L

CSB

N

M B

N L L

AUX

NN L

ALIM

230V/50HzOT

0V +

AFBF0-10V/

E.TELS.SYST

C BCDI C CDI B/

CDR

9

10

11

2

4

3

1

6

7

N

L

8

C003745-C

A 3 way valve circuit B

Z Heating pump circuit B

E Outlet sensor circuit B

R Heating circuit B

T Outside sensor

Y Boiler

U Boiler control at 230 V

I System sensor used as boiler sensor

O DHW storage tank

P DHW sensor

a D.H.W. load pump

z Heating pump circuit C

4. Installation VM iSystem

41 19/03/2012 - 300028025-001-01

Page 43: VM iSystem - Akvedukts€¦ · 3 Technical description 3.1 Operating modes 3.1.1. Appliance set to VM/MR VM iSystem module networked with one or more generators equipped with a DIEMATIC

e Heating circuit C

CAUTION

The VM iSystem module does not fulfil the boiler'soverheating safety functions.

4 Earth the various pumps and 3-way valves.4 Connect a safety thermostat if the heating circuit is for

underfloor heating.

Settings to be made for this type of installationParameters Access Settings to be made See chapterINSTALLATION Installer level

Menu #SYSTEMEXTENDED ¼ "Displaying the parameters

in extended mode", page 51CIRC.CURVE B Installer level

Menu #SECONDARYINSTAL.P

To be customised ¼ "Setting the heating curve",page 55

MAX. CIRC. B Installer levelMenu #SECONDARY LIMITS

To be customised ¼ "Professional settings",page 59

If circuit C is a direct circuitwithout a flow sensor:CIRC. C:(1)

Installer levelMenu #SYSTEM

DIRECT ¼ "Setting the parametersspecific to the installation", page52

CIRC.CURVE C Installer levelMenu #SECONDARYINSTAL.P

To be customised ¼ "Setting the heating curve",page 55

(1) The parameter is only displayed if INSTALLATION parameter is set to EXTENDED.

n Pool connection

N L

CSC

N

M C

N L

CSB

N

M B

N L L

AUX

NN L

ALIM

230V/50HzOT

0V +

AFBF0-10V/

E.TELS.SYST

C BCDI C CDI B/

CDR

L

N

4

1

35

2

6

7

8

C003746-C

A Connect the secondary swimming pool pump.

Z Connect the swimming pool sensor.

E Plate heat exchanger.

VM iSystem 4. Installation

19/03/2012 - 300028025-001-01 42

Page 44: VM iSystem - Akvedukts€¦ · 3 Technical description 3.1 Operating modes 3.1.1. Appliance set to VM/MR VM iSystem module networked with one or more generators equipped with a DIEMATIC

R Pool heating cut-off control

When the parameter I.TEL: is on 0/1 B, theswimming pool is no longer heated when thecontact is open (factory setting), only theantifreeze continues to be active.The contact direction can still be adjusted by theparameter CT.TEL.

T Connect the primary swimming pool pump.

Y Boiler

U Boiler control at 230 V

I System sensor used as boiler sensor

CAUTION

The VM iSystem module does not fulfil the boiler'soverheating safety functions.

Settings to be made for this type of installationParameters Access Settings to be made See chapterINSTALLATION Installer level

Menu #SYSTEMEXTENDED ¼ "Displaying the

parameters in extendedmode", page 51

MAX. CIRC. B Installer levelMenu #SECONDARYLIMITS

Set the value of MAX.CIRC. B to the temperaturecorresponding to the needsof the exchanger

¼ "Professional settings",page 59

CIRC. B:(1) Installer levelMenu #SYSTEM

SWIM.P. ¼ "Setting the parametersspecific to the installation",page 52

If a heating shutdown commandis connected to the 0-10V inlet onthe terminal block:IN 0-10V

Installer levelMenu #SYSTEM

NO ¼ "Setting the parametersspecific to the installation",page 52

If a heating shutdown commandis connected to the 0-10V inlet onthe terminal block:I.TEL:(2)

Installer levelMenu #SYSTEM

0/1 B ¼ "Setting the parametersspecific to the installation",page 52

(1) The parameter is only displayed if INSTALLATION parameter is set to EXTENDED.(2) The parameter is only displayed if the parameter IN 0-10V is set to OFF.

Controlling the pool circuit

The control system can be used to manage a swimming pool circuitin both cases:

Case 1: The control system regulates the primary circuit (boiler/exchanger) and the secondary circuit (exchanger/pool).

4 Connect the primary circuit pump (boiler/exchanger) to thepump B outlet. The temperature MAX. CIRC. B is then guaranteedduring comfort periods on programme B in summer and winteralike.

4 Connect the pool sensor (package AD212) to the S OUTL B input.4 Set the set point of the pool sensor using key C in the range 5 -

39°C.

4. Installation VM iSystem

43 19/03/2012 - 300028025-001-01

Page 45: VM iSystem - Akvedukts€¦ · 3 Technical description 3.1 Operating modes 3.1.1. Appliance set to VM/MR VM iSystem module networked with one or more generators equipped with a DIEMATIC

Case 2: The pool has already a regulation system that is to bekept. The control system only regulates the primary circuit(boiler/exchanger).

4 Connect the primary circuit pump (boiler/exchanger) to thepump B outlet.The temperature MAX. CIRC. B is then guaranteed during comfortperiods on programme B in summer and winter alike.

The swimming pool can also be connected to circuit C:

4 Make the connection to the terminal blocks markedC.

4 Set the parameters for circuit C.

Hourly programming of the secondary circuit pump

The secondary pump operates during programme B comfort periodsin summer and winter alike.Stopping

To prepare your pool for winter, consult your pool specialist.

n Connecting the options

For example: TELCOM remote vocal monitoring module, remotecontrols for circuits B and C, second DHW tank

N L

CSC

N

M C

N L

CSB

N

M B

N NL L

AUX

N L

ALIM

230V/50HzOT

0V +

AFBF0-10V/

E.TELS.SYST

C BCDI C CDI B/

CDR

V

PRG

TELCOM 2

ALPAL2AL1

321

SET#09

V8765

4321

1

MODE r

x 0 2 4 6 8 10 12 14 16 18 22 2420

c

MODE r

x 0 2 4 6 8 10 12 14 16 18 22 2420

c

2

C003831-A

A Connect the remote control (Package AD254/FM52).

Z Connect the TELCOM remote vocal monitoring module.

VM iSystem 4. Installation

19/03/2012 - 300028025-001-01 44

Page 46: VM iSystem - Akvedukts€¦ · 3 Technical description 3.1 Operating modes 3.1.1. Appliance set to VM/MR VM iSystem module networked with one or more generators equipped with a DIEMATIC

Settings to be made for this type of installationParameters Access Settings to be made See chapterINSTALLATION Installer level

Menu #SYSTEMEXTENDED ¼ "Displaying the parameters in

extended mode", page 51If a remote monitoring module is connectedto the 0-10V inlet on the terminal block:IN 0-10V

Installer levelMenu #SYSTEM

NO ¼ "Setting the parametersspecific to the installation", page52

If a remote monitoring module is connectedto the 0-10V inlet on the terminal block:I.TEL:(1)

Installer levelMenu #SYSTEM

ANTIFR ¼ "Setting the parametersspecific to the installation", page52

(1) The parameter is only displayed if the parameter IN 0-10V is set to OFF.

4.7.2. Slave control system in cascade

n Connecting 2 x 2 valve circuits and a DHW tank

DHW priority is activated on all of the system'ssecondary circuits.

A Master boiler equipped with a Diematic 3 / Diematic m3 /Diematic iSystem control panelMaster boiler equippedwith a Diematic 3 / Diematic m3 / iSense Pro control panel

Secondary boiler

Z Low loss header

E BUS cable

R 3 way valve circuit B

T Heating pump circuit B

Y Outlet sensor circuit B

U Heating circuit B

I 3 way valve circuit C

1

N L

CSC

N

M C

N L

CSB

N

M B

N L L

AUX

NN L

ALIM

230V/50HzOT

0V +

AFBF0-10V/

E.TELS.SYST

C BCDI C CDI B/

CDR

15

16

17

1 1

16

2

4

5

3

6

8

9

10

117

12

14

13N°1 N°2

C003747-D

VM N°2

4. Installation VM iSystem

45 19/03/2012 - 300028025-001-01

Page 47: VM iSystem - Akvedukts€¦ · 3 Technical description 3.1 Operating modes 3.1.1. Appliance set to VM/MR VM iSystem module networked with one or more generators equipped with a DIEMATIC

O Heating pump circuit C

P Outlet sensor circuit C

a Heating circuit C

z D.H.W. load pump

e DHW sensor (Package AD212)

r DHW storage tank

t Outside sensor (Optional)

y System sensor used as boiler sensor

u Boiler control at 230 V

Settings to be made for this type of installation: VM iSystem slave moduleParameters Access Settings to be made See chapterINSTALLATION Installer level

Menu #SYSTEMEXTENDED ¼ "Displaying the parameters in extended

mode", page 51CASCADE:(1) Installer level

Menu #NETWORKON ¼ "Configuring the network", page 66

MASTER CONTROLLER(1) Installer levelMenu #SYSTEM

OFF

SLAVE NUMBER(1) Installer levelMenu #SYSTEM

2, 3, ...

(1) The parameter is only displayed if INSTALLATION parameter is set to EXTENDED

VM iSystem 4. Installation

19/03/2012 - 300028025-001-01 46

Page 48: VM iSystem - Akvedukts€¦ · 3 Technical description 3.1 Operating modes 3.1.1. Appliance set to VM/MR VM iSystem module networked with one or more generators equipped with a DIEMATIC

5 Operating the appliance

5.1 Powering up for the first time

1. Press the spring-loaded tab to open the protective cover.2. Press button ON.3. Press button AUTO.4. The first time the boiler is powered up, the LANGUAGE menu is

displayed. Select the desired language by turning the rotarybutton.

5. To confirm, press the rotary button.6. Set parameter CONFIGURATION. Select the desired setting:

Setting DescriptionVM/MR Operation with all Diematic control systems - No DHW priority.

If CONFIGURATION parameter is set to VM/MR:

1. Press key - for around 5 seconds.2. Select the menu #SYSTEM.3. Set the parameter INSTALLATION to EXTENDED.4. Select the menu #NETWORK.5. Select the parameter VM NUMBER.6. Assign a code (from 20 to 39) to the appliance. The codes

assigned to the devices must always be done in increasingorder starting with 20 and without omitting any numbers.Never assign the same code to 2 different VM iSystemcontrol systems.

3WV+ Operation with Diematic-m 3 - Diematic iSystem controlsystems - DHW priority available.

0/1+V3V Control for an ON/OFF generatorOTH+3WV Control for a generator by BUS OpenTherm

7. To confirm, press the rotary button.8. Insert the 2 screws (provided in the documentation bag) at the

front of the module to guarantee protection rating IP21.

C003569-A

Français - Deutsch - English - Italiano - Espanol - Nederlands- Pycck - Polski - Türk -

bar

1

1

2

2

rc

STD( ' t

v

0 2 4 6 8 10 12 14 16 18 22 2420

pb x c rg m

ÿLANGUE FRANCAIS

C002286-C

C003568-D

5. Operating the appliance VM iSystem

47 19/03/2012 - 300028025-001-01

Page 49: VM iSystem - Akvedukts€¦ · 3 Technical description 3.1 Operating modes 3.1.1. Appliance set to VM/MR VM iSystem module networked with one or more generators equipped with a DIEMATIC

5.2 Access to the various browsing levels

5.2.1. User level

The information and settings in the User level can be accessed byeveryone.

1. Press the > key.

5.2.2. Installer level

The information and settings in the Installer level can be accessed byexperienced people.

1. Press the > key.

2. Press the - key.

It is also possible to access the installer level by pressingonly the - key for around 5 seconds.

bar

1

1

2

2

rc

STD( ' t

v

0 2 4 6 8 10 12 14 16 18 22 2420

pb AUTOx c rjMg m

SUNDAY 11:45

C002219-D-04

bar

1

1

2

2

rc

STD( ' t

v

0 2 4 6 8 10 12 14 16 18 22 2420

pb AUTOx c rjMg m

SUNDAY 11:45

C002219-D-04

1

1

2

2

rc

STD( ' t

v

0 2 4 6 8 10 12 14 16 18 22 2420

pb AUTOx c rjMg m

SUNDAY 11:45

TEMP.: 68°

C002271-F-04

VM iSystem 5. Operating the appliance

19/03/2012 - 300028025-001-01 48

Page 50: VM iSystem - Akvedukts€¦ · 3 Technical description 3.1 Operating modes 3.1.1. Appliance set to VM/MR VM iSystem module networked with one or more generators equipped with a DIEMATIC

5.2.3. After Sales level

The information and settings in the After Sales level can be accessedby initiates.

1. Press the > key.

2. Press key - for around 5 seconds.

It is also possible to access the After Sales level bypressing only the - key for around 10 seconds.

5.3 Browsing in the menus

1. To select the desired menu, turn the rotary button.2. To access the menu, press the rotary button.

To go back to the previous display, press the key j.

3. To select the desired parameter, turn the rotary button.4. To modify the parameter, press the rotary button.

To go back to the previous display, press the key j.

bar

1

1

2

2

rc

STD( ' t

v

0 2 4 6 8 10 12 14 16 18 22 2420

pb AUTOx c rjMg m

SUNDAY 11:45

C002219-D-04

1

1

2

2

rc

STD( ' t

v

0 2 4 6 8 10 12 14 16 18 22 2420

pb AUTOx c rjMg m

SUNDAY 11:45

5"

TEMP.: 68°

C002235-F-04

bar

1

1

2

2

rc

STD( ' t

v

0 2 4 6 8 10 12 14 16 18 22 2420

pb AUTOx c rjLg m

#MEASURES

#CHOICE TIME PROG.

#TIME PROGRAM

#SETTING

#TIME .DAYa

C002220-B-04

bar

1

1

2

2

rc

STD( ' t

v

0 2 4 6 8 10 12 14 16 18 22 2420

pb AUTOx c rjLg m

CURRENT PROG.B

CURRENT PROG.C

P2

P3

a

C002221-C-04

5. Operating the appliance VM iSystem

49 19/03/2012 - 300028025-001-01

Page 51: VM iSystem - Akvedukts€¦ · 3 Technical description 3.1 Operating modes 3.1.1. Appliance set to VM/MR VM iSystem module networked with one or more generators equipped with a DIEMATIC

5. To modify the parameter, turn the rotary button.6. To confirm, press the rotary button.

To cancel, press key h.

7. To go back to the main display, press key j2 times.

It is possible to use the ( and ' keys instead of the rotarybutton.

5.4 Reading out measured values

The various values measured by the appliance are displayed in the#MEASURES menu.

1. To access user level: Press the > key.2. Select the menu #MEASURES.

4 Turn the rotary button to scroll through the menus ormodify a value.

4 Press the rotary button to access the menu selectedor confirm a value modification.

¼ For a detailed explanation of menu browsing, referto the chapter: "Browsing in the menus", page 49.

User level - #MEASURES menu

Parameter Description UnitOUTSIDE TEMP. Outside temperature °CROOMTEMP. B (1) Room temperature of circuit B °C

ROOMTEMP. C (1) Room temperature of circuit C °C

BOILER TEMP.(2) Water temperature in the boiler °C

WATER TEMP. (1) Water temperature in the DHW tank °CSTOR.TANK.TEMP(1)

Water temperature in the storage tank °C

SWIMMING P.T.B(1)

Water temperature of the swimming pool on circuit B °C

SWIMMING P.T.C(1)

Water temperature of the swimming pool on circuit C °C

OUTLET TEMP. B(1)

Temperature of the flow water in circuit B °C

(1) The parameter is only displayed for the options, circuits or sensors actually connected.(2) According to the configuration

bar

1

1

2

2

rc

STD( ' t

v

0 2 4 6 8 10 12 14 16 18 22 2420

pb AUTOx c rjLg m

CURRENT PROG.C"Choice of the timeprogram applied C"

P4

a

C002222-C-04

bar

1

1

2

2

rc

STD( ' t

v

0 2 4 6 8 10 12 14 16 18 22 2420

pb AUTOx c rjMg m

LUNDI 11:45

C002224-D-04

2x

bar

1

1

2

2

rc

STD( ' t

v

0 2 4 6 8 10 12 14 16 18 22 2420

pb AUTOx c rjMg m

SUNDAY 11:45

C002219-D-04

VM iSystem 5. Operating the appliance

19/03/2012 - 300028025-001-01 50

Page 52: VM iSystem - Akvedukts€¦ · 3 Technical description 3.1 Operating modes 3.1.1. Appliance set to VM/MR VM iSystem module networked with one or more generators equipped with a DIEMATIC

User level - #MEASURES menu

Parameter Description UnitOUTLET TEMP. C(1)

Temperature of the flow water in circuit C °C

SYSTEM TEMP. (1) Temperature of the system flow water if multi-generator °CT.DHW BOTTOM(1)

Water temperature in the bottom of the DHW tank °C

TEMP.TANK AUX(1)

Water temperature in the second DHW tank connected to the AUX circuit °C

TEMP.SOL.TANK(1)(2)

Temperature of the hot water produced by solar power (TS) °C

SOLAR.COLL.T. (1)

(2)Solar panel temperature (TC) °C

SOLA.ENERGY (1)

(2)Solar energy accumulated in the tank kWh

IN 0-10V (1)(2) Voltage at input 0-10 V VCTRL Software control number (1) The parameter is only displayed for the options, circuits or sensors actually connected.(2) According to the configuration

5.5 Settings after powering up for the first time

5.5.1. Displaying the parameters in extendedmode

The display mode on the control panel is set as standard in such away as only to show the conventional parameters. It is possible toswitch to extended mode by proceeding as follows:

1. Access the installer level: Press key - for around 5 seconds.2. Select the menu #SYSTEM.

4 Turn the rotary button to scroll through the menus ormodify a value.

4 Press the rotary button to access the menu selectedor confirm a value modification.

¼ For a detailed explanation of menu browsing, referto the chapter: "Browsing in the menus", page 49

3. Set parameter INSTALLATION to EXTENDED.

Installer level - Menu #SYSTEMParameter Adjustment range Description Factory setting Customer settingINSTALLATION CLASSIC Displays the parameters of a conventional

installationCLASSIC

EXTENDED Displays all parameters

Regardless of what is done to the keys, the regulatorswitches back to CLASSIC mode after 30 minutes.

1

1

2

2

rc

STD( ' t

v

0 2 4 6 8 10 12 14 16 18 22 2420

pb AUTOx c rjMg m

SUNDAY 11:45

5"

TEMP.: 68°

C002235-F-04

5. Operating the appliance VM iSystem

51 19/03/2012 - 300028025-001-01

Page 53: VM iSystem - Akvedukts€¦ · 3 Technical description 3.1 Operating modes 3.1.1. Appliance set to VM/MR VM iSystem module networked with one or more generators equipped with a DIEMATIC

5.5.2. Setting the parameters specific to theinstallation

1. Access the installer level: Press key - for around 5 seconds.2. Select the menu #SYSTEM.

4 Turn the rotary button to scroll through the menus ormodify a value.

4 Press the rotary button to access the menu selectedor confirm a value modification.

¼ For a detailed explanation of menu browsing, referto the chapter: "Browsing in the menus", page 49

3. Set the following parameters according to the connections madeto the PCBs:

Installer level - #SYSTEM menu

Parameter Adjustment range Description Factory setting Customersetting

CIRC. B: (1) 3WV Connecting a circuit with 3-way valve ( For example:Underfloor heating)

3WV

SWIM.P. Using the circuit for pool managementDIRECT Use of circuit in direct heating circuit

Check and set the heating curve if necessary. Seechapter: ¼ "Setting the heating curve", page55

CIRC. C: (1) 3WV Connecting a circuit with 3-way valve (For example:Underfloor heating)

3WV

SWIM.P. Using the circuit for pool managementDIRECT Use of circuit in direct heating circuit

Check and set the heating curve if necessary. Seechapter: ¼ "Setting the heating curve", page55

S.AUX: (1) DHW LOOP Use as a domestic loop pump DHW LOOP PROGRAM. Use as an independent programmable outletPRIMARY PUMP The outlet MAUX is active if a heating demand is

present on the secondary pumpDHW Use of primary circuit of second DHW tankFAILURE The outlet MAUX is active if an fault is detectedDHW ELEC Used to control the electrical resistor according to the

timer programme on circuit AUX in summer mode.CTC.I.SYST(2) CLOSE See table below. CLOSE

OPEN(1) The parameter is only displayed if INSTALLATION is set to EXTENDED(2) According to the configuration(3) The parameter is only displayed if IN 0-10V is set to OFF

1

1

2

2

rc

STD( ' t

v

0 2 4 6 8 10 12 14 16 18 22 2420

pb AUTOx c rjMg m

SUNDAY 11:45

5"

TEMP.: 68°

C002235-F-04

VM iSystem 5. Operating the appliance

19/03/2012 - 300028025-001-01 52

Page 54: VM iSystem - Akvedukts€¦ · 3 Technical description 3.1 Operating modes 3.1.1. Appliance set to VM/MR VM iSystem module networked with one or more generators equipped with a DIEMATIC

Installer level - #SYSTEM menu

Parameter Adjustment range Description Factory setting Customersetting

I.SYST (1) SYSTEM(2) The inlet sensor is used to connect the common flowsensor of a cascade system

SYSTEM

STORAGETANK(2)

Hot water storage tank affected to heating only

DHW STRAT(2) Using the DHW tank with 2 sensors (top and bottom)

ST.TANK+DHW(2) Hot water storage tank affected to heating anddomestic hot water

ANTIFR Start anti-freeze in boiler command0/1 B ON or OFF contact: I.SYST can be used as an

antifreeze activation inlet on circuit B0/1 C ON or OFF contact: I.SYST can be used as an

antifreeze activation inlet on circuit C0/1 DHW ON or OFF contact: I.SYST can be used as an

antifreeze activation inlet on circuit ECS0/1 AUX(2) ON or OFF contact: I.SYST can be used as an

antifreeze activation inlet on circuit AUXWhenI.SYST is not active, the auxiliary circuit (AUX) followsthe maximum boiler temperature (parameter BOILERMAX).

CT.TEL (1) CLOSE See table below. CLOSE OPEN

I.TEL: (1)(3) ANTIFR Start anti-freeze in boiler command ANTIFR 0/1 B ON or OFF contact: I.TEL: can be used as an

antifreeze activation inlet on circuit B0/1 C ON or OFF contact: I.TEL: can be used as an

antifreeze activation inlet on circuit C0/1 DHW ON or OFF contact: I.TEL: can be used as an

antifreeze activation inlet on circuit ECS0/1 AUX(2) ON or OFF contact: I.TEL: can be used as an

antifreeze activation inlet on circuit AUXWhenI.TEL: is not active, the auxiliary circuit (AUX) followsthe maximum boiler temperature (parameter BOILERMAX).

IN 0-10V(2) OFF The 0-10V inlet on the terminal block can be used asa telephone inlet.

OFF

ON Activating the control at 0-10 V(1) The parameter is only displayed if INSTALLATION is set to EXTENDED(2) According to the configuration(3) The parameter is only displayed if IN 0-10V is set to OFF

Influence of the parameter setting CT.TEL on the I.TEL: contactCT.TEL I.TEL: I.TEL: contact closed I.TEL: contact openCLOSE ANTIFR The antifreeze mode is active on all boiler circuits. The mode selected on the boiler is active.

0/1 B The mode selected on the circuit is active. The antifreeze mode is active on the circuitconcerned.

0/1 C The mode selected on the circuit is active. The antifreeze mode is active on the circuitconcerned.

0/1 DHW The mode selected on the DHW circuit is active. The antifreeze mode is active for the DHW circuit.0/1 AUX 4 The MAUX outlet on the connection terminal

block is active.4 The boiler operates at a set point temperature

equal to BOILER MAX.

4 The MAUX outlet on the connection terminalblock is not active.

4 The boiler operates with a set point temperatureas a function of the outside temperature.

5. Operating the appliance VM iSystem

53 19/03/2012 - 300028025-001-01

Page 55: VM iSystem - Akvedukts€¦ · 3 Technical description 3.1 Operating modes 3.1.1. Appliance set to VM/MR VM iSystem module networked with one or more generators equipped with a DIEMATIC

Influence of the parameter setting CT.TEL on the I.TEL: contactCT.TEL I.TEL: I.TEL: contact closed I.TEL: contact openOPEN ANTIFR The mode selected on the boiler is active. The antifreeze mode is active on all boiler circuits.

0/1 B The antifreeze mode is active on the circuitconcerned.

The mode selected on the circuit is active.

0/1 C The antifreeze mode is active on the circuitconcerned.

The mode selected on the circuit is active.

0/1 DHW The antifreeze mode is active for the DHW circuit. The mode selected on the DHW circuit is active.0/1 AUX 4 The MAUX outlet on the connection terminal

block is not active.4 The boiler operates with a set point temperature

as a function of the outside temperature.

4 The MAUX outlet on the connection terminalblock is active.

4 The boiler operates at a set point temperatureequal to BOILER MAX.

Influence of the parameter setting CTC.I.SYST on the I.SYST contactCTC.I.SYST I.SYST I.SYST contact closed I.SYST contact openCLOSE ANTIFR The antifreeze mode is active on all boiler circuits. The mode selected on the boiler is active.

0/1 B The mode selected on the circuit is active. The antifreeze mode is active on the circuitconcerned.

0/1 C The mode selected on the circuit is active. The antifreeze mode is active on the circuitconcerned.

0/1 DHW The mode selected on the DHW circuit is active. The antifreeze mode is active for the DHW circuit.0/1 AUX 4 The MAUX outlet on the connection terminal

block is active.4 The boiler operates at a set point temperature

equal to BOILER MAX.

4 The MAUX outlet on the connection terminalblock is not active.

4 The boiler operates with a set pointtemperature as a function of the outsidetemperature.

OPEN ANTIFR The mode selected on the boiler is active. The antifreeze mode is active on all boiler circuits.0/1 B The antifreeze mode is active on the circuit

concerned.The mode selected on the circuit is active.

0/1 C The antifreeze mode is active on the circuitconcerned.

The mode selected on the circuit is active.

0/1 DHW The antifreeze mode is active for the DHW circuit. The mode selected on the DHW circuit is active.0/1 AUX 4 The MAUX outlet on the connection terminal

block is not active.4 The boiler operates with a set point

temperature as a function of the outsidetemperature.

4 The MAUX outlet on the connection terminalblock is active.

4 The boiler operates at a set point temperatureequal to BOILER MAX.

5.5.3. Naming the circuits and generators

1. Access the installer level: Press key - for around 5 seconds.2. Select the menu #NAMES OF THE CIRCUITS.

4 Turn the rotary button to scroll through the menus ormodify a value.

4 Press the rotary button to access the menu selectedor confirm a value modification.

¼ For a detailed explanation of menu browsing, referto the chapter: "Browsing in the menus", page 49

1

1

2

2

rc

STD( ' t

v

0 2 4 6 8 10 12 14 16 18 22 2420

pb AUTOx c rjMg m

SUNDAY 11:45

5"

TEMP.: 68°

C002235-F-04

VM iSystem 5. Operating the appliance

19/03/2012 - 300028025-001-01 54

Page 56: VM iSystem - Akvedukts€¦ · 3 Technical description 3.1 Operating modes 3.1.1. Appliance set to VM/MR VM iSystem module networked with one or more generators equipped with a DIEMATIC

3. Select the circuit or generator you wish to rename.

Installer level - #NAMES OF THE CIRCUITS menu

Parameter Description Name given by the customerCIRC. B: Circuit B CIRC. C: Circuit C CIRC.AUX Auxiliary circuit CIRC.DHW Domestic hot water circuit GENE Generator

4. Turn the rotary button to choose the first character from the list.To confirm, press the rotary button.

5. Then press again to enter a second character or turn the rotarybutton to leave an empty space.

6. Choose the other characters in the same way. The input zone maycontain up to 6 characters.

To move from one character to another, turn the rotarybutton. To exit without modifications, press key h.

7. To confirm the name, press the rotary button and then turn thebutton slightly anti-clockwise. When the symbol U appears, pressthe rotary button. The name is confirmed.

If the name reaches 6 characters, it is automaticallyconfirmed when the last character is confirmed.

5.5.4. Setting the heating curve

1. Access the installer level: Press key - for around 5 seconds.2. Select the menu #SECONDARY INSTAL.P.

4 Turn the rotary button to scroll through the menus ormodify a value.

4 Press the rotary button to access the menu selectedor confirm a value modification.

¼ For a detailed explanation of menu browsing, referto the chapter: "Browsing in the menus", page 49.

bar

1

1

2

2

rc

STD( ' t

v

0 2 4 6 8 10 12 14 16 18 22 2420

pb AUTOx c rjLg m

CIRC.B I

"Personalize the nameof this circuit B"

a

E

F

G

H

..

.

C002344-E-04

I

bar

1

1

2

2

rc

STD( ' t

v

0 2 4 6 8 10 12 14 16 18 22 2420

pb AUTOx c rjLg m

CIRC.B FLOOR1

"Personalize the nameof this circuit B"

a

X

Y

Z

.

.

.

C002345-D-04

1

1

2

2

rc

STD( ' t

v

0 2 4 6 8 10 12 14 16 18 22 2420

pb AUTOx c rjMg m

SUNDAY 11:45

5"

TEMP.: 68°

C002235-F-04

5. Operating the appliance VM iSystem

55 19/03/2012 - 300028025-001-01

Page 57: VM iSystem - Akvedukts€¦ · 3 Technical description 3.1 Operating modes 3.1.1. Appliance set to VM/MR VM iSystem module networked with one or more generators equipped with a DIEMATIC

3. Select the parameter CIRC. CURVE ....

4. To modify the value directly, turn the rotary button.To modify the value by displaying the curve, press key f.

5. To modify the curve, turn the rotary button.6. To confirm, press the rotary button.

To cancel, press key h.

0.7 = Heating curve set.

n Heating curve without BCT

The BCT (Base heat Curve Temperature) parameter allows aminimum operating temperature to be imposed on the heating circuit(this temperature may be constant if the circuit gradient is nil).

A Maximum temperature of the circuit

Z Water temperature in the circuit for an outsidetemperature of 0°C

E DAY set point on the circuit

R Outside temperature for which the maximum watertemperature in the circuit is reached

T Value of the heating curveSelect the parameter CIRC. CURVE ...

When you modify the heating curve, Z and R arerecalculated and repositioned automatically.

bar

1

1

2

2

rc

STD( ' t

v

0 2 4 6 8 10 12 14 16 18 22 2420

pb AUTOx c rjMg m

BUILD.INERTIA

CIRC.CURVE B

CIRC.CURVE C

SCREED DRYING

3

2.0

0.7

No a

C002316-E-04

bar

1

1

2

2

rc

STD( ' t

v

0 2 4 6 8 10 12 14 16 18 22 2420

pb AUTOx c rjMg m

CIRC.CURVE B"Slope of the heatcurve of the circuit B"

2.0

C002317-D-04

bar

1

1

2

2

rc

STD( ' t

v

0 2 4 6 8 10 12 14 16 18 22 2420

pb AUTOx c rjMg m

7564

50

020 -15

C002318-B-04

0,7

0.7

20 0 -16

50

75

1.5

C002319-B

1

2

3

4

5

VM iSystem 5. Operating the appliance

19/03/2012 - 300028025-001-01 56

Page 58: VM iSystem - Akvedukts€¦ · 3 Technical description 3.1 Operating modes 3.1.1. Appliance set to VM/MR VM iSystem module networked with one or more generators equipped with a DIEMATIC

n Heating curve with BCT

The BCT (Base heat Curve Temperature) parameter allows aminimum operating temperature to be imposed on the heating circuit(this temperature may be constant if the circuit gradient is nil).

A Maximum temperature of the circuit

Z Water temperature in the circuit for an outsidetemperature of 0°C

E DAY set point on the circuit

R Outside temperature for which the maximum watertemperature in the circuit is reached

T Value of the heating curveSelect the parameter CIRC. CURVE ...

x Value set to the parameter HCZP D

When you modify the heating curve, Z and R arerecalculated and repositioned automatically.

5.6 Changing the settings

The module is set for the most common heating systems. With thesesettings, practically all heating systems operate correctly. The user orinstaller can optimise the parameters according to own preferences.

¼ For the user settings, refer to the user instructions.

5.6.1. Language selection

1. Access the installer level: Press key - for around 5 seconds.2. Select the menu #LANGUAGE.

4 Turn the rotary button to scroll through the menus ormodify a value.

4 Press the rotary button to access the menu selectedor confirm a value modification.

¼ For a detailed explanation of menu browsing, referto the chapter: "Browsing in the menus", page 49

Installer level - Menu #LANGUAGEAdjustment range DescriptionFRANCAIS Display in FrenchDEUTSCH Display in GermanENGLISH Display in EnglishITALIANO Display in ItalianESPANOL Display in SpanishNEDERLANDS Display in DutchPOLSKI Display in PolishPУCCKИЙ Display in RussianTÜRK Display in Turkish

20 0 -15

64

50

75

0.7

C002320-B

1

2

X

3

4

5

1

1

2

2

rc

STD( ' t

v

0 2 4 6 8 10 12 14 16 18 22 2420

pb AUTOx c rjMg m

SUNDAY 11:45

5"

TEMP.: 68°

C002235-F-04

5. Operating the appliance VM iSystem

57 19/03/2012 - 300028025-001-01

Page 59: VM iSystem - Akvedukts€¦ · 3 Technical description 3.1 Operating modes 3.1.1. Appliance set to VM/MR VM iSystem module networked with one or more generators equipped with a DIEMATIC

5.6.2. Defining the configuration mode

1. Access the installer level: Press key - for around 5 seconds.2. Select the menu #SYSTEM.

4 Turn the rotary button to scroll through the menus ormodify a value.

4 Press the rotary button to access the menu selectedor confirm a value modification.

¼ For a detailed explanation of menu browsing, referto the chapter: "Browsing in the menus", page 49

3. Set parameter CONFIGURATION:

Installer level - #SYSTEM menu

Parameter Adjustmentrange

Description Customersetting

CONFIGURATION VM/MR Operation with all Diematic control systems - No DHW priority.If CONFIGURATION parameter is set to VM/MR:

1. Select the menu #NETWORK.2. Select the parameter VM NUMBER.3. Assign a code (from 20 to 39) to the appliance. The codes

assigned to the devices must always be done in increasing orderstarting with 20 and without omitting any numbers. Never assignthe same code to 2 different VM iSystem control systems.

3WV+ Operation with Diematic-m 3 - Diematic iSystem control systems -DHW priority available.

0/1+V3V Control for an ON/OFF generatorOTH+3WV Control for a generator by BUS OpenTherm

5.6.3. Calibrating the sensors

1. To access user level: Press the > key.2. Select the menu #SETTING.

4 Turn the rotary button to scroll through the menus ormodify a value.

4 Press the rotary button to access the menu selectedor confirm a value modification.

¼ For a detailed explanation of menu browsing, referto the chapter: "Browsing in the menus", page 49

3. To set the following parameters:

1

1

2

2

rc

STD( ' t

v

0 2 4 6 8 10 12 14 16 18 22 2420

pb AUTOx c rjMg m

SUNDAY 11:45

5"

TEMP.: 68°

C002235-F-04

bar

1

1

2

2

rc

STD( ' t

v

0 2 4 6 8 10 12 14 16 18 22 2420

pb AUTOx c rjMg m

SUNDAY 11:45

C002219-D-04

VM iSystem 5. Operating the appliance

19/03/2012 - 300028025-001-01 58

Page 60: VM iSystem - Akvedukts€¦ · 3 Technical description 3.1 Operating modes 3.1.1. Appliance set to VM/MR VM iSystem module networked with one or more generators equipped with a DIEMATIC

User level - #SETTING menu

Parameter Adjustment range Description Factory setting Customersetting

SUM/WIN 15 to 30 °C Used to set the outside temperature abovewhich heating will be shut down.

4 The heating pumps are shut down.4 Domestic hot water continues to be

produced.4 The symbol p appears.

22 °C

NO Heating is never shut down automaticallyCALIBR. OUT Outside sensor calibration: Used to

correct the outside temperatureOutside temperature

CALIBR. ROOM B (1)

(2)(3) Calibration of the room sensor on

circuit BMake this setting 2 hours after switchingon, when the room temperature hasstabilised

Room temperatureof circuit B

OFFSET ROOM B (1)

(4)(3)-5.0 to +5.0 °C Room offset on circuit B: Is used to set a

room offsetMake this setting 2 hours after switchingon, when the room temperature hasstabilised

0.0

ANTIFR. ROOM B (1)

(2)(3)0.5 to 20 °C Room temperature at which the

antifreeze mode is activated on circuit B6 °C

CALIBR. ROOM C (1)

(2)(3) Calibration of the room sensor on

circuit CMake this setting 2 hours after switchingon, when the room temperature hasstabilised

Room temperatureof circuit C

OFFSET ROOM C (1)

(4)(3)-5.0 to +5.0 °C Room offset on circuit C: Is used to set a

room offsetMake this setting 2 hours after switchingon, when the room temperature hasstabilised

0.0

ANTIFR. ROOM C (1)

(2)(3)0.5 to 20 °C Room temperature antifreeze activation

on circuit C6 °C

(1) The parameter is only displayed if INSTALLATION parameter is set to EXTENDED(2) The parameter is only displayed if a room sensor is connected to the circuit concerned(3) The parameter is only displayed if the circuit concerned is actually connected(4) The parameter is only displayed if no room sensor is connected to the circuit concerned or the sensor has no influence

5.6.4. Professional settings

1. Access the installer level: Press key - for around 5 seconds.2. To set the following parameters:

4 Turn the rotary button to scroll through the menus ormodify a value.

4 Press the rotary button to access the menu selectedor confirm a value modification.

¼ For a detailed explanation of menu browsing, referto the chapter: "Browsing in the menus", page 49.

1

1

2

2

rc

STD( ' t

v

0 2 4 6 8 10 12 14 16 18 22 2420

pb AUTOx c rjMg m

SUNDAY 11:45

5"

TEMP.: 68°

C002235-F-04

5. Operating the appliance VM iSystem

59 19/03/2012 - 300028025-001-01

Page 61: VM iSystem - Akvedukts€¦ · 3 Technical description 3.1 Operating modes 3.1.1. Appliance set to VM/MR VM iSystem module networked with one or more generators equipped with a DIEMATIC

Installer level - #PRIMARY LIMITS menu(1)

Parameter Adjustment range Description Factory setting Customer settingBOILER MAX(1) 40 to 90 °C Maximum temperature authorised by the boiler 90 °C BOILER MIN(1) 10 to 50 °C Minimum temperature authorised by the boiler 20 °C (1) According to the configuration

Installer level - #SECONDARY LIMITS menu

Parameter Adjustment range Description Factory settingMAX.CIRC.B 20 to 95 °C Maximum temperature (Circuit B)

¼ "MAX.CIRC...", page 6350 °C

MAX.CIRC.C 20 to 95 °C Maximum temperature (Circuit C)¼ "MAX.CIRC...", page 63

50 °C

OUT.ANTIFREEZE OFF, -8 to +10 °C Outside temperature at which the installation's antifreezeprotection is activated.Below this temperature the pumps are permanently on and theminimum temperatures for each circuit are respected.When NIGHT : STOP is set, the reduced temperature ismaintained in each circuit (#SECONDARY INSTAL.P menu).OFF: Antifreeze protection is not activated

+3 °C

HCZP D B (1)(2) OFF, 20 to 90 °C Curve base temperature in Daytime mode (Circuit B) OFF

HCZP N B (1)(2) OFF, 20 to 90 °C Curve base temperature in Nighttime mode (Circuit B) OFF

HCZP D C (1)(2) OFF, 20 to 90 °C Curve base temperature in Daytime mode (Circuit C) OFF

HCZP N C (1)(2) OFF, 20 to 90 °C Curve base temperature in Nighttime mode (Circuit C) OFF

PRIM.TEMP.DHW(1) 50 to 90 °C Set point temperature if domestic hot water production 80 °C(1) The parameter is only displayed if INSTALLATION parameter is set to EXTENDED(2) The parameter can be set to the heating curve by pressing key f.

Installer level - #SECONDARY INSTAL.P menu

Parameter Adjustment range Description Factorysetting

Customersetting

BUILD. INERTIA (1) 0 (10 hours) to 10(50 hours)

Characterisation of building's inertia:0 for a building with low thermal inertia.3 for a building with normal thermal inertia.10 for a building with high thermal inertia.Modification of the factory setting isonly useful in exceptional cases.

3 (22 hours)

CIRC.CURVE B(2) 0 to 4 Heating curve of the circuit B¼ "CIRC. CURVE ...", page 63

0.7

ANTICIP.B 0.0 to 10.0 Activation and adjustment of theanticipation time¼ "ANTICIP.B, ANTICIP.C ",page 63

NO

ROOM INFL. B (1) 0 to 10 Influence of room sensor B¼ "ROOM S.INFL", page 64

3

(1) The parameter is only displayed if INSTALLATION parameter is set to EXTENDED(2) The parameter can be set to the heating curve by pressing key f(3) The parameter is only displayed if SCREED DRYING is other than OFF(4) According to the configuration(5) The parameter is only displayed if IN 0-10V is set to ON.(6) If a reversal valve is connected, DHW priority will always be total regardless of the setting.

VM iSystem 5. Operating the appliance

19/03/2012 - 300028025-001-01 60

Page 62: VM iSystem - Akvedukts€¦ · 3 Technical description 3.1 Operating modes 3.1.1. Appliance set to VM/MR VM iSystem module networked with one or more generators equipped with a DIEMATIC

Installer level - #SECONDARY INSTAL.P menu

Parameter Adjustment range Description Factorysetting

Customersetting

CIRC.CURVE C(2) 0 to 4 Heating curve of the circuit C¼ "CIRC. CURVE ...", page 63

0.7

ANTICIP.C 0.0 to 10.0 Activation and adjustment of theanticipation time¼ "ANTICIP.B, ANTICIP.C ",page 63

NO

ROOM INFL. C (1) 0 to 10 Influence of room sensor C¼ "ROOM S.INFL", page 64

3

SCREED DRYING NO, B, C, B+C Drying the floor¼ "SCREED DRYING", page64

NO

START DRYINGTEMP(3)

20 to 50 °C Screed drying start temperature 20 °C

STOP DRYINGTEMP(3)

20 to 50 °C Screed drying stop temperature 20 °C

NB DAYS DRYING(3) 0 to 99 0 NIGHT (1) DEC. The lower temperature is maintained (Night

mode)¼ "NIGHT", page 65

DEC.

STOP The boiler is stopped (Night mode)¼ "NIGHT", page 65

IN 0-10V(4) OFF / TEMPERATURE Activating the control at 0-10 V¼ "Function 0-10 V", page 65

OFF

VMIN/OFF 0-10V (1)(5) 0 to 10 V Voltage corresponding to the instructionset minimum

0.5 V

VMAX 0-10V (1)(5) 0 to 10 V Voltage corresponding to the instructionset maximum

9.5 V

CONS.MIN 0-10V (1)

(5)10 to 70 °C Instruction minimum set temperature 20 °C

CONS.MAX 0-10V (1)

(5)10 to 100 °C Maximum set temperature 80 °C

BAND WIDTH (1) 4 to 16 K Control unit bandwidth for the 3-wayvalves.Option of increasing the bandwidth if thevalves are rapid or of reducing it if they areslow.

12 K

BOIL/3WV SHIFT (1) 0 to 16 K Minimum temperature difference betweenthe boiler and the valves

4 K

H. PUMP DELAY (1) 0 to 15 minutes Timing of the shutdown of the heatingpumps.The timing of heating pump shutdownprevents the boiler overheating.

4 minutes

(1) The parameter is only displayed if INSTALLATION parameter is set to EXTENDED(2) The parameter can be set to the heating curve by pressing key f(3) The parameter is only displayed if SCREED DRYING is other than OFF(4) According to the configuration(5) The parameter is only displayed if IN 0-10V is set to ON.(6) If a reversal valve is connected, DHW priority will always be total regardless of the setting.

5. Operating the appliance VM iSystem

61 19/03/2012 - 300028025-001-01

Page 63: VM iSystem - Akvedukts€¦ · 3 Technical description 3.1 Operating modes 3.1.1. Appliance set to VM/MR VM iSystem module networked with one or more generators equipped with a DIEMATIC

Installer level - #SECONDARY INSTAL.P menu

Parameter Adjustment range Description Factorysetting

Customersetting

HW. PUMP DELAY (1) 0 to 15 minutes Timing of the shutdown of the domestic hotwater pump.The timing of the domestic hot water loadpump shutdown prevents the boiler and theheating circuits overheating (Only if a loadpump is used).

2 minutes

ADAPT ON Automatic adaptation of the heating curvesfor each circuit with a room sensor with aninfluence of >0.

ON

OFF The heating curves can only be modifiedmanually.

PRIORITY DHW(6) TOTAL Interruption of pool heating and reheatingduring domestic hot water production.

TOTAL

SLIDING Domestic hot water production and heatingon the valve circuits if the available outputis sufficient and the hydraulic connectionallows.

NO Heating and domestic hot water productionin parallel if the hydraulic connectionallows.a Risk of overheating in the direct circuit.

LEG PROTEC The anti legionella function acts to preventthe development of legionella in the dhwtank, these bacteria are responsible forlegionellosis.

OFF

OFF Anti-legionella function not activatedDAILY The tank is overheated every day from

4:00 o'clock to 5:00 o'clockWEEKLY The tank is overheated every Saturday

from 4:00 o'clock to 5:00 o'clock(1) The parameter is only displayed if INSTALLATION parameter is set to EXTENDED(2) The parameter can be set to the heating curve by pressing key f(3) The parameter is only displayed if SCREED DRYING is other than OFF(4) According to the configuration(5) The parameter is only displayed if IN 0-10V is set to ON.(6) If a reversal valve is connected, DHW priority will always be total regardless of the setting.

Installer level - Menu #SOLAR(1)

Parameter Adjustment range Description Factorysetting

Customersetting

DEC.SOLAR DHW 0 to 30 °C Maximum drop in the DHW set point whenthe solar pump is running at 100%

5°C

REFERENCE DT 10 to 20 °C Temperature difference that the solarpump tries to maintain between the solarDHW sensor and the panel

10°C

MAX.T.COLLECTOR 100 to 125 °C Temperature of the panel above whichthe solar pump starts up.The pump does not operate if thetemperature of the solar tank is higherthan 80°C

100°C

MAX TPS PUMP 1 to 5 min Minimum operating duration of the solarpump at 100% on start-up

1 minute

(1) The menu is only displayed if the solar control system is connected and the INSTALLATION parameter is set to EXTENDED

VM iSystem 5. Operating the appliance

19/03/2012 - 300028025-001-01 62

Page 64: VM iSystem - Akvedukts€¦ · 3 Technical description 3.1 Operating modes 3.1.1. Appliance set to VM/MR VM iSystem module networked with one or more generators equipped with a DIEMATIC

Installer level - Menu #SOLAR(1)

Parameter Adjustment range Description Factorysetting

Customersetting

MIN.PUMP SPEED 50 to 100 % Minimum speed of the solar pump 50% TUBULAR COLLECTOR YES / NO Set to YES if tubular collectors are used NO MAX FLOW 0 to 20 l/min Maximum flow rate of the solar pump

¼ "MAX FLOW", page 666.7 l/mim.

(1) The menu is only displayed if the solar control system is connected and the INSTALLATION parameter is set to EXTENDED

n MAX.CIRC...

WARNING

If using underfloor heating, do not modify the factorysetting (50 °C). To install this, please consult existinglegislation.

Connect a safety thermostat to the CS contact on the pumpconnector.

n CIRC. CURVE ...

Heating curve circuit B or C

x Outside temperature (°C)y Water flow temperature (°C)

A Maximum temperature of the circuit B - C

n ANTICIP.B, ANTICIP.C

A Room temperature instruction - Comfort

Z Room temperature instruction - Low

E Time schedule

R Anticipation time = Accelerated reheating phase

The anticipation function calculates the heating restart time to reachthe desired room temperature less 0.5 K at the time programmed forswitching to comfort mode.The start time of the timed programmed corresponds to the end of theaccelerated reheating phase.The function is activated by setting a different OFF value.The value set corresponds to the time considered necessary to returnthe installation to the required temperature (outside temperature0°C), starting from a residual room temperature corresponding to thelow nocturnal instruction.Anticipation is optimised if a room sensor is connected.The regulator will automatically fine set the anticipation time.

M001678-B

1

0,5K

8801N033

1

4

2

3

5. Operating the appliance VM iSystem

63 19/03/2012 - 300028025-001-01

Page 65: VM iSystem - Akvedukts€¦ · 3 Technical description 3.1 Operating modes 3.1.1. Appliance set to VM/MR VM iSystem module networked with one or more generators equipped with a DIEMATIC

This function is dependent on the surplus output availablein the installation.

n SCREED DRYING

Used to force a constant flow temperature or a train to acceleratescreed drying on underfloor heating.The setting for these temperatures must follow the screed-layer'srecommendations.The activation of this parameter (setting other than OFF) forces thepermanent display of SCREED DRYING and deactivates all otherfunctions on the control unit.When floor drying is active on a circuit, all other circuits (e.g. DHW)are shut down. The use of this function is only possible on circuits Band C.

A STOP DRYING TEMP

Z START DRYING TEMP

E Today

R NB DAYS DRYING

T Normal regulation (End of drying)

Y Heating temperature setting (°C)

For example

A STOP DRYING TEMP: 47 °C

Z START DRYING TEMP: 20 °C

R NB DAYS DRYING

T Normal regulation (End of drying)

Y Heating temperature setting (°C)

Every day at midnight (00:00): the set point (STARTDRYING TEMP) is recalculated and the remaining numberof days (NB DAYS DRYING) is decremented.

n ROOM S.INFL

Used to adjust the influence of the room sensor on the watertemperature for the circuit concerned.

0 No influence (remote control fitted in a location with no influence)1 Slight influence3 Average influence (recommended)10 Room thermostat type operation

2

34

1

6

5

C002768-A

00:00 00:00 00:00

2

10 9 8 7 6 5 4 3 2 1

23

20

26

29

32

35

38

41

44

47

4

4

5

1

6

C002769-A

00:00 00:00 00:00

VM iSystem 5. Operating the appliance

19/03/2012 - 300028025-001-01 64

Page 66: VM iSystem - Akvedukts€¦ · 3 Technical description 3.1 Operating modes 3.1.1. Appliance set to VM/MR VM iSystem module networked with one or more generators equipped with a DIEMATIC

n NIGHT

This parameter is displayed if at least one circuit does notinclude a room sensor.

For circuits without a room sensor:

4 NIGHT :DEC. (Reduced): The reduced temperature is maintainedduring reduced periods. The circuit pump operates constantly.

4 NIGHT :STOP (Stop): Heating is shut down during reducedperiods. When installation antifreeze is active, the reducedtemperature is maintained during reduced periods.

For circuits with a room sensor:

4 When the room temperature is lower than the room sensor setpoint: The reduced temperature is maintained during reducedperiods. The circuit pump operates constantly.

4 When the room temperature is higher than the room sensor setpoint: Heating is shut down during reduced periods. Wheninstallation antifreeze is active, the reduced temperature ismaintained during reduced periods.

n Function 0-10 V

This function controls the boiler using an external system thatincludes a 0-10 V output connected to the 0-10 V input. This controlimposes an instruction set temperature on the boiler. It will benecessary to ensure that the parameter BOILER MAX is higher thanCONS.MAX 0-10V.

1 Instruction set outlet temperature (°C)2 Power input signal (V) - DC3 0 V4 CONS.MIN 0-10V

5 CONS.MAX 0-10V

6 VMIN/OFF 0-10V

7 VMAX 0-10V

8 10 Vx Voltage at inputy Boiler temperature

If the input voltage is less than VMIN/OFF 0-10V, the boiler is off.The boiler temperature setting corresponds strictly to the 0-10 Vinput. The secondary boiler circuits continue to operate but have noimpact on the water temperature in the boiler. If using the 0-10 V inputand a secondary boiler circuit, the external regulator providing this0-10 V power supply must always request a temperature at leastequal to the needs of the secondary circuit.

M001679-A

5

1

4

3 6 2 7 8

5. Operating the appliance VM iSystem

65 19/03/2012 - 300028025-001-01

Page 67: VM iSystem - Akvedukts€¦ · 3 Technical description 3.1 Operating modes 3.1.1. Appliance set to VM/MR VM iSystem module networked with one or more generators equipped with a DIEMATIC

n MAX FLOW

In order for the regulator to calculate the quantity of heat produced bythe installation (parameter kWh), input parameter MAX FLOW. Theparameter MAX FLOW is equal to the flow in litres per minute in thesolar circuit.Establish the MAX FLOW value with the help of the table below,according to the configuration of the installation and the number orsurface area of collectors.When the flow is input incorrectly, the display kWh will also beincorrect.

The quantity of heat (kWh value) can only be used forchecks carried out for personal reasons.

Flat solar panelsSolar panelinstallation

Area (m2) Number ofpanels

Flow rate(l/h)

Flow rate(l/min)

3...5 1 or 2 400 6,76...8 3 or 4 300 5,08...10 4 or 5 250 4,18...10 2x2 750 12,512...15 2x3 670 11,216...20 2x4 450 7,512...15 3x2 850 14,218...23 3x3 800 13,424...30 3x4 650 10,916...20 4x2 1200 20,024...30 4x3 850 14,2

5.6.5. Configuring the network

1. Access the installer level: Press key - for around 5 seconds.2. Select the menu #NETWORK.

4 Turn the rotary button to scroll through the menus ormodify a value.

4 Press the rotary button to access the menu selectedor confirm a value modification.

¼ For a detailed explanation of menu browsing, referto the chapter: "Browsing in the menus", page 49

3. To set the following parameters:

1

1

2

2

rc

STD( ' t

v

0 2 4 6 8 10 12 14 16 18 22 2420

pb AUTOx c rjMg m

SUNDAY 11:45

5"

TEMP.: 68°

C002235-F-04

VM iSystem 5. Operating the appliance

19/03/2012 - 300028025-001-01 66

Page 68: VM iSystem - Akvedukts€¦ · 3 Technical description 3.1 Operating modes 3.1.1. Appliance set to VM/MR VM iSystem module networked with one or more generators equipped with a DIEMATIC

Installer level - Menu #NETWORK(1)

Parameter Adjustment range Description Factory setting Customer settingVM NUMBER(2) 20 to 39 Set the module's network address 20 CASCADE:(2) ON / NO ON: System in cascade NO VM NETWORK(2) Specific menu: Enlist VMs in cascade

mode¼ See chapter: "ConnectingVM iSystem in cascade", page68

MASTER CONTROLLER(3)

ON / NO Configure this control system asmaster on the bus

ON

SYSTEM NETWORK (4) Specific menu: Enlist VMs in cascademode¼ See chapter: "ConnectingVM iSystem in cascade", page68

FUNCT (4) CLASSIC Operation in cascade: Successivetriggering of the various boilers in thecascade according to requirements

CLASSIC

PARALLEL Functioning in parallel cascade: If theoutside temperature is lower than thevalue PARALLEL CASC., all of theboilers are started up at the same time

PARALLEL CASC. (5) -10 to 20 °C Outside temperature triggering allstages in parallel mode

10 °C

TIMER GENE P. CASC(3) 0 to 30 min Minimum duration of post-operation ofthe generator pump

0 mn

INTER STAGE TIMER (3) 1 to 60 min Time delay for starting up or shuttingdown generators.

4 mn

SLAVE NUMBER (6) 2 to 10 Set the network address of thesecondary generator

2

(1) The menu is displayed only if the INSTALLATION parameter is set to EXTENDED(2) According to the configuration(3) The parameter is only displayed if CASCADE: is set to ON(4) The parameter is only displayed if MASTER CONTROLLER is set to ON(5) The parameter is only displayed if FUNCT is set to PARALLEL(6) The parameter is only displayed if MASTER CONTROLLER is set to OFF

User level - Menu #SETTING

Parameter Adjustment range Description Factory setting Customer settingPERMUT(1) AUTO / 1 ... 10 This parameter is used to set the master boiler.

4 AUTO: The master boiler switches automaticallyevery 7 days

4 1 ... 10: The master boiler is always the onedefined by this value

AUTO

(1) The parameter is only displayed if CASCADE: is on ON and MASTER CONTROLLER on ON

n Connecting appliances in cascade

It is possible, in a cascade configuration, to enlist generators and/orVM iSystem as slaves. Proceed as follows:

1. Set parameter CASCADE: to ON.

5. Operating the appliance VM iSystem

67 19/03/2012 - 300028025-001-01

Page 69: VM iSystem - Akvedukts€¦ · 3 Technical description 3.1 Operating modes 3.1.1. Appliance set to VM/MR VM iSystem module networked with one or more generators equipped with a DIEMATIC

2. Select SYSTEM NETWORK and press the rotary button to go tothe specific menu.

3. To add a slave appliance to the network, select ADD SLAVE.

4. The screen displayed allows you to choose numbers for the slaveboilers to be added to the network. Numbers 2 to 10 are dedicatedto the generators and numbers 20 to 39 to the VM iSystem. Turnthe rotary button to scroll through the numbers and press toconfirm the number chosen. Press j to go back to the previouslist.

5. To remove a slave appliance from the network, select ERASENETWORK.

6. The screen displayed allows you to choose the numbers of theslave boilers to be removed from the network. Turn the rotarybutton to scroll through the numbers and press to remove thenumber chosen. Press j to go back to the previous list.

7. Select NB. ELEMENTS.NETWORK. This screen summarises theelements in the network recognised by the system. Press j to goback to the previous list.

n Connecting VM iSystem in cascade

It is possible to assign VMs only as slaves. Proceed as follows:

1. Set parameter CASCADE: to NO.

1

1

2

2

rc

STD( ' t

v

0 2 4 6 8 10 12 14 16 18 22 2420

pb AUTOx c rjLg m

CASCADE

MASTER CONTROLER

SYSTEM NETWORK

FUNCT

INTER STAGE TIMER

ON

ON

TRADITIONAL

4'a

C002409-C-04

1

1

2

2

rc

STD( ' t

v

0 2 4 6 8 10 12 14 16 18 22 2420

pb AUTOx c rjLg m

NB.NETWORK ELEMENTS

ADD SLAVE

ERASE NETWORK

4

a

C002410-C-04

1

1

2

2

rc

STD( ' t

v

0 2 4 6 8 10 12 14 16 18 22 2420

pb AUTOx c rjLg m

ADD SLAVEGENE: 2, 5,VM: 29,

4

a

C002412-B-04

1

1

2

2

rc

STD( ' t

v

0 2 4 6 8 10 12 14 16 18 22 2420

pb AUTOx c rjLg m

ERASE NETWORKGENE: 2, 5,VM: 29,

4

a

C002413-B-04

1

1

2

2

rc

STD( ' t

v

0 2 4 6 8 10 12 14 16 18 22 2420

pb AUTOx c rjLg m

NB.NETWORK ELEMENTSGENE: 2, 5,VM: 29,

4

a

C002411-C-04

VM iSystem 5. Operating the appliance

19/03/2012 - 300028025-001-01 68

Page 70: VM iSystem - Akvedukts€¦ · 3 Technical description 3.1 Operating modes 3.1.1. Appliance set to VM/MR VM iSystem module networked with one or more generators equipped with a DIEMATIC

2. Select VM NETWORK and press the rotary button to go to thespecific menu.

3. The screen displayed is used to select the numbers of the slaveVMs to be added to the network. Numbers 20 to 39 are dedicatedto the VMs. Turn the rotary button to scroll through the numbersand press to confirm the number chosen. Press j to go back tothe previous list.

4. To remove a slave VM from the network, select DELETE VM.5. The screen displayed is used to select the numbers of the slave

VMs to be removed from the network. Turn the rotary button toscroll through the numbers and press to remove the numberchosen. Press j to go back to the previous list.

6. Select NB. ELEMENTS.NETWORK. This screen summarises theelements in the network recognised by the system. Press j to goback to the previous list.

5.6.6. Return to the factory settings

To reset the appliance, proceed as follows:

1. Press key C, > and j simultaneously for 4 seconds. The menu#RESET is displayed.

2. To set the following parameters:

Menu #RESETChoice of generator Parameter DescriptionGENERATOR RESET TOTAL Performs a TOTAL RESET of all parameters

EXCEPT PROG. Performs a parameter RESET but retains the timer programmesPROG. Performs a RESET on the timer programmes but retains the parametersSENSOR SCU Performs a RESET of the generator sensors connectedROOM SENSOR Performs a RESET of the room sensors connected

bar

1

1

2

2

rc

STD( ' t

v

0 2 4 6 8 10 12 14 16 18 22 2420

pb AUTOx c rjMg m

MODE

SUNDAY 11:45

C002296-B-04

4"

+ +

5. Operating the appliance VM iSystem

69 19/03/2012 - 300028025-001-01

Page 71: VM iSystem - Akvedukts€¦ · 3 Technical description 3.1 Operating modes 3.1.1. Appliance set to VM/MR VM iSystem module networked with one or more generators equipped with a DIEMATIC

After reset (TOTAL RESET and RESET EXCEPT PROG.), thecontrol system goes back to the display of the language choice aftera few seconds.

1. Select the desired language by turning the rotary button.2. To confirm, press the rotary button.

Français - Deutsch - English - Italiano - Espanol - Nederlands- Pycck - Polski - Türk -

bar

1

1

2

2

rc

STD( ' t

v

0 2 4 6 8 10 12 14 16 18 22 2420

pb x c rg m

ÿLANGUE FRANCAIS

C002286-C

VM iSystem 5. Operating the appliance

19/03/2012 - 300028025-001-01 70

Page 72: VM iSystem - Akvedukts€¦ · 3 Technical description 3.1 Operating modes 3.1.1. Appliance set to VM/MR VM iSystem module networked with one or more generators equipped with a DIEMATIC

6 Switching off the appliance

6.1 Installation shutdown

CAUTION

Do not switch off the mains supply to the appliance. If thecentral heating system is not used for a long period, werecommend activating the HOLIDAYS mode (to ensurethe anti-grip of the heating pump).

6.2 Frost protection

CAUTION

4 The antifreeze protection does not function if theappliance is switched off.

4 To protect the installation, set the appliance toHOLIDAYS mode.

The HOLIDAYS mode protects:

4 The installation if the outside temperature is lower than 3°C(factory setting).

4 The room temperature if a remote control is connected and theroom temperature is lower than 6 °C (factory setting).

4 The domestic hot water tank if the tank temperature is lowerthan 4 °C (the water is reheated to 10 °C).

To configure the holidays mode: ¼ Refer to the user instructions.

6. Switching off the appliance VM iSystem

71 19/03/2012 - 300028025-001-01

Page 73: VM iSystem - Akvedukts€¦ · 3 Technical description 3.1 Operating modes 3.1.1. Appliance set to VM/MR VM iSystem module networked with one or more generators equipped with a DIEMATIC

7 Troubleshooting

7.1 Installer's contact details

To display the installer's telephone number when an error isdisplayed, proceed as follows:

1. Access the "After Sales" level: Hold key - down until#PARAMETERS is displayed.

2. Select the menu #SUPPORT.

4 Turn the rotary button to scroll through the menus ormodify a value.

4 Press the rotary button to access the menu selectedor confirm a value modification.

¼ For a detailed explanation of menu browsing, referto the chapter: "Browsing in the menus", page 49

3. To set the following parameters:

After Sales level - #SUPPORT menu

Parameter DescriptionNAME Input the installer's nameTELEPHONE NUM. Input the installer's telephone number

When an error is displayed, press ? to display the installer's telephonenumber.

bar

1

1

2

2

rc

STD( ' t

v

0 2 4 6 8 10 12 14 16 18 22 2420

pb AUTOx c rjMg m

SUNDAY 11:45

10"

TEMP.: _ _ _ _

C002272-C-04

bar

1

1

2

2

rc

STD( ' t

v

0 2 4 6 8 10 12 14 16 18 22 2420

pb AUTOx c rjMg m

SUNDAY 11:45

TEMP. : 68°

PCU COM.FAIL D27

C002302-D-04

VM iSystem 7. Troubleshooting

19/03/2012 - 300028025-001-01 72

Page 74: VM iSystem - Akvedukts€¦ · 3 Technical description 3.1 Operating modes 3.1.1. Appliance set to VM/MR VM iSystem module networked with one or more generators equipped with a DIEMATIC

7.2 Messages (type code Mxx)

The module may display the following messages:

Codeno.

Messages Description Checking / solution

FL.DRY.B XX DAYS Floor drying is activeXX DAYS = Number of days'floor drying remaining.

Floor drying is underway. Heating on the circuits notconcerned is shut down.

4 Wait for the number of days shown to change to 04 Set the parameter SCREED DRYING to OFF

FL.DRY.C XX DAYS FL.DRY.B+C XX DAYS

M30 BL.COM.MODBUS No communication with themaster regulation by thenetwork MODBUS.

Check the wiring between the module and the masterappliance.

M31 BL.SYSTEMNETWORK

Incorrect configuration of thenetwork MODBUS.

4 Check that the address of the appliance is correctlyconfigured in the #NETWORK menu.

4 Check that the cascade configuration is set correctlyon the master module.

7.3 Message history

The menu (#MESSAGE HISTORIC) is used to consult the last 10messages displayed by the control panel.

1. Access the "After Sales" level: Hold down the - key until#PARAMETERS is displayed.

2. Select the menu (#MESSAGE HISTORIC).

4 Turn the rotary button to scroll through the menus ormodify a value.

4 Press the rotary button to access the menu selectedor confirm a value modification.

¼ For a detailed explanation of menu browsing, referto the chapter: "Browsing in the menus", page 49

3. The list of the last 10 messages is displayed.

bar

1

1

2

2

rc

STD( ' t

v

0 2 4 6 8 10 12 14 16 18 22 2420

pb AUTOx c rjMg m

SUNDAY 11:45

10"

TEMP.: _ _ _ _

C002272-C-04

bar

1

1

2

2

rc

STD( ' t

v

0 2 4 6 8 10 12 14 16 18 22 2420

pb AUTOx c rjLg m

BL.HEATING SPEED

BL.WATER MIS.

BL.RL OPEN

BL.FLAME LOS

21/10

02/09

26/08

26/08 a

C002381-B-04

7. Troubleshooting VM iSystem

73 19/03/2012 - 300028025-001-01

Page 75: VM iSystem - Akvedukts€¦ · 3 Technical description 3.1 Operating modes 3.1.1. Appliance set to VM/MR VM iSystem module networked with one or more generators equipped with a DIEMATIC

4. Select a message to consult the information pertaining to it.

7.4 Faults

If a malfunction occurs, the module flashes and displays an errormessage and a corresponding code.

1. Make a note of the code displayed.The code is important for the correct and rapid diagnosis of thetype of failure and for any technical assistance that may beneeded.

2. Press the ? key. Follow the instructions displayed to solve theproblem.

3. Consult the meaning of the codes in the table below:

Code Faults Description Checking / solutionD03D04

OUTL S.B FAIL.OUTL S.C FAIL.

Circuit B flow sensor faultCircuit C flow sensor faultRemarks:The circuit pump is running.The 3-way valve motor on the circuitis no longer powered and can beadjusted manually.

Bad connection

4 Check whether the sensor is connected: ¼ Seechapter: "Deletion of sensors from the memory inthe PCB", page 76

4 Check the link and the connectors4 Check that the sensor has been correctly fittedSensor fault

4 Check the Ohmic value of the sensor4 Replace the sensor if necessary

D05 OUTSI.S.FAIL. Outside temperature sensor faultRemarks:The set point of the appliance isequal to the maximum.The valve setting is no longerensured but monitoring themaximum temperature of the circuitafter the valve is ensured.Valves may be manually operated.Reheating the domestic hot waterremains ensured.

Bad connection

4 Check whether the sensor is connected4 Check the link and the connectors4 Check that the sensor has been correctly fittedSensor fault

4 Check the Ohmic value of the sensor4 Replace the sensor if necessary

bar

1

1

2

2

rc

STD( ' t

v

0 2 4 6 8 10 12 14 16 18 22 2420

pb AUTOx c rjLg m

BL INPUT OPEN M21

28/08/2008 - 13h32

NUMBER OF CASE

OUTSIDE TEMP.

OUTLET TEMP.B

8

1.0 °C

12.0°Ca

C002382-B-04

bar

1

1

2

2

rc

STD( ' t

v

0 2 4 6 8 10 12 14 16 18 22 2420

pb AUTOx c rjMg m

SUNDAY 11:45

TEMP. : 68°

PCU COM.FAIL D27

C002302-D-04

VM iSystem 7. Troubleshooting

19/03/2012 - 300028025-001-01 74

Page 76: VM iSystem - Akvedukts€¦ · 3 Technical description 3.1 Operating modes 3.1.1. Appliance set to VM/MR VM iSystem module networked with one or more generators equipped with a DIEMATIC

Code Faults Description Checking / solutionD07 SYST.SENS.FAIL. System sensor fault Bad connection

4 Check whether the sensor is connected: ¼ Seechapter: "Deletion of sensors from the memory inthe PCB", page 76

4 Check the link and the connectors4 Check that the sensor has been correctly fittedSensor fault

4 Check the Ohmic value of the sensor4 Replace the sensor if necessary

D09 DHW S.FAILURE Domestic hot water sensor faultRemarks:Domestic hot water heating is nolonger controlled.The load pump operates.The load temperature of the dhwtank is the same as the boiler.

Bad connection

4 Check whether the sensor is connected: ¼ Seechapter: "Deletion of sensors from the memory inthe PCB", page 76

4 Check the link and the connectors4 Check that the sensor has been correctly fittedSensor fault

4 Check the Ohmic value of the sensor4 Replace the sensor if necessary

D12D13

ROOM S.B FAIL.ROOM S.C FAIL.

B room temperature sensor faultC room temperature sensor faultNote:The circuit concerned operateswithout any influence from the roomsensor.

Bad connection

4 Check whether the sensor is connected: ¼ Seechapter: "Deletion of sensors from the memory inthe PCB", page 76

4 Check the link and the connectors4 Check that the sensor has been correctly fittedSensor fault

4 Check the Ohmic value of the sensor4 Replace the sensor if necessary

D14 MC COM.FAIL Break in communication betweenthe iSystem module and the boilerradio module

Bad connection

4 Check the link and the connectorsBoiler module failure

4 Change the boiler moduleD15 ST.TANK S.FAIL Storage tank sensor fault

Note:The hot water storage tankreheating operation is no longerassured.

Bad connection

4 Check whether the sensor is connected: ¼ Seechapter: "Deletion of sensors from the memory inthe PCB", page 76

4 Check the link and the connectors4 Check that the sensor has been correctly fittedSensor fault

4 Check the Ohmic value of the sensor4 Replace the sensor if necessary

D16D16

SWIM.P.B. S.FAILSWIM.P.C. S.FAIL

Swimming pool sensor fault circuitBSwimming pool sensor fault circuitCNote:Pool reheating is independent of itstemperature.

Bad connection

4 Check whether the sensor is connected: ¼ Seechapter: "Deletion of sensors from the memory inthe PCB", page 76

4 Check the link and the connectors4 Check that the sensor has been correctly fittedSensor fault

4 Check the Ohmic value of the sensor4 Replace the sensor if necessary

7. Troubleshooting VM iSystem

75 19/03/2012 - 300028025-001-01

Page 77: VM iSystem - Akvedukts€¦ · 3 Technical description 3.1 Operating modes 3.1.1. Appliance set to VM/MR VM iSystem module networked with one or more generators equipped with a DIEMATIC

Code Faults Description Checking / solutionD17 DHW 2 S.FAIL Sensor fault tank 2 Bad connection

4 Check whether the sensor is connected: ¼ Seechapter: "Deletion of sensors from the memory inthe PCB", page 76

4 Check the link and the connectors4 Check that the sensor has been correctly fittedSensor fault

4 Check the Ohmic value of the sensor4 Replace the sensor if necessary

D18 ST.TANK S.FAIL Solar tank sensor fault Bad connection

4 Check whether the sensor is connected: ¼ Seechapter: "Deletion of sensors from the memory inthe PCB", page 76

4 Check the link and the connectors4 Check that the sensor has been correctly fittedSensor fault

4 Check the Ohmic value of the sensor4 Replace the sensor if necessary

D19 SOL.COL.S.FAIL Header sensor fault Bad connection

4 Check whether the sensor is connected: ¼ Seechapter: "Deletion of sensors from the memory inthe PCB", page 76

4 Check the link and the connectors4 Check that the sensor has been correctly fittedSensor fault

4 Check the Ohmic value of the sensor4 Replace the sensor if necessary

D20 SOL COM.FAIL 4 Switch the boiler off and switch back on

4 Check whether the solar module is switched on. If necessary, replace the fuse ¼ Referto the installation, commissioning and service manual for the DHW tank

4 Check the connection between the SCU-C and the solar moduleD50 DEF.COM.OTH Break in communication between

the iSystem module and the boilercontrol panel.

4 Check the wiring between the iSystem module and thecontrol panel

4 Check that the CONFIGURATION parameter in the#SYSTEM menu is set to OTH+3WV

D51 DEF XX:SEE BOIL. An error is displayed on the boilercontrol panel.

4 Refer to the boiler's installation and service manual.

7.4.1. Deletion of sensors from the memory in thePCB

The configuration of the sensors is memorised by the PCB. If asensor fault appears whilst the corresponding sensor is notconnected or has been voluntarily removed, please delete the sensorfrom the PCB memory.

4 Press key ? repeatedly until Do you want to delete thissensor? is displayed.

4 Select YES by turning the rotary button and press to confirm.

VM iSystem 7. Troubleshooting

19/03/2012 - 300028025-001-01 76

Page 78: VM iSystem - Akvedukts€¦ · 3 Technical description 3.1 Operating modes 3.1.1. Appliance set to VM/MR VM iSystem module networked with one or more generators equipped with a DIEMATIC

7.5 Failure history

The menu #DEFAULT HISTORIC is used to consult the last 10 faultsdisplayed by the control panel.

1. Access the "After Sales" level: Hold down the - key until#PARAMETERS is displayed.

2. Select the menu #DEFAULT HISTORIC.

4 Turn the rotary button to scroll through the menus ormodify a value.

4 Press the rotary button to access the menu selectedor confirm a value modification.

¼ For a detailed explanation of menu browsing, referto the chapter: "Browsing in the menus", page 49

3. The list of the last 10 faults is displayed.

4. Select a fault to consult the information pertaining to it.

7.6 Parameter and input/output check (mode tests)

Use the following menus to target the cause of a malfunction.

1. Access the "After Sales" level: Hold down the - key until#PARAMETERS is displayed.

2. Check the following parameters:

4 Turn the rotary button to scroll through the menus ormodify a value.

4 Press the rotary button to access the menu selectedor confirm a value modification.

¼ For a detailed explanation of menu browsing, referto the chapter: "Browsing in the menus", page 49

bar

1

1

2

2

rc

STD( ' t

v

0 2 4 6 8 10 12 14 16 18 22 2420

pb AUTOx c rjMg m

SUNDAY 11:45

10"

TEMP.: _ _ _ _

C002272-C-04

bar

1

1

2

2

rc

STD( ' t

v

0 2 4 6 8 10 12 14 16 18 22 2420

pb AUTOx c rjLg m

aAUX1.SENS.FAIL 21/10

C002274-F-04

bar

1

1

2

2

rc

STD( ' t

v

0 2 4 6 8 10 12 14 16 18 22 2420

pb AUTOx c rjLg m

AUX1.SENS.FAIL D07

28/08/2008 - 13h32

NUMBER OF CASE

OUTSIDE TEMP.

OUTLET TEMP.B

8

1.0 °C

35.0°Ca

C002275-C-04

bar

1

1

2

2

rc

STD( ' t

v

0 2 4 6 8 10 12 14 16 18 22 2420

pb AUTOx c rjMg m

SUNDAY 11:45

10"

TEMP.: _ _ _ _

C002272-C-04

7. Troubleshooting VM iSystem

77 19/03/2012 - 300028025-001-01

Page 79: VM iSystem - Akvedukts€¦ · 3 Technical description 3.1 Operating modes 3.1.1. Appliance set to VM/MR VM iSystem module networked with one or more generators equipped with a DIEMATIC

After Sales level - #PARAMETERS menu

Parameter DescriptionPERMUT Master boiler activeSTAGE Number of boilers requesting heatingNB.CASC.:(1) Number of boilers recognised in the cascade

NB. VM:(1) Number of VM iSystem control systems recognised in the cascadeOUTPUT SOL P. Solar pump commandMEAN OUTSIDE T Average outside temperatureCALC.T. BOILER(1) Temperature calculated by the boiler

BOILER. T. (2) Measurement of the boiler flow sensor

CALCULATED T. B (3) Calculated temperature for circuit B

CALCULATED T. C (3) Calculated temperature for circuit CDHW SETP.CORRECT(3)

DHW set point used by the boiler bearing solar back-up in mind

OUTLET TEMP. B (2) (3) Temperature of the flow water in circuit B

OUTLET TEMP. C (2) (3) Temperature of the flow water in circuit C

OUTSIDE TEMP. (2) Outside temperature

ROOMTEMP. B (2) (3) Room temperature of circuit B

ROOMTEMP. C (2) (3) Room temperature of circuit C

WATER TEMP. (2)(3) Water temperature in the DHW tank

IN 0-10V (2)(3) Voltage at input 0-10 V

STOR.TANK.TEMP (2)

(3)Water temperature in the storage tank

SYSTEM TEMP. (2)(3) Temperature of the system flow water if multi-generator

T.DHW BOTTOM (2)(3) Water temperature in the bottom of the DHW tank

TEMP.TANK AUX (2)(3) Water temperature in the second DHW tank connected to the AUX circuit

KNOB B(3) Position of temperature setting button on room sensor B

KNOB C(3) Position of temperature setting button on room sensor C

OFFSET ADAP B (3) Parallel trigger calculated for circuit B

OFFSET ADAP C (3) Parallel trigger calculated for circuit C(1) According to the configuration(2) The parameter can be displayed by pressing key f.(3) The parameter is only displayed for the options, circuits or sensors actually connected

After Sales level - #TEST OUTPUTS menu

Parameter Adjustment range DescriptionP. CIRC. B (1) ON / NO Stop/start pump circuit B

P. CIRC. C (3) ON / NO Stop/start pump circuit C

HW. PUMP (3) ON / NO Stop/start domestic hot water pump

AUX.CIRC. (3) ON / NO On/Off auxiliary outlet

SOLAR P. (3) ON / NO Solar pump On/Off

3WV B (3) REST No commandOPEN: Opening 3-way valve circuit BCLOSE: Closure 3-way valve circuit B

3WV C (3) REST No commandOPEN: Opening 3-way valve circuit CCLOSE: Closure 3-way valve circuit C

(1) The parameter is only displayed for the options, circuits or sensors actually connected

VM iSystem 7. Troubleshooting

19/03/2012 - 300028025-001-01 78

Page 80: VM iSystem - Akvedukts€¦ · 3 Technical description 3.1 Operating modes 3.1.1. Appliance set to VM/MR VM iSystem module networked with one or more generators equipped with a DIEMATIC

After Sales level - #TEST INPUTS menu

Parameter Status DescriptionPHONE REM.(1) 0 / 1 Status of the telephone inlet

I.SYST(2) 0 / 1 Status of the telephone inlet

R.CTRL B (3) ON Presence of a remote control BNO No remote control B

R.CTRL C (3) ON Presence of a remote control CNO No remote control C

(1) The parameter is only displayed if IN 0-10V is set to OFF(2) According to the setting of the I.SYST parameter(3) The parameter is only displayed for the options, circuits or sensors actually connected

After Sales level - #INFORMATION menu(1)

Parameter Adjustment range DescriptionS/N SCU Serial no. of the Diematic iSystem DIN control panelCTRL Control versionMC.VERSION (2) Version of the boiler radio module programmeCALIBRA.CLOCK Clock calibration(1) The menu is displayed only if the INSTALLATION parameter is set to EXTENDED(2) The parameter is only displayed for the options, circuits or sensors actually connected

After Sales level - #CONFIGURATION menu

Parameter Adjustment range DescriptionMODE: MONO/ ALL.CIRC. To chose if the exemption made for one remote control applies to a single circuit (MONO) or

if it must be transmitted to a group of circuits (ALL CIRC)

7. Troubleshooting VM iSystem

79 19/03/2012 - 300028025-001-01

Page 81: VM iSystem - Akvedukts€¦ · 3 Technical description 3.1 Operating modes 3.1.1. Appliance set to VM/MR VM iSystem module networked with one or more generators equipped with a DIEMATIC

VM iSystem 7. Troubleshooting

19/03/2012 - 300028025-001-01 80

Page 82: VM iSystem - Akvedukts€¦ · 3 Technical description 3.1 Operating modes 3.1.1. Appliance set to VM/MR VM iSystem module networked with one or more generators equipped with a DIEMATIC
Page 83: VM iSystem - Akvedukts€¦ · 3 Technical description 3.1 Operating modes 3.1.1. Appliance set to VM/MR VM iSystem module networked with one or more generators equipped with a DIEMATIC
Page 84: VM iSystem - Akvedukts€¦ · 3 Technical description 3.1 Operating modes 3.1.1. Appliance set to VM/MR VM iSystem module networked with one or more generators equipped with a DIEMATIC

AD

001-

AG

DUEDI S.r.l.www.duediclima.it

Distributore Ufficiale EsclusivoDe Dietrich-Thermique Italia

Via Passatore, 12 - 12010San Defendente di CervascaCUNEO

+39 0171 857170+39 0171 [email protected]

IT

DE DIETRICH THERMIQUE Iberia S.L.U.

DE DIETRICH THERMIQUE S.A.S

www.dedietrich-calefaccion.es

Av. Princep d’Astúries 43-4508012 BARCELONA

+34 932 920 520+34 932 184 709